COOLING AND VENTILATION IN THE TUNNEL

Post on 06-Jan-2016

93 views 3 download

Tags:

description

CLIC WORKSHOP - 2008. COOLING AND VENTILATION IN THE TUNNEL. J. Inigo-Golfin - C. Martel CERN TS/CV Wednesday 15 th October 2008. CLIC WORKSHOP - 2008. This is a preliminary study. Some concepts are presented based on estimated values to be confirmed. - PowerPoint PPT Presentation

transcript

COOLING AND VENTILATION

IN THE TUNNEL

J. Inigo-Golfin - C. MartelCERN TS/CV

Wednesday 15th October 2008

CLIC WORKSHOP - 2008

- Ventilation functions- Heat load levels- HVAC principle - Tunnel section- Safety - Equipment - Perspectives

Ventilation

- Water cooling requirements- Fluid circuits - Cooling principle - Main cooling station- Tunnel section. Piping- Equipment - Perspectives

Cooling

This is a preliminary study. Some concepts are presented based on estimated values to be confirmed.

The confirmation of rate air/water is still standing.

CLIC WORKSHOP - 2008

- Fresh air for people and ventilation (obligation).- Requested ambient conditions (T°C and humidity).- Remove heat loads in the air.- Prevent from any air stratification, condensation. - Purge before access.- Smoke or gas extraction (obligation).- Overpressure control linked to radiation (obligation).

Tunnel ventilation functions

CLIC WORKSHOP - Ventilation

INJ ECTORLINACS

MAIN BEAMS

DRIVE BEAMS

5 3 1

PHASE 1

90 kW

250 kW

200 kW

Heat loads in the air

Heat loads in the tunnel:250 kW / DB sector1250 kW between two shafts

CLIC WORKSHOP – Ventilation

Drive Beam sector = 250 kWUTRA cavern = 200 kWLoop = 90 kW

Heat loads in the Loops & UTRA:290 kW / DB sector1450 kW between two shafts

LOOP

UTRA

CLIC WORKSHOP - Ventilation

200 kW

90 kW

UTRA

Loop

Local coolingproduction

HVAC of underground areas

Three systems:• Tunnel • UTRAs• LOOPs

Tunnel Air flow rate considerations

250 kW

1250 kW

500 kW

DB sector

Intershafts

Heat loadsin the tunnel

75 000 m3/h

370 000 m3/h

150 000 m3/h

Air flow rate

1.73 m2

8.56 m2

3.3 m2

Air duct section

1.48 m

3.3 m

2 m

Air duct Diameter

Intershafts

Basic data: Delta Temperature (Extraction – Supply) = 28 – 18 = 10°C

CLIC WORKSHOP - Ventilation

To be Optimised …

Tunnel section = 20 m2

DB sector volume =17 000 m3

Inter shaft volume = 90 000 m3

Input data

Proposal

INJ ECTORLINACS

MAIN BEAMS

DRIVE BEAMS

5 3 1

PHASE 1

Tunnel Air handling from the surface

Air supply

Extraction

Air supply

Extraction

HVAC equipment in surface buildings

CLIC WORKSHOP - Ventilation

Semi transversal ventilation in tunnel

SHAFTPOINT

Extraction

Air supply

NEXTSHAFTPOINT

Extraction

Air supply

Optimisation of the air flow rate.Low air speed in the tunnel < 0.1 m/s.Optimisation of the temperature gradient.Recycling of the tunnel air possible.Reversible operation possible.Energy recovery possible.

CLIC WORKSHOP - Ventilation

SHAFTPOINT

Extraction

Air supply

NEXTSHAFTPOINT

Extraction

Air supply

1 Smoke extraction trapper sector

1 supply and 1 extraction grillesper 30 m

Minimum maintenanceSealed, modulated

Fire resistantCompressed air control

Possible fire resistant sectors, with 2 emergency exits per sector

Semi transversal ventilation in tunnel

CLIC WORKSHOP - Ventilation

Safety considerations

SHAFTPOINT

Extraction

Air supply

Extraction

Air supply

• Control of the pressure from both ends of a sector.• Control of the pressure (overpressure or underpressure in each area).• Fire detection per sector compatible to fire fighting via water mist.

