Earth resistance:
Earth Resistance is the resistance offered by the earth electrode to the
flow of current in to the ground. The fault current is to be cleared as
quickly as possible and this is done by having the earth resistancelow. Persons touching any of the non current carrying grounded parts
shall not receive a dangerous shock during an earth fault. Each
structure, transformer tank, body of equipment, etc, should be
connected to earthing mat by their own earth connection.
Generally lower earth resistance is preferable but for certainapplications following earth resistance are satisfactory
In large power station - 0.5
Major Substation above 110KV - 1.0
Minor Substations Below 110KV - 2.0
7/30/2019 Final Presentation Earthing 22
3/20
Monitoring the condition of earth
For monitoring the healthiness of earth, the condition monitoring equipment
used is EARTH MEGGER.
The megger is a portable instrument used to measure insulation resistance. Itis used to measure very high resistance of the order of mega ohms.
Checking and testing
The Earthing systems are to be inspected regularly.
Regular checking of joints and broken connections, if any and rectifying thesame will prove to be of immense help in maintenance of earth grid and
equipments.
The condition of the electrodes, joints are also to be checked.
Ifthe electrodes are corroded immediate
steps for replacement are to be taken. The earth resistance is to be measured
periodically.
7/30/2019 Final Presentation Earthing 22
4/20
7/30/2019 Final Presentation Earthing 22
5/20
Earth Electrodes
A conductor buried in the ground, used to maintain conductors
connected to it at ground potential and dissipate current conducted
to it into the earth, known as earth electrode; grounding electrode.
Why must we have earth electrodes?
The purpose of the earth electrode is to connect to the general mass
of earth.The principle of earthing is to consider the general mass of
earth as a reference (zero) potential. Thus, everything connecteddirectly to it will be at this zero potential.
The effectiveness of an earth electrode in making good contact with
the general mass of earth depends on factors such as soil type,
moisture content, and so on. A permanently-wet situation may
provide good contact with earth, but may also limit the life of theelectrode since corrosion is likely to be greater
7/30/2019 Final Presentation Earthing 22
6/20
Earth electrode types
Driven Rod
Grounding Plates
Electrolytic Electrode
Driven Rod
The standard driven rod or copper-cladrod consists of an 8 to 10 foot length of
steel with a 5 to 10-mil coating of copper.This is by far the most commongrounding device used in the field today.
Driven rods are relatively inexpensive topurchase, however ease of installation isdependent upon the type of soil and
terrain where the rod is to be installed.The steel used in the manufacture of astandard driven rod tends to be relativelysoft.Purpose of copper on the rod is to
provide corrosion protection for the steelunderneath.
7/30/2019 Final Presentation Earthing 22
7/20
Grounding Plates
Grounding plates are typically thin copper plates buried in direct
contact with the earth. The National Electric Code requires that
ground plates have at least 2 ft2 of surface area exposed to thesurrounding soil. Ferrous materials must be at least .20 inches thick,
while non-ferrous materials (copper) need only be .060 inches thick.
Grounding plates are typically placed under poles or supplementing
counterpoises.
7/30/2019 Final Presentation Earthing 22
8/20
Electrolytic Electrode
The electrolytic electrode was specifically engineered to eliminate the
drawbacks of other grounding electrodes. This active grounding
electrode consists of a hollow copper shaft filled with natural earthsalts and desiccants whose hygroscopic nature draws moisture from
the air. The moisture mixes with the salts to form an electrolytic
solution that continuously seeps into the surrounding backfill material,
keeping it moist and high in ionic content. The electrolytic electrode is
installed into an augured hole and backfilled with a special highlyconductive product.
The electrolytic solution and the special backfill
material work together to provide a solid connection
between the electrode and the surrounding soil that
is free from the effects of temperature, environment,
and corrosion
7/30/2019 Final Presentation Earthing 22
9/20
Earthing ElectrodesA typical earthing electrode (left),
consisting of a conductive rod driven
into the ground
7/30/2019 Final Presentation Earthing 22
10/20
7/30/2019 Final Presentation Earthing 22
11/20
Soil Resistivity Soil resistivity is a measure of how much the soil resists the flow of
electricity.
