PT. SIEMENS INDONESIA
Diagrams and charts
for
Purchaser
User
Plant
Document Title
(3)G73012-23336-A1000-A
H23336
02.04.12
A / =00_COV / /1
Order number
Date of issue
Identification No.
Energy Sector
Power Distribution Division
E D MV
Jl. Jendral A. Yani Kav B67-68, Pulomas, Jakarta 13210, Indonesia
JATIM TAMAN STEEL 2
20kV SWITCHGEAR
GENERAL DOCUMENTS
COVER SHEET
CV. SEMBRANI MITRA TEKNIK
CV. SEMBRANI MITRA TEKNIK
Document designation
Producer document No.
GENERAL INFORMATION :
SWITCHBOARD TYPE
PROTECTION DEGREE
PAINTED
BUSBAR SYSTEM
MAIN BUS RATED CURRENT
SERVICE VOLTAGE
MAX. RATED VOLTAGE
INSULATION LEVEL (LOW FREQ/IMPULSE)
SHORT TIME CURRENT CARRYING
POWER CABLE ENTRY
POWER CABLE ACCESS
CONTROL CABLE ENTRY
POWER CABLE GLANDPLATE
CONTROL CABLE GLANDPLATE
MIMIC DIAGRAM
WIRE INFORMATION :
WIRE TYPE
CT WIRE - PHASE 1
CT WIRE - PHASE 2
CT WIRE - PHASE 3
CT WIRE - NEUTRAL
VT WIRE - PHASE 1
VT WIRE - PHASE 2
VT WIRE - PHASE 3
VT WIRE - NEUTRAL
DC CONTROL CIRCUIT
AC CONTROL CIRCUIT (L/N)
VCB/VC/TRUCK & E/S AUX. WIRE
EARTH/GROUND CIRCUIT
: SIMOPRIME A4
: IP4X
: RAL 7035
: BARE COPPER
: 2500A
: 20kV
: 24kV
: 50kV / 125kV
: 25kA/1s
: BOTTOM / TOP
: REAR
: BOTTOM
: ALUMUNIUM, 5mm THICK
: ALUMUNIUM, 5mm THICK
: BLACK PLASTIC FOIL
: NYAF 0.4/0.7kV
: BLACK (BK) - 2.5mm²
: BLACK (BK) - 2.5mm²
: BLACK (BK) - 2.5mm²
: BLACK (BK) - 2.5mm²
: BLACK (BK) - 1.5mm²
: BLACK (BK) - 1.5mm²
: BLACK (BK) - 1.5mm²
: BLACK (BK) - 1.5mm²
: BLACK (BK) - 1.5mm²
: BLACK (BK) - 1.5mm² / BLACK (BK) - 1.5mm²
: BLACK (BK) - 1.0mm²
: GREEN YELLOW (GYL) - 4.0mm²
Designation Producer document No. Sheet Sheets Date Description Designed by
1 2 3 4 5 6 7 8
F
E
D
C
B
A
F
E
D
C
B
A
1 2 3 4 5 6 7 8
TRIANGGONO
MEYRI
30.03.2012
YUWONO
BARE COPPER RAL 7035 24kV 50Hz 20kV (BIL) L2
20kV SWITCHGEAR
CV. SEMBRANI MITRA TEKNIK DOCUMENT LIST
SIMOPRIME A4 (3)G73012-23336-L1001-A
A
+JZ00
=01_TOC
Sheet 1-
1 Sh.
CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved
Orig./Repl.f./Repl.by
A1
Date
Drawn
Appr.
Date
A FOR APPROVAL 02.04.12 MH
RemarksRev. Name Norm
Project:
Symbol library 1:
Symbol library 2:
Symbol library 3:
Symbol library 4:
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro
GY
GR
YL
RD
ELCAD-Version
Translate file A:
Translate file B:
Translate file C:
Translate file D:
7.3.2 SP2
2.5
4 BK
Archive: =01_TOC / A / A / 1
C_FB_EN.etr, 04-11-24
Last used: 02.04.12
GENERAL DOCUMENTS
COVER SHEET
02.04.12 IC LMV MV AE11-(3)G73012-23336-A1000-A
+JZ00
/1A =00_COV
DOCUMENT LIST02.04.12 IC LMV MV AE11-(3)G73012-23336-L1001-A
+JZ00
A1A =01_TOC
GENERAL DOCUMENTS
LEGENDS
ANSI CODE NUMBER
02.04.12 IC LMV MV AE41+(3)G73012-23336-S1002-A
+JZ00
B1A =02_LGD
GENERAL DOCUMENTS
LEGENDS
ANSI CODE NUMBER
02.04.12 IC LMV MV AE42+(3)G73012-23336-S1002-A
+JZ00
B2A =02_LGD
GENERAL DOCUMENTS
LEGENDS
02.04.12 IC LMV MV AE43+(3)G73012-23336-S1002-A
+JZ00
B3A =02_LGD
GENERAL DOCUMENTS
LEGENDS
02.04.12 IC LMV MV AE44-(3)G73012-23336-S1002-A
+JZ00
B4A =02_LGD
GENERAL DOCUMENT
SINGLE LINE DIAGRAM
02.04.12 IC LMV MV AE11-(3)G73012-23336-S1003-A
+JZ00
C1A =03_SLD
GENERAL DOCUMENT
PANEL FRONT VIEW
02.04.12 IC LMV MV AE11-(3)G73012-23336-B1004-A
+JZ00
DA =04_FVW
GENERAL DOCUMENT
PANEL FLOOR CUTOUT
02.04.12 IC LMV MV AE31+(3)G73012-23336-B1005-A
+JZ00
E1A =05_FLC
GENERAL DOCUMENT
SWITCHGEAR CLEARANCE
02.04.12 IC LMV MV AE32+(3)G73012-23336-B1005-A
+JZ00
E2A =05_FLC
GENERAL DOCUMENT
FIXING DETAIL
02.04.12 IC LMV MV AE33-(3)G73012-23336-B1005-A
+JZ00
E3A =05_FLC
GENERAL DOCUMENT
PANEL CONFIGURATION
=JZ01 - INCOMING FEEDER
02.04.12 IC LMV MV AE21+(3)G73012-23336-B1006-A
+JZ00
F1A =06_SEC
GENERAL DOCUMENT
PANEL CONFIGURATION
=JZ02 - CONNECTION PANEL
02.04.12 IC LMV MV AE22-(3)G73012-23336-B1006-A
+JZ00
F2A =06_SEC
1 2 3 4 5 6 7 8
F
E
D
C
B
A
F
E
D
C
B
A
20kV SWITCHGEAR
CV. SEMBRANI MITRA TEKNIK
JATIM TAMAN STEEL 2
ANSI CODE NUMBER
LEGENDS
GENERAL DOCUMENTS
(3)G73012-23336-S1002-A
A
+JZ00
=02_LGD
Sheet 1+
4 Sh.
CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved
Orig./Repl.f./Repl.by
B1
1 2 3 4 5 6 7 8
Date
Drawn
Appr.
