Post on 28-Jul-2020
transcript
Hospitality Selection Guide
eMer
Gen
cY
E2 www.acuitybrandslighting.com
Introduction Emergency Systems Synergy Control Systems
EMERGENCY SYSTEMS Emergency lighting is required by building codes to ensure
that a route to exit a building is clearly identified during an
emergency situation.
Lithonia Emergency Systems manufactures a comprehensive
selection of exit signs, emergency lighting units, fluorescent
battery packs and emergency power systems for a wide
range of commercial applications.
Our extensive product offering includes architectural,
commercial and industrial models in a choice of materials
and light sources. A substantial range of options and
accessories also is available.
SYNERGY CONTROL SYSTEMS Lithonia Lighting produces a wide range of control systems for both architectural dimming and lighting energy management. These systems are
suitable for a multitude of commercial applications. Lighting controls dramatically enhance efficiency by governing the amount of light needed to
maintain illuminance levels and by limiting light use to occupied spaces. Lithonia offers a variety of lighting control solutions to meet ASHRAE 90.1 and
similar legislation requirements.
Lithonia Emergency Systems E3 - E16
Lithonia Synergy Control Systems SS1 - SS9{
Hospitality Selection Guide
eMerG
enc
Y
E3www.acuitybrandslighting.com
contents
exit signs E4
emergency lighting units E9
remote lamp Heads E13
Battery Packs E14
Power systems E16
Lithonia Emergency Systems
Hospitality Selection Guide
eMer
Gen
cY
E4 www.acuitybrandslighting.com
Accessories4 (Order separately)
LED ROUGH-IN SECTION5
Standard ELA LCRIS 1 or 2 face red or green ELA LRIS 120 X2 1 or 2 face 120V w/ X2 option ELA LRIS 277 X2 1 or 2 face 277V w/ X2 optionEmergency ELA R LRIS 120/277 EL N 1-face red ELA R 2LRIS 120/277 EL N 2-face red ELA G LRIS 120/277 EL N 1-face green ELA G 2LRIS 120/277 EL N 2-face green
Pendant Mounting (Top mount only) ELA US12 12" pendant kit with brushed
aluminum canopy
NOTES:
1 Single-face exits only.
2 Mirror background simulates clear for double-face option.
3 Non-emergency exits only. No rough-in section required.
4 For additional options, accessories and fixture compatibility see page ES21.
5 Supplied standard with exit unless PNL suffix is specified. Order separately only if necessary for early installation. When ordering rough-in separately, all options must be included with rough-in nomenclature. Example: ELA LCRIS 120/277 FI
6 Must specify input voltage 120 or 277.
Edge-Lit Exits
Precise®
LED
Top Mount
Back Mount
Intended Use
Suitable for architectural applications where aesthetics and superior performance are re-quired.
Features
Injection-molded acrylic panels, ultrasonically welded to eliminate visible hardware.
Depth of molded letters increases toward bot-tom of panel for better, more uniform illumina-tion. Chevron directional indicators.
Long-life LEDs feature very low energy consump-tion and rated life up to 25 years.
Ordering Information Example: lrP Bs 1 rc la 120/277 el n eM
Family
LRP LED
Number of faces
1 Single 2 Double
Mounting
(blank) Ceiling or back
EM End TM Top3
Input voltage
120/277 Dual voltage
Housing color
(blank) Brushed aluminum
W White B Black BZ Bronze BS Brass CR Chrome
Panel color letter/background
RW Red on white RC Red on clear1
RMR Red on mirror2
GW Green on white GC Green on clear1
GMR Green on mirror2
Operation
(blank) Standard non-emergency EL N Nickel-cadmium battery X2 Lamps wired on two
separate circuits6
Directional indicators
(blank) No chevrons LA Left RA Right LRA Left and right DA Double-face chevrons
Item type
(blank) Complete exit panel and rough-in section
PNL Panel assembly only
Chevron Direction
Dimensions are shown in inches (millimeters) unless otherwise noted. Certification
(blank) UL Listed
RECESSED BACK MOUNTPanel length: 13-1/4 (336)Trim length: 14-3/4 (375)Total height: 11-1/2 (292)Depth (from wall): 1-7/8 (47)Weight: 5 lbs. (2.3 kgs.)
RECESSED CEILING MOUNTPanel length: 13-1/4 (336)Trim length: 14-3/4 (375)Height (below ceiling): 8 (203)Trim width: 5 (127)Weight: 5 lbs. (2.3 kgs.)
RECESSED END MOUNTPanel length (from wall): 13-1/2 (343)Panel height: 10 (254)Trim height: 14-3/4 (375)Panel depth: 1-7/8 (47)Weight: 5 lbs. (2.3 kgs.)
Panel/Trim Assembly
TOP MOUNT(Standard non-emergency only)Panel length: 13-1/4 (336)Trim length: 13-1/8 (333)Panel height: 8 (203)Weight:5 lbs. (2.3 kgs.)
Length: 13-5/8 (346)Width: 4-1/2 (114)Depth: 3-1/8 (80)
Rough-In Section
eXit
siG
ns
Emergency operation exits use maintenance-free nickel-cadmium battery.
Recessed mounting. Extruded aluminum housing recessed into wall or ceiling for top, back or end mounting capability.
Surface top-mount (TM) option available on non-emergency exits and attaches directly to J-box. Can be used for pendant mounting.
Special wording available; consult factory.
Listings
UL Listed (standard).
Electrical Application DataType Volts Faces Amps WattsPrimary Circuit 120 1 .087 1.5Standard 120 2 .178 3.1LED Red 277 1 .089 1.8 277 2 .178 3.4 120 1 .093 2.3Emergency 120 2 .084 3.2LED Red 277 1 .095 2.7 277 2 .094 3.9 120 1 .064 1.2Standard 120 2 .059 2.0LED Green 277 1 .062 1.3 277 2 .061 2.3 120 1 .066 1.7Emergency 120 2 .138 3.7LED Green 277 1 .064 1.9 277 2 .130 3.8
Hospitality Selection Guide
eMerG
enc
Y
E5www.acuitybrandslighting.com
Intended Use
Suitable for applications requiring attractive edge-lit exit signage, universal installation and low en-ergy consumption.
