Amazon VRF Products Overview

2

Product Lineup

3

Product LineupOffers Overview

T1 Mini VRF Outdoor T1/T3 Modular VRF Outdoor

Broad Indoor Offering

Note: The capacity mentioned in following pages is basically for cooling

Side Discharge Mini VRF Outdoor Units Dual Frequency 50/60Hz

DC Inverter Rotary Compressor

BLDC Fan ( BrushLess DC motor )

4

VProduct LineupT1 Mini VRF Outdoor Units

10kW

15/18kW

Note: 1hp is 2.8kW, 1TR is 3.52kW, and 1kW is 3.41kBtu/h

*: EER is W/W

Model NameNominalCapacity

kW

NominalCapacity

[TR]

CoolingEER/Heating COP

Power SupplyMax.

IndoorUnits

YV2VYH010KAR-D-X 10 3 3.14/4.39 220-230V/1Ph/50-60Hz 4YV2VYH015KAR-D-X 15 4 3.53/4.02 220-230V/1Ph/50-60Hz 8YV2VYH015KAS-D-X 15 4 3.17/4.16 380-400V/3Ph/50-60Hz 8YV2VYH018KAS-D-X 18 5 2.94/3.52 380-400V/3Ph/50-60Hz 9

Top Discharge Modular VRF Outdoor Units Dual Frequency 50/60Hz - 380V, 60Hz - 230V

DC Inverter Scroll Compressor & BLDC Fan

5 Basic Modular Units: 8hp, 10hp, 12hp, 14hp, 16hp

Free Combination Up to 48hp with incremental 2hp, max.

Indoor units up to 64

5

VProduct LineupT1 Modular VRF Outdoor Units

8/10hp

12/14/16hp

Note: 1hp is 2.8kW, 1TR is 3.52kW, and 1kW is 3.41kBtu/h*: EER/COP is W/W

Model NameNominalCapacity

hp

NominalCapacity

NominalCapacity

[TR]

CoolingEER/Heating COP

IEERBtu/W.h

Power SupplyMax.

IndoorUnits

YV2VYH022KAS-D-X 8 22.8kW 6 4.12/4.31 19.77 380-400V/3Ph/50-60Hz 13YV2VYH028KAS-D-X 10 28.9kW 8 3.97/4.12 18.91 380-400V/3Ph/50-60Hz 16YV2VYH033KAS-D-X 12 34.8kW 10 3.54/3.71 19.98 380-400V/3Ph/50-60Hz 19YV2VYH040KAS-D-X 14 41.5kW 11 3.70/3.95 19.37 380-400V/3Ph/50-60Hz 23YV2VYH045KAS-D-X 16 46.4kW 13 3.49/3.87 18.79 380-400V/3Ph/50-60Hz 26YV2VYH077BAH-D-X 8 81kBtu/h 6 4.21/4.40 20.15 220-230V/3Ph/60Hz 13YV2VYH096BAH-D-X 10 100kBtu/h 8 3.48/3.77 18.85 220-230V/3Ph/60Hz 16YV2VYH114BAH-D-X 12 120kBtu/h 10 3.48/3.87 19.61 220-230V/3Ph/60Hz 19YV2VYH137BAH-D-X 14 142kBtu/h 11 3.45/3.76 18.98 220-230V/3Ph/60Hz 23YV2VYH154BAH-D-X 16 153kBtu/h 13 3.22/3.53 18.33 220-230V/3Ph/60Hz 26

Top Discharge Modular VRF Outdoor Units Dual Frequency 50/60Hz

DC Inverter Scroll Compressor & BLDC Fan

3 Basic Modular Units: 8hp, 10hp, 12hp

Free Combination Up to 36hp with incremental 2hp, max.

