Use on AC off track equipment such as long wall miners loaders, drills, shovels, conveyors, pumps and mobile equipment requiring grounding conductors and a ground check conductor and metallic shielding overall. Other industrial, mining applications
SHD-GC 2kV CSA C22.2 No.96-17 —————————————————————————
Round portable power cable Mining grade
APPLICATIONS
CONSTRUCTIONConductors Soft drawn flexible stranded tinned copper wires
Separator Polyester tape
Insulation Ethylene-propylene rubber (EPR)
Insulation shield Non-conducting bedding tape + composite tinned copper/polyamide braid. Covering minimum 60%
Circuit identification The polyamide in the shielding braid is colored black, blue, red
Grounding Soft drawn flexible stranded tinned copper wires
Ground check Yellow PP insulated soft drawn flexible stranded tinned copper wires
Assembly Three power, ground check and two non-insulated grounding conductors cabled together to form a round cable core
Separator Polyamide open braid applied overall
Outer jacket Extra heavy duty, high torsion resistant, integral-filled, reinforced poly-chloroprene (CR) thermosetting jacket
Color of outer jacket Black
Minimum bending radius Six times overall diameter of the cable
FeaturesExcellent flexibility. Highly ozone, sun, weather and flame resistant. Rated and flexible at -40ºC. Excellent impact and abrasion resistant. Oil and heat resistant. Indent printed for easy identification.
CSA: 1523058 (LR 103932), FT 1, FT-5. MSHA: P-07-KA060012-2
Approvals
Selection Data
Electrical parameters
PartNumber
Cond. Size
Cond. Strand
Cond. Size Nominal Insulation Thickness
Nominal Jacket Thickness
Outside Diameter
Approx. Weight Max. Tensile ForceGRD GC
AWG/MCM
No. of wires
AWG Inches mm Inches mm Inches mm Lbs./ 1000ft.
kg/km N
SHDGC2KV14-3CSA* 14 49 14 14 0.070 1.78 0.125 3.18 0.91 23.0 489 727 94
SHDGC2KV12-3CSA* 12 49 12 14 0.070 1.78 0.125 3.18 0.91 23.0 515 767 148
SHDGC2KV10-3CSA* 10 49 12 12 0.070 1.78 0.125 3.18 0.97 24.6 594 884 238
SHDGC2KV8-3CSA* 8 133 10 10 0.070 1.78 0.140 3.56 1.05 26.6 746 1110 380
SHDGC2KV6-3CSA 6 133 10 10 0.070 1.78 0.155 3.94 1.22 31.0 1011 1504 600
SHDGC2KV4-3CSA 4 259 9 10 0.070 1.78 0.155 3.94 1.34 34.1 1296 1928 950
SHDGC2KV2-3CSA 2 259 7 8 0.070 2.03 0.170 4.32 1.52 38.5 1804 2684 1500
SHDGC2KV1-3CSA 1 259 6 8 0.080 2.03 0.190 4.83 1.67 42.4 2151 3201 1900
SHDGC2KV1/0-3CSA 1/0 266 5 8 0.080 2.03 0.190 4.83 1.78 45.2 2595 3862 2400
SHDGC2KV2/0-3CSA 2/0 342 4 8 0.080 2.03 0.205 5.21 1.89 48.1 3019 4492 3000
SHDGC2KV3/0-3CSA 3/0 418 3 8 0.080 2.03 0.205 5.21 2.05 52.0 3600 5357 3800
SHDGC2KV4/0-3CSA 4/0 532 2 8 0.080 2.03 0.220 5.59 2.19 55.7 4312 6416 4800
SHDGC2KV250-3CSA 250 627 1 8 0.095 2.41 0.220 5.59 2.38 60.5 5002 7443 5800
SHDGC2KV350-3CSA 350 888 1/0 8 0.095 2.41 0.235 5.97 2.68 68.1 6598 9819 7900
SHDGC2KV500-3CSA 500 1221 3/0 8 0.095 2.41 0.265 6.73 3.05 77.5 8958 13330 11400
* Not covered by MSHA P-07-KA060012-2 certificate
Power-Grounding Conductor Size
Power Conductor Resistance at 25°C
Grounding ConductorResistance at 25°C
Ground-checkConductorResistance at 25°C
Inductance per unit length
OperatingCapacitance per unit length
Permissible short-circuitCurrent (1s) (2)
Ampacity(1)40°C AmbientTemp
AWG or MCM Ω/1000Ft Ω/1000Ft Ω/1000Ft mH/1000Ft µF/1000Ft kA A
6 AWG 0,436 1,08 1,08 0,118 0,09 1,90 93
4 AWG 0,274 0,857 1,08 0,107 0,11 3,03 122
2 AWG 0,172 0,539 0,679 0,101 0,13 4,80 159
1 AWG 0,137 0,436 0,679 0,100 0,13 6,06 184
Power-Grounding Conductor Size
Power Conductor Resistance at 25°C
Grounding ConductorResistance at 25°C
Ground-checkConductorResistance at 25°C
Inductance per unit length
OperatingCapacitance per unit length
Permissible short-circuitCurrent (1s) (2)
Ampacity(1)40°C AmbientTemp
AWG or MCM Ω/1000Ft Ω/1000Ft Ω/1000Ft mH/1000Ft µF/1000Ft kA A
1/0 AWG 0,109 0,346 0,679 0,097 0,14 7,65 211
2/0 AWG 0,0868 0,274 0,679 0,092 0,16 9,64 243
4/0 AWG 0,0546 0,172 0,679 0,088 0,19 15,30 321
(1) Ampacity –Based on continuous duty at 90°C conductor temperature(2) Short-circuit current (1s) – Based on conductor temperature from 90°C up to 250°C
Special factory option
Jacket: Other colors available
Jacket: TPU jacket available
All the information in this document – including tables and diagrams – is given in good faith and believed to be correct at the time of publication. The information does not constitute a warranty nor representation for which TELE-FONIKA Kable assumes legal responsibility. TELE-FONIKA Kable reserves rights to introduce changes to the document at any time
Standard print legend:
For size 6AWG and larger For size up to 8AWG
TF CABLE 2000V 3/C (SIZE) TYPE SHD-GC CSA LR 103932 FT1 FT5 (-40C) +90C P-07-KA060012-2-MSHA
TF CABLE 2000V 3/C (SIZE) TYPE SHD-GC CSA LR 103932 FT1 FT5 (-40C) +90C