Product Services
lEG 60614-2-1 :1993
The complete detail of the tests performedand the results are recorded in
asl Test Report No: 286/4271935 Dated: 4 September 2002
Description of item tested: 20mm diameter Galvanised Steel Conduit25mm diameter Galvanised Steel Conduit32mm diameter Galvanised Steel Conduit
Tamco Electrical & Electronics (HK) Ltd1701-2 Top Glory Tower262 Gloucester Road
Causeway BayHong Kong
r-C 7-~ ~ft S~a--G R Essam
Title Principal Engineer
Date 4 September 2002
Attention is drawn to the conditions upon which this declarationis issued, namely:
2. This Declaration applied only to the particular sample testedand to the specific tests carried out as detailed in theReport refe"ed to above.
1. This declaration does not indicate provide or imply anymeasure of Approval, Certification, Supervision, Control orSurveillance by asl to this or any related product.
3. The general and specific conditions of the asl ProductServices, Test Leaflet 1 apply in all respects. Copies of thisleaflet are available on request.
BSI Product Services, Maylands Avenue, Hemel Hempstead, Hertfordshire HP2 4SQ
Product Services
as! Product SelVices hereby declares that theitem described below has been tested
by as! and complies with the requirements of
BS 4568:Part 1: 1970
The complete detail of the tests peliormedand the results are recorded in
asl Test Report No: 286/4271935 Dated: 4 September 2002)
20mm diameter Galvanised Steel Conduit25mm diameter Galvanised Steel Conduit32mm diameter Galvanised Steel Conduit
Tamco Electrical & Electronics (HK) Ltd1701-2 Top Glory Tower262 Gloucester Road
Causeway BayHong Kong
,----:S.RC...Y.S'a.- G R Essam
Title Principal Engineer
Date 4 September 20Q2 II
2. This Declaration applied only to the particular sample testedand to the specific tests carried out as detailed in theReport referred to above.
Attention is drawn to the conditions upon which this declarationis issued, namely:
1. This declaration does not indicate provide or imply anymeasure of Approval, Certification, Supervision, Control orSurveillance by asl to this or any related product.
3. The general and specific conditions of the asl ProductServices, Test Leaflet 1 apply in all respects. Copies of thisleaflet are available on request.
BSI Product Services, Maylands Avenue, Hemel Hempstead, Hertfordshire HP2 4SQ
--~--"",Product Services
as! Product Services hereby declares that theitem described below has been tested
by asl and complies with the requirements of
BS EN 50086-2-1 :1996
The complete detail of the tests performedand the results are recorded in
asl Test Report No: 286/4271935 Dated: 4 September 2002
20mm diameter Galvanised Steel Conduit
25mm diameter Galvanised Steel Conduit32mm diameter Galvanised Steel Conduit
Tamco Electrical & Electronics (HK) Ltd1701-2 Top Glory Tower262 Gloucester Road
Causeway BayHong Kong
r--~..~'t::SS'o.-- .G REssam
Title Principal Engineer, .
Date 4 September 2002 I!
Attention is drawn to the conditions upon which this declarationis issued, namely:
2. This Declaration applied only to the particular sample testedand to the specific tests carried out as detailed in theReport referred to above.
This declaration does not indicate provide or imply anymeasure of Approval, Certification, Supervision, Control orSurveillance by asl to this or any related product.
3. The general and specific conditions of the asl ProductSeNices, Test Leaflet 1 apply in all respects. Copies of thisleaflet are available on request.
