Post on 02-Jun-2018
transcript
8/10/2019 Explosion Proof Actuators
1/76
2 0 1 4
Schischek Explosion Proof. Actuators and Sensors for Hazardous (Classied) Locations.Protection of Life. Health. Assets.
North American Price List valid from January 1, 2014
www.schischek.com
Technical Short Information North America
8/10/2019 Explosion Proof Actuators
2/76
8/10/2019 Explosion Proof Actuators
3/76www.schischek.com
North American Price List 2014
3
Explosion Protection Since 1975Since 1975 Schischek has supplied electric explosionproof products worldwide for heating, ventilation andair-conditioning, for industrial and offshore applications.
Schischek Explosionproof has become an importantpartner for consultants, public authorities, control com-panies, installers, OEMs and, not least of all, the enduser.
As supplier of components, we have always consideredit our duty to develop products in conjunction with othercontrol equipment. Modern Ex equipment, reliable,proven and with state of the art technology.
Safety is EssentialWith this motto we state that explosion protection is nota question of statistics or half hearted solutions but that100% safety must be guaranteed at all times. Explosionprotection means taking on responsibility.
There is No Little Ex Protection!People have confidence in us as Ex protection special-ists and in you as consultant, installer and contractor.
All Schischek Ex products are, therefore, PTB certified,approved by and produced according to the very lateststandards and regulations. According to type and kindof protection, our products are suitable for operation inEx areas, zones 0, 1, 2, 20, 21 and 22, including gases,vapours, mists and dusts of course in accordancewith ATEX 94/9/EC.
Schischek supplies control companies and contractorsin the Building Automation market. We have developedequipment which is compatible with nearly all controlsystems. By combining Schischek products with con-ventional switching and control equipment, reliablehigh quality systems are implemented that conform toEx protection standards. Some examples of use are
fire and smoke dampers, paintspray areas, exhaustsystems in chemical laboratories, battery rooms, sew-age treatment plants, pumping stations etc.
Whether you need air flow control in a pharmaceuticalplant or temperature regulation of paint tanks in the carindustry, Schischek offers cost-effective solutions spe-cifically designed for control integration. Ex protectionis required for applications from paint spray shops to
drying stations. System compatibility with all aspectsof control facilitates integrated planning from design to
completion. At the same time, safety and reliability increase in planning, installation, approval and operationSince all equipment is maintenance-free, cost savingsare realised.
In co-operation with valve and damper manufactur-ers, industrial control companies and contractors,Schischek products are in use worldwide. Our productsare characterised by the highest protection class, com-pact size and easy handling.
We can provide solutions to problems as far as Exventilation and precise temperature control in industriaplants are concerned.
Harsh environmental conditions and robust quality
cause stringent design / construction requirements oncomponents and materials. A fast closing electric ac-tuator for fire / smoke dampers of less than 3 secondsis a requirement on oil and gas platforms as well ason FPSOs. After an intense development processincluding trials, a completely new concept in actua-tor engineering was produced. Since, thousands of
Schischek actuators in special aluminium, C5-M and
stainless steel housings have been delivered and in-stalled, moreover, the product range has been continu-ously enlarged and refined.
Chemical, Pharmaceutical, Car Industries
Water Treatment Plants, Compressor Stations
Offshore, Onshore, Shipbuilding
Heating, Ventilation, Air-Conditioning
Safety, Worldwide,in Thousands of Applications!
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
4/76
North American Price List 2014
www.schischek.com4
M
+
P F
M
M
M
Hz
%rF
P
%rH
Air damper Air filter Heater Fan Hum
S a
f e a r e a
E x a r e a
O r d
i n a r y
L o c a
t i o n
H a z a r d o u s
L o c a
t i o n 676
43
3
2
2
1
1
Which Components Have to be Explosion Proof?
Temperature and Humidity Sen
ExCos-DRedCos-D
40+257 F 0100 %rH full range adjustable
Linear Valve Actuators
ExRunRedRun
1102,200 lbf 0.22.36" stroke 2...15 sec/ mm On-off, 3-pos modulating
Failsafe Linear Valve Actuators
ExMax + LINRedMax + LIN
110670 lbf 0.31.65" stroke 0,1...15 sec/ mm On-off, 3-pos modulating with spring return
Quarter Turn Actuators for Dampers and Valves
ExMaxRedMax
451,350 in-lbs 3...150 sec/ 90 On-off, 3-pos modulating with/without spring return
In the diagram below, a typical air-handling system shows which equipment is allowedin the Hazardous location and which should only be placed in the ordinary location.The diagram does not claim to be complete.
If in doubt, please do not hesitate to consult us at Schischek. We will advise you in anycase. A brief discussion in the early stages of planning can avoid substantial costs inremedial work later and gives you the peace of mind that you have a safely installed
operating system.
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
5/76www.schischek.com
North American Price List 2014
5
C M
C VAV
%rF MP PC
PLC-SystemPLC-System
%rH
Air damper Fire damper Restrictor Restrictor
87
7
65
4 5 8 18 1
Thermostats, Humidistats, Frost Protection Controller
ExReg-VDifferential pressure 0300 Pa (VAV)
ExReg-DTemperature/Humidity
40+257 F 0100 %rH
Filter Monitoring, Fan Belt Protection
ExBin-PRedBin-P
05.000 Pa Pressure/Differential pressure Fan-belt protection Filter protection 1- or 2-stage switching point
ressure/ Differential Pressure Sensors
Cos-PdCos-P
100 7.500 Paull range adjustable
ExBin-DRedBin-D
40+257 F 0100 %rH 1- or 2-stage
ExBin-FRRedBin-FR +14+59 F Capillary: 118", 236" 1-stage switching point
You should be aware of the areas of installation where an explosive atmospheremay build up. Furthermore, you should have the responsible authority classify therelevant Ex zone and in combination with type and condition of the explosive medium,
you should be able to select suitable explosion proof equipment.
With Schischek products this is simple because all equipment is certifiedaccording to the highest safety standards according to ATEX, of course!
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
6/76
North American Price List 2014
www.schischek.com6
Table of contents Installation Areas in Division/Zones Gas Dust Gas Dust Gas DustApprovals According to Zone System Zone 0 20 1 21 2 22 OL**Approvals According to Division System Cl. I Cl. II, III Cl. I Cl. II, III Cl. I Cl. II, III OL** Div 1 Div 1 Div 1 Div 1 Div 2 Div 2Product Line PageQuarter Turn Actuators 90Overview electrical actuators with 90 angle of rotation 8-9
ExMax size S 45 270 in-lbs with/ without spring return (HL*) 10 ExMax size M 270 1,350 in-lbs with/ without spring return (HL*) 11 RedMax size S 45 270 in-lbs with/ without spring return (HL*) 12 RedMax size M 270 1,350 in-lbs with/ without spring return (HL*) 13 InMax size S 45 270 in-lbs with/ without spring return (OL**) 14 InMax size M 270 1,350 in-lbs with/ without spring return (OL**) 15 Linear Valve Actuators with Spring Return with 0.30"/0.39"/0.59"/0.79"/1.18"/1.65" Stroke (Fixed)Overview electrical linear actuators 16-17LIN-..+ ExMax.. size S, M 110 670 lbf with spring return (HL*) 18-19 LIN-..+ RedMax.. size S, M 110 670 lbf with spring return (HL*) 18-19 LIN-..+ InMax.. size S, M 110 670 lbf with spring return (OL**) 18-19 Valve Actuators with 0.2"2.36" (5...60 mm) Stroke ExRun size S 110 2,200 lbf without spring return (HL*) 20-21 RedRun size S 110 2,200 lbf without spring return (HL*) 20-21 InRun size S 110 2,200 lbf without spring return (OL**) 20-21 Special Options for ActuatorsOverview special options for actuators 22-23
Overview heating system ExPolar for actuators 24ExPolar heating system for actuators use in Ex areas down to 58 F (50 C) (HL*) 25 InPolar heating system for actuators use in ordinary location down to 58 F (50 C) (OL**) 25 Controller for VAV, Pressure, Temperature, HumidityOverview control system 26-27ExReg-V volume flow and pressure controller 0 300 Pa (1.2 inch water) (HL*) 28-29 InReg-V volume flow and pressure controller 0 300 Pa (1.2 inch water) (OL**) 28-29 ExReg-D temperature and humidity controller 40 +257 F/ 0100 %rH (HL*) 30-31 InReg-D temperature and humidity controller 40 +257 F/ 0100 %rH (OL**) 30-31 Modulating Sensors for Temperature, Humidity, Pressure/ Differential PressureOverview modulating sensors 32-34ExCos-P differential pressure, VAV sensors 100 7.500 Pa (0.430 inch water) (HL*) 35 RedCos-P differential pressure, VAV sensors 100 7.500 Pa (0.430 inch water) (HL*) 35 InCos-P differential pressure, VAV sensors 100 7.500 Pa (0.430 inch water) (OL**) 35 ExCos-D temperature and humidity transducer for ExPro-C sensors (HL*) 36 RedCos-D temperature and humidity transducer for ExPro-C sensors (HL*) 36 InCos-D temperature and humidity transducer for InPro-C sensors (OL**) 36 ExPro-C temperature and humidity sensor probes for operation in HVAC systems (HL*) 37 InPro-C temperature and humidity sensor probes for operation in HVAC systems (OL**) 37 ExCos-A transducer for passive, potential free, modulating ExSens sensors (HL*) 38 RedCos-A transducer for passive, potential free, modulating ExSens sensors (HL*) 38 InCos-A transducer for passive, potential free, modulating sensors (OL**) 38 ExSens modulating, passive temperature-/ humidity-/pressure sensors (HL*) 39 ( ) ( ) ( ) Binary Sensors (Thermostats, Hygrostats, Pressostats, Fan Belt Protection, Frost Protection)Overview binary sensor technology 40-42ExBin-P pressure/ differential pressure 0 5.000 Pa (0.420 inch water) (HL*) 43 RedBin-P pressure/ differential pressure 0 5.000 Pa (0.420 inch water) (HL*) 43 InBin-P pressure/ differential pressure 0 5.000 Pa (0.420 inch water) (OL**) 43 ExBin-FR frost protection thermostat 14 59 F (HL*) 44 RedBin-FR frost protection thermostat 14 59 F (HL*) 44 InBin-FR frost protection thermostat 14 59 F (OL**) 44 ExBin-N drive belt monitoring 0 10.000 U/min-1 (HL*) 45 RedBin-N drive belt monitoring 0 10.000 U/min-1 (HL*) 45 InBin-N drive belt monitoring 0 10.000 U/min-1 (OL**) 45 ExBin-D temperature and humidity thermostat for ExPro-B probe sensors (HL*) 46 RedBin-D temperature and humidity thermostat for ExPro-B probe sensors (HL*) 46 InBin-D temperature and humidity thermostat for InPro-B probe sensors (OL**) 46 ExPro-B digital thermostat/ hygrostat sensor probes for operation in HVAC systems (HL*) 47 InPro-B digital thermostat/ hygrostat sensor probes for operation in HVAC systems (OL**) 47 ExBin-A modules for adaptation of 1-5 passive, potential free, binary ExSens sensors (HL*) 48 RedBin-A modules for adaptation of 1-5 passive, potential free, binary ExSens sensors (HL*) 48 InBin-A modules for adaptation of 1-5 passive, potential free, binary sensors (OL**) 48 ExSens binary, passive temperature-/humidity-/ pressure sensors (HL*) 49 ( ) ( ) ( ) Special Options for SensorsOverview special options for sensors 50Overview heating system ExPolar for sensors 51ExPolar heating system for sensors' use in Ex areas down to 58 F (50 C) (HL*) 51 InPolar heating system for sensors' use in ordinary location down to 58 F (50 C) (OL**) 51 Door Holder Magnets ExMag door holder magnets with 146, 292, 450 lbf force (HL*) 52
*HL = Hazardous Location **OL = Ordinary Location( ) Zone System Only
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
7/76www.schischek.com
North American Price List 2014
7
Table of contents Installation Areas in Division/Zones Gas Dust Gas Dust Gas DustApprovals According to Zone System Zone 0 20 1 21 2 22 OL**Approvals According to Division System Cl. I Cl. II, III Cl. I Cl. II, III Cl. I Cl. II, III OL** Div 1 Div 1 Div 1 Div 1 Div 2 Div 2Content/Description PageAdditional InformationConversation tables 53
Product codes/definitions 54-55Installation according to NEC 500 (Division system, North America) 56Installation according to ATEX (Zone system) 57Features of actuators in combination with ExPro-TT.. or programming stick 58Electrical installation codes according to NEC/FM/CSA 60Labelling of explosion proof equipment in accordance with NEC 500/ 505 61Explosion proof information 62Classification of hazardous areas 63Division and zone system comparison 64-65SIL Safety Integrity Level information 66-67Certification information 68-69Valve automation 70-71Rotork Products 72-75
Typical Class I Locations Respective Zones 0, 1 and 2: Petroleum refineries, gasoline storage and dispensing areas
Industrial firms that use flammable liquids in dip tanks for parts cleaning or other operations
Petrochemical companies that manufacture chemicals from gas and oil Dry cleaning plants where vapors from cleaning fluids can be present
Companies that have spraying areas where they coat products with paint or plastics
Aircraft hangars and fuel servicing areas
Utility gas plants, and operations involving storage and handling of liquefied petroleum gas or natural gas
Typical Class II Locations respective Zone 20, 21, 22: Grain elevators, flour and feed mills
Plants that manufacture, use, or store magnesium or aluminum powders Plants that have chemical or metallurgical processes of plastics, medicines, fireworks, etc.