Date
A FOR APPROVAL 02.04.12 MH
RemarksRev.
TRIANGGONO
MEYRI
30.03.2012
YUWONOName NormSIMOPRIME A4
Project:
Symbol library 1:
Symbol library 2:
Symbol library 3:
Symbol library 4:
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro
ELCAD-Version
Translate file A:
Translate file B:
Translate file C:
Translate file D:
7.3.2 SP2
Archive: =02_LGD / A / B / 1
C_FB_EN.etr, 04-11-24
Last used: 02.04.12
1
2
3
4
5
6
7
8
9
10
11
12
Master Element is the initiating device, such as a
control switch, voltage relay, float switch, etc.,
which serves either directly, or through such
permissive devices as protective and time-delay
relays to place an equipment in or out of
operation.
Time-delay starting, or closing relay is a device
which functions to give a desired amount of time
delay before or after any point of operation in a
switching sequence or protective relay system,
except as specifically provided by device
functions 48, 62, and 79 descrived later.
Checking or interlocking relay is a device which
operates in response to the position of a number
of other devices, (or to a number of predetermined
conditions), in an equipment, to allow an
operating sequence to proceed, to stop, or to
provide a check of the position of these devices or
of these conditions for any purpose.
Master contactor is a device, generally controlled
by device No. 1 or equivalent, and the required
permissive and protective devices, that serves to
make and break the necessary control circuits to
place and equipment into operation under the
desired conditions and to take it out of operation
under other or abnormal conditions.
Stopping device is a control device used primarily
to shut down an equipment and hold it out of
operation. [This device may be manually or
electrically actuated, but excludes the function of
electrical lockout (see device function 86) on
abnormal conditions.]
Starting circuit breaker is a device whose principal
function is to connect a machine to its source of
starting voltage.
Anode circuit breaker is one used in the anode
circuits of a power rectifier for the primary
purpose of interrupting the rectifier circuit if
an arc back should occur.
Control power disconnecting device is a disconnective device
such as a knife switch, circuit breaker or pullout
fuse block, used for the purpose of
connecting and disconnecting the source of
control power to and from the control bus of equipment.
Note: control power is considered to include
auxiliary power which supplies apparatus as
small motors and heaters.
Reversing device is used for the purpose of reversing
a machine field or for performing any other
reversing functions.
Unit sequence switch is used to change the sequence
in which units may be placed in and out
of service in multiple-unit equipments.
Reserved for future application.
Over-speed device is usually a direct-connected
speed switch which function on machine
over-speed.
13
14
15
16
17
18
19
20
21
22
23
24
Synchronous-speed device, such as a centrifugal-
speed switch, a slip-frequency relay, a voltage
relay, an undercurrent relay or any type of device,
operates at approximately synchronous speed of
a machine.
Under-speed device functions when the speed of
a machine falls below a predetermined value.
Speed or frequency matching device functions to
match and hold the speed or the frrequency of a
machine or of a system equal to, or approximately
equal to, that of another machine, shource or system.
Reserved for future application.
Shunting or discharge switch serves to open or to
close a shunting circuit around any piece of
apparatus (except a resistor), such as a machine
field, a machine armature, a capcitor or a reactor.
Notes: this excludes devices which perform such
shunting operations as may be necessary in the
process of starting a machine by devices 6 or 42,
or their equivalent, and also excludes device 73
function which serves for the switching of
resistor.
Accelerating or decelerating device is used to close
or to cause the closing of circuits which are used
increase or to decrease the speed of a machine.
Starting-to-running transition contactor is a device
which operates to initiate or cause the
automatic transfer of a machine from the starting
to the running power connection.
Electrically operated valve is an electrically
operated, controlled or monitored valve in
a fluid line.
Note: the function of the valve may be
indicated by the use of the suffixes.
Distance relay is a device which functions when
the circuit admittance, impedance or reactance
increases or decreases beyond predetermined
limits.
Equalizer circuit breaker is a breaker which
serves to control or to make and break the
equalizer or the current-balancing connections
for a machine field, or for regulating equipment,
in a multiple-unit installation.
Temperature control device functions to raise or
lower the temperature of a machine or other apparatus
or of any medium, when its temperature falls below,
or rises above, a predetermided value.
Note: an example is a thermostat which switches
on a space heater in a switchgear assembly when
the temperature falls to a desired value as
distinguished from a device which is used to
provide automatic temperature regulation between close
limits and would be designated as 90T.
Reserved for future application.
31
32
33
34
35
36
37
25
26
27
28
29
30
Separate excitation device connects a circuit such
as the shunt field of a synchronous converter, to
a source of separate excitation during the starting
sequence; or one which energizes the excitation
and ignition circuits or a power rectifier.
Directional power relay is one which functions on
a desired value of power flow in a given directrion
or upon reverse power resulting from arc back in
the anode or cathode circuits of a power rectifier.
Position switch makes or breaks contact when the
main device or piece of apparatus, which has no
device function number, reaches a given position.
Master sequence device is a device such as a motor
operated multi-contact switch, or the equivalent
or a programming device, such as a computer
that establishes or determines the operating
sequence of the major devices in an equipment during
starting and stopping or during sequential
switching operations.
Brush-operating, or slip-ring-short-circuiting, device
is used for raising, lowering, or shifting the
brushes of a machine, or for short-circuiting its
slip rings, or for engaging or disengaging the
contactos of a mechanical rectifier.
Polarity or polarizing voltage device operates or
permits the operation of another device on a
predetermined polarity only or verifies the presence
of a polarizing voltage in an equipment.
Undercurrent or underpower relay functions
when the current or power flow decreases below
the predetermined value.
Synchronizing or synchronism-check device operates
when two ac circuits are within the desired limits
of frequency, phase angle or voltage, to permit
or to cause the paralleling of these two circuits.