Features
Extruded aluminum or white finish lamp housing.
Clear thermoplastic panels with precision out-line engraved letters measuring 6" high with 3/4" stroke.
Single face on clear background. Double face on mirrored separator panel to simulate clear back-ground.
Expected LED life over 10 years.
Ordering Information Example: eDG 1 r el
Family
EDG Surface mount LED edge-lit
Number of faces
1 Single 2 Double
Operation
(blank) Standard non-emergency EL Nickel-cadmium battery SD1 Self Diagnostic (available with
EL option only) X2 Provides primary and
secondary AC input (available with green letters and AC operation only)
Housing color
(blank) Aluminum W White
Letter color
R Red G Green
Surface Mount Edge-lit Exits
EDGLED
Dimensions are shown in inches (millimeters) unless otherwise noted. Shipping weight 4lbs. (1.81 kgs.)
Width: 13-5/8 (345)
Height: 11-3/4 (299)
Depth: 4-3/8 (110)
Width: 4-3/8 (110)
Height: 11-3/4 (299)
Depth: 13 (330)
Width: 13 (330)
Height: 12-1/2 (318)
Depth: 2-3/8 (59)
Back Mount
Test Switch Pilot Light
(Emergency Only)
End Mount Top Mount
eXit siG
ns
Low energy consumption – less than 5 watts.
Universal (top, end or back) mounting. Double face available with top or end mounting only (canopy provided).
Universal directional indicators. Field selected and attached.
Listings
UL Listed (standard). Meets NFPA 101 (current Life Safety Code), NEC and OSHA illumination stan-dards.
Electrical Application DataType Volts Amps Watts
Primary CircuitStandard LED Red 120 0.21 2.52 277 0.10 2.77Standard LED Green 120 0.18 2.16 277 0.08 2.20Emergency LED Red 120 0.25 3.00 277 0.11 3.05Emergency LED Green 120 0.22 2.64 277 0.10 2.77
NOTES:
1 Consult factory.
Hospitality Selection Guide
eMer
Gen
cY
E6 www.acuitybrandslighting.com
Ordering Information Example: le s W 1 r 120/277 el n sD
NOTES:
1 Not available with recessed exits.
2 Must specify input voltage 120 or 277.
3 For additional accessories see page ES21.
4 Add W for white canopy.
5 For use with emergency exits only.
Accessories3 (Order separately)
ELA B US12 12" pendant kit with black canopy4
ELA LEHO 120/277 N Remote capable with black canopy. Provides 90 minutes of 10.2 watt capacity for remote head4,5
LED
END MOUNT TOP MOUNT BACK MOUNT
Width: 11-3/8 (289)
Height: 7-7/8 (200)
Depth: 1-3/4 (45)
Add 2-1/4 (57) for canopy
Weight: (Standard) 5 lbs. (2.3 kgs)
(Emergency) 8 lbs. (3.6 kgs)
Electrical Application DataType Volts Faces Amps WattsPrimary CircuitStandard 120 1 or 2 .04 .73LED red 277 1 or 2 .05 .94Standard 120 1 or 2 .04 1.2LED green 277 1 or 2 .05 1.5
Die-Cast Aluminum Exits
Signature®LED
Housing color
(blank) Brushed aluminum face & matte black housing
BZ Dark bronze W White B Matte black
Operation
(blank) Standard non-emergency EL N Nickel-cadmium
battery1
EL N SD Nickel-cadmium battery with self diagnostics
X2 Lamps wired on two separate circuits2
Panel color
R Red G Green
Family
LE LED LRE LED recessed
Number of faces
1 Single 2 Double
Face type
S Stencil
Intended Use
Ideal for applications requiring attractive die-cast aluminum signage, superior illumination and low energy consumption.
Features
Solid, die-cast aluminum housing – smallest sign on the market. Standard finish is brushed aluminum face with matte black housing. Oth-er finishes available.
The self-diagnostic emergency signs comply with NFPA Life Safety Code and automatically tests the battery once a month for five minutes and once every six months for 30 minutes.
Completely concealed chevron directional in-dicator knockouts and mounting hardware.
Long-life LEDs feature very low energy con-sumption and rated life up to 25 years.
A non-emergency red LED exit consumes only .73 watts of electricity at 120 volts.
Dimensions are shown in inches (millimeters) unless otherwise noted.
Width: 13 (329)
Depth: 4 (102)
Height: 9-1/2 (240)
Weight: (Standard) 10 lbs. (4.5 kgs)
(Emergency) 13 lbs. (5.9 kgs)
Recessed
eXit
siG
ns
LEDs provide uniform graphics illumination. Meets 3/4" letter stroke requirements. Main-tains 100% brightness in emergency mode.
Emergency exits contain maintenance-free nickel-cadmium battery and reliable, solid-state charging system.
Universal mounting – top, back or end. Double face available with top or end mounting only (canopy included).
US patent no. 5,954,423.
Listings
UL Listed (standard).