Producers of starch or candies
Spice-grinding plants, sugar plants and cocoa plants
Coal preparation plants and other carbon-handling or processing areas
Typical Class III Locations Respective Zones 20, 21, 22: Textile mills, cotton gins, cotton seed mills, and flax processing plants
Any plant that shapes, pulverizes, or cuts wood and creates sawdust or flyings
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
8/76
North American Price List 2014
www.schischek.com8
Introducing ExMax Damper Actuators for Hazardous Locations!Quarter Turn and Rotary Applications for Damper Control ...
FAST SPRING RETURN TIME
HAZARDOUS LOCATIONS ZONE 1, 2, 21, 22
SIL2 FAIL SAFE FUNCTION
UNIVERSAL POWER SUPPLY
STAINLESS STEEL SOLUTION
EASY INSTALLATION
COMPACT DIMENSIONS
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
9/76www.schischek.com
North American Price List 2014
9
ExMax..
ExMax..
in-lbs
in-lbs
ExMax..
ExMax..
ExMax..in-lbs
in-lbs
in-lbs
95
95
95
95
95
Electrical Drive Engineering with 90 Angle of Rotation
Ordinary Location Hazardous Location
Overview ..Max Quarter-Turn Actuators
The actuator series are subdivided in 3 installation and 5 application areas.
Installation Areas:ExMax- .....................actuators for use in hazardous location Div. 1 and zone 1, 2, 21, 22
RedMax- ...................actuators for use in hazardous location Div. 2 and zone 2, 22InMax- .......................actuators for use in ordinary location
Application Areas:Ex/Red/InMax ......... for air and fire dampers, VAV, ball valves, control dampers
The actuator concept offers obvious advantages:
1. Small dimension, compact, easy installation, highest protection classes, cost effective2. Universal power supply 24 to 240 Volt AC/DC, selfadjustable
3. SIL2 fail safe function4. With or without spring return (in accordance with type)5. Robust aluminium housing, NEMA4X/ IP666. Integrated heater for low temperatures7. On site adjustable motor running time8. Integrated manual override9. Useful accessories such as retrofit limit switches10. Actuators are to offer direct coupling
Actuators for Air Dampers
Actuators for Smoke and Fire Dampers
ExMax.., RedMax.., InMax.. Turn Actuators
90 actuators from 45 to 1,350 in-lbs, with or w/ospring return (run time 1, 3, 10, 20 s depending ontype), for air-dampers.
ExMax.., RedMax.., InMax.. Turn Actuators
90 actuators from 45 to 1,350 in-lbs, with or w/ospring return (run time 1, 3, 10, 20 s depending ontype), for smoke- and fire-dampers.
Actuators for Ball Valves
Actuators for Butterfly Valves and Other Turn Valves
ExMax.., RedMax.., InMax.. Turn Actuators
90 actuators from 45 to 1,350 in-lbs, with or w/ospring return (run time 1, 3, 10, 20 s depending ontype), for ball valves.
ExMax.., RedMax.., InMax.. Turn Actuators
90 actuators from 45 to 1,350 in-lbs, with or w/ospring return (run time 1, 3, 10, 20 s dependingon type), for butterfly valves and other quarter turnvalves.
Actuators for VAV Control ExMax.., RedMax.., InMax.. Turn Actuators
90 actuators from 45 to 1,350 in-lbs, with or w/ospring return (run time 1, 3, 10, 20 s depending ontype), for VAV control.
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
10/76
North American Price List 2014
www.schischek.com10
ExMax 90 Quarter-Turn Actuators Size "S" for Class I/II/III, Div. 1, zone 1, 2, 21, 22
ExMax-
Cl. I/II/III, Div. 1Zone 1/2/21/22
Gas + Dustcertified accordingUL, CSA
ATEX, SIL, IECExGOST-R, RTN
INMETRO, KOSHA
Basics for all ExMax-.. size "S" 24240 VAC/DC self adaptable power supply 95angle of rotation (5 for preload) 100% overload protected Aluminum housing NEMA4X / IP66, cable ~ 39.4" -40F...+104F/+122F, integrated heater Emergency manual override Squared shaft connection 0.47" 0.47" Dimensions (H W D) 8.27" 3.74" 3.15" Approximate weight 8 lbs (..VAS = 16 lbs)
Description
ExMax are, in accordance with type, for automation ofair dampers, fire and smoke dampers, volume control, as
well as for ball valves, throttle valves and other quarter-turn armatures.
Scope of Delivery: 1 actuator, ~ 39.4 inch cable, allen key for manual over -ride, 4 screws, manuals.
Size "S"
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators Without Spring Return, 24 to 240 VAC/DC, for Division 1 and Zone 1, 2, 21, 22
ExMax-45.90-F-A 45 / 90 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos - - SExMax- 135-F-A 135 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos - - SExMax-45.90-SF-A 45 / 90 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 2 limit switches (5/85) - SExMax- 135-SF-A 135 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 2 limit switches (5/85) - SExMax-45.90-YF-A 45 / 90 in-lbs 7.5/15/30/60 s ~ 3 s / 10 s 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - SExMax- 135-YF-A 135 in-lbs 7.5/15/30/60 s ~ 3 s / 10 s 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - SExMax-45.90-UF-A 45 / 90 in-lbs 7.5/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 0...10 VDC, 4...20 mA - SExMax- 135-UF-A 135 in-lbs 7.5/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 0...10 VDC, 4...20 mA - S
ExMax-45.90-BF-A 45 / 90 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 2 limit switches (5/85) ExPro-TT connector SExMax- 135-BF-A 135 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 2 limit switches (5/85) ExPro-TT connector S
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators With Spring Return, 24 to 240 VAC/DC, for Division 1 and Zone 1, 2, 21, 22
ExMax- 72-F1-A 72 in-lbs 3/15/30/60 s 1 s On-off - - SExMax-135-F1-A 135 in-lbs 3/15/30/60 s 1 s On-off - - SExMax- 72-SF1-A 72 in-lbs 3/15/30/60 s 1 s On-off 2 limit switches (5/85) - SExMax-135-SF1-A 135 in-lbs 3/15/30/60 s 1 s On-off 2 limit switches (5/85) - SExMax- 72-BF1-A 72 in-lbs 3/15/30/60 s 1 s On-off 2 limit switches (5/85) ExPro-TT connector SExMax-135-BF1-A 135 in-lbs 3/15/30/60 s 1 s On-off 2 limit switches (5/85) ExPro-TT connector S
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators With 1 Second Spring Return, 24 to 240 VAC/DC, for Division 1 and Zone 1, 2, 21, 22
Stick Stick to change parameter and factory settings such as running time, torque, spring return time, force control and write protection depending on actuator ExPro-TT-72 Safety temperature trigger for fire dampers, switching at 162F / 72C, with electrical connector, only connectable to Max--BF actuators!KB-A Shaft connection for North American actuators for damper shafts " adaptable to all ..Max-.. actuators size SKB-S Mounting clamp for round damper shafts 0.4" to 0.75" and squared shafts 0.4" to 0.6", including bracket, connectable to all ..Max-.. actuators size SHV-SK, HV-SL Manual override, connectable to actuators size S. HV-SK = short version, HV-SL = long version for add. mounting of ..Box/ ..Switch (not suitable for ..Max-..-..F1!)AR-12-xx Squared reduction part from 0.47" 0.47" to shafts with 0.43" (type AR-12-11), 0.39" (type AR-12-10), 0.32" (type AR-12-08)D-F-S-A Adaptation with flange according to DIN EN 5211 for butterfly or ball-valves suitable for size S, see page 70 for more information
Type Technical Data
Accessories
Explosion Proof Features of ExMax - ... size "S"
ExMax- 45.90-A 45 / 90 in-lbs 3/15/30/60 s - On-off, 3-pos - - SExMax-135.270-A 135 / 270 in-lbs 3/15/30/60 s - On-off, 3-pos - - SExMax- 45.90-S-A 45 / 90 in-lbs 3/15/30/60 s - On-off, 3-pos 2 limit switches (5/85) - SExMax-135.270-S-A 135 / 270 in-lbs 3/15/30/60 s - On-off, 3-pos 2 limit switches (5/85) - SExMax- 45.90-Y-A 45 / 90 in-lbs 7.5/15/30/60 s - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - SExMax-135.270-Y-A 135 / 270 in-lbs 7.5/15/30/60 s - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - SExMax- 45.90-U-A 45 / 90 in-lbs 7.5/15/30/60 s - On-off, 3-pos 0...10 VDC, 4...20 mA - SExMax-135.270-U-A 135 / 270 in-lbs 7.5/15/30/60 s - On-off, 3-pos 0...10 VDC, 4...20 mA - S
Special options and offshore kits see page23
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
11/76www.schischek.com
North American Price List 2014
11
ExMax 90 Quarter-Turn Actuators Size "M" for Class I/II/III, Div. 1, zone 1, 2, 21, 22
ExMax-
Cl. I/II/III, Div. 1Zone 1/2/21/22
Gas + Dustcertified accordingUL, CSA
ATEX, SIL, IECExGOST-R, RTN
INMETRO
Basics for all ExMax-.. size "M" 24240 VAC/DC self adaptable power supply 95angle of rotation (5 for preload) 100% overload protected Aluminum housing NEMA4X / IP66, cable ~ 39.4" -40F...+104F/+122F, integrated heater Emergency manual override Squared shaft connection 0.63" 0.63" Dimensions (H W D) 11.34" 5.87" 4.57" Approximate weight 21 lbs
Description
ExMax are, in accordance with type, for automation ofair dampers, fire and smoke dampers, volume control, as
well as for ball valves, throttle valves and other quarter-turn armatures.
