Post on 28-Nov-2021
transcript
Eaton’s Cooper Controls Business203 Cooper CirclePeachtree City, GA 30269tel: 800-553-3879 fax: 800-954-7016
Submittal Transmittal
Date:
Transmitted To:
Eaton’s Cooper Lighting 203 Cooper CirclePeachtree City, GA 30269
Transmitted By:
Eaton’s Cooper Lighting 203 Cooper CirclePeachtree City, GA 30269
Project
Remarks
1 This is a complete shop drawing submittal with lighting controls added to lighting plan as follows:1.1 Added boundary for each control zone 1.2 Existing notes and lighting control symbols have been replaced with Eaton’s Cooper Lighting notes and symbols
2 Additional Drawings have also been added by Eaton’s Cooper Lighting: 2.1 Device Wiring Diagrams2.2 Lighting Riser Diagrams
3 Contractor must install each device supplied by Eaton’s Cooper Lighting as per the “Device Wiring Diagrams” above.
4 Contractor to terminate all lighting control wires as per the “Schedules” provided.
5 Contractor to test and verify the operation of all lighting controls as per the “Testing and Startup Procedures” provided in this submittal.
Eaton Lighting Systems
Oct 26, 2016 8:40 AM CDT
Newington Forest Elementary
Kendra Shell
Eaton’s Cooper Controls Business203 Cooper CirclePeachtree City, GA 30269tel: 800-553-3879 fax: 800-954-7016
Table of Contents
1. Cover Page
2. Transmittal Form
3. Table of Contents
4. Submittal & Order Release
5. Bill of Materials
6. Device Placement Drawings
7. Riser Diagram
8. Wiring Diagrams
9. Factory Start-up
10. Commissioning Test Procedures
11. Training
12. Startup Checklist
13. Panel Schedules
14. Spec Sheets
15. Warranty Information
Eaton’s Cooper Controls Business 203 Cooper Circle Peachtree City, GA 30269
tel: 800-553-3879 fax: 800-954-7016
Submittal & Order Release Job Name:
Please forward this form and a copy of the bill of material page to Eaton’s Cooper Controls releasing PO for manufacturing and shipment. Please verify the bill of material, quantities, voltages and switches and wall plate configurations, colors, and finishes are correct. Please make any changes required on this sheet or on the bill of materials page. If the information provided is not correct and has been built for this order or shipped you may incur restocking or handling fees.
The order will not be released without this form.
_____ Bill of Material Is Correct, please release.
_____ Bill of Material Is Not Correct. Please see notes below or attached sheet and release.
Notes:
Signature
Company Name
Date
Newington Forest Elementary
SUBMITTAL PACKAGE
Notes
1.2.
3.
4.
5.
6.
7.
8.
9.10. 11. If the number of shade controllers are not provided to Eaton then Eaton has assumed that there will be one shade controller per
floor. If there more shade controllers then a scope change will be required.
In the absence of a detailed Sequence of operations, Eaton will be implemented its default sequence of operations. Any deviation from the implement sequence of operations will require a scope change request.The Lighting Control Panels and Central Managers require unique IP addresses. These IP addresses must be provided as part of thRequest For Information form (ref section 10).
All third party DALI ballasts and drivers shall be IEC 62386/DALI Ed 1 compliant and must not respond in any way to frames other than the 16-bit frames as defined in the published standards (IEC 62386 parts 101, 102, 2xx). The DALI frame used by these devices must be encapsulated by the IEC 62386 defined start bit and the defined two stop bits to be considered a valid frame. To reduce project risks, Eaton recommends using the third party DALI ballasts and driver listed on the "Fifth light verified ballasts and Drivers" application note (ref section 11 - Specification Sheets).
Fifth Light system does not support open loop daylighting control.The fire alarm signal, a dry contact, must be home wired to each LCP and connected to the digital input card.
A pre-wire request form must be completed and transmitted to Eaton (ref section 10) for pre-wired visit. A factory startup request form must be completed and transmitted to Eaton (ref section 10 of the submittal package). The installation sign-off form must be completed and submitted at this time.For the BACNet integration, Eaton's scope of work is limited to exposing the BACNet objects. Eaton will use the Chipkin BACNet Explorer software to prove to the interested parties that the objects are exposed. A list of the BACNet objects with associated Fifth Light device ID will be provided to the building automation system integrator (refer to the FLT-BACNet specification sheet for more information with regards to the objects being exposed).For integration with the Crestron® MC3 controllers the FLT-XML is used. A dry contact closure such as a digital output card, DALI field relay or DALI DAC can be used for all other A/V systems. FLT-SHADE is used for integration with shades controllers provided by Mechosystem, Embedia and Somfy. For all other shade manufacturers, a digital out and relay output is used such as a DALI DAC or DALI Field Relay.
Quote based on drawings EL3.01, E3.02, E3.03, E3.04, E3.05 dated 3.14.16. If newer drawings become available, please contact Eaton Controls for a requote.
Items not included on this quotation are not included in this price. If the Bill of Materials changes please contact Cooper Controls for a re-quote.Adders are not included in the quote total.Quoted startup amount covers commissioning during normal business hours M-F. After hours commissioning will require a revisedquoteNo receptacle control included in this quoteNo site lighting included in this quoteNo DMX integration included in this quote.No metering included in this quote.All dimming is assumed to be 0-10V.Standard warranty appliesStandard submittals applyNo spare relays included in this quoteNo graphical interface included in this quoteNo spare hardware included in this quote.Relays are not individually replaceable.Factory startup broken into 3 phases per drawings.
SUBMITTAL PACKAGE
Bill of Materials
Bill of Material
Newington Forest Elementary
Quantity Brand Catalog #/Line Comments
15 Greengate Panels CK4A-SLRCControlKeeper 4A 0-10V dimming panel with latching relays
3 Greengate Panels DF10P-C1Decorator Dimmer 0-10V, 120/277 VAC, w/ White, Ivory andAlmond faceplate color kit
2 Greengate Panels GDS-2TLB-WGDS 2 Large button White
2 Cooper Controls ENGRV-2BTNL-W2 Large Button White Requires Custom Text Order Form
2 Greengate Panels GDS-3TLB-WGDS 3 Large button White
2 Cooper Controls ENGRV-3BTNL-W3 Large Button White Requires Custom Text Order Form
3 Greengate Panels GDS-5TSB-WGDS 5 Small button White
3 Cooper Controls ENGRV-5BTNS-W5 Small Button White Requires Custom Text Order Form
2 Greengate Panels GDS-6TSB-WGDS 6 Small button White
1 Cooper Controls ENGRV-6BTNS-W6 Small Button White Requires Custom Text Order Form
5 Greengate Panels GDS-I-KITGDS Integrator KIT
71 Greengate Occupancy Sensors SP20-MVSwitchpack Heavy Duty, 120/277V
79 Greengate Panels GMDS-WMomentary Decorator Switch - White
137 Greengate Occupancy Sensors OAC-DT-2000-RMicroSet Dual Technology 2000 sq ft ceiling sensor w/BASRelay & Daylight Sensor
47 Greengate Panels OCC-RJ45RJ45 to standard Greengate Low Voltage Occupancy Sensoralso BMS and Egress output Device
86 Greengate Panels RC3D-PL-N3 Relay + 3 Dimmers Room Controller Network 120/277VAC
86 Greengate Panels PDR-RC-6TSBWhite 6 Small Button Station Custom
55 Greengate Occupancy Sensors ONW-D-1001-MV-WWhite Dual Technology Single Level Switch Sensor 120/277
install white, provide othercolor plates to owner forstorage (BGA)
Bill of Material
10 Greengate Occupancy Sensors OSP20-RDHPack w/Dry Contact & Override Inputs
4 Greengate Panels PC-IAnalog Indoor Photosensor
10 Greengate Panels PPS-5Contact Input Outdoor Photosensor
1 Greengate Panels KEEPER NW KITNetwork Keeper Enterprise Includes Cable Kit
1 Greengate Panels EIM(EIM) Ethernet Interface Module Requires buliding LANconnection
1 Greengate Panels FPC-N34-1130BMS Pro.BACnet
1 Greengate Panels HHPR-RCPersonal Control/Scene Programmer
3 Greengate Occupancy Sensors OAWC-DT-120W-ROAWC-DT Dual Technology Wall/Corner Sensor 1200 sq ftw/BAS
Greengate Panels, CooperControls, Greengate OccupancySensors
Certified Factory Scheduled Commissioning trip and training by Eaton LightingSystems Factory Representative
Drawing Service >75K Drawing Services, Centralized Greengate/ iLumin Systemsgreater than $75K project price.
Standard Warranty Standard product warranty based on date of product shipment.See product documentation for standard warranty information.
10 Greengate Panels PDR-RC-6TSB (SPARE) White 6 Small Button Station Custom
2 Greengate Panels RPTR Network Repeater
1/8" = 1'-0"
QTY SYMBOL
MODEL/DESCRIPTION
-R = isolated relay
-N = Neutral required
PROJECT NAME
DATE
SCALE
SHEET
Eaton's Cooper Controls Business
1-800-553-3879 Phone
1-800-954-7016 Fax
203 Cooper Circle
Peachtree City, GA 30269
GENERAL NOTES
SENSOR NOTES:
1.LOCATION OF ALL SENSORS IS
APPROXIMATE. REVIEW
INSTALLATION INSTRUCTIONS
BEFORE INSTALLING SENSORS.