Apparatus thermal device functions when the
temperature of the shunt field or the armortisseur
winding or a machine, or that of a load limiting
or load shifting resistor or of a liquid or other
medium exceeds a predetermined value; or if the
temperature of the protected apparatus, such as a
power rectifier, or of any medium decreases
below a predetermined value.
Undervoltage relay is a device which functions of
a given value of undervoltage.
Flame detector is a device that monitors the
presence of the pilot or mail flame in such apparatus
as a gas turbince or a steam boiler.
Isolating contactor is used expressly for disconnecting
one circuit from another for the purposes
of emergency operation, maintenance, or test.
Annunciator relay is a nonautomatically reset device
that gives a number of separate visual indications
upon the functioning of protective devices and which
may also be arranged to perform a lockout function.
46
47
48
49
38
39
40
41
42
43
44
45
Reverse-phase, or phase-balance, current relay is a
relay which functions when the polyphase currents
are of reverse-phase sequence, or when the polyphase
currents are unbalanced or contain negative
phase-sequence components above a given amount.
Phase-sequence voltage relay functions upon a
predetermined value of polyphase voltage in the
desired phase sequence.
Incomplete sequence relay is a relay that generally
returns the equipment to the normal, or off,
position and locks it out if the normal starting,
operating or stopping sequence is not properly
completed within a predetermined time. If the device
is used for alarm purposes only, it should
preferably be designated as 48A (alarm).
Machine, or transformer, thermal relay is a relay
that functions when the temperature of a machine
armature, or other load carrying winding or element
of a machine, or the temperature of a
power rectifier or power transformer (including
a power rectifier transformer) exceeds a
predetermined value.
Bearing protective device functions on execessive
bearing temperature, or on other abnormal
mechanical conditions, such as undue wear, which
may eventually result in excessive bearing
temperature.
Mechanical condition monitor is a device that
functions upon the occurrence of an abnormal
mechanical condition (except that associated
with bearings as covered under device function
38), such as excessive vibration, eccentricity,
expansion, shock, tilting, or seal failure.
Field relay functions on a given or abnormally
low value or failure of machine field current, or
on an excessive value of the reactive component
or armature current in an ac machine indicating
abnormally low dield excitation.
Field circuit breaker is a device whose functions
to apply, or to remove, the field excitation of a
machine.
Running circuit breaker is a device whose principal
function is to connect a machine to its source
of running or operating voltage. This function
may also be used for a device, such as a contactor,
that is used in series with a circuit breaker or
other fault protecting means, primarily for
frequent opening and closing of the circuit.
Manual transfer or selector device transfers the
control circuits so as to modify the plan of operation
of the switching equipment or of some of
the devices.
Unit sequence starting relay is a device which
functions to start the next available unit in a
multiple-unit equipment on the failure or on the
non-availability of the normally preceding unit.
Atmospheric condition monitor is a device that
functions upon the occurence of an abnormal
armospheric condition, such as damaging fumes,
explosive mixtures, smoke, or fire.
1 2 3 4 5 6 7 8
F
E
D
C
B
A
F
E
D
C
B
A
20kV SWITCHGEAR
CV. SEMBRANI MITRA TEKNIK
JATIM TAMAN STEEL 2
ANSI CODE NUMBER
LEGENDS
GENERAL DOCUMENTS
(3)G73012-23336-S1002-A
A
+JZ00
=02_LGD
Sheet2+
4 Sh.
CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved
Orig./Repl.f./Repl.by
B2
1 2 3 4 5 6 7 8
Date
Drawn
Appr.
Date
A FOR APPROVAL 02.04.12 MH
RemarksRev.
TRIANGGONO
MEYRI
30.03.2012
YUWONOName NormSIMOPRIME A4
Project:
Symbol library 1:
Symbol library 2:
Symbol library 3:
Symbol library 4:
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro
ELCAD-Version
Translate file A:
Translate file B:
Translate file C:
Translate file D:
7.3.2 SP2
Archive: =02_LGD / A / B / 2
C_FB_EN.etr, 04-11-24
Last used: 02.04.12
50
51
52
53
54
55
56
57
58
59
60
61
62
63
Instantaneous overcurrent, or rate-of-rise relay is
a relay that functions instantaneously on an excessive
value of current, or on an excessive rate of
current rise, thus indicating a fault in the
apparatus or curcuit being protected.
Ac time overcurrent relay is a relay with either a
definite or inverse time characteristic that functions
when the current in an ac circuit exceeds a
predetermined value.
Ac circuit breaker is a device that is used to close
and interrupt an ac power circuit under normal
conditions or to interrupt this circuit under fault
or emergency conditions.
Excite or dc generator relay is a relay that forces
the dc machine field excitation to build up during
starting or which functions when the machine voltage
has built up to a given value.
Reserved for future application.
Power factor relay is a relay that operates when
the power factor in an ac circuit rises above or
below a predetermined value.
Field application relay is a relay that automatically
controls the application of the field excitation to
an ac motor at some predetermined point in the
slip cycle.
Chort-circuiting or grounding device is primary
circuit switching device that functions to short-
circuit or to ground a circuit in response to
automatic or manual means.
Rectification failure relay is a device that functions
if one or more anodes of a power rectifier
fail to fire, or to detec an arc-back or on failure
of a diode to conduct or block properly.
Overvoltage relay is a relay that functions on a
given value of overvoltage.
Voltage or current balance relay is a relay that
operates on a given difference in voltage, or
current input or output of two circuits.
Reserved for future applications.
Time-delay stopping or opening relay is a time-
delay relay that serves in conjunction with the
device that initiates the shutdown, stopping, or
opening operation in an automatic sequence.
Pressure switch is a switch which operates on
given values or on a given rate of change of
pressure.
64
65
66
67
68
69
70
71
72
73
Ground protective relay is a relay that functions
on failure of the insulation of a machine,
transformer or of other apparatus to ground, or on
flashover of a dc machine to ground.
Note: This function is assigned only to a relay
which detects the flow of current from the frame
of a machine or enclosing case or structure of a
piece of apparatus to ground, or detects a ground
on a normally ungrounded winding or circuit. It is
not applied to a device connected in the secondary
circuit or secondary neutral of a current
transformer, on in the secondary neutral of current
transformer, connected in the power circuit of a
normally grounded system.
Governor is the assembly of fluid, electrical, or
mechanical control equipment used for regulating
the flow of water, steam, or other medium to the
prime mover for such purposes as starting, holding
speed or load, or stopping.