Scope of Delivery: 1 actuator, ~ 39.4 inch cable, allen key for manual over -ride, 4 screws, manuals.
Size "M"
ExMax-450.675-A 450 / 675 in-lbs 40/60/90/120 s - On-off, 3-pos - - MExMax- 900-A 900 in-lbs 40/60/90/120 s - On-off, 3-pos - - MExMax- 1350-A 1,350 in-lbs 40/60/90/120 s - On-off, 3-pos - - MExMax-450.675-S-A 450 / 675 in-lbs 40/60/90/120 s - On-off, 3-pos 2 limit switches (5/ 85) - MExMax- 900-S-A 900 in-lbs 40/60/90/120 s - On-off, 3-pos 2 limit switches (5/ 85) - MExMax- 1350-S-A 1,350 in-lbs 40/60/90/120 s - On-off, 3-pos 2 limit switches (5/ 85) - MExMax-450.675-Y-A 450 / 675 in-lbs 40/60/90/120 s - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - MExMax- 900-Y-A 900 in-lbs 40/60/90/120 s - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - MExMax-450.675-U-A 450 / 675 in-lbs 40/60/90/120 s - On-off, 3-pos 0...10 VDC, 4...20 mA - MExMax- 900-U-A 900 in-lbs 40/60/90/120 s - On-off, 3-pos 0...10 VDC, 4...20 mA - M
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators Without Spring Return, 24 to 240 VAC/DC, for Division 1 and Zone 1, 2, 21, 22
ExMax-270-F-A 270 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos - - MExMax-450-F-A 450 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos - - MExMax-540-F-A 540 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos - - MExMax-270-SF-A 270 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) - MExMax-450-SF-A 450 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) - MExMax-540-SF-A 540 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) - M
ExMax-270-YF-A 270 in-lbs 40/60/90/120 s ~ 20 s 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - MExMax-450-YF-A 450 in-lbs 40/60/90/120 s ~ 20 s 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - MExMax-270-UF-A 270 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 0...10 VDC, 4...20 mA - MExMax-450-UF-A 450 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 0...10 VDC, 4...20 mA - MExMax-540-UF-A 540 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 0...10 VDC, 4...20 mA - MExMax-270-BF-A 270 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) ExPro-TT connector MExMax-450-BF-A 450 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) ExPro-TT connector MExMax-540-BF-A 540 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) ExPro-TT connector M
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators With Spring Return, 24 to 240 VAC/DC, for Division 1 and Zone 1, 2, 21, 22
ExMax-270-F3-A 270 in-lbs 40/60/90/120 s 3 s On-off - - MExMax-450-F3-A 450 in-lbs 40/60/90/120 s 3 s On-off - - MExMax-270-SF3-A 270 in-lbs 40/60/90/120 s 3 s On-off 2 limit switches (5/ 85) - M
ExMax-450-SF3-A 450 in-lbs 40/60/90/120 s 3 s On-off 2 limit switches (5/ 85) - MExMax-270-BF3-A 270 in-lbs 40/60/90/120 s 3 s On-off 2 limit switches (5/ 85) ExPro-TT connector MExMax-450-BF3-A 450 in-lbs 40/60/90/120 s 3 s On-off 2 limit switches (5/ 85) ExPro-TT connector M
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators With 3 Second Spring Return, 24 to 240 VAC/DC, for Division 1 and Zone 1, 2, 21, 22
Explosion Proof Features of ExMax - ... size "M"
Stick Stick to change parameter and factory settings such as running time, torque, spring return time, force control and write protection depending on actuator ExPro-TT-72 Safety temperature trigger for fire dampers, switching at 162F / 72C, with electrical connector, only connectable to ..Max-..-BF actuators!HV-MK Manual override, connectable to actuators size M (not suitable for ..Max-..-..F3 !)AR-16-xx Squared reduction part from 0.63" 0.63" to shafts with 0.55" (type AR-16-14), 0.47" (type AR-16-12)D-F-M-A Adaptation with flange according to DIN EN 5211 for butterfly or ball-valves suitable for size M, see page70 for more information
Type Technical DataAccessories
Special options and offshore kits see page 23
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
12/76
North American Price List 2014
www.schischek.com12
RedMax 90 Quarter-Turn Actuators Size "S" for Class I/II/III, Div. 2, zone 2, 22
RedMax-
Cl. I/II/III, Div. 2Zone 2, 22
Gas + Dustcertified accordingUL, CSA
ATEX, SIL, IECExGOST-R, RTN
Basics for all RedMax-.. size "S" 24240 VAC/DC self adaptable power supply 95angle of rotation (5 for preload) 100% overload protected Aluminum housing NEMA4X / IP66, cable ~ 39.4" -40F...+104F/+122F, integrated heater Emergency manual override Squared shaft connection 0.47" 0.47" Dimensions (H W D) 8.27" 3.74" 3.15" Approximate weight 8 lbs (..VAS = 16 lbs)
Description
RedMax are, in accordance with type, for automation ofair dampers, fire and smoke dampers, volume control, as
well as for ball valves, throttle valves and other quarter-turn armatures.
Scope of Delivery: 1 actuator, ~ 39.4 inch cable, allen key for manual over -ride, 4 screws, manuals.
Size "S"
Explosion Proof Features of RedMax - ... size "S"
Stick Stick to change parameter and factory settings such as running time, torque, spring return time, force control and write protection depending on actuator ExPro-TT-72 Safety temperature trigger for fire dampers, switching at 162F / 72C, with electrical connector, only connectable to Max--BF actuators!KB-A Shaft connection for North American actuators for damper shafts " adaptable to all ..Max-.. actuators size SKB-S Mounting clamp for round damper shafts 0.4" to 0.75" and squared shafts 0.4" to 0.6", including bracket, connectable to all ..Max-.. actuators size SHV-SK, HV-SL Manual override, connectable to actuators size S. HV-SK = short version, HV-SL = long version for add. mounting of ..Box/ ..Switch (not suitable for ..Max-..-..F1!)AR-12-xx Squared reduction part from 0.47" 0.47" to shafts with 0.43" (type AR-12-11), 0.39" (type AR-12-10), 0.32" (type AR-12-08)D-F-S-A Adaptation with flange according to DIN EN 5211 for butterfly or ball-valves suitable for size S, see page 70 for more information
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators Without Spring Return, 24 to 240 VAC/DC, for Division 2 and Zone 2, 22
RedMax-45.90-F-A 45 / 90 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos - - SRedMax- 135-F-A 135 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos - - SRedMax-45.90-SF-A 45 / 90 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 2 limit switches (5/85) - SRedMax- 135-SF-A 135 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 2 limit switches (5/85) - SRedMax-45.90-YF-A 45 / 90 in-lbs 7.5/15/30/60 s ~ 3 s / 10 s 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - SRedMax- 135-YF-A 135 in-lbs 7.5/15/30/60 s ~ 3 s / 10 s 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - SRedMax-45.90-UF-A 45 / 90 in-lbs 7.5/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 0...10 VDC, 4...20 mA - SRedMax- 135-UF-A 135 in-lbs 7.5/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 0...10 VDC, 4...20 mA - S
RedMax-45.90-BF-A 45 / 90 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 2 limit switches (5/85) ExPro-TT connector SRedMax- 135-BF-A 135 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 2 limit switches (5/85) ExPro-TT connector S
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators With Spring Return, 24 to 240 VAC/DC, for Division 2 and Zone 2, 22
Type Technical Data
Accessories
RedMax- 45.90-A 45 / 90 in-lbs 3/15/30/60 s - On-off, 3-pos - - SRedMax-135.270-A 135 / 270 in-lbs 3/15/30/60 s - On-off, 3-pos - - SRedMax- 45.90-S-A 45 / 90 in-lbs 3/15/30/60 s - On-off, 3-pos 2 limit switches (5/85) - SRedMax-135.270-S-A 135 / 270 in-lbs 3/15/30/60 s - On-off, 3-pos 2 limit switches (5/85) - SRedMax- 45.90-Y-A 45 / 90 in-lbs 7.5/15/30/60 s - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - SRedMax-135.270-Y-A 135 / 270 in-lbs 7.5/15/30/60 s - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - SRedMax- 45.90-U-A 45 / 90 in-lbs 7.5/15/30/60 s - On-off, 3-pos 0...10 VDC, 4...20 mA - SRedMax-135.270-U-A 135 / 270 in-lbs 7.5/15/30/60 s - On-off, 3-pos 0...10 VDC, 4...20 mA - S
RedMax- 72-F1-A 72 in-lbs 3/15/30/60 s 1 s On-off - - SRedMax-135-F1-A 135 in-lbs 3/15/30/60 s 1 s On-off - - SRedMax- 72-SF1-A 72 in-lbs 3/15/30/60 s 1 s On-off 2 limit switches (5/85) - SRedMax-135-SF1-A 135 in-lbs 3/15/30/60 s 1 s On-off 2 limit switches (5/85) - SRedMax- 72-BF1-A 72 in-lbs 3/15/30/60 s 1 s On-off 2 limit switches (5/85) ExPro-TT connector SRedMax-135-BF1-A 135 in-lbs 3/15/30/60 s 1 s On-off 2 limit switches (5/85) ExPro-TT connector S
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators With 1 Second Spring Return, 24 to 240 VAC/DC, for Division 2 and Zone 2, 22
Special options and offshore kits see page23
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
13/76www.schischek.com
North American Price List 2014
13
RedMax 90 Quarter-Turn Actuators Size "M" for Class I/II/III, Div. 2, zone 2, 22
RedMax-
Cl. I/II/III, Div. 2Zone 2, 22
Gas + Dustcertified accordingUL, CSA
ATEX, SIL, IECExGOST-R, RTN
Basics for all RedMax-.. size "M" 24240 VAC/DC self adaptable power supply 95angle of rotation (5 for preload) 100% overload protected Aluminum housing NEMA4X / IP66, cable ~ 39.4" -40F...+104F/+122F, integrated heater Emergency manual override Squared shaft connection 0.63" 0.63" Dimensions (H W D) 11.34" 5.87" 4.57" Approximate weight 21 lbs
Description
RedMax are, in accordance with type, for automation ofair dampers, fire and smoke dampers, volume control, as
well as for ball valves, throttle valves and other quarter-turn armatures.
Scope of Delivery: 1 actuator, ~ 39.4 inch cable, allen key for manual over -ride, 4 screws, manuals.