Input voltage
120/277 Dual voltage
Certification
(blank) UL Listed
Hospitality Selection Guide
eMerG
enc
Y
E7www.acuitybrandslighting.com
Electrical Application Data Electrical Standard Lamp
AC Lamp AC Input Output Output Watts Catalog Description Volts Amps Watts Volts 1.5 hrs. 2 hrs 3 hrs. Number Watts 120 .23 3.3 6 14 10 7 Red LED MR24 K0606 5.4 277 .23 3.3 6 (HO) 24 18 12
120 .23 3.3 6 14 10 7 Green LED MR24 K0606 5.4 277 .23 3.3 6 (HO) 24 18 12
Width: 21-1/4 (539)
Depth: 4 (102)
Height: 9-7/8 (250)
Labor-Saving Exit/Unit Combos
Quantum®
LED Quick-Mount ®
Accessories (Order separately) ELA MR24 K0606 Compact MR24 remote head (6W, 6V krypton lamp)
ELA MR24 K0906 Compact MR24 remote head (9W, 6V krypton lamp)
ELA NX H0606 NEMA 4X sealed-beam remote fixture (6W, 6V halogen lamp)
ELA WGHQM Wireguard (backmount only)
Intended Use
Suitable for applications requiring quick-installa-tion of both exit sign and unit equipment. Attrac-tive 10-inch tall, streamlined design is great for above the door applications and other tight fits.
Features
UV-stabilized thermoplastic housing resists discoloration from sunlight and man-made sources.
QUICK-MOUNT installation. Innovative, snap-together design allows for installation in less than three minutes.
Factory assembled and prewired.
Replaceable chevron directional indicator knockouts for choice of direction.
Side-mount lamp heads reduce overall height, al-lowing for easy fit over doorways.
Long-life LEDs feature very low energy consump-tion and rated life up to 25 years.
Ordering Information Example: lHQM s W 3 r
Dimensions are shown in inches (millimeters) unless otherwise noted.
Family
LHQM LED exit/unit
Housing color
(blank) Black W White
Number of faces
3 Single with extra faceplate and color panel
Options
N Nickel-cadmium battery2
HO High-output lead- calcium battery
R0 HO Less lamp heads high-output lead- calcium battery
NOTES:
1 For custom signage only. Special wording available on panel face, white housing with red letters only. Consult factory. Not available with SD, SDFIFA or X2 operation.
2 Not available with HO.
Face type
S Stencil P1 Panel
Panel color
R Red G Green
eXit siG
ns
120/277 dual input voltage standard.
Sealed, maintenance-free, lead-calcium battery standard. Nickel-cadmium battery optional.
Two 5.4W wedge-based krypton lamps offer 32 percent more light output than standard incan-descent lamps.
Patented MR24, multi-faceted reflector signifi-cantly improves photometric performance; 60 to 100 percent more light delivered to the path of egress. Dual-voltage input capability (120/277V). Edge connectors on printed circuit board ensure long-term durability.
Top, back or end mounting (canopy included).
Optional high-output battery (HO) to power a remote head or exit.
U.S. Patent No. 5,611,163, 5,646,502, 5,526,251, 5,797,673 and D379,373. Other patents pending.
Listings
UL Listed (standard). Damp location listed stan-dard.
Remote Output Capacity Combo/ Combo/no Combo/ high- heads (R0) &Family Standard ni-cad output high-output combo battery (N) battery (HO) battery (HO)
LHQM NA NA 12 W 24.0 W
Hospitality Selection Guide
eMer
Gen
cY
E8 www.acuitybrandslighting.com
Family
LQM
Ordering Information Example: lQM s W 3 r 120/277 el n sD
Housing color
(blank) Black W White
Letter color
R Red G Green
Face type
S Stencil P1 Panel
Number of faces
3
Input voltage2
120/277
Contemporary Thermoplastic Exits
Quantum®
NOTES:
1 For custom signage only. Special wording available on panel face, white housing with red letters only. Consult factory. Not available with SD, SDFIFA or X2 operation.
2 Some special voltages available. Consult factory.
3 Available with EL N operation only.
4 Available with AC operation only.
5 Available with Stencil or Panel faces in white housing and red letters only.
6 Replace "W" with "B" for black canopy.
Operation
(blank) AC operation EL N Nickel-cadmium battery SD3 Self-diagnostics SDFIFA3 Self-diagnostics, fire alarm flashing
interface and flashing emergency operation and intermittent audible alarm (one flash/one sec.)
X24 Provides primary and secondary AC input
Dimensions are shown in inches (millimeters) unless otherwise noted.
Intended Use
Ideal for applications requiring attractive, quick installation exit signs and low energy consumption.
Features
Precision-molded thermoplastic housing is im-pact and scratch resistant, corrosion proof and UV-stabilized to resist discoloration.
Innovative snap-together design allows instal-lation in less than three minutes.
Long-life LEDs feature very low energy con-sumption and rated life up to 25 years. Con-sumes less than one watt of energy.
Fully assembled single-face exit with option-al extra faceplate for easy field conversion to double face.
Replaceable chevron directional indicator knock-outs for choice of direction.
Universal mounting capability – top, back or end (canopy provided).
Certification
(blank) UL 924 Listed NOM5 NOM Certified
End Mount Top Mount Back Mount
Width: 11 (298)
Height: 7-5/8 (193)
(Add 7/8 (22) for canopy)
Depth: 2 (49)
eXit
siG
ns
LED Quick-Mount ®
Automatic recharge after discharge.
Conveniently located test switch and status indicator provide visual and manual means of monitoring system operation.
The self diagnostic emergency signs comply with NFPA Life Safety Code and automatically test the battery once a month for five minutes and once every six months for 30 minutes.
U.S. Patent No. 5,526,251, 5,611,163, 5,739,639 and 5,954,423. Other patents pending.
Listings
UL Listed (standard). NOM Certified (see Options). Damp location listed standard.