Notching or jogging device functions to allow
only a specified number of operations of a given
device, or equipment, or a specified number of
successive operations within a given time of each
other. It also functions to energize a circuit
periodically or for fractions of specified time in
tervals, or that is used to permit intermittent
acceleration or jogging of a machine at low speeds
for machanical positioning.
Ac directional overcurrent relay is a relay that
functions on desired value of ac overcurrent
flowing in a predetermined direction.
Blocking relay is a relay that initiates a pilot signal
for blocking or tripping on external faults in
a transmission line or in other apparatus under
predetermined conditions, or cooperates with
other devices to block tripping or to block
reclosing on an our-of-step condition or on power
swing.
Permissive control deice is generally a two-
position, manually operated switch that in one
position permits the closing of a circuit breaker
or the placing of an equipment into operation,
and in the other position prevents the circuit
breaker or the equipment from being operated.
Rheostat is a variable resistance device used in an
electric circuit, which is electrically operated or
has other electrical accessories, such as auxiliary,
position, or limit switches.
Level switch is a switch which operates on given
values, or on a given rate of change, of level.
Dc circuit breaker is used to close and interrupt
dc power circuit under normal conditions or to
interrupt this circuit under fault or emergency
conditions.
Load-resistor contactor is used to shunt or insert
a step of load limiting, shifting, or indicating
resistance in a power circuit, or to switch a space
heater in circuit, or to switch a light, or regenerative
load resistor of a power rectifier or other machine in
and out of circuit.
74
75
76
77
78
79
80
81
82
83
84
85
86
87
Alarm relay is a device other than an annunciator,
as covered under device No. 30, which is used to
operate, or to operatein connection with a
visual or audible alarm.
Position changing mechanism is a mechanism
that is used for moving a main device from one
position to another in an equipment; as for
example, shifting a removable circuit breaker unit
to and from the connected, disconnected, and
test position.
Dc overcurrent relay is arelay that functions
when the current in a dc circuit exceeds a given
value.
Pulse transmitter is used to generate and transmit
pulses over a telemetering or pilot-wire circuit
to the remote indicating or receiving device.
Phase angle measuring, or out-of-step protective
relay is a relay that functions at a predetermined
phase angle between two voltages or between
two currents or between voltage and current.
Ac reclosing relay is a relay that controls the
automatic reclosing and locking out of an ac
circuit interrupter.
Flow switch is a switch which operates on
given values, or on a given rate of change, of
flow.
Frequency relay is a relay that functions on a
predetermined value of frequency - either
under or over or on normal system frequency -
or rate of change of frequency.
Dc reclosing relay is a relay that controls the
automatic closing and reclosing of a dc circuit
interrupter, generally in response to load circuit
conditions.
Automatic selective control or transfer relay is
a relay that operates to select automatically
between certain cources or conditions in an
equipment, or performs a transfer operation
automatically.
Operating mechanism is the complete electrical
mechanism or servo-mechanism, including the
operating motor, solenoids, position switches,
etc., for a tap changer, induction regulator or
any similar piece of apparatus which has no
device function number.
Carrier or pilot-wire receiver relay is a relay that
operated or restrained by a signal used in
connection with carrier-current or dc pilot-wire fault
directional relaying.
Locking-out relay is an electrically operated,
hand or electrically reset, relay that functions to
shut down and hold an equipment out of service
on the occurence of abnormal conditions.
Differential protective relay is a protective relay
that functions on a percentage or phase angle or
other quantities difference of two currents or
of some other electrical quantities.
Special alocated ANSI device number (Siemens Note)
90
91
92
93
94
95
96
97
50BF
74TC
88
89
Regulating device functions to regulate a quantity,
or quantities, such as voltage, current, power,
speed, frequency, temperature, and load, at a
certain value or between certain (generally close)
limits for machines, tie lines or other apparatus.
Voltage directional relayis a relay that operates
when the voltage across an open circuit breaker
or contactor exceeds a given value in a given
direction.
Voltage and power directional relay is a relay that
permits or causes the connection of two circuits
when the voltage difference between them
exceeds a given value in a predetermined direction
and causes these two circuits to be disconnected
from each other when the power flowing between
them exceeds a given value in the opposite
direction.
Field changing contactor functions to increase or
decrease in one step the value of field excitation
on a machine.
Tripping or trip-free relay functions to trip a
circuit breaker, contactor, or equipment, or to permit
immediate tripping by other devices; or to
prevent immediate reclosure of a circuit interrupter,
in case it should open automatically
even though its closing circuit is maintained
closed.
Used only for specific applications on individual
installations where none of the assigned numbered
functions from 1 to 94 is suitable.
Breaker failure protection.
Trip coil supervision relay.
Auxiliary motor or motor generator is one used
for operating auxiliary equipment such as pumps,
blowers, exciters, rotating magnetic amplifiers,
etc.
Line switch is used as disconnecting load-
interrupter, or isolating switch in an ac or dc
power circuit, when this device is electrically
operated or has electrical accessories, such as an
auxiliary switch, magnetic lock, etc.
M
1 2 3 4 5 6 7 8
F
E
D
C
B
A
F
E
D
C
B
A
20kV SWITCHGEAR
CV. SEMBRANI MITRA TEKNIK
JATIM TAMAN STEEL 2
LEGENDS
GENERAL DOCUMENTS
(3)G73012-23336-S1002-A
A
+JZ00
=02_LGD
Sheet3+
4 Sh.
CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved
Orig./Repl.f./Repl.by
B3
1 2 3 4 5 6 7 8
P
Date
Drawn
Appr.
Date
A FOR APPROVAL 02.04.12 MH
RemarksRev.
