MANUAL CODE: SYJS-005 -03 Rev.0 .
Haier Group
Auto-Restart function
Group control(with a group controller)
Auto-changeover
The same outdoor unit can match with cassette \convertible\
duct type indoor unit
With new environment friendly refrigerant R407C
Weekly timing(with a weekly timer)
Features
Service ManualCommercial Air Conditioning
24 28 Universal Outdoor Unit air conditioning
AC28NACBEA+AU28NAHBEAAD28NAMBEA+AU28NAHBEA
AB28NACBEA+AU28NAHBEA
Remotoe control and Wired remote control(Optional)
AB242ACBEA+AU242AHBEAAC242ACBEA+AU242AHBEAAD242AMBEA+AU242AHBEAAD242AHBE A+ AU242AHBEAAP242ACBE A+ AU242AHBEA
AU282AHBEA
CONTENTS
1. Description of Products & Features…………………...…….2
2. Specifications…………………………. ………………...……8
3. Safety precaution…………………………..………………….12 4. Net dimensions of indoor and outdoor unit………………...14
5. Installation instructions ……………………. ………………. 16
6. Parts and functions …………………………..…… ..……….19
7. Remote controller functions………………………….………22
8. Refrigerant diagram…………………………..……………....24
9. Electrical control functions……………………………………25
10. Diagnostic information(trouble shooting)…………….……29
11. Electrical data.........................................…………….……35
12. Exploded views and parts lists...............……………. …...4113. Performance curves……………............................... ……57
15. Air velocity distribution …………............................... ……48
CONTENTS
Contents……..............................................…...………...…….1
- 1 -
14. Noise level charts....... …………............................... ……48
1 .Description of Products & Features Products coding direction United Outdoor unit: A U 24 2 A H B E A
Climate type: T1 (see table 1) Design number E
Product type: A stands for heat pump type, refrigerant is R22 B stands for heat pump type, refrigerant is R407 M stands for cool only type, refrigerant is R22 N stands for cool only type, refrigerant is R407 Appearance character Product series: common icon-shelled outdoor unit type Applicable voltage: 2 stands for 220-240V/50Hz 4 stands for 220v/60Hz N stand for 380V/50Hz Cooling / Heating capacity,24=24000BTU/h Product type : “B” stands for cassette type “C” stands for convertible type “D” stands for duct “S” stands for split type “Q” stands for chiller system “U” stands for outdoor unit Abbreviation of Air conditioner
Indoor units of Cassette type: A C 24 2 A C B E A
Climate type: T1 (see table 1) Design number E
Product type: A stands for heat pump type, refrigerant is R22 B stands for heat pump type, refrigerant is R407 M stands for cool only type, refrigerant is R22 N stands for cool only type, refrigerant is R407 Appearance character Product series: common icon-shelled outdoor unit type Applicable voltage: 2 stands for 220-240V/50Hz 4 stands for 220v/60Hz N stand for 380V/50Hz Cooling / Heating capacity,24=24000BTU/h Product type : “B” stands for cassette type “C” stands for convertible type “D” stands for duct “S” stands for split type “Q” stands for chiller system “U” stands for outdoor unit Abbreviation of Air conditioner
-2-
a) Description of the coding rule of the models
A U 28 N A H B E A
Climate type:T1
Design serial number
Air conditioner
Product series:one-to-one
Outdoor unit
Cooling capacity:28=28000BTU/h
Adaptive voltage:380-400V/50Hz
Appearance features
Product type: heat pump R407C
A B 28 N A C B E A
Climate type:T1
Design serial number
Air conditioner
Product series:one-tag-one
Product specification:valid digit above kilobi
Adaptive voltage:380-400V/50Hz
Appearance features
Product type: heat pump R407C
Product type:indoor unit P:Cabinet typeC:Convertible type B:Cassette type D:Duct type
b). Standard working condition
Operating Mode Indoor Operating Mode Outdoor Operating Mode
Nominal Cooling
Temp. Temp.Humidity
DB:27 WB:19 DB:35
DB:7 WB:6
WB:24
Humidity
DB:20 WB:15Nominal Heating
No.
1
2
Temp.Humidity
DB:27 WB:19 DB:35
DB:7 WB:6
WB:24
Humidity
DB:20 WB:15Nominal Heating
No.
1
2
-3-
c)Brief introduction of the series: Convertible type: AC242ACBEA AC28NACBEA (1).Ceiling convertible,flexible installation,convenient
maintenance,saving the users' expenditures (2)Adopting single-phase & three-phase power supply,applicable for
household and commercial usage (3).Dual air outlet design,floor air blowing,accelerating the indoor air
circulation, quick temperature adjustment (4).Long-distance air blowing,large power,large cooling/heating
ratio (5).Intelligent remote control,convenient and flexible control (6).Super-slim indoor unit design,luxury and nice-looking,saving
space,harmonious and unitive with the indoor environment (7).Adopting screw-fastening for the air inlet grill,firmly
fixed;adopting slipway insert-lock fastening method for the filter screen,convenient cleaning or replacing the filter screen without opening the air inlet grill.
(8).Group control,units up to 128 sets can be controlled . Duct type : AD242AMBHA AD242AHBEA AD28NAMBEATotally concealed machine body All the machine body is to be installed inside the ceiling, having no effect on the beauty of the room and without taking any room space. Air intake via the rear air intake duct This new design has changed the former unique pattern of air intake, and a larger distance between air intake and air return cycles as well as better air quality can be achieved. Flexible and easier installation The machine body is to be installed in a totally concealed way,its fan system has a longer distance coverage so as to supply its airflow to several rooms, and the indoor unit may be installed inside the ceiling of a room or corridor. The installation is simple and flexible, and there is no need to have specified personnel for management, thus cutting down the expenses; the machine is lighter and smaller, and convenient for installation, it takes an extremely small building space, thus lower the construction cost; the indoor unit is to be concealed inside the ceiling, and hence the usable space can be saved and the room decoration will not be affected.
-4-
AB242ACBEA AB28NACBEAProducts characteristic: Completely invisible machine body: The whole machine body is completely concealed inside the ceiling. Due to its compact size it neither breaks the harmonization of indoor decoration nor occupies the indoor spaces. The stylish look of air conditioner allows it to blend right into ceiling. Superbly efficient healthy filter: Superbly efficient antibiotic materials are utilized and can prevent germs from breeding efficiently . Flexible and easy installation Slim design with machine body, completely ceiling concealing and portable shape, all make it greatly easier to install. Moreover, it occupies least constructional spaces, which help to reduce constructional cost prices. It also features a specific drainage system with up to 600mm lift , which allows reducing installation spaces and ensures to drain smoothly. Thanks to its "smudge-free" mobile outlet grill, the ceiling can be protected from pollution effectively and allow the airflow to fit people's comfortable need much more. Compensation function of power failure: When meeting a power failure during running, no matter how long it will be, once the power is restored, air conditioner will automatic restart with the previous status. Safety and reliable control due to various signal controls 1 Inputting with press buttons on the panel 2 Inputting with temperature sensors (indoor ambient temperature sensors, indoor coil pipe temperature sensors, 3 Piping pressure signals 4 Compressor current signals 5 Testing signals 6 System time-shorten signal 7 Water overflowing signal 8 Communication signals between indoor unit and front plate or between indoor unit and outdoor unit . Silent design The use of radial outward flow turbine fan produces larger cyde airflow volume and acts to significantly decrease operating noise.
When using remote-controlling mode, it is comfortable and convenient to operate. Advanced wire-controller and convenient remote-controllerThe new wired controller can connect with 16 indoor units without any device such as detectors.The new remote controller can be used for single unit or muti-free unit, or H-MRV,very convenient.
Cassette type:
In addition, it can be compatible with the old remote controllers.
Low ambient temperature cooling function (optional) Equipped with high/low pressure protection switch
NEW
NEW
The indoor units of AU282AHBEA and AU28NAHBEA are the same.
Climate type Type of Air Conditioner
T1 T2 T3
Cool only 18 43 0 35 21 52
Heat pump -7 43 -7 35 -7 52
Electricity heating 43 35 52
d). Brief Introduction for T1\ T2\ T3 working condition
Climate type Type of Air Conditioner
T1 T2 T3
Cool only 18 43 10 35 21 52
Heat pump -7 43 -7 35 -7 52
Electricity heating 43 35 52
-6-
2 Specifications Model Item AU242AHBEA AC242ACBEA AB242ACBEA AD242AMBEAE AD242AHBEA
Cooling capacity① Btu/h 24000 24000 24000 24000 24000 Heating capacity① Btu/h 27000 27000 27000 27000 27000 Power 1PH 220-230V 50Hz
Cooling power(W) 2700 2700 2700 2700 2700 Cooling EER(Btu/W) 8.89 8.89 8.89 8.89 8.89 Cooling operation current (A) 12.5 12.5 12.5 12.5 12.5
Power factor(%) 0.95 0.95 0.95 0.95 0.95 Heating power (W) 2700 2700 2700 2700 2700 Heating COP(Btu/W) 10 10 10 10 10 Cooling operation current (A) 12.5 12.5 12.5 9.5 9.5
Power factor(%) 0.95 0.95 0.95 0.95 0.95
Ope
ratio
n da
ta
Noise level(high-mid-low)dB(A)
58 48-44-38 39-37-35 35-32-29 42-41-40
External (L×W×H) 948x340x830 990×655×199 840×840×240 990×650×300 820×830×360 Dimension
mm×mm×mm Package (L×W×H) 1050x440x979 1150×750×300 910×910×300 1137×800×320 940×1051×510
Weight (net/gross)
Kg/Kg 74/89 30/39 28/30 40/57 48/58
Compressor Model ZR34K3E-PFJ-522 \ \ \ \ Manufacture Copeland \ \ \ \ Starting method PSC \ \ \ \ Starting
current(A) 75 \ \ \ \
Protection devices IOL \ \ \ \
Crankcase heater power (W) \ \ \ \ \ Heat exchanger 0.92m2 0.084 m2 0.199m2 0.199m2 0.199m2 Refrigerant control capillary capillary capillary capillary capillary Refrigerant Type R407C \ \ Charge(g) 2400 \ \ \ Defrost method Auto Auto Auto Auto Auto Fan Type×Number Axial fan×1 Axial fan×2 Cross flow fan×2 Cross flow fan×2 Cross flow fan×2 Fan motor Motor output (W) 130 45 40 100 130 Air-flow (high-mid-low)m3/h 4000 900/840/790 1300/1100/870 1470/1300/1100 900/1250/1500 Anti-vibration and sound insulation devices
XPE XPE XPE XPE XPE
Control method( remote/wire-controlled ) \ Remote
controlled Remote
controlled Wired
controlled Wired
controlled Safety devices Fuse Fuse Fuse Fuse Fuse
Liquid pipe:(mm) Φ9.52 Φ9.52 Φ9.52 Φ9.52 Φ9.52 Dimension of refrigerant pipe
Gas pipe:(mm) Φ15.88 Φ15.88 Φ15.88 Φ15.88 Φ15.88
Connection method Bugle joint Bugle joint Bugle joint Bugle joint Bugle joint Drainage pipe(material , I.D./O.D.)Mm \ PVC 26/32 PVC 25/32 PVC 25/32 PVC 26/32
Appearance colour white white white white white Accessories To see manual To see manual To see manual To see manual To see manual
-7-
Function cooling heating
Capacity BTU/h 24000 28000
Capacity kW 7.1 7.9
W 2.7 2.7
W 3.2 3.2
EER or COP W/W 2.6 2.9
Dehumidifying capacity 10‐³×m³/h
Power cable
Power source N,V,Hz
A / A13.5/16 14.5/19.5
Start Current A
Fuse A
Unit model (color)
Type × Number
Speed(H-M-L) r/min
Fan motor output power kW
Air-flow(H-M-L) m³/h
Type / Diameter mm
Total Area m²
Temp. scope ℃
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
Drainage pipe (material , I.D./O.D.) mm
Control type (Remote /wired)
kW
dB(A)
kg / kg
Type / Charge g
Recharge quantity g/m
Liquid mm
Gas mm
Connecting Methodm
m
Refrigerant
Fan
Heat exchanger
1.848/46/44
remote type
MAX.Piping length 30
PIP
ING
R407C/2400
65
Pipe9.52
15.88
flared
Between I.D &O.MAX.Drop 20
TP2M/9.52
Weight (Net / Shipping) 45/57
PVC 26/32
1821×532×300
item Model AP242ACBEA
3.0
3*3.0
Total power input
Max. power input
Running /Max.Runningcurrent
centrifugal*1
Dimension
0.338
1000/900/800
2-7
1920×625×377
0.04
Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DBOutdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB
560±30/ 490±40/380±50
1, 220~230, 50
Indo
or u
nit
AP242ACBEA
Noise level (H-M-L)
Electricity Heater
60
21
Function Cooling HeatingCapacity BTU/h 28000 32000
W 3200 3300W 4500 5500
EER or COP BTU/W 8.75 9.7Dehumidifying capacity 10‐³×m³/hPower cable
Power source N,V,HzA / A
Start Current AUnit model (color)
Fan Type × Number
Speed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h
Heat exchanger Type / Diameter mmTotal Area m²Temp. scope ℃
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)
Fresh air hole dimension mmkW
dB(A)kg / kg
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
kg / kgUnit model (color)Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/minFan motor output power kWAir-flow(H-M-L) m³/h
Heat exchanger Type / Diameter mmTotal area m²Temp. scope ℃
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm
Volume of Accumulator LNoise level dB(A)
material of reduce noise crankcase heater power W
kg / kgRefrigerant Type / Charge g
Recharge quantity g/mLiquid mmGas mm
Connecting Methodmm
item Model AU28NAHBEA
Total power inputMax. power input
3/
3N 380V-400V 50HZRunning /Max.Running
currentCooling 5.5/8.0 Heating 5.8/9.5
30
Dimension
Electricity Heater Noise level (H-M-L)Weight (Net / Shipping)
Pane
l Dimension //
Weight (Net / Shipping) /
Indo
or u
nit
Out
door
uni
t
AU28NAHBEA(WHITE£©ZR40K3E-TFD-522 Copelan
ScrollAxial-flow×1
1180+301304000
TP2M/9.520.92
43-60Dimension 948x340x830
1050x440x979/
main capillary 2.4x220;auxiliary capillaryDefrosting Auto
/58/--/50
Type of Four way valve /
MAX.Drop 20
XPE/
Weight (Net / Shipping) 74/89
MAX.Piping length 30
PIPI
NG
R407C 240060
Pipe 9.5215.88flared
Between I.D &O.D
-8-
Function cooling heating
Capacity BTU/h 28000 34000
Capacity kW 8.2 10
Sensible heat ratio 75%W 3400 3600
W 4300 4600
EER or COP W/W 2.41 2.77
Dehumidifying capacity 10‐³×m³/hPower cablePower source N, V, Hz
A / A
Start Current AUnit model (color)
Model / ManufactureTypeType × NumberSpeed r/minFan motor output power kWAir-flow(H-M-L) m³/hType / Diameter mmTotal area m²Temp. scope ℃
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm
Volume of Accumulator LNoise level dB(A)
material of reduce noise crankcase heater power W
kg / kgType / Charge gRecharge quantity g/mLiquid mmGas mm
Connecting Methodmm
Norminal condition: indoor temperature (cooling): 27℃DB/19℃WB, indoor temperature (heating): 20℃DBOutdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB
1, 220-240, 50cooling: 16A/20A heating: 17A/22A
80
Item Model AU282AHBEA
2.473*3.0
Total power inputMax. power input
Running /Max.Runningcurrent
0.063200/-/-
Out
door
uni
t
AU282AHBEA(WHITE)
0.9243-60
Heat exchanger
TP2M/Φ9.52
15
Dimension948x340x830
1050x440x979
Defrosting
PIP
ING
R407C 260065
Pipe9.52
15.88flared
Between I.D &O.MAX.Drop
scrollaxial×1
C-SBN261H5A(Sanyo)
MAX.Piping length 30
Weight (Net / Shipping) 74/89
Type of Four way valve /XPE
Refrigerant
Compressor
Fan
without
56
auto3.5
/capillary Φ4.0XΦ2.5X600
920r/min
Function Cooling HeatingCapacity BTU/h 28000 32000
W 3200 3300W 4500 5500
EER or COP BTU/W 8.75 9.7Dehumidifying capacity 10‐³×m³/hPower cable
Power source N,V,HzA / A
Start Current AUnit model (color)
Fan Type × Number
Speed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h
Heat exchanger Type / Diameter mmTotal Area m²Temp. scope ℃
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)
Fresh air hole dimension mmkW
dB(A)kg / kg
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
kg / kgUnit model (color)Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/minFan motor output power kWAir-flow(H-M-L) m³/h
Heat exchanger Type / Diameter mmTotal area m²Temp. scope ℃
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm
Volume of Accumulator LNoise level dB(A)
material of reduce noise crankcase heater power W
kg / kgRefrigerant Type / Charge g
Recharge quantity g/mLiquid mmGas mm
Connecting Methodmm 30
item Model AD28NAMBEA
Total power inputMax. power input
3/
3N 380V-400V 50HZRunning /Max.Running Cooling :5.5/8.0 Heating :5.8/9.5
30
Indo
or u
nit
AD28NAMBEA(WHITE)CentrifugalX 2
980+30/890 +30/810 +500.13
1470/1300/1100TP2M/9.52
0.1992-7
Dimension 990×650×3001137×800×320
PVC 26/32Wired+Remote
/Electricity Heater /Noise level (H-M-L) 35/32/29Weight (Net / Shipping) 40/57
Pane
l Dimension //
Weight (Net / Shipping) /
Out
door
uni
t
//////////
Dimension ////
Defrosting ///
Type of Four way valve /
MAX.Drop 20
//
Weight (Net / Shipping) /
MAX.Piping length
-9-
PIPI
NG
R407C 255060
Pipe 9.5215.88flared
Between I.D &O.D
Function Cooling HeatingCapacity BTU/h 28000 32000
W 3200 3300W 4500 5500
EER or COP BTU/W 8.75 9.7Dehumidifying capacity 10‐³×m³/hPower cable
Power source N,V,HzA / A
Start Current AUnit model (color)
Fan Type × Number
Speed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h
Heat exchanger Type / Diameter mmTotal Area m²Temp. scope ℃
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)
Fresh air hole dimension mmkW
dB(A)kg / kg
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
kg / kgUnit model (color)Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/minFan motor output power kWAir-flow(H-M-L) m³/h
Heat exchanger Type / Diameter mmTotal area m²Temp. scope ℃
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm
Volume of Accumulator LNoise level dB(A)
material of reduce noise crankcase heater power W
kg / kgRefrigerant Type / Charge g
Recharge quantity g/mLiquid mmGas mm
Connecting MethodmmMAX.Piping length 30
PIPI
NG
R407C 255060
Pipe 9.5215.88flared
Between I.D &O.DMAX.Drop 20
//
Weight (Net / Shipping) /
//
Type of Four way valve /
//
Defrosting /
/Dimension /
/
Out
door
uni
t
/////////
Pane
l Dimension //
Weight (Net / Shipping) /
Noise level (H-M-L) 42/40/38Weight (Net / Shipping) 40/57
Remote/
Electricity Heater /
Dimension 1320×715×2351380×770×300
PVC 18/20
30
Indo
or u
nit
AC28NACBEA(WHITE)CentrifugalX2
1300 +30/1250 +40/1150 +500.04
1300/1250/1150TP2M/9.52
0.1992-7
3/
3N 380V-400V 50HZRunning /Max.Running Cooling :5.5/8.0 Heating :5.8/9.5
item Model AC28NACBEA
Total power inputMax. power input
-10--
Function Cooling HeatingCapacity BTU/h 28000 32000
W 3200 3300W 4500 5500
EER or COP BTU/W 8.75 9.7Dehumidifying capacity 10‐³×m³/hPower cable
Power source N,V,HzA / A
Start Current AUnit model (color)
Fan Type × Number
Speed(H-M-L) r/minFan motor output power kWAir-flow(H-M-L) m³/h
Heat exchanger Type / Diameter mmTotal Area m²Temp. scope ℃
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
Drainage pipe (material , I.D./O.D.) mmControl type (Remote /wired)
Fresh air hole dimension mmkW
dB(A)kg / kg
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
kg / kgUnit model (color)Compressor Model / Manufacture
Type
Fan Type × Number
Speed r/minFan motor output power kWAir-flow(H-M-L) m³/h
Heat exchanger Type / Diameter mmTotal area m²Temp. scope ℃
External (L×W×H) mm×mm×mm
Package (L×W×H) mm×mm×mm
Drainage pipe (material , I.D./O.D.) mmRefrigerant control method mm/mm
Volume of Accumulator LNoise level dB(A)
material of reduce noise crankcase heater power W
kg / kgRefrigerant Type / Charge g
Recharge quantity g/mLiquid mmGas mm
Connecting Methodmm
item Model AB28NACBEA
Total power inputMax. power input
3/
3N 380V-400V 50HZRunning /Max.Running Cooling :5.5/8.0 Heating :5.8/9.5
30
TP2M/70.199
2-7Dimension
Centrifugal×1700+30/590+40/470+50
0.041300/1100/870
840×840×240910×910×300
PVC 26/32Remote
/Electricity Heater /Noise level (H-M-L) 39/37/35Weight (Net / Shipping) 28/30
Pane
l Dimension 950x950x80980x980x100
Weight (Net / Shipping) 6/9
Indo
or u
nit
AB28NACBEA(WHITE)
Out
door
uni
t
//////////
Dimension ////
Defrosting ///
Type of Four way valve /
MAX.Drop 20
//
Weight (Net / Shipping) /
MAX.Piping length 30
PIPI
NG
R407C 255060
Pipe 9.5215.88flared
Between I.D &O.D
11-
WARNING
CAUTIONWARNING
CAUTION
This system should be applied to places of office, restaurant, residence and the like. Appliaction to inferior
environment such as engineering shop could cause equipment malfunction.
Please entrust installation to either the company which sold you the equipment or to a professional contractor.
Defects from improper installations can be the cause of water leakage, electric shocks and fires.
Execute the installation accurately, based on following the installation manual. Again, improper installations can
result in water leakage, electric shocks and fires.
When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned
countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration.
In regards to preparing this countermeasure, consult with the company from which you purchased the equipment,
and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold
concentration does occur,there is the danger of a resultant oxygen deficiency accident.
For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient,
injury can result from a falling of the unit.
Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and
hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit.
For electrical work, please see that a licensed electrician executes the work while following the safety standards
related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive
use circuits are used.
Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and
fires.
Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to
the terminal connection part, through properly securing it. Improper connection or securing can result in heat
generation or fire.
Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can
also result in heat generation or fire.
WARNING
In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.After completing the installation, along with confirming that no abnormalities were seen from the operation tests, pleaseexplain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's manual.Moreover, ask the customer to keep this sheet together with the owner's manual.
Please read these "Safety Precautions" first then accurately execute the installation work.Though the precautionary points indicated herein are divided under two headings, and those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed in the section. However, there is also a possibility of serious consequences in relationship to the points listed in the section as well.
- 12 -
SAFETY PRECAUTIONS
3 SAFETY PRECAUTIONS
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated
refrigerant (please see nameplate) within the refrigeration cycle.
Rupture and injury caused by abnormal high pressure can result from such mixing.
Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this
company can result in water leakage, electric shock, fire and refigerant leakage.
The position of indoor unit must be above the floor 2.5m.
WARNING
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightening rod or a telephone
ground wire.
Improper placement of ground wires can result in electric shock.
The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not
installing an earth leakage breaker may result in electric shock.
Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to
prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
CAUTION
- 13 -
SAFETY PRECAUTIONS
4.Net dimensions of indoor and outdoor unit Indoor unit Models
1) AB242ACBEA AB28NACBEA
2) AD242AMBEA AD28NAMBEA
-14-
3526027535
A-A
A-A
drainage pipe
B-B
fresh air outlet655
liquid pipe
gas pipe
3) AD242AHBEA
4) AC242ACBEA
655
240
200
9
-15-
185 185
55
70
70
Screw Hole
(M10)
580
Power Wiring Terminal
Power Wiring
Distribution Hole
70
1024
18
18
340
38
08
40
25
6)AU242AHBEA AU28NAHBEA AU282AHBEA
110
180
60
85
100
30
555
630 690
105 195 300
600 600
310.63
8525
300
10
10
545590
85 15060
1200
150235
1320
195
100
85
45
65
R15
5)AC28NACBEA
5.Installation Instructions 1. Installation Tools
1) Driver 2) Hacksaw 3) Hole core drill 4)Hexagon wrench(5mm) 5) Spanner(14,17,19 and 24mm) 6) Torque wrench(17,22,24mm) 7) Pipe cutter 8) Flaring tool
For example: use two spanner to joint the pipe
2. Standard Accessories The standard accessories includes : 1) Measuring type 2) Reamer 3) Refrigerant oil 4) Gas leakage detector or soap-and-water solution 5) Knife 6) Nipper 3. Installation Dimensions of Indoor & Outdoor units Please to see the Mechanical Data 4. Installation procedures & Points of attention 4.1 The Order of Installation Work
Work Main points Before installation Work division To ascertain the responsible for installation of pipes and wiring Make installation diagram To ascertain the pipe installation dimension and position of electronic
expansion valve, to make control wiring diagram Work Installation of indoor and
outdoor unit To prevent the ventilation from short circuit and guarantee repair space
Refrigerant pipe work Pay attention to dry, clean and seal Drain pipe work Slant downward Heat insulation work No gaps in the joint of heat insulation material Wiring work (control wire,
power cord) Choose the proper wire and cord
Set every set switch Should be complied with control wiring system diagram Airtight test Close all the gas, liquid valve Vacuum drying Should the vacuum pump that can reach 200Pa vacuity Additional refrigerant Wire down the additional refrigerant amount on the outdoor unit body and
record table Test run adjustment Do test run to indoor unit by one to verify if there is wrong pipes Training of use and
maintenance Explain to user, simultaneously provide all the documents
4.2 Attentive matters of safety · Before installing, do read this [Attention matter of safety] carefully to guarantee the proper installation. · The below attentive matters are divided into [warning] and [note] two parts. When the wrong installation occurs, it is very possible lead to death and severe injury, and other serious accidents will happen. For those items are listed in [warning] part. But even the items very important contents related to safety, so they must be obeyed. · After installation, do test operation to verify everything is normal, after that please explains the use method and maintenance method to the user according to the operation manual. Additionally, give the installation manual together with operation manual to the user and ask them to keep them properly.