Indoor units up to 36

High Ambient Operation Up to 52 ℃

6

VProduct LineupT3 Modular VRF Outdoor Units

8hp

10/12hp

Note: 1hp is 2.8kW, 1TR is 3.52kW, and 1kW is 3.41kBtu/h

*: EER/COP is W/W

Model NameNominalCapacity

hp

NominalCapacity

kW

NominalCapacity

[TR]

CoolingEER/Heating COP

IEERBtu/W.h

Power SupplyMax.

IndoorUnits

YV2VYH022KAS-D-X 8 23.2 7 3.58/4.33 20.50 380-400V/3Ph/50-60Hz 10YV2VYH028KAS-D-X 10 28.6 8 3.70/4.38 19.70 380-400V/3Ph/50-60Hz 13YV2VYH033KAS-D-X 12 35.2 10 3.76/4.28 19.76 380-400V/3Ph/50-60Hz 16

7

VProduct LineupIndoor Units – Ductless Type

220-230V/1Ph/50-60Hz Fit for All Outdoor Units

8

VProduct LineupIndoor Units – Ducted Type

220-230V/1Ph/50-60Hz Fit for All Outdoor Units

Note: HRV has air flow as its capacity

Capacity kBtu/h 7.5 9.5 12.3 15.3 19.1 24.2 27.3 30.7 38.2 47.7 77.1 95.5

Capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 22.6 28.0

Low Static PressureSlim Duct 185mm

(0/20Pa)

Low Static PressureDuct (0/20Pa)

Medium StaticPressure Duct

(50/96Pa)

Medium StaticPressure Duct

(80/120Pa)

Heat RecoveryVentilator

(CMH/CFM)

150/88

260/153

800/471

1000/588

Product Family

High Static PressureDuct (100-196Pa)

Fresh Air Unit

9

Broad Indoor Offering

Global Exclusive Front

Stylish Design & LED Display

Built in EEV & Easy to Installation

Without Built-in Drain Pump & Not Available for External Drain Pump

Vitamin C and ESF

Filter Optional

6 Models Ranging from 2.2kW to 7.1kW

10

VIndoor FeaturesHigh Wall

2.2/2.8/3.6/.4.5kW

5.6/7.1kW

Model NameNominalCapacity

kW

NominalCapacity[kBTU/h]

Power SupplyDimension (mm)

W*H*D

YVHVXH022WAR--FX 2.2 8 220-230V/1Ph/50-60Hz 938*265*187YVHVXH028WAR--FX 2.8 10 220-230V/1Ph/50-60Hz 938*265*187YVHVXH036WAR--FX 3.6 12 220-230V/1Ph/50-60Hz 938*265*187YVHVXH045WAR--FX 4.5 15 220-230V/1Ph/50-60Hz 938*265*187YVHVXH056WAR--FX 5.6 19 220-230V/1Ph/50-60Hz 1046*299*239YVHVXH071WAR--FX 7.1 24 220-230V/1Ph/50-60Hz 1046*299*239

Compact Design

280mm Ultra Thin Body

Two Way Air Flow

Quite Operation

Built in High Head Drain Pump

4 Models Ranging from 2.8kW to 5.6kW

11

VIndoor FeaturesTwo Way Cassette

2.8/3.6/.4.5/5.6kW

Model NameNominalCapacity

kW

NominalCapacity[kBTU/h]

Power SupplyDimension (mm)

W*H*D

Panel Dimension(MM)

W*H*D

YV8VXH028WAR--GX 2.8 10 220-230V/1Ph/50-60Hz 817*280*620 1055*80*680YV8VXH036WAR--GX 3.6 12 220-230V/1Ph/50-60Hz 817*280*620 1055*80*680YV8VXH045WAR--GX 4.5 15 220-230V/1Ph/50-60Hz 817*280*620 1055*80*680YV8VXH056WAR--GX 5.6 19 220-230V/1Ph/50-60Hz 817*280*620 1055*80*680

