1X Series(phase 1)
Conventional Fire Panel
GE job title/2
GE internal information - Not for external distribution
2GE Security EMEA NPI template – v1
Signaling Devices
Up to 4 conventional zones with up to 32* devices per zone
FACP
Detection Devices
* Detector line dependent
2 x Inputs
240/110PSU
The 1X-F4 System
Up to 8 additional
supervised or un-
supervised auxiliary
relay outputs
Auxiliary Boards
GE job title/3
GE internal information - Not for external distribution
3GE Security EMEA NPI template – v1
The 1X-F4 System We decide to offer the customer the 1X-F4
2.8 kg
GE job title/4
GE internal information - Not for external distribution
4GE Security EMEA NPI template – v1
Preparation
• Cable Specifications
• System Specifications
• Bills of Quantities
• Standby Time
• Default System Configuration
• Planning the Installation
GE job title/5
GE internal information - Not for external distribution
5GE Security EMEA NPI template – v1
System Specifications System specifications (power supply for 2 and 4 zone panels)
•Mains Supply:110/240 VAC 50/60Hz (+10%/−15%) - < 2 A
•24 VDC Supply: (±2%) - < 2 A
•Batteries: (SLA) - < 7.2 Ah
•Battery charger:27.3 V @ 20ºC (−36mV/ºC) - < 0.5 A
•Auxiliary supply: - < 250 mA @ 21 - 28 VDC (24 V Nominal)
GE job title/7
GE internal information - Not for external distribution
7GE Security EMEA NPI template – v1
System Specifications System specifications (others - for 2 and 4 zone panels)
•Zone Supply: - < 65 mA @ 18-24 VDC (22 V nominal)
Zone equipment spec - < 2.6 mA
•Supervised Outputs: - < 250 mA @ 28 VDCSupervision Voltage - -15 VDC
•Unsupervised Outputs: - < 2 A @ 30 VDC
•Auxiliary Boards:Standard Relay Board - < 2 A @ 30 VDC
Supervised Relay Board - < 2.5 A @ 28 VDC
GE job title/9
GE internal information - Not for external distribution
9GE Security EMEA NPI template – v1
System Specifications Environmental specifications
•Temperature Specifications:Storage Temperature - -10 to +70°C
Operating temperature - -10 to +40°C
•Humidity: (non condensing) - 10 to 95%
•IP Rating: - IP30
GE job title/10
GE internal information - Not for external distribution
10GE Security EMEA NPI template – v1
Installing the Hardware in the Cabinet The hardware of the 1X-F4 (and 1X-F2) Back Box
Battery Plate
BS127N7.5 Ah Batteries
Mains Power Connector
1X-4F-MB
2010-1-RB / 2010-1-SB
2010-PS-20
1X-C2
GE job title/11
GE internal information - Not for external distribution
11GE Security EMEA NPI template – v1
Connecting the Field EquipmentSystem installation
INPUT1:unused
INPUT2:to the intrusion panel
Z1: to the showroom
Z2: to the office area
Z3: to the canteen
Z 4:unused
OUT1:showroom notification devices
OUT2:offices notification devices
OUT3:canteen notification devices
OUT4:unused
24V AUX:unused
FAULT: unused
FIRE: unused
Only required if non GE devices are used
GE job title/12
GE internal information - Not for external distribution
12GE Security EMEA NPI template – v1
Optional relay board required for door control• 2010-1-RB Un-supervised (4 relays COM-NO-NC)
Connected behind the mainPCB with a ribbon cablesupplied with therelay board.
Connectorsare still visibleand pluggable.
Connecting the Field EquipmentConnecting any auxiliary boards
SHOWROOM
OFFICES/TOILETS
CANTEEN
GE job title/13
GE internal information - Not for external distribution
13GE Security EMEA NPI template – v1
SHOWROOM
OFFICES/TOILETS
CANTEEN
The User InterfaceLocalisation
Easy language/country variant implementation allows for the panel to be available in local language using customised language inserts
Common control/indicator locationson all X series panels
Main indications
Main controls/indicators
Sounder controls/indicatorsFire routing controls/indicators
Maintenance controls/indicators
GE job title/14
GE internal information - Not for external distribution
14GE Security EMEA NPI template – v1
The User Interface Front panel (for everyone)
SHOWROOM
OFFICES/TOILETS
CANTEEN
GE job title/15
GE internal information - Not for external distribution
15GE Security EMEA NPI template – v1
The 7-Segment Display 7-Segment display (for the installer and maintenance engineer)
SHOWROOM
OFFICES/TOILETS
CANTEEN
GE job title/16
GE internal information - Not for external distribution
16GE Security EMEA NPI template – v1
The 7-Segment Display Features
ModeValue
• Provides the possibility to eliminate DIP switches and jumpers and makes the panel ready for PC programming
• Provides clear English menu extensions for easy configuration options
• Indicates default values ad user selections on 8th-segmentLEDs ON Default settingLEDs Blinking New selectionLEDs OFF No selection
• Indicates if in a main or sub menu with indication LEDs
GE job title/17
GE internal information - Not for external distribution
17GE Security EMEA NPI template – v1
Basic ProgrammingEntering basic programming mode
Default BASIC MENU password = 3333 and
The LED on RESET button indicates programming mode by blinking ON and OFF
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
GE job title/18
GE internal information - Not for external distribution
18GE Security EMEA NPI template – v1
Basic Programming The basic menu
ModeValue
43
1 2The basic menu allows the installer to set up most common parameters (if necessary) that are different to the factory default configuration.
