1. GENERAL CONTRACTOR SHALL VISIT THE SITE, REVIEW THEBUILDING SHELL DRAWINGS AS SUBMITTED BY THE LICENSEE'S ARCHITECTAND BECOME THOROUGHLY FAMILIAR WITH THE SITE CONDITIONS PRIORTO BIDDING OR CONSTRUCTION.
2. GENERAL CONTRACTOR SHALL CONSULT WITH LICENSEE'SARCHITECT AND STARBUCKS PROJECT DEVELOPMENT MANAGER TORESOLVE ANY CHANGES, OMISSIONS OR PLAN DISCREPANCIES PRIOR TOBIDDING OR CONSTRUCTION.
3. ALL WORK SHALL BE PERFORMED IN STRICT COMPLIANCE WITHLOCAL, COUNTY, STATE AND FEDERAL CODES AND ORDINANCES.
4. GENERAL CONTRACTOR SHALL VERIFY THE LOCATION OF ALLUTILITIES.
5. GENERAL CONTRACTOR TO VERIFY ALL DIMENSIONS, INCLUDINGCLEARANCES REQUIRED BY OTHER TRADES AND NOTIFY THE LICENSEE'SARCHITECT AND STARBUCKS PROJECT DEVELOPMENT MANAGER OF ANYDISCREPANCIES PRIOR TOPROCEEDING WITH THE WORK. ALL DIMENSIONSARE TO THE FACE OF THE FINISHED SURFACE UNLESS NOTED OTHERWISE.ALL DIMENSIONS TO BE TAKEN FROM DESIGNATED DATUM POINT. DO NOTSCALE DRAWINGS.
6. GENERAL CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTINGWALLS, FLOORS, CEILINGS, OR OTHER SURFACES IDENTIFIED TO REMAINTHAT MAY BECOME DAMAGED DURING THE COURSE OF THE WORK.
7. GENERAL CONTRACTOR IS RESPONSIBLE FOR OBTAINING PERMITSFOR FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICALSYSTEMS PRIOR TO INSTALLATION OF SUCH SYSTEMS.
8. GENERAL CONTRACTOR SHALL RETAIN ONE SET OF THE PLANS TONOTE AND DOCUMENT ALL CHANGES DURING CONSTRUCTION. THIS SETSHALL BE SUBMITTED TO THE STARBUCKS PROJECT DEVELOPMENTMANAGER FOR RECORD.
9. GENERAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING DELIVERYOF MATERIALS FROM STARBUCKS CONTRACTED THIRD PARTY LOGISTICSDISTRIBUTION SERVICES AND VENDOR DIRECT SHIPMENTS.
10. RESPONSIBILITY FOR SUPPLY AND DELIVERY OF MATERIALS ANDEQUIPMENT IS IDENTIFIED IN THE DRAWING SCHEDULE SHEETS UNDER THECOLUMN LABELED "RESPONSIBILITY".
11. FOR THE PURPOSE OF THESE DOCUMENTS, TO “INSTALL” SHALLMEAN TO PROVIDE ALL FASTENERS, MISCELLANEOUS HARDWARE,BLOCKING, ELECTRICAL CONNECTIONS, PLUMBING CONNECTIONS, ANDOTHER ITEMS REQUIRED FOR A COMPLETE AND OPERATIONALINSTALLATION, UNLESS OTHERWISE NOTED.
12. ALL ITEM SUBSTITUTIONS MUST BE APPROVED BY THE STARBUCKSDESIGN MANAGER.
13. REFER TO ITEM CUTSHEETS FOR ADDITIONAL INFORMATION.
GENERAL NOTES
MAILINGADDRESS:
DESIGNMANAGER:
PROJECTDEVELOPMENTMANAGER:
LICENSEE:
ARCHITECTOF RECORD:
STRUCTURAL/CIVIL ENGINEER
MEP ENGINEEROF RECORD:
STARBUCKS COFFEE COMPANY2401 UTAH AVENUE SOUTHMS STOP: S-SD9SEATTLE, WASHINGTON 98134
ANDREW HUMAYDANSTARBUCKS COFFEE COMPANY60 SPEAR STREET, 7TH FLRSAN FRANCISCO, CA 94105(415)537-7174ahumayda@starbucks.com
JACQUIE HANNIBALSTARBUCKS COFFEE COMPANY(206)318.8867jhanniba@starbucks.com
AURARIA HIGHER EDUCATION CENTER1201 5th STREET, SUITE 370DENVER, CO 80204303.556.3349
KRISTINE ROUSE / BILL FURMANSLATERPAULL | HORD COPLAN MACHT1331 19th STREETDENVER, CO 80202303.607.0977krouse@slaterpaull.combfurman@slaterpaull.com
STAN LEWIS PEANDERSON & HASTINGS CONSULTANTS, INC.12596 WEST BAYAUD AVENUE, SUITE 200LAKEWOOD, CO 80228720.452.0524slewis@ahceinc.com
RICHARD MATTHIES, PEBCER ENGINEERING5420 WARD ROAD SUITE 200ARVADA, CO 80002303.405.2871dick@bcer.com
PROJECT CONTACTS INDEX OF SHEETS
SCOPE OF WORK
TENANT IMPROVEMENT AND ALTERATION OF EXISTING SPACE TO CAFE
VICINITY PLAN
SB / GCSB / FCGC / GCLC / GCLC / LCFC / GC
RESPONSIBILITY LEGEND - LICENSED STORES
FURNISHED BY STARBUCKS / INSTALLED BY LICENSEE'S GENERAL CONTRACTORFURNISHED BY STARBUCKS / INSTALLED BY STARBUCKS FIXTURE CONTRACTORFURNISHED BY LICENSEE'S GENERAL CONTRACTOR / INSTALLED BY LICENSEE'S GENERAL CONTRACTORFURNISHED BY LICENSEE / INSTALLED BY LICENSEE'S GENERAL CONTRACTORFURNISHED BY LICENSEE / INSTALLED BY LICENSEEFURNISHED BY STARBUCKS FIXTURE CONTRACTOR / INSTALLED BY LICENSEE'S GENERAL CONTRACTOR
CUSTOM DESIGN ID KEY
SIGNAGEGRAPHICS AND ARTWORK
SITEDOORS
DATA DEVICESPECIALITY EQUIPMENT
CASEWORKFURNITURE
LIGHTING FIXTUREPLUMBING / MECHANICAL
FINISHES - PAINTFINISHES - FLOOR TREATMENT
FINISHES - WALL TREATMENTFINISHES - CEILING TREATMENT
"S" x0000 - x0999 "G" x1000 - x1099 "Y" x1100 - x1199 "D" x2000 - x2999 "A" x3000 - x3999 "E" x4000 - x4999 "C" x5000 - x5999 "F" x6000 - x6999 "L" x7000 - x7999 "P" / "M" x8000 - x8999 x9000 - x9199 "T" x9200 - x9399 "Q" / "R" x9400 - x9799 "U" x9800 - x9999
SCHEDULE PREFIX
A - DATA DEVICE SCHEDULEB - WALL BASE SCHEDULEC - CASEWORK SCHEDULED - DOOR SCHEDULEE - SPECIALTY EQUIPMENT SCHEDULEF - FURNITURE SCHEDULEG - GRAPHICS AND ARTWORK SCHEDULEL - LIGHTING FIXTURE SCHEDULEM - MECHANICAL EQUIPMENT SCHEDULEP - PLUMBING FIXTURE SCHEDULEQ - WALL TREATMENT (AREA) SCHEDULER - WALL TREATMENT (LENGTH) SCHEDULES - SIGNAGE SCHEDULET - FLOOR TREATMENT SCHEDULEU - CEILING TREATMENT SCHEDULEW - WINDOW SCHEDULEY - SITE SCHEDULE
ABBREVIATIONS
3PL THIRD PARTY LOGISTICS
AC AIR CONDITIONINGACC ACCESSIBLEACT ACOUSTICAL CEILING TILEADJ ADJUSTABLEAFF ABOVE FINISHED FLOORAHJ AUTHORITIES HAVING JURISDICTIONAMP AMPEREAOR ARCHITECT OF RECORDAPPROX APPROXIMATE
