7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
1/32
Inspection No. 44682-3128Date: 23-Aug-2012
Visual Property Inspection43460 SW Gaston Rd
Gaston, Oregon 97118
Prepared for :
Kieran MullenGaston, Oregon
Inspected by :Casey Livingston
520 E Washington StCarlton, Oregon 97111
Phone: (503) 537-0415 Fax: (866) 238-3421 Email:casey.livingston@pillartopost.com
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
2/32
THIS REPORT IS INTENDED ONLY FOR THE USE OF THE PERSON PURCHASING THEHOME INSPECTION SERVICES. NO OTHER PERSON, INCLUDING A PURCHASER OF
THE INSPECTED PROPERTY WHO DID NOT PURCHASE THE HOME INSPECTIONSERVICES, MAY RELY UPON ANY REPRESENTATION MADE IN THE REPORT.This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
Property and Site1.0
Building
For the purposes of this review, the front of the structure faces east. All references to direction contained within thisreport reflect this orientation.
The house has been vacant. This can make finding some problems such as plumbing leaks, etc, more difficult (if notimpossible) to detect.
House is older and may have systems or components that by todays standards would be insufficient or improper. It isnot the responsibility of the home inspector to detail individual components or systems that were acceptable at timeof construction but may be considered improper or insufficient by todays standards.
Older vintage home in a state of deferred maintenance needing a significant amount of repairs and upgrades, manyof a minor or cosmetic nature too numerous to mention.
Porch
Loose and warped deck boards noted at the east large deck creating trip hazards. Repairs advised for safety.
Porch Railing
Railing on porch is loose and requires rectification.
Front Porch Receptacle
Hot & neutral wires are reversed in outlet (outlet itself or something somewhere "upstream" from the outlet was wiredbackwards). This can cause some things to not work correctly and is a safety hazard. Correction required by alicensed electrician.
Exterior 2.0
Foundation Wall
Foundation has typical cracks.
Undermining noted at the west wall. Backfilling required to reduce the chance of settlement or damages.
Ensure all openings to the crawl space are properly closed and covered to reduce the chance of vermin intrusion andrelated damages.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
3/32
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
Exterior 2.0
Wall Surface
Siding, trims, and some soffits are unpainted. Proper prepping and painting required to prolong the life of thematerials.
Caulking appears to be separating at various places around the house. Recommend inspection and repair by alicensed & qualified siding contractor to reduce the chance of moisture problems.
The upper edges of the siding on the east and west walls of the north addition are only protected from moistureintrusion by trims that are caulked in place but may still be allowing moisture intrusion. Review and correction by aqualified contractor advised.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
4/32
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
Exterior 2.0
Windows
North window at the east end of the addition is improperly installed and could allow moisture intrusion and lead todamages.
Receptacle
Recommend installation of a GFCI (Ground Fault Circuit Interrupter) receptacle in the outside Christmas lightreceptacle on the roof to reduce risk of electrical shock.
Roof Structure3.0
Gutter/Downspout
Downspouts are missing around the house and the garage. Replacement required to provide proper drainage awayfrom the house in order to reduce the chance of moisture intrusion at the crawl space or foundation damages.
Clean and maintain gutter system to promote drainage toward downspout.
Fascia
Signs of rot noted at the SW fascia. Repairs to all damaged materials required.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
5/32
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
Roof Structure3.0
Covering
Moss treatment & removal recommended to reduce the chance of premature damage to the roof.
Recommend cleaning tree debris out of valleys and between shingles (the keyways) for improved water run-off.
All tree branches should be kept trimmed back at least 6 to 8 feet from roof & gutters to extend their life, reducedebris & the chance of damage.
Unable to determine exact number of layers but there appears to be 3 if not more.Many shingles do not appear to beproperly secured, have minimal fasteners, or are just installed wrong. Advise review by a qualified roofer todetermine the need for repair or replacement to reduce the chance of premature failure or damages.
Ladder blocking was still in place on the north side of the west crawl space. This can cause a back up of debris andtrap moisture leading to leaks or damages. Removal and sealing of holes required to reduce the chance of damages.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
6/32
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
Roof Structure3.0
Accessory
There is no plumbing vent stack pipe in the boot on the south side of the roof leaving a hole that will allow moistureintrusion. Repairs required.
Attic4.0
Structure
Rot noted in the framing at the upper attic hatch. Insulation prevents me from being able to determine if additionaldamages exist. Repairs to damages required. If additional damages are found they too require repairs.Low clearances and deep insulation prevent me from accessing the upper attic.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
7/32
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
Attic4.0
Sheathing
Original sheathing boards have staining from previous moisture intrusion, however new plywood sheathing above itfrom newer roof shows no evidence of continued leakage.
Crawlspace5.0Floor Joists
Old termite mud tubes noted in the west crawl space on the east side of the crawl at floor joist ends and a fewlocations along the beam. Damages only appeared to be superficial, but as I was limited by waste water I was unableto access the west side to determine if additional damages exist. Advise review to determine if damaged areas existthat should be repaired. Repair or replace damages as needed.
