Post on 25-Feb-2016
description
transcript
Citect SCADA PricingSynergist SCADA Inc
Version 1.4 – October 3, 2012
Synergist SCADA INCwww.SynergistSCADA.com 1
#1 Rule:Always work with your local Schneider Sales Representative to properly price and license your Vijeo Citect SCADA licenses
2
USB License Keys• Contain License CALs “Client Access Licenses”• CALs are shared across the network to any server that require
it• Typical CALS:
• Full License• Required to run an IO / Alarm / Report / Trend server • Includes 1 client license which can run locally on the server
(Or can be used by another computer if the Computer Setup Wizard Full License box is checked)
• Client • Control Client• View Only Client• Web / Internet Control Client• Web / Internet View Only Client
3
SCADA Point Count• Maximum number of runtime variable tags that can be used
by your system
• Memory or Disk variable do NOT count against your points
4
Citect’s “Dynamic” Point Count• Citect / Vijeo Citect 7.0 and higher use a “dynamic-point
licensing” model (See Knowledgebase article Q4939 ) • Citect uses the Dynamic Runtime count of all tags used
• Alarms• Trends• Reports• Events• Page Tags• Super Genies• TagRead() and TagWrite() Cicode functions• DDE, OPC, ODBC, ADO or the CTAPI (Historian)
5
Dynamic Runtime Count
Variable count != Point count• 1200 Variable Tags defined in your project may not require a
1200 point license.• The runtime Dynamic point count in your project is often
much lower than your total variable count.
6
!WARNING:If the Runtime Dynamic Point Count is ever greater than the license’s point count, a license error will occur and Citect will shutdown.
Version Licensing Changes• V2.0 - V6.10
• V7.0, V7.10, V7.20
• V7.3+
Dynamic Runtime Count
Static Tag Count Compile Time
Sum of Dynamic Runtime Count of Each Process
Dynamic Runtime Count 7
Tag Count in Citect 7.3+
•No more “Double Point” counting in multi-process mode
•Tags shared by different processes in multi-process mode will now be only counted once
8
Viewing The Dynamic Count • Using the Citect Kernel’s “General” View you can see the
current Dynamic count (you may need to resize the window)
9
Helpful Citect.ini Parameters• [General]WatermarkedPointCount
Enables displaying of “watermark messages” when the dynamic point count reaches the limit set points
• [General]PointCountHighPercentage at which “watermark message” will be displayed
• [General]PointCountHighHighPercentage at which a 2nd “watermark message” will be displayed
• [General]PointLimitMsgDetermine weather Citect will stop the point limit from being exceeded or simply shutdown. 10
*DISABLED BY DEFAULT
Citect CAL License Types
• Full Licenses• Control Client Licenses• Web Control Client Licenses• View-Only Client Licenses• Web View-Only Client Licenses• Speciality Drivers• Historian• Ampla
11
Full Licenses
• Full Licenses• A Full license is a scalable HMI/SCADA system
that can be used across all industries. It provides users and Integrators a fullyfeatured, flexible HMI/SCADA system that includes over 100 drivers.
12
How Citect Validates a License
13
CAL exists
SCADA Points
VALIDLICENSE
Example License Key • SCADA Point Count 42,000• CALs for 1x Full Licenses, 1x Control Client, 1x View Only Client
…
14
1 Full + Dongle key Per Server• Each Physically Separated Server will Require 1 Full License
4 Servers = 4 Dongle Keys with 4 full licenses15
4 Full Licenses1 Display
Client41,392
IO POINTS
42,000SCADA POINT
COUNT
=
Required License Key• Here is the required license key for 41,392 points, 4 Servers
and 1 Control Client We will need 4 licenses with this configuration
16
X 4
Client Licenses• Clients typically retrieve their licenses from the IO Server’s
license key
17
1 Full License
With 6 Client CALs
42,000SCADA POINT
COUNT
38,832 IO POINTS
Required License Key• Here is the required license key for 38,832 points, 1 Server and
6 Control Client We only have 1 server so we only need 1 key with 6 client CALs
18
Software Keys• In Citect / Vijeo Citect 7.30 we now have the option of using
Software keys• Please contact your local Schneider Sales Representative for
more details.
19
Pricing Citect Licensing• Three Components to Citect Licenses:
•Support Units•License Price•USB Key Price
20
Support Units
Listed next to the license price of all software is a “Support Unit”. Multiply the support units by the associated dollar support level price.
21
SUPPORT UNIT X UNIT COST
Support Unit Types
• Silver• Citect Upgrades Not Provided
• Gold• Upgrades Provided • Day time support only
• Gold Plus• Upgrades Provided• 24 / 7 Support
22
Support Unit Part Numbers
• VJC = Vijeo Citect SCADA• CIT = Citect SCADA
23
Support Type PriceCitect / VijeoCitect Part Numbers Historian Part Numbers Facilities Part Number
Silver $ XXX109102 VJH109102 CIT109139Gold $$ XXX109103 VJH109103 CIT109125GoldPlus $$$ XXX109138 VJH109130 CIT109126
Support Unit Part Example
•1500 Point Full License Citect SCADA
•Gold Plus Support
24
Sample Support Unit Calculation
25
$$$
$
Solution Support Unit Calculation
26
84 Support UnitsX
$ per Gold Plus Unit
Single Key Version Upgrade Only
• Allows the customer to do a one-time upgrade to the latest version and does not include access to the website or Technical Support Engineers.
• The upgrade only can be purchased on an individual key but must purchase upgrade for all licenses on the key.
27
Support Reinstatement
• If a site has expired more than 3 months then a reinstatement fee applies. This is because upgrades are included in the Gold or GoldPlus Support Offerings.
• In addition, the first year of Gold or GoldPlus Support must be purchased and then the new support dates will be valid a year from purchase date.
28
Citect SCADA License Example
• 1500 Point Full License Citect SCADA
29
$$$
USB Key Example
30
Citect License Total Estimate Example
• 1500 Point Full License Citect SCADA• Gold Plus Support• USB License Key
31
Citect License Total Calculation
32
$$$
$
Citect License Total Solution
•$ X 84 Gold Plus Support•$$$ License•$ USB Key
•$$$$$$ Total 33
Citect License Example #2
• New Vijeo Citect Customer purchasing a 1,500 point Full
• 2 floating View-Only Clients• 1 year of GoldPlus support • USB License Key
34
Citect License Example #2 Solution
35
Citect Example #3 Multi-Key Order Example
• New CitectSCADA Customer purchasing an Unlimited point Full
• Redundant Full license, • 1 Web View-Only Clients, • 1 Redundant Web View-Only Clients• 2 stand alone Unlimited Control Clients• Software key packs (USB)
36
Citect Multi-Key #3 Solution
37