2.TO PREVENT FALSE ACTIVATION,
ULTRASONIC CEILING MOUNT
SENSORS SHOULD BE MOUNTED
AWAY FROM THE PATH OF
STRONG AIR TURBULENCE. IN
NORMAL AIRFLOW CONDITIONS
SENSORS SHOULD BE MOUNTED
FOUR TO SIX FEET AWAY FROM
SOURCE. FOR TYPICAL
PLACEMENT, REFER TO LOCATION
DIAGRAMS. IN LOCATIONS WITH
STRONG AIR TURBULENCE A PIR
CEILING SENSOR SHOULD BE
CONSIDERED.
3.CONTRACTOR IS RESPONSIBLE
FOR PROPER TIME DELAY AND
SENSITIVITY ADJUSTMENTS WHEN
APPLICABLE.
4.CONTRACTOR SHOULD FOLLOW
MANUFACTURER'S RECOMMENDED
PLACEMENT AND VERIFY CIRCUITS
WITH RESPECT TO SWITCHPACKS
NEEDED IN THE FIELD.
5.CONTRACTOR IS RESPONSIBLE
FOR FIELD VERIFICATION OF THE
NUMBER OF SWITCHPACKS
NEEDED. ONE SWITCHPACK PER
CIRCUIT.
6.MULTIPLE CIRCUITS MAY BE
CONTROLLED BY ONE SENSOR BY
USING ADDITIONAL SWITCHPACKS.
MAXIMUM OF TEN SWITCHPACKS
PER SENSOR.
SENSOR LEGEND
REVISION
0.0
MS
MS MS
MS
MS
MS
MS
MS
MS
MS
MS
3 3
33
4 4 4 4
MS
J
J
MS
MS
MS
J
J
MS
MS
J
J
MS
MS
MS
MS
MS
MS
J
MS
MS
MS
MS MS
MS
CMP1
CMP1
CMP1
CMP1
CMP1
CMP1
CMP1
J
MS
EU
F
H
K
MEB.2
EOEK
EREG
PEJ EN
ET
ET
EDEB.3
MECHANICAL115
MUSICCLASSROOM
110
KITCHEN106
CAFETERIA105
GYM120
KINDERGARTENCLASSROOM
124
KINDERGARTENCLASSROOM
125
KINDERGARTENCLASSROOM
127
COMMUNICATIONSROOM
121
INSTRUMENTALMUSIC
STORAGE112B
GYM OFFICE120B
??
circ285
MUSICCLASSROOM
107
GIRLS TOILET117
BOYS TOILET118
CUSTODIAN'SOFFICE
116
ELECTRICALROOM
129
INSTRUMENTALMUSIC ROOM
112
CAFETERIASTORAGE
105B
KINDERGARTENCLASSROOM
126
GYMSTORAGE(LARGE)
120D
OUTDOORSTORAGE
111
GENERALSTORAGE
167B
GENERALMUSIC
STORAGE110B
MUSICSTORAGE
107A
GYMSTORAGE
(SML)120E
STORAGE123
CORRIDOR122
MAINCORRIDOR
102
CORRIDOR109B
TOILET125A
SOUTHVESTIBULE
104
TOILET127A
SOUTHCORRIDOR
103
NORTHVESTIBULE
101
1A
4A
OC
8B
ZONE 1ZONE 2
DS1
DS1
7B67A
2D
67A7B
2D
27B
7B
67A67A
67A 70B 70B 67A 67AP
P
AD
AD
2D
2D
2D
2D
ADAD
26B
3
3
27B
DS-D
11A
DS-B
1A
AA
AA 67A
AA
20B
67A
2D
TOILET124A
DS1
DS1
TOILET126A
OC
OC
OC
DS1
DS1
DS1
3
RAMP105C
DS1
DS1
DS1
DS1
OC
OC
OCOC
KITCHENOFFICE
106A
DRY FOODSTORAGE
106B
TOILET/LOCKERRM
106D CUSTODIAN'SCLOSET
106C
OC OC
gym circ37
OC
OC
1A
1A
8B
8B
1A
1A
8B
7B
8B
4A
ZONE 1
ZONE 1
4A
67A
OC
OC
27B
27B
DS1
DS1
4A
4A
1A
4A
EMEM
EM
20B2D
27B
1A
1A
8B
7B
7B
7B
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM EM
EM
EM
EM
EM
EM
EM
A
A
70A
70A
70A
7B
7B
7B
7B
7B
7B
OC
53A
53A
53A
37A
51A
53A
27B
EM EM
ZONE 2
ZONE 2
ZONE 1ZONE 2
ZONE 2
5
7B
7B
7B
7B
7B
7B
3
4
6
6
4
7
7
1
OC
1
1
1
OC
OC
OC
1
P
EM
P
EM70A
1
1
1
OC
OC
70A
3
3
EM
EM
EM
EM
EM
EM
EM
6
EM EM
EM
H1A - 13
15B
15B
OC
1
ZONE 1
ZONE 2
OC
OC
OC
OC OC
OC
OC
OC
ZONE 2
ZONE 1
2
2
1A
11
11
11
2
EM
7B
EM
EM 15B
15A
EM
10
8
8
ZONE 1
DS-C
EM
EM
15B
EM
15A
15B
15B
OC
1
1ZONE 2
ZONE 1
HA-12
HA - 4
H1A-6
H1A- 7
H1A - 9
H1A-12
H1A-4
HA - 8
3
HA - 7
HA-6
15A
15A
H1A-8
EH-1
H1A - 11
EH-5
HA-3
H1A-10
EM
EM
HA-3
HA-10
H1A - 5
6
67A
67A
EM
EM
EM
ZONE 1ZONE 2
1A
11
(TYP.)
9
10
11
11
11
50.6FC
1
E4.06
DS1
4A
EM
52A
1
1
51A
8B
8B
P
11B
11B
11A
51A
51A
7B
ZONE 1
(Z1)
51A
1
EM
EM
EM
EM
ZONE 2
ZONE 152.7FC
52.8FC
50.4FC
55.9FC
56.6FC
47.0FC
(Z2)
EM
EM
D
51A
P
12
2PHASE 2AREA OF
WORK
AREA OFWORK PHASE 1
AREA OFWORK
PAR
W
ELECTRICALROOM
11413
69A
14
SPARE PARTSSTORAGE
115A
CUSTODIAN'SSUPPLY
113WALK INCOOLER
8
L1A-32
R OC
2
E4.06
25.1FC
37.3FC
29.2FC 43.6FC
30.5FC
30.6FC
27.0FC
56.6FC
56.0FC
50.1FC
30.3FC
55.9FC
35.4FC
30.8FC
25.1FC
32.6FC
(TYP.)
(TYP.)
(TYP.)15B
(TYP.)
OC
27B
27B
5
SHWR120C
8B
7A
E4.06
EM
15A (TYP.)
EM
EM EM
3
16
(TYP.)
(TYP.)
(TYP.)
11A
(TYP.)
2
E3.01
gym circ37
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
RUN RELAY CONTROL LEG VIA LIGHTING CONTROL PANEL LCP-A IN ELEC. RM. 114. CONTROL RISER DIAGRAM AND SCHEDULE ON DRAWINGS E3.06 AND E3.07.
ALL PENDANT MOUNTED LIGHT FIXTURES SHALL BE SUSPENDED AT MINIMUM OF 1FINISHED CEILING TO THE TOP OF THE FIXTURE. REFER TO ARCHITECTURAL DWGS
REFER TO ARCHITECTURAL DWGS FOR FIXTURE MOUNTING AND CONDUIT ROUTING
MOUNTING SHALL BE MADE WATERTIGHT.
EXPOSED CONDUITS/SURFACE MOUNTED RACEWAYS ARE NOT PERMITTED IN THISSPECIFICALLY DIRECTED OTHERWISE.
ALL EXIT SIGNS AND CONTROL DEVICES IN THIS SPACE SHALL BE PROVIDED WITH W
DIMMER SWITCH SHALL NOT BE GANGED WITH STANDARD SWITCHES.
REFER TO DETAIL#1 ON THIS SHEET FOR CONTINUATION OF CIRCUIT.
REFER TO DETAIL#2 ON THIS SHEET FOR CONTINUATION OF CIRCUIT.
CONTRACTOR TO COORDINATE WITH ARCHITECT FOR EXACT SWITCH LOCATION.
KEY NOTES
1.
2.
3.
4.
5.
6.
7.
TO THE NEXT DIGITAL SWITCH. SEE TYPICAL CLASSROOM LIGHTING DETAIL ON DWG. E3.06 FORCONNECTION OF CLASSROOM LIGHTS AND SWITCHES.
LIGHT SWITCH NOTED CONTROLS LIGHTS IN THIS ROOM ONLY.