Compact Design, 570mm*570mm Installation Size

Quite Operation

Built in High Head Drain Pump

5~10% Fresh Air Inlet Except for 5.6/7.1/8.0 kW

Branch Outlet Except for 2.8/3.6/4.5kW

9 Models Ranging from 2.8kW to 14kW

12

VIndoor FeaturesFour Way Cassette

2.8/3.6/.4.5kW(Compact)

5.6/7.1/8.0kW

9.0/12/14kW

Model NameNominalCapacity

kW

NominalCapacity[kBTU/h]

Power SupplyDimension (mm)

W*H*D

Panel Dimension(MM)

W*H*D

YVKVXH028WAR--GX 2.8 10 220-230V/1Ph/50-60Hz 570*260*570 700*60*700YVKVXH036WAR--GX 3.6 12 220-230V/1Ph/50-60Hz 570*260*570 700*60*700YVKVXH045WAR--GX 4.5 15 220-230V/1Ph/50-60Hz 570*260*570 700*60*700YVKVXH056WAR--GX 5.6 19 220-230V/1Ph/50-60Hz 840*240*840 950*80*950YVKVXH071WAR--GX 7.1 24 220-230V/1Ph/50-60Hz 840*240*840 950*80*950YVKVXH080WAR--GX 8 27 220-230V/1Ph/50-60Hz 840*240*840 950*80*950YVKVXH090WAR--GX 9 31 220-230V/1Ph/50-60Hz 840*295*840 950*80*950YVKVXH112WAR--GX 12 38 220-230V/1Ph/50-60Hz 840*295*840 950*80*950YVKVXH140WAR--GX 14 48 220-230V/1Ph/50-60Hz 840*295*840 950*80*950

Compact Design & Small Space Occupation

Quite Operation

Air Discharge through Top(Cooling) or Bottom(Heating)

Without Built-in Drain Pump & Not Available for External Drain Pump

4 Models Ranging from 2.2kW to 5.6kW

13

VIndoor FeaturesConsole

2.2/2.8/3.6/5.6kWModel Name

NominalCapacity

kW

NominalCapacity[kBTU/h]

Power SupplyDimension (mm)

W*H*D

YV5VXH022WAR--FX 2.2 8 220-230V/1Ph/50-60Hz 720*640*255YV5VXH028WAR--FX 2.8 10 220-230V/1Ph/50-60Hz 720*640*255YV5VXH036WAR--FX 3.6 12 220-230V/1Ph/50-60Hz 720*640*255YV5VXH056WAR--FX 5.6 19 220-230V/1Ph/50-60Hz 720*640*255

Compact Design

Quite Operation

Wide Range Angle Air Flow

ESF Filter Optional

9 Models Ranging from 2.8kW to 14kW

14

VIndoor FeaturesFloor Ceiling

2.8/3.6/4.5/5.6/7.1kWUltra Thin Unit Body 199mm

8.0/9.0/11.2/14kW

Model NameNominalCapacity

kW

NominalCapacity[kBTU/h]

Power SupplyDimension (mm)

W*H*D

YVFVXH028WAR--GX 2.8 10 220-230V/1Ph/50-60Hz 990*655*199YVFVXH036WAR--GX 3.6 12 220-230V/1Ph/50-60Hz 990*655*199YVFVXH045WAR--GX 4.5 15 220-230V/1Ph/50-60Hz 990*655*199YVFVXH056WAR--GX 5.6 19 220-230V/1Ph/50-60Hz 990*655*199YVFVXH071WAR--GX 7.1 24 220-230V/1Ph/50-60Hz 990*655*199YVFVXH080WAR--GX 8 27 220-230V/1Ph/50-60Hz 1298*700*240 YVFVXH090WAR--GX 9 31 220-230V/1Ph/50-60Hz 1298*700*240 YVFVXH112WAR--GX 11.2 38 220-230V/1Ph/50-60Hz 1580*700*240YVFVXH140WAR--GX 14 48 220-230V/1Ph/50-60Hz 1580*700*240