Sill Plate
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
8/32
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
Crawlspace5.0
Sill plate at the top of the stem walls as seen near the NE access hatch are damaged by past insect activity. I amunable to determine the extent of the damages. Removal and repair of all damaged materials required.
Bearing Wall
What appeared to be settlement noted at the stem walls as seen in the Northern most crawl space. No damageswere noted in relation to this, but it is one of the likely causes of the unlevel floors in the house. Shimming has beenadded to make joists as level as they could.
Crawl Space
Pooling waste water from damaged waste lines requires removal and area treated for any bacteria that may be leftdue to this.
No vapor barrier was laid across the ground under the north addition and no insulation was installed on the sub floor.Installation of 6mm black visqueen vapor barrier with 6" (min) overlaps at seams required over all exposed dirt incrawlspace. Advise adding insulation as well for improved insulating values.
Heating6.0
Smoke Detectors
Current smoke alarms do not meet the new standards.
As of January 1, 2002, per HB2586 & ORS479-260 (revised) when a dwelling is sold, Oregon State Law nowrequires that ionization smoke alarms must include a hush feature, and, if solely battery-powered, must have a ten-year battery. For added occupant safety it is advised that all steps necessary to comply with this law be taken. Allnon-compliant alarms must be removed and if alarms are already hard-wired the replacement alarms must also behard-wired.
Recommend placing smoke alarms on every level of the home, outside each sleeping area (ie. the hall outside thebedrooms) and in every bedroom for added safety.
CO Detectors
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
9/32
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
Heating6.0Carbon monoxide detectors were not found but are recommended for occupant safety on each living floor in homeswith any of the following: fossil burning fuels used in any appliance or fireplace, wood burning fireplaces, an attachedgarage.
Electric Heating
I am only able to determine if the electric heaters are operational and not their ability to actually heat the home.
Minimal heating noted in the house. Review and as needed installation of additional heat sources advised by aqualified contractor.
Plumbing Components7.0
Hose Bibb
Leaking bibb handle noted at the SW corner. Repairs advised to reduce the chance of damages.
Distribution Piping
Water lines and waste line ran on the outside of the house. This is improper and very prone to damages. Removal or relocation required.
Plumbing lines are not properly secured, this can lead to leaks, repair recommended by a licensed plumber.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
10/32
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
Plumbing Components7.0
Waste Drainage
Water was noted pooling in the crawl space from an open waste line under the bathroom. Review and repairs to thewaste line system required.
Sewer odor was detected which suggests poor or improper venting. This could also suggest the lack of a trap.
Slope of the waste piping is not conducive to good drainage, inspection and correction by a licensed plumber recommended.
Old waste lines were noted in the SW corner of the crawl space. These were left open and may still be connected tothe main waste line which would allow sewer gases to enter the house or crawl space. If gases accumulate at theright levels it could, in the worst case scenario, run the risk of combusting. Removal and capping required.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
11/32
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
Bathroom8.0
Water Flow
Low flow noted at the sink. Review and repairs by a qualified contractor required.
Floor
Floor surface is uneven and there are elevated moisture levels near the toilet and sink areas. I am unable todetermine if hidden damages exist. Invasive review and as needed repairs to all damaged materials required.
Lighting
Missing light fixture. Provide replacement.
Receptacle
Recommend installation of GFCI (Ground Fault Circuit Interrupter) receptacles within 6' of any water source (sink,tub, etc) to reduce the risk of electrical shock.
Trap/Drain
There is no trap in the plumbing line under the sink, this can allow sewer gases to enter the dwelling, correctionrequired by a licensed plumber.
Kitchen9.0
Receptacle
Receptacles require covers.
Loose outlets require securing.
No power to fridge outlet and romex is spliced and wrapped in tape near the outlet. Repair required by a licensedelectrician.
Faucet
Faucet base leaks. Repairs required.
Trap/Drain
Waste line is held together with bungee cords and there is no trap. Repairs required by a qualified plumber.
Waste line is leaking below the level of the cabinets. I am unable to determine the source of the leak, but at least theentire home slopes to the south side providing adequate slope for drainage to the bathroom.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
12/32
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
Kitchen9.0
Cabinet
Damaged cabinets and doors noted. Repairs required.
Range Hood
Electrical to the exhaust hood is connected to the outlet down and to the right in the wall and flickers on whenshaking the outlet. Review and repairs required by a qualified electrician.
Foyer 10.0
Stairway
Damaged tread noted at the top of the stairs. Repairs required for safety.
Railing
Handrail on upper stairs is loose and should be secured.
Front Door
Weather stripping is damaged, repair or replacement advised.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
13/32
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
North Family Room11.0
Wall
Possible mold or mildew noted on wall. Unable to determine if it is a type that can cause health problems or if hiddendamage has occurred. Elimination of mold required for health reasons and repair any damage if found. If concern stillexists have inspected by a contractor specializing in this type condition.