Accessories (Order separately) ELA W US12 12” stem kit with white canopy6
ELA WGEX Back-mount wireguard
ELA WGEXT Top-mount wireguard
ELA WGEXE End-mount wireguard
Electrical Application DataType Volts Amps WattsPrimary CircuitStandard 120 .04 .57LED red 277 .05 .68Standard 120 .05 .62LED green 277 .05 .72Emergency 120 .04 .72LED red 277 .92 .92Emergency 120 .04 .72LED green 277 .05 .92
Hospitality Selection Guide
eMerG
enc
Y
E9www.acuitybrandslighting.com
Contemporary Thermoplastic Emergency Lighting Units
Quantum®
ELM/ELM2Quick-Mount ®
ELM2
ELM Width: 11-1/2 (292) Depth: 3-3/4 (95.25) Height: 5 (127)
ELM2 Width: 12-1/2 (317) Depth: 3-3/4 (95.25) Height: 5 (127)
Intended Use
Provides a minimum of 90 minutes of illumi-nation for the rated wattage upon loss of AC power. Ideal for applications requiring attrac-tive unit equipment with quick installation.
Features
White, compact, low-profile contemporary de-sign with high-impact thermoplastic housing that is impact-resistant, corrosion-proof and UV-stable to resist discoloration from artificial light sources or sunlight.
Maintenance-free lead-calcium battery.
Two 5.4W wedge-based krypton lamps offer 32 percent more light output than standard incandescent lamps.
Patented MR24, multi-faceted reflector (ELM2) significantly improves photometric perfor-mance; 60 to 100 percent more light delivered
Ordering Information Example: elM2 sD
NOTES:
1 Available on ELM2 only.
2 Available on ELM only.
Drawings are for dimensional detail only and may not represent actual mechanical configuration. Dimensions are shown in inches (millimeters) unless otherwise noted.
ELM
Options
SD Self-diagnostics1
B Black housing DL Damp locations -10 ° to 40 ° C (50 °-140 ° F) CSR 6-foot cordset attached2
NOM NOM Certified1
to the path of egress. Dual-voltage input capa-bility (120/277V). Edge connectors on printed circuit board ensure long-term durability.
Unique track-and-swivel design permits full range of lamp head adjustment (ELM2). Uni-versal J-box mounting pattern. Tool-less access for maintenance. Flexible conduit entry provi-sion on top of the unit.
Quick-Mount® snap-together construction permits installation in three easy steps in less than three minutes.
Vandal-resistant ELA VS polycarbonate shield available.
Wall or ceiling mounted.
Listings
UL Listed (standard). NOM Certified (see Options).
Family
ELM 6V,12W ELM2 6V,12W
Accessories (Order Separately) ELA VS Polycarbonate vandal shield ELA WGST Wireguard
Electrical Application Data AC Input Output Output WattsType Volts Amps Watts Volts 1½ hrs
ELM 120 .11 1.2 6 12 277 .12 1.5
ELM2 120 .11 1.2 6 12 277 .12 1.5
eMerG
enc
Y liGH
tinG
un
its
Hospitality Selection Guide
eMer
Gen
cY
E10 www.acuitybrandslighting.com
Intended Use
Provides 90 minutes of illumination for the rated wattage upon the loss of AC power. Ideal for applications that require ensconced emergency lighting in wall or ceiling.
Features
Trim and door housing panels are finished in durable white textured powder coated paint. Can be wallpapered or field painted. Trim and panel doors lay flush with mounting surface. No exposed hardware. Low profile recessed test switch and status indicator configuration minimizes exposed interfaces. Rugged, 22 GA galvanized steel box with (3) 3/4” knock-outs. Galvanized bar hangers span up to 30” on center.
Two MR16 halogen 12W to 75W lamps are fully adjustable to meet aiming requirements. Lamps are ensconced until activated in the emergency mode.
Sealed, maintenance-free lead-calcium bat-tery with capacity of 24W to 150W for 90 minutes of emergency operation. Optional nickel-cadmium battery. Low voltage discon-nect prevents excessive deep discharge that can permanently damage the battery.
Dual voltage input capability (120/277V). Pre-cision-controlled motor and cam system en-sures reliable extraction and retraction of light sources. Single, multi-chromatic LED indicator to display two-state charging, test activation and four-state diagnostic status. Standard self-diagnostic feature tests the unit for 30 minutes every 28 days without turning lamps on. Pro-vided with an ir receiver for remote testing. Requires the ELA RTVEL remote transmitter (see accessories). Selectable 30-second or 90-minute manual testing.
Listings
UL Listed (standard) .
Concealed Emergency Lighting Units
Velaré™
Ordering Information Example: vel1270 H3512 n
Family
VEL1224 12V, 24W VEL1240 12V, 40W VEL1270 12V, 70W VEL12100 12V, 100W VEL12150 12V, 150W
Lamp type1
H1212 12W/12V halogen MR16 H2012 20W/12V halogen MR16 H3512 35W/12V halogen MR16 H5012 50W/12V halogen MR16 H7512 75W/12V halogen MR16
Options N Maintenance-free nickel-cadmium battery TD Time delay LRIS Less rough-in section2
Accessories (Order Separately)
ELA RTVEL Remote transmitter with selectable 30-second or 90-minute testing3.
ELA VEL RIS VEL rough-in section (supplied standard with fixture unless LRIS suffix is specified) ships with mounting hardware only. Order ELA VEL RIS if needed for rough-in phase of construction.
NOTES:
1 Two lamps provided. Total lamp load cannot exceed the fixture capacity rating.
2 VEL rough-in section ships standard with fixture unless LRIS suffix is specified. Requires ELA VEL RIS accessory for installation.
3 Minimum one per job required.
Drawings are for dimensional detail only and may not represent actual me-chanical configuration. Dimensions are shown in inches (centimeters) unless otherwise noted.
VEL1224 (12V, 24W) – 20 lbs.
VEL1240 (12V, 40W) – 20 lbs.
VEL1270 (12V, 70W) – 26 lbs.
VEL12100 (12V, 100W) – 26 lbs.
VEL12150 (12V, 150W) – 32 lbs.
