Post on 28-Apr-2018
transcript
_____________________________________________________________________________ New Jersey BPU LGEA – County of Essex – Hall of Records
COUNTY OF ESSEX
HALL OF RECORDS 465 Dr. Martin Luther King Blvd, Newark, NJ, 07102
LOCAL GOVERNMENT ENERGY AUDIT PROGRAM
FOR NEW JERSEY
BOARD OF PUBLIC UTILITIES
January 2015
Prepared by:
6 Campus Drive Parsippany, NJ 07054
(973) 538-2120
CHA PROJECT NO. 29142
_____________________________________________________________________________ New Jersey BPU LGEA – County of Essex - Hall of Records i
TABLE OF CONTENTS
EXECUTIVE SUMMARY .................................................................................................... 1
BUILDING INFORMATION AND EXISTING CONDITIONS ................................................ 4
UTILITIES ........................................................................................................................... 8
BENCHMARKING ..............................................................................................................11
ENERGY CONSERVATION MEASURES ..........................................................................12
5.1 ECM-1 Reduce the Steam Pressure from 120 Psig to 100 Psig ................................................... 13
5.2 ECM-2 Replace Old RTUs with High Efficiency RTUs ................................................................... 13
5.3 ECM-3 Install Window AC Units Control System ........................................................................ 14
5.4 ECM-4 Install a Central Web-Based DDC System to Control the HVAC Equipment ................... 14
5.5 ECM-5 Replace Domestic Hot Water Heaters with Condensing DHW Heaters .......................... 15
5.6 ECM-6 Install Walk-in Cooler/Freezer Control ............................................................................ 16
5.7.1 ECM-L1 Lighting Replacement / Upgrades ................................................................................. 16
5.7.2 ECM-L2 Install Lighting Controls (Occupancy Sensors) .............................................................. 17
5.7.3 ECM-L3 Lighting Replacements with Controls (Occupancy Sensors) ......................................... 17
5.8 Additional O&M Opportunities ................................................................................................... 18
PROJECT INCENTIVES ....................................................................................................19
6.1 Incentives Overview .................................................................................................................... 19
6.1.1 New Jersey Smart Start Program ................................................................................................ 19
6.1.2 Direct Install Program ................................................................................................................. 19
6.1.3 New Jersey Pay For Performance Program (P4P) ....................................................................... 20
6.1.4 Energy Savings Improvement Plan ............................................................................................. 21
6.1.5 Renewable Energy Incentive Program ........................................................................................ 22
ALTERNATIVE ENERGY SCREENING EVALUATION .....................................................23
7.1 Solar ............................................................................................................................................ 23
7.1.1 Photovoltaic Rooftop Solar Power Generation .......................................................................... 23
7.1.2 Solar Thermal Hot Water Generation......................................................................................... 24
7.2 Wind Powered Turbines ............................................................................................................. 24
7.3 Combined Heat and Power Plant and Fuel Cell System .............................................................. 25
7.4 Demand Response Curtailment .................................................................................................. 25
CONCLUSIONS & RECOMMENDATIONS ........................................................................28
_____________________________________________________________________________ New Jersey BPU LGEA – County of Essex - Hall of Records ii
APPENDICES A Utility Usage Analysis and List of Third Party Energy Suppliers
B Equipment Inventory C ECM Calculations and Cost Estimates D New Jersey BPU Incentive Programs i. Smart Start ii. Direct Install iii. Pay For Performance Incentive Program (P4P) iv. Energy Savings Improvement Plan (ESIP) E Photovoltaic (PV) Solar Power Generation Analysis F Photos G EPA Benchmarking Report
_____________________________________________________________________________ New Jersey BPU LGEA – County of Essex - Hall of Records iii
REPORT DISCLAIMER
This audit was conducted in accordance with the standards developed by the American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) for a Level II audit. Cost and savings calculations for a given measure were estimated to within ±20%, and are based on data obtained from the owner, data obtained during site observations, professional experience, historical data, and standard engineering practice. Cost data does not include soft costs such as engineering fees, legal fees, project management fees, financing, etc. A thorough walkthrough of the building was performed, which included gathering nameplate information and operating parameters for all accessible equipment and lighting systems. Unless otherwise stated, model, efficiency, and capacity information included in this report were collected directly from equipment nameplates and /or from documentation provided by the owner during the site visit. Typical operation and scheduling information was obtained from interviewing staff and spot measurements taken in the field.
_____________________________________________________________________________ New Jersey BPU LGEA – County of Essex - Hall of Records iv
List of Common Energy Audit Abbreviations
A/C – Air Conditioning
AHS – Air Handling Unit
BMS – Building Management System
Btu – British thermal unit
CDW – Condenser Water
CFM – Cubic feet per minute
CHW – Chilled Water
DCV – Demand Control Ventilation
DDC – Direct Digital Control
DHW – Domestic Hot Water
DX – Direct Expansion
EER – Energy Efficiency Ratio
EF – Exhaust Fan
EUI – Energy Use Intensity
Gal – Gallon
GPD – Gallons per day
GPF – Gallons Per Flush
GPH – Gallons per hour
GPM – Gallons per minute
GPS – Gallons per second
HHW – Heating Hot Water
HID – High Intensity Discharge
HP – Horsepower
HRU – Heat Recovery Unit
HVAC – Heating, Ventilation, Air Conditioning
HX – Heat Exchanger
kbtu/mbtu – One thousand (1,000) Btu
kW – Kilowatt (1,000 watts)
kWh – Kilowatt-hours
LED – Light Emitting Diode
mbh – Thousand Btu per hour
mmbtu – One million (1,000,000) Btu
OCC – Occupancy Sensor
PSI – Pounds per square inch
RTU – Rooftop Unit
SBC – System Benefits Charge
SF – Square foot
UH – Unit Heater
V – Volts
VAV – Variable Air Volume
VSD – Variable Speed Drive
W – Watt
New Jersey BPU LGEA 1 | P a g e County of Essex - Hall of Records
EXECUTIVE SUMMARY
This report summarizes the energy audit performed by CHA for Essex County (EC) in connection with the New Jersey Board of Public Utilities (NJBPU) Local Government Energy Audit (LGEA) Program. The purpose of this report is to identify energy savings opportunities associated with major energy consumers and inefficient practices. Low-cost and no-cost are also identified during the study. This report details the results of the energy audit conducted for the building listed below:
Building Name Address Square
Feet Construction
Date
Hall of Records
465 Dr. Martin Luther King Blvd, Newark,
NJ, 07102 205,696 1925
The potential total annual energy and cost savings for the recommended energy conservation measures (ECM) identified in the survey are shown below:
Building Name Electric Savings (kWh)
NG Savings (therms)
Total Savings
($)
Payback (years)
Hall of Records 611,234 15,100 108,106 10.2
Each individual measure’s annual savings are dependent on that measure alone, there are no interactive effects calculated. There are three options shown for Lighting ECM savings; only one option can be chosen. Incentives shown (if any) are based only on the SmartStart Incentive Program. Other NJBPU or local utility incentives may also be available/ applicable and are discussed in Section 6.0. Each measure recommended by CHA typically has a stand-alone simple payback period of 15 years or less. However, if the owner choses to pursue an Energy Savings Improvement Plan (ESIP), high payback measures could be bundled with lower payback measures which ultimately can result in a payback which is favorable for an ESIP project to proceed. Occasionally, we will recommend an ECM that has a longer payback period, based on the need to replace that piece(s) of equipment due to its age, such as a boiler for example.
New Jersey BPU LGEA 2 | P a g e County of Essex - Hall of Records
The following table provides a detailed summary of each ECM for the building surveyed, including costs, savings, SmartStart incentives and payback.
Summary of Energy Conservation Measures
EC
M #
Energy Conservation Measure
Est. Costs
($)
Est. Savings ($/year)
Payback w/o
Incentive
Potential Incentive
($)*
Payback w/
Incentive
Recom
mend
ed
ECM-1
Reduce the Steam Pressure from 120 Psig to 100 Psig 60,846 6,490 9.4 0 9.4 Y
ECM-2
Replace Old RTUs with High Efficiency
RTUs 79,800 1,464 54.5 2,925 52.5 Y
ECM-3
Install Window AC Units Control System 21,200 8,479 2.5 0 2.5 Y
ECM-4
Install a Central Web-Based DDC System to
Control the HVAC Equipment 305,175 8,188 37.3 0 37.3 Y
ECM-5
Replace Domestic Hot Water Heaters with Condensing DHW
Heaters 24,698 1,041 23.7 3,000 20.8 Y
ECM-6
Install Walk-in Cooler/Freezer Control 20,625 1,410 14.6 0 14.6 Y
ECM-L1**
Lighting Replacements / Upgrades 504,915 76,053 6.6 97,405 6.6 N
ECM-L2**
Install Lighting Controls (Add
Occupancy Sensors) 85,860 14,381 6.0 11,130 5.9 N
ECM-L3
Lighting Replacements with Controls
(Occupancy Sensors) 590,775 81,034 7.3 108,535 6.0 Y
Total** 1,103,119 108,106 10.2 114,460 9.1
Total(Recommended) 1,103,119 108,106 10.2 114,460 9.1 * Incentive shown is per the New Jersey SmartStart Program. ** These ECMs are not included in the Total, as they are alternate measures not recommended.
The following alternative energy measures are also recommended for further study: Photovoltaic (PV) Rooftop Solar Power Generation – 80 kW System
New Jersey BPU LGEA 3 | P a g e County of Essex - Hall of Records
If County of Essex implements the recommended ECMs, energy savings would be as follows:
Existing
Conditions
Post Recommended
ECMs Percent Savings
Costs ($) 745,060 636,954 15%
Electricity (kWh) 3,680,750 3,069,516 17%
Natural Gas (therms) 280,832 265,732 5%
Site EUI (kbtu/SF/Yr) 197.6 180.1
Existing Conditions Post RecommnededECMs
0
500,000
1,000,000
1,500,000
2,000,000
2,500,000
3,000,000
3,500,000
4,000,000
Costs ($)
Electricity (kWh)
Natural Gas (therms)
New Jersey BPU LGEA 4 | P a g e County of Essex - Hall of Records
BUILDING INFORMATION AND EXISTING CONDITIONS
The following is a summary of building information related to HVAC, plumbing, building envelope, lighting, kitchen equipment and domestic hot water systems as observed during CHAs site visit. See appendix B for detailed information on mechanical equipment, including capacities, model numbers and age. See appendix F for some representative photos of some of the existing conditions observed while onsite. Building Name: Hall of Records/Annex Address: 465 Dr. Martin Luther King Blvd, Newark, NJ, 07102 Gross Floor Area: 205,696 Number of Floors: 5 floors and one basement Year Built: 1925
Building Envelope
Description of Spaces: This is a historic building which contains superior court judges’ offices, human resources offices, purchase and other administrative offices, cafeteria and meeting room in Annex. Description of Occupancy: The facility serves judges and county staff. Number of Computers: The amount of computers is not available due to the county security requirements. Building Usage: The typical office operating hours are from 7:00AM to 5:00PM. Construction Materials: Stone, marble and concrete block. Roof: The building has a flat roof which is covered with white rubber membrane. It is believed that the roof is well insulated. The roof is in good condition and no ECMs associated with roof replacement. Windows: The building has single pane windows with wood frame. Single pane windows lead extra energy loss and therefore an ECM associated with window replacement were evaluated. However, a further study is also recommended to ensure the new double windows meet the requirements of this historic building. Exterior Doors: Exterior doors are bronze doors and in good condition. No ECMs associated with the door seals replacement were evaluated.
New Jersey BPU LGEA 5 | P a g e County of Essex - Hall of Records
Heating Ventilation & Air Conditioning (HVAC) Systems Heating: There are two new steam boilers located in the Annex boiler room providing heating for Hall of Records, Veteran Courthouse and Historic Courthouse. Each of the steam boilers can produce 20,700 lbm/hr steam at 200 psig. These two boilers were made in 2012 and just installed because the old boilers do not meet the flue gas requirements. In discussions with the facility staff, it was noted that the steam boilers produce 120 psig steam in the main steam line and the steam is regulated down to 50 psig downstream and supplied to each facility. Hall of Records and Annex are heated by fan coil units equipped with steam radiators. Each room has a thermostat to control the room temperature. Apart from the central steam system, the Annex cafeteria area has four RTUs equipped with gas fired furnaces to provide additional heat for the cafeteria and kitchen. An ECM associated with reducing the steam pressure was evaluated. Cooling: The Annex is cooled by four roof top units (RTU) equipped with direct expansion (DX) units. Hall of Records has fifteen (15) RTUs spread on the roof to provide cooling for the building. The details of these RTUs are shown in the table below:
Name Manufacturer Function Cooling Capacity
RTU Carrier Roof top unit with DX cooling 15 ton
RTU LuxAire Roof top unit with DX cooling ~7.5 ton
RTU Lennex Roof top unit with DX cooling ~7.5 ton
RTU Carrier Roof top unit with DX cooling ~8 ton
RTU Trane Roof top unit with DX cooling 10 ton
RTU Trane Roof top unit with DX cooling 10 ton
RTU Carrier Roof top unit with DX cooling ~5 ton
RTU Carrier Roof top unit with DX cooling ~8 ton
RTU Trane Roof top unit with DX cooling ~5 ton
RTU Carrier Roof top unit with DX cooling ~5 ton
RTU York Roof top unit with DX cooling 10 ton
RTU Trane Roof top unit with DX cooling 10 ton
RTU Trane Roof top unit with DX cooling 10 ton
RTU Carrier Roof top unit with DX cooling ~8 ton
RTU York Roof top unit with DX cooling ~9 ton
Apart from the RTUs, there are about 110 window air conditioner (AC) units used to cool individual offices in the building.
New Jersey BPU LGEA 6 | P a g e County of Essex - Hall of Records
ECMs are included that evaluate replacing old HVAC units and adding window AC units control in this report. Ventilation: The ventilation of the building is provided by the RTUs located on the roof. Each of the RTU has an air intake from outside to bring fresh air into the building. The ventilation system appears to be in good condition and therefore, there is no ECM associated with the ventilation system. Exhaust: This building has multiple fractional horsepower exhaust fans serving restrooms and general exhaust all located on the roof. The fans are enclosed and therefore the capacities of fan motors are unknown. The exhaust fans are small and do not consume a lot of energy, therefore no ECMs were evaluated for the exhaust fans.
Controls Systems This building does not have a central direct digital control (DDC) system. The RTUs and heating system are controlled by thermostats located in rooms. These thermostats are manually controlled and do not have automatic temperature setback feature. The window AC units are controlled by remote control panels. It appears that the building is lack of control therefore, ECMs associated with installing a central DDC system to reduce the HVAC energy usage and window AC unit control system are evaluated.
Domestic Hot Water Systems The Annex mechanical room has two A.O smith PVI DHW heaters which supply hot water for the kitchen in the Annex and the sinks for Hall of Records /Annex. These two heaters are not high efficiency condensing water heaters, therefore, an ECM associated with replacing the DHW heaters with high efficiency gas fired condensing DHW heater is evaluated.
Kitchen Equipment There is a kitchen and a cafeteria in the Annex of Hall of Records. The kitchen was operating and not accessible during the site visit. In discussions with facility staff, it was noted that there are two walk-in coolers and one freezer. The condensing units of the walk-in coolers and freezers are on the roof. The walk-in cooler and freezer each has a Russell condensing unit located on the roof and the rated cooling capacity of them is 7,080 BTH. The kitchen hood has a designated Dayton make-up air unit to compensate the air exhausted by the kitchen hood. The Dayton unit is running based on the kitchen hood operating hours. An ECM related to upgrade the control on the walk-in cooler/freezer is evaluated.
Plug Load This building has computers, LCD monitors copiers and printers which contribute to the plug load in the building. The plug load devices appear to be Energy Star devices and therefore, there is no ECM associated with plug load devices.
Plumbing Systems The plumbing fixtures were renovated and the restrooms contain new style low flow toilets and urinals. The sink faucets are single handle type and have low-flow type aerators. The plumbing
New Jersey BPU LGEA 7 | P a g e County of Essex - Hall of Records
fixtures are low flow fixtures and appear to be in good condition. Therefore, no ECM related to plumbing system is evaluated.
Lighting Systems The building has a mixture of some 32W T-8 fluorescent lighting and incandescent lights in chandeliers. The majority of lighting fixtures are spot lights and incandescent lights. The lights in this building are controlled by manual switches. Some rooms were occupied and not observed during the site visit. LEDs are recommended in this study, however, a comprehensive photometric study should be conducted before implementation because this building is a historic building and have special requirements on the lights. We have provided three alternatives for the observed lighting that include adding occupancy sensors to the existing lights, replacing the lights with LED lights and a third ECM that evaluates adding occupancy sensors to the proposed LED lights.
New Jersey BPU LGEA 8 | P a g e County of Essex - Hall of Records
UTILITIES
This building shares one electricity meter with Veterans Courthouse and Leroy Smith Public Safety building. The electric meter is located in Veterans Courthouse. It is heated by the steam provided by the steam plant in Hall of Records which also serves Veterans Courthouse and Historic Courthouse. The utility usages of these buildings are calculated by using the assumption that the usage is proportional to the square feet of each building. It is suggested that the County work with the utility company to sub-meter each building individually in order to understand the energy consumption of each building better. Natural gas and electricity are delivered and supplied by the following utility companies:
Electric Natural Gas
Deliverer PSE&G PSE&G
Supplier PSE&G HESS
The utility usage for each building that shares the same meter are calculated based on the square feet of each building. For the 12-month period ending in January 2014, the utilities usages and costs for the building were as follows:
Electric
Annual Consumption 3,595,777 kWh
Annual Cost 542,633 $
Blended Unit Rate 0.151 $/kWh
Supply Rate 0.143 $/kWh
Demand Rate 3.79 $/kW
Peak Demand 881.8 kW
Natural Gas
Annual Consumption 144,882 Therms
Annual Cost 97,817 $
Unit Rate 0.675 $/therm Blended Rate: Average rate charged determined by the annual cost / annual usage Supply Rate: Estimated Demand Rate: Rate charged for actual electrical demand in kW (based on most recent electric bill)
New Jersey BPU LGEA 9 | P a g e County of Essex - Hall of Records
The electric usage fluctuates with the building usage. The usage is higher in the summer season when AC units in the building are used.
The natural gas usage in this building is for heating and domestic hot water heating and therefore there is small usage in the summer months. The gas usage during the heating season is correlated to winter weather conditions.
0
100
200
300
400
500
600
700
800
900
1,000
0
50,000
100,000
150,000
200,000
250,000
300,000
350,000
400,000
Feb
-13
Ma
r-1
3
Apr-
13
Ma
y-1
3
Jun-1
3
Jul-1
3
Aug-1
3
Sep-1
3
Oct-
13
No
v-1
3
De
c-1
3
Jan-1
4
Dem
an
d (
kW
)
Usag
e (
kW
h)
Month
Hall of Records Electric Usage
(kWh) (kW)
0
5,000
10,000
15,000
20,000
25,000
30,000
35,000
$-
$5,000.00
$10,000.00
$15,000.00
$20,000.00
$25,000.00
Feb
-13
Mar
-13
Ap
r-1
3
May
-13
Jun
-13
Jul-
13
Au
g-1
3
Sep
-13
Oct
-13
No
v-1
3
De
c-1
3
Jan
-14
Co
nsu
mp
tio
n (
The
rms)
Hall of Records Gas Usage
Total ($) Consumption (Therms)
New Jersey BPU LGEA 10 | P a g e County of Essex - Hall of Records
See Appendix A for utility analysis. Under New Jersey’s energy deregulation law, the supply portion of the electric (or natural gas) bill is separated from the delivery portion. The supply portion is open to competition, and customers can shop around for the best price for their energy suppliers. The electric and natural gas distribution utilities will still deliver the gas/ electric supplies through their wires and pipes – and respond to emergencies, should they arise – regardless of where those supplies are purchased. Purchasing the energy supplies from a company other than your electric or gas utility is purely an economic decision; it has no impact on the reliability or safety of the service.
Comparison of Utility Rates to NJ State Average Rates* Recommended to Shop for Third Party Supplier?
Utility Units Average Rate NJ Average Rate
Electricity $/kWh $0.15 $0.13 Y
Natural Gas $/Therm $0.675 $0.96 N * Per U.S. Energy Information Administration (2013 data – Electricity and Natural Gas, 2012 data – Fuel Oil)
Additional information on selecting a third party energy supplier is available here: http://www.state.nj.us/bpu/commercial/shopping.html. See Appendix A for a list of third-party energy suppliers licensed by the Board of Public Utilities to sell within the building’s service area. The charts below represent estimated utility end-use utility profiles for the building. The values used within the charts were estimated from a review of the utility analysis and the energy savings calculations.
Site End-Use Utility Profile
Lighting28%
Motors16%
Cooling36%
Plug Load8%
Computers
6%Other
4%
Electricity Use (kWh):
Boilers97%
DHW3%
Natural Gas End Use
Boilers
DHW
New Jersey BPU LGEA 11 | P a g e County of Essex - Hall of Records
BENCHMARKING
The EPA Portfolio Manager benchmarking tool provides a site and source Energy Use Intensity (EUI), as well as an Energy Star performance rating for qualifying building types. The EUIs are provided in kBtu/ft2/year, and the performance rating represents how energy efficient a building is on a scale of 1 to 100, with 100 being the most efficient. In order for a building to receive and Energy Star label, the energy benchmark rating must be at least 75. As energy use decreases from implementation of the proposed measures, the Energy Star rating will increase. However, the EPA does not have score for all types of buildings. The buildings that do not have energy rating now are compared with national median EUI. The site EUI is the amount of heat and electricity consumed by a building as reflected in utility bills. Site energy may be delivered to a facility in the form of primary energy, which is raw fuel burned to create heat or electricity, such as natural gas or oil; or as secondary energy, which is the product created from a raw fuel such as electricity or district steam. To provide an equitable comparison for different buildings with varying proportions of primary and secondary energy consumption, Portfolio Manager uses the convention of source EUIs. The source energy also accounts for losses incurred in production, storage, transmission, and delivery of energy to the site, which provide an equivalent measure for various types of buildings with differing energy sources. The results of the benchmarking are contained in the table below.
Site EUI kBtu/ft2/yr Source EUI (kBtu/ft2/yr)
Energy Star Rating (1-100)
130.1 272 30
The building has higher EUIs than the national median EUIs (national median site EUI is 105.1 kBtu/ft2 and national median source EUI is 219.8 kBtu/ft2). It is believed that the higher EUIs is due to the lack of control of the HVAC equipment and lights. By implementing the energy conservation measures in the report, the EUI would be reduced and the Energy Start Rating would be improved.
New Jersey BPU LGEA 12 | P a g e County of Essex - Hall of Records
ENERGY CONSERVATION MEASURES
The following types of energy savings opportunities are identified in this section of the report:
Energy conservation measures (ECMs) are energy savings recommendations that typically require a financial investment. For these areas of opportunity, CHA prepared detailed calculations, as summarized in this section and in Appendix C. In general, additional savings may exist from reductions in maintenance activities associated with new equipment or better controls; however for conservatism, maintenance savings are not accounted for in this report; instead the only savings which are reported are those derived directly from reductions in energy which can be tracked by the utility bills.
Operational and Maintenance measures (O&M) consist of low- or no-cost operational opportunities, which if implemented would have positive impacts on overall building operation, comfort levels, and/or energy usage. There are no estimated savings, costs or paybacks associated with the O&M measures included as part of this study.
Energy savings were quantified in the form of:
electrical usage (kWh=Kilowatt-hour),
electrical demand (kW=kilowatts),
natural gas (therms=100,000 Btu),
propane gas (gallons=91,650 Btu),
fuel oil (gallons =138,700 Btu), and
water (kgal=1,000 gallons). These recommendations are influenced by the time period that it takes for a proposed project to “break even” referred to as “Simple Payback”. Simple payback is calculated by dividing the estimated cost of implementing the ECM by the energy cost savings (in dollars) of that ECM. Another financial indicator of the performance of a particular ECM is the Return on Investment or ROI, which represents the benefit (annual savings over the life of a project) of an investment divided by the cost of the investment. The result is expressed as a percentage or ratio. Two other financial analyses included in this report are Internal Rate of Return (IRR) and Net Present Value (NPV). Internal Rate of Return is the discount rate at which the present value of a project costs equals the present value of the project savings. Net Present Value is the difference between present value of an investment’s future net cash flows and the initial investment. If the NPV equals “0”, the project would equate to investing the same amount of dollars at the desired rate. NPV is sometimes referred to as Net Present Worth. These values are provided in the Summary Tab in Appendix C.
New Jersey BPU LGEA 13 | P a g e County of Essex - Hall of Records
5.1 ECM-1 Reduce the Steam Pressure from 120 Psig to 100 Psig
Currently, the steam boilers are operating at 120 psig and the pressure is regulated down to 50 psig to distribute to the buildings that are using steam. Then the steam pressure is reduced to the suitable range for the steam end users. Based on the discussions with the boiler operators, it was noted that the steam pressure does not need to be at 120 psig and 50 psig is sufficient to transport the steam to the buildings. It is a waste of energy to produce higher pressure steam and regulate it down by using pressure regulating valves. This measure looks at the energy savings from reducing the steam pressure from 120 psig down to 100 psig based on the existing steam pressure relief valve and the existing steam system requirements. The energy savings calculations are based on the enthalpy difference from the steam table, heating hours and the boiler nameplate data. It should be noted that a comprehensive steam system study should be performed to ensure the steam piping, pressure relief valves and accessories work fine with 100 psig. The implementation cost and savings related to this ECM are presented in Appendix C and summarized below:
ECM-1 Reduce the Steam Pressure from 120 Psig to 100 Psig
Budgetary Cost
Annual Utility Savings ROI
Potential Incentive*
Payback (without
incentive)
Payback (with
incentive) Electricity Natural Gas Total
$ kW kWh Therms $ $ Years Years
60,846 0 0 8,310 6,490 1.7 0 9.4 9.4
* Does not qualify for Incentive from the New Jersey SmartStart Program. See section 6.0 for other incentive opportunities This measure is recommended.
5.2 ECM-2 Replace Old RTUs with High Efficiency RTUs
The three HVAC roof top units (RTU) serving the Annex contain DX cooling and steam heating. Each RTU is mounted on an extended curb. Supply and return ductwork is routed down through the roof curbs to a duct distribution system above the ceilings to each space. The capacities are received from the manufacturer based on the nameplate model and serial number. It appears that these units are not high efficiency cooling units. It is recommended that the RTUs be replaced with RTUs equipped with high efficiency direct expansion (DX) cooling units. This ECM assesses the replacement of each size of RTU and gives the resulting energy savings. The assumption of this calculation is that the operating hours, number of units, and capacity stays the same. The energy savings result from operating higher efficiency units than the existing. The implementation cost and savings related to this ECM are presented in Appendix C and summarized below:
New Jersey BPU LGEA 14 | P a g e County of Essex - Hall of Records
ECM-2 Replace Old RTUs with High Efficiency RTUs
Budgetary Cost
Annual Utility Savings ROI
Potential Incentive*
Payback (without
incentive)
Payback (with
incentive) Electricity Natural Gas Total
$ kW kWh Therms $ $ Years Years
79,800 5 8,617 0 1,464 (0.7) 2,925 54.5 52.5
* Incentive shown is per the New Jersey SmartStart Program. See section 6.0 for other incentive opportunities. This measure is recommended since the overall payback with other measures is favorable.
5.3 ECM-3 Install Window AC Units Control System
There are approximately a hundred and ten (110) window air conditioners located throughout the building. This ECM evaluates the installation of programmable “smart” timers that interrupt the electrical supply to the window air conditioners when cooling is not needed due to the room being unoccupied. The timers are configurable to operate as a standalone timer or they can be wirelessly interconnected to provide remote temperature control using software. The implementation cost and savings related to this ECM are presented in Appendix C and summarized below:
ECM-3 Install Window AC Units Control System
Budgetary Cost
Annual Utility Savings ROI
Potential Incentive*
Payback (without
incentive)
Payback (with
incentive) Electricity Natural Gas Total
$ kW kWh Therms $ $ Years Years
21,200 0 56,150 0 8,479 5.0 0 2.5 2.5
* Does not qualify for Incentive from the New Jersey SmartStart Program. See section 6.0 for other incentive opportunities This measure is recommended.
5.4 ECM-4 Install a Central Web-Based DDC System to Control the HVAC Equipment
This building does not have a central direct digital control (DDC) system. The RTUs and heating system are controlled by thermostats located in rooms. These thermostats are manually controlled and do not have automatic temperature setback feature. A Full Direct Digital Control (DDC) building automation system consists of automatic control of individual space heating and ventilation equipment, and provides monitoring, trending and alarms which notify an operator when a piece of equipment fails or operates outside a given set-point. This system allows for the implementation of energy efficient strategies, such as: time of day (TOD) optimization, set point optimization, staggered start, night setback, economizer (free cooling), demand control ventilation,
New Jersey BPU LGEA 15 | P a g e County of Essex - Hall of Records
exhaust fan TOD optimization, and holiday TOD optimization. It also allows for remote access and control of the building’s systems. Energy savings are seen from temperature reduction during the day and night as well as other controls sequences mentioned above. The implementation cost and savings related to this ECM are presented in Appendix C and summarized below:
ECM-4 Install a Central Web-Based DDC System to Control the HVAC Equipment
Budgetary Cost
Annual Utility Savings ROI
Potential Incentive*
Payback (without
incentive)
Payback (with
incentive) Electricity Natural Gas Total
$ kW kWh Therms $ $ Years Years
305,175 0 26,000 5,457 8,188 (0.6) 0 37.3 37.3
Does not qualify for Incentive from the New Jersey SmartStart Program. See section 6.0 for other incentive opportunities This measure is recommended since the overall payback with other measures is favorable.
5.5 ECM-5 Replace Domestic Hot Water Heaters with Condensing DHW Heaters
The Annex mechanical room has two A.O smith PVI DHW heaters which supply hot water for the kitchen in the Annex and the sinks for Hall of Records /Annex. These two heaters are not high efficiency condensing water heaters, therefore, an ECM associated with replacing the DHW heaters with high efficiency gas fired condensing DHW heater is evaluated. Implementation of this ECM will entail replacing the existing DHW heater with a high efficiency condensing water heater. The tank size of the existing system will remain the same. The proposed DHW heaters include one (1) high efficiency condensing heater. The implementation cost and savings related to this ECM are presented in Appendix C and summarized below:
ECM-5 Replace Domestic Hot Water Heaters with Condensing DHW Heaters
Budgetary Cost
Annual Utility Savings ROI
Potential Incentive*
Payback (without
incentive)
Payback (with
incentive) Electricity Natural Gas Total
$ kW kWh Therms $ $ Years Years
24,698 0 0 1,333 1,041 (0.4) 3,000 23.7 20.8
* Incentive shown is per the New Jersey SmartStart Program. See section 6.0 for other incentive opportunities. This measure is recommended since the overall payback with other measures is favorable.
New Jersey BPU LGEA 16 | P a g e County of Essex - Hall of Records
5.6 ECM-6 Install Walk-in Cooler/Freezer Control
There are two walk-in coolers and one freezer in the building. The condensing units of the walk-in coolers and freezers are located on the roof. The walk-in cooler and freezer each has a Russell condensing unit located on the roof and the rated cooling capacity of them is 7,080 BTH. Installing a walk-in cooler control system was assessed. The system will monitor both dry and wet bulb temperature within the walk-in unit and allow evaporators and compressors to modulate up and down based on enthalpy set points rather than by dry bulb temperature alone. Savings is a result of reduced run time of evaporator fans, compressors and door heaters. The implementation cost and savings related to this ECM are presented in Appendix C and summarized as follows:
ECM-6 Install Walk-in Cooler/Freezer Control
Budgetary Cost
Annual Utility Savings ROI
Potential Incentive*
Payback (without
incentive)
Payback (with
incentive) Electricity Natural Gas Total
$ kW kWh Therms $ $ Years Years
20,625 0 9,338 0 1,410 0.0 0 14.6 14.6
* Does not qualify for Incentive from the New Jersey SmartStart Program. See section 6.0 for other incentive opportunities This measure is recommended.
5.7.1 ECM-L1 Lighting Replacement / Upgrades The building has a mixture of some 32W T-8 fluorescent lighting and incandescent lights in chandeliers. The majority of lighting fixtures are spot lights and incandescent lights. Recent technological improvements in light emitting diode (LED) technologies have driven down the initial costs making it a viable option for installation. Overall energy consumption can be reduced by replacing inefficient bulbs and linear fluorescent bulbs with more efficient LED technology. To compute the annual savings for this ECM, the energy consumption of the current lighting fixtures was established and compared to the proposed fixture power requirement with the same annual hours of operation. The difference between the existing and proposed annual energy consumption was the energy savings. These calculations are based on 1 to 1 replacements of the fixtures, and do not take into account lumen output requirements for a given space. However, this building is a historic building and has specific request on the lighting output and distribution. Therefore, a photometric study of the lighting system and a more comprehensive engineering study should be performed to determine the feasibility of replacing existing lights. Supporting calculations, including assumptions for lighting hours and annual energy usage for each fixture, are provided in Appendix C and summarized below:
New Jersey BPU LGEA 17 | P a g e County of Essex - Hall of Records
ECM-L1 Lighting Replacement / Upgrades
Budgetary Cost
Annual Utility Savings ROI
Potential Incentive*
Payback (without
incentive)
Payback (with
incentive) Electricity Natural Gas Total
$ kW kWh Therms $ $ Years Years
504,915 175 476,300 0 76,053 1.4 97,405 6.6 5.4
* LED retrofits must go through the “custom” measures incentive option under New Jersey SmartStart Program. There are no “prescriptive” incentives for LED retrofits. Projects must achieve a minimum of 75,000 kWh annual savings to qualify for “custom” incentives. See section 6.0 for other incentive opportunities This measure is not recommended in lieu of ECM L3.
5.7.2 ECM-L2 Install Lighting Controls (Occupancy Sensors) Presently, most of the interior lighting fixtures are controlled by wall mounted switches. Review of the comprehensive lighting survey determined that lighting in some areas could benefit from installation of occupancy sensors to turn off lights when they are unoccupied.
This measure recommends installing occupancy sensors for the current lighting system. Using a process similar to that utilized in Section ECM-L1, the energy savings for this measure was calculated by applying the known fixture wattages in the space to the estimated existing and proposed times of operation for each fixture. The implementation cost and savings related to this ECM are presented in Appendix C and summarized below:
ECM-L2 Install Lighting Controls (Occupancy Sensors)
Budgetary Cost
Annual Utility Savings ROI
Potential Incentive*
Payback (without
incentive)
Payback (with
incentive) Electricity Natural Gas Total
$ kW kWh Therms $ $ Years Years
85,860 0 100,569 0 14,381 1.7 11,130 6.0 5.2
* Incentive shown is per the New Jersey SmartStart Program. See section 6.0 for other incentive opportunities. This measure is not recommended in lieu of ECM L3.
5.7.3 ECM-L3 Lighting Replacements with Controls (Occupancy Sensors)
This measure is a combination of ECM-L1 and ECM-L2; recommending replace/upgrade the current lighting fixtures to more efficient ones and installing occupancy sensors on the new lights. Interactive effects of the higher efficiency lights and occupancy sensors lead the energy and cost savings for this measure to not be cumulative or equivalent to the sum of replacing the lighting fixtures alone and installing occupancy sensors without the lighting upgrade. The implementation cost and savings related to this ECM are presented in Appendix C and summarized below:
New Jersey BPU LGEA 18 | P a g e County of Essex - Hall of Records
ECM-L3 Lighting Replacements with Controls (Occupancy Sensors)
Budgetary Cost
Annual Utility Savings ROI
Potential Incentive*
Payback (without
incentive)
Payback (with
incentive) Electricity Natural Gas Total
$ kW kWh Therms $ $ Years Years
590,775 175 511,129 0 81,034 1.2 108,535 7.3 6.0
* LED retrofits must go through the “custom” measures incentive option under New Jersey SmartStart Program. There are no “prescriptive” incentives for LED retrofits. Projects must achieve a minimum of 75,000 kWh annual savings to qualify for “custom” incentives. See section 6.0 for other incentive opportunities This measure is recommended.
5.8 Additional O&M Opportunities This list of operations and maintenance (O&M) - type measures represent low-cost or no-cost opportunities, which if implemented will have a positive impact on the overall building operations, comfort and/or energy consumption. The recommended O&M measures for this building are as follows:
Install window AC unit covers during winter season
Develop an Energy Master Plan to measure and track energy performance
Perform steam trap survey
Check and repair window seals regularly
New Jersey BPU LGEA 19 | P a g e County of Essex - Hall of Records
PROJECT INCENTIVES
6.1 Incentives Overview
The following sections give detailed information on available incentive programs including New Jersey Smart Start, Direct Install, New Jersey Pay for Performance (P4P) and Energy Savings Improvement Plan (ESIP). If Essex County wishes to and is eligible to participate in the Energy Savings Improvement Plan (ESIP) program and/or the Pay for Performance Incentive Program (P4P), it cannot participate in either the Smart Start or Direct Install Programs. Refer to Appendix D for more information on the Smart Start program.
6.1.1 New Jersey Smart Start Program For this energy audit, The New Jersey Smart Start Incentives are used in the energy savings calculations, where applicable. This program is intended for medium and large energy users and provides incentives for:
Electric Chillers
Gas Chillers
Gas Heating
Unitary HVAC
Ground Source Heat Pumps
Variable frequency Drives/ motors
Refrigeration
Prescriptive and performance lighting and lighting controls The equipment is procured using a typical bid- build method, installed and paid for and then the incentives are reimbursed to the owner. Refer to Appendix D for more information on the Smart Start program.
6.1.2 Direct Install Program The Direct Install Program applies to smaller facilities that have a peak electrical demand of 200 kW or less in any of the previous 12 months. Buildings must be located in New Jersey and served by one of the state’s public, regulated electric utility companies. Direct Install is funded through New Jersey’s Clean Energy Program and is designed to provide capital for building energy upgrade projects to fast track implementation. The program will pay up to 70% of the costs for lighting, HVAC, motors, refrigeration, and other equipment upgrades with higher efficiency alternatives. If a building is eligible for this funding, the Direct Install Program can reduce the implementation cost of energy conservation projects. The Direct Install program has specific HVAC equipment and lighting requirements and is generally applicable only to smaller package HVAC units, small boilers and lighting retrofits.
New Jersey BPU LGEA 20 | P a g e County of Essex - Hall of Records
The program pays a maximum amount of $75,000 per building, and up to $250,000 per customer per year. Installations must be completed by an approved Direct Install participating contractor, a list of which can be found on the New Jersey Clean Energy Website. Contractors will coordinate with the applicant to arrange installation of recommended measures identified in a previous energy assessment, such as this energy audit. The incentive is reimbursed to the Owner upon successful replacement and payment of the equipment. The building does not qualify for this program because its electrical demand is more than the maximum peak electrical demand of 200 kW for the last 12 month period. Refer to Appendix D for more information on this program.
6.1.3 New Jersey Pay For Performance Program (P4P) This building may be eligible for incentives from the New Jersey Office of Clean Energy. The most significant incentives are available from the New Jersey Pay for Performance (P4P) Program. The P4P program is designed to offset the cost of energy conservation projects for facilities that pay the Societal Benefits Charge (SBC) and whose demand (kW) in any of the preceding 12 months exceeds 100 kW. This demand minimum has been waived for buildings owned by local governments or municipalities and non-profit organizations and is not applicable to public schools. Facilities that meet this criterion must also achieve a minimum performance target of 15% energy reduction by using the EPA Portfolio Manager benchmarking tool before and after implementation of the measure(s). Additionally, the overall return on investment (ROI) must exceed 10%. If the participant is a municipal electric company customer, and a customer of a regulated gas New Jersey Utility, only gas measures will be eligible under the Program. Available incentives are as follows: Incentive #1: Energy Reduction Plan – This incentive is designed to offset the cost of services associated with the development of the Energy Reduction Plan (ERP). The ERP must include a detailed energy audit of the desired ECMs, energy savings calculations (using building modeling software) and inputting of all utility bills into the EPA Portfolio Manager website.
Incentive Amount: $0.10/SF
Minimum incentive: $5,000
Maximum Incentive: $50,000 or 50% of Facility annual energy cost The standard incentive pays $0.10 per square foot, up to a maximum of $50,000, not to exceed 50% of facility annual energy cost, paid after approval of application. For building audits funded by the New Jersey Board of Public Utilities, which receive an initial 75% incentive toward performance of the energy audit, facilities are only eligible for an additional $0.05 per square foot, up to a maximum of $25,000, rather than the standard incentive noted above. The ERP must be completed by a Certified Energy Manager (CEM) and submitted along with the project application. Incentive #2: Installation of Recommended Measures – This incentive is based on projected energy savings as determined in Incentive #1 (Minimum 15% savings must be achieved), and is paid upon successful installation of recommended measures. Electric
New Jersey BPU LGEA 21 | P a g e County of Essex - Hall of Records
Base incentive based on 15% savings: $0.09/ per projected kWh saved.
For each % over 15% add: $0.005 per projected kWh saved.
Maximum incentive: $0.11/ kWh per projected kWh saved. Gas
Base incentive based on 15% savings: $0.90/ per projected Therm saved.
For each % over 15% add: $0.05 per projected Therm saved.
Maximum incentive: $1.25 per projected Therm saved. Incentive cap: 25% of total project cost Incentive #3: Post-Construction Benchmarking Report – This incentive is paid after acceptance of a report proving energy savings over one year utilizing the Environmental Protection Agency (EPA) Portfolio Manager benchmarking tool. Electric
Base incentive based on 15% savings: $0.09/ per projected kWh saved.
For each % over 15% add: $0.005 per projected kWh saved.
Maximum incentive: $0.11/ kWh per projected kWh saved.
Gas
Base incentive based on 15% savings: $0.90/ per projected Therm saved.
For each % over 15% add: $0.05 per projected Therm saved.
Maximum incentive: $1.25 per projected Therm saved. Combining Incentives #2 and #3 will provide a total of $0.18/ kWh and $1.8/therm not to exceed 50% of total project cost. Additional Incentives for #2 and #3 are increased by $0.005/kWh and $0.05/therm for each percentage increase above the 15% minimum target to 20%, calculated with the EPA Portfolio Manager benchmarking tool, not to exceed 50% of total project cost. For the purpose of demonstrating the eligibility of the ECM’s to meet the minimum savings requirement of 15% annual savings and 10% ROI for the Pay for Performance Program, all ECM’s identified in this report have been included in the incentive calculations. The results for the building are shown in Appendix C, with more detailed program information in Appendix D.
6.1.4 Energy Savings Improvement Plan The Energy Savings Improvement Program (ESIP) allows government agencies to make energy related improvements to their facilities and pay for the costs using the value of energy savings that result from the improvements. Under the recently enacted Chapter 4 of the Laws of 2009 (the law), the ESIP provides all government agencies in New Jersey with a flexible tool to improve and reduce energy usage with minimal expenditure of new financial resources. ESIP allows local units to use “energy savings obligations” (ESO) to pay for the capital costs of energy improvements to their facilities. ESIP loans have a maximum loan term of 15 year. ESOs are not considered “new general obligation debt” of a local unit and do not count against debt limits or require voter approval. They may be issued as refunding bonds or leases. Savings generated from the installation of energy conservation
New Jersey BPU LGEA 22 | P a g e County of Essex - Hall of Records
measures pay the principal of and interest on the bonds; for that reason, the debt service created by the ESOs is not paid from the debt service fund, but is paid from the general fund. For local governments interested in pursuing an ESIP, the first step is to perform an energy audit. Pursuing a Local Government Energy Audit through New Jersey's Clean Energy Program is a valuable first step to the ESIP approach. The “Local Finance Notice” outlines how local governments can develop and implement an ESIP for their facilities. The ESIP can be prepared internally if the entity has qualified staff. If not, the ESIP must be implemented by an independent contractor and not by the energy savings company producing the Energy Reduction Plan. The ESIP approach may not be appropriate for all energy conservation and energy efficiency improvements. Local units should carefully consider all alternatives to develop an approach that best meets their needs. Refer to Appendix D for more information on this program.
6.1.5 Renewable Energy Incentive Program The Renewable Energy Incentive Program (REIP) is part of New Jersey's efforts to reach its Energy Master Plan goals of striving to use 30 percent of electricity from renewable sources by 2020. Incentives for sustainable bio-power projects and for energy storage projects are currently under development, with competitive solicitations for each of those technologies expected to begin in the first quarter of 2014. The wind program is currently on hold. New solar projects are no longer eligible for REIP incentives, but can register for Solar Renewable Energy Certificates (SRECs) through the SREC Registration Program (SRP).