Edging
(2) Installation where the area with strong winds.Install the unit so that the air outlet section of the unit must NOT be facedtoward wind direction.
(1) Open space requirement around the unit
2. Selection of the place of installation
1. Accessories"Edging" for protection of electric wires from anopening edge.
Select the place of installation satisfying the following conditions and, at the same time, obtaina consent from the client or user.
Place where air circulates.Place free from heat radiation from other heat sources.Place where drain water may be discharged.Place where noise and hot air may not disturb the neighborhood.Place where there is not heavy snowfall in the winter time.Place where obstacles do not exist near the air inlet and air outlet .Place where the air outlet may not be exposed to a strong wind.Place surrounded at four sides are not suitable for installation. A 1m or more of overheadspace is needed for the unit.Mount guide-louvers to place where short-circuit is a possibility.When installing several units, secure sufficient suction space to avoid short circuiting.
<Heat Pump model/Cooling Only model >WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNINGINSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUSINJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.
Wind direction
NO
Unit
Concrete foundationAnchor bolt
Concrete foundationFoundation anchor
Note (1) Give enough room for theconcrete foundation to fix by anchor bolts.
(a)
Note (1) Place the concrete foundation deepenough.
Install the unit so that the angle of inclination must be less than 3 degrees.
3. Installation of outdoor unit
Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .(1) Installation
L2
•L3
•L1
•500
(Servicingspace)
Air outlet
Air inlet
Airinlet
Unit: mm
•Case
Distance I II III
open open
open
500
150150 300
300 0
L1
L2
L3
Anchor boltConcrete foundationUnitTo fix by bolts
To fix by bolts
Anchor bolt Concrete foundation
Unit
Anchor boltUnit
Concrete foundation
(1) Outline piping
4. Refrigerant piping
(2) Piping size
(3) Limitations for one way piping length and vertical height difference.One way piping length: less than 15m (for 14,18 series), less than 30m (for 24,28 series), Vertical height difference: Less than 5m (for 14,18 series), Less than 15m (for 24,28 series),
(4) Purging method ( the refrigerant is R407C)90
0.5
Outdoorunit
Service valve
Flare connection
Check joint
Gas pipe
Liquidpipe
Flare connection
Indoorunit
Install the removed flared nuts to the pipes to be connected,then flare the pipes.
Precautions for refrigerant piping
Do not twist or crush piping.Be sure that no dust is mixed in piping.Bend piping with as wide angle as possible.Keep insulating both gas and liquid piping.Check flare-connected area for gas leakage.
1
Detach the service port's cap of 3-way valve, thevalve rod's cap for 2-way valve and 3-way's, connectthe service port into the projection of charge hose(low) for gaugemanifold. Then connect the projectionof charge hose (center) for gaugemanifold intovacuum pump.
To use vacuum pump
3
Vacuumize for over 15min. And check the level gaugewhich should read -0.1 MPa (-76 cm Hg) at lowpressure side. After the completion of vacuumizing,close the handle 'Lo' in gaugemanifold and stop theoperation of the vacuum pump.Check the condition of the scale and hold it for 1-2min.If the scale-moves back in spite of tightening, makeflaring work again, the return to the beginning of 3 .
2Open the handle at low in gaugemanifold, operatevacuum pump. If the scale-moves of gause (low)reach vacuum condition in a moment, check 1 again.
2-way valve
3-way valve
90•Service port4 90• for 6 sec.
Open
For series 36,42
3 Close
2 Open
4
Open the valve rod for the 2-way valve to and angleofanticlockwise 90 degree.After 6 seconds later, close the 2-way valve andmalethe inspection of gas leakage.
Vacuum pump
For series 24,28
3-way valve
2-way valve
Gaugemanifold
Gaugemanifold
Vacuum pump
2-way valve
3-way valve
For series 36,42
3-way valve
2-way valve
Open
90•Service port
90•4 90• for 6 sec.
For series 24,28
90•
Model
Gas piping
Liquid piping
19.05(3/4")x1.0mm
9.52(3/8")x0.8mm
15.88(5/8")x1.0mm
9.52(3/8")x0.8mm
36,42 series24,28 series14,18 series
15.88(5/8")x1.0mm
6.35(1/4")x0.8mm
+_
less than 50m (for 36,42 series).
less than 30m (for 36,42 series).
30mA
5. Electric wiringWARNING
DANGER OF BODILY INJURY OR DEATHTURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFOREMAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BECOMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting wires.
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel.Do not connect more than three wires to the terminal block. Always use round type crimpedterminal lugs with insulated grip on the ends of the wires.Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m lengthwires with less than 2% voltage drop.)
Item
ModelPhase
3
Switch breaker(A)
Circuit breaker
Overcurrent protectorrated capacity (A)
Power sourcewire size
(minimum)
30 20 2.5mm2
1 40 26 4.0mm2
36,42 series, 28 series(380-400V,3N~,50Hz)
14,18, 24, 28 series (1PH,220-230V,50Hz)
Switchbreaker
Earth leakage breaker
Leakcurrent
30 30mA
40
Liquid pipe 9.52mm
Gas pipe 19.05mm
2-way valve
3-way valve
66
For series 36,42
For series 24,28
3-way valve
2-way valve
6
6
If needing to remove the refrigerant gas when installation or repair , please refer to the following procedures:1. Cut off the power2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure pressure-switch out.
3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After powering on the unit again and switch to COOLING mode,perform refrigerant gas removing according to the normal refrigerant gas removing procedure.4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals of the low-pressure pressure-switch properly.
3-way valve
2-way valve
7 Valve rod cap
Service port cap7
For series 36,42
3-way valve
2-way valve
7 Valve rod capValve rod cap7
Service port cap7
For series 24,28
If it does not stop gas leakage, dischargewhole refrigerants from the serice port.After flaring work again and vacuumize,fill up prescribed refrigerant from the gascylinder.
Detach the charge hose from the service port, open2-way valve and 3-way. Turn the valve rodanticlockwise until hitting lightly.
6
In case of gas leakage, tightenparts of pipe connection. Ifleakage stops, then proceedsteps.
6No gas leakage?
5
CAUTION:If the refrigerant of the air conditioner leaks, it is necessary tomake all the refrigerant out, then charge the liquid refrigerantinto air conditioner according to the amount marked on thename plate.
7
8
After attaching the each caps, check the gasleakage around the caps.
To prevent the gas leakage, turn the service port'scap, the valve rod'd cap for 2-way valve and 3-way'sa lottle more than the point where the torqueincreases suddenly.
Outdoor Unit Installation
Note : (1). Fix the parts with screws(2).Don't intake the strong wind directly to the outlet air-flow hole.
2. Selection of the place of installation
(3).A one meter distance should be kept from the unit top
1. Accessories
(4).Don't block the surroundings of the unit with sundries
"Edging" for protection of electric wires from an opening edge.
Select the place of installation satisfying the following conditions and, at the same time, obtain a consent from the client or user.
Edging
Place where air circulates.Place free from heat radiation from other heat sources.Place where drain water may be discharged.Place where noise and hot air may not disturb the neighborhood.Place where there is not heavy snowfall in the winter time.Place where obstacles do not exist near the air inlet and air outlet .Place where the air outlet may not be exposed to a strong wind.Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit.Mount guide-louvers to place where short-circuit is a possibility.When installing several units, secure sufficient suction space to avoid short circuiting.
Wind direction
NO
(2) Installation where the area with strong winds.Install the unit so that the air outlet section of the unit must NOT be faced
(1) Open space requirement around the unit
toward wind direction.
L2
L3
L1
500
(Servicingspace)
Air outlet
Air inlet
Air inlet
CaseDistance
Unit: mm
open open
open
500
150150 300
300 0
L1
L2
L3
I II III
One way piping length:
less than 30m (for AU242AHBEA ).
Vertical height difference:
less than 20m (for AU242AHBEA).
(2) Piping size
AU242AHBEA
Install the removed flare nuts to the pipes to be connected, then flare the pipes.
90+0.5
Pipe dia Fastening torque
Liquid pipe 9.52mm
Gas pipe 15.88mm
42N.m
98N.m
Liquid pipe
Gas pipe
9.52x0.8mm
15.88x1.0mm
(3) Limitations for one way piping length and vertical height difference.
Precautions for refrigerant piping
Do not twist or crush piping.Be sure that no dust is mixed in piping.Bend piping with as wide angle as possible.Keep insulating both gas and liquid piping.Check flare-connected area for gas leakage.
Connecting method (indoor unit)Apply refrigerant oil at half union as large and flare nut.To bend a pipe, give the roundness as possible not to crush the pipe.When connecting pipe, hold the pipe centre to centre then screw nut on by hand, refer to Fig.Be careful not to let foreign matters, such as sands enter the pipe.
(4) Piping connection
Forced fastening without centering may damage the threads and cause a gas leakage.
In the first to third test steps, if the pressure drops, check the leakage in each jointuse sense of hearing, feeling and soap water, etc. methods to find the leaking point.After confirming the leaking point, welding it again or tighten the nut tightly again.
From pressurizing to 24 hours later, each 1* difference of ambient temperaturewill make 0.01MPa(0.1kg/cm2g) pressure change. It shall be corrected during test.
Checking the leaking point
Check if the pressure dropsThe pressure does not drop-passedThe pressure drops-check the leaking point.
First step: 0.3MPa (3.0kg/cm2g) pressurize over 3 minutes.
Second step: 1.5Mpa (15kg/cm2g) pressurize over 3 minutes. Large leakage will be found.
Third step: 3.0 MPa (30kg/cm2g) pressurize about 24 hours. Little leakage will be found.
5. Air discharging methodAfter finishing connection of refrigerant pipe, it shall perform air tightness test.The air tightness test adopts nitrogen tank to give pressure according to the pipe connectionmode as the following figure shown.The gas and liquid valve are all in close state. In order to prevent the nitrogen entering thecirculation system of outdoor unit, tighten the valve rod before giving pressure (both gasand liquid valve rods).
Outdoor
Completely tightened
Completely tightened
Flare part
Outdoor units
Manhole
Discharging valve
3-way valve totally closed(Gas side)
Low pressure peizometer
High pressure peizometer
Meter separator
Dropping valve
2-way valve totally closed(Liquid side)
Nitrogen tank
VL VH
Indoor units
Indoor
Flare part
It shall use the vacuum pump of (lower than -755mmHg)high vacuum degree and large air discharging (over 40l/min).The vacuumizing time depends on the length of the connecting pipe, generally is 1~2 hours.When vacuumizing, it shall be confirmed both gas and liquid side valves are closed.If after 2 hours vacuumizing, it cannot reach the vacuum degree below -755mmHg, it can bevacuumized for other 1 hour.If after 3 hours vacuumizing, it still cannot reach the vacuum degree below -755mmHg, check if there is any leaking point and repair the them.If after over 2 hours vacuumizing, the vacuum degree is below -755mmHg, close the VLand VH on the meter separator and stop vacuumizing. 1 hour later to confirm if the vacuumdegree changes. If changes, it indicates there is leaking point in the system. Check the leaking point and repair.After finishing the above vacuumizing, change the vacuum pump into refrigerant pump tocharge the refrigerant.
Use vacuum pump to perform vacuumizing. It is strictly forbidden to use the refrigerant to remove the air inside the system.After air tightness test and discharging all the nitrogen, connect the vacuum pumpas the following figure shown.
When the total length (L) of the two indoor units' connecting pipe is less than 5m, it is unnecessary to charge additional refrigerant.If the connecting pipe (L) exceeds 5m, it shall charge Mg additional refrigerant per meter.That is: Refrigerant charging amount = (L-5) x M (g)
For AU242AHBEA, M=65
Only in COOLING operation can charge the additional refrigerant.When charging, the refrigerant shall be charged from the charging nozzle of low pressure vavle.Be carefull when charging refrigerant, do not let the air mix into the system,and must charge the additional refrigerant in liquid condition.
6. Piping and indoor unit vacuumizing
7. Charging amount of refrigerant
2-way valve totally closed(Liquid side)
Indoor units
Indoor Outdoor
Completely tightened
Completely tightened
Outdoor units
Vacuum pump
Discharging valve
3-way valve totally closed (Gas side)
Low pressure peizometerHigh pressure peizometer
Meter separatorV L VH
Flare part
Flare part
P
Warning · The distributing shop, where you brought the air conditioner, or the specified shops shall do the installation work. If you do the installation work by yourself, the improper installation will cause water leakage, electric shock fire and other accidents. · The installation work shall be in line with what the installation manual specified. If installation is not proper, water leakage, electric shock, fire and other accidents will occur. · Install the conditioner to a place where can definitely stand its weight. Please not firm enough, it will cause droop down of unit resulting in body hurt. · The installation work shall be preventive to typhoon and earthquake. If the installation work is not met with the requirements, overturn of the unit will occur resulting in accidents. · The wiring work should be down by a qualified person and referred to the “technical standard of electric equipment “, ”indoor wiring regulation” and what the manual specified. Do use special circuit. If the capacity of the circuit is not enough or bad work, electric shock, fire and other accidents will happen. · Using the specified cable to do wiring work and connecting firmly and properly. Fix the connecting part of the terminals to prevent it from the external force. Improper connection and fixing will cause heating and fire etc. accidents. · Wring shall be kept in correct shape avoiding extrusion. After installation, the electric box cover and the external panel shall not nip the wire. Improper installation will cause heating and fire etc. accidents. · when setting or moving the air conditioner do not let the air and things alike get into the refrigeration system except the specified refrigerant (R407C). If air and other things enter, abnormal high pressure will occur, which easily cause breaks and body injuries etc. accidents. · When installing, do not use the accessories or specified parts. If not using the parts specified by our company, water leakage, electric shock, fire and refrigerant leakage will occur. · Do not lead the drainpipe to where the sulphur gas may be involved. Otherwise, the poisonous gas will enter into the door. · During installation, if refrigerant leakage occur, do the ventilation work immediately. As soon as the refrigerant gas meets fire, poisonous gas will be produce. If the refrigerant gas enter into room and meet the air blowing heater, heater or stove etc. fire source, the poisonous gas may be produced. After installation, confirm there is no leakage of refrigerant. · Do not install the unit in a place where the combustible gas may be leaks. In any case the combustible gas leaks and accumulated around the unit, fire accident will occur. · Do heat insulation work to the refrigerant gas pipes and liquid pipes to reach the purpose of heat preservation. If the heat insulation measure is not sufficient, water generated by condensing dew will drip leading to wet the floor and indoor articles. · Do not damage the power line or change it arbitrarily to avoid occurrence of fire or electric shock. · Do not extend the power line or using other electric appliance in the same power receptacle to avoid fire or electric shock.
Note · Do grounding work. Do not connect the grounding wire to gas pipe, tap, lighting rod or telephone line. Improper grounding will cause electric shock. ·In some places the electric leakage breaker shall be installed. If do not install the breaker, electric shock may occur. ·After installation, power on to do electric leakage detecting test.
5.3 Special Work and Main Points in Installation Warning
· During installation, if refrigerant leakage occurs, take ventilation measurement immediately. ·As soon as the leaked refrigerant gas meets fire, poisonous gas will generate.
·After finishing installation, confirm the refrigerant gas dose not leak. ·If the refrigerant gas leaks in the room, once it meets heater, burner and gas stove etc. fire source, the poisonous gas will generate.
A. Choosing of pipes According to the following indoor unit and unit installation diagram to choose the material and size of pipes and branch pipes.
B. Connection of pipes 1. Method of pipe connection ·The pipe shall be as short as possible to guarantee efficiency ·Daub the refrigerant oil on the connection and flare nut · When bending the pipes, give the roundness as large as possible, to avoid crashing the pipes ·To connect the pipe, fit the center and screw the nut with hand, the use spanner or torque wrench to tighten it. The fastening torque showed in below table, and shown in figure. ·Be careful alien matter, such as sands, water etc. shall not enter the pipes. Forced fastening without careful centering may damage the threads and cause gas leakage 2. Welding of pipes
·In welding, the nitrogen shall be used to avoid oxidation of the pipe inner part. ·The refrigerating pipe shall use clean new pipes. When working, it shall take steps to prevent
water and dust from entering. ·When loosening and tightening the nuts, two spanners shall be used. If using one spanner, it can
not reach the desired degree of tightness. Using the specified fastening torque to fasten nuts.
Pipe diameter (mm) Installation torque(N.M.) Fastening torque (N.M.) Φ6.35 11.8(1.20kgf.m) 13.7(1.4kgf.m) Φ9.52 24.5(2.50kgf.m) 29.4(3.0kgf.m) Φ1 2.7 49.0(5.0kgf.m) 53.9(5.5kgf.m) Φ15.88 78.4(8.0kgf.m) 98.0(10.0 kgf.m)
5 Checks after the installation
After the installation, please to check the connection of wire: If the wire have the same diameter in the two sides of the terminal If the wire placed on both the side of terminal but one side
To see the follow figure:
Ο means the right connection × means wrong
5.1 Installation tools
1. Cross screwdriver 2 .Metal saw 3 .60,70mm drill 4. Inner hexagon spanner,
shifting spanner 5 .Spanner(14, 17, 19,24,27mm diameter) 6. Pipe cutter
7. Pipe expander 8. Knife 9 .Pliers 10. Leak detector or soap liquor
11. Measuring tape 12 .Scraper 13. Refrigeration oil 14 .Vacuum pump 15 .Flat screwdriver
5.2 Standard accessories
Part name
QTY
Shape
Clamp
2 Piece
Washer
8 Piece 6 Piece
Clamp Paper pattern
1 Set
6321
3 Piece
Screw(M5 size)
For installationofpaper pattern
Drain hose
1 Piece
Please check if your unit is delivered with following
Part name
QTY
Shape
Dry batteryInsulator Sealing pad Sealing pad Sealing pad7 8 9 12
1 Piece 1 Piece
Insulator
2 Piece 1 Piece 1 Piece 2 Piece
Small sizeMedium sizeLarge sizeFor liquid pipeFor gas pipe R03, 7#
[Other]
OperationManualOrnamentpanel
Remotecontroller
54
1110
5.3 Installation of indoor unit5.3.1 Before installation
Determine the way kto carry unit to installation place.Don't remove packing until unit reaches installation place.If unpacking is unkavoidable, protect unit properly.
5.3.2 Selection of installation place(1) Installation place shall meet the following and agreed by customers:
Place where proper air flow can be ensured.No block to air flow.Water drainage is smpoth.Place strong enough to support unit weight.Place where inclination is not evident on ceiling.Enough space for mainenance.Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.)Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radio. Thisis helpful to avoid picture disturbance and noise. (Even if 1 m is kept, noise can still appear if radiowave is strong)
INSTALLATION INSTRUCTIONS
5 INSTALLATION INSTRUCTIONS
8
260
260
(2) Ceiling heightIndoor unit can be installed on ceiling of 2.5-3m in height. (Refer to Foeld setting and InstallationManual of ornament panel.)
(3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take necessary measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern for place need be reinforced)
Installation space
Air inletAir outlet
2500
Ove
r
Air outlet1500 Over1500 Over 1500 Over 1500 Over
Air outletAir inlet
Air inlet
5.3.3 Preparation
Orn
amen
t pan
el 6
30m
m
ceili
ng o
peni
ng 6
00m
m
Indo
or u
nit 5
70m
m
Distance between
Indoor unit 570mm
Ceiling opening 600mm
Ornament panel 630mm
suspending bolts 460mm21
0mm
335m
m
35m
m
Overlap between ceiling andornament panel shall be 15mm
Suspending bolts
Ceiling Ornament panel
(1) Position of ceiling opening between unit and suspending bolt.
AB14, 18
Unit: mm
INSTALLATION INSTRUCTIONS
50~1
00
RoofAnchor boltLong nut
Suspending bolt
Ceiling
(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.) Refer to paper pattern for dimension of ceiling hole. Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation. Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration. Contact your real estate dealer(3) Install a suspending bolt. (Use a M10 bolt)
To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For newceiling, use built-in type bolt or parts prepared in the field.Before going on installing adjust space between ceiling.
<Installation example>
Note: All the above mentioned parts shall be prepared in field.
A
950(
Orn
amen
t pan
el)
890(
Cei
ling
open
ing)
840(
Indo
or u
nit)
780
(Dist
ance
bet
ween
susp
endin
g bo
lts)
(Distance between suspending bolts)A
950(Ornament panel)
890(Ceiling opening)
840(Indoor unit)
Suspending bolts
Refrigerant pipe
A
(160
)
Suspending bracket
Ceiling
890(Ceiling opening)(Distance between suspending bolts)1070
515
515
(Dist
ance
betw
een s
uspe
nding
bolts
)
860(
Cei
ling
open
ing)
780 20 Over
Note:Dimension of ceiling opening marked with * can be aslarge as 910mm, but the matching part of ceiling withornament panel shall be over 20mm.
AB24,28
AB36,42
INSTALLATION INSTRUCTIONS
5.3.4 Installation
4 5
7
(2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details. Center of the hole is marked on the paper pattern. Center of the unit is marked on the card in the unit and on the paper pattern. Mount paper pattern onto unit using 3 screws . Fix the corner of the drain pan at piping outlet.
(1) Install unit temporally
In the case of new ceiling
Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.
< After installation on the ceiling >(3) Adjust unit to its right position. (Refer to preparation for the installation-(1))(4) Check unit's horizontal level.
Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level usinghorizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage, problemmay occur on floating switch, causing water leakage.)
(5) Remove the washer mounlting , and tighten the nut above.(6) Remove the paper pattern.
(1) Install unit temporally Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket. Fix the bracket firmly.(2) Adjust the height and position of the unit. (Refer to preparation for the installation (1) ).(3) Proceed with and of "In the case of new ceiling".
LevelPolythene pipe
3 4
In the case of ceiling already exists
Scrtews at the piping outlet is fixed at the cornerof drain pan.
Center of ceiling hole Paper pattern 4Paper pattern
5Screw (accessory)5Screw(accessory)
[Fix the paper pattern]
5.3.5 Refrigerant piping
As for outdoor piping, please refer to installation Manual of outdoor unit.
6 9
Apple refrigerant oil
Torque spanner
spanner
Piping joing
Flare nut
Medium size seal pad 9 (accessory)
Clip 3
Gas pipe
Liquid pipe
Insulator (accessory)
(For liquid pipe)
Insulator (accessory)
(For gas pipe)
7
6
(Cover the piping joint with seal pad.) R0.4 ~ 0.8
A
Pipesize
Tightentorque A(mm) Flare shape
9.52 3270~3990N.cm
(333~407kgf.cm)
6180~7540N.cm
(630~770kgf.cm)15.88
19.059720~11860N.cm
(990~1210kgf.cm)
12.0~12.4
18.6~19.0
22.9~23.3
900.
545
2
Outdoor is precharged with refrigerant.Be sure to see the Fig.1, when connecting and removing piping from unit.For the size of the flare nut, please refer to Table 1.Apply refrigerant oil at both inside and outsid of lflare nut. Tighten it band tight 3-4 turns then tighten it.Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage).Check piping joints for gas leakage. Insulate piping as shown in Fig. below.Cover joint of gas piping and insulator with seal .
Table 1
Diameter of Pipe
Liquid Pipe 6.35mm
Gas Pipe 12.7mm
Tighten Torque
18 N. m
50N. m
INSTALLATION INSTRUCTIONS
5.3.6 Installation of drainage pipe
1-1.5m
Use the self-provided stiff pipe and clip with unit. Insert water pipe into water plug until it reaches the white tape.Tighten the clip until head of the screw is less than 4mm from hose.Wind the drain hose to the clip using seal pad 8 .Insulate drain hose in the room.
2
<Cautions for the drain water lifting pipe>
Clip 2
Tape (White) Self-provided stiff pipe
Clip 2
4mm below
(accessory)
(accessory)Large size seal pad
Clip 2
10
Installation height shall be less than 280mm.There should be a right angle with unit, 300mm from unit.
Waterring can of plastic
(1) Install water drainage pipe
Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm)Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.If downward slope can't be made, take other measures to lift it up.Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.
Slope over 1/100
75 b
elow
Self-provided stiff pipe(accessory)
500
belo
w
300mm below 1~1.5m
280
belo
w
500
belo
w
220
Drain hose 1(accessory) drain water lifting pipe
Suspending bracket
Clip(accessory)
2
Ove
r 100
(Note)
If several water hoses join together, do as per following proceedures.
Connect water hoses with a T joint.
Specifieations of the water hoses shall meet the requirements for the unit running.
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.
Method of water charging
11
When wiring is not complete
Charge water fromair outlet
Charge water frominspecting hole
Watering can of plasticpipe should be about100 mm long
100mm
Water drainage port formaintenance
(Drain water fromthis hole)
Self-provided stiff pipe Maintenance
Inspecting hole
Cover of controll box
PCB on indoorTerminal
Terminal blockConnect withoutdoor unit
1 2 3
L N
Power
1 2 3
Indoor
Outdoor
H07RN-F3G 4mm2
H05RN-F4G 0.75mm2
1 2 3R S T
1 2 3
N
Indoor
Power Outdoor
H05RN-F4G 0.75mm2
H07RN-F5G 2.5mm2
(2) Check if water drainage is smooth after installation.Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.
After wiring
Remove cover of control box, short connect "CHECK" terminal of the indoor unit, which is on the uperpart of indoor unit PCB. Connect 1PH power to terminal 1 and 2 on terminal block.Note, in this operation, fan will be running.Upon confirmation of a smooth water drainage, be sure to cut off power supply andremove shortconnection of "CHECK" terminal.
