Post on 07-Feb-2021
transcript
2BC AC1 Type A Bushing for up to 24kV Application
Apparatus Bushing
APPARATUS BUSHING (24kV)
•Features
•Electrical Ratings :
For use on oil-insulated equipment such as transformers, capacitors, and switchgear.System voltage up to 24kV with 250A continuous current.For indoor and outdoor applications.
Can be mounted either vertically or horizontally.The bushing meets the requirements of CENELEC 50180, IEEE Std 386 and IEC 60137
Ardry Group 195 Industrial Blvd. Rincon, GA 31326 USAPhone: +1 (912) 754-2474 www.cablematepower.com
Max. System Voltage : 24kV Impulse withstand : 125kV
Short Circuit Withstand1 sec. (rms sym.) : >12.5kA
Partial Discharge Extinction 10pC max. At : 21kVAC Withatand : 54kVContinuous Current : 250AOverload, 8 hours period : 300A
apparatus bushing 2BC AC1
2BC AC1
Apparatus Bushing
Protective cap to preventcontamination during shipment
Internal screen with earthing plate forcontrolling electrical stress.
High grade copper conductorwith M10 thread for apparatusconnections.
Ardry Group 195 Industrial Blvd.
Rincon, GA 31326 USA Phone: +1 (912) 754-2474
www.cablematepower.com
Suggested minimum oil level.
Drawing for installation
Voltage(kV) X(mm)
1224
4050
Drawing
Ordering information
To order a bushing, please specify :
2BC AC1
To order a clamping device and gasket set,
2BC AC1- DIN
Type A Bushing for up to 24kV Application
out of oursupply scope ▶
OILLEVEL
223.
5
8.0
86.0
108.
021
.5
ø76.0
ø110.0
M10*1.5