New Jersey BPU LGEA 23 | P a g e County of Essex - Hall of Records
ALTERNATIVE ENERGY SCREENING EVALUATION
7.1 Solar
7.1.1 Photovoltaic Rooftop Solar Power Generation
The building was evaluated for the potential to install rooftop photovoltaic (PV) solar panels for power generation. Present technology incorporates the use of solar cell arrays that produce direct current (DC) electricity. This DC current is converted to alternating current (AC) with the use of an electrical device known as an inverter. The amount of available roof area determines how large of a solar array can be installed on any given roof. The table below summarizes the approximate roof area available on the building and the associated solar array size that can be installed.
Available Roof Area
Potential PV Array Size
(Ft2) (kW)
28,069 80
The PVWATTS solar power generation model was utilized to calculate PV power generation; this model is provided in Appendix E. Installation of (PV) arrays in the state New Jersey will allow the owner to participate in the New Jersey Solar Renewable Energy Certificates Program (SREC). This is a program that has been set up to allow entities with large amounts of environmentally unfriendly emissions to purchase credits from zero emission (PV) solar-producers. An alternative compliance penalty (ACP) is paid for by the high emission producers and is set each year on a declining scale of 3% per year. One SREC credit is equivalent to 1000 kilowatt hours of PV electrical production; these credits can be traded for period of 15 years from the date of installation. Payments that will be received by the PV producer will change from year to year dependent upon supply and demand. There is no definitive way to calculate an exact price that will be received by the PV producer for SREC credits over the next 15 years. Renewable Energy Consultants estimates an average of $170/SREC for 2014 and this number was utilized in the cash flow for this report. The system costs for PV installations were derived from recent solar contractor budgetary pricing in the state of New Jersey and include the total cost of the system installation (PV panels, inverters, wiring, ballast, controls). The cost of installation is currently about $4.00 per watt or $4,000 per kW of installed system, for a typical system. There are other considerations that have not been included in this pricing, such as the condition of the roof and need for structural reinforcement. Photovoltaic systems can be ground mounted if the roof is not suitable, however, this installation requires a substantial amount of open property (not wooded) and underground wiring, which adds more cost. PV panels have an approximate 20 year life span; however, the inverter device that converts DC electricity to AC has a life span of 10 to 12 years and will most likely need to be replaced during the useful life of the PV system. The implementation cost and savings related to this ECM are presented in Appendix E and summarized as follows:
New Jersey BPU LGEA 24 | P a g e County of Essex - Hall of Records
Photovoltaic (PV) Rooftop Solar Power Generation – 80 kW System
Budgetary Cost
Annual Utility Savings Total
Savings
New Jersey
Renewable SREC
Payback (without SREC)
Payback (with SREC)
Recom
mended
Electricity Natural Gas
$ kW kWh Therms $ $ Years Years Y/N
$320,000 80.0 105,940 0 $15,987 $18,010 20.0 9.4 FS
Note: CHA typically recommends a more detailed evaluation be conducted for the installation of PV Solar arrays when the screening evaluation shows a payback of less than 20 years. Therefore, this ECM is recommended for further study. Before implementation is pursued, the county should consult with a certified solar PV contractor.
7.1.2 Solar Thermal Hot Water Generation Active solar thermal systems use solar collectors to gather the sun’s energy to heat a fluid. An absorber in the collector (usually black colored piping) converts the sun’s energy into heat. The heat is transferred to circulating water, antifreeze, or air for immediate use or is storage for later utilization. Applications for active solar thermal energy include supplementing domestic hot water, heating swimming pools, space heating or preheating air in residential and commercial buildings. A standard solar hot water system is typically composed of solar collectors, heat storage vessel, piping, circulators, and controls. Systems are typically integrated to work alongside a conventional heating system that provides heat when solar resources are not sufficient. The solar collectors are usually placed on the roof of the building, oriented south, and tilted at the same angle as the site’s latitude, to maximize the amount of solar radiation collected on a yearly basis. Several options exist for using active solar thermal systems for space heating. The most common method is called a passive solar hot water system involves using glazed collectors to heat a liquid held in a storage tank (similar to an active solar hot water system described above which requires pumping). The most practical system would transfer the heat from the panels to thermal storage tanks and then use the pre-heated water for domestic hot water production. DHW is presently produced by natural gas fired water heaters and, therefore, this measure would offer natural gas utility savings. Unfortunately, the amount of domestic hot water that is currently used by this building is very small. Installing a solar domestic hot water system is not recommended due to the limited amount of domestic hot water presently consumed by the building. This measure is not recommended due to the relatively low domestic hot water usage.
7.2 Wind Powered Turbines Wind power is the conversion of kinetic energy from wind into mechanical power that is used to drive a generator which creates electricity by means of a wind turbine. A wind turbine consists of rotor and blades connected to a gearbox and generator that are mounted onto a tower. Newer wind turbines also use advanced technology to generate
New Jersey BPU LGEA 25 | P a g e County of Essex - Hall of Records
electricity at a variety of frequencies depending on the wind speed, convert it to DC and then back to AC before sending it to the grid. Wind turbines range from 50 – 750 kW for utility scale turbines down to below 50 kW for residential use. On a scale of 1 (the lowest) to 7 (the highest), Class 3 and above (wind speeds of 13 mph or greater) are generally considered “good wind resource” according to the Wind Energy Development Programmatic EIS Information Center hosted by the Bureau of Land Management. According to the map below, published by NREL, Newark, NJ is classified as Class 1 at 50m, meaning the city would not be a good candidate for wind power.
This measure is not recommended due to the location of the building.
7.3 Combined Heat and Power Plant
Combined heat and power (CHP), cogeneration, is self-production of electricity on-site with beneficial recovery of the heat byproduct from the electrical generator. Common CHP equipment includes reciprocating engine-driven, micro turbines, steam turbines, and fuel cells. Typical CHP customers include industrial, commercial, institutional, educational institutions, and multifamily residential facilities. CHP systems that are commercially viable at the present time are sized approximately 50 kW and above, with numerous options in blocks grouped around 300 kW, 800 kW, 1,200 kW and larger. Typically, CHP systems are used to produce a portion of the electricity needed by a facility some or all of the time, with the balance of electric needs satisfied by purchase from the grid.
Any proposed CHP project will need to consider many factors, such as existing system load, use of thermal energy produced, system size, natural gas fuel availability, and proposed plant location. The building has sufficient need for electrical generation and the ability to use most of the thermal byproduct during the winter and the summer. An absorption chiller could be installed to utilize the heat to produce chilled water. The most viable selection for a CHP plant at this location would be a reciprocating engine natural
New Jersey BPU LGEA 26 | P a g e County of Essex - Hall of Records
gas-fired unit. Purchasing this system and performing modifications to the existing HVAC and electrical systems would greatly outweigh the savings over the life of the equipment.
The CHP screening analysis was conducted utilizing the characteristics of the site before any of the ECMs described above are implemented. If any of the ECMs are implemented, the feasibility of installing a CHP system is reduced and the payback would likely be slightly extended.
Combined Heat and Power (CHP) – 1,000kW
Budgetary Cost
Annual Utility Usage Total
Savings
New Jersey
Incentive
Payback (without
Incentive)
Payback (with
Incentive)
Recom
mended
Existing Utility
Cost
CHP Operating
Cost
$ $ $ $ $ Years Years Y/N
4,560,000 640,450 298,531 341,919 550,000 13.3 11.7 FS
This measure recommended for further study—see details Appendix E.
Although NJBPU LGEA program offers potential incentive for this measure as outlined above, the exact value must be determined by NJBPU. The savings outlined are evaluated at a screening level and should be refined during the design phase. It is recommended that Essex County pursue a more detailed CHP feasibility study to provide a more accurate depiction of the proposed CHP system to allow for application for incentives. The energy savings and implementation costs for this analysis have not been included in the project totals.
7.4 Demand Response Curtailment Presently, electricity is delivered by PSE&G, which receives the electricity from regional power grid RFC. PSE&G is the regional transmission organization (RTO) that coordinates the movement of wholesale electricity in all or parts of 13 states and the District of Columbia including the State of New Jersey. Utility Curtailment is an agreement with the utility provider’s regional transmission organization and an approved Curtailment Service Provider (CSP) to shed electrical load by either turning major equipment off or energizing all or part of a facility utilizing an emergency generator; therefore, reducing the electrical demand on the utility grid. This program is to benefit the utility company during high demand periods and utility provider offers incentives to the CSP to participate in this program. Enrolling in the program will require program participants to drop electrical load or turn on emergency generators during high electrical demand conditions or during emergencies. Part of the program also will require that program participants reduce their required load or run emergency generators with notice to test the system.
New Jersey BPU LGEA 27 | P a g e County of Essex - Hall of Records
A pre-approved CSP will require a minimum of 100 kW of load reduction to participate in any curtailment program. From February 2013 through January 2014 the following table summarizes the electricity load profile for the building.
Building Electric Load Profile
Peak Demand kW
Min Demand kW
Avg Demand kW
Onsite Generation
Y/N Eligible?
Y/N
902.6 576.9 744.6 N Y
*the demand is estimated from one month bill
This measure is not recommended due to the lack of onsite power generators.
New Jersey BPU LGEA 28 | P a g e County of Essex - Hall of Records
CONCLUSIONS & RECOMMENDATIONS
The following section summarizes the LGEA energy audit conducted by CHA for the Essex County. The following projects should be considered for implementation:
Reduce the Steam Pressure from 120 Psig to 100 Psig
Replace Old RTUs with High Efficiency RTUs
Install Window AC Units Control System
Install a Central Web-Based DDC System to Control the HVAC Equipment
Replace Domestic Hot Water Heaters with Condensing DHW Heater
Install Walk-in Cooler/Freezer Control
Lighting Replacements with Controls (Occupancy Sensors)
The potential annual energy and cost savings for the recommended ECMs are shown in the following table.
Electric Savings (kWh)
Natural Gas Savings (therms)
Total Savings ($)
Payback (years)
611,234 15,100 108,106 10.2
If the county implements the recommended ECMs, energy savings would be as follows:
Existing
Conditions
Post Recommended
ECMs Percent Savings
Costs ($) 745,060 636,954 15%
Electricity (kWh) 3,680,750 3,069,516 17%
Natural Gas (therms) 280,832 265,732 5%
Site EUI (kbtu/SF/Yr) 197.6 180.1
New Jersey BPU LGEA 29 | P a g e County of Essex - Hall of Records
Next Steps: This energy audit has identified several areas of potential energy savings. Essex County can use this information to pursue incentives offered by the NJBPU's NJ Clean Energy Program. Additional meetings will be scheduled with EC staff members to review possible options.
Existing Conditions Post RecommnededECMs
0
500,000
1,000,000
1,500,000
2,000,000
2,500,000
3,000,000
3,500,000
4,000,000
Costs ($)
Electricity (kWh)
Natural Gas (therms)
APPENDIX A
Utility Usage Analysis and Alternate Utility Suppliers
Essex County Hall of Records Electric Usage
Annual Utilities12-month Summary
Annual Usage 3,595,777 kWh/yrAnnual Cost 542,633 $Blended Rate 0.151 $/kWhConsumption Rate 0.143 $/kWhDemand Rate 3.79 $/kWPeak Demand 881.8 kWMin. Demand 563.6 kWAvg. Demand 727.4 kW
Annual Usage 144,882 therms/yrAnnual Cost 97,817 $Rate 0.675 $/therm
Electric
Natural Gas
Essex County Hall of Records
Utility Bills: Account Numbers
Account Number Building Name Location Type Notes4206450706 Hall of Records 465 Dr. Martin Luther King Blvd, Newark, NJ, 07102 Electricity4215701600 Hall of Records 466 Dr. Martin Luther King Blvd, Newark, NJ, 07102 Natural Gas4206450706 Hall of Records 467 Dr. Martin Luther King Blvd, Newark, NJ, 07102 Natural Gas
Copy of Hall of Records Utility Data Rev1.xlsxElectric
Essex County Hall of Records Electric Usage
For Service at:Account No.: 4206450706 Delivery - PSE&GMeter No.: 778015129 Supplier - N/AElectric Service
Consumption Demand Delivery Supplier Total Consumption Demand Blended Rate Consumption DemandMonth (kWh) (kW) ($) ($) ($) ($) ($) ($/kWh) ($/kWh) ($/kW)February-13 263,833 567 9,907.36 27,702.49 37,609.85 35,600.65 2,009.20 0.14 0.13 3.54March-13 271,064 572 9,823.34 28,461.67 38,285.01 36,257.30 2,027.72 0.14 0.13 3.54April-13 281,981 671 10,482.96 29,607.98 40,090.94 37,712.80 2,378.14 0.14 0.13 3.54May-13 267,977 647 10,000.60 28,137.54 38,138.15 35,845.73 2,292.42 0.14 0.13 3.54June-13 315,396 750 18,322.63 33,116.55 51,439.18 48,779.62 2,659.56 0.16 0.15 3.54July-13 379,343 870 22,044.63 39,831.06 61,875.69 58,792.20 3,083.48 0.16 0.15 3.54August-13 352,979 882 21,386.68 37,062.77 58,449.45 55,324.00 3,125.45 0.17 0.16 3.54September-13 345,456 836 20,604.55 36,272.90 56,877.45 53,915.94 2,961.51 0.16 0.16 3.54October-13 292,860 690 11,458.26 30,750.27 42,208.53 39,764.08 2,444.46 0.14 0.14 3.54November-13 245,362 652 9,645.85 25,762.99 35,408.84 33,134.05 2,274.79 0.14 0.14 3.49December-13 289,797 564 10,620.21 30,428.73 41,048.94 39,083.87 1,965.07 0.14 0.13 3.49January-14 289,730 576 10,779.08 30,421.62 41,200.70 39,178.13 2,022.57 0.14 0.14 3.51Total (All) 3,595,777 881.80 $165,076.15 $377,556.57 $542,632.73 $513,388.36 $29,244.37 $0.151 $0.143 $3.53Total (12 Months) 3,595,777 881.80 $165,076.15 $377,556.57 $542,632.73 $513,388.36 $29,244.37 $0.151 $0.143 $3.79
Notes 1 2 3 4 5 6 7 8 9 101.) Number of kWh of electric energy used per month2.) Number of kW of power measured3.) Electric charges from Delivery provider4.) Electric charges from Supply provider5.) Total charges (Delivery + Supplier)6.) Charges based on the number of kWh of electric energy used $0.105 /kWh Estimated supply rate due to missing data7.) Charges based on the number of kW of power measured8.) Total Charges ($) / Consumption (kWh)9.) Consumption Charges ($) / Consumption (kWh)
10.) Demand Charges ($) / Demand (kW)
Provider Charges Unit CostsUsage (kWh) vs. Demand (kW) Charges
Copy of Hall of Records Utility Data Rev1.xlsxElectric Graph
0
100
200
300
400
500
600
700
800
900
1,000
0
50,000
100,000
150,000
200,000
250,000
300,000
350,000
400,000
Feb-
13
Mar
-13
Apr
-13
May
-13
Jun-
13
Jul-1
3
Aug
-13
Sep
-13
Oct
-13
Nov
-13
Dec
-13
Jan-
14
Dem
and
(kW
)
Usa
ge (k
Wh)
Month
Hall of Records Electric Usage
(kWh) (kW)
Essex County Hall of Records Gas Usage
For Service at:Account No.: 4215701600 4206450706Meter No: 3499595Natural Gas Service Delivery - PSE&G
Supplier - HESS
Consumption Delivery Supply Total Delivery Supply Total(Therms) ($) ($) ($) ($/Therm) ($/Therm) ($/Therm)
February-13 27,508 4,145 14,359 18,504.33$ 0.151$ 0.522$ 0.673$ March-13 24,993 3,747 13,046 16,793.10$ 0.150$ 0.522$ 0.672$ April-13 8,370 1,389 4,369 5,758.03$ 0.166$ 0.522$ 0.688$ May-13 267 240 139 379.39$ 0.899$ 0.522$ 1.421$ June-13 292 244 152 396.60$ 0.836$ 0.522$ 1.358$ July-13 373 254 195 448.42$ 0.681$ 0.522$ 1.203$ August-13 381 255 199 453.75$ 0.668$ 0.522$ 1.190$ September-13 240 235 125 359.72$ 0.979$ 0.522$ 1.501$ October-13 3,443 683 1,797 2,480.06$ 0.198$ 0.522$ 0.720$ November-13 21,821 3,057 11,391 14,448.09$ 0.140$ 0.522$ 0.662$ December-13 26,118 3,637 13,634 17,270.41$ 0.139$ 0.522$ 0.661$ January-14 31,077 4,304 16,222 20,525.54$ 0.138$ 0.522$ 0.660$ Total (All) 144,882.06 97,817.45 0.675$ Total (12 Months) 144,882.06 97,817.45 0.675$
Charges Unit Costs
Month
0
5,000
10,000
15,000
20,000
25,000
30,000
35,000
$-
$5,000.00
$10,000.00
$15,000.00
$20,000.00
$25,000.00
Cons
umpt
ion
(The
rms)
Tota
l ($)
Hall of Records Gas Usage
Total ($) Consumption (Therms)
PSE&G GAS SERVICE TERRITORY
Last Updated: 12/11/14
*CUSTOMER CLASS - R – RESIDENTIAL C – COMMERCIAL I - INDUSTRIAL
Supplier Telephone & Web Site
*CustomerClass
Ambit Northeast, LLC d/b/a Ambit Energy 103 Carnegie Center Suite 300 Princeton, NJ 08540
877-282-6284
www.ambitenergy.com
R/C
ACTIVE
Amerigreen Energy, Inc. 333 Sylvan Avenue Suite 206 Englewood Cliffs, NJ 07632
(888)559-4567
www.amerigreen.com
R/C/I
ACTIVE
Astral Energy LLC 16 Tyson Place Bergenfield, NJ 07621
888-850-1872
www.AstralEnergyLLC.com
R/C/I
ACTIVE
BBPC, LLC Great Eastern Energy 116 Village Blvd. Suite 200 Princeton, NJ 08540
888-651-4121
www.greateasternenergy.com
C
ACTIVE
Choice Energy, LLC 4257 US Highway 9, Suite 6C Freehold, NJ 07728
(888) 565-4490
www.4choiceenergy.com
R/C/I
Clearview Electric Inc. d/b/a Clearview Gas 1744 Lexington Ave. Pennsauken, NJ 08110
800-746-4720
www.clearviewenergy.com
R/C
ACTIVE
Colonial Energy, Inc. 83 Harding Road Wyckoff, NJ 07481
845-429-3229
www.colonialgroupinc.com
C/I
ACTIVE
Commerce Energy, Inc. 7 Cedar Terrace Ramsey, NJ 07746
888 817-8572
www.commerceenergy.com
R
ACTIVE
Compass Energy Services, Inc.33 Wood Avenue South, 610 Iselin, NJ 08830
866-867-8328
www.compassenergy.net
C/I
ACTIVE
Compass Energy Gas Services, LLC 33 Wood Avenue South Suite 610 Iselin, NJ 08830
866-867-8328
www.compassenergy.net
C/I
ACTIVE
ConocoPhillips Company 224 Strawbridge Drive, Suite 107 Moorestown, NJ 08057
800-646-4427
www.conocophillips.com
C/I
ACTIVE
Consolidated Edison Energy, Inc. d/b/a Con Edison Solutions 535 State Highway 38, Suite 140 Cherry Hill, NJ 08002
888-686-1383 x2130
www.conedenergy.com
Consolidated Edison Solutions, Inc. Cherry Tree Corporate Center 535 State Highway 38, Suite 140 Cherry Hill, NJ 08002
888-665-0955
www.conedsolutions.com
C/I
ACTIVE
Constellation NewEnergy-Gas Division, LLC 116 Village Boulevard, Suite 200 Princeton, NJ 08540
800-785-4373
www.constellation.com
C/I
ACTIVE
Constellation Energy Gas Choice, Inc. 116 Village Blvd., Suite 200 Princeton, NJ 08540
800-785-4373
www.constellation.com
R/C/I
ACTIVE
Direct Energy Business, LLC 120 Wood Avenue, Suite 611 Iselin, NJ 08830
888-925-9115
http://www.business.directenergy.com/
R
ACTIVE
Direct Energy Business Marketing, LLC (fka Hess Energy Marketing) One Hess Plaza Woodbridge, NJ 07095
(800) 437-7872
http://www.business.directenergy.com/
C/I
ACTIVE
Direct Energy Services, LLC 120 Wood Avenue, Suite 611 Iselin, NJ 08830
(888) 925-9115
www.directenergy.com
R
ACTIVE
Direct Energy Small Business, LLC (fka Hess Small Business Services, LLC) One Hess Plaza Woodbridge, NJ 07095
(888) 464-4377
http://www.business.directenergy.com/
C/I
ACTIVE
Gateway Energy Services Corp. 120 Wood Avenue Suite 611 Iselin, NJ 08830
(866) 348-4193
www.gesc.com
R/C
ACTIVE
Glacial Energy of New Jersey, Inc. 21 Pine Street, Suite 237 Rockaway, NJ 07866
888-452-2425
www.glacialenergy.com
C/I
ACTIVE
Global Energy Marketing, LLC 129 Wentz Avenue Springfield, NJ 07081
800-542-0778
www.globalp.com
C/I
ACTIVE
Great Eastern Energy 116 Village Blvd., Suite 200 Princeton, NJ 08540
888-651-4121
www.greateastern.com
C/I
ACTIVE
Greenlight Energy 330 Hudson Street, Suite 4 Hoboken, NJ 07030
718-204-7467
www.greenlightenergy.us
C
ACTIVE
Harborside Energy LLC 101 Hudson Street, Suite 2100 Jersey City, NJ 07302
877-940-3835
www.harborsideenergynj.com
R/C
ACTIVE
Hess Energy, Inc. One Hess Plaza Woodbridge, NJ 07095
800-437-7872
www.hess.com
C/I
ACTIVE
HIKO Energy, LLC 655 Suffern Road Teaneck, NJ 07666
888 264-4908
www.hikoenergy.com
R/C/I
ACTIVE
Hudson Energy Services, LLC7 Cedar Street Ramsey, NJ 07446
877- Hudson 9
www.hudsonenergyservices.com
C
ACTIVE
IDT Energy, Inc. 550 Broad Street Newark, NJ 07102
877-887-6866
www.idtenergy.com
R/C
ACTIVE
Infinite Energy dba Intelligent Energy 1200 Route 22 East Suite 2000 Bridgewater, NJ 08807-2943
(800) 927-9794
www.InfiniteEnergy.com
R/C/I
ACTIVE
Integrys Energy Services-Natural Gas, LLC 101 Eisenhower Parkway Suite 300 Roseland, NJ 07068
(800) 536-0151
www.integrysenergy.com
C/I ACTIVE
Jsynergy LLC 445 Cental Ave. Suite 204 Cedarhurst, NY 11516
(516) 331-2020
www.Jsnergyllc.com
R/C/I
ACTIVE
Major Energy Services, LLC 1001 East Lawn Drive Teaneck NJ 07666
888-625-6760
www.majorenergy.com
R/C/I
ACTIVE
Marathon Power LLC 302 Main Street Paterson, NJ 07505
888-779-7255
www.mecny.com
R/C/I
ACTIVE
Metromedia Energy, Inc. 6 Industrial Way Eatontown, NJ 07724
1-877-750-7046
www.metromediaenergy.com
C/I
ACTIVE
Metro Energy Group, LLC 14 Washington Place Hackensack, NJ 07601
888-53-Metro
www.metroenergy.com
R/C
ACTIVE
MPower Energy NJ LLC One University Plaza, Suite 507 Hackensack, NJ 07601
877-286-7693
www.mpowerenergy.com
R/C/I
ACTIVE
NATGASCO (Supreme Energy, Inc.) 532 Freeman Street Orange, NJ 07050
800-840-4427
www.supremeenergyinc.com
R/C/I
ACTIVE
New Energy Services LLC 101 Neptune Avenue Deal, New Jersey 07723
800-660-3643
www.newenergyservicesllc.com
R/C/I
ACTIVE
New Jersey Gas & Electric 10 North Park Place Suite 420 Morristown, NJ 07960
866-568-0290
www.njgande.com
R/C
ACTIVE
Noble Americas Energy Solutions The Mac-Cali Building 581 Main Street, 8th fl. Woodbridge, NJ 07095
877-273-6772
www.noblesolutions.com
C/I
ACTIVE
North American Power & Gas, LLC d/b/a North American Power 197 Route 18 South Ste. 300 New Brunswick, NJ 08816
888- 313-8086
www.napower.com
R/C/I
ACTIVE
North Eastern States, Inc. d/b/a Entrust Energy 90 Washington Valley Road Bedminster, NJ 07921
(888) 535-6340
www.entrustenergy.com
R/C/I ACTIVE
Oasis Power, LLC d/b/a Oasis Energy 11152 Westheimer, Suite 901 Houston, TX 77042
(800)324-3046 www.oasisenergy.com
R/C ACTIVE
Palmco Energy NJ, LLC One Greentree Centre 10,000 Lincoln Drive East, Suite 201 Marlton, NJ 08053
877-726-5862
www.PalmcoEnergy.com
R/C/I
ACTIVE
Plymouth Rock Energy, LLC 338 Maitland Avenue Teaneck, NJ 07666
855-32-POWER (76937)
www.plymouthenergy.com
R/C/I
ACTIVE
PPL EnergyPlus, LLC Shrewsbury Executive Offices 788 Shrewsbury Avenue Suite 2200 Tinton Falls, NJ 07724
(732) 741-0505
www.pplenergyplus.com
C/I
ACTIVE
PPL EnergyPlus Retail, LLC Shrewsbury Executive Offices 788 Shrewsbury Avenue, Suite 220 Tinton Falls, NJ 07724
(732) 741-0505 – 2000 www.pplenergyplus.com
C/I ACTIVE
Public Power & Utility of New Jersey, LLC One International Blvd, Suite 400 Mahwah, NJ 07495
(888) 354-4415 www.ppandu.com
R/C/I ACTIVE
Residents Energy, LLC 550 Broad Street Newark, NJ 07102
(888) 828-7374 www.residentsenergy.com
R/C
Respond Power LLC 1001 East Lawn Drive Teaneck, NJ 07666
(877) 973-7763
www.respondpower.com
R/C/I
ACTIVE
Save on Energy, LLC 1101 Red Ventures Drive Fort Mill, SC 29707
1 (877) 658-3183
www.saveonenergy.com
R/C ACTIVE
SFE Energy One Gateway Center Suite 2600 Newark, NJ 07012
1 (877) 316-6344
www.sfeenergy.com
R/C/I
ACTIVE
S.J. Energy Partners, Inc. 208 White Horse Pike, Suite 4 Barrington, NJ 08007
(800) 695-0666
www.sjnaturalgas.com
C ACTIVE
South Jersey Energy Company 1 South Jersey Plaza, Route 54 Folsom, NJ 08037
800-266-6020
www.southjerseyenergy.com
R/C/I
ACTIVE
SouthStar Energy d/b/a New Jersey Energy 1085 Morris Avenue, Suite 155 Union, NJ 07083
(866) 477-8823
www.newjerseyenergy.com
R/C ACTIVE
Spark Energy Gas, LP/ Spark Energy 2105 City West Blvd. Suite 100 Houston, TX 77042
(713)600-2600
www.sparkenergy.com
R/C/I ACTIVE
Sperian Energy Corp. Bridgewater Center 1200 Route 22 East Bridgewater, NJ 08807
888-682-8082
www.sperianenergy.com
R/C/I
ACTIVE
Sprague Energy Corp. 12 Ridge Road Chatham Township, NJ 07928
855-466-2842
www.spragueenergy.com
C/I
ACTIVE
Stuyvesant Energy LLC 10 West Ivy Lane, Suite 4 Englewood, NJ 07631
800-640-6457
www.stuyfuel.com
C
ACTIVE
Stream Energy New Jersey, LLC 309 Fellowship Road Suite 200 Mt. Laurel, NJ 08054
(877) 369-8150
www.streamenergy.net
R/C
ACTIVE
Summit Energy Services, Inc. 10350 Ormsby Park Place Suite 400 Louisville, KY 40223
1 (800) 90-SUMMIT
www.summitenergy.com
C/I
ACTIVE
Systrum Energy 1 Bergen Blvd. Fairview, NJ 07022
877-797-8786
www.systrumenergy.com
R/C/I
ACTIVE
Tiger Natural Gas, Inc. dba Tiger, Inc. 234 20th Avenue Brick, NJ 008724
888-875-6122
www.tigernaturalgas.com
R/C/I
ACTIVE
UGI Energy Services, Inc. dba UGI Energy Link 224 Strawbridge Drive, Suite 107 Moorestown, NJ 08057
800-427-8545
www.ugienergylink.com
C/I
ACTIVE
UGI Energy Services, Inc. d/b/a GASMARK 224 Strawbridge Drive, Suite 107 Moorestown, NJ 08057
856-273-9995
www.ugienergylink.com
C/I ACTIVE
Verde Energy USA, Inc. 2001 Route 46 Waterview Plaza, Suite 301 Parsippany, NJ 07054
800-388-3862
www.lowcostpower.com
R/C
ACTIVE
Viridian Energy PA LLC 2001 Route 46, Waterview Plaza Suite 230 Parsippany, NJ 07054
866-663-2508
www.viridian.com
R/C
ACTIVE
Vista Energy Marketing, L.P. 197 State Route 18 South, Suite 3000 South Wing East Brunswick, NJ 08816
888-508-4782
www.vistaenergymarketing.com
R/C/I
ACTIVE
Woodruff Energy 73 Water Street Bridgeton, NJ 08302
800-557-1121
www.woodruffenergy.com
R/C/I
ACTIVE
Woodruff Energy US LLC 73 Water Street, P.O. Box 777 Bridgeton, NJ 08302
856-455-1111 800-557-1121
www.woodruffenergy.com
C/I
ACTIVE
XOOM Energy New Jersey, LLC 744 Broad Street. 16th Floor Newark, NJ 07102
888-997-8979
www.xoomenergy.com
R/C/I ACTIVE
Your Energy Holdings, LLC One International Boulevard Suite 400 Mahwah, NJ 07495-0400
855-732-2493
www.thisisyourenergy.com
R/C/I
ACTIVE
Back to main supplier information page
PSE&G ELECTRIC SERVICE TERRITORY Last Updated: 12/11/14
*CUSTOMER CLASS - R – RESIDENTIAL C – COMMERCIAL I –INDUSTRIAL
Supplier Telephone & Web Site
*CustomerClass
Abest Power & Gas of NJ, LLC 202 Smith Street Perth Amboy, NJ 08861
(888)987-6937
www.AbestPower.com
R/C/I
ACTIVE
AEP Energy, Inc. f/k/a BlueStar Energy Services 309 Fellowship Road, Fl. 2 Mount Laurel, NJ 08054
(866) 258-3782
www.aepenergy.com
R/C/I
ACTIVE
Alpha Gas and Electric, LLC 641 5th Street Lakewood, NJ 08701
(855) 553-6374
www.alphagasandelectric.com
R/C
ACTIVE
Ambit Northeast, LLC d/b/a Ambit Energy 103 Carnegie Center Suite 300 Princeton, NJ 08540
877-282-6284
www.ambitenergy.com
R/C
ACTIVE
American Powernet Management, LP 437 North Grove St. Berlin, NJ 08009
(877) 977-2636
www.americanpowernet.com
C/I
ACTIVE
Amerigreen Energy, Inc. 333Sylvan Avenue Englewood Cliffs, NJ 07632
888-559-4567
www.amerigreen.com
R/C
ACTIVE
AP Gas & Electric, (NJ) LLC 10 North Park Place, Suite 420 Morristown, NJ 07960
(855) 544-4895
www.apgellc.com
R/C/I
ACTIVE
Astral Energy LLC 16 Tyson Place Bergenfield, NJ 07621
(888)850-1872
www.AstralEnergyLLC.com
R/C/I
ACTIVE
Barclays Capital Services, Inc. 70 Hudson Street Jersey City, NJ 07302-4585
(800) 526-7000
www.barclays.com
C
ACTIVE
BBPC, LLC d/b/a Great Eastern Energy
(888) 651-4121 C
116 Village Blvd. Suite 200 Princeton, NJ 08540
www.greateasternenergy.com
ACTIVE
Berkshire Energy Partners, LLC 9 Berkshire Road Landenberg, PA 19350 Attn: Dana A. LeSage, P.E.