Rough-in opening: 13-1/2 (341) X 6-3/4 (170)
Overlap trim: 14-7/16 (365) X 7-5/8 (193)
14-1/2"
7-5/8"
13-1/2” to 30”16”
4”
13-1/2”6-3/4"Rough-in
openingRough-in opening
Universal adjusted mounting rails. Two per unit mount on 13-1/2" or 16" sides.
Total depth =
Depth behind wallfor 3/4" wall thickness = 3-1/4"
Electrical Application Data AC Input Output Output Watts Type Volts Amps Watts Volts 1-1/2hr.
Primary CircuitVEL1224 120 .20 30 12 24 277 .20 30 12 24 VEL1240 120 .20 30 12 40 277 .20 30 12 40 VEL1270 120 .20 30 12 70 277 .20 30 12 70 VEL12100 120 .20 30 12 100 277 .20 30 12 100 VEL12150 120 .20 30 12 150 277 .20 30 12 150
eMer
Gen
cY
liG
Hti
nG
un
its
Hospitality Selection Guide
eMerG
enc
Y
E11www.acuitybrandslighting.com
eMerG
enc
Y liGH
tinG
un
its
Family
AFN
Ordering Information Example: aFn Bn PreM
Width: 6-1/2 (165)
Depth: 2-7/10 (69)
Height: 9-1/2 (241)
Weight: 3.5 lbs. (1.59 kgs.)
Dimensions are shown in inches (millimeters) unless otherwise noted.
Intended Use
Provides a minimum of 90 minutes illumination for the rated wattage upon loss of AC power. Ideal for applications requiring attractive unit equipment.
Features
Compact, low-profile, architectural design with die-cast aluminum housing that has a contempo-rary brushed nickel-plated finish. Other available finishes are texturized polyester powder coat paint in white, black and dark bronze.
U.S. Patent No. D468,046.
Two 6W wedge-base xenon lamps offer 55 percent more light output than standard incandescent lamps.
Patent-pending reflector/refractor design features superior vac-metalized, die-casted reflectors and multi-faceted, highly transmissive refractor that sig-nificantly improve photometrics.
Maintenance-free lead-calcium battery (as a stan-dard). Nickel-cadmium optional.
Option packages
(blank) Features lead-calcium battery PREM Features nickel-cadmium battery, self-diagnostics and damp location 0° to 50°C (32° to 122°F) EXT Features high-temperature nickel-cadmium battery listed from -18° to 50°C (0° to 122°F), self-
diagnostics, time delay, damp and wet location
Finish
W White B Black BN Brushed nickel DB Dark bronze1
Input voltage
(blank) 120/277V
NOTES:
1 Dark bronze can only be ordered with the exterior package. This finish is not available on other units.
2 To order white, black or brushed nickel, replace DB with W, B or BN.
For fixture performance charts, see page EL24.
Accessories (Order Separately)ELA AFNR DB Remote fixture (less batteries and electronics) to
be powered by 6V battery equipment as part of an emergency lighting system (listed from -40°C to 60°C)2
The self-diagnostic option complies with NFPA Life Safety Code and automatically tests the bat-tery once a month for five minutes and once every six months for thirty minutes.
Dual-voltage input capability (120/277V).
Low-profile, integrated test switch/pilot light lo-cated below the lens.
Rigid conduit entry provision on top of the unit.
Remote version available for exterior use. Ideal for exit discharge applications.
Listings
UL Listed (standard). Wet location (EXT) listed. Damp location (PREM, EXT) listed. Cold Weather (EXT) listed. Meets UL 924, NFPA 101, NFPA 70-NEC and OSHA illumination standards.
Die-Cast Architectural Emergency Lighting Units
Affinity®
Electrical Application Data
AC Input Output Output WattsType Volts Amps Watts Volts 1-1/2 hrs
AFN 120 .11 1.1 6 12 277 .12 1.3
AFN PREM 120 .15 1.4 6 12 277 .14 1.4
AFN EXT 120 .23 21 6 12 277 .25 35
Hospitality Selection Guide
eMer
Gen
cY
E12 www.acuitybrandslighting.com
Recessed Emergency Lighting Units
ELR
Ordering Information Example: elr2 cDs
Options Standard Lamp Catalog Watts/ Type SD N R0 H CDS N1812 N2512 H1212 TD NOM Number Lamp
ELR2 ■ ■ ■ ■ ■ N0806 8
ELR2P N ❑ ■ ■ ■ ■ N0806 8
ELR4 ■ ■ ■ ■ ■ ■ ■ ■ ■ N1212 12
PAR36 Length: 12 (303) Width: 12 (303) Depth: 5-7/8 (149) below ceiling plane Weight: (ELR2) 16 lbs. (7.3 kgs.) (ELR4) 22.5 lbs. (10.2 kgs.)
Compact Designer Square Length: 12 (303) Width: 13-3/8 (340) Depth: 2-3/4 (70) below ceiling plane Weight: (ELR2 CDS) 15 lbs. (6.8 kgs.) (ELR4 CDS) 22.5 lbs. (10.2 kgs.)
Electrical Application Data AC Input Output Output Watts Volts Amps Watts Volts 1-1/2 hrs 2 hrs 3 hrs 4 hrsELR2 120 .167 20 6 16 12 8 6 277 .072 20ELR2P N 120 .167 20 6 24 18 12 9 277 .072 20ELR4 120 .250 30 12 50 37 25 18 277 .108 30
Special voltages/frequencies available; consult factory.
For additional lamp heads, remote fixtures, options and accessories, see pages EL16.
Intended Use
Provides a minimum of 90 minutes of illumination for the rated wattage upon loss of AC power. Ideal for applications that require attractive unit equip-ment or when wall mounting is undesirable.
Features
Heavy-duty recessed housing suitable for use in air-handling plenums.
PAR36 lamp heads standard; compact designer square lamp heads optional.
Dimensions are shown in inches (millimeters) unless otherwise noted.