TRIANGGONO
MEYRI
30.03.2012
YUWONOName NormSIMOPRIME A4
Project:
Symbol library 1:
Symbol library 2:
Symbol library 3:
Symbol library 4:
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro
ELCAD-Version
Translate file A:
Translate file B:
Translate file C:
Translate file D:
7.3.2 SP2
Archive: =02_LGD / A / B / 3
C_FB_EN.etr, 04-11-24
Last used: 02.04.12
Wh
VARh
Wh
VARh
Wh
VARh
A
A
V
V
Hz
PF
W
VAR
3
3
AMPERE METER
3 UNITS AMPERE METER
VOLT METER
3 UNITS VOLT METER
FREQUENCY METER
POWER-FACTOR METER
WATT METER
VAR METER
WATT-HOUR METER
SINGLE-TARIFF
VAR-HOUR METER
SINGLE-TARIFF
WATT-HOUR METER
DOUBLE-TARIFF
VAR-HOUR METER
DOUBLE-TARIFF
WATT-HOUR METER
EXPORT-IMPORT
VAR-HOUR METER
EXPORT-IMPORT
TRANSDUCER/
POWER SUPPLY UNIT
METERING AND MEASUREMENT
%H₂O
L/R
CS
θ
CABLE CONNECTION
SURGE ARRESTOR/
LIMITER
LOCAL/REMOTE SELECTOR
CONTROL SWITCH
RECTIFIER
LED
LAMP
VARISTOR
CAPACITOR
HEATER
MOTOR
DIODE
THERMOSTAT
HYGROSTAT
BINARY INPUT
POTENTIAL DESIGNATION
BASIC REPRESENTATION
M
BUSDUCT CONNECTION
MECHANICAL INTERLOCK
ENERGY-STORED MECHANISM
OPERATED BY
HANDLE
OPERATING MECHANISM
PLUG AND SOCKET
AMPERE/VOLTAGE SELECTOR
PROVISION FOR PADLOCKING
THROUGH VENTILATION
FORCED VENTILATION
SHIPPING SEPARATION
(PANEL/PACKING)
PRESSURE ACTIVATOR
EARTHING/GROUNDING
INFORMATION
BASIC REPRESENTATION
NORMALLY OPEN
CONTACT
NORMALLY CLOSE
CONTACT
NORMALLY OPEN
CONTACT (CLOSED CONDITION)
MECHANICAL ACTIVATED
CHANGE OVER
CONTACT
MAKE CONTACT
DELAYED WHEN
CLOSING
MAKE CONTACT
DELAYED WHEN
OPENING
BREAK CONTACT
DELAYED WHEN
CLOSING
BREAK CONTACT
DELAYED WHEN
RECLOSING
CHANGE OVER
CONTACT
ON-DELAY
CHANGE OVER
CONTACT
OFF-DELAY
CONTACTS
SOLENOID/COIL
OFF-DELAY COIL
ON-DELAY COIL
ON-/OFF-DELAY COIL
LATCHED COIL
CONTACTOR
1 2 3 4 5 6 7 8
F
E
D
C
B
A
F
E
D
C
B
A
20kV SWITCHGEAR
CV. SEMBRANI MITRA TEKNIK
JATIM TAMAN STEEL 2
LEGENDS
GENERAL DOCUMENTS
(3)G73012-23336-S1002-A
A
+JZ00
=02_LGD
Sheet4-
4 Sh.
CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved
Orig./Repl.f./Repl.by
B4
1 2 3 4 5 6 7 8
Date
Drawn
Appr.
Date
A FOR APPROVAL 02.04.12 MH
RemarksRev.
TRIANGGONO
MEYRI
30.03.2012
YUWONOName NormSIMOPRIME A4
Project:
Symbol library 1:
Symbol library 2:
Symbol library 3:
Symbol library 4:
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro
ELCAD-Version
Translate file A:
Translate file B:
Translate file C:
Translate file D:
7.3.2 SP2
Archive: =02_LGD / A / B / 4
C_FB_EN.etr, 04-11-24
Last used: 02.04.12
WITHDRAWABLE CIRCUIT BREAKER
- MOTORIZED SPRING CHARGING MECHANISM
- WITH TRUCK MOVEMENT BLOCKING COIL
- INTEGRATED VOLTAGE TRANSFORMER
- VOLTAGE TRANSFORMER WITH PRIMARY FUSE
WITHDRAWABLE VACUUM CONTACTOR
- WITH PRIMARY FUSES
- WITH CONTROL POTENTIAL TRANSFORMER
WITHDRAWABLE BUS METERING VT
- WITH PRIMARY FUSES
- WITH SINGLE WINDING VOLTAGE TRANSFORMER
M
COMPOSITE REPRESENTATION
3
EARTHING SWITCH
- WITH OPERATION BLOCKING COIL
- WITH PADLOCKING FACILITY
CORE2
CORE1
CORE1
P1
P2
P2
P1
P2
P1
P1
P2
3
S1
S2
S1
S2
3 3 UNITS CURRENT TRANSFORMER
- TWO CORES
- BLOCK TYPE
- SECONDARY TERMINAL AT P2
3 UNITS CURRENT TRANSFORMER
- ONE CORES
- GENERAL REPRESENTATION
- APPLICABLE FOR TOROID TYPE
PHASE CURRENT TRANSFORMER
- USED IN WIRING DIAGRAM
ZERO CURRENT TRANSFORMER (ZCT)
- USED IN WIRING DIAGRAM
COMPOSITE REPRESENTATION
CONTROL SWITCH
- SPRING RETURN TO CENTER
- 3 POLES
LOCAL-REMOTE SELECTOR SWITCH
- WITH PADLOCKING FACILITY
- 3 POLES
-Q01
630A
OPEN
LOC
I >
I >
I >
CLOSE
REM
1-POLE MINIATURE CIRCUIT BREAKER (MCB)
I >
I >
3 1
21 3
2
2-POLE MCB
COMPOSITE REPRESENTATION
I >
3-POSITION SWITCH
CONNECTED
DISCONNECTED
EARTHED
3-POLE MCB
7 5
65 7
6
11 9
109 11
10
1 2 3 4 5 6 7 8
F
E
D
C
B
A
F
E
D
C
B
A
20kV SWITCHGEAR
CV. SEMBRANI MITRA TEKNIK
JATIM TAMAN STEEL 2
SINGLE LINE DIAGRAM
GENERAL DOCUMENT
(3)G73012-23336-S1003-A
A
+JZ00
=03_SLD
Sheet 1-
1 Sh.
CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved
Orig./Repl.f./Repl.by
C1
1 2 3 4 5 6 7 8
Date
Drawn
Appr.
Date
A FOR APPROVAL 02.04.12 MH
RemarksRev.
