Daniel LUNARDELLI

MODERN TRENDS OF FIRE PROTECTIONIN ROLLING STOCK

INTER-LABORATORY COMPARISON FOR EN 45545-2 TESTS

25 June 2014

1

• CERTIFER is a Notified Body (NoBo) to the European Community for the interoperability of the rail system

• CERTIFER is also an Designed Body (OQA-De Bo) to evaluate the design and implementation of systems or sub-systems new or substantially modified rail

• In 2006 , SNCF and RATP has transferred to CERTIFER the accreditation of the laboratories for I-F classification ( NF F16-101)

• From 2007, CERTIFER has introduced inter-laboratory comparison for EN 45545 tests• Inter-laboratory is a tool of selection of

laboratories in addition to the accreditation ISO/CEI 17025

2PROGRESS OF INTER-LABORATORY CAMPAIGNS

•An Assessment Team composed with experts from laboratories and railway operators who were involved in the drafting of EN 45545•The statistical analysis is realized according to ISO 5725

1. Determination of average and standard deviation for the different laboratories

2. 2σ preliminary test: each extreme value must be included in less than 2 Standard deviations (2σ) above or below the average of other laboratories, if not the value is excluded

3. Search of aberrant value according to IS0 5725 with Mandel test. Determination of the repeatability and reproducibility

4. Send Deviation Form to the laboratories who are excluded by 2σ or aberrant value

5. Analysis of the answer of the laboratories and exchange6. Publication of a list of recognized laboratories

Laboratories involved in 200716 in 8 country

• BODYCOTE WARRINGTON FIRE

• BRE• QinetiQ

• AEF• CREPIM• LCPP• LNE• RATP• RESCOLL

• LAPI• LSF

• CURRENTA (BAYER)

• VTT

• CNTK

• SINTEF

• SP

3

Laboratories involved in period 2008-201333 in14 country

• EXOVA (WARRINGTON FIRE)• BRE• QINETIQ

• AEF• CREPIM• IFTH• LCPP• LNE• RATP• RESCOLL• HERAKLES(SNPE)• STRATIFORME

• CSI• LAPI• LSF• TECNALIA

• BASF• CURRENTA (BAYER)• RST

• VTT

• IK (CNTK)• KTZO• SYCHTA

• SINTEF

• SP

• CENTEXBEL

• AITEX• GAIKER

• OFI• TGM• LANTAL

• DBI

• SGS-CSTC

4

INTER-LABORATORY 2014

Five new laboratories involved

- JECTEC (Japan)- Deutsche Bahn (Germany)- DMT (Germany)- TUDOR (Luxembourg)- GIORDANO (Italy)

5

EN 45545-2 Tests Parameter Requirements Inter-Laboratory

EN ISO 4589-2 OI R22, R23, R24 X

ISO 5658-2 CFE R1to R4, R7R11, R12, R17

X

ISO 5660-1 MAHRE R1 to R3, R5 to R12, R17 to R21

X

EN ISO 9239-1 CHF R8, R10 X

EN ISO 11925-2 30 s flame application R4, R5

EN 12952-2 Time Burning R20

ISO TR 9705/2 MAHRE R18

EN 60332..,50305.. Height of chared zone R15, R16

EN ISO 5659-2 Ds4, VOF4, Dsmax R1 to R3, R5 to R12, R17, R20 to R23

X

EN 45545 Annexe C CITGR1 to R12, R17, R20, R21

X

NF X 70-100 CITNLP R22, R23 X(1)

EN 60695-2-11 Temperature R25

EN 60695-11-10 Flame R26

6

(1) Results of French Inter-laboratory campaign without NO and NOx

7

Few laboratories excluded by 2σ and aberrant value

Results without correction

2σAberrant

Good reproducibility

8Results after Deviation Form

9

HL2

HL3

HL1

Minor exclusion by 2σ and aberrant value

Results without correction

2σAberrant

10

Good reproducibility

HL3

Results after Deviation Form

11

A lot of dispertion for materials with high fire property

NC

HL

Results without correction

Aberrant

12

Good reproducibility for materials with flame propagation

NC

HL

Results after Deviation Form

13

Large range of value with aberrant value

HL3

HL2

Results without correction

14

Variable reproducibility according the materials

HL3

HL2

Results after Deviation Form

15

Large range of value for Polyamide carpet

HL2/HL3

NC

Results without correction

16

Not enough campaign for judgement but seems identical to 50 kW/m2

HL2/HL3

NC

Results after Deviation Form

17

Few aberrant value

HL3

Results without correction

18

Good reproducibility

HL3

Results after Deviation Form

19

Few exclusion by 2σ and aberrant value

HL3

HL1

2σAberrant

20

Good reproducibility

HL3

HL1

Results after Deviation Form

21

Large range of value (But only two campaign)

HL3

HL2

22

Large range of value for some materials

23

Identical to CO

24

Large range of value for some materials

25

HBr was only expected for GRP

26

HCl was only expected for GRP

27

Large range of value for some materials

28

SO2 was not expected for GRP /Large range of value for wool carpet

29

Large range of value (but far from the limit of the standard)

30

Identical to 4 min

Grouped results for some materials

31Results after Deviation Form

Less divergence for NF X70-100

32COMPARISON CIT NF X70-100/EN 45545

EN 45545-2 tests Parameter Reproducibilty Commentary

EN ISO 4589-2 OI **** Robust test

EN ISO 9239-1 CHF **** Robust test

ISO 5658-2 CFE ** Limit in the standard at 13 and 20 kW/m2 will minimize the consequence

ISO 5660-1 MAHRE **Can reject some materials at the limit of

the classification

EN ISO 5659-2 Ds4VOF4 ****

Robust test

EN ISO 5659-2 Dsmax ***Depends if inflammation or not

EN 45545 Annexe C CIT G **Will no affect the classification of

materials. Very few materials will be rejected (ex: PVC)

NF X 70-100 CIT NLP ***Long experience of laboratories

33CONCLUSION