BOH BACK OF HOUSEBLDG BUILDING
CAB CABINETCKT CIRCUITCL CENTER LINECLG CEILINGCLR CLEAR OR CLEARANCECOL COLUMNCOMP COMPARTMENTCONST CONSTRUCTIONCONT CONTINUOUSCTR CENTERCW COLD WATERCWF COLD WATER FILTEREDCX COMMISSIONINGCXA COMMISSIONING AGENT
DEG DEGREESDET DETAILDIA DIAMETERDISP DISPENSERDIM DIMENSIONDM STARBUCKS DESIGN MANAGERDN DOWNDWG(S) DRAWING(S)
EA EACHEC ELECTRICAL CONTRACTOREG EXHAUST GRILLEEL ELEVATIONELEC ELECTRICALEM EMERGENCYEQ EQUALEQUIP EQUIPMENTEXIST OR (E) EXISTINGEXP EXPOSEDEXT EXTERIOR
FC STARBUCKS FIXTURE CONTRACTOR/INSTALLERFCO FLOOR CLEANOUTFD FLOOR DRAINFF&E FURNITURE, FIXTURE AND EQUIPMENTF&I FURNISH AND INSTALLFIN FINISHFLR FLOORFOH FRONT OF HOUSEFRP FIBERGLAS REINFORCED PANELFS FLOOR SINKFT FOOT OR FEET
GC GENERAL CONTRACTORGFCI GROUND FAULT CIRCUIT INTERRUPTERGND GROUND
HC HOLLOW COREHDW HARDWAREHM HOLLOW METALHORIZ HORIZONTALHR HOURHS HAND SINKHT HEIGHTHVAC HEATING, VENTILATING AND AIR CONDITIONINGHW HOT WATER
ID INSIDE DIAMETER
LC LICENSEELL LANDLORDLV LOW VOLTAGE
MAX MAXIMUMMC MECHANICAL CONTRACTORMECH MECHANICALMEP MECHANICAL, ELECTRICAL AND PLUMBINGMFR MANUFACTURERMIN MINIMUMMS MOP SINK
NIC NOT IN CONTRACTNTS NOT TO SCALE
OA OVER ALLOC ON CENTEROD OUTSIDE DIAMETER
PC PLUMBING CONTRACTORPD STARBUCKS PRODUCTION DESIGNERPDM STARBUCKS PROJECT DEVELOPMENT MANAGERPLAM PLASTIC LAMINATEPOS POINT OF SALE
R RADIUSREF REFERENCEREQ(‘D) REQUIRE(D)REV REVISIONRG RETURN GRILLERND ROUNDRT ROOF TOP
SB STARBUCKSSC SOLID CORESF SQUARE FEETSHT SHEETSIM SIMILARSPEC SPECIFICATIONSQ SQUARESST STAINLESS STEELSUSP SUSPENDED
TEL TELEPHONETEMP TEMPORARYTW TEMPERED WATERTYP TYPICAL
UC UNDERCOUNTERUON UNLESS OTHERWISE NOTED
VD VENDOR DIRECTVERT VERTICALVIF VERIFY IN FIELD
W SANITARY WASTEWH WATER HEATERWP WEATHER PROOFWCO WALL CLEANOUT
PXXX-ES
X' XX"
X
N
NORTHARROW
XXXX AFF
ARCHITECTURAL SYMBOL LEGEND
XXXXXW
XX
Scale: X =X
0 2 4 8
GRAPHICSCALE
DATUMPOINT
EXTERIORELEVATIONCALL-OUT
INTERIORELEVATIONCALL-OUT
SECTIONCALL-OUT
DETAILCALL-OUT
REVISIONTAG
PAINTTAG
XXXXXX
DESIGN IDTAG
XXXXXD
DOORTAG
WINDOWTAG
SHEETNOTE
CALLOUT
ABOVE FINISHFLOOR
HEIGHT TAG
FINISH FACETO FINISH
FACEDIMENSION
REVISIONCLOUD
CONSULTANT:
ISSUE:
OWNER:
PROJECT:
DRAWING INFORMATION:
DRAWN BY:
PROJECT NO:
SHEET TITLE:
APPROVED BY:
CHECKED BY:
SHEET OF
1 2 3 4 5
A
B
C
D
1 2 3 4 5
THESE RECORD DRAWINGS HAVE BEENPREPARED, IN PART, ON THE BASIS OF
INFORMATION COMPILED ANDFURNISHED BY OTHERS. THE ARCHITECT
WILL NOT BE RESPONSIBLE FOR ANYERRORS OR OMISSIONS WHICH HAVE
BEEN INCORPORATED INTO THISDOCUMENT AS A RESULT.
P 303.607.0977www.slaterpaull.com
1331 Nineteenth StreetDenver, CO. 80202
5/26
/201
5 4:
36:3
7 PM
C:\U
sers
\bfu
rman
\Doc
umen
ts\1
1530
Tiv
oli S
tarb
ucks
_A_
2015
_bfu
rman
.rvt
G-0001G-0001G-0001G-0001
GENERALINFORMATION
AURARIA HIGHEREDUCATION CENTER
AURARIA CAMPUSTIVOLI STARBUCKS
CheckerAuthor
11530.000
Approver
900 AURARIA PKWYDENVER, CO 80204
05/22/2015 CONSTRUCTION DOCUMENTS
SHEET SHEET TITLE
GENERAL
G-0001 GENERAL INFORMATION
G-0010 SPECIFICATIONS
G-0011 SPECIFICATIONS
G-0012 SPECIFICATIONS
G-0013 SPECIFICATIONS
G-0014 SPECIFICATIONS
G-0015 SPECIFICATIONS
G-0016 SPECIFICATIONS
G-0017 SPECIFICATIONS
G-0018 SPECIFICATIONS
ARCHITECTURE
A-0001 CODE PLAN
INTERIORS
I-1101 DEMOLITION FLOOR PLAN
I-1102 DEMOLITION REFLECTED CEILING PLAN
I-1103 FLOOR PLAN & DOOR SCHEDULE
I-1104 PENETRATION PLAN
I-1105 FF AND E PLAN
I-1106 CASEWORK PLAN
I-1107 CASEWORK UPPERS PLAN
I-1108 REFLECTED CEILING PLAN
I-1109 LIGHTING DIMENSION PLAN
I-1110 FLOOR FINISH PLAN
I-1111 WALL FINISH PLAN
I-2101 INTERIOR ELEVATIONS
I-2102 INTERIOR ELEVATIONS
I-5001 DESIGN DETAILS
I-5002 DESIGN DETAILS
I-5004 CHILLED WALL CASE DETAILS
I-6001 SCHEDULES
STRUCTURAL
S-1000 PARTIAL 1ST FLOOR STAIR FRAMING PLAN & SECTIONS
MECHANICAL
M-0001 MECHANICAL GENERAL INFORMATION
M-0002 MECHANICAL SCHEDULES AND DETAILS
M-0003 MECHANICAL SPECIFICATIONS
M-1001 MECHANICAL DESIGN PLAN
M-1011 MECHANICAL PIPING & FIRE PROTECTION DESIGN PLAN
M-7001 MECHANICAL REMOVAL PLAN
ELECTRICAL
E-0001 ELECTRICAL GENERAL INFORMATION
E-0002 ELECTRICAL SCHEDULES
E-1001 ELECTRICAL LIGHTING DESIGN PLAN
E-1011 ELECTRICAL POWER DESIGN PLAN
E-1021 ELECTRICAL SYSTEMS DESIGN PLAN
PLUMBING
P-0001 PLUMBING GENERAL INFORMATION
P-0002 PLUMBING SCHEDULES
P-0003 PLUMBING SPECIFICATIONS
P-1000 BELOW FLOOR PLUMBING PLAN
P-1000C LEVEL 1 PLUMBING DESIGN PLAN - AREA C
P-1000D LEVEL 1 PLUMBING DESIGN PLAN - AREA D
P-1001 PLUMBING DESIGN PLAN
P-5001 PLUMBING DETAILS
P-7000 LEVEL 1 PLUMBING REMOVAL PLAN - AREA C
P-7001 LEVEL 1 PLUMBING REMOVAL PLAN - AREA D
EXISTING
4"
ABBREVIATIONS AND DESCRIPTIONS
ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT
MECHANICAL LEGEND
SHEET METAL FITTINGS AND EQUIPMENT
PIPING DESIGNATIONS, FITTINGS AND EQUIPMENT
CONTROLS DEVICES
BEVELED TAP OFF OF TOP
H
T
VCP
TYP
(E)
(R)
(N)
DIA, D
C
EL.
CI
CL
AFF
AP
FIRE DEPARTMENT CONNECTION
MANUAL VOLUME DAMPER
MOTORIZED DAMPER
MVD
MD
MIXED AIR
INVERT ELEVATION
MA
I.E.