Previously noted mold/mildew as well as staining was noted in the inner corners where the room meets the outer wallof the house as well as along the outer walls on the sides of the room where they meet the roof. I am unable todetermine the moisture source leading to these issues but it could be due to roof leaks, improper attic ventilation,lack of siding flashings at siding joints on the outer walls, or improper insulation and vapor barrier under the addition
allowing moisture vapor to enter through the structure from below. Advise review by a qualified contractor.Repair/renovate as needed.
Lighting
Missing light fixtures. Provide replacements.
Living Room12.0
Lighting
Missing light fixtures. Provide replacements.
Receptacle
No power to receptacles in the north half of the room. Breaker or GFCI may be off. If this is not the case or resettingthese devices does not correct the problem then inspection and repair of problem is recommended by a licensedelectrician.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
14/32
This summary is not the entire report. The complete report may include additional information of concern to theclient. It is recommended that the client read the entire report.
Casey LivingstonCCB 156934 OCHI 779
43460 SW Gaston Rd, Gaston, Oregon 97118
Report Commentary
Date: 23-Aug-2012
Upper Bedroom13.0
Lighting
Light not working. Check bulb, if this is not the problem investigation by a licensed electrician is required.
Heat Source
Knob is missing, recommend replacement.
SE Bedroom14.0
Window
South window does not appear to have proper header framing. Advise review by a qualified contractor. Repair asneeded.
Heat Source
Loose wall heater cover requires securing for safety. Replace missing knob for thermostat
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
15/32
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
16/32
Foundation has typical cracks.
Undermining noted at the west wall. Backfilling required to reduce the chance of settlement or damages.
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
structure such as bees, non-wood destroying ants, flies, spiders, rodents, etc are not reported in this inspection.
Foundation Vents BuriedErosionEarth to WoodRavineTreePlantsFlower BedSlopes to House
Damaged: NoLandscaping
Trip HazardCrack SettlementSlopes to HouseBrick ConcreteGravelPaving StoneAsphalt
Damaged: NoDriveway
Trip HazardSettlementSlopes to HouseCrack GravelWoodAsphaltConcreteBrick Patio Block Paving Stone
Damaged: NoWalkway/Path
SettlementResealEarth to WoodRotCorrosionCrack UnsecuredTileWoodBrick CompositeConcrete
Damaged: NoPorch
Loose and warped deck boards noted at the east large deck creating trip hazards. Repairs advised for safety.
RotIncomplete NoneUnsecuredWoodMetalPlasticComposite
Damaged: NoPorch Railing
Railing on porch is loose and requires rectification.
Unsecured NoneOperational: YesFront Porch Lighting
Cover Damaged No Cover Recommend GFCIHot/Neutral Reversed
Damaged: NoFront Porch Receptacle
Hot & neutral wires are reversed in outlet (outlet itself or something somewhere "upstream" from the outlet was wired backwards). This can cause some things to not work correctly and is a safety hazard. Correction required by a licensed electrician.
Exterior
RestrictedSnowVegetationDebrisSeasonal Storm WindowsClearance
Limitations
Foundation Parged Not VisibleDeteriorationCrack Post and Pier ConcreteBrick Cinder Block Stone
Damaged: NoFoundation Wall
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
17/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
Cracks that could be seen in the foundation at the time of the inspection appeared to be typical. Recommendmonitoring for signs of future movement/expansion. If still concerned, even though all concrete will crack slightly whiledrying, I would recommend further evaluation by a qualified contractor.
Ensure all openings to the crawl space are properly closed and covered to reduce the chance of vermin intrusion and related damages.
Earth to SidingStainingRotMold/MildewCrack Recaulk RepaintBlister/PeelRepointLooseSplitVinylAluminumEFISStoneCompositeWoodBrick Shingle
Damaged: NoWall Surface
A piece-by-piece search of the siding was not performed and is beyond the scope of this inspection.
Siding, trims, and some soffits are unpainted. Proper prepping and painting required to prolong the life of the materials.
Caulking appears to be separating at various places around the house. Recommend inspection and repair by alicensed & qualified siding contractor to reduce the chance of moisture problems.
The upper edges of the siding on the east and west walls of the north addition are only protected from moistureintrusion by trims that are caulked in place but may still be allowing moisture intrusion. Review and correction by aqualified contractor advised.
StainingRotDamaged FlashingPoor TrimMold/MildewRecaulk RepaintBlister/PeelStormInspected with Binoculars
Damaged: NoWindows
North window at the east end of the addition is improperly installed and could allow moisture intrusion and lead todamages.
DelaminatingSplitStainingMold/MildewRotRecaulk RepaintUnsecuredStormDamagedBinds
Operational: YesDoors
Exposed WiringUnsecured NoneOperational: YesLighting
Open Ground No GroundReverse PolarityInstall GFCIDamagedOperational: YesReceptacle
Recommend installation of a GFCI (Ground Fault Circuit Interrupter) receptacle in the outside Christmas light receptacle on the roof to reduce risk of electrical shock.