Check water drainage in cooling operation. See also test run.
INSTALLATION INSTRUCTIONS
5.3.7 Wiring
Terminal blockClip A
Cover of control box 1
Rubber tube A
Grounding lead
Cover of control box 2
Terminal blockConnect withoutdoor unit
OutIn
Field wiringAttach seal pad
Don't fail to seal it, or, water may come in.
Rubber tube Note: Have it sealed, leaving no space.
Seal pad (small size)( ) (Wind around wire)
12
•
All supplied parts. materials and wiring operation must in appliance with local code and regulations.Use copper wire only.When make wiring, please refer to wiring diagram also.All wiring work must be done by qualified electricians.A circuit breaker must be installed, which can cut power supply to all system.See Installation Manual of outdoor unit for specifications of wires, circuit breaker, switches and wiring etc.Connecting of unitRemove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires,tighten clamp A. Connect wires of correct pole to the terminal block inside.Wind seal (12) around wires. (Be sure to do that, or, dew may occur).Upon connecting, replace control box cover (1) and (2).
Obscrve the following when connecting power supply terminal block: Don't connect wires of different specifications to the same terminal block. (Loose wire may cause overheating of circuit) Connect wires of same specifications as shown in right Fig.
Connect wires of the samespecifications at two sides.
Don't connect wires of thesame specifications at one side.
Don't connect wires of thedifferent specifications.
<<WARNING>>
5.3.8 Wiring example
As for outdoor unit circuit, please see Installation Manual of outdoor unit.Note: All electric wires have their own poles, poles must match that on terminal block.
5.3.9 Installation of ornament panel
1. Prepare ornament panel Handling of ornament panel
Ornament panel shall not be placed face down or against wall, neither on an uneven object.Don' t bend carelessly the swing flap, or, problem may occur.
(1) Remove air inlet grill from ornament panel:Push in the bar on inlet grill and lift it up. (Refer to Fig. 1)
Lift it up for about 45 degree and remove it from ornament.Tear off adhesive tape fixing air filter on the back of the airinlet grill. (Refer to Fig. 2)
Cautions for the installationBe sure to show customers Operation Manual and guide them how to operate unit correctly. Before installation, read alsothe Installation Manual of indoor unit.With this ornament , 2 or 3 air flow direction is not available. Suitable height is 3 m.
2
Accessory Pad Pad
1
Bar
INSTALLATION INSTRUCTIONS
5 _ 8mm
3
2
2
1
4
Holding ring
Piping hole position
Swing flap motor
Fig. 7
SealIndoor unitCeiling material
Ornament panel
(2) Remove cover plate at corner Tear off the adhesive tape, and slide it off. (Refer to Fig. 3)
(1)
(2)
2. Install ornament panel on indoor unit.
As shown in Fig . 7, match the position ofswing flap motor with that of the indoor unitpiping hole , so that ormament panel can beplaced on to indoor unit.Installation of ornament panelPlace the holding ring on swing flao motorside teporarily on hooks of the indoor unit.(2 pcs)Put the other two holding rings on the hooks atboth side of the indoor unit. (Care should betaken not to push wiring of swing flap motorinto seals).Screw in all 4 screws under holding ring forabout 15mm. (Pancl will rise).Adjust the ornament panel as per Fig. 7 tocover opening on the ceiling.Tighten screws to redrce the thickness of sealsbetween ornament and indoor unit to 5-8mm.
1
2
3
4
5
If indoor unit is at horizontal leveland water drainage is smooth,then, indoor unit height can be ad-justed throrgh holes at corners ofornament panel.
If screws are not tighten tight, problems in Fig, 8might occur. Tighten screws properly.
If there are still space after tighteningof screws, please readjust the heightof indoor unit. (Refer to Fig. 9)
Leave no space.Fig. 9
Gas leakage.
Gas leakage from roof.
Contamination Mist exists and drop down.
Fig. 8
45
Fig. 2
Adhesive tape
Slide
Fig. 3
For indoor unit installation, please refer to Installation Manual.Hook
Caution
12
Leave no space.
Fig. 6
3. Mounting on high ceiling(1) Ornament panel can be mounted on ceiling as high as 3 m.(2) Please install pad as accessary.
Cut open the pad along cutting ling. Use part a only and discard part b . (Refer to Fig. 4)Install part a of the pad on the place shown in Fig. 5. Refer to Fig. 6.
Fig. 4
(3)Wiring on ornament panel Connecting of wiring of the swing flap motor on ornament panel. (2 places) (Refer to Fit . 10)
50
Cutting line
100a b
Place it on the frame.
Part a of the padPart a of the pad
Swing flap motor Fig. 5
Side of ornament panel
Fig. 10
Wiring diagramSide of indoor unit
If connecting is not made, error code(A7) appears on remote controller. So,make proper connecting.
INSTALLATION INSTRUCTIONS
1
2
4. Installation of inlet grill and cover plateInstallation of inlet grillInstall in reversed order of “Prepare ornament pandl”.Inlet grill can be adjusted into four directions by turning inlet grill. Inlet grill position can be adjusted asper customers request.
(1)
When installing inlet grill, take care not to twist wiring of swing flap motor.
Install cover plate on the corner As shown in Fig. 11 tie the cover plate onto the bolt on ornament plate. Install cover plate onto ornament plate. (Refer to Fig. 12)
(2)
Slide all five hold rings
to let them drop in holes
on ornament plate,
Fig. 12Fig. 11
bolt
5.3.10 Test running
Refer toTake special care during installation, check after working
(1)(2)(3)(4)(5)(6)
Proce-dure OperationOpen check valve on gas pipe.Open check valve on liquid pipe.Press ON/OFF button, select Cooling mode.Let it run for 3 min.Press air flow adjust button to make unit run properlyConfirm unit functions according to Operation Manual.
Upon installation of piping, water drainage and wiringwork, make test run to ensure proper unit operation.
(1)
(2)
(3)
(4)
(5)
Procedure Operation
Open check valve on gas pipe.
Open check valve on liquid pipe.
Press ON/OFF button, select Cooling mode.
Let it run for 3 min.
Cut main power supply after operation.
Conduct test run before installing ornament panel
Note:If unit doesn’t run due to certain problem, please see‘‘Note to unit maintenance’’.
Conduct test run after installation of ornament panel
INSTALLATION INSTRUCTIONS
Preparation before installing convertible type unit Before installation of convertible type unit, please confirm which type will be selected: in the ceiling or on the floor. There is a dial switch K1 on the PCB, if you select D, that means the installation is in the ceiling. If you select L, that means installation position is on the floor. In the ceiling mode, there will a 4 degrees temperature compensation in heating mode. Because in heating mode, the warm air will rise and stay in higher position. If there is not temperature compensation, when the set temperature has arrived, it may happen that the air in higher position has become the set temperature, but the air in lower position has not arrived the set temperature. There is no different for the operation of swing and the heating capacity.
D
L
K1
Installation procedure of convertible type unit
CAUTION!
INSTALLATION PROCEDUREInstall the room air conditioning unit as follows:
PREPARING INDOOR UNIT INSTALLATIONFIRST REMOVE THE INTAKE GRILL
A. FLOOR MOUNTING(AC36/42 only suitable for exposed ceiling mounting)
1. DRILLING FOR PIPINGThe piping and drain can exit the unit in two directions as shown below in (Fig. 2)
(Fig. 2)
The drain hose must be connected to the right side asshown in (Fig.3).
After the piping and drainage exit has been selected,drill a 7 cm dia. hole through the wall so that thehole is slanting downward toward the outside toensure good drainage. When the pipe is led out fromthe rear, make a hole as Fig.4, at the position shown.
2. INSTALLING DRAIN HOSEThe drain hose must be connected to the right side ofthe unit (Fig.3)Insert the drain hose into the drain pan, then securethe drain hose with a nylon fastener. (Fig.5)
Be sure to arrange the drain hose correctly as shownin Fig. 7 so that it is lower than the drain hoseconnecting point of the indoor unit, if condensatepump is not fitted to system.
B. UNDER CEILING MOUNTINGUsing the installation template, drill holes for pipingand anchor bolts(for holes).(Fig.9)
Fig 9
1. DRILLING FOR PIPINGSelect piping and drain directions. (Fig.10)
Fig 10
(Fig. 6) Drain pan
Drain hose
Insulation(Drain hose)
Arrange the drain hoselower than this portion.
Fig. 7 OK NO NO
Drain hose
rear
down
(Fig. 3)
Drain hose (Right side)
Wall
7cm6mm
Indoor unit outdoor unit
(Fig. 4)
Drain pan
Drain hose
Nylon fastener(supplied by others)
(Fig. 5)
A
Drain hose
Rear (Install the drain hosein this direction.)
AB40 40
100mm
720m
m
87.5mm
147m
m32
6mm
247m
m
8553
Wrap the insulation around the drain hoseconnection.(Fig.6)
Ensure that the unit is fixed level. Height ‘A’ must be lessthan 5 mm.(Fig.8)
Model A BAC24 990 500AC28 1320 1240AC36/42 1920 1840
68 16 21 28
381
232
26.5
26.5
2-R2.5
10
187.5
4-R5
68162128381
232
26.5
26.5
2-R2.5
10
18
7.54-R5
Wall6mm
12.5mm
Fig. 11
Fig. 12
Fig. 13
Spring washer
Special nutBracket
CAUTION
Hex bolt
8 to 13mmIndoor unit
Fig. 14
Fig. 16Remove the hole cover.
OK
Arrange the drain hoselower than this portion
Drain hose
NO
Fig. 15
Bolt Bracket
Indoor unit
Install the drain hose at the rear; it should not beinstalled on the top or right side.
After the piping and drainage exit has been selected,drill 80mm and 50mm or 150mm dia. hole through thewall. So that the hole is slanting downward toward theoutside for smooth water flow if a condensate pump isnot fitted to system.
4. INSTALLING INDOOR UNITReset the hex bolts as shown in Fig.14.
Apply the indoor unit to the brackets.(Fig.15)
Now, securely tighten the hex bolts in both sides.
5. INSTALL THE DRAIN HOSEThe drain hose will be connected to the right side.(Fig.3)Insert the drain hose into the drain pan, then secure thedrain hose with a nylon fastener.(Fig.5)Wrap the insulation (drain hose)around the drain hoseconnection. (Fig.9)Be sure to arrange the drain hose correctly so that it islower than the drain hose connecting port of the indoorunit (Fig.16) if condensate pump is not fitted to system.
Insert the anchor bolts into the drilled holes, and drivethe pins completely into the anchor bolts with ahammer. (Fig. 12)
3. INSTALLING BRACKETSInstall the brackets with nuts, washers and spring washers.(Fig. 13)
2. DRILLING HOLES FOR ANCHOR BOLTS ANDINSTALLING THE ANCHOR BOLTS
using a masonry drill, drill four 12.5 mm dia.Holes.(Fig.11)
Fig. 11
Installation procedure of convertible type unit
Wiring
CAUTION(1) Match the terminal block numbers and connection cable colours with those of the outdoor unit. Incorrect wiring may cause damage to the electrical parts.
(2) Connect the connection cables firmly to the terminal block. Incorrect installation may result in a fire.
(3) Always fasten the outside covering of the connection cable with the cable clamp.(If the insulation is chafed, a short curcuit may occur.)
(4) Always connect the earth wire.
Fig. 26Electrical component box
Remove the four selftapping screws.
CAUTIONDo not remove the screws. If the screwsare removed, the electrical componentbox will fall.
Fig. 25
Electrical component box
ELECTRICAL WIRING
1. INDOOR UNIT SIDE(1) Remove the electrical component box.
INDOOR UNIT SIDE
Wiring
Fig. 27
Electrical component box
Fig. 28
Base
Electrical component box cover
CAUTIONBe careful not to pinch the wiringbetween the electric component boxand base.
(1) Ensure all wiring complies with current regulations.
(2) It is recommended that a MCB of the correct rating is used to protect the system.
(3) Always use a circuit breaker that can trip all the poles of the wiring is fitted and has an isolation distance of at least 3mm between the contacts of each pole.
WARNING
(2) Pull out the electrical component box.
ELECTRICAL WIRING
(3) Remove the electrical component box cover.
(4) WiringSee wiring diagrams for indoor unit.
Remove the three tapping screws
CUSTOMER GUIDANCEExplain the following to the customer in accordance withthe operating manual:(1) Starting and stopping method, operation switching,
temperature adjustment, timer, air flow switching, andother remote control unit operations.
(2) Air filter removal and cleaning, and how to use airlouvres.
(3) Give the operating and installation manuals to thecustomer.
NOTICEAll Wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATIONS.These instructions do not cover all variations for every kind of installation circumstance. Should furtherinformation be desired or should particular problems occur, the matter should be referred to your localdistributor.
WARNINGBE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAI-LURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENTMALFUNCTION AND/OR PROPERTY DAMAGE.
(1) Preparation of indoor unitBefore or during the installation of the unit, assemble necessary optional panel etc. dependingon the specific type.
(2) Select places for installation satisfying following conditions and at the same time obtainthe consent on the part of your client user.
(a) Places where chilled or heated air circulates freely.When the installation height exceeds 3m warmed air stays close to the ceiling. In such cases,suggest your client users to install air circulators.(b) Places where perfect drainage can be prepared and sufficient drainage.(c) Places free from air disturbances to the suction port and blowout hole of the indoor unit,places where the fire alarm may not malfunction or short-circuit.(d) Places with the environmental dew-point temperature is lower than 28 and the relativehumidity is less than 80%. (When installing at a place under a high humidity environment, paysufficient attention to the prevention of dewing such as thermal insulation of the unit.)(e) Ceiling height shall have the following height.
(3) Avoid installation and use at those places listed(a) Places exposed to oil splashes or steam (e.g. kitchens and machine plants).Installation and use at such places incur deteriorations in the performance or corrosion withthe heat exchanger or damage in molded synthetic resin parts.(b) Places where corrosive gas (such as sulfurous acid gas) or inflammable gas (thinner,gasoline, etc) in generated or remains. Installation and use at such places cause corrosionin the heat exchanger and damage in molded synthetic resin parts.(c) Places adjacent to equipment generating electromagnetic waves or high-frequency wavessuch as in hospitals. Generated noise may cause malfunctioning of the controller.
Combinationwith silentpanel
416mm366mm
50 or more
Obstacle
100 ormore
100 ormore
1000
or m
ore
Unit: mm
Installation space
36,42 series14,18,24,28 series
(4) Preparation for suspending the unit
(a) Size of hole at ceiling and position of hanging bolts<Combination with silent panel>
57 A
B
C
(Hanging bolt position)
(Ceiling hole size)
(Panel dimensions)
137
30
30
(Ceiling ~ panelwrap dimensions)
(Cei
ling
~ pa
nel
wra
p di
men
sion
s)
(Han
ging
bol
t pos
ition)
(Cei
ling
hole
siz
e)
(Pan
el d
imen
sion
s)
7554
5
690
750
70
(Pip
e co
-nn
ectio
n si
de)
(b) Hanger bolts installationUse care of the piping direction when the unit is
DimensionsA
Unit: mm
B C
1406 1600 1660
986 1180 1240
Model
36,42 series
14,18,24,28 series
Hanging bolt M10
Hole-in anchorHole-in plug
Insert
Concrete
installed.
Installation procedure of mid ESP duct type
(5) Installation of indoor unitFix the indoor unit to the hanger bolts.If required, it ispossible to suspend the unit to the beam, etc.Directly by use of the bolts without using the hanger bolts.
When the dimensions of main unit and ceiling holes does not match, it can be adjusted withthe slot holes of hanging bracket.
Note
Adjusting to the levelness(a) Adjust the out-of levelness using a level orby the following method.
Make adjustment so that the relation betweenthe lower surface of the unit proper and waterlevel in the hose becomes as given below.
(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of thefloat switch may occur.
Tap selection on blower unit (When the high performance filter is used.)Taps of blower unit are set at the standard selection at the shipping from factory. Wherethe static pressure is raised by employing such option as the high performance filter,etc., change the connection of connectors provided at the flank of control box as shownbelow.
(6) Drain Piping(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding acrossan elevation or making traps.
When connecting the drain pipe to unit, paysuffcient attention not to apply excess force tothe piping on the unit side. Also, fix the pipingat a point as close as possible to the unit.For drain pipe, use hard PVC general purposepipe VP-25(I.D.1") which can be purchasedlocally. When connecting, insert a PVC pipeend securely into the drain socket beforetightening securely using the attached drainhose and clamp. Adhesive must not be usedconnection of the drain socket and drain hose(accessory).
Drain hoseStagedifferencepartDrain socket
Drain socket
Main unit
VP 25 joint(field purchased)Pipe cover(large)
[for insulation](accessory)
VP 25(field purchased)
Pipe cover[for insulation](field purchased)
Drain hose(accessory)
Pipe cover(small)[for insulation](accessory)
Clamp(accessory) Adhesion
PVC hose
Piping sideSupply water
Water level
0~5 mm(0~0.2")
Bring the piping side slightly lower.
Hanging boltM10 nut
Main unit
M10 washer
M10 spring washer
Do not pipe under water
Keep free from traps
Avoid riding across an elevation
Air vent
Inproper pipingGood piping1.5m ~ 2m
Suspensionbolts
Heatinsulation
A downhill gradeof 1/100 or more
(b)
(c)
Red
Yellow
WhiteStandard tap (at shipping) High speed tap
Black
Whi
te
Conn
ector
whit
e
Conn
ector
whit
e
Con
trol b
ox s
ide
Mot
er s
ide
Mot
er s
ide
Red
Blue
Red
Yellow
White
Blue
Red
Yellow
White
Blue White
Blue
Red
VP 30
Secure the elevation as high as possible(approx. 100 mm)
A downhill grade of1/100 or more
Drain hose
Joint for VP 25(Local procurement)
600
(Max
imum
loca
l dra
in u
p di
men
sion
)
Right overhead
290~325mm
Attached drain hose clamp
Drain pipingMain unit
Drain situation can be checked with transparent socket
Remove grommet.Make sure to installit back after test.
Insert water supply hosefor 20 mm ~ 30 mm tosupply water.(Insert hose facingtoward bottom.)
Pour water into a convex joint.
When constructing drain piping for several units, positionthe common pipe about 100 mm below the drain outletof each unit as shown in the sketch. Use VP-30(11/4")or thicker pipe for this purpose.Be sure to provide heat insulation to hard PVC pipes ofindoor placement.Do not ever provide an air vent.The height of the drain head can be elevated up to apoint 500 mm above the ceiling, and when an obstacleexists in the ceiling space, elevate the piping to avoidthe obstacle using an elbow or corresponding gadget.When doing this, if the stretch for the needed height ishigher than 500 mm, the back-flow quantity of drain atthe event of interruption of the operation gets too muchand it may cause overflow at the drain pan. Therefore,make the height of the drain pipe within the distancegiven in the sketch below.Avoid positioning the drain piping outlet at a place wheregeneration of odor may be stimulated. Do not lead thedrain piping direct into a sewer from where sulfur gas
Drainage Test
Conduct a drainage test after completion of the electrical work.During the trial, make sure that drain flows properly through the piping and that no waterleaks from connections.In case of a new building, conduct the test before it is furnished with the ceiling.Be sure to conduct this test even when the unit is installed in the heating season.
Procedures
Supply about 1000 cc of water to the unit through the air outlet using a feed waterpump.
(d)
(e)
(f)
(h)
(g)
12
3
4
12
(In the electrical work has not beencompleted, connect a convex joint in thedrain pipe connection to provide a waterinlet. Then, check if water leaks from thepiping system and that drain flows through
Exhaust holeState seeing from top of unit
Side fresh air inlet
Rear fresh air inlet
Fig.1 Fig.2
(7) Installation work for air outlet ducts
Calculate the draft and external static pressure and select the length, shape and blowout.A Blowout duct
2-spot, 3-spot and 4-spot with 200 type duct are the standard specifications. Determinethe number of spots based on following table.Note (1) Shield the central blowout hole for 2-spot. (2) Shield the blowout hole around the center for 3-spot.
Limit the difference in length between spots at less than 2:1.Reduce the length of duct as much as possible.Reduce the number of bends as much as possible. (Corner R should be as larger aspossible.)
Use a band. etc. to connect the main unit and the blowout duct flange.Conduct the duct installation work before finishing the ceiling.
(8) Connection of suction, exhaust ducts
(a) Duct connection positioni) Fresh air inlet
Inlet can be selected from the side or rear faces depending on the working conditions.Use the rear fresh air inlet when the simultaneous intake and exhaust is conducted.(Side inlet cannot be used.)
ii) Exhaust (Make sure to use also the suction.)Use the side exhaust port.
Good exampleBad exampleBad example
Ceiling surface
Heatinsulation Suction panel
(Silent panel)
Air conditioner main unit
B Special blowout (Option)
A Blowout duct (Optional or marketed item)
C
Hole for check
special inlet (option)(with air filter)
inlet duct (optional or
marketat item)
1. Before installation [Before finishing installation, do not throw the attached parts installation needs]
Confirm the way to move the unit to the installation place.Before moving the unit to the installation place, do not remove their packages.When have to remove the package, use a soft material or protection board with rope to lift the unit assembly to avoid unit damage or bumping a scrape.
2. Choose installation place(1) The chosen installation place should meet the following requirements and get the userís consent.
Place ensures ideal airflow distribution.The passage of airflow has no obstacles.When importing outside air, it should be imported directly from outdoors. (if the pipe can not be extended, it also can not be imported from top)Place ensures enough space for maintenance.The pipe length between indoor and outdoor unit is in the permitted limit (referring to outdoor unit installation part).The indoor unit, outdoor unit, electric wire and connection wire is at least 1m away from television and radio. This is to avoid the image disturbance and noise caused by the above-mentioned home appliance. (Even if 1m away, if the electromagnetic wave is too strong, it can also cause noise.)
(2) The height of ceilingThe indoor unit can install on the ceiling, which height is no more than 3m.
(3) Install and use the hoisting screw. Check if the installation place can bear the weight of unit assembly.
If not certain, strengthen it before install the unit.
(600x600)
Over 100 Over 900
Air out
Air in
Checking meatus
Ceiling
Ove
r 300
Ove
r 200
Indoor unit installation (High ESP Indoor unit installation (High ESP duct)
(1) The position relation among hoisting screw (unit: mm)
(3) Hanger bolts installationUse care of the piping direction when the unit is installed.
Hanging bolt M10
Hole-in anchorHole-in plug
Insert
Concrete
370250
910
603
628
590
Down side
Up side
(2) If necessary, cut the opening installation and checking needed on the ceiling. (If has ceiling)Before installation, finish the preparation work of all the pipes (refrigerant, drainage) and wire (wire controller connection wire, indoor and outdoor unit connection wire) of indoor unit, so that after installation, they can be immediately connected with outdoor unit.
Cut the opening on the ceiling. Maybe it needs to strengthen the ceiling to keep the ceiling even and flat and prevent the ceiling from vibration. For details, please consult to the builder.
(Use M10 screw bolt)
In order to bear the weight of the unit, for existed ceiling, using foundation screw bolt, for new ceiling, using burying embedded screw bolt, burying screw bolt or spot supplied other parts.
Before going on installation, adjust the gaps with ceiling.
3. Preparation before installation
AD242AHBEA
4. Installation of indoor unitFix the indoor unit to the hanger bolts.If required, it is possible to suspend the unit to the beam, etc.Directly by use of the bolts without using the hanger bolts.
When the dimensions of main unit and ceiling holes does not match, it can be adjusted with the slot holes of hanging bracket.
Note
Adjusting to the levelness
(a) Adjust the out-of levelness using a level or by the following method.
Make adjustment so that the relation between the lower surface of the unit proper and water level in the hose becomes as given below.
(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float switch may occur.
PVC hose
Piping sideSupply water
Water level
0~5 mm(0~0.2")
Bring the piping side slightly lower.
Hanging boltM10 nut
Main unit
M10 washer
M10 spring washer
Drain hoseStagedifferencepartDrain socket
Drain socket
Main unit
VP 25 joint(field purchased)Pipe cover(large)
[for insulation](accessory)
VP 25(field purchased)
Pipe cover[for insulation](field purchased)
Drain hose(accessory)
Pipe cover(small)[for insulation](accessory)
Clamp(accessory) Adhesion
For drain pipe, use hard PVC general purpose pipe VP-25(I.D.1") which can be purchased locally. When connecting, insert a PVC pipe end securely into the drain socket before tightening securely using the attached drain hose and clamp. Adhesive must not be used connection of the drain socket and drain hose (accessory).
(c)
5. Drain Piping
(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an elevation or making traps.
When connecting the drain pipe to unit, pay suffcient attention not to apply excess force to the piping on the unit side. Also, fix the piping at a point as close as possible to the unit.
Do not pipe under water
Keep free from traps
Avoid riding across an elevation
Air vent
Inproper pipingGood piping
1.5m ~ 2mSuspensionbolts
Heatinsulation
A downhill gradeof 1/100 or more
(b)
26
Drainage Test
Conduct a drainage test after completion of the electrical work.During the trial, make sure that drain flows properly through the piping and that no water leaks from connections.In case of a new building, conduct the test before it is furnished with the ceiling.Be sure to conduct this test even when the unit is installed in the heating season.
Procedures
Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.Check the drain while cooling operation.
(g)
12
3
4
12
VP 30
Secure the elevation as high as possible(approx. 100 mm)
A downhill grade of1/100 or more
When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit as shown in the sketch. Use VP-30(11/4") or thicker pipe for this purpose.
(d)
(e) The stiff PVC pipe put indoor side should be heat insulated.
(f) Avoid putting the outlet of drain hose in the places with irritant gas generated. Do not insert the drain hose directly into drainage, where the gas with sulfur may be generated.Backwater bendBecause the drain spout is at the position, which negative pressure may occur. So with the rise of water level in the drain pan, water leakage may occur. In order to prevent water leakage, we designed a backwater bend.The structure of backwater bend should be able to be cleaned. As the below figure shown, use T type joint. The backwater bend is set near the air conditioner.
