Protection Coordination ReportOwner
Project:
Compiled by
Interface Electronics Pvt Ltd,Chennai
Email:ife@vsnl.com
website:www.ifepwrana.com
mobile:9884370326
JANKI CORPN LTD
JANKI CORPN LTD., STEEL DIVISION ,SIDIGINAMOLA VILLAGE,BELLARYI
Sl.No Descriptiion Page No
1 Executive Summary 3
2 Reference Documents 4
3 Single Line Diagram 5
4 Short circuit Report Grid 7
5 Device Details 11
6 Transformer Relay Setting Calculations 12
7 Setting Details for Relay and Control Panel 24
8 Setting Details for 11 kV HT Switch Board 32
9 Setting Details for 6.6 kV HT Switch Board 57
10 Setting Details for LT PCC/ MCC 89
11 Time Current Characteristic Curves 102
12 Observation and Comments 109
Contents
Introduction
Project: 1x 15 MW Captive Power Plant at Janki Corpn Ltd,Bellary
Owner:JCL Janki Corpn Ltd Steel Divn,Madpiya Chordia,Chittor Road,Bhilwara-311001,Rajasthan
ElectricalDistribution System11 kV Power Generation,6.6 kV Station Service and 6.6 kV for Unit Auxiliarysystem 110 kV for Transmission and Distribution and distribution at 0.415 kV
Power System DataMax Source Fault level(assumed)
5000 MVA sec at 110 kV
Min Source Fault level (assumed) 10000 MVA sec at 400 kV
Tools used: Paladin Design Base 5- an Electrical Design softwareProtection Coordination
The short circuit currents at various busbars are calculated based on the aboveassumptions. Calculated Short circuit currents are shown in the SLD.Selectivity of relays and circuit breakers were worked out based on the cablesize and flow of short circuit currents.Time current characterstic curves are generated for every path and verified .
ConclusionSettings for each device,short circuit currents at every busbars,detailedcalculations for the settings are given in the following pages. While doing thisexercise certain discrepencies were noticed and these are brought outseperately under heading 'Comments and Observations'.
Executive Summary
Settings for each device,short circuit currents at every busbars,detailedcalculations for the settings are given in the following pages. While doing thisexercise certain discrepencies were noticed and these are brought outseperately under heading 'Comments and Observations'.
Sl.No File name Title of the Document Document/drawing No1 JCLSLD.DWG OVERALL SINGLE LINE DIAGRAM FOR 15 MW,3.5MW &
110 KvJCL-CPP-ELE-0001
2 RELAYS IN JCL.DOCX Single Line diagram for 110 kV Switch Yard Extension3 2600KW HT motor test report.pdf TEST CERTIFICATE ON 2600kW MOTOR4 211218 ID fan 1000KW.jpg TEST CERTIFICATE ON 1000kW MOTOR5 803448 AHF -1 315KW.jpg TEST CERTIFICATE ON 315kW MOTOR6 2000KVA transformer.pdf TECHNICAL PARTICULARS ON TRANSFORMERS7 20 MVA TR 1.jpg TECHNICAL PARTICULARS ON TRANSFORMERS 20 MVA8 1250 kVA TR 1.jpg TECHNICAL PARTICULARS ON TRANSFORMERS 1250kVA9 1600 kVA TR 1.jpg TECHNICAL PARTICULARS ON TRANSFORMERS 1600kVA10 1000 kVA TR 1.jpg TECHNICAL PARTICULARS ON TRANSFORMERS 1000kVA11 3.5 TG 1.jpg TECHNICAL PARTICULARS ON TRANSFORMERS 3.5 MW
TG12 16 TG 1.jpg TECHNICAL PARTICULARS ON TRANSFORMERS 16 MW TG13 15 MVA TR 1.jpg TECHNICAL PARTICULARS ON TRANSFORMERS 15 MVA14 750 kVA TR 1.jpg TECHNICAL PARTICULARS ON TRANSFORMERS 750 kVA
Reference Documents/Drawings
SINGLE LINE DIAGRAMSINGLE LINE DIAGRAM
DWG SIZE:SCALE:
MFG. APP./DATE:
ENG. APP./DATE:
DRAWN BY/DATE: REV.DWG No.:
Address
Address
Your Company Name
THIS DRAWING IS PROPRIETARY INFORMATION
PART No.:
DWG. No.
REV. DATE ECO# DWN APP DESCRIPTION
Phone and web site
Electrical One-Line Diagramfor Protection Coordination StudyElectrical One-Line Diagramfor Protection Coordination Study
TG_C
ABLE
5051
GCB
GENTG2
5051
11 kV HT LCSS-1 UA IC1
11 kV HT LCSS-1 UA_LH
5051
LCSS1_ET5051
KILN1&2
5051
PELLET PLANT 1
5051
LCSS1_FDR1 5051
AFBC FEEDER
ET
CAB_ET
11kV
HT
LCSS
-1 U
A BC
11 kV HT LCSS-1 UA_RH
5051
11 kV HT LCSS-1 UA IC2
5051
LCSS1_FDR25051
RMP35051
KILN3&45051
S T P5051
AFBC FEEDER 2
CAB_KILN
1
TRAF01_2MVA
CAB_PELLET
CAB_LC
SS1_FDR
1
CAB_LC
SS_FDR
2
CAB_R
MP3
CAB_KILN
3
CAB_SW
TP
415V LCSS1 CPP IC1
415V LCSS1 CPP LH
TRAF02_2MVA
415V LCSS1 CPP IC2
415V LCSS1 CPP RH5051 INT.PANEL
TRAF01_15 MVA
5051
6.6kV_LBSS1_IC1
CAB_TR
AFO_SW
BD
6.6kV_LBSS1_LH
5051
1F1:HT MOTOR5051
2F1:LCSS25051
3F1:LCSS35051
4F1:LBDS15051
5F1:LBDS25051
6F1:SPARE
6.6k
V_LB
SS1_
BC
6.6kV_LBSS1_RH
5051
12F1:LBDS25051
13F1:LBDS25051
14F1:LCSS35051
15F1:LCSS25051
16F1:SPARE5051
17F1:HTMOTOR
5051
6.6kV_LBSS1_IC2
CAB_SW
BD_TR
AFOTRAF03_LCSS3
CAB_O
RE BEN
PLANT
TRAF2_LCSS2
415 V LCSS-2 OCGS IC2415 V LCSS-3 APP IC2
415 V LCSS-3 APP RH
415 V LCSS-2 OCGS RH
91
TRAFO1_LCSS2
415 V LCSS-2 OCGS IC1
415 V LCSS-2 OCGS LH
TRAFO1_LCSS3
415 V LCSS-3 APP IC1
415 V LCSS-3 APP LH
103
TRAF01_20MVA
110 kV BUS
5051
LINE_CB
GRID KPCTL
5051
TR_CB
5051
STP PLANT1
TRAF02_0.75 MVA
415 V LCSS-7 STP IC1
415 V LCSS-7 STP LH
5051
BC
125
5051
126
5051
133
134
135
138
GENDG1
141
RMP3 TR KILN 3 TR
CAB:AFBC
2
AFBC TR2
I2600kW
5051
AH03
154
5051
AH215051
AH23
5051
AH175051
AH195051
AH155051
AH13
162
5051
AH105051
AH125051
AH145051
AH165051
AH185051
AH20
5051
AH04
170
172174
176
178 179
BALLING MCC2SC.BLDG.MCC RHS
184
191
192
TG MCC1
196
I
AH FAN1_315kW
105
106
CAP PNL1 500 kVAR
205
I
IDFAN_1000kW
208
210
211
BALLING MCC1
215217
219
220
P_MIXING MCC1
224226
5051
AH 11
SC MCC TR
230
SC.BLDG.MCC LHS
234236
5051
AH095051
AH07
5051
AH01 BC5051
AH65051
AH8
270
272
P_MIXING MCC2
183
238
239
240
283
285
287
TG MCC2
290
IAH FAN2_315kW
293
295
CAP PNL 2_500 kVAR
I
ORE GRINDING MOTOR
CAB_O
RE G
RIN
DIN
G
CAB_LBD
S2
415V
LC
SS1
CPP
IC3
415 V LCSS-2 OCGS1 RH
415 V LCSS-2 OCGS IC3
415
V LC
SS-2
OC
GS
IC4
CAB_SW
BD_TR
AFO1
TRAFO1_LCSS4
233
415 V LCSS-7 STP IC2
415 V LCSS-7 STP LH1
KILN 3
kiln 3
GENTG1
ÊSINGLE LINE DIAGRAM
SHORT CIRCUIT CURRENTS-GRID 2500 MVASEC
DWG SIZE:SCALE:
MFG. APP./DATE:
ENG. APP./DATE:
DRAWN BY/DATE: REV.DWG No.:
Address
Address
Your Company Name
THIS DRAWING IS PROPRIETARY INFORMATION
PART No.:
DWG. No.
REV. DATE ECO# DWN APP DESCRIPTION
Phone and web site
Electrical One-Line Diagramfor Protection Coordination StudyShort circuit currents for source fault of 2500 MVAsec @ 110kVElectrical One-Line Diagramfor Protection Coordination Study
Short circuit currents for source fault of 2500 MVAsec @ 110kV
TG_C
ABLE
5051
GCB
GENTG2
5051
11 kV HT LCSS-1 UA IC1
11 kV HT LCSS-1 UA_LHIk" : 9966.52AVp: 11000 V
5051
LCSS1_ET5051
KILN1&2
5051
PELLET PLANT 1
5051
LCSS1_FDR1 5051
AFBC FEEDER
ETIk" : 9864.91AVp: 11000 V
CAB_ET
11kV
HT
LCSS
-1 U
A BC
11 kV HT LCSS-1 UA_RHIk" : 9965.19AVp: 11000 V
5051
11 kV HT LCSS-1 UA IC2
5051
LCSS1_FDR25051
RMP35051
KILN3&45051
S T P5051
AFBC FEEDER 2
CAB_KILN
1
TRAF01_2MVA
CAB_PELLET
CAB_LC
SS1_FDR
1
CAB_LC
SS_FDR
2
CAB_R
MP3
CAB_KILN
3
CAB_SW
TP
415V LCSS1 CPP IC1
415V LCSS1 CPP LHIk" : 39626.53AVp: 433 V
TRAF02_2MVA
415V LCSS1 CPP IC2415V LCSS1 CPP RHIk" : 39642.44AVp: 433 V
5051 INT.PANEL
TRAF01_15 MVA
5051
6.6kV_LBSS1_IC1
CAB_TR
AFO_SW
BD
6.6kV_LBSS1_LHIk" : 7735.55AVp: 6600 V
5051
1F1:HT MOTOR5051
2F1:LCSS25051
3F1:LCSS35051
4F1:LBDS15051
5F1:LBDS25051
6F1:SPARE
6.6k
V_LB
SS1_
BC
6.6kV_LBSS1_RHIk" : 7734.19AVp: 6600 V
5051
12F1:LBDS25051
13F1:LBDS25051
14F1:LCSS35051
15F1:LCSS25051
16F1:SPARE5051
17F1:HTMOTOR
5051
6.6kV_LBSS1_IC2
CAB_SW
BD_TR
AFOTRAF03_LCSS3
CAB_O
RE BEN
PLANT
TRAF2_LCSS2
415 V LCSS-2 OCGS IC2415 V LCSS-3 APP IC2
415 V LCSS-3 APP RHIk" : 28200.14AVp: 433 V
415 V LCSS-2 OCGS RHIk" : 28200.14AVp: 433 V
91
TRAFO1_LCSS2
415 V LCSS-2 OCGS IC1
415 V LCSS-2 OCGS LHIk" : 28186.51AVp: 433 V
TRAFO1_LCSS3
415 V LCSS-3 APP IC1
415 V LCSS-3 APP LHIk" : 28186.51AVp: 433 V
103
TRAF01_20MVA
110 kV BUSIk" : 13144.79AVp: 110000 V
5051
LINE_CB
GRIDKPCTLIk" : 13145.13AVp: 110000 V
5051
TR_CB
5051
STP PLANT1
TRAF02_0.75 MVA
415 V LCSS-7 STP IC1415 V LCSS-7 STP LHIk" : 20049.81AVp: 433 V
5051
BC
125
5051
126
5051
133
134
135
138
GENDG1
141
RMP3 TR KILN 3 TR
CAB:AFBC
2
AFBC TR2
I2600kWIk" : 7735.31AVp: 6600 V
5051
AH03
154Ik" : 7650.15AVp: 6600 V
5051
AH215051
AH23
5051
AH175051
AH195051
AH155051
AH13
162Ik" : 7661.83AVp: 6600 V
5051
AH105051
AH125051
AH145051
AH165051
AH185051
AH20
5051
AH04
170
172174
176
178 179
BALLING MCC2Ik" : 23441.38AVp: 433 V
SC.BLDG.MCC RHSIk" : 23441.38AVp: 433 V
184
191
192
TG MCC1Ik" : 28456.18AVp: 433 V
196
I
AH FAN1_315kWIk" : 7564.94AVp: 6600 V
105
106
CAP PNL1 500 kVARIk" : 7575.52AVp: 6600 V
205
I
IDFAN_1000kWIk" : 7577.09AVp: 6600 V
208
210
211
BALLING MCC1Ik" : 28456.18AVp: 433 V
215217
219
220
P_MIXING MCC1Ik" : 23433.37AVp: 433 V
224226
5051
AH 11
SC MCC TR
230
SC.BLDG.MCC LHSIk" : 23433.37AVp: 433 V
234236
5051
AH095051
AH07
5051
AH01 BC5051
AH65051
AH8
270
272
P_MIXING MCC2Ik" : 23441.38AVp: 433 V
183
238
239
240
283
285
287
TG MCC2Ik" : 23441.38AVp: 433 V
290
IAH FAN2_315kWIk" : 7588.28AVp: 6600 V
293
295
CAP PNL 2_500 kVARIk" : 7586.7AVp: 6600 V
I
ORE GRINDING MOTORIk" : 7662.86AVp: 6600 V
CAB_O
RE G
RIN
DIN
G
CAB_LBD
S2
415V
LC
SS1
CPP
IC3
415 V LCSS-2 OCGS1 RHIk" : 28200.14AVp: 433 V
415 V LCSS-2 OCGS IC3
415
V LC
SS-2
OC
GS
IC4
CAB_SW
BD_TR
AFO1
TRAFO1_LCSS4
233
415 V LCSS-7 STP IC2
415 V LCSS-7 STP LH1Ik" : 26090.57AVp: 433 V
KILN 3Ik" : 44146.08AVp: 415 V
kiln 3
GENTG1
ÊSINGLE LINE DIAGRAM
SHORT CIRCUIT CURRENTS-GRID 5000 MVASEC
DWG SIZE:SCALE:
MFG. APP./DATE:
ENG. APP./DATE:
DRAWN BY/DATE: REV.DWG No.:
Address
Address
Your Company Name
THIS DRAWING IS PROPRIETARY INFORMATION
PART No.:
DWG. No.