Roof Structure
Walk OnRoof EdgeBinocular Inspected By:
Other No AccessSolar PanelSlick SurfaceSnowIceRainFragileSteep SlopeHeight
Limitations
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
18/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
Estimated Slope: med-steepEstimated Age: 4-7 yearsOther ShedHipValleyGableFlat
Main Roof Type
CleanRedirect Leader Extended Leader Drainage Below GroundDrainage Above GroundLeak CorrosionDent
IncompletePlasticCopper GalvanizedAluminumUnsecuredDamaged: NoGutter/Downspout
Monitor gutters and downspouts on a continuing basis during periods of rain. Seal any leaking joints and clean andclogs in the gutters, downspouts and drains as needed.
Downspouts are missing around the house and the garage. Replacement required to provide proper drainage away from the house in order to reduce the chance of moisture intrusion at the crawl space or foundation damages.
Clean and maintain gutter system to promote drainage toward downspout.
RepaintUnpaintedPaint PeelingStainRotMildew/MoldLooseOther VinylWoodAluminum
Damaged: NoFascia
Signs of rot noted at the SW fascia. Repairs to all damaged materials required.
RepaintPaint Peel/Flake Not VentedUnpaintedStainedRotVinylWoodMetal
Damaged: NoSoffit
Estimated # of Layers 3MossImproper Installation
CurlWornMildewPatchedCrack BrokenMissingLoose Nail PopOther RollMetalTar Wood ShakeWood ShingleTileShingle
Damaged: NoCovering
The evaluation of the roof provided by this inspection is meant as a general guideline only and does not constitute aformal roof certification. Some deficiencies such as leaks may or may not be visible on the day of the inspection.
Accordingly it does not include any guarantees against leaking nor the need for roof repairs or replacement. If a preciseestimate of the current condition and remaining usefulness of the roof is needed contact a licensed roofer for a fulltechnical evaluation.
Moss treatment & removal recommended to reduce the chance of premature damage to the roof.
Recommend cleaning tree debris out of valleys and between shingles (the keyways) for improved water run-off.
All tree branches should be kept trimmed back at least 6 to 8 feet from roof & gutters to extend their life, reduce debris& the chance of damage.
Unable to determine exact number of layers but there appears to be 3 if not more.Many shingles do not appear to be properly secured, have minimal fasteners, or are just installed wrong. Advise review by a qualified roofer to determinethe need for repair or replacement to reduce the chance of premature failure or damages.
Ladder blocking was still in place on the north side of the west crawl space. This can cause a back up of debris and trap moisture leading to leaks or damages. Removal and sealing of holes required to reduce the chance of damages.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
19/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
DishAntennaSkylightSolar PanelElectrical MastMechanical VentPlumbing Stack Attic VentUnsecured
Damaged: NoAccessory
There is no plumbing vent stack pipe in the boot on the south side of the roof leaving a hole that will allow moistureintrusion. Repairs required.
Replace When Re-roofingImproper ResealTarredCorrosionDeteriorationGapRubber Copper AluminumRoll RoofingValleyStack Roof to WallSkylightFlat Roof Drip EdgeDormer Chimney Not Checked
Damaged: NoFlashing
Attic
InsulatedPull DownHatchEnteredLooked InStored ItemsSealed No Access
Limitations
SplitSagStainWarpedRafter TrussDamaged: NoStructure
Rot noted in the framing at the upper attic hatch. Insulation prevents me from being able to determine if additional damages exist. Repairs to damages required. If additional damages are found they too require repairs.Low clearances and deep insulation prevent me from accessing the upper attic.
StainSagMildewBoardPlywoodOSBCondensation
Damaged: NoSheathing
Original sheathing boards have staining from previous moisture intrusion, however new plywood sheathing above it from newer roof shows no evidence of continued leakage.
Estimated Depth 16RequiredSprayedBlownBatt
Other FoamRigid PlasticWood ShavingsCelluloseMineralFiberglassVapor Barrier NoneFinishedConcealedRadiant Barrier
Damaged: NoInsulation
RequiredBlockedRoof BafflesMechanicalTurbineGable EndSoffit None
Damaged: NoVentilation
MetalPlasticInto Attic Not InsulatedConcealedDamaged: NoExhaust Duct
FrayedOpen SpliceKnob & TubAbandonedConcealedDamaged: NoElectrical
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
20/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
Crawlspace
Dry GroundDry Weather Clutter Limitations
Mold/Mildew/FungusRotStainSplitUnsecuredConcealed
Damaged: NoFloor Joists
Old termite mud tubes noted in the west crawl space on the east side of the crawl at floor joist ends and a few locationsalong the beam. Damages only appeared to be superficial, but as I was limited by waste water I was unable to accessthe west side to determine if additional damages exist. Advise review to determine if damaged areas exist that should be repaired. Repair or replace damages as needed.