FDC
EA OUTSIDE AIR
SUPPLY AIR
RETURN AIR
NIC
RA
SA
NORMALLY OPEN
NOT IN CONTRACT
NORMALLY CLOSED
OA
NC
NO
ROUND DUCT UP (1.5D ELBOW)
AIR FLOW - SUPPLY
AIR FLOW DIRECTION
RELOCATED
VITRIFIED CLAY PIPE
NEW
EXISTING
TYPICAL
UNIT MOUNTED THERMOSTAT
HUMIDISTAT
TRANSFER DUCT & GRILLES
M
BD
T
VANED ELBOW
LINEAR SLOT DIFFUSER
VANED ELBOW
RADIUS ELBOW; 1 DIAMETER
DOUBLE VANED ELBOW
CONDENSER WATER SUPPLY
CHILLED WATER RETURN
CHILLED WATER SUPPLY
HEATING WATER RETURN
HEATING WATER SUPPLY
LOW PRESSURE STEAM
CONDENSER WATER RETURNCR
LPR
LPS
HWR
CWR
CS
CWS
HWS
WALL MOUNTED THERMOSTATN - INDICATES NIGHTS - INDICATES SENSOR
FLEXIBLE DUCT CONNECTION
MOTORIZED DAMPER MOTOR
MANUAL VOLUME DAMPER
FLEXIBLE DUCT
DOOR UNDERCUT
ACCESS PANEL
BACK DRAFT DAMPER
REFRIGERANT HOT GAS
REFRIGERANT SUCTION
REFRIGERANT LIQUID
RHG
RS
RL
MEDIUM PRESSURE STEAM
HIGH PRESSURE STEAM
HPR
HPS
MPR
MPS
SUPPLY AIR DIFFUSER
RADIUS ELBOW
F
UC
TCOAD
TCEAD
VENT THROUGH ROOFVTR
S
FS
RETURN DUCT UP
SUPPLY DUCT UP
EXHAUST DUCT UP
F
INSTRUMENT AIR SIGNAL
INTERNAL SYSTEMSOFTWARE OR DATA LINK
AIR FLOW DIRECTION ARROW
FLOW SWITCH
FLOW TRANSMITTER
FS
FT
H HUMIDITY SENSOR
PDT
PI
PDS
PRESSURE DIFFERENTIALTRANSMITTER
POSITION INDICATOR
PRESSUREDIFFERENTIAL SWITCH
PSL PRESSURE SWITCH LOW
PSH PRESSURE SWITCH HIGH
TSH
TSL TEMPERATURE SWITCH LOW
TEMPERATURE SWITCH HIGH
T TEMPERATURE SENSOR
MANUAL SWITCH
P PRESSURE SENSOR
S
SP STATIC PRESSURE SENSOR
SENSOR
CO CARBON MONOXIDE
N
AQUASTATT
PRESSURE SWITCH
PRESSURE INDICATORPI
PS
HEAT RECOVERY RETURN
HEAT RECOVERY SUPPLY
HRR
HRS
INDICATOR LIGHT
CONDENSATE DRAINCD
(F) FUTURE
ROUND DUCT DOWN (1.5D ELBOW)
RETURN DUCT DOWN(MITERED ELBOW)
EXHAUST DUCT DOWN(MITERED ELBOW)
SUPPLY DUCT DOWN(MITERED ELBOW)
BOD
BOP
UNO UNLESS NOTED OTHERWISE
CONDENSER WATER (COMMON)
PRE-COOLING WATER RETURN
PRE-COOLING WATER SUPPLY
PWR
CDW
PWS
NON-POTABLE WATERNP
POTABLE (COLD) WATERCW
GASG
UNIT HEATER
EXHAUST FAN ON ROOF
BASEBOARD HEATER
SOUND ATTENUATOR
ABOVE FINISHED FLOOR
ACCESS PANEL
BOTTOM OF DUCT
BOTTOM OF PIPE
COMMON
CAST IRON
CENTER LINE ELEVATION
DIAMETER
EXHAUST AIR
ARROW PARALLEL TOLINE INDICATES PITCH
ARROW IN LINE INDICATESDIRECTION OF FLOW
LOW PRESSURE STEAM(CONDENSATE) RETURN
MEDIUM PRESSURE STEAM(CONDENSATE) RETURN
HIGH PRESSURE STEAM(CONDENSATE) RETURN
ROUND 90° CONICAL TAKE OFFFROM RECTANGLE TRUNK
RECTANGULAR 90° TAKEOFFFROM RECTANGULAR TRUNK
RECTANGULAR 90° TAKEOFFON END OF MAIN W/MIN. 12"AIR CUSHION DOWNSTREAM ROUND 90° CONICAL TAKEOFF
FROM RECTANGULAR TRUNK W/MANUAL VOLUME DAMPER
ROUND 90° SPIN-IN TAKEOFFFROM RECTANGULAR TRUNKW/MANUAL VOLUME DAMPER
DUCT TRANSITION CONCENTRIC
DUCT TRANSITION ECCENTRIC
SIDE TAKEOFF ATREGISTER OR GRILLE
BOTTOM TAKEOFF ATDIFFUSER. PROVIDE TYPICALPROJECT BALANCING
SIDE TAKEOFF AT DIFFUSER
RECTANGULAR 90° TAKEOFFWITH BEVELED TAP
ROUND DUCT DROP/RISE IN PLAN
RECTANGLE DUCTDROP/RISE IN PLAN
DIRECTION OF VIEW
M-?
1
DRAWN ON THIS SHEET
BOX ##__
A PICTURE DESIGNATION
NEW
LIGHT LINE WEIGHT FOREQUIPMENT, PIPING, SYMBOLS,TEXT, ETC. INDICATESEXISTING CONDITIONS WITHNEW WORK SHOWN AS DARK
HEATING COIL
CONTROL/COILACCESS
INDICATESSUPPLYAND RETURNPIPING TO UNIT
EQUIPMENTTERMINALOR VAV BOX
CFM
GPM
TB-103
650
1.2
POINT OFCONNECTION NEWTO EXISTING
STEAM TRAP
TEMPERATURE GAUGE
METERM
TEE DOWN
ELBOW DOWN
TEE UP
BRANCH-BOTTOM CONNECTION
BRANCH-TOP CONNECTION
RISE OR DROP
ELBOW UP
UNION
PIPE CAP OR PLUG
PIPE ALIGNMENT GUIDE
PIPE ANCHOR
STRAINER
FLEXIBLE CONNECTION
STRAINER W/BLOWOFF VALVE
EXPANSION JOINT
PIPE CONNECTION HOSE END BALL VALVE W/ CAP
VENTURI
VACUUM BREAKER
WELL
2-WAY CONTROL VALVE
3-WAY CONTROL VALVE
PRESSURE REDUCING VALVE
PRESSURE/TEMPERATURE TAP
AUTOMATIC AIR VENT
PRESSURE GAUGE W/ COCK
CIRCUIT SETTER
GLOBE VALVE
CHECK VALVE
TEMPERATURE/PRESSURE RELIEF VALVE
BUTTERFLY VALVE
BALANCING VALVE
BALL VALVE
PLUG VALVE
SOLENOID VALVE
CALIBRATED BALANCE VALVE
GAUGE W/ PIGTAIL
MANUAL AIR VENT
NEEDLE VALVE
PRESSURE INDEPENDENT VALVE
GAS COCK
GAS PRESSURE REGULATOR
BASE MOUNTED PUMP
IN-LINE PUMP
2-WAY VALVE
DUCT SMOKE DETECTORS
OPPOSED BLADE DAMPER
PARALLEL BLADE DAMPER
VFD
MS MOTOR STARTER
VARIABLE FREQUENCY DRIVE
DM DAMPER ACTUATOR
H HUMIDIFIER
CS CURRENT SENSOR
HORNH
FLOW SWITCHFS
DIRECTION OF CUT
SECTION DESIGNATION
TCRAD
RETURN OREXHAUSTREGISTER/GRILLE
UNSHADED AREAS INDICATEDIRECTION OF AIR FLOW (IF NOSHADING, 4-WAY ORADJUSTABLE)
ROUND DUCT TAKE OFFFROM TOP OF DUCT
BURIED,UNDERFLOOR ORUNDER DUCT
AIR FLOW -RETURNOR EXHAUST
4"
TEMPERATURE CONTROLEXHAUST AIR DAMPER
TEMPERATURE CONTROLOUTSIDE AIR DAMPER
TEMPERATURE CONTROLRETURN AIR DAMPER
EQUIPMENT TYPE
FLOOR #__IF MULTIPLE
TRANSITIONTOSIZE ON PLANS
CONTROLENCLOSURE
DASHED INDICATESEXISTING TO BE REMOVED
FIRE/SMOKE DAMPER (#REFERS TO SCHEDULE)
FIRE DAMPER
SMOKE DAMPER
CEILING AIR DEVICEWITH FIRE DAMPER
DASHED INDICATESEXISTING TO BE REMOVED
R
DR
D
SOFT COLD WATERSCW
CO CARBON DIOXIDE
RTS
FEK
FED
FECA
FECO2
FEABC
FEBC
WF
PS
AA
VS
R
P
CO
FA-?