Ordering Information Example: elrG
ELRG 6V, self-contained recessed gimbal
Recessed Gimbal Emergency Lighting Unit
ELRG
Electrical Application Data
AC Input
Type Volts Amps Watts
ELRG 120 .052 5.8 277 .023 5.9
Intended Use
Provides a minimum of 90 minutes of illumi-nation for the rated wattage upon loss of AC power. Ideal for applications requiring unob-trusive emergency lighting.
Features
Matte white, baked enamel finish. All-metal housing and gimbal assembly.
High-output, 8W halogen lamp. Lamp adjusts in
Dimensions are shown in inches (millimeters) unless otherwise noted.
Options
SD Self diagnostic (ELR4 only) N Maintenance-free nickel-cadmium batteries R0 Less lamp heads H 6V/8W or 12V/8W halogen lamps CDS Compact designer square lamp heads N1812 18W/12V incandescent lamps N2512 25W/12V incandescent lamps H1212 12W/12V incandescent lamps TD Time delay (12V only)
Sealed, maintenance-free battery (lead-cal cium stan dard, nickel-cadmium optional) provides ca-pacity for 90 minutes of emergency illumination.
Sturdy T-bar clips secure unit to grid members.
Adjustable bar hangers for easy mounting in walls and exposed or concealed suspended ceilings.
Listings
UL Listed (standard).
two planes to 26°.
Low-profile pilot light and test switch.
Approved for use in air-handling plenums.
Maintenance-free lead-calcium battery.
Mounts in 6" diameter opening.
Listings
UL Listed (standard).
❑ Standard
■ Option available
(blank) Option not available
Height: 7-1/2 (191)
Length: 10 (254)
Width: 18-1/2 (470)
Ceiling opening: 8-1/2 (216)10
(254)
18-1/2(470)
8-1/2(216)
8-1/2(216)
8-1/2(216)
7-1/2(191)
eMer
Gen
cY
liG
Hti
nG
un
its
Hospitality Selection Guide
eMerG
enc
Y
E13www.acuitybrandslighting.com
laM
P coM
PatiBilitY
Multi-Faceted reflector
sealed & Gasketed Par36
Compact Designer square
Ordering Information – Lamp heads on this page can be ordered as separate fixtures, or as individual or twin remote heads with a mounting plate.
To Order Remotes: Order as separate line items.
NOTES:
For photometric information, visit our website at www.lithonia.com. Consult factory for additional lamp availability.
Dimensions are shown in inches (millimeters) unless otherwise noted
Remote Lamp Heads
Emergency lightingaccessory
ELA
Hazardous Par36indura® remote
square Par36
Width: 5-7/8" (149) single head,
7-1/8" (181) twin heads
Height: 5-1/8" (130)
Depth: 5-3/8" (137)
Standard color: Gray head and mounting plate, blue lamp housing
Width: 4-3/4" (121) single head,
13" (330) twin heads
Height: 7-3/4" (197)
Depth: 5-1/16" (129)
Standard
color: Gray Z Series match
Width: 4-3/4" (121) single head, 13" (330) twin headsHeight: 7-3/4" (197) Depth: 5-1/16" (129)Standardcolor: Gray
Width: 4-5/8" (118) single head, 110-1/2" (267) twin headsHeight: 5-1/8" (130) Depth: 6-1/2" (165)Standardfinish: Chrome
Optional finish: White
Width: 4-5/8" (117) single head,
6-5/8" (168) twin heads
Height: 6-5/8" (168) single head, 4-1/2" (114) twin heads
Depth: 2-1/2" (63)
Standard color: White Quantum® match
Width: 3-7/8" (98) single head,
10-5/8" (270) twin heads
Height: 4-1/4" (108)
Depth: 4-1/8" (107)
Standard color: Ivory white
Width: 4-3/4" (121) single head,
10-1/2" (267) twin heads
Height: 5" (108)
Depth: 4-1/2" (107)
Standard color: White
Ordering Information EXAMPLE: ela inD H2012
Metal Par36
standard Par36
Width: 4-3/4" (121) single head,
13" (330) twin heads
Height: 7-3/4" (197)
Depth: 5-1/16" (129)
Standard color: Desert tan
Lamp type
Select from lamp compatibility chart at bottom of the page.(For Indura® sealed beam lamps add suffix S to lamp nomenclature. Example: H35I2S)
Lamp head style
(blank) Standard PAR36 MR24 Multi-faceted reflector CDS Compact designer square SSB Square PAR36
Color
(blank) Standard color B Black W White ITN Instrument tan (Titan® Series
match). Available on standard PAR36 and NX head only
Number of lamps
(blank) Single T Twin
Mr24(blank)
inD
cDs ssB
MX Mt Z
Composite Lamps
Sealed-Beam Lamps
6 Volt 12 Volt 24 Volt
Incandescent Halogen Krypton Incandescent Halogen Krypton Incandescent Halogen Lamp Type N0606 N0806 N0906 H0606 H0806 H1006 H1206 H2006 K0606 K0906 N0912 N1212 N1812 H0812 H1212 H2012 K0912 N0924 N1824 H2024
Wattage 6W 8W 9W 6W 8W 12W 20W 6W 9W 9W 12W 8W 12W 20W 9W 9W 18W 20W
MR24 ■ ■ ■ ■ ■ ■ ■
CDS ■ ■ ■ ■ ■ ■ ■ ■ ■
IND ■ ■ ■ ■ ■ ■ ■ ■
■ Available (blank) Not available
■ Available (blank) Not available
IND Indura® NX Sealed and gasketed PAR36 MT Metal PAR36 Z Hazardous PAR36 (Class I, Division II)
6 Volt 12 Volt 24 Volt
Incandescent Halogen Incandescent Halogen Incand.