185mm Height Ultra Thin Design

Built in Drain Pump

Bottom or Rear Air Return

Install With or Without Discharge & Return Plenum

Static Pressure Setting 0/30Pa

6 Models Ranging from 2.2kW to 7.1kW

15

VIndoor FeaturesSlim Low Static Pressure Duct

2.2/2.8/3.6kW

4.5/5.6/7.1kW

Model NameNominalCapacity

kW

NominalCapacity[kBTU/h]

Power SupplyDimension (mm)

W*H*D

YV3VXH022WAR--GX 2.2 8 220-230V/1Ph/50-60Hz 610*185*500YV3VXH028WAR--GX 2.8 10 220-230V/1Ph/50-60Hz 610*185*500YV3VXH036WAR--GX 3.6 12 220-230V/1Ph/50-60Hz 610*185*500YV3VXH045WAR--GX 4.5 15 220-230V/1Ph/50-60Hz 1105*185*500YV3VXH056WAR--GX 5.6 19 220-230V/1Ph/50-60Hz 1105*185*500YV3VXH071WAR--GX 7.1 24 220-230V/1Ph/50-60Hz 1105*185*500

220mm Height Ultra Thin Design

Optional External Drain Pump

Bottom or Rear Air Return

Install With or Without Discharge & Return Plenum

Knock Down Coil From Bottom

Static Pressure Setting 0/20Pa

6 Models Ranging from 2.2kW to 7.1kW

16

VIndoor FeaturesLow Static Pressure Duct

2.2/2.8/3.6kW

4.5/5.6/7.1kW

Model NameNominalCapacity

kW

NominalCapacity[kBTU/h]

Power SupplyDimension (mm)

W*H*D

YVDVXH022WAR--GX 2.2 8 220-230V/1Ph/50-60Hz 610*220*500YVDVXH028WAR--GX 2.8 10 220-230V/1Ph/50-60Hz 610*220*500YVDVXH036WAR--GX 3.6 12 220-230V/1Ph/50-60Hz 610*220*500YVDVXH045WAR--GX 4.5 15 220-230V/1Ph/50-60Hz 1105*220*500YVDVXH056WAR--GX 5.6 19 220-230V/1Ph/50-60Hz 1105*220*500YVDVXH071WAR--GX 7.1 24 220-230V/1Ph/50-60Hz 1105*220*500

Built in Drain Pump for 5.6/7.1/8.0kW

Optional External Drain Pump for 9.0/11.2/14kW

Rear Air Return with Plenum

Flexible Discharge Duct Connection

Static Pressure Setting 50/96Pa or 80/120Pa

6 Models Ranging from 5.6kW to 14kW

17

VIndoor FeaturesMedium Static Pressure Duct

5.6/7.1/8.0kW50/96Pa

9.0/11.2/14kW80/120Pa

Model NameNominalCapacity

kW

NominalCapacity[kBTU/h]

Power SupplyDimension (mm)

W*H*D

YVEVXH056WAR--GX 5.6 19 220-230V/1Ph/50-60Hz 990*300*655YVEVXH071WAR--GX 7.1 24 220-230V/1Ph/50-60Hz 990*300*655YVEVXH080WAR--GX 8 27 220-230V/1Ph/50-60Hz 990*300*655YVEVXH090WAR--GX 9 31 220-230V/1Ph/50-60Hz 1135*270*742YVEVXH112WAR--GX 11.2 38 220-230V/1Ph/50-60Hz 1135*270*742YVEVXH140WAR--GX 14 48 220-230V/1Ph/50-60Hz 1135*270*742

Optional External Drain Pump

Rear Air Return With Plenum

Flexible Discharge Duct Connection

Static Pressure Setting 100/196Pa

8 Models Ranging from 5.6kW to 28kW

18

VIndoor FeaturesHigh Static Pressure Duct

5.6/7.1/8.0kW

22.6/28kW

9.0/11.2/14kW

Model NameNominalCapacity

kW

NominalCapacity[kBTU/h]