(610) 255-5070
www.berkshireenergypartners.com
C/I
ACTIVE
Blue Pilot Energy, LLC 197 State Rte. 18 South Ste. 3000 East Brunswick, NJ 08816
(800) 451-6356
www.bluepilotenergy.com
R/C
ACTIVE
Brick Standard, LLC 235 Hudson Street Suite 1 Hoboken, NJ 07030
(201)706-8101
www.standardalternative.com
C/I
ACTIVE
CCES LLC dba Clean Currents Energy Services 566 Terhune Street Teaneck, NJ 07666
(877) 933-2453
www.cleancurrents.com
R/C
ACTIVE
Champion Energy Services, LLC 1200 Route 22 Bridgewater, NJ 08807
(888) 653-0093
www.championenergyservices.com
R/C/I
ACTIVE
Choice Energy, LLC 4257 US Highway 9, Suite 6C Freehold, NJ 07728
(888) 565-4490
www.4choiceenergy.com
R/C
ACTIVE
Clearview Electric, Inc. 1744 Lexington Avenue Pennsauken, NJ 08110
(888) CLR-VIEW (800) 746- 4702 www.clearviewenergy.com
R/C/I
ACTIVE
Commerce Energy, Inc. 7 Cedar Terrace Ramsey, NJ 07446
1-866-587-8674
www.commerceenergy.com
R/C
ACTIVE
Community Energy Inc. 51 Sandbrook Headquarters Road Stockton, NJ 08559
(866)946-3123
www.communityenergyinc.com
R/C/I
ACTIVE
ConEdison Solutions Cherry Tree Corporate Center 535 State Highway Suite 180 Cherry Hill, NJ 08002
(888) 665-0955
www.conedsolutions.com
C/I
ACTIVE
ConocoPhillips Company 224 Strawbridge Drive Suite 107 Moorestown, NJ 08057
(800) 646-4427
www.conocophillips.com
C/I
ACTIVE
Constellation NewEnergy, Inc. 900A Lake Street, Suite 2 Ramsey, NJ 07446
(888) 635-0827
www.constellation.com
R/C/I
ACTIVE
Constellation Energy 900A Lake Street, Suite 2 Ramsey, NJ 07446
(877) 997-9995
www.constellation.com
R
ACTIVE
Credit Suisse, (USA) Inc. 700 College Road East Princeton, NJ 08450
(212) 538-3124
www.creditsuisse.com
C
ACTIVE
Direct Energy Business, LLC 120 Wood Avenue, Suite 611 Iselin, NJ 08830
(888) 925-9115
http://www.business.directenergy.com/
R
ACTIVE
Direct Energy Business Marketing, LLC (fka Hess Energy Marketing) 1 Hess Plaza Woodbridge, NJ 07095
(800) 437-7872
http://www.business.directenergy.com/
C/I
ACTIVE
Direct Energy Services, LLC 120 Wood Avenue, Suite 611 Iselin, NJ 08830
(888) 925-9115
www.directenergy.com
R
ACTIVE
Direct Energy Small Business, LLC (fka Hess Small Business Services, LLC) One Hess Plaza Woodbridge, NJ 07095
(888) 464-4377
http://www.business.directenergy.com/
C/I
ACTIVE
Discount Energy Group, LLC 811 Church Road, Suite 149 Cherry Hill, New Jersey 08002
(800) 282-3331
www.discountenergygroup.com
R/C
ACTIVE
DTE Energy Supply, Inc. One Gateway Center, Suite 2600 Newark, NJ 07102
(877) 332-2450
www.dtesupply.com
C/I
ACTIVE
Energy.me Midwest LLC 90 Washington Blvd Bedminster, NJ 07921
(855) 243-7270
www.energy.me
R/C/I
ACTIVE
Energy Plus Holdings LLC 309 Fellowship Road East Gate Center, Suite 200 Mt. Laurel, NJ 08054
(877) 866-9193
www.energypluscompany.com
R/C
ACTIVE
Ethical Electric Benefit Co. d/b/a Ethical Electric 100 Overlook Center, 2nd Fl. Princeton, NJ 08540
(888) 444-9452
www.ethicalelectric.com
R/C
ACTIVE
Energy Service Providers, Inc., d/b/a New Jersey Gas & Electric 1 Bridge Plaza fl. 2 Fort Lee, NJ 07024
(866) 568-0290
www.njgande.com
R/C
ACTIVE
FirstEnergy Solutions 150 West State Street Trenton, NJ 08608
(866) 625-7318
www.fes.com
C/I
ACTIVE
Gateway Energy Services Corp. 120 Wood Avenue Suite 611 Iselin, NJ 08830
(866)348-4193
www.directenergybusiness.com
R/C
ACTIVE
GDF SUEZ Energy Resources NA, Inc. 333 Thornall Street Sixth Floor Edison, NJ 08837
(866) 999-8374
www.gdfsuezenergyresources.com
C/I
ACTIVE
GDF Suez Retail Energy Solutions LLC d/b/a THINK ENERGY 333 Thornall St. Sixth Floor Edison, NJ 08819
1-866-252-0078
www.mythinkenergy.com
R/C/I
ACTIVE
Glacial Energy of New Jersey, Inc. 21 Pine Street, Suite 237 Rockaway, NJ 07866
(888) 452-2425
www.glacialenergy.com
C/I
ACTIVE
Global Energy Marketing LLC 129 Wentz Avenue Springfield, NJ 07081
(800) 542-0778
www.globalp.com
R/C/I
ACTIVE
Green Mountain Energy Company 211 Carnegie Center Drive Princeton, NJ 08540
(866) 767-5818
www.greenmountain.com/commercial-home
C/I
ACTIVE
Harborside Energy LLC 101 Hudson Street Suite 2100 Jersey City, NJ 07302
(877) 940-3835
www.harborsideenergynj.com
R/C
ACTIVE
Hess Corporation 1 Hess Plaza Woodbridge, NJ 07095
(800) 437-7872
www.hess.com
C/I
ACTIVE
HIKO Energy, LLC 655 Suffern Road Teaneck, NJ 07666
(888) 264-4908
www.hikoenergy.com
R/C/I
ACTIVE
Hudson Energy Services, LLC 7 Cedar Street Ramsey, New Jersey 07446
(877) Hudson 9
www.hudsonenergyservices.com
C
ACTIVE
IDT Energy, Inc. 550 Broad Street Newark, NJ 07102
(877) 887-6866
www.idtenergy.com
R/C
ACTIVE
Independence Energy Group, LLC 211 Carnegie Center Princeton, NJ 08540
(877) 235-6708
www.chooseindependence.com
R/C
ACTIVE
Inspire Energy Holdings LLC 923 Haddonfield Road 3rd Fl. Building B2 Cherry Hill, NJ 08002
(866) 403-2620
www.inspireenergy.com
R/C/I
Integrys Energy Services, Inc. 33 Wood Ave, South, Suite 610 Iselin, NJ 08830
(800) 536-0151
www.integrysenergy.com
C/I
ACTIVE
Jsynergy, LLC 445 Central Ave. Suite 204 Cedarhurst, NY 11516
(516) 331-2020
Jsynergyllc.com
R/C/I
ACTIVE
Kuehne Chemical Company, Inc. 86 North Hackensack Avenue South Kearney, NJ 07032
(973) 589-0700
kuehnechemical@comcast.net
I
Liberty Power Delaware, LLC 1973 Highway 34, Suite 211 Wall, NJ 07719
(866) 769-3799
www.libertypowercorp.com
C/I
ACTIVE
Liberty Power Holdings, LLC 1973 Highway 34, Suite 211 Wall, NJ 07719
(866) 769-3799
www.libertypowercorp.com
R/C/I
ACTIVE
Linde Energy Services 575 Mountain Avenue Murray Hill, NJ 07974
(800) 247-2644
www.linde.com
C/I
ACTIVE
Marathon Power LLC 302 Main Street Paterson, NJ 07505
( 888) 779-7255
www.mecny.com
R/C/I
ACTIVE
MP2 Energy NJ, LLC 111 River Street, Suite 1204 Hoboken, NJ 07030
(877) 238-5343
www.mp2energy.com
R/C/I
ACTIVE
Natures Current, LLC 95 Fairmount Avenue Philadelphia, Pennsylvania 19123
(215) 464-6000
www.naturescurrent.com
R/C/I
ACTIVE
MPower Energy NJ LLC One University Plaza, Suite 507 Hackensack, NJ 07601
(877) 286-7693
www.mpowerenergy.com
R/C/I
ACTIVE
NATGASCO, Inc. (Supreme Energy, Inc.) 532 Freeman St. Orange, NJ 07050
(800) 840-4427
www.supremeenergyinc.com
R/C/I
ACTIVE
New Jersey Gas & Electric 10 North Park Place Suite 420 Morristown, NJ 07960
(866) 568-0290
www.njgande.com
R/C/
ACTIVE
NextEra Energy Services New Jersey, LLC 651 Jernee Mill Road Sayreville, NJ 08872
(877) 528-2890 Commercial (800) 882-1276 Residential
www.nexteraenergyservices.com
R/C/I
ACTIVE
Noble Americas Energy Solutions The Mac-Cali Building 581 Main Street, 8th Floor Woodbridge, NJ 07095
(877) 273-6772
www.noblesolutions.com
C/I
ACTIVE
Nordic Energy Services, LLC 50 Tice Boulevard, Suite 340 Woodcliff Lake, NJ 07677
(877) 808-1027
www.nordiceenergy.us.com
R/C/I
ACTIVE
North American Power and Gas, LLC 222 Ridgedale Avenue Cedar Knolls, NJ 07927
(888) 313-9086
www.napower.com
R/C/I
ACTIVE
North Eastern States, Inc. d/b/a Entrust Energy 90 Washington Valley Road Bedminster, NJ 07921
(888) 535-6340
www.entrustenergy.com
R/C/I
ACTIVE
Oasis Power, LLC d/b/a Oasis Energy 11152 Westheimer, Suite 901 Houston, TX 77042
(800)324-3046
www.oasisenergy.com
R/C
ACTIVE
Palmco Power NJ, LLC One Greentree Centre 10,000 Lincoln Drive East, Suite 201 Marlton, NJ 08053
(877) 726-5862
www.PalmcoEnergy.com
R/C/I
ACTIVE
Park Power, LLC 1200 South Church St. Suite 23 Mount Laurel, NJ 08054
(856) 778-0079
www.parkpower.com
R/C/I
ACTIVE
Plymouth Rock Energy, LLC 338 Maitland Avenue Teaneck, NJ 07666
(855) 32-POWER (76937)
www.plymouthenergy.com
R/C/I
ACTIVE
Power Management Co., LLC b/b/a PMC Lightsavers Limited Liability Company 1600 Moseley Road Victor, NY 14564
(585) 249-1360
www.powermanagementco.com
C/I
ACTIVE
PPL Energy Plus, LLC 811 Church Road Cherry Hill, NJ 08002
(800) 281-2000
www.pplenergyplus.com
C/I
ACTIVE
PPL EnergyPlus Retail, LLC 788 Shrewsbury Avenue, Suite 220 Tinton Falls, NJ 07724
(732) 741-0505 – 2000
www.pplenergyplus.com
C/I
ACTIVE
Progressive Energy Consulting, LLC
(917) 837-7400
R/C/I
PO Box 4582 Wayne, New Jersey 07474
Progressivenrg@optionline.net ACTIVE
Prospect Resources, Inc. 208 W. State Street Trenton, NJ 08608-1002
(847) 673-1959
www.prospectresources.com
C
ACTIVE
Public Power & Utility of New Jersey, LLC One International Blvd, Suite 400 Mahwah, NJ 07495
(888) 354-4415
www.ppandu.com
R/C/I
ACTIVE
Reliant Energy 211 Carnegie Center Princeton, NJ 08540
(877) 297-3795 (877) 297-3780
www.reliant.com
R/C/I
ACTIVE
ResCom Energy LLC 18C Wave Crest Ave. Winfield Park, NJ 07036
(888) 238-4041
http://rescomenergy.com
R/C/I
ACTIVE
Residents Energy, LLC 550 Broad Street Newark, NJ 07102
(888) 828-7374
www.residentsenergy.com
R/C
Respond Power LLC 1001 East Lawn Drive Teaneck, NJ 07666
(877) 973-7763
www.majorenergy.com
R/C/I
ACTIVE
Save on Energy, LLC 1101 Red Ventures Drive Fort Mill, SC 29707
1 (877)-658-3183
www.saveonenergy.com
R/C
SFE Energy One Gateway Center Suite 2600 Newark, NJ 07012
1 (877) 316-6344
www.sfeenergy.com
R/C/I
ACTIVE
S.J. Energy Partners, Inc. 208 White Horse Pike, Suite 4 Barrington, NJ 08007
(800) 695-0666
www.sjnaturalgas.com
C
ACTIVE
SmartEnergy Holdings, LLC 100 Overlook Center 2nd Floor Princeton, NJ NJ 08540 United States of America
(800) 443-4440
www.smartenergy.com
R/C/I
ACTIVE
South Jersey Energy Company 1 South Jersey Plaza, Route 54 Folsom, NJ 08037
(800) 266-6020
www.southjerseyenergy.com
R/C/I
ACTIVE
Spark Energy Gas, LP/ Spark Energy 2105 City West Blvd. Suite 100 Houston, TX 77042
(713)600-2600
www.sparkenergy.com
R/C/I
ACTIVE
Sperian Energy Corp. 1200 Route 22 East, Suite 2000 Bridgewater, NJ 08807
(888) 682-8082
www.sperianenergy.com
R/C/I
ACTIVE
Starion Energy PA Inc. 101 Warburton Avenue Hawthorne, NJ 07506
(800) 600-3040
www.starionenergy.com
R/C/I
ACTIVE
Stream Energy New Jersey, LLC 309 Fellowship Rd., Suite 200 Mt. Laurel, NJ 08054
(877) 369-8150
www.streamenergy.net
R/C
ACTIVE
Summit Energy Services, Inc. 10350 Ormsby Park Place Suite 400 Louisville, KY 40223
1 (800) 90-SUMMIT
www.summitenergy.com
C/I
ACTIVE
Texas Retail Energy LLC Park 80 West Plaza II, Suite 200 Saddle Brook, NJ 07663 Attn: Chris Hendrix
(866) 532-0761
Texasretailenergy.com
C/I
ACTIVE
TransCanada Power Marketing Ltd. 190 Middlesex Essex Turnpike, Suite 200 Iselin, NJ 08830
(877) MEGAWAT
www.transcanada.com/powermarketing
C/I
ACTIVE
TriEagle Energy, LP 90 Washington Valley Rd Bedminster, NJ 07921
(877) 933-2453
www.trieagleenergy.com
R/C/I
ACTIVE
UGI Energy Services, Inc. dba UGI Energy Link 224 Strawbridge Drive Suite 107 Moorestown, NJ 08057
(800) 427-8545
www.ugienergylink.com
C/I
ACTIVE
Verde Energy USA, Inc. 2001 Route 46 Waterview Plaza Suite 301 Parsippany, NJ 07054
(800) 388-3862
www.lowcostpower.com
R/C
ACTIVE
Viridian Energy 2001 Route 46, Waterview Plaza Suite 310 Parsippany, NJ 07054
(866) 663-2508
www.viridian.com
R/C/I
ACTIVE
XOOM Energy New Jersey, LLC 744 Broad Street. 16th Floor Newark, NJ 07102
(888) 997-8979
www.xoomenergy.com
R/C/I
ACTIVE
YEP Energy 89 Headquarters Plaza North #1463 Morristown, NJ 07960
(855) 363-7736
www.yepenergyNJ.com
R/C/I
ACTIVE
Your Energy Holdings, LLC One International Boulevard Suite 400 Mahwah, NJ 07495-0400
(855) 732-2493
www.thisisyourenergy.com
R/C/I
ACTIVE
Back to the main supplier page
APPENDIX B
Equipment Inventory
CHA Project # 29142
Hall of Records
Essex County
Description QTY Manufacturer Name Model No. Serial No.Equipment Type /
UtilityCapacity/Size /Efficiency Efficiency Location Areas/Equipment Served Date Installed Remaining Useful Life (years)
Current year Years Old ASHRAE life expectancy
Steam Boiler 2 Superior Boiler Works Inc X6-X-3000 17296 Steam Boiler
20700 lb/hr steam @200
psig 600HP Heating
capacity
~80%Annex Mechanical
Room
Hall of Records, Veteran
Courthouse and Historic
Courthouse
2012 23 2014 2 25
RTU 1 Carrier 50TM-016-511YA 378196X54Roof top unit with DX
cooling15ton cooling capacity N/A Roof Annex 2000 6 2014 14 20
RTU 1 LuxAire N/A N/ARoof top unit with DX
cooling~7.5 ton N/A Roof Annex 2000 6 2014 14 20
RTU 1 Lennex N/A N/ARoof top unit with DX
cooling~7.5 ton N/A Roof Annex 2000 6 2014 14 20
RTU 1 Carrier 38ARZ008-511 N/ARoof top unit with DX
cooling~8 ton ~11.1 EER Roof Hall of Records 2004 10 2014 10 20
RTU 1 Trane TTA120A300FA N/ARoof top unit with DX
cooling10 ton cooling capacity N/A Roof Hall of Records 2004 10 2014 10 20
RTU 1 Trane TTA120A300FA N/ARoof top unit with DX
cooling10 ton cooling capacity N/A Roof Hall of Records 2004 10 2014 10 20
RTU 1 Carrier 24A135360A00S0010 N/ARoof top unit with DX
cooling~5 ton N/A Roof Hall of Records 2004 10 2014 10 20
RTU 1 Carrier 38ARZ008-511 N/ARoof top unit with DX
cooling~8 ton ~11.1 EER Roof Hall of Records 2004 10 2014 10 20
RTU 1 Trane N/A N/ARoof top unit with DX
cooling~5 ton N/A Roof Hall of Records 2004 10 2014 10 20
RTU 1 Carrier 24ABS330 N/ARoof top unit with DX
cooling~5 ton N/A Roof Hall of Records 2004 10 2014 10 20
RTU 1 York DL-10C00 N/ARoof top unit with DX
cooling10 ton cooling capacity N/A Roof Hall of Records 2004 10 2014 10 20
RTU 1 Trane TTA120A300FA N/ARoof top unit with DX
cooling10 ton cooling capacity N/A Roof Hall of Records 2004 10 2014 10 20
RTU 1 Trane TTA180BB300CB N/ARoof top unit with DX
cooling10 ton cooling capacity N/A Roof Hall of Records 2004 10 2014 10 20
RTU 1 Carrier 38ARZ008-511 N/ARoof top unit with DX
cooling~8 ton ~11.1 EER Roof Hall of Records 2004 10 2014 10 20
RTU 1 York HEHB-T09DAA N/ARoof top unit with DX
cooling~9 ton N/A Roof Hall of Records 2004 10 2014 10 20
RTU 4 N/A ZS-105N13ATAA1A N1A2498927Roof top unit with DX
coolingN/A N/A Roof Cafeteria in Annex 2004 10 2014 10 20
MAU 1 Dayton 44C478 13101958
Make up air unit for
the kitchen exhaust
fan
N/A N/A Roof Kitchen in Annex 2004 10 2014 10 20
DHW 2 A O Smith BTH N/A Gas fired DHW heater ~120MBH and 100 gallon 80%Annex Mechanical
RoomHall of Records and Annex 2004 10 2014 10 20
Walkin Cooler 1 Ressul RLH080M44-D N/A Walkin Cooler7,080 BTH cooling
capacityN/A Roof Kitchen 2004 10 2014 10 20
Walkin Freezer 1 Ressul RLH080M44-D N/A Walkin Cooler7,080 BTH cooling
capacityN/A Roof Kitchen 2004 10 2014 10 20
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
Existing Lighting & Audit Input $3.79 $/kW
Area Description Usage
No. of
Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space Exist Control Annual Hours Annual kWh
Field
Code
Unique description of the location - Room number/Room
name: Floor number (if applicable)
Describe Usage Type
using Operating Hours
No. of
fixtures
before the
retrofit
Lighting Fixture Code Code from Table of Standard Fixture
Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
Pre-inst. control
device
Estimated
annual hours for
the usage group
(kW/space) *
(Annual Hours)
Retrofit control
device
Notes
32LED 3rd floor Hallway Hallways 12 1T 32 R F 2 (ELE) F42LL 60 0.72 SW 8736 6,290 NONE
185LED 338B Offices 8 T 40 R F 4 (ELE) F44SE 172 1.38 SW 2184 3,005 NONE
119 338 Offices 6 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 1.30 SW 2184 2,830 C-OCC
35LED 338 Offices 2 T 32 R F 3 (ELE) F43ILL/2 90 0.18 SW 2184 393 C-OCC
185LED 340 Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
185LED 342 Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
185LED 342 Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
185LED 343 Offices 8 T 40 R F 4 (ELE) F44SE 172 1.38 SW 2184 3,005 C-OCC
35LED 344 Offices 3 T 32 R F 3 (ELE) F43ILL/2 90 0.27 SW 2184 590 C-OCC
185LED 345 Offices 6 T 40 R F 4 (ELE) F44SE 172 1.03 SW 2184 2,254 C-OCC
185LED 346 Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
185LED 346 Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
185LED 348 Offices 8 T 40 R F 4 (ELE) F44SE 172 1.38 SW 2184 3,005 C-OCC
185LED 348 Offices 3 T 40 R F 4 (ELE) F44SE 172 0.52 SW 2184 1,127 C-OCC
119 347 Offices 3 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 0.65 SW 2184 1,415 C-OCC
119 347 Offices 1 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 0.22 SW 2184 472 C-OCC
32LED Hallway Hallways 14 1T 32 R F 2 (ELE) F42LL 60 0.84 SW 8736 7,338 NONE
41LED 303A Offices 5 1B 40 R F 2 (MAG) F42SS 94 0.47 SW 2184 1,026 C-OCC
41LED Judge Chamber Offices 4 1B 40 R F 2 (MAG) F42SS 94 0.38 SW 2184 821 C-OCC
71 Courthouse Courthouse 94 I 60 I60/1 60 5.64 SW 2125 11,985 NONE
41LED Courthouse Courthouse 1 1B 40 R F 2 (MAG) F42SS 94 0.09 SW 2125 200 NONE
41LED 302B Offices 5 1B 40 R F 2 (MAG) F42SS 94 0.47 SW 2184 1,026 C-OCC
247LED 304 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
41LED 304 Offices 1 1B 40 R F 2 (MAG) F42SS 94 0.09 SW 2184 205 C-OCC
247LED 304 Offices 1 T 40 R F 3 (MAG) F43SE 136 0.14 SW 2184 297 C-OCC
185LED 304 Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
185LED 304 Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
32LED Hallway Hallways 10 1T 32 R F 2 (ELE) F42LL 60 0.60 SW 8736 5,242 NONE
247LED 312 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
185LED Hallway Hallways 10 T 40 R F 4 (ELE) F44SE 172 1.72 SW 8736 15,026 NONE
185LED Mens Room Restroom 3 T 40 R F 4 (ELE) F44SE 172 0.52 SW 2184 1,127 C-OCC
185LED Womens Room Restroom 3 T 40 R F 4 (ELE) F44SE 172 0.52 SW 2184 1,127 C-OCC
247LED 321A Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
32LED 321A Offices 2 1T 32 R F 2 (ELE) F42LL 60 0.12 SW 2184 262 C-OCC
247LED 321 Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
247LED 322 Offices 12 T 40 R F 3 (MAG) F43SE 136 1.63 SW 2184 3,564 C-OCC
185LED Mail Room Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
185LED 325 Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
185LED 325 Offices 5 T 40 R F 4 (ELE) F44SE 172 0.86 SW 2184 1,878 C-OCC
185LED 325 Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
32LED Hallway Hallways 4 1T 32 R F 2 (ELE) F42LL 60 0.24 SW 8736 2,097 C-OCC
185LED 335 Offices 19 T 40 R F 4 (ELE) F44SE 172 3.27 SW 2184 7,137 C-OCC
247LED café Cafeteria 28 T 40 R F 3 (MAG) F43SE 136 3.81 SW 1820 6,931 NONE
185LED café Cafeteria 10 T 40 R F 4 (ELE) F44SE 172 1.72 SW 1820 3,130 C-OCC
247LED Café Individual Room Cafeteria 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 1820 495 C-OCC
185LED Café Individual Room Cafeteria 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 1820 626 C-OCC
196LED Hallway Hallways 4 W 32 C F 4 (ELE) F44ILL 112 0.45 SW 8736 3,914 C-OCC
196LED 331 Offices 32 W 32 C F 4 (ELE) F44ILL 112 3.58 SW 2184 7,827 C-OCC
247LED 331 Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
5LED Mens Room Restroom 1 2T 32 R F 2 (u) (ELE) FU2LL 60 0.06 SW 2184 131 C-OCC
250 329 Offices 6 T 54 W F 3 (ELE) (T-5) F43GHL 177 1.06 SW 2184 2,319 C-OCC
247LED 328 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
250 4th Floor 436 Offices 4 T 54 W F 3 (ELE) (T-5) F43GHL 177 0.71 SW 2184 1,546 C-OCC
247LED 436 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
247LED Office Offices 8 T 40 R F 3 (MAG) F43SE 136 1.09 SW 2184 2,376 C-OCC
32LED Office Offices 1 1T 32 R F 2 (ELE) F42LL 60 0.06 SW 2184 131 C-OCC
196LED 435 Offices 4 W 32 C F 4 (ELE) F44ILL 112 0.45 SW 2184 978 C-OCC
247LED 435 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
185LED Hallway Hallways 7 T 40 R F 4 (ELE) F44SE 172 1.20 SW 8736 10,518 C-OCC
247LED 438 Offices 14 T 40 R F 3 (MAG) F43SE 136 1.90 SW 2184 4,158 C-OCC
247LED 439 Offices 9 T 40 R F 3 (MAG) F43SE 136 1.22 SW 2184 2,673 C-OCC
247LED 439 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 439 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
247LED 443 Offices 6 T 40 R F 3 (MAG) F43SE 136 0.82 SW 2184 1,782 C-OCC
247LED 444 Offices 14 T 40 R F 3 (MAG) F43SE 136 1.90 SW 2184 4,158 C-OCC
185LED Hallway Hallways 10 T 40 R F 4 (ELE) F44SE 172 1.72 SW 8736 15,026 C-OCC
247LED 445 Offices 14 T 40 R F 3 (MAG) F43SE 136 1.90 SW 2184 4,158 C-OCC
247LED 445 Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
247LED 449A Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 449A Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
247LED 449A Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
Retrofit
Control
EXISTING CONDITIONS
1/22/2015 Page 1, Existing
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
Existing Lighting & Audit Input $3.79 $/kW
Area Description Usage
No. of
Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space Exist Control Annual Hours Annual kWh
Field
Code
Unique description of the location - Room number/Room
name: Floor number (if applicable)
Describe Usage Type
using Operating Hours
No. of
fixtures
before the
retrofit
Lighting Fixture Code Code from Table of Standard Fixture
Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
Pre-inst. control
device
Estimated
annual hours for
the usage group
(kW/space) *
(Annual Hours)
Retrofit control
device
Notes
Retrofit
Control
EXISTING CONDITIONS
5LED 402 Offices 8 2T 32 R F 2 (u) (ELE) FU2LL 60 0.48 SW 2184 1,048 C-OCC
5LED 402 Offices 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.30 SW 2184 655 C-OCC
5LED 402 Offices 9 2T 32 R F 2 (u) (ELE) FU2LL 60 0.54 SW 2184 1,179 C-OCC
185LED Hallway Hallways 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 8736 6,010 C-OCC
196LED Hallway Hallways 3 W 32 C F 4 (ELE) F44ILL 112 0.34 SW 8736 2,935 C-OCC
71 Hallway Hallways 2 I 60 I60/1 60 0.12 SW 8736 1,048 NONE
5LED 405 Offices 2 2T 32 R F 2 (u) (ELE) FU2LL 60 0.12 SW 2184 262 C-OCC
25 405 Offices 1 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.03 SW 2184 61 C-OCC
5LED 405 Offices 6 2T 32 R F 2 (u) (ELE) FU2LL 60 0.36 SW 2184 786 C-OCC
5LED 405 Offices 1 2T 32 R F 2 (u) (ELE) FU2LL 60 0.06 SW 2184 131 C-OCC
196LED 405 Offices 1 W 32 C F 4 (ELE) F44ILL 112 0.11 SW 2184 245 C-OCC
5LED 405 Offices 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.30 SW 2184 655 C-OCC
5LED 405 Offices 4 2T 32 R F 2 (u) (ELE) FU2LL 60 0.24 SW 2184 524 C-OCC
5LED 405 Offices 10 2T 32 R F 2 (u) (ELE) FU2LL 60 0.60 SW 2184 1,310 C-OCC
25 405 Offices 16 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.45 SW 2184 978 C-OCC
5LED 403 Offices 8 2T 32 R F 2 (u) (ELE) FU2LL 60 0.48 SW 2184 1,048 C-OCC
25 403 Offices 14 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.39 SW 2184 856 C-OCC
247LED 408 Offices 15 T 40 R F 3 (MAG) F43SE 136 2.04 SW 2184 4,455 C-OCC
35LED 411 Offices 10 T 32 R F 3 (ELE) F43ILL/2 90 0.90 SW 2184 1,966 C-OCC
185LED 411 Offices 6 T 40 R F 4 (ELE) F44SE 172 1.03 SW 2184 2,254 C-OCC
185LED Hallway Hallways 10 T 40 R F 4 (ELE) F44SE 172 1.72 SW 8736 15,026 NONE
35LED 413 Offices 8 T 32 R F 3 (ELE) F43ILL/2 90 0.72 SW 2184 1,572 C-OCC
35LED 414 Offices 4 T 32 R F 3 (ELE) F43ILL/2 90 0.36 SW 2184 786 C-OCC
32LED 414 Offices 1 1T 32 R F 2 (ELE) F42LL 60 0.06 SW 2184 131 C-OCC
35LED 416 Offices 6 T 32 R F 3 (ELE) F43ILL/2 90 0.54 SW 2184 1,179 C-OCC
35LED 417A Offices 7 T 32 R F 3 (ELE) F43ILL/2 90 0.63 SW 2184 1,376 C-OCC
35LED 417A Offices 12 T 32 R F 3 (ELE) F43ILL/2 90 1.08 SW 2184 2,359 C-OCC
35LED 417A Offices 5 T 32 R F 3 (ELE) F43ILL/2 90 0.45 SW 2184 983 C-OCC
35LED 417A Offices 4 T 32 R F 3 (ELE) F43ILL/2 90 0.36 SW 2184 786 C-OCC
35LED 417A Offices 4 T 32 R F 3 (ELE) F43ILL/2 90 0.36 SW 2184 786 C-OCC
247LED 417A Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
247LED 422A Offices 15 T 40 R F 3 (MAG) F43SE 136 2.04 SW 2184 4,455 C-OCC
247LED 427D Offices 8 T 40 R F 3 (MAG) F43SE 136 1.09 SW 2184 2,376 C-OCC
185LED Hallway Hallways 10 T 40 R F 4 (ELE) F44SE 172 1.72 SW 8736 15,026 NONE
35LED 428 Offices 15 T 32 R F 3 (ELE) F43ILL/2 90 1.35 SW 2184 2,948 C-OCC
35LED 428 Offices 4 T 32 R F 3 (ELE) F43ILL/2 90 0.36 SW 2184 786 C-OCC
35LED 428 Offices 4 T 32 R F 3 (ELE) F43ILL/2 90 0.36 SW 2184 786 C-OCC
196LED Womens Room Restroom 3 W 32 C F 4 (ELE) F44ILL 112 0.34 SW 2184 734 C-OCC
196LED Mens Room Restroom 3 W 32 C F 4 (ELE) F44ILL 112 0.34 SW 2184 734 C-OCC
32LED 5th Floor Hallway Hallways 10 1T 32 R F 2 (ELE) F42LL 60 0.60 SW 8736 5,242 C-OCC
247LED 530 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
41LED 530 Offices 1 1B 40 R F 2 (MAG) F42SS 94 0.09 SW 2184 205 C-OCC
247LED 530 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
196LED Womens Room Restroom 4 W 32 C F 4 (ELE) F44ILL 112 0.45 SW 2184 978 C-OCC
247LED 535 Offices 10 T 40 R F 3 (MAG) F43SE 136 1.36 SW 2184 2,970 C-OCC
32LED 535 Offices 5 1T 32 R F 2 (ELE) F42LL 60 0.30 SW 2184 655 C-OCC
247LED 535 Offices 5 T 40 R F 3 (MAG) F43SE 136 0.68 SW 2184 1,485 C-OCC
185LED 535 Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
185LED 535 Offices 3 T 40 R F 4 (ELE) F44SE 172 0.52 SW 2184 1,127 C-OCC
185LED 535 Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
247LED 524A Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
247LED 524A Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
32LED Hallway Hallways 12 1T 32 R F 2 (ELE) F42LL 60 0.72 SW 8736 6,290 NONE
247LED 556 Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
247LED 556 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
185LED 558 Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
185LED 558 Offices 16 T 40 R F 4 (ELE) F44SE 172 2.75 SW 2184 6,010 C-OCC
247LED 558 Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
41LED 558 Offices 2 1B 40 R F 2 (MAG) F42SS 94 0.19 SW 2184 411 C-OCC
196LED 558 Offices 4 W 32 C F 4 (ELE) F44ILL 112 0.45 SW 2184 978 C-OCC
71 558 Offices 5 I 60 I60/1 60 0.30 SW 2184 655 C-OCC Locked
5LED 501A Offices 24 2T 32 R F 2 (u) (ELE) FU2LL 60 1.44 SW 2184 3,145 C-OCC Locked
71 502 Offices 6 I 60 I60/1 60 0.36 SW 2184 786 C-OCC Locked
20LED 503A Offices 3 S 28 P F 1 (ELE) F41ILL 31 0.09 SW 2184 203 C-OCC Locked
20LED 503A Offices 2 S 28 P F 1 (ELE) F41ILL 31 0.06 SW 2184 135 C-OCC
20LED 503A Offices 6 S 28 P F 1 (ELE) F41ILL 31 0.19 SW 2184 406 C-OCC
71 Restroom Restroom 1 I 60 I60/1 60 0.06 SW 2184 131 C-OCC
71 Suite 502 Offices 1 I 60 I60/1 60 0.06 SW 2184 131 C-OCC
71 Hallway Hallways 28 I 60 I60/1 60 1.68 SW 8736 14,676 NONE
196LED 504 Offices 2 W 32 C F 4 (ELE) F44ILL 112 0.22 SW 2184 489 C-OCC
196LED 504 Offices 5 W 32 C F 4 (ELE) F44ILL 112 0.56 SW 2184 1,223 C-OCC
1/22/2015 Page 2, Existing
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
Existing Lighting & Audit Input $3.79 $/kW
Area Description Usage
No. of
Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space Exist Control Annual Hours Annual kWh
Field
Code
Unique description of the location - Room number/Room
name: Floor number (if applicable)
Describe Usage Type
using Operating Hours
No. of
fixtures
before the
retrofit
Lighting Fixture Code Code from Table of Standard Fixture
Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
Pre-inst. control
device
Estimated
annual hours for
the usage group
(kW/space) *
(Annual Hours)
Retrofit control
device
Notes
Retrofit
Control
EXISTING CONDITIONS
5LED 508 Offices 4 2T 32 R F 2 (u) (ELE) FU2LL 60 0.24 SW 2184 524 C-OCC
5LED 508 Offices 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.30 SW 2184 655 C-OCC
71 508 Offices 2 I 60 I60/1 60 0.12 SW 2184 262 C-OCC
196LED 507 Offices 4 W 32 C F 4 (ELE) F44ILL 112 0.45 SW 2184 978 C-OCC
196LED 507 Offices 5 W 32 C F 4 (ELE) F44ILL 112 0.56 SW 2184 1,223 C-OCC
196LED 507A Offices 2 W 32 C F 4 (ELE) F44ILL 112 0.22 SW 2184 489 C-OCC
196LED 507A Offices 4 W 32 C F 4 (ELE) F44ILL 112 0.45 SW 2184 978 C-OCC
247LED 509 Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
247LED 509 Offices 6 T 40 R F 3 (MAG) F43SE 136 0.82 SW 2184 1,782 C-OCC
247LED 509 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 509 Offices 1 T 40 R F 3 (MAG) F43SE 136 0.14 SW 2184 297 C-OCC
196LED 560A Offices 6 W 32 C F 4 (ELE) F44ILL 112 0.67 SW 2184 1,468 C-OCC
41LED 559 Offices 1 1B 40 R F 2 (MAG) F42SS 94 0.09 SW 2184 205 C-OCC
247LED 554 Offices 6 T 40 R F 3 (MAG) F43SE 136 0.82 SW 2184 1,782 C-OCC
196LED 553 Offices 3 W 32 C F 4 (ELE) F44ILL 112 0.34 SW 2184 734 C-OCC
196LED 552 Offices 1 W 32 C F 4 (ELE) F44ILL 112 0.11 SW 2184 245 C-OCC
196LED 552 Offices 5 W 32 C F 4 (ELE) F44ILL 112 0.56 SW 2184 1,223 C-OCC
247LED 550 Offices 8 T 40 R F 3 (MAG) F43SE 136 1.09 SW 2184 2,376 C-OCC
247LED 551 Offices 7 T 40 R F 3 (MAG) F43SE 136 0.95 SW 2184 2,079 C-OCC
247LED 551 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
5LED 519 Offices 2 2T 32 R F 2 (u) (ELE) FU2LL 60 0.12 SW 2184 262 C-OCC
5LED 519 Offices 16 2T 32 R F 2 (u) (ELE) FU2LL 60 0.96 SW 2184 2,097 C-OCC
5LED 519 Offices 6 2T 32 R F 2 (u) (ELE) FU2LL 60 0.36 SW 2184 786 C-OCC
5LED 519 Offices 7 2T 32 R F 2 (u) (ELE) FU2LL 60 0.42 SW 2184 917 C-OCC
196LED 514C Offices 6 W 32 C F 4 (ELE) F44ILL 112 0.67 SW 2184 1,468 C-OCC
247LED 516 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
247LED 515 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
196LED 510 Offices 1 W 32 C F 4 (ELE) F44ILL 112 0.11 SW 2184 245 C-OCC
247LED 510 Offices 6 T 40 R F 3 (MAG) F43SE 136 0.82 SW 2184 1,782 C-OCC
196LED 510 Offices 1 W 32 C F 4 (ELE) F44ILL 112 0.11 SW 2184 245 C-OCC
196LED 510 Offices 6 W 32 C F 4 (ELE) F44ILL 112 0.67 SW 2184 1,468 C-OCC
196LED 511 Offices 4 W 32 C F 4 (ELE) F44ILL 112 0.45 SW 2184 978 C-OCC
247LED 511A Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
247LED 511 Small Offices Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
247LED 511 Small Offices Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
185LED 511 Small Offices Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
247LED 511 Small Offices Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 511 Small Offices Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
5LED 511 Small Offices Offices 12 2T 32 R F 2 (u) (ELE) FU2LL 60 0.72 SW 2184 1,572 C-OCC
32LED Hallway Hallways 10 1T 32 R F 2 (ELE) F42LL 60 0.60 SW 8736 5,242 NONE
247LED 549 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 549 Offices 6 T 40 R F 3 (MAG) F43SE 136 0.82 SW 2184 1,782 C-OCC
247LED 548 Offices 7 T 40 R F 3 (MAG) F43SE 136 0.95 SW 2184 2,079 C-OCC
247LED 547 Offices 5 T 40 R F 3 (MAG) F43SE 136 0.68 SW 2184 1,485 C-OCC
32LED Hallway Hallways 8 1T 32 R F 2 (ELE) F42LL 60 0.48 SW 8736 4,193 NONE
247LED 536 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 536 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 537 Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
247LED 537 Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
247LED 546 Offices 7 T 40 R F 3 (MAG) F43SE 136 0.95 SW 2184 2,079 C-OCC
247LED 546 Offices 7 T 40 R F 3 (MAG) F43SE 136 0.95 SW 2184 2,079 C-OCC
247LED 544 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 544 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 543 Offices 8 T 40 R F 3 (MAG) F43SE 136 1.09 SW 2184 2,376 C-OCC
247LED 542 Offices 6 T 40 R F 3 (MAG) F43SE 136 0.82 SW 2184 1,782 C-OCC
247LED 542 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
35LED 542 Offices 6 T 32 R F 3 (ELE) F43ILL/2 90 0.54 SW 2184 1,179 C-OCC
247LED 542 Offices 8 T 40 R F 3 (MAG) F43SE 136 1.09 SW 2184 2,376 C-OCC
247LED 542 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 539 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 539 Offices 23 T 40 R F 3 (MAG) F43SE 136 3.13 SW 2184 6,832 C-OCC
185LED 2nd Floor 201 Offices 6 T 40 R F 4 (ELE) F44SE 172 1.03 SW 2184 2,254 C-OCC
247LED 202 Offices 14 T 40 R F 3 (MAG) F43SE 136 1.90 SW 2184 4,158 C-OCC
185LED 202 Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
247LED 204 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 205 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 205 next Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
247LED 205 next Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
185LED 206 Offices 12 T 40 R F 4 (ELE) F44SE 172 2.06 SW 2184 4,508 C-OCC
41LED 207 Offices 6 1B 40 R F 2 (MAG) F42SS 94 0.56 SW 2184 1,232 C-OCC
247LED 208 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
1/22/2015 Page 3, Existing
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
Existing Lighting & Audit Input $3.79 $/kW
Area Description Usage
No. of
Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space Exist Control Annual Hours Annual kWh
Field
Code
Unique description of the location - Room number/Room
name: Floor number (if applicable)
Describe Usage Type
using Operating Hours
No. of
fixtures
before the
retrofit
Lighting Fixture Code Code from Table of Standard Fixture
Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
Pre-inst. control
device
Estimated
annual hours for
the usage group
(kW/space) *
(Annual Hours)
Retrofit control
device
Notes
Retrofit
Control
EXISTING CONDITIONS
41LED 208 Offices 2 1B 40 R F 2 (MAG) F42SS 94 0.19 SW 2184 411 C-OCC
247LED 209 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
41LED 209 Offices 2 1B 40 R F 2 (MAG) F42SS 94 0.19 SW 2184 411 C-OCC
5LED 211 Offices 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.30 SW 2184 655 C-OCC
25 213 Offices 10 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.28 SW 2184 612 C-OCC
185LED 213 Offices 1 T 40 R F 4 (ELE) F44SE 172 0.17 SW 2184 376 C-OCC
25 214 Offices 6 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.17 SW 2184 367 C-OCC
185LED 214 Offices 1 T 40 R F 4 (ELE) F44SE 172 0.17 SW 2184 376 C-OCC
247LED 215 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
185LED 216 Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
247LED 217 Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
41LED 217 Offices 2 1B 40 R F 2 (MAG) F42SS 94 0.19 SW 2184 411 C-OCC
41LED 219 Offices 19 1B 40 R F 2 (MAG) F42SS 94 1.79 SW 2184 3,901 C-OCC
41LED 220 Offices 4 1B 40 R F 2 (MAG) F42SS 94 0.38 SW 2184 821 C-OCC
185LED 222 Offices 30 T 40 R F 4 (ELE) F44SE 172 5.16 SW 2184 11,269 C-OCC
196LED Men's Room Restroom 3 W 32 C F 4 (ELE) F44ILL 112 0.34 SW 2184 734 C-OCC
196LED Women's Room Restroom 3 W 32 C F 4 (ELE) F44ILL 112 0.34 SW 2184 734 C-OCC
32LED Service Room Offices 2 1T 32 R F 2 (ELE) F42LL 60 0.12 SW 2184 262 C-OCC
185LED 226 Offices 7 T 40 R F 4 (ELE) F44SE 172 1.20 SW 2184 2,630 C-OCC
32LED 226 Offices 1 1T 32 R F 2 (ELE) F42LL 60 0.06 SW 2184 131 C-OCC
185LED 226 Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
247LED 227 Offices 8 T 40 R F 3 (MAG) F43SE 136 1.09 SW 2184 2,376 C-OCC
185LED 228 Offices 3 T 40 R F 4 (ELE) F44SE 172 0.52 SW 2184 1,127 C-OCC
247LED 231 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
185LED 231 Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
41LED 232 Offices 4 1B 40 R F 2 (MAG) F42SS 94 0.38 SW 2184 821 C-OCC
247LED 232 Offices 8 T 40 R F 3 (MAG) F43SE 136 1.09 SW 2184 2,376 C-OCC
41LED 233 Offices 5 1B 40 R F 2 (MAG) F42SS 94 0.47 SW 2184 1,026 C-OCC
247LED 233 Offices 14 T 40 R F 3 (MAG) F43SE 136 1.90 SW 2184 4,158 C-OCC
71 233 Storage Storage Areas 2 I 60 I60/1 60 0.12 SW 2912 349 C-OCC
185LED 236 Offices 19 T 40 R F 4 (ELE) F44SE 172 3.27 SW 2184 7,137 C-OCC
185LED 238 Offices 15 T 40 R F 4 (ELE) F44SE 172 2.58 SW 2184 5,635 C-OCC
185LED 242 Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
247LED 242 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
32LED 242 Offices 6 1T 32 R F 2 (ELE) F42LL 60 0.36 SW 2184 786 C-OCC
196LED lobby Hallways 2 W 32 C F 4 (ELE) F44ILL 112 0.22 SW 8736 1,957 NONE
247LED 244 Offices 12 T 40 R F 3 (MAG) F43SE 136 1.63 SW 2184 3,564 C-OCC
41LED 244 Offices 6 1B 40 R F 2 (MAG) F42SS 94 0.56 SW 2184 1,232 C-OCC
41LED Attendent Offices 5 1B 40 R F 2 (MAG) F42SS 94 0.47 SW 2184 1,026 C-OCC
41LED 247 Offices 155 1B 40 R F 2 (MAG) F42SS 94 14.57 SW 2184 31,821 C-OCC
247LED 247 Offices 3 T 40 R F 3 (MAG) F43SE 136 0.41 SW 2184 891 C-OCC
41LED 247 Offices 4 1B 40 R F 2 (MAG) F42SS 94 0.38 SW 2184 821 C-OCC
5LED 248 Offices 66 2T 32 R F 2 (u) (ELE) FU2LL 60 3.96 SW 2184 8,649 C-OCC
5LED 248 Offices 66 2T 32 R F 2 (u) (ELE) FU2LL 60 3.96 SW 2184 8,649 C-OCC
196LED 248 Offices 45 W 32 C F 4 (ELE) F44ILL 112 5.04 SW 2184 11,007 C-OCC
196LED 248 Offices 2 W 32 C F 4 (ELE) F44ILL 112 0.22 SW 2184 489 C-OCC
196LED 248 Offices 2 W 32 C F 4 (ELE) F44ILL 112 0.22 SW 2184 489 C-OCC
35LED 1st Floor 101 Offices 29 T 32 R F 3 (ELE) F43ILL/2 90 2.61 SW 2184 5,700 C-OCC
35LED 102 Offices 5 T 32 R F 3 (ELE) F43ILL/2 90 0.45 SW 2184 983 C-OCC
41LED 103 Offices 2 1B 40 R F 2 (MAG) F42SS 94 0.19 SW 2184 411 C-OCC
185LED 104 Offices 8 T 40 R F 4 (ELE) F44SE 172 1.38 SW 2184 3,005 C-OCC
71 Entrance Hall Hallways 16 I 60 I60/1 60 0.96 SW 8736 8,387 NONE
71 Entrance Hall Offices 36 I 60 I60/1 60 2.16 SW 2184 4,717 C-OCC
247LED 107 Offices 14 T 40 R F 3 (MAG) F43SE 136 1.90 SW 2184 4,158 C-OCC
185LED 107 Small Room Offices 1 T 40 R F 4 (ELE) F44SE 172 0.17 SW 2184 376 C-OCC
247LED 107 Small Room Offices 2 T 40 R F 3 (MAG) F43SE 136 0.27 SW 2184 594 C-OCC
41LED Chief Room Offices 6 1B 40 R F 2 (MAG) F42SS 94 0.56 SW 2184 1,232 C-OCC
247LED 110 Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
41LED 111 Offices 11 1B 40 R F 2 (MAG) F42SS 94 1.03 SW 2184 2,258 C-OCC
185LED 111 Offices 3 T 40 R F 4 (ELE) F44SE 172 0.52 SW 2184 1,127 C-OCC
185LED Assitant Chief Offices 8 T 40 R F 4 (ELE) F44SE 172 1.38 SW 2184 3,005 C-OCC
185LED 115 Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
41LED 115 Offices 4 1B 40 R F 2 (MAG) F42SS 94 0.38 SW 2184 821 C-OCC
247LED 115 Offices 20 T 40 R F 3 (MAG) F43SE 136 2.72 SW 2184 5,940 C-OCC
185LED Men's Room Restroom 3 T 40 R F 4 (ELE) F44SE 172 0.52 SW 2184 1,127 C-OCC
185LED Women's Room Restroom 3 T 40 R F 4 (ELE) F44SE 172 0.52 SW 2184 1,127 C-OCC
5LED Receiving Room Offices 8 2T 32 R F 2 (u) (ELE) FU2LL 60 0.48 SW 2184 1,048 C-OCC
185LED Comparing Room Offices 6 T 40 R F 4 (ELE) F44SE 172 1.03 SW 2184 2,254 C-OCC
185LED Comparing Room Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
185LED Comparing Room Offices 1 T 40 R F 4 (ELE) F44SE 172 0.17 SW 2184 376 C-OCC
32LED Hallway Hallways 10 1T 32 R F 2 (ELE) F42LL 60 0.60 SW 8736 5,242 NONE
1/22/2015 Page 4, Existing
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
Existing Lighting & Audit Input $3.79 $/kW
Area Description Usage
No. of
Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space Exist Control Annual Hours Annual kWh
Field
Code
Unique description of the location - Room number/Room
name: Floor number (if applicable)
Describe Usage Type
using Operating Hours
No. of
fixtures
before the
retrofit
Lighting Fixture Code Code from Table of Standard Fixture
Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
Pre-inst. control
device
Estimated
annual hours for
the usage group
(kW/space) *
(Annual Hours)
Retrofit control
device
Notes
Retrofit
Control
EXISTING CONDITIONS
247LED 131 Offices 5 T 40 R F 3 (MAG) F43SE 136 0.68 SW 2184 1,485 C-OCC
185LED Copying Room Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
247LED Copying Room Offices 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2184 1,188 C-OCC
35LED Copying Room Offices 5 T 32 R F 3 (ELE) F43ILL/2 90 0.45 SW 2184 983 C-OCC
247LED Copying Room Offices 12 T 40 R F 3 (MAG) F43SE 136 1.63 SW 2184 3,564 C-OCC
196LED Copying Room Offices 1 W 32 C F 4 (ELE) F44ILL 112 0.11 SW 2184 245 C-OCC
247LED Copying Room Offices 14 T 40 R F 3 (MAG) F43SE 136 1.90 SW 2184 4,158 C-OCC
35LED Deeds Offices 3 T 32 R F 3 (ELE) F43ILL/2 90 0.27 SW 2184 590 C-OCC
185LED Deeds Offices 1 T 40 R F 4 (ELE) F44SE 172 0.17 SW 2184 376 C-OCC
185LED Registers Vault Offices 60 T 40 R F 4 (ELE) F44SE 172 10.32 SW 2184 22,539 C-OCC
196LED Registers Vault Offices 1 W 32 C F 4 (ELE) F44ILL 112 0.11 SW 2184 245 C-OCC
196LED Registers Vault Offices 12 W 32 C F 4 (ELE) F44ILL 112 1.34 SW 2184 2,935 C-OCC
185LED Index Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
41LED Index Offices 2 1B 40 R F 2 (MAG) F42SS 94 0.19 SW 2184 411 C-OCC
247LED Index Offices 7 T 40 R F 3 (MAG) F43SE 136 0.95 SW 2184 2,079 C-OCC
35LED Index Offices 6 T 32 R F 3 (ELE) F43ILL/2 90 0.54 SW 2184 1,179 C-OCC
41LED Basement Men's Locker Locker 11 1B 40 R F 2 (MAG) F42SS 94 1.03 SW 2184 2,258 C-OCC
32LED Closet Storage Areas 2 1T 32 R F 2 (ELE) F42LL 60 0.12 SW 2912 349 C-OCC
32LED Closet Offices 1 1T 32 R F 2 (ELE) F42LL 60 0.06 SW 2184 131 C-OCC
71 Toilet Restroom 2 I 60 I60/1 60 0.12 SW 2184 262 C-OCC
41LED Hallway Hallways 44 1B 40 R F 2 (MAG) F42SS 94 4.14 SW 8736 36,132 NONE
41LED B33 Offices 4 1B 40 R F 2 (MAG) F42SS 94 0.38 SW 2184 821 C-OCC
41LED B33 Offices 11 1B 40 R F 2 (MAG) F42SS 94 1.03 SW 2184 2,258 C-OCC
41LED B35 Offices 2 1B 40 R F 2 (MAG) F42SS 94 0.19 SW 2184 411 C-OCC
71 Mechanical Shop Storage Areas 9 I 60 I60/1 60 0.54 SW 2912 1,572 C-OCC
41LED B27 Offices 9 1B 40 R F 2 (MAG) F42SS 94 0.85 SW 2184 1,848 C-OCC
41LED B25 Offices 4 1B 40 R F 2 (MAG) F42SS 94 0.38 SW 2184 821 C-OCC
41LED B38 Offices 4 1B 40 R F 2 (MAG) F42SS 94 0.38 SW 2184 821 C-OCC
196LED B39 Offices 6 W 32 C F 4 (ELE) F44ILL 112 0.67 SW 2184 1,468 C-OCC
32LED B39A Offices 2 1T 32 R F 2 (ELE) F42LL 60 0.12 SW 2184 262 C-OCC
32LED B39A Offices 4 1T 32 R F 2 (ELE) F42LL 60 0.24 SW 2184 524 C-OCC
32LED B39A Offices 4 1T 32 R F 2 (ELE) F42LL 60 0.24 SW 2184 524 C-OCC
32LED B40 Offices 4 1T 32 R F 2 (ELE) F42LL 60 0.24 SW 2184 524 C-OCC
32LED B40 Offices 3 1T 32 R F 2 (ELE) F42LL 60 0.18 SW 2184 393 C-OCC
32LED B40 Offices 3 1T 32 R F 2 (ELE) F42LL 60 0.18 SW 2184 393 C-OCC
32LED B40 Offices 6 1T 32 R F 2 (ELE) F42LL 60 0.36 SW 2184 786 C-OCC
32LED B40 Offices 23 1T 32 R F 2 (ELE) F42LL 60 1.38 SW 2184 3,014 C-OCC
41LED B2 Offices 8 1B 40 R F 2 (MAG) F42SS 94 0.75 SW 2184 1,642 C-OCC
196LED Carpentor Shop Offices 16 W 32 C F 4 (ELE) F44ILL 112 1.79 SW 2184 3,914 C-OCC
71 B6 Offices 11 I 60 I60/1 60 0.66 SW 2184 1,441 C-OCC
71 131 Offices 2 I 60 I60/1 60 0.12 SW 2184 262 C-OCC
247LED Book Binding Offices 6 T 40 R F 3 (MAG) F43SE 136 0.82 SW 2184 1,782 C-OCC
71 B14 Offices 2 I 60 I60/1 60 0.12 SW 2184 262 C-OCC
247LED Electric Room Mechanical Room 4 T 40 R F 3 (MAG) F43SE 136 0.54 SW 2912 1,584 NONE
5LED B45 Offices 1 2T 32 R F 2 (u) (ELE) FU2LL 60 0.06 SW 2184 131 C-OCC
185LED B45 Offices 4 T 40 R F 4 (ELE) F44SE 172 0.69 SW 2184 1,503 C-OCC
71 B45 Restroom 2 I 60 I60/1 60 0.12 SW 2184 262 C-OCC
185LED B45 Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
185LED B46 Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
185LED B47 Offices 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2184 751 C-OCC
71 B48 Offices 4 I 60 I60/1 60 0.24 SW 2184 524 C-OCC
41LED B48 Offices 1 1B 40 R F 2 (MAG) F42SS 94 0.09 SW 2184 205 C-OCC
25 B48 Offices 2 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.06 SW 2184 122 C-OCC
41LED Hallway Hallways 7 1B 40 R F 2 (MAG) F42SS 94 0.66 SW 8736 5,748 NONE
41LED Mechanical Room Mechanical Room 1 1B 40 R F 2 (MAG) F42SS 94 0.09 SW 2912 274 NONE
185LED Mechanical Room Mechanical Room 1 T 40 R F 4 (ELE) F44SE 172 0.17 SW 2912 501 NONE
41LED Mechanical Room Mechanical Room 6 1B 40 R F 2 (MAG) F42SS 94 0.56 SW 2912 1,642 NONE
185LED Mechanical Room Mechanical Room 2 T 40 R F 4 (ELE) F44SE 172 0.34 SW 2912 1,002 NONE
185LED Storage Storage Areas 1 T 40 R F 4 (ELE) F44SE 172 0.17 SW 2912 501 C-OCC
32LED Hallway next to Elevator Hallways 10 1T 32 R F 2 (ELE) F42LL 60 0.60 SW 8736 5,242 NONE
SW
Total 2,475 268.23 738,066
1/22/2015 Page 5, Existing
APPENDIX C
ECM Calculations
Essex County - Hall of Records
CHA Project Number: 29142 Rate of Discount (used for NPV) 3.0%
Yearly UsageMetric Ton Carbon Dioxide
Equivalent Building Area
0.151$ $/kWh blended 0.000420205 205,696 Electric Natural Gas Fuel Oil
0.143$ $/kWh supply 3,680,750 0.000420205 555,456$ 189,604$
3.79$ $/kW 902.6 0
0.78$ $/Therm 280,832 0.00533471
Estimated 7.50$ $/kgals 0
$/Gal
Item Cost Simple Life Equivalent CO2 NJ Smart Start Direct Install Payback w/ ROI NPV IRR
Y or N kW kWh therms No. 2 Oil gal Water kgal $ Payback Expectancy (Metric tons) Incentives Eligible (Y/N) Incentives kW kWh therms kgal/yr $
Y ECM-1 Reduce the Steam Pressure from 120 Psig to 100 Psig 0.0 0 8,310 0 0 6,490 60,846$ 9.4 25 44.3 -$ N 9.4 0.0 0 207,755 0 $ 162,256 1.7 $52,170 9.6%
Y ECM-2 Replace Old RTUs with High Efficiency RTUs 5.1 8,617 0 0 0 1,464 79,800$ 54.5 15 3.6 2,925$ N 52.5 76.6 129,257 0 0 $ 23,000 (0.7) ($59,393) -12.7%
Y ECM-3 Install Window AC Units Control System 0.0 56,150 0 0 0 8,479 21,200$ 2.5 15 23.6 -$ N 2.5 0.0 842,249 0 0 $ 127,180 5.0 $80,017 39.7%
Y ECM-4 Install a Central Web-Based DDC System to Control the HVAC Equipment 0.0 26,000 5,457 0 0 8,188 305,175$ 37.3 15 40.0 -$ N 37.3 0.0 390,000 81,850 0 $ 122,815 (0.6) ($207,432) -9.7%
Y ECM-5 Replace Domestic Hot Water Heaters with Condensing DHW Heaters 0.0 0 1,333 0 0 1,041 24,698$ 23.7 15 7.1 3,000$ N 20.8 0.0 0 20,000 0 $ 15,620 (0.4) ($9,267) -3.9%
Y ECM-6 Install Walk-in Cooler/Freezer Control 0.0 9,338 0 0 0 1,410 20,625$ 14.6 15 3.9 -$ N 14.6 0.0 140,068 0 0 $ 21,150 0.0 ($3,792) 0.3%
N ECM-L1 Lighting Replacements / Upgrades 175 476,300 0 0 0 76,053 504,915$ 6.6 15 200.1 97,405$ N 5.4 2,619.5 7,144,500 0 0 $ 1,197,952 1.4 $500,407 16.9%
N ECM-L2 Install Lighting Controls (Add Occupancy Sensors) 0 100,569 0 0 0 14,381 85,860$ 6.0 15 42.3 11,130$ N 5.2 0.0 1,508,535 0 0 $ 227,789 1.7 $96,954 17.5%
Y ECM-L3 Lighting Replacements with Controls (Occupancy Sensors) 175 511,129 0 0 0 81,034 590,775$ 7.3 15 214.8 108,535$ N 6.0 2,619.5 7,666,935 0 0 $ 1,276,840 1.2 $485,134 14.6%
Total (Does Not Include ECM-L1 & ECM-L2) 179.7 611,234 15,100 0 0 $ 108,106 $ 1,103,119 10.2 16.4 337 $ 114,460 9.1 2,696 9,168,509 309,604 - $ 1,748,861 0.6 337,438 7.5%
Recommended Measures (highlighted green above) 179.7 611,234 15,100 0 0 $ 108,106 $ 1,103,119 10.2 16.4 337 $ 114,460 0 9.1 2,696 9,168,509 309,604 - $ 1,748,861 0.6 337,438 7.5%
% of Existing 20% 17% 5% 0 0
Multipliers
168 Material: 1.027
Building Auditorium Gymnasium Library Classrooms Labor: 1.246
Enthalpy Operating Occupied Occupied Occupied Occupied Equipment: 1.124Temp h (Btu/lb) Bin Hours Hours Hours Hours Hours Hours
102.5 Heating System Efficiency 70%
97.5 35.4 6 6 0 0 0 0 Cooling Eff (kW/ton) 1.3
92.5 37.4 31 31 0 0 0 0
87.5 35.0 131 131 0 0 0 0
82.5 33.0 500 500 0 0 0 0
77.5 31.5 620 620 0 0 0 0
72.5 29.9 664 664 0 0 0 0
67.5 27.2 854 854 0 0 0 0
62.5 24.0 927 927 0 0 0 0 Hours 4,427 Hrs
57.5 20.3 600 600 0 0 0 0 Weighted Avg 40 F
52.5 18.2 730 730 0 0 0 0 Avg 28 F
47.5 16.0 491 491 0 0 0 0
42.5 14.5 656 656 0 0 0 0
37.5 12.5 1,023 1,023 0 0 0 0 Hours 4,333 Hrs
32.5 10.5 734 734 0 0 0 0 Weighted Avg 68 F
27.5 8.7 334 334 0 0 0 0 Avg 78 F
22.5 7.0 252 252 0 0 0 0
17.5 5.4 125 125 0 0 0 0
12.5 3.7 47 47 0 0 0 0
7.5 2.1 34 34 0 0 0 0
2.5 1.3 1 1 0 0 0 0
-2.5
-7.5
Recommend?
