Air Technology Systems, Inc.
Compact-Line CWCentrifugal Fan Systems
Engineering Manual
Precision Air Conditioning10 - 40 Tons(60 Hz Data)
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Stulz Air Technology Systems, Inc.
STULZ-ATS is dedicated to providing innovative solutions for critical temperature and humidity control needs. STULZ-ATS designs and manufactures specialized envi-ronmental control equipment for commercial, industrial and custom military applications. SATS serves a diverse marketplace - including telecommunications, information technology, medical, financial, educational, industrial process and government contracts - utilizing world-class “island” manufacturing processes in a modern, 150,000 ft2 facility. STULZ-ATS combines a global network of sales and service companies with an extensive factory engineer-ing staff and highly flexible manufacturing resources dedicated to providing world-class quality, innovation and customer service.
ISO-9001:2001Quality RegisteredSTULZ-ATS is committed to satisfying customer expectations by meeting and exceeding requirements. Our Quality Policy ensures that every Employee is committed to Customer Satisfaction, Teamwork and utilizing Continuous Process Improvement methods in order to deliver an exceptional product. We will continually measure our performance to improve the effectiveness of our quality management system
Precision A/C ApplicationsSTULZ-ATS is dedicated to the manufacturing of supplemental and precision air conditioning products. With an extensive installation base, Stulz-ATS has earned a solid reputation as a quality supplier and leader in its field.
Compact CW vertical, floor mounted air condi-tioning units provide precision temperature and hu-midity control for computer rooms and other critical areas where continuous 24 hourrs/day, 365 days/year operation is required. Designed for front only ac-cess.
Compact CW systems require minimal floor space. The units are designed with a wide range of options to handle both precision and comfort cooling applications.
Typical applications include:INDUSTRIES:
Internet / Web Hosting
Telecommunications
Financial / Banking
Insurance
Airlines / Mass Transit
Legal Services
Entertainment
Government
Colleges / Universities
APPL ICAT IONS :
Data Centers
Computer / LAN Rooms
Telecommunications Rooms
Co-location Centers
ISP (Internet Service Providers)
ASP (Applications Service Providers)
Hospital Operating & Isolation Rooms
Laboratories
1-1
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Table of Contents
Table of Contents
SECTION - 1
Introduction to SATS ....................................................1-1 Table of Contents .........................................................1-2
SECTION - 2
Compact CW SYSTEMS: Outstanding Advantages ..............................................2-1 User Oriented Features & Options .................................2-2 Available Configurations ...........................................2-3/4 Nomenclature Chart .....................................................2-5 Standard Features “Quick Reference Table” ..................2-6
SECTION - 3
GUIDE SPECIFICATIONS:Standard Features: Standard Guide Specifications ...................................3-1/4
Optional Features: Optional Features Index ................................................3-5 Optional Features Guide Specification .......................3-6/7
SECTION - 4
PERFORMANCE / CAPACITY SPECIFICATIONS: Performance/ Capacity Data Index ................................4-1 Performance Specifications ..........................................4-2 Capacity Data @ 45°F EWT ...........................................4-3 Capacity Data @ 50°F LWT ...........................................4-4
ELECTRICAL DATA: Electrical Data (FLA / MCA / MFS) .................................4-5 Electrical Calculation Example .......................................4-5
SECTION - 5
DIMENSIONAL / INSTALLATION DRAWINGS: Dimensional Data Index ................................................5-1
Standard Compact-CW Systems: 10 Ton, Up-Flow Systems ..............................................5-2 10 Ton, Down-Flow Systems .........................................5-3 20 - 40 Ton, Up-Flow Systems ......................................5-4 20 - 40 Ton, Down-Flow Systems ..................................5-5
Compact CW - Vertical Floor Systems
1-2
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Compact CW Systems
Compact CW Systems Offer Outstanding AdvantagesVersatility• Down-Flow and Up-Flow Air Patterns• Ducted Systems• Raised Floor Mounting with Floor Stands
100% Front Service AccessFrom 10-40 tons, Compact CW systems are designed for 100% Front-Only Access. The compact foot-prints require minimal floor space and are easily tucked into a corner, between cabinetry or side-by-side.
Non-Proprietary PartsCompact CW systems incorporate non-proprietary components where possible. Most major HVAC, refrigera-tion and electrical distributors stock an exact model cross reference or an alternate to most factory provided compo-nents.
Compact CW floor mounted A/C’s are designed to be the compact solution to your precision air conditioning requirements. Systems are available in sizes from 10 to 40 tons in the five space saving cabinet foot prints.
Efficiently designed for 100% front service access, Compact CW units can easily be tucked into a corner, between cabinetry or side-by-side. Compact CW units are especially adaptable to raised floors and are available in a down-flow air pattern configuration.
Microprocessor ControlPrecision temperature and/or humidity control with user-friendly microprocessor controls, offer a wide range of expanded control functions and alarms and is fully compat-able with the leading building management system plat-forms. For more information and specifications for Stulz-ATS contols please refer to our Stulz-ATS Controls Manual.
Code (UL / CSA) Conformance
- NYC MEA Approved (MEA-433-00-E)- CSA Compliance
CHILLED WATER SYSTEMS
(supplied by others)Remote Liquid Chiller
2-1
Air Technology Systems, Inc.
Air Technology Systems, Inc.