Power SupplyDimension (mm)

W*H*D

YVGVXH056WAR--GX 5.6 19 220-230V/1Ph/50-60Hz 970*360*875YVGVXH071WAR--GX 7.1 24 220-230V/1Ph/50-60Hz 970*360*875YVGVXH080WAR--GX 8 27 220-230V/1Ph/50-60Hz 970*360*875YVGVXH090WAR--GX 9 31 220-230V/1Ph/50-60Hz 1350*360*875YVGVXH112WAR--GX 11.2 38 220-230V/1Ph/50-60Hz 1350*360*875YVGVXH140WAR--GX 14 48 220-230V/1Ph/50-60Hz 1350*360*875YVGVXH226WAR--GX 22.6 77 220-230V/1Ph/50-60Hz 1610*360*840YVGVXH280WAR--GX 28 96 220-230V/1Ph/50-60Hz 1610*360*840

Install with Other Indoor Units Together

Static Pressure 100Pa

Operation Range -5~43 ℃

Installed Capacity Must Less Than 30% of Outdoor Units

3 Models Ranging from 14kW to 28kW

19

VIndoor FeaturesFresh Air Unit

14kW100~180Pa

22.6/28kW100~200Pa

Model NameNominalCapacity

kW

NominalCapacity[kBTU/h]

Power SupplyDimension (mm)

W*H*D

YV4VXH140WAR--GX 14 48 220-230V/1Ph/50-60Hz 1350*360*875YV4VXH226WAR--GX 22.6 77 220-230V/1Ph/50-60Hz 1750*360*840YV4VXH280WAR--GX 28 96 220-230V/1Ph/50-60Hz 1750*360*840

Efficient Heat Recovery Air Processing

Heat Recovery Media Element

Is Replacement As Spare part

4 Models Ranging from

150CMH to 1000CMH

20

VIndoor FeaturesHeat Recovery Ventilator

Warm, Exhaust Air from Inside

Pre-heatedFresh Air to Inside

Fresh Air From Outside

Exhaust Airto Outside

Illustration of how it works

Model NameNominalCapacity

CMH

NominalCapacity

CFMPower Supply

Dimension (mm)W*H*D

YV6VXH015CAR--GX 150 88 220-230V/1Ph/50-60Hz 940**276*685YV6VXH026CAR--GX 260 153 220-230V/1Ph/50-60Hz 1750*360*840YV6VXH080CAR--GX 800 471 220-230V/1Ph/50-60Hz 1227*387*1115YV6VXH100CAR--GX 1000 588 220-230V/1Ph/50-60Hz 1227*387*1115

21

Features & Benefits

22

Features & BenefitsOverview

Five Star FeaturesEnergy

Efficient

Broad and Flexible Indoor

Offering

Reliable Accurate

Temperature Control

Modular and

Compact Design

- Saves Energy

- HealthyEnvironment

- Low OperationCosts

Comfortable -Environment

Easy to Transport -And Install

23

180°vector dc inverter drive technology High precision control, variable frequency drive from 20 to180Hz

Sine wave current drive, efficiency improve 17% comparing to conventional rectangle wave

Inverter module equipped with heat dissipating fan, enhancing compressor reliability

Features & BenefitsEnergy Efficient

Conventional Drive Control 180° Vector Drive Control

24

High efficiency heat exchanging technology

Outdoor high efficiency four way air return heat exchanger design

The compressor and condenser are placed in separated chamber

High efficiency heat exchanger design

Efficient φ8 inner grooved tube and 0.11 hydrophilic aluminum coil fin, corrosion and oxidation resistance treatment

Features & BenefitsEnergy Efficient

25

High efficiency DC Inverter Scroll Compressor

DC Inverter Scroll Compressor from Mitsubishi Electric

Equipped with a “Frame Compliance Mechanism” that allows movement in the axial direction of the frame supporting the cradle scroll. This greatly reduces both leakage and friction loss, ensuring very high efficiency throughout the whole speed range