UnsecuredSolid WoodX-WoodX-MetalContinuousConcealedDamaged: NoBridging
Insect FrassRotStainConcealedDamaged: NoSill Plate
Sill plate at the top of the stem walls as seen near the NE access hatch are damaged by past insect activity. I amunable to determine the extent of the damages. Removal and repair of all damaged materials required.
Mildew/Mold/FungusRotSagMetalWoodLaminateConcealedUnsecured
Damaged: NoBeam
WoodConcreteBrick AdjustableConcealedOn Slab Damaged: NoPost
ConcealedDamaged: NoBearing Wall
What appeared to be settlement noted at the stem walls as seen in the Northern most crawl space. No damages werenoted in relation to this, but it is one of the likely causes of the unlevel floors in the house. Shimming has been added tomake joists as level as they could.
Standing Water Ventilation Blocked Inadequate Ventilation No AccessInadequate Clearance
Mold/MildewMoisture Barrier RequiredEarth Floor Concrete Floor DampMoisture StainingEnteredLooked InInsulatedVapor Barrier
Damaged: NoCrawl Space
Pooling waste water from damaged waste lines requires removal and area treated for any bacteria that may be left dueto this.
No vapor barrier was laid across the ground under the north addition and no insulation was installed on the sub floor.Installation of 6mm black visqueen vapor barrier with 6" (min) overlaps at seams required over all exposed dirt incrawlspace. Advise adding insulation as well for improved insulating values.
InsulatedLeak UnsecuredPipes/Ducts
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
21/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
RequiredBlockedMechanicalVentilation
Electrical Service
DamagedFrayedUnsecured120/240 Volt No ConduitOverheadUnderground
Service Entrance
Electrical systems are inspected only in a very limited and general way. We do not check low voltage wiring, 220-voltoutlets and/or systems. This is not a direct attempt to identify code violations.
Per State standards personal items will not be moved or unplugged. Therefore accessible receptacles and switches willbe checked for operations but not load capacity. Only exterior receptacles attached to the house will be checked. Noancillary or low voltage wiring is checked. 3-prong receptacles are checked for polarity and grounding, 2-prong
receptacles for polarity and operation. Volt meters are not used.
Double TappingCopper AluminumConcealedEntrance Cable
Breaker Switch/Cartridge FuseMain Disconnect
Amps 125 No Main Shut-Off
Disconnect Rating
Location living roomObsolete
CorrosionUnsecuredObstructed Non Standard Installation Not OpenedDamaged: NoDistribution Panel
Amps 125Room For Expansion
Panel Rating
Over-FusedAFCI Breaker GFCI Breaker Breaker Breakers
Determining if electrical panels are labeled accurately is beyond the scope of this inspection.
ScorchedCorrosionDouble TappingKnob & TubOther Copper Braided AluminumSolid AluminumTin Clad
Damaged: NoCircuit Wire
Improper Water MainGround RodConcealedGrounding
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
22/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
Heating
Other 3rd Floor 2nd Floor 1st Floor BasementOperational: YesSmoke Detectors
Current smoke alarms do not meet the new standards.
As of January 1, 2002, per HB2586 & ORS479-260 (revised) when a dwelling is sold, Oregon State Law now requiresthat ionization smoke alarms must include a hush feature, and, if solely battery-powered, must have a ten-year battery.For added occupant safety it is advised that all steps necessary to comply with this law be taken. All non-compliant alarms must be removed and if alarms are already hard-wired the replacement alarms must also be hard-wired.
Recommend placing smoke alarms on every level of the home, outside each sleeping area (ie. the hall outside thebedrooms) and in every bedroom for added safety.
Other 3rd Floor 2nd Floor 1st Floor BasementOperational: YesCO Detectors
Carbon monoxide detectors were not found but are recommended for occupant safety on each living floor in homeswith any of the following: fossil burning fuels used in any appliance or fireplace, wood burning fireplaces, an attached garage.
ScorchedCorrosionDamaged FinsLoose ConnectionRadiantBaseboardBoiler Forced Air Not Tested
Damaged: NoElectric Heating
I am only able to determine if the electric heaters are operational and not their ability to actually heat the home.
Minimal heating noted in the house. Review and as needed installation of additional heat sources advised by a qualified contractor.
Plumbing Components
Other Water is Shut Off Private SystemFinished BasementNot ApplicableLimitation
HighTypicalLowNot ApplicableWater Pressure
CorrosionOperational: YesWell System
Leak CorrosionUnsecuredRecaulk DamagedAnti-SiphonFrost Free Not Checked
Operational: NoHose Bibb
What is a hose bibb you ask? A hose bibb is an apparatus used to extend a water line allowing a garden hose toconnect with a hose end attachment for tasks such as watering plants, washing the car, etc.
Do not leave hoses connected to faucets during cold weather as this may allow freezing and consequent damage.