REV. DATE ECO# DWN APP DESCRIPTION
Phone and web site
Electrical One-Line Diagramfor Protection Coordination StudyShort circuit currents for source fault of 5000 MVAsec @ 110kVElectrical One-Line Diagramfor Protection Coordination Study
Short circuit currents for source fault of 5000 MVAsec @ 110kV
TG_C
ABLE
5051
GCB
GENTG2
5051
11 kV HT LCSS-1 UA IC1
11 kV HT LCSS-1 UA_LHIk" : 10338.33AVp: 11000 V
5051
LCSS1_ET5051
KILN1&2
5051
PELLET PLANT 1
5051
LCSS1_FDR1 5051
AFBC FEEDER
ETIk" : 10228.38AVp: 11000 V
CAB_ET
11kV
HT
LCSS
-1 U
A BC
11 kV HT LCSS-1 UA_RHIk" : 10336.89AVp: 11000 V
5051
11 kV HT LCSS-1 UA IC2
5051
LCSS1_FDR25051
RMP35051
KILN3&45051
S T P5051
AFBC FEEDER 2
CAB_KILN
1
TRAF01_2MVA
CAB_PELLET
CAB_LC
SS1_FDR
1
CAB_LC
SS_FDR
2
CAB_R
MP3
CAB_KILN
3
CAB_SW
TP
415V LCSS1 CPP IC1
415V LCSS1 CPP LHIk" : 39832.03AVp: 433 V
TRAF02_2MVA
415V LCSS1 CPP IC2
415V LCSS1 CPP RHIk" : 39848.12AVp: 433 V
5051 INT.PANEL
TRAF01_15 MVA
5051
6.6kV_LBSS1_IC1
CAB_TR
AFO_SW
BD
6.6kV_LBSS1_LHIk" : 7858.11AVp: 6600 V
5051
1F1:HT MOTOR5051
2F1:LCSS25051
3F1:LCSS35051
4F1:LBDS15051
5F1:LBDS25051
6F1:SPARE
6.6k
V_LB
SS1_
BC
6.6kV_LBSS1_RHIk" : 7856.7AVp: 6600 V
5051
12F1:LBDS25051
13F1:LBDS25051
14F1:LCSS35051
15F1:LCSS25051
16F1:SPARE5051
17F1:HTMOTOR
5051
6.6kV_LBSS1_IC2
CAB_SW
BD_TR
AFOTRAF03_LCSS3
CAB_O
RE BEN
PLANT
TRAF2_LCSS2
415 V LCSS-2 OCGS IC2415 V LCSS-3 APP IC2
415 V LCSS-3 APP RHIk" : 28297.62AVp: 433 V
415 V LCSS-2 OCGS RHIk" : 28297.62AVp: 433 V
91
TRAFO1_LCSS2
415 V LCSS-2 OCGS IC1
415 V LCSS-2 OCGS LHIk" : 28283.92AVp: 433 V
TRAFO1_LCSS3
415 V LCSS-3 APP IC1
415 V LCSS-3 APP LHIk" : 28283.92AVp: 433 V
103
TRAF01_20MVA
110 kV BUSIk" : 26265.38AVp: 110000 V
5051
LINE_CB
GRIDKPCTLIk" : 26266.72AVp: 110000 V
5051
TR_CB
5051
STP PLANT1
TRAF02_0.75 MVA
415 V LCSS-7 STP IC1
415 V LCSS-7 STP LHIk" : 20102.28AVp: 433 V
5051
BC
125
5051
126
5051
133
134
135
138
GENDG1
141
RMP3 TR KILN 3 TR
CAB:AFBC
2
AFBC TR2
I2600kWIk" : 7857.85AVp: 6600 V
5051
AH03
154Ik" : 7769.84AVp: 6600 V
5051
AH215051
AH23
5051
AH175051
AH195051
AH155051
AH13
162Ik" : 7781.73AVp: 6600 V
5051
AH105051
AH125051
AH145051
AH165051
AH185051
AH20
5051
AH04
170
172174
176
178 179
BALLING MCC2Ik" : 23508.66AVp: 433 V
SC.BLDG.MCC RHSIk" : 23508.66AVp: 433 V
184
191
192
TG MCC1Ik" : 28555.3AVp: 433 V
196
I
AH FAN1_315kWIk" : 7681.84AVp: 6600 V
105
106
CAP PNL1 500 kVARIk" : 7692.77AVp: 6600 V
205
I
IDFAN_1000kWIk" : 7694.37AVp: 6600 V
208
210
211
BALLING MCC1Ik" : 28555.3AVp: 433 V
215217
219
220
P_MIXING MCC1Ik" : 23500.59AVp: 433 V
224226
5051
AH 11
SC MCC TR
230
SC.BLDG.MCC LHSIk" : 23500.59AVp: 433 V
234236
5051
AH095051
AH07
5051
AH01 BC5051
AH65051
AH8
270
272
P_MIXING MCC2Ik" : 23508.66AVp: 433 V
183
238
239
240
283
285
287
TG MCC2Ik" : 23508.66AVp: 433 V
290
IAH FAN2_315kWIk" : 7705.74AVp: 6600 V
293
295
CAP PNL 2_500 kVARIk" : 7704.14AVp: 6600 V
I
ORE GRINDING MOTORIk" : 7782.78AVp: 6600 V
CAB_O
RE G
RIN
DIN
G
CAB_LBD
S2
415V
LC
SS1
CPP
IC3
415 V LCSS-2 OCGS1 RHIk" : 28297.62AVp: 433 V
415 V LCSS-2 OCGS IC3
415
V LC
SS-2
OC
GS
IC4
CAB_SW
BD_TR
AFO1
TRAFO1_LCSS4
233
415 V LCSS-7 STP IC2
415 V LCSS-7 STP LH1Ik" : 26179.51AVp: 433 V
KILN 3Ik" : 44412.14AVp: 415 V
kiln 3
GENTG1
Details of DevicesTransformers
To From Primary Volt
Secondary Volt
Ratingin kVA HV LV Vector
Group Z in % Type ofCooling
HVRATED
CURRENT
LV RATEDCURRENT
11 kV Switch Board GRID 110000 11000 20000 STAR DELTA YNd1 10 ONAN/ONAF 104.98 1049.76FDR 07 LBSS-1 6.6 kV LBSS-1 SWBD FDR 4 11 kV SWBD 11000 6900 15000 DELTA STAR Dyn11 8.35 ONAN/ONAF 787.32 1255.15Screening MCC LHS AH11 HV distribution 6600 433 1000 DELTA STAR Dyn11 5 ONAN 87.48 1333.38Screening MCC RHS AH10 HV distribution 6600 433 1000 DELTA STAR Dyn11 5 ONAN 87.48 1333.38TG MCC RHS AH16 HV distribution 6600 433 1600 DELTA STAR Dyn11 5 ONAN 139.96 2133TG MCC LHS AH17 HV distribution 6600 433 1600 DELTA STAR Dyn11 5 ONAN 139.96 2133BALLING SYSTEM LHS AH15 HV distribution 6600 433 1600 DELTA STAR Dyn11 5 ONAN 139.96 2133BALLING SYSTEM RHS AH14 HV distribution 6600 433 1600 DELTA STAR Dyn11 5 ONAN 139.96 2133PROPORTION & MIXING MCC LHS AH13 HV distribution 6600 433 1000 DELTA STAR Dyn11 5 ONAN 87.48 1333.38PROPORTION & MIXING MCC RHS AH12 HV distribution 6600 433 1000 DELTA STAR Dyn11 5 ONAN 87.48 1333.38ORE CRUSHING GRINDING SYSTEM LHS LCSS-2 FDR 02 6.6 kV LBBSS-1 SWBD 6600 433 1250 DELTA STAR Dyn11 5 ONAN 109.35 1666.76ORE CRUSHING GRINDING SYSTEM RHS LCSS-1 FDR 15 6.6 kV LBBSS-1 SWBD 6600 433 1250 DELTA STAR Dyn11 5 ONAN 109.35 1666.76CPP LCSS-1 FDR 5 11 kV SWBD 11000 433 2000 DELTA STAR Dyn11 6.25 ONAN 104.98 2666.82CPP LCSS-1 FDR12 11 kV SWBD 11000 433 2000 DELTA STAR Dyn11 6.25 ONAN 104.98 2666.82KILN 1&2 FDR 3 11 kV SWBD 11000 433 1250 DELTA STAR Dyn11 5 ONAN 65.61 1666.76AFBC FEEDER LHS FDR 6 11 kV SWBD 11000 433 750 DELTA STAR Dyn11 5 ONAN 39.37 1000.06AFBC FEEDER RHS FDR 16 11 kV SWBD 11000 433 750 DELTA STAR Dyn11 5 ONAN 39.37 1000.06RMP3 FDR 13 11 kV SWBD 11000 433 1000 DELTA STAR Dyn11 5.16 ONAN 52.49 1333.38RMP3 FDR 13 11 kV SWBD 11000 433 1000 DELTA STAR Dyn11 5.16 ONAN 52.49 1333.38KILN 3,4&5 FDR 14 11 kV SWBD 11000 433 2500 DELTA STAR Dyn11 6.5 ONAN 131.22 3333.53STP FEEDER FDR 15 11 kV SWBD 11000 433 750 DELTA STAR Dyn11 5 ONAN 39.37 1000.06
SETTING CALCULATIONS
DG SETS
SETTING CALCULATIONSFOR TRANSFORMERSFOR TRANSFORMERS
Transformer capacity PT 2000 kVAPrimary Voltage Vp 11 kVSecondary Voltage Vs 0.433 kVTransformer HV side CT details CTHV 125/1Turns Ratio CTRP 125Transformer LV side ACB CT details 3200Percentage Impedance of Transformer Z 6.25%Through Fault current at 0.415 kV Bus 33337 AmpsTransformer HV side current as per name plate 104.98 AmpsRelay drop off Ratio 0.95HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x 104.98/0.95121.55
Transformer HV side CT Secondary Pick up Current Isfl 0.97
Setting Calculation for Distribution Transformers 2 MVA
11kV,
11
125/12000 kVA
433 V
3200
75/1000 kVA
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
Transformer HV side CT Secondary Pick up Current Isfl 0.97IDMT setting at 11 kV side 1Setting proposed on HV side Ip 1Curve Extreme InverseTransformer LV side current as per name plate 2666.82Relay drop off Ratio 0.95LV Pick up Current 1.1 x LV Currrent/ Drop off ratio
=1.1 x 2666.82/0.953087.90
Transformer LV side CT Secondary Pick up Current =3087.90/3200Relay setting for over current 1Setting proposed on LV side Ip 1
Through Fault current at 0.415kV Bus 33337.00 AmpsHV side current due to fault at 0.415 kV bus 1312.27 AmpsHV side CT Secondary current due to fault at 0.415kV bus 10.50 AmpsSetting proposed on HV side relay I>> 13.00 AmpsSetting proposed on LV side relay I>> 6
11kV,
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
Transformer capacity PT 1000 kVAPrimary Voltage Vp 11 kVSecondary Voltage Vs 0.433 kVTransformer HV side CT details CTHV 75/1Turns Ratio CTRP 75Transformer LV side ACB Rating 1600Percentage Impedance of Transformer Z 5.16%Through Fault current at 0.415 kV Bus 23208.00 AmpsTransformer HV side current as per name plate 52.49 AmpsRelay drop off Ratio 0.95HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x 52.49/0.9560.78
Transformer HV side CT Secondary Pick up Current Isfl 0.81
Setting Calculation for Distribution Transformers 1 MVA
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
2500 kVA
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
Transformer HV side CT Secondary Pick up Current Isfl 0.81IDMT setting at 11 kV side 0.8Setting proposed on HV side Ip 0.8Curve Extremel InverseTransformer LV side current as per name plate 1333.41Relay drop off Ratio 0.95LV Pick up Current 1.1 x LV Currrent/ Drop off ratio
=1.1 x1333.41/0.951543.95
Transformer LV side CT Secondary Pick up Current =1543.95/1600ACB setting for over current 0.96496875Setting proposal on ACB 1Through Fault current at 0.415kV Bus 23208.00 AmpsHV side current due to fault at 0.415 kV bus 913.55 AmpsHV side CT Secondary current due to fault at 0.415kV bus 12.18 AmpsSetting proposed on HV side relay I>> 14.00 AmpsSetting proposed on LV sideACB I>> 6.00
Transformer capacity PT 2500 kVAPrimary Voltage Vp 11 kVSecondary Voltage Vs 0.433 kVTransformer HV side CT details CTHV 150/1Turns Ratio CTRP 150Transformer LV side ACB Rating 4000Percentage Impedance of Transformer Z 6.50%Through Fault current at 0.415 kV Bus as per report 36209 AmpsTransformer HV side current as per name plate 131.22 AmpsRelay drop off Ratio 0.95HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x 131.22/0.95151.94
Transformer HV side CT Secondary Pick up Current Isfl 1.01
Setting Calculation for Distribution Transformers 2.5 MVA
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
1250 kVA
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
Transformer HV side CT Secondary Pick up Current Isfl 1.01IDMT setting at 11 kV side 1Setting proposed on HV side Ip 1Curve Extreme InverseTransformer LV side current as per name plate 3333.53Relay drop off Ratio 0.95LV Pick up Current 1.1 x LV Currrent/ Drop off ratio
=1.1 x 3333.53/0.953859.88
Transformer LV side CT Secondary Pick up Current =3859.88/4000ACB setting for over current 1Setting proposed on LV side Ip 1Through Fault current at 0.415kV Bus 36209.00 AmpsHV side current due to fault at 0.415 kV bus 1425.32 AmpsHV side CT Secondary current due to fault at 0.415kV bus 9.50 AmpsSetting proposed on HV side relay I>> 12.00 AmpsSetting proposed on LV side relay I>> 6
Transformer capacity PT 1250 kVAPrimary Voltage Vp 11 kVSecondary Voltage Vs 0.433 kVTransformer HV side CT details CTHV 100/1Turns Ratio CTRP 100Transformer LV side ACB Rating 2000Percentage Impedance of Transformer Z 5.00% Fault current at 0.415 kV Bus as per report 25029.00 AmpsTransformer HV side current as per name plate 65.61 AmpsRelay drop off Ratio 0.95HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x65.61/0.9575.97
Transformer HV side CT Secondary Pick up Current Isfl 0.76
Setting Calculation for Distribution Transformers 1.25 MVA
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
750 kVA
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
Transformer HV side CT Secondary Pick up Current Isfl 0.76IDMT setting at 11 kV side 0.75Setting proposed on HV side Ip 0.75Curve Extreme l InverseTransformer LV side current as per name plate 1666.76Relay drop off Ratio 0.95LV Pick up Current 1.1 x LV Currrent/ Drop off ratio
=1.1 x1666.76/0.951929.93
Transformer LV side CT Secondary Pick up Current =1929.93/2000ACB setting for over current 0.964615Setting proposed on LV side Ip 1Through Fault current at 0.415kV Bus 25029.00 AmpsHV side current due to fault at 0.415 kV bus 985.23 AmpsHV side CT Secondary current due to fault at 0.415kV bus 9.85 AmpsSetting proposed on HV side relay I>> 12.00 AmpsSetting proposed on LV side relay I>> 6
Transformer capacity PT 750 kVAPrimary Voltage Vp 11 kVSecondary Voltage Vs 0.433 kVTransformer HV side CT details CTHV 100/1Turns Ratio CTRP 100Transformer LV side ACB Rating 1250Percentage Impedance of Transformer Z 5.00% Through Fault current at 0.433 kV Bus 18303.00 AmpsTransformer HV side current as per name plate 39.37 AmpsRelay drop off Ratio 0.95HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x39.37/0.9545.59
Transformer HV side CT Secondary Pick up Current Isfl 0.46
Setting Calculation for Transformers 0.75 MVA
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
1000 kVA1600 A
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
Transformer HV side CT Secondary Pick up Current Isfl 0.46IDMT setting at 11 kV side 0.5Setting proposed on HV side Ip 0.5Curve Extreme InverseTransformer LV side current as per name plate 1000.06Relay drop off Ratio 0.95LV Pick up Current 1.1 x LV Currrent/ Drop off ratio
=1.1 x1000.06/0.951157.96
Transformer LV side CT Secondary Pick up Current =1157/1250ACB setting for over current 0.925616Setting proposed onLV side Ip 0.95Through Fault current at 0.415 kV Bus 18303.00 AmpsHV side current due to fault at 0.415 kV bus 720.47 AmpsHV side CT Secondary current due to fault at 0.415 kV bus 7.20 AmpsSetting proposed on HV side relay I>> 9.00 AmpsSetting proposed on LV side relay I>> 6
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
Transformer capacity PT 1000 kVAPrimary Voltage Vp 6.6 kVSecondary Voltage Vs 0.433 kVTransformer HV side CT details CTHV 150/5Turns Ratio CTRP 30Transformer LV side ACB Rating 1600Percentage Impedance of Transformer Z 5.00%Through Fault current at 0.415 kV Bus 23208 AmpsTransformer HV side current as per name plate 87.48 AmpsRelay drop off Ratio 0.95HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x 87.48/0.95101.29
Transformer HV side CT Secondary Pick up Current Isfl 3.38 Amps
Setting Calculation for Transformers 1 MVA Feeding Screening MCC
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
1000 kVA
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
Transformer HV side CT Secondary Pick up Current Isfl 3.38 AmpsIDMT setting at 6.6 kV side 0.675283281Setting proposed on HV side Ip 0.7Curve Extremel InverseTransformer LV side current as per name plate 1333.41Relay drop off Ratio 0.95LV Pick up Current 1.1 x LV Currrent/ Drop off ratio
=1.1 x1333.41/0.951543.95
Transformer LV side CT Secondary Pick up Current =1543.95/1600ACB setting for over current 0.96496875Setting proposal on ACB 1Through Fault current at 0.415kV Bus 23208.00 AmpsHV side current due to fault at 0.415 kV bus 1522.59 AmpsHV side CT Secondary current due to fault at 0.415kV bus 50.75 AmpsSetting proposed on HV side relay I>> 60 (12) AmpsSetting proposed on LV sideACB I>> 6.00
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
Transformer capacity PT 1000 kVAPrimary Voltage Vp 6.6 kVSecondary Voltage Vs 0.433 kVTransformer HV side CT details CTHV 300/5Turns Ratio CTRP 60Transformer LV side ACB Rating 1600Percentage Impedance of Transformer Z 5.00%Through Fault current at 0.415 kV Bus 21210 AmpsTransformer HV side current as per name plate 87.48 AmpsRelay drop off Ratio 0.95HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x 87.48/0.95101.29