BSI Product Services, Maylands Avenue, Hemel Hempstead, Hertfordshire HP2 4SQ
':";:~""l:::
: ':"="":::;",0';"."""'"2 ,
Product Services
Report No 286/4271935 This Report consists of 16 pages
Client Tamco Electrical & Electronics (HK) Ltd1701-2 Top Glory Tower262 Gloucester Road
Causeway BayHong Kong
Authority & date Fax from client dated 20 December 2001
)Items tested Steel Conduits
Specification BS 4568: Part 1: 1970 Clauses 5.1, 5.3.. 5.4, 6.1, 7, 8, 9 and 10BS EN 50086-2-1:1996 Clauses 7.1,7.5,8.1,9.1,10..2,10.3,10.4,11.5,and 14.2.2.3IEC 60614-2-1:1993 Clauses 6.1,6.2,6.3,7.1,8.1,9.2,9.3,9.4,12.1.2and 13.4.5Independent Test
Results See summary of results on page 2
)
Prepared by Engineer
Authorized by G R Essam,~:1~~E~ so-- Principal Engineer
Issue Date
Conditions of issue This Test Report is issued subject to the conditions stated in current issue of Test Leaflet 1'Genera! conditions relating to acceptance of testing'. The results contained herein apply only tothe particular sample/s tested and to the specific tests carried out, as detailed in this Test Report.The Issuing of this Test Report does not indicate any measure of Approval, Certification,Supervision, Control or Surveillance by BSI of any product. No extract, abridgement orabstraction from a Test Report may be published or used to advertise a product without the writtenconsent of the General Manager, BSI Product Services, who reserves the absolute right to agreeor reject all or any of the details of any items or publicity for which consent may be sought.
851 PrOOud Ser.;res ~ A~ue I-EmeI Hem~tead Hertfadshire HP2 4SQ Telepnc:.1e:(O1442) 230442
Report No 286/4271935
Page 2 of 16
TESTING, EXAMINATION AND ASSESSMENT OF STEEL CONDUITS SUBMITTED ASINDEPENDENT TEST SAMPLES
INTRODUCTION
At the request of Tamco Electrical & Electronics (HK) Ltd the steel conduits detailed below,received on 15 May 2002, were tested and assessed against the requirements of BS 4568:Part1 :1970, BS EN 50086-2-1 :1996 and lEG 60614-2-1 :1993 from 23 May 2002, as indicated onthe following pages of this Report. This request was made in a Fax from client dated 20December 2001. It is emphasized that assessments were not made against the other clausesof the Specification.
I his Report only relates to the actual samples which have been tested and assessed. The,esults obtained do not necessarily relate to samples from the production line and in no wayimply that the performance or quality of the continuing production will be maintained.
TEST ITEMS
15 off 1 metre lengths 20mm diameter Galvanised Steel Conduit15 off 1 metre lengths 25mm diameter Galvanised Steel Conduit15 off 1 metre lengths 32mm diameter Galvanised Steel Conduit
SUMMARY OF RESULTS
)5 4568: Part 1: 1970
The Galvanised steel conduits met the requirements of those clauses, or parts thereof, of theSpecification against which assessments were made.
BS EN 50086-2-1 :1996
The Galvanised steel conduits met the requirements of those clauses, or parts thereof, of theSpecification against which assessments were made.
Report No 286/4271935
Page 3 of 16SUMMARY OF RESULTS (Continued)
I EC 60614-2-1 : 1993
The Galvanised steer conduits met the requirements of those clauses, or parts thereof, of theSpecification against which assessments were made.
The potential variability in, both the items tested and the method of measurement used,. meansthat for measurements close to a specified limit, the level of confidence in a compliancestatement mayor may not be reduced.
Further advice on the specific measurements in this report that may be affected can beobtained from the report authoriser shown on the front cover.
Report No 286/4271935
Page 4 of 16EXAMINATION AND TEST
BS 4568:Part 1:1970
CLAUSE
4.ASSESSMENT
CLASSIFICATION
The Galvanised steel conduits were classified as screwedconduits.
The Galvanised steel conduits were further classified as having aClass 4, heavy protection both inside and outside. Pass
5.
)
MARKING
Specified Marking.(1) The name or trademark of the manufacturer or responsible
Vendor.(2) BS 4568: Part 1: 1970(3) The Class of finish
Actual Marking
20 mm diameter Galvanised Steel Conduit:
RMG 20 G.E.-MARUIGHI5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan
25 mm diameter Galvanised Steel Conduit:
RMG 25 G.E.-MARUIGHI5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass
32 mm diameter Galvanised Steel Conduit:
RMG 32 G.E.-MARUIGHI5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan
Report No 286/4271935
Page 5 of 16EXAMINATION AND TEST (CONTINUED)
BS 4568:Part 1:1970 (CONTINUED)
CLAUSE ASSESSMENT
5.
5.4
MARKING (CONTINUED)
Marking durabilityMarking shall be checked by inspection and by rubbing themarking by hand, suitably protected, for 15 s with a piece ofcloth soaked with water and again for 15 s with a piece of clothsoaked with petroleum spirit. Pass
6.