Cooling
Simple Projected Lifetime Savings
Utility Costs
Essex County -Hall of Records
Annual Utility Cost
Heating
Newark, NJ
Occupied Hours/Week
City:
Savings
Essex County - Hall of Records
CHA Project Number: 29142
Essex County -Hall of Records
Notes/Comments:
3,680,750 Total Based on utility analysis
1,000,000 Lighting From Lighting Calculations 27%
600,000 Motors Estimated 16%
1,300,000 Cooling Estimated 35%
300,000 Plug Load Estimated 8%
300,000 Computers Estimated 8%
130,750 Other Remaining 4%
Notes/Comments:
280,832 Total Based on utility analysis
272,832 Boilers Therms/SF x Square Feet Served 97%
8,000 DHW Based on utility analysis 3%
Utility End Use Analysis
Electricity Use (kWh):
Natural Gas Use (Therms):
Lighting28%
Motors16%
Cooling36%
Plug Load8%
Computers
6%Other
4%
Electricity Use (kWh):
Boilers97%
DHW3%
Natural Gas End Use
Boilers
DHW
Essex County - Hall of Records
CHA Project Number: 29142
Essex County -Hall of Records
ECM-1 Reduce the Steam Pressure from 120 Psig to 100 Psig
Item Value Units
Demand Rate 0.78$ / therm
Boiler Capacity 32,307 lb/h
Existing Pressure 120.0 Psig
Existing Enthalpy 1,193.0 Btu/lb
Equivalent Full Load Hours 1,131 hrs
Boiler Efficiency 70%
Heating Capacity 32,307 lb/h
Steam Pressure 100.0 Psig
Steam Enthalpy 1,189.0 Btu/lb
Equivalent Full Load Hours 1,131 hrs
Steam Head Loss Reduction 1% Estimated
Heating Savings 8,310.18 therms
Cost Savings 6,490$
Description: This ECM evaluates reducing the steam pressure from 120 pisg down to 100 psig. According to the
boiler operator and facility staff, 50 psig is sufficient to provide the heating for the buildings the steam system
serves. However, it is recommended that a more comprehensive steam study be carried out to verify that all
components in the steam system can be running at 100psig.
Estimated
SAVINGS
Proposed Pressure
See Table Below
See Table Below
NJ Protocols
See Table Below
See Table Below
NJ Protocols
Existing Pressure
Formula/Comments
Essex County - Hall of Records
CHA Project Number: 29142 Multipliers
Essex County -Hall of Records Material: 1.03
Labor: 1.25
ECM-1 Reduce the Steam Pressure from 120 Psig to 100 Psig - Cost Equipment: 1.12
MAT. LABOR EQUIP. MAT. LABOR EQUIP.
Steam Reduction Assessment 1 EA 1,000$ 10,000$ 1,027$ 12,460$ -$ 13,487$ Estimated
Pressure Adjustment 1 EA 10,000$ 20,000$ 10,270$ 24,920$ -$ 35,190$ Estimated
-$ -$ -$ -$
48,677$ Subtotal
**Cost Estimates are for Energy Savings calculations only, do not use for procurement 12,169$ 25% Contingency
60,846$
REMARKS
Total
Description QTY UNITUNIT COSTS SUBTOTAL COSTS
TOTAL COST
Essex County - Hall of Records
CHA Project Number: 29142
Essex County -Hall of Records
ECM-2 Replace Old RTUs with High Efficiency RTUs
Equipment
Tag
Equipment
Description General Type Cooling Capacity (Btu/h) Heating Capacity (Btu/h)
LuxAire RTU HVAC 90,000
Lennex RTU HVAC 90,000
Carrier RTU HVAC 180,000
Item Value Units
Demand Rate 3.79$ / kW
Electricity Rate 0.14$ /kWh
Coincidence Factor 0.67
Conversion 3.412 btu/kW
Cooling Capacity 360,000 btu/hr btuh
Baseline EER 10.8 EERb
Proposed EER 14.0 EERq
Equivalent Full Load Hours 1,131 hrs
Demand Savings 5.10 kW
Energy Savings 8,617 kWh
Demand Savings 5.10 kW
Energy Savings 8,617 kWh
Cost Savings 1,464$
Savings calculation formulas are taken from NJ Protocols document for Electric HVAC Equipment
SAVINGS
COOLING
See Table Below
Equipment
NJ Protocols
NJ Protocols
Description: This ECM evaluates the energy savings associated with replacing older less efficient cooling equipment with modern high efficiency unitary equipment
which has the same capacity
Formula/Comments
FORMULA CONSTANTS
Essex County - Hall of Records
CHA Project Number: 29142 Multipliers
Essex County -Hall of Records Material: 1.03
Labor: 1.25
Equipment: 1.12
ECM-2 Replace Old RTUs with High Efficiency RTUs - Cost
QTY UNIT
MAT. LABOR EQUIP. MAT. LABOR EQUIP.
-$ -$ -$ -$
Crane 1 EA -$ 1,000$ 5,000$ -$ 1,246$ 5,620$ 6,866$ RS Means 2012
(2) 7.5 Ton Rooftop Unit 2 EA 9,700$ 2,750$ 19,924$ 6,853$ -$ 26,777$ RS Means 2012
- Reprogram DDC system for (1) RTU 2 EA 75$ 300$ 154$ 748$ -$ 902$ RS Means 2012
(1) 5 Ton Rooftop Unit 1 EA 8,525$ 2,000$ 8,755$ 2,492$ -$ 11,247$ RS Means 2012
- Reprogram DDC system for (1) RTU 1 EA 75$ 300$ 77$ 374$ -$ 451$ RS Means 2012
Electrical - misc. 1 LS 5,000$ 10,000$ 5,135$ 12,460$ -$ 17,595$ Estimated
63,837$ Subtotal
**Cost Estimates are for Energy Savings calculations only, do not use for procurement 15,959$ 25% Contingency
79,800$ Total
Description UNIT COSTS SUBTOTAL COSTS TOTAL
COSTREMARKS
Essex County - Hall of Records
CHA Project Number: 29142
Essex County -Hall of Records
AREA/EQUIPMENT SERVED
110 Offices 1,320,000
Total btu/h of all window A/C Units: 1,320,000 btu/h
ECM-3 Install Window AC Units Control System
Electric Cost $0.151 / kWh
Average run hours per Week 80 Hours
Space Balance Point 55 F
Space Temperature Setpoint 72 deg F
BTU/Hr Rating of existing DX equipment 1,320,000 Btu / Hr
Average EER 10.0
Existing Annual Electric Usage 122,697 kWh
Item Value Units
Proposed Annual Electric Usage 66,547 kWh
Annual Electrical Usage Savings 56,150 kWh
Annual Cost Savings $8,479
Total Project Cost $21,200
Simple Payback 3 years
OAT - DB Existing Proposed
Bin Annual Hours of hrs of
Temp F Hours Operation Operation
102.5 0 0 100% 0
97.5 6 3 100% 3
92.5 31 15 88% 13
87.5 131 62 76% 48
82.5 500 238 65% 154
77.5 620 295 53% 156
72.5 664 316 41% 130
67.5 854 0 0% 0
62.5 927 0 0% 0
57.5 600 0 0% 0
52.5 730 0 0% 0
47.5 491 0 0% 0
42.5 656 0 0% 0
37.5 1,023 0 0% 0
32.5 734 0 0% 0
27.5 334 0 0% 0
22.5 252 0 0% 0
17.5 125 0 0% 0
12.5 47 0 0% 0
7.5 34 0 0% 0
2.5 1 0 0% 0
-2.5 0 0 0% 0
-7.5 0 0 0% 0
Total 8,760 930 54% 504
COOLING
CAPACITY
(btu/h)EQUIPMENT
ASSUMPTIONS Comments
ECM Description : Window A/C units are currently controlled manually by the occupants and are not turned off when the room is unoccupied. This ECM evaluates
implementation of a digital timer device that will automatically turn the window A/C unit off at a preset time .
110 Window AC Units
Proposed % of
time of operation
Setpoint.
Total BTU/hr of DX cooling equipment to be replaced.
Comments
Unit will cycle on w/ temp of room. Possible operating time shown below
ANNUAL SAVINGS
Essex County - Hall of Records
CHA Project Number: 29142 Multipliers
Essex County -Hall of Records Material: 1.03
Labor: 1.25
ECM-3 Install Window AC Units Control System - Cost Equipment: 1.12
QTY UNIT
MAT. LABOR EQUIP. MAT. LABOR EQUIP.
0 -$ -$ -$
Window AC Controller 110 EA 150$ -$ -$ 16945.5 -$ -$ 16,946$ Estimated
-$ -$ -$ -$
16,946$ Subtotal
**Cost Estimates are for Energy Savings calculations only, do not use for procurement 4,236$ 25% Contingency
21,200$ Total
Description UNIT COSTS SUBTOTAL COSTS TOTAL
COSTREMARKS
Essex County - Hall of Records
CHA Project Number: 29142
Essex County -Hall of Records
ECM-4 Install a Central Web-Based DDC System to Control the HVAC Equipment
Building Information:
205,696 Sq Footage $0.15 $/kWh Blended
Y Cooling $0.78 $/Therm
Y Heating
3,680,750 kWh
72 F 280,832 Therms
168 hrs 1,300,000.0 kWh1
72 F 272,832 Therms2
0%
2,360 Mbtu/yr 26,000 kWh
2,360,000 Btu/hr 5,457 Therms
100 hrs
70% 26,000 kWh
5,457 Therms72 F
168 hrs Assumptions
72 F 1 35% of facility total electricity dedicated to Cooling; based on utility information
0% 2 97% of facility total natural gas dedicated to Heating; based on utility information
200 Tons 3 2%
100 hrs
10.0
0 Therms
0 kWh
5,457 Therms
26,000 kWh
72 F 8,188$ 40 hrs 305,175$
62 F 37.3 Yrs
0%
2,360 Mbtu/yr
2,360,000 Btu/hr
100 hrs
70%
72 F
168 hrs
80 F
0%
200 Tons
100 hrs
10.0
0 Therms3
0 kWh
Savings calculation formulas for setback are taken from NJ Protocols document for Occupancy Controlled Thermostats
Savings calculations for additional controls are estimated based on the level of control to be added and prior experience
Natural Gas Savings
Cooling Electricity Savings
Cooling Season Setback Temp
Cooling Season % Savings per Degree Setback
Connected Cooling Load Capacity
Equivalent Full Load Cooling Hours
Cooling Equipment EER
Cooling
Cooling Season Facility Temp
Weekly Occupied Hours
S A V I N G S
Heating Season % Savings per Degree Setback
Annual Boiler Capacity
Connected Heating Load Capacity
Equivalent Full Load Heating Hours
Heating Equipment Efficiency
Heating Existing Facility Total Electric usage
FULL DDC - TEMPERATURE SETBACK SAVINGS CALCULATION FULL DDC - ADDITIONAL CONTROLS SAVINGS CALCULATION
E X I S T I N G C O N D I T I O N S E X I S T I N G C O N D I T I O N S
Heating Season Facility Temp Existing Facility Total Gas usage
Weekly Occupied Hours Existing Facility Cooling Electric usageHeating Season Setback Temp Existing Facility Heating Natural Gas usage
Heating Season % Savings per Degree Setback P R O P O S E D C O N D I T I O N S
Annual Boiler Capacity Proposed Facility Cooling Electric Savings
Connected Heating Load Capacity Proposed Facility Natural Gas Savings
Cooling Equipment EER
S A V I N G S
Equivalent Full Load Heating Hours S A V I N G S
Heating System Efficiency Electric Savings
Cooling Natural Gas Savings
Weekly Occupied Hours
Cooling Season Setback Temp
Cooling Season % Savings per Degree Setback
Connected Cooling Load Capacity
Equivalent Full Load Cooling Hours
Iit is estimated there would be 2% savings after upgrading the system
Description: This ECM evaluates the energy savings associated with installing a central control system for the building. The central DDC system
would reset room temperature when the rooms are not occupied and have more pricise control on the temperature and valve opening positions
which results in energy savings.
Total Cost SavingsEstimated Total Project Cost
Simple Payback
Cooling Electricity Savings
COMBINED SAVINGS
Natural Gas Savings
Cooling Electricity Savings
Nighttime Setback
E X I S T I N G C O N D I T I O N S
Heating
Heating Season Facility TempWeekly Occupied Hours
Heating Season Setback Temp
Natural Gas Savings
Cooling Season Facility Temp
Essex County - Hall of Records
CHA Project Number: 29142 Multipliers
Essex County -Hall of Records Material: 1.03
Labor: 1.25
Equipment: 1.00
ECM-4 Install a Central Web-Based DDC System to Control the HVAC Equipment - Cost
MAT. LABOR EQUIP. MAT. LABOR EQUIP.
-$ -$ -$ -$
1 ea 30,000$ 50,000$ 30,810$ 62,300$ -$ 93,110$
1 ls 50,000$ 80,000$ 51,350$ 99,680$ -$ 151,030$
-$ -$ -$ -$
-$ -$ -$ -$
244,140$ Subtotal
**Cost Estimates are for Energy Savings calculations only, do not use for procurement 61,035$ 25% Contingency
305,175$
Estimated
Estimated
REMARKS
Total
TOTAL COST
Sensors
Controller & Programming
Description QTY UNITUNIT COSTS SUBTOTAL COSTS
Essex County - Hall of Records
CHA Project Number: 29142
Essex County -Hall of Records
ECM-5 Replace Domestic Hot Water Heaters with Condensing DHW Heaters
Item Value Units
Avg. Monthly Utility Demand by Water Heater 667 Therms/month
Total Annual Utility Demand by Water Heater 800,000 MBTU/yr
Existing DHW Heater Efficiency 80%
Total Annual Hot Water Demand (w/ standby losses) 640,000 MBTU/yr
Existing Tank Size 200 GallonsHot Water Piping System Capacity 5 Gallons
Hot Water Temperature 120 ˚F
Room Temperature 72 ˚FStandby Losses (% by Volume) 2.5%
Standby Losses (Heat Loss) 2.1 MBH
Annual Standby Hot Water Load 17,958 MBTU/yr
New Tank Size 200 GallonsHot Water Piping System Capacity 5 Gallons
Hot Water Temperature 120 ˚F
Room Temperature 72 ˚F
Standby Losses (% by Volume) 2.5%Standby Losses (Heat Loss) 2.1 MBH
Annual Standby Hot Water Load 17,958 MBTU/yr
Total Annual Hot Water Demand 640,000 MBTU/yr
Proposed Avg. Hot water heater efficiency 96%Proposed Fuel Use 6,667 Therns
Utility Cost $0.78 $/Therm
Existing Operating Cost of DHW $6,248 $/yr
Proposed Operating Cost of DHW $5,207 $/yr
Savings Summary:
Utility Energy Cost
Savings Savings
Therms/yr 1,333 $1,041
Estimated Per existing system (includes HWR piping)Based on A O Smith, condensing DHW Heater
( 2.5% of stored capacity per hour, per U.S. Department of Energy )
Per manufacturer nameplate
Per building personnel
Estimated Per existing system (includes HWR piping)
Based on A O Smith, condensing DHW HeaterStandby Losses and inefficient DHW heater eliminated
( 2.5% of stored capacity per hour, per U.S. Department of Energy )
Description: This ECM evaluates the energy savings associated with replacing a gas fired tank type water heater with an equivalent capacity condensing gas fired water
heater.
Calculated from utility bill
1therm = 100 MBTU
Per manufacturer nameplate
Formula/Comments
Essex County - Hall of Records
CHA Project Number: 29142 Multipliers
Essex County -Hall of Records Material: 1.03
Labor: 1.25
ECM-5 Replace Domestic Hot Water Heaters with Condensing DHW Heaters - Cost Equipment: 1.12
MAT. LABOR EQUIP. MAT. LABOR EQUIP.
DHW Heater Removal 1 LS 50$ -$ 62$ -$ 62$ RS Means 2012
High Efficiency Gas-Fired DHW Heater 1 EA 12,000$ 1,000$ 12,324$ 1,246$ -$ 13,570$ Estimated
Miscellaneous Electrical 1 LS 300$ 308$ -$ -$ 308$ RS Means 2012
Venting Kit 1 EA 450$ 650$ 462$ 810$ -$ 1,272$ RS Means 2012
Miscellaneous Piping and Valves 1 LS 2,000$ 2,000$ 2,054$ 2,492$ -$ 4,546$ Estimated
19,758$ Subtotal
**Cost Estimates are for Energy Savings calculations only, do not use for procurement 4,940$ 25% Contingency
24,698$
Description
Total
TOTAL
COSTREMARKSQTY UNIT
UNIT COSTS SUBTOTAL COSTS
Essex County - Hall of Records
CHA Project Number: 29142
Essex County -Hall of Records
ECM-6 Install Walk-in Cooler/Freezer Control
Utility Cost
$0.15 $/kWh Blended
N
1
3.3 AmpsEF
208 VoltsEF
1 PhaseEF
0.55 PFEF
8,760 hrs
65% LR
2,150 kWh kWhEF
963 kWh kWhRH
3,113 kWh
N
2
3.3
208
1
0.55
8,760 hrs
65%
4,299 kWh
1,926 kWh
6,225 kWh
9,338 kWh
1,410$
20,625$
14.6 years
Savings calculation formulas are taken from NJ Protocols document for Walk-in Controller
**Cost Estimates are for Energy Savings calculations only, do not use for procurement
Nameplate Volts of Freezer Evaporator Fan
Walk-In Freezer(s)
Walk-In Cooler(s)
Phase of Evaporator Fan
Power Factor of Evaporator Fan
Existing Freezer Controls?
Operating Hours
Load Reduction
Electricity Savings (Evaporator Fan)
Electricity Savings (Evaporator Fan Reduced Heat)
Total Walk-In Freezer(s) Electricity Savings
ECM Description :
For kitchens that contain walk-in coolers and freezers, CoolTrol is a controller that reduces energy consumption by controlling off of
dewpoint temperature. Compressor cycling is reduced and the evaporator fans run 25% to 80% less. Door and frame heaters are
also installed and controlled by store dew point temperature; this can reduce run time by up to 95% in coolers and 60% in freezers.
The evaporator fan motors are also replaced with hi-efficiency fan motors saving 40% to 70% in energy. The proposed system
comprises of an anti-sweat door controller, evaporator fan motor replacement and CoolTrol Cooler Control System.
E X I S T I N G C O N D I T I O N S
Quantity of Walk-In Freezers
Nameplate Amps of Freezer Evaporator Fan
S A V I N G S
Total Electricity Savings
Simple Payback
Total Cost Savings
Estimated Cost
Electricity Savings (Evaporator Fan Reduced Heat)
Total Walk-In Cooler(s) Electricity Savings
Phase of Evaporator Fan
Power Factor of Evaporator Fan
Operating Hours
Load Reduction
Electricity Savings (Evaporator Fan)
Nameplate Amps of Cooler Evaporator Fan
Nameplate Volts of Cooler Evaporator Fan
Existing Cooler Controls?
Quantity of Walk-In Coolers
Essex County - Hall of Records
CHA Project Number: 29142 Multipliers
Essex County -Hall of Records Material: 1.03
Labor: 1.25
ECM-6 Install Walk-in Cooler/Freezer Control - Cost Equipment: 1.12
MAT. LABOR EQUIP. MAT. LABOR EQUIP.
-$
Turnkey Walk-In Controller & Equipment 1 EA 10,000$ 5,000$ -$ 10,270$ 6,230$ -$ 16,500$
-$ -$ -$ -$
16,500$ Subtotal
**Cost Estimates are for Energy Savings calculations only, do not use for procurement 4,125$ 25% Contingency
20,625$
REMARKS
Vendor Estimate
Total
TOTAL
COSTDescription QTY UNIT
UNIT COSTS SUBTOTAL COSTS
Essex County - Hall of Records
CHA Project Number: 29142
Essex County -Hall of Records
New Jersey Pay For Performance Incentive Program
Note: The following calculation is based on the New Jersey Pay For Performance Incentive Program per April, 2012.
Building must have a minimum average electric demand of 100 kW. This minimum is waived for buildings owned by local
governements or non-profit organizations.
At a minimum, all recommended measures were used for this calculation. To qualify for P4P incentives, the following P4P requirements must be met:
- At least 15% source energy savings
- No more than 50% savings from lighting measures - Scope includes more than one measure
- Project has at least a 10% internal rate of return
- At least 50% of the source energy savings must come from investor-owned electricity and/or natural gas (note: exemption for fuel conversions)
Total Building Area (Square Feet) 205,696 $0.05 $/sqft
Is this audit funded by NJ BPU (Y/N) Yes
Board of Public Utilites (BPU)
kWh Therms
Existing Cost (from utility) $555,456 $189,604
Existing Usage (from utility) 3,680,750 280,832
Proposed Savings 611,234 15,100
Existing Total MMBtus
Proposed Savings MMBtus
% Energy Reduction
Proposed Annual Savings
$/kWh $/therm $/kWh $/therm $/kWh $/therm $/kWh $/therm
Incentive #2 $0.09 $0.90 $0.005 $0.05 $0.11 $1.25 $0.00 $0.00
Incentive #3 $0.09 $0.90 $0.005 $0.05 $0.11 $1.25 $0.00 $0.00
Elec Gas Total
Incentive #1 $0 $0 $0
Incentive #2 $0 $0 $0
Incentive #3 $0 $0 $0
Total All Incentives $0 $0 $0
Total Project Cost $1,103,119
Allowable
Incentive
% Incentives #1 of Utility Cost* 0.0% $0
% Incentives #2 of Project Cost** 0.0% $0
% Incentives #3 of Project Cost** 0.0% $0
Total Eligible Incentives*** w/o Incentives w/ Incentives
Project Cost w/ Incentives 10.2 10.2
* Maximum allowable incentive is 50% of annual utility cost if not funded by NJ BPU, and %25 if it is.
** Maximum allowable amount of Incentive #2 is 25% of total project cost.
Maximum allowable amount of Incentive #3 is 25% of total project cost.
*** Maximum allowable amount of Incentive #1 is $50,000 if not funded by NJ BPU, and $25,000 if it is.
Maximum allowable amount of Incentive #2 & #3 is $1 million per gas account and $1 million per electric account; maximum 2 million per project
$1,103,119
Max Incentive
3,596
8.8%
$108,106
Min (Savings = 15%) Increase (Savings > 15%) Achieved Incentive
Incentives $
Project Payback (years)
$0
Incentive #1
Audit is funded by NJ BPU
Annual Utilities
40,646
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
ECM-L1 Lighting Replacements $3.79 $/kW
Area Description No. of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space Exist Control Annual Hours Annual kWh Number of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space
Retrofit
Control Annual Hours Annual kWh
Annual kWh
Saved Annual kW Saved Annual $ Saved Retrofit Cost
NJ Smart Start
Lighting Incentive
Simple Payback
With Out
Incentive Simple Payback
Field Code Unique description of the location - Room number/Room
name: Floor number (if applicable)
No. of fixtures
before the retrofit
"Lighting Fixture Code" Example 2T
40 R F(U) = 2'x2' Troff 40 w Recess. Floor 2
lamps U shape
Code from Table of Standard
Fixture Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
Pre-inst.
control device
Estimated daily
hours for the
usage group
(kW/space) *
(Annual Hours)
No. of fixtures after
the retrofit
"Lighting Fixture Code" Example
2T 40 R F(U) = 2'x2' Troff 40 w
Recess. Floor 2 lamps U shape
Code from Table of
Standard Fixture
Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) *
(Number of
Fixtures)
Retrofit control
device
Estimated
annual hours
for the usage
group
(kW/space) *
(Annual
Hours)
(Original Annual
kWh) - (Retrofit
Annual kWh)
(Original Annual
kW) - (Retrofit
Annual kW)
(kWh Saved) *
($/kWh)
Cost for
renovations to
lighting system
Prescriptive
Lighting
Measures
Length of time
for renovations
cost to be
recovered
Length of time for
renovations cost to
be recovered
32LED 3rd floor Hallway 12 1T 32 R F 2 (ELE) F42LL 60 0.7 SW 8736 6,290 12 4 ft LED Tube 200732x2 30 0.4 SW 8,736 3,145 3,145 0.4 466.10$ 2,804.40$ $0 6.0 6.0
185LED 338B 8 T 40 R F 4 (ELE) F44SE 172 1.4 SW 2184 3,005 8 T 74 R LED RTLED50 50 0.4 SW 2,184 874 2,132 1.0 349.20$ 1,890.00$ $0 5.4 5.4
119 338 6 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 1.3 SW 2184 2,830 6 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 1.3 SW 2,184 2,830 - 0.0 -$ -$ $0 #DIV/0!
35LED 338 2 T 32 R F 3 (ELE) F43ILL/2 90 0.2 SW 2184 393 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 227 0.1 37.21$ 472.50$ $0 12.7 12.7
185LED 340 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
185LED 342 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
185LED 342 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
185LED 343 8 T 40 R F 4 (ELE) F44SE 172 1.4 SW 2184 3,005 8 T 74 R LED RTLED50 50 0.4 SW 2,184 874 2,132 1.0 349.20$ 1,890.00$ $0 5.4 5.4
35LED 344 3 T 32 R F 3 (ELE) F43ILL/2 90 0.3 SW 2184 590 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 341 0.2 55.82$ 708.75$ $0 12.7 12.7
185LED 345 6 T 40 R F 4 (ELE) F44SE 172 1.0 SW 2184 2,254 6 T 74 R LED RTLED50 50 0.3 SW 2,184 655 1,599 0.7 261.90$ 1,417.50$ $0 5.4 5.4
185LED 346 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
185LED 346 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
185LED 348 8 T 40 R F 4 (ELE) F44SE 172 1.4 SW 2184 3,005 8 T 74 R LED RTLED50 50 0.4 SW 2,184 874 2,132 1.0 349.20$ 1,890.00$ $0 5.4 5.4
185LED 348 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 799 0.4 130.95$ 708.75$ $0 5.4 5.4
119 347 3 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 0.6 SW 2184 1,415 3 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 0.6 SW 2,184 1,415 - 0.0 -$ -$ $0 #DIV/0!
119 347 1 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 0.2 SW 2184 472 1 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 0.2 SW 2,184 472 - 0.0 -$ -$ $0 #DIV/0!
32LED Hallway 14 1T 32 R F 2 (ELE) F42LL 60 0.8 SW 8736 7,338 14 4 ft LED Tube 200732x2 30 0.4 SW 8,736 3,669 3,669 0.4 543.79$ 3,271.80$ $0 6.0 6.0
41LED 303A 5 1B 40 R F 2 (MAG) F42SS 94 0.5 SW 2184 1,026 5 4 ft LED Tube 200732x2 30 0.2 SW 2,184 328 699 0.3 114.49$ 1,168.50$ $0 10.2 10.2
41LED Judge Chamber 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 SW 2,184 262 559 0.3 91.59$ 934.80$ $0 10.2 10.2
71 Courthouse 94 I 60 I60/1 60 5.6 SW 2125 11,985 94 CF 26 CFQ26/1-L 27 2.5 SW 2,125 5,393 6,592 3.1 1,083.70$ 634.50$ $0 0.6 0.6
41LED Courthouse 1 1B 40 R F 2 (MAG) F42SS 94 0.1 SW 2125 200 1 4 ft LED Tube 200732x2 30 0.0 SW 2,125 64 136 0.1 22.36$ 233.70$ $0 10.5 10.5
41LED 302B 5 1B 40 R F 2 (MAG) F42SS 94 0.5 SW 2184 1,026 5 4 ft LED Tube 200732x2 30 0.2 SW 2,184 328 699 0.3 114.49$ 1,168.50$ $0 10.2 10.2
247LED 304 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
41LED 304 1 1B 40 R F 2 (MAG) F42SS 94 0.1 SW 2184 205 1 4 ft LED Tube 200732x2 30 0.0 SW 2,184 66 140 0.1 22.90$ 233.70$ $0 10.2 10.2
247LED 304 1 T 40 R F 3 (MAG) F43SE 136 0.1 SW 2184 297 1 T 59 R LED RTLED38 38 0.0 SW 2,184 83 214 0.1 35.06$ 236.25$ $0 6.7 6.7
185LED 304 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
185LED 304 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
32LED Hallway 10 1T 32 R F 2 (ELE) F42LL 60 0.6 SW 8736 5,242 10 4 ft LED Tube 200732x2 30 0.3 SW 8,736 2,621 2,621 0.3 388.42$ 2,337.00$ $0 6.0 6.0
247LED 312 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
185LED Hallway 10 T 40 R F 4 (ELE) F44SE 172 1.7 SW 8736 15,026 10 T 74 R LED RTLED50 50 0.5 SW 8,736 4,368 10,658 1.2 1,579.57$ 2,362.50$ $0 1.5 1.5
185LED Mens Room 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 799 0.4 130.95$ 708.75$ $0 5.4 5.4
185LED Womens Room 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 799 0.4 130.95$ 708.75$ $0 5.4 5.4
247LED 321A 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
32LED 321A 2 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 262 2 4 ft LED Tube 200732x2 30 0.1 SW 2,184 131 131 0.1 21.47$ 467.40$ $0 21.8 21.8
247LED 321 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
247LED 322 12 T 40 R F 3 (MAG) F43SE 136 1.6 SW 2184 3,564 12 T 59 R LED RTLED38 38 0.5 SW 2,184 996 2,568 1.2 420.76$ 2,835.00$ $0 6.7 6.7
185LED Mail Room 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
185LED 325 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
185LED 325 5 T 40 R F 4 (ELE) F44SE 172 0.9 SW 2184 1,878 5 T 74 R LED RTLED50 50 0.3 SW 2,184 546 1,332 0.6 218.25$ 1,181.25$ $0 5.4 5.4
185LED 325 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
32LED Hallway 4 1T 32 R F 2 (ELE) F42LL 60 0.2 SW 8736 2,097 4 4 ft LED Tube 200732x2 30 0.1 SW 8,736 1,048 1,048 0.1 155.37$ 934.80$ $0 6.0 6.0
185LED 335 19 T 40 R F 4 (ELE) F44SE 172 3.3 SW 2184 7,137 19 T 74 R LED RTLED50 50 1.0 SW 2,184 2,075 5,063 2.3 829.36$ 4,488.75$ $0 5.4 5.4
247LED café 28 T 40 R F 3 (MAG) F43SE 136 3.8 SW 1820 6,931 28 T 59 R LED RTLED38 38 1.1 SW 1,820 1,936 4,994 2.7 838.95$ 6,615.00$ $0 7.9 7.9
185LED café 10 T 40 R F 4 (ELE) F44SE 172 1.7 SW 1820 3,130 10 T 74 R LED RTLED50 50 0.5 SW 1,820 910 2,220 1.2 373.00$ 2,362.50$ $0 6.3 6.3
247LED Café Individual Room 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 1820 495 2 T 59 R LED RTLED38 38 0.1 SW 1,820 138 357 0.2 59.93$ 472.50$ $0 7.9 7.9
185LED Café Individual Room 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 1820 626 2 T 74 R LED RTLED50 50 0.1 SW 1,820 182 444 0.2 74.60$ 472.50$ $0 6.3 6.3
196LED Hallway 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 8736 3,914 4 T 74 R LED RTLED50 50 0.2 SW 8,736 1,747 2,167 0.2 321.09$ 945.00$ $0 2.9 2.9
196LED 331 32 W 32 C F 4 (ELE) F44ILL 112 3.6 SW 2184 7,827 32 T 74 R LED RTLED50 50 1.6 SW 2,184 3,494 4,333 2.0 709.86$ 7,560.00$ $0 10.6 10.6
247LED 331 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
5LED Mens Room 1 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 SW 2184 131 1 2T XX R LED 2RTLED 25 0.0 SW 2,184 55 76 0.0 12.52$ 202.50$ $0 16.2 16.2
250 329 6 T 54 W F 3 (ELE) (T-5) F43GHL 177 1.1 SW 2184 2,319 6 T 54 W F 3 (ELE) (T-5) F43GHL 177 1.1 SW 2,184 2,319 - 0.0 -$ -$ $0 #DIV/0!
247LED 328 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
250 4th Floor 436 4 T 54 W F 3 (ELE) (T-5) F43GHL 177 0.7 SW 2184 1,546 4 T 54 W F 3 (ELE) (T-5) F43GHL 177 0.7 SW 2,184 1,546 - 0.0 -$ -$ $0 #DIV/0!
247LED 436 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
247LED Office 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 SW 2,184 664 1,712 0.8 280.51$ 1,890.00$ $0 6.7 6.7
32LED Office 1 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 131 1 4 ft LED Tube 200732x2 30 0.0 SW 2,184 66 66 0.0 10.73$ 233.70$ $0 21.8 21.8
196LED 435 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 2184 978 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 542 0.2 88.73$ 945.00$ $0 10.6 10.6
247LED 435 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
185LED Hallway 7 T 40 R F 4 (ELE) F44SE 172 1.2 SW 8736 10,518 7 T 74 R LED RTLED50 50 0.4 SW 8,736 3,058 7,461 0.9 1,105.70$ 1,653.75$ $0 1.5 1.5
247LED 438 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 SW 2,184 1,162 2,996 1.4 490.89$ 3,307.50$ $0 6.7 6.7
247LED 439 9 T 40 R F 3 (MAG) F43SE 136 1.2 SW 2184 2,673 9 T 59 R LED RTLED38 38 0.3 SW 2,184 747 1,926 0.9 315.57$ 2,126.25$ $0 6.7 6.7
247LED 439 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 439 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
247LED 443 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 SW 2,184 498 1,284 0.6 210.38$ 1,417.50$ $0 6.7 6.7
247LED 444 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 SW 2,184 1,162 2,996 1.4 490.89$ 3,307.50$ $0 6.7 6.7
185LED Hallway 10 T 40 R F 4 (ELE) F44SE 172 1.7 SW 8736 15,026 10 T 74 R LED RTLED50 50 0.5 SW 8,736 4,368 10,658 1.2 1,579.57$ 2,362.50$ $0 1.5 1.5
247LED 445 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 SW 2,184 1,162 2,996 1.4 490.89$ 3,307.50$ $0 6.7 6.7
247LED 445 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
247LED 449A 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 449A 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
247LED 449A 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
5LED 402 8 2T 32 R F 2 (u) (ELE) FU2LL 60 0.5 SW 2184 1,048 8 2T XX R LED 2RTLED 25 0.2 SW 2,184 437 612 0.3 100.18$ 1,620.00$ $0 16.2 16.2
5LED 402 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.3 SW 2184 655 5 2T XX R LED 2RTLED 25 0.1 SW 2,184 273 382 0.2 62.61$ 1,012.50$ $0 16.2 16.2
5LED 402 9 2T 32 R F 2 (u) (ELE) FU2LL 60 0.5 SW 2184 1,179 9 2T XX R LED 2RTLED 25 0.2 SW 2,184 491 688 0.3 112.70$ 1,822.50$ $0 16.2 16.2
185LED Hallway 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 8736 6,010 4 T 74 R LED RTLED50 50 0.2 SW 8,736 1,747 4,263 0.5 631.83$ 945.00$ $0 1.5 1.5
196LED Hallway 3 W 32 C F 4 (ELE) F44ILL 112 0.3 SW 8736 2,935 3 T 74 R LED RTLED50 50 0.2 SW 8,736 1,310 1,625 0.2 240.82$ 708.75$ $0 2.9 2.9
71 Hallway 2 I 60 I60/1 60 0.1 SW 8736 1,048 2 CF 26 CFQ26/1-L 27 0.1 SW 8,736 472 577 0.1 85.45$ 13.50$ $0 0.2 0.2
5LED 405 2 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 SW 2184 262 2 2T XX R LED 2RTLED 25 0.1 SW 2,184 109 153 0.1 25.05$ 405.00$ $0 16.2 16.2
25 405 1 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.0 SW 2184 61 1 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.0 SW 2,184 61 - 0.0 -$ -$ $0 #DIV/0!
5LED 405 6 2T 32 R F 2 (u) (ELE) FU2LL 60 0.4 SW 2184 786 6 2T XX R LED 2RTLED 25 0.2 SW 2,184 328 459 0.2 75.14$ 1,215.00$ $0 16.2 16.2
5LED 405 1 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 SW 2184 131 1 2T XX R LED 2RTLED 25 0.0 SW 2,184 55 76 0.0 12.52$ 202.50$ $0 16.2 16.2
196LED 405 1 W 32 C F 4 (ELE) F44ILL 112 0.1 SW 2184 245 1 T 74 R LED RTLED50 50 0.1 SW 2,184 109 135 0.1 22.18$ 236.25$ $0 10.6 10.6
5LED 405 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.3 SW 2184 655 5 2T XX R LED 2RTLED 25 0.1 SW 2,184 273 382 0.2 62.61$ 1,012.50$ $0 16.2 16.2
5LED 405 4 2T 32 R F 2 (u) (ELE) FU2LL 60 0.2 SW 2184 524 4 2T XX R LED 2RTLED 25 0.1 SW 2,184 218 306 0.1 50.09$ 810.00$ $0 16.2 16.2
5LED 405 10 2T 32 R F 2 (u) (ELE) FU2LL 60 0.6 SW 2184 1,310 10 2T XX R LED 2RTLED 25 0.3 SW 2,184 546 764 0.4 125.23$ 2,025.00$ $0 16.2 16.2
25 405 16 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.4 SW 2184 978 16 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.4 SW 2,184 978 - 0.0 -$ -$ $0 #DIV/0!
5LED 403 8 2T 32 R F 2 (u) (ELE) FU2LL 60 0.5 SW 2184 1,048 8 2T XX R LED 2RTLED 25 0.2 SW 2,184 437 612 0.3 100.18$ 1,620.00$ $0 16.2 16.2
25 403 14 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.4 SW 2184 856 14 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.4 SW 2,184 856 - 0.0 -$ -$ $0 #DIV/0!