Lamp type N0606 N0806 N1206 N1806 N2506 H0606 H0806 H1206 H2006 N1212 N1812 N2512 N3512 N5012 H0812 H1212 H3512 H5012 N5024
Wattage 8W 12W 18W 25W 6W 8W 12W 12W 18W 25W 35W 50W 8W 12W 35W 50W 50W
SSB ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
IND ■ ■ ■
NX ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Standard PAR36 ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
MT ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Z ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
Hospitality Selection Guide
eMer
Gen
cY
E14 www.acuitybrandslighting.com
Bat
terY
Pa
cKs
Reduced-Profile Fluorescent Battery Packs, Linear Fluorescent Fixtures
PowerSentry®
Ordering Information Example: Ps1400QD sD
Options
SD Self-diagnostics2
DW UL Listed for use inside damp or wet location listed fixtures 0-50°C (32-122°F)3
Accessories (Order Separately)
PSSD Field installable self-diagnostic modules for PSQ500 DW, PSQ500QD, PS600 DW, PS600QD, PS1400 DW or PS1400QD
ELA TSPLP Remote or replacement test switch/pilot light and mounting plate PS300, PS300QD, PSQ500, PSQ500QD, PS600, PS600QD, PS1400 and PS1400QD.
ELA TSPLP SD Remote or replacement test switch/pilot light and mounting plate for self-diag-nostics PSQ500SD, PSQ500QDSD, PS600SD, PS600QDSD, PS1400SD and PS1400QDSD
ELA PSTS Double-pole, single-throw test switch (no pilot light)
ELA PSMK External mounting kit
ELA PSMKSD External mounting kit for self-diagnostics module
ELA PSDMT External mounting tray
ELA PSPRSB Field-installable interface for enhanced compatibility with lamp EOL (end of life) protected ballasts. For use with PSQ500, PS600 and PSI400 with quick disconnect (QD) and damp/wet (DW)7
NOTES:
1 Luminaire rating based on initial output of one 32W, T8 lamp.
2 Self-diagnostics (PSSD) module ships separately. See PSSD spec sheet for details. Not available on PS300QD.
3 Not available with Quick Disconnect wire harness. See below for housing dimensions.
4 To order a factory-installed battery pack, add suffix to fluorescent fixture catalog number.
5 Add DW to factory installed suffix to receive as wet or damp location listed, depending on the fixture. Applies to EL, EL5, EL6, EL14. Example: EL14 DW.
6 Add SD to suffix to receive self-diagnostics version. Example: EL5SD. Applies to EL5, EL6 and EL14.
6 Do not use with PSSD self-diagnostics module.
Length: 13.8 (351) – PS1400QD Length: 9.5 (241) – all others Width: 2.19 (59.5) Height: 1.18 (29.9)Shipping weight PS300QD: 1.0 lbs. (0. 45 kgs.) PS500QD: 1.0 lbs (0.45 kgs.) PS600QD: 1.5 lbs (0.68 kgs.) PS1400QD: 2.0 lbs (0.9 kgs.)
Intended Use
Factory- or field-installed inside or outside (field only) a fluorescent fixture to operate lamp(s) at an initial output of 10% to 95% of rated lamp lumens, providing optimum glare-free illumination for a minimum of 90 minutes upon interruption of normal power.
Features
Mounts concealed within fixture wireway for clean appearance and protection against van-dalism.
Reduced-profile footprint fits in the tightest application. Durable thermoplastic/metal housing resists impact, scratches or corrosion.
Sealed, maintenance-free, high-temperature nickel-cadmium batteries.
Factory installation4,5
EL PS300QD installed4,5
EL5 PSQ500QD installed4,5,6
EL6 PS600QD installed4,5,6
EL61LP PS600QD one-lamp operation installed4,5,6
EL14 PS1400QD installed4,5,6
EL141LP PS1400QD one-lamp operation installed4,5,6
PS300QD Reduced profile, Quick-Disconnect, 300 lumen output1
PSQ500QD Reduced profile, Quick-Disconnect, 15-minute installa-tion, 500 lumen output1
PS600QD Reduced profile, Quick-Disconnect, 600 lumen output1
PS1400QD Reduced profile, Quick-Disconnect, 1400 lumen output1
Dimensions are shown in inches (millimeters) unless otherwise noted.
Quick-Disconnect connector system allows for quick and easy replacements at end of life without re-wiring.
U.S. patent No. 5,814,971.
Listings
UL Listed. Damp location listing available.
2-1/2 (64)
1-5/8 (41)
Length: 13.8 (351) – PS1400 DW Length: 9.5 (241) – all others Width: 2.5 (63.5) Height: 1.675 (41)Shipping weight PS300DW: 1.4 lbs. (0. 6 kgs.) PS500DW: 1.0 lbs (0.45 kgs.) PS600DW: 1.8 lbs (0.8 kgs.) PS1400DW: 4.0 lbs (2.3 kgs.)
Electrical Application Data AC InputType Volts Amps WattsPS300QD 120/277 .29 2.5
PSQ500QD 120/277 .29 2.5PS600QD 120/277 .29 3.0PS1400QD 120/277 .29 3.5
PS300 DW / PSQ500 DW / PS600 DW / PS1400 DWCross section end view
PS300QD/PSQ500QD/PS600QD/PS1400QDCross section end view
2-1/4(56)
1-1/8(44)
Hospitality Selection Guide
eMerG
enc
Y
E15www.acuitybrandslighting.com
Fluorescent Battery Packs, Downlighting Fluorescent Fixtures
Power Sentry®
PSDL1 Bi-pin 18-26W quad-tube lampsPSDL2 Bi-pin 7-13W twin-tube or quad-tube lampsPSDL3 Four-pin 9-42W quad-tube or triple-tube lamps
Accessories (Order Separately)
ELA TSPLP Remote or replacement test switch/mounting plate for PSDL3
ELA PSTS Double-pole, single-throw test switch (no pilot light)
ELA PSDMT External mounting tray (PSDL1, PSDL2, PSDL3)
ELA RTS3 Remote test switch and pilot light for PSDL1 2LP
NOTES:
1 Available on PSDL3. Self-diagnostics (PSSD) module ships separately. See PSSD spec sheet for details.
2 Must specify PSDL1 2LP for two-lamp version. The PSDL3 product may be wired for a 2-lamp operation as a standard feature, see wiring diagrams. 2LP option does not need to be specified for the PSDL3.