6.1
6.1.1
DIMENSIONS
Conduit
Test
(1) External Diameter
The EXternal diameter of the 20mm, 25mm and 32mmDiameter Galvanised steel conduits was checked by means ofthe gauge according to figure 4 of the standard.
(2) Ovality
The Ovality of the 20mm, 25mm and 32mm DiameterGalvanised steel conduits was checked by means of the gaugeaccording to figure 5 of the standard. Pass
(3) Screw Threads
The Screw Threads of the 20mm, 25mm and 32mm DiameterGalvanised steel conduits were checked by means of thegauge according to figure 2 of the standard. Pass
(4) Wall ThicknessThe Wall thickness of the 20mm, 25mm and 32mm DiameterGalvanised steel conduits was tested in accordance to therequirements of the clause. Pass
7. CONSTRUCTION
The Galvanised steel conduits were seamed by welding. Pass7.1
The Galvanised steel conduits showed no appreciableunevenness and the interior and ends were free from burrs,fins and the like which may cause damage to cables.
7.2
8. MECHANICAL PROPERTIES OF CONDUIT
The Galvanised steel conduits were tested by the methoddescribed in the text of Appendix A.2. On completion of thetest it was possible to pass the appropriate steel balls throughthe conduits.
8.1
The Galvanised steel conduits when bent showed no signs ofcracking nor were they deformed to such an extent that theintroduction of cables became difficult or damaged when,.j~~...:~~ :~
Report No 286/4271935
Page 6 of 16
EXAMINATION AND TEST (CONTINUED)
BS 4568:Part 1 :1970 (CONTINUED)
CLAUSE ASSESSMENT
9.
RESISTANCE AGAINST CORROSION
When tested in accordance with the method described inclause 9.1.1. and Appendix A.3.3. (Heavy protection)
The Galvanised steel conduits displayed no signs of corrosion. Pass
10. ELECTRICAL CONTINUITY
The Galvanised steel conduits met the requirements of theclause and Appendix A..5. Pass
Report No 286/4271935
Page 7 of 16EXAMINATION AND TEST (CONTINUED)
BS EN 50086-2-1:1996
CLAUSE
6.ASSESSMENT
CLASSIFICATIONThe Galvanised steel conduits did not have a Classificationnumber marked. Therefore, it was assumed the samples had avery heavy mechanical strength, lower temperature range of -SoC.
7 MARKINGSpecified Marking(a) The name or trademark of manufacturer.(b) A product identification mark.
Actual Marking
20 mm diameter Galvanised Steel Conduit:
RMC 20 C.E.-MARUICHI 5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass
25 mm diameter Galvanised Steel Conduit:
RMG 25 G.E.-MARUIGHI 5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass
32 mm diameter Galvanised Steel Conduit:
RMC 32 C.E.-MARUICHI5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass
The marking shall be shall be durable and easily legible. Pass7.5
Report No 286/4271935
Page 8 of16EXAMINATION AND TEST {CONTINUED}
BS EN 50086.2.1 :1996 (CONTINUED)
CLAUSE ASSESSMENT
8.
DIMENSIONS
The outside diameters and threads shall comply withBS EN 60423:1995
The maximum outside diameter of the 20mm, 25mm and 32mmdiameter Galvanised steel conduits was checked by means ofthe gauge according to figure 2 of BS EN 60423: 1995
The minimum outside diameter of the 20mm, 25mm and 32mmdiameter Galvanised steel conduits was checked by means ofthe gauge according to figure 3 of BS EN 60423: 1995
The screw threads of the 20mm, 25mm and 32mm diameterGalvanised steel conduits was checked by means of the gaugeaccording to figure 4 of BS EN 60423: 1995
9.9.1
CONSTRUCTIONWithin the Conduit System there shall be no sharp edges, burrsor surface projections which are likely to damage insulatedconductors or cables or inflict injury to the installer or used.
Report No 286/4271935
Page 9 of 16EXAMINATION AND TEST (CONTINUED)
BS EN 50086-2-1:1996 (CONTINUED)
CLAUSE
10.10.2
ASSESSMENT
MECHANICAL PROPERTIES
Compression testThe Conduits were tested in accordance with the methoddescribed in this clause. When a force of 4000N (Very heavygrade) the sample shall not exceed 25% of the initial outsidediameter.