Transformer HV side CT Secondary Pick up Current Isfl 1.69 Amps
Setting Calculation for Transformers 1 MVA Feeding Proportion Mixing MCC
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
300/51000 kVA
433 V
1600 A
1600 kVA
6.6kV
200/51250 kVA
433 V
2000 A
Transformer HV side CT Secondary Pick up Current Isfl 1.69 AmpsIDMT setting at 6.6 kV side 0.337641641Setting proposed on HV side Ip 0.35Curve Extremel InverseTransformer LV side current as per name plate 1333.41Relay drop off Ratio 0.95LV Pick up Current 1.1 x LV Currrent/ Drop off ratio
=1.1 x1333.41/0.951543.95
Transformer LV side CT Secondary Pick up Current =1543.95/1600ACB setting for over current 0.96496875Setting proposal on ACB 1Through Fault current at 0.415kV Bus 21210.00 AmpsHV side current due to fault at 0.415 kV bus 1391.50 AmpsHV side CT Secondary current due to fault at 0.415kV bus 23.19 AmpsSetting proposed on HV side relay I>> 28(5.5) AmpsSetting proposed on LV sideACB I>> 6.00
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
Transformer capacity PT 1600 kVAPrimary Voltage Vp 6.6 kVSecondary Voltage Vs 0.433 kVTransformer HV side CT details CTHV 200/5Turns Ratio CTRP 40Transformer LV side ACB Rating 2500Percentage Impedance of Transformer Z 5.00%Through Fault current at 0.415 kV Bus 25244.00 AmpsTransformer HV side current as per name plate 139.97 AmpsRelay drop off Ratio 0.95HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x139.97/0.95162.07
Transformer HV side CT Secondary Pick up Current Isfl 4.05 Amps
Setting Calculation for Transformers 1.6 MVA Feeding TG/BALLING SYSTEM MCC
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
1250 kVA2000 A
Transformer HV side CT Secondary Pick up Current Isfl 4.05 AmpsIDMT setting at 6.6 kV side 0.810339938Setting proposed on HV side Ip 0.85Curve Extremel InverseTransformer LV side current as per name plate 2133.46Relay drop off Ratio 0.95LV Pick up Current 1.1 x LV Currrent/ Drop off ratio
=1.1 x2133.46/0.952470.32
Transformer LV side CT Secondary Pick up Current =2470/2500ACB setting for over current 0.988128146Setting proposal on ACB 1Through Fault current at 0.415kV Bus 25244.00 AmpsHV side current due to fault at 0.415 kV bus 1656.16 AmpsHV side CT Secondary current due to fault at 0.415kV bus 41.40 AmpsSetting proposed on HV side relay I>> 50(10) AmpsSetting proposed on LV sideACB I>> 6.00
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51250 kVA
433 V
2000 A
Transformer capacity PT 1250 kVAPrimary Voltage Vp 6.6 kVSecondary Voltage Vs 0.433 kVTransformer HV side CT details CTHV 125/1Turns Ratio CTRP 125Transformer LV side ACB Rating 2500Percentage Impedance of Transformer Z 5.00%Through Fault current at 0.415 kV Bus 28226.00 AmpsTransformer HV side current as per name plate 109.35 AmpsRelay drop off Ratio 0.95HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x109.35/0.95126.62
Transformer HV side CT Secondary Pick up Current Isfl 1.01 Amps
Setting Calculation for Transformers 1.25 MVA Feeding ORE C.SYSTEM MCC
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
15000 kVA
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
Transformer HV side CT Secondary Pick up Current Isfl 1.01 AmpsIDMT setting at 6.6 kV side 1Setting proposed on HV side Ip 1Curve Extremel InverseTransformer LV side current as per name plate 1666.76Relay drop off Ratio 0.95LV Pick up Current 1.1 x LV Currrent/ Drop off ratio
=1.1 x1666.76/0.951929.94
Transformer LV side CT Secondary Pick up Current =1929/2500ACB setting for over current 0.771975114Setting proposal on ACB 0.8Through Fault current at 0.415kV Bus 28226.00 AmpsHV side current due to fault at 0.415 kV bus 1851.80 AmpsHV side CT Secondary current due to fault at 0.415kV bus 14.81 AmpsSetting proposed on HV side relay I>> 17.00 AmpsSetting proposed on LV sideACB I>> 4.00
Transformer capacity PT 15000 kVAPrimary Voltage Vp 11 kVSecondary Voltage Vs 6.9 kVTransformer HV side CT details CTHV 800/1Turns Ratio CTRP 800TransformerLV side CT details CTLV 1500/1Turns Ratio 1500Percentage Impedance of Transformer Z 8.35% Fault current at 6.6 kV Bus as per report 4915.00 AmpsTransformer HV side current as per name plate 787.32 AmpsRelay drop off Ratio 0.95HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x 787.32/0.95911.63
Setting Calculation for Transformers 15 MVA
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
125/120000 kVA
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
911.63Transformer HV side CT Secondary Pick up Current Isfl 1.14IDMT setting at 11kV side 1.15Setting proposed on HV side Ip 1.15Curve Normal InverseTransformer LV side current as per name plate 1255.15Relay drop off Ratio 0.95LV Pick up Current 1.1 x LV Currrent/ Drop off ratio
=1.1 x1255.15/0.951453.33
Transformer LV side CT Secondary Pick up Current =1453/1500ACB setting for over current 0.968884708Setting proposed onLV side Ip 1Curve Normal InverseFault current at 6.6 kV Bus as per report,for MINIMUM SOURCE Fault4915.00 AmpsHV side current due to fault at 6.6 kV bus 3083.05 AmpsHV side CT Secondary current due to fault at 6.6 kV bus 3.85 AmpsSetting proposed on HV side relay I>> 5.00Setting proposed on LV side relay I>> 6
Transformer capacity PT 20000 kVAPrimary Voltage Vp 110 kVSecondary Voltage Vs 11 kVTransformer HV side CT details CTHV 125/1Turns Ratio CTRP 125TransformerLV side CT details CTLV 1250/1Turns Ratio 1250Percentage Impedance of Transformer Z 10.00% Fault current at 11 kV Bus as per report 9996 AmpsTransformer HV side current as per name plate 104.98 AmpsRelay drop off Ratio 0.95HV Pick up Current 1.1 x HV Currrent/ Drop off ratio
=1.1 x104.98/0.95121.55
Setting Calculation for Transformer 20 MVA
11kV,
11
125/12000 kVA
433 V
3200
11
75/1000 kVA
433 V
1600 A
11
800/12500 kVA
433 V
4000 A
11
75/1250 kVA
433 V
2000 A
11
100/1750 kVA
433 V
1250 A
11
800/115000 kVA
6.9kV
1500/1
110 kV
125/120000 kVA
11 kV
1250/1
6.6kV
150/51000 kVA
433 V
1600 A
6.6kV
300/51000 kVA
433 V
1600 A
6.6kV
200/51600 kVA
433 V
2500 A
6.6kV
200/51250 kVA
433 V
2000 A
121.55Transformer HV side CT Secondary Pick up Current Isfl 0.97IDMT setting at 110kV side 1Setting proposed on HV side Ip 1Curve Normal InverseTransformer LV side current as per name plate 1049.76Relay drop off Ratio 0.95LV Pick up Current 1.1 x LV Currrent/ Drop off ratio
=1.1 x1049.76/0.951212.04
Transformer LV side CT Secondary Pick up Current =1212.04/1250ACB setting for over current 0.969632Setting proposed onLV side Ip 1Curve Normal InverseThrough Fault current at 11 kV Bus 9996.00 AmpsHV side current due to fault at 11 kV bus 999.60 AmpsHV side CT Secondary current due to fault at 11 kV bus 8.00 AmpsSetting proposed on HV side relay I>> 10.00Setting proposed on LV side relay I>> 3
SETTING DETAILS FORSETTING DETAILS FOR RELAY CONTROL PANEL
110kV SwitchYard -Relay & Control Panel
Relay type Siemens Reyrolle 7SA610
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings are displayed andall others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 150ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime
Line Circuit Breaker
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTL Overcurrent elementis enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 1 150
51-1 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
Normal Inverse ,VeryInverse ,ExtremelyInverse ,Long Inverse
NormalInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.05..3.20 s, oo 1
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrent element isenabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 10 1500
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 1.05
4.2 50-1
4.1 51-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derived Earth Faultelement is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP0.01
0.125 18.75
51N-1 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
Normal Inverse ,VeryInverse ,ExtremelyInverse ,Long Inverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.05..3.20 s, oo 0.5
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earth fault element isenabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP0.01
1.1 165
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 1.45
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
6 Directional Current Protection :676.1 67-1Description Range Setting Prime
67 ElementSelects whether the 51-1 IDMTL Overcurrent element is enabled
Enabled, Disabled Enabled
67 SettingPickup level
0.05, 0.06 ... 2.49, 2.5 0.7 105
67 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
DTL, IEC-NI, IEC-VI,IEC-EI, IEC-LTI, ANSI-MI, ANSI-VI, ANSI-EIIEC-NI IEC-NI
IEC-NI
67 Time Mult (IEC/ANSI)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.025, 0.05 ... 1.575, 1.60.1
Characteristic Angle -179….180 deg -45
6.1 67-1
Description Range Setting Prime67N-1 ElementSelects whether the DTL derived Earth fault element is
Enabled, Disabled Enabled
67N-1 SettingPickup level
0.05, 0.06 ... 49.5, 50 0.06X In 9
Gn 67N-1 DelaySets operate delay time
0, 0.01 ... 14300, 144000.65
Characteristic Angle -179….180 deg -45
Setting name Range Setting 50BF Element Diasabled/Enabled Enabled50BF Setting 0.05..2 0.2 x In 3050BF-1 delay 20..60000 100ms 50BF-2 delay 20..60000 250 ms
Parameter Value (Range) Settings Unit Unom PRIMARY 1.0 .. 1200.0 kV 110 kV Unom Secondary 80..125 110 VCT Primary 10~5000 150 ACT Secondary 1A/5A 1 ASystemStarpoint Solid Earthed
Peterson-CoilIsolated
Solid Earthed
Uph / Udelta 0.10 .. 9.99 1.73Rated Frequency 50/60 Hz 50 Hz
6.2 67N-1
7 Breaker failure Protection -CB Fail Supervision : 50LBB
8 Distance Protection setting 21
Rated Frequency 50/60 Hz 50 HzPhase Seq L1 L2 L3L1 L3 L2 L1 L2 L3Distance Unit km/Miles kmFull scale volt 1.0~1200 110 kVFull scale Current 10~5000 150 ALine Angle 10~89 deg 67.38 degP,Q sign Not reversedReversed not reversedR1 Conductor in ohms per km @ 85 deg C 0.16 ohms/kmX1 Conductor in ohms per km 0.0050~9.5 0.39 ohms/kmc' 0.0~100 0.01 mfd / kmZ1 Moose conductor in ohms per km @ 85 deg C 0.42 ohms/kmR0 Zero seq.Moose conductor in ohms per km @ 85 deg C 0.31 ohms/km
X0 zero seq.Moose conductor in ohms per km 0.0050~9.5 1.30 ohms/km
Z0 Moose conductor in ohms per km @ 85 deg C 1.34 ohms/km
Line length 0.1~1000 5 kmAdj short line 5.22 kmAdj Long line 16.23 kmLine Positive Sequence impedance (mag) 2.10 Ohms
Line Positive Sequence impedance (Phase angle ) 67.38 deg
Line Positive Sequence impedance (mag) sec 0.32LineZero Sequence impedance (mag) 0.0050~9.5 6.70 OhmsLine zero Sequence impedance (Phase angle ) 76.60 degLineZero Sequence impedance (mag)sec 0.0050~9.5 1.01Zone 1 reach impedance setting (mag) 1.68 OhmsZone 1 reach impedance setting (Phase angle) 67.38 degZone 1 reach impedance setting (mag) sec 0.25 OhmsZone 1 reach impedance setting (Phase angle) 67.38 degTime delay Zone 1 0 secCT ratio/VT ratio for impedance Conversion 0.15Zone 2 reach impedance setting (mag) 1.10 OhmsZone 2 reach impedance setting (Phase angle) 67.38 degZone 2 reach impedance setting (mag) sec 0.16 OhmsZone2 reach impedance setting (Phase angle) 67.38 degZone 3 reach impedance setting (mag) 6.83 OhmsZone 3 reach impedance setting (Phase angle) 79.46 degZone 3 reach impedance setting (mag) sec 1.02 OhmsZone3 reach impedance setting (Phase angle) 79.46 degTime delay Zone 2 0.5 secTime delay Zone 3 1 secRe/R1 0.31Xe/X1 0.79Ko 0.73Rm/Ri 0.54Rm/Ri 0.54Xm/Xi 0.59R1 Phase-Phase 0.70X1 Phase-Phase 0.23R2 Phase-Phase 0.79X2 Phase-Phase 0.44R3 Phase-Phase 1.12X3 Phase-Phase 1.24Reverse Resistive reach 0.05Reverse Reactive Reach 0.12
Function Range Setting UnitsConnection of the input V.T.s Y/DELT YVector surge logic 1Ph / 3Ph 3PhΔΘ 2°...22° (EXIT) 6° degVoltage theshold for vector surge measuring U N = 100 V: 5...100
V U N = 230 V:12...230 V U N = 400V: 20...400 V
80 V
Vector Surge Relay CSPC make MRG2Vector Surge Protection
110kV SwitchYard -Relay & Control Panel
Relay type Siemens Reyrolle 7UT612
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings are displayed andall others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 125ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
Transformer Circuit Breaker
1 SYSTEM CONFIG
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTL Overcurrent elementis enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 1 125
51-1 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
Normal Inverse ,VeryInverse ,ExtremelyInverse ,Long Inverse
NormalInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.05..3.20 s, oo 1
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrent element isenabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 10 1250
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.9
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derived Earth Faultelement is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP0.01
0.125 15.625
51N-1 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
Normal Inverse ,VeryInverse ,ExtremelyInverse ,Long Inverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.05..3.20 s, oo 0.5
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earth fault element isenabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP0.01
1.1 137.5
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 1.3
Description Range Setting Prime
5.1 51N-1
5.2 50N-1
6 Differential Protection: 87
5 DERIVED E/F
Description Range Setting PrimeDiff.Prot ON/OFF ONPick up value of differential current I-diff> 0.05..2 I/InO 0.2T I-diff> time delay T I-diff> 0.00..60.00 s 0Pick up value of High set trip I-diff>> 0.5..35 I/InO 8T I-diff> time delay T I-diff>> 0.00..60.00 s 0Slope 1 of tripping charecterstic Slope 1 0.1..0.5 0.3Base point for slope1 of charecterstic Base point 1 0.00..2 I/InO 0Slope 2 of tripping charecterstic Slope 2 0.25..0.95 0.7Base point for slope2 of charecterstic Base point 2 0.00..10 I/InO 2.5Pick up for add on stablisation I Add on stab 2..15 I/InO 4Duration for add on stablisation T Add on stab 2..250 Cycles 15