Size "M"
Explosion Proof Features of RedMax - ... size "M"
Stick Stick to change parameter and factory settings such as running time, torque, spring return time, force control and write protection depending on actuator ExPro-TT-72 Safety temperature trigger for fire dampers, switching at 162F / 72C, with electrical connector, only connectable to ..Max-..-BF actuators!HV-MK Manual override, connectable to actuators size M (not suitable for ..Max-..-..F3!)AR-16-xx Squared reduction part from 0.63" 0.63" to shafts with 0.55" (type AR-16-14), 0.47" (type AR-16-12)D-F-M-A Adaptation with flange according to DIN EN 5211 for butterfly or ball-valves suitable for size M, see page70 for more information
Type Technical DataAccessories
RedMax-450.675-A 450 / 675 in-lbs 40/60/90/120 s - On-off, 3-pos - - MRedMax- 900-A 900 in-lbs 40/60/90/120 s - On-off, 3-pos - - MRedMax- 1350-A 1,350 in-lbs 40/60/90/120 s - On-off, 3-pos - - MRedMax-450.675-S-A 450 / 675 in-lbs 40/60/90/120 s - On-off, 3-pos 2 limit switches (5/ 85) - MRedMax- 900-S-A 900 in-lbs 40/60/90/120 s - On-off, 3-pos 2 limit switches (5/ 85) - MRedMax- 1350-S-A 1,350 in-lbs 40/60/90/120 s - On-off, 3-pos 2 limit switches (5/ 85) - MRedMax-450.675-Y-A 450 / 675 in-lbs 40/60/90/120 s - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - MRedMax- 900-Y-A 900 in-lbs 40/60/90/120 s - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - MRedMax-450.675-U-A 450 / 675 in-lbs 40/60/90/120 s - On-off, 3-pos 0...10 VDC, 4...20 mA - MRedMax- 900-U-A 900 in-lbs 40/60/90/120 s - On-off, 3-pos 0...10 VDC, 4...20 mA - M
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators Without Spring Return, 24 to 240 VAC/DC, for Division 2 and Zone 2, 22
RedMax-270-F-A 270 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos - - MRedMax-450-F-A 450 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos - - MRedMax-540-F-A 540 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos - - MRedMax-270-SF-A 270 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) - MRedMax-450-SF-A 450 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) - MRedMax-540-SF-A 540 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) - M
RedMax-270-YF-A 270 in-lbs 40/60/90/120 s ~ 20 s 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - MRedMax-450-YF-A 450 in-lbs 40/60/90/120 s ~ 20 s 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - MRedMax-270-UF-A 270 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 0...10 VDC, 4...20 mA - MRedMax-450-UF-A 450 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 0...10 VDC, 4...20 mA - MRedMax-540-UF-A 540 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 0...10 VDC, 4...20 mA - MRedMax-270-BF-A 270 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) ExPro-TT connector MRedMax-450-BF-A 450 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) ExPro-TT connector MRedMax-540-BF-A 540 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) ExPro-TT connector M
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators With Spring Return, 24 to 240 VAC/DC, for Division 2 and Zone 2, 22
RedMax-270-F3-A 270 in-lbs 40/60/90/120 s 3 s On-off - - MRedMax-450-F3-A 450 in-lbs 40/60/90/120 s 3 s On-off - - MRedMax-270-SF3-A 270 in-lbs 40/60/90/120 s 3 s On-off 2 limit switches (5/ 85) - M
RedMax-450-SF3-A 450 in-lbs 40/60/90/120 s 3 s On-off 2 limit switches (5/ 85) - MRedMax-270-BF3-A 270 in-lbs 40/60/90/120 s 3 s On-off 2 limit switches (5/ 85) ExPro-TT connector MRedMax-450-BF3-A 450 in-lbs 40/60/90/120 s 3 s On-off 2 limit switches (5/ 85) ExPro-TT connector M
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators With 3 Second Spring Return, 24 to 240 VAC/DC, for Division 2 and Zone 2, 22
Special options and offshore kits see page 23
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
14/76
North American Price List 2014
www.schischek.com14
InMax 90 Quarter-Turn Actuators Size "S" for Ordinary Locations
InMax-
NOT explosion proofand only for use in
ordinary locationscertified according togeneral purpose
standardNEMA4X / IP66
Basics for all InMax-.. size "S" 24240 VAC/DC self adaptable power supply 95angle of rotation (5 for preload) 100% overload protected Aluminum housing NEMA4X/ IP66, cable ~ 39.4" -40F...+122F, integrated heater Emergency manual override Squared shaft connection 0.47" 0.47" Dimensions (H W D) 8.27" 3.74" 3.15" Approximate weight 8 lbs (..VAS = 16 lbs)
Description
InMax are, in accordance with type, for automation of airdampers, fire and smoke dampers, volume control, as
well as for ball valves, throttle valves and other quarter-turn armatures.
Scope of Delivery: 1 actuator, ~ 39.4 inch cable, allen key for manual over -ride, 4 screws, manuals.
Size "S"
Industrial Features of InMax - ... size "S"
Stick Stick to change parameter and factory settings such as running time, torque, spring return time, force control and write protection depending on actuator InPro-TT-72 Temperature trigger for fire dampers, switching at 162F / 72C, with electrical connector, only connectable to InMax--BF actuators!KB-A Shaft connection for North American actuators for damper shafts " adaptable to all ..Max-.. actuators size SKB-S Mounting clamp for round damper shafts 0.4" to 0.75" and squared shafts 0.4" to 0.6", including bracket, connectable to all ..Max-.. actuators size SHV-SK, HV-SL Manual override, connectable to actuators size S. HV-SK = short version, HV-SL = long version for add. mounting of ..Box/ ..Switch (not suitable for ..Max-..-..F1!)AR-12-xx Squared reduction part from 0.47" 0.47" to shafts with 0.43" (type AR-12-11), 0.39" (type AR-12-10), 0.32" (type AR-12-08)D-F-S-A Adaptation with flange according to DIN EN 5211 for butterfly or ball-valves suitable for size S, see page 70 for more information
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators Without Spring Return, 24 to 240 VAC/DC, for Ordinary Location
InMax-45.90-F-A 45 / 90 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos - - SInMax- 135-F-A 135 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos - - SInMax-45.90-SF-A 45 / 90 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 2 limit switches (5/85) - SInMax- 135-SF-A 135 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 2 limit switches (5/85) - SInMax-45.90-YF-A 45 / 90 in-lbs 7.5/15/30/60 s ~ 3 s / 10 s 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - SInMax- 135-YF-A 135 in-lbs 7.5/15/30/60 s ~ 3 s / 10 s 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - SInMax-45.90-UF-A 45 / 90 in-lbs 7.5/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 0...10 VDC, 4...20 mA - SInMax- 135-UF-A 135 in-lbs 7.5/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 0...10 VDC, 4...20 mA - S
InMax-45.90-BF-A 45 / 90 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 2 limit switches (5/85) InPro-TT connector SInMax- 135-BF-A 135 in-lbs 3/15/30/60 s ~ 3 s / 10 s On-off, 3-pos 2 limit switches (5/85) InPro-TT connector S
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators With Spring Return, 24 to 240 VAC/DC, for Ordinary Location
Type Technical Data
Accessories
InMax- 45.90-A 45 / 90 in-lbs 3/15/30/60 s - On-off, 3-pos - - SInMax-135.270-A 135 / 270 in-lbs 3/15/30/60 s - On-off, 3-pos - - SInMax- 45.90-S-A 45 / 90 in-lbs 3/15/30/60 s - On-off, 3-pos 2 limit switches (5/85) - SInMax-135.270-S-A 135 / 270 in-lbs 3/15/30/60 s - On-off, 3-pos 2 limit switches (5/85) - SInMax- 45.90-Y-A 45 / 90 in-lbs 7.5/15/30/60 s - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - SInMax-135.270-Y-A 135 / 270 in-lbs 7.5/15/30/60 s - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - SInMax- 45.90-U-A 45 / 90 in-lbs 7.5/15/30/60 s - On-off, 3-pos 0...10 VDC, 4...20 mA - SInMax-135.270-U-A 135 / 270 in-lbs 7.5/15/30/60 s - On-off, 3-pos 0...10 VDC, 4...20 mA - S
InMax- 72-F1-A 72 in-lbs 3/15/30/60 s 1 s On-off - - SInMax-135-F1-A 135 in-lbs 3/15/30/60 s 1 s On-off - - SInMax- 72-SF1-A 72 in-lbs 3/15/30/60 s 1 s On-off 2 limit switches (5/85) - SInMax-135-SF1-A 135 in-lbs 3/15/30/60 s 1 s On-off 2 limit switches (5/85) - SInMax- 72-BF1-A 72 in-lbs 3/15/30/60 s 1 s On-off 2 limit switches (5/85) InPro-TT connector SInMax-135-BF1-A 135 in-lbs 3/15/30/60 s 1 s On-off 2 limit switches (5/85) InPro-TT connector S
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators With 1 Second Spring Return, 24 to 240 VAC/DC, for Ordinary Location
Special options and offshore kits see page23
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
15/76www.schischek.com
North American Price List 2014
15
InMax 90 Quarter-Turn Actuators Size "M" for Ordinary Locations
InMax-
NOT explosion proofand only for use in
ordinary locationscertified according togeneral purpose
standardNEMA4X / IP66
Basics for all InMax-.. size "M" 24240 VAC/DC self adaptable power supply 95angle of rotation (5 for preload) 100% overload protected Aluminum housing NEMA4X/ IP66, cable ~ 39.4" -40F...+104F/+122F, integrated heater Emergency manual override Squared shaft connection 0.63" 0.63" Dimensions (H W D) 11.34" 5.87" 4.57" Approximate weight 21 lbs
Description
InMax are, in accordance with type, for automation of airdampers, fire and smoke dampers, volume control, as
well as for ball valves, throttle valves and other quarter-turn armatures.
Scope of Delivery: 1 actuator, ~ 39.4 inch cable, allen key for manual over -ride, 4 screws, manuals.