As figure shown, set a backwater bend in the middle of drain hose.
H1
H2 H1=100mm or the static pressure of air sending motor
H2=1/2H1 (or between 50~100mm)
6. Installation of air suction and discharging duct
AInsulation
muffler cavity (air sending)
Sacking joint
Air volume adjuster
Air outlet
Enlarging chart of profile chart A
Vibration resistance hook
Checking meatus
Air conditioner main unit
Ceiling
Air suction grille with air filter
Please consult the after-sales service worker of Haier Air Conditioner for the choosing and installation of suction inlet, suction duct, discharging outlet and discharging duct. Calculating the design drawing and outer static pressure, and choose the discharging duct with proper length and shape.
The calculation of duct resistance (the simple calculation is as follow table)
Straight part
Bend part
Air out part
Static pressure box
Air inlet grille (with air filter)
Calculate as per 1m length 1Pa, 1Pa/m
Each bend takes as a3~4m long straight duct
Calculate as 25PaCalculate as 50Pa/each
Calculate as 40Pa/each
Good exampleBad exampleBad example
The length difference among every duct is limited below 2:1.Reduce the length of duct as possible as can.Reduce the amount of bend as possible as can.
Use heat insulation material to bind and seal the part connecting main unit and the flare part of air discharging duct. Perform duct installation work, before the fitment of ceiling.
7. Calculation method of the dimension of the simple quadrate air ductPresuming the unit length friction impedance of the duct is 1Pa/m, when the dimension of one side of the air duct is fixed as 250mm, as shown below:
Note:1Pa/m=0.1mmAg/mThe chosen chart of simple duct
m3/h(m3/n)100200300400500600(10)800
1,0001,200(20)
250 x 60(mmxmm)
250 x 90250 x 120250 x 140250 x 170250 x 190250 x 230250 x 270250 x 310
Shape
ItemAir volume
Square duct
Dimension
m3/h(m3/n)
1,4001,600
1,800(30)200024003,000(50)3,5004,0004,5005,0005,5006,000(100)
(mmxmm)
250 x 350250 x 390
250 x 430250 x 470250 x 560250 x 650250 x 740250 x 830250 x 920250 x 1000250 x 1090250 x 1180
Shape
ItemAir volume
Square duct
Dimension
Static pressure box
Air conditioner
Equipped with air filter (bought)
BA
A
A
600m3/h(10m3/min)
2400m3/h(40m3/min)
Air volume
B
A
8. The attentive matters in installation of air suction and discharging duct
Recommend to use anti-frost and sound-absorbing duct. (locally bought)The duct installation work should be finished before the fitment of ceiling.The duct must be heat insulated.
The specific air-discharging outlet should be installed at the place where the airflow can be reasonably distributed.The surface should leave a checking meatus for checking and maintenance.
9. The examples of improper installation
Do not use air in duct and take the ceiling inner side instead. The result is because of the irregular outer air mass, strong wind and sunshine, the humidity is increased.There may be water drop on the outside of duct. For cement and other new constructions, even if not taking ceiling inner side as duct, the humidity will also be so high. At this time, use glass fiber to perform heat preservation to the whole. (use iron net to bind the glass fiber)
Affected by the capacity of air discharging fan, the strong wind in the outer duct and wind direction, when unit air sending volume exceeds the limit, the discharged water of heat exchanger will overflow, leading to water leakage.
AirAir
Duct
Special air discharging outletUse screw bolt to fix
Air discharging fan
Improper example
200
150
100
50
026 30 34 35 40 43
*
*
***
**
** *
*
*
*
*
Figure 1 Figure 2
Through the fan controller switch in the electric box, the air volume of this unit can be continuously adjusted.
10. The operation method of fan controller
It is unnecessary to adjust air volume through the duct side wind level (unit outside static adjustment).The air volume set should be in the operation air volume range.Figure I shows the position of fan controller in the electric box and operation method.
After finishing the electric work, perform test run. According to the main points in Figure II making the chosen switch No. accordant. And confirm if it reaches the needed air volume.
Note:1) When operating the fan controller, it is possible to touch the electric charging part, so do cut off the power supply.
2) Do not set the dial at the position less than 1.
3) The figure circled in Figure II indicate the capacity number of fan controller. The non-listed capacity number may exceed the permitted operation capacity range, so it is impossible to operate.
4) When delivering from factory, the capacity number of fan controller is set at ìNo.5î.
Rotate this switch(capacity number setting: No. 1 ~ No. 8)
Once the fan controller has trouble, this linker can perform emergency assistant control. When this linker is connected to the linker from the PCB, it can operate with total load.
When this linker is connected to the linker from the PCB, through the fan speed adjustment panel to adjust speed.
High Condition of standard air volumeLow (air volume 100Pa)
Out
er s
tatic
pre
ssur
e Pa
Example of duct
Lower limit Upper limit
Standard air volume(m3/min)
The example of the method of choosing capacity number:1) If the unit is in high-speed operation, needing take outer static pressure is 180Pa in capacity air volume 34m3/min as working condition point, according to Figure II ìThe characteristic chart of air volumeî, the capacity number of fan controller is No. 2.
2) If the unit is in low speed operation, needing take outer static pressure is 60Pa in capacity air volume 32m3/min as working condition point, according to Figure II ìThe characteristic chart of air volumeî, the capacity number of fan controller is No. 4.
310
30530
80 510
11. Refrigerant pipe[The air side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause water leakage.]
The outdoor unit has been charged with refrigerant.When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown, use spanner and torque spanner together.When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Use hand to twist 3-4 rings, then fasten with spanner.Referring to Table I to confirm the fasten torque. (too tight may damage nut leading to leakage)Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown.Only use seal cushion to bind the joint part of air pipe and heat insulation parts.
Paste the refrigerant oil here
Torque spanner
Spanner
Pipe jointCone nut
Middle size seal cushion (accessory)(Use seal cushion to bind the pipe joint)
Clamp
Heat insulation (accessory) (for liquid pipe)
(for gas pipe)Heat insulation (accessory)
Gas pipeLiquid pipe
Liquid pipe Gas pipe Electric boxUpper
Air inlet Air outlet
Down sideDrain hose connection mouthVP25 PVC pipe
9.52 12.0~12.43270~3990 N.cm(333~407 kgf.cm)
(mm)Specification of pipe Tighten torque ConeCone dimension
A (mm)
R0.4~0.8
A
90 0.5
45 2
22.9~23.39720~11860 N.cm(990~1210 kgf.cm)
19.05
Drain Hose
Swing fender
Refrigerant pipeCable lineEarthing line
Air filter
Outlet
(located in the suction grill)
In cooling operation,todischarge the waterfrom inside the room.
Discharge unit (built in)
(located in the outlet)
Remote Controller
6.PARTS AND FUNCTIONS
3
Air inlet
AB242ACBEA AB28NACBEA
High ESP duct type:Air outlet
Air inlet
Duct
Duct
Drainpipe
Air outlet
Air inlet
Compressor (inside)
Fig.1 Indoor Unit1 Operating Control Panel (Fig.2)2 Emergency switch3 Remote Control Signal Receiver4 Power Indicator Lamp (Red)5 OPERATION Indicator Lamp (Green)6 TIMER Indicator Lamp (Yellow)
4 5 6
2
3
POWER OPER TIMER
EMER
Fig.3
AC28NACBEA
PARTS AND FUNCTIONS
Air outlet
Air inlet
Duct
AU242AHBEA AU28NAHBEA
1
AD242AMBEA AD28NAMBEA
Fig.1 Indoor Unit
14
67
3Fig.2
POWER
OPER
TIMER
COMP
EMER 2
1 Operating Control Panel (Fig.2)2 Emergency switch3 Remote Control Signal Receiver4 Power Indicator Lamp (Red)5 OPERATION Indicator Lamp (Green)6 TIMER Indicator Lamp (Yellow)7 Compressor Run Lamp (Green)8 Intake Grill (Fig.3)9 Air Filter
10 UP/DOWN Air Direction Flaps11 RIGHT/LEFT Air Direction Louvers (behind UP/DOWN Air Direction Flaps)
3
9
8
Fig.1
1110
5
AC242ACBEA
REMOTE CONTROLLER FUNCTIONS
14.HIGH/SO ButtonUsed to select HIGH or SOFT operation.
21
22
31
29
32
FRESH
HIGH/SOTIMER
SET
FILTER
B A
M D
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ONOFFSWING
MODE
CLOCK
CODE LIGHT
OFF
AUTO
1
2
3
4
67
9
10
11
15
13
5
8
16
17
30
34
35
33 2324
25
26
2728
20
12
14
Remote controller
1.TEMP Setting Button(Used to set temperature. Setting ranges:16 C to 30 C)In Up/Down function, for controlling up anddown filter.
2.SWING ButtonIf you press this button once, auto swing willbe activated.If you press this button again, the louver willfix in the present position.
3.Power ON/OFF Button Used for unit start and stopAfter power on, the LCD of remote controllerwill display the previous operation state (exceptfor TIMER,SLEEP and SWING state).
4.Operation MODEUsed to select operation mode.Every time you press MODE button, operation modechanges according to following sequence:
5.HEALTH ButtonUsed to set health mode, if the unit has the negative ion functionand oxygen bar function.
AUTO FANHEATCOOL DRY
6.CLOCK ButtonUsed to set correct time.
(Note: if time of TIMER ON is the same as TIMEROFF,TIMER ON/OFF cannot be set)
10.RESET ButtonPress this button by using a sharp article to resumethe correct operation of the remote controller in caseof need, i.e. for example in case of malfunctions dueto electromagnetic noise.
17.SLEEP Button(The clock must be corrected before setting sleepfunction)Used to set sleep mode.
13.Up and down ButtonUsed to set TIMER and CLOCK up or down.
8. FILTER ButtonUsed to set up/down function of filter.
NOTE: 1.Cooling only air conditioner does not have the displays and functions related to heating. 2.HIGH/SO button This button is activated in Cooling/Heating mode, the fan speed is in AUTO mode after pressing it and "high functon" will be cancelled automatically after 15 minutes running.
11.LOCK ButtonUsed to lock operation button and LCD displaycontents: by pressing this button, other buttons comesout of function and lock state display appears; if you pressit again, lock state will be no more active and lock statedisplay will disappear.
7.Remote controller functions
7.CLOCK ButtonUsed to select TIMER ON, TIMER OFF.
9. CODE ButtonUsed to select code A or B, for this unit, the code is A.
18
12.LIGHT ButtonUsed to light the control panel (only for cabinet unit)
15.SET ButtonUsed to confirm TIMER and CLOCK settings.16.FRESH ButtonUsed to set fresh mode, the unit will draw in fresh air.
19
36
Clock Set
Displays when healthy run function is set.
22.TEMPERATURE Display
34.LOCK State Display
33.BATTERY Energy DisplayNotify the user when it is time to changethe batteries.
24.HIGH/SO Display25.SIGNAL SENDING Display26.FRESH AIR Display27.ELECTRICAL HEATING Display
29.HEALTH Display
32.SLEEP State Display
31.Operation MODE DisplayAUTO RUN COOL RUN DRY RUN HEAT RUN FAN RUN
35.FAN SPEED Display
23.AUTO SWING Display
19.TIMER OFF Display
21.FILTER Display
36.TIMER ON Display
When unit is started for the first time and after replacing batteries in remotecontroller, clock should be adjusted as follows:1.Press CLOCK button, clock indication of " AM " or " PM " flashes.2.Press or to set correct time. Each press will increase or decrease 1 min. If the button is kept pressed, time will increase or decrease quickly.3.After time setting is confirmed, press "SET" : AM or PM stop flashing, while clock starts working.Note:AM means morning and PM means afternoon.
When operating the remote controller in an area whereelectronically controlled lights are installed or wireless handsetsare used, please move closer to the indoor unit as the functionof the remote controller might be affected by signals emittedby the above mentioned equipments.
Battery loading
Confirmation indicatorIf no indication is displayed after press ON/OFF button,reload the batteries.
AUTO
LO
MID
HI
AUTO
Remote Controller' OperationWhen in use, direct signal transmissionhead to the receiver placed on the indoorunit
The distance between the remote controller and the receivershould be max 7m and there should be no obstacle between them.Do not throw the remote controller; prevent it from beingdamaged.
18.FAN ButtonUsed to select fan speed:LOW,MID,HIGH,AUTO.
Note:It is recommended that the batteries be removed from thecompartment if the remote controller is not used for an extendedperiod.The remote controller is programmed for automatic test ofoperation mode after the batteries are replaced. When the testis conducted, all icons will appear on the screen and thendisappear if the batteries are properly fitted.
Caution:
If the remote controller does not operate as designed afterfitting new batteries of the sametype, press the Reset button (marked ) with a pointed article.
20.CLOCK Display
30.DEHUMIDIFICATION Display
28.Some other buttonsAll these functions are not available now.
FRESH
HIGH/SOTIMER
SET
FILTER
HEALTH
RESET LOCK
SLEEPMODE
CLOCK
CODE LIGHT
321
Battery loadingBatteries are fitted as follows:
Loading the batteryEnsure that batteries are correctly placed in the compartmentas required for positive and negative terminals.
Replacing the battery compartment lidThe battery compartment lid is reinstalled in the reversesequence.
Display reviewPress the button to see if batteries are properly fitted. Ifno display appears, refit the batteries.
Remove the battery compartment lidSlightly press and disengage the battery compartment lid markedwith ì î and then hold the remote controller by the uppersection and then remove the battery compartment lid by pressingin the direction of the arrow as shown in the figure above.
* ** *
Fan Operation 1.Unit startPress ON/OFF button to start your air conditioner.Previous operation status appears on LCD (except forTIMER, SLEEP, and SWING setting).
2.Select operating modePress MODE button. At each press, operation modechanges as follows:
3. Adjust fan speedPress FAN button. At each press, fan speed changes asfollows:
Air conditioner will run at the selected fan speed.When in AUTO mode, unit will adjust fan speedaccording to room temperature automatically.
4. Unit stopPress ON/OFF button to stop unit.
Then select FAN
About FAN modeWhen the air conditioner runs in FAN mode,it is not possible to select AUTO FAN or toset temperature.
AUTO FANHEATCOOL DRY
A
FRESH
HIGH/SOTIMER
SET
FILTER
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ONOFFSWING
MODE
CLOCK
CODE LIGHT
AUTO
41 3
2LOW MID HIGH
AUTO, COOL , HEAT and DRY Operation
1. Unit startPress ON/OFF button,unit starts.Previous operation status appears on LCD (except for TIMER,SLEEP and SWING setting)
3.Temperature setting
Then select AUTO run or select COOL operation or
select DRY operation or select HEAT operation
2.Select operation modePress MODE button. At each press, operation mode changesas follows:
Press TEMP button.Every time the button is pressed, temp. setting increases1 C; if the button is kept pressed, temp. setting will increasequickly.
Every time the button is pressed, temp. setting decreases1 C, if the button is kept pressed, temp. setting will decreasequickly.Set proper temperature
4.Adjust FAN buttonPress FAN button. At each press, fan speed changes as follows:
Air conditioner will run at the selected fan speed.
5. Unit stopPress ON/OFF button,unit stops.
In ATUO mode, the temperature setting is not displayed on LCD. In this mode, during running air conditionerwill select COOL, HEAT or FAN mode automatically according to the room temperature.In DRY mode, when room temperature becomes 2 C higher than temperature setting, unit will run intermittentlyat LOW speed regardless of FAN setting. When room temperature is lower than temperature setting, unit willonly run FAN operation.In HEAT mode,warm air will blow out after a short period of time due to cold-draft prevention function.
AUTO FANHEATCOOL DRY
AUTO LOW MID HIGH
FRESH
HIGH/SOTIMER
SET
FILTER
A
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ONOFFSWING
MODE
CLOCK
CODE LIGHT
AUTO
Temp. setting +2 CTemp.setting
On reaching temp.setting+2 C, unit will run in mildDRY mode.
Ultra-low air flow
COOL operation startswhen room temp.ishigher than temp.setting.
3
5 1
3
4
2
AUTO
Press SWING button.Up and down airflow varies upwardsand downwards. Left and right airflowvaries left and right sides.
Always use SWING button on the remotecontroller to adjust flaps. Adjusting them by handmay result in air conditioner's abnormally running.
Displays on the LCD disappear.All indicators on the indoor unit go out.Swing louver automatically close the air outlet.
After unit stops:
AUTO SWING
Adjusting air flow direction
AUTO SWING
When the automatic swing louver moves to the properangle, press SWING button can fix the airflow direction.
Please carefully set temperature when children,old or infirm people ues the air conditioner.
In case of great humidity, If the vertical flapsare completely turned towards left or right, thelouver will drop water.
Never adjust the louver directly by hand, as thiscould make it work abnormally.If the louver workabnormally, stop unit, restart and adjust the louverby remote controller.
Hints:As in COOL mode air flows downwards, adjusting airflow horizontally will be much more helpfulfor a better air circulationAs in HEAT mode air flows upwards, adjusting airflow downward will be much more helpful fora better air circulation.Be careful not to catch a cold when cold air blows downward directly.
In COOL or DRY mode, do not leave the louver indownward position for a long time, as the watervapor close to the grille may condense and watermay drop from the air conditioner.
FRESH
HIGH/SOTIMER
SET
FILTER
A
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ONOFFSWING
MODE
CLOCK
CODE LIGHT
AUTO
Sleep FunctionBefore going to bed you can press down the SLEEP button and the air conditioner will run so as to makeyou sleep more comfortably.Before using this function, the clock must be set.
Use of SLEEP functionAfter the unit's start, set running mode and then press SLEEP button once to make the air conditionerhave the previous-set sleep time (first power-on is "1h"). The sleep symbol will appear. Press time button / : you can choose the time in 1~8 hours. Each time the button is pressed, the time increases/decreases 1hour: "xh" and "OFF" indications appear on the display.
Operation Mode
1.In COOL, DRY modeOne hour after sleeping operation start, the temperatureis 1 C higher than the setting one. After another hour,temperature rises 1 C: sleep run continuously for another6 hours and then stops. The actual temperature is higherthan the setting one which is to prevent from being toocold to your sleep.
2.In HEAT modeOne hour after sleeping operation start, the temperatureis 2 C lower than the setting one. After another hour,temperature decreases by 2 C more. Temperature willautomatically rise by 1 C after another 3 hours'continuous operation. The actual temperature is lowerthan the setting one which is to prevent from being toohot to your sleep.
3.In AUTO mode.The air conditioner will run in corresponding sleepoperation according to the automatically selectedoperation mode.
SLEEP RUN BEGINS SLEEP RUN STOPS
SETTING T SHUT DOWN
about 6 hrs
1 hrs
In COOL,DRY mode
increase 1 C
increase 1 C
SLEEP RUN BEGINS SLEEP RUN STOPS
SETTING T SHUT DOWN
1 hrs1 hrs
3 hrsabout 6 hrs
increase 1 C
decrease 2 C
decrease 2 C
Notes:After setting SLEEP function, it is not possible to set clock.If set-sleep time does not reach 8 hours, unit will automatically stop operationafter set time is reached.Set " TIMER ON " or " TIMER OFF "In COOL,DRY mode function first,then set SLEEP. After set SLEEP function, the TIMER function cannot beset.
In HEAT mode
FRESH
HIGH/SOTIMER
SET
FILTER
A
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ONOFFSWING
MODE
CLOCK
CODE LIGHT
OFF
AUTO
Every time the button is pressed, time increases 10 minuts.If the button is kept pressed, time changes quickly.
Timer ON/OFF FunctionSet clock correctly before starting TIMER operation
1.Unit startAfter unit start, select your desired operation mode (operationmode will be displayed on LCD)
2.TIMER mode selectionPress TIMER button on the remote controller to change TIMERmode. Every time the button is pressed, display of TIMER modechanges as follows:
ON OFF ON OFFAM12:00 AM12:00PM 12:00 PM 12:00
TIMER ON TIMER OFF TIMER ON-OFF
blank
Then select TIMER mode as needed (TIMER ON or TIMER OFF).Now or will flash.
3.TIMER setting (press time adjust buttons )
Every time the button is pressed, time decreases 10 minuts.If the button is kept pressed, time changes quickly.It can be adjusted within 24 hours at will.
4.Confirm settingAfter setting correct time, press SET button to confirm time. Now
Time displayed: unit starts or stops at X hour X min (TIMER ONor TIMER OFF)5.Cancel TIMER modeJust press TIMER button several times until TIMER mode disappears.
Hints:After replacing batteries or if a power failure occurs, TIMER settingmust be reset.Remote controller has memory function. When you use TIMERmode next time, just press SET button after mode selection if timersetting is the same as the previous one.
Note:After setting TIMER function, the remote controller displays TIMER time. If you want to see clock time,just press CLOCK button once: clock time will be displayed (if you press the button again continuously,youcan adjust clock). 5 seconds later, the display will show TIMER time again.
ON OFF
ON OFFor stop flashing.
FRESH
HIGH/SOTIMER
SET
FILTER
A
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ONOFFSWING
MODE
CLOCK
CODE LIGHT
1
2
3 4
Timer ON-OFF FunctionSet clock correctly before starting TIMER operation
1.Unit startAfter unit start, select your desired operation mode (operationmode will be displayed on LCD)
2.TIMER mode selectionPress TIMER button on the remote controller to change TIMERmode. Every time the button is pressed, display of TIMER modechanges as follows:
OFF
3.Time setting for TIMER ON
4.Timer confirming for TIMER ONAfter setting correct time, press TIMER button to confirm time. Now
5.Timer setting for TIMER OFFPress time buttons and follow the same procedures in " Time settingfor TIMER ON"
Press time button
ON stops to flash, while starts flashing.
Time displayed : unit starts at X hour X min.
6.Time confirming for TIMER OFFAfter time setting, press SET button to confirm time. stops to flash.
Time displayed: unit starts at X hour X min.
7.Canel TIMER modeJust press TIMER button several times until TIMER mode disappears.According to the time setting sequence of TIMER ON and TIMER OFF,either start-stops or stops-start can be realized.
If the time setting of TIMER ON is the same as TIMER OFF, TIMERON-OFF function cannot be set.
ONThen select TIMER ON-OFF mode. will flash.
Every time the button is pressed, time increases 10 minuts.If the button is kept pressed, time will changes quickly.
Every time the button is pressed, time decreases 10 minuts.If the button is kept pressed ,time will changes quickly.It can be adjusted within 24 hours at will.AM refers to morning and PM refers to afternoon.
OFF
FRESH
HIGH/SOTIMER
SET
FILTER
A
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ONOFFSWING
MODE
CLOCK
CODE LIGHT
OFF
1
3 654
2
ON OFF ON OFFAM12:00 AM12:00PM 12:00 PM 12:00
TIMER ON TIMER OFF TIMER ON-OFF
blank
After the air conditioner has operated for a certain period, dust hasaccumulated on the filter, and the filter up/down function can be usedto clean it.
1.Whether unit starts or stops, continuously press FILTER button for 3 seconds, and enter the filter up/down waiting status (when unit stops, the yellow TIMER indicator flashes, and filter and clock indication are displayed on the remote controller. Only the FILTER button, the temperature buttons " " " " and time buttons are active).
2.Press temperature button or time button in filter up/down waiting status: the up/down mechanism makes the filter moving downward and does not stop until it has reached the maximum limit.
3.Press temperature button or time button in filter up/down waiting status: the up/down mechanism makes the filter to moving upward till near the surface board and then automatically adjusts it to reset (when adjusting to reset, it will not be controlled by the remote controller till the adju- stment is finished).
4.During moving downward, press temperature button or time button: moving stops.
5.During moving downward, press temperature button or time button: moving stops.
6.Continuously press FILTER button 3 seconds again to cancel the filter up/down waiting mode (unit stops, the yellow timer indicator stops flashing, the filter goes back to the original position, the remote controller goes back to off status and only clock is displayed).
Note:If the filter does not thoroughly go back to the original position, only needs tooperate several times repeatedly.
Filter Up/Down
" "
" "
" "
" "
" "
" "" "
" "
(Only for AB182ACBEA)
FRESH
HIGH/SOTIMER
SET
FILTER
A
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ONOFFSWING
MODE
CLOCK
CODE LIGHT1
Press the HIGH/SO button twice
NOTICE:When the air conditioner is operating in " High Mode " , unevenness of room air temperaturemay occur due to the intensive operation in a short time.Anyway, operation in "High Mode", does not last for more than 15 minutes, then regularoperation is automatically restored.
" High mode " Operation
If the button is pressed once, the indication is displayedon the remote controller. If you press the button once again,the indication disappears, regular operation is restored and fanspeed goes back to the mode set before "High Mode" operation.
Press the HIGH/SO button noceThe indication appears on the display of the remotecontroller and operation in "High Mode" starts.The AUTO fan speed is automatically set and the correspondingindication is also displayed.
Outline of operation in "High Mode"This function is suitable when the set temperature must bereached in the shortest delay.The button "HIGH/SO", referred to this function, is effectivein Cooling/Heating mode (not in Auto/Dry/Fan modes).
ON
OFF
FRESH
HIGH/SOTIMER
SET
FILTER
A
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ONOFFSWING
MODE
CLOCK
CODE LIGHT
AUTO
1
Press the HIGH/SO button twice
NOTICE:When the air conditioner is operating in " High Mode " , unevenness of room air temperaturemay occur due to the intensive operation in a short time.Anyway, operation in "High Mode", does not last for more than 15 minutes, then regularoperation is automatically restored.
" Soft mode " Operation
If the button is pressed once, the indication is disappearsfrom the remote controller's display. If you press the buttononce again, regular operation is restored and fan speed goesback to the mode set before "Soft Mode" operation.
Press the HIGH/SO button twiceThe indication appears on the display of the remotecontroller and operation in "Soft Mode" starts.The AUTO fan speed is automatically set and the correspondingindication is also displayed.