1
A
RP
XX
SP
XX
F
ABBREVIATIONS and DESCRIPTIONS
ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT
FIRE AND LIFE SAFETY LEGEND
4"
FIRE ALARM
FIRE EXTINGUISHERS
FIRE PROTECTION VALVES and FITTINGS
FIRE SPRINKLERS
V
A
H
J
LIFE SAFETY
FDC
PA
STANDPIPE
DAS
FIREMAIN
DRY/AUTOMATIC SPRINKLER
SP/AS
FM
SP
AUTOMATIC SPRINKLERAS
TEE DOWN
ELBOW DOWN
TEE UP
BRANCH-BOTTOM CONNECTION
BRANCH-TOP CONNECTION
RISE OR DROP
ELBOW UP
UNION
PIPE CAP OR PLUG
PIPE GUIDE
PIPE ANCHOR
STRAINER
FLEXIBLE CONNECTION
STRAINER W/BLOWOFF VALVE
EXPANSION JOINT
BACKFLOW PREVENTER
VENTURI
PRESSURE REDUCING VALVE
GLOBE VALVE
CHECK VALVE
BALL VALVE
SOLENOID VALVE
MANUAL AIR VENT
EXISTING TO BE REMOVED
DIRECTION OF VIEW
DRAWN ON THIS SHEET
SECTION DESIGNATION
PICTURE DESIGNATION
4"
EXIST.
NEW
DIA, D DIAMETER
EL.
C
LC
CI
AP
AFF
CENTER LINE ELEVATION
ABOVE FINISHED FLOOR
ACCESS PANEL
COMMON
CAST IRON
INVERT ELEVATIONI.E.
NC
NO
NIC
VITRIFIED CLAY PIPE
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
TYPICAL
EXISTING
NEW
RELOCATED
(N)
(R)
(E)
TYP
VCP
VENT THROUGH ROOFVTR
FIRE DEPT. CONNECTION
DSP DRY/STANDPIPE
CLEAN AGENTCA
WATERMISTWM
CO
D
RM
FARP
FSCP
SPEAKER/HORN
FIRE ALARM PULL STATION
MINI HORN
CARBON MONOXIDE DETECTOR
SPEAKER
SPEAKER/HORN
FIRE ALARM PHONE
ABORT SWITCH
MAGNETIC DOOR HOLDER
FIRE SMOKE DAMPER
MONITOR MODULE
CONTROL MODULE
RELEASE MODULE
FIRE ALARM RELEASE PANEL
FIRE ALARM ANNUNCIATOR
FIRE ALARM PANEL
DUCT DETECTOR
FIRE ALARM CONTROL PANEL
R/F
R/C RATE COMPENSATION
F FIXED TEMPERATURE
-
-
-
C COMBINATION SMOKE/-
I IONIZED-
BT BEAM TRANSMITTER-
BR BEAM RECIEVER-
ASD AIR SAMPLING-
F FLAME-
UV ULTRA VIOLET-
IR INFRAED-
VR VISIBLE RADIATION-
HEAT DETECTOR
FLAME DETECTOR
SMOKE DETECTOR
FIRE FIGHTER CONTROL PANEL
TYPE 'ABC'
TYPE 'BC'
PREACTIONAUTOMATIC SPRINKLER
COMBINATION STANDPIPE/AUTOMATIC SPRINKLER
DELUGE AUTOMATICSPRINKLER
FIRESTANDPIPEDESIGNATION
FIRE SPRINKLERRISERDESIGNATION
LIGHT LINE WEIGHT FOREQUIPMENT, PIPING, SYMBOLS,TEXT, ETC. INDICATES EXISTINGCONDITIONS WITH NEW WORKSHOWN AS DARK
DASHED INDICATESEXISTING TO BEREMOVED
POINT OF CONNECTIONNEW TO EXISTING
TEMPERATURE/PRESSURE RELIEF VALVE
PRESSURE GAUGEWITH GUAGE COCK
HOSE END BALL VALVEWITH VACUUM BREAKER
FIRE HOSE VALVE CABINET(SURFACE MOUNTED)
BACKFLOW PREVENTER(REDUCED PRESSURE)
FIRE HOSE VALVECABINET (RECESSED)
BUTTERFLY VALVEW/TAMPER SWITCH
FREE STANDING FIREDEPARTMENT CONNECTION
CARBON MONOXIDE DETECTORWITH AUDIBLE ALARM
xxcd
15cd
F
COMBINATION: RATEOF RISE AND FIXEDTERMPERATURE
MAIN DRAIN ASSEMBLY
FIRE DEPARTMENTCONNECTION
WATER FLOW SWITCH
ANGLE VALVE
DRY PIPE VALVE
PRESSURE SWITCH
PREACTION VALVE
POST INDICATOR VALVE
FIRE HOSE RACK
FUTURE(F)
TRAVELDISTANCE
66.8 ft²
2 OCC.46.45
B
OCCUPANCY FLOOR AREA
OCCUPANT LOADFACTOR (OLF)
OCCUPANT LOAD
EXITING LOAD1 HR. FIRE PARTITION
2 HR. FIRE/SMOKE BARRIER
30 MIN. FIRE PARTITION
3 HR. FIRE RESISTANCE
WALL RATING LEGEND
STORAGE/PARKINGGROUP (S-1/S-2)
MEMORY CAREGROUP (I-2)
ASSISTED LIVINGGROUP (I-1)
INDEPENDENTLIVINGGROUP (R-2)
X
"DISTANCE IN FT"
30 MINUTE FIRE RATEDSMOKE PARTITION
P
WP
VALVE SUPERVISORYSWITCH
FIRE HYDRANT
xxcd
LHD
15cd
SS - SUPPLY
R - RETURN
REMOTE TEST SWITCH
FABP FIRE ALARM BOOSTER PANEL
ASFP
ACCESS CONTROL PANELACP
DACT
GRAPHIC MAPGMAP
ADDRESSABLE OUTPUT MODULEAOM
WITH GUARDWG
UNLESS OTHERWISE NOTEDUNO
WEATHER PROOFWP
DRY UPRIGHT SPRINKLER
UPRIGHT SPRINKLER
DRY PENDANT SPRINKLER
PENDANT SPRINKLER
SPRINKLER WITH GUARD
DRY SPRINKLER WITH GUARD
HORIZONTAL SIDEWALL SPRINKLER
OUTSIDE SPRINKLER
DRY OUTSIDE SPRINKLER
WATER SPRAY NOZZLE - DELUGE
WATER WASH WINDOW SPRINKLER
DRY SIDEWALL SPRINKLERC CONCEALED-R RECESSED-
TYPE 'CO2'TYPE 'CA'
TYPE 'D'
TYPE 'K'
V = BELLVS = BELL/STROBEC = CHIMECS = CHIME/STROBE
FIRE OR EMERGENCY PHONEFIRE OREMERGENCY PHONE- ACCESSIBLE
FIRE OR EMERGENCYPHONE - HANDSET
FIRE OR EMERGENCYPHONE - JACK
F
R RATE OF RISE ONLY-
P PHOTOELECTRIC-
HEAT DETECTOR
WATER FLOW SWITCH
PRESSURE SWITCH
VALVE SUPERVISORY SWITCH
LOW AIR PRESSURE ALARM
VS
WF
PS
AA
FIRE HOSE VALVE
SYMBOLS LEGEND
OCCUPANCY LEGEND
LIGHT HAZARD0.10GPM/1500 SQ. FT.
SPRINKLER DENSITY
ORDINARY HAZARDG1 0.15GPM/1500 SQ. FT.
EXTRA HAZARD G10.30 GPM/2500 SQ. FT.
ORDINARY HAZARDG2 0.20 GPM/1500SQ. FT.
NOTE: "EC" DENOTES EXTENDED COVERAGE SPRINKLER
DELUGE VALVE
NOTE: SIZES INDICATED IN SPECS / DRAWINGS
HEAT DETECTOR -LINE TYPE (CABLE)
STROBEWALL MOUNTED
STROBECEILING MOUNTED
SPEAKER/HORN/STROBE CEILING MOUNTED
SPEAKER/HORN/STROBEWALL MOUNTED WPDENOTES WEATHERPROOF
SMOKE DETECTORPHOTOELECTRIC WITH CARBONMONOXIDE DETECTION
FIRE FIGHTERS SMOKECONTROL PANEL
DIGITAL ALARMCOMMUNICATOR TERMINAL
AIR SAMPLING CONTROLDETECTION PANEL
LOW AIR SUPERVISORYSWITCH PRESSURE ALARM
GATE VALVE IN VERTICALWITH TAMPER SWITCH
NON-INDICATING VALVE(NON-RISING STEM)
T
T
T
T
T
T
T
FAA
FACP
FAP
FFCP
CM
MM
EXTRA HAZARD G20.40 GPM/2500 SQ. FT.
FACTORY (I-1)
CO
M
S
FS
OWNERSHIP OF DOCUMENTS:ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THEPROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THEOWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THEENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.