247LED 408 15 T 40 R F 3 (MAG) F43SE 136 2.0 SW 2184 4,455 15 T 59 R LED RTLED38 38 0.6 SW 2,184 1,245 3,210 1.5 525.95$ 3,543.75$ $0 6.7 6.7
35LED 411 10 T 32 R F 3 (ELE) F43ILL/2 90 0.9 SW 2184 1,966 10 T 59 R LED RTLED38 38 0.4 SW 2,184 830 1,136 0.5 186.05$ 2,362.50$ $0 12.7 12.7
185LED 411 6 T 40 R F 4 (ELE) F44SE 172 1.0 SW 2184 2,254 6 T 74 R LED RTLED50 50 0.3 SW 2,184 655 1,599 0.7 261.90$ 1,417.50$ $0 5.4 5.4
185LED Hallway 10 T 40 R F 4 (ELE) F44SE 172 1.7 SW 8736 15,026 10 T 74 R LED RTLED50 50 0.5 SW 8,736 4,368 10,658 1.2 1,579.57$ 2,362.50$ $0 1.5 1.5
35LED 413 8 T 32 R F 3 (ELE) F43ILL/2 90 0.7 SW 2184 1,572 8 T 59 R LED RTLED38 38 0.3 SW 2,184 664 909 0.4 148.84$ 1,890.00$ $0 12.7 12.7
35LED 414 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 SW 2184 786 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 454 0.2 74.42$ 945.00$ $0 12.7 12.7
32LED 414 1 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 131 1 4 ft LED Tube 200732x2 30 0.0 SW 2,184 66 66 0.0 10.73$ 233.70$ $0 21.8 21.8
35LED 416 6 T 32 R F 3 (ELE) F43ILL/2 90 0.5 SW 2184 1,179 6 T 59 R LED RTLED38 38 0.2 SW 2,184 498 681 0.3 111.63$ 1,417.50$ $0 12.7 12.7
35LED 417A 7 T 32 R F 3 (ELE) F43ILL/2 90 0.6 SW 2184 1,376 7 T 59 R LED RTLED38 38 0.3 SW 2,184 581 795 0.4 130.24$ 1,653.75$ $0 12.7 12.7
35LED 417A 12 T 32 R F 3 (ELE) F43ILL/2 90 1.1 SW 2184 2,359 12 T 59 R LED RTLED38 38 0.5 SW 2,184 996 1,363 0.6 223.26$ 2,835.00$ $0 12.7 12.7
35LED 417A 5 T 32 R F 3 (ELE) F43ILL/2 90 0.5 SW 2184 983 5 T 59 R LED RTLED38 38 0.2 SW 2,184 415 568 0.3 93.03$ 1,181.25$ $0 12.7 12.7
35LED 417A 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 SW 2184 786 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 454 0.2 74.42$ 945.00$ $0 12.7 12.7
35LED 417A 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 SW 2184 786 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 454 0.2 74.42$ 945.00$ $0 12.7 12.7
247LED 417A 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
247LED 422A 15 T 40 R F 3 (MAG) F43SE 136 2.0 SW 2184 4,455 15 T 59 R LED RTLED38 38 0.6 SW 2,184 1,245 3,210 1.5 525.95$ 3,543.75$ $0 6.7 6.7
247LED 427D 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 SW 2,184 664 1,712 0.8 280.51$ 1,890.00$ $0 6.7 6.7
185LED Hallway 10 T 40 R F 4 (ELE) F44SE 172 1.7 SW 8736 15,026 10 T 74 R LED RTLED50 50 0.5 SW 8,736 4,368 10,658 1.2 1,579.57$ 2,362.50$ $0 1.5 1.5
35LED 428 15 T 32 R F 3 (ELE) F43ILL/2 90 1.4 SW 2184 2,948 15 T 59 R LED RTLED38 38 0.6 SW 2,184 1,245 1,704 0.8 279.08$ 3,543.75$ $0 12.7 12.7
35LED 428 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 SW 2184 786 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 454 0.2 74.42$ 945.00$ $0 12.7 12.7
35LED 428 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 SW 2184 786 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 454 0.2 74.42$ 945.00$ $0 12.7 12.7
196LED Womens Room 3 W 32 C F 4 (ELE) F44ILL 112 0.3 SW 2184 734 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 406 0.2 66.55$ 708.75$ $0 10.6 10.6
196LED Mens Room 3 W 32 C F 4 (ELE) F44ILL 112 0.3 SW 2184 734 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 406 0.2 66.55$ 708.75$ $0 10.6 10.6
32LED 5th Floor Hallway 10 1T 32 R F 2 (ELE) F42LL 60 0.6 SW 8736 5,242 10 4 ft LED Tube 200732x2 30 0.3 SW 8,736 2,621 2,621 0.3 388.42$ 2,337.00$ $0 6.0 6.0
247LED 530 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
41LED 530 1 1B 40 R F 2 (MAG) F42SS 94 0.1 SW 2184 205 1 4 ft LED Tube 200732x2 30 0.0 SW 2,184 66 140 0.1 22.90$ 233.70$ $0 10.2 10.2
247LED 530 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
196LED Womens Room 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 2184 978 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 542 0.2 88.73$ 945.00$ $0 10.6 10.6
247LED 535 10 T 40 R F 3 (MAG) F43SE 136 1.4 SW 2184 2,970 10 T 59 R LED RTLED38 38 0.4 SW 2,184 830 2,140 1.0 350.64$ 2,362.50$ $0 6.7 6.7
32LED 535 5 1T 32 R F 2 (ELE) F42LL 60 0.3 SW 2184 655 5 4 ft LED Tube 200732x2 30 0.2 SW 2,184 328 328 0.2 53.67$ 1,168.50$ $0 21.8 21.8
247LED 535 5 T 40 R F 3 (MAG) F43SE 136 0.7 SW 2184 1,485 5 T 59 R LED RTLED38 38 0.2 SW 2,184 415 1,070 0.5 175.32$ 1,181.25$ $0 6.7 6.7
185LED 535 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
185LED 535 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 799 0.4 130.95$ 708.75$ $0 5.4 5.4
185LED 535 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
247LED 524A 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
COST & SAVINGS ANALYSISRETROFIT CONDITIONSEXISTING CONDITIONS
1/22/2015 Page 6, ECM-L1
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
ECM-L1 Lighting Replacements $3.79 $/kW
Area Description No. of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space Exist Control Annual Hours Annual kWh Number of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space
Retrofit
Control Annual Hours Annual kWh
Annual kWh
Saved Annual kW Saved Annual $ Saved Retrofit Cost
NJ Smart Start
Lighting Incentive
Simple Payback
With Out
Incentive Simple Payback
Field Code Unique description of the location - Room number/Room
name: Floor number (if applicable)
No. of fixtures
before the retrofit
"Lighting Fixture Code" Example 2T
40 R F(U) = 2'x2' Troff 40 w Recess. Floor 2
lamps U shape
Code from Table of Standard
Fixture Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
Pre-inst.
control device
Estimated daily
hours for the
usage group
(kW/space) *
(Annual Hours)
No. of fixtures after
the retrofit
"Lighting Fixture Code" Example
2T 40 R F(U) = 2'x2' Troff 40 w
Recess. Floor 2 lamps U shape
Code from Table of
Standard Fixture
Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) *
(Number of
Fixtures)
Retrofit control
device
Estimated
annual hours
for the usage
group
(kW/space) *
(Annual
Hours)
(Original Annual
kWh) - (Retrofit
Annual kWh)
(Original Annual
kW) - (Retrofit
Annual kW)
(kWh Saved) *
($/kWh)
Cost for
renovations to
lighting system
Prescriptive
Lighting
Measures
Length of time
for renovations
cost to be
recovered
Length of time for
renovations cost to
be recovered
COST & SAVINGS ANALYSISRETROFIT CONDITIONSEXISTING CONDITIONS
247LED 524A 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
32LED Hallway 12 1T 32 R F 2 (ELE) F42LL 60 0.7 SW 8736 6,290 12 4 ft LED Tube 200732x2 30 0.4 SW 8,736 3,145 3,145 0.4 466.10$ 2,804.40$ $0 6.0 6.0
247LED 556 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
247LED 556 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
185LED 558 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
185LED 558 16 T 40 R F 4 (ELE) F44SE 172 2.8 SW 2184 6,010 16 T 74 R LED RTLED50 50 0.8 SW 2,184 1,747 4,263 2.0 698.41$ 3,780.00$ $0 5.4 5.4
247LED 558 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
41LED 558 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 SW 2,184 131 280 0.1 45.80$ 467.40$ $0 10.2 10.2
196LED 558 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 2184 978 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 542 0.2 88.73$ 945.00$ $0 10.6 10.6
71 558 5 I 60 I60/1 60 0.3 SW 2184 655 5 CF 26 CFQ26/1-L 27 0.1 SW 2,184 295 360 0.2 59.04$ 33.75$ $0 0.6 0.6
5LED 501A 24 2T 32 R F 2 (u) (ELE) FU2LL 60 1.4 SW 2184 3,145 24 2T XX R LED 2RTLED 25 0.6 SW 2,184 1,310 1,835 0.8 300.55$ 4,860.00$ $0 16.2 16.2
71 502 6 I 60 I60/1 60 0.4 SW 2184 786 6 CF 26 CFQ26/1-L 27 0.2 SW 2,184 354 432 0.2 70.84$ 40.50$ $0 0.6 0.6
20LED 503A 3 S 28 P F 1 (ELE) F41ILL 31 0.1 SW 2184 203 3 4 ft LED Tube 200732x1 15 0.0 SW 2,184 98 105 0.0 17.17$ 435.60$ $0 25.4 25.4
20LED 503A 2 S 28 P F 1 (ELE) F41ILL 31 0.1 SW 2184 135 2 4 ft LED Tube 200732x1 15 0.0 SW 2,184 66 70 0.0 11.45$ 290.40$ $0 25.4 25.4
20LED 503A 6 S 28 P F 1 (ELE) F41ILL 31 0.2 SW 2184 406 6 4 ft LED Tube 200732x1 15 0.1 SW 2,184 197 210 0.1 34.35$ 871.20$ $0 25.4 25.4
71 Restroom 1 I 60 I60/1 60 0.1 SW 2184 131 1 CF 26 CFQ26/1-L 27 0.0 SW 2,184 59 72 0.0 11.81$ 6.75$ $0 0.6 0.6
71 Suite 502 1 I 60 I60/1 60 0.1 SW 2184 131 1 CF 26 CFQ26/1-L 27 0.0 SW 2,184 59 72 0.0 11.81$ 6.75$ $0 0.6 0.6
71 Hallway 28 I 60 I60/1 60 1.7 SW 8736 14,676 28 CF 26 CFQ26/1-L 27 0.8 SW 8,736 6,604 8,072 0.9 1,196.33$ 189.00$ $0 0.2 0.2
196LED 504 2 W 32 C F 4 (ELE) F44ILL 112 0.2 SW 2184 489 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 271 0.1 44.37$ 472.50$ $0 10.6 10.6
196LED 504 5 W 32 C F 4 (ELE) F44ILL 112 0.6 SW 2184 1,223 5 T 74 R LED RTLED50 50 0.3 SW 2,184 546 677 0.3 110.92$ 1,181.25$ $0 10.6 10.6
5LED 508 4 2T 32 R F 2 (u) (ELE) FU2LL 60 0.2 SW 2184 524 4 2T XX R LED 2RTLED 25 0.1 SW 2,184 218 306 0.1 50.09$ 810.00$ $0 16.2 16.2
5LED 508 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.3 SW 2184 655 5 2T XX R LED 2RTLED 25 0.1 SW 2,184 273 382 0.2 62.61$ 1,012.50$ $0 16.2 16.2
71 508 2 I 60 I60/1 60 0.1 SW 2184 262 2 CF 26 CFQ26/1-L 27 0.1 SW 2,184 118 144 0.1 23.61$ 13.50$ $0 0.6 0.6
196LED 507 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 2184 978 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 542 0.2 88.73$ 945.00$ $0 10.6 10.6
196LED 507 5 W 32 C F 4 (ELE) F44ILL 112 0.6 SW 2184 1,223 5 T 74 R LED RTLED50 50 0.3 SW 2,184 546 677 0.3 110.92$ 1,181.25$ $0 10.6 10.6
196LED 507A 2 W 32 C F 4 (ELE) F44ILL 112 0.2 SW 2184 489 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 271 0.1 44.37$ 472.50$ $0 10.6 10.6
196LED 507A 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 2184 978 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 542 0.2 88.73$ 945.00$ $0 10.6 10.6
247LED 509 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
247LED 509 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 SW 2,184 498 1,284 0.6 210.38$ 1,417.50$ $0 6.7 6.7
247LED 509 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 509 1 T 40 R F 3 (MAG) F43SE 136 0.1 SW 2184 297 1 T 59 R LED RTLED38 38 0.0 SW 2,184 83 214 0.1 35.06$ 236.25$ $0 6.7 6.7
196LED 560A 6 W 32 C F 4 (ELE) F44ILL 112 0.7 SW 2184 1,468 6 T 74 R LED RTLED50 50 0.3 SW 2,184 655 812 0.4 133.10$ 1,417.50$ $0 10.6 10.6
41LED 559 1 1B 40 R F 2 (MAG) F42SS 94 0.1 SW 2184 205 1 4 ft LED Tube 200732x2 30 0.0 SW 2,184 66 140 0.1 22.90$ 233.70$ $0 10.2 10.2
247LED 554 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 SW 2,184 498 1,284 0.6 210.38$ 1,417.50$ $0 6.7 6.7
196LED 553 3 W 32 C F 4 (ELE) F44ILL 112 0.3 SW 2184 734 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 406 0.2 66.55$ 708.75$ $0 10.6 10.6
196LED 552 1 W 32 C F 4 (ELE) F44ILL 112 0.1 SW 2184 245 1 T 74 R LED RTLED50 50 0.1 SW 2,184 109 135 0.1 22.18$ 236.25$ $0 10.6 10.6
196LED 552 5 W 32 C F 4 (ELE) F44ILL 112 0.6 SW 2184 1,223 5 T 74 R LED RTLED50 50 0.3 SW 2,184 546 677 0.3 110.92$ 1,181.25$ $0 10.6 10.6
247LED 550 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 SW 2,184 664 1,712 0.8 280.51$ 1,890.00$ $0 6.7 6.7
247LED 551 7 T 40 R F 3 (MAG) F43SE 136 1.0 SW 2184 2,079 7 T 59 R LED RTLED38 38 0.3 SW 2,184 581 1,498 0.7 245.45$ 1,653.75$ $0 6.7 6.7
247LED 551 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
5LED 519 2 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 SW 2184 262 2 2T XX R LED 2RTLED 25 0.1 SW 2,184 109 153 0.1 25.05$ 405.00$ $0 16.2 16.2
5LED 519 16 2T 32 R F 2 (u) (ELE) FU2LL 60 1.0 SW 2184 2,097 16 2T XX R LED 2RTLED 25 0.4 SW 2,184 874 1,223 0.6 200.36$ 3,240.00$ $0 16.2 16.2
5LED 519 6 2T 32 R F 2 (u) (ELE) FU2LL 60 0.4 SW 2184 786 6 2T XX R LED 2RTLED 25 0.2 SW 2,184 328 459 0.2 75.14$ 1,215.00$ $0 16.2 16.2
5LED 519 7 2T 32 R F 2 (u) (ELE) FU2LL 60 0.4 SW 2184 917 7 2T XX R LED 2RTLED 25 0.2 SW 2,184 382 535 0.2 87.66$ 1,417.50$ $0 16.2 16.2
196LED 514C 6 W 32 C F 4 (ELE) F44ILL 112 0.7 SW 2184 1,468 6 T 74 R LED RTLED50 50 0.3 SW 2,184 655 812 0.4 133.10$ 1,417.50$ $0 10.6 10.6
247LED 516 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
247LED 515 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
196LED 510 1 W 32 C F 4 (ELE) F44ILL 112 0.1 SW 2184 245 1 T 74 R LED RTLED50 50 0.1 SW 2,184 109 135 0.1 22.18$ 236.25$ $0 10.6 10.6
247LED 510 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 SW 2,184 498 1,284 0.6 210.38$ 1,417.50$ $0 6.7 6.7
196LED 510 1 W 32 C F 4 (ELE) F44ILL 112 0.1 SW 2184 245 1 T 74 R LED RTLED50 50 0.1 SW 2,184 109 135 0.1 22.18$ 236.25$ $0 10.6 10.6
196LED 510 6 W 32 C F 4 (ELE) F44ILL 112 0.7 SW 2184 1,468 6 T 74 R LED RTLED50 50 0.3 SW 2,184 655 812 0.4 133.10$ 1,417.50$ $0 10.6 10.6
196LED 511 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 2184 978 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 542 0.2 88.73$ 945.00$ $0 10.6 10.6
247LED 511A 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
247LED 511 Small Offices 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
247LED 511 Small Offices 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
185LED 511 Small Offices 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
247LED 511 Small Offices 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 511 Small Offices 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
5LED 511 Small Offices 12 2T 32 R F 2 (u) (ELE) FU2LL 60 0.7 SW 2184 1,572 12 2T XX R LED 2RTLED 25 0.3 SW 2,184 655 917 0.4 150.27$ 2,430.00$ $0 16.2 16.2
32LED Hallway 10 1T 32 R F 2 (ELE) F42LL 60 0.6 SW 8736 5,242 10 4 ft LED Tube 200732x2 30 0.3 SW 8,736 2,621 2,621 0.3 388.42$ 2,337.00$ $0 6.0 6.0
247LED 549 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 549 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 SW 2,184 498 1,284 0.6 210.38$ 1,417.50$ $0 6.7 6.7
247LED 548 7 T 40 R F 3 (MAG) F43SE 136 1.0 SW 2184 2,079 7 T 59 R LED RTLED38 38 0.3 SW 2,184 581 1,498 0.7 245.45$ 1,653.75$ $0 6.7 6.7
247LED 547 5 T 40 R F 3 (MAG) F43SE 136 0.7 SW 2184 1,485 5 T 59 R LED RTLED38 38 0.2 SW 2,184 415 1,070 0.5 175.32$ 1,181.25$ $0 6.7 6.7
32LED Hallway 8 1T 32 R F 2 (ELE) F42LL 60 0.5 SW 8736 4,193 8 4 ft LED Tube 200732x2 30 0.2 SW 8,736 2,097 2,097 0.2 310.73$ 1,869.60$ $0 6.0 6.0
247LED 536 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 536 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 537 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
247LED 537 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
247LED 546 7 T 40 R F 3 (MAG) F43SE 136 1.0 SW 2184 2,079 7 T 59 R LED RTLED38 38 0.3 SW 2,184 581 1,498 0.7 245.45$ 1,653.75$ $0 6.7 6.7
247LED 546 7 T 40 R F 3 (MAG) F43SE 136 1.0 SW 2184 2,079 7 T 59 R LED RTLED38 38 0.3 SW 2,184 581 1,498 0.7 245.45$ 1,653.75$ $0 6.7 6.7
247LED 544 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 544 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 543 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 SW 2,184 664 1,712 0.8 280.51$ 1,890.00$ $0 6.7 6.7
247LED 542 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 SW 2,184 498 1,284 0.6 210.38$ 1,417.50$ $0 6.7 6.7
247LED 542 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
35LED 542 6 T 32 R F 3 (ELE) F43ILL/2 90 0.5 SW 2184 1,179 6 T 59 R LED RTLED38 38 0.2 SW 2,184 498 681 0.3 111.63$ 1,417.50$ $0 12.7 12.7
247LED 542 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 SW 2,184 664 1,712 0.8 280.51$ 1,890.00$ $0 6.7 6.7
247LED 542 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 539 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 539 23 T 40 R F 3 (MAG) F43SE 136 3.1 SW 2184 6,832 23 T 59 R LED RTLED38 38 0.9 SW 2,184 1,909 4,923 2.3 806.46$ 5,433.75$ $0 6.7 6.7
185LED 2nd Floor 201 6 T 40 R F 4 (ELE) F44SE 172 1.0 SW 2184 2,254 6 T 74 R LED RTLED50 50 0.3 SW 2,184 655 1,599 0.7 261.90$ 1,417.50$ $0 5.4 5.4
247LED 202 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 SW 2,184 1,162 2,996 1.4 490.89$ 3,307.50$ $0 6.7 6.7
185LED 202 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
247LED 204 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 205 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 205 next 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
247LED 205 next 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
185LED 206 12 T 40 R F 4 (ELE) F44SE 172 2.1 SW 2184 4,508 12 T 74 R LED RTLED50 50 0.6 SW 2,184 1,310 3,197 1.5 523.81$ 2,835.00$ $0 5.4 5.4
41LED 207 6 1B 40 R F 2 (MAG) F42SS 94 0.6 SW 2184 1,232 6 4 ft LED Tube 200732x2 30 0.2 SW 2,184 393 839 0.4 137.39$ 1,402.20$ $0 10.2 10.2
247LED 208 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
41LED 208 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 SW 2,184 131 280 0.1 45.80$ 467.40$ $0 10.2 10.2
247LED 209 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
41LED 209 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 SW 2,184 131 280 0.1 45.80$ 467.40$ $0 10.2 10.2
5LED 211 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.3 SW 2184 655 5 2T XX R LED 2RTLED 25 0.1 SW 2,184 273 382 0.2 62.61$ 1,012.50$ $0 16.2 16.2
25 213 10 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.3 SW 2184 612 10 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.3 SW 2,184 612 - 0.0 -$ -$ $0 #DIV/0!
185LED 213 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2184 376 1 T 74 R LED RTLED50 50 0.1 SW 2,184 109 266 0.1 43.65$ 236.25$ $0 5.4 5.4
25 214 6 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.2 SW 2184 367 6 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.2 SW 2,184 367 - 0.0 -$ -$ $0 #DIV/0!
185LED 214 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2184 376 1 T 74 R LED RTLED50 50 0.1 SW 2,184 109 266 0.1 43.65$ 236.25$ $0 5.4 5.4
247LED 215 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
185LED 216 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
247LED 217 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
41LED 217 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 SW 2,184 131 280 0.1 45.80$ 467.40$ $0 10.2 10.2
41LED 219 19 1B 40 R F 2 (MAG) F42SS 94 1.8 SW 2184 3,901 19 4 ft LED Tube 200732x2 30 0.6 SW 2,184 1,245 2,656 1.2 435.08$ 4,440.30$ $0 10.2 10.2
41LED 220 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 SW 2,184 262 559 0.3 91.59$ 934.80$ $0 10.2 10.2
185LED 222 30 T 40 R F 4 (ELE) F44SE 172 5.2 SW 2184 11,269 30 T 74 R LED RTLED50 50 1.5 SW 2,184 3,276 7,993 3.7 1,309.52$ 7,087.50$ $0 5.4 5.4
196LED Men's Room 3 W 32 C F 4 (ELE) F44ILL 112 0.3 SW 2184 734 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 406 0.2 66.55$ 708.75$ $0 10.6 10.6
196LED Women's Room 3 W 32 C F 4 (ELE) F44ILL 112 0.3 SW 2184 734 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 406 0.2 66.55$ 708.75$ $0 10.6 10.6
32LED Service Room 2 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 262 2 4 ft LED Tube 200732x2 30 0.1 SW 2,184 131 131 0.1 21.47$ 467.40$ $0 21.8 21.8
185LED 226 7 T 40 R F 4 (ELE) F44SE 172 1.2 SW 2184 2,630 7 T 74 R LED RTLED50 50 0.4 SW 2,184 764 1,865 0.9 305.55$ 1,653.75$ $0 5.4 5.4
32LED 226 1 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 131 1 4 ft LED Tube 200732x2 30 0.0 SW 2,184 66 66 0.0 10.73$ 233.70$ $0 21.8 21.8
185LED 226 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
247LED 227 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 SW 2,184 664 1,712 0.8 280.51$ 1,890.00$ $0 6.7 6.7
185LED 228 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 799 0.4 130.95$ 708.75$ $0 5.4 5.4
247LED 231 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
185LED 231 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
41LED 232 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 SW 2,184 262 559 0.3 91.59$ 934.80$ $0 10.2 10.2
247LED 232 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 SW 2,184 664 1,712 0.8 280.51$ 1,890.00$ $0 6.7 6.7
41LED 233 5 1B 40 R F 2 (MAG) F42SS 94 0.5 SW 2184 1,026 5 4 ft LED Tube 200732x2 30 0.2 SW 2,184 328 699 0.3 114.49$ 1,168.50$ $0 10.2 10.2
247LED 233 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 SW 2,184 1,162 2,996 1.4 490.89$ 3,307.50$ $0 6.7 6.7
71 233 Storage 2 I 60 I60/1 60 0.1 SW 2912 349 2 CF 26 CFQ26/1-L 27 0.1 SW 2,912 157 192 0.1 30.49$ 13.50$ $0 0.4 0.4
185LED 236 19 T 40 R F 4 (ELE) F44SE 172 3.3 SW 2184 7,137 19 T 74 R LED RTLED50 50 1.0 SW 2,184 2,075 5,063 2.3 829.36$ 4,488.75$ $0 5.4 5.4
1/22/2015 Page 7, ECM-L1
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
ECM-L1 Lighting Replacements $3.79 $/kW
Area Description No. of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space Exist Control Annual Hours Annual kWh Number of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space
Retrofit
Control Annual Hours Annual kWh
Annual kWh
Saved Annual kW Saved Annual $ Saved Retrofit Cost
NJ Smart Start
Lighting Incentive
Simple Payback
With Out
Incentive Simple Payback
Field Code Unique description of the location - Room number/Room
name: Floor number (if applicable)
No. of fixtures
before the retrofit
"Lighting Fixture Code" Example 2T
40 R F(U) = 2'x2' Troff 40 w Recess. Floor 2
lamps U shape
Code from Table of Standard
Fixture Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
Pre-inst.
control device
Estimated daily
hours for the
usage group
(kW/space) *
(Annual Hours)
No. of fixtures after
the retrofit
"Lighting Fixture Code" Example
2T 40 R F(U) = 2'x2' Troff 40 w
Recess. Floor 2 lamps U shape
Code from Table of
Standard Fixture
Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) *
(Number of
Fixtures)
Retrofit control
device
Estimated
annual hours
for the usage
group
(kW/space) *
(Annual
Hours)
(Original Annual
kWh) - (Retrofit
Annual kWh)
(Original Annual
kW) - (Retrofit
Annual kW)
(kWh Saved) *
($/kWh)
Cost for
renovations to
lighting system
Prescriptive
Lighting
Measures
Length of time
for renovations
cost to be
recovered
Length of time for
renovations cost to
be recovered
COST & SAVINGS ANALYSISRETROFIT CONDITIONSEXISTING CONDITIONS
185LED 238 15 T 40 R F 4 (ELE) F44SE 172 2.6 SW 2184 5,635 15 T 74 R LED RTLED50 50 0.8 SW 2,184 1,638 3,997 1.8 654.76$ 3,543.75$ $0 5.4 5.4
185LED 242 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
247LED 242 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
32LED 242 6 1T 32 R F 2 (ELE) F42LL 60 0.4 SW 2184 786 6 4 ft LED Tube 200732x2 30 0.2 SW 2,184 393 393 0.2 64.40$ 1,402.20$ $0 21.8 21.8
196LED lobby 2 W 32 C F 4 (ELE) F44ILL 112 0.2 SW 8736 1,957 2 T 74 R LED RTLED50 50 0.1 SW 8,736 874 1,083 0.1 160.55$ 472.50$ $0 2.9 2.9
247LED 244 12 T 40 R F 3 (MAG) F43SE 136 1.6 SW 2184 3,564 12 T 59 R LED RTLED38 38 0.5 SW 2,184 996 2,568 1.2 420.76$ 2,835.00$ $0 6.7 6.7
41LED 244 6 1B 40 R F 2 (MAG) F42SS 94 0.6 SW 2184 1,232 6 4 ft LED Tube 200732x2 30 0.2 SW 2,184 393 839 0.4 137.39$ 1,402.20$ $0 10.2 10.2
41LED Attendent 5 1B 40 R F 2 (MAG) F42SS 94 0.5 SW 2184 1,026 5 4 ft LED Tube 200732x2 30 0.2 SW 2,184 328 699 0.3 114.49$ 1,168.50$ $0 10.2 10.2
41LED 247 155 1B 40 R F 2 (MAG) F42SS 94 14.6 SW 2184 31,821 155 4 ft LED Tube 200732x2 30 4.7 SW 2,184 10,156 21,665 9.9 3,549.30$ 36,223.50$ $0 10.2 10.2
247LED 247 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 642 0.3 105.19$ 708.75$ $0 6.7 6.7
41LED 247 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 SW 2,184 262 559 0.3 91.59$ 934.80$ $0 10.2 10.2
5LED 248 66 2T 32 R F 2 (u) (ELE) FU2LL 60 4.0 SW 2184 8,649 66 2T XX R LED 2RTLED 25 1.7 SW 2,184 3,604 5,045 2.3 826.50$ 13,365.00$ $0 16.2 16.2
5LED 248 66 2T 32 R F 2 (u) (ELE) FU2LL 60 4.0 SW 2184 8,649 66 2T XX R LED 2RTLED 25 1.7 SW 2,184 3,604 5,045 2.3 826.50$ 13,365.00$ $0 16.2 16.2
196LED 248 45 W 32 C F 4 (ELE) F44ILL 112 5.0 SW 2184 11,007 45 T 74 R LED RTLED50 50 2.3 SW 2,184 4,914 6,093 2.8 998.24$ 10,631.25$ $0 10.6 10.6
196LED 248 2 W 32 C F 4 (ELE) F44ILL 112 0.2 SW 2184 489 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 271 0.1 44.37$ 472.50$ $0 10.6 10.6
196LED 248 2 W 32 C F 4 (ELE) F44ILL 112 0.2 SW 2184 489 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 271 0.1 44.37$ 472.50$ $0 10.6 10.6
35LED 1st Floor 101 29 T 32 R F 3 (ELE) F43ILL/2 90 2.6 SW 2184 5,700 29 T 59 R LED RTLED38 38 1.1 SW 2,184 2,407 3,293 1.5 539.55$ 6,851.25$ $0 12.7 12.7
35LED 102 5 T 32 R F 3 (ELE) F43ILL/2 90 0.5 SW 2184 983 5 T 59 R LED RTLED38 38 0.2 SW 2,184 415 568 0.3 93.03$ 1,181.25$ $0 12.7 12.7
41LED 103 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 SW 2,184 131 280 0.1 45.80$ 467.40$ $0 10.2 10.2
185LED 104 8 T 40 R F 4 (ELE) F44SE 172 1.4 SW 2184 3,005 8 T 74 R LED RTLED50 50 0.4 SW 2,184 874 2,132 1.0 349.20$ 1,890.00$ $0 5.4 5.4
71 Entrance Hall 16 I 60 I60/1 60 1.0 SW 8736 8,387 16 CF 26 CFQ26/1-L 27 0.4 SW 8,736 3,774 4,613 0.5 683.62$ 108.00$ $0 0.2 0.2
71 Entrance Hall 36 I 60 I60/1 60 2.2 SW 2184 4,717 36 CF 26 CFQ26/1-L 27 1.0 SW 2,184 2,123 2,595 1.2 425.06$ 243.00$ $0 0.6 0.6
247LED 107 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 SW 2,184 1,162 2,996 1.4 490.89$ 3,307.50$ $0 6.7 6.7
185LED 107 Small Room 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2184 376 1 T 74 R LED RTLED50 50 0.1 SW 2,184 109 266 0.1 43.65$ 236.25$ $0 5.4 5.4
247LED 107 Small Room 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 SW 2,184 166 428 0.2 70.13$ 472.50$ $0 6.7 6.7
41LED Chief Room 6 1B 40 R F 2 (MAG) F42SS 94 0.6 SW 2184 1,232 6 4 ft LED Tube 200732x2 30 0.2 SW 2,184 393 839 0.4 137.39$ 1,402.20$ $0 10.2 10.2
247LED 110 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
41LED 111 11 1B 40 R F 2 (MAG) F42SS 94 1.0 SW 2184 2,258 11 4 ft LED Tube 200732x2 30 0.3 SW 2,184 721 1,538 0.7 251.89$ 2,570.70$ $0 10.2 10.2
185LED 111 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 799 0.4 130.95$ 708.75$ $0 5.4 5.4
185LED Assitant Chief 8 T 40 R F 4 (ELE) F44SE 172 1.4 SW 2184 3,005 8 T 74 R LED RTLED50 50 0.4 SW 2,184 874 2,132 1.0 349.20$ 1,890.00$ $0 5.4 5.4
185LED 115 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
41LED 115 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 SW 2,184 262 559 0.3 91.59$ 934.80$ $0 10.2 10.2
247LED 115 20 T 40 R F 3 (MAG) F43SE 136 2.7 SW 2184 5,940 20 T 59 R LED RTLED38 38 0.8 SW 2,184 1,660 4,281 2.0 701.27$ 4,725.00$ $0 6.7 6.7
185LED Men's Room 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 799 0.4 130.95$ 708.75$ $0 5.4 5.4
185LED Women's Room 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 SW 2,184 328 799 0.4 130.95$ 708.75$ $0 5.4 5.4
5LED Receiving Room 8 2T 32 R F 2 (u) (ELE) FU2LL 60 0.5 SW 2184 1,048 8 2T XX R LED 2RTLED 25 0.2 SW 2,184 437 612 0.3 100.18$ 1,620.00$ $0 16.2 16.2
185LED Comparing Room 6 T 40 R F 4 (ELE) F44SE 172 1.0 SW 2184 2,254 6 T 74 R LED RTLED50 50 0.3 SW 2,184 655 1,599 0.7 261.90$ 1,417.50$ $0 5.4 5.4
185LED Comparing Room 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
185LED Comparing Room 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2184 376 1 T 74 R LED RTLED50 50 0.1 SW 2,184 109 266 0.1 43.65$ 236.25$ $0 5.4 5.4
32LED Hallway 10 1T 32 R F 2 (ELE) F42LL 60 0.6 SW 8736 5,242 10 4 ft LED Tube 200732x2 30 0.3 SW 8,736 2,621 2,621 0.3 388.42$ 2,337.00$ $0 6.0 6.0
247LED 131 5 T 40 R F 3 (MAG) F43SE 136 0.7 SW 2184 1,485 5 T 59 R LED RTLED38 38 0.2 SW 2,184 415 1,070 0.5 175.32$ 1,181.25$ $0 6.7 6.7
185LED Copying Room 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
247LED Copying Room 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 SW 2,184 332 856 0.4 140.25$ 945.00$ $0 6.7 6.7
35LED Copying Room 5 T 32 R F 3 (ELE) F43ILL/2 90 0.5 SW 2184 983 5 T 59 R LED RTLED38 38 0.2 SW 2,184 415 568 0.3 93.03$ 1,181.25$ $0 12.7 12.7
247LED Copying Room 12 T 40 R F 3 (MAG) F43SE 136 1.6 SW 2184 3,564 12 T 59 R LED RTLED38 38 0.5 SW 2,184 996 2,568 1.2 420.76$ 2,835.00$ $0 6.7 6.7
196LED Copying Room 1 W 32 C F 4 (ELE) F44ILL 112 0.1 SW 2184 245 1 T 74 R LED RTLED50 50 0.1 SW 2,184 109 135 0.1 22.18$ 236.25$ $0 10.6 10.6
247LED Copying Room 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 SW 2,184 1,162 2,996 1.4 490.89$ 3,307.50$ $0 6.7 6.7
35LED Deeds 3 T 32 R F 3 (ELE) F43ILL/2 90 0.3 SW 2184 590 3 T 59 R LED RTLED38 38 0.1 SW 2,184 249 341 0.2 55.82$ 708.75$ $0 12.7 12.7
185LED Deeds 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2184 376 1 T 74 R LED RTLED50 50 0.1 SW 2,184 109 266 0.1 43.65$ 236.25$ $0 5.4 5.4
185LED Registers Vault 60 T 40 R F 4 (ELE) F44SE 172 10.3 SW 2184 22,539 60 T 74 R LED RTLED50 50 3.0 SW 2,184 6,552 15,987 7.3 2,619.04$ 14,175.00$ $0 5.4 5.4
196LED Registers Vault 1 W 32 C F 4 (ELE) F44ILL 112 0.1 SW 2184 245 1 T 74 R LED RTLED50 50 0.1 SW 2,184 109 135 0.1 22.18$ 236.25$ $0 10.6 10.6
196LED Registers Vault 12 W 32 C F 4 (ELE) F44ILL 112 1.3 SW 2184 2,935 12 T 74 R LED RTLED50 50 0.6 SW 2,184 1,310 1,625 0.7 266.20$ 2,835.00$ $0 10.6 10.6
185LED Index 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
41LED Index 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 SW 2,184 131 280 0.1 45.80$ 467.40$ $0 10.2 10.2
247LED Index 7 T 40 R F 3 (MAG) F43SE 136 1.0 SW 2184 2,079 7 T 59 R LED RTLED38 38 0.3 SW 2,184 581 1,498 0.7 245.45$ 1,653.75$ $0 6.7 6.7
35LED Index 6 T 32 R F 3 (ELE) F43ILL/2 90 0.5 SW 2184 1,179 6 T 59 R LED RTLED38 38 0.2 SW 2,184 498 681 0.3 111.63$ 1,417.50$ $0 12.7 12.7
41LED Basement Men's Locker 11 1B 40 R F 2 (MAG) F42SS 94 1.0 SW 2184 2,258 11 4 ft LED Tube 200732x2 30 0.3 SW 2,184 721 1,538 0.7 251.89$ 2,570.70$ $0 10.2 10.2
32LED Closet 2 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2912 349 2 4 ft LED Tube 200732x2 30 0.1 SW 2,912 175 175 0.1 27.71$ 467.40$ $0 16.9 16.9
32LED Closet 1 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 131 1 4 ft LED Tube 200732x2 30 0.0 SW 2,184 66 66 0.0 10.73$ 233.70$ $0 21.8 21.8
71 Toilet 2 I 60 I60/1 60 0.1 SW 2184 262 2 CF 26 CFQ26/1-L 27 0.1 SW 2,184 118 144 0.1 23.61$ 13.50$ $0 0.6 0.6
41LED Hallway 44 1B 40 R F 2 (MAG) F42SS 94 4.1 SW 8736 36,132 44 4 ft LED Tube 200732x2 30 1.3 SW 8,736 11,532 24,601 2.8 3,645.95$ 10,282.80$ $0 2.8 2.8
41LED B33 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 SW 2,184 262 559 0.3 91.59$ 934.80$ $0 10.2 10.2
41LED B33 11 1B 40 R F 2 (MAG) F42SS 94 1.0 SW 2184 2,258 11 4 ft LED Tube 200732x2 30 0.3 SW 2,184 721 1,538 0.7 251.89$ 2,570.70$ $0 10.2 10.2
41LED B35 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 SW 2,184 131 280 0.1 45.80$ 467.40$ $0 10.2 10.2
71 Mechanical Shop 9 I 60 I60/1 60 0.5 SW 2912 1,572 9 CF 26 CFQ26/1-L 27 0.2 SW 2,912 708 865 0.3 137.18$ 60.75$ $0 0.4 0.4
41LED B27 9 1B 40 R F 2 (MAG) F42SS 94 0.8 SW 2184 1,848 9 4 ft LED Tube 200732x2 30 0.3 SW 2,184 590 1,258 0.6 206.09$ 2,103.30$ $0 10.2 10.2
41LED B25 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 SW 2,184 262 559 0.3 91.59$ 934.80$ $0 10.2 10.2
41LED B38 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 SW 2,184 262 559 0.3 91.59$ 934.80$ $0 10.2 10.2
196LED B39 6 W 32 C F 4 (ELE) F44ILL 112 0.7 SW 2184 1,468 6 T 74 R LED RTLED50 50 0.3 SW 2,184 655 812 0.4 133.10$ 1,417.50$ $0 10.6 10.6
32LED B39A 2 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 262 2 4 ft LED Tube 200732x2 30 0.1 SW 2,184 131 131 0.1 21.47$ 467.40$ $0 21.8 21.8
32LED B39A 4 1T 32 R F 2 (ELE) F42LL 60 0.2 SW 2184 524 4 4 ft LED Tube 200732x2 30 0.1 SW 2,184 262 262 0.1 42.94$ 934.80$ $0 21.8 21.8
32LED B39A 4 1T 32 R F 2 (ELE) F42LL 60 0.2 SW 2184 524 4 4 ft LED Tube 200732x2 30 0.1 SW 2,184 262 262 0.1 42.94$ 934.80$ $0 21.8 21.8
32LED B40 4 1T 32 R F 2 (ELE) F42LL 60 0.2 SW 2184 524 4 4 ft LED Tube 200732x2 30 0.1 SW 2,184 262 262 0.1 42.94$ 934.80$ $0 21.8 21.8
32LED B40 3 1T 32 R F 2 (ELE) F42LL 60 0.2 SW 2184 393 3 4 ft LED Tube 200732x2 30 0.1 SW 2,184 197 197 0.1 32.20$ 701.10$ $0 21.8 21.8
32LED B40 3 1T 32 R F 2 (ELE) F42LL 60 0.2 SW 2184 393 3 4 ft LED Tube 200732x2 30 0.1 SW 2,184 197 197 0.1 32.20$ 701.10$ $0 21.8 21.8
32LED B40 6 1T 32 R F 2 (ELE) F42LL 60 0.4 SW 2184 786 6 4 ft LED Tube 200732x2 30 0.2 SW 2,184 393 393 0.2 64.40$ 1,402.20$ $0 21.8 21.8
32LED B40 23 1T 32 R F 2 (ELE) F42LL 60 1.4 SW 2184 3,014 23 4 ft LED Tube 200732x2 30 0.7 SW 2,184 1,507 1,507 0.7 246.88$ 5,375.10$ $0 21.8 21.8
41LED B2 8 1B 40 R F 2 (MAG) F42SS 94 0.8 SW 2184 1,642 8 4 ft LED Tube 200732x2 30 0.2 SW 2,184 524 1,118 0.5 183.19$ 1,869.60$ $0 10.2 10.2
196LED Carpentor Shop 16 W 32 C F 4 (ELE) F44ILL 112 1.8 SW 2184 3,914 16 T 74 R LED RTLED50 50 0.8 SW 2,184 1,747 2,167 1.0 354.93$ 3,780.00$ $0 10.6 10.6
71 B6 11 I 60 I60/1 60 0.7 SW 2184 1,441 11 CF 26 CFQ26/1-L 27 0.3 SW 2,184 649 793 0.4 129.88$ 74.25$ $0 0.6 0.6
71 131 2 I 60 I60/1 60 0.1 SW 2184 262 2 CF 26 CFQ26/1-L 27 0.1 SW 2,184 118 144 0.1 23.61$ 13.50$ $0 0.6 0.6
247LED Book Binding 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 SW 2,184 498 1,284 0.6 210.38$ 1,417.50$ $0 6.7 6.7
71 B14 2 I 60 I60/1 60 0.1 SW 2184 262 2 CF 26 CFQ26/1-L 27 0.1 SW 2,184 118 144 0.1 23.61$ 13.50$ $0 0.6 0.6
247LED Electric Room 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2912 1,584 4 T 59 R LED RTLED38 38 0.2 SW 2,912 443 1,142 0.4 181.06$ 945.00$ $0 5.2 5.2
5LED B45 1 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 SW 2184 131 1 2T XX R LED 2RTLED 25 0.0 SW 2,184 55 76 0.0 12.52$ 202.50$ $0 16.2 16.2
185LED B45 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 SW 2,184 437 1,066 0.5 174.60$ 945.00$ $0 5.4 5.4
71 B45 2 I 60 I60/1 60 0.1 SW 2184 262 2 CF 26 CFQ26/1-L 27 0.1 SW 2,184 118 144 0.1 23.61$ 13.50$ $0 0.6 0.6
185LED B45 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
185LED B46 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
185LED B47 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 SW 2,184 218 533 0.2 87.30$ 472.50$ $0 5.4 5.4
71 B48 4 I 60 I60/1 60 0.2 SW 2184 524 4 CF 26 CFQ26/1-L 27 0.1 SW 2,184 236 288 0.1 47.23$ 27.00$ $0 0.6 0.6
41LED B48 1 1B 40 R F 2 (MAG) F42SS 94 0.1 SW 2184 205 1 4 ft LED Tube 200732x2 30 0.0 SW 2,184 66 140 0.1 22.90$ 233.70$ $0 10.2 10.2
25 B48 2 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.1 SW 2184 122 2 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.1 SW 2,184 122 - 0.0 -$ -$ $0 #DIV/0!