Size "M"
Industrial Features of InMax - ... size "M"
Stick Stick to change parameter and factory settings such as running time, torque, spring return time, force control and write protection depending on actuator InPro-TT-72 Temperature trigger for fire dampers, switching at 162F / 72C, with electrical connector, only connectable to InMax-..-BF actuators!HV-MK Manual override, connectable to actuators size M (not suitable for ..Max-..-..F3!)AR-16-xx Squared reduction part from 0.63" 0.63" to shafts with 0.55" (type AR-16-14), 0.47" (type AR-16-12)D-F-M-A Adaptation with flange according to DIN EN 5211 for butterfly or ball-valves suitable for size M, see page70 for more information
Type Technical Data
InMax-450.675-A 450 / 675 in-lbs 40/60/90/120 s - On-off, 3-pos - - MInMax- 900-A 900 in-lbs 40/60/90/120 s - On-off, 3-pos - - MInMax- 1350-A 1,350 in-lbs 40/60/90/120 s - On-off, 3-pos - - MInMax-450.675-S-A 450 / 675 in-lbs 40/60/90/120 s - On-off, 3-pos 2 limit switches (5/ 85) - MInMax- 900-S-A 900 in-lbs 40/60/90/120 s - On-off, 3-pos 2 limit switches (5/ 85) - MInMax- 1350-S-A 1,350 in-lbs 40/60/90/120 s - On-off, 3-pos 2 limit switches (5/ 85) - MInMax-450.675-Y-A 450 / 675 in-lbs 40/60/90/120 s - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - MInMax- 900-Y-A 900 in-lbs 40/60/90/120 s - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - MInMax-450.675-U-A 450 / 675 in-lbs 40/60/90/120 s - On-off, 3-pos 0...10 VDC, 4...20 mA - MInMax- 900-U-A 900 in-lbs 40/60/90/120 s - On-off, 3-pos 0...10 VDC, 4...20 mA - M
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators Without Spring Return, 24 to 240 VAC/DC, for Ordinary Location
InMax-270-F-A 270 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos - - MInMax-450-F-A 450 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos - - MInMax-540-F-A 540 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos - - MInMax-270-SF-A 270 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) - MInMax-450-SF-A 450 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) - MInMax-540-SF-A 540 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) - M
InMax-270-YF-A 270 in-lbs 40/60/90/120 s ~ 20 s 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - MInMax-450-YF-A 450 in-lbs 40/60/90/120 s ~ 20 s 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - MInMax-270-UF-A 270 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 0...10 VDC, 4...20 mA - MInMax-450-UF-A 450 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 0...10 VDC, 4...20 mA - MInMax-540-UF-A 540 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 0...10 VDC, 4...20 mA - MInMax-270-BF-A 270 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) InPro-TT connector MInMax-450-BF-A 450 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) InPro-TT connector MInMax-540-BF-A 540 in-lbs 40/60/90/120 s ~ 20 s On-off, 3-pos 2 limit switches (5/ 85) InPro-TT connector M
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators With Spring Return, 24 to 240 VAC/DC, for Ordinary Location
InMax-270-F3-A 270 in-lbs 40/60/90/120 s 3 s On-off - - MInMax-450-F3-A 450 in-lbs 40/60/90/120 s 3 s On-off - - MInMax-270-SF3-A 270 in-lbs 40/60/90/120 s 3 s On-off 2 limit switches (5/ 85) - M
InMax-450-SF3-A 450 in-lbs 40/60/90/120 s 3 s On-off 2 limit switches (5/ 85) - MInMax-270-BF3-A 270 in-lbs 40/60/90/120 s 3 s On-off 2 limit switches (5/ 85) InPro-TT connector MInMax-450-BF3-A 450 in-lbs 40/60/90/120 s 3 s On-off 2 limit switches (5/ 85) InPro-TT connector M
Type Torque Running Time 90 Spring Return Control Mode Feedback Features SizeQuarter-Turn Actuators With 3 Second Spring Return, 24 to 240 VAC/DC, for Ordinary Location
Accessories
Special options and offshore kits see page 23
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
16/76
North American Price List 2014
www.schischek.com16
Introducing ExMax+LIN&ExRun Valve Actuators for Hazardous Locations!Linear Applications for Valve Control ...
FAST SPRING RETURN TIME
HAZARDOUS LOCATIONS ZONE 1, 2, 21, 22
SIL2 FAIL SAFE FUNCTION
UNIVERSAL POWER SUPPLY
C5-M SOLUTION
EASY INSTALLATION
COMPACT DIMENSIONS
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
17/76www.schischek.com
North American Price List 2014
17
ExRun..
ExMax..+LIN
lbf
lbf
2.36"
1.65"
0.2"-
0.39"-
North American PriceList 2012
www.schischek.comwww.schischek.com
North American PriceList 2012
48 49
231
210
8 0
95
118,536
V 1 2
7 0
7 4
1 18 ,5 6 0
3077,6
M 4 ( 6 x ) - 8 d e e p
4, 4 ( 6 x
)
3 5
3 7
4 7
, 718
44
Rev Descri p tio n D at e V is
OriginSubs titutefor
SignedCheckedApproved
Drawin g No .
ExMax5.10-Y/15.30-Y
090.0000.A4_Dimensions
A3
Sch isch ek Gmb HM h lsteig 4 5
Gewerb eg eb ietVD-9 0 5 7 9 Lan g enzen n
Scale1:2 Sheet1/1
Dimensions
Lis tofparts
ProjectNo.
Pro ject
Title
. .
Rev
ExMaxActuator .
. .
...
.
.
.
.
.A0
.. ..
. . ..
. . ..
. . ..
. . ..
E X P L O S I O N P R O O F
..Run Linear ValveActuator
Valve LinkageExample
ValveExample
..Max -Turn Actuator
ValveExample
Valve LinkageExample
A
D
E
U
V
Spindle
B C
A
X
F
Y
Adapterplate Areaforscrewconnecetion
-B-
FlangetypeDIN5211
F03
F04F05
F07
F10
F12
Other
-A-
S q u ar e T w o at F i t t in g k e y
9 9 12
11 11 1414 14 18
17 17 22
19 19
22 2227 27
O th er O th er O th er
mm mm mmZ ol l Z ol l Z ol l
-D-
Height
mmZoll
-E-
Flangethickness
mmZoll
-X -
Torque
Nmlb-in
Actuator typeArmature
Type Manufacturer
-F-
Distance
mmZoll
-C-
Thread Holediameter
M mm
UNC Zoll
UNF Zoll
-Y-
Nominal size
DNZoll
C us to me r C ou nt ry Project
-Z-
Material
standard
VAAISI316-U- -V -
Increment
mm mmZ ol l Z ol l
Rev Descri p tio n D at e V is
OriginSubs titutefor
SignedCheckedApproved
Drawin g No .
2011.070.E0-USAA3
Sch isch ek Gmb HM h lsteig 4 5
Gewerb eg eb ietS d 5D-9 0 5 7 9 Lan gen zen n
S c a l e1 : 1 . 5 S h e e t 1 / 1
ExMaxonballvalve
Lis tofparts
ProjectNo.
Pro ject
Title
. .
Rev
. . .. .. .
.
.
..
. . ..
. . ..
. . ..
. . ..
. . ..
E X P L O S I O N P R O O F
Valve Automation Valve Automation Quarter-Turn Actuators Linear Motion Actuators Schischek Valve Linkages
Option2
Schischekdesignsanddeliversthelinkage
Price:
Wecan q u o t ey o u ap r i cefo r a l i n kag efo r an y t y p i ca l v a l vemo u n t i n g p a t t e rnandstem (for exampleISO 5211) with-outknowing theexact valvedimensions.Contactus atcustome rservice@schischek. com.
Order:
Whenyou order thelinkagehowever, weneedthedimensionsofthetopplate/ mount-ingpatternas wellasthe stemshapeanddimensionstodesignthe linkage.Thecutsheetfor your valvewilltypicallyhavethatinformation.Simplysendus thecut sheetandwewilldothe rest.
Option1
Youmakethelinkageyourselfor sourceitsomewhereelse.Inthatcasewewouldbehappytoprovideyouwithall theactuatordimensionsnecessarytodoso.WecanevengiveyouSTEPfilesyoucan importdirectlyintoyour CAD system.Contactusatcustomerservice@schischek.com.
Technical Short Information North America 2013 Technical Short Information North America 2013
..Max + LIN and ..Run Electrical Drive Engineering for Valves Overview
Ordinary Location Hazardous Location
Overview ..Max + LIN Linear Guide Unit and ..Run Valve Actuators
The actuator series are subdivided in 3 installation and 2 application areas.
Installation Areas:ExMax-..+LIN, ExRun- .........................for use in hazardous location Div. 1 and zone 1, 2, 21, 22
RedMax-..+LIN, RedRun- ....................for use in hazardous location Div. 2 and zone 2, 22InMax-..+LIN, InRun- ............................for use in ordinary location
Application Areas:Ex/Red/ InMax + LIN ............................for globe or 3-way valves (with safety function)Ex/Red/InRun ......................................for globe or 3-way valves
The actuator concept offers obvious advantages:
1. Small dimension, compact, easy installation, highest protection classes, cost effective2. Universal power supply 24 to 240 Volt AC/DC, selfadjustable
3. SIL2 fail safe function (only at ..Max + LIN)4. With or without spring return (spring return only at ..Max + LIN linear guide unit)5. Robust aluminium housing, NEMA4X/ IP666. Integrated heater for low temperatures7. On site adjustable motor running time8. Integrated manual override9. Useful accessories such as retrofit limit switches
Actuators for 2-Way and 3-Way Valves
Actuators with Spring Return for 2-Way and 3-Way Valves
ExRun.., RedRun.., InRun.. Valve Actuators
Valve actuators from 110 to 2,200 lbf. On site ad- justable stroke from 0.2" to 2.36", for automation ofglobe or 3-way valves. Linkage to numerous valvetypes and brands available.
ExMax.., RedMax.., InMax.. + LIN Linear Guide Unit
Linear motion valve actuators with spring returnfrom 110 to 670 lbf. Fixed stroke with 0.39"/0.59"/0.79"/1.18"/1.65" for automation of globe or 3-wayvalves. Linkage to numerous valve types andbrands available.
Please see pages 70-71 for more
information on valve linkages.
Valve Linkages Information
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
18/76
North American Price List 2014
www.schischek.com18
Explosion Proof
InMax-.. + LIN-..
NOT explosion proofand only for use in
ordinary locationscertified according togeneral purpose
standardNEMA4X/IP66
Industrial
RedMax-.. + LIN-..
Cl. I/II/III, Div. 2Zone 2, 22
Gas + Dustcertified accordingUL, CSA
ATEX, SIL, IECEx,GOST-R, RTN,
INMETRO
ExMax-.. + LIN-..
Cl. I/II/III, Div. 1Zone 1, 2, 21, 22
Gas + Dustcertified accordingUL, CSA
ATEX, SIL, IECExGOST-R, RTN
INMETRO, KOSHA11ExMax size S only
Features ..Max-.. + LIN-.. (Size "S" and "M")
..Max-.. + LIN-..Linear Valve Actuators Size "S" and "M"with Spring Return
Basics for ..Max-.. + LIN-.. valve actuators
24240 VAC/DC self adaptable powersupply
Running time 0.115 sec./mm Stroke 0.30"/ 0.39"/ 0.59"/ 0.79"/ 1.18"/ 1.65" Force 110670 lbf Spring return 3 or 10 sec. (size "S"),20 sec. (size "M")
Control mode On-off, 3-pos., 0-10 VDC,4-20 mA
Aluminium housing, NEMA4X/ IP66 External terminal box optional Ambient temperature -4F...+104F (T6), -4F...+122F (T5)
Weight (including actuator) ~ 18 lbs (size "S"), ~ 31 lbs (size "M")
in accordance with type applies for actuator
Description
..Max-.. + LIN-.. linear valve actuatorswithspring return for automation of globe- or
3-way valves.Use as actuator with safety function, On-offor 3-pos. actuator or modulating actuator.
Scope of Delivery: Linear unit, suitable forall ..Max-..-F actuators size "S" or "M".Required Accessories: Valve adaptation in accordance with valvemanufacturer, type and nominal size(diameter).Ordering Example: Modulating valve actuator with spring returnin hazardous location zone 2, for a globevalve with 0.79" stroke and a required forceof 335 lbf.