User Oriented Features & Options
Complete Temperature & Humidity Control • Electrode Canister Steam Humidification • Dehumidification Mode with - Staged Electric Reheat/Heat - Optional Hot Water Reheat/Heat - OptionalSCR controlled Reheat/Heat
Temperature / Humidity ControlCompact CW A/C’s incorporate modulating 2 or 3 way control valves and come standard with electrode canister steam humidifiers and a staged electric reheat for dehu-midification mode.
24/7 Year Round OperationOption offerings available with Compact CW A/C’s allow for year-round, 24 hrs-a-day A/C operation in any environ-ment in the world.
Modular Motor ControllersCompact CW systems incorporate modular motor con-trollers with motor circuit breakers in lieu of inconvenient replaceable fuses, eliminating the need for ANY motor fusing.
Quiet OperationLow RPM blowers, acoustically lined cabinets and low velocity grilles provide the optimum in quiet operation.
Warranty - 2 Year Parts Standard
Selected Standard Features:• Compact Foot Print• Microprocessor Control• Main Power Non-Fused Disconnect Switch• Modular Motor Controllers (w/motor circuit breakers)• Acoustical/Thermal Insulation• Aluminum Finned / Copper Tube Coils• Modulating 600 psi rated Chilled Water Control Valves
Other Available Options:• Automatic Switchover to Back-up Power• 2 & 3-way Grilled Plenum Boxes• Floor Stands • Condensate Pumps• Firestats• Smoke Detectors• Water Leak Detectors• High Static Belt-Drive Blowers• Special High Efficiency Filtration (Filters up-to 60% Avg. Efficiency)• Many more options available
100% Front Access
Compact CWModel CCD-900-CW (shown)
2-2
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Application Dependent Configuration Choices
CHILLED WATER SYSTEMS
CCU-( )-CW(Up-flow Air Pattern)
CCD-( )-CW(Down-flow Air Pattern)
Up-Flow Air Pattern
Down-Flow Air Pattern
2-3
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Flexible Air Pattern Configuration ChoicesUp-Flow Systems:
Down-Flow Systems:Top “Free” or “Ducted” Return with:
1 2
Top Discharge Through 2 or 3-way Grilled Plenum Box with:
Top “Ducted” Discharge with:
3 4
Rear “Ducted” ReturnFront “Free” Return
5
Rear “Ducted” ReturnFront “Free” Return
Bottom Discharge Into Raised Floor
2-4
Air Technology Systems, Inc.
Air Technology Systems, Inc.
No
men
clature
- Mo
del N
om
enclatu
re Ch
art
Model Nomenclature - “CCU/D” Systems
Up-FlowAir Patterns
Down-FlowAir Patterns
Nominal Capacity in kW
CC = Compact CW System
D = Down Flow Air PatternU = Up Flow Air Pattern
CW = Chilled Water System
CC D-90 0-CW E*
Number of Refrigeration Circuits
E = EC Fan* Please see the Stulz-ATS Compact-
CWE engineerng Manual for Chilled Water units ultilizing the EC Fan.
2-5
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Stand
ard Featu
res - “Qu
ick Referen
ce” Table
Selected Standard Features - “Compact CW Series”
Model 300 600 900SELECTED STANDARD FEATURES:TEMPERATURE CONTROL
2-Way Modulating Chilled Water Control Valve Standard Standard Standard
3-Way Modulating Chilled Water Control Valve Optional Optional Optional
2-Stage Electric Reheating/Heating Standard Standard Standard
3-Stage Electric Reheating/Heating N/A N/A N/A
Hot Water Reheat Optional Optional Optional
Cooling &/or Heating Only (No Humidity Control) Optional Optional Optional
High Efficiency, Aluminum Fin/Copper Tube Coils Standard Standard Standard
HUMIDITY CONTROL
Electrode Canister Steam Humidifier Standard Standard Standard
Dehumidification Mode- Electric Reheat Standard Standard Standard
CABINET
Galvannealed Steel, Powder Coated Finish Standard Standard Standard
2 lb Density Thermal & Sound Insulation Standard Standard Standard
Floor Stand (Adjustable, turning vanes optional) Optional Optional Optional
FILTERS / PLENUMS
2”, 30% Avg. Eff. Pleated Filters Standard Standard Standard
2”, 60% Avg. Eff. Pleated Filters Optional Optional Optional
2 or 3-way Plenum Box (Up-Flow Units) Optional Optional Optional
4”, 30% Avg. Eff. Pleated Filters N/A N/A N/A
4”, 60% Avg. Eff. Pleated Filters N/A N/A N/A
ELECTRICAL
3-Phase Power Supply - - - - - - See Electrical Table Section 4 - - - - - -
Multi-Voltage Control Transformer (24V Class 2) Standard Standard Standard
SAFETY FEATURES
Visual Local & Remote Alarms Standard Standard Standard
Main Power Non-Fused Disconnect, unit mounted Standard Standard Standard
Motor Overload Protection Standard Standard Standard
2-6
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Gu
ide Sp
ecificatio
ns - Stan
dard
Equ
ipm
ent
Guide Specifications - Standard Equipment • Motor branch circuit short
circuit protection • Motor load switching con-
trollers (contactors) • Motor overload protection
The system shall incorporate over-current and overload protection in accordance with UL 1995 require-ments. Each blower motor, electric heater stage and humidifier (if applicable) shall be provided with a factory mounted and wired starter/contactor.
The control circuit shall be a 24 VAC low voltage circuit including a circuit breaker for protection. Low voltage, high voltage and common wires shall be color coded and shall be individually numbered at each end for ease of service tracing. All wiring shall be in accordance with the National Electric Code (NEC).