Outline of operation in "Soft Mode"Operation in "Soft Mode", more silent, is suitable when noisesshould be reduced, e.g.. for reading or sleeping.The button "HIGH/SO", referred to this operation, is effectivein Cooling/Heating mode (not in Auto/Dry/Fan modes).
ON
OFF
FRESH
HIGH/SOTIMER
SET
FILTER
A
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ONOFFSWING
MODE
CLOCK
CODE LIGHT
OFF
AUTO
1
Auto restart function setting
Setting method (to be applied for a necessary situation) :
Setting Method: When the remote controller is on (excluding timer mode and fan mode), press the "Sleeping" button on the remote controller 10 times within 5 seconds, and after the buzzer rings 4 times, the air conditioner will enter the state of power failure compensation.
Cancel Method: Press the "Sleeping" button on the remote controller 10 times within 5 seconds, and after the buzzer rings 2 timer, the power failure compensation mode will be cancelled.
Notes: When a power failure suddenly occurs during the air conditioner is working after the powerfailure compensation is set, if the air conditioner will not be used for a long time, please cut off thepower supply to prevent its operation from being resumed after the power is supplied again, or pressthe "Switch On/Off" button after the power comes again.
After the power failure compensation is set, if power failure suddenly occurs while the air conditioneris working, it will resume the previous working state when the power is supplied again.
FRESH
HIGH/SOTIMER
SET
FILTER
A
HEALTH
RESET LOCK
SLEEP
FAN
TEMP
ONOFFSWING
MODE
CLOCK
CODE LIGHT
AUTO
C
HEALTH
SET RECOVERY
CHECK
F
Cautions:On cooling only unit, heatingmode is not available.
Note:The above information is the explanation ofthe displayed information therefore varieswith those displayed in actual operation.
CLOCKUsed to adjust time.
TIMERUsed to set timermode.
stands for time plus/minus,used to adjust time.
Used for unit start andstop.
POWER ON/OFF
MODE
Used for selectindoor operationmode.
FAN SPEED
Used for select indoorair flow.
HEALTHUsed for settingindoor healthfunction.
TEMP + -
Used for changingset temperature.
RECOVERYused to switchover air-exchanging mode.
SWING
Used for sett ingindoor swing mode.
Auto-diagnost icbutton.
Filter-cleaned button.
FILTER
RESETReset correctmode button.
Wired controller functions:
CHECK
+ -
Buttons and functions of the wired controller
Buttons function: MODE:used for select indoor operation mode. FAN:used for select indoor air flow. SWING:used for setting indoor swing mode. HEALTH:used for setting indoor health function. TEMP + -:used for changing set temperature. CLOCK:used to adjust time. +、-:stands for time plus/minus, used to adjust time. TIMER:used to set timer mode. RECOVERY:used to switch over air-exchanging mode. CHECK:auto-diagnostic button. FILTER:filter-cleaned button.
RESET:reset correct mode button. Display description:
[MODE] [AUTO]:auto operation mode [MODE] [FAN ONLY]:air-throwing mode [MODE] [COOL]:Cooling operation mode [MODE] [DRY]:Dehumidification mode [MODE] [HEAT]:Heating operation mode [MODE] [HEAT] [TES]:In heating mode, auxiliary electric heater is running. Only when the
unit with auxiliary electric heater is in auxiliary electric heating mode, it will display. [FAN] [AUTO]:auto fan running
[FAN] [HIGH]:high fan speed [FAN] [MED]: medium fan speed [FAN] [LOW]: low fan speed [FAN] [FIX]: fixed fan speed, it will display only when fixed fan speed is requested to main
indoor unit. [CENTRAL]: central control mode [OPERATION] :running mode [STAND BY] : waiting mode [PRE-HEAT] : pre-heating mode [DEFROST]: defrosting mode [FILTER] : request of filter to be cleaned [HEALTH]:health function [UNIT NO.] [CEN.ADD]:central control address, the address number will display on “88” [SYS.ADD.]:system address, the address number will display on “88” [CHECK]:auto-diagnostic, trouble shooting [DEMAND]:compulsory operation function, when it works, [CENTRAL] will flash [SWING]:swing mode [ROOM TEMP.]:indoor ambient temperature [SET TEMP.]:set admired temperature [TIMER][ON] :timer function is on, it will switch over in the sequence below:
[ON][OFF] → [ON][OFF][DAILY] →[ ] [TIMER][OFF] :timer function is off [TIMER][ON][OFF] :timer function ON-OFF [TIMER][ON][OFF][DAILY]:timer ON-OFF will switch over in turn daily [CLOCK]:clock display, the displaying time is the current time of the clock. [UP]、[DOWN]:indicator of filter elevating [VENTILATION][AUTO]:auto ventilation mode [VENTILATION][RECOVERY]:fully heat exchanging ventilation mode [VENTILATION][NORMAL]:normal ventilation mode FAN ONLY OPERATION: 1)Start up operation: press the button of ON/OFF, the system will start up, and will display [MODE][AUTO];[FAN][AUTO];[ROOM TEMP.]+“24℃”;[CLOCK]+”12:00”. 2) Select MODE: press the MODE button, then you will see in the display section [MODE]
switch over in below sequence:[FAN ONLY]→[COOL]→[DRY]→[HEAT]→[AUTO]→[FAN ONLY]. Select [FAN ONLY].
3)Select fan speed: press FAN button, then you see in the display section [FAN] switch over in below sequence: [HIGH]→[MED]→[LOW]→[HIGH]. Select proper fan speed. 4)Power off: press ON/OFF button, indoor unit will be powered off, there are only time and the ambient temperature in the screen.
AUTO operation, COOLING, HEATING and DEHUMIDIFICATION operation 1) Start up operation: press the button of ON/OFF, the system will start up, and will display [MODE][AUTO];[FAN][AUTO];[ROOM TEMP.]+“24℃”;[CLOCK]+”12:00”. 2) Select MODE: press the MODE button, then you will see in the display section [MODE] switch over in below sequence:[FAN ONLY]→[COOL]→[DRY]→[HEAT]→[AUTO]→[FAN ONLY]. Select [FAN ONLY]. 3) Change set temperature: press TEMP + or – every time, [SET] will display, and set temperature will increase/reduce 1℃(F). 4) Select fan speed: press FAN button, then you see in the display section [FAN] switch over in below sequence: [HIGH]→[MED]→[LOW]→[HIGH]. Select proper fan speed. 5) Select [SWING]: press [SWING] button, swing function is valid. Press again, swing
function is invalid. 6) Set [HEALTH]: used to set the indoor health function. Press it once, [HEALTH] will display in the display section, then indoor health function is valid. Press it again, [HEALTH] will disappear, then the health function is invalid. This function is valid only for the unit with health function. 7) Power off: press ON/OFF button, indoor unit is powered off. There are only time and the ambient temperature in the screen. Set TIMER operation: Adjust clock: when powered on, for the first time to set timer function, the clock will be adjusted. Press “CLOCK” button, and set the current clock. Now, “CLOCK” will flash at the frequency of 2Hz every minute. Press the clock +/- button; the current clock can be adjusted. Until the proper time comes, press [SET]. TIMER ON operation: Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] →[ ]. Select [TIMER] [ON], then [TIMER] [ON] flashes, press the clock +/- button to adjust the time of TIMER ON, press [SET] button. TIMER OFF operation: Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] →[ ]. Select [TIMER] [OFF], then [TIMER] [OFF] flashes, press the clock +/- button to adjust the time of TIMER OFF, press [SET] button. TIMER ON-OFF operation: Press TIMER button, and keep pressing it, in the display section [TIMER] will switch over in below sequence: [ON]→[OFF]→[ON][OFF] → [ON][OFF][DAILY] →[ ]. Select [TIMER] [ON] [OFF]. Firstly, [TIMER][ON] flashes, press the clock +/- button to adjust the time of
TIMER ON, press [TIMER]. [TIMER][ON] will be constant on. Then [TIMER] [OFF] flashes, press the clock +/- button to adjust the time of TIMER OFF, press [SET]. The time sequence of timer on and timer off will determine the mode is [TIMER] [ON] →[OFF] or [TIMER] [OFF] →[ON]. If you want the current time, press [CLOCK] once, current time will display; press again, [CLOCK] will flash, and press [+][-] to adjust the time. Note: 1. If the two times are same, the timer state which is set later will flash, in this case, timer can not be set. 2. When entering TIMER setting state, if you do not input any button in continuous 10 seconds, the unit will quit from the TIMER mode. Cancel TIMER operation: In the timer operation state, press [TIMER] button, the unit will quit from the current timer operation state, and the set data will be memorized, then enter the next timer mode. [FILTER] function When the wired controller receives the filter-cleaned signal from indoor unit, [FILTER] will display. After finishing clean, press [FILTER], the sign [FILTER] disappears, and the controller will send the filter reset signal to indoor unit. When the sign [FILTER] not display, it is invalid to press [FILTER] in short time. FILTER ELEVATING function: (only for the unit with elevating function) When the filter needs to be cleaned, the panel can be lowered to the admired height by the [FILTER][UP][DOWN] function. Method is below: In power off state, press [HEALTH] for 15 seconds to enter filter elevating set state. In this state, the sign [FILTER] will flash and [UP] [DOWN] will display simultaneously, Press TEMP [+], in timer section [UP] will display, while press TEMP [-], in timer section [DOWN] will display. When it arrives the appropriate position, press [UP], [UP][DOWN] will display simultaneously, filter will stop going down. Press [UP] again, filter will go up. Press [FILTER] button to quit the mode. DEMAND operation function: By this function, all the indoor units can be made in nominal mode. Set the operation mode in cooling and then shut off the unit. In the stop state, press [ON/OFF] button for 5 seconds to enter cooling trial operation state. If it is in heating mode before shut off the unit, then press [ON/OFF] button for 5 minutes, it will enter heating trial operation state. In cooling, there will be “LL” in the position where the set temperature displays. In heating, there will be “HH” in the position where the set temperature displays. The wired controller will send the [DEMAND] signal to indoor unit. In the [DEMAND] operation, “COOL” or “HEAT” will display at 1Hz frequency. Indoor fan motor will be fixed at “AUTO” mode. The indoor units in the same group will quit the [DEMAND] in turn. At this time, only the buttons of [ON/OFF] and temperature [+] [-] are valid. Press [ON/OFF] to quit [DEMAND] mode.
CENTRAL control function When the central controller selects [CENTRAL] mode, the buttons in the wired controller except for [CHECK] will be invalid. VENTILATION mode (only for the unit with fresh air function or heat recovery function) Press [RECOVERY] button, then the unit will switch over the ventilation mode: [ ] → [VENTILATION][AUTO] → [VENTILATION][RECOVERY] → [VENTALATION][NORMAL] →[ ], please select appropriate ventilation mode. Query indoor malfunction history: In the state of power on or power off, press [CHECK] button, enter the malfunction-querying mode of all indoor units in the group. Then [CHECK] and [UNIT NO.] will display, and the actual indoor numbers will be displayed in some sequence (unit number is in decimals). At the same time, in the time region, there will be the current malfunction and the latest time malfunction, the displaying format is [XX:YY], in which XX stands for the current malfunction, if normal, it will display “――”; YY stands for the latest time malfunction. The failure code of every unit will display for 3 seconds. After the failure codes of all indoor units in the whole group are displayed, the mode will quit automatically. Clear abnormal state and malfunction history: In normal state, press [CHECK] button for 5 seconds to clear abnormal states, at the same time, wired controller will send the data of “clear abnormal state”, but the malfunction history still retains. In normal state, press [CHECK] button for 15 seconds, except for malfunction states, the malfunction history in wired controller will be cleared. Query indoor performance state: In normal state, press both buttons of [CHECK] and [FILTER] for 5 seconds, in the set temperature region in the screen, [XX] will display, XX is indoor number, which can be selected by pressing [TEMP] [+] [-]. In the timer region in the screen, [YZZZ] will display, in which Y stands for data type, ZZZ stands for the corresponding data. which can be selected by pressing [CLOCK] [+] [-].
Y ZZZ Type A Indoor capacity (W) Nominal cooling
capacity/10, decimal B Request of indoor capacity(Hz) Actual value, decimal C Temperature of indoor ambient
temp. sensor TA Actual value, decimal
d Temperature of indoor gas pipe sensor TC1
Actual value, decimal
E Temperature of indoor liquid pipe sensor TC2
Actual value, decimal
F Open degree of indoor PMV Actual value, decimal
g Preset ――― H Outdoor total capacity Actual value, decimal
In check mode, press [CHECK] to quit the check mode, and go into normal running mode.
How to change the function switches? No. Type State of
switch Function description
Connected Central controller J01 Changeover of Wired controller and central controller
Cut off Wired controller
Connected Set as simple controller J02 Changeover of type of wired controller Cut off Set as standard controller
Connected Use the sensor in the wired controller
J06 Selection of room temp. sensor
Cut off Use the sensor in the indoor unit Connected Common control J07 Auto restart after power
failure Cut off Auto restart after power failure Connected Yes J03 Display of room
temperature Cut off No ON Set as slave controller SW01
① Changeover of master or slave controller OFF Set as master controller
ON ℉ SW01②
℃ or ℉ OFF ℃ Connected Indoor unit in shorted time
function D1 Shorten time function
Cut off Common control Connected Send compulsorily defrost signal
to indoor unit D2 Compulsorily defrost
Cut off Common control Note: 1. The switches in grey can be operated after opening the cover of wired controller. 2. Switches or jumper wire must be adjusted when the wired controller is powered off. If the wired controller is powered on, the above operations will be invalid. 3. Shorten time function In normal operation, D1 is in short circuit, it will enter shorten time mode, and the time will be shortened in the proportion of 60:1. In shorten time mode, LED will flash at the frequency of 0.5 second. Cut off D1, it will quit the shorten time mode and return to the normal operation mode. 4. Compulsorily defrost In heating mode, D2 is in short circuit, it will enter compulsorily defrost mode; cut off D2, it will quit. 5. Lock function There is no lock function only in the wired controller. But when it is connected with a central
controller, if the central controller is set to “central”, the buttons in the wired controller will be invalid, or the buttons will be valid. Failure code:
For remote type, flash times
Failure code on
wired controller
For central control, failure code
Failure description Reason Remarks
10 08(08H) 21D Drainage system abnormal
Float switch broken down for more than 25m continuously
○
1 01(01H) 01D Indoor ambient temp. sensor failure
sensor broken down or short circuit for more than 2m continuously
○
2 02(02H) 02D Indoor coil temp. sensor failure
sensor broken down or short circuit for more than 2m continuously
○
3 74(4AH) 11D Outdoor ambient temp. sensor failure
sensor broken down or short circuit for more than 2m continuously
○
4 73(49H) 12D Outdoor coil temp. sensor failure (compressor discharging temp. sensor)
Sensor broken down or short circuit for more than 2m continuously
○
5 72(48H) 10D Over-current protection
CT check abnormal 3 times in 30m
※
6 83(53H) 14D High pressure abnormal
High pressure switch acts 3 times in 30m
※
7 71(47H) 22D Power supply abnormal
Fault phase, short of phase, out of balance greatly
※
8 07(07H) 06D Communication between wired controller and indoor abnormal
Communication abnormal for more than 4m continuously
○
9 06(06H) 05D Communication between indoor and outdoor abnormal
Communication abnormal for more than 4m continuously
○
11 11(0BH) 30D Outside alarm signal input
Outside signal broken down for more than 10s
○
12 03(03H) 20D Gas pipe temp. sensor abnormal
Sensor broken down or short circuit for more than
○
2m continuously 13 13(0DH) 31D Solenoid valve
abnormal Solenoid valve act incorrectly 3 times continuously
○
14 76(4CH) 15D Discharging temp. sensor abnormal
Sensor broken down or short circuit for more than 2m continuously
○
15 05(05H) 17D EEPROM abnormal EEPROM data missing Run as the default value
16 84(54H) 26D Pressure abnormal(low pressure)
Low pressure switch acts in normal running
○
17 80(50H) 15D Compressor overheat the discharging temperature is higher than 120degree
Resumable if lower than 100degree
18 12(0CH) 23D Abnormal mode Indoor operation mode is different with the running indoor unit.
○
19 75(4BH) 18D Outdoor coil B(suction temp sensor—for MRV II)
Sensor broken down or short circuit for more than 2m continuously
○
20 77(4DH) 15D Outdoor discharging B(oil temp sensor—for MRV II)
Sensor broken down or short circuit for more than 2m continuously
○
○ shows resumable fault, ※ shows it is not resumable fault. Setting address method: The address setting can be realized by setting indoor PCB. If you use the group control function, there should be a master unit and 15 sets of slave units. For the master unit, the SW5-3 should be at “1”. For the slave units, the SW5-3 should be at “0”. Please refer the below table, Indoor
unit address
SW1-4 SW1-3 SW1-2 SW1-1
1 OFF OFF OFF OFF 2 OFF OFF OFF ON 3 OFF OFF ON OFF 4 OFF OFF ON ON 5 OFF ON OFF OFF 6 OFF ON OFF ON 7 OFF ON ON OFF
8 OFF ON ON ON 9 ON OFF OFF OFF 10 ON OFF OFF ON 11 ON OFF ON OFF 12 ON OFF ON ON 13 ON ON OFF OFF 14 ON ON OFF ON 15 ON ON ON OFF 16 ON ON ON ON
If you use central control type, SW1, SW2 will be used simultaneously. Wiring request in central control type: port A-B is connected with indoor port CN16(A-B)through 2-core shield wire. Requirements: 1. Port A connects with port CN16(A)of all indoor units. 2. Port B connects with port CN16(B)of all indoor units. Address on central controller
Indoor unit address
SW2-3 SW2-2 SW2-1 SW1-4 SW1-3 SW1-2 SW1-1
1 1 ON OFF OFF OFF OFF OFF OFF 2 2 ON OFF OFF OFF OFF OFF ON 3 3 ON OFF OFF OFF OFF ON OFF 4 4 ON OFF OFF OFF OFF ON ON 5 5 ON OFF OFF OFF ON OFF OFF 6 6 ON OFF OFF OFF ON OFF ON 7 7 ON OFF OFF OFF ON ON OFF 8 8 ON OFF OFF OFF ON ON ON 9 9 ON OFF OFF ON OFF OFF OFF 10 10 ON OFF OFF ON OFF OFF ON 11 11 ON OFF OFF ON OFF ON OFF 12 12 ON OFF OFF ON OFF ON ON 13 13 ON OFF OFF ON ON OFF OFF 14 14 ON OFF OFF ON ON OFF ON 15 15 ON OFF OFF ON ON ON OFF 16 16 ON OFF OFF ON ON ON ON 17 -------- ON OFF ON OFF OFF OFF OFF 18 -------- ON OFF ON OFF OFF OFF ON 19 -------- ON OFF ON OFF OFF ON OFF 20 -------- ON OFF ON OFF OFF ON ON 21 -------- ON OFF ON OFF ON OFF OFF 22 -------- ON OFF ON OFF ON OFF ON 23 -------- ON OFF ON OFF ON ON OFF 24 -------- ON OFF ON OFF ON ON ON 25 -------- ON OFF ON ON OFF OFF OFF
26 -------- ON OFF ON ON OFF OFF ON 27 -------- ON OFF ON ON OFF ON OFF 28 -------- ON OFF ON ON OFF ON ON 29 -------- ON OFF ON ON ON OFF OFF 30 -------- ON OFF ON ON ON OFF ON 31 -------- ON OFF ON ON ON ON OFF 32 -------- ON OFF ON ON ON ON ON 33 -------- ON ON OFF OFF OFF OFF OFF 34 -------- ON ON OFF OFF OFF OFF ON 35 -------- ON ON OFF OFF OFF ON OFF 36 -------- ON ON OFF OFF OFF ON ON 37 -------- ON ON OFF OFF ON OFF OFF 38 -------- ON ON OFF OFF ON OFF ON 39 -------- ON ON OFF OFF ON ON OFF 40 -------- ON ON OFF OFF ON ON ON 41 -------- ON ON OFF ON OFF OFF OFF 42 -------- ON ON OFF ON OFF OFF ON 43 -------- ON ON OFF ON OFF ON OFF 44 -------- ON ON OFF ON OFF ON ON 45 -------- ON ON OFF ON ON OFF OFF 46 -------- ON ON OFF ON ON OFF ON 47 -------- ON ON OFF ON ON ON OFF 48 -------- ON ON OFF ON ON ON ON 49 -------- ON ON ON OFF OFF OFF OFF 50 -------- ON ON ON OFF OFF OFF ON 51 -------- ON ON ON OFF OFF ON OFF 52 -------- ON ON ON OFF OFF ON ON 53 -------- ON ON ON OFF ON OFF OFF 54 -------- ON ON ON OFF ON OFF ON 55 -------- ON ON ON OFF ON ON OFF 56 -------- ON ON ON OFF ON ON ON 57 -------- ON ON ON ON OFF OFF OFF 58 -------- ON ON ON ON OFF OFF ON 59 -------- ON ON ON ON OFF ON OFF 60 -------- ON ON ON ON OFF ON ON 61 -------- ON ON ON ON ON OFF OFF 62 -------- ON ON ON ON ON OFF ON 63 -------- ON ON ON ON ON ON OFF 64 -------- ON ON ON ON ON ON ON 65 -------- ON OFF OFF OFF OFF OFF OFF 66 -------- ON OFF OFF OFF OFF OFF ON 67 -------- ON OFF OFF OFF OFF ON OFF -------- ON OFF OFF OFF OFF ON ON
-------- ON OFF OFF OFF ON OFF OFF -------- ON OFF OFF OFF ON OFF ON -------- ON OFF OFF OFF ON ON OFF -------- ON OFF OFF OFF ON ON ON -------- ON OFF OFF ON OFF OFF OFF -------- ON OFF OFF ON OFF OFF ON -------- ON OFF OFF ON OFF ON OFF -------- ON OFF OFF ON OFF ON ON -------- ON OFF OFF ON ON OFF OFF -------- ON OFF OFF ON ON OFF ON -------- ON OFF OFF ON ON ON OFF -------- ON OFF OFF ON ON ON ON -------- ON OFF ON OFF OFF OFF OFF -------- ON OFF ON OFF OFF OFF ON -------- ON OFF ON OFF OFF ON OFF -------- ON OFF ON OFF OFF ON ON -------- ON OFF ON OFF ON OFF OFF -------- ON OFF ON OFF ON OFF ON -------- ON OFF ON OFF ON ON OFF -------- ON OFF ON OFF ON ON ON -------- ON OFF ON ON OFF OFF OFF -------- ON OFF ON ON OFF OFF ON -------- ON OFF ON ON OFF ON OFF -------- ON OFF ON ON OFF ON ON -------- ON OFF ON ON ON OFF OFF -------- ON OFF ON ON ON OFF ON -------- ON OFF ON ON ON ON OFF -------- ON OFF ON ON ON ON ON -------- ON ON OFF OFF OFF OFF OFF -------- ON ON OFF OFF OFF OFF ON -------- ON ON OFF OFF OFF ON OFF -------- ON ON OFF OFF OFF ON ON -------- ON ON OFF OFF ON OFF OFF -------- ON ON OFF OFF ON OFF ON -------- ON ON OFF OFF ON ON OFF -------- ON ON OFF OFF ON ON ON -------- ON ON OFF ON OFF OFF OFF -------- ON ON OFF ON OFF OFF ON -------- ON ON OFF ON OFF ON OFF -------- ON ON OFF ON OFF ON ON -------- ON ON OFF ON ON OFF OFF -------- ON ON OFF ON ON OFF ON -------- ON ON OFF ON ON ON OFF
-------- ON ON OFF ON ON ON ON -------- ON ON ON OFF OFF OFF OFF -------- ON ON ON OFF OFF OFF ON -------- ON ON ON OFF OFF ON OFF -------- ON ON ON OFF OFF ON ON -------- ON ON ON OFF ON OFF OFF -------- ON ON ON OFF ON OFF ON -------- ON ON ON OFF ON ON OFF -------- ON ON ON OFF ON ON ON -------- ON ON ON ON OFF OFF OFF -------- ON ON ON ON OFF OFF ON -------- ON ON ON ON OFF ON OFF -------- ON ON ON ON OFF ON ON -------- ON ON ON ON ON OFF OFF -------- ON ON ON ON ON OFF ON -------- ON ON ON ON ON ON OFF 128 -------- ON ON ON ON ON ON ON
Electrical functions of wired controller:
1.Function difference between master wired controller and slave one: Contrastive items Master wired controller Slave wired controller Function All of functions Only with below functions:
ON/OFF, MODE, FAN SPEED, SET TEMP., SWING
2. Wiring connections of wired controller:
indoor N
BA C
wired controller
indoor 1 indoor 2
indoor 1
21 3
A B C A B C
indoor 16
control wiring of wired controller, polar.
indoor 15
1 2 3
A B C
wired controller wired controller wired controller
wired controller wired controller
wired controller
wired controller
indoor 1
wired controller wired controller wired controller
A
B C
(master unit)
polar wirepolar wire
polar wire
There are three methods to connection wired controller and the indoor units: A. One wired controller can control max. up to 16 sets of indoor units, and 3 pieces of polar wire must connect the wired controller and the master unit (the indoor unit connected with wired controller directly), the others connect with the master unit through 2 pieces of polar wire.
B. One wired controller controls one indoor unit, and the indoor unit connects with the wired controller through 3 pieces of polar wire. C. Two wired controllers control one indoor unit. The wired controller connected with indoor unit is called master one, the other is called slave one. Master wired controller and indoor unit; master and slave wired controllers are all connected through 3 pieces of polar wire. 3. Communication wiring: The wired controller is equipped with special communication wiring in the accessories. 3-core terminal (1-white 2-yellow 3-red) is connected with the terminal A、B、C of wired controller respectively. The communication wiring is 4 meter long; if the actual length is more than it, please distribute wiring according to below table:
Communication wiring length(m) Dimensions of wiring <100 0.3mm2X3-core shielded wire ≥100 and <200 0.5mm2X3-core shielded wire ≥200 and <300 0.75mm2X3-core shielded wire ≥300 and <400 1.25mm2X3-core shielded wire ≥400 and <600 2mm2X3-core shielded wire
※ One side of the shielded sheet of communication wire must be earthed.
