CO1224TCarbon MonoxideDetectorwith RealTest™ Technology

The System Sensor CO1224T CO detector provides early

warning by using electrochemical sensing technology

to measure carbon monoxide levels in the air.

FeaturesRealTest• ™technologyallowsinstallertotestdetectorwithCOgas

FullcompliancewithUL2075•

Acoderequiredtroublerelay•

WiringsupervisionwithSEMSterminals•

Asixyearend-of-lifetimer•

12/24VDC•

Acurrentdrawof20mAinstandbyand40mAinalarm•

Versatilemountingforwallandceiling•

Electrochemicalsensingtechnology•

With RealTest™ technology, theCOgassensingcelloftheCO1224TCOdetectorcanbetestedusingacarbonmonoxidegasagent.Simplyholdthetestbuttonfortwoseconds.Afterthealarmcycle(temp4)thegreenLEDwillflashaboutoncepersecond,indicatingthatthedetectorisreadytoacceptCOfortesting.SprayasmallamountofCOintothedetectorpertheinstallationinstructions,andwithinsecondsthedetectorwillalarm,indicatingsuccessfulgasentry.

Ifdangerousamountsofcarbonmonoxideisdetected,theCO1224Tdetectorwillalertresidentsbysoundingandflashingatemp-4signalalarm.Protectionisguaranteed24/7byacentralstation,regardlessofwhetherresidentsareawayfromhome,sleepingoralreadysufferingfromtheeffectsofCO.

Thisspecificdeviceisdesignedforsystemoperation.ThedetectorisfullylistedtoUL2075.Itoffersacoderequiredtroublerelaytosendasensorfailureorend-of-lifesignaltothecontrolpanelandthecentralstation.ItalsousesSEMS-typeterminalPhilipsheadscrewstoprovideaquickerandmorepositivewiringconnectionandcoderequiredwiringsupervision.TheCO1224Tdetectoroffersalowcurrentdraw,allowingmoredevicestobeconnectedtothepanelwithouthavingtopurchaseamoreexpensivepaneloranextrapowersupply.

TheCO1224Tmodelwilloperateonmostindustrysecurityandfirealarmcontrolpanelsbecauseitisisa12/24VDCdetector.

2075

3825OhioAvenue•St.Charles,IL60174Phone:800-SENSOR2•Fax:630-377-6495

©2008SystemSensor.Productspecificationssubjecttochangewithoutnotice.Visitsystemsensor.comfor

currentproductinformation,includingthelatestversionofthisdatasheet.A05-0437-000•8/08•#1953

Ordering InformationPart No. DescriptionCO1224T 12/24volt,4-wiresystem-monitoredcarbonmonoxidedetectorwithRealTest™Technology

CO1224T Carbon Monoxide Detector SpecificationsArchitectural/Engineering SpecificationsCarbonmonoxidedetectorshallbeaSystemSensormodelnumberCO1224T,listedtoUnderwritersLaboratoriesUL2075forGasandVaporDetectorsandSensors.Thedetectorshallbeequippedwithasounderandatroublerelay.Thedetector’sbaseshallbeabletomounttoasingle-gangelectricalboxordirect(surface)mounttothewallorceiling.WiringconnectionsshallbemadebymeansofSEMSscrews.ThedetectorshallprovidedualcolorLEDindication,whichblinkstoindicatenormalstandby,alarm,orend-of-life.Whenthesensorsupervisionisinatroublecondition,thedetectorshallsendatroublesignaltothepanel.Whenthedetectorgivesatroubleorend-of-lifesignal,thedetectorshallbereplaced.ThedetectorshallprovideameanstotestCOgasentryintotheCOsensingcell.ThedetectorshallprovidethiswithatestmodethatacceptsCOgasfromatestagentandalarmsimmediatelyuponsensingCOentry.

Electrical SpecificationsOperating Voltage 12/24VDC

Audible Signal 85dBinalarm

Standby Current 20mA

Alarm Current 40mA(75mAtest)

Alarm Contact Ratings 0.5A@30VDC

Trouble Contact Ratings 0.5A@30VDC

Physical SpecificationsSize Length:5.1in,Width:3.3in,Height:1.3in

Approximate Weight 7oz

Operating Temperature Range 32°Fto104°F(0°Cto40°C)

Operating Humidity Range 22to90%RH

Input Terminals 14to22AWG

Mounting Single-gangbackbox;surfacemounttowallorceiling

Operation ModesOperation Mode Green LED Red LED Sounder

Normal(standby) Blink1perminute — —

Alarm — Blinkintemp4pattern Soundintemp4pattern

RealTest™Feature: TheSystemSensorCO1224TcarbonmonoxidedetectorwithRealTest™canevaluatethefunctionalityoftheCOsensingcellusingcannedtestagent.

NOTE:CheckwithlocalcodesandtheAHJtodeterminewhetherornotafunctionalgastestisdesiredforaninstallation.

HushFeature: PushingtheTest/Hushbuttonwillsilencethesounderfor5minutes(exceptinRealTestmode).TroubleFeature: Whenthedetectorisinatroublecondition,itwillsendatroublesignaltothepanel.End-of-lifeTimer: Afterthedetector’sinternalsensorhasreachedtheendofitslife,atroublesignalwillbesenttothepanel.Thiswillindicatethatitis

timetoreplacethedetector.Anelectrochemicalcarbonmonoxidedetectorlifespanisapproximatelysixyears,andthedetectormustbereplacedbythedatemarkedontheinsideoftheproduct.

1. 2. 3.

PushandholdtheTest/HushbuttonfortwosecondstoenterRealTestmode.ThegreenLEDwillflashonceeverysecondtoindicateRealTestmodehasstarted.

SpraycannedCOagentintothedetector. VerifyCOsensingatthecontrolpanel.ThedetectorwillautomaticallyexitRealTestalarmmodeafterabout20-60seconds.