Remote Start/Stop ContactsIncluded in the system’s electrical control circuit shall be a 2–pin terminal connection for remote stop/start of the Compact CW air conditioner by remote source.
Main Power Service Switch
The chilled water air handling unit (evaporator) shall be provided with a unit mounted main power service switch.
SATS Compact CW Series10 - 30 Tons “CCU/CCD” Vertical Floor Mounted
Precision Control Air Conditioners Chilled Water Systems
Product Guide Specification
This section must be carefully re-viewed and edited by the Engineer to meet the requirements of the specific project. Coordinate with other speci-fication sections and the drawings as necessary.
GENERAL
SUMMARYThe SATS Compact CW vertical floor-mounted air conditioning system shall provide precision temperature and/or humidity control for computer rooms or rooms containing telecommunica-tions or other highly-sensitive heat load equipment where continuous 24 hour a day, 365 days a year air conditioning is required. Designed for front-only access, Compact CW systems require minimum floor space. The units are designed with a wide range of options to handle both precision and comfort cooling ap-plications.
The supplied system shall be provided with ETL Certification.
The system shall be manufactured by Stulz Air Technology Systems, Inc. in Frederick, Maryland, USA.
DESIGN REQUIREMENTSThe environmental control system shall be an SATS COMPACT CW fac-tory-assembled unit. The unit shall be designed for corner installation, requiring front only access through a hinged and removable front access panel.
No allowance for side service access shall be required. The COMPACT CW Series units are especially adapted to raised floors and are available in down-flow air pattern configura-tions.
QUALITY ASSURANCESATS COMPACT CW systems shall be subjected to a complete operational and functional test procedure at the factory. The manufacturer shall be ISO-9001 certified.
PRODUCT
Cabinet and Frame Construction
Access panels shall be fabricated from heavy gauge steel and shall be securely attached to the base and top plates. Both shall be painted with a powder coat paint to match and provide corrosion protection. The panels shall be lined with 2 lb., high-density sound and thermal insulation and sealed with self-extinguishing gasketing conforming to NFPA 90A and 90B.
Electrical System
Modular Motor Controllers
The system shall incorporate modu-lar motor controllers utilizing motor start protectors and circuit breakers to eliminate the need for fuses. All wiring shall be in accordance with the National Electric Code (NEC) and shall include:
3-1
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Gu
ide Sp
ecificatio
ns - Stan
dard
Equ
ipm
ent
Guide Specifications - Standard EquipmentChilled Water
System Components
Chilled Water Cooling Coil:
The coil shall be constructed of seamless drawn copper tubes, mechanically bonded to tempered aluminum fins with a fin design for maximum heat transfer, and mounted in a condensate drain pan. The coil shall be designed for under 500 ft/min face velocity. The water circuit shall be designed to distribute water into the entire coil face area
CW Control Valve:
The water circuit shall include a factory mounted, 2-way modulat-ing control valve. Design pressure shall be 600 psig. Note: 3-way valves are optional.
Blowers / Motors
Belt-Driven Systems
The blower(s) shall be belt driven with a double-width, double-inlet housing and forward-curved blades and permanently lubricated ball bearings sized for a minimum life span of 100,000 hours of service life (L10 Life). The blower(s) shall be dynamically and statically bal-
anced to minimize vibration and oper-ate in the Class 1 operating range. The blower(s) shall be corrosion protected. The blower(s) shall be belt driven with dual belts sized for 200% of the fan motor horsepower. The blower shall have an adjustable base for belt ten-sioning and a locking system to prevent the motors from moving. The motor’s drive sheaves shall have an adjustable pitch to change the speed of the blow-ers. The motor shall be 1725 rpm and shall have overload protection and a minimum NEMA service factor of 1.15.
HUMIDITY CONTROL:
The humidifier shall be of a self-con-tained steam generating electrode type utilizing a plastic disposable cylinder with full probes connected to electric power via electrode screw connectors. The electrodes shall be constructed from expanded low car-bon steel, zinc plated and dynamically formed for precise current control. The humidifier assembly shall include integral fill cup, fill and drain valves and associated piping.The canister shall be designed to col-lect the mineral deposits in the water and provide clean particle free steam to the air stream, thereby reducing maintenance cost.
The microprocessor control shall main-tain humidifier operation through fill and drain cycles based on the water conductivity. Overflow and loss of flow protection shall be provided
along with a manual drain switch. A high water alarm with built-in time delay shall provide an indication to change canister. The humidification system shall require no cleaning main-tenance during the cylinder life.
The humidifier shall discharge steam at 212°F, atmospheric pressure. It shall be capable of operating with water in the range of 200 to 1500 microm-hos. The steam shall be introduced into the air stream after the chilled water coil by a calibrated discharge tube, designed to equally distribute the steam to the air stream without condensation. The humidifier shall be provided with a manual adjustable capacity control.
Reheat / Heat
A factory mounted and wired low-watt density, plated fin-tubular design electric resistance heater shall be in-cluded to provide automatic sensible re-heating as required during the dehumidification cycle and automatic heating mode. Electric heaters shall be provided with miniature thermal/magnetic circuit breakers, which shall protect each ungrounded conductor. Also included will be one automatic reset and one manual reset over-tem-perature safety device (pilot duty)
Dehumidification CycleThe system shall provide a dehu-midification control mode. The chilled water valve shall be opened proportionally as needed to allow chilled water flow to the cooling coil when a dehumidification demand is activated. Moisture is condensed on the cooling coil and discharged through the condensate drain.