8.Refrigerant Diagram
Heating operation
Cooling operation
air-liquid departor
compressor
4-way vavle
Outdoor unit
muffler one way vavle
heat exchanger of indoor unit
Indoor unit
-44-
9.Electrical Control Functions Flow Chart for Operation 1) Turn on/off unit
On/off
Trouble
Mode determinati
Heating operation
Cooling operation
Fan motor turn off,electronic expansionvalve close, louvermotor turn off
Dehumidifying operation
A
Power indicator turn off,operation indicator turnoff
Trouble indication
Abnormal operation
Chose mode
Buzzer sound twice, refuse to receive signal
No
Ye
Off
YeOn
Off
Control function treat module
-45-
2) Cooling operation
Electronic expansion valve:overheat control,Swing flap:cooling standard position,Fan motor: rated speed
Close
Open
No
No Yes
Yes
No
Yes
Electronic expansion valve:close, send turning off unitsignal to outdoor unit
According to the state of thermostat
Electronic expansion valve:overheat control, sendturning on unit signal to
Emergency
Electronic expansion valve:overheat control,Swing flap:cooling standard position,Fan motor: auto
Electronic expansion valve:overheat control,Swing flap:cooling standard position,Fan motor: high speed
Rated operation
Test
No
Yes
Yes
No
Adjust fan speedaccording totemperature set and in
Operate in fanspeed set
Automatic fan speed
Swing action
Swing flap in the cooling standard position
Swing
Cooling
-46-
Note: ① When abnormal phenomenon occur, the indoor unit indicator will indicate abnormality according to the abnormal parts. ② When temperature of the evaporator inlet is lower than 0℃ and keeps for 5 minutes, unit will operate in anti-icing mode. 3)Dehumidifying operation
-47-
SwingNo
Swing flap in the coolingstandard position
Swing action
If enter coolingoperation
Adjust fan speed according to temperature set and in
Yes
Yes
No
Anti-defrosting n
Yes
No
Yes
No
Determine if dehumidifyaccording to airtemperature
Send indoor unit Operation State to outdoor unit
Electronic expansion valve totally open
Electronic expansion valves open, indoor unit fan motor weak wind
Electronic expansionvalves open, indoor unitfan motor weak wind
A
Dehumidifying
4) Heating operation
-48-
or unit
Heating operation
No Swing flap in set fanspeed position
SwingYes
Swing action
On side: wind off,expansion valve steadyOff side: Electronicexpansion valve totallyopen
Yes Defrosting
No No Rated
According to temperature sensor to adjust state and valve open degree
Fan motor operate in rated fan speed
Yes
If stop unit protection
Overload protection
No Yes No (not rated
Electronic expansion valve close
Auto fan
Yes
Operate in set fan speed
According to room temp and settemp to determine fan speed
Protect according to temperature difference section value
Send indoor unit Operation State to outdo
A
10. Diagnostic information10.1 Failure coderemote control type unit:
failure description indoor runninglamp flash times
indoor ambient temp. sensor failure 1indoor coil temp.sensor failure 2outdoor ambient temp. sensor failureor 4-way valve broken down in heating mode
3
outdoor coil temp. sensor failure 4over-current protection failure or phase sequence fault 5refrigerant system pressure too high or low 6communication between indoor PCB and receiver panel failure 8communication between indoor PCB and outdoor PCB 9drainage failure 10Note: For convertible type unit, drainage failure is not available.
Wired control type unit failure code:
Failure description Failure code on wired controller
Indoor ambient temp. sensor abnormal E1 Indoor coil temp. sensor abnormal E2 Outdoor ambient temp. sensor abnormal E3 Outdoor coil temp. sensor abnormal E4 Over current protection E5 Over high or low pressure protection E6 Communication between panel and indoor abnormal
E8
Communication between indoor and outdoor abnormal
E9
Water pump failure E0
Failure code with wired controller YR-E12: For
remote
type, flash
times
Failure
code on
wired
controller
For central
control,
failure code
Failure description Reason
10 08 21 Drainage system failure Float switch broken down for more than
25m continuously
1 01 01 Indoor ambient temp. sensor
failure
sensor broken down or short circuit for
more than 2m continuously
2 02 02 Indoor coil temp. sensor failure sensor broken down or short circuit for
more than 2m continuously
3 4A 11 Outdoor ambient temp. sensor
failure
sensor broken down or short circuit for
more than 2m continuously
4 49 12 Outdoor coil temp. sensor
failure (compressor
discharging temp. sensor)
Sensor broken down or short circuit for
more than 2m continuously
5 48 10 Over-current protection CT check abnormal 3 times in 30m
6 53 14 High pressure abnormal High pressure switch acts 3 times in 30m
8 07 06 Communication between wired
controller and indoor abnormal
Communication abnormal for more than
4m continuously
9 06 05 Communication between
indoor and outdoor abnormal
Communication abnormal for more than
4m continuously
11 0B 30 Outside alarm signal input Outside signal broken down for more than
10s
12 03 20 Gas pipe temp. sensor
abnormal
Sensor broken down or short circuit for
more than 2m continuously
13 0D 31 Solenoid valve abnormal Solenoid valve act incorrectly 3 times
continuously
15 05 17 EEPROM abnormal EEPROM data missing
10.2 Trouble Shooting - Detailed for engineer Malfunction flow chart: analyze and diagnose If the air-condition fails to cooling or heating function and other functions, please check
the system as follows:
1.Cooling
Y
change the designed TEMP.
replacing compressor
superaddition condensate
clear the filter
enact fan speed of high or middle speed
airiness circle improperly
heat insulation of condensate pipeline between indoor unit and outdoor unit is normal
N
N
compressor fault
quantity of condensate charge is not enough
fan speed at low-speed
air entrance filter obstruct
Y
Y
Y
Y
condensate flowage failure
fails in cooling
begining
N
N
fault in 4-way vavle
the cooling load beyond the allowable arange
the enactment TEMP. right or not
Y
Y
Y
insulate the two pipeline respective
redesign the TEMP.
change the 4-way vavle
use arange is right or not
Y
Figure 7-1
-50-
2. Heating
Y
change the designed TEMP.
replacing compressor
superaddition condensate
clear the filter
enact fan speed of high or middle speed
airiness circle improperly
heat insulation of condensate pipeline between indoor unit and outdoor unit is normal
N
N
compressor fault
quantity of condensate charge is not enough
fan speed at low-speed
air entrance filter obstruct
Y
Y
Y
Y
condensate flowage failure
fails in heating
begining
N
N
fault in 4-way vavle
the heating load beyond the allowable arange
the enactment TEMP. right or not
Y
Y
Y
insulate the two pipeline respective
redesign the TEMP.
change the 4-way vavle
use arange is right or not
Y
blowing cold air fault in 4-way vavlereplacing the 4-way vavle
Y
prevent cold air failure
pipe sensor of indoor unit is fault
replacing the 4-way vavle
Y
Figure 7-2
-51-
3 Malfunction and Solution of Wired controller 1) There is nothing on display of wire control organ, and the air-conditioner failure to
operate
if the diode on indoor unit is lumines
if there's voltage on the primary side of tranaformer
if the fuse of indoor unit PCB.is normal
if the primary side of power supply transformer is short
replacing the transformer
check the port row of power supply
if the transform of PCB.socket is normal
replacing the transformer
redo the connection work
if power supply and communication line are connected correctly
replacing the PCB. of indoor unit
if there'e DC 12V between the four ports:A,B,C and D which on wire control organ
begining
Y
Y
if there's AC 220V of power suplay on PCB. of indoor unit
Y
repacing the wire control organ
Y
N
Y
Y
Y
N
NY
NN
if there's AC 15V on transformer subside of indoor unit PCB.
N
Y
Figure 7-3
-52-
2) The wire control organ displays the alarm signal with “E0” “E0” means the floater switch of indoor unit is abnormal
replacing the switch
if the function of the floater is normal
if the floater swith is orientated correctly
the alarm signal of wire control organ is E0
begining
amend the oritation of the floater switch
N
Y
N
Figure 7-4
3) The wire control organ displays the alarm signal with “E1”
“E1” means indoor ambient temperature sensor is abnormal
amend the position of the sensor
if the indoor ambient sensor is orientated correctly
replacing the sensor
N
if the resistance of sensor is right
Y
N
wire control organ displays the alarm signal with E1
begining
Figure 7-5
Notation: The resistance of indoor ambient sensor is 23K
-53-
4) The wire control organ displays the alarm signal with “E2” “E2” means indoor piping temperature sensor is abnormal
the alarm signal of wire control organ is E2
replacing the sensor
if the resistance of the sensor is right
N
Y
amend the position of sensor
N
begining
if the position of piping Temp.sensor is right
Figure 7-6 Notation: The resistance of piping temperature sensor is 10K 8) The wire control organ displays the alarm signal with “E8” “E8” means malfunction of communication between control panel and indoor units
if the potrs A and B,or C and D are short
replacing the wire control organ
connect the wire correctly
if the four ports on wire control connected correspondingwith the port on PCB of indoor unit
if the ports:A,B,C and D are connected well
if the wire control organ can matches the PCB of indoor units
begining
connect the wire correctly
connect the wire correctly
N
Y
Y
Y
N
N
N
Figure 7-7
-54-
11. Electrical Data 11.1 Wiring Diagram 11.1.1 Outdoor unit
2. Dashed parts is optional for Low Ambient Temp. Cooling,and there is no relay in only Cooling type
NOTE:1. Dashed parts is not available for only Cooling type
single phase outdoor wiring diagram
3. Dashed parts is optional for Low Ambient Temp. Cooling,and there is no relay in only Cooling type
2. Dashed parts are not available for only Cooling type
NOTE:1. Dashed parts is not available for Cooling capacity below 42000Btu/h
3-phase outdoor wiring diagram
11.1.2 Indoor unit
NOTE:1. Dashed parts are not availble in convertible type2. Dashes part is not avaliable below Cooling capacity 42000Btu type3. Remote central controller is optional4. P16 and P17 are used for room card function
over 24000BTU/h convertible type wiring diagram
NOTE:1. Parts in dashed frame are not available for cassette type unit2. Central controller is optional3. P16 and P17 are used for room card function
over 24000BTU/h cassette type wiring diagram
2. Dashed part is ont avaliable below Cooling capacity 28000Btu type
over 24000BTU/h mid ESP duct type wiring diagram
Note:1.Dashed parts are not available in duct type.
3.Remote central controller is optional.4.P16 and P17 are used for room card function
WYR
High ESP duct type wiring diagram
Note:1.Dashed parts are not available in duct type2.Dashed part is fan speed controller kit.3.Remote central controller is optional4.P16 and P17 are used for room card function
WYR
Cabinet unit wiring diagram:
Wiring Diagram For 24000/42000BTU/h cabinet Unit
TERMINAL BLOCK
TO O
UTD
OO
R U
NIT
Y/G
RB
W
Y/G
R
B
W
T3.15A/250VAC
FUSE
TRANS.PIPING TEMP
CONTROLLERCN3
CN12
CN11
CN8DOOR SWITCH
CN5
CN6
CN7
SWING MOTOR
FAN MOTOR
FAN MOTOR CAP.
CN1N S(N-W)
CN9
ROOM TEMP.
0010451167 PCB information – circuit diagram
12345678
10111213141516
9
IC1
2003
C32 104
1 P2-P6187
E64.7uF
INOUT
W1
7812
RL1JQ1AP-1
RL3JQ1AP-A
RL6JQ1AP-A
RC30.033uF+120
N8
9013
765
1234
8IC5
24C
01A
XT1
8.00M
1
7
CN13
1
4
CN14
升降控制
12
CN16
12345678
10111213141516
9
IC2
2003
RL8JQ1P-A
RL7JQ1P-A
RL5JQ1AP-A
RL2JQ1AP-A
RL4JQ1AP-A
N7 9013
N6 9013
1
IRQ/50Hz2
RESET3
56
NOP4
BEEP7
IR89
101112
NET-O13
NET-I141516
NOP171819
NOP20
Vss21
Vdd22
25
SCL23
SDA24
A26
B27
C28
D29303132 NOP 33
3435363738394041
4748
VDDAREF 44AVss 45
4950
4243
NOP 46
515253VREFH 54VDDA 55VSSA 56CGMXFC 57OSC2 58OSC1 596061626364
升降门开关
升降方向升降电源
空电源灯/内故障灯定时灯487使能
线控器输入线控器输出
外部报警输入
高压滤网开关浮子开关无源触点
换新风低风
高风中风
电加热
健康加湿摆风
水泵/水泵灯四通/室外通讯输入外风/室外通讯输出
压机/压机灯
选择1选择2选择3地址1地址1气管
内盘管/液管室温
低压开关高压开关
P/G反馈P/G输出
IC3
AB32
RB4
SW2
RO 1/RE 2DE 3DI 4GND5
VCC8 B7 A6
IC4 MAX487
R23 1K
R52
10K
R661M
R294.7K
R284.7K
R53 10K
R54 10K
R19
1K
C23103
C26 104
C28 104
1 P11187
1 P8187
1 P7187
1 P12187
1 P13187
1 P14187
C34 104
+5
+5
+12
+5
+5
+5
+12
+12
+5
+12
RC20.033uF+120
RC10.033uF+120
低风
中风
高风
电加热
健康
加湿
摆风
水泵
BUZ1
+12R67 100 R35 4.7K
R46 10KR16 1K
R17 1K
R18 1K
R57 4.7K
R55
10K
C25 104
C6102
C19103
C17103
C18103
C5 102
C27
104
水泵灯电源灯定时灯压机灯
遥控接收GND+5V
14 CN6
12
CN11
1
CN15
R45 10K
R44 10K
RB3RB2 RB5
SW1+5v
E74.7uF
1 P1187
C2
0.1UF/275V
FUSE1
T3.15A/250VC1
0.1UF/275V
CN1RV1
D1-D4
1
4
CN4
火线
零线T1
TRAN1-2
E12200uF
INOUT
W2
7805通讯线
C33
104
N49013
N59013 压机指示灯
R26 4.7K
R27 4.7K水泵指示灯
DL2DL1
LED1
R12560
R13
1K
R61 20K
LB1
E3
470uF/16V
E9
1uF
D18
1N41
48
步进电机A步进电机B步进电机C步进电机D
步进电机A步进电机B步进电机C步进电机D
1 2 3 4 5CN19
+5
室内外通讯接收室内外通讯发送
R47 10KR48 10K
R40 10K
R304.7K
N9
R10
330
IC6TLP371
R5 33K
C4 103LED3
D9IC7TLP521
R21
1K
R3610K
+5
C3
103
R4
2.2K
R210K/0.5W
R3 10K/0.5W
D101N4007
1
24
5 6
1
2 3
4零线
C22103
C29104
E4100uF
室内外通讯接收
室内外通讯发送
R62 20KR60 20K
室温盘管(液)
外部报警
门开关
浮子开关
无源触点开关
1
P15
187
to遥控接收板
远程控制
R51 10KR59 10KR56 10K
R50 10K
+5
1
CN12
RB1
C12103
C13103
R49 10K
室内外通讯电路
+5
EEPROM电路
+5
C8102
C11103
C10103
C9103
+5
复位电路
无源触点开关
12CN8
盘管(气)
E5
4.7uF
R14
1K
R15
1K
D17
1N4148
C14 103
C15 103
C16 103
1 P9187
1 P10187
1 2 3 4 5CN20
C31 104
R8 10
+12
VDD
1
CN7
1
CN5
D124148D134148
ABC
R344.7K
R41 10K
R6456K
R4310K C21
103N1 9013
R24
1K
+5
IC10
TLP741/541
IC9
TLP521
R6327K
C24103
D164148
D154148D144148
LED4
R324.7K
R7 10
R25 2.4K
LED5
N29013
N39013
R33
1K
R11 330
R22 1K
R314.7K
C7102
+5
+5
+5
R39 10K
D111N4007
IC8
TLP521-1
+5
1
P17187
1
P16187R9 220
R6680
R1100K/1W
R65200K
R201K E8
2.2uFC20103
无源火线
无源零线
无源触点开关
J1 J2 J3 J4 J5 J6 J7 J8 J9 J10
连接
断开
换新风
电脑板型号
专用号
KFR-120Q
0010451167J1
J2
J3
J4
J5
J6
J7
J8
J9
J10
1/60
CHECK
+5
传感器
to线控器
线控
遥控 有温度补偿
无温度补偿
室外有室
室外无室
冷暖
单冷
有装饰面板
无装饰面板 加氧
负离子
2P吊落
其它机型
内机地址选择
不选择
一拖一
一拖多
备用
C35104
C36
104
+5v
N109013
12
CN17D194148
+12
故障输出
VDD
12
CN22
12
CN23
一拖一
一拖多
去掉R58,短接CN22
去掉R4,R5,C3,C4,D9,D10
短接CN23
12
CN10
LED2
R58
1K
版本号 5
0010451167 PCB information – characters on board(horizontal)
0010451167 characters on board(vertical)
Condition for the PCB data: 1.Working ambient temperature:-10℃~70℃, relative humidity:30%~95% 2.Preserved ambient temperature:-20℃~80℃,relative humidity:30%~95% 3.Power supply:220VAC、50/60Hz,voltage range:160V~250V 4.Precise of temperature control:±1℃
0010451167 PCB information – port and definition
P1——connect to external power supply, live line: L (220VAC) P2——connect to external power supply, neutral line: N (0VAC) P3、4、5、6——control external load, neutral line: N1、N2、N3、N4(0VAC) P7——control external load, electrical heat: HEAT (control output 220VAC) P8——control external load, health function: OXYGEN (control output 220VAC) P9——control external load, humidification: HUMI (control output 220VAC) P10——control external load, SWING(control output 220VAC) P11——control external load, WATER PUMP(control output 220VAC) P12——control external load, indoor fan motor low speed: L(control output 220VAC) P13——control external load, indoor fan motor mid speed: M(control output 220VAC) P14——control external load, indoor fan motor high speed: H(control output 220VAC) P15——communication with fixed frequency single outdoor unit: COMM(0~220VAC) P16——input control, signal live line: L’(220VAC) P17——input control, signal neutral line: N’(0VAC) CN1——input port of transformer (220VAC) CN2——input port 1 of transformer (no use) CN3——input port 2 of transformer (no use) CN4——input port 3 of transformer (1-2、14VAC,3-4、12VAC) CN5——input control, connecting port to wired controller: CONTROLLER(three bits: 1. power supply:
12VAC, 2. power supply: 0VAC, 3. communication: COMM.). CN6——input control, ambient temp.-coil temp. sensor connecting port: ROOM/PIPE(1-2、ROOM,
3-4、PIPE。) Indoor ambient temp. sensor: R25=23KΩ+-2.5%,B25/50=4200K+-3%,range:(-40,80) Indoor coil temp. sensor: R25=10KΩ+-3%,B25/50=3700K+-3%,range:(-20,90) CN7——control external load, fresh air control: FRESH(1. blank, 2. power supply 0VDC, 3. control
output: 12VDC.) CN8——input signal: FREEZE(no use) CN9——input control(no use) CN10——communication with fixed frequency single outdoor unit: (0~12VDC) CN11——input signal, door switch: DOOR(1-2 short circuit is normal, cut off P8 output) CN12—— input signal, external alarm input: ALARM(1-3 short circuit is normal, if cut off, air
conditioner stops work.) Note: For convertible type, cassette type, duct type units, CN11 and CN12 must be in short
circuit, or PCB will display failure information. CN13——input signal, wiring port of remote receiver board: RECEIVE BOARD(1. power supply 5VDC,
2. power supply 0VDC, 3. remote signal, 4. signal output of running lamp 0VDC, 5. signal output of timer
lamp 0VDC,6. signal output of power lamp 0VDC, 7. signal output of water pump running lamp 0VDC) CN14——control external load, auto elevating function (1. signal of door switch close, 2. output of
elevating direction control 0VDC, 3. output of elevating power control 0VDC, 4. power supply 12VDC) CN15——input signal, detecting water level of float switch (1-3 short circuit is normal, cut off shows
that level exceeds the limitation).If float switch cuts off or occurs other failure, LED1 will flash 10 times. CN16——input control, wiring port of central controller: REMOTE(1、RS485-B,2、RS485-A。) CN17——output signal, output signal of failure alarm, control external load, 12V/ALM(1. control output
0VDC, 2. power supply 12VDC) CN18——output signal (no use) CN19——control external load, swing 1(1、16VDC,2、0VDC,3、0VDC,4、0VDC,5、0VDC.) CN20——control external load, swing 2(1、16VDC,2、0VDC,3、0VDC,4、0VDC,5、0VDC.) CN21——input signal, spring switch, CHECK(1、input signal of earthing, 2. power supply 0VDC) CN22——short circuit means selecting single split communication type. CN23——short circuit means selecting multi split communication type.
0010451167 PCB information – function selection(ON is 1, OFF is 0) The standard condition for PCB in factory SW1:4 bits are OFF SW2:4 bits are OFF SW3:4 bits are ON SW4:2 bits are ON SW5:4 bits are ON
SW1-SW2: used for indoor unit to set unit address from 1 to 16’ SW3-SW5: used for indoor unit to select different functions.(every dip switches are corresponding to
J1-J10. SW2-4——logistic relationship of control function(door card control and remote/ wired control)0
means logistic relationship is “and”, 1 means the later coming is preferential. J1,SW3-1——function selection-control type: 1 means remote control, 0 means wired control.
J2,SW3-2——function selection-temperature compensation in heating mode: 1means “yes”, 0means “no”.
J3,SW3-3——function selection-outdoor communication: 1means “yes”, 0means “no”. This PCB must be 1. J4,SW3-4——function selection-heat pump unit: 1means “heat pump”, 0means “cooling only”. 1/60——test in short circuit, but in operation short circuit mustn’t be permitted. CHECK——short spring switch control, it also can be used as switch of convertible type except for
testing. J5,SW4-1——function selection-elevating function: 1means “yes”, 0means “no”. J6,SW4-2——function selection –health function: 1means common (indoor fan motor running); 0
means special (indoor, outdoor running). J7,SW5-1——function selection –swing mode: 1 means common(simultaneous motor), 0 means
special (swing motor). J8,SW5-2——function selection – system combination: 1means fixed frequency single unit, 0 means
fixed frequency multi split. J9,SW5-3——function selection –group control: 1 stands for the master unit (its address in wired
controller is 0), 0 stands for the slave units (the address should be set by the dip switch, their addresses only can be in the range: 1~15)
J10,SW5-4——function selection –preset: 1 no meaning, 0 no meaning
0010451167 PCB information- control type Control type selection between remote and wired: select by dip switch J1, SW3-1(1 means remote control;0means wired control). For remote control type, please use remote controller YR-H71, and a remote receiver is equipped with indoor unit. For wired control type, wired controller YR-E12 will be used, 3-core shied wire is equipped with indoor unit.
Door card control: controls ON/OFF, the start up setting will comply with last time request memorized according to condition memorize function. Its difference with emergency switch of convertible type unit lies: the emergency switch control will perform in the condition: 24degrees, auto fan speed in auto mode. The function combination between door card and remote/wired control type: select by dip switch: SW2-4(0 means “and”, 1 means later coming is preferential.) Dip switch position in wired control type: Only one indoor unit of all indoor units connected with wired controller is the master unit, whose address is 0, function selection switch(J9,SW5-3)is 1. The others are slave units, and the quantity can be 0~15, whose addresses are(SW1:1~4)from 1 ~15, and cannot repeat. Wiring request in wired control type: the wired controller ports A-B-C are connected with indoor port CN5(1-2-3) through 3-core shield wire. Requirements: 1. Port A only connects with either of indoor port CN5(1) 2. Port B connects with port CN5 (2) of all indoor units. 3. Port C connects with port CN5 (3) of all indoor units.
Dip switch position in central control type: the addresses (SW1:1~4;SW2:1~4)of indoor units connected with central controller can not repeat. In principle, they should be in the order from small to big. Wiring request in central control type: port A-B is connected with indoor port CN16(A-B)through 2-core shield wire. Requirements: 1. Port A connects with port CN16(A)of all indoor units. 2. Port B connects with port CN16(B)of all indoor units.
When only use remote control type, please select remote control unit, and install according to installation
manual, there is no other special request. When only use wired control type, please select wired control unit, and install according to installation
manual. When control multi indoor units, take care the requirements of dip switch and wiring, there is no other special request.
When only use central control type, please firstly install according to air conditioner requests and set the dipswitch, there is no other special request.
When central control type(128×)and remote control type are used simultaneously, set the dip switch according to central control type, there is no other special request.
When central control type(128×)and wired control type (16×)are used simultaneously, max. indoor
units sets: 128×16 can be controller. Address setting of central controller can be met firstly, and then modulate the address setting of slave unit wired controlled. LED in indoor PCB: 1. LED1:is the state lamp for remote receiver as well as failure lamp. If indoor unit is normal, LED1 is on,
or if failure occurs, LED1 flashes regularly, and you can adjust failure type according to the flash times. 2. LED2:is used for multi split units as communication lamp. If communication between indoor and
outdoor is normal, LED2 will be on. 3. LED3:is used for single split units as communication lamp. If communication between indoor and
outdoor is normal, LED3 will be on. 4. LED4、LED5:is the lamp that shows the data receiving or sending between wired controller and PCB,
If LED4、LED5 be on in turn, communication between wired controller and PCB is normal.