CONSULTANT:
ISSUE:
OWNER:
PROJECT:
DRAWING INFORMATION:
DRAWN BY:
PROJECT NO:
SHEET TITLE:
APPROVED BY:
CHECKED BY:
SHEET OF
1 2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
P 303.607.0977www.slaterpaull.com
1331 Nineteenth StreetDenver, CO. 80202
THESE RECORD DRAWINGS HAVE BEENPREPARED, IN PART, ON THE BASIS OF
INFORMATION COMPILED AND FURNISHEDBY OTHERS. THE ARCHITECT WILL NOT BE
RESPONSIBLE FOR ANY ERRORS OROMISSIONS WHICH HAVE BEEN
INCORPORATED INTO THIS DOCUMENT ASA RESULT.
5/2
6/2
015 2
:34:0
6 P
M
C:\
Users
\JP
EC
KO
VIT
CH
\Docum
ents
\Local R
evit F
iles\1
5915074 -
Tiv
oli
Sta
rbucks -
ME
P_R
15_jp
eckovitch.r
vt
M-0001
MECHANICALGENERALINFORMATION
Starbucks CoffeeCompany
AURARIA CAMPUSTIVOLI
RDM
JMP
65043-001
RDM
900 AURARIA PKWYDENVER, CO 80204
05/26/15 CONSTRUCTION DOCUMENTS
MECHANICAL SHEET LISTM-0001 MECHANICAL GENERAL INFORMATION
M-0002 MECHANICAL SCHEDULES AND DETAILS
M-0003 MECHANICAL SPECIFICATIONS
M-1001 MECHANICAL DESIGN PLAN
M-1011 MECHANICAL PIPING & FIRE PROTECTION DESIGN PLAN
M-7001 MECHANICAL REMOVAL PLAN
THE "ENGINE" SPACE OF STARBUCKS WILL REQUIRE THE INSTALLATION OF A NEW VAVTERMINAL WITH HEATING WATER HEAT COIL. DISTRIBUTED FROM THIS VAV WILL BE NEW.CONTROLS FOR THIS VAV WILL BE JOHNSON "METASYS" AND WILL BE CONNECTED TOBUILDING AND CAMPUS BAS SYSTEM.
THE PROJECT SCOPE FOR THE STARBUCKS OPEN SPACE WILL INCLUDE NEW SUPPLYDIFFUSER DISTRIBUTION FROM THE EXISTING VAV ZONE PRESENTLY INSTALLED ABOVE THECEILING.
MECHANICAL NARRATIVE
LOCATION:
OUTDOOR CONDITIONS:
INDOOR CONDITIONS:
ENVELOPECHARACTERISTICS:
INTERNAL LOADS:
OUTDOOR AIR VENTILATION RATE:
SPECIAL CONDITIONS:
SUMMERWINTER
COOLINGHEATING
(E) GLASS SHADING COEF.:(E) GLASS "U" FACTOR:(E) GLASS LOW-E:(E) GLASS INTERIOR SHADING:(E) WALL INSULATION "R":(E) ROOF INSULATION "R":
AVERAGE LIGHTING:AVERAGE MISC. ELECTRICAL:AVERAGE OCCUPANT LOAD:
LOAD CALCULATION DESIGN DATA
= 7.5 CFM/PERSON
= (1.0) WATTS/S.F.= (0.9) WATTS/S.F.= (150) S.F./PERSON
= (0.80)= (0.45)= (N)= (Y)= (14.0)= (NA)
= (93 DEGREES F/ 59 DEGREES (MEAN COINCIDENT W.B.)= (-10) DEGREES F
= (75) DEGREES F= (68) DEGREES F
Denver, Colorado; 5280 FT. ELEVATION,39° 5' DEGREES LATITUDE, 104° 5' DEGREESLONGITUDE
E. NATURAL GAS INPUTS ARE AT SEA LEVEL.
D. HORSEPOWERS ARE CORRECTED FOR ALTITUDE.
C. HEATING AND COOLING CAPACITIES ARE AT ALTITUDE OF PROJECT.
B. STATIC PRESSURES AND AIR PRESSURE DROPS ARE AT SEA LEVEL.
A. CFM IS AT ALTITUDE OF PROJECT.
23. CONVENTIONS USED IN THE PRESENTATION OF THE CONTRACT DOCUMENTS:
22. EXISTING EQUIPMENT AS NOTED ON THE DRAWINGS SHALL BE RETURNED TO THEOWNER AT THEIR DESIGNATED LOCATION.
21. EQUIPMENT E.E.R. AND/OR C.O.P. VALUES SHALL COMPLY WITH THE CURRENT EDITIONOF ASHRAE 90.1.
20. PROVIDE REDLINE MARK-UPS FOR ANY FIELD CHANGES OR MODIFICATIONS ON THECONSTRUCTION DOCUMENTS. REDLINE DRAWINGS SHALL BE PROVIDED WHETHERCOORDINATION DRAWINGS ARE REQUIRED OR NOT.
19. MOUNT THERMOSTAT AT 54" ON CENTER ABOVE FINISHED FLOOR UNLESSOTHERWISE NOTED. ADA REQUIREMENT.
18. RIGID INLET DUCTS TO VAV BOXES SHALL BE THE SAME SIZE AS THE VAV BOX INLETCONNECTION UNLESS NOTED OTHERWISE FOR A MINIMUM OF THREE DIAMETERS OFSTRAIGHT DUCT.
16. SPIN-IN FITTINGS TO VAV BOXES AND DIFFUSERS SHALL BE CONICAL TYPE (EXCEPTLOCATIONS WHERE LISTED DUCT HEIGHT DOES NOT ACCOMMODATE). SPIN-INFITTINGS TO DIFFUSERS SHALL INCLUDE AN INTEGRAL MANUAL VOLUME DAMPER.
15. ALL DUCT DIMENSIONS ARE OUTSIDE DIMENSIONS. WHERE DUCT LINER IS USED, THETHICKNESS OF THE LINER TO MAINTAIN THE CLEAR INSIDE DIMENSION HAS BEENINCLUDED. REFER TO DUCT INSULATION / LINER SCHEDULE AND/OR DIVISION 23 OFTHE SPECIFICATIONS.
14. CONTRACTOR SHALL CONSTRUCT AND INSTALL DUCTWORK ACCORDING TO SMACNASTANDARDS AS A MINIMUM REQUIREMENT. REFER TO SPECIFICATIONS FORADDITIONAL INFORMATION.
13. PROVIDE MANUAL AIR VENTS ON CLOSED SYSTEM WATER PIPING AT ALL CHANGES INELEVATION DOWNWARD IN DIRECTION OF WATER FLOW.
12. ALL EXISTING EQUIPMENT TO BE REMOVED SHALL HAVE ALL RELATEDHOUSEKEEPING PADS, PIPING, CONTROLS, GAUGES, ELECTRICAL SERVICE,HANGERS, SUPPORTS AND ANY MISCELLANEOUS RELATED SERVICE OR PARTS...
11. CONTRACTOR SHALL PROVIDE SUBMITTALS ON ITEMS LISTED IN THE MECHANICALSCHEDULES AND AS REQUIRED IN EACH SECTION OF SPECIFICATION TO THEENGINEER/OWNER FOR REVIEW PRIOR TO THE ORDER, PURCHASE OR INSTALLATIONOF THESE SAME ITEMS.
10. ALL MECHANICAL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THECURRENT VERSION OF INTERNATIONAL BUILDING CODE, 2009 INTERNATIONAL FIRECODE OR NFPA 2012, 2012 INTERNATIONAL MECHANICAL CODE, AND 2009INTERNATIONAL PLUMBING CODE AND 2012 INTERNATIONAL ENERGY CONSERVATIONCODE. REFER TO ARCHITECTURAL CODE PLAN.
9. CONTRACTOR SHALL FIELD VERIFY ALL MECHANICAL ITEMS PRIOR TO COMMENCINGNEW WORK AND FOR SUBMITTING A BID. NO ADDITIONAL COST WILL BE ALLOWEDFOR CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS.
8. CONTRACTOR SHALL CLOSELY COORDINATE NEW MECHANICAL WITH ALL NEW ANDEXISTING MECHANICAL, PLUMBING, ELECTRICAL, FIRE PROTECTION, ARCHITECTURALAND STRUCTURAL MEMBERS.
7. CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATION AND INSTALLING SLEEVES,INSERTS AND SUPPORTS AS REQUIRED FOR THIS SCOPE OF WORK AND/OR COREDRILL REQUIREMENTS. COORDINATE WITH GENERAL CONTRACTOR ANDSTRUCTURAL ENGINEER AS REQUIRED.
6. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'SRECOMMENDATIONS UNLESS SPECIFICALLY DIRECTED OTHERWISE.
5. CONTRACTOR SHALL NOT SHUT-OFF/PUT OUT OF SERVICE ANY SYSTEMS/SERVICESWITHOUT FIRST COORDINATING ALL DOWNTIME WITH OWNER'S PERSONNEL.CONTRACTOR SHALL PROVIDE A DETAILED M.O.P. AS REQUIRED. DO NOT BEGINWORK WITHOUT WRITTEN APPROVAL.
4. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL DESIGN INTENT,ARRANGEMENT AND EXTENT OF SYSTEMS. DO NOT SCALE DRAWINGS NOR USE ASSHOP DRAWINGS. WHERE ALTERNATE ROUTING, OFFSETS AND TRANSITIONS AREREQUIRED FOR FIELD COORDINATION OF ALL TRADES, THIS CONTRACTOR SHALLMAKE CHANGES WITHOUT ADDITIONAL COSTS.
3. COORDINATE ALL DIFFUSER AND GRILLE LOCATIONS WITH ARCHITECTURALREFLECTED CEILING PLAN, FIRE PROTECTION, AND ELECTRICAL DRAWINGS.
2. THE EQUIPMENT SPECIFIED ON THE DRAWINGS HAVE BEEN SELECTED AS THE BASISOF DESIGN. THE USE OF REVIEWED OR SPECIFIED EQUALS SHALL BE COORDINATEDBY THE CONTRACTOR AS TO SPACE REQUIREMENTS, EQUIPMENT DIMENSIONS ANDPERFORMANCE. ANY ADDITIONAL COSTS EITHER DIRECTLY OR INDIRECTLY CAUSEDBY EQUALS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
1. DUCT AND PIPE SIZE DIMENSIONS ARE IN INCHES UNLESS NOTED OTHERWISE.
MECHANICAL GENERAL NOTES
DUCT LINER / INSULATION SCHEDULE
REMARKSPHYSICAL DUCT DIMENSIONSLISTED ON DRAWINGS
INSULATIONOR LINER
SYSTEM
NOTES:
1. REFER TO SPECIFICATIONS FOR THICKNESS OF DUCT LINER AND EXTERIOR INSULATION FOR EACH SYSTEM.
SUPPLY AIR FROM FANDISCHARGE TO TERMINAL BOX
SUPPLY AIR DOWNSTREAMOF TERMINAL BOX
RETURN AIR
EXHAUST AIR
TRANSFER AIR
OUTSIDE AIR INTAKEDUCTS AND PLENUMS
EXTERNALLYINSULATED
EXTERNALLYINSULATED
NO INSULATIONOR LINER
--
DUCT SIZES LISTED ARE ACTUAL SHEET METALSIZE AND INCLUDE THICKNESS OF LINER
--
DUCT SIZES LISTED ARE ACTUAL SHEET METALSIZE AND INCLUDE THICKNESS OF LINER
DUCT SIZES LISTED ARE ACTUAL SHEET METALSIZE AND INCLUDE THICKNESS OF LINER
-
-
-
-
-
-
--
INTERNALLYLINED
INTERNALLYLINED
INTERNALLYLINED
BCER CONTACT LIST
Arvada Office Colorado Springs Office
10807 New Allegiance Dr.Suite 400Colorado Springs, CO 80921P - 719.533.1112
5420 Ward Rd.Suite 200Arvada, CO 80002P - 303.422.7400
Project Engineer
Dick Matthies303.422.7400 X239dick@bcer.com
Dick Matthies303.422.7400 X239dick@bcer.com
Project Manager
17. PROVIDE DIMENSIONALLY LOCATED PIPE MAINS AND BRANCH LINES TO FACILITIESSTRUCTURE SUCH AS COLUMN LINES, WALLS, RECOGNIZED BENCH MARKS, ETC.
16. FIRE SPRINKLER SHOP DRAWINGS TO LOCATE AND DESCRIBE GUIDES, ANCHORS ANDHANGARS FOR ALL PIPING. FIRE SPRINKLER SHOP DRAWINGS TO PROVIDEPROTECTION FOR UNDERNEATH DUCTWORK AND OTHER OBSTRUCTIONS ASNEEDED.
15. PROVIDE SPRINKLER PROTECTION A BOTTOM OF ELEVATOR SHAFT PER NFPA 14 ANDXXX AMENDMENTS.
14. PROVIDE TAMPER VALVES AND FLOW SWITCHES FOR EACH FIRE ZONE. VERIFY WITHFIRE ALARM CONTRACTOR FOR WIRING.
13. INSTALL SPRINKLER IN THE CENTER OR QUARTER POINT OF CEILING TILES, WHEREAPPLICABLE.
12. THE FIRE PROTECTION CONTRACTOR/ENGINEER OF RECORD SHALL SECURE THESITE FLOW TEST INFORMATION AND DOCUMENTATION FROM THE LOCAL WATERDEPARTMENT PRIOR TO THE DESIGN OF THE FIRE PROTECTION SYSTEM.
11. THIS CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTINGCONDITIONS PRIOR TO PURCHASE OF ANY MATERIALS AND THE COMMENCEMENT OFANY WORK. CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ANY DISCREPANCIESFOR RESOLUTION.
10. PROVIDE FIELD COORDINATION OF PIPING AND SPRINKLER HEAD INSTALLATIONSWITH EXISTING DUCTWORK, LIGHTS, SMOKE DETECTORS, DIFFUSERS, ETC..
9. FOR REMODEL AREAS NEW SPRINKLER HEADS SHALL MATCH EXISTING SPRINKLERS.EXISTING SPRINKLER HEADS SHALL NOT BE RELOCATED. INSTALL ALL NEW HEADS INREMODEL AREAS IF MATCHING HEADS CANNOT BE FOUND.
8. FIRE SUPPRESSION SYSTEM TO BE HYDRAULICALLY CALCULATED BASED ON NFPA 13AND 14 REQUIREMENTS. SPRINKLERS SHALL BE SPACED PER NFPA 13 REGARDINGOBSTRUCTIONS, BEAM POCKETS, HVAC DUCTWORK, PENETRATIONS AND ANY OTHERCLEARANCE RELATED ITEMS. CONTRACTOR SHALL VERIFY ALL SPACING ANDOBSTRUCTIONS BEFORE INSTALLATION.
7. PROVIDE ALL FITTINGS, RISER NIPPLES, ARM-OVERS, HANGERS, ETC. TO MAINTAINCONFORMANCE WITH APPLICABLE STANDARDS AND TO POSITION THE SPRINKLERHEADS IN THE PROPER LOCATIONS.
6. SEAL ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS AND FLOORS WITH ULLISTED FIRE PROOF MATERIALS AS REQUIRED TO MAINTAIN THE INTEGRITY OF THERATING.
5. FIRE PROTECTION CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL NEWFIRE PROTECTION EQUIPMENT AND PIPING WITH ALL OTHER TRADES PRIOR TOSUBMITTAL OF SHOP DRAWINGS AND SYSTEM INSTALLATION, SO AS NOT TOINTERFERE WITH THE ROUTING OF NEW DUCTWORK, PLUMBING, PIPING, ETC. REFERTO SPECIFICATION DIVISION 230000 FOR CEILING CAVITY SPACE ALLOCATIONPRIORITY.
4. ALL FIRE PROTECTION SYSTEMS INSTALLED SHALL BE IN ACCORDANCE WITH NFPA13, 14, 20 ETC. AND LOCAL BUILDING CODES AND ORDINANCES.
3. THE INFORMATION PRESENTED ON THESE DRAWINGS IS DIAGRAMMATIC. IT DOESNOT NECESSARILY REPRESENT ALL ELBOWS, OFFSETS, HANGERS, ETC. REQUIREDFOR A COMPLETE WORKING SYSTEM.
2. FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES NECESSARY FOR THEINSTALLATION OF A COMPLETE AND PROPERLY FUNCTIONING FIRE PROTECTIONSYSTEM.
1. THE SUCCESSFUL CONTRACTOR WILL BE THE ENGINEER OF RECORD FOR THEDESIGN ALTERATIONS OF THE FIRE PROTECTION SYSTEM. THE DESIGN ANDENGINEERING OF THE FIRE PROTECTION SYSTEM SHALL BE BY THE FIREPROTECTION CONTRACTOR. IT IS THE CONTRACTOR'S RESPONSIBILITY THAT THESYSTEM MEET ALL THE REQUIREMENTS OF NFPA AND THE AUTHORITY HAVINGJURISDICTION.
FIRE PROTECTION GENERAL NOTES
STARBUCKS
AURARIA HIGHEREDUCATION CENTER
OBD WHERE SPECIFIEDREFER TO G.R.D.SCHEDULE FORREQUIREMENTS.
AIR DEVICE REFER TOG.R.D. SCHEDULE ANDPLANS FOR TYPE.
1" DUCT LINER
BRANCH DUCT
CEILING
SPIN-IN W/ MVD
FLEXIBLE DUCT (MAX.6'-0")SUPPORT AT 3'-0"O.C.
FLEXMASTER TYPE"6M" OR EQUAL ELBOWW/ 3/4" DIAMETERINNER RADIUSMINIMUM
CONNECT FLEX TO AIRDEVICE PER SPECS.