3-2
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Gu
ide Sp
ecificatio
ns - Stan
dard
Equ
ipm
ent
Guide Specifications - Standard EquipmentAir Patterns and Filtration
UP-FLOW:(CCU-( )-( ))
The air conditioner shall be config-ured for an up-flow air pattern with free return air through front filtered grille and conditioned supply air through the top of the unit.
Top “Ducted” Discharge with:
Front “Free” Return
Top Discharge Through 2- or 3-way Grille Plenum
Box with: Front “Free” Return
DOWN-FLOW:(CCD-( )-( ))
The air conditioner shall be config-ured for a down-flow air pattern with free return air from the top and conditioned supply air discharge through bottom of the A/C into the raised floor.
(Floor Stands are optionally available)
Air Filtration
The A/C unit shall have slide out, class 2 (per U.L. Standard 900) filters. The filters shall be easily ac-cessed through the front. The filters shall have an average efficiency rat-ing of 30% as measured by ASHRAE Standard 52-76 test method.
3-3
Air Technology Systems, Inc.
Air Technology Systems, Inc.
NotesN
otes
3-4
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Optional Features - Guide SpecificationsGu
ide Sp
ecificatio
ns - M
icrop
rocesso
r Co
ntro
l Op
tion
s
OPTION ..........................................................page
OPTIONS & ACCESSORIES
• Adjustable Floor Stands - Seismic Floor Stand ....................................................... 3-6 - Turning Vanes ............................................................... 3-6• EC Fans ............................................................................. 3-6• IAQ High Efficiency Filters .............................................. 3-6• 2 or 3-Way Plenum Discharge Box ................................. 3-6• Automatic Dual Power Transfer Switch ........................ 3-6• 2-Way Chilled Water Control Valve ................................ 3-6• Condensate Pump ........................................................... 3-7• Smoke Detector .............................................................. 3-7• Firestat ............................................................................. 3-7• Remote Water Detector: - Qty. One, Spot Type ...................................................... 3-7 - Qty. Two, Spot Type ...................................................... 3-7 - 25 Ft. Strip/Cable Type .................................................. 3-7
Optional Features Index
Compact CWModel CCD-900-CW
3-5
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Optional Features - Guide SpecificationsG
uid
e Specifi
cation
s - Micro
pro
cessor C
on
trol O
ptio
ns
ACCESSORIES
Adjustable Floor Stand
An adjustable floor stand shall be provided to allow for ease of installation of the A/C onto a raised floor. Floor stand height shall be adjustable. The Floor stand shall ship separately for field installation.
Additional Floor Stand Options:
Seismic Zone-4 Rated:
The adjustable floor stand shall be certified rated for seismic zone-4 installation.
Turning Vane:
Turning vanes shall be factory in-stalled to each unit’s floor stand.
High Efficiency EC Fan
Stulz-ATS Compact-Line Models ranging rom 10-100 tons are available with the energy efficient EC Fans in our unique, energy-saving cabinet design. Refer to the SATS Compact CWE™ engineer-ing manual for complete specifica-tions on Compact Chilled Water A/C systems utilizing EC Fans.
Filtration
Compact CW A/C’s are available with the following optional, high efficiency IAQ conscious filtration:
2”, 60% Eff. Filters (opt 300/900) 4”, 60% Eff. Filters (opt 1800)
Filters ratings are based on dust spot efficiency ratings based on ASHRAE Test Standard 52-76.
Top Discharge Plenum Box(Upflow Units Only)
A 2- or 3-way plenum discharge box shall be provided.The plenum box shall include double-deflecting, adjustable grilles.
3-Way Chilled Water Control Valve
A 3-way fully modulating valve shall be factory piped and wired. The 3-way chilled water modulating valve
shall automatically meter the flow of chilled water to the cooling coil as needed for cooling load control, the remaining flow shall bypass the cooling coil. A proportional signal (0-10 VDC) is provided to the valve by the microprocessor controller. The pressure rating of the valve is 600 psi. Manual override capabilities shall be standard on the actuator drive.
Manual Control Override Switch
A front panel mounted keyed switch shall allow full fan operation and 100% chilled water valve flow once engaged in the unlikely event of a controller failure.
Automatic Dual Power Transfer Switch
Two individual main power input dis-connect switches shall be provided, one for each incoming power source. In the event the primary power fails or a phase loss/imbalance occurs, the automatic transfer switch immedi-ately transfers power to the second-ary power source. Once the primary power has been restored, the transfer switch automatically shifts the power load back to the primary power. The transfer time from one source to the other is user adjustable to allow stag-ing or sequence restart of load.
In addition to the automatic transfer switch function, the local controller display shall indicate which power source has failed. This indication is a visual depiction that allows the user to determine the status of the input source. This status can also be conveyed thru the BMS serial com-munication link.
Compact CW systems include the C6000 Microprocessor Controller, Electrode Canister Steam Humidi-fier and Dehumidification Mode with Electric Reheat/Heat for total temperature and humidity control, as a standard.
However, these standard features can be deleted and/or substituted with alternate features to allow you the flexibility to select the configuration best suited for your application.
SELECTED OPTIONS
3-6
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Optional Features - Guide SpecificationsOp
tion
al Features - G
uid
e Specifi
cation
s
Optional - A thru-the-door indicator light is available for a fast local notifi-cation of available power sources. The indication is on if power is available.