12 Exploded Views & Part Lists 12.1 Outdoor Units-24\28
No.Spare partsnumber
Spare parts description inEnglish
Qty. Model Failure rate
the proportion of thespare-part stock Remark
1 001A0100122 Front grille 1 AU242AHBEA 0.0000% 0.0000% X
2 001A1436160 handle 2 AU242AHBEA 0.0000% 0.0000% X
3 001A0100261 Front panel 1 AU242AHBEA 0.0000% 0.0000% X
4 001A5402022 Axial fan 1 AU242AHBEA 0.0200% 0.0240% *
5 0010450687 Fan motor 1 AU242AHBEA 0.0200% 0.0240% *
6 001A1301321 Bracket for fan motor 1 AU242AHBEA 0.0000% 0.0000% X
7 0010750926 Condenser assy. 1 AU242AHBEA 0.0200% 0.0240% *
8 001A1301708 Electric box 1 AU242AHBEA 0.0100% 0.0120%9 001A5745009 cable clamp 1 AU242AHBEA 0.0000% 0.0000% X
10 001A3600018 Capacitor for fan motor 1 AU242AHBEA 0.0400% 0.0480% *
11 0010451346 Resumable transformer 1 AU242AHBEA 0.0500% 0.0600% *
12 001A5736055 clip for sensor 1 AU242AHBEA 0.0100% 0.0120%13 001A3900110 ambient temp. sensor 1 AU242AHBEA 0.0100% 0.0120% *
14 001A3600030 Capacitor for compressor 1 AU242AHBEA 0.0400% 0.0480% *
15 0010100001 Capacitor clamp 1 AU242AHBEA 0.0000% 0.0000% X
16 0010451293 PCB 1 AU242AHBEA 0.0200% 0.0240% *
17 0010451291 AC contactor 1 AU242AHBEA 0.0300% 0.0360% *
18 0010451265 Terminal block 1 AU242AHBEA 0.0100% 0.0120%19 0010451258 electrical source connection blo 1 AU242AHBEA 0.0100% 0.0120%20 0010850849 4-way valve 1 AU242AHBEA 0.0000% 0.0000% X
21 001A2500076 coil of 4-way valve 1 AU242AHBEA 0.0100% 0.0120%22 0010451039 High pressure switch 1 AU242AHBEA 0.0000% 0.0000% X
23 001A2611255 Assistant capillary 1 AU242AHBEA 0.0000% 0.0000% X
24 0010451312 pipe temp. sensor 1 AU242AHBEA 0.0100% 0.0120%24 0010451313 discharging temp. sensor 1 AU242AHBEA 0.0100% 0.0120%25 001A2411023 filter 1 AU242AHBEA 0.0000% 0.0000% X
26 001A2611288 capillary 1 AU242AHBEA 0.0000% 0.0000% X
27 001a2500154 3-way stop valve 1 AU242AHBEA 0.0000% 0.0000% X
28 001a2500153 2-way stop valve 1 AU242AHBEA 0.0000% 0.0000% X
29 0010751079 muffle 1 AU242AHBEA 0.0000% 0.0000% X
30 001A2000201 Compressor 1 AU242AHBEA 0.0600% 0.0720% *
31 001A2101857 Accumulator 1 AU242AHBEA 0.0000% 0.0000% X
32 001A0100350 Partition plate 1 AU242AHBEA 0.0000% 0.0000% X
33 001A0100524 Front panel 1 AU242AHBEA 0.0000% 0.0000% X
34 001A0100351 Bottom cover assy. 1 AU242AHBEA 0.0000% 0.0000% X
35 001A1301117 branch triby 2 AU242AHBEA 0.0000% 0.0000% X
36 001A1301506 Valve pedestal 1 AU242AHBEA 0.0000% 0.0000% X
37 001A0100264 Top cover assy. 1 AU242AHBEA 0.0000% 0.0000% X
38 001A0100109 Back grille 1 AU242AHBEA 0.0000% 0.0000% X
39 001A0100394 Junction box 1 AU242AHBEA 0.0000% 0.0000% X
40 001A0100390 Slide plate(right) 1 AU242AHBEA 0.0000% 0.0000% X
41 0010451430 wire assy. 1 AU242AHBEA 0.0100% 0.0120%
4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.Thespare parts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-part warehouse,should be marked with " x ".5,Above should be improved accord with the reply of the market half a year per time.6.The spare parts price on net is FOB Qingdao term.
Parts list
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjustedwith the actual quantity 3 months later.2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-partswarehouse,and should be marked with"*"3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer maystock in the spare-part warehouse accord with the actual case,should be marked with " ".
No.Spare partsnumber
Spare parts description inEnglish
Qty. Model Failure rate
the proportion of thespare-part stock Remark
1 001A0100122 Front grille 1 AU28NAHBEA 0.0000% 0.0000% X2 001A1436160 handle 2 AU28NAHBEA 0.0000% 0.0000% X3 001A0100261 Front panel 1 AU28NAHBEA 0.0000% 0.0000% X4 001A5402022 Axial fan 1 AU28NAHBEA 0.0200% 0.0240% *5 0010450687 Fan motor 1 AU28NAHBEA 0.0200% 0.0240% *6 001A1301321 Bracket for fan motor 1 AU28NAHBEA 0.0000% 0.0000% X7 0010750926 Condenser assy. 1 AU28NAHBEA 0.0200% 0.0240% *8 001A1301453 Electric box 1 AU28NAHBEA 0.0100% 0.0120%9 001A5745009 cable clamp 1 AU28NAHBEA 0.0000% 0.0000% X10 001A3600134 Capacitor for fan motor 1 AU28NAHBEA 0.0400% 0.0480% *11 0010451346 Resumable transformer 1 AU28NAHBEA 0.0500% 0.0600% *12 001A5736055 clip for sensor 1 AU28NAHBEA 0.0100% 0.0120%13 001A3900110 ambient temp. sensor 1 AU28NAHBEA 0.0100% 0.0120% *14 / / / AU28NAHBEA / / /15 / / / AU28NAHBEA / / /16 0010451295 PCB 1 AU28NAHBEA 0.0200% 0.0240% *17 0010451291 AC contactor 1 AU28NAHBEA 0.0300% 0.0360% *18 001A4000158 Terminal block 1 AU28NAHBEA 0.0100% 0.0120%19 0010451258 electrical source connection block 1 AU28NAHBEA 0.0100% 0.0120%20 0010850849 4-way valve 1 AU28NAHBEA 0.0000% 0.0000% X21 001A2500076 coil of 4-way valve 1 AU28NAHBEA 0.0100% 0.0120%22 0010451039 High pressure switch 1 AU28NAHBEA 0.0000% 0.0000% X23 001A2611255 Assistant capillary 1 AU28NAHBEA 0.0000% 0.0000% X24 0010450243 pipe temp. sensor 1 AU28NAHBEA 0.0100% 0.0120%24 0010450398 discharging temp. sensor 1 AU28NAHBEA 0.0100% 0.0120%25 001A2411023 filter 1 AU28NAHBEA 0.0000% 0.0000% X26 001A2611288 capillary 1 AU28NAHBEA 0.0000% 0.0000% X27 001a2500154 3-way stop valve 1 AU28NAHBEA 0.0000% 0.0000% X28 001a2500153 2-way stop valve 1 AU28NAHBEA 0.0000% 0.0000% X29 0010751079 muffle 1 AU28NAHBEA 0.0000% 0.0000% X30 0010700989 Compressor 1 AU28NAHBEA 0.0600% 0.0720% *31 001A2101857 Accumulator 1 AU28NAHBEA 0.0000% 0.0000% X32 001A0100350 Partition plate 1 AU28NAHBEA 0.0000% 0.0000% X33 001A0100524 Front panel 1 AU28NAHBEA 0.0000% 0.0000% X34 001A0100351 Bottom cover assy. 1 AU28NAHBEA 0.0000% 0.0000% X35 001A1301117 branch triby 2 AU28NAHBEA 0.0000% 0.0000% X36 001A1301506 Valve pedestal 1 AU28NAHBEA 0.0000% 0.0000% X37 001A0100264 Top cover assy. 1 AU28NAHBEA 0.0000% 0.0000% X38 001A0100109 Back grille 1 AU28NAHBEA 0.0000% 0.0000% X39 001A0100394 Junction box 1 AU28NAHBEA 0.0000% 0.0000% X40 001A0100390 Slide plate(right) 1 AU28NAHBEA 0.0000% 0.0000% X41 0010451355 wire assy. 1 AU28NAHBEA 0.0100% 0.0120%
4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spareparts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-partwarehouse,should be marked with " x ".
5,Above should be improved accord with the reply of the market half a year per time.6.The spare parts price on net is FOB Qingdao term.
Parts list
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with theactual quantity 3 months later.
2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,andshould be marked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer maystock in the spare-part warehouse accord with the actual case,should be marked with " ".
No.Spare partsnumber Spare parts description in English
Qty. Model Failure rate
the proportion ofthe spare-part stock Remark
1 001A0100122 Front grille 1 AU282AHBEA 0.0000% 0.0000% X2 001A1436160 handle 2 AU282AHBEA 0.0000% 0.0000% X3 001A0100261 Front panel 1 AU282AHBEA 0.0000% 0.0000% X4 001A5402022 Axial fan 1 AU282AHBEA 0.0200% 0.0240% *5 0010450687 Fan motor 1 AU282AHBEA 0.0200% 0.0240% *6 001A1301321 Bracket for fan motor 1 AU282AHBEA 0.0000% 0.0000% X7 0010750926 Condenser assy. 1 AU282AHBEA 0.0200% 0.0240% *8 001A1301453 Electric box 1 AU282AHBEA 0.0100% 0.0120%9 001A5745009 cable clamp 1 AU282AHBEA 0.0000% 0.0000% X10 001A3600018 Capacitor for fan motor 1 AU282AHBEA 0.0400% 0.0480% *11 0010451346 Resumable transformer 1 AU282AHBEA 0.0500% 0.0600% *12 001A5736055 clip for sensor 1 AU282AHBEA 0.0100% 0.0120%13 001A3900110 ambient temp. sensor 1 AU282AHBEA 0.0100% 0.0120% *14 / / / AU282AHBEA / / /15 / / / AU282AHBEA / / /16 0010451293 PCB 1 AU282AHBEA 0.0200% 0.0240% *17 0010400334 AC contactor 1 AU282AHBEA 0.0300% 0.0360% *18 0010451265 Terminal block 1 AU282AHBEA 0.0100% 0.0120%19 0010451258 electrical source connection block 1 AU282AHBEA 0.0100% 0.0120%20 001A2500155 4-way valve 1 AU282AHBEA 0.0000% 0.0000% X21 001A2500076 coil of 4-way valve 1 AU282AHBEA 0.0100% 0.0120%22 0010400127 High pressure switch 1 AU282AHBEA 0.0000% 0.0000% X23 001A0500365 Assistant capillary 1 AU282AHBEA 0.0000% 0.0000% X24 0010451314 pipe temp. sensor 1 AU282AHBEA 0.0100% 0.0120%24 0010450398 discharging temp. sensor 1 AU282AHBEA 0.0100% 0.0120%25 001A2411023 filter 1 AU282AHBEA 0.0000% 0.0000% X26 0010753601 capillary 1 AU282AHBEA 0.0000% 0.0000% X27 001a2500154 3-way stop valve 1 AU282AHBEA 0.0000% 0.0000% X28 001a2500153 2-way stop valve 1 AU282AHBEA 0.0000% 0.0000% X29 0010751079 muffle 1 AU282AHBEA 0.0000% 0.0000% X30 0010753600 Compressor 1 AU282AHBEA 0.0600% 0.0720% *31 0010751125 Accumulator 1 AU282AHBEA 0.0000% 0.0000% X32 001A0100350 Partition plate 1 AU282AHBEA 0.0000% 0.0000% X33 001A0100524 Front panel 1 AU282AHBEA 0.0000% 0.0000% X34 001A0100351 Bottom cover assy. 1 AU282AHBEA 0.0000% 0.0000% X35 001A1301117 branch triby 2 AU282AHBEA 0.0000% 0.0000% X36 001A1301506 Valve pedestal 1 AU282AHBEA 0.0000% 0.0000% X37 001A0100264 Top cover assy. 1 AU282AHBEA 0.0000% 0.0000% X38 001A0100109 Back grille 1 AU282AHBEA 0.0000% 0.0000% X39 001A0100394 Junction box 1 AU282AHBEA 0.0000% 0.0000% X40 001A0100390 Slide plate(right) 1 AU282AHBEA 0.0000% 0.0000% X41 0010451430 wire assy. 1 AU282AHBEA 0.0100% 0.0120%
4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spareparts may be air freighted by the factory if they were damaged.The customer nees not stock in the spare-partwarehouse,should be marked with " x ".
5,Above should be improved accord with the reply of the market half a year per time.6.The spare parts price on net is FOB Qingdao term.
Parts list
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjusted with theactual quantity 3 months later.
2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-partswarehouse,and should be marked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer maystock in the spare-part warehouse accord with the actual case,should be marked with " ".
Model 2: AC242ACBEA
No. Spare parts number Spare parts description in english Qty. Model Failure rate
theproportion ofthe spare-part stock Remark
1 001A2400087 air filter 2 AC242ACBEA 0.00% 0.000% ×2 001A0100330 inlet grill assy 1 AC242ACBEA 0.00% 0.000% ×3 001A1301398 fixing plate 2 AC242ACBEA 0.00% 0.000% ×4 001A1301395 strengthen tendon 1 AC242ACBEA 0.00% 0.000% ×5 001A1301399 pinch plate 2 AC242ACBEA 0.00% 0.000% ×6 0010451478 wiring assembly 1 AC242ACBEA 0.00% 0.000% ×7 001A3600009B Fan motor capacitor 2uf 1 AC242ACBEA 0.04% 0.048% *8 0010451262 transformer 1 AC242ACBEA 0.01% 0.012%9 0010451167 indoor PCB 1 AC242ACBEA 0.02% 0.024% *
10 0010451494 termonal block 1 AC242ACBEA 0.00% 0.000% ×11 001A14311292 Power line clip 1 AC242ACBEA 0.00% 0.000% ×12 001A1431326 wiring block 1 AC242ACBEA 0.00% 0.000% ×13 001A3900006 environment temp. Sensor indoor 1 AC242ACBEA 0.00% 0.000% ×14 001A1301382 clamp plate of motor 1 AC242ACBEA 0.00% 0.000% ×15 001A1301383 connecting rod of motor 1 AC242ACBEA 0.00% 0.000% ×16 001A1301381 Fan motor bracket 1 AC242ACBEA 0.00% 0.000% ×17 001A1443592 small block 1 AC242ACBEA 0.00% 0.000% ×18 10450779 Indoor fan motor 1 AC242ACBEA 0.02% 0.024% *19 001A2300042 centrifugal fan 2 AC242ACBEA 0.02% 0.024% *20 001A1436664 drainage elbow 1 AC242ACBEA 0.00% 0.000% ×21 001A1431608 scroll case 1 2 AC242ACBEA 0.00% 0.000% ×22 001A1431609 scroll case 2 2 AC242ACBEA 0.00% 0.000% ×23 001A3900159 Pipe temp. sensor indoor 1 AC242ACBEA 0.00% 0.000% ×24 001A0500252 Air inlet tube assy. 1 AC242ACBEA 0.00% 0.000% ×25 0010750130 liquid pipe 1 AC242ACBEA 0.00% 0.000% ×26 001A1734862 back framework 2 AC242ACBEA 0.00% 0.000% ×27 001A1436606 handle 4 AC242ACBEA 0.00% 0.000% ×28 001A1101104 right wallboard 1 AC242ACBEA 0.00% 0.000% ×29 001A1101041 plate assy right 1 AC242ACBEA 0.00% 0.000% ×30 001A1431593 long blade 1 1 AC242ACBEA 0.00% 0.000% ×31 001A1301394 strengthen tendon 1 AC242ACBEA 0.00% 0.000% ×32 001A1231180 outlet grill hold middle 1 AC242ACBEA 0.00% 0.000% ×33 001A1431599 mini fan blade 1 AC242ACBEA 0.00% 0.000% ×34 001A0100329 cover 1 AC242ACBEA 0.00% 0.000% ×35 001A1431586 display panel 1 AC242ACBEA 0.00% 0.000% ×36 001A1431827 Airflow oriented board affix 3 AC242ACBEA 0.00% 0.000% ×37 001A3000107 stepping motor 1 AC242ACBEA 0.02% 0.024% *38 0010450309 receive panel 1 AC242ACBEA 0.00% 0.000% ×39 001A1431587 Indicator light base 1 AC242ACBEA 0.00% 0.000% ×40 001A1431598 Prompting pole 2 AC242ACBEA 0.00% 0.000% ×41 001A3000107 curving connecting rod 2 AC242ACBEA 0.00% 0.000% ×42 001A1301400 fixing layering 1 AC242ACBEA 0.00% 0.000% ×43 001A1233191 Drain pan 1 AC242ACBEA 0.00% 0.000% ×44 001A1301396 Evaporator left holder 1 AC242ACBEA 0.00% 0.000% ×45 0010753604 Evaporator assembly 1 AC242ACBEA 0.01% 0.012%46 001A1101099 plate assy left 1 AC242ACBEA 0.00% 0.000% ×47 001A1101103 left wallboard 1 AC242ACBEA 0.00% 0.000% ×48 001A1231192 assistant drain pan 1 AC242ACBEA 0.00% 0.000% ×49 001A1231182 cover assy 1 AC242ACBEA 0.00% 0.000% ×50 001A1101098 back framework 1 AC242ACBEA 0.00% 0.000% ×51 001A1301401 Evaporator right holder 1 AC242ACBEA 0.00% 0.000% ×52 0010451255 Remote Controller 1 AC242ACBEA 0.01% 0.012%
Parts list
Model 2: AC28NACBEA
No. Spare parts number Spare parts description in english Qty. Model Failure ratethe proportion of thespare-part stock Remark
1 001A1231278 inlet grill assy 2 AC28NACBEA 0.00% 0.000% ×
2 001A2400108 air filter 2 AC28NACBEA 0.00% 0.000% ×
3 001A1101174 front panel assy 1 AC28NACBEA 0.00% 0.000% ×
4 001A17341062 pad 1 AC28NACBEA 0.00% 0.000% ×
5 001A3900006 Pipe temperature sensor 1 AC28NACBEA 0.00% 0.000% ×
6 001A1200185 drain pan assy 1 AC28NACBEA 0.00% 0.000% ×
7 001A1101179 mounting plate 1 AC28NACBEA 0.00% 0.000% ×
8 001A1301574 left scroll case 1 AC28NACBEA 0.00% 0.000% ×
9 001A1301581 motor holder 1 AC28NACBEA 0.00% 0.000% ×
10 001A2331071 centrifugal fan 2 AC28NACBEA 0.02% 0.024% *
11 001A1301580 motor bracket 2 AC28NACBEA 0.00% 0.000% ×
12 0010450626 motor 1 AC28NACBEA 0.02% 0.024% *
13 001A01001102 electric box assy 1 AC28NACBEA 0.00% 0.000% ×
14 001A1301591 PCB bracket 1 1 AC28NACBEA 0.00% 0.000% ×
15 0010451167 indoor PCB 1 AC28NACBEA 0.02% 0.024% *
16 001A1301378 Eletrical box 1 AC28NACBEA 0.00% 0.000% ×
17 001A1431750 Terminal block cover 1 AC28NACBEA 0.00% 0.000% ×
18 0010451262 transformer 1 AC28NACBEA 0.01% 0.012%
19 001A3600009B capacitor 1 AC28NACBEA 0.04% 0.048% *
20 0010451494 termonal block 1 AC28NACBEA 0.00% 0.000% ×
21 001A1301592 PCB bracket 2 1 AC28NACBEA 0.00% 0.000% ×
22 001A5701009 Power line clip 1 AC28NACBEA 0.00% 0.000% ×
23 001A1301582 scroll case right 1 AC28NACBEA 0.00% 0.000% ×
24 001A3900005 environment temperature sensor 1 AC28NACBEA 0.00% 0.000% ×
25 0010753606 gas pipe 1 AC28NACBEA 0.00% 0.000% ×
26 0010753605 liquid pipe 1 AC28NACBEA 0.00% 0.000% ×
27 001A1301588 partition plate 1 AC28NACBEA 0.00% 0.000% ×
28 001A1301577 plate assy right 1 AC28NACBEA 0.00% 0.000% ×
29 001A1301579 right wallboard 1 AC28NACBEA 0.00% 0.000% ×
30 001A1231277 ornamental plate right 1 AC28NACBEA 0.00% 0.000% ×
31 0010752959 evaporator 1 AC28NACBEA 0.01% 0.012%
32 001A1231276 ornamental plate left 1 AC28NACBEA 0.00% 0.000% ×
33 001A1301578 left wallboard 1 AC28NACBEA 0.00% 0.000% ×
34 001A1301575 plate assy left 1 AC28NACBEA 0.00% 0.000% ×
35 001A1101178 rear guard plate 1 AC28NACBEA 0.00% 0.000% ×
36 001A1101176 blade assy 1 AC28NACBEA 0.00% 0.000% ×
37 001A1431746 fixing bracket right 1 AC28NACBEA 0.00% 0.000% ×
38 001A1443745 prompting pole 1 AC28NACBEA 0.00% 0.000% ×
39 001A3000198 Synchromotor 1 AC28NACBEA 0.02% 0.024% *
40 001A1431878 Indicator light cover 1 AC28NACBEA 0.00% 0.000% ×
41 0010400410 receive panel 1 AC28NACBEA 0.02% 0.024% *
42 001A1231279 ornamental plate 1 AC28NACBEA 0.00% 0.000% ×
43 001A1431800 fixing bracket left 1 AC28NACBEA 0.00% 0.000% ×
44 001A1231280 middle ornamental plate 2 AC28NACBEA 0.00% 0.000% ×
45 001A1231272 left top cover assy 1 AC28NACBEA 0.00% 0.000% ×
46 001A1231281 ornamental plate right 1 AC28NACBEA 0.00% 0.000% ×
47 001A1231274 front top cover assy 1 AC28NACBEA 0.00% 0.000% ×
48 001A0100431 left fixing bracket 1 AC28NACBEA 0.00% 0.000% ×
49 001A1101177 blade assy2 1 AC28NACBEA 0.00% 0.000% ×
50 001A1231275 top cover assy 1 AC28NACBEA 0.00% 0.000% ×
51 001A1231284 middle outlet grill hold 1 AC28NACBEA 0.00% 0.000% ×
52 001A1231273 right top cover assy 1 AC28NACBEA 0.00% 0.000% ×
53 001A0100432 outlet grill hold right 1 AC28NACBEA 0.00% 0.000% ×
Parts list
Model 3: AD242AMBEA AD28NAMBEA
No. Spare parts numberSpare parts description inEnglish Qty. Model Failure rate
the proportion of thespare-part stock Remark
1 0010800086 Guard plate 1 1 AD242AMBEA 0.000% 0.000% X2 0010100228 Guard plate 2 1 AD242AMBEA 0.000% 0.000% X3 0010752516 Evaporator assembly 1 AD242AMBEA 0.010% 0.012%4 0010800106 Right fixing plate assembly 1 AD242AMBEA 0.000% 0.000% X5 0010100016 Supporting plate assembly 1 AD242AMBEA 0.000% 0.000% X6 001A1301988 Seal ring for scroll case 2 AD242AMBEA 0.000% 0.000% X7 001A2331089 Centrifugal fan 2 AD242AMBEA 0.020% 0.024% *8 001A5401035 Cushion 1 AD242AMBEA 0.000% 0.000% X9 0010200120 Cushion 1 AD242AMBEA 0.000% 0.000% X
10 001A17341291 Cushion 3 AD242AMBEA 0.000% 0.000% X11 001A14311066 Air outlet 3 AD242AMBEA 0.000% 0.000% X12 001A17341292 Cushion 3 AD242AMBEA 0.000% 0.000% X13 0010100017 Base plate assembly 1 AD242AMBEA 0.000% 0.000% X14 001A17341292 Cushion 3 AD242AMBEA 0.000% 0.000% X15 0010200122 Cushion 1 AD242AMBEA 0.000% 0.000% X16 0010100224 Long fixing tendon 2 AD242AMBEA 0.000% 0.000% X17 0010100226 Enclosure 1 AD242AMBEA 0.000% 0.000% X18 0010100227 Inlet wind connect frame 1 AD242AMBEA 0.000% 0.000% X19 0010451262 Transformer 1 AD242AMBEA 0.010% 0.012%20 001A1101206 Electrical box 1 AD242AMBEA 0.010% 0.012%21 001A1452909 Rubber ring 1 AD242AMBEA 0.000% 0.000% X22 001A1452861 Rubber ring 2 AD242AMBEA 0.000% 0.000% X23 0010451167 PCB 1 AD242AMBEA 0.020% 0.024% *24 0010451265 Terminal block 1 AD242AMBEA 0.010% 0.012%25 001A3600134 Fan capacitor 1 AD242AMBEA 0.040% 0.048% *26 001A1301796 Electrical box cover assembly 1 AD242AMBEA 0.000% 0.000% X27 001A14341141 Water drain pipe assembly 1 AD242AMBEA 0.000% 0.000% X28 001A5002256 Fixing bolt 3 AD242AMBEA 0.000% 0.000% X29 001A1301784 Water pump fixing stand 1 AD242AMBEA 0.000% 0.000% X30 001A17511246 Damping pad 3 AD242AMBEA 0.000% 0.000% X31 001A3000250 Dual shaft electric motor 1 AD242AMBEA 0.000% 0.000% X32 0010450169 Water pump motor 1 AD242AMBEA 0.020% 0.024% *33 001A1301786 Floater fixing stand 1 AD242AMBEA 0.000% 0.000% X34 001A1301782 Connecting plate 1 1 AD242AMBEA 0.000% 0.000% X35 001A1309785 Water pump support 1 AD242AMBEA 0.000% 0.000% X36 001A1301783 Connecting plate 2 1 AD242AMBEA 0.000% 0.000% X37 001A3400076 Float switch 1 AD242AMBEA 0.020% 0.024% *38 001A1301789 Fixed handle 1 1 AD242AMBEA 0.000% 0.000% X39 001A1301790 Fixed handle 2 1 AD242AMBEA 0.000% 0.000% X40 001A1101205 Scroll case 2 AD242AMBEA 0.000% 0.000% X41 0010800105 Left fixing plate assembly 1 AD242AMBEA 0.000% 0.000% X42 0010800085 Water collecting pan assembly 1 AD242AMBEA 0.000% 0.000% X43 0010200114 Cushion 1 AD242AMBEA 0.000% 0.000% X44 0010451521 Wired controller 1 AD242AMBEA 0.010% 0.012%
4,not need provided :The spare-part which is seldom damaged or the maintenance man could not maitmains.The spare parts may beair freighted by the factory if they were damaged.The customer nees not stock in the spare-part warehouse,should be marked with "x ".5,Above should be improved accord with the reply of the market half a year per time.6.The spare parts price on net is FOB Qingdao term.