Leaking bibb handle noted at the SW corner. Repairs advised to reduce the chance of damages.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
23/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
InsulatedConcealedLeak CorrosionUnsecuredDissimilar MaterialCopper PlasticGalvanizedLead
Damaged: NoDistribution Piping
The purpose of the inspection is to determine if the plumbing system is currently functional or not. A technicalevaluation to determine the adequacy or ongoing usefulness of the plumbing pipes, fixtures, etc is not included. Thisservice can be performed by a licensed plumber if desired. Also, drain lines from the house to the street, particularly inolder homes, may fail over time and require repair or replacement.
It is recommended that you have the drain lines "scoped" from the house to the street or septic tank prior to closing.
Water lines and waste line ran on the outside of the house. This is improper and very prone to damages. Removal or relocation required.
Plumbing lines are not properly secured, this can lead to leaks, repair recommended by a licensed plumber.
Advise System be ScopedConcealedLeak CorrosionUnsecuredOdor Copper PlasticCast IronGalvanized
Damaged: NoWaste Drainage
Buried &/or concealed sewer drain lines are outside the scope of this inspection. Sewer lines can often be partiallyobstructed, cracked, crushed, disconnected or in some other way damaged in a way that would not be detected in thisinspection. Repairs for this type of deficiency can be quite costly. Having such lines inspected/scoped by a qualifiedplumbing contractor may be prudent.
Water was noted pooling in the crawl space from an open waste line under the bathroom. Review and repairs to thewaste line system required.
Sewer odor was detected which suggests poor or improper venting. This could also suggest the lack of a trap.
Slope of the waste piping is not conducive to good drainage, inspection and correction by a licensed plumber recommended.
Old waste lines were noted in the SW corner of the crawl space. These were left open and may still be connected to themain waste line which would allow sewer gases to enter the house or crawl space. If gases accumulate at the right
levels it could, in the worst case scenario, run the risk of combusting. Removal and capping required.
ConcealedLeak CorrosionUnsecuredUndersizedCopper PlasticCast IronGalvanized
Damaged: NoVent Stack/Piping
Damaged Cover Improper PlugConcealedDamaged: NoMain Sewage Cleanout
Serial #: 0209r10179Estimated Capacity/Gallons 50Year: 2009Leak Corrosion
UnsecuredOilGasElectricPower-VentedHybrid HeatingOperational: YesWater Heater
ExceededEndMiddleTypicalLife Expectancy
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
24/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
RequiredRecommendedImproper MissingEarthquake Strapping
Other Corrosion No Test Lever Not ApplicableRelief Valve
DischargeUndersizedDischarge Tube
Bathroom
Other 3rd Floor 2nd Floor 1st Floor BasementNot ApplicableLocation
LowSuspect NormalNot ApplicableWater Flow
Low flow noted at the sink. Review and repairs by a qualified contractor required.
WornTornCrack StainCeramicConcreteVinylLaminateWoodCarpet
Damaged: NoFloor
Floor surface is uneven and there are elevated moisture levels near the toilet and sink areas. I am unable to determineif hidden damages exist. Invasive review and as needed repairs to all damaged materials required.
StainCrack PatchedBrick CeramicDrywallPlaster WoodWallpaper
Damaged: NoWall
StainPatchedCrack TileStippleDrywallPlaster WoodWallpaper
Damaged: NoCeiling
Damaged
Not TestedFoggedBindsStainMold/MildewVinyl CladVinylWoodMetalSingle PaneThermal PaneSkylightAwningCasementSlidingFixedDouble HungSingle Hung
Operational: YesWindow
DamagedBindsMissingWoodCompositeHingedBi-FoldPocket
Operational: YesDoor
Exposed WiringUnsecured NoneOperational: YesLighting
Missing light fixture. Provide replacement.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
25/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
Open J-BoxOpen Ground2 ProngedReverse PolarityInstall GFCIUnsecured No Cover Damaged
Operational: YesReceptacle
Recommend installation of GFCI (Ground Fault Circuit Interrupter) receptacles within 6' of any water source (sink, tub,etc) to reduce the risk of electrical shock.
Advise InstallationDamaged NoisyCover MissingOperational: YesExhaust Fan
CorrosionUnsecuredCrack ChipWornPedestalDamaged: NoSink
DamagedSpraysLeak CorrosionUnsecuredSticks No Shut-off Operational: YesFaucet
Flex PipeLeak CorrosionSlow DrainImproper TrapUnsecuredDamaged: NoTrap/Drain
There is no trap in the plumbing line under the sink, this can allow sewer gases to enter the dwelling, correctionrequired by a licensed plumber.