RUN BRANCH CIRCUIT WIRING VIA LIGHTING CONTROL PANEL LCP-F IN ELEC. RM. 129. SEELIGHTING CONTROL RISER DIAGRAM AND SCHEDULE ON DRAWINGS E3.06 AND E3.07.
CORRIDOR LIGHTING CONTROL OCCUPANCY SENSOR HOMERUN CABLE TO CONTACT CLOSUREINPUT DEVICE IN LCP-M LOCATED IN COMM. RM. 121. SEE LIGHTING CONTROL RISER DIAGRAMAND SCHEDULES ON DRAWINGS E3.06 AND E3.07.
RUN RELAY CONTROL LEG VIA LIGHTING CONTROL PANEL LCP-F IN ELEC. RM. 129. SEE LIGHTINGCONTROL RISER DIAGRAM AND SCHEDULE ON DRAWINGS E3.06 AND E3.07.
RUN BRANCH CIRCUIT WIRING VIA LIGHTING CONTROL PANEL LCP-A IN ELEC. RM. 114. SEELIGHTING CONTROL RISER DIAGRAM AND SCHEDULE ON DRAWINGS E3.06 AND E3.07.
CORRIDOR LIGHTING CONTROL OCCUPANCY SENSOR HOMERUN CABLE TO CONTACT CLOSUREINPUT DEVICE IN LCP-A LOCATED IN ELEC. RM. 114. SEE LIGHTING CONTROL RISER DIAGRAMAND SCHEDULES ON DRAWINGS E3.06 AND E3.07.
#
15
K
MEB.2
E10
1314
ED
EC EC.1EB.1 EB.3
27B
OC
15
17
SCALE: 1/8" = 1'-0"E3.01
1 FIRST FLOOR LIGHTING PLAN AREA A-NEW WORK1
SCALE: 1/8" = 1'-0"E3.01
2 MEZZANINE LEVEL2
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1 D1
D1
D1
D1
MV
OAC-DT-2000-RMicroSet Dual Technology 2000 sq ft ceiling sensor w/BASRelay & Daylight Sensor
SP20-MVSwitchpack Heavy Duty, 120/277V
RC3D-PL-N3 Relay + 3 Dimmers Room Controller Network 120/277VAC
OCC-RJ45RJ45 to standard Greengate Low Voltage Occupancy Sensoralso BMS and Egress output Device
ONW-D-1001-MV-WWhite Dual Technology Single Level Switch Sensor 120/277
GDS-2TLB-WGDS 2 Large button White
GDS-5TSB-WGDS 5 Small button White
GDS-6TSB-WGDS 6 Small button White
GMDS-WMomentary Decorator Switch - White
OSP20-RDHPack w/Dry Contact & Override Inputs
PPS-5Contact Input Outdoor Photosensor
OAWC-DT-120W-ROAWC-DT Dual Technology Wall/Corner Sensor 1200 sq ftw/BAS
PDR-RC-6TSBWhite 6 Small Button Station Custom
29
1
9
14
6
17
15
18
6
2
1
2
14
Newington Forest Elementary
16505.02 140
xx
11/30/16
1/8" = 1'-0"
QTY SYMBOL
MODEL/DESCRIPTION
-R = isolated relay
-N = Neutral required
PROJECT NAME
DATE
SCALE
SHEET
Eaton's Cooper Controls Business
1-800-553-3879 Phone
1-800-954-7016 Fax
203 Cooper Circle
Peachtree City, GA 30269
GENERAL NOTES
SENSOR NOTES:
1.LOCATION OF ALL SENSORS IS
APPROXIMATE. REVIEW
INSTALLATION INSTRUCTIONS
BEFORE INSTALLING SENSORS.
2.TO PREVENT FALSE ACTIVATION,
ULTRASONIC CEILING MOUNT
SENSORS SHOULD BE MOUNTED
AWAY FROM THE PATH OF
STRONG AIR TURBULENCE. IN
NORMAL AIRFLOW CONDITIONS
SENSORS SHOULD BE MOUNTED
FOUR TO SIX FEET AWAY FROM
SOURCE. FOR TYPICAL
PLACEMENT, REFER TO LOCATION
DIAGRAMS. IN LOCATIONS WITH
STRONG AIR TURBULENCE A PIR
CEILING SENSOR SHOULD BE
CONSIDERED.
3.CONTRACTOR IS RESPONSIBLE
FOR PROPER TIME DELAY AND
SENSITIVITY ADJUSTMENTS WHEN
APPLICABLE.
4.CONTRACTOR SHOULD FOLLOW
MANUFACTURER'S RECOMMENDED
PLACEMENT AND VERIFY CIRCUITS
WITH RESPECT TO SWITCHPACKS
NEEDED IN THE FIELD.
5.CONTRACTOR IS RESPONSIBLE
FOR FIELD VERIFICATION OF THE
NUMBER OF SWITCHPACKS
NEEDED. ONE SWITCHPACK PER
CIRCUIT.
6.MULTIPLE CIRCUITS MAY BE
CONTROLLED BY ONE SENSOR BY
USING ADDITIONAL SWITCHPACKS.
MAXIMUM OF TEN SWITCHPACKS
PER SENSOR.
SENSOR LEGEND
REVISION
0.0
MS
MS MS
MS MS
MS
MS
MS
33
MS
MS
3 3
MS
MSMS
MS
JJJ J
J
MS
MS
J
MS
MS
MS
MS
MS
MS
MS
MS
MS
MS
MS
MS
MS
MS
MS
MS
CMP1
CMP1
CMP1
CMP1
CMP1CMP1
EU S UO R
AP/FINANCEOFFICER'S
OFFICE157
CONFERENCE153
VAULT/RECORDS150
CLINIC149
ASSISTANTPRINCPALS
OFFICE155
MULTIPURPOSEROOM
131
PTA ROOM128
GUIDANCECOUNSELOR
OFFICE137
ELEVATOR374
STAFFLOUNGE
144
ITINERANTCONFERENCE
ROOM 3143
CORRIDOR133A
STAIR AS01-1
ELECTRICALROOM162B
CHARGINGROOM
146
VIDEOPRODUCTION
159
MULTIPURPOSEROOM/SACC
142
SAAC140 HEAD START
138
RECEPTION130
PRINCIPAL'SOFFICE
151
CORRIDOR147
ELECTRICALROOM
141
TOILET142A
TOILET140A
EW EXEREH EPELEG ET
GUIDANCECOUNSELOR
OFFICE139
DS1
ZONE 1
ZONE 2
1A
1A
1A
67A
P
P
DS
1
27B
2D 2D
2D
AD
2D
7B
7B
7B1A
1A
AD1B
DS1
1A
1A
OFFICEWORKROOMM/MEDIA
STORAGE162
LIBRARY160
AUDIO/VISUALSTORAGE
162A
PROFESSIONALRESOURCE/
CONFERENCEROOM
161
LIBRARY160
WORK ROOM134
ADULT TOILET- WOMEN
148
ADULT MEN'STOILET
136
TOILET138A
DS1
DS
1
OC OC
DS1 OC
CUSTODIAN'SCLOSET
133E
OC
OCOC
SPEDSTORAGE
135
1A
1A
DS
1
DS1
1A
8B
8B
8B
8B
8B
8B
27B
rcpt circ41
OC
27B
OC
8B
7B
1A
53A
53A
1A1A
2D
2D
OC
OCEM
EM EM EM
EM
EMEM
7B
1A
53A
53A1D
7B
7B
7B7B
7B
7B
53A
53A
1A
70A 70A
70A
70A
70A70A
4A
ZONE 1
ZONE 2
OC
DS
1
2D
2D
7B
7B
7B
7B
1A
1A
30B
1A
1A
1A
7B
DS1
EMEM
4
3
EMEM
1A
OC
EM
EM
H1B - 9
8
1
ZONE 1
ZONE 2
OC
1
1
8B
8B
1
1
OC
1
1
OC
CUBICCURTA
OC
1
1
OC
OC
OC
OC
OC
OCOC
OC
OC
1
OC
2 1
7
ZONE 1
ZONE 2
OC
aa
aa
EM EM
R5OC
R OC
L1B-55
DS
-F
30B
DS
-G
DS
-F
DS
1
H1B-3
H1B-10H1B-1 H1B-4
H1B - 6
H1B-5
H1B - 8
H1B-7
EH - 3
EM
EM
67A
H1B-13
H2B-13
D
H2B-14
6
H1B-11
4
E4.06
51A
51A
51A
D
67A
H2B-13
52A
56.3FC
54.3FC
9
9
E4.06
PHASE 3AREA OF
WORK
PHASE 2AREA OF
WORK
37A
10
D10
ELEVATORMECHANICAL
ROOM132
CORRIDOR133D
CORRIDOR133C
CORRIDOR133B11
12
3
38.1FC
45.1FC
44.1FC
53.3FC
46.5FC
41.8FC49.0FC
49.6FC
33.9FC
41.0FC
42.0FC49.6FC
46.9FC
29.3FC
EM
6
1A
1A
1B
6
4
3
3
EM
1414
14
1B
1B
1A
EM
27B
ZONE 1
ZONE 2
OC
EM
SCALE: 1/8" = 1'-0"E3.02
1 FIRST FLOOR LIGHTING PLAN AREA B-NEW WORK1
D1
D1
D1
D1D1
D1
D1
D1
D1
D1 D1
D1
MV
OAC-DT-2000-RMicroSet Dual Technology 2000 sq ft ceiling sensor w/BASRelay & Daylight Sensor
SP20-MVSwitchpack Heavy Duty, 120/277V
RC3D-PL-N3 Relay + 3 Dimmers Room Controller Network 120/277VAC
OCC-RJ45RJ45 to standard Greengate Low Voltage Occupancy Sensoralso BMS and Egress output Device
ONW-D-1001-MV-WWhite Dual Technology Single Level Switch Sensor 120/277
GDS-2TLB-WGDS 2 Large button White
GDS-5TSB-WGDS 5 Small button White
GMDS-WMomentary Decorator Switch - White
OSP20-RDHPack w/Dry Contact & Override Inputs
PPS-5Contact Input Outdoor Photosensor
OAWC-DT-120W-ROAWC-DT Dual Technology Wall/Corner Sensor 1200 sq ftw/BAS
PDR-RC-6TSBWhite 6 Small Button Station Custom
DF10P-C1Decorator Dimmer 0-10V, 120/277 VAC, w/ White, Ivory andAlmond faceplate color kit
31
1
6
12
4
27
11
11
33
2
2
2
3
Newington Forest Elementary
16505.02 140
xx
11/30/16
1/8" = 1'-0"
QTY SYMBOL
MODEL/DESCRIPTION
-R = isolated relay
-N = Neutral required
PROJECT NAME
DATE
SCALE
SHEET
Eaton's Cooper Controls Business
1-800-553-3879 Phone
1-800-954-7016 Fax
203 Cooper Circle
Peachtree City, GA 30269
GENERAL NOTES
SENSOR NOTES:
1.LOCATION OF ALL SENSORS IS
APPROXIMATE. REVIEW
INSTALLATION INSTRUCTIONS
BEFORE INSTALLING SENSORS.