Features & BenefitsEnergy Efficient

26

64 stage speed adjustment DC Fan Motor

Efficiency increase 45% comparing with AC motor and power input largely decrease

64 stage speed adjustment plus DC inverter drive, stabilizing compressor discharge pressure and suction pressure to ensure high system reliability

Features & BenefitsEnergy Efficient

27

Two stage deep sub cooling technology

1st stage sub cooling added a sub cooling coil to Condenser

2nd stage sub cooling added a stand alone Sub Cooler

After further cooling, sub-cooling degree can be up to 30℃ , with the heat exchanging capacity per unit mass of refrigerant improved by 46% and flow resistance reduced by 55%, and running efficiency improved by 9%

Features & BenefitsEnergy Efficient

Condenser

1st Stage

2nd Stage

28

Patent flow channel design

Special design of streamline fan , airflow improved by 17.5%, noise reduced 3dB/A compare to previous product

The new fan reduce air loss and increase heat exchange efficiency

Features & BenefitsEnergy Efficient

29

100% Independent Fresh Air System

Fresh air unit can be installed with other indoor units, and introduce the outdoor fresh air into indoor

Features & BenefitsHealthy Environment

30

3-in-1 High Efficient ESF Filter

Effectively purifying indoor air by trapping harmful dust and removing unpleasant odors

Features & BenefitsHealthy Environment

Note: ESF filter is only optional for High Wall and Floor Ceiling

31

The first 2-stages oil separation and cross oil return technology in the industry – Inside module 1st stage oil separation: built-in oil separating unit ,greatly reduced the oil from the

compressor discharge

2nd stage oil separation: external oil separator to separate the small amount oil from discharge

Cross oil return: on the one hand to ensure the own compressor oil (red line) ,on the other hand to supply the redundant oil to other compressor (blue line)

Features & Benefits Reliable

Inverter Compressor

Oil Separator

Fixed Compressor

32

High pressure difference oil equalization – Among modules

Using the pressure difference between suction and discharge ,to realize fast oil balance between module

Cycle every 15 minutes

Features & Benefits Reliable

CompressorSuction Line

Separator

33

Duty cycle operation to extend the system lifetime (combination model)

The outdoor units operating changes every 24 hours

Outdoor units start in turn and operation time can be balanced

Inverter compressor lifetime can be extend maximum 3 times

Features & Benefits Reliable

First time operation Second time operation Third time operation

1 2 3 3 1 2 2 3 1

34

Backup operation

If one outdoor unit get into malfunction, the other units continue to operate without affecting the whole system

Features & Benefits Reliable

35

Low noise and Night silent running

Machinery chamber is separated from air supply chamber; built-in high efficient muffler in the machinery chamber greatly reduce the compressor noise

The night silent running function can be set on the outdoor PCB. The noise can be reduced by 8 dB/A at most

Features & BenefitsComfortable Environment

Note: The night silent mode has to be turn on and off manually

36

Intelligent defrost Conventional defrost control(left) heating operation after all the outdoor finish the

defrost

Amazon outdoor defrosting(right) help each other to accelerate defrosting, not only accelerate defrosting speed, but also reach rapid heating

Features & Benefits Comfortable Environment

Defrost rapidly Defrost clean

Heat support

Module 1

Module 2

Module 3

Indoor temperature fluctuations small

Condenser heat absorption

Condenser heat dissipation

37

Precise temperature control

DC inverter control, temperature could be controlled precisely within range of ±0.5℃

Features & Benefits Comfortable Environment

38

Easy transportation

Outdoor footprint only occupy 0.74m^2(8/10hp) and 1.04m^2 (12/14/16hp)