Condensate Pump
A condensate pump shall be factory in-stalled within the Compact CW system (up-flow) and field installed (ship loose for down-flow units) for automatic removal of condensate and humidifier flush water (if applicable). The con-densate pump shall include an internal overflow safety float which, when wired to the unit’s remote stop/start terminals, shall open the unit’s control circuit, thereby shutting the unit down in the event of a condensate overflow. The condensate pump shall be specifically designed to operate with the higher condensate temperatures caused by the flush and drain cycle of the electrode canister humidifiers.
Smoke Detection
A photo-electric smoke detector shall be factory installed and wired in the evaporator section of the suction side of the blower. The air conditioner will shut down upon sensing smoke in the return air stream.
Firestat
The air conditioner shall be provided with a factory wired and mounted fir-estat. The firestat will shut down the air conditioner upon sensing a high return air temperature.
Remote Water Detectors
Single (one) - Spot Type Detector:
A remote single point water/leak detec-tor shall be factory supplied and shall ship separately for field installation. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the A/C unit.
Dual (two) - Spot Type Detectors:
Quantity 2-(two) remote spot type water/leak detectors per A/C unit shall be factory provided for remote field installation. Upon sensing a water leak, the normally closed water detector con-trol circuit shall open, thereby shutting down AC unit.
Remote Water Detector - Strip Type:
A 25 ft. in length remote strip/cable type water/leak detector shall be provided for remote field installa-tion. Upon sensing a water leak, the normally closed water detector control circuit shall open, thereby shutting down the A/C unit.
3-7
Air Technology Systems, Inc.
Air Technology Systems, Inc.
NotesN
otes
3-8
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Specifi
cation
Data
- Ind
ex
Specification Data - 10 to 40 Ton “CCU/D”
“Index”
Category ..................................................page
Chilled Water Systems
Specifications:
PerformanceSpecifications .........................................4-2Performance/Capacity Data 45°F EWT .........................4-3Performance/Capacity Data 50°F EWT .........................4-4
Electrical:
Electrical Data .............................................................4-5Calculation Example ....................................................4-5
Compact CWModel CCD-900-CW
4-1
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Perform
ance Sp
ecificatio
ns - C
hilled
Water (10-40 To
n System
s)
Chilled Water - 10 to 40 Ton Systems“CW” Model CCU/D-300 CCU/D-600 CCU/D-900Chilled Water Control Valve - Sized for Medium Flow @ 75°FDB/62.5°FWB EAT Conditions2-way (standard) - Modulating
Size / (Cv) 1”/(14 Cv) 1 1/4”/(20 Cv) 1 1/2”/(28 Cv)
Valve Pressure Rating - psi 600 600 600
Close-off Pressure Rating - psi 200 200 200
3-way (optional) - Modulating
Size / (Cv) 1”/(14 Cv) 1 1/4”/(20 Cv) 1 1/2”/(28 Cv)
Valve Pressure Rating 600 psig 600 psig 600 psig
Chilled Water Coil - Aluminum Fin, Copper TubeRows/Face Area (ft2) 6 / 15.2 4 / 27.6 6 / 27.6
Face Velocity, fpm 408 380 416
Evaporator Blower / Motor - DWDI Centrifugal - Belt Driven, Variable Pitch PulleysHorsepower 5 Hp 5.0 Hp 7.5 Hp
CFM @ ext. st. press. 6,200 @ 0.3” 10,500 @ 0.3” 11,500 @ 0.3”
Drive Method Belt Belt Belt
Reheat/Heat - Performance Capacities Include Evaporator Blower Motor HeatELECTRIC REHEAT / HEAT - Finned Tubular Heaters, (Standard)
Heater Kw Rating (No. of Stages) 12 Kw (2-stg) 24 Kw (2-stg) 24 Kw (2-stg)
Total BTU/H w/ Evap Mtr Ht: 53,670 94,625 100,980
HOT WATER REHEAT / HEAT - Reheat rated @ 180°F Entering Water Temperature, EAT = 72°F DB, 60°F WB (Optional)
BTU/H 115,809 110,995 117,290
GPM / Press. Drop (ft.wg) 11.8 / 17.8 11.3 / 16.6 12.0 / 18.1
EWT / LWT 180 / 160 180 / 160 180 / 160
Control VALVE: ON/OFF 2-Way, 1” 300PSI, CV=8.0
Humidification - Electrode Steam Canister Humidifier with Adjustable Output, (Standard)Lbs/Hr, (Kw Input) 4-15, (5.1) 4-15, (5.1) 4-15, (5.1)
Std Control Cycling Cycling Cycling
Filters - 30% Average Efficiency, throwawayUp-Flow:
Nom. Size (in.), (Qty.) 20 x 25 x 2 (2) 18 x 25 x 2 (4) 18 x 25 x 2 (4)
Down-Flow:
Nom. Size (in.), (Qty.) 14 x 32 x 4 (3) 25 x 32 x 4 (3) 25 x 32 x 4 (3)
Connection Sizes - Copper, (Water In/Out connections are sized for flow rates at 75°FDB/62.5°FWB EAT condi-tions.)
Condensate Drain, (w/ pump) 7/8” OD, (1/2”OD) 7/8” OD, (1/2”OD) 7/8” OD, (1/2”OD)
Humidifier Inlet 1/4” OD 1/4” OD 1/4” OD
Water In/Out 1” Sweat 1-5/8” Sweat 1-5/8” Sweat
Physical DataApprox. Weight 705lbs 990lbs 1,080lbs.