TRIANGGONO
MEYRI
30.03.2012
YUWONOName NormSIMOPRIME A4
Project:
Symbol library 1:
Symbol library 2:
Symbol library 3:
Symbol library 4:
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro
ELCAD-Version
Translate file A:
Translate file B:
Translate file C:
Translate file D:
7.3.2 SP2
Archive: =03_SLD / A / C / 1
C_FB_EN.etr, 04-11-24
File name: 000330
Last used: 02.04.12
DESIGNATION
LOCATION
TYPICAL
NAME PLATE
CABLE
BARE COPPER RAL 7035 24kV 50Hz 20kV (BIL) L2
=J01
+J01
=JZ02
=J01
CONNECTION
PANEL
12X1Cx500mm²
CU/XLPE/PVC
4
-Y8
-Q1
3
M
-Q8
5
-T1L1,L2,L3
CORE2:
700/5A
10VA, CL.0.5
CORE1:
700/5A
10VA, 5P20
2
P2
P1
=J02
+J02
=JZ01
=J02
INCOMING
PANEL 1
-Q0
6X1Cx500mm²
CU/XLPE/PVC
1250A
25kA
1
-T5L1,L2,L3
20
3
0.11
3
50VA CL.0.5
30VA CL.3P
0.11
3kV
3
-F5
L1,L2,L3
3,15A
4
-Y8
-Q1
3
M
-Q8
5
-T1L1,L2,L3
CORE2:
700/5A
10VA, CL.0.5
CORE1:
700/5A
10VA, 5P20
2
P2
P1
=J03
+J03
=JZ01
=J03
INCOMING
PANEL 2
-Q0
6X1Cx500mm²
CU/XLPE/PVC
1250A
25kA
1
-T5L1,L2,L3
20
3
0.11
3
50VA CL.0.5
30VA CL.3P
0.11
3kV
3
-F5
L1,L2,L3
3,15A
4
-Y8
-Q1
3
M
-Q8
5
-T1L1,L2,L3
CORE2:
700/5A
10VA, CL.0.5
CORE1:
700/5A
10VA, 5P20
2
P2
P1
=J04
+J04
=JZ01
=J04
INCOMING
PANEL 3
-Q0
6X1Cx500mm²
CU/XLPE/PVC
1250A
25kA
1
-T5L1,L2,L3
20
3
0.11
3
50VA CL.0.5
30VA CL.3P
0.11
3kV
3
-F5
L1,L2,L3
3,15A
LEGEND
1
2
3
4
5
-Y8
PADLOCK FACILITY FOR INDEPENDENT
SHUTTER OPERATION HOLE
PADLOCK FACILITY FOR
EARTHING SWITCH OPERATION HOLE
PADLOCK FACILITY FOR TRUCK
WITHDRAWABLE OPERATION HOLE
PADLOCK FACILITY FOR HV DOOR
KEY OPERATION HOLE
PADLOCK FACILITY FOR
CB (OPEN - CLOSE) OPERATION HOLE
CABLE EARTHING SWITCH BLOCKING COIL.
(EARTHING CANNOT BE CLOSED OR OPENED
WHEN THIS COIL IS NOT ENERGIZED).
CT SECONDARY TERMINAL BOX POSITION
2250
35 800 800 800 800 35
1 2 3 4 5 6 7 8
F
E
D
C
B
A
F
E
D
C
B
A
20kV SWITCHGEAR
CV. SEMBRANI MITRA TEKNIK
JATIM TAMAN STEEL 2
PANEL FRONT VIEW
GENERAL DOCUMENT
(3)G73012-23336-B1004-A
A
+JZ00
=04_FVW
Sheet 1-
1 Sh.
CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved
Orig./Repl.f./Repl.by
D
1 2 3 4 5 6 7 8
630
OVERALL LENGTH = 3270
Date
Drawn
Appr.
Date
A FOR APPROVAL 02.04.12 MH
RemarksRev.
TRIANGGONO
MEYRI
30.03.2012
YUWONOName NormSIMOPRIME A4
Project:
Symbol library 1:
Symbol library 2:
Symbol library 3:
Symbol library 4:
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro
ELCAD-Version
Translate file A:
Translate file B:
Translate file C:
Translate file D:
7.3.2 SP2
Archive: =04_FVW / A / D / 1
C_FB_EN.etr, 04-11-24
File name: 000267
Last used: 02.04.12
ALL DIMENSIONS ARE IN MILLIMETER.
DESIGNATION
LOCATION
TYPICAL
NAME PLATE
WEIGHT (KGs)
APPROXIMATELY
0
140.0
55.0
200
SCALE
400
=J01
+J01
=JZ02
=J01
CONNECTION
PANEL
725
600
800
140.0
55.0
NOTES:
1. MEANS PANEL/PACKING FOR SHIPPING SEPARATION.
=J02
+J02
=JZ01
=J02
INCOMING
PANEL 1
1095
140.0
55.0
=J03
+J03
=JZ01
=J03
INCOMING
PANEL 2
1095
140.0
55.0
=J04
+J04
=JZ01
=J04
INCOMING
PANEL 3
1095
38.5
2500
25
800 800 800
38.5
1900
25
1 2 3 4 5 6 7 8
F
E
D
C
B
A
F
E
D
C
B
A
20kV SWITCHGEAR
CV. SEMBRANI MITRA TEKNIK
JATIM TAMAN STEEL 2
PANEL FLOOR CUTOUT
GENERAL DOCUMENT
(3)G73012-23336-B1005-A
A
+JZ00
=05_FLC
Sheet 1+
3 Sh.
CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved
Orig./Repl.f./Repl.by
E1
1 2 3 4 5 6 7 8
800
OVERALL LENGTH = 3200
Date
Drawn
Appr.
Date
A FOR APPROVAL 02.04.12 MH
RemarksRev.
TRIANGGONO
MEYRI
30.03.2012
YUWONOName NormSIMOPRIME A4
Project:
Symbol library 1:
Symbol library 2:
Symbol library 3:
Symbol library 4:
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro
ELCAD-Version
Translate file A:
Translate file B:
Translate file C:
Translate file D:
7.3.2 SP2
Archive: =05_FLC / A / E / 1
C_FB_EN.etr, 04-11-24
File name: 000519
Last used: 02.04.12
ALL DIMENSIONS ARE IN MILLIMETER.
