Post on 13-Jan-2016
description
transcript
Introducing GAC’s New Line of Intelligent Generator Set Controllers
The InteliGen• Stand-By, Prime Mover (single and multiple set), and Parralel to Utility (single and multiple set) Applications• Features:
128 x 64 LCD9 / 9 Discrete Inputs and Outputs (Configurable) Expandable
to 21 / 213 Analog Inputs (Fuel Level, Coolant Temp., Oil Press.)
Expandable to 7 and 1 Analog OutputSpeed Measurement (Mag Pick-Up)3 Phase Generator / Utility Voltage Measurement3 Phase Generator Current Measurement1 CT Input for Utility Measurement or Earth Fault ProtectionRS232 for Direct CommunicationMeets NFPA110 (w/ Annunciator Module iGL-RA15)Remote Communication (Analog, Internet, and GSM)
InteliGen Connections3 Phase Generator Voltage 9 Configurable
Discrete Inputs
Direct PC or Modem Connection
12 or 24 V DC
3 Analog Inputs (Oil, Temp., Fuel.)
Mag. Pick-up
2 Relay Outputs (Starter, Fuel Solenoid) 7 Config. Outputs
Connection forIOM / COM
Module
3 Phase Utility Voltage
Connection for Power Modules
Utility Current
and Current
InteliGen’s Modules
• Power Control Modules: PCM and PCLSM (with Load Sharing)
• AVR control (needs 18 V AC power supply)• Communications• Expandable I / O• Modem Support (multiple set applications)
Power Control ModulesShielded Analog Load Sharing Line (PCLSM
only)
Governor Control Output
AVRi Output
4 Discrete Inputs 4 Discrete Outputs
12 or 24 V DC
Mounts Directly to Back of InteliGen
AVRi Module
Input from PCLSM
18 V AC Power Supply
Output for AVR Control
DIN Rail Mounting
Output Level Adjustment (turn pot)
Communication Module
• Used for Multiple Set Applications• Communications Between Sets• Mount: Back of InteliGen• Up to 32 Sets • Use one Modem (w/iG-MU)• RS232 port for IOM
IOM / PTM Module
PO WER
8-36V DC
BIN ARY OUTPUTS
BIN ARY INPU TS AN ALOG INPU TS AN ALOG OUT
BO
8B
I8
BI7
BI6
BI5
BI4
BI3
BI2
CO
M AI4
BI1
BO
1
BO
2
BO
3
BO
4
BO
5
BO
6
BO
7S eria l No.
IG-IO M
IG-C
U
RS
232
9 Discrete Inputs w/ Active LED
4 Analog Inputs* 1 Analog Output
12 or 24 V DC w/Power LED
9 Discrete Outputs w/ Active LED
RS232 Connection to InteliGen
RS232 for Direct PC Connection
DIN Rail Mounting
InteliMains: InteliGen With Special Software
• Mains (= Utility) Circuit Breaker Control–Reverse Synchronization–Vector surge protection (locally required)
• Power Management - Engine Usage Optimization–Number of running engines: Dependent on required load–Engine starting order: Dependent on running hours
• Import/Export Control
Parallel To Utility & Other Gen Set’s
G
G+ iG-COM +
iG-PCLSM
iG-PCLSM
iG-C
OM
+ iG-COM + iG-PCLSM
iG-PCLSM
iG-C
OM
InteliMains
InteliGen’s User Friendly Operating Software
• Free•User Friendly• PC Format
Controller Setpoints
ValuesHistory
Value Screen
All Metered Values in Real Time.
Screen Selection
Metering
History
• Every Action Logged• All Values Associated w/ that Action• Up to 177 events (FIFO)
Controller• Same as Keypad• Essential Metering• Alarm List
Setpoints• Change any Setpoint • Current Value• Range
Screen Selection
Value
Acceptable Rangefor Parameter
Customizable Software• Parameters
Nominal RPM 80 300• Multilingual Texts
Overspeed Überdrehzahl Sobrevelocidad• Units
°C F; kPa bar psi• Controller Operating Mode
SPM SSB SPtM MINT MEXT• Text
Water temp Coolant temp
Local connection to the Control System
Modem connection to remote monitoring*
SMS (Mobile phones) connection*
Internet connection*
Communications
Controller Screens
Water Temp 91°C
Oil Pressure 5.1bar
Fuel level 75%
Battery voltage 25.2V
• Analog Meters• Bar Graphs• Numeric Values• Controller Screens Allow for Similar Interface as WinEdit Software
MAINS:230 228 233V 50.0Hz GENERATOR: 1517RPM221 223 220V 50.6Hz872 896 932A 0.98L 183 194 208kW 118kVAr
Running in Island
Setpoint Adjustment
PARAMETERS MF-Start Delay 3sStart Attempts 5 Mains OK-Delay 10sCooling time 30s
• Adjustable via iG Keypad• Three Level Password Protection
History Screens
121 125 124A 62kVAr 27 29 29kW 72 73 71A 48kVAr 17 18 16kW 0 0 0A 0 0 0kW 0 0 0A 0 0 0kW
-15 FINISHED HOUR 07:00:00 16.10.-16 GCB CLOSED-ISLAND 06:23:53 16.10.-17 ENGINE START 06:23:49 16.10.-18 MF-MCB OPENED 06:23:44 16.10.
85kW 1503RPM 0.81L 88C 6.1bar 24.9V 84% 50kW 1495RPM 0.72L 25C 5.3bar 24.7V 87% 0kW 0RPM - 22C 0.0bar 25.8V 87% 0kW ORPM - 22C 0.0bar 25.8V 87%
M 0 0 0V 0.0HzG233 227 229V 50.1HzM 0 0 0V 0.0HzG230 228 223V 49.8HzM 0 0 0V 0.0HzG 0 0 0V 0.0HzM190 195 201V 48.7HzG 0 0 0V 0.0Hz
• History Events Can be Viewed From iG Screens as well as WinEdit• Viewed on Multiple Screens
• Adjustable Delay Settings• Five Protective Actions
– Warning– Slow stop – Shut-down – Unloading – History Record
• Reset Function (Horn + Flashing Light)
Protection Handling
Protections• Generator / Utility Over / Under Voltage and Frequency• Voltage and Current Asymmetry• OverCurrent• OverLoad• Excitation Failure• Earth Fault• Oil Pressure (two level: warning, shutdown)• Coolant Temp. (three level: low temp warning, high temp warning, and high temp shutdown) Fuel Level (two level: warning, shutdown)• …
Summary
The InteliGen Offers the Right Solution for the Application.Never Pay for Unneeded Features.