UnsecuredWornLoose HardwareDamaged Hardware
Mold/MildewLaminateWoodPlywoodMetalDamaged: NoVanity
UnsecuredWornRegroutRecaulk LaminateTileSolid SurfaceMarble/Granite
Damaged: NoCounter Top
Leak Crack UnsecuredTank Loose No Shut-Off Operational: YesToilet
WornCrack MildewRecaulk/RegroutCast IronPlasticFiberglassCultured MarbleTileUnsecured
Damaged: NoTub/Enclosure
Leak MissingCorrosionUnsecuredCloggedSticks Not Tested
Operational: YesTub Faucet/Shower Head
CrackedStopper DamagedStopper MissingSlow DrainDamaged: NoTub Drain
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
26/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
WornScratchMildewRegroutPlasticFiberglassCultured MarbleTileUnsecured
Damaged: NoShower Enclosure
Leak MisingCorrosionUnsecuredCloggedSticks Not Tested
Operational: YesShower Faucet/Head
NoneHeat LampAir Register Electric Wall Heater Radiant Floor Baseboard
Heat Source
Kitchen
WornTornStainCrack TileConcreteVinylLaminateWoodCarpet
Damaged: NoFloor
StainCrack PatchedBrick CeramicDrywallPlaster WoodWallpaper
Damaged: NoWall
StainPatchedCrack TileStippleDrywallPlaster WoodWallpaper
Damaged: NoCeiling
Damaged Not TestedFoggedBindsStainedMold/MildewVinyl CladVinylWoodMetalSingle PaneThermal PaneSkylightAwningCasementSlidingFixedDouble HungSingle Hung
Operational: YesWindow
Exposed WiringUnsecuredMissingOperational: YesLighting
Open J BoxOpen Ground2 ProngedReverse PolarityInstall GFCIUnsecured No Cover Damaged
Operational: YesReceptacle
Receptacles require covers.
Loose outlets require securing.
No power to fridge outlet and romex is spliced and wrapped in tape near the outlet. Repair required by a licensed electrician.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
27/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
Leak CorrosionCrack ChipEnamelCompositeMetalConcrete
Damaged: NoSink(s)
DamagedSpraysLeak CorrosionUnsecuredSticks No Shut-Off Valve
Operational: YesFaucet
Faucet base leaks. Repairs required.
Flex PipeLeak CorrosionSlow DrainImproper TrapUnsecuredDamaged: NoTrap/Drain
Waste line is held together with bungee cords and there is no trap. Repairs required by a qualified plumber.
Waste line is leaking below the level of the cabinets. I am unable to determine the source of the leak, but at least theentire home slopes to the south side providing adequate slope for drainage to the bathroom.
UnsecuredWornRegroutRecaulk LaminateTileSolid SurfaceMarble/Granite
Damaged: NoCounter Top
UnsecuredWornLoose HardwareDamaged HardwareMold/MildewLaminateWoodPlywoodMetal
Damaged: NoCabinet
Damaged cabinets and doors noted. Repairs required.
Noisy No Light No ExhaustCorrosionCooktop ExhaustOperational: YesRange Hood
Electrical to the exhaust hood is connected to the outlet down and to the right in the wall and flickers on when shaking the outlet. Review and repairs required by a qualified electrician.
Improper ConcealedTo Exterior Into AtticWith Other ExhaustUnsecuredDuctless
Damaged: NoExhaust Vent
UnsecuredGreasyMissingDamaged: NoExhaust Filter
Did Not Test All FunctionsTested ON/OFF only.Not ApplicableMajor Appliances (Built-in)
If the future operation of the kitchen appliances is a concern we recommend that you invest in a home warrantydesigned for repair or replacement of mechanical item failures in the homes. Appliances are tested to insure that thereis power to the unit. They are not tested at various operational settings etc. and no warranties concerning satisfactoryoperation are given.
Appliances are not moved during the inspection.
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
28/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
NoneElectric Wall Heater Air Register Radiant CeilingRadiant Floor Baseboard
Heat Source
Foyer
WornTornStainCrack TileConcreteCarpetVinylWoodLaminate
Damaged: NoFloor
StainCrack PatchedBrick TileDrywallPlaster WoodWallpaper
Damaged: NoWall
StainPatchedCrack TileStippleDrywallPlaster WoodWallpaper
Damaged: NoCeiling
Exposed WiringUnsecuredMissingOperational: YesLighting
Open J BoxOpen Ground2 ProngedReverse PolaritySwitchedUnsecured No Cover Damaged
Operational: YesReceptacle
Trip HazardWornWoodVinylCarpetUnsecuredDamaged: NoStairway
Damaged tread noted at the top of the stairs. Repairs required for safety.
NoneUnsafe SpacingIncompleteWoodMetalUnsecuredDamaged: NoRailing
Handrail on upper stairs is loose and should be secured.
WornSplit
Weather SealDead BoltWoodMetal CladBindsDamagedOperational: YesFront Door
Weather stripping is damaged, repair or replacement advised.
North Family Room
WornTornStainCrack TileConcreteCarpetVinylWoodLaminate
Damaged: NoFloor
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
29/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
StainCrack PatchedBrick CeramicDrywallPlaster WoodWallpaper
Damaged: NoWall
Possible mold or mildew noted on wall. Unable to determine if it is a type that can cause health problems or if hiddendamage has occurred. Elimination of mold required for health reasons and repair any damage if found. If concern still exists have inspected by a contractor specializing in this type condition.