DESIGNATION
LOCATION
TYPICAL
NAME PLATE
POWER
CABLE
C3
=J01
+J01
=JZ02
=J01
CONNECTION
PANEL
12X1Cx500mm²
CU/XLPE/PVC
C1
C2
C1
=J02
+J02
=JZ01
=J02
INCOMING
PANEL 1
6X1Cx500mm²
CU/XLPE/PVC
=J03
+J03
=JZ01
=J03
INCOMING
PANEL 2
6X1Cx500mm²
CU/XLPE/PVC
=J04
+J04
=JZ01
=J04
INCOMING
PANEL 3
6X1Cx500mm²
CU/XLPE/PVC
LEGEND:
C1
C2
C3
C4
PANEL FIXING HOLES ( 22 x 46mm SOCKET )
OPENING AREA FOR POWER CABLE ENTRY
FOR REAR ACCESS
FLOOR OPENING AREA
FOR CONTROL CABLE - BOTTOM ENTRY
SWITCHGEAR END WALL
1 2 3 4 5 6 7 8
F
E
D
C
B
A
F
E
D
C
B
A
20kV SWITCHGEAR
CV. SEMBRANI MITRA TEKNIK
JATIM TAMAN STEEL 2
SWITCHGEAR CLEARANCE
GENERAL DOCUMENT
(3)G73012-23336-B1005-A
A
+JZ00
=05_FLC
Sheet2+
3 Sh.
CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved
Orig./Repl.f./Repl.by
E2
1 2 3 4 5 6 7 8
Date
Drawn
Appr.
Date
A FOR APPROVAL 02.04.12 MH
RemarksRev.
TRIANGGONO
MEYRI
30.03.2012
YUWONOName NormSIMOPRIME A4
Project:
Symbol library 1:
Symbol library 2:
Symbol library 3:
Symbol library 4:
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro
ELCAD-Version
Translate file A:
Translate file B:
Translate file C:
Translate file D:
7.3.2 SP2
Archive: =05_FLC / A / E / 2
C_FB_EN.etr, 04-11-24
File name: 000419
Last used: 02.04.12
ALL DIMENSIONS ARE IN MILLIMETER.
MOST LEFT
PANEL
MOST BACK PANEL LINE
MOST RIGHT
PANEL
NOTES:
1.
2.
DIMENSIONS SHOWN ARE MINIMUM VALUES.
MINIMUM ROOM HEIGHT: 2850mm
500
500
2000
1 2 3 4 5 6 7 8
F
E
D
C
B
A
F
E
D
C
B
A
20kV SWITCHGEAR
CV. SEMBRANI MITRA TEKNIK
JATIM TAMAN STEEL 2
FIXING DETAIL
GENERAL DOCUMENT
(3)G73012-23336-B1005-A
A
+JZ00
=05_FLC
Sheet3-
3 Sh.
CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved
Orig./Repl.f./Repl.by
E3
1 2 3 4 5 6 7 8
THIS DRAWING IS FOR REFERENCE ONLY.
ACTUAL CIVIL WORK IS NOT SCOPE OF
PT. SIEMENS INDONESIA
Date
Drawn
Appr.
Date
A FOR APPROVAL 02.04.12 MH
RemarksRev.
TRIANGGONO
MEYRI
30.03.2012
YUWONOName NormSIMOPRIME A4
Project:
Symbol library 1:
Symbol library 2:
Symbol library 3:
Symbol library 4:
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro
ELCAD-Version
Translate file A:
Translate file B:
Translate file C:
Translate file D:
7.3.2 SP2
Archive: =05_FLC / A / E / 3
C_FB_EN.etr, 04-11-24
File name: 000097
Last used: 02.04.12
ALL DIMENSIONS ARE IN MILLIMETER.
HEXAGON CREW & WASHER
HEXAGON CREW & WASHER
EXPANDING ANCHOR WITH
EXPANDING ANCHOR WITH
MOUNTING PLATE
MOUNTING PLATE
BASE CONCRETE
BASE CONCRETE
SCREED
SCREED
44
FLOOR LEVEL
TOP OF FLOOR
FINISH
TOP OF FLOOR
FINISH
+0mm
-0.5mm
80.0
80.0
44
TYPE 1
FLOOR FIXING WELDED
TYPE 2
FLOOR FIXING SCREWED
TYPE 3
FLOOR FIXING SCREWED WITH SPRING NUT
BASEFRAME OF
SWITCHGEAR
BASEFRAME OF
SWITCHGEAR
M12 SPRING NUT
WELDING IN FIXING OPENING
OF SWGR BASE FRAME
HAMMER HEAD SCREW M16x35-4.6-A3L,
WASHER R18 OR PLATE 6x55x70 (18mm DRILLING),
HEXAGON NUT M16-8-A4L
FOUNDATION CHANNEL
(UNISTRUT)
U50 PROFILE
C PROFILE CB 50x30
CEMENT FILLING
MIN. 55mm
MIN. 90mm
MIN. 55mm
MIN. 90mm
13.0
30.0
30.0
(e.p. PROFILE 70x40x2)
MOUNTING CHANNEL
APPROX. 36mm
FLOOR PLATE
145.0
50.0
60.0
MOUNTING PLATE DETAIL
TOP OF
FALSE FLOOR
40.0
80.0
TYPE 4
FIXING ON FALSE FLOOR
HEXAGON SCREW M10
WASHER 10.5-St-A3L
HEXAGON NUT M10-8-A4L
35.0
BASE FRAME OF
THE SWITCHGEAR
NOTE FOR FLOOR FIXING
NOTE FOR FIXING ON FALSE FLOOR
THE METAL FIXING RAIL SHOULD BE LEVEL AND FLAT IN ACCORDANCE WITH THE TOLERANCE
LAID DOWN , THAT IS, 1mm PER M, BUT A MAXIMUM OF 2mm OVER THE TOTAL SWITCHBOARD
LENGTH
WHERE FOUNDATION RAILS BUTT GAINST EACH OTHER, THEY SHOULD BE WELDED TOGETHER
OVER FULL CROSS-SECTION IN ORDER TO SATISFY THE EARTH CONTINUITY REQUIREMENTS.
BEFORE LAYING THE FINAL FLOOR SCREED, ENSURE THAT THE RAILS ARE PROPERLY ALIGNED
LEVELLED WITH WATER GAUGE (OR SIMILAR DEVICE) BY LAYING UNDER OF STEEL SHEETS
AND WELDED TOGETHER THE SUPPPORTING CEMENT FOR FOUNDATION RAILS MUST BE
CONTINUOUS AND LOAD BEARING OVER THE TOTAL RAIL LENGTH.