Dimensions: (H”xW”xD”), includes access panels, w/o Plenum Box option.CCU-( )-CW (up-flow) 75.5” x 46.2” x 35.4” 75.5” x 77.6” x 35.4”
CCD-( )-CW (down-flow) 75.5” x 46.2” x 34.6” 75.5” x 77.6” x 34.6”
4-2
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Perform
ance/C
apacity D
ata - C
hilled
Water (10-40 To
n System
s)
Chilled Water - 45°F EWT, 0% GlycolModel: 300-CW 600-CW 900-CW
NET COOLING CAPACITY - BTU/H @ 45°F EWT, 0% Glycol Solution (Includes motor heat @ std CFM & e.s.p. ratings)
80°FDB/67°FWB, 50% RHHigh Flow Total 189,079 341,823 436,967
(10°F ∆Tw) Sensible 137,738 265,746 306,781
GPM / (pd. Ft.) 40.3 / 32.7 70.9 / 71.1 91.2 / 65.1
Med. Flow Total 169,644 325,679 417,884
(12°F ∆Tw) Sensible 129,356 257,301 298,017
GPM / (pd. Ft.) 30.4 / 20.3 56.3 / 47.1 72.9 / 43.7
Low Flow Total 150,642 310,557 394,133
(14°F ∆Tw) Sensible 120,762 248,759 287,013
GPM / (pd. Ft.) 23.4 / 13.6 46.1 / 33.4 59.1 / 30.4
75°FDB/62.5°FWB, 50% RHHigh Flow Total 135,487 260,721 335,950
(10°F ∆Tw) Sensible 118,808 234,149 273,092
GPM / (pd. Ft.) 29.7 / 19.6 54.6 / 44.8 71 / 41.7
Med. Flow Total 97,850 242,764 319,107
(12°F ∆Tw) Sensible 97,850 221,984 264,157
GPM / (pd. Ft.) 18.5 / 10 42.6 / 19.7 56.5 / 28.3
Low Flow Total 97,867 219,954 297,771
(14°F ∆Tw) Sensible 97,867 205,683 252,447
GPM / (pd. Ft.) 14.5 / 7.8 33.2 / 19.7 45.3 / 19.9
72°FDB/60°FWB, 50% RHHigh Flow Total 93,339 199,089 282,000
(10°F ∆Tw) Sensible 93,339 199,089 249,863
GPM / (pd. Ft.) 21.3 / 12 42.4 / 29.1 60.3 / 31.6
Med. Flow Total 79,468 178,914 216,415
(12°F ∆Tw) Sensible 79,468 178,914 216,415
GPM / (pd. Ft.) 15.5 / 6.7 32 / 18.7 39.3 / 16.1
Low Flow Total 72,557 155,064 189,756
(14°F ∆Tw) Sensible 72,557 155,064 189,756
GPM / (pd. Ft.) 12.3 / 6.7 24 / 12.5 30 / 11.1
80°FDB/65°FWB, 45% RHHigh Flow Total 176,928 319,648 410,447
(10°F ∆Tw) Sensible 147,835 282,621 327,433
GPM / (pd. Ft.) 37.9 / 29.4 66.2 / 63 85.7 / 58.2
Med. Flow Total 159,218 306,162 396,399
(12°F ∆Tw) Sensible 139,620 273,790 320,249
GPM / (pd. Ft.) 28.7 / 18.5 53.1 / 42.5 69.3 / 40
Low Flow Total 118,327 289,304 379,809
(14°F ∆Tw) Sensible 118,327 262,337 311,591
GPM / (pd. Ft.) 18.8 / 10.2 43.1 / 29.9 57.2 / 28.8
75°FDB/61°FWB, 45% RHHigh Flow Total 114,994 233,168 324,169
(10°F ∆Tw) Sensible 114,994 233,168 289,782
GPM / (pd. Ft.) 25.6 / 15.6 49.1 / 37.3 68.6 / 39.3
Med. Flow Total 97,466 214,860 303,188
(12°F ∆Tw) Sensible 97,466 214,860 278,301
GPM / (pd. Ft.) 18.5 / 10 38 / 24.4 53.7 / 26
Low Flow Total 97,619 193,607 235,874
(14°F ∆Tw) Sensible 87,619 193,607 235,874
GPM / (pd. Ft.) 14.4 / 7.7 29.5 / 16.6 36.5 / 14.5
72°FDB/59°FWB, 45% RHHigh Flow Total 93,044 198,633 237,675
(10°F ∆Tw) Sensible 93,044 198,633 237,675
GPM / (pd. Ft.) 21.3 / 12 42.3 / 28.9 51.5 / 24.4
Med. Flow Total 79,271 178,430 215,840
(12°F ∆Tw) Sensible 79,271 178,430 215,840
GPM / (pd. Ft.) 15.5 / 833 31.9 / 18.6 39.2 / 16.1
Low Flow Total 72,359 154,531 189,106
(14°F ∆Tw) Sensible 72,359 154,531 189,106
GPM / (pd. Ft.) 12.3 / 6.7 24 / 12.5 29.9 / 11.1
4-3
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Chilled Water - 50°F EWT, 0% Glycol Perform
ance/C
apacity D
ata - C
hilled
Water (10-40 To
n System
s)
Model: 300-CW 600-CW 900-CWNET COOLING CAPACITY - BTU/H @ 50°F EWT, 0% Glycol Solution (Includes motor heat @ std CFM & e.s.p. ratings)
80°FDB/67°FWB, 50% RHHigh Flow Total 144,442 268,350 348,803
(10°F ∆Tw) Sensible 119,891 233,549 270,830
GPM / (pd. Ft.) 31.6 / 21.7 56.2 / 46.9 73.7 / 44.3
Med. Flow Total 119,756 255,766 334,492
(12°F ∆Tw) Sensible 108,911 224,906 263,705
GPM / (pd. Ft.) 22.2 / 12.6 44.7 / 31.6 59 / 30.2
Low Flow Total 88,565 236,187 317,517
(14°F ∆Tw) Sensible 88,565 211,689 254,925
GPM / (pd. Ft.) 14.6 / 7.7 35.6 / 21.9 48.2 / 21.8
75°FDB/62.5°FWB, 50% RHHigh Flow Total 82,188 179,881 216,065