Previously noted mold/mildew as well as staining was noted in the inner corners where the room meets the outer wall of the house as well as along the outer walls on the sides of the room where they meet the roof. I am unable to determinethe moisture source leading to these issues but it could be due to roof leaks, improper attic ventilation, lack of siding flashings at siding joints on the outer walls, or improper insulation and vapor barrier under the addition allowing moisture vapor to enter through the structure from below. Advise review by a qualified contractor. Repair/renovate asneeded.
StainPatchedCrack TileStippleDrywallPlaster WoodWallpaper
Damaged: NoCeiling
Damaged Not TestedFoggedBindsStainMold/MildewVinyl CladVinylWoodMetalSingle PaneThermal PaneSkylightAwningCasementSlidingFixedDouble HungSingle Hung
Operational: YesWindow
MissingDamagedBindsWoodCompositeHingedBi-FoldPocket
Operational: YesDoor
Exposed WiringUnsecuredMissingOperational: YesLighting
Missing light fixtures. Provide replacements.
Open J BoxOpen Ground2 ProngedReversed PolaritySwitchedUnsecured No Cover Damaged
Operational: YesReceptacle
NoneElectric Wall Heater Air Register Radiant CeilingRadiant Floor Baseboard
Heat Source
Living Room
WornTornStainCrack TileConcreteCarpetVinylWoodLaminate
Damaged: NoFloor
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
30/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
StainCrackedPatchedConcreteCeramicDrywallPlaster WoodWallpaper
Damaged: NoWall
StainCrack PatchedTileStippleDrywallPlaster WoodWallpaper
Damaged: NoCeiling
Damaged Not TestedFoggedBindsStainMold/MildewVinyl CladVinylWoodMetalSingle PaneThermal PaneSkylightAwningCasementSlidingFixedDouble HungSingle Hung
Operational: YesWindow
VinylMetalWoodHingedSlidingDamagedBinds
Operational: YesPatio Door
Exposed WiringUnsecuredMissingOperational: YesLighting
Missing light fixtures. Provide replacements.
Open J BoxOpen Ground2 Pronged
Reversed PolaritySwitchedUnsecured No Cover DamagedOperational: YesReceptacle
No power to receptacles in the north half of the room. Breaker or GFCI may be off. If this is not the case or resetting these devices does not correct the problem then inspection and repair of problem is recommended by a licensed electrician.
NoneElectric Wall Heater Air Register Radiant CeilingRadiant Floor Baseboard
Heat Source
Upper Bedroom
WornTornStainCrack TileConcreteCarpetVinylWoodLaminate
Damaged: NoFloor
StainCrack PatchedConcreteCeramicDrywallPlaster WoodWallpaper
Damaged: NoWall
StainPatchedCrack TileStippleDrywallPlaster WoodWallpaper
Damaged: NoCeiling
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
31/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
Damaged Not TestedFoggedBindsStainMold/MildewVinyl CladVinylWoodMetalSingle PaneThermal PaneSkylightAwningCasementSlidingFixedDouble HungSingle Hung
Operational: YesWindow
Exposed WiringUnsecuredMissingOperational: YesLighting
Light not working. Check bulb, if this is not the problem investigation by a licensed electrician is required.
Open J BoxOpen Ground2 ProngedReversed PolaritySwitchedUnsecured No Cover Damaged
Operational: YesReceptacle
NoneElectric Wall Heater Air Register Radiant CeilingRadiant Floor Baseboard
Heat Source
Knob is missing, recommend replacement.
SE Bedroom
WornTornStainCrack
TileConcreteCarpetVinylWoodLaminateDamaged: NoFloor
StainCrack PatchedConcreteCeramicDrywallPlaster WoodWallpaper
Damaged: NoWall
StainPatchedCrack TileStippleDrywallPlaster WoodWallpaper
Damaged: NoCeiling
Damaged Not TestedFoggedBindsStainMold/MildewVinyl CladVinylWoodMetalSingle PaneThermal PaneSkylightAwningCasementSlidingFixedDouble HungSingle Hung
Operational: YesWindow
South window does not appear to have proper header framing. Advise review by a qualified contractor. Repair asneeded.
DamagedBindsMissingWoodCompositeHingedBi-FoldPocket
Operational: YesDoor
44682-3128
7/31/2019 43460 Sw Gaston Rd Inspection 8-28-12
32/32
43460 SW Gaston Rd, Gaston, Oregon 97118
CCB 156934 OCHI 779Casey Livingston
Date: 23-Aug-2012
Exposed WiringUnsecuredMissingOperational: YesLighting
Open J BoxOpen Ground2 ProngedReversed PolaritySwitchedUnsecured No Cover Damaged
Operational: YesReceptacle
NoneElectric Wall Heater Air Register Radiant CeilingRadiant Floor Baseboard
Heat Source
Loose wall heater cover requires securing for safety. Replace missing knob for thermostat