STAINLESS STEELCLAMPING BAND
RETURN GRILLE REFERTO G.R.D. SCHEDULEAND PLANS FOR TYPE.
2 TIMES NECK SIZENECK SIZE
FLOW
6"1" DUCT LINER
OPEN TO PLENUM
CEILING
1/2
NE
CK
SIZ
E(M
INIM
UM
12")
SUPPORT SOUND BOOTFROM STRUCTURE PERSMACNA.
STAINLESS STEELCLAMPING BAND
FLEX DUCT
SPIN-IN W/MVD
AIR FLOW
PROVIDE MINIMUM 3DIAMETERS OFSTRAIGHT DUCT ONINLET OF BOX
TRANSITION FROMDUCT SIZE SHOWNON DRAWINGS
1/2" DRAIN VALVEW/CAP AND CHAIN
ACCESS DOOR(FACTORY INSTALLED)
INSTALL HWS ON LOWERCOIL CONNECTION ANDLEAVING AIR SIDE OF COIL
SUPPORT TERMINAL BOXINDEPENDENTLY FROMSTRUCTURE WITH SHEET METALSTRAPS (MINIMUM OF 4)
UNION (TYP.)
HEATING COIL
TRANSITION TERMINALBOX DISCHARGE TODUCT SIZE SHOWNON DRAWINGS
6'-0"MINIMUM
1" MINIMUMACOUSTICAL LINER
P/T PORT (TYP.)
HWS MAIN
STRAINER
BALL VALVE (TYP.)
SWING JOINT
SWING JOINT
HWR MAIN
CALIBRATED BALANCINGVALVE ASSEMBLY
TWO-WAY MODULATINGCONTROL VALVE
MANUAL AIR VENT
TO FIRSTTAKE-OFF
NOTE:
1. HWS/HWR PIPING SHALL BE 3/4" UNLESS NOTED OTHERWISEON DRAWINGS.
2. INLET DUCT SIZE TO TERMINAL BOX SHALL BE THE SAME SIZEAS INLET OF TERMINAL BOX UNLESS NOTED OTHERWISE ONDRAWINGS.
3. PROVIDE PROPER RIGHT HAND/LEFT HAND COILCONNECTIONS TO PIPE AS SHOWN. DO NOT ROTATE COIL.
VAV TERMINAL BOX
PROVIDE DDC CONTROLS AS FOLLOWS. INCLUDE DAT SENSOR, H.C. TCV POSITION, AND AIRFLOW CFMSETPOINT AND ACTUAL.
OCCUPIED MODE:
1. HEATING: WHEN SPACE TEMPERATURE FALLS BELOW THE HEATING THERMOSTAT SETPOINTMODULATE THE HEATING COIL CONTROL VALVE TOWARD THE OPEN POSITION. AS HEATINGDEMAND INCREASES MODULATE THE VAV DAMPER WITH THE HEATING COIL CONTROL VALVETOWARD THE MAX HEATING CFM (ADJ).
a. OCCUPANCY SENSOR CONTROL: HEATING THERMOSTAT SETPOINT SHALL BE 70°F (ADJ). SETPOINT SHALL REDUCE TO 65°F (ADJ) WHEN ALL OCCUPANCY SENSORS WITHIN THE VAV ZONE INDICATE ROOMS ARE UNOCCUPIED FOR GREATER THAN 30 MIN.
2. COOLING: WHEN SPACE TEMPERATURE RISES ABOVE THE COOLING SETPOINT MODULATE THE VAVDAMPER FROM FROM MINIMUM TO MAXIMUM COOLING CFM (ADJ). HEATING COIL CONTROL VALVE ISCLOSED.
a. OCCUPANCY SENSOR CONTROL: COOLING THERMOSTAT SETPOINT SHALL BE 75°F (ADJ). SETPOINT SHALL INCREASE TO 80°F (ADJ) WHEN ALL OCCUPANCY SENSORS WITHIN THE VAV ZONE INDICATE ROOMS ARE UNOCCUPIED FOR GREATER THAN 30 MIN.
UNOCCUPIED MODE:
1. WHEN SPACE TEMPERATURE FALLS BELOW THE UNOCCUPIED HEATING THERMOSTAT SETPOINTMODULATE THE VAV DAMPER TOWARD THE MAX HEATING CFM (ADJ). HEATING COIL CONTROL VALVESHALL BE CLOSED.
SEQUENCE OF OPERATION:
MAX HEATING
ROOMTEMP.INCREASE
MINSETPOINT
MAX COOLING
CF
M
HEATING TSTAT SETPOINT COOLING TSTAT SETPOINT
HEATING WATERCONTROL VALVEPOSITION
VAV BOX
SPACETEMPERATURESENSOR
T
TS
4
3
12
5
OWNERSHIP OF DOCUMENTS:ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THEPROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THEOWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THEENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.
CONSULTANT:
ISSUE:
OWNER:
PROJECT:
DRAWING INFORMATION:
DRAWN BY:
PROJECT NO:
SHEET TITLE:
APPROVED BY:
CHECKED BY:
SHEET OF
1 2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
P 303.607.0977www.slaterpaull.com
1331 Nineteenth StreetDenver, CO. 80202
THESE RECORD DRAWINGS HAVE BEENPREPARED, IN PART, ON THE BASIS OF
INFORMATION COMPILED AND FURNISHEDBY OTHERS. THE ARCHITECT WILL NOT BE
RESPONSIBLE FOR ANY ERRORS OROMISSIONS WHICH HAVE BEEN
INCORPORATED INTO THIS DOCUMENT ASA RESULT.
5/2
6/2
015 2
:34:1
0 P
M
C:\
Users
\JP
EC
KO
VIT
CH
\Docum
ents
\Local R
evit F
iles\1
5915074 -
Tiv
oli
Sta
rbucks -
ME
P_R
15_jp
eckovitch.r
vt
M-0002
MECHANICALSCHEDULES ANDDETAILS
Starbucks CoffeeCompany
AURARIA CAMPUSTIVOLI
RDM
JMP
65043-001
RDM
900 AURARIA PKWYDENVER, CO 80204
05/26/15 CONSTRUCTION DOCUMENTS
TERMINAL BOX SCHEDULE
PLAN CODE
DESIGN INSTALLED INLET SIZE (IN.) AIRFLOW SETPOINTS MAXIMUM AIRPRESSURE DROP
(IN. W.C.)
MAXDISCHARGE
N.C.
HEATING COIL DATA
REMARKSMFR. MODEL MFR. MODEL DIA. W HCOOLING MAX
(CFM)AIRFLOW MIN
(CFM)HEATING MAX
(CFM) EAT (°F) LAT (°F) EWT (°F) LWT (°F)COILMBH GLYCOL % GPM
MAX WATERP.D. (FT. W.C.)
TB-15-201(3) TITUS DESV 12 1,500 800 800 0.5 25 55 85 180 150 21.6 0 1.4 0.00 psi
TB-15-201(4) TITUS DESV 14 2,250 1,200 1,200 0.5 25 55 85 180 150 32.4 0 2.2 0.00 psi
NOT TO SCALE
AIR DEVICE DETAIL
NOT TO SCALE
CEILING GRILLE RETURN AIR BOOT
NOT TO SCALE
ROUND DUCT TAKE-OFF DETAIL
NOT TO SCALE
AIR TERMINAL BOX DETAIL (2-WAY CONTROL VALVE)
GRILLES, REGISTERS AND DIFFUSERS SCHEDULE
PLAN CODE
DESIGN
TYPE
INSTALLED
FRAME MATERIAL FINISHDAMPER
TYPE LEGEND REMARKSMFR. MODEL MFR. MODEL
RG-1 TITUS PXP CEILING PERFORATED LAY-IN STEEL (1) - - 24x24 FACE
SD-3 TITUS TDC 12x12 - 10Ø NECK CEILING LOUVERED FACE LAY-IN STEEL (1) - 24x24 FACE
SD-4 TITUS TDC 12x12 - 10Ø NECK CEILING LOUVERED FACE GYP BOARD CLG STEEL (1) - 24x24 FACE
NOT TO SCALE
TYPICAL VAV BOX CONTROL DIAGRAM
VAV BOX POINTS LIST
TAG DESCRIPTION TYPE
1 ZONE DAMPER AO
2 SUPPLY AIR AIRFLOW AI
3 DISCHARGE AIR TEMPERATURE AI
4 REHEAT VALVE AO
5 ZONE TEMPERATURE AI
(2) BASED ON 0% PROPYLENE GLYCOL SOLUTION.
(1) PROVIDE EACH BOX WITH CONTROLS AND/OR COIL CONNECTIONS TO MATCH THE MAINTENANCE ACCESS LOCATION INDICATED ONTHE DRAWING.
(1) PAINT COLOR SELECTION BY ARCHITECT.