Setting name Range Setting64R Element Diasabled/Enabled Enabled64R Setting 0.05..2 0.1 x In 12.564R-1 delay 20..60000 100ms
Setting name Range Setting51G Element Diasabled/Enabled Enabled51G Setting 0.05..2 0.15 x In 18.7551G-1 delay 20..60000 500ms
8 RESTRICTED EARTH FAULT PROTECTION 51G
7 RESTRICTED EARTH FAULT PROTECTION 64
110kV SwitchYard -Relay & Control Panel
Relay type Siemens Reyrolle 7UT613
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings are displayed andall others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTsGT HV side CT rated primary 10..50000 A 125A
CT rated secondary 1 A / 5 A 1AGT LV side CT rated primary 10..50000 A 1250A
CT rated secondary 1 A / 5 A 1AGenerator neutral side CT rated primary 10..50000 A 1250A
CT rated secondary 1 A / 5 A 1APTs
PT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimeDiff.Prot ON/OFF ON
Transformer Circuit Breaker overall Differential Protection
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 Differential Protection: 87Description Range Setting PrimeDiff.Prot ON/OFF ONPick up value of differential current I-diff> 0.05..2 I/InO 0.2T I-diff> time delay T I-diff> 0.00..60.00 s 0Pick up value of High set trip I-diff>> 0.5..35 I/InO 8T I-diff> time delay T I-diff>> 0.00..60.00 s 0Slope 1 of tripping charecterstic Slope 1 0.1..0.5 0.3Base point for slope1 of charecterstic Base point 1 0.00..2 I/InO 0Slope 2 of tripping charecterstic Slope 2 0.25..0.95 0.7Base point for slope2 of charecterstic Base point 2 0.00..10 I/InO 2.5Pick up for add on stablisation I Add on stab 2..15 I/InO 4Duration for add on stablisation T Add on stab 2..250 Cycles 15
SETTING DETAILS FORSETTING DETAILS FOR 11kV SWITCH BOARD
11 kV HT LCSS-1 Unit Auxiliary Switch Board
Relay type Siemens Reyrolle 7SJ803
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings aredisplayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 1250ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
Incomer from Generator Transformer
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 1 1250
51-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 0.9
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrentelement is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 7 8750
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.75
4.2 50-1
Description Range Setting Prime
51N-1 ElementSelects whether the 51N-1 IDMTL derivedEarth Fault element is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.1 125
51N-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 0.4
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earthfault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 1 1250
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 1.15s
6 Over Voltage Protection :59Setting name Range Setting Prim Value6.1 59-1 Element 1V Operation OFF, O/V, U/V o/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 120 12000
5.2 50N-1
5 DERIVED E/F 5.1 51N-1
V Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 120 12000V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.03
V Hysteresis 1,2…90 5 V Block Threshold OFF,1,2…5…100 -V O/P Phases Any One, All Any6.2 59 Element 2V Operation OFF, O/V, U/V o/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 126 12600
V Delay 0.00, 0.01…20,20.5…100.0,101.0…600.0
1.5
V Hysteresis 1,2…90 10 V Block Threshold OFF,1,2…5…100 -V O/P Phases Any One, All Any
7 Under Voltage Protection:27Setting name Range Setting Prim Value7.1 27-1 Element 1V Operation OFF, O/V, U/V u/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 99 9900V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.01
V Hysteresis 1,2…90 3 V Block Threshold OFF,1,2…5…100 - V O/P Phases Any One, All Any7.2 27 Element 2V Operation OFF, O/V, U/V u/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 93.5 9350V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.01.5
V Hysteresis 1,2…90 10 V Block Threshold OFF,1,2…5…100 - V O/P Phases Any One, All Any
Description Range Setting Prime
67 ElementSelects whether the 51-1 IDMTL Overcurrentelement is enabled
Enabled, Disabled Enabled
67 SettingPickup level
0.05, 0.06 ... 2.49, 2.5 0.9 1125
67 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-MI, ANSI-VI, ANSI-EIIEC-NI IEC-NI
IEC-NI
67 Time Mult (IEC/ANSI)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.025, 0.05 ... 1.575, 1.6 0.12
8 Directional Current Protection :678.1 67-1
67 Time Mult (IEC/ANSI)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.025, 0.05 ... 1.575, 1.6 0.12
Characteristic Angle -179….180 deg -45
Description Range Setting Prime67N-1 ElementSelects whether the DTL derived Earth faultelement is enabled
Enabled, Disabled Enabled
67N-1 SettingPickup level
0.05, 0.06 ... 49.5, 50 0.08X In 187.5
Gn 67N-1 DelaySets operate delay time
0, 0.01 ... 14300, 14400 0.5
Characteristic Angle -179….180 deg -45
Setting name Range Setting 50BF Element Diasabled/Enabled Enabled50BF Setting 0.05..2 0.2 x In 25050BF-1 delay 20..60000 100ms 50BF-2 delay 20..60000 250 ms
9 Breaker failure Protection -CB Fail Supervision : 50LBB
8.2 67N-1
Relay type Siemens Reyrolle 7SJ803
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from
50, 60 50HzSetting DependenciesWhen enabled only active settings are
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 1250ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTL
Enabled, Disabled Enabled51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.95 1187.551-1 CharSelects characteristic curve to be IEC or
Normal Inverse ,Very Inverse,Extremely Inverse ,Long
Normal Inverse-IEC51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and0.05..3.20 s, oo 0.18
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrent
Enabled, Disabled Enabled50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 4 5000
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
4.2 50-1
Incomer from Turbo Generator 1
1 SYSTEM CONFIG
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 4 500050-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.7
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derived
Enabled, Disabled Enabled51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.08 10051N-1 CharSelects characteristic curve to be IEC or
Normal Inverse ,Very Inverse,Extremely Inverse ,Long
direct51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC and
0.05..3.20 s, oo 1.8
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earth
Enabled, Disabled Enabled50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 1.8 225050N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.016 Over Voltage Protection :59Setting name Range Setting Prim Value6.1 59-1 Element 1V Operation OFF, O/V, U/V o/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 120 12000V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.03
V Hysteresis 1,2…90 5 V Block Threshold OFF,1,2…5…100 -V O/P Phases Any One, All Any6.2 59 Element 2V Operation OFF, O/V, U/V o/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 126 12600V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.01.5
V Hysteresis 1,2…90 10 V Block Threshold OFF,1,2…5…100 -V O/P Phases Any One, All Any7 Under Voltage Protection:27
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
7 Under Voltage Protection:27Setting name Range Setting Prim Value7.1 27-1 Element 1V Operation OFF, O/V, U/V u/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 99 9900V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.03
V Hysteresis 1,2…90 5 V Block Threshold OFF,1,2…5…100 - V O/P Phases Any One, All Any
7.2 27 Element 2V Operation OFF, O/V, U/V u/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 93.5 9350V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.01.5
V Hysteresis 1,2…90 10 V Block Threshold OFF,1,2…5…100 - V O/P Phases Any One, All Any
Description Range Setting Prime 67 ElementSelects whether the 51-1 IDMTL Overcurrent
Enabled, Disabled Enabled67 SettingPickup level
0.05, 0.06 ... 2.49, 2.5 0.9 112567 CharSelects characteristic curve to be IEC or
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI67 Time Mult (IEC/ANSI)Time multiplier (applicable to IEC and
0.025, 0.05 ... 1.575, 1.6 0.12Characteristic Angle -179….180 deg -45
Description Range Setting Prime67N-1 ElementSelects whether the DTL derived Earth fault
Enabled, Disabled Enabled67N-1 SettingPickup level
0.05, 0.06 ... 49.5, 50 0.08 187.5Gn 67N-1 DelaySets operate delay time
0, 0.01 ... 14300, 14400 0.5Characteristic Angle -179….180 deg -45
Setting name Range Setting 50BF Element Diasabled/Enabled Enabled50BF Setting 0.05..2 0.2 x In 25050BF-1 delay 20..60000 100ms 50BF-2 delay 20..60000 250 ms
8 Directional Current Protection :67
9 Breaker failure Protection -CB Fail Supervision : 50LBB
8.1 67-1
8.2 67N-1
Relay type Siemens Reyrolle 7SJ803
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from
50, 60 50HzSetting DependenciesWhen enabled only active settings are
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 300ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTL
Enabled, Disabled Enabled51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.9 27051-1 CharSelects characteristic curve to be IEC or
Normal Inverse ,Very Inverse,Extremely Inverse ,Long
Normal Inverse-IEC51-1 Time Mult (IEC/ANSI) (Tp)
Time multiplier (applicable to IEC and0.05..3.20 s, oo 0.18
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrent
Enabled, Disabled Enabled50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 4 1200
4.1 51-1
4.2 50-1
Incomer from Turbo Generator 2
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 4 120050-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.7
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derived
Enabled, Disabled Enabled51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.08 10051N-1 CharSelects characteristic curve to be IEC or
Normal Inverse ,Very Inverse,Extremely Inverse ,Long
Direct51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC and
0.05..3.20 s, oo 1.8
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earth
Enabled, Disabled Enabled50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 3.5 437550N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.016 Over Voltage Protection :59Setting name Range Setting Prim Value6.1 59-1 Element 1V Operation OFF, O/V, U/V o/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 120 12000V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.03
V Hysteresis 1,2…90 5 V Block Threshold OFF,1,2…5…100 -V O/P Phases Any One, All Any6.2 59 Element 2V Operation OFF, O/V, U/V o/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 126 12600V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.01.5
V Hysteresis 1,2…90 10 V Block Threshold OFF,1,2…5…100 -V O/P Phases Any One, All Any7 Under Voltage Protection:27
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
7 Under Voltage Protection:27Setting name Range Setting Prim Value7.1 27-1 Element 1V Operation OFF, O/V, U/V u/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 99 9900V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.03
V Hysteresis 1,2…90 5 V Block Threshold OFF,1,2…5…100 - V O/P Phases Any One, All Any
7.2 27 Element 2V Operation OFF, O/V, U/V u/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 93.5 9350V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.01.5
V Hysteresis 1,2…90 10 V Block Threshold OFF,1,2…5…100 - V O/P Phases Any One, All Any
Description Range Setting Prime 67 ElementSelects whether the 51-1 IDMTL Overcurrent
Enabled, Disabled Enabled67 SettingPickup level
0.05, 0.06 ... 2.49, 2.5 0.9 27067 CharSelects characteristic curve to be IEC or
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-MI, ANSI-VI, ANSI-EI
IEC-NI67 Time Mult (IEC/ANSI)Time multiplier (applicable to IEC and
0.025, 0.05 ... 1.575, 1.6 0.12Characteristic Angle -179….180 deg -45
Description Range Setting Prime67N-1 ElementSelects whether the DTL derived Earth fault
Enabled, Disabled Enabled67N-1 SettingPickup level
0.05, 0.06 ... 49.5, 50 0.08 45Gn 67N-1 DelaySets operate delay time
0, 0.01 ... 14300, 14400 0.5Characteristic Angle -179….180 deg -45
Setting name Range Setting 50BF Element Diasabled/Enabled Enabled50BF Setting 0.05..2 0.2 x In 6050BF-1 delay 20..60000 100ms 50BF-2 delay 20..60000 250 ms
8 Directional Current Protection :678.1 67-1
8.2 67N-1
9 Breaker failure Protection -CB Fail Supervision : 50LBB
Relay type Siemens Reyrolle 7SJ600
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings aredisplayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 100ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
2 CT/VT CONFIG
Transformer Feeder 750 kVA STP & AFBC FDR 1 & 2 Panel Nos 5, 14&15
1 SYSTEM CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.5 50
51-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 1
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrentelement is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 10 1000
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.05
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derivedEarth Fault element is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.1 10
51N-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 0.1
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earthfault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 1 100
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.25s
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
Relay type Siemens Reyrolle 7SJ600
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings aredisplayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 125ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