Use the ^ (1) and v (3) keys to navigate through the menus.
GE job title/19
GE internal information - Not for external distribution
19GE Security EMEA NPI template – v1
Basic Programming The basic menu
ModeValue
43
1 2
Panel configuration using regional defaults sets all system parameters up for immediate use.
Press to access the sub-menu to change the basic operating mode.
ModeValue
Default value = 01
Use the ^ (2) and v (4) keys to navigate through the available options.
GE job title/20
GE internal information - Not for external distribution
20GE Security EMEA NPI template – v1
Basic Programming The basic menu – Modes of operation
43
1 2
ModeValue
Check/verify the default operating mode selected in the basic menu.
Press to access the sub-menu to view the basic operating mode.
ModeValue
Default value = En
GE job title/21
GE internal information - Not for external distribution
21GE Security EMEA NPI template – v1
Basic Programming The basic menu – Sounder Delay
ModeValue
43
1 2
Set the required sounder delay time.
Press to access the sub-menu to change the sounder delay time.
ModeValue
Default value = 00
Use the ^ (2) and v (4) keys to navigate through the available options.
Options: 01 to 10 minutesin 1 minute intervals
GE job title/22
GE internal information - Not for external distribution
22GE Security EMEA NPI template – v1
Basic Programming The basic menu – Fire Routing Delay
ModeValue
43
1 2
Here we set the required fire routing (fire brigade) delay time.
Press to access the sub-menu to change the fire routing delay time.
ModeValue
Default value = 00
Use the ^ (2) and v (4) keys to navigate through the available options.
Options: 01 to 10 minutesin 1 minute intervals
GE job title/24
GE internal information - Not for external distribution
24GE Security EMEA NPI template – v1
Basic Programming The basic menu – Number of modules
ModeValue
43
1 2
Set the number of auxiliary modules installed in the panel.
Press to access the sub-menu to change the number of auxiliary boards installed in the panel.
ModeValue
Default value = 00
Use the ^ (2) and v (4) keys to navigate through the available options.
Options: 00 to 04in 1 unit increments
GE job title/25
GE internal information - Not for external distribution
25GE Security EMEA NPI template – v1
Basic Programming The basic menu – Module A (only available when modules are configured)
ModeValue
43
1 2
Module A through D is assigned from left to right in the cabinet housing.
Press to access the sub-menu to change the module functionality.
ModeValue
Default = 01
Use the ^ (2) and v (4) keys to navigate through the available options.
Options: 01 to 92in unit increments
GE job title/26
GE internal information - Not for external distribution
26GE Security EMEA NPI template – v1
Basic Programming The basic menu – Restore configuration
ModeValue
43
1 2Returns the panel to the previous saved configuration.
Press to restore the panel to its previous configuration.
GE job title/27
GE internal information - Not for external distribution
27GE Security EMEA NPI template – v1
Basic Programming The basic menu – Factory configuration
ModeValue
43
1 2Returns the panel to the factory default configuration.
Press to return the panel to the factory default configuration.
GE job title/28
GE internal information - Not for external distribution
28GE Security EMEA NPI template – v1
Basic Programming The basic menu – Exit without saving
ModeValue
43
1 2Exits the basic menu without saving.
Press to exit the menu and abandon all changes.
The panel returns to normal operating mode.
GE job title/29
GE internal information - Not for external distribution
29GE Security EMEA NPI template – v1
Basic Programming The basic menu – Exit & Save
ModeValue
43
1 2Exits the basic menu and stores the latest configuration. The previous configuration is also saved as a backup.
Press to exit the menu and abandon all changes.
The panel returns to normal operating mode.
GE job title/30
GE internal information - Not for external distribution
30GE Security EMEA NPI template – v1
Basic ProgrammingExiting programming mode
After exiting the menu, the panel returns to normal operation.
Our application is set-up!
SHOWROOM
OFFICES/TOILETS
CANTEEN Remember that enabling the sounder
delay is a manual operation at EN54
level 2!
GE job title/31
GE internal information - Not for external distribution
31GE Security EMEA NPI template – v1
Advanced ProgrammingEntering advanced programming mode
Default ADVANCED MENU password = 4444 and
The LED on RESET button indicates programming mode by flashing ON and OFF
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
GE job title/32
GE internal information - Not for external distribution
32GE Security EMEA NPI template – v1
Advanced Programming The advanced menu -
ModeValue
43
1 2The advanced menu allows the installer to set up all configurations options.