CLIC WORKSHOP - Ventilation

Tunnel section

Circuit D : compressed air

Circuit C : Fire Fighting

Circuit A : Module cooling

Circuit B : general cooling

EXTRACTION DUCTSUPPLY DUCT

This cross section is for study purposes only

Approved CLIC tunnel Diameter is currently 4.5m

CLIC WORKSHOP - Ventilation

Equipment issuesNot standard industrial fans

High pressure fansAdapted products

Not standard equipment

CLIC WORKSHOP - Ventilation

Fan in specific concrete section Concrete air ductsDirect driven fans (no belts)Fan in specific concrete section Concrete sound attenuation

Extraction unit

Supply unit

6000

Equipment issuesSpecial design

CLIC WORKSHOP - Ventilation

Perspectives

- Heat loads in tunnel air to optimize- Heat loads in Exp. caverns, Klystrons to be defined?- Radiation levels in the various areas to be defined- Integration of ventilation ducts in the tunnel section to finalize

CLIC WORKSHOP - Ventilation

Cooling

- Water cooling requirements- Fluid circuits - Cooling production - Main cooling station- Tunnel section. Piping- Equipment considerations- Perspectives

CLIC WORKSHOP - Cooling

INJ ECTORLINACS

MAIN BEAMS

DRIVE BEAMS

5 3 1

878 878 878 878 878 878 878

1756

4390 m

PHASE 1

7911

4390 m4390 m4390 m

CLIC WORKSHOP - Cooling

Modules total power: 70 MWRequired flow-rate: 3215 m3/hDelta temperature: 20 KTemp. Supply: 25 °C

Water cooling requirements

Modules cooling (circuit A)

CLIC WORKSHOP - Cooling

1000 kW

1000 kW0 kW ?

1000 kW

1000 kW

0 kW ?

UTRAUTRC

Dump Dump

LoopLoop

Water cooling requirements

General cooling (circuit B)

Modules total power: 15 MWRequired flow-rate: 1612 m3/hDelta temperature: 8 KTemp. Supply: 27 C

• CIRCUIT A : MODULES COOLING – 70 MW Demineralised water, 25/45°C, 2 pipes Ø600

Accelerator structure, Loads, PETS, Quadripoles

• CIRCUIT B : GENERAL COOLING – 15 MW Demineralised water, 27/35°C, 2 pipes Ø300 UTRA, UTRC, Loop, Vacuum, Beam Dump

• CIRCUIT C : FIRE FIGHTING - Water mist – Ø80

• CIRCUIT D : REGULATION Compressed Air – 760 m3/h, Ø150, 8 bars

- For solids (dust): class 1 with max. 0.1 mg/m3

- For water : class 2 with -40°C dew point - For oil : class 1 with max. 0.01 mg/m3

CLIC WORKSHOP - Cooling

Fluid circuits per side

INJ ECTORLINACS

MAIN BEAMS

DRIVE BEAMS

5 3 1

878 878 878 878 878 878 878

1756

4390 m

PHASE 1

7911

4390 m4390 m4390 m

CLIC WORKSHOP - CoolingRaising circuits

Raising pumps

Drain

Tunnel section

CLIC WORKSHOP - Cooling

Pumpingstation

CoolingProduction

CLIC WORKSHOP - Cooling

Main Cooling stationINJ ECTOR

LINACSMAIN BEAMS

DRIVE BEAMS

5 3 1

878 878 878 878 878 878 878

1756

4390 m

PHASE 1

7911

4390 m4390 m4390 m

Back to lake

WATER MISTCIRCUIT ACIRCUIT B

10 MW

Fromlake

N+1 M~

? MW ? MW

MainLinac Z.E.

2 m?

11 EXCHANGERS

CLIC WORKSHOP - Cooling

Tunnel section. Piping

Circuit D : compressed air

Circuit C : Fire Fighting

Circuit A : Module cooling

Circuit B : general cooling

This cross section is for study purposes only

Approved CLIC tunnel Diameter is currently 4.5m

CLIC WORKSHOP - Cooling

Equipment considerations

- Out of standard pipe diameters- Special tooling, welding process- On request manufacturing, PN an issue?- Extra large heat exchangers

1.2 m1.8 m

3.2 m

6 MWHeat

Exchanger

CLIC WORKSHOP - Cooling

Missing items affecting main cooling station

- Cooling power for experimental cavern ?- Cooling power for Main dumps- HVAC and cooling for klystrons- Confirmation about the rate air/water

Other items to be considered:- Fire-fighting flow-rates- Infiltration water, raising pumps, slopes

Longitudinal principle

SHAFTPOINT

Air supply

NEXTSHAFTPOINT

Extraction

Large air flow rateHigh speedTemperature gradient

CLIC WORKSHOP - 2008

Base:150 000 m3/h1250 kWDelta T°C = 24 = (41-17)Air speed = 2 m/s