Actuator: RedMax-30-YFLinear adaptation: LIN-20Valve adaptation: suitable for valve type
on request
LIN-7.5 0.30" Linear unit up to max. 0.30" stroke, suitable for all ..Max-..-F actuators size "S" or "M" with spring returnLIN-10 0.39" Linear unit up to max. 0.39" stroke, suitable for all ..Max-..-F actuators size "S" or "M" with spring returnLIN-15 0.59" Linear unit up to max. 0.59" stroke, suitable for all ..Max-..-F actuators size "S" or "M" with spring returnLIN-20 0.79" Linear unit up to max. 0.79" stroke, suitable for all ..Max-..-F actuators size "S" or "M" with spring returnLIN-30 1.18" Linear unit up to max. 1.18" stroke, suitable for all ..Max-..-F actuators size "S" or "M" with spring returnLIN-40 1.65" Linear unit up to max. 1.65" stroke, suitable for all ..Max-..-F actuators size "S" or "M" with spring return
Type Stroke (max.) Description
Linear Unit for Actuators with Spring Return, 24 to 240 VAC/DC
LIN-..-CT C5-M painted aluminium housing, resistant against corrosive and/ or maritime atmosphere. Lifting rod, connecting parts and screws in VA
Type Description/ Technical Data
LIN-.. Options
LIN Special Options for Linear Unit Suitable for Actuators
LIN-CT
available for linearunit LIN-..
In accordance with..Max type for use in
Hazardous location orordinary location
Basics LIN--CT
CT: C5-M painted aluminium housing Resistant against corrosive and/or maritime atmosphere
Description
CT version with aluminium housing and C5-M painting,resistant against corrosive and maritime atmosphere,some parts nickel plated.
Delivery: 1 linear unit with special optionOrdering Example: LIN-20-CT
Special Options
Explosion Proof/Ordinary Location Features LIN--CT
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
19/76www.schischek.com
North American Price List 2014
19
Mounting Variations Valve Adaptation
To select the right valve adaptation and get the rightprice information the following information is required:
1. Valve manufacturer
2. Valve type
3. Valve nominal size (diameter) DN
For adaptations which are already designed bySchischek this information is sufficient.
To design new adaptations we need additionaldetails of the valve body as well as drawings.
With the purchase order you have to provideactuator type + type of adaptation.
Actuator ..Max-..-F LIN-.. Adaptation Valve Actuator with Spring Return
Selection of Recommended Actuators in Relation of Force (lbf) and max. Stroke (inch)
Nominal Force in lbf (N) at Spring of Actuator in Relation of max. Stroke of LIN at Temperatures between 4+104 F
Nominal Force in lbf (N) at Spring of Actuator in Relation of max. Stroke of LIN at Temperatures between +32+104 F
Attention: Limitation of resolution at YF-actuators with strokes < nominal (motor blockade)! Note the maximum force of the actuator to prevent damage to your valve!Info: Suitable actuators with spring return see page10-15.
Attention: Limitation of resolution at YF-actuators with strokes < nominal (motor blockade)! Note the maximum force of the actuator to prevent damage to your valve!
Above mentioned values are nominal trusts with performed self adjustment drive.The maximum trusts can read values which are up to three to four times higher than values of tables. Without performed self adjustment drive there can occur much higher trust values,which can cause damages on the mentioned valve or linkages.
0.3" (7,5 mm)
335 lbf (1,500 N)670 lbf (3,000 N)
670 lbf (3,000 N)1,350 lbf (6,000 N)
670 lbf (3,000 N)1,350 lbf (6,000 N)
335 lbf (1,500 N)670 lbf (3,000 N)
225 lbf (1,000 N)450 lbf (2,000 N)670 lbf (3,000 N)
450 lbf (2,000 N) 900 lbf (4,000 N)1,350 lbf (6,000 N)
225 lbf (1,000 N)450 lbf (2,000 N)900 lbf (4,000 N)
360 lbf (1,600 N)670 lbf (3,000 N)
1,350 lbf (6,000 N)
360 lbf (1,600 N)670 lbf (3,000 N)
110 lbf (500 N)225 lbf (1,000 N)450 lbf (2,000 N)
180 lbf (800 N)335 lbf (1,500 N)670 lbf (3,000 N)
180 lbf (800 N)335 lbf (1,500 N)
110 lbf (500 N)
180 lbf (800 N)225 lbf (1,000 N)335 lbf (1,500 N)450 lbf (2,000 N)560 lbf (2,500 N)670 lbf (3,000 N)
0.39" (10 mm) 0.59" (15 mm) 0.79" (20 mm)
At strokes betweentwo values use the nexthigher linear unite.g. 0.94" (24 mm)stroke = LIN-30
Max-135-F
Max-270-F Max-270-F
Max-270-F
Max-450-FMax-450-F
Max-450-FMax-450-FMax-270-F
Max-270-FMax-270-F
1.18" (30 mm) 1.65" (42 mm)
Max-135-F Max-135-FMax-135-F
Max-135-F
Max-135-F
Max-135-F
Max-270-F
Max-270-F
Max-450-F
Max-450-F
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
20/76
North American Price List 2014
www.schischek.com20
Valve Actuators Without Spring Return, 24 to 240 VAC/DC, for Division 1 and Zone 1, 2, 21, 22
Explosion Proof Features of ExRun, RedRun, InRun
RedRun...
Cl. I/II/II, Div. 2Zone 2, 22
Gas + Dustcertified accordingUL, CSA
ATEX, IECExGOST-R, RTN
ExRun...
Cl. I/II/III, Div. 1Zone 1, 2, 21, 22
Gas + Dustcertified accordingUL, CSA
ATEX, IECExGOST-R, RTN, KOSHA
InRun
NOT explosion proofand only for use in
ordinary locationscertified according togeneral purpose
standardNEMA4X/IP66
Industrial
Basics for all Run Valve Actuators
24240 VAC/DC self adaptable power supply Up to 5 different running times adjustable on site
0.2" to 2.36" stroke, mechanical limitationon each position Automatic adaptation of modulating signalat Ex-, Red-, InRun--Y..
Aluminum housing NEMA4X/ IP66 -4F...+104F/ +122F, integrated heater Emergency manual override Dimension (H1W D) 10.24" 8.2" 4.53" (without valve and adaptation)
Approximate weight 1617 lbs2
(without valve and adaptation)1Height varies depending on type2Weight varies depending on type
Description
ExRun, RedRun and InRun valve actuatorsare used for automation of linear valves
with 3-pos. on-off or modulating mode.
Scope of Delivery: 1 actuator with NPT1/2 conduit connectionand 39.4 inch cable extention, emergencymanual override, manuals
Required Accessories: valve adaptation in accordance with valvemanufacturer, type and nominal size(diameter).
ExRun/RedRun/InRun Valve Actuators Size "S" for Div. 1/2, Class I/II/III, zone 1, 2, 21, 22
Valve Actuators Without Spring Return, 24 to 240 VAC/DC, for Division 2 and Zone 2, 22
ExRun- 110.220-A 110 / 220 lbf 2/3/6/9 s / 0.0394" - On-off, 3-pos - - S
ExRun- 550.1100-A 550 / 1,100 lbf 2/3/6/9 s / 0.0394" - On-off, 3-pos - - S
ExRun-1650.2200-A 1,650 / 2,200 lbf (1,760 lbf) 4/6/9/12 s / 0.0394" - On-off, 3-pos - - S
ExRun- 110.220-Y-A 110 / 220 lbf 2/3/6/9 s / 0.0394" - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - S
ExRun- 550.1100-Y-A 550 / 1,100 lbf 2/3/6/9 s / 0.0394" - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - S
ExRun-1650.2200-Y-A 1,650 / 2,200 lbf (1,760 lbf) 4/6/9/12 s / 0.0394" - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - S
ExRun- 110.220-U-A 110 / 220 lbf 2/3/6/9 s / 0.0394" - On-off, 3-pos 0...10 VDC, 4...20 mA - S
ExRun- 550.1100-U-A 550 / 1,100 lbf 2/3/6/9 s / 0.0394" - On-off, 3-pos 0...10 VDC, 4...20 mA - S
ExRun-1650.2200-U-A 1,650 / 2,200 lbf (1,760 lbf) 4/6/9/12 s / 0.0394" - On-off, 3-pos 0...10 VDC, 4...20 mA - S
RedRun- 110.220-A 110 / 220 lbf 2/3/6/9 s / 0.0394" - On-off, 3-pos - - S
RedRun- 550.1100-A 550 / 1,100 lbf 2/3/6/9 s / 0.0394" - On-off, 3-pos - - S
RedRun-1650.2200-A 1,650 / 2,200 lbf (1,760 lbf) 4/6/9/12 s / 0.0394" - On-off, 3-pos - - S
RedRun- 110.220-Y-A 110 / 220 lbf 2/3/6/9 s / 0.0394" - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - S
RedRun- 550.1100-Y-A 550 / 1,100 lbf 2/3/6/9 s / 0.0394" - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - S
RedRun-1650.2200-Y-A 1,650 / 2,200 lbf (1,760 lbf) 4/6/9/12 s / 0.0394" - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - S
RedRun- 110.220-U-A 110 / 220 lbf 2/3/6/9 s / 0.0394" - On-off, 3-pos 0...10 VDC, 4...20 mA - S
RedRun- 550.1100-U-A 550 / 1,100 lbf 2/3/6/9 s / 0.0394" - On-off, 3-pos 0...10 VDC, 4...20 mA - S
RedRun-1650.2200-U-A 1,650 / 2,200 lbf (1,760 lbf) 4/6/9/12 s / 0.0394" - On-off, 3-pos 0...10 VDC, 4...20 mA - S
Type Force Running Time Spring Return Control Mode Feedback Features Size
Type Force Running Time Spring Return Control Mode Feedback Features Size
Valve Actuators Without Spring Return, 24 to 240 VAC/DC, for Ordinary Location
InRun- 110.220-A 110 / 220 lbf 2/3/6/9 s / 0.0394" - On-off, 3-pos - - S
InRun- 550.1100-A 550 / 1,100 lbf 2/3/6/9 s / 0.0394" - On-off, 3-pos - - S
InRun-1650.2200-A 1,650 / 2,200 lbf (1,760 lbf) 4/6/9/12 s / 0.0394" - On-off, 3-pos - - S
InRun- 110.220-Y-A 110 / 220 lbf 2/3/6/9 s / 0.0394" - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - S
InRun- 550.1100-Y-A 550 / 1,100 lbf 2/3/6/9 s / 0.0394" - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - S
InRun-1650.2200-Y-A 1,650 / 2,200 lbf (1,760 lbf) 4/6/9/12 s / 0.0394" - 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA - S
InRun- 110.220-U-A 110 / 220 lbf 2/3/6/9 s / 0.0394" - On-off, 3-pos 0...10 VDC, 4...20 mA - S
InRun- 550.1100-U-A 550 / 1,100 lbf 2/3/6/9 s / 0.0394" - On-off, 3-pos 0...10 VDC, 4...20 mA - S
InRun-1650.2200-U-A 1,650 / 2,200 lbf (1,760 lbf) 4/6/9/12 s / 0.0394" - On-off, 3-pos 0...10 VDC, 4...20 mA - S
Type Force Running Time Spring Return Control Mode Feedback Features Size
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
21/76www.schischek.com
North American Price List 2014
21
ExRun-
RedRun-
InRun-
AccessoriesType Technical Data
Stick Stick to change parameter and factory settings such as running time, torque, spring return time, force control and write protection depending on actuator
HV-R Manual override with locking mechanism suitable for ..Run valve actuators size S
GMB-1 Rubber bellow up to 2.36", colour black
Adaption Different adaptations for different valve types and sizes available. Please dont hesitate to ask for technical solution
Special options and offshore kits see page 23
To select the right valve adaptation and get the right price information thefollowing data are required: 1. Valve manufacturer 2. Valve type 3. Valve nominal size (diameter) DNFor adaptations which are already designed by Schischek this informationis sufficient.To design new adaptations we need additional details of the valve bodyas well as drawings.With the purchase order you have to provide actuator type and type ofadaptation.