4 CURRENT PROTECTION
Transformer Feeder LCSS 1 2000 kVA FDR 1 & 2 Panel Nos 4 & 11
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4.1 51-1
51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 1 125
51-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 1
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrentelement is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 13 1625
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.05
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derivedEarth Fault element is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.1 12.5
51N-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 0.3
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earthfault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 0.8 100
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.25s
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
Relay type Siemens Reyrolle 7SJ600
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings aredisplayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 100ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
Transformer Feeder RMP3 1000 kVA Panel Nos
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.6 60
51-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 1
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrentelement is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 10.5 1050
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.05
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derivedEarth Fault element is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.08 8
51N-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 0.3
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earthfault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 0.6 60
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.25s
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
Relay type Siemens Reyrolle 7SJ600
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings aredisplayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 100ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
Transformer Feeder 1250 kVA KILN 1&2 Panel No 2
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.75 75
51-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 1
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrentelement is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 12 1200
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.05
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derivedEarth Fault element is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.08 8
51N-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 0.3
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earthfault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 0.8 80
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.25s
5.1 51N-1 5 DERIVED E/F
5.2 50N-1
Relay type Siemens Reyrolle 7SJ600
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings aredisplayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 800ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
Transformer Feeder 15000 kVA Pellet Plant Panel No 3
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 1.15 920
51-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 0.8
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrentelement is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 7 5600
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.6
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derivedEarth Fault element is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.125 12.5
51N-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 0.4
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earthfault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 1 800
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 1
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
Relay type Siemens Reyrolle 7SJ600
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings aredisplayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 150ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
4.1 51-1
Transformer Feeder KILN 3 2500 kVA Panel No13
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION
51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 1 150
51-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 1
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrentelement is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 12 1800
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.05
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derivedEarth Fault element is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.125 18.75
51N-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 0.3
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earthfault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 0.9 135
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.25s
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
11 kV HT LBSS-1 Switch Board
Relay type Siemens Reyrolle 7UT612
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings aredisplayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 800ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 11000 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
Inter Panel Incomer from Main Panel for 15 MVA Transformer standalone Panel
51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 1.15 920
51-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 0.65
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrentelement is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 6 4800
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.52
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derivedEarth Fault element is enabled
Enabled, Disabled Enabled
4.2 50-1
5 DERIVED E/F 5.1 51N-1
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.11 88
51N-1 CharSelects characteristic curve to be IEC orANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC andANSI curves but not DTL selection)
0.05..3.20 s, oo 0.35
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earthfault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 0.95 760
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.9s
Description Range Setting PrimeDiff.Prot ON/OFF ONPick up value of differential current I-diff> 0.05..2 I/InO 0.2T I-diff> time delay T I-diff> 0.00..60.00 s 0Pick up value of High set trip I-diff>> 0.5..35 I/InO 8T I-diff> time delay T I-diff>> 0.00..60.00 s 0Slope 1 of tripping charecterstic Slope 1 0.1..0.5 0.3
Base point for slope1 of charectersticBase point 1
0.00..2 I/InO 0
Slope 2 of tripping charecterstic Slope 2 0.25..0.95 0.7
5.2 50N-1
6 Differential Protection: 87
Slope 2 of tripping charecterstic Slope 2 0.25..0.95 0.7
Base point for slope2 of charectersticBase point 2
0.00..10 I/InO 2.5
Pick up for add on stablisation I Add onstab
2..15 I/InO 4
Duration for add on stablisation T Add onstab
2..250 Cycles 15
SETTING DETAILS FORSETTING DETAILS FOR 6.6 kV SWITCH BOARDS
6.6 kV HV Distribution Board
Relay type ABB REF615
Description Range Setting PrimeSystem FrequencySelects the Power SystemFrequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settingsare displayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 600ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 6600 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
4.1 51-1
Incomers 1 and 2 from Siemens make 6.6kV Board
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION
51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.9 540
51-1 CharSelects characteristic curve to beIEC or ANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IECand ANSI curves but not DTLselection)
0.05..3.20 s, oo 0.7
Description Range Setting Prime50-1 ElementSelects whether the INST/DTLOvercurrent element is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 8 4800
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.15
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTLderived Earth Fault element isenabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.1 60
51N-1 CharSelects characteristic curve to beIEC or ANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IECand ANSI curves but not DTLselection)
0.05..3.20 s, oo 0.2
Description Range Setting Prime
50N-1 ElementSelects whether the DTL derivedEarth fault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 0.8 480
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.4
6 Over Voltage Protection :59Setting name Range Setting Prim Value6.1 59-1 Element 1V Operation OFF, O/V, U/V o/vV Setting (Ph-N) Gn V Setting (Ph-Ph)
5.0, 5.5…80.0…200.0 120 7200
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
V Setting (Ph-N) Gn V Setting (Ph-Ph)
5.0, 5.5…80.0…200.0 120 7200V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.03
V Hysteresis 1,2…90 5 V Block Threshold OFF,1,2…5…100 -V O/P Phases Any One, All Any6.2 59 Element 2V Operation OFF, O/V, U/V o/vV Setting (Ph-N) Gn V Setting (Ph-Ph)
5.0, 5.5…80.0…200.0 126 7560V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.01.5
V Hysteresis 1,2…90 10 V Block Threshold OFF,1,2…5…100 -V O/P Phases Any One, All Any7 Under Voltage Protection:27Setting name Range Setting Prim Value7.1 27-1 Element 1V Operation OFF, O/V, U/V u/vV Setting (Ph-N) Gn V Setting (Ph-Ph)
5.0, 5.5…80.0…200.0 99 5940V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.01
V Hysteresis 1,2…90 3 V Block Threshold OFF,1,2…5…100 - V O/P Phases Any One, All Any
7.2 27 Element 2V Operation OFF, O/V, U/V u/vV Setting (Ph-N) Gn V Setting (Ph-Ph)
5.0, 5.5…80.0…200.0 93.5 5610V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.01.5
V Hysteresis 1,2…90 10 V Block Threshold OFF,1,2…5…100 - V O/P Phases Any One, All Any
Setting name Range Setting 50BF Element Diasabled/Enabled Enabled50BF Setting 0.05..2 0.2 x In 25050BF-1 delay 20..60000 100ms 50BF-2 delay 20..60000 250 ms
8 Breaker failure Protection -CB Fail Supervision : 50LBB
Relay type ABB REF610
Description Range Setting PrimeSystem FrequencySelects the Power SystemFrequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settingsare displayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 600ACT rated secondary 1 A / 5 A 1A
PTsPT rated primary 0~132000 V 6600 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.9 540
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
Buscoupler panel
1 SYSTEM CONFIG
2 CT/VT CONFIG
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.9 540
51-1 CharSelects characteristic curve to beIEC or ANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IECand ANSI curves but not DTLselection)
0.05..3.20 s, oo 0.7
Description Range Setting Prime50-1 ElementSelects whether the INST/DTLOvercurrent element is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 8 4800
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.15
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTLderived Earth Fault element isenabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.1 60
51N-1 CharSelects characteristic curve to beIEC or ANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IECand ANSI curves but not DTLselection)
0.05..3.20 s, oo 0.2
Description Range Setting Prime50N-1 ElementSelects whether the DTL derivedEarth fault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 0.8 480
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.4
5.1 51N-1
5.2 50N-1
5 DERIVED E/F
Relay type ABB REF 610
Description Range Setting PrimeSystem FrequencySelects the Power SystemFrequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settingsare displayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 200ACT rated secondary 1 A / 5 A 5A
PTsPT rated primary 0~132000 V 6600 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.85 170
4.1 51-1
Transformer Feeder 1600 kVA TG FDR1 &2 Panels No__& __
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.85 170
51-1 CharSelects characteristic curve to beIEC or ANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IECand ANSI curves but not DTLselection)
0.05..3.20 s, oo 1
Description Range Setting Prime50-1 ElementSelects whether the INST/DTLOvercurrent element is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 10 2000
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.05
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTLderived Earth Fault element isenabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.08 16
51N-1 CharSelects characteristic curve to beIEC or ANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IECand ANSI curves but not DTLselection)
0.05..3.20 s, oo 0.1
Description Range Setting Prime50N-1 ElementSelects whether the DTL derivedEarth fault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 0.8 160
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.25s
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
Relay type ABB REF 610
Description Range Setting PrimeSystem FrequencySelects the Power SystemFrequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settingsare displayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 200ACT rated secondary 1 A / 5 A 5A
PTsPT rated primary 0~132000 V 6600 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.85 170
Transformer Feeder 1600 kVA BALLING SYSTEM FDR1 &2 Panels No__& __
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.85 170
51-1 CharSelects characteristic curve to beIEC or ANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IECand ANSI curves but not DTLselection)
0.05..3.20 s, oo 1
Description Range Setting Prime50-1 ElementSelects whether the INST/DTLOvercurrent element is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 10 2000
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.05
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTLderived Earth Fault element isenabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.08 16