It is a critical factor in design of systems that rely on passing current
through the Earth's surface. An understanding of the soil resistivity and
how it varies with depth in the soil is necessary to design thegrounding system in an electrical substation.
In general there is some value above which the impedance of the earth
connection must not rise, and some maximum step voltage which must
not be exceeded to avoid endangering people and livestock.
7/30/2019 Final Presentation Earthing 22
12/20
The soil resistivity value is subject to great variation, due to moisture,
temperature and chemical content.
Typical values are: Usual values: from 10 up to 1000 (m)
Exceptional values: from 1 up to 10000 (m)
SI unit of resistivity The SI unit of resistivity is the Ohm-meter (m); in the United States
the Ohm-centimeter (cm) is often used instead.
Measurement of soil resistivity
Wenner method
Schlumberger method
7/30/2019 Final Presentation Earthing 22
13/20
Wenner method
The Wenner four-pin method, as shown in figure above, is the most
commonly used technique for soil resistivity measurements.
Using the Wenner method, the apparent soil resistivity value is:
where E = measured apparent soil resistivity (m)
a = electrode spacing (m)
b = depth of the electrodes (m)
RW = Wennerresistance measured as V/I in Figure ()
7/30/2019 Final Presentation Earthing 22
14/20
Schlumberger method
In the Schlumberger method the distance between the voltages probe is aand the distances from voltages probe and currents probe are c.
Using the Schlumberger method, if b is small compared to a and c, andc>2a, the apparent soil resistivity value is:
where
E = measured apparent soil resistivity (m)
a = electrode spacing (m)
b = depth of the electrodes (m)
c = electrode spacing (m)
RS = Schlumberger resistance measured as V/I in Figure ()
7/30/2019 Final Presentation Earthing 22
15/20
Measurement of soil resistivity
7/30/2019 Final Presentation Earthing 22
16/20
METHODS TO IMPROVE SOIL RESISTIVITY
The following are the methods to lowering the earth
Lengthen the earth electrode in the earth
Use multiple rods.
Treat the Soil-
1. Using Bendonite Powder
2. Using Fly Ash3. Using Safe Earth Electrode(SSE)
4. Using Erico GEM
7/30/2019 Final Presentation Earthing 22
17/20
7/30/2019 Final Presentation Earthing 22
18/20
EARTH MAT DESIGN Earthing System in a Sub Station comprises of Earth Mat or Grid,
EarthElectrode, Earthing Conductor and Earth Connectors.
Earth Mat or grid: Bonding all metal parts of the system to be earthed, the earth conductor and
the earth electrodes put all together form an Earth Grid.
Primary requirement of Earthing is to have a low earth resistance.Substation involves many Earthings thro individual Electrodes, which will
have fairly high resistance. But if these individual electrodes are inter linkedinside the soil, it increases the area in contact with soil and creates numberof parallel paths. Hence the value of the earth resistance in the interlinkedstate which is called combined earth value which will be much lower thanthe individual value. The inter link is made thro flat or rod conductor whichis called as Earth Mat or Grid. It keeps the surface of substation equipment
as nearly as absolute earth potential as possible. To achieve the primaryrequirement of Earthing system, the Earth Mat should be design properly byconsidering the safe limit of Step Potential, Touch Potential and TransferPotential.
7/30/2019 Final Presentation Earthing 22
19/20
STEP POTENTIAL- which is the potential difference available betweenthe legs while standing on the ground.
TOUCH POTENTIAL -which is the potential difference between thelegand the hand touching the equipment in operation.
The factors which influence the Earth Mat design are
a. Magnitude of Fault Current
b. Duration of Fault
c. Soil Resistivity
d. Resistivitiy of Surface Material
e. Shock Duration f. Material of Earth Mat Conductor
g. Earthing Mat Geometry
7/30/2019 Final Presentation Earthing 22
20/20
EARTH MAT