STARBUCKS
AURARIA HIGHEREDUCATION CENTER
T
FS FS
T
T
T
WORKROOM
30
CAFE
32
BAR
33
RETAIL
34
M2
M2
(E)RG-1 (E)RG-1(E)SD-3
350(E)SD-3
350(E)SD-3
350
(E)SD-3
350
(E)SD-3
350
(E)SD-3
350
(E)SD-3
450
(E)RG-1
(E)SD-3
450
(E)SD-3
450
(E)RG-1
M1
M2
(E)32x16
(E)11x15 (E)17x15 (E)25x15
(E)2
4x12
(E)52x20
(E
)56
x2
4
(E)48x20
(E
)16
x1
4 (E
)14
x1
4
(E)22x18
(E)1
4x10
(E)52x20
M4
M2
M2
M2M2M1M2M1
(E)TB-201(1)
2,450
(E)TB-201(2)
2,700
M12
(E)64x44 RA UP
TO RTU-2
(E)64x44 SA MP
UP TO RTU-2
EXTENT OF HVACPROJECT SCOPE
TB-15-201(3)1,500
SD-3500
SD-3500
RG-1
SD-3500
20x16
(E
)16
x1
4
(E)24x10
SD-4450
SD-3450
SD-4450
SD-4450
SD-4450
SD-3450
SD-3450
SD-3350
M9
M6M6
M6
M7M8
M5
M5
M5
M5
RG-1
M9
M3
M3
M3M11
M11
M10M13
M2
24x14
SD-4450
TB-15-201(4)2,250
(E)32x16
M15
M17
M16
M14
OWNERSHIP OF DOCUMENTS:ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THEPROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THEOWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THEENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.
CONSULTANT:
ISSUE:
OWNER:
PROJECT:
DRAWING INFORMATION:
DRAWN BY:
PROJECT NO:
SHEET TITLE:
APPROVED BY:
CHECKED BY:
SHEET OF
1 2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
P 303.607.0977www.slaterpaull.com
1331 Nineteenth StreetDenver, CO. 80202
THESE RECORD DRAWINGS HAVE BEENPREPARED, IN PART, ON THE BASIS OF
INFORMATION COMPILED AND FURNISHEDBY OTHERS. THE ARCHITECT WILL NOT BE
RESPONSIBLE FOR ANY ERRORS OROMISSIONS WHICH HAVE BEEN
INCORPORATED INTO THIS DOCUMENT ASA RESULT.
5/2
6/2
015 2
:34:1
6 P
M
C:\
Users
\JP
EC
KO
VIT
CH
\Docum
ents
\Local R
evit F
iles\1
5915074 -
Tiv
oli
Sta
rbucks -
ME
P_R
15_jp
eckovitch.r
vt
M-1001
MECHANICAL DESIGNPLAN
Starbucks CoffeeCompany
AURARIA CAMPUSTIVOLI
RDM
JMP
65043-001
RDM
900 AURARIA PKWYDENVER, CO 80204
05/26/15 CONSTRUCTION DOCUMENTS
WORK NOTES
M1 EXISTING RG TO REMAIN.
M2 EXISTING SD-3; 255 CFM; TO REMAIN IN LAY-IN CEILING.
M3 EXISTING SD-3; 255 CFM; RELOCATE IN LAY-IN CEILING GRID.
M4 EXISTING SD-3 (255 CFM); TO REMAIN IN GYP. BRD. CEILING.
M5 PROVIDE NEW SD-4, BALANCE TO 255 CFM.
M6 REUSE EXISTING LAY-IN SD-3, 500 CFM EACH.
M7 NEW TB-15-201(3), 1500 CFM.
M8 CONNECT NEW 12Ø TO EXISTING 16X14 SUPPLY AIR.
M9 NEW RG-1.
M10 NEW THERMOSTAT TO NEW TERMINAL BOX.
M11 EXISTING TERMINAL BOX, REBALANCE TO CFM INDICATED.
M12 EXISTING SMOKE MANAGEMENT DUCT TO REMAIN.
M13 RELOCATED EXISTING THERMOSTAT SERVING EXISTING TB-15-201(2).
M14 PROVIDE NEW DUCT DIVIDER IN EXISTING 32X16 SA DUCT.
M15 NEW 24X14 REPLACING EXISTING 16X14.
M16 EXISTING THERMOSTAT TO REMAIN.
M17 NEW 14Ø SUPPLY AIR DUCT.
0'2' 1' 2' 4' 8'
1/4" = 1'-0"
HVAC DESIGN PLAN
2. REVIEW VAV AND THERMOSTAT CALIBRATION.
1. REBALANCE ALL DIFFUSERS AND VAV TERMINALS IN WORK AREA.
GENERAL NOTES
STARBUCKS
AURARIA HIGHEREDUCATION CENTER
RTU02(NIC)
TB20101
TB1520102
TB20102 TB1520101
1
2
3
45
1
2
3
1
2 3
4
5
1 2
3
4
567
T
T
T
T
WORKROOM
30
CAFE
32
BAR
33
RETAIL
34
H2
3/4" HWR
3/4" HWS
(E)1" HWS
(E)1" HWR
(E
)1"
HW
R
(E
)1"
HW
S
(E
)1"
HW
R
(E
)1"
HW
S
(E
)1"
HW
R
(E
)1"
HW
S
TB-15-201(3)1.4
(E)TB-201(2)
(E)TB-201(1)
(E)3/4" HWS
(E)3/4" HWR
(E)1" HWS
(E)1" HWR
(E
)CR
(E
)CS
H1
H3H3
H4
H4
FP1
H3
H3
H3
EXTENT OF HVACPROJECT SCOPE
TB-15-201(4)2.2
3/4" HWS
3/4" HWR
H1
OWNERSHIP OF DOCUMENTS:ALL DRAWINGS, SPECIFICATIONS AND OTHER WORK PRODUCT OF THE ENGINEER FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF THE ENGINEER WHETHER THEPROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE OF THE ENGINEER BY THE OWNER OF EXTENSIONS OF THIS PROJECT WITHOUT WRITTEN PERMISSION OF THE ENGINEER SHALL BE AT THEOWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY AND HOLD HARMLESS THE ENGINEER FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THEENGINEER'S INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER.
CONSULTANT:
ISSUE:
OWNER:
PROJECT:
DRAWING INFORMATION:
DRAWN BY:
PROJECT NO:
SHEET TITLE:
APPROVED BY:
CHECKED BY:
SHEET OF
1 2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
P 303.607.0977www.slaterpaull.com
1331 Nineteenth StreetDenver, CO. 80202
THESE RECORD DRAWINGS HAVE BEENPREPARED, IN PART, ON THE BASIS OF
INFORMATION COMPILED AND FURNISHEDBY OTHERS. THE ARCHITECT WILL NOT BE
RESPONSIBLE FOR ANY ERRORS OROMISSIONS WHICH HAVE BEEN
INCORPORATED INTO THIS DOCUMENT ASA RESULT.
5/2
6/2
015 2
:34:2
1 P
M
C:\
Users
\JP
EC
KO
VIT
CH
\Docum
ents
\Local R
evit F
iles\1
5915074 -
Tiv
oli
Sta
rbucks -
ME
P_R
15_jp
eckovitch.r
vt
M-1011
MECHANICAL PIPING& FIRE PROTECTIONDESIGN PLAN
Starbucks CoffeeCompany
AURARIA CAMPUSTIVOLI
RDM
JMP
65043-001
RDM
900 AURARIA PKWYDENVER, CO 80204
05/26/15 CONSTRUCTION DOCUMENTS
WORK NOTES
FP1 EXISTING FIRE SPRINKLER HEAD LOCATIONS ARE INDICATED. FIRE SPRINKLERCONTRACTOR SHALL REMOVE AND REPLACE WITH NEW HEADS OF SAME TYPETO PROVIDE COVERAGE THAT MEETS CURRENT IFC/NFPA CODES.
H1 PROVIDE NEW THERMOSTAT FOR NEW VAV TERMINAL.
H2 RELOCATED EXISTING THERMOSTAT SERVING EXISTING TB-201(2).
H3 EXISTING HEATING WATER PIPING.
H4 MEASURE EXISTING TERMINAL BOX GPM WITH TEMPERATURE CONTROL VALVEFULL OPEN; REBALANCE TO GPM AFTER NEW TERMINAL BOX IS INSTALLED.ADDITIONAL HEADS TO ALLOW FOR NEW WALLS AND COVERAGE IN ROOMSSHALL BE PROVIDED BY THE CONTRACTOR.
0'2' 1' 2' 4' 8'
1/4" = 1'-0"
MECHANICAL PIPING DESIGN PLAN/EXISTING FIRE PROECTION HEAD LAYOUT PLAN
STARBUCKS
AURARIA HIGHEREDUCATION CENTER