41LED Hallway 7 1B 40 R F 2 (MAG) F42SS 94 0.7 SW 8736 5,748 7 4 ft LED Tube 200732x2 30 0.2 SW 8,736 1,835 3,914 0.4 580.04$ 1,635.90$ $0 2.8 2.8
41LED Mechanical Room 1 1B 40 R F 2 (MAG) F42SS 94 0.1 SW 2912 274 1 4 ft LED Tube 200732x2 30 0.0 SW 2,912 87 186 0.1 29.56$ 233.70$ $0 7.9 7.9
185LED Mechanical Room 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2912 501 1 T 74 R LED RTLED50 50 0.1 SW 2,912 146 355 0.1 56.35$ 236.25$ $0 4.2 4.2
41LED Mechanical Room 6 1B 40 R F 2 (MAG) F42SS 94 0.6 SW 2912 1,642 6 4 ft LED Tube 200732x2 30 0.2 SW 2,912 524 1,118 0.4 177.37$ 1,402.20$ $0 7.9 7.9
185LED Mechanical Room 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2912 1,002 2 T 74 R LED RTLED50 50 0.1 SW 2,912 291 711 0.2 112.70$ 472.50$ $0 4.2 4.2
185LED Storage 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2912 501 1 T 74 R LED RTLED50 50 0.1 SW 2,912 146 355 0.1 56.35$ 236.25$ $0 4.2 4.2
32LED Hallway next to Elevator 10 1T 32 R F 2 (ELE) F42LL 60 0.6 SW 8736 5,242 10 4 ft LED Tube 200732x2 30 0.3 SW 8,736 2,621 2,621 0.3 388.42$ 2,337.00$ $0 6.0 6.0
SW SW
Total 2,475 268.2 738,066 2,475 13,973 93.6 261,765 476,300 174.6 $76,053 $504,915 $0
174.6 $7,942Demand Savings
1/22/2015 Page 8, ECM-L1
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
ECM-L2 Install Occupancy Sensors $3.79 $/kW
Area Description No. of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space kW/Space Retrofit Control Annual Hours Annual kWh
Annual kWh
Saved Annual kW Saved Annual $ Saved Retrofit Cost
NJ Smart Start
Lighting
Incentive
Simple Payback
With Out
Incentive Simple Payback
Field Code Unique description of the location - Room number/Room
name: Floor number (if applicable)
No. of fixtures
before the retrofit
Lighting Fixture Code Code from Table of Standard
Fixture Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
(Watts/Fixt) *
(Number of
Fixtures)
Retrofit control
device
Estimated
annual hours for
the usage group
(kW/space) *
(Annual Hours)
(Original Annual
kWh) - (Retrofit
Annual kWh)
(Original Annual
kW) - (Retrofit
Annual kW)
(kW Saved) *
($/kWh)
Cost for
renovations to
lighting system
Length of time
for renovations
cost to be
recovered
Length of time for
renovations cost to
be recovered
32LED 3rd floor Hallway 12 1T 32 R F 2 (ELE) F42LL 60 0.7 0.7 NONE 8736 6,289.9 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
185LED 338B 8 T 40 R F 4 (ELE) F44SE 172 1.4 1.4 NONE 2184 3,005.2 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
119 338 6 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 1.3 1.3 C-OCC 1747.2 2,264.4 566.1 0.0 $80.95 $270.00 $35.00 3.3 2.9
35LED 338 2 T 32 R F 3 (ELE) F43ILL/2 90 0.2 0.2 C-OCC 1747.2 314.5 78.6 0.0 $11.24 $270.00 $35.00 24.0 20.9
185LED 340 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
185LED 342 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
185LED 342 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
185LED 343 8 T 40 R F 4 (ELE) F44SE 172 1.4 1.4 C-OCC 1747.2 2,404.1 601.0 0.0 $85.95 $270.00 $35.00 3.1 2.7
35LED 344 3 T 32 R F 3 (ELE) F43ILL/2 90 0.3 0.3 C-OCC 1747.2 471.7 117.9 0.0 $16.86 $270.00 $35.00 16.0 13.9
185LED 345 6 T 40 R F 4 (ELE) F44SE 172 1.0 1.0 C-OCC 1747.2 1,803.1 450.8 0.0 $64.46 $270.00 $35.00 4.2 3.6
185LED 346 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
185LED 346 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
185LED 348 8 T 40 R F 4 (ELE) F44SE 172 1.4 1.4 C-OCC 1747.2 2,404.1 601.0 0.0 $85.95 $270.00 $35.00 3.1 2.7
185LED 348 3 T 40 R F 4 (ELE) F44SE 172 0.5 0.5 C-OCC 1747.2 901.6 225.4 0.0 $32.23 $270.00 $35.00 8.4 7.3
119 347 3 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 0.6 0.6 C-OCC 1747.2 1,132.2 283.0 0.0 $40.48 $270.00 $35.00 6.7 5.8
119 347 1 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 0.2 0.2 C-OCC 1747.2 377.4 94.3 0.0 $13.49 $270.00 $35.00 20.0 17.4
32LED Hallway 14 1T 32 R F 2 (ELE) F42LL 60 0.8 0.8 NONE 8736 7,338.2 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
41LED 303A 5 1B 40 R F 2 (MAG) F42SS 94 0.5 0.5 C-OCC 1747.2 821.2 205.3 0.0 $29.36 $270.00 $35.00 9.2 8.0
41LED Judge Chamber 4 1B 40 R F 2 (MAG) F42SS 94 0.4 0.4 C-OCC 1747.2 656.9 164.2 0.0 $23.49 $270.00 $35.00 11.5 10.0
71 Courthouse 94 I 60 I60/1 60 5.6 5.6 NONE 2125 11,985.0 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
41LED Courthouse 1 1B 40 R F 2 (MAG) F42SS 94 0.1 0.1 NONE 2125 199.8 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
41LED 302B 5 1B 40 R F 2 (MAG) F42SS 94 0.5 0.5 C-OCC 1747.2 821.2 205.3 0.0 $29.36 $270.00 $35.00 9.2 8.0
247LED 304 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
41LED 304 1 1B 40 R F 2 (MAG) F42SS 94 0.1 0.1 C-OCC 1747.2 164.2 41.1 0.0 $5.87 $270.00 $35.00 46.0 40.0
247LED 304 1 T 40 R F 3 (MAG) F43SE 136 0.1 0.1 C-OCC 1747.2 237.6 59.4 0.0 $8.49 $270.00 $35.00 31.8 27.7
185LED 304 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
185LED 304 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
32LED Hallway 10 1T 32 R F 2 (ELE) F42LL 60 0.6 0.6 NONE 8736 5,241.6 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
247LED 312 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
185LED Hallway 10 T 40 R F 4 (ELE) F44SE 172 1.7 1.7 NONE 8736 15,025.9 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
185LED Mens Room 3 T 40 R F 4 (ELE) F44SE 172 0.5 0.5 C-OCC 1747.2 901.6 225.4 0.0 $32.23 $270.00 $35.00 8.4 7.3
185LED Womens Room 3 T 40 R F 4 (ELE) F44SE 172 0.5 0.5 C-OCC 1747.2 901.6 225.4 0.0 $32.23 $270.00 $35.00 8.4 7.3
247LED 321A 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
32LED 321A 2 1T 32 R F 2 (ELE) F42LL 60 0.1 0.1 C-OCC 1747.2 209.7 52.4 0.0 $7.50 $270.00 $35.00 36.0 31.4
247LED 321 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
247LED 322 12 T 40 R F 3 (MAG) F43SE 136 1.6 1.6 C-OCC 1747.2 2,851.4 712.9 0.0 $101.94 $270.00 $35.00 2.6 2.3
185LED Mail Room 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
185LED 325 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
185LED 325 5 T 40 R F 4 (ELE) F44SE 172 0.9 0.9 C-OCC 1747.2 1,502.6 375.6 0.0 $53.72 $270.00 $35.00 5.0 4.4
185LED 325 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
32LED Hallway 4 1T 32 R F 2 (ELE) F42LL 60 0.2 0.2 C-OCC 8736 2,096.6 0.0 0.0 $0.00 $270.00 $35.00 #DIV/0!
185LED 335 19 T 40 R F 4 (ELE) F44SE 172 3.3 3.3 C-OCC 1747.2 5,709.8 1,427.5 0.0 $204.13 $270.00 $35.00 1.3 1.2
247LED café 28 T 40 R F 3 (MAG) F43SE 136 3.8 3.8 NONE 1820 6,930.6 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
185LED café 10 T 40 R F 4 (ELE) F44SE 172 1.7 1.7 C-OCC 1820 3,130.4 0.0 0.0 $0.00 $270.00 $35.00 #DIV/0!
247LED Café Individual Room 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1820 495.0 0.0 0.0 $0.00 $270.00 $35.00 #DIV/0!
185LED Café Individual Room 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1820 626.1 0.0 0.0 $0.00 $270.00 $35.00 #DIV/0!
196LED Hallway 4 W 32 C F 4 (ELE) F44ILL 112 0.4 0.4 C-OCC 8736 3,913.7 0.0 0.0 $0.00 $270.00 $35.00 #DIV/0!
196LED 331 32 W 32 C F 4 (ELE) F44ILL 112 3.6 3.6 C-OCC 1747.2 6,262.0 1,565.5 0.0 $223.87 $270.00 $35.00 1.2 1.0
247LED 331 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
5LED Mens Room 1 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 0.1 C-OCC 1747.2 104.8 26.2 0.0 $3.75 $270.00 $35.00 72.0 62.7
250 329 6 T 54 W F 3 (ELE) (T-5) F43GHL 177 1.1 1.1 C-OCC 1747.2 1,855.5 463.9 0.0 $66.34 $270.00 $35.00 4.1 3.5
247LED 328 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
250 4th Floor 436 4 T 54 W F 3 (ELE) (T-5) F43GHL 177 0.7 0.7 C-OCC 1747.2 1,237.0 309.3 0.0 $44.22 $270.00 $35.00 6.1 5.3
247LED 436 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
247LED Office 8 T 40 R F 3 (MAG) F43SE 136 1.1 1.1 C-OCC 1747.2 1,901.0 475.2 0.0 $67.96 $270.00 $35.00 4.0 3.5
32LED Office 1 1T 32 R F 2 (ELE) F42LL 60 0.1 0.1 C-OCC 1747.2 104.8 26.2 0.0 $3.75 $270.00 $35.00 72.0 62.7
196LED 435 4 W 32 C F 4 (ELE) F44ILL 112 0.4 0.4 C-OCC 1747.2 782.7 195.7 0.0 $27.98 $270.00 $35.00 9.6 8.4
247LED 435 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
185LED Hallway 7 T 40 R F 4 (ELE) F44SE 172 1.2 1.2 C-OCC 8736 10,518.1 0.0 0.0 $0.00 $270.00 $35.00 #DIV/0!
247LED 438 14 T 40 R F 3 (MAG) F43SE 136 1.9 1.9 C-OCC 1747.2 3,326.7 831.7 0.0 $118.93 $270.00 $35.00 2.3 2.0
247LED 439 9 T 40 R F 3 (MAG) F43SE 136 1.2 1.2 C-OCC 1747.2 2,138.6 534.6 0.0 $76.45 $270.00 $35.00 3.5 3.1
247LED 439 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 439 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
247LED 443 6 T 40 R F 3 (MAG) F43SE 136 0.8 0.8 C-OCC 1747.2 1,425.7 356.4 0.0 $50.97 $270.00 $35.00 5.3 4.6
247LED 444 14 T 40 R F 3 (MAG) F43SE 136 1.9 1.9 C-OCC 1747.2 3,326.7 831.7 0.0 $118.93 $270.00 $35.00 2.3 2.0
185LED Hallway 10 T 40 R F 4 (ELE) F44SE 172 1.7 1.7 C-OCC 8736 15,025.9 0.0 0.0 $0.00 $270.00 $35.00 #DIV/0!
247LED 445 14 T 40 R F 3 (MAG) F43SE 136 1.9 1.9 C-OCC 1747.2 3,326.7 831.7 0.0 $118.93 $270.00 $35.00 2.3 2.0
247LED 445 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
247LED 449A 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 449A 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
247LED 449A 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
5LED 402 8 2T 32 R F 2 (u) (ELE) FU2LL 60 0.5 0.5 C-OCC 1747.2 838.7 209.7 0.0 $29.98 $270.00 $35.00 9.0 7.8
5LED 402 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.3 0.3 C-OCC 1747.2 524.2 131.0 0.0 $18.74 $270.00 $35.00 14.4 12.5
5LED 402 9 2T 32 R F 2 (u) (ELE) FU2LL 60 0.5 0.5 C-OCC 1747.2 943.5 235.9 0.0 $33.73 $270.00 $35.00 8.0 7.0
185LED Hallway 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 8736 6,010.4 0.0 0.0 $0.00 $270.00 $35.00 #DIV/0!
196LED Hallway 3 W 32 C F 4 (ELE) F44ILL 112 0.3 0.3 C-OCC 8736 2,935.3 0.0 0.0 $0.00 $270.00 $35.00 #DIV/0!
71 Hallway 2 I 60 I60/1 60 0.1 0.1 NONE 8736 1,048.3 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
5LED 405 2 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 0.1 C-OCC 1747.2 209.7 52.4 0.0 $7.50 $270.00 $35.00 36.0 31.4
25 405 1 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.0 0.0 C-OCC 1747.2 48.9 12.2 0.0 $1.75 $270.00 $35.00 154.4 134.4
5LED 405 6 2T 32 R F 2 (u) (ELE) FU2LL 60 0.4 0.4 C-OCC 1747.2 629.0 157.2 0.0 $22.49 $270.00 $35.00 12.0 10.5
5LED 405 1 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 0.1 C-OCC 1747.2 104.8 26.2 0.0 $3.75 $270.00 $35.00 72.0 62.7
196LED 405 1 W 32 C F 4 (ELE) F44ILL 112 0.1 0.1 C-OCC 1747.2 195.7 48.9 0.0 $7.00 $270.00 $35.00 38.6 33.6
5LED 405 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.3 0.3 C-OCC 1747.2 524.2 131.0 0.0 $18.74 $270.00 $35.00 14.4 12.5
5LED 405 4 2T 32 R F 2 (u) (ELE) FU2LL 60 0.2 0.2 C-OCC 1747.2 419.3 104.8 0.0 $14.99 $270.00 $35.00 18.0 15.7
5LED 405 10 2T 32 R F 2 (u) (ELE) FU2LL 60 0.6 0.6 C-OCC 1747.2 1,048.3 262.1 0.0 $37.48 $270.00 $35.00 7.2 6.3
25 405 16 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.4 0.4 C-OCC 1747.2 782.7 195.7 0.0 $27.98 $270.00 $35.00 9.6 8.4
5LED 403 8 2T 32 R F 2 (u) (ELE) FU2LL 60 0.5 0.5 C-OCC 1747.2 838.7 209.7 0.0 $29.98 $270.00 $35.00 9.0 7.8
25 403 14 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.4 0.4 C-OCC 1747.2 684.9 171.2 0.0 $24.49 $270.00 $35.00 11.0 9.6
247LED 408 15 T 40 R F 3 (MAG) F43SE 136 2.0 2.0 C-OCC 1747.2 3,564.3 891.1 0.0 $127.42 $270.00 $35.00 2.1 1.8
35LED 411 10 T 32 R F 3 (ELE) F43ILL/2 90 0.9 0.9 C-OCC 1747.2 1,572.5 393.1 0.0 $56.22 $270.00 $35.00 4.8 4.2
185LED 411 6 T 40 R F 4 (ELE) F44SE 172 1.0 1.0 C-OCC 1747.2 1,803.1 450.8 0.0 $64.46 $270.00 $35.00 4.2 3.6
185LED Hallway 10 T 40 R F 4 (ELE) F44SE 172 1.7 1.7 NONE 8736 15,025.9 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
COST & SAVINGS ANALYSISEXISTING CONDITIONS RETROFIT CONDITIONS
1/22/2015 Page 9, ECM-L2
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
ECM-L2 Install Occupancy Sensors $3.79 $/kW
Area Description No. of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space kW/Space Retrofit Control Annual Hours Annual kWh
Annual kWh
Saved Annual kW Saved Annual $ Saved Retrofit Cost
NJ Smart Start
Lighting
Incentive
Simple Payback
With Out
Incentive Simple Payback
Field Code Unique description of the location - Room number/Room
name: Floor number (if applicable)
No. of fixtures
before the retrofit
Lighting Fixture Code Code from Table of Standard
Fixture Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
(Watts/Fixt) *
(Number of
Fixtures)
Retrofit control
device
Estimated
annual hours for
the usage group
(kW/space) *
(Annual Hours)
(Original Annual
kWh) - (Retrofit
Annual kWh)
(Original Annual
kW) - (Retrofit
Annual kW)
(kW Saved) *
($/kWh)
Cost for
renovations to
lighting system
Length of time
for renovations
cost to be
recovered
Length of time for
renovations cost to
be recovered
COST & SAVINGS ANALYSISEXISTING CONDITIONS RETROFIT CONDITIONS
35LED 413 8 T 32 R F 3 (ELE) F43ILL/2 90 0.7 0.7 C-OCC 1747.2 1,258.0 314.5 0.0 $44.97 $270.00 $35.00 6.0 5.2
35LED 414 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 0.4 C-OCC 1747.2 629.0 157.2 0.0 $22.49 $270.00 $35.00 12.0 10.5
32LED 414 1 1T 32 R F 2 (ELE) F42LL 60 0.1 0.1 C-OCC 1747.2 104.8 26.2 0.0 $3.75 $270.00 $35.00 72.0 62.7
35LED 416 6 T 32 R F 3 (ELE) F43ILL/2 90 0.5 0.5 C-OCC 1747.2 943.5 235.9 0.0 $33.73 $270.00 $35.00 8.0 7.0
35LED 417A 7 T 32 R F 3 (ELE) F43ILL/2 90 0.6 0.6 C-OCC 1747.2 1,100.7 275.2 0.0 $39.35 $270.00 $35.00 6.9 6.0
35LED 417A 12 T 32 R F 3 (ELE) F43ILL/2 90 1.1 1.1 C-OCC 1747.2 1,887.0 471.7 0.0 $67.46 $270.00 $35.00 4.0 3.5
35LED 417A 5 T 32 R F 3 (ELE) F43ILL/2 90 0.5 0.5 C-OCC 1747.2 786.2 196.6 0.0 $28.11 $270.00 $35.00 9.6 8.4
35LED 417A 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 0.4 C-OCC 1747.2 629.0 157.2 0.0 $22.49 $270.00 $35.00 12.0 10.5
35LED 417A 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 0.4 C-OCC 1747.2 629.0 157.2 0.0 $22.49 $270.00 $35.00 12.0 10.5
247LED 417A 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
247LED 422A 15 T 40 R F 3 (MAG) F43SE 136 2.0 2.0 C-OCC 1747.2 3,564.3 891.1 0.0 $127.42 $270.00 $35.00 2.1 1.8
247LED 427D 8 T 40 R F 3 (MAG) F43SE 136 1.1 1.1 C-OCC 1747.2 1,901.0 475.2 0.0 $67.96 $270.00 $35.00 4.0 3.5
185LED Hallway 10 T 40 R F 4 (ELE) F44SE 172 1.7 1.7 NONE 8736 15,025.9 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
35LED 428 15 T 32 R F 3 (ELE) F43ILL/2 90 1.4 1.4 C-OCC 1747.2 2,358.7 589.7 0.0 $84.32 $270.00 $35.00 3.2 2.8
35LED 428 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 0.4 C-OCC 1747.2 629.0 157.2 0.0 $22.49 $270.00 $35.00 12.0 10.5
35LED 428 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 0.4 C-OCC 1747.2 629.0 157.2 0.0 $22.49 $270.00 $35.00 12.0 10.5
196LED Womens Room 3 W 32 C F 4 (ELE) F44ILL 112 0.3 0.3 C-OCC 1747.2 587.1 146.8 0.0 $20.99 $270.00 $35.00 12.9 11.2
196LED Mens Room 3 W 32 C F 4 (ELE) F44ILL 112 0.3 0.3 C-OCC 1747.2 587.1 146.8 0.0 $20.99 $270.00 $35.00 12.9 11.2
32LED 5th Floor Hallway 10 1T 32 R F 2 (ELE) F42LL 60 0.6 0.6 C-OCC 8736 5,241.6 0.0 0.0 $0.00 $270.00 $35.00 #DIV/0!
247LED 530 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
41LED 530 1 1B 40 R F 2 (MAG) F42SS 94 0.1 0.1 C-OCC 1747.2 164.2 41.1 0.0 $5.87 $270.00 $35.00 46.0 40.0
247LED 530 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
196LED Womens Room 4 W 32 C F 4 (ELE) F44ILL 112 0.4 0.4 C-OCC 1747.2 782.7 195.7 0.0 $27.98 $270.00 $35.00 9.6 8.4
247LED 535 10 T 40 R F 3 (MAG) F43SE 136 1.4 1.4 C-OCC 1747.2 2,376.2 594.0 0.0 $84.95 $270.00 $35.00 3.2 2.8
32LED 535 5 1T 32 R F 2 (ELE) F42LL 60 0.3 0.3 C-OCC 1747.2 524.2 131.0 0.0 $18.74 $270.00 $35.00 14.4 12.5
247LED 535 5 T 40 R F 3 (MAG) F43SE 136 0.7 0.7 C-OCC 1747.2 1,188.1 297.0 0.0 $42.47 $270.00 $35.00 6.4 5.5
185LED 535 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
185LED 535 3 T 40 R F 4 (ELE) F44SE 172 0.5 0.5 C-OCC 1747.2 901.6 225.4 0.0 $32.23 $270.00 $35.00 8.4 7.3
185LED 535 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
247LED 524A 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
247LED 524A 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
32LED Hallway 12 1T 32 R F 2 (ELE) F42LL 60 0.7 0.7 NONE 8736 6,289.9 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
247LED 556 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
247LED 556 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
185LED 558 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
185LED 558 16 T 40 R F 4 (ELE) F44SE 172 2.8 2.8 C-OCC 1747.2 4,808.3 1,202.1 0.0 $171.90 $270.00 $35.00 1.6 1.4
247LED 558 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
41LED 558 2 1B 40 R F 2 (MAG) F42SS 94 0.2 0.2 C-OCC 1747.2 328.5 82.1 0.0 $11.74 $270.00 $35.00 23.0 20.0
196LED 558 4 W 32 C F 4 (ELE) F44ILL 112 0.4 0.4 C-OCC 1747.2 782.7 195.7 0.0 $27.98 $270.00 $35.00 9.6 8.4
71 558 5 I 60 I60/1 60 0.3 0.3 C-OCC 1747.2 524.2 131.0 0.0 $18.74 $270.00 $35.00 14.4 12.5
5LED 501A 24 2T 32 R F 2 (u) (ELE) FU2LL 60 1.4 1.4 C-OCC 1747.2 2,516.0 629.0 0.0 $89.95 $270.00 $35.00 3.0 2.6
71 502 6 I 60 I60/1 60 0.4 0.4 C-OCC 1747.2 629.0 157.2 0.0 $22.49 $270.00 $35.00 12.0 10.5
20LED 503A 3 S 28 P F 1 (ELE) F41ILL 31 0.1 0.1 C-OCC 1747.2 162.5 40.6 0.0 $5.81 $270.00 $35.00 46.5 40.5
20LED 503A 2 S 28 P F 1 (ELE) F41ILL 31 0.1 0.1 C-OCC 1747.2 108.3 27.1 0.0 $3.87 $270.00 $35.00 69.7 60.7
20LED 503A 6 S 28 P F 1 (ELE) F41ILL 31 0.2 0.2 C-OCC 1747.2 325.0 81.2 0.0 $11.62 $270.00 $35.00 23.2 20.2
71 Restroom 1 I 60 I60/1 60 0.1 0.1 C-OCC 1747.2 104.8 26.2 0.0 $3.75 $270.00 $35.00 72.0 62.7
71 Suite 502 1 I 60 I60/1 60 0.1 0.1 C-OCC 1747.2 104.8 26.2 0.0 $3.75 $270.00 $35.00 72.0 62.7
71 Hallway 28 I 60 I60/1 60 1.7 1.7 NONE 8736 14,676.5 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
196LED 504 2 W 32 C F 4 (ELE) F44ILL 112 0.2 0.2 C-OCC 1747.2 391.4 97.8 0.0 $13.99 $270.00 $35.00 19.3 16.8
196LED 504 5 W 32 C F 4 (ELE) F44ILL 112 0.6 0.6 C-OCC 1747.2 978.4 244.6 0.0 $34.98 $270.00 $35.00 7.7 6.7
5LED 508 4 2T 32 R F 2 (u) (ELE) FU2LL 60 0.2 0.2 C-OCC 1747.2 419.3 104.8 0.0 $14.99 $270.00 $35.00 18.0 15.7
5LED 508 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.3 0.3 C-OCC 1747.2 524.2 131.0 0.0 $18.74 $270.00 $35.00 14.4 12.5
71 508 2 I 60 I60/1 60 0.1 0.1 C-OCC 1747.2 209.7 52.4 0.0 $7.50 $270.00 $35.00 36.0 31.4
196LED 507 4 W 32 C F 4 (ELE) F44ILL 112 0.4 0.4 C-OCC 1747.2 782.7 195.7 0.0 $27.98 $270.00 $35.00 9.6 8.4
196LED 507 5 W 32 C F 4 (ELE) F44ILL 112 0.6 0.6 C-OCC 1747.2 978.4 244.6 0.0 $34.98 $270.00 $35.00 7.7 6.7
196LED 507A 2 W 32 C F 4 (ELE) F44ILL 112 0.2 0.2 C-OCC 1747.2 391.4 97.8 0.0 $13.99 $270.00 $35.00 19.3 16.8
196LED 507A 4 W 32 C F 4 (ELE) F44ILL 112 0.4 0.4 C-OCC 1747.2 782.7 195.7 0.0 $27.98 $270.00 $35.00 9.6 8.4
247LED 509 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
247LED 509 6 T 40 R F 3 (MAG) F43SE 136 0.8 0.8 C-OCC 1747.2 1,425.7 356.4 0.0 $50.97 $270.00 $35.00 5.3 4.6
247LED 509 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 509 1 T 40 R F 3 (MAG) F43SE 136 0.1 0.1 C-OCC 1747.2 237.6 59.4 0.0 $8.49 $270.00 $35.00 31.8 27.7
196LED 560A 6 W 32 C F 4 (ELE) F44ILL 112 0.7 0.7 C-OCC 1747.2 1,174.1 293.5 0.0 $41.97 $270.00 $35.00 6.4 5.6
41LED 559 1 1B 40 R F 2 (MAG) F42SS 94 0.1 0.1 C-OCC 1747.2 164.2 41.1 0.0 $5.87 $270.00 $35.00 46.0 40.0
247LED 554 6 T 40 R F 3 (MAG) F43SE 136 0.8 0.8 C-OCC 1747.2 1,425.7 356.4 0.0 $50.97 $270.00 $35.00 5.3 4.6
196LED 553 3 W 32 C F 4 (ELE) F44ILL 112 0.3 0.3 C-OCC 1747.2 587.1 146.8 0.0 $20.99 $270.00 $35.00 12.9 11.2
196LED 552 1 W 32 C F 4 (ELE) F44ILL 112 0.1 0.1 C-OCC 1747.2 195.7 48.9 0.0 $7.00 $270.00 $35.00 38.6 33.6
196LED 552 5 W 32 C F 4 (ELE) F44ILL 112 0.6 0.6 C-OCC 1747.2 978.4 244.6 0.0 $34.98 $270.00 $35.00 7.7 6.7
247LED 550 8 T 40 R F 3 (MAG) F43SE 136 1.1 1.1 C-OCC 1747.2 1,901.0 475.2 0.0 $67.96 $270.00 $35.00 4.0 3.5
247LED 551 7 T 40 R F 3 (MAG) F43SE 136 1.0 1.0 C-OCC 1747.2 1,663.3 415.8 0.0 $59.46 $270.00 $35.00 4.5 4.0
247LED 551 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
5LED 519 2 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 0.1 C-OCC 1747.2 209.7 52.4 0.0 $7.50 $270.00 $35.00 36.0 31.4
5LED 519 16 2T 32 R F 2 (u) (ELE) FU2LL 60 1.0 1.0 C-OCC 1747.2 1,677.3 419.3 0.0 $59.96 $270.00 $35.00 4.5 3.9
5LED 519 6 2T 32 R F 2 (u) (ELE) FU2LL 60 0.4 0.4 C-OCC 1747.2 629.0 157.2 0.0 $22.49 $270.00 $35.00 12.0 10.5
5LED 519 7 2T 32 R F 2 (u) (ELE) FU2LL 60 0.4 0.4 C-OCC 1747.2 733.8 183.5 0.0 $26.23 $270.00 $35.00 10.3 9.0
196LED 514C 6 W 32 C F 4 (ELE) F44ILL 112 0.7 0.7 C-OCC 1747.2 1,174.1 293.5 0.0 $41.97 $270.00 $35.00 6.4 5.6
247LED 516 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
247LED 515 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
196LED 510 1 W 32 C F 4 (ELE) F44ILL 112 0.1 0.1 C-OCC 1747.2 195.7 48.9 0.0 $7.00 $270.00 $35.00 38.6 33.6
247LED 510 6 T 40 R F 3 (MAG) F43SE 136 0.8 0.8 C-OCC 1747.2 1,425.7 356.4 0.0 $50.97 $270.00 $35.00 5.3 4.6
196LED 510 1 W 32 C F 4 (ELE) F44ILL 112 0.1 0.1 C-OCC 1747.2 195.7 48.9 0.0 $7.00 $270.00 $35.00 38.6 33.6
196LED 510 6 W 32 C F 4 (ELE) F44ILL 112 0.7 0.7 C-OCC 1747.2 1,174.1 293.5 0.0 $41.97 $270.00 $35.00 6.4 5.6
196LED 511 4 W 32 C F 4 (ELE) F44ILL 112 0.4 0.4 C-OCC 1747.2 782.7 195.7 0.0 $27.98 $270.00 $35.00 9.6 8.4
247LED 511A 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
247LED 511 Small Offices 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
247LED 511 Small Offices 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
185LED 511 Small Offices 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
247LED 511 Small Offices 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 511 Small Offices 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
5LED 511 Small Offices 12 2T 32 R F 2 (u) (ELE) FU2LL 60 0.7 0.7 C-OCC 1747.2 1,258.0 314.5 0.0 $44.97 $270.00 $35.00 6.0 5.2
32LED Hallway 10 1T 32 R F 2 (ELE) F42LL 60 0.6 0.6 NONE 8736 5,241.6 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
247LED 549 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 549 6 T 40 R F 3 (MAG) F43SE 136 0.8 0.8 C-OCC 1747.2 1,425.7 356.4 0.0 $50.97 $270.00 $35.00 5.3 4.6
1/22/2015 Page 10, ECM-L2
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
ECM-L2 Install Occupancy Sensors $3.79 $/kW
Area Description No. of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space kW/Space Retrofit Control Annual Hours Annual kWh
Annual kWh
Saved Annual kW Saved Annual $ Saved Retrofit Cost
NJ Smart Start
Lighting
Incentive
Simple Payback
With Out
Incentive Simple Payback
Field Code Unique description of the location - Room number/Room
name: Floor number (if applicable)
No. of fixtures
before the retrofit
Lighting Fixture Code Code from Table of Standard
Fixture Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
(Watts/Fixt) *
(Number of
Fixtures)
Retrofit control
device
Estimated
annual hours for
the usage group
(kW/space) *
(Annual Hours)
(Original Annual
kWh) - (Retrofit
Annual kWh)
(Original Annual
kW) - (Retrofit
Annual kW)
(kW Saved) *
($/kWh)
Cost for
renovations to
lighting system
Length of time
for renovations
cost to be
recovered
Length of time for
renovations cost to
be recovered
COST & SAVINGS ANALYSISEXISTING CONDITIONS RETROFIT CONDITIONS
247LED 548 7 T 40 R F 3 (MAG) F43SE 136 1.0 1.0 C-OCC 1747.2 1,663.3 415.8 0.0 $59.46 $270.00 $35.00 4.5 4.0
247LED 547 5 T 40 R F 3 (MAG) F43SE 136 0.7 0.7 C-OCC 1747.2 1,188.1 297.0 0.0 $42.47 $270.00 $35.00 6.4 5.5
32LED Hallway 8 1T 32 R F 2 (ELE) F42LL 60 0.5 0.5 NONE 8736 4,193.3 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
247LED 536 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 536 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 537 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
247LED 537 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
247LED 546 7 T 40 R F 3 (MAG) F43SE 136 1.0 1.0 C-OCC 1747.2 1,663.3 415.8 0.0 $59.46 $270.00 $35.00 4.5 4.0
247LED 546 7 T 40 R F 3 (MAG) F43SE 136 1.0 1.0 C-OCC 1747.2 1,663.3 415.8 0.0 $59.46 $270.00 $35.00 4.5 4.0
247LED 544 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 544 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 543 8 T 40 R F 3 (MAG) F43SE 136 1.1 1.1 C-OCC 1747.2 1,901.0 475.2 0.0 $67.96 $270.00 $35.00 4.0 3.5
247LED 542 6 T 40 R F 3 (MAG) F43SE 136 0.8 0.8 C-OCC 1747.2 1,425.7 356.4 0.0 $50.97 $270.00 $35.00 5.3 4.6
247LED 542 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
35LED 542 6 T 32 R F 3 (ELE) F43ILL/2 90 0.5 0.5 C-OCC 1747.2 943.5 235.9 0.0 $33.73 $270.00 $35.00 8.0 7.0
247LED 542 8 T 40 R F 3 (MAG) F43SE 136 1.1 1.1 C-OCC 1747.2 1,901.0 475.2 0.0 $67.96 $270.00 $35.00 4.0 3.5
247LED 542 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 539 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 539 23 T 40 R F 3 (MAG) F43SE 136 3.1 3.1 C-OCC 1747.2 5,465.2 1,366.3 0.0 $195.38 $270.00 $35.00 1.4 1.2
185LED 2nd Floor 201 6 T 40 R F 4 (ELE) F44SE 172 1.0 1.0 C-OCC 1747.2 1,803.1 450.8 0.0 $64.46 $270.00 $35.00 4.2 3.6
247LED 202 14 T 40 R F 3 (MAG) F43SE 136 1.9 1.9 C-OCC 1747.2 3,326.7 831.7 0.0 $118.93 $270.00 $35.00 2.3 2.0
185LED 202 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
247LED 204 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 205 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 205 next 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
247LED 205 next 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
185LED 206 12 T 40 R F 4 (ELE) F44SE 172 2.1 2.1 C-OCC 1747.2 3,606.2 901.6 0.0 $128.92 $270.00 $35.00 2.1 1.8
41LED 207 6 1B 40 R F 2 (MAG) F42SS 94 0.6 0.6 C-OCC 1747.2 985.4 246.4 0.0 $35.23 $270.00 $35.00 7.7 6.7
247LED 208 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
41LED 208 2 1B 40 R F 2 (MAG) F42SS 94 0.2 0.2 C-OCC 1747.2 328.5 82.1 0.0 $11.74 $270.00 $35.00 23.0 20.0
247LED 209 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
41LED 209 2 1B 40 R F 2 (MAG) F42SS 94 0.2 0.2 C-OCC 1747.2 328.5 82.1 0.0 $11.74 $270.00 $35.00 23.0 20.0
5LED 211 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.3 0.3 C-OCC 1747.2 524.2 131.0 0.0 $18.74 $270.00 $35.00 14.4 12.5
25 213 10 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.3 0.3 C-OCC 1747.2 489.2 122.3 0.0 $17.49 $270.00 $35.00 15.4 13.4
185LED 213 1 T 40 R F 4 (ELE) F44SE 172 0.2 0.2 C-OCC 1747.2 300.5 75.1 0.0 $10.74 $270.00 $35.00 25.1 21.9
25 214 6 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.2 0.2 C-OCC 1747.2 293.5 73.4 0.0 $10.49 $270.00 $35.00 25.7 22.4
185LED 214 1 T 40 R F 4 (ELE) F44SE 172 0.2 0.2 C-OCC 1747.2 300.5 75.1 0.0 $10.74 $270.00 $35.00 25.1 21.9
247LED 215 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
185LED 216 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
247LED 217 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
41LED 217 2 1B 40 R F 2 (MAG) F42SS 94 0.2 0.2 C-OCC 1747.2 328.5 82.1 0.0 $11.74 $270.00 $35.00 23.0 20.0
41LED 219 19 1B 40 R F 2 (MAG) F42SS 94 1.8 1.8 C-OCC 1747.2 3,120.5 780.1 0.0 $111.56 $270.00 $35.00 2.4 2.1
41LED 220 4 1B 40 R F 2 (MAG) F42SS 94 0.4 0.4 C-OCC 1747.2 656.9 164.2 0.0 $23.49 $270.00 $35.00 11.5 10.0
185LED 222 30 T 40 R F 4 (ELE) F44SE 172 5.2 5.2 C-OCC 1747.2 9,015.6 2,253.9 0.0 $322.31 $270.00 $35.00 0.8 0.7
196LED Men's Room 3 W 32 C F 4 (ELE) F44ILL 112 0.3 0.3 C-OCC 1747.2 587.1 146.8 0.0 $20.99 $270.00 $35.00 12.9 11.2
196LED Women's Room 3 W 32 C F 4 (ELE) F44ILL 112 0.3 0.3 C-OCC 1747.2 587.1 146.8 0.0 $20.99 $270.00 $35.00 12.9 11.2
32LED Service Room 2 1T 32 R F 2 (ELE) F42LL 60 0.1 0.1 C-OCC 1747.2 209.7 52.4 0.0 $7.50 $270.00 $35.00 36.0 31.4
185LED 226 7 T 40 R F 4 (ELE) F44SE 172 1.2 1.2 C-OCC 1747.2 2,103.6 525.9 0.0 $75.20 $270.00 $35.00 3.6 3.1
32LED 226 1 1T 32 R F 2 (ELE) F42LL 60 0.1 0.1 C-OCC 1747.2 104.8 26.2 0.0 $3.75 $270.00 $35.00 72.0 62.7
185LED 226 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
247LED 227 8 T 40 R F 3 (MAG) F43SE 136 1.1 1.1 C-OCC 1747.2 1,901.0 475.2 0.0 $67.96 $270.00 $35.00 4.0 3.5
185LED 228 3 T 40 R F 4 (ELE) F44SE 172 0.5 0.5 C-OCC 1747.2 901.6 225.4 0.0 $32.23 $270.00 $35.00 8.4 7.3
247LED 231 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
185LED 231 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
41LED 232 4 1B 40 R F 2 (MAG) F42SS 94 0.4 0.4 C-OCC 1747.2 656.9 164.2 0.0 $23.49 $270.00 $35.00 11.5 10.0
247LED 232 8 T 40 R F 3 (MAG) F43SE 136 1.1 1.1 C-OCC 1747.2 1,901.0 475.2 0.0 $67.96 $270.00 $35.00 4.0 3.5
41LED 233 5 1B 40 R F 2 (MAG) F42SS 94 0.5 0.5 C-OCC 1747.2 821.2 205.3 0.0 $29.36 $270.00 $35.00 9.2 8.0
247LED 233 14 T 40 R F 3 (MAG) F43SE 136 1.9 1.9 C-OCC 1747.2 3,326.7 831.7 0.0 $118.93 $270.00 $35.00 2.3 2.0
71 233 Storage 2 I 60 I60/1 60 0.1 0.1 C-OCC 2329.6 279.6 69.9 0.0 $9.99 $270.00 $35.00 27.0 23.5
185LED 236 19 T 40 R F 4 (ELE) F44SE 172 3.3 3.3 C-OCC 1747.2 5,709.8 1,427.5 0.0 $204.13 $270.00 $35.00 1.3 1.2
185LED 238 15 T 40 R F 4 (ELE) F44SE 172 2.6 2.6 C-OCC 1747.2 4,507.8 1,126.9 0.0 $161.15 $270.00 $35.00 1.7 1.5
185LED 242 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
247LED 242 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
32LED 242 6 1T 32 R F 2 (ELE) F42LL 60 0.4 0.4 C-OCC 1747.2 629.0 157.2 0.0 $22.49 $270.00 $35.00 12.0 10.5
196LED lobby 2 W 32 C F 4 (ELE) F44ILL 112 0.2 0.2 NONE 8736 1,956.9 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
247LED 244 12 T 40 R F 3 (MAG) F43SE 136 1.6 1.6 C-OCC 1747.2 2,851.4 712.9 0.0 $101.94 $270.00 $35.00 2.6 2.3
41LED 244 6 1B 40 R F 2 (MAG) F42SS 94 0.6 0.6 C-OCC 1747.2 985.4 246.4 0.0 $35.23 $270.00 $35.00 7.7 6.7
41LED Attendent 5 1B 40 R F 2 (MAG) F42SS 94 0.5 0.5 C-OCC 1747.2 821.2 205.3 0.0 $29.36 $270.00 $35.00 9.2 8.0
41LED 247 155 1B 40 R F 2 (MAG) F42SS 94 14.6 14.6 C-OCC 1747.2 25,456.7 6,364.2 0.0 $910.08 $270.00 $35.00 0.3 0.3
247LED 247 3 T 40 R F 3 (MAG) F43SE 136 0.4 0.4 C-OCC 1747.2 712.9 178.2 0.0 $25.48 $270.00 $35.00 10.6 9.2
41LED 247 4 1B 40 R F 2 (MAG) F42SS 94 0.4 0.4 C-OCC 1747.2 656.9 164.2 0.0 $23.49 $270.00 $35.00 11.5 10.0
5LED 248 66 2T 32 R F 2 (u) (ELE) FU2LL 60 4.0 4.0 C-OCC 1747.2 6,918.9 1,729.7 0.0 $247.35 $270.00 $35.00 1.1 1.0
5LED 248 66 2T 32 R F 2 (u) (ELE) FU2LL 60 4.0 4.0 C-OCC 1747.2 6,918.9 1,729.7 0.0 $247.35 $270.00 $35.00 1.1 1.0
196LED 248 45 W 32 C F 4 (ELE) F44ILL 112 5.0 5.0 C-OCC 1747.2 8,805.9 2,201.5 0.0 $314.81 $270.00 $35.00 0.9 0.7
196LED 248 2 W 32 C F 4 (ELE) F44ILL 112 0.2 0.2 C-OCC 1747.2 391.4 97.8 0.0 $13.99 $270.00 $35.00 19.3 16.8
196LED 248 2 W 32 C F 4 (ELE) F44ILL 112 0.2 0.2 C-OCC 1747.2 391.4 97.8 0.0 $13.99 $270.00 $35.00 19.3 16.8
35LED 1st Floor 101 29 T 32 R F 3 (ELE) F43ILL/2 90 2.6 2.6 C-OCC 1747.2 4,560.2 1,140.0 0.0 $163.03 $270.00 $35.00 1.7 1.4
35LED 102 5 T 32 R F 3 (ELE) F43ILL/2 90 0.5 0.5 C-OCC 1747.2 786.2 196.6 0.0 $28.11 $270.00 $35.00 9.6 8.4
41LED 103 2 1B 40 R F 2 (MAG) F42SS 94 0.2 0.2 C-OCC 1747.2 328.5 82.1 0.0 $11.74 $270.00 $35.00 23.0 20.0
185LED 104 8 T 40 R F 4 (ELE) F44SE 172 1.4 1.4 C-OCC 1747.2 2,404.1 601.0 0.0 $85.95 $270.00 $35.00 3.1 2.7
71 Entrance Hall 16 I 60 I60/1 60 1.0 1.0 NONE 8736 8,386.6 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
71 Entrance Hall 36 I 60 I60/1 60 2.2 2.2 C-OCC 1747.2 3,774.0 943.5 0.0 $134.92 $270.00 $35.00 2.0 1.7
247LED 107 14 T 40 R F 3 (MAG) F43SE 136 1.9 1.9 C-OCC 1747.2 3,326.7 831.7 0.0 $118.93 $270.00 $35.00 2.3 2.0
185LED 107 Small Room 1 T 40 R F 4 (ELE) F44SE 172 0.2 0.2 C-OCC 1747.2 300.5 75.1 0.0 $10.74 $270.00 $35.00 25.1 21.9
247LED 107 Small Room 2 T 40 R F 3 (MAG) F43SE 136 0.3 0.3 C-OCC 1747.2 475.2 118.8 0.0 $16.99 $270.00 $35.00 15.9 13.8
41LED Chief Room 6 1B 40 R F 2 (MAG) F42SS 94 0.6 0.6 C-OCC 1747.2 985.4 246.4 0.0 $35.23 $270.00 $35.00 7.7 6.7
247LED 110 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
41LED 111 11 1B 40 R F 2 (MAG) F42SS 94 1.0 1.0 C-OCC 1747.2 1,806.6 451.7 0.0 $64.59 $270.00 $35.00 4.2 3.6
185LED 111 3 T 40 R F 4 (ELE) F44SE 172 0.5 0.5 C-OCC 1747.2 901.6 225.4 0.0 $32.23 $270.00 $35.00 8.4 7.3
185LED Assitant Chief 8 T 40 R F 4 (ELE) F44SE 172 1.4 1.4 C-OCC 1747.2 2,404.1 601.0 0.0 $85.95 $270.00 $35.00 3.1 2.7
185LED 115 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
41LED 115 4 1B 40 R F 2 (MAG) F42SS 94 0.4 0.4 C-OCC 1747.2 656.9 164.2 0.0 $23.49 $270.00 $35.00 11.5 10.0
1/22/2015 Page 11, ECM-L2
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
ECM-L2 Install Occupancy Sensors $3.79 $/kW
Area Description No. of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space kW/Space Retrofit Control Annual Hours Annual kWh
Annual kWh
Saved Annual kW Saved Annual $ Saved Retrofit Cost
NJ Smart Start
Lighting
Incentive
Simple Payback
With Out
Incentive Simple Payback
Field Code Unique description of the location - Room number/Room
name: Floor number (if applicable)
No. of fixtures
before the retrofit
Lighting Fixture Code Code from Table of Standard
Fixture Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
(Watts/Fixt) *
(Number of
Fixtures)
Retrofit control
device
Estimated
annual hours for
the usage group
(kW/space) *
(Annual Hours)
(Original Annual
kWh) - (Retrofit
Annual kWh)
(Original Annual
kW) - (Retrofit
Annual kW)
(kW Saved) *
($/kWh)
Cost for
renovations to
lighting system
Length of time
for renovations
cost to be
recovered
Length of time for
renovations cost to
be recovered
COST & SAVINGS ANALYSISEXISTING CONDITIONS RETROFIT CONDITIONS
247LED 115 20 T 40 R F 3 (MAG) F43SE 136 2.7 2.7 C-OCC 1747.2 4,752.4 1,188.1 0.0 $169.90 $270.00 $35.00 1.6 1.4
185LED Men's Room 3 T 40 R F 4 (ELE) F44SE 172 0.5 0.5 C-OCC 1747.2 901.6 225.4 0.0 $32.23 $270.00 $35.00 8.4 7.3
185LED Women's Room 3 T 40 R F 4 (ELE) F44SE 172 0.5 0.5 C-OCC 1747.2 901.6 225.4 0.0 $32.23 $270.00 $35.00 8.4 7.3
5LED Receiving Room 8 2T 32 R F 2 (u) (ELE) FU2LL 60 0.5 0.5 C-OCC 1747.2 838.7 209.7 0.0 $29.98 $270.00 $35.00 9.0 7.8
185LED Comparing Room 6 T 40 R F 4 (ELE) F44SE 172 1.0 1.0 C-OCC 1747.2 1,803.1 450.8 0.0 $64.46 $270.00 $35.00 4.2 3.6
185LED Comparing Room 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
185LED Comparing Room 1 T 40 R F 4 (ELE) F44SE 172 0.2 0.2 C-OCC 1747.2 300.5 75.1 0.0 $10.74 $270.00 $35.00 25.1 21.9
32LED Hallway 10 1T 32 R F 2 (ELE) F42LL 60 0.6 0.6 NONE 8736 5,241.6 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
247LED 131 5 T 40 R F 3 (MAG) F43SE 136 0.7 0.7 C-OCC 1747.2 1,188.1 297.0 0.0 $42.47 $270.00 $35.00 6.4 5.5
185LED Copying Room 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
247LED Copying Room 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 C-OCC 1747.2 950.5 237.6 0.0 $33.98 $270.00 $35.00 7.9 6.9
35LED Copying Room 5 T 32 R F 3 (ELE) F43ILL/2 90 0.5 0.5 C-OCC 1747.2 786.2 196.6 0.0 $28.11 $270.00 $35.00 9.6 8.4
247LED Copying Room 12 T 40 R F 3 (MAG) F43SE 136 1.6 1.6 C-OCC 1747.2 2,851.4 712.9 0.0 $101.94 $270.00 $35.00 2.6 2.3
196LED Copying Room 1 W 32 C F 4 (ELE) F44ILL 112 0.1 0.1 C-OCC 1747.2 195.7 48.9 0.0 $7.00 $270.00 $35.00 38.6 33.6
247LED Copying Room 14 T 40 R F 3 (MAG) F43SE 136 1.9 1.9 C-OCC 1747.2 3,326.7 831.7 0.0 $118.93 $270.00 $35.00 2.3 2.0
35LED Deeds 3 T 32 R F 3 (ELE) F43ILL/2 90 0.3 0.3 C-OCC 1747.2 471.7 117.9 0.0 $16.86 $270.00 $35.00 16.0 13.9
185LED Deeds 1 T 40 R F 4 (ELE) F44SE 172 0.2 0.2 C-OCC 1747.2 300.5 75.1 0.0 $10.74 $270.00 $35.00 25.1 21.9
185LED Registers Vault 60 T 40 R F 4 (ELE) F44SE 172 10.3 10.3 C-OCC 1747.2 18,031.1 4,507.8 0.0 $644.61 $270.00 $35.00 0.4 0.4
196LED Registers Vault 1 W 32 C F 4 (ELE) F44ILL 112 0.1 0.1 C-OCC 1747.2 195.7 48.9 0.0 $7.00 $270.00 $35.00 38.6 33.6
196LED Registers Vault 12 W 32 C F 4 (ELE) F44ILL 112 1.3 1.3 C-OCC 1747.2 2,348.2 587.1 0.0 $83.95 $270.00 $35.00 3.2 2.8
185LED Index 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
41LED Index 2 1B 40 R F 2 (MAG) F42SS 94 0.2 0.2 C-OCC 1747.2 328.5 82.1 0.0 $11.74 $270.00 $35.00 23.0 20.0
247LED Index 7 T 40 R F 3 (MAG) F43SE 136 1.0 1.0 C-OCC 1747.2 1,663.3 415.8 0.0 $59.46 $270.00 $35.00 4.5 4.0
35LED Index 6 T 32 R F 3 (ELE) F43ILL/2 90 0.5 0.5 C-OCC 1747.2 943.5 235.9 0.0 $33.73 $270.00 $35.00 8.0 7.0
41LED Basement Men's Locker 11 1B 40 R F 2 (MAG) F42SS 94 1.0 1.0 C-OCC 1747.2 1,806.6 451.7 0.0 $64.59 $270.00 $35.00 4.2 3.6
32LED Closet 2 1T 32 R F 2 (ELE) F42LL 60 0.1 0.1 C-OCC 2329.6 279.6 69.9 0.0 $9.99 $270.00 $35.00 27.0 23.5
32LED Closet 1 1T 32 R F 2 (ELE) F42LL 60 0.1 0.1 C-OCC 1747.2 104.8 26.2 0.0 $3.75 $270.00 $35.00 72.0 62.7
71 Toilet 2 I 60 I60/1 60 0.1 0.1 C-OCC 1747.2 209.7 52.4 0.0 $7.50 $270.00 $35.00 36.0 31.4
41LED Hallway 44 1B 40 R F 2 (MAG) F42SS 94 4.1 4.1 NONE 8736 36,132.1 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
41LED B33 4 1B 40 R F 2 (MAG) F42SS 94 0.4 0.4 C-OCC 1747.2 656.9 164.2 0.0 $23.49 $270.00 $35.00 11.5 10.0
41LED B33 11 1B 40 R F 2 (MAG) F42SS 94 1.0 1.0 C-OCC 1747.2 1,806.6 451.7 0.0 $64.59 $270.00 $35.00 4.2 3.6
41LED B35 2 1B 40 R F 2 (MAG) F42SS 94 0.2 0.2 C-OCC 1747.2 328.5 82.1 0.0 $11.74 $270.00 $35.00 23.0 20.0
71 Mechanical Shop 9 I 60 I60/1 60 0.5 0.5 C-OCC 2329.6 1,258.0 314.5 0.0 $44.97 $270.00 $35.00 6.0 5.2
41LED B27 9 1B 40 R F 2 (MAG) F42SS 94 0.8 0.8 C-OCC 1747.2 1,478.1 369.5 0.0 $52.84 $270.00 $35.00 5.1 4.4
41LED B25 4 1B 40 R F 2 (MAG) F42SS 94 0.4 0.4 C-OCC 1747.2 656.9 164.2 0.0 $23.49 $270.00 $35.00 11.5 10.0
41LED B38 4 1B 40 R F 2 (MAG) F42SS 94 0.4 0.4 C-OCC 1747.2 656.9 164.2 0.0 $23.49 $270.00 $35.00 11.5 10.0
196LED B39 6 W 32 C F 4 (ELE) F44ILL 112 0.7 0.7 C-OCC 1747.2 1,174.1 293.5 0.0 $41.97 $270.00 $35.00 6.4 5.6
32LED B39A 2 1T 32 R F 2 (ELE) F42LL 60 0.1 0.1 C-OCC 1747.2 209.7 52.4 0.0 $7.50 $270.00 $35.00 36.0 31.4
32LED B39A 4 1T 32 R F 2 (ELE) F42LL 60 0.2 0.2 C-OCC 1747.2 419.3 104.8 0.0 $14.99 $270.00 $35.00 18.0 15.7
32LED B39A 4 1T 32 R F 2 (ELE) F42LL 60 0.2 0.2 C-OCC 1747.2 419.3 104.8 0.0 $14.99 $270.00 $35.00 18.0 15.7
32LED B40 4 1T 32 R F 2 (ELE) F42LL 60 0.2 0.2 C-OCC 1747.2 419.3 104.8 0.0 $14.99 $270.00 $35.00 18.0 15.7
32LED B40 3 1T 32 R F 2 (ELE) F42LL 60 0.2 0.2 C-OCC 1747.2 314.5 78.6 0.0 $11.24 $270.00 $35.00 24.0 20.9
32LED B40 3 1T 32 R F 2 (ELE) F42LL 60 0.2 0.2 C-OCC 1747.2 314.5 78.6 0.0 $11.24 $270.00 $35.00 24.0 20.9
32LED B40 6 1T 32 R F 2 (ELE) F42LL 60 0.4 0.4 C-OCC 1747.2 629.0 157.2 0.0 $22.49 $270.00 $35.00 12.0 10.5
32LED B40 23 1T 32 R F 2 (ELE) F42LL 60 1.4 1.4 C-OCC 1747.2 2,411.1 602.8 0.0 $86.20 $270.00 $35.00 3.1 2.7
41LED B2 8 1B 40 R F 2 (MAG) F42SS 94 0.8 0.8 C-OCC 1747.2 1,313.9 328.5 0.0 $46.97 $270.00 $35.00 5.7 5.0
196LED Carpentor Shop 16 W 32 C F 4 (ELE) F44ILL 112 1.8 1.8 C-OCC 1747.2 3,131.0 782.7 0.0 $111.93 $270.00 $35.00 2.4 2.1
71 B6 11 I 60 I60/1 60 0.7 0.7 C-OCC 1747.2 1,153.2 288.3 0.0 $41.23 $270.00 $35.00 6.5 5.7
71 131 2 I 60 I60/1 60 0.1 0.1 C-OCC 1747.2 209.7 52.4 0.0 $7.50 $270.00 $35.00 36.0 31.4
247LED Book Binding 6 T 40 R F 3 (MAG) F43SE 136 0.8 0.8 C-OCC 1747.2 1,425.7 356.4 0.0 $50.97 $270.00 $35.00 5.3 4.6
71 B14 2 I 60 I60/1 60 0.1 0.1 C-OCC 1747.2 209.7 52.4 0.0 $7.50 $270.00 $35.00 36.0 31.4
247LED Electric Room 4 T 40 R F 3 (MAG) F43SE 136 0.5 0.5 NONE 2912 1,584.1 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
5LED B45 1 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 0.1 C-OCC 1747.2 104.8 26.2 0.0 $3.75 $270.00 $35.00 72.0 62.7
185LED B45 4 T 40 R F 4 (ELE) F44SE 172 0.7 0.7 C-OCC 1747.2 1,202.1 300.5 0.0 $42.97 $270.00 $35.00 6.3 5.5
71 B45 2 I 60 I60/1 60 0.1 0.1 C-OCC 1747.2 209.7 52.4 0.0 $7.50 $270.00 $35.00 36.0 31.4
185LED B45 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
185LED B46 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
185LED B47 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 C-OCC 1747.2 601.0 150.3 0.0 $21.49 $270.00 $35.00 12.6 10.9
71 B48 4 I 60 I60/1 60 0.2 0.2 C-OCC 1747.2 419.3 104.8 0.0 $14.99 $270.00 $35.00 18.0 15.7
41LED B48 1 1B 40 R F 2 (MAG) F42SS 94 0.1 0.1 C-OCC 1747.2 164.2 41.1 0.0 $5.87 $270.00 $35.00 46.0 40.0
25 B48 2 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.1 0.1 C-OCC 1747.2 97.8 24.5 0.0 $3.50 $270.00 $35.00 77.2 67.2
41LED Hallway 7 1B 40 R F 2 (MAG) F42SS 94 0.7 0.7 NONE 8736 5,748.3 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
41LED Mechanical Room 1 1B 40 R F 2 (MAG) F42SS 94 0.1 0.1 NONE 2912 273.7 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
185LED Mechanical Room 1 T 40 R F 4 (ELE) F44SE 172 0.2 0.2 NONE 2912 500.9 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
41LED Mechanical Room 6 1B 40 R F 2 (MAG) F42SS 94 0.6 0.6 NONE 2912 1,642.4 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
185LED Mechanical Room 2 T 40 R F 4 (ELE) F44SE 172 0.3 0.3 NONE 2912 1,001.7 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
185LED Storage 1 T 40 R F 4 (ELE) F44SE 172 0.2 0.2 C-OCC 2329.6 400.7 100.2 0.0 $14.32 $270.00 $35.00 18.8 16.4
32LED Hallway next to Elevator 10 1T 32 R F 2 (ELE) F42LL 60 0.6 0.6 NONE 8736 5,241.6 0.0 0.0 $0.00 $0.00 $0.00 #DIV/0!