(10°F ∆Tw) Sensible 82,188 179,881 216,065
GPM / (pd. Ft.) 19.1 / 10.4 28.6 / 24.9 47.2 / 21.7
Med. Flow Total 69,750 159,297 193,312
(12°F ∆Tw) Sensible 69,750 159,297 193,312
GPM / (pd. Ft.) 13.9 / 7.4 28.7 / 15.9 35.7 / 14
Low Flow Total 62,744 134,513 165,332
(14°F ∆Tw) Sensible 62,744 134,513 165,332
GPM / (pd. Ft.) 10.9 / 6.1 21.1 / 10.6 26.5 / 9.5
72°FDB/60°FWB, 50% RHHigh Flow Total 61,137 143,529 173,569
(10°F ∆Tw) Sensible 61,137 143,529 173,569
GPM / (pd. Ft.) 14.9 / 7.9 31.3 / 18 38.7 / 15.7
Med. Flow Total 54,176 119,503 146,209
(12°F ∆Tw) Sensible 54,176 119,503 146,209
GPM / (pd. Ft.) 11.3 / 6.3 22.1 / 11.3 27.7 / 9.7
Low Flow Total 46,988 88,904 105,941
(14°F ∆Tw) Sensible 46,988 88,904 105,941
GPM / (pd. Ft.) 8.7 / 5.4 14.7 / 7.1 18 / 6.5
80°FDB/65°FWB, 45% RHHigh Flow Total 119,060 235,799 332,681
(10°F ∆Tw) Sensible 119,060 235,799 294,196
GPM / (pd. Ft.) 26.4 / 16.4 49.8 / 38 70.4 / 41
Med. Flow Total 102,911 219,848 315,085
(12°F ∆Tw) Sensible 102,911 219,848 284,966
GPM / (pd. Ft.) 19.4 / 10.5 38.7 / 25 55.8 / 27.6
Low Flow Total 88,191 200,146 243,954
(14°F ∆Tw) Sensible 88,191 200,146 243,954
GPM / (pd. Ft.) 14.5 / 7.7 30.5 / 17.3 37.7 / 15.1
75°FDB/61°FWB, 45% RHHigh Flow Total 81,866 179,393 215,500
(10°F ∆Tw) Sensible 81,866 179,393 215,500
GPM / (pd. Ft.) 19.1 / 10.3 38.5 / 24.6 47.1 / 21
Med. Flow Total 69,543 158,773 193,300
(12°F ∆Tw) Sensible 69,543 158,773 193,300
GPM / (pd. Ft.) 13.9 / 7.4 28.7 / 15.8 35.6 / 14
Low Flow Total 62,534 133,922 164,610
(14°F ∆Tw) Sensible 62,534 133,922 164,610
GPM / (pd. Ft.) 10.9 / 6.1 21 / 10.6 26.4 / 9.5
72°FDB/59°FWB, 45% RHHigh Flow Total 61,298 143,131 173,102
(10°F ∆Tw) Sensible 61,298 143,131 173,102
GPM / (pd. Ft.) 15 / 8 31.2 / 18 38.6 / 15.6
Med. Flow Total 54,339 119,054 145,661
(12°F ∆Tw) Sensible 54,339 119,054 145,661
GPM / (pd. Ft.) 11.3 / 6.3 22.1 / 11.2 27.6 / 10
Low Flow Total 47,154 88,750 105,191
(14°F ∆Tw) Sensible 47,154 88,750 105,191
GPM / (pd. Ft.) 8.7 / 5.4 14.7 / 7.1 17.9 / 6.4
4-4
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Electrical Data - Chilled Water SystemsElectrical Data
- Ch
illed W
ater Systems
Model300 600 900
FLA MCA MFS FLA MCA MFS FLA MCA MFSCooling w/ Electric Reheat & Humidification208/3/60 59.1 73.9 80 89.3 111.6 125 97.5 121.9 125460/3/60 28.7 35.9 40 43.7 54.6 60 47.6 59.5 70575/3/60 23.0 28.8 30 35 43.8 50 37.8 47.3 50Cooling w/ Electric Reheat 208/3/60 44.9 56.1 70 75.1 93.9 100 83.3 104.1 125460/3/60 22.3 27.9 35 37.3 46.6 50 41.2 51.5 60575/3/60 17.9 22.4 25 29.9 37.4 40 32.7 40.9 50Cooling w/ Humidification208/3/60 28.9 36.1 50 28.9 36.1 50 37.1 46.4 70460/3/60 13.5 16.9 25 13.5 16.9 25 17.4 21.8 35575/3/60 11.0 13.8 20 11.0 13.8 20 13.8 17.2 25Cooling Only208/3/60 14.7 18.4 35 14.7 18.4 35 22.9 28.6 60460/3/60 7.1 8.9 20 7.1 8.9 20 11.0 13.8 25575/3/60 5.9 7.4 15 5.9 7.4 15 8.7 10.9 20
EXAMPLES - Electrical Data Calculation
Example 1:Suppose an application calls for a nominal 10 Ton Compact-Line CW model CCD-300-CW with the following features: - 208/3/60 Main Power Supply - Electric Reheat/Heat, (Standard) - Steam Humidifier, (Standard)Solution:From Electrical Data table page 4-5 for model CCD-300-CW incorporating COOLING with ELECTRIC REHEAT/HEAT and HUMIDIFIER: CCD-300-CW @ 208/3/60 with above options: FLA (OEM Rated) = 59.1 MCA = 73.9 MFS = 80
Example 2:Suppose an application calls for a nominal 30 Ton Compact-Line CW model CCD-900-CW system with the following features: - 460/3/60 Main Power Supply - Electric Reheat, (Standard) - No HumidifierSolution:From Electrical Data table page 4-5 for model CCD-900-CW incorpo-rating COOLING Only with Electric Reheat: CCD-900-CW @ 460/3/60 with above options:
FLA (OEM Rated) = 41.2 MCA = 51.5 MFS = 60
4-5
Air Technology Systems, Inc.