51N-1 CharSelects characteristic curve to beIEC or ANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IECand ANSI curves but not DTLselection)
0.05..3.20 s, oo 0.1
Description Range Setting Prime50N-1 ElementSelects whether the DTL derivedEarth fault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 0.8 160
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.25s
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
Relay type ABB REF 610
Description Range Setting PrimeSystem FrequencySelects the Power SystemFrequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settingsare displayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 150ACT rated secondary 1 A / 5 A 5A
PTsPT rated primary 0~132000 V 6600 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.7 105
Transformer Feeder 1000 kVA SCREENING MCC FDR 1 &2 Panels No__& __
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.7 105
51-1 CharSelects characteristic curve to beIEC or ANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IECand ANSI curves but not DTLselection)
0.05..3.20 s, oo 1
Description Range Setting Prime50-1 ElementSelects whether the INST/DTLOvercurrent element is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 12 1800
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.05
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTLderived Earth Fault element isenabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.1 15
51N-1 CharSelects characteristic curve to beIEC or ANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IECand ANSI curves but not DTLselection)
0.05..3.20 s, oo 0.1
Description Range Setting Prime50N-1 ElementSelects whether the DTL derivedEarth fault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 0.9 135
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.25s
5.2 50N-1
5 DERIVED E/F 5.1 51N-1
Relay type ABB REF 610
Description Range Setting PrimeSystem FrequencySelects the Power SystemFrequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settingsare displayed and all others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 300ACT rated secondary 1 A / 5 A 5A
PTsPT rated primary 0~132000 V 6600 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTLOvercurrent element is enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.35 105
Transformer Feeder 1000 kVA PROPORTION & MIXING MCC FDR1 &2 Panels No__& __
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.35 105
51-1 CharSelects characteristic curve to beIEC or ANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IECand ANSI curves but not DTLselection)
0.05..3.20 s, oo 1
Description Range Setting Prime50-1 ElementSelects whether the INST/DTLOvercurrent element is enabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 6 1800
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.05
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTLderived Earth Fault element isenabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.05 15
51N-1 CharSelects characteristic curve to beIEC or ANSI IDMTL or DTL
Normal Inverse ,Very Inverse,Extremely Inverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IECand ANSI curves but not DTLselection)
0.05..3.20 s, oo 0.1
Description Range Setting Prime50N-1 ElementSelects whether the DTL derivedEarth fault element is enabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 0.45 135
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.25s
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
Relay type ABB REF 615
Description Range Setting PrimeSystem FrequencySelects the Power System
50, 60 50HzSetting DependenciesWhen enabled only active settings
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 150ACT rated secondary 1 A / 5 A 5A
PTsPT rated primary 0~132000 V 6600 VPT rated Secondary 110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTL
Enabled, Disabled Enabled51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP 0.1 0.4 6051-1 CharSelects characteristic curve to be
Normal Inverse ,Very Inverse,Extremely Inverse ,Long
Normal Inverse51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC
0.05..3.20 s, oo 0.2
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL
Enabled, Disabled Enabled50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 12 1800
1 SYSTEM CONFIG
Capacitor Feeder 600 kVAr FDR 1 &2 Panels No__& __
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
4.2 50-1
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP 0.1 12 180050-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.05
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL
Enabled, Disabled Enabled51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP 0.01 0.05 7.551N-1 CharSelects characteristic curve to be
Normal Inverse ,Very Inverse,Extremely Inverse ,Long
Normal Inverse51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC
0.05..3.20 s, oo 0.2
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived
Enabled, Disabled Enabled50N-1 Setting (IE>>)Pickup level
0.05..25.00 A STEP 0.01 0.5 7550N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.25s 6 OVER VOLTAGE PROTECTION :59Setting name Range Setting Prim Value
V Operation OFF, O/V, U/V o/vV Setting (Ph-N) Gn V Setting (Ph-Ph)
5.0, 5.5…80.0…200.0 126.5 7590 V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.01
V Hysteresis 1,2…90 5 V Block Threshold OFF,1,2…5…100 - V O/P Phases Any One, All Any
V Operation OFF, O/V, U/V o/vV Setting (Ph-N) Gn V Setting (Ph-Ph)
5.0, 5.5…80.0…200.0 132 7920 V Delay 0.00, 0.01…20,20.5…
100.0,101.0…600.00.5
V Hysteresis 1,2…90 10 V Block Threshold OFF,1,2…5…100 - V O/P Phases Any One, All Any
6.1 59-1 Element 1
6.2 59 Element 2
5.1 51N-1
5.2 50N-1
5 DERIVED E/F
7 UNBALANCE PROTECTION : 46Parameter Value (Range) Set Value Set Units
Current Set I2> 0.04 to 0.8 In, STEP 0.01 0.1 xInTime delay 0.02 to 99.9, STEP 0.1 1 sCurrent Set I2>> 0.04 to 0.8 In, STEP 0.01 0.2 xInTime Multiple setting ( TMS) I2>> 0.2 to 2, STEP 0.1 1
Setting name Range Setting 59N Element Diasabled/Enabled Enabled 59N Element setting 1.8 V to 200 V in steps of 0.1 V 10 Volts 59 N Element Delay 0.04 to 320 sec 1 sec
8 NEUTRAL VOLTAGE DISPLACEMENT PROTECTION : 59N
Size Value unitsPower 315 kWRated voltage 6.6 kVMotor rated current IA 32.87 AMax. starting current (at 100 % Vn) 6X IA
Starting time (at 100% Vn 1.7 secStarting time (at 80% Vn 3.2 secHeating time constant 45 minCooling time constant at standstill 240 minMax. continuous thermal rating current 34.5135 AMax. blocked rotor time HOT 10 secMax. blocked rotor time COLD 20 secLocked rotor Current 197.22 APermissible max.accelerating time (WITH LOAD ) 1.7 sec
Parameter Value Unit
CurrentTransformer rated current,phase primary 100 ATransformer rated current, phase secondary 1 ACore Balance CurrentTransformer rated current,phase primary 50 ATransformer rated current, earth secondary 1 A Thermal replica (ANSI 49)Parameter Value (Range) Step Set ValueThermal current threshold Iθ> 0.2 to 1.5 x In 0.01 0.35Trip thermal threshold Set to 100%Thermal Alarm stage: 20 to 100% 1.00% 80%Reset ratio for Thermal trip 30 to 99% 1.00% 70%Tripping time 0.1 to 50 s 0.1 2
Motor Feeders 315kW Panel Nos 1 &17 Relay: ABB REM 6151. Available motor data ANTI HEAT FAN 1 &2
General power system data
Tripping time 0.1 to 50 s 0.1 2Io> (Earth Fault) (ANSI 50N/51N)Parameter Value (Range) Step Set ValueCurrent set 0.002 to 1.0 0.01 0.1Time delay 0-100 sec 0.01 0.05
Short Circuit Protection (ANSI 50/51)Parameter Value (Range) Step Set ValueCurrent set I>> 0.5 to 40 1 2.7Time delay t>> 0-150 0.1 0.05Current set I> 0.1 to 25 0.1 0.4Time delay t> ( tms) 0.1 -3.2 0.1 2.7Curve IEC-NI,IEC-EI,IEC-VI IEC-VIUnbalance Protection ( ANSI 46)Parameter Value (Range) Step Set ValueCurrent Set I2> 0.04 to 0.8 In 0.01 0.1Time delay 0.02 to 99.9 0.1 1Current Set I2>> 0.04 to 0.8 In 0.01 0.2Time Multiple setting ( TMS) I2>> 0.2 to 2 0.1 1Ph:AS (Load Assymetry) (ANSi 47)Parameter Value (Range) Step Set ValueCurrent set 15 to 50% 1 15Time delay 0.02 to 99.9 0.1 1Number of permitted starts (ANSI 66)Parameter Value (Range) Step Set ValueNumber of Cold Starts 0-5 1 3Number of Hot Starts 0-5 1 2T reference 10-120 mins 5 60Restart Inhibition time 1-120 mins 1 20Time between 2 Start ups 1-120 mins 1 20Locked Rotor Protection ( ANSI 51LR/50s)Current set 0.5 to 5 In 0.01 2Time Delay for prolonged start: 1 to 60 s 1 4
Size Value unitsPower 1000 kWRated voltage 6.6 kVMotor rated current IA 105.39 AMax. starting current (at 100 % Vn) 6X IA
Starting time (at 100% Vn 1.7 secStarting time (at 80% Vn 3.2 secHeating time constant 45 minCooling time constant at standstill 240 minMax. continuous thermal rating current 110.6595 AMax. blocked rotor time HOT 10 secMax. blocked rotor time COLD 20 secLocked rotor Current 632.34 APermissible max.accelerating time (WITH LOAD ) 1.7 sec
Parameter Value Unit
CurrentTransformer rated current,phase primary 150 ATransformer rated current, phase secondary 1 ACore Balance CurrentTransformer rated current,phase primary 50 ATransformer rated current, earth secondary 1 A Thermal replica (ANSI 49)Parameter Value (Range) Step Set ValueThermal current threshold Iθ> 0.2 to 1.5 x In 0.01 0.75Trip thermal threshold Set to 100%Thermal Alarm stage: 20 to 100% 1.00% 80%Reset ratio for Thermal trip 30 to 99% 1.00% 70%Tripping time 0.1 to 50 s 0.1 2
1. Available motor data ID FAN 1
General power system data
Motor Feeders 1000kW Panel Nos 1 &17 Relay: ABB REM 615
Tripping time 0.1 to 50 s 0.1 2Io> (Earth Fault) (ANSI 50N/51N)Parameter Value (Range) Step Set ValueCurrent set 0.002 to 1.0 0.01 0.1Time delay 0-100 sec 0.01 0.05Short Circuit Protection (ANSI 50/51)
Parameter Value (Range) Step Set ValueCurrent set I>> 0.5 to 40 1 5.5Time delay t>> 0-150 0.1 0.05Current set I> 0.1 to 25 0.1 0.77Time delay t> ( tms) 0.1 -3.2 0.1 3Curve IEC-NI,IEC-EI,IEC-VI IEC-VIUnbalance Protection ( ANSI 46)Parameter Value (Range) Step Set ValueCurrent Set I2> 0.04 to 0.8 In 0.01 0.1Time delay 0.02 to 99.9 0.1 1Current Set I2>> 0.04 to 0.8 In 0.01 0.2Time Multiple setting ( TMS) I2>> 0.2 to 2 0.1 1Ph:AS (Load Assymetry) (ANSi 47)Parameter Value (Range) Step Set ValueCurrent set 15 to 50% 1 15Time delay 0.02 to 99.9 0.1 1Number of permitted starts (ANSI 66)Parameter Value (Range) Step Set ValueNumber of Cold Starts 0-5 1 3Number of Hot Starts 0-5 1 2T reference 10-120 mins 5 60Restart Inhibition time 1-120 mins 1 20Time between 2 Start ups 1-120 mins 1 20Locked Rotor Protection ( ANSI 51LR/50s)Current set 0.5 to 5 In 0.01 4.5Time Delay for prolonged start: 1 to 60 s 1 4
6.6 kV HT LBSS-1 Switch Board
Relay type Siemens Reyrolle 7SJ803
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings are displayed andall others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 1500ACT rated secondary1 A / 5 A 1A
PTsPT rated primary 0~132000 V 6600 VPT rated Secondary110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled
Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTL Overcurrent elementis enabled
Enabled, Disabled Enabled
Incomer from 15 MVA Transformer
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
51-1 ElementSelects whether the 51-1 IDMTL Overcurrent elementis enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP0.1
1 1500
51-1 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
Normal Inverse,Very Inverse,ExtremelyInverse ,LongInverse
NormalInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.05..3.20 s, oo 0.5
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrent element isenabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP0.1
4.5 6750
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.45
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derived Earth Faultelement is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP0.01
0.08 120
51N-1 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
Normal Inverse,Very Inverse,ExtremelyInverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.05..3.20 s, oo 0.35
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earth fault element isenabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 ASTEP 0.01
0.8 1200
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.7
6 Over Voltage Protection :59Setting name Range Setting Prim Value6.1 59-1 Element 1V Operation OFF, O/V, U/V o/v
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
V Operation OFF, O/V, U/V o/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 120 7200V Delay 0.00,
0.01…20,20.5…100.0,101.0…600.0
3
V Hysteresis 1,2…90 5 V Block Threshold OFF,1,2…5…100 -V O/P Phases Any One, All Any6.2 59 Element 2V Operation OFF, O/V, U/V o/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 126 7560V Delay 0.00,
0.01…20,20.5…100.0,101.0…600.0
1.5
V Hysteresis 1,2…90 10 V Block Threshold OFF,1,2…5…100 -V O/P Phases Any One, All Any
7 Under Voltage Protection:27Setting name Range Setting Prim Value7.1 27-1 Element 1V Operation OFF, O/V, U/V u/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 99 5940V Delay 0.00,
0.01…20,20.5…100.0,101.0…600.0
1
V Hysteresis 1,2…90 3 V Block Threshold OFF,1,2…5…100 - V O/P Phases Any One, All Any7.2 27 Element 2V Operation OFF, O/V, U/V u/vV Setting (Ph-N) Gn V Setting (Ph-Ph) 5.0, 5.5…80.0…200.0 93.5 5610V Delay 0.00,
0.01…20,20.5…100.0,101.0…600.0
1.5
V Hysteresis 1,2…90 10 V Block Threshold OFF,1,2…5…100 - V O/P Phases Any One, All Any
Setting name Range Setting 50BF Element Diasabled/Enabled Enabled50BF Setting 0.05..2 0.2 x In 25050BF-1 delay 20..60000 100ms 50BF-2 delay 20..60000 250 ms
Setting name Range Setting64R Element Diasabled/Enabled Enabled
8 Breaker failure Protection -CB Fail Supervision : 50LBB
9 RESTRICTED EARTH FAULT PROTECTION 64
64R Element Diasabled/Enabled Enabled64R Setting 0.05..2 0.1 x In 15064R-1 delay 20..60000 100ms