2.TO PREVENT FALSE ACTIVATION,
ULTRASONIC CEILING MOUNT
SENSORS SHOULD BE MOUNTED
AWAY FROM THE PATH OF
STRONG AIR TURBULENCE. IN
NORMAL AIRFLOW CONDITIONS
SENSORS SHOULD BE MOUNTED
FOUR TO SIX FEET AWAY FROM
SOURCE. FOR TYPICAL
PLACEMENT, REFER TO LOCATION
DIAGRAMS. IN LOCATIONS WITH
STRONG AIR TURBULENCE A PIR
CEILING SENSOR SHOULD BE
CONSIDERED.
3.CONTRACTOR IS RESPONSIBLE
FOR PROPER TIME DELAY AND
SENSITIVITY ADJUSTMENTS WHEN
APPLICABLE.
4.CONTRACTOR SHOULD FOLLOW
MANUFACTURER'S RECOMMENDED
PLACEMENT AND VERIFY CIRCUITS
WITH RESPECT TO SWITCHPACKS
NEEDED IN THE FIELD.
5.CONTRACTOR IS RESPONSIBLE
FOR FIELD VERIFICATION OF THE
NUMBER OF SWITCHPACKS
NEEDED. ONE SWITCHPACK PER
CIRCUIT.
6.MULTIPLE CIRCUITS MAY BE
CONTROLLED BY ONE SENSOR BY
USING ADDITIONAL SWITCHPACKS.
MAXIMUM OF TEN SWITCHPACKS
PER SENSOR.
SENSOR LEGEND
REVISION
0.0
MS MS
MS
MS
MSMS
MS
MS
J
MS
J
JMS
MS
J
MS
J
MS
J
MS
MS
J
MS
J J
MS
MS MS
MS
MSMS
J
MS
MS
CMP1
CMP1
CMP1
CMP1 CMP1
CMP1
CMP1CMP1
CMP1
CMP1
J LC N
NCE166
RESOURCECLASSRM 1
169
1ST GRADECLASSROOM
171
WORK ROOM1
167
TOILET185A
TOILET179A
TOILET183A
CUSTODIAN'SCLOSET
164E
GENERALSTORAGE
167B
ADULT TOILET- W
167ATOILET173A
TOILET171A
ITINERANTCONFERENCE
ROOM 1176
ITINERANTCONFERENCE
ROOM 2174
CONFERENCEROOM 1
168
GENERALSTORAGE
180TOILET181A
TOILET175A
STAIR DS04-1
2ND GRADECLASSROOM
185
2ND GRADECLASSROOM
181
2ND GRADECLASSROOM
183
GENERALSTORAGE
184
2ND GRADECLASSROOM
179
1ST GRADECLASSROOM
177
1ST GRADECLASSROOM
175
1ST GRADECLASSROOM
173
E2
E5
E3
EHEGEB EDECEA EEEB.3
DS1
ZONE 1
ZONE 2
DS1
TOILET177A
1A
4A
OC
8B
OC
7B
A
P
2D 2D
2D
2D
2D2D
2D
7B
SPECIALEDUCATIONSTORAGE 2
172
1A
DS1
DS1
OC
1A
ZONE 1
ZONE 2
8B
DS1
DS1
1A
4A
OC
8B
1A
4A1A
OC
8BDS1
DS1
OC
DS1
DS1
8B
4A
DS1
1A
4A
DS1
OC
DS1
1A
4A
OC
DS1
8B 8B
OC
DS1
DS1
1A
4A
8B
DS1
DS1
4A 1A
OC
7B
ZONE 1
ZONE 2
ZONE 1
ZONE 2
ZONE 2
ZONE 1
ZONE 2
ZONE 1
ZONE 2
ZONE 1
ZONE 2
ZONE 1ZONE 2
ZONE 1EM
EM
EM EM EM
EMEM
7B
7B
70A
1D
OC
1A
1A
53A 53A
53A
53A
53A
EM
1A
7B
RM167-VESTIBULE
42
8B
OC
7B
1A
DS1
DS1TOILET
166A
7B
OC
7B
7B
7B7B
7B 7B
7B
7B
7B
7B
7B
8B
4
3
1
1
EM
1
1
1
1
70A
70A 70A
EM
OC
OC
OC
1
1
3H1C - 1
OC
1
1
1
1
1
1
OC
OC
1
1
OC
OC
8B
8B
1
1
OC
4A
1
1
1A
OC8B
OC
OC OC
OC
OC
OCOC
OC OC
OC
OCEM
27B2
6
6
(TYP.)
R5
8B
H1C-3
H1C - 5
H1C-7
H1C-4
H1C-6
H1C-9
H1C-8
EH-2
OCEM
EM
EM
1A
1A
52A
52A
52A52A
54.6FC
7B
PHASE 1AREA OF
WORK
STAIR CS03-1
STORAGE182
ITINERANTCONFERENCE
ROOM 3170
CORRIDOR164C
CORRIDOR164D
CORRIDOR164A
CORRIDOR164B ELECTRICAL
ROOM186
OC
EM
47.3FC 45.1FC 51.4FC
40.5FC
31.7FC
51.0FC
53.3FC52.0FC
52.9FC
54.5FC
39.4FC 39.3FC47.1FC
52.7FC
31.0FC
7
7
3
E4.06
53A
EM
51A
51A
4A
51A
51A
SCALE: NOT TO SCALEE3.03
1 FIRST FLOOR LIGHTING PLAN AREA C-NEW WORK1
D1
D1
D1
D1
D1
D1
D1 D1
D1D1
D1
D1
D1
D1
D1
D1
MV
OAC-DT-2000-RMicroSet Dual Technology 2000 sq ft ceiling sensor w/BASRelay & Daylight Sensor
SP20-MVSwitchpack Heavy Duty, 120/277V
RC3D-PL-N3 Relay + 3 Dimmers Room Controller Network 120/277VAC
OCC-RJ45RJ45 to standard Greengate Low Voltage Occupancy Sensoralso BMS and Egress output Device
ONW-D-1001-MV-WWhite Dual Technology Single Level Switch Sensor 120/277
PPS-5Contact Input Outdoor Photosensor
OAWC-DT-120W-ROAWC-DT Dual Technology Wall/Corner Sensor 1200 sq ftw/BAS
PDR-RC-6TSBWhite 6 Small Button Station Custom
GMDS-WMomentary Decorator Switch - White
1
23
10
20
11
15
1
20
11
Newington Forest Elementary
16505.02 140
xx
11/30/16
1/8" = 1'-0"
QTY SYMBOL
MODEL/DESCRIPTION
-R = isolated relay
-N = Neutral required
PROJECT NAME
DATE
SCALE
SHEET
Eaton's Cooper Controls Business
1-800-553-3879 Phone
1-800-954-7016 Fax
203 Cooper Circle
Peachtree City, GA 30269
GENERAL NOTES
SENSOR NOTES:
1.LOCATION OF ALL SENSORS IS
APPROXIMATE. REVIEW
INSTALLATION INSTRUCTIONS
BEFORE INSTALLING SENSORS.