Parts list
1,The failure rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first timeshould be stocked accroded with the proportion of the spare-parts,and it should be adjusted with the actual quantity 3 months later.
2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-parts warehouse,and should bemarked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customer may stock in the spare-part warehouse accord with the actual case,should be marked with " ".
No. Spare parts numberSpare parts description inEnglish Qty. Model Failure rate
the proportionof the spare-part stock Remark
1 0010800086 Guard plate 1 1 AD28NAMBEA 0.000% 0.000% X
2 0010100228 Guard plate 2 1 AD28NAMBEA 0.000% 0.000% X
3 0010752957 Evaporator assembly 1 AD28NAMBEA 0.010% 0.012%
4 0010800106 Right fixing plate assembly 1 AD28NAMBEA 0.000% 0.000% X
5 0010100016 Supporting plate assembly 1 AD28NAMBEA 0.000% 0.000% X
6 001A1301988 Seal ring for scroll case 2 AD28NAMBEA 0.000% 0.000% X
7 001A2331089 Centrifugal fan 2 AD28NAMBEA 0.020% 0.024% *
8 001A5401035 Cushion 1 AD28NAMBEA 0.000% 0.000% X
9 0010200120 Cushion 1 AD28NAMBEA 0.000% 0.000% X
10 001A17341291 Cushion 3 AD28NAMBEA 0.000% 0.000% X
11 001A14311066 Air outlet 3 AD28NAMBEA 0.000% 0.000% X
12 001A17341292 Cushion 3 AD28NAMBEA 0.000% 0.000% X
13 0010100017 Base plate assembly 1 AD28NAMBEA 0.000% 0.000% X
14 001A17341292 Cushion 3 AD28NAMBEA 0.000% 0.000% X
15 0010200122 Cushion 1 AD28NAMBEA 0.000% 0.000% X
16 0010100224 Long fixing tendon 2 AD28NAMBEA 0.000% 0.000% X
17 0010100226 Enclosure 1 AD28NAMBEA 0.000% 0.000% X
18 0010100227 Inlet wind connect frame 1 AD28NAMBEA 0.000% 0.000% X
19 0010451262 Transformer 1 AD28NAMBEA 0.010% 0.012%
20 001A1101206 Electrical box 1 AD28NAMBEA 0.010% 0.012%
21 001A1452909 Rubber ring 1 AD28NAMBEA 0.000% 0.000% X
22 001A1452861 Rubber ring 2 AD28NAMBEA 0.000% 0.000% X
23 0010451167 PCB 1 AD28NAMBEA 0.020% 0.024% *
24 0010451265 Terminal block 1 AD28NAMBEA 0.010% 0.012%
25 001A3600134 Fan capacitor 1 AD28NAMBEA 0.040% 0.048% *
26 001A1301796 Electrical box cover assembly 1 AD28NAMBEA 0.000% 0.000% X
27 001A14341141 Water drain pipe assembly 1 AD28NAMBEA 0.000% 0.000% X
28 001A5002256 Fixing bolt 3 AD28NAMBEA 0.000% 0.000% X
29 001A1301784 Water pump fixing stand 1 AD28NAMBEA 0.000% 0.000% X
30 001A17511246 Damping pad 3 AD28NAMBEA 0.000% 0.000% X
31 001A3000250 Dual shaft electric motor 1 AD28NAMBEA 0.000% 0.000% X
32 0010450169 Water pump motor 1 AD28NAMBEA 0.020% 0.024% *
33 001A1301786 Floater fixing stand 1 AD28NAMBEA 0.000% 0.000% X
34 001A1301782 Connecting plate 1 1 AD28NAMBEA 0.000% 0.000% X
35 001A1309785 Water pump support 1 AD28NAMBEA 0.000% 0.000% X
36 001A1301783 Connecting plate 2 1 AD28NAMBEA 0.000% 0.000% X
37 001A3400076 Float switch 1 AD28NAMBEA 0.020% 0.024% *
38 001A1301789 Fixed handle 1 1 AD28NAMBEA 0.000% 0.000% X
39 001A1301790 Fixed handle 2 1 AD28NAMBEA 0.000% 0.000% X
40 001A1101205 Scroll case 2 AD28NAMBEA 0.000% 0.000% X
41 0010800105 Left fixing plate assembly 1 AD28NAMBEA 0.000% 0.000% X
42 0010800085 Water collecting pan assembly 1 AD28NAMBEA 0.000% 0.000% X
43 0010200114 Cushion 1 AD28NAMBEA 0.000% 0.000% X
44 0010451521 Wired controller 1 AD28NAMBEA 0.010% 0.012%
Parts list
Model 4: AD242AHBEA and AD28NAHBEA are the same.
No.Spare partsnumber
Spare parts description inenglish Qty. Model
Failurerate
the proportionof the spare-part stock Remark
1 0010150130 connection frame of inlet air 1 AD242AHBEA 0.00% 0.000% ×2 0010151123 hanging 4 AD242AHBEA 0.00% 0.000% ×3 0010851049 boarding assy. of liquid pipe 1 AD242AHBEA 0.00% 0.000% ×4 001A13011068 evaporator brackt 1 1 AD242AHBEA 0.00% 0.000% ×5 0010100502 bottom plate assy. 1 AD242AHBEA 0.00% 0.000% ×6 0010100511 fix slot assy. 1 AD242AHBEA 0.00% 0.000% ×7 0010100503 air discharge framework 1 AD242AHBEA 0.00% 0.000% ×8 001A13011069 evaporator brackt 2 1 AD242AHBEA 0.00% 0.000% ×9 0010100504 evaporator fixing plate 1 1 AD242AHBEA 0.00% 0.000% ×
10 0010800284 cover board assy. 1 1 AD242AHBEA 0.00% 0.000% ×11 0010800285 cover board assy. 2 1 AD242AHBEA 0.00% 0.000% ×12 0010800282 fix tendon assy. 1 1 AD242AHBEA 0.00% 0.000% ×13 0010800290 evaporator fixing plate 3 1 AD242AHBEA 0.00% 0.000% ×14 0010800286 cover board assy.3 1 AD242AHBEA 0.00% 0.000% ×15 0010800283 fix tendon assy. 2 1 AD242AHBEA 0.00% 0.000% ×16 0010451262 transformer 1 AD242AHBEA 0.01% 0.012%17 0010451167 PCB 1 AD242AHBEA 0.02% 0.024% *18 001A3300352 fan speed adjusting board 1 AD242AHBEA 0.02% 0.024% *19 001A3600254 fan motor capacitor 1 AD242AHBEA 0.04% 0.048% *20 0010850004 electrical box cover 1 AD242AHBEA 0.00% 0.000% ×21 0010451265 termianl block 1 AD242AHBEA 0.00% 0.000% ×22 001A13011036 electrical box assy. 1 AD242AHBEA 0.00% 0.000% ×23 001A13011050 bracket of floater 1 AD242AHBEA 0.00% 0.000% ×24 001A3400160 float switch 1 AD242AHBEA 0.00% 0.000% ×25 001A1436026 sensor bracket 1 AD242AHBEA 0.00% 0.000% ×26 001A3900006 coil temp. sensor 1 AD242AHBEA 0.00% 0.000% ×27 001A1101236 supporting plate 1 AD242AHBEA 0.00% 0.000% ×28 001A13011043 snail shell 2 1 AD242AHBEA 0.00% 0.000% ×29 001A2301105 fan 2 1 AD242AHBEA 0.02% 0.024% *30 0010750004 evaporator assy. 1 AD242AHBEA 0.01% 0.012%31 001A13011044 hermitic circle of snail shell 2 AD242AHBEA 0.00% 0.000% ×32 001A2301104 fan 1 1 AD242AHBEA 0.02% 0.024% *33 001A13011042 snail shell 1 1 AD242AHBEA 0.00% 0.000% ×34 001A13011039 motor bracket 1 AD242AHBEA 0.00% 0.000% ×35 001A13011045 motor fixing bolt 2 AD242AHBEA 0.00% 0.000% ×36 001A3000290 indoor motor 1 AD242AHBEA 0.02% 0.024% *37 0010201091 drain pan assy. 1 AD242AHBEA 0.00% 0.000% ×38 0010851049 guarding plate assy.2 1 AD242AHBEA 0.00% 0.000% ×39 0010100498 guarding plate assy.1 1 AD242AHBEA 0.00% 0.000% ×
Parts list
Cassette type -AB242ACBEA AB28NACBEA
No.Spare partsnumber
Spare parts description inenglish Qty. Model
Failurerate
the proportion ofthe spare-partstock Remark
1 001A0100708 Bottom plate assy. 1 AB242ACBEA 0.00% 0.000% ×2 001A1301741 Swing 4 AB242ACBEA 0.00% 0.000% ×3 001A1301743 Motor holder 1 AB242ACBEA 0.00% 0.000% ×4 001A1301668 Motor bracket 1 AB242ACBEA 0.00% 0.000% ×5 001A3000219 Indoor fan motor 1 AB242ACBEA 0.02% 0.024% *6 001A1301742 wiring fix plate 1 AB242ACBEA 0.00% 0.000% ×7 001A2300088 Indoor fan 1 AB242ACBEA 0.02% 0.024% *8 001A1301752 pipe holder plate 1 AB242ACBEA 0.00% 0.000% ×9 001A1301751 Evaporator holded plate 1 AB242ACBEA 0.00% 0.000% ×
10 001A1301710 Fan in-built part 1 AB242ACBEA 0.00% 0.000% ×11 001A5102015 Flange screw nut 1 AB242ACBEA 0.00% 0.000% ×12 001A3900006 Pipe temp. sensor indoor 1 AB242ACBEA 0.00% 0.000% ×13 0010752481 liquid pipe assy. 1 AB242ACBEA 0.00% 0.000% ×14 0010700299 air pipe assy. 1 AB242ACBEA 0.00% 0.000% ×15 001A0100711 Pump Bracket assy. 1 AB242ACBEA 0.00% 0.000% ×16 001A1434920 Drainage pipe 1 AB242ACBEA 0.00% 0.000% ×17 0010450169 Water pump motor 1 AB242ACBEA 0.02% 0.024% *18 0010450154 Float Switch 1 AB242ACBEA 0.00% 0.000% ×19 0010752522 Evaporator assembly 1 AB242ACBEA 0.01% 0.012%20 001A1301750 Evaporator holder 2 AB242ACBEA 0.00% 0.000% ×21 001A0900089 Drain pan assy. 1 AB242ACBEA 0.00% 0.000% ×22 001A1301753 bottom plate of electrical box 1 AB242ACBEA 0.00% 0.000% ×23 001A1232305 Eletrical box 1 AB242ACBEA 0.00% 0.000% ×24 001A3600232 Fan motor capacitor 4.5 uf 1 AB242ACBEA 0.04% 0.048% *25 0010451265 Terminal block 1 AB242ACBEA 0.00% 0.000% ×26 0010451262 Transformer 1 AB242ACBEA 0.01% 0.012%27 0010451167 indoor PCB 1 AB242ACBEA 0.02% 0.024% *28 001A1232306 Electrical box cover 1 1 AB242ACBEA 0.00% 0.000% ×29 001A1232307 Electrical box cover2 1 AB242ACBEA 0.00% 0.000% ×30 001A1431661 inlet circle 1 AB242ACBEA 0.00% 0.000% ×31 001A3900159 environment temp. Sensor indoor 1 AB242ACBEA 0.00% 0.000% ×32 001A1301756 guarding grill 1 AB242ACBEA 0.00% 0.000% ×33 001A13001077 hoop 1 AB242ACBEA 0.00% 0.000% ×34 0010451255 Controller 1 AB242ACBEA 0.01% 0.012%35 001A1434574A Heat insulation pipe 1 1 AB242ACBEA 0.00% 0.000% ×36 001A1434925 Heat insulation pipe2 1 AB242ACBEA 0.00% 0.000% ×37 001A6645007 cable clamp 6 AB242ACBEA 0.00% 0.000% ×
Parts list
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjustedwith the actual quantity 3 months later.
6.The spare parts price on net is FOB Qingdao term.
2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-partswarehouse,and should be marked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customermay stock in the spare-part warehouse accord with the actual case,should be marked with " ".
4,not need provided :The spare-part which is seldom damaged or the maintenance man could notmaitmains.The spare parts may be air freighted by the factory if they were damaged.The customer nees notstock in the spare-part warehouse,should be marked with " x ".
5,Above should be improved accord with the reply of the market half a year per time.
No.Spare partsnumber
Spare parts description inenglish Qty. Model
Failurerate
theproportion ofthe spare-part stock Remark
1 001A0100708 Bottom plate assy. 1 AB28NACBEA 0.00% 0.000% ×2 001A1301741 Swing 4 AB28NACBEA 0.00% 0.000% ×3 001A1301743 Motor holder 1 AB28NACBEA 0.00% 0.000% ×4 001A1301668 Motor bracket 1 AB28NACBEA 0.00% 0.000% ×5 001A3000219 Indoor fan motor 1 AB28NACBEA 0.02% 0.024% *6 001A1301742 wiring fix plate 1 AB28NACBEA 0.00% 0.000% ×7 001A2300088 Indoor fan 1 AB28NACBEA 0.02% 0.024% *8 001A1301752 pipe holder plate 1 AB28NACBEA 0.00% 0.000% ×9 001A1301751 Evaporator holded plate 1 AB28NACBEA 0.00% 0.000% ×
10 001A1301710 Fan in-built part 1 AB28NACBEA 0.00% 0.000% ×11 001A5102015 Flange screw nut 1 AB28NACBEA 0.00% 0.000% ×12 001A3900006 Pipe temp. sensor indoor 1 AB28NACBEA 0.00% 0.000% ×13 0010752919 liquid pipe assy. 1 AB28NACBEA 0.00% 0.000% ×14 0010700299 air pipe assy. 1 AB28NACBEA 0.00% 0.000% ×15 001A0100711 Pump Bracket assy. 1 AB28NACBEA 0.00% 0.000% ×16 001A1434920 Drainage pipe 1 AB28NACBEA 0.00% 0.000% ×17 0010450169 Water pump motor 1 AB28NACBEA 0.02% 0.024% *18 0010450154 Float Switch 1 AB28NACBEA 0.00% 0.000% ×19 0010752958 Evaporator assembly 1 AB28NACBEA 0.01% 0.012%20 001A1301750 Evaporator holder 2 AB28NACBEA 0.00% 0.000% ×21 001A0900089 Drain pan assy. 1 AB28NACBEA 0.00% 0.000% ×22 001A1301753 bottom plate of electrical box 1 AB28NACBEA 0.00% 0.000% ×23 001A1232305 Eletrical box 1 AB28NACBEA 0.00% 0.000% ×24 001A3600232 Fan motor capacitor 4.5 uf 1 AB28NACBEA 0.04% 0.048% *25 0010451265 Terminal block 1 AB28NACBEA 0.00% 0.000% ×26 0010451262 Transformer 1 AB28NACBEA 0.01% 0.012%27 0010451167 indoor PCB 1 AB28NACBEA 0.02% 0.024% *28 001A1232306 Electrical box cover 1 1 AB28NACBEA 0.00% 0.000% ×29 001A1232307 Electrical box cover2 1 AB28NACBEA 0.00% 0.000% ×30 001A1431661 inlet circle 1 AB28NACBEA 0.00% 0.000% ×31 001A3900159 environment temp. Sensor indoor 1 AB28NACBEA 0.00% 0.000% ×32 001A1301756 guarding grill 1 AB28NACBEA 0.00% 0.000% ×33 001A13001077 hoop 1 AB28NACBEA 0.00% 0.000% ×34 0010451255 Controller 1 AB28NACBEA 0.01% 0.012%35 001A1434574A Heat insulation pipe 1 1 AB28NACBEA 0.00% 0.000% ×36 001A1434925 Heat insulation pipe2 1 AB28NACBEA 0.00% 0.000% ×37 001A6645007 cable clamp 6 AB28NACBEA 0.00% 0.000% ×
Parts list
1,The failer rate and the proportion of the spare-part stock are regarded as the reference of the stock for spare-parts;The first time should be stocked accroded with the proportion of the spare-parts,and it should be adjustedwith the actual quantity 3 months later.
6.The spare parts price on net is FOB Qingdao term.
2,easy-damaged;The spare-part which is often damaged and the customer must stock in the spare-partswarehouse,and should be marked with"*"
3,possible damaged:The spare-part which is not often damaged like the easy damaged one and the customermay stock in the spare-part warehouse accord with the actual case,should be marked with " ".
4,not need provided :The spare-part which is seldom damaged or the maintenance man could notmaitmains.The spare parts may be air freighted by the factory if they were damaged.The customer nees notstock in the spare-part warehouse,should be marked with " x ".
5,Above should be improved accord with the reply of the market half a year per time.
No. Spare parts number Spare parts description in english Qty. ModelFailurerate
the proportion of thespare-part stock Remark
1 001A1231233 Inlet grill 1 AP242ACBEA 0.00% 0.000% ×2 001A1301502 Inlet grill insert 2 AP242ACBEA 0.00% 0.000% ×3 001A1231234 Front panel 1 AP242ACBEA 0.00% 0.000% ×4 0010450638 Operation panel 1 AP242ACBEA 0.00% 0.000% ×5 001A1432687 Horizontal blade 6 AP242ACBEA 0.00% 0.000% ×6 001A1734970 Vertical air outlet pad 2 AP242ACBEA 0.00% 0.000% ×7 001A0100357 Vertical blade 1 AP242ACBEA 0.00% 0.000% ×8 001A1734832 Air damper pad 1 AP242ACBEA 0.00% 0.000% ×9 001A1301508 Air damper 1 AP242ACBEA 0.00% 0.000% ×10 001A0400118 Heat exchanger assembly 1 AP242ACBEA 0.01% 0.012%11 001A1301440 Evaporator left mounting plate 1 AP242ACBEA 0.00% 0.000% ×12 001A1301441 Evaporator right mounting plate 1 AP242ACBEA 0.00% 0.000% ×13 0010150192 Left board 1 AP242ACBEA 0.00% 0.000% ×14 001A17341250 Left board pad 1 AP242ACBEA 0.00% 0.000% ×15 001A1231237 Top cover plate 1 AP242ACBEA 0.00% 0.000% ×16 001A1742836 Cover 1 AP242ACBEA 0.00% 0.000% ×17 001A1734023 Side board horizontal pad 1 AP242ACBEA 0.00% 0.000% ×18 0010150193 Right board 1 AP242ACBEA 0.00% 0.000% ×19 001A0100828 Back guard 1 AP242ACBEA 0.00% 0.000% ×20 001A1101145 Wiring plate 1 AP242ACBEA 0.00% 0.000% ×21 001A1734842 Thermal insulation pipe 1 AP242ACBEA 0.00% 0.000% ×22 001A5002078 Special nut 1 AP242ACBEA 0.00% 0.000% ×23 001A0100575 Bottom plate 1 AP242ACBEA 0.00% 0.000% ×24 001A1745106 Plastic cushion 1 AP242ACBEA 0.00% 0.000% ×25 0010402372 Motor 1 AP242ACBEA 0.02% 0.024% *26 001A5739020 Mounting wiring clamp 1 AP242ACBEA 0.00% 0.000% ×27 001A1101146 Pipe press plate 1 AP242ACBEA 0.00% 0.000% ×28 001A1752911 Cushion rubber 1 AP242ACBEA 0.00% 0.000% ×29 001A1452695 Cushion rubber 1 AP242ACBEA 0.00% 0.000% ×30 0010250163 Drain pan 1 AP242ACBEA 0.00% 0.000% ×31 001A1452695 Fan pad 1 AP242ACBEA 0.00% 0.000% ×32 001A5102050 Nut 1 AP242ACBEA 0.00% 0.000% ×33 001A2300062 Centrifugal fan 1 AP242ACBEA 0.02% 0.024% *34 001A1742931 Down shell press plate cushion 1 AP242ACBEA 0.00% 0.000% ×35 001A1301445 Down shell press plate 1 AP242ACBEA 0.00% 0.000% ×36 001A1431647 Wiring clamp (plasticizing) 1 AP242ACBEA 0.00% 0.000% ×
001A1301437 Reinforcing plate (left) 1 AP242ACBEA 0.00% 0.000% ×001A1301438 Reinforcing plate (right) 1 AP242ACBEA 0.00% 0.000% ×
38 0010200026 Air ring 1 AP242ACBEA 0.00% 0.000% ×39 001A0100385 Down shell 1 AP242ACBEA 0.00% 0.000% ×40 001A2400102 Filter 1 AP242ACBEA 0.00% 0.000% ×41 001A0100075 Lock 1 AP242ACBEA 0.00% 0.000% ×42 001A1734967 Sealing plate 1 AP242ACBEA 0.00% 0.000% ×43 001A17621241 Sealing plate 1 AP242ACBEA 0.00% 0.000% ×44 001A1757833 Cushion rubber 1 AP242ACBEA 0.00% 0.000% ×45 001A3000236 Synchro-motor 1 AP242ACBEA 0.02% 0.024% *46 001A1301448 Electric box cover 1 AP242ACBEA 0.00% 0.000% ×47 0010250201 Wire clamp 1 AP242ACBEA 0.00% 0.000% ×48 001A4000151 Terminal block 1 AP242ACBEA 0.00% 0.000% ×49 0010450450 Transformer 1 AP242ACBEA 0.01% 0.012%50 001A3600018 Fan capacitor 1 AP242ACBEA 0.04% 0.048% *51 001A1452695 Cushion rubber 1 AP242ACBEA 0.00% 0.000% ×52 0010400911 Indoor PCB 1 AP242ACBEA 0.02% 0.024% *53 / / AP242ACBEA54 001A13011074 Electric box 1 AP242ACBEA 0.00% 0.000% ×55 001A1301444 Fixing horizontal plate 1 AP242ACBEA 0.00% 0.000% ×56 001A1734967 Sealing cushion 1 AP242ACBEA 0.00% 0.000% ×57 001A1752840 Supporting pad 1 AP242ACBEA 0.00% 0.000% ×58 001A3800128 Pipe temp. sensor 1 AP242ACBEA 0.00% 0.000% ×59 001A0100407 Supporting plate assembly 1 AP242ACBEA 0.00% 0.000% ×
Parts list
37
13.Performance Curves 1 Cooling
When air conditioner operate on cooling status, the indoor air humid ball and outdoor air dry ball which means humid degree of indoor and dry degree of outdoor unit make important mean on cooling capacity. 1) Chart of humid ball of indoor unit air
℃
modify coefficient
2) Chart of dry ball of outdoor unit air
℃
modify coefficient
2 Heating
When air conditioner operate on heating status,the outdoor air humid ball and indoor air dry ball which means humid degree of outdoor and dry degree of indoor unit also make important mean on heating capacity. 1)Chart of humid ball of outdoor unit air
℃
modify coefficient
2)Chart of dry ball of indoor unit air
modify coefficient
℃
Model: AD28NAMBEA
PERFORMANCE CURVES
Cool capacity graph
0
2
4
6
8
10
12
-7 5 15 25 35 43
Outdoor DB( )
Cap
acity
(KW
) 20
22
25
27
30
32
Indoor
DB( )
EER graph
1
2
3
4
5
-7 5 15 25 35 43
Outdoor DB( )
EER
20
22
25
27
30
32
Indoor
DB( )
Heat capacity graph
4
5
6
7
8
9
10
11
12
-7 -5 0 7 10 15
Outdoor DB( )
Cap
acity
(KW
)
16
18
20
22
24
26
28
Indoor
DB( )
COP graph
1
2
3
4
-7 -5 0 7 10 15
Outdoor DB( )
CO
P
16
18
20
22
24
26
28
)
AC28NACBEA
PERFORMANCE CURVES
Cool capacity graph
0
2
4
6
8
10
12
-7 5 15 25 35 43
Outdoor DB( )
Cap
acity
(KW
) 20
22
25
27
30
32
Indoor
DB( )
EER graph
1
2
3
4
5
-7 5 15 25 35 43
Outdoor DB( )
EER
20
22
25
27
30
32
Indoor
DB( )
AB28NACBEA
EER graph
PERFORMANCE CURVES
0
2
4
6
8
10
12
-5 5 15 25 35 43
Outdoor DB( )
Cap
acity
(KW
) 20
22
25
27
30
32
Indoor
DB( )
1
2
3
4
5
-5 5 15 25 35 43
Outdoor DB( )
EER
20
22
25
27
30
32
Indoor
DB( )
Noise level charts
Model: AC28NACBEA
Air Velocity Distribution
CoolingBlowy angle:25
Temperature Distribution
CoolingBlowy angle:25
a. Cooling / Air Velocity Distribution
b. Cooling / Temperature Distribution
15.AIR VELOCITY DISTRIBUTION
0
2.4
5.5
25
0
2.4
22
27
5.5
Model: AB28NACBEA
Air Velocity Distribution
CoolingBlowy angle:40
Temperature Distribution
CoolingBlowy angle:40
a. Cooling / Air Velocity Distribution
b. Cooling / Temperature Distribution
4 2 1 0 1 20
4
m/s m/s 2
4 2 1
27
25
22
27
10 2
25
22
04
2
AIR VELOCITY DISTRIBUTION
AD28NAMBEA
cooling
coolingair discharge angle 5
Air Velocity distribution
Temperature distribution
0
1.8
2.4
0.5
5.5
air discharge angle 5
1.8
0
22
25
27
5.5
2.4
AIR VELOCITY DISTRIBUTION