Nominal Size Sample Compression (%)20mm Conduit 1 3.8
2 3.93 3.9Mean 3.9
PassPassPass
25mm Conduit 3.53.52.83.3
123Mean
PassPassPass
3.23.23.23.2
PassPassPass
32mm Conduit 123Me
~an
Report No 286/4271935
Page 10 of 16EXAMINATION AND TEST (CONTINUED)
BS EN 50086-2-1:1996 (CONTINUED)
CLAUSE
10.10.2
ASSESSMENT
MECHANICAL PROPERTIES (CONTINUED)
Compression test (Continued)The Force and the intermediate piece are then removed and, 60safter removal, the outside diameter of the samples, where theyhave flattened, shall be measured again.
The difference between the initial diameter and the diameter ofthe flattened samples shall not exceed 10% of the outsidediameter, measured before test.
Nominal Size20mm Conduit
Sample123Mean
Change in diameter (%)0.60.80.80.7
PassPassPass
25mm Conduit 123Mean
0.70.80.80.8
PassPassPass
32mm Conduit 123Mean
0.30.50.40.4
PassPassPass
Report No 286/4271935
Page 11 of16EXAMINATION AND TEST (CONTINUED)
as EN 50086-2-1:1996 (CONTINUED)
CLAUSE ASSESSMENT10.10.3
MECHANICAL PROPERTIES (CONTINUED)
Impact testThe Conduits were tested at -5°C in accordance with themethod described in this clause. After the test, at least nineof the samples shall show no signs of disintegration, nor shallthere be any crack visible to normal or corrected visionwithout magnification and there shall be no deformationimpairing its normal use.
NominalSize
MassUsed
(kg)6.86.86.8
Dropheight(mm)300300300
No.failuresout of 12000
20mm Conduit25mm Conduit32mm Conduit
PassPassPass
10.4 Bending testThe Galvanised steel conduits were tested in accordance tothe method described in this clause.
After the test, the samples showed no cracks visible to normalor corrected vision without magnification. It was possible topass the appropriate gauges through the samples. Pass
1111.5
ELECTRICAL PROPERTIESElectrical Bonding
The Galvanised steel conduits were tested by the methoddescribed in the text of clause 11.5 of BS EN 50086-1 :1994.
The Galvanised steel conduits met the requirements of theclause Pass
14.
14.2
14.2.2
EXTERNALINFUUENCES
Resistance against corrosion
Tests for resistance to corrosion for steel conduit
systems
The Galvanised steel conduits were tested in accordance withJ.'-- -_J.L._-'d :L._-' :- _I_ U A 2 2 3 &_p h:~h P~~~~~~:~ nLilt:: IIICLIIUU t::;:II.,IIIUCU 1111...10 ;:It:: 1"1'. ..IVI III~II IU..t:;\.-~lul
The steel conduits displayed no signs of corrosion Pass
Report No 286/4271935
Page 12of 16EXAMINATION AND TEST (CONTINUED)
lEG 60614.2.1:1993
CLAUSE6. ASSESSMENT
6.1
MARKING
Specified MarkingConduits shall be marked with:(.1) the name or trademark of the manufacturer or responsible
Vendor, trade mark, or other indentifying symbol.(2) a classification code .in accordance with clause A.1
of annex A..(3) any other mark or symbol required by the relevant section of
part 2 of this standard.