2.TO PREVENT FALSE ACTIVATION,
ULTRASONIC CEILING MOUNT
SENSORS SHOULD BE MOUNTED
AWAY FROM THE PATH OF
STRONG AIR TURBULENCE. IN
NORMAL AIRFLOW CONDITIONS
SENSORS SHOULD BE MOUNTED
FOUR TO SIX FEET AWAY FROM
SOURCE. FOR TYPICAL
PLACEMENT, REFER TO LOCATION
DIAGRAMS. IN LOCATIONS WITH
STRONG AIR TURBULENCE A PIR
CEILING SENSOR SHOULD BE
CONSIDERED.
3.CONTRACTOR IS RESPONSIBLE
FOR PROPER TIME DELAY AND
SENSITIVITY ADJUSTMENTS WHEN
APPLICABLE.
4.CONTRACTOR SHOULD FOLLOW
MANUFACTURER'S RECOMMENDED
PLACEMENT AND VERIFY CIRCUITS
WITH RESPECT TO SWITCHPACKS
NEEDED IN THE FIELD.
5.CONTRACTOR IS RESPONSIBLE
FOR FIELD VERIFICATION OF THE
NUMBER OF SWITCHPACKS
NEEDED. ONE SWITCHPACK PER
CIRCUIT.
6.MULTIPLE CIRCUITS MAY BE
CONTROLLED BY ONE SENSOR BY
USING ADDITIONAL SWITCHPACKS.
MAXIMUM OF TEN SWITCHPACKS
PER SENSOR.
SENSOR LEGEND
REVISION
0.0
MS
MS
MS
MS
MS
MSMS
MS
MS
MS MS
J J J J
MS
MSMS
MS
J
J J J
MS
J
MS
MS
MS
MS
MS
MS
MS
MS
MS MS
CMP1
CMP1 CMP1 CMP1
CMP1
CMP1
CMP1
CMP1
CMP1
MS
S UO R
ARTCLASSROOM
201
SPEECHSPECIALIST
205
BOYS TOILET230
GIRLS TOILET228
GALLERY200
5TH GRADECLASSROOM
206
5TH GRADECLASSROOM
210
STORAGE201B
ELECTRICALROOM
203
RESOURCE/CLASSROOM207
TLT-W216
STORAGE219
MAINCORRIDOR
102
5TH GRADECLASSROOM
212
6TH GRADECLASSROOM
226
6TH GRADECLASSROOM
224
6TH GRADECLASSROOM
222
6TH GRADECLASSROOM
218
CORRIDOR203A
EW EXEREPELEG ETEE
STAIR AS01-2
ZONE 1
ZONE 2
1A
4A
2D
7B
67A
67A
7B 2D
27B
7B
OC
2D
2D
2D2D
2D
2D7B
67A
CHARGINGROOM 2
214
1A 1A
DS1
ZONE 1 ZONE 2
CONFERENCEROOM 3
202
LIBRARY160 CUSTODIAN'S
CLOSET203E
WK RM 3208
53A
1A
4A
ZONE 1
ZONE 2
DS1
DS1
DS1
DS1
ZONE 1
ZONE 2
4A
4A
ZONE 1
ZONE 2
DS1
DS1
DS1
ZONE 1
ZONE 2
4A
DS1
53A
2D
6B
EM
7B
7B7B
EM
7B
53A
EM
7B
53A
EM
7B
7B
8B
OC DS1
DS1
DS1
ZONE 1ZONE 2
1A
4A
DS1
ZONE 1
ZONE 2
1A
1A
DS1
DS1
DS1
ZONE 1
1A
4A
ZONE 2
5B
27B
OC
8B
OC 7B
1A 7B
1A
1A
53A
BB OC
7B
EM
EM
1A 1A
1A
7B
7B
4A
ZONE 1
ZONE 2
EM
2D
EM EM
EM
EM
6B
34
5
7
EM
1
DS1
OC
OC
1
OCOC
1
1
1
1
OC
1
1
1
OC
OC
1
1
1
1
1
OC
1
OC
1
1 1
OC
EM
EM
OC
BB
EM
EM
EM
EM
EM
EM
EM
EM
EM
OC OC
OCOCOC
OC
OC
OC
OC
OC
EM
EM
EM
EM
EM
BB
R8
7
EM2
ZONE 1
ZONE 3
DS1
ADULT TOILET- MEN
204
27B
H2B-4
H2B-8
H2B-9 H2B-11
H2B-7
H2B-12
H2B-10EH-4
EM
H2B-5
9
OC
4A
14 14PC
10
PC
10
COMMUNICATIONSROOM200A
48.6FC
PC
10
6B
EMEMEM
1112
13
H2B-6
51A
52A
52A
51A
5
E4.06
15
15
PHASE 2AREA OF
WORK PHASE 3AREA OF
WORK
KILN201A
CORRIDOR203C
CORRIDOR203D
CORRIDOR203B
5
H2B-16 75
56.3FC
33.7FC
65.9FC
33.6FC
33.4FC
47.8FC 45.4FC 45.6FC 48.6FC
47.9FC
47.9FC
48.8FC49.4FC
31.5FC
45.2FC
42.8FC
6
6
DAYLIGHTHARVESTING
ZONE 1
PC
10
DAYLIGHTHARVESTING
ZONE 2DAYLIGHTHARVESTING
ZONE 3
HA-11
16
16
HA-16
16
HA-13
HA-15
16
HA-15
16
HA-15
16
EH-10
14
(TYP.)
14
1414
14
BB
(TYP.)(TYP.)BB
(TYP.)
(TYP.)
BB
(TYP.)
BB
(TYP.)
BB
(TYP.)
HA-11 16
EMAD
EM
SCALE: 1/8" = 1'-0"E3.04
1 SECOND FLOOR LIGHTING PLAN AREA B-NEW WORK1
D1
D1
D1
D1
D1
D1
D1
MV
OAC-DT-2000-RMicroSet Dual Technology 2000 sq ft ceiling sensor w/BASRelay & Daylight Sensor
SP20-MVSwitchpack Heavy Duty, 120/277V
RC3D-PL-N3 Relay + 3 Dimmers Room Controller Network 120/277VAC
OCC-RJ45RJ45 to standard Greengate Low Voltage Occupancy Sensoralso BMS and Egress output Device
ONW-D-1001-MV-WWhite Dual Technology Single Level Switch Sensor 120/277
PDR-RC-6TSBWhite 6 Small Button Station Custom
GMDS-WMomentary Decorator Switch - White
PC-IAnalog Indoor Photosensor
4
6
7
18
11
18
9
27
Newington Forest Elementary
16505.02 140
xx
11/30/16
1/8" = 1'-0"
QTY SYMBOL
MODEL/DESCRIPTION
-R = isolated relay
-N = Neutral required
PROJECT NAME
DATE
SCALE
SHEET
Eaton's Cooper Controls Business
1-800-553-3879 Phone
1-800-954-7016 Fax
203 Cooper Circle
Peachtree City, GA 30269
GENERAL NOTES
SENSOR NOTES:
1.LOCATION OF ALL SENSORS IS
APPROXIMATE. REVIEW
INSTALLATION INSTRUCTIONS
BEFORE INSTALLING SENSORS.
2.TO PREVENT FALSE ACTIVATION,
ULTRASONIC CEILING MOUNT
SENSORS SHOULD BE MOUNTED
AWAY FROM THE PATH OF
STRONG AIR TURBULENCE. IN
NORMAL AIRFLOW CONDITIONS
SENSORS SHOULD BE MOUNTED
FOUR TO SIX FEET AWAY FROM
SOURCE. FOR TYPICAL
PLACEMENT, REFER TO LOCATION
DIAGRAMS. IN LOCATIONS WITH
STRONG AIR TURBULENCE A PIR
CEILING SENSOR SHOULD BE
CONSIDERED.
3.CONTRACTOR IS RESPONSIBLE
FOR PROPER TIME DELAY AND
SENSITIVITY ADJUSTMENTS WHEN
APPLICABLE.
4.CONTRACTOR SHOULD FOLLOW
MANUFACTURER'S RECOMMENDED
PLACEMENT AND VERIFY CIRCUITS
WITH RESPECT TO SWITCHPACKS
NEEDED IN THE FIELD.
5.CONTRACTOR IS RESPONSIBLE
FOR FIELD VERIFICATION OF THE
NUMBER OF SWITCHPACKS
NEEDED. ONE SWITCHPACK PER
CIRCUIT.
6.MULTIPLE CIRCUITS MAY BE
CONTROLLED BY ONE SENSOR BY
USING ADDITIONAL SWITCHPACKS.
MAXIMUM OF TEN SWITCHPACKS
PER SENSOR.