Adaption
Run + Valve AdaptationRequired Data for Valve Adaptation
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
22/76
North American Price List 2014
www.schischek.com22
VASCTS
VAMCTM
WS-SWS-MWS-R
CTS
..Max-.. S
..Max-.. M
..Max-.. S/M
..Run-..
..Run-..
VAS
VAM
WS-S WS-M
CTS
CTM
WS-R
CTS
VA/CT Special Options Actuators Overview
Special Options Quarter Turn Actuators Size S
Special Options Quarter Turn Actuators Size M
Weather Shield for Quarter Turn and Valve Actuators
Special Options Valve Actuators
normal wiring
normal wiring
normal wiring
normal wiring
Overview of Special Options of Schischek Actuators for use under Extreme Weather Conditions
Installation/Application Area:
Usage in hazardous areas under extreme weather conditions and/or for offshore/onshore applications.
Ordinary Location Hazardous Location
Advantages of Special Options:
Resistant against corrosive and/or maritime atmosphere Usage under extreme weather conditions Approved for offshore-/ onshore applications Robust and thereby extended period of application time of actuators
..Max-.. Turn Actuators Size S
Housing material in stainless steel (VAS) oraluminium housing with C5-M painting (CTS) foruse under extreme weather conditions.
..Max-.. Turn Actuators Size MSurrounding housing in stainless steel (VAM) oraluminium housing with C5-M painting (CTM) foruse under extreme weather conditions.
..Max-.. Turn and ..Run Valve Actuators
Weather shield made of stainless steel for protec-tion against weather influences like rain, sun orsnow.
..Run-.. Valve Actuators
Aluminium housing with C5-M painting (CTS) foruse under extreme weather conditions.
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
23/76www.schischek.com
North American Price List 2014
23
..Max--VAS Housing material of ..Max quarter turn actuator size S in stainless steel AISI 316, some parts nickel plated
..Max--VAM Enclosure for ..Max quarter turn actuator size M, made of stainless steel AISI 316
..Max--CTS Aluminium housing of ..Max quarter turn actuator size S with C5-M painting, resistant against corrosive and maritime atmosphere, some parts nickel plated
..Max--CTM Aluminium housing of ..Max quarter turn actuator size M with C5-M painting, resistant against corrosive and maritime atmosphere, some parts nickel plated
WS-S Weather shield in stainless steel, suitable for all ..Max actuators size S
WS-M Weather shield in stainless steel, suitable for all ..Max actuators size M
..Run--CTS Aluminium housing with C5-M painting for ..Run valve actuator, resistant against corrosive/ maritime atmosphere, some parts nickel plated
WS-R Weather shield in stainless steel, suitable for all ..Run valve actuators
Type Description/ Technical Data
Type Description/ Technical Data
..Max-.. Options
..Run-.. Options
..Max Special Options for Quarter Turn Actuators Size S or M
..Run Special Options for Valve Actuators
..Max-VA/CT
available for ExMax,RedMax and InMax
In accordance with typefor use inHazardous location or
ordinary location
..Run-CTS
available for ExRun,RedRun and InRun
In accordance with typefor use in
Hazardous location orordinary location
Basics ..Max-VA/CT
VA: Housing material in stainless s teel AISI 316, some parts
nickel platedCT:
C5-M painted aluminium housing Resistant against corrosive and/or maritime atmosphere Cable glands brass nickel plated Screws in stainless steel
For general basics see ..Max quarter turn actuators.
Basics ..Run-CTS
CTS: C5-M painted aluminium housing Resistant against corrosive and/or maritime atmosphere Cable glands brass nickel plated Screws in stainless steel
For general basics see ..Run valve actuators.
Description
VA version with housing material in stainless steel AISI316, some parts nickel plated.CT version with aluminium housing and C5-M painting,resistant against corrosive and maritime atmosphere,some parts nickel plated.
Delivery: 1 quarter turn actuator size S or Mwith special option
Ordering Example: ExMax-15.30-VAS
Description
CTS version with aluminium housing and C5-M painting,resistant against corrosive and maritime atmosphere,some parts nickel plated.
Delivery: 1 valve actuator withspecial option
Ordering Example: ExRun-25.50-CTS
Special Options
Special Options
Explosion Proof
Explosion Proof
Features ..Max-VA/CT
Features ..Run-CTS
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
24/76
North American Price List 2014
www.schischek.com24
F
F
F
ExPolar-..-MS
ExPolar-..-MM
ExPolar-..-R
ExPolar Heating System Overview
Heating System for Quarter Turn Actuators ExMax Size S
Heating System for Quarter Turn Actuators ExMax Size M
Heating System for Valve Actuators ExRun
normal wiring
normal wiring
normal wiring
Overview of New Heating System for Use with Schischek Actuators Down to 58 F (50C)
Installation/Application Area:
Usage in hazardous areas for temperatures down to 58 F (50 C).
Advantages of ExPolar:
Especially for usage under high sub-zero temperatures Suitable for applications with high temperature fluctuations (58 F up to +122 F)
Usage directly in hazardous locations Adaptable on Schischek actuator series type ExMax size S or M, ExRun
ExPolar-..-MS
Adaptable on Schischek quarter turn actuators typeExMax-.. size S.
ExPolar-..-MM
Adaptable on Schischek quarter turn actuators typeExMax-.. size M.
ExPolar-..-R
Adaptable on Schischek valve actuators typeExRun-...
Ordinary Location Hazardous Location
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
25/76www.schischek.com
North American Price List 2014
25
ExPolar--MS ExMax-../ RedMax size S 58 F up to +122 F 24 VAC/DC 48 VAC/DC 120 VAC 240 VAC 40 W zone 1, 2, 21, 22InPolar- -MS InMax-.. size S 58 F up to +122 F 24 VAC/DC 48 VAC/DC 120 VAC 240 VAC 40 W ordinary location
ExPolar--R ExRun /RedRun 58 F up to +122 F 24 VAC/DC 48 VAC/DC 120 VAC 240 VAC 60 W zone 1, 2, 21, 22InPolar- -R InRun 58 F up to +122 F 24 VAC/DC 48 VAC/DC 120 VAC 240 VAC 60 W ordinary location
ExPolar--MM ExMax-../ RedMax size M 58 F up to +122 F 24 VAC/DC 48 VAC/DC 120 VAC 240 VAC 60 W zone 1, 2, 21, 22InPolar- -MM InMax-.. size M 58 F up to +122 F 24 VAC/DC 48 VAC/DC 120 VAC 240 VAC 60 W ordinary location
Supply voltage *Nominal value
Supply voltage *Nominal value
Supply voltage *Nominal value
VAS option not considered!
Type Adaptable on Operation Temperature Supply Power* Installation Area
Type Adaptable on Operation Temperature Supply Power* Installation Area
Type Adaptable on Operation Temperature Supply Power* Installation Area
ExPolar--MS/InPolar--MS
ExPolar--R/InPolar--R
ExPolar--MM/InPolar--MM
ExPolar/InPolar Heating System for Turn Actuators ..Max-.. Size S
ExPolar/InPolar Heating System for Valve Actuators ..Run
ExPolar/InPolar Heating System for Turn Actuators ..Max-.. size M
ExPolar--MSZone 1, 2, 21, 22
Gas + Dustcertified according
ATEX, IECEx
ExPolar--RZone 1, 2, 21, 22
Gas + Dust
certified according ATEX, IECEx
ExPolar--MMZone 1, 2, 21, 22
Gas + Dustcertified according
ATEX, IECEx
InPolar--MSNOT explosion proof and only for use inordinary locationNEMA4X / IP66
InPolar--RNOT explosion proof and only for use in
ordinary locationNEMA4X / IP66
InPolar--MMNOT explosion proof and only for use inordinary locationNEMA4X / IP66
Basics ..Polar
24/48 VAC/DC, 120/240 VAC 40 W
58+122 F (50+50 C) ExPolar for zone 1, 2, 21, 22 InPolar for ordinary location
Basics ..Polar
24/48 VAC/DC, 120/240 VAC 60 W 58+122 F (50+50 C) ExPolar for zone 1, 2, 21, 22 InPolar for ordinary location
Basics ..Polar
24/48 VAC/DC, 120/240 VAC 60 W 58+122 F (50+50 C) ExPolar for zone 1, 2, 21, 22 InPolar for ordinary location
Description
Controlled heating system for use insub-zero regions down to 58 F or at high
temperature fluctuations from 58 Fup to +122 F. Adaptable on Schischek quarter turn actua-tors ..Max-.. size S (depending on type).Delivery: 1 heating system
(adaptable)Ordering Example: ExPolar-240-MS
Description
Controlled heating system for use insub-zero regions down to 58 F or at hightemperature fluctuations from 58 Fup to +122 F. Adaptable on Schischek valve actuators..Run (depending on type).Delivery: 1 heating system
(adaptable)Ordering Example: ExPolar-240-R
Description
Controlled heating system for use insub-zero regions down to 58 F or at hightemperature fluctuations from 58 Fup to +122 F. Adaptable on Schischek quarter turn actua-tors ..Max-.. size M (depending on type).Delivery: 1 heating system
(adaptable)Ordering Example: ExPolar-240-MM
Features ..Polar--MS
Features ..Polar--R
Features ..Polar--MM
Explosion Proof
Explosion Proof
Explosion Proof
Industrial
Industrial
Industrial
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
26/76
North American Price List 2014
www.schischek.com26
Introducing ExReg HVAC Control Unit for Hazardous Locations!VAV/CAV and Pressure Control Applications ...
DECENTRALISED CONTROL STRUCTURES
HAZARDOUS LOCATIONS ZONE 1, 2, 21, 22
REDUCED LIFE-CYCLE-COSTS
NO INTRINSIC SAFE CIRCUITS NEEDED
INTEGRAL PID LOOP
PREDEFINED SETTINGS
PREDEFINED DAMPER CHARACTERISTICS
COMPATIBILITY TO MARKET STANDARDS
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
27/76
8/10/2019 Explosion Proof Actuators
28/76
North American Price List 2014
www.schischek.com28
M
VAV
P
PLC-System
Air damper Restrictor
S a
f e a r e a
E
x a r e a
O r d
i n a r y
L o c a
t i o n
H a z a r d o u s
L o c a
t i o n
ExReg-../RedReg-../InReg-V300-.. Volume Flow and Pressure Controller CAV/ VAVVAV Applications in a Typical HVAC System
Controller
ExReg-V300-..