Actual Marking
20 mm diameter Galvanised Steel Conduit:
RMC 20 C.E.-MARUICHI 5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass
25 mm diameter'Galvanised Steel Conduit
RMC 25 C.E.-MARUICHI 5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass
32 mm diameter Galvanised Steel Conduit:
RMC 32 C.E.-MARUICHI 5/100060 lEG 614-2-1 BS 4568 class 4Made in Japan Pass
)
Report No 286/4271935
Page 13 of 16EXAMINATION AND TEST (CONTINUED)
IEC 60614-2-1:1993 (CONTINUED)
CLAUSE ASSESSMENT
6.6.2
MARKING (CONTINUED)
Marking of ConduitsRigid conduits shall be marked at least once on eachmanufacturing length, preferably 50mm from one end Pass
6.3 Marking shall be durable and easily legibleMarking according to 6.1 to 6.3 shall be checked by inspection,and by rubbing the marking by hand, suitably protected, for 15 swith a piece of cloth soaked with water and again for 15 s with apiece of cloth soaked with petroleum spirit Pass
DIMENSIONS
The outside diameters and threads shall comply with lEG 4237.1
The maximum outside diameter of the 20mm, 25mm and 32mmdiameter Galvanised steel conduits was checked by means of thegauge according to figure 2 of lEG 423
71 1
Pass
The minimum outside diameter of the 20mm, 25mm and 32mmdiameter Galvanised steel conduits was checked by means of thegauge according to figure 101 of this specification
7.1.2
Pass
7.2 The waH thickness of the 20mm, 25mm and 32mm diameterGalvanised steel conduits shaH comply to Standard sheet 2 of this
specification Pass
8.
CONSTRUCTION
The inside and outside surfaces of the conduits shall bereasonably free from burrs, flash and similar defects; in additionthe edges over which the conductors or cables are likely to bedrawn, shall not damage these conductors or cables
Compliance shall be checked by inspection, if necessary, after
cutting the samples apart Pass
Conduits shall be solid drawn or seam joined by welding Pass8.101
Report No 286/4271935
Page 14 of 16EXAMINATION AND TEST (CONTINUED)
IEC 60614-2-1 :1993 (CONTINUED)
CLAUSE ASSESSMENT
9.
9.1MECHANICAL PROPERTIES
Conduits shall have adequate mechanical strength
Conduits according to their types, when bent or compressed, orexposed to shocks or extreme specified temperatures, eitherduring or after installation, shall show no cracks and shatl not bedeformed to such an extent that the introduction of the cablesbecomes difficult, or that the installed conductors or cables arelikely to be damaged, while being drawn in
Compliance shall be checked by the test specified in Sub-clauses9.2 and 9.3
9.2 Bending testThe 20mm, 25mm and 32mm diameter Galvanised steel conduitswere subjected to a bending test by means of a device as shownin figure 102 of this specification
After the test, the samples showed no cracks visible to normal orcorrected vision without magnification. It was possible to pass theappropriate gauges through the samples Pass
9.3 Compression testThe Conduits were tested in accordance with the methoddescribed in this clause. When a force of 4000N (very heavygrade) the sample shall not exceed 25% of the initial outsidediameter
Nominal Size Sample Compression (%)20mm Conduit 1 3.8
2 3.93 3.9Mean 3.9
PassPassPass
25mm Conduit 3.53.52.83.3
PassPassPass
123Mean
PassPassPass
32mm Conduit 123Me
3.23.23.23.2
.~an
Report No 286/4271935
Page 15 of 16EXAMINATION AND TEST (CONTINUED)
IEC 60614-2-1 :1993 (CONTINUED)
CLAUSEASSESSMENT
9.
9.3MECHANICAL PROPERTIES (CONTINUED)
Compression test (Continued)The Force and the intermediate piece are then removed and, 60safter removal, the outside diameter of the samples, where theyhave flattened, shall be measured again
The difference between the initial diameter and the diameter ofthe flattened samples shall not exceed 10% of the outsidediameter, measured before test
Nominal Size20mm Conduit
Sample123Mean
Change in diameter (%)0..60.80.80.7
PassPassPass
25mm Conduit 123Mean
0.70.80.80.8
PassPassPass
32mm Conduit 123Me
0.30.50.40.4
PassPassPass
an
Report No 286/4271935
Page 16 of 16EXAMINATION AND TEST (CONTINUED)
IEC 60614-2-1 :1993 (CONTINUED)
CLAUSE
12.
12.1
ASSESSMENTELECTRICAL CHARACTERISTICS
Conduits with electrical continuity characteristics
12.1.1 Conduits shall be so constructed that they can be used in aninstallation system as an earthing or protective conductor Pass
12.1.2 Conduits shall have a resistance of not more than 5 x 10 -3.0. Pass
13.4 RESISTANCE AGAINST CORROSION
When tested in accordance with the method described in clause13.4.5 for conduits with High Protection
The Galvanised steel conduits displayed no signs of corrosion Pass
)