0 #N/A #VALUE! #VALUE! #N/A #VALUE! #VALUE! #VALUE!
0 #N/A #VALUE! #VALUE! #N/A #VALUE! #VALUE! #VALUE!
0 #N/A #VALUE! #VALUE! #N/A #VALUE! #VALUE! #VALUE!
0 #N/A #VALUE! #VALUE! #N/A #VALUE! #VALUE! #VALUE!
Total 2,475 268.2 268.2 637,496.56 100,568.98 0.0 14381.4 85860.0 11130.0
0.0 $0Demand Savings
1/22/2015 Page 12, ECM-L2
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
ECM-L3 Lighting Replacements with Occupancy Sensors $3.79 $/kW
Area Description No. of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space Exist Control Annual Hours Annual kWh Number of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space
Retrofit
Control Annual Hours Annual kWh
Annual kWh
Saved Annual kW Saved Annual $ Saved Retrofit Cost
NJ Smart Start
Lighting
Incentive
Simple Payback
With Out
Incentive Simple Payback
Field Code Unique description of the location - Room number/Room
name: Floor number (if applicable)
No. of fixtures
before the retrofit
Lighting Fixture Code Code from Table of Standard
Fixture Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
Pre-inst.
control device
Estimated daily
hours for the
usage group
(kW/space) *
(Annual Hours)
No. of fixtures after
the retrofit
Lighting Fixture Code Code from Table of
Standard Fixture
Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) *
(Number of
Fixtures)
Retrofit control
device
Estimated
annual hours
for the usage
group
(kW/space) *
(Annual
Hours)
(Original Annual
kWh) - (Retrofit
Annual kWh)
(Original Annual
kW) - (Retrofit
Annual kW)
(kWh Saved) *
($/kWh)
Cost for
renovations to
lighting system
Prescriptive
Lighting
Measures
Length of time
for renovations
cost to be
recovered
Length of time for
renovations cost to
be recovered
32LED 3rd floor Hallway 12 1T 32 R F 2 (ELE) F42LL 60 0.7 SW 8736 6,290 12 4 ft LED Tube 200732x2 30 0.4 NONE 8,736 3,145 3,145 0.4 466.10$ 2,804.40$ -$ 6.0 6.0
185LED 338B 8 T 40 R F 4 (ELE) F44SE 172 1.4 SW 2184 3,005 8 T 74 R LED RTLED50 50 0.4 NONE 2,184 874 2,132 1.0 349.20$ 1,890.00$ -$ 5.4 5.4
119 338 6 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 1.3 SW 2184 2,830 6 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 1.3 C-OCC 1,747 2,264 566 0.0 80.95$ 270.00$ 35$ 3.3 2.9
35LED 338 2 T 32 R F 3 (ELE) F43ILL/2 90 0.2 SW 2184 393 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 260 0.1 41.96$ 742.50$ 35$ 17.7 16.9
185LED 340 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
185LED 342 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
185LED 342 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
185LED 343 8 T 40 R F 4 (ELE) F44SE 172 1.4 SW 2184 3,005 8 T 74 R LED RTLED50 50 0.4 C-OCC 1,747 699 2,306 1.0 374.19$ 2,160.00$ 35$ 5.8 5.7
35LED 344 3 T 32 R F 3 (ELE) F43ILL/2 90 0.3 SW 2184 590 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 390 0.2 62.94$ 978.75$ 35$ 15.6 15.0
185LED 345 6 T 40 R F 4 (ELE) F44SE 172 1.0 SW 2184 2,254 6 T 74 R LED RTLED50 50 0.3 C-OCC 1,747 524 1,730 0.7 280.64$ 1,687.50$ 35$ 6.0 5.9
185LED 346 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
185LED 346 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
185LED 348 8 T 40 R F 4 (ELE) F44SE 172 1.4 SW 2184 3,005 8 T 74 R LED RTLED50 50 0.4 C-OCC 1,747 699 2,306 1.0 374.19$ 2,160.00$ 35$ 5.8 5.7
185LED 348 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 865 0.4 140.32$ 978.75$ 35$ 7.0 6.7
119 347 3 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 0.6 SW 2184 1,415 3 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 0.6 C-OCC 1,747 1,132 283 0.0 40.48$ 270.00$ 35$ 6.7 5.8
119 347 1 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 0.2 SW 2184 472 1 DC BOX 34 6 (12 LAMP FIXTURE) F46EE 216 0.2 C-OCC 1,747 377 94 0.0 13.49$ 270.00$ 35$ 20.0 17.4
32LED Hallway 14 1T 32 R F 2 (ELE) F42LL 60 0.8 SW 8736 7,338 14 4 ft LED Tube 200732x2 30 0.4 NONE 8,736 3,669 3,669 0.4 543.79$ 3,271.80$ -$ 6.0 6.0
41LED 303A 5 1B 40 R F 2 (MAG) F42SS 94 0.5 SW 2184 1,026 5 4 ft LED Tube 200732x2 30 0.2 C-OCC 1,747 262 764 0.3 123.86$ 1,438.50$ 35$ 11.6 11.3
41LED Judge Chamber 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 210 612 0.3 99.09$ 1,204.80$ 35$ 12.2 11.8
71 Courthouse 94 I 60 I60/1 60 5.6 SW 2125 11,985 94 CF 26 CFQ26/1-L 27 2.5 NONE 2,125 5,393 6,592 3.1 1,083.70$ 634.50$ -$ 0.6 0.6
41LED Courthouse 1 1B 40 R F 2 (MAG) F42SS 94 0.1 SW 2125 200 1 4 ft LED Tube 200732x2 30 0.0 NONE 2,125 64 136 0.1 22.36$ 233.70$ -$ 10.5 10.5
41LED 302B 5 1B 40 R F 2 (MAG) F42SS 94 0.5 SW 2184 1,026 5 4 ft LED Tube 200732x2 30 0.2 C-OCC 1,747 262 764 0.3 123.86$ 1,438.50$ 35$ 11.6 11.3
247LED 304 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
41LED 304 1 1B 40 R F 2 (MAG) F42SS 94 0.1 SW 2184 205 1 4 ft LED Tube 200732x2 30 0.0 C-OCC 1,747 52 153 0.1 24.77$ 503.70$ 35$ 20.3 18.9
247LED 304 1 T 40 R F 3 (MAG) F43SE 136 0.1 SW 2184 297 1 T 59 R LED RTLED38 38 0.0 C-OCC 1,747 66 231 0.1 37.44$ 506.25$ 35$ 13.5 12.6
185LED 304 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
185LED 304 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
32LED Hallway 10 1T 32 R F 2 (ELE) F42LL 60 0.6 SW 8736 5,242 10 4 ft LED Tube 200732x2 30 0.3 NONE 8,736 2,621 2,621 0.3 388.42$ 2,337.00$ -$ 6.0 6.0
247LED 312 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
185LED Hallway 10 T 40 R F 4 (ELE) F44SE 172 1.7 SW 8736 15,026 10 T 74 R LED RTLED50 50 0.5 NONE 8,736 4,368 10,658 1.2 1,579.57$ 2,362.50$ -$ 1.5 1.5
185LED Mens Room 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 865 0.4 140.32$ 978.75$ 35$ 7.0 6.7
185LED Womens Room 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 865 0.4 140.32$ 978.75$ 35$ 7.0 6.7
247LED 321A 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
32LED 321A 2 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 262 2 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 105 157 0.1 25.22$ 737.40$ 35$ 29.2 27.9
247LED 321 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
247LED 322 12 T 40 R F 3 (MAG) F43SE 136 1.6 SW 2184 3,564 12 T 59 R LED RTLED38 38 0.5 C-OCC 1,747 797 2,768 1.2 449.25$ 3,105.00$ 35$ 6.9 6.8
185LED Mail Room 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
185LED 325 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
185LED 325 5 T 40 R F 4 (ELE) F44SE 172 0.9 SW 2184 1,878 5 T 74 R LED RTLED50 50 0.3 C-OCC 1,747 437 1,441 0.6 233.87$ 1,451.25$ 35$ 6.2 6.1
185LED 325 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
32LED Hallway 4 1T 32 R F 2 (ELE) F42LL 60 0.2 SW 8736 2,097 4 4 ft LED Tube 200732x2 30 0.1 C-OCC 8,736 1,048 1,048 0.1 155.37$ 1,204.80$ 35$ 7.8 7.5
185LED 335 19 T 40 R F 4 (ELE) F44SE 172 3.3 SW 2184 7,137 19 T 74 R LED RTLED50 50 1.0 C-OCC 1,747 1,660 5,477 2.3 888.70$ 4,758.75$ 35$ 5.4 5.3
247LED café 28 T 40 R F 3 (MAG) F43SE 136 3.8 SW 1820 6,931 28 T 59 R LED RTLED38 38 1.1 NONE 1,820 1,936 4,994 2.7 838.95$ 6,615.00$ -$ 7.9 7.9
185LED café 10 T 40 R F 4 (ELE) F44SE 172 1.7 SW 1820 3,130 10 T 74 R LED RTLED50 50 0.5 C-OCC 1,820 910 2,220 1.2 373.00$ 2,632.50$ 35$ 7.1 7.0
247LED Café Individual Room 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 1820 495 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,820 138 357 0.2 59.93$ 742.50$ 35$ 12.4 11.8
185LED Café Individual Room 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 1820 626 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,820 182 444 0.2 74.60$ 742.50$ 35$ 10.0 9.5
196LED Hallway 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 8736 3,914 4 T 74 R LED RTLED50 50 0.2 C-OCC 8,736 1,747 2,167 0.2 321.09$ 1,215.00$ 35$ 3.8 3.7
196LED 331 32 W 32 C F 4 (ELE) F44ILL 112 3.6 SW 2184 7,827 32 T 74 R LED RTLED50 50 1.6 C-OCC 1,747 2,796 5,032 2.0 809.80$ 7,830.00$ 35$ 9.7 9.6
247LED 331 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
5LED Mens Room 1 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 SW 2184 131 1 2T XX R LED 2RTLED 25 0.0 C-OCC 1,747 44 87 0.0 14.08$ 472.50$ 35$ 33.5 31.1
250 329 6 T 54 W F 3 (ELE) (T-5) F43GHL 177 1.1 SW 2184 2,319 6 T 54 W F 3 (ELE) (T-5) F43GHL 177 1.1 C-OCC 1,747 1,856 464 0.0 66.34$ 270.00$ 35$ 4.1 3.5
247LED 328 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
250 4th Floor 436 4 T 54 W F 3 (ELE) (T-5) F43GHL 177 0.7 SW 2184 1,546 4 T 54 W F 3 (ELE) (T-5) F43GHL 177 0.7 C-OCC 1,747 1,237 309 0.0 44.22$ 270.00$ 35$ 6.1 5.3
247LED 436 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
247LED Office 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 531 1,845 0.8 299.50$ 2,160.00$ 35$ 7.2 7.1
32LED Office 1 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 131 1 4 ft LED Tube 200732x2 30 0.0 C-OCC 1,747 52 79 0.0 12.61$ 503.70$ 35$ 40.0 37.2
196LED 435 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 2184 978 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 629 0.2 101.22$ 1,215.00$ 35$ 12.0 11.7
247LED 435 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
185LED Hallway 7 T 40 R F 4 (ELE) F44SE 172 1.2 SW 8736 10,518 7 T 74 R LED RTLED50 50 0.4 C-OCC 8,736 3,058 7,461 0.9 1,105.70$ 1,923.75$ 35$ 1.7 1.7
247LED 438 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 C-OCC 1,747 930 3,229 1.4 524.12$ 3,577.50$ 35$ 6.8 6.8
247LED 439 9 T 40 R F 3 (MAG) F43SE 136 1.2 SW 2184 2,673 9 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 598 2,076 0.9 336.93$ 2,396.25$ 35$ 7.1 7.0
247LED 439 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 439 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
247LED 443 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 398 1,384 0.6 224.62$ 1,687.50$ 35$ 7.5 7.4
247LED 444 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 C-OCC 1,747 930 3,229 1.4 524.12$ 3,577.50$ 35$ 6.8 6.8
185LED Hallway 10 T 40 R F 4 (ELE) F44SE 172 1.7 SW 8736 15,026 10 T 74 R LED RTLED50 50 0.5 C-OCC 8,736 4,368 10,658 1.2 1,579.57$ 2,632.50$ 35$ 1.7 1.6
247LED 445 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 C-OCC 1,747 930 3,229 1.4 524.12$ 3,577.50$ 35$ 6.8 6.8
247LED 445 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
247LED 449A 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 449A 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
247LED 449A 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
5LED 402 8 2T 32 R F 2 (u) (ELE) FU2LL 60 0.5 SW 2184 1,048 8 2T XX R LED 2RTLED 25 0.2 C-OCC 1,747 349 699 0.3 112.67$ 1,890.00$ 35$ 16.8 16.5
5LED 402 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.3 SW 2184 655 5 2T XX R LED 2RTLED 25 0.1 C-OCC 1,747 218 437 0.2 70.42$ 1,282.50$ 35$ 18.2 17.7
5LED 402 9 2T 32 R F 2 (u) (ELE) FU2LL 60 0.5 SW 2184 1,179 9 2T XX R LED 2RTLED 25 0.2 C-OCC 1,747 393 786 0.3 126.76$ 2,092.50$ 35$ 16.5 16.2
185LED Hallway 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 8736 6,010 4 T 74 R LED RTLED50 50 0.2 C-OCC 8,736 1,747 4,263 0.5 631.83$ 1,215.00$ 35$ 1.9 1.9
196LED Hallway 3 W 32 C F 4 (ELE) F44ILL 112 0.3 SW 8736 2,935 3 T 74 R LED RTLED50 50 0.2 C-OCC 8,736 1,310 1,625 0.2 240.82$ 978.75$ 35$ 4.1 3.9
71 Hallway 2 I 60 I60/1 60 0.1 SW 8736 1,048 2 CF 26 CFQ26/1-L 27 0.1 NONE 8,736 472 577 0.1 85.45$ 13.50$ -$ 0.2 0.2
5LED 405 2 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 SW 2184 262 2 2T XX R LED 2RTLED 25 0.1 C-OCC 1,747 87 175 0.1 28.17$ 675.00$ 35$ 24.0 22.7
25 405 1 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.0 SW 2184 61 1 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.0 C-OCC 1,747 49 12 0.0 1.75$ 270.00$ 35$ 154.4 134.4
5LED 405 6 2T 32 R F 2 (u) (ELE) FU2LL 60 0.4 SW 2184 786 6 2T XX R LED 2RTLED 25 0.2 C-OCC 1,747 262 524 0.2 84.51$ 1,485.00$ 35$ 17.6 17.2
5LED 405 1 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 SW 2184 131 1 2T XX R LED 2RTLED 25 0.0 C-OCC 1,747 44 87 0.0 14.08$ 472.50$ 35$ 33.5 31.1
196LED 405 1 W 32 C F 4 (ELE) F44ILL 112 0.1 SW 2184 245 1 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 87 157 0.1 25.31$ 506.25$ 35$ 20.0 18.6
5LED 405 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.3 SW 2184 655 5 2T XX R LED 2RTLED 25 0.1 C-OCC 1,747 218 437 0.2 70.42$ 1,282.50$ 35$ 18.2 17.7
5LED 405 4 2T 32 R F 2 (u) (ELE) FU2LL 60 0.2 SW 2184 524 4 2T XX R LED 2RTLED 25 0.1 C-OCC 1,747 175 349 0.1 56.34$ 1,080.00$ 35$ 19.2 18.5
5LED 405 10 2T 32 R F 2 (u) (ELE) FU2LL 60 0.6 SW 2184 1,310 10 2T XX R LED 2RTLED 25 0.3 C-OCC 1,747 437 874 0.4 140.84$ 2,295.00$ 35$ 16.3 16.0
25 405 16 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.4 SW 2184 978 16 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.4 C-OCC 1,747 783 196 0.0 27.98$ 270.00$ 35$ 9.6 8.4
5LED 403 8 2T 32 R F 2 (u) (ELE) FU2LL 60 0.5 SW 2184 1,048 8 2T XX R LED 2RTLED 25 0.2 C-OCC 1,747 349 699 0.3 112.67$ 1,890.00$ 35$ 16.8 16.5
25 403 14 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.4 SW 2184 856 14 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.4 C-OCC 1,747 685 171 0.0 24.49$ 270.00$ 35$ 11.0 9.6
247LED 408 15 T 40 R F 3 (MAG) F43SE 136 2.0 SW 2184 4,455 15 T 59 R LED RTLED38 38 0.6 C-OCC 1,747 996 3,459 1.5 561.56$ 3,813.75$ 35$ 6.8 6.7
35LED 411 10 T 32 R F 3 (ELE) F43ILL/2 90 0.9 SW 2184 1,966 10 T 59 R LED RTLED38 38 0.4 C-OCC 1,747 664 1,302 0.5 209.79$ 2,632.50$ 35$ 12.5 12.4
185LED 411 6 T 40 R F 4 (ELE) F44SE 172 1.0 SW 2184 2,254 6 T 74 R LED RTLED50 50 0.3 C-OCC 1,747 524 1,730 0.7 280.64$ 1,687.50$ 35$ 6.0 5.9
185LED Hallway 10 T 40 R F 4 (ELE) F44SE 172 1.7 SW 8736 15,026 10 T 74 R LED RTLED50 50 0.5 NONE 8,736 4,368 10,658 1.2 1,579.57$ 2,362.50$ -$ 1.5 1.5
35LED 413 8 T 32 R F 3 (ELE) F43ILL/2 90 0.7 SW 2184 1,572 8 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 531 1,041 0.4 167.83$ 2,160.00$ 35$ 12.9 12.7
35LED 414 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 SW 2184 786 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 521 0.2 83.92$ 1,215.00$ 35$ 14.5 14.1
32LED 414 1 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 131 1 4 ft LED Tube 200732x2 30 0.0 C-OCC 1,747 52 79 0.0 12.61$ 503.70$ 35$ 40.0 37.2
35LED 416 6 T 32 R F 3 (ELE) F43ILL/2 90 0.5 SW 2184 1,179 6 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 398 781 0.3 125.87$ 1,687.50$ 35$ 13.4 13.1
35LED 417A 7 T 32 R F 3 (ELE) F43ILL/2 90 0.6 SW 2184 1,376 7 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 465 911 0.4 146.85$ 1,923.75$ 35$ 13.1 12.9
35LED 417A 12 T 32 R F 3 (ELE) F43ILL/2 90 1.1 SW 2184 2,359 12 T 59 R LED RTLED38 38 0.5 C-OCC 1,747 797 1,562 0.6 251.75$ 3,105.00$ 35$ 12.3 12.2
35LED 417A 5 T 32 R F 3 (ELE) F43ILL/2 90 0.5 SW 2184 983 5 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 332 651 0.3 104.89$ 1,451.25$ 35$ 13.8 13.5
35LED 417A 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 SW 2184 786 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 521 0.2 83.92$ 1,215.00$ 35$ 14.5 14.1
35LED 417A 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 SW 2184 786 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 521 0.2 83.92$ 1,215.00$ 35$ 14.5 14.1
247LED 417A 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
247LED 422A 15 T 40 R F 3 (MAG) F43SE 136 2.0 SW 2184 4,455 15 T 59 R LED RTLED38 38 0.6 C-OCC 1,747 996 3,459 1.5 561.56$ 3,813.75$ 35$ 6.8 6.7
247LED 427D 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 531 1,845 0.8 299.50$ 2,160.00$ 35$ 7.2 7.1
185LED Hallway 10 T 40 R F 4 (ELE) F44SE 172 1.7 SW 8736 15,026 10 T 74 R LED RTLED50 50 0.5 NONE 8,736 4,368 10,658 1.2 1,579.57$ 2,362.50$ -$ 1.5 1.5
35LED 428 15 T 32 R F 3 (ELE) F43ILL/2 90 1.4 SW 2184 2,948 15 T 59 R LED RTLED38 38 0.6 C-OCC 1,747 996 1,952 0.8 314.68$ 3,813.75$ 35$ 12.1 12.0
35LED 428 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 SW 2184 786 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 521 0.2 83.92$ 1,215.00$ 35$ 14.5 14.1
35LED 428 4 T 32 R F 3 (ELE) F43ILL/2 90 0.4 SW 2184 786 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 521 0.2 83.92$ 1,215.00$ 35$ 14.5 14.1
196LED Womens Room 3 W 32 C F 4 (ELE) F44ILL 112 0.3 SW 2184 734 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 472 0.2 75.92$ 978.75$ 35$ 12.9 12.4
196LED Mens Room 3 W 32 C F 4 (ELE) F44ILL 112 0.3 SW 2184 734 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 472 0.2 75.92$ 978.75$ 35$ 12.9 12.4
32LED 5th Floor Hallway 10 1T 32 R F 2 (ELE) F42LL 60 0.6 SW 8736 5,242 10 4 ft LED Tube 200732x2 30 0.3 C-OCC 8,736 2,621 2,621 0.3 388.42$ 2,607.00$ 35$ 6.7 6.6
247LED 530 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
41LED 530 1 1B 40 R F 2 (MAG) F42SS 94 0.1 SW 2184 205 1 4 ft LED Tube 200732x2 30 0.0 C-OCC 1,747 52 153 0.1 24.77$ 503.70$ 35$ 20.3 18.9
247LED 530 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
196LED Womens Room 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 2184 978 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 629 0.2 101.22$ 1,215.00$ 35$ 12.0 11.7
247LED 535 10 T 40 R F 3 (MAG) F43SE 136 1.4 SW 2184 2,970 10 T 59 R LED RTLED38 38 0.4 C-OCC 1,747 664 2,306 1.0 374.37$ 2,632.50$ 35$ 7.0 6.9
32LED 535 5 1T 32 R F 2 (ELE) F42LL 60 0.3 SW 2184 655 5 4 ft LED Tube 200732x2 30 0.2 C-OCC 1,747 262 393 0.2 63.04$ 1,438.50$ 35$ 22.8 22.3
247LED 535 5 T 40 R F 3 (MAG) F43SE 136 0.7 SW 2184 1,485 5 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 332 1,153 0.5 187.19$ 1,451.25$ 35$ 7.8 7.6
185LED 535 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
185LED 535 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 865 0.4 140.32$ 978.75$ 35$ 7.0 6.7
185LED 535 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
247LED 524A 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
EXISTING CONDITIONS RETROFIT CONDITIONS COST & SAVINGS ANALYSIS
1/22/2015 Page 13, ECM-L3
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
ECM-L3 Lighting Replacements with Occupancy Sensors $3.79 $/kW
Area Description No. of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space Exist Control Annual Hours Annual kWh Number of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space
Retrofit
Control Annual Hours Annual kWh
Annual kWh
Saved Annual kW Saved Annual $ Saved Retrofit Cost
NJ Smart Start
Lighting
Incentive
Simple Payback
With Out
Incentive Simple Payback
Field Code Unique description of the location - Room number/Room
name: Floor number (if applicable)
No. of fixtures
before the retrofit
Lighting Fixture Code Code from Table of Standard
Fixture Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
Pre-inst.