Differential Pressure 0300 Pa (1.2 inchwater, VAV)
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
29/76www.schischek.com
North American Price List 2014
29
ExReg-V300-A Differential pressure 24 VAC/DC 0300 Pa (1.2 inch water) 1 actuator, 1 set point, 1 actual value, 1 pos. actuator zone 1, 2, 21, 22
ExReg-V300-B Differential pressure 24 VAC/DC 0300 Pa (1.2 inch water) 1 actuator, RS485 communication zone 1, 2, 21, 22
RedReg-V300-A Differential pressure 24 VAC/DC 0300 Pa (1.2 inch water) 1 actuator, 1 set point, 1 actual value, 1 pos. actuator Cl. I, Div. 2, zone 2
RedReg-V300-B Differential pressure 24 VAC/DC 0300 Pa (1.2 inch water) 1 actuator, RS485 communication Cl. I, Div. 2, zone 2
Type Sensor Supply Meas. Range Connection/ Interface (Analogue) Installation
Type Sensor Supply Meas. Range Connection/ Interface (Analogue) Installation
ExReg-V300-.. Volume Flow and Pressure Controller for Zone 1, 2, 21, 22 (ATEX only)
RedReg-V300-.. Volume Flow and Pressure Controller for Class I, Div. 2, Zone 2
ExMax- 5.10-CY 45 / 90 in-lbs 7.5/15/30/60/120 sec. - 4...20 mA 010 VDC combination with ExReg-.. S
ExMax-15.30-CY 135 / 270 in-lbs 7.5/15/30/60/120 sec. - 4...20 mA 010 VDC combination with ExReg-.. S
ExMax- 5.10-CYF 45 / 90 in-lbs 7.5/15/30/60/120 sec. ~ 10 sec. 4...20 mA 010 VDC combination with ExReg-.. S
ExMax-15 -CYF 135 in-lbs 7.5/15/30/60/120 sec. ~ 10 sec. 4...20 mA 010 VDC combination with ExReg-.. S
RedMax- 45.90 -CY -A 45 / 90 in-lbs 7.5/15/30/60/120 sec. - 4...20 mA 010 VDC combination with RedReg-.. S
RedMax-135.270-CY -A 135 / 270 in-lbs 7.5/15/30/60/120 sec. - 4...20 mA 010 VDC combination with RedReg-.. S
RedMax- 45.90 -CYF-A 45 / 90 in-lbs 7.5/15/30/60/120 sec. ~ 10 sec. 4...20 mA 010 VDC combination with RedReg-.. S
RedMax-135 -CYF-A 135 in-lbs 7.5/15/30/60/120 sec. ~ 10 sec. 4...20 mA 010 VDC combination with RedReg-.. SInMax- 5.10-CY 45 / 90 in-lbs 7.5/15/30/60/120 sec. - 4...20 mA 010 VDC combination with InReg-.. S
InMax- 15.30-CY 135 / 270 in-lbs 7.5/15/30/60/120 sec. - 4...20 mA 010 VDC combination with InReg-.. S
InMax- 5.10-CYF 45 / 90 in-lbs 7.5/15/30/60/120 sec. ~ 10 sec. 4...20 mA 010 VDC combination with InReg-.. S
InMax- 15 -CYF 135 in-lbs 7.5/15/30/60/120 sec. ~ 10 sec. 4...20 mA 010 VDC combination with InReg-.. S
Type Torque Running time 90 Spring Return Control Mode Feedback Features Size
Actuators for ExReg-../RedReg-../InReg-.. Controller
ExReg-/RedReg-/InReg-V300-.. Volume Flow and Pressure Controller CAV/ VAV
InReg-V300-A Differential pressure 24 VAC/DC 0300 Pa (1.2 inch water) 1 actuator, 1 set point, 1 actual value, 1 pos. actuator ordinary location
InReg-V300-B Differential pressure 24 VAC/DC 0300 Pa (1.2 inch water) 1 actuator, RS485 communication ordinary location
Type Sensor Supply Meas. Range Connection/ Interface (Analogue) Installation
InReg-V300-.. Volume Flow and Pressure Controller for Ordinary Location
Special options and offshore kits see page 50
MKR Mounting bracket for installation on round air-ducts, diameter up to 23.6" (600 mm)
Kit 2 Includes 2 meter pressure hose, inner diameter 0.24" (6 mm) and 2 plastic fittings
Type Technical Data
Accessories
ExReg-V300-..
Zone 1, 2, 21, 22Gas + Dust
certified according ATEX, IECExGOST-R
RedReg-V300-..
Cl. I, Div. 2Cl. I, Zone 2
Gascertified accordingCSA
Description
Compact controller for use in hazardousareas zone 1, 2, 21, 22 for control/regula-
tion of air/gas flows and pressure inventilation systems.Suitable actuator ..Max-...-CY or ..Max-...-CYF (with fail safe spring return) availableseparately.
Delivery:Electric volume flow/pressure controllerwith integrated terminal box (ExReg.. withEx-e), 3 tapping screws, short circuit tube
Basics for all ..Reg-V300-.. Controller
No additional module in the panel required No intrinsically safe wiring required
Adjustable k-factor Measurement range 0300 Pa (1.2 inch water) 24 VAC/DC Switch-on delay 3 seconds Air volume monitoring PID controller Programmable w/o additional tools Alarm with alarm delay function LCD backlight, defeatable Aluminium housing, protection NEMAX4X/IP6 Integrated terminal box (ExReg.. with Ex-e) Optional C5-M or stainless steel edition Dimensions (H W D) 7.1" 4.2" 2.6"
InReg-V300-..
NOT explosion proofand only for use in
ordinary locationscertified according toNEMA4X/IP66
Explosion Proof Industrial Features of ExReg-.., RedReg-.., InReg-V300-..
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
30/76
North American Price List 2014
www.schischek.com30
M
PLC-System
Humidifier
%rH
% rH
+
M C
C
PLC-System
Heater
O r d
i n a r y
L o c a
t i o n
H a z
a r d o u s
L o c a
t i o n
ExReg-../RedReg-../InReg-D-.. Temperature F/Humidity %rH Controller Temperature and Humidity Applications in a Typical HVAC System
Controller
ExReg-D-..
Temperature/Humidity 40+257 F(40+125 C)
0100 %rH
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
31/76www.schischek.com
North American Price List 2014
31
ExReg-D-A* ExPro-C.. 24 VAC/DC 40+257 F/ 0100 %rH 1 actuator, 1 set point, 1 actual value, 1 pos. actuator zone 1, 2, 21, 22
ExReg-D-B* ExPro-C.. 24 VAC/DC 40+257 F/ 0100 %rH 1 actuator, RS485 communication zone 1, 2, 21, 22
RedReg-D-A* ExPro-C.. 24 VAC/DC 40+257 F/ 0100 %rH 1 actuator, 1 set point, 1 actual value, 1 pos. actuator Cl. I, Div. 2, zone 2
RedReg-D-B* ExPro-C.. 24 VAC/DC 40+257 F/ 0100 %rH 1 actuator, RS485 communication Cl. I, Div. 2, zone 2
Type Sensor Supply Meas. Range Connection/ Interface (Analogue) Installation
Type Sensor Supply Meas. Range Connection/ Interface (Analogue) Installation
ExReg-D-.. Temperature/Humidity Controller for Zone 1, 2, 21, 22 (ATEX only)
RedReg-D-.. Temperature/Humidity Controller for Class I, Div. 2, Zone 2
InReg-D-A* InPro-C.. 24 VAC/DC 40+257 F/ 0100 %rH 1 actuator, 1 set point, 1 actual value, 1 pos. actuator ordinary location
InReg-D-B* InPro-C.. 24 VAC/DC 40+257 F/ 0100 %rH 1 actuator, RS485 communication ordinary location
Type Sensor Supply Meas. Range Connection/ Interface (Analogue) InstallationInReg-D-.. Temperature/Humidity Controller for Ordinary Location
ExPro-CT.. Temperature sensor probe for connection on ExReg-D-.. controller, installation in zone 1, 2, 21, 22
ExPro-CF.. Humidity sensor probe for connection on ExReg-D-.. controller, installation in zone 1, 2, 21, 22
InPro-CT.. Temperature sensor probe for connection on InReg-D-.. controller, installation in ordinary location
InPro-CF.. Humidity sensor probe for connection on InReg-D-.. controller, installation in ordinary location
Type Technical Data
Sensor Probes for ..Reg-D.. Controller
ExReg-../RedReg-../InReg-D-.. Temperature F/Humidity %rH Controller
Combi sensor probes not applicable!For more details about ExPro-C../InPro-C.. see page37
*Availability in second quarter.
*Availability in second quarter.
*Availability in second quarter.
For suitable ..Max actuators see previous page29For suitable ..Run valve actuators see page 20
Special options and offshore kits see page 50
MKR Mounting bracket for installation on round air-ducts diameter up to 23.6" (600 mm)
Type Technical Data
Accessories
ExReg-D-..
Zone 1, 2, 21, 22Gas + Dust
certified according ATEX, IECExGOST-R
RedReg-D-..
Cl. I, Div. 2Cl. I, Zone 2
Gascertified accordingCSA
Description
Compact temperature or humidity controllerfor use in hazardous areas zone 1, 2, 21, 22.
Suitable actuator ..Max-...-CY, ..Max-...-CYF(with fail safe spring return) or ExRun-..available separately.
Delivery:Electric temperature or humidity controllerwith integrated terminal box (ExReg.. withEx-e) and connection for 1 ExPro-C../InPro-C.. sensor probe, 3 tapping screws
Basics for all ..Reg-D-.. Controller
No additional module in the panel required No intrinsically safe wiring required
Meas. range 40+257 F/0100 %rH 24 VAC/DC Switch-on delay 3 seconds PID controller Programmable w/o additional tools Alarm with alarm delay function LCD backlight, defeatable Aluminium housing, protection NEMAX4X/IP6 Integrated terminal box (ExReg.. with Ex-e) Optional C5-M or stainless steel edition Dimensions (H W D) 7.1" 4.2" 2.6"
Explosion Proof Industrial Features ExReg-.., RedReg-.., InReg-D-..
InReg-D-..
NOT explosion proofand only for use in
ordinary locationscertified according toNEMA4X/IP66
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
32/76
North American Price List 2014
www.schischek.com32
Introducing ExCos Modulating Sensor Series for Hazardous Locations!Differential Pressure, Temperature and Humidity Control Applications ...
NO TRANSDUCER IN PANEL NEEDED
HAZARDOUS LOCATIONS ZONE 1, 2, 21, 22
NO INTRINSIC SAFE CIRCUITS NEEDED
EASY INSTALLATION
EASY PARAMETERISATION
REDUCED INSTALLATION COST
STAINLESS STEEL SOLUTION
ACTUAL VALUE INDICATION
Technical Short Information North America 2014
8/10/2019 Explosion Proof Actuators
33/76www.schischek.com
North American Price List 2014
33
Table of contents Installation Areas in Division/Zones Gas Dust Gas Dust Gas DustApprovals According to Zone System Zone 0 20 1 21 2 22 OL**Approvals According to Division System Cl. I Cl. II, III Cl. I Cl. II, III Cl. I Cl. II, III OL** Div 1 Div 1 Div 1 Div 1 Div 2 Div 2Product Line PageModulating Sensors for Temperature, Humidity, Pressure/ Differential PressureOverview modulating sensors 32-34
ExCos-P differential pressure, VAV s