Air Technology Systems, Inc.
Dimensional Data - Standard “CCU/D” Configurations Dim
ensio
nal D
ata - In
dex
(Drwg. #) MODEL TYPE .................................................... page
Vertical Floor Systems
CCU/D - 300 - CW:
(CW-01) “Up-Flow” Air Pattern Configuration .............. 5-2(CW-02) “Down-Flow” Air Pattern Configuration ........ 5-3
CCU/D - 600/900 - CW:
(CW-03) “Up-Flow” Air Pattern Configuration .............. 5-4(CW-04) “Down-Flow” Air Pattern Configuration ........ 5-5
Index
5-1
Air Technology Systems, Inc.
Air Technology Systems, Inc.
10 Ton CCU - “Up-Flow” Air Pattern Systems Dim
ensio
nal D
ata - 10 Ton
s (“Up
-Flow
” Air Pattern
Systems)
(CW-01) CCU-300-CW“Up-Flow” Vertical A/C
(as “Ducted” or with Opt. “2 or 3-way Plenum Box”)
Adjustable Floor Stand: (Optional)
4 - 10” Up-flow only
ISO DWGDim A
Nominal(inches)
Dim A Minimum(inches)
Dim A Maximum
(inches)
4” - 10” 4 3.7 4.5
4” - 10” 6 5 7
4” - 10” 8 7 9
4” - 10” 10 9 11
12” - 24” 12 11 15
12” - 24” 15 14 18
12” - 24” 18 17 21
12” - 24” 24 23 26
12 - 24”
5-2
Air Technology Systems, Inc.
Air Technology Systems, Inc.
(CW-02) CCD-300-CW“Down-Flow” Vertical A/C
10 Ton CCU - “Down-Flow” Air Pattern Systems Dim
ensio
nal D
ata - 10 Ton
s (“Do
wn
-Flow
” Air Pattern
Systems)
Adjustable Floor Stand: (Optional)
ISO DWGDim A
Nominal(inches)
Dim A Minimum(inches)
Dim A Maximum
(inches)
12” - 24” 12 11 15
12” - 24” 15 14 18
12” - 24” 18 17 21
12” - 24” 24 23 26
5-3
Air Technology Systems, Inc.
Air Technology Systems, Inc.
20 to 40 Ton CCU - “Up-Flow” Air Pattern SystemsDim
ensio
nal D
ata - 20 to 40 To
ns (“U
p-Flo
w” A
ir Pattern System
s)
(CW-03) CCU-600/900-CW“Up-Flow” Vertical A/C
(as “Ducted” or with Opt. “2 or 3-way Plenum Box”)
Adjustable Floor Stand: (Optional)
FRONT/RIGHT REAR/LEFT
ISO DWGDim A
Nominal(inches)
Dim A Minimum(inches)
Dim A Maximum
(inches)
4” - 10” 4 3.7 4.5
4” - 10” 6 5 7
4” - 10” 8 7 9
4” - 10” 10 9 11
12” - 24” 12 11 15
12” - 24” 15 14 18
12” - 24” 18 17 21
12” - 24” 24 23 26
4 - 10” Up-flow only
12 - 24”
5-4
Air Technology Systems, Inc.
Air Technology Systems, Inc.
(CW-04) CCD-600/900-CW“Down-Flow” Vertical A/C
(“Free Return” or with Opt. “Ducted Return”)
20 to 40 Ton CCU - “Down-Flow” Air Pattern Systems Dim
ensio
nal D
ata - 20 to 40 To
ns (“D
ow
n-Flo
w” A
ir Pattern System
s)
Adjustable Floor Stand: (Optional)
FRONT/RIGHT REAR/LEFT
ISO DWGDim A
Nominal(inches)
Dim A Minimum(inches)
Dim A Maximum
(inches)
12” - 24” 12 11 15
12” - 24” 15 14 18
12” - 24” 18 17 21
12” - 24” 24 23 26
5-5
Air Technology Systems, Inc.
Air Technology Systems, Inc.
1572TilcoDrive,Frederick,Maryland21704Phone:301.620.2033,Fax:301.662.5487E-mail:info@stulz-ats.com
ISO-9001:2001 Quality RegisteredISO9001
Registered
Quality System
Air Technology Systems, Inc.
www.stulz-ats.com
This document was printed on recycled paper, with ecosmarttm environmentally responsible ink products.
Copyright, February 2010QE-CCW0028 Rev A
Specifications subject to change without notice.
thegreenerwayofcoolingyourdatacenter.