SENSOR LEGEND
REVISION
0.0
MSMS
MS
MS MS
MSMS
MS
MS
MS
MS
J
MS MS MS
J J J
MS
J
MSMS MS
J
J
MS
MS
MS
J J
MS
MS
J
MS
MS
MS
MSCMP1
CMP1
CMP1CMP1 CMP1
CMP1
CMP1 CMP1
CMP1 CMP1CMP1
J
J L MC N
E5
E3
EB EDECEA EEEB.3
ESOL/LD/SPLSRV
CLASSROOM238
ITINERANTCONFERENCE
ROOM 2239
4TH GRADECLASSROOM
231
4TH GRADECLASSROOM
233
RESOURCE/CLASSROOM2
259
3RD GRADECLASSROOM
253
3RD GRADECLASSROOM
249
3RD GRADECLASSROOM
247
WORK ROOM2
237
READINGSPECIALIST
232
GIRLS TOILET234
CONFERENCEROOM 2
235
T249A
ITINERANTCONFERENCE
ROOM 1240
ELECTRICALROOM
251
TOILET247A
T253A
3RD GRADECLASSROOM
245
4TH GRADECLASSROOM
243
4TH GRADECLASSROOM
241
CORRIDOR229A
CUSTODIAN'SCLOSET
229E
DS1
ZONE 1ZONE 2
DS1
OC
8B
7B
2D
7B
2D
67A
TOILET177A
7B
OC27B
GEN STOR248
2D2D
2D2D
2D2D
7B
1A
1A
STAIR DS04-2
DS1
1A
OC OCOC
8B
8B8B
DS1
DS1
DS1
DS1
1A
1A
4A 4A
DS1
4A
DS1
1A
DS1 DS1
53A
DS1
DS1
1A
4A
1A
DS1DS1
53A 53A
DS1
53A
1A
53A
1A
4A
DS1
DS1
1A
4A
DS1
1A
5B
EM
EM
EM
EMEM
EM
OC
ZONE 1
ZONE 1
ZONE 2
ZONE 1 ZONE 1ZONE 2 ZONE 1 ZONE 2
7B
7B
7B
EM7B
EM
7B
2D
2D
DS1
53A
53A
1A
7B7B
2D
EM7B
7BEM
7B
3
4
OC
1
1
OC
1
OC
1
1
OC
1
1 1
1
1
OC
1
1 1
1
OC
OC
1
1
1
1
OC
BOYS TOILET236
OC
OC
OC
EM
1
R 5
1
EM EM
2
DS1
DS1
H2C-1
H2C-4H2C-6
H2C-3
H2C - 8
H2C-5
H2C-10EH - 6
7B
ZONE 2
ZONE 2
4A
1A
1A
4A
4A
OC
1A
1
OC
ZONE 2 ZONE 2
ZONE 1 ZONE 1
ZONE 2
ZONE 1
OC
1
51A
52A
52A52A
51A
OC
OC
OC
OC OC OC
OC
9
7
8
6
E4.06
52A
52A
PHASE 1AREA OF
WORK
CORRIDOR229D
CORRIDOR229C
CORRIDOR229B
EM
57.9FC
53.3FC
51.8FC 44.8FC
39.8FC
47.0FC47.2FC
46.9FC
28.0FC
38.6FC30.6FC30.2FC
48.2FC
45.0FC
38.6FC
52.7FC
48.4FC48.7FC51.6FC
6
6
EM
51A
51A 51A
51A
SCALE: 1/8" = 1'-0"E3.05
1 SECOND FLOOR LIGHTING PLAN AREA C-NEW WORK1
D1
D1
D1
D1D1
D1
D1
MV
OAC-DT-2000-RMicroSet Dual Technology 2000 sq ft ceiling sensor w/BASRelay & Daylight Sensor
SP20-MVSwitchpack Heavy Duty, 120/277V
RC3D-PL-N3 Relay + 3 Dimmers Room Controller Network 120/277VAC
OCC-RJ45RJ45 to standard Greengate Low Voltage Occupancy Sensoralso BMS and Egress output Device
ONW-D-1001-MV-WWhite Dual Technology Single Level Switch Sensor 120/277
PDR-RC-6TSBWhite 6 Small Button Station Custom
GMDS-WMomentary Decorator Switch - White
27
6
10
22
11
22
10
Newington Forest Elementary
16505.02 140
xx
11/30/16
1/8" = 1'-0"
QTY SYMBOL
MODEL/DESCRIPTION
-R = isolated relay
-N = Neutral required
PROJECT NAME
DATE
SCALE
SHEET
Eaton's Cooper Controls Business
1-800-553-3879 Phone
1-800-954-7016 Fax
203 Cooper Circle
Peachtree City, GA 30269
GENERAL NOTES
SENSOR NOTES:
1.LOCATION OF ALL SENSORS IS
APPROXIMATE. REVIEW
INSTALLATION INSTRUCTIONS
BEFORE INSTALLING SENSORS.
2.TO PREVENT FALSE ACTIVATION,
ULTRASONIC CEILING MOUNT
SENSORS SHOULD BE MOUNTED
AWAY FROM THE PATH OF
STRONG AIR TURBULENCE. IN
NORMAL AIRFLOW CONDITIONS
SENSORS SHOULD BE MOUNTED
FOUR TO SIX FEET AWAY FROM
SOURCE. FOR TYPICAL
PLACEMENT, REFER TO LOCATION
DIAGRAMS. IN LOCATIONS WITH
STRONG AIR TURBULENCE A PIR
CEILING SENSOR SHOULD BE
CONSIDERED.
3.CONTRACTOR IS RESPONSIBLE
FOR PROPER TIME DELAY AND
SENSITIVITY ADJUSTMENTS WHEN
APPLICABLE.
4.CONTRACTOR SHOULD FOLLOW
MANUFACTURER'S RECOMMENDED
PLACEMENT AND VERIFY CIRCUITS
WITH RESPECT TO SWITCHPACKS
NEEDED IN THE FIELD.
5.CONTRACTOR IS RESPONSIBLE
FOR FIELD VERIFICATION OF THE
NUMBER OF SWITCHPACKS
NEEDED. ONE SWITCHPACK PER
CIRCUIT.
6.MULTIPLE CIRCUITS MAY BE
CONTROLLED BY ONE SENSOR BY
USING ADDITIONAL SWITCHPACKS.
MAXIMUM OF TEN SWITCHPACKS
PER SENSOR.
SENSOR LEGEND
REVISION
0.0
MAIN ELEC.RM 129
DIGITAL SWITCH SCHEDULE
DS-A
SWITCH BUTTON LOCATION RELAY'S CONTROLLED LABEL REMARKS
1
LIBRARYCIRC. DESK
160
DS-BGYM
OFFICE120B
CONTROLS SITE LTG ONTHE NORTH & NORTH WEST
SIDES
ALL ON
ALL OFF
LC-00311/13UPDATED
CAFETERIA105
123
DS-CDS-D
DS-E
45
DS-F
DS-G
DS-H
LIBRARYTEACH.
160
LIBRARYSTORY PIT
160
LCP RELAY SCHEDULE (LCP-M)RELAY
NO.CIRCUIT
NO.DESCRIPTION DESCRIPTION CIRCUIT
NO.RELAY
NO.
MAIN COMM. RM. 121
1 2
3 45 67 8
9 1011 12
13 14
15 16
SPARE
LCP RELAY SCHEDULE (LCP-A)RELAY
NO.CIRCUIT
NO.DESCRIPTION DESCRIPTION CIRCUIT
NO.RELAY
NO.
ELEC. RM. 114
1 2
3 45 67 8
CANOPY LIGHTING (FRONT ENTRANCE)
LCP RELAY SCHEDULE (LCP-B)RELAY
NO.CIRCUIT
NO.DESCRIPTION DESCRIPTION CIRCUIT
NO.RELAY
NO.
ELEC. RM. 141
1 2
3 45 6
7 8
LCP RELAY SCHEDULE (LCP-D) ELEC. RM. 206
CAFETERIA (Z1)H1A-4
NORTH VESTIBULE LIGHTINGH1A-11
H1A-13BUILDING MOUNTED LIGHTING
H1A-4
H1A-12 H1A-12
SPAREH1A-5
LCP-A 5, 6; LCP-F 1, 2; LCP-B 2, 3;LCP-C 1, 2; LCP-LIB
TOGGLE
DIMMINGDIMMINGDIMMINGDIMMING
LCP-F 5, 6LCP-F 6LCP-F 6LCP-F 5LCP-F 5
ALL ON/OFF
Z1 (RAISE)Z1 (LOWER)Z2 (RAISE)
Z2 (LOWER)123456
LCP-A 1,2 100% ILLUMINATIONZ1 (ON)LCP-A 1 (ON), LCP-A 2 (OFF) 50% ILLUMINATIONZ1 (A/V)
LCP-A 1,2 Z1 (OFF)LCP-A 3,4 100% ILLUMINATIONZ2 (ON)
LCP-A 3 (ON), LCP-A 4 (OFF) 50% ILLUMINATIONZ2 (A/V)LCP-A 3,4 Z2 (OFF)
1 ALL ON CONTROLS CORRIDORLIGHTING
LCP-B 1; LCP-C 3; LCP-D 1, 2, 3, 4, 5;LCP-E 1; LCP-F 1
ALL OFFLCP-B 1; LCP-C 3; LCP-D 1, 2, 3, 4, 5;
LCP-E 1; LCP-F 3, 4
12345
TOGGLE
DIMMINGDIMMINGDIMMINGDIMMING
ALL ON/OFF
Z1 (RAISE)Z1 (LOWER)Z2 (RAISE)
Z2 (LOWER)
LCP-LIB 1 THRU 5LCP-LIB 1, 5LCP-LIB 1, 5
LCP-LIB 2, 3, 4123 LCP-LIB 2, 4
LCP-LIB 3LCP-LIB 3LCP-LIB 3
TOGGLE
DIMMINGDIMMING
ON/OFF
(RAISE)(LOWER)
------ ------
------ ------
------ ------------ ------------ ------------ ------
------ ------------ ------
------ ------------ ------
MASTER PANELLC&D "LTD"
MICRO PANEL
CAFETERIA (Z1)
CAFETERIA (Z2) CAFETERIA (Z2)
------
MICRO PANEL
H1B-7 CORRIDOR LIGHTING SITE LIGHTING H1B-12H1B-9 BUILDING MOUNTED LIGHTING SPARE ------
------ ------------ ------
------ ------------ ------
LCP RELAY SCHEDULE (LCP-C)RELAY
NO.CIRCUIT
NO.DESCRIPTION DESCRIPTION CIRCUIT
NO.RELAY
NO.