control device
Estimated daily
hours for the
usage group
(kW/space) *
(Annual Hours)
No. of fixtures after
the retrofit
Lighting Fixture Code Code from Table of
Standard Fixture
Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) *
(Number of
Fixtures)
Retrofit control
device
Estimated
annual hours
for the usage
group
(kW/space) *
(Annual
Hours)
(Original Annual
kWh) - (Retrofit
Annual kWh)
(Original Annual
kW) - (Retrofit
Annual kW)
(kWh Saved) *
($/kWh)
Cost for
renovations to
lighting system
Prescriptive
Lighting
Measures
Length of time
for renovations
cost to be
recovered
Length of time for
renovations cost to
be recovered
EXISTING CONDITIONS RETROFIT CONDITIONS COST & SAVINGS ANALYSIS
247LED 524A 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
32LED Hallway 12 1T 32 R F 2 (ELE) F42LL 60 0.7 SW 8736 6,290 12 4 ft LED Tube 200732x2 30 0.4 NONE 8,736 3,145 3,145 0.4 466.10$ 2,804.40$ -$ 6.0 6.0
247LED 556 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
247LED 556 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
185LED 558 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
185LED 558 16 T 40 R F 4 (ELE) F44SE 172 2.8 SW 2184 6,010 16 T 74 R LED RTLED50 50 0.8 C-OCC 1,747 1,398 4,613 2.0 748.38$ 4,050.00$ 35$ 5.4 5.4
247LED 558 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
41LED 558 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 105 306 0.1 49.55$ 737.40$ 35$ 14.9 14.2
196LED 558 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 2184 978 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 629 0.2 101.22$ 1,215.00$ 35$ 12.0 11.7
71 558 5 I 60 I60/1 60 0.3 SW 2184 655 5 CF 26 CFQ26/1-L 27 0.1 C-OCC 1,747 236 419 0.2 67.47$ 303.75$ 35$ 4.5 4.0
5LED 501A 24 2T 32 R F 2 (u) (ELE) FU2LL 60 1.4 SW 2184 3,145 24 2T XX R LED 2RTLED 25 0.6 C-OCC 1,747 1,048 2,097 0.8 338.02$ 5,130.00$ 35$ 15.2 15.1
71 502 6 I 60 I60/1 60 0.4 SW 2184 786 6 CF 26 CFQ26/1-L 27 0.2 C-OCC 1,747 283 503 0.2 80.96$ 310.50$ 35$ 3.8 3.4
20LED 503A 3 S 28 P F 1 (ELE) F41ILL 31 0.1 SW 2184 203 3 4 ft LED Tube 200732x1 15 0.0 C-OCC 1,747 79 124 0.0 19.98$ 705.60$ 35$ 35.3 33.6
20LED 503A 2 S 28 P F 1 (ELE) F41ILL 31 0.1 SW 2184 135 2 4 ft LED Tube 200732x1 15 0.0 C-OCC 1,747 52 83 0.0 13.32$ 560.40$ 35$ 42.1 39.4
20LED 503A 6 S 28 P F 1 (ELE) F41ILL 31 0.2 SW 2184 406 6 4 ft LED Tube 200732x1 15 0.1 C-OCC 1,747 157 249 0.1 39.97$ 1,141.20$ 35$ 28.6 27.7
71 Restroom 1 I 60 I60/1 60 0.1 SW 2184 131 1 CF 26 CFQ26/1-L 27 0.0 C-OCC 1,747 47 84 0.0 13.49$ 276.75$ 35$ 20.5 17.9
71 Suite 502 1 I 60 I60/1 60 0.1 SW 2184 131 1 CF 26 CFQ26/1-L 27 0.0 C-OCC 1,747 47 84 0.0 13.49$ 276.75$ 35$ 20.5 17.9
71 Hallway 28 I 60 I60/1 60 1.7 SW 8736 14,676 28 CF 26 CFQ26/1-L 27 0.8 NONE 8,736 6,604 8,072 0.9 1,196.33$ 189.00$ -$ 0.2 0.2
196LED 504 2 W 32 C F 4 (ELE) F44ILL 112 0.2 SW 2184 489 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 314 0.1 50.61$ 742.50$ 35$ 14.7 14.0
196LED 504 5 W 32 C F 4 (ELE) F44ILL 112 0.6 SW 2184 1,223 5 T 74 R LED RTLED50 50 0.3 C-OCC 1,747 437 786 0.3 126.53$ 1,451.25$ 35$ 11.5 11.2
5LED 508 4 2T 32 R F 2 (u) (ELE) FU2LL 60 0.2 SW 2184 524 4 2T XX R LED 2RTLED 25 0.1 C-OCC 1,747 175 349 0.1 56.34$ 1,080.00$ 35$ 19.2 18.5
5LED 508 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.3 SW 2184 655 5 2T XX R LED 2RTLED 25 0.1 C-OCC 1,747 218 437 0.2 70.42$ 1,282.50$ 35$ 18.2 17.7
71 508 2 I 60 I60/1 60 0.1 SW 2184 262 2 CF 26 CFQ26/1-L 27 0.1 C-OCC 1,747 94 168 0.1 26.99$ 283.50$ 35$ 10.5 9.2
196LED 507 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 2184 978 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 629 0.2 101.22$ 1,215.00$ 35$ 12.0 11.7
196LED 507 5 W 32 C F 4 (ELE) F44ILL 112 0.6 SW 2184 1,223 5 T 74 R LED RTLED50 50 0.3 C-OCC 1,747 437 786 0.3 126.53$ 1,451.25$ 35$ 11.5 11.2
196LED 507A 2 W 32 C F 4 (ELE) F44ILL 112 0.2 SW 2184 489 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 314 0.1 50.61$ 742.50$ 35$ 14.7 14.0
196LED 507A 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 2184 978 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 629 0.2 101.22$ 1,215.00$ 35$ 12.0 11.7
247LED 509 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
247LED 509 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 398 1,384 0.6 224.62$ 1,687.50$ 35$ 7.5 7.4
247LED 509 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 509 1 T 40 R F 3 (MAG) F43SE 136 0.1 SW 2184 297 1 T 59 R LED RTLED38 38 0.0 C-OCC 1,747 66 231 0.1 37.44$ 506.25$ 35$ 13.5 12.6
196LED 560A 6 W 32 C F 4 (ELE) F44ILL 112 0.7 SW 2184 1,468 6 T 74 R LED RTLED50 50 0.3 C-OCC 1,747 524 943 0.4 151.84$ 1,687.50$ 35$ 11.1 10.9
41LED 559 1 1B 40 R F 2 (MAG) F42SS 94 0.1 SW 2184 205 1 4 ft LED Tube 200732x2 30 0.0 C-OCC 1,747 52 153 0.1 24.77$ 503.70$ 35$ 20.3 18.9
247LED 554 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 398 1,384 0.6 224.62$ 1,687.50$ 35$ 7.5 7.4
196LED 553 3 W 32 C F 4 (ELE) F44ILL 112 0.3 SW 2184 734 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 472 0.2 75.92$ 978.75$ 35$ 12.9 12.4
196LED 552 1 W 32 C F 4 (ELE) F44ILL 112 0.1 SW 2184 245 1 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 87 157 0.1 25.31$ 506.25$ 35$ 20.0 18.6
196LED 552 5 W 32 C F 4 (ELE) F44ILL 112 0.6 SW 2184 1,223 5 T 74 R LED RTLED50 50 0.3 C-OCC 1,747 437 786 0.3 126.53$ 1,451.25$ 35$ 11.5 11.2
247LED 550 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 531 1,845 0.8 299.50$ 2,160.00$ 35$ 7.2 7.1
247LED 551 7 T 40 R F 3 (MAG) F43SE 136 1.0 SW 2184 2,079 7 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 465 1,614 0.7 262.06$ 1,923.75$ 35$ 7.3 7.2
247LED 551 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
5LED 519 2 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 SW 2184 262 2 2T XX R LED 2RTLED 25 0.1 C-OCC 1,747 87 175 0.1 28.17$ 675.00$ 35$ 24.0 22.7
5LED 519 16 2T 32 R F 2 (u) (ELE) FU2LL 60 1.0 SW 2184 2,097 16 2T XX R LED 2RTLED 25 0.4 C-OCC 1,747 699 1,398 0.6 225.35$ 3,510.00$ 35$ 15.6 15.4
5LED 519 6 2T 32 R F 2 (u) (ELE) FU2LL 60 0.4 SW 2184 786 6 2T XX R LED 2RTLED 25 0.2 C-OCC 1,747 262 524 0.2 84.51$ 1,485.00$ 35$ 17.6 17.2
5LED 519 7 2T 32 R F 2 (u) (ELE) FU2LL 60 0.4 SW 2184 917 7 2T XX R LED 2RTLED 25 0.2 C-OCC 1,747 306 612 0.2 98.59$ 1,687.50$ 35$ 17.1 16.8
196LED 514C 6 W 32 C F 4 (ELE) F44ILL 112 0.7 SW 2184 1,468 6 T 74 R LED RTLED50 50 0.3 C-OCC 1,747 524 943 0.4 151.84$ 1,687.50$ 35$ 11.1 10.9
247LED 516 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
247LED 515 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
196LED 510 1 W 32 C F 4 (ELE) F44ILL 112 0.1 SW 2184 245 1 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 87 157 0.1 25.31$ 506.25$ 35$ 20.0 18.6
247LED 510 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 398 1,384 0.6 224.62$ 1,687.50$ 35$ 7.5 7.4
196LED 510 1 W 32 C F 4 (ELE) F44ILL 112 0.1 SW 2184 245 1 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 87 157 0.1 25.31$ 506.25$ 35$ 20.0 18.6
196LED 510 6 W 32 C F 4 (ELE) F44ILL 112 0.7 SW 2184 1,468 6 T 74 R LED RTLED50 50 0.3 C-OCC 1,747 524 943 0.4 151.84$ 1,687.50$ 35$ 11.1 10.9
196LED 511 4 W 32 C F 4 (ELE) F44ILL 112 0.4 SW 2184 978 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 629 0.2 101.22$ 1,215.00$ 35$ 12.0 11.7
247LED 511A 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
247LED 511 Small Offices 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
247LED 511 Small Offices 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
185LED 511 Small Offices 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
247LED 511 Small Offices 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 511 Small Offices 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
5LED 511 Small Offices 12 2T 32 R F 2 (u) (ELE) FU2LL 60 0.7 SW 2184 1,572 12 2T XX R LED 2RTLED 25 0.3 C-OCC 1,747 524 1,048 0.4 169.01$ 2,700.00$ 35$ 16.0 15.8
32LED Hallway 10 1T 32 R F 2 (ELE) F42LL 60 0.6 SW 8736 5,242 10 4 ft LED Tube 200732x2 30 0.3 NONE 8,736 2,621 2,621 0.3 388.42$ 2,337.00$ -$ 6.0 6.0
247LED 549 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 549 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 398 1,384 0.6 224.62$ 1,687.50$ 35$ 7.5 7.4
247LED 548 7 T 40 R F 3 (MAG) F43SE 136 1.0 SW 2184 2,079 7 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 465 1,614 0.7 262.06$ 1,923.75$ 35$ 7.3 7.2
247LED 547 5 T 40 R F 3 (MAG) F43SE 136 0.7 SW 2184 1,485 5 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 332 1,153 0.5 187.19$ 1,451.25$ 35$ 7.8 7.6
32LED Hallway 8 1T 32 R F 2 (ELE) F42LL 60 0.5 SW 8736 4,193 8 4 ft LED Tube 200732x2 30 0.2 NONE 8,736 2,097 2,097 0.2 310.73$ 1,869.60$ -$ 6.0 6.0
247LED 536 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 536 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 537 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
247LED 537 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
247LED 546 7 T 40 R F 3 (MAG) F43SE 136 1.0 SW 2184 2,079 7 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 465 1,614 0.7 262.06$ 1,923.75$ 35$ 7.3 7.2
247LED 546 7 T 40 R F 3 (MAG) F43SE 136 1.0 SW 2184 2,079 7 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 465 1,614 0.7 262.06$ 1,923.75$ 35$ 7.3 7.2
247LED 544 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 544 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 543 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 531 1,845 0.8 299.50$ 2,160.00$ 35$ 7.2 7.1
247LED 542 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 398 1,384 0.6 224.62$ 1,687.50$ 35$ 7.5 7.4
247LED 542 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
35LED 542 6 T 32 R F 3 (ELE) F43ILL/2 90 0.5 SW 2184 1,179 6 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 398 781 0.3 125.87$ 1,687.50$ 35$ 13.4 13.1
247LED 542 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 531 1,845 0.8 299.50$ 2,160.00$ 35$ 7.2 7.1
247LED 542 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 539 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 539 23 T 40 R F 3 (MAG) F43SE 136 3.1 SW 2184 6,832 23 T 59 R LED RTLED38 38 0.9 C-OCC 1,747 1,527 5,304 2.3 861.06$ 5,703.75$ 35$ 6.6 6.6
185LED 2nd Floor 201 6 T 40 R F 4 (ELE) F44SE 172 1.0 SW 2184 2,254 6 T 74 R LED RTLED50 50 0.3 C-OCC 1,747 524 1,730 0.7 280.64$ 1,687.50$ 35$ 6.0 5.9
247LED 202 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 C-OCC 1,747 930 3,229 1.4 524.12$ 3,577.50$ 35$ 6.8 6.8
185LED 202 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
247LED 204 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 205 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 205 next 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
247LED 205 next 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
185LED 206 12 T 40 R F 4 (ELE) F44SE 172 2.1 SW 2184 4,508 12 T 74 R LED RTLED50 50 0.6 C-OCC 1,747 1,048 3,459 1.5 561.28$ 3,105.00$ 35$ 5.5 5.5
41LED 207 6 1B 40 R F 2 (MAG) F42SS 94 0.6 SW 2184 1,232 6 4 ft LED Tube 200732x2 30 0.2 C-OCC 1,747 314 917 0.4 148.64$ 1,672.20$ 35$ 11.3 11.0
247LED 208 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
41LED 208 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 105 306 0.1 49.55$ 737.40$ 35$ 14.9 14.2
247LED 209 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
41LED 209 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 105 306 0.1 49.55$ 737.40$ 35$ 14.9 14.2
5LED 211 5 2T 32 R F 2 (u) (ELE) FU2LL 60 0.3 SW 2184 655 5 2T XX R LED 2RTLED 25 0.1 C-OCC 1,747 218 437 0.2 70.42$ 1,282.50$ 35$ 18.2 17.7
25 213 10 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.3 SW 2184 612 10 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.3 C-OCC 1,747 489 122 0.0 17.49$ 270.00$ 35$ 15.4 13.4
185LED 213 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2184 376 1 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 87 288 0.1 46.77$ 506.25$ 35$ 10.8 10.1
25 214 6 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.2 SW 2184 367 6 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.2 C-OCC 1,747 294 73 0.0 10.49$ 270.00$ 35$ 25.7 22.4
185LED 214 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2184 376 1 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 87 288 0.1 46.77$ 506.25$ 35$ 10.8 10.1
247LED 215 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
185LED 216 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
247LED 217 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
41LED 217 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 105 306 0.1 49.55$ 737.40$ 35$ 14.9 14.2
41LED 219 19 1B 40 R F 2 (MAG) F42SS 94 1.8 SW 2184 3,901 19 4 ft LED Tube 200732x2 30 0.6 C-OCC 1,747 996 2,905 1.2 470.68$ 4,710.30$ 35$ 10.0 9.9
41LED 220 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 210 612 0.3 99.09$ 1,204.80$ 35$ 12.2 11.8
185LED 222 30 T 40 R F 4 (ELE) F44SE 172 5.2 SW 2184 11,269 30 T 74 R LED RTLED50 50 1.5 C-OCC 1,747 2,621 8,649 3.7 1,403.21$ 7,357.50$ 35$ 5.2 5.2
196LED Men's Room 3 W 32 C F 4 (ELE) F44ILL 112 0.3 SW 2184 734 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 472 0.2 75.92$ 978.75$ 35$ 12.9 12.4
196LED Women's Room 3 W 32 C F 4 (ELE) F44ILL 112 0.3 SW 2184 734 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 472 0.2 75.92$ 978.75$ 35$ 12.9 12.4
32LED Service Room 2 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 262 2 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 105 157 0.1 25.22$ 737.40$ 35$ 29.2 27.9
185LED 226 7 T 40 R F 4 (ELE) F44SE 172 1.2 SW 2184 2,630 7 T 74 R LED RTLED50 50 0.4 C-OCC 1,747 612 2,018 0.9 327.42$ 1,923.75$ 35$ 5.9 5.8
32LED 226 1 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 131 1 4 ft LED Tube 200732x2 30 0.0 C-OCC 1,747 52 79 0.0 12.61$ 503.70$ 35$ 40.0 37.2
185LED 226 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
247LED 227 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 531 1,845 0.8 299.50$ 2,160.00$ 35$ 7.2 7.1
185LED 228 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 865 0.4 140.32$ 978.75$ 35$ 7.0 6.7
247LED 231 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
185LED 231 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
41LED 232 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 210 612 0.3 99.09$ 1,204.80$ 35$ 12.2 11.8
247LED 232 8 T 40 R F 3 (MAG) F43SE 136 1.1 SW 2184 2,376 8 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 531 1,845 0.8 299.50$ 2,160.00$ 35$ 7.2 7.1
41LED 233 5 1B 40 R F 2 (MAG) F42SS 94 0.5 SW 2184 1,026 5 4 ft LED Tube 200732x2 30 0.2 C-OCC 1,747 262 764 0.3 123.86$ 1,438.50$ 35$ 11.6 11.3
247LED 233 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 C-OCC 1,747 930 3,229 1.4 524.12$ 3,577.50$ 35$ 6.8 6.8
71 233 Storage 2 I 60 I60/1 60 0.1 SW 2912 349 2 CF 26 CFQ26/1-L 27 0.1 C-OCC 2,330 126 224 0.1 34.98$ 283.50$ 35$ 8.1 7.1
185LED 236 19 T 40 R F 4 (ELE) F44SE 172 3.3 SW 2184 7,137 19 T 74 R LED RTLED50 50 1.0 C-OCC 1,747 1,660 5,477 2.3 888.70$ 4,758.75$ 35$ 5.4 5.3
1/22/2015 Page 14, ECM-L3
Energy Audit of Essex County - Hall of Records
CHA Project No.29142 Cost of Electricity: $0.143 $/kWh
ECM-L3 Lighting Replacements with Occupancy Sensors $3.79 $/kW
Area Description No. of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space Exist Control Annual Hours Annual kWh Number of Fixtures Standard Fixture Code Fixture Code
Watts per
Fixture kW/Space
Retrofit
Control Annual Hours Annual kWh
Annual kWh
Saved Annual kW Saved Annual $ Saved Retrofit Cost
NJ Smart Start
Lighting
Incentive
Simple Payback
With Out
Incentive Simple Payback
Field Code Unique description of the location - Room number/Room
name: Floor number (if applicable)
No. of fixtures
before the retrofit
Lighting Fixture Code Code from Table of Standard
Fixture Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) * (Fixt
No.)
Pre-inst.
control device
Estimated daily
hours for the
usage group
(kW/space) *
(Annual Hours)
No. of fixtures after
the retrofit
Lighting Fixture Code Code from Table of
Standard Fixture
Wattages
Value from
Table of
Standard
Fixture
Wattages
(Watts/Fixt) *
(Number of
Fixtures)
Retrofit control
device
Estimated
annual hours
for the usage
group
(kW/space) *
(Annual
Hours)
(Original Annual
kWh) - (Retrofit
Annual kWh)
(Original Annual
kW) - (Retrofit
Annual kW)
(kWh Saved) *
($/kWh)
Cost for
renovations to
lighting system
Prescriptive
Lighting
Measures
Length of time
for renovations
cost to be
recovered
Length of time for
renovations cost to
be recovered
EXISTING CONDITIONS RETROFIT CONDITIONS COST & SAVINGS ANALYSIS
185LED 238 15 T 40 R F 4 (ELE) F44SE 172 2.6 SW 2184 5,635 15 T 74 R LED RTLED50 50 0.8 C-OCC 1,747 1,310 4,324 1.8 701.61$ 3,813.75$ 35$ 5.4 5.4
185LED 242 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
247LED 242 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
32LED 242 6 1T 32 R F 2 (ELE) F42LL 60 0.4 SW 2184 786 6 4 ft LED Tube 200732x2 30 0.2 C-OCC 1,747 314 472 0.2 75.65$ 1,672.20$ 35$ 22.1 21.6
196LED lobby 2 W 32 C F 4 (ELE) F44ILL 112 0.2 SW 8736 1,957 2 T 74 R LED RTLED50 50 0.1 NONE 8,736 874 1,083 0.1 160.55$ 472.50$ -$ 2.9 2.9
247LED 244 12 T 40 R F 3 (MAG) F43SE 136 1.6 SW 2184 3,564 12 T 59 R LED RTLED38 38 0.5 C-OCC 1,747 797 2,768 1.2 449.25$ 3,105.00$ 35$ 6.9 6.8
41LED 244 6 1B 40 R F 2 (MAG) F42SS 94 0.6 SW 2184 1,232 6 4 ft LED Tube 200732x2 30 0.2 C-OCC 1,747 314 917 0.4 148.64$ 1,672.20$ 35$ 11.3 11.0
41LED Attendent 5 1B 40 R F 2 (MAG) F42SS 94 0.5 SW 2184 1,026 5 4 ft LED Tube 200732x2 30 0.2 C-OCC 1,747 262 764 0.3 123.86$ 1,438.50$ 35$ 11.6 11.3
41LED 247 155 1B 40 R F 2 (MAG) F42SS 94 14.6 SW 2184 31,821 155 4 ft LED Tube 200732x2 30 4.7 C-OCC 1,747 8,124 23,696 9.9 3,839.75$ 36,493.50$ 35$ 9.5 9.5
247LED 247 3 T 40 R F 3 (MAG) F43SE 136 0.4 SW 2184 891 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 692 0.3 112.31$ 978.75$ 35$ 8.7 8.4
41LED 247 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 210 612 0.3 99.09$ 1,204.80$ 35$ 12.2 11.8
5LED 248 66 2T 32 R F 2 (u) (ELE) FU2LL 60 4.0 SW 2184 8,649 66 2T XX R LED 2RTLED 25 1.7 C-OCC 1,747 2,883 5,766 2.3 929.56$ 13,635.00$ 35$ 14.7 14.6
5LED 248 66 2T 32 R F 2 (u) (ELE) FU2LL 60 4.0 SW 2184 8,649 66 2T XX R LED 2RTLED 25 1.7 C-OCC 1,747 2,883 5,766 2.3 929.56$ 13,635.00$ 35$ 14.7 14.6
196LED 248 45 W 32 C F 4 (ELE) F44ILL 112 5.0 SW 2184 11,007 45 T 74 R LED RTLED50 50 2.3 C-OCC 1,747 3,931 7,076 2.8 1,138.78$ 10,901.25$ 35$ 9.6 9.5
196LED 248 2 W 32 C F 4 (ELE) F44ILL 112 0.2 SW 2184 489 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 314 0.1 50.61$ 742.50$ 35$ 14.7 14.0
196LED 248 2 W 32 C F 4 (ELE) F44ILL 112 0.2 SW 2184 489 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 314 0.1 50.61$ 742.50$ 35$ 14.7 14.0
35LED 1st Floor 101 29 T 32 R F 3 (ELE) F43ILL/2 90 2.6 SW 2184 5,700 29 T 59 R LED RTLED38 38 1.1 C-OCC 1,747 1,925 3,775 1.5 608.38$ 7,121.25$ 35$ 11.7 11.6
35LED 102 5 T 32 R F 3 (ELE) F43ILL/2 90 0.5 SW 2184 983 5 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 332 651 0.3 104.89$ 1,451.25$ 35$ 13.8 13.5
41LED 103 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 105 306 0.1 49.55$ 737.40$ 35$ 14.9 14.2
185LED 104 8 T 40 R F 4 (ELE) F44SE 172 1.4 SW 2184 3,005 8 T 74 R LED RTLED50 50 0.4 C-OCC 1,747 699 2,306 1.0 374.19$ 2,160.00$ 35$ 5.8 5.7
71 Entrance Hall 16 I 60 I60/1 60 1.0 SW 8736 8,387 16 CF 26 CFQ26/1-L 27 0.4 NONE 8,736 3,774 4,613 0.5 683.62$ 108.00$ -$ 0.2 0.2
71 Entrance Hall 36 I 60 I60/1 60 2.2 SW 2184 4,717 36 CF 26 CFQ26/1-L 27 1.0 C-OCC 1,747 1,698 3,019 1.2 485.77$ 513.00$ 35$ 1.1 1.0
247LED 107 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 C-OCC 1,747 930 3,229 1.4 524.12$ 3,577.50$ 35$ 6.8 6.8
185LED 107 Small Room 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2184 376 1 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 87 288 0.1 46.77$ 506.25$ 35$ 10.8 10.1
247LED 107 Small Room 2 T 40 R F 3 (MAG) F43SE 136 0.3 SW 2184 594 2 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 133 461 0.2 74.87$ 742.50$ 35$ 9.9 9.4
41LED Chief Room 6 1B 40 R F 2 (MAG) F42SS 94 0.6 SW 2184 1,232 6 4 ft LED Tube 200732x2 30 0.2 C-OCC 1,747 314 917 0.4 148.64$ 1,672.20$ 35$ 11.3 11.0
247LED 110 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
41LED 111 11 1B 40 R F 2 (MAG) F42SS 94 1.0 SW 2184 2,258 11 4 ft LED Tube 200732x2 30 0.3 C-OCC 1,747 577 1,682 0.7 272.50$ 2,840.70$ 35$ 10.4 10.3
185LED 111 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 865 0.4 140.32$ 978.75$ 35$ 7.0 6.7
185LED Assitant Chief 8 T 40 R F 4 (ELE) F44SE 172 1.4 SW 2184 3,005 8 T 74 R LED RTLED50 50 0.4 C-OCC 1,747 699 2,306 1.0 374.19$ 2,160.00$ 35$ 5.8 5.7
185LED 115 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
41LED 115 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 210 612 0.3 99.09$ 1,204.80$ 35$ 12.2 11.8
247LED 115 20 T 40 R F 3 (MAG) F43SE 136 2.7 SW 2184 5,940 20 T 59 R LED RTLED38 38 0.8 C-OCC 1,747 1,328 4,613 2.0 748.74$ 4,995.00$ 35$ 6.7 6.6
185LED Men's Room 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 865 0.4 140.32$ 978.75$ 35$ 7.0 6.7
185LED Women's Room 3 T 40 R F 4 (ELE) F44SE 172 0.5 SW 2184 1,127 3 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 262 865 0.4 140.32$ 978.75$ 35$ 7.0 6.7
5LED Receiving Room 8 2T 32 R F 2 (u) (ELE) FU2LL 60 0.5 SW 2184 1,048 8 2T XX R LED 2RTLED 25 0.2 C-OCC 1,747 349 699 0.3 112.67$ 1,890.00$ 35$ 16.8 16.5
185LED Comparing Room 6 T 40 R F 4 (ELE) F44SE 172 1.0 SW 2184 2,254 6 T 74 R LED RTLED50 50 0.3 C-OCC 1,747 524 1,730 0.7 280.64$ 1,687.50$ 35$ 6.0 5.9
185LED Comparing Room 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
185LED Comparing Room 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2184 376 1 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 87 288 0.1 46.77$ 506.25$ 35$ 10.8 10.1
32LED Hallway 10 1T 32 R F 2 (ELE) F42LL 60 0.6 SW 8736 5,242 10 4 ft LED Tube 200732x2 30 0.3 NONE 8,736 2,621 2,621 0.3 388.42$ 2,337.00$ -$ 6.0 6.0
247LED 131 5 T 40 R F 3 (MAG) F43SE 136 0.7 SW 2184 1,485 5 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 332 1,153 0.5 187.19$ 1,451.25$ 35$ 7.8 7.6
185LED Copying Room 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
247LED Copying Room 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2184 1,188 4 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 266 923 0.4 149.75$ 1,215.00$ 35$ 8.1 7.9
35LED Copying Room 5 T 32 R F 3 (ELE) F43ILL/2 90 0.5 SW 2184 983 5 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 332 651 0.3 104.89$ 1,451.25$ 35$ 13.8 13.5
247LED Copying Room 12 T 40 R F 3 (MAG) F43SE 136 1.6 SW 2184 3,564 12 T 59 R LED RTLED38 38 0.5 C-OCC 1,747 797 2,768 1.2 449.25$ 3,105.00$ 35$ 6.9 6.8
196LED Copying Room 1 W 32 C F 4 (ELE) F44ILL 112 0.1 SW 2184 245 1 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 87 157 0.1 25.31$ 506.25$ 35$ 20.0 18.6
247LED Copying Room 14 T 40 R F 3 (MAG) F43SE 136 1.9 SW 2184 4,158 14 T 59 R LED RTLED38 38 0.5 C-OCC 1,747 930 3,229 1.4 524.12$ 3,577.50$ 35$ 6.8 6.8
35LED Deeds 3 T 32 R F 3 (ELE) F43ILL/2 90 0.3 SW 2184 590 3 T 59 R LED RTLED38 38 0.1 C-OCC 1,747 199 390 0.2 62.94$ 978.75$ 35$ 15.6 15.0
185LED Deeds 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2184 376 1 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 87 288 0.1 46.77$ 506.25$ 35$ 10.8 10.1
185LED Registers Vault 60 T 40 R F 4 (ELE) F44SE 172 10.3 SW 2184 22,539 60 T 74 R LED RTLED50 50 3.0 C-OCC 1,747 5,242 17,297 7.3 2,806.42$ 14,445.00$ 35$ 5.1 5.1
196LED Registers Vault 1 W 32 C F 4 (ELE) F44ILL 112 0.1 SW 2184 245 1 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 87 157 0.1 25.31$ 506.25$ 35$ 20.0 18.6
196LED Registers Vault 12 W 32 C F 4 (ELE) F44ILL 112 1.3 SW 2184 2,935 12 T 74 R LED RTLED50 50 0.6 C-OCC 1,747 1,048 1,887 0.7 303.67$ 3,105.00$ 35$ 10.2 10.1
185LED Index 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
41LED Index 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 105 306 0.1 49.55$ 737.40$ 35$ 14.9 14.2
247LED Index 7 T 40 R F 3 (MAG) F43SE 136 1.0 SW 2184 2,079 7 T 59 R LED RTLED38 38 0.3 C-OCC 1,747 465 1,614 0.7 262.06$ 1,923.75$ 35$ 7.3 7.2
35LED Index 6 T 32 R F 3 (ELE) F43ILL/2 90 0.5 SW 2184 1,179 6 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 398 781 0.3 125.87$ 1,687.50$ 35$ 13.4 13.1
41LED Basement Men's Locker 11 1B 40 R F 2 (MAG) F42SS 94 1.0 SW 2184 2,258 11 4 ft LED Tube 200732x2 30 0.3 C-OCC 1,747 577 1,682 0.7 272.50$ 2,840.70$ 35$ 10.4 10.3
32LED Closet 2 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2912 349 2 4 ft LED Tube 200732x2 30 0.1 C-OCC 2,330 140 210 0.1 32.71$ 737.40$ 35$ 22.5 21.5
32LED Closet 1 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 131 1 4 ft LED Tube 200732x2 30 0.0 C-OCC 1,747 52 79 0.0 12.61$ 503.70$ 35$ 40.0 37.2
71 Toilet 2 I 60 I60/1 60 0.1 SW 2184 262 2 CF 26 CFQ26/1-L 27 0.1 C-OCC 1,747 94 168 0.1 26.99$ 283.50$ 35$ 10.5 9.2
41LED Hallway 44 1B 40 R F 2 (MAG) F42SS 94 4.1 SW 8736 36,132 44 4 ft LED Tube 200732x2 30 1.3 NONE 8,736 11,532 24,601 2.8 3,645.95$ 10,282.80$ -$ 2.8 2.8
41LED B33 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 210 612 0.3 99.09$ 1,204.80$ 35$ 12.2 11.8
41LED B33 11 1B 40 R F 2 (MAG) F42SS 94 1.0 SW 2184 2,258 11 4 ft LED Tube 200732x2 30 0.3 C-OCC 1,747 577 1,682 0.7 272.50$ 2,840.70$ 35$ 10.4 10.3
41LED B35 2 1B 40 R F 2 (MAG) F42SS 94 0.2 SW 2184 411 2 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 105 306 0.1 49.55$ 737.40$ 35$ 14.9 14.2
71 Mechanical Shop 9 I 60 I60/1 60 0.5 SW 2912 1,572 9 CF 26 CFQ26/1-L 27 0.2 C-OCC 2,330 566 1,006 0.3 157.42$ 330.75$ 35$ 2.1 1.9
41LED B27 9 1B 40 R F 2 (MAG) F42SS 94 0.8 SW 2184 1,848 9 4 ft LED Tube 200732x2 30 0.3 C-OCC 1,747 472 1,376 0.6 222.95$ 2,373.30$ 35$ 10.6 10.5
41LED B25 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 210 612 0.3 99.09$ 1,204.80$ 35$ 12.2 11.8
41LED B38 4 1B 40 R F 2 (MAG) F42SS 94 0.4 SW 2184 821 4 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 210 612 0.3 99.09$ 1,204.80$ 35$ 12.2 11.8
196LED B39 6 W 32 C F 4 (ELE) F44ILL 112 0.7 SW 2184 1,468 6 T 74 R LED RTLED50 50 0.3 C-OCC 1,747 524 943 0.4 151.84$ 1,687.50$ 35$ 11.1 10.9
32LED B39A 2 1T 32 R F 2 (ELE) F42LL 60 0.1 SW 2184 262 2 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 105 157 0.1 25.22$ 737.40$ 35$ 29.2 27.9
32LED B39A 4 1T 32 R F 2 (ELE) F42LL 60 0.2 SW 2184 524 4 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 210 314 0.1 50.43$ 1,204.80$ 35$ 23.9 23.2
32LED B39A 4 1T 32 R F 2 (ELE) F42LL 60 0.2 SW 2184 524 4 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 210 314 0.1 50.43$ 1,204.80$ 35$ 23.9 23.2
32LED B40 4 1T 32 R F 2 (ELE) F42LL 60 0.2 SW 2184 524 4 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 210 314 0.1 50.43$ 1,204.80$ 35$ 23.9 23.2
32LED B40 3 1T 32 R F 2 (ELE) F42LL 60 0.2 SW 2184 393 3 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 157 236 0.1 37.82$ 971.10$ 35$ 25.7 24.7
32LED B40 3 1T 32 R F 2 (ELE) F42LL 60 0.2 SW 2184 393 3 4 ft LED Tube 200732x2 30 0.1 C-OCC 1,747 157 236 0.1 37.82$ 971.10$ 35$ 25.7 24.7
32LED B40 6 1T 32 R F 2 (ELE) F42LL 60 0.4 SW 2184 786 6 4 ft LED Tube 200732x2 30 0.2 C-OCC 1,747 314 472 0.2 75.65$ 1,672.20$ 35$ 22.1 21.6
32LED B40 23 1T 32 R F 2 (ELE) F42LL 60 1.4 SW 2184 3,014 23 4 ft LED Tube 200732x2 30 0.7 C-OCC 1,747 1,206 1,808 0.7 289.98$ 5,645.10$ 35$ 19.5 19.3
41LED B2 8 1B 40 R F 2 (MAG) F42SS 94 0.8 SW 2184 1,642 8 4 ft LED Tube 200732x2 30 0.2 C-OCC 1,747 419 1,223 0.5 198.18$ 2,139.60$ 35$ 10.8 10.6
196LED Carpentor Shop 16 W 32 C F 4 (ELE) F44ILL 112 1.8 SW 2184 3,914 16 T 74 R LED RTLED50 50 0.8 C-OCC 1,747 1,398 2,516 1.0 404.90$ 4,050.00$ 35$ 10.0 9.9
71 B6 11 I 60 I60/1 60 0.7 SW 2184 1,441 11 CF 26 CFQ26/1-L 27 0.3 C-OCC 1,747 519 923 0.4 148.43$ 344.25$ 35$ 2.3 2.1
71 131 2 I 60 I60/1 60 0.1 SW 2184 262 2 CF 26 CFQ26/1-L 27 0.1 C-OCC 1,747 94 168 0.1 26.99$ 283.50$ 35$ 10.5 9.2
247LED Book Binding 6 T 40 R F 3 (MAG) F43SE 136 0.8 SW 2184 1,782 6 T 59 R LED RTLED38 38 0.2 C-OCC 1,747 398 1,384 0.6 224.62$ 1,687.50$ 35$ 7.5 7.4
71 B14 2 I 60 I60/1 60 0.1 SW 2184 262 2 CF 26 CFQ26/1-L 27 0.1 C-OCC 1,747 94 168 0.1 26.99$ 283.50$ 35$ 10.5 9.2
247LED Electric Room 4 T 40 R F 3 (MAG) F43SE 136 0.5 SW 2912 1,584 4 T 59 R LED RTLED38 38 0.2 NONE 2,912 443 1,142 0.4 181.06$ 945.00$ -$ 5.2 5.2
5LED B45 1 2T 32 R F 2 (u) (ELE) FU2LL 60 0.1 SW 2184 131 1 2T XX R LED 2RTLED 25 0.0 C-OCC 1,747 44 87 0.0 14.08$ 472.50$ 35$ 33.5 31.1
185LED B45 4 T 40 R F 4 (ELE) F44SE 172 0.7 SW 2184 1,503 4 T 74 R LED RTLED50 50 0.2 C-OCC 1,747 349 1,153 0.5 187.09$ 1,215.00$ 35$ 6.5 6.3
71 B45 2 I 60 I60/1 60 0.1 SW 2184 262 2 CF 26 CFQ26/1-L 27 0.1 C-OCC 1,747 94 168 0.1 26.99$ 283.50$ 35$ 10.5 9.2
185LED B45 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
185LED B46 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
185LED B47 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2184 751 2 T 74 R LED RTLED50 50 0.1 C-OCC 1,747 175 577 0.2 93.55$ 742.50$ 35$ 7.9 7.6
71 B48 4 I 60 I60/1 60 0.2 SW 2184 524 4 CF 26 CFQ26/1-L 27 0.1 C-OCC 1,747 189 335 0.1 53.97$ 297.00$ 35$ 5.5 4.9
41LED B48 1 1B 40 R F 2 (MAG) F42SS 94 0.1 SW 2184 205 1 4 ft LED Tube 200732x2 30 0.0 C-OCC 1,747 52 153 0.1 24.77$ 503.70$ 35$ 20.3 18.9
25 B48 2 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.1 SW 2184 122 2 R 13 C CF 2 (ELE) CFQ13/2-L 28 0.1 C-OCC 1,747 98 24 0.0 3.50$ 270.00$ 35$ 77.2 67.2
41LED Hallway 7 1B 40 R F 2 (MAG) F42SS 94 0.7 SW 8736 5,748 7 4 ft LED Tube 200732x2 30 0.2 NONE 8,736 1,835 3,914 0.4 580.04$ 1,635.90$ -$ 2.8 2.8
41LED Mechanical Room 1 1B 40 R F 2 (MAG) F42SS 94 0.1 SW 2912 274 1 4 ft LED Tube 200732x2 30 0.0 NONE 2,912 87 186 0.1 29.56$ 233.70$ -$ 7.9 7.9
185LED Mechanical Room 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2912 501 1 T 74 R LED RTLED50 50 0.1 NONE 2,912 146 355 0.1 56.35$ 236.25$ -$ 4.2 4.2
41LED Mechanical Room 6 1B 40 R F 2 (MAG) F42SS 94 0.6 SW 2912 1,642 6 4 ft LED Tube 200732x2 30 0.2 NONE 2,912 524 1,118 0.4 177.37$ 1,402.20$ -$ 7.9 7.9
185LED Mechanical Room 2 T 40 R F 4 (ELE) F44SE 172 0.3 SW 2912 1,002 2 T 74 R LED RTLED50 50 0.1 NONE 2,912 291 711 0.2 112.70$ 472.50$ -$ 4.2 4.2
185LED Storage 1 T 40 R F 4 (ELE) F44SE 172 0.2 SW 2912 501 1 T 74 R LED RTLED50 50 0.1 C-OCC 2,330 116 384 0.1 60.52$ 506.25$ 35$ 8.4 7.8
32LED Hallway next to Elevator 10 1T 32 R F 2 (ELE) F42LL 60 0.6 SW 8736 5,242 10 4 ft LED Tube 200732x2 30 0.3 NONE 8,736 2,621 2,621 0.3 388.42$ 2,337.00$ -$ 6.0 6.0
0 #N/A #VALUE!
0 #N/A #VALUE!
0 #N/A #VALUE!
0 #N/A #VALUE!
S Total 2,475 268.2 738,066 2,475 93.6 226,936 174.6 81,034 590,775 $11,130
S 174.6 $7,942
S 511,129 $73,091
Demand Savings
kWh Savings
1/22/2015 Page 15, ECM-L3
APPENDIX D
New Jersey Board of Public Utilities Incentives
i. Smart Start
ii. Direct Install
iii. Pay for Performance (P4P)
iv. Energy Savings Improvement Plan (ESIP)
APPENDIX E
Photovoltaic Analysis
Photovoltaic (PV) Solar Power Generation - Screening Assessment
Essex County Department of Parks
Hall of Records
Cost of Electricity $0.151 /kWh
Electricity Usage 3,680,750 kWh/yr
System Unit Cost $4,000 /kW
Budgetary Estimated Total
New Jersey
Renewable Payback Payback
Cost Maintenance Savings
Federal Tax
Credit ** SREC
(without
incentive)
(with
incentive)
Savings
$ kW kWh therms $ $ $ $ $ Years Years
$320,000 80.0 105,940 0 $15,987 0 $15,987 $0 $18,010 20.0 9.4
** Estimated Solar Renewable Energy Certificate Program (SREC) SREC for 15 Years= $170 /1000kwh
Area Output*
2,608 m2
28,069 ft2
Perimeter Output*
470 m
1,543 ft
Available Roof Space for PV:
(Area Output - 10 ft x Perimeter) x 85%
10,741 ft2
Approximate System Size: Is the roof flat? (Yes/No) Yes
8 watt/ft2
85,929 DC watts
80 kW Enter into PV Watts
PV Watts Inputs***
Array Tilt Angle 20
Array Azimuth 180
Zip Code 07052
DC/AC Derate Factor 0.83
PV Watts Output
105,940 annual kWh calculated in PV Watts program
% Offset Calc
Usage 3,680,750 (from utilities)
PV Generation 105,940 (generated using PV Watts )
% offset 3%
* http://www.freemaptools.com/area-calculator.htm
** http://www.flettexchange.com
*** http://gisatnrel.nrel.gov/PVWatts_Viewer/index.html
Enter info PV Watts
Photovoltaic (PV) Solar Power Generation - Screening Assessment
Annual Utility Savings
Enter into PV Watts (always 20 if flat, if
pitched - enter estimated roof angle)
Enter into PV Watts (default)
Enter into PV Watts
1/27/2015 Page 1, Hall of Records
Please send questions and comments to WebmasterDisclaimer and copyright notice.
RReDC home page (http://rredc.nrel.gov )
* * * * *AC Energy
&Cost Savings
* * * * *
(Type comments here to appear on printout; maximum 1 row of 90 characters.)
Saving Text from a Browser
Station IdentificationCell ID: 0268370
State: New Jersey
Latitude: 40.9 ° N
Longitude: 74.2 ° W
PV System SpecificationsDC Rating: 80.0 kW
DC to AC Derate Factor: 0.830
AC Rating: 66.4 kW
Array Type: Fixed Tilt
Array Tilt: 40.9 °
Array Azimuth: 180.0 °
Energy SpecificationsCost of Electricity: 15.1 ¢/kWh
Results
MonthSolar
Radiation(kWh/m2/day)
ACEnergy(kWh)
EnergyValue
($)
1 3.18 6800 1026.80
2 3.90 7480 1129.48
3 5.05 10251 1547.90
4 5.16 9772 1475.57
5 5.47 10498 1585.20
6 5.70 10296 1554.70
7 5.36 9793 1478.74
8 5.32 9798 1479.50
9 5.16 9445 1426.19
10 4.60 9038 1364.74
11 3.32 6476 977.88
12 3.00 6293 950.24
Year 4.60 105940 15996.94
(Gridded data is monthly, hourly output not available.)
Output Hourly Performance Data
(Output Results as Text - Temporarily Unavailable)
Output Results as Text
Run PVWATTS v.2 for another location Run PVWATTS v.1
Page 1 of 1PVWatts v.2: AC Energy and Cost Savings
10/21/2014http://rredc.nrel.gov/solar/calculators/PVWATTS/version2/pvwattsv2.cgi
CHP SCREENING LEVEL PRELIMINARY EVALUATION
LeRoy Smith Public Safety Building 22-Dec-14
CASE 1 - two 500kW Reciprocating Engines 1
BASE CASE
Boiler Efficiency 80%
Natural Gas Cost 6.75 $/MMBtu
Electricity Purchase Cost 0.15 $/kWh
Total Electricity Purchase Cost $542,633
Total Gas Purchase Cost $97,817
Total Energy Purchase Cost $640,450
CHP CASE
CHP Basis Recip Cogen Eng.
Engine Generator Ener-G
Configuration Recip. Engines
Power Gross Output 1,000 kW
Plant Auxiliary Power 6%
Engine Availability 0.97
Plant Net Output 940 kW
Fuel Gas LHV 1736 Btu/scft
Fuel Gas HHV 1927 Btu/scft
Fuel Consumption (HHV) 2.3 MMBtu/hr
Heat Recovery Jacket Water Cooler 0.8 MMBtu/hr
Heat Recovery Engine Exhaust 0.4 MMBtu/hr
Engine Maintenance Cost 0.018 $/kWh
Natural Gas Cost 6.75 $/MMBtu
Electricity Purchase Cost 0.15 $/kWh
Total Electricity Purchase Cost $0
Total Gas Purchase Cost $298,531
Engine Maintenance Cost $0
Total CHP Operating Cost $298,531Potential Maximum NJBPU Grant $550,000
ECONOMIC EVALUATION
Annual Energy Cost Savings $341,919
Project Cost Multiplier 3,800 $/kW
Project Cost (Incentives Not Included) $3,800,000
Total Cost (+20% Soft Cost Markup) $4,560,000.0
Simple Payback 13.3 Years
11.7
Notes:
1) Existing electrical loads are an based on electrical utility data provided by the facility.
2) Existing natural gas loads are based on natural gas utility data provided by the facility.
3) Reciprocating engine purchase and maintenance costs are budget costs are estimated based on previous projects
BASE CASE
Heat to Chiller
Month Days Peak Average Total Total Average Average Total Avg. Flow Power Load
kW kW kWh MMBtu MMBtu/hr MMBtu/hr MMBtu GPM Ratio Ton
Jan 31 576.05 389.4 289,730 3107.7 4.2 2.88 2,144 144 1.47 0
Feb 28 566.87 392.6 263,833 2750.8 4.1 2.82 1,898 141 1.46 0
Mar 31 572.09 364.3 271,064 2499.3 3.4 2.32 1,724 116 1.19 50
Apr 30 670.96 391.6 281,981 837.0 1.2 0.80 578 40 0.35 150
May 31 646.77 360.2 267,977 26.7 0.0 0.02 18 1 0.01 300
Jun 30 750.36 438.0 315,396 29.2 0.0 0.03 20 1 0.01 400
Jul 31 869.96 509.9 379,343 37.3 0.1 0.03 26 2 0.01 400
Aug 31 881.80 474.4 352,979 38.1 0.1 0.04 26 2 0.01 300
Sep 30 835.55 479.8 345,456 24.0 0.0 0.02 17 1 0.01 200
Oct 31 689.67 393.6 292,860 344.3 0.5 0.32 238 16 0.14 100
Nov 30 652.44 340.8 245,362 2182.1 3.0 2.09 1,506 105 0.94 50
Dec 31 563.61 389.5 289,797 2611.8 3.5 2.42 1,802 121 1.26 0
Annual 690 3,595,777 14,488 1.15 9,997 58 0.49 163
CHP CASE
Power Total Fuel CHP
Month Average Total Import Average Total Cooling Power Red. Heat Total Total Coolers Exhaust Average Heat Gas Use Consumption Efficiency
kW kWh kWh MMBtu/hr MMBtu Ton kW MMBtu/hr MMBtu/hr MMBtu MMBtu/hr MMBtu/hr MMBtu/hr MMBtu/hr MMBtu MMBtu MMBtu MMBtu %
Jan 576 415,722 0 1.40 1,010 0 0.0 0.0 2.88 2,144 0.77 0.23 1.00 1.00 724 1,420 1,775 2,785 230%
Feb 567 369,506 0 1.38 897 0 0.0 0.0 2.82 1,898 0.77 0.23 1.00 1.00 652 1,247 1,558 2,455 231%
Mar 572 412,866 0 1.39 1,003 50 35.0 0.8 3.12 2,320 0.77 0.23 1.00 1.00 723 1,597 1,996 2,999 231%
Apr 671 468,597 0 1.63 1,138 150 105.0 2.4 3.20 2,306 0.77 0.27 1.04 1.04 727 1,578 1,973 3,111 220%
May 647 466,762 0 1.57 1,133 300 210.0 4.8 4.82 3,590 0.77 0.26 1.03 1.03 745 2,845 3,556 4,690 223%
Jun 750 524,048 0 1.82 1,273 400 280.0 6.4 6.43 4,628 0.77 0.30 1.07 1.07 750 3,878 4,848 6,121 214%
Jul 870 627,832 0 2.11 1,525 400 280.0 6.4 6.43 4,787 0.77 0.35 1.12 1.12 809 3,978 4,972 6,497 207%
Aug 882 636,377 0 2.14 1,545 300 210.0 4.8 4.84 3,598 0.77 0.36 1.13 1.13 813 2,785 3,481 5,026 206%
Sep 836 583,546 0 2.03 1,417 200 140.0 3.2 3.22 2,321 0.77 0.34 1.11 1.11 774 1,547 1,934 3,351 209%
Oct 690 497,719 0 1.67 1,209 100 70.0 1.6 1.92 1,428 0.77 0.28 1.05 1.05 757 671 839 2,047 219%
Nov 652 455,663 0 1.58 1,106 50 35.0 0.8 2.89 2,082 0.77 0.26 1.03 1.03 722 1,360 1,699 2,806 222%
Dec 564 406,743 0 1.37 988 0 0.0 0.0 2.42 1,802 0.77 0.23 1.00 1.00 720 1,082 1,352 2,340 232%
Annual 690 5,865,381 0 1.67 14,243 163 114 2.6 3.75 32,902 0.77 0.28 1.05 1.05 8,915 23,987 29,984 44,227 220%
Power Generation Engine Gas Usage (HHV) Absorption Chiller
Electricity
Total Heating Required Engine Heat Recovery Available Heat Used by Facility Existing Boilers
From Recip. Engine
Natural Gas (HHV) Heating Hot Water
CHP Screening-Recip Engine - Hall of Record - Recip. Engine By: Gryphon (CHA) Page 1 of 2
Payback
(with
Incentive)
Existing
Utility Cost
CHP
Operating
Cost
$ $ $ $ $ Years Years Y/N
4,560,000 640,450 298,531 341,919 550,000 13.3 11.7 FS
Recom
mendedBudgetary
CostAnnual Utility Usage
Total
Savings
New Jersey
Incentive
Payback
(without
Incentive)
APPENDIX F
Photos
ECM-1 Reduce Steam Pressure
Existing Steam Boiler
ECM-2 Replace old RTUs with high efficiency RTUs
Existing AHUs
ECM-3 Install window AC units control system
Existing Window ACs
ECM-4 Install a Central Web-Based DDC System to control the HVAC equipment
Existing Individual Thermostat
ECM-5 Replace Domestic Hot Water Heaters with Condensing DHW Heater
Existing DHW Heaters
ECM-6 Install Control on the Walk-in Fridges and Freezers
No Pictures Available
ECM-L1 Lighting Replacement / Upgrades
Existing Lights
ECM-L2 Install Lighting Controls (Occupancy Sensors)
No Pictures Available
ECM-L3 Lighting Replacements with Controls (Occupancy Sensors)
See ECM L-1 and L-2
APPENDIX G
EPA Benchmarking Report
ENERGY STAR® Statement of EnergyPerformance
30ENERGY STAR®
Score1
Hall of Records
Primary Property Function: CourthouseGross Floor Area (ft²): 205,696Built: 1925
For Year Ending: January 31, 2014Date Generated: December 18, 2014
1. The ENERGY STAR score is a 1-100 assessment of a building’s energy efficiency as compared with similar buildings nationwide, adjusting forclimate and business activity.
Property & Contact Information
Property AddressHall of Records465 Dr. Martin Luther King BlvdNewark, New Jersey 07102
Property Owner__________________,(____)____-______
Primary Contact____ ________,(____)____-________________________
Property ID: 4279698
Energy Consumption and Energy Use Intensity (EUI)
Site EUI130.1 kBtu/ft²
Annual Energy by FuelElectric - Grid (kBtu) 12,268,767 (46%)District Steam (kBtu) 14,488,101 (54%)
National Median ComparisonNational Median Site EUI (kBtu/ft²) 105.1National Median Source EUI (kBtu/ft²) 219.8% Diff from National Median Source EUI 24%
Source EUI272 kBtu/ft²
Annual EmissionsGreenhouse Gas Emissions (Metric TonsCO2e/year)
2,604
Signature & Stamp of Verifying Professional
I ___________________ (Name) verify that the above information is true and correct to the best of my knowledge.
Signature: _______________________Date: ___________
Licensed Professional
____ ________,(____)____-________________________
Professional Engineer Stamp(if applicable)