Can lift with elevators and save lots of transport cost and time

Features & BenefitsModular & Compact Design

39

Flexible installation

Long pipe length and large drop

Total 300m liquid refrigerant piping length

Max.175m refrigerant piping length for single way

Max.50m height drop when outdoor unit is above indoor unit

Max.40m height drop when outdoor unit is below indoor unit

Max.15m height drop between indoor units under same outdoor unit

Features & Benefits Modular & Compact Design

40

Outdoor high external static pressure

Up to 50Pa and can be installed at different floors

Features & Benefits Modular & Compact Design

50Pa ESP

41

Controllers and BMS

42

Controllers and BMSSolutions Overview

Stand Alone Controllers Central Controllers

BacNet ConverterLonWorks Converter

Stand Alone Controllers Auto/Cool/Dry/Heat/Fan Mode Setting

Auto/Low/Mid/High Fan Speed Setting

Temperature Setting

Clock and Timer Setting

Central Controllers Group Control & Unit Control

Weekly and Monthly Timer Management

Power Metering, System Running Recording and Report

BMS Converters BMS Integration

Group Control & Unit Control

Failure Code Display, System Running Recording and Report

Remote Monitoring

43

VControllers & BMSFunctions Overview

Wireless Controller LCD Display

Standard offer for High Wall and Console Units

Optional for Duct, Cassette and Floor Ceiling Units

Wired Controller LCD Display

Standard offer for Duct, Cassette, Floor Ceiling,

and Fresh Air Units

Not optional for High Wall and Console Units

Can also work as a group controller controlling up

to 16 indoor units

44

VControllers & BMSIndividual Controllers

45

VControllers & BMSTouch Screen Central Controller

IGU05Protocol Translator

Max.64 indoor units under one IGU05(one modular or combination outdoor system)

YCZ-A003Touch Screen Central Controller

Max

. 32

un

its

of

IGU

05

No.1

No..2

No..32

220-240V/1/50-60Hz

Touch Screen Central Controller can control up to 128 indoor units

No.1 No..2 No..64

RS

-485

max

. 10

00m

Note: (number of IGU05) x (number of indoor units under each IGU05)should be no more than 128

46

VControllers & BMSCentral Controller With Monitor Software

IGU02Protocol Translator

Max

. 32

un

its

of

IGU

02

No.1

No..2

No..32

Central Controller With Monitor Software can control up to 400 indoor units

No.1 No..2 No..40

RS

-485

max

. 10

00m

RS

-232

or

US

B

HCM-01Central Controller With Monitor Software

Monitor Software

Ammeter

Ammeter

Ammeter

Max.40 indoor units under one IGU02(one modular or combination outdoor system)

Note: (number of IGU02) x (number of indoor units under each IGU02)should be no more than 400

47

VControllers & BMSLonWorks

IGU06Protocol Translator

LonWorks Converter can control up to 32 indoor units

No.1 No..2 No..32

RS

-485

max

. 10

00m

Lo

nW

ork

s

IGU07 LonWorks Converter

JCI Net Control Engine

Note:1. One LonWorks IG07 Converter can Only work with ONE Protocol Translator IGU062. Please use LonTalk Card U10(75010R) to commissioning NCE & IGU073. Please buy U10(75010R) locally from Echelon, suggestOne branch office getting one Card

JCIMetasys

TC

P/

IP

Max.32 indoor units under one IGU06(one modular or combination outdoor system)

U10(75010R) LonTalk Card

48

VControllers & BMSBacNet/IP

IGU02Protocol Translator

Max

. 20

un

its

o

f IG

U02

No.1

No..2

No..20

BaNet/IP Converter can control up to 72 indoor units

No.1 No..2 No..40

RS

-485

max

. 10

00m

fo

r ea

ch

gro

up

Bac

Net

/IP

HCM-03 BacNet/IP Converter

Ammeter

Ammeter

Ammeter

JCIMetasys

TC

P/

IP

JCI Net Control Engine

Note: (number of IGU02) x (number of indoor units under each IGU02)should be no more than 72