ELEC. RM. 186
1 2
3 45 67 8
MICRO PANEL
H1C-10CORRIDOR LIGHTING
H1C-1H1C-8
BUILDING MOUNTED LIGHTINGSPARE ------
------ ------------ ------
------ ------------ ------
CANOPY LIGHTING (REAR ENTRANCE)
RELAYNO.
CIRCUITNO.
DESCRIPTION DESCRIPTION CIRCUITNO.
RELAYNO.
1 2
3 45 67 8
MICRO PANEL
CORRIDOR LIGHTING
SPARE ------
------------ ------
H2B-7
LCP RELAY SCHEDULE (LCP-LIB) ELEC. RM. 206
RELAYNO.
CIRCUITNO.
DESCRIPTION DESCRIPTION CIRCUITNO.
RELAYNO.
1 2
3 45 6
7 8
MICRO PANEL
LIBRARY LIGHTING H2B-5TEACH. AREA LIGHTING
------ ------
H2B-6
H2B-13STORY PIT LIGHTINGH2B-16
LCP RELAY SCHEDULE (LCP-E) ELEC. RM. 251
RELAYNO.
CIRCUITNO.
DESCRIPTION DESCRIPTION CIRCUITNO.
RELAYNO.
1 2
3 45 6
7 8
SPARECORRIDOR LIGHTINGH2C-10 SPARE
MICRO PANEL
------ ------
------ ------
LC-00411/13UPDATED
LCP RELAY SCHEDULE (LCP-F) ELEC. RM. 129
RELAYNO.
CIRCUITNO.
DESCRIPTION DESCRIPTION CIRCUITNO.
RELAYNO.
1 2
3 45 67 8SPARE
SITE LIGHTINGHA-1
MICRO PANEL
------
------
------------
------
------
------
HA-6HA-10------
CORRIDOR LIGHTINGGYMNASIUM LIGHTING (Z2)
HA-3
HA-7HA-10------SPARE
BUILDING MOUNTED LIGHTING
SOUTH CORRIDOR LIGHTINGGYMNASIUM LIGHTING (Z1)
------
123
TOGGLE
DIMMINGDIMMING
ON/OFF
(RAISE)(LOWER)
TEACH. AREA DOWN LIGHTING
2
2
HA-12MAIN LOBBY LIGHTING
MAIN LOBBY (DAYLIGHT HARVEST ZONE)
SPARE
SPARESPARE------------ ------
------
SPARE------
SPARE
SPARESPARE
HA-11 MAIN LOBBY (DAYLIGHT HARVEST ZONE)
MAIN LOBBY (DAYLIGHT HARVEST ZONE) HA-14HA-13
SPARE SPARELIBRARY DOWN LIGHTINGH2B-13 H2B-14BUILDING MOUNTED LIGHTING
LCP-LIB 2, 4LCP-LIB 2, 4
LCP-LIB 2, 3, 4
LCP-A 5, 6; LCP-F 1, 2; LCP-B 2, 3;LCP-C 1, 2; LCP-LIB
MAIN ELEC.RM 129
16505.02 140
xx
11/30/16
SUBMITTAL PACKAGE
Riser and Wiring Diagrams
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
Keeper Enterprise Software
Requires Ethernet Connection
or RS232 Serial Connection
PC by others
KEEPER NW KIT
Building 1
PC-I
102
PC-I
102
PC-I
102
120V Power
Receptacle Required
To Building LAN
EIM
Building 1
BMS interface via network
BMS Pro BACNet
FPC-N34-1130
Building 1
PPS-5
Building 1
PPS-5
Roof
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
GDS-I-KIT
Building 1
6-Button White
GDS - Control Station
GDS-6TSB-W
105
6-Button White
GDS - Control Station
GDS-6TSB-W
105
PPS-5
Site
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
PPS-5
North Vestibule
OAC-DT-2000-R
North Vestibule
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
OAC-DT-2000-R
133A-C
OAC-DT-2000-R
133A-C
OAC-DT-2000-R
133A-C
OAC-DT-2000-R
133A-C
OAC-DT-2000-R
133A-C
OAC-DT-2000-R
133A-C
OAC-DT-2000-R
133A-C
OAWC-DT-120W-R
Site
PPS-5
Site
PPS-5
Site
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
OAC-DT-2000-R
164A-D
OAC-DT-2000-R
164A-D
OAC-DT-2000-R
164A-D
OAC-DT-2000-R
164A-D
OAC-DT-2000-R
164A-D
OAC-DT-2000-R
164A-D
OAC-DT-2000-R
164A-D
OAWC-DT-120W-R
Site
PPS-5
Site
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
PC-I
160
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
GDS-I-KIT
Building 1
3-Button White
GDS - Control Station
GDS-3TLB-W
160
3-Button White
GDS - Control Station
GDS-3TLB-W
160
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
OAC-DT-2000-R
229A-D
OAC-DT-2000-R
229A-D
OAC-DT-2000-R
229A-D
OAC-DT-2000-R
229A-D
OAC-DT-2000-R
229A-D
OAC-DT-2000-R
229A-D
OAC-DT-2000-R
229A-D
OAC-DT-2000-R
229A-D
OAC-DT-2000-R
229A-D
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
PPS-5
Site
GDS-I-KIT
Building 1
2-Button White
GDS - Control Station
GDS-2TLB-W
129
2-Button White
GDS - Control Station
GDS-2TLB-W
129
OAC-DT-2000-R
122
OAC-DT-2000-R
122
OAC-DT-2000-R
122
OAC-DT-2000-R
103
OAC-DT-2000-R
103
OAC-DT-2000-R
104
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
PPS-5
Site
GDS-I-KIT
Building 1
5-Button White
GDS - Control Station
GDS-5TSB-W
120B
OAC-DT-2000-R
109B
OAC-DT-2000-R
109B
OAC-DT-2000-R
109B
PPS-5
Site
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
120/277V Transformer Power
Dedicated Circuit
To Lighting loads
To 0-10 Ballasts
RS232
3rd Party
Dry Contacts
ControlKeeper 4A
0-10V Dimming
CK4A-SLRC
Building 1
Three 0-10V
Outputs
Normal
Circuits
Room Controller
11.5Hx7.5Wx2.25D
RC3D-PL-N
Room #s Below
6-Button White
RC - Wallstation
PDR-RC-6TSB
Room #s Below
6-Button White
RC - Wallstation
PDR-RC-6TSB
Room #s Below
Connects to any
Occupancy Sensor
BMS or Egress
OCC-RJ45
Room #s Below
OAC-DT-2000-R
Room #s Below
Three 0-10V
Outputs
Normal
Circuits
Room Controller
11.5Hx7.5Wx2.25D
RC3D-PL-N
Room #s Below
1
This one-line drawing is for concept only. Every wire is not shown. Wire according to the product installation / wiring instructions .
2
Refer to plans for locations,size and quantity.
3
Refer to all manufacturers installation instructions for correct wiring information
Notes
RS485 RS-485 Network Cable, Eaton GG9841(Non Plenum), Eaton GG89841(Plenum) or equivalent
RS232 RS-232 Cable (6 feet), provided with product
CAN Use Eaton Lighting systems LCCNP non-plenum cable or LCCP plenum cable.