Default Access Code = 4444 and
Use the ^ (1) and v (3) keys to navigate through the menu.
GE job title/33
GE internal information - Not for external distribution
33GE Security EMEA NPI template – v1
Advanced Programming The advanced menu – Auxiliary Reset
ModeValue
43
1 2
Allows the configuration mode of the auxiliary supply.
Press to access the sub-menu to change the module functionality.
ModeValue
Default = OF
Use the ^ (2) and v (4) keys to navigate through the available options.
Options: 0N or OF
GE job title/34
GE internal information - Not for external distribution
34GE Security EMEA NPI template – v1
FaultfindingExtensive diagnostic LEDs on the front panel
Faultfinding panel indications
• General Fault LED (Blinking)
This indication will always be accompanied by one of the other fault indicators (zone, device or function LEDs) to indicate the exact location of a problem.
Depending on the type of fault, this fault may reset automatically when the condition is removed or require user intervention.
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
GE job title/35
GE internal information - Not for external distribution
35GE Security EMEA NPI template – v1
Faultfinding panel indications
• Fire Routing Fault (blinking)
Supervision (open & short circuit detection) or overload fault on one of the fire routing outputs
This fault does not reset automatically
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
FaultfindingExtensive diagnostic LEDs on the front panel
GE job title/36
GE internal information - Not for external distribution
36GE Security EMEA NPI template – v1
Faultfinding panel indications
• Supply Fault (blinking)
Indicates a battery failure – no batteries, low batteries or high resistance failure
• Supply Fault (constant)
Indicates a mains or mains fuse failure
These faults reset automatically when the conditions are removed.
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
FaultfindingExtensive diagnostic LEDs on the front panel
GE job title/37
GE internal information - Not for external distribution
37GE Security EMEA NPI template – v1
Faultfinding panel indications
• Earth Fault (constant)
Indicates a connection (+ or -) to earth somewhere in the panel or field wiring.
This fault does not reset automatically.
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
FaultfindingExtensive diagnostic LEDs on the front panel
GE job title/38
GE internal information - Not for external distribution
38GE Security EMEA NPI template – v1
Faultfinding panel indications
• Out of Service (Constant)
The control panel is in-operative. It does not have sufficient power to operate on either mains or batteries.
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
FaultfindingExtensive diagnostic LEDs on the front panel
GE job title/39
GE internal information - Not for external distribution
39GE Security EMEA NPI template – v1
Faultfinding panel indications
• System fault
µProcessor failure SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
FaultfindingExtensive diagnostic LEDs on the front panel
GE job title/40
GE internal information - Not for external distribution
40GE Security EMEA NPI template – v1
Faultfinding panel indications
• Sounder Fault (blinking)
Supervision (open & short circuit detection) or overload fault on one of the sounder outputs.
This fault does not reset automatically
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
FaultfindingExtensive diagnostic LEDs on the front panel
GE job title/41
GE internal information - Not for external distribution
41GE Security EMEA NPI template – v1
Faultfinding panel indications
• Service Detector (constant)
Indicates that one or more detectors require servicing (CleanMe)*
Enter a valid password. Hold the silence buzzer key for 3 seconds. The zone in maintenance will be indicated on the zone fault LED for the affected zone.
* available on Dx700 series detectors only
This fault does not reset automatically.
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
FaultfindingExtensive diagnostic LEDs on the front panel
GE job title/42
GE internal information - Not for external distribution
42GE Security EMEA NPI template – v1
Faultfinding panel indications
• Expansion IO Fault
Communication and supervision (if applicable) fault on any of the auxiliary boards.
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
FaultfindingExtensive diagnostic LEDs on the front panel
GE job title/43
GE internal information - Not for external distribution
43GE Security EMEA NPI template – v1
Faultfinding panel indications
• Zone fault
Supervision (open & short circuit detection) or overload fault on the indicated zone.
This fault resets automatically when the condition is removed.
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
FaultfindingExtensive diagnostic LEDs on the front panel
GE job title/44
GE internal information - Not for external distribution
44GE Security EMEA NPI template – v1
TestingLamp Test
Can be performed at level EN54 level 1
Push and hold the test button for 3 seconds
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE
GE job title/45
GE internal information - Not for external distribution
45GE Security EMEA NPI template – v1
TestingEntering test mode
Default EN54-2 level 2 password = 2222 and
LED on RESET button indicates LEVEL 2 mode by being constantly ON
Use the TEST button together with the test/disable buttons for:
Zones –to test up to 4 zones simultaneously
Fire Routing –to test the fire routing outputs
Sounder –to test the sounder outputs (if required)
-to test the auxiliary board outputs
SHOWROOM
OFFICES/TOILETS
CANTEEN
WAREHOUSE