IF EARTHQUAKE RESISTENT INSTALLATION IS REQUIRED, THE COMPENSATING PLATES,
FOUNDATION RAILS AND THE SWITCHBOARD STRUCTURE MUST BE WELDED TO ONE ANOTHER AND
TO A FLAT STEEL PLATE ANCHORED INTO THE BASE CONCRETE (NELSON ANCHOR) AS
DESCRIBED
THE DETAILS RELATING TO FOUNDATION RAILS, COMPENSATION PLATES AND METHOD OF
FLOOR FINISH : THE FLOOR FINISH SHOULD BE SUCH THAT IT WILL WITHSTAND
THE LOADS STATED THE SPECIFICATIONS. FOR SWITCHGEAR ROOMS A FLOOR FINISH, LOAD
BEARING QUALITY AT LEAST RATED COMPRESSIVE STREGTH 45N/mm², FLEXURALE
THE SUPPORT FRAME SHOULD BE LEVEL AND FLAT WITH TOLERANCE 1mm PER M, BUT
A MAXIMUM 2mm OVER THE TOTAL SWITCHBOARD LENGTH
IF EARTHQUAKE RESISTENT INSTALLATION IS REQUIRED, THE SUPPORT FRAME AND
THE SYSTEM PORT MUST BE WELDED TOGETHER.
EVEN IT WILL BE CONSIDERED THE DIAGONAL STAYS FROM THE SUPPORT FRAME.
THE DETAILS RELATING TO SUPPORT FRAME AND SYSTEM FIXING ARE NOT THEN VALID,
THEY SHOULD BE MODIFIED TO SUIT THE METHOD OF FIXING.
SECURING THE SWITCHBOARD ARE NOT THEN VALID, THEY SHOULD BE MODIFIED TO SUIT
THE METHOD OF FIXING
TENSIDE, GRINDING WEAR 9cm²/50cm² IS NECESSARY. THE UPPER SURFACE OF THE
FLOOR FINISH OR SCREED SHOULD NOT BE HIGHER THAN THE UPPER SURFACE OF THE
FOUNDATION RAILS.
1 2 3 4 5 6 7 8
F
E
D
C
B
A
F
E
D
C
B
A
20kV SWITCHGEAR
CV. SEMBRANI MITRA TEKNIK
JATIM TAMAN STEEL 2
=JZ01 - INCOMING FEEDER
PANEL CONFIGURATION
GENERAL DOCUMENT
(3)G73012-23336-B1006-A
A
+JZ00
=06_SEC
Sheet 1+
2 Sh.
CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved
Orig./Repl.f./Repl.by
F1
1 2 3 4 5 6 7 8
800
FRONT VIEW
310 290
105
590
105
445 775 3050
38.5190025
800
400
50
180
40
1963.5
SIDE VIEW
PANEL OPENING
LEGEND
Date
Drawn
Appr.
Date
A FOR APPROVAL 02.04.12 MH
RemarksRev.
TRIANGGONO
MEYRI
30.03.2012
YUWONOName NormSIMOPRIME A4
Project:
Symbol library 1:
Symbol library 2:
Symbol library 3:
Symbol library 4:
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro
ELCAD-Version
Translate file A:
Translate file B:
Translate file C:
Translate file D:
7.3.2 SP2
Archive: =06_SEC / A / F / 1
C_FB_EN.etr, 04-11-24
File name: 000337
Last used: 02.04.12
ALL DIMENSIONS ARE IN MILLIMETER.
A5
A3
140.0
55.0 A1
A4
A7
A8
A9
A2
A6
2250
25 1900 38.5
697.5
395
B4
C1
B2
C2
B3
C1 C1
C3
B1
FRONT OF
PANELS
FRONT OF
PANELS
A1
A2
A3
A4
A5
A6
A7
A8
A9
B1
B2
B3
B4
C1
C2
C3
PANEL NAMEPLATE
TRUCK INSPECTION WINDOW
HV-DOOR LOCK ACCESS HOLE
MANUAL SPRING CHARGING ACCESS HOLE
MANUAL CB ON / OFF ACCESS HOLES
HANDLE FOR OPENING
OF CB-COMPARTMENT DOOR
INSPECTION WINDOW FOR SPRING CHARGING
INDICATOR AND OPERATING COUNTER
TRUCK MOVEMENT ACCESS HOLES
CABLE EARTHING SWITCH ACCESS HOLE
LOW-VOLTAGE COMPARTMENT
BUSBAR COMPARTMENT
CIRCUIT BREAKER COMPARTMENT
CABLE COMPARTMENT
PANEL FIXING POINTS (46 x 20mm SOCKET)
OPENING AREA FOR BOTTOM POWER CABLE ENTRY
OPENING AREA FOR BOTTOM CONTROL CABLE ENTRY
1 2 3 4 5 6 7 8
F
E
D
C
B
A
F
E
D
C
B
A
20kV SWITCHGEAR
CV. SEMBRANI MITRA TEKNIK
JATIM TAMAN STEEL 2
=JZ02 - CONNECTION PANEL
PANEL CONFIGURATION
GENERAL DOCUMENT
(3)G73012-23336-B1006-A
A
+JZ00
=06_SEC
Sheet2-
2 Sh.
CopyRight (C) PT. Siemens Indonesia 2012 All Rights Reserved
Orig./Repl.f./Repl.by
F2
1 2 3 4 5 6 7 8
800
FRONT VIEW
25 1900 38.5
396.5
600
1045 775 30
50
38.51900
800
400
50
180
40
2563.5
50
25 600
290
105
590
105
SIDE VIEW
PANEL OPENING
LEGEND
Date
Drawn
Appr.
Date
A FOR APPROVAL 02.04.12 MH
RemarksRev.
TRIANGGONO
MEYRI
30.03.2012
YUWONOName NormSIMOPRIME A4
Project:
Symbol library 1:
Symbol library 2:
Symbol library 3:
Symbol library 4:
F:/01_PROJ/23336_/ECAD/23336_AA (LATEST).pro
ELCAD-Version
Translate file A:
Translate file B:
Translate file C:
Translate file D:
7.3.2 SP2
Archive: =06_SEC / A / F / 2
C_FB_EN.etr, 04-11-24
File name: 000216
Last used: 02.04.12
ALL DIMENSIONS ARE IN MILLIMETER.
140.0
55.0 A1
B4
C2 C1
B2
C1 C1
C3
B1
FRONT OF
PANELS
FRONT OF
PANELS
A1
A2
A3
A4
A5
A6
A7
A8
A9
B1
B2
B3
B4
C1
C2
C3
PANEL NAMEPLATE
-
-
-
-
-
-
-
-
LOW-VOLTAGE COMPARTMENT
BUSBAR COMPARTMENT
-
CABLE COMPARTMENT
TOP ENTRY
PANEL FIXING POINTS (46 x 20mm SOCKET)
OPENING AREA FOR TOP POWER CABLE ENTRY
OPENING AREA FOR BOTTOM CONTROL CABLE ENTRY