LV3 Low Voltage Input wire - #18 AWG, 3 conductor wire
LAN LAN Cable, Category 5 cable provided by others
QC Quick Connect Cable, Pre-Terminated RJ45 - Category 5 cable
Cables
110, 112, 124, 125, 126, 127
128, 131, 138, 140, 142, 166
5-Button White
GDS - Control Station
GDS-5TSB-W
141
Three 0-10V
Outputs
Normal
Circuits
Room Controller
11.5Hx7.5Wx2.25D
RC3D-PL-N
Room #s Below
6-Button White
RC - Wallstation
PDR-RC-6TSB
Room #s Below
Connects to any
Occupancy Sensor
BMS or Egress
OCC-RJ45
Room #s Below
OAC-DT-2000-R
Room #s Below
Three 0-10V
Outputs
Normal
Circuits
Room Controller
11.5Hx7.5Wx2.25D
RC3D-PL-N
Room #s Below
144
Three 0-10V
Outputs
Normal
Circuits
Room Controller
11.5Hx7.5Wx2.25D
RC3D-PL-N
Room #s Below
6-Button White
RC - Wallstation
PDR-RC-6TSB
Room #s Below
Connects to any
Occupancy Sensor
BMS or Egress
OCC-RJ45
Room #s Below
OAC-DT-2000-R
Room #s Below
Three 0-10V
Outputs
Normal
Circuits
Room Controller
11.5Hx7.5Wx2.25D
RC3D-PL-N
Room #s Below
107
Connects to any
Occupancy Sensor
BMS or Egress
OCC-RJ45
Room #s Below
OAC-DT-2000-R
6-Button White
RC - Wallstation
PDR-RC-6TSB
Room #s Below
6-Button White
RC - Wallstation
PDR-RC-6TSB
Room #s Below
169, 171, 173, 175, 179, 181
183, 185, 207, 212, 218, 222
Three 0-10V
Outputs
Normal
Circuits
Room Controller
11.5Hx7.5Wx2.25D
RC3D-PL-N
Room #s Below
6-Button White
RC - Wallstation
PDR-RC-6TSB
Room #s Below
Connects to any
Occupancy Sensor
BMS or Egress
OCC-RJ45
Room #s Below
OAC-DT-2000-R
Room #s Below
Three 0-10V
Outputs
Normal
Circuits
Room Controller
11.5Hx7.5Wx2.25D
RC3D-PL-N
Room #s Below
201, 206, 210
Connects to any
Occupancy Sensor
BMS or Egress
OCC-RJ45
Room #s Below
OAC-DT-2000-R
6-Button White
RC - Wallstation
PDR-RC-6TSB
Room #s Below
224, 226, 231, 233, 238 (Typical of 2), 241
243, 245, 247, 249, 253, 259
201, 206, 210107144
110, 112, 124, 125, 126, 127
128, 131, 138, 140, 142, 166
169, 171, 173, 175, 179, 181
183, 185, 207, 212, 218, 222
224, 226, 231, 233, 238 (Typical of 2), 241
243, 245, 247, 249, 253, 259
OAC-DT-2000-R
200
OAC-DT-2000-R
200
OAC-DT-2000-R
203A-203D
OAC-DT-2000-R
203A-203D
OAC-DT-2000-R
203A-203D
OAC-DT-2000-R
203A-203D
OAC-DT-2000-R
203A-203D
OAC-DT-2000-R
203A-203D
OAC-DT-2000-R
203A-203D
5-Button White
GDS - Control Station
GDS-5TSB-W
160
Exterior Lighting Control
Exterior Lighting Control
RPTR
Building 1
Typical 1 of 2
1 needed for every 32 panels
OAWC-DT-120W-R
Room #s Below
GDS-I-KIT
Building 1
SANDYHOOK ELEMENTARY
ART
09-04-2015
N.T.S.
DATE
SCALE
EATON'S COOPER CONTROLS
BUSINESS
1-800-553-3879 PHONE
1-800-954-7016 FAX
203 COOPER CIRCLE
PEACHTREE CITY, GA 30269
Newington Forest Elementary16505.02 140
xx
11/30/16
ONW-D-1001-MV-W
Typical of 16 1st Floor Area A
SP20-MV
Room #s Below
Momentary Decorator
White Switch
GMDS-W
Room #s Below
OAC-DT-2000-R
Room #s Below
SP20-MV
Room #s Below
Momentary Decorator
White Switch
GMDS-W
Room #s Below
SP20-MV
Room #s Below
OAC-DT-2000-R
Room #s Below
1
This one-line drawing is for concept only. Every wire is not shown. Wire according to the product installation / wiring instructions .
2
Refer to plans for locations,size and quantity.
3
Refer to all manufacturers installation instructions for correct wiring information
Notes
RS485 RS-485 Network Cable, Eaton GG9841(Non Plenum), Eaton GG89841(Plenum) or equivalent
RS232 RS-232 Cable (6 feet), provided with product
CAN Use Eaton Lighting systems LCCNP non-plenum cable or LCCP plenum cable.
LV3 Low Voltage Input wire - #18 AWG, 3 conductor wire
LAN LAN Cable, Category 5 cable provided by others
QC Quick Connect Cable, Pre-Terminated RJ45 - Category 5 cable
Cables
120 106, 106A, 113, 116, 120, 130
SP20-MV
Room #s Below
Momentary Decorator
White Switch
GMDS-W
Room #s Below
OAC-DT-2000-R
Room #s Below
105B, 112B, 167B, 201B
SP20-MV
Room #s Below
Momentary Decorator
White Switch
GMDS-W
Room #s Below
OAC-DT-2000-R
Room #s Below
SP20-MV
Room #s Below
0-10V Decorator Dimmer
White Switch
DF10P-C1
Room #s Below
159 159
1 of 2
137, 139, 143, 147, 149
150, 151, 153, 155, 157
OAC-DT-2000-R
Room #s Below
Momentary Decorator
White Switch
GMDS-W
Room #s Below
147
167, 168, 170, 174, 176
202, 205, 208, 232, 235
SP20-MV
Room #s Below
OAC-DT-2000-R
Room #s Below
117, 118, 228, 230, 234, 236
237, 239, 240
OSP20-RDH
Room #s Below
OAC-DT-2000-R
Room #s Below
OAC-DT-2000-R
Room #s Below
Momentary Decorator
White Switch
GMDS-W
Room #s Below
106
OSP20-RDH
Momentary Decorator
White Switch
GMDS-W
Room #s Below
Room #s Below
OSP20-RDH
Momentary Decorator
White Switch
GMDS-W
Room #s Below
Room #s Below
OSP20-RDH
Momentary Decorator
White Switch
GMDS-W
Room #s Below
Room #s Below
OSP20-RDH
Momentary Decorator
White Switch
GMDS-W
Room #s Below
Room #s Below
OSP20-RDH
Momentary Decorator
White Switch
GMDS-W
Room #s Below
Room #s Below
106 106 106 106 106
SP20-MV
Momentary Decorator
White Switch
GMDS-W
Room #s Below
OAC-DT-2000-R
Room #s Below
SP20-MV
Momentary Decorator
White Switch
GMDS-W
Room #s Below
OAC-DT-2000-R
Room #s Below
Room #s Below Room #s Below
162 162
1 of Mezzanine
(55)
Typical of 11 1st Floor Area B
Typical of 15 1st Floor Area C
Typical of 6 2nd Floor Area C
Typical of 6 2nd Floor Area B
16505.02 140
xx
11/30/16
Date:
Project:
Title: Wiring Details
Product: (SP15 & SP20)Heavy Duty Switchpack
Eaton1121 Highway 74 South Peachtree City, GA 30269
Date:
Project:
Title: Wiring Details
Product: (SP15 & SP20)Heavy Duty Switchpack
Eaton1121 Highway 74 South Peachtree City, GA 30269
Date:
Project:
Title: Wiring Details
Product: (SP15 & SP20)Heavy Duty Switchpack
Eaton1121 Highway 74 SouthPeachtree City, GA 30269
Date:
Project:
Title: Wiring Details
Product: (SP15 & SP20)Heavy Duty Switchpack
Eaton1121 Highway 74 SouthPeachtree City, GA 30269
Date:
Project:
Title: Wiring Details
Product: (SP15 & SP20)Heavy Duty Switchpack
Eaton1121 Highway 74 South Peachtree City, GA 30269
Date:
Project:
Title: General/Network Detail
Product: Greengate Digital Switch
Eaton1121 Highway 74 SouthPeachtree City, GA 30269
Date:
Project:
Title: Network Wiring Detail
Product: Greengate Digital Switch
Eaton1121 Highway 74 SouthPeachtree City, GA 30269
ControlsControls Date:
Project:
Title: General Information
Product: Contact Input Photocells
ControlsControls Date:
Project:
Title: General/Coverage Information
Product: (OAWC-DT)Dual Tech Wall/Corner Mount
ControlsControls Date:
Project:
Title: Wiring Details
Product: (OAWC-DT)Dual Tech Wall/Corner Mount
ControlsControls Date:
Project:
Title: DIP Switch Information
Product: (OAWC-DT)Dual Tech Wall/Corner Mount
ControlsControls Date:
Project:
Title: General/Coverage Information
Product: NeoSwitch (ONW-D)Dual Tech Single Level (Ground Required)
ControlsControls Date:
Project:
Title: Wiring Details
Product: NeoSwitch (ONW-D)Dual Tech Single Level (Ground Required)
ControlsControls Date:
Project:
Title: DIP Switch Information
Product: NeoSwitch (ONW-D)Dual Tech Single Level (Ground Required)
Date:
Project:
Title: Enclosure/Interior Reference
Product: ControlKeeper 4A
Eaton1121 Highway 74 SouthPeachtree City, GA 30269