3 To order a factory-installed battery pack, add suffix to fluorescent downlighting fixture catalog number. PSDL1/PSDL2/PSDL3 will be determined automatically based on ballast and lamp type. Add 2LP (example: EL2LP) to suffix to specify 2-lamp emergency operation for all 4-pin or 2-pin quad lamps. (Available for Gotham® downlighting and Lithonia downlighting.)
Ordering Information Example: PsDl3 sD
Intended Use
Factory- or field-installed on fluorescent down-lighting fixtures to operate lamps at an initial light output of 20% to 85% of full lumen rating, providing optimum glare-free illumination for a minimum of 90 minutes upon interruption of normal power.
Features
PSDL1 operates one two-pin 18W or 26W quad-tube compact fluorescent lamp. PSDL1 2LP operates 2 two-pin (13-26W) quad-tube fluorescent lamps.
PSDL2 operates one two-pin 7W, 9W or 13W quad-tube compact fluorescent lamp. PSDL3 operates one or two four-pin twin-tube (9-13W), triple-tube (18-42W*), quad-tube (13-26W) or 2D com-pact fluorescent lamp(s). *42W triple-tube is one lamp only.
Factory installation3
EL PSDL1/PSDL2/PSDL3 installed, compact fluorescent ELR PSDL1/PSDL2/PSDL3 installed, compact fluorescent
with remote pilot light/test switch
Dimensions are shown in inches (millimeters) unless otherwise noted.
Length: 12 (304) Shipping weight: 3.0 lbs. (1.4 kgs.)
PSDL1 2LPCross section end view
2-2/5(60)
1-1/2(38)
Options
SD Self-diagnostics1
DL Damp location listed 0-50°C (32-122°F)1 2LP Operates (2) two-pin quad-tube lamps (PSDL1)2
Length: 17-1/8 (435) Shipping weight: 5.0 lbs. (2.3 kgs.)
Length: 10-5/8 (270) Shipping weight: 2.14 lbs. (.9 kgs.)
PSDL1 and PSDL2 Cross section end view
2-3/8 (60)
1-1/2(38)
PSDL3Cross section end view
1-3/4(43)
Sealed, maintenance-free, high-temperature nickel-cadmium batteries.
Housing is permanently sealed steel enclo-sure.
Listings
UL Listed. Damp location listing available.
3-1/4 (81)
Electrical Application Data
AC Input
Type Volts Amps WattsPSDL1 120 .275 3.5 277 .255 3.5
PSDL2 120 .275 3.5 277 .255 3.5
PSDL3 120 .27 3.3 277 .25 3.2
BatterY Pa
cKs
Hospitality Selection Guide
eMer
Gen
cY
E16 www.acuitybrandslighting.com
AC Power Systems
EAC ISTEAC ISS
Options
Miscellaneous Modem External modem for RS232 3WS External 3-way switch RMP Remote meter panel2
FSP Factory start-up program RS232 Diagnostic interface DFC Form "C" contact DBR Dimmer bypass relay
(blank) NoneBattery 2HR 2-hour run time 4HR 4-hour run time1
Input/Output OTA Output trip alarm
Ordering Information Example: eac lc ist 1350 120/120 ota
Intended Use
Automatic standby AC power systems for incan-descent and fluorescent emergency lighting loads that provide full light output for 90 minutes of op-eration.
Features
Microprocessor-controlled PWM inverter with IGBT technology allows for universal compat-ibility.
RS232 interface option allows communication with system from remote computer. Low voltage disconnect, short circuit protection, current limit-ing and brown-out protection.
EAC IST:
One compact self-contained cabinet.
12-hour battery recharge. Input circuit breaker. Normally on and off output circuit breakers.
20-character display with touch pad (4x4) controls, functions and data logging.
Battery type
(blank) Lead-calcium LC20 Lead-calcium bat-
tery. 20-year life
System type
ISS Interruptible
VA rating1
1500225030003750500060008000
100001250016700
Options
Miscellaneous FSP Factory start-up
program RMP Remote panel meter MBYP Maintenance bypass
switch RS232 Diagnostic interface DFC Form "C" contact
(blank) NoneBattery 12HR 12-hour battery recharge Electronic TD Time delay (15 minute)Input/Output OCB Output circuit breaker (specify
quantity and amps)3
OTA Output trip alarm
Ordering Information Example: eac lc iss 1500 120/120 ocB
Voltage2
Input/Output120/120277/277277/120
120/120-277277/120-277
Family
EAC Emergency AC power system
NOTES:
1 Only available on the 750 VA.
2 Not available with the RS232.
NOTES:
1 Systems 5000VA (5KVA) or larger require external battery cabinets.
2 Consult factory for other voltages.
3 Standard 20-amp, normally on unless otherwise specified.
PoW
er s
Yste
Ms
Programmable self-diagnostic testing for 5 min-utes monthly and 90 minutes annually is stan-dard.
20 millisecond transfer time.
EAC ISS:
Stackable, modular cabinet design enabling ver-satile installation.
Systems 4KVA and below are self-contained. Larger systems require external, stackable battery cabinets.
Standard digital meter panel displays input/out-put voltage, battery voltage and output current.
24-hour battery recharge standard.
50 millisecond transfer time.
Listings
UL 924 Listed – 90 minutes of emergency op-eration.
Battery type
(blank) Lead-calcium
System type
IST Interruptible
VA rating
750 1350
Voltage
Input/Output120/120277/277
Family
EAC Emergency AC power system