Setting name Range Setting51G Element Diasabled/Enabled Enabled51G Setting 0.05..2 0.15 x In 1551G-1 delay 20..60000 500ms
10 RESTRICTED EARTH FAULT PROTECTION 51G
Relay type Siemens Reyrolle 7SJ600
Description Range Setting Prime
System FrequencySelects the Power System Frequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings are displayed andall others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 125ACT rated secondary1 A / 5 A 1A
PTsPT rated primary 0~132000 V 6600 VPT rated Secondary110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTL Overcurrent elementis enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP0.1
1 125
4.1 51-1
Transformer Feeder 1250 kVA LCSS1 ,LCSS3& Spare Panels No 2,3,6,14 &15
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP0.1
1 125
51-1 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
Normal Inverse,Very Inverse,ExtremelyInverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.05..3.20 s, oo 1
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrent element isenabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP0.1
17 2550
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.05
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derived Earth Faultelement is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP0.01
0.1 12.5
51N-1 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
Normal Inverse,Very Inverse,ExtremelyInverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.05..3.20 s, oo 0.3
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earth fault element isenabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 ASTEP 0.01
1 125
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.25s
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
Relay type Siemens Reyrolle 7SJ600
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings are displayed andall others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 600ACT rated secondary1 A / 5 A 1A
PTsPT rated primary 0~132000 V 6600 VPT rated Secondary110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTL Overcurrent elementis enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP0.1
1 600
Feeders LBDS1& Spare Panels No 4,13 &16
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP0.1
1 600
51-1 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
Normal Inverse,Very Inverse,ExtremelyInverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.05..3.20 s, oo 0.7
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrent element isenabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP0.1
10 6000
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.3
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derived Earth Faultelement is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP0.01
0.125 75
51N-1 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
Normal Inverse,Very Inverse,ExtremelyInverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.05..3.20 s, oo 0.3
Description Range Setting Prime50N-1 ElementSelects whether the DTL derived Earth fault element isenabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 ASTEP 0.01
0.9 540
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.55s
5 DERIVED E/F 5.1 51N-1
5.2 50N-1
Relay type Siemens Reyrolle 7SJ600
Description Range Setting PrimeSystem FrequencySelects the Power System Frequency from 50 or 60 Hz
50, 60 50Hz
Setting DependenciesWhen enabled only active settings are displayed andall others hidden
Enabled, Disabled Enabled
Description Range Setting PrimeCTs
CT rated primary 10..50000 A 750 ACT rated secondary1 A / 5 A 1A
PTsPT rated primary 0~132000 V 6600 VPT rated Secondary110…230 110
Description Range Setting PrimePhase Overcurrent 50/51 Enabled, Disabled Enabled Derived E/F 50N/51N Enabled, Disabled Enabled
Description Range Setting Prime51-1 ElementSelects whether the 51-1 IDMTL Overcurrent elementis enabled
Enabled, Disabled Enabled
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP0.1
1 750
Feeders Ore Benefl Plant LBDS2 Panels No 5 &12
1 SYSTEM CONFIG
2 CT/VT CONFIG
3 FUNCTION CONFIG
4 CURRENT PROTECTION 4.1 51-1
51-1 Setting (Ip)Pickup level
0.1..4.00 A STEP0.1
1 750
51-1 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
Normal Inverse,Very Inverse,ExtremelyInverse ,LongInverse
ExtremelyInverse-IEC
51-1 Time Mult (IEC/ANSI) (Tp)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.05..3.20 s, oo 0.6
Description Range Setting Prime50-1 ElementSelects whether the INST/DTL Overcurrent element isenabled
Enabled, Disabled Enabled
50-1 Setting (I>>)Pickup level
0.1..25.00 A STEP0.1
8 6000
50-1 Delay (T-I>>)Sets operate delay time
0.00..60.00 s 0.3
4.2 50-1
Description Range Setting Prime51N-1 ElementSelects whether the 51N-1 IDMTL derived Earth Faultelement is enabled
Enabled, Disabled Enabled
51N-1 Setting (IEp)Pickup level
0.05..4.00 A STEP0.01
0.08 60
51N-1 CharSelects characteristic curve to be IEC or ANSI IDMTLor DTL
Normal Inverse,Very Inverse,ExtremelyInverse ,LongInverse
Normal Inverse
51N-1 Time Mult (IEC/ANSI) (TEp)Time multiplier (applicable to IEC and ANSI curves butnot DTL selection)
0.05..3.20 s, oo 0.3
Description Range Setting Prime
50N-1 ElementSelects whether the DTL derived Earth fault element isenabled
Enabled, Disabled Enabled
50N-1 Setting (IE>>)Pickup level
0.05..25.00 ASTEP 0.01
0.8 600
50N-1 Delay (TE>>)Sets operate delay time
0.00..60.00 s 0.55
5.1 51N-1
5.2 50N-1
5 DERIVED E/F
Size Value unitsPower 2600 kWRated voltage 6.6 kVMotor rated current IA 294 AMax. starting current (at 100 % Vn) 6X IA
Starting time (at 100% Vn 1.7 secStarting time (at 80% Vn 3.2 secHeating time constant 45 minCooling time constant at standstill 240 minMax. continuous thermal rating current 308.7 AMax. blocked rotor time HOT 10 secMax. blocked rotor time COLD 20 secLocked rotor Current 1764 APermissible max.accelerating time (WITH LOAD ) 1.7 sec
Parameter Value Unit
CurrentTransformer rated current,phase primary 400 ATransformer rated current, phase secondary 1 ACore Balance CurrentTransformer rated current,phase primary 50 ATransformer rated current, earth secondary 1 A Thermal replica (ANSI 49)Parameter Value (Range) Step Set ValueThermal current threshold Iθ> 0.2 to 1.5 x In 0.01 0.77Trip thermal threshold Set to 100%Thermal Alarm stage: 20 to 100% 1.00% 80%Reset ratio for Thermal trip 30 to 99% 1.00% 70%Tripping time 0.1 to 50 s 0.1 2
Motor Feeders 2600kW Panel Nos 1 &17 Relay: 7UM6211. Available motor data Iron Ore Grinding
General power system data
Tripping time 0.1 to 50 s 0.1 2Io> (Earth Fault) (ANSI 50N/51N)Parameter Value (Range) Step Set ValueCurrent set 0.002 to 1.0 0.01 0.1Time delay 0-100 sec 0.01 0.05
Short Circuit Protection (ANSI 50/51)Parameter Value (Range) Step Set ValueCurrent set I>> 0.5 to 40 1 5.8Time delay t>> 0-150 0.1 0.05Current set I> 0.1 to 25 0.1 0.8Time delay t> ( tms) 0.1 -3.2 0.1 2Curve IEC-NI,IEC-EI,IEC-VI IEC-VIUnbalance Protection ( ANSI 46)Parameter Value (Range) Step Set ValueCurrent Set I2> 0.04 to 0.8 In 0.01 0.1Time delay 0.02 to 99.9 0.1 1Current Set I2>> 0.04 to 0.8 In 0.01 0.2Time Multiple setting ( TMS) I2>> 0.2 to 2 0.1 1Ph:AS (Load Assymetry) (ANSi 47)Parameter Value (Range) Step Set ValueCurrent set 15 to 50% 1 15Time delay 0.02 to 99.9 0.1 1Number of permitted starts (ANSI 66)Parameter Value (Range) Step Set ValueNumber of Cold Starts 0-5 1 3Number of Hot Starts 0-5 1 2T reference 10-120 mins 5 60Restart Inhibition time 1-120 mins 1 20Time between 2 Start ups 1-120 mins 1 20Locked Rotor Protection ( ANSI 51LR/50s)Current set 0.5 to 5 In 0.01 4.4Time Delay for prolonged start: 1 to 60 s 1 4
SETTING DETAILS FORSETTING DETAILS FOR LT MCC PANELSS
SETTINGRANGE
IR=In X…
Long timePick upCurrent
setting (I1)
PrimaryCurrent
Settingrange fortime-lag
class tR atI2t
time lagsetting in
sec
SettingrangeIsd =In × ...
Short timePick upCurrent
Settint (Isd)
PrimaryCurrent
Settingrange for
delay timetsd in ms
Short timedelay in
sec (Tsd) inms
Settingrange Ii = In
× ...
Instantaneous Currentsetting (I3)
PrimaryCurrent
Settingrange of
theoperatingcurrent Ig
Operatingcurrent
setting Ig
PrimaryCurrent
Settingrange ofthe delaytime tg in
ms
Delay timetg in ms
1F1 3200AACB,ETU45
INCOMER 1 2500 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 2500 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 5000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 15000 A-B-C-D-E A 100-200-300-400-500
100
3F1 3200AACB,ETU45
INCOMER 2 2500 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 2500 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 5000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 15000 A-B-C-D-E A 100-200-300-400-500
100
2F1 3200AACB,ETU45
BUSCOUPLER 2500 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.8 2000 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
1.25 3125 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
4 10000 A-B-C-D-E A 100-200-300-400-500
100
Setting Details for 415V LT TG MCCLocation of
deviceDevice
descriptionand release
Sevice ID Breaker Set Current In
Phase Current Settings Ground Current Settings
OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit protection Ground-fault protection
SETTINGRANGE
IR=In X…
Long timePick upCurrent
setting (I1)
PrimaryCurrent
Settingrange fortime-lag
class tR atI2t
time lagsetting in
sec
SettingrangeIsd =In × ...
Short timePick upCurrent
Settint (Isd)
PrimaryCurrent
Settingrange for
delay timetsd in ms
Short timedelay in
sec (Tsd) inms
Settingrange Ii = In
× ...
Instantaneous Currentsetting (I3)
PrimaryCurrent
Settingrange of
theoperatingcurrent Ig
Operatingcurrent
setting Ig
PrimaryCurrent
Settingrange ofthe delaytime tg in
ms
Delay timetg in ms
1F1 1600AACB,ETU45
INCOMER 1 1600 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 1600 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 3200 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 9600 A-B-C-D-E A 100-200-300-400-500
100
3F1 1600AACB,ETU45
INCOMER 2 1600 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 1600 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 3200 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 9600 A-B-C-D-E A 100-200-300-400-500
100
2F1 1600AACB,ETU45
BUSCOUPLER 1600 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.65 1040 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
1.25 2000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
4 6400 A-B-C-D-E A 100-200-300-400-500
100
Setting Details for 415V LT SCREENING MCCLocation of
deviceDevice
descriptionand release
Sevice ID Breaker Set Current In
Phase Current Settings Ground Current Settings
OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit protection Ground-fault protection
SETTINGRANGE
IR=In X…
Long timePick upCurrent
setting (I1)
PrimaryCurrent
Settingrange fortime-lag
class tR atI2t
time lagsetting in
sec
SettingrangeIsd =In × ...
Short timePick upCurrent
Settint (Isd)
PrimaryCurrent
Settingrange for
delay timetsd in ms
Short timedelay in
sec (Tsd) inms
Settingrange Ii = In
× ...
Instantaneous Currentsetting (I3)
PrimaryCurrent
Settingrange of
theoperatingcurrent Ig
Operatingcurrent
setting Ig
PrimaryCurrent
Settingrange ofthe delaytime tg in
ms
Delay timetg in ms
1F1 3200AACB,ETU45
INCOMER 1 2500 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 2500 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 5000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 15000 A-B-C-D-E A 100-200-300-400-500
100
3F1 3200AACB,ETU45
INCOMER 2 2500 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 2500 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 5000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 15000 A-B-C-D-E A 100-200-300-400-500
100
2F1 3200AACB,ETU45
BUSCOUPLER 2500 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.8 2000 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
1.25 3125 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
4 10000 A-B-C-D-E A 100-200-300-400-500
100
Setting Details for 415V LT BALLING SYSTEM MCCLocation of
deviceDevice
descriptionand release
Sevice ID Breaker Set Current In
Phase Current Settings Ground Current Settings
OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit protection Ground-fault protection
SETTINGRANGE
IR=In X…
Long timePick upCurrent
setting (I1)
PrimaryCurrent
Settingrange fortime-lag
class tR atI2t
time lagsetting in
sec
SettingrangeIsd =In × ...
Short timePick upCurrent
Settint (Isd)
PrimaryCurrent
Settingrange for
delay timetsd in ms
Short timedelay in
sec (Tsd) inms
Settingrange Ii = In
× ...
Instantaneous Currentsetting (I3)
PrimaryCurrent
Settingrange of
theoperatingcurrent Ig
Operatingcurrent
setting Ig
PrimaryCurrent
Settingrange ofthe delaytime tg in
ms
Delay timetg in ms
1F1 1600AACB,ETU45
INCOMER 1 1600 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 1600 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 3200 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 9600 A-B-C-D-E A 100-200-300-400-500
100
3F1 1600AACB,ETU45
INCOMER 2 1600 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 1600 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 3200 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 9600 A-B-C-D-E A 100-200-300-400-500
100
2F1 1600AACB,ETU45
BUSCOUPLER 1600 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.65 1040 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
1.25 2000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
4 6400 A-B-C-D-E A 100-200-300-400-500
100
Setting Details for 415V LT PROPORTION & MIXING MCCLocation of
deviceDevice
descriptionand release
Sevice ID Breaker Set Current In
Phase Current Settings Ground Current Settings
OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit protection Ground-fault protection
SETTINGRANGE
IR=In X…
Long timePick upCurrent
setting (I1)
PrimaryCurrent
Settingrange fortime-lag
class tR atI2t
time lagsetting in
sec
SettingrangeIsd =In × ...
Short timePick upCurrent
Settint (Isd)
PrimaryCurrent
Settingrange for
delay timetsd in ms
Short timedelay in
sec (Tsd) inms
Settingrange Ii = In
× ...
Instantaneous Currentsetting (I3)
PrimaryCurrent
Settingrange of
theoperatingcurrent Ig
Operatingcurrent
setting Ig
PrimaryCurrent
Settingrange ofthe delaytime tg in
ms
Delay timetg in ms
1F1 2000AACB,ETU45
INCOMER 1 2000 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 2000 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 4000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 12000 A-B-C-D-E A 100-200-300-400-500
100
3F1 2000AACB,ETU45
INCOMER 2 2000 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 2000 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 4000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 12000 A-B-C-D-E A 100-200-300-400-500
100
2F1 2000AACB,ETU45
BUSCOUPLER 2000 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.65 1300 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
1.25 2500 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
4 8000 A-B-C-D-E A 100-200-300-400-500
100
Ground Current Settings
OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit protection Ground-fault protection
Setting Details for 415V LT ORE CRUSHING GRINDING SYSTEM MCCLocation of
deviceDevice
descriptionand release
Sevice ID Breaker Set Current In
Phase Current Settings
SETTINGRANGE
IR=In X…
Long timePick upCurrent
setting (I1)
PrimaryCurrent
Settingrange fortime-lag
class tR atI2t
time lagsetting in
sec
SettingrangeIsd =In × ...
Short timePick upCurrent
Settint (Isd)
PrimaryCurrent
Settingrange for
delay timetsd in ms
Short timedelay in
sec (Tsd) inms
Settingrange Ii = In
× ...
Instantaneous Currentsetting (I3)
PrimaryCurrent
Settingrange of
theoperatingcurrent Ig
Operatingcurrent
setting Ig
PrimaryCurrent
Settingrange ofthe delaytime tg in
ms
Delay timetg in ms
1F1 3200AACB,ETU45
INCOMER 1 3200 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 3200 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 6400 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 19200 A-B-C-D-E A 100-200-300-400-500
100
3F1 3200AACB,ETU45
INCOMER 2 3200 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 3200 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 6400 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 19200 A-B-C-D-E A 100-200-300-400-500
100
2F1 3200AACB,ETU45
BUSCOUPLER 3200 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.8 2560 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
1.25 4000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
4 12800 A-B-C-D-E A 100-200-300-400-500
100
Setting Details for 415V LT CPP LCSSLocation of
deviceDevice
descriptionand release
Sevice ID Breaker Set Current In
Phase Current Settings Ground Current Settings
OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit protection Ground-fault protection
SETTINGRANGE
IR=In X…
Long timePick upCurrent
setting (I1)
PrimaryCurrent
Settingrange fortime-lag
class tR atI2t
time lagsetting in
sec
SettingrangeIsd =In × ...
Short timePick upCurrent
Settint (Isd)
PrimaryCurrent
Settingrange for
delay timetsd in ms
Short timedelay in
sec (Tsd) inms
Settingrange Ii = In
× ...
Instantaneous Currentsetting (I3)
PrimaryCurrent
Settingrange of
theoperatingcurrent Ig
Operatingcurrent
setting Ig
PrimaryCurrent
Settingrange ofthe delaytime tg in
ms
Delay timetg in ms
1F1 2000AACB,ETU45
INCOMER 1 2000 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 2000 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 4000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 12000 A-B-C-D-E A 100-200-300-400-500
100
3F1 2000AACB,ETU45
INCOMER 2 2000 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 2000 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 4000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 12000 A-B-C-D-E A 100-200-300-400-500
100
2F1 2000AACB,ETU45
BUSCOUPLER 2000 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.65 1300 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
1.25 2500 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
4 8000 A-B-C-D-E A 100-200-300-400-500
100
Setting Details for 415V LT KILN 1 &2 MCCLocation of
deviceDevice
descriptionand release
Sevice ID Breaker Set Current In
Phase Current Settings Ground Current Settings
OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit protection Ground-fault protection
SETTINGRANGE
IR=In X…
Long timePick upCurrent
setting (I1)
PrimaryCurrent
Settingrange fortime-lag
class tR atI2t
time lagsetting in
sec
SettingrangeIsd =In × ...
Short timePick upCurrent
Settint (Isd)
PrimaryCurrent
Settingrange for
delay timetsd in ms
Short timedelay in
sec (Tsd) inms
Settingrange Ii = In
× ...
Instantaneous Currentsetting (I3)
PrimaryCurrent
Settingrange of
theoperatingcurrent Ig
Operatingcurrent
setting Ig
PrimaryCurrent
Settingrange ofthe delaytime tg in
ms
Delay timetg in ms
1F1 1600AACB,ETU45
INCOMER 1 1600 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 1600 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 3200 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 9600 A-B-C-D-E A 100-200-300-400-500
100
3F1 1600AACB,ETU45
INCOMER 2 1600 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 1600 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 3200 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 9600 A-B-C-D-E A 100-200-300-400-500
100
2F1 1600AACB,ETU45
BUSCOUPLER 1600 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.65 1040 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
1.25 2000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
4 6400 A-B-C-D-E A 100-200-300-400-500
100
Setting Details for 415V LT RMP 3 MCCLocation of
deviceDevice
descriptionand release
Sevice ID Breaker Set Current In
Phase Current Settings Ground Current Settings
OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit protection Ground-fault protection
SETTINGRANGE
IR=In X…
Long timePick upCurrent
setting (I1)
PrimaryCurrent
Settingrange fortime-lag
class tR atI2t
time lagsetting in
sec
SettingrangeIsd =In × ...
Short timePick upCurrent
Settint (Isd)
PrimaryCurrent
Settingrange for
delay timetsd in ms
Short timedelay in
sec (Tsd) inms
Settingrange Ii = In
× ...
Instantaneous Currentsetting (I3)
PrimaryCurrent
Settingrange of
theoperatingcurrent Ig
Operatingcurrent
setting Ig
PrimaryCurrent
Settingrange ofthe delaytime tg in
ms
Delay timetg in ms
1F1 1250AACB,ETU45
INCOMER 1 1250 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.5 625 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 2500 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 7500 A-B-C-D-E A 100-200-300-400-500
100
3F1 1250AACB,ETU45
INCOMER 2 1250 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.5 625 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 2500 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 7500 A-B-C-D-E A 100-200-300-400-500
100
2F1 1250AACB,ETU45
BUSCOUPLER 1250 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.65 812.5 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
1.25 1562.5 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
4 5000 A-B-C-D-E A 100-200-300-400-500
100
Setting Details for 415V LT STP MCCLocation of
deviceDevice
descriptionand release
Sevice ID Breaker Set Current In
Phase Current Settings Ground Current Settings
OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit protection Ground-fault protection
SETTINGRANGE
IR=In X…
Long timePick upCurrent
setting (I1)
PrimaryCurrent
Settingrange fortime-lag
class tR atI2t
time lagsetting in
sec
SettingrangeIsd =In × ...
Short timePick upCurrent
Settint (Isd)
PrimaryCurrent
Settingrange for
delay timetsd in ms
Short timedelay in
sec (Tsd) inms
Settingrange Ii = In
× ...
Instantaneous Currentsetting (I3)
PrimaryCurrent
Settingrange of
theoperatingcurrent Ig
Operatingcurrent
setting Ig
PrimaryCurrent
Settingrange ofthe delaytime tg in
ms
Delay timetg in ms
1F1 1250AACB,ETU45
INCOMER 1 1250 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.5 625 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 2500 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 7500 A-B-C-D-E A 100-200-300-400-500
100
3F1 1250AACB,ETU45
INCOMER 2 1250 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.5 625 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 2500 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 7500 A-B-C-D-E A 100-200-300-400-500
100
2F1 1250AACB,ETU45
BUSCOUPLER 1250 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.35 437.5 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
1.25 1562.5 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
4 5000 A-B-C-D-E A 100-200-300-400-500
100
Setting Details for 415V LT AFBC MCCLocation of
deviceDevice
descriptionand release
Sevice ID Breaker Set Current In
Phase Current Settings Ground Current Settings
OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit protection Ground-fault protection
SETTINGRANGE
IR=In X…
Long timePick upCurrent
setting (I1)
PrimaryCurrent
Settingrange fortime-lag
class tR atI2t
time lagsetting in
sec
SettingrangeIsd =In × ...
Short timePick upCurrent
Settint (Isd)
PrimaryCurrent
Settingrange for
delay timetsd in ms
Short timedelay in
sec (Tsd) inms
Settingrange Ii = In
× ...
Instantaneous Currentsetting (I3)
PrimaryCurrent
Settingrange of
theoperatingcurrent Ig
Operatingcurrent
setting Ig
PrimaryCurrent
Settingrange ofthe delaytime tg in
ms
Delay timetg in ms
1F1 4000AACB,ETU45
INCOMER 1 4000 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 4000 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 8000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 24000 A-B-C-D-E A 100-200-300-400-500
100
3F1 4000AACB,ETU45
INCOMER 2 4000 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
1 4000 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
2 8000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
6 24000 A-B-C-D-E A 100-200-300-400-500
100
2F1 4000AACB,ETU45
BUSCOUPLER 4000 0.4-0.45-0.5-0.55-0.6-0.65-0.7-0.8-0.9-1.0
0.8 3200 2-3.5-5.5-8-10-14-17-21-25-30 s
2 1.25-1.5-2-2.5-3-4-6-8-10-12 xIn
1.25 5000 100-200-300-400
100 1.5-2.2-3-4-6-8-10-12
4 16000 A-B-C-D-E A 100-200-300-400-500
100
Ground Current Settings
OVERLOAD PROTECTION Short-time delayed short-circuit protection Instantaneous short-circuit protection Ground-fault protection
Setting Details for 415V LT KILN 3 MCCLocation of
deviceDevice
descriptionand release
Sevice ID Breaker Set Current In
Phase Current Settings
Relay setting data for LT MCC s
Description Range Setting PrimeCTsfor Restricted Earth fault Protection CT rated primary 10..50000 A 3000
CT rated secondary 1 A / 5 A 5Afor Earth fault Protection CT rated primary 10..50000 A 3000
CT rated secondary 1 A / 5 A 5A
Setting name Range Setting64R Element Diasabled/Enabled Enabled64R Setting 0.05..2 0.1 x In 30064R-1 delay 20..60000 100ms
Setting name Range Setting51N Element Diasabled/Enabled Enabled51N Setting 0.05..2 0.15 x In 45051N-1 delay 20..60000 500ms
Description Range Setting PrimeCTsfor Restricted Earth fault Protection CT rated primary 10..50000 A 2000
CT rated secondary 1 A / 5 A 5A
CPP LCSS 1
2 RESTRICTED EARTH FAULT PROTECTION 64
3 DIRECT EARTH FAULT PROTECTION 51N
1 CT/VT CONFIG
ORE CRUSHING & GRINDING SYSTEM LCSS 21 CT/VT CONFIG
for Restricted Earth fault Protection CT rated primary 10..50000 A 2000CT rated secondary 1 A / 5 A 5A
for Earth fault Protection CT rated primary 10..50000 A 2000CT rated secondary 1 A / 5 A 5A
Setting name Range Setting64R Element Diasabled/Enabled Enabled64R Setting 0.05..2 0.1 x In 20064R-1 delay 20..60000 100ms
Setting name Range Setting51N Element Diasabled/Enabled Enabled51N Setting 0.05..2 0.15 x In 30051N-1 delay 20..60000 500ms
2 RESTRICTED EARTH FAULT PROTECTION 64
3 DIRECT EARTH FAULT PROTECTION 51N
TIME CURRENTCHARACTERISTIC CURVES
TIME CURRENTCHARACTERISTIC CURVES
11000 Volt Phase Time-Current Characteristic Curves2 - PATH:GRID-TGMCC
12-27-201422:40:53
newjanki_06122014
.01
.11
1010
010
0010
000
Tim
e in
Sec
onds
.5 1 10 100 1000 10000Current in Amperes X 10
TG_IC
AH17
AH01 BCAH03
4F1:LBDS1
6.6kV_LBSS1_IC1INT.PANEL
PELLET PLANT 1
TR_CB
GCB
LINE_CB
A
20000.0 KVA Transformer
INRUSH 20MVA
A
15000.0 KVA Transformer
Inrush 15 MVA
A
1600.0 KVA Transformer
Inrush TG_TR
11000 Volt Ground Time-Current Characteristic Curves2 - PATH:GRID-TGMCC
12-27-201422:40:06
newjanki_06122014
.01
.11
1010
010
0010
000
Tim
e in
Sec
onds
.5 1 10 100 1000 10000Current in Amperes
PELLET PLANT 1
INT.PANEL
6.6kV_LBSS1_IC1
4F1:LBDS1
LINE_CB
TR_CBGCB
AH03
AH17
192
11000 Volt Phase Time-Current Characteristic Curves8 - PATH:GRID-RMP1000kVA TRAFO
12-27-201422:32:01
newjanki_06122014
.01
.11
1010
010
0010
000
Tim
e in
Sec
onds
.5 1 10 100 1000 10000Current in Amperes X 10
RMP3
A
20000.0 KVA Transformer
INRUSH 20MVA
TR_CB
GCB
A
RMP3 TR 1000.0 KVA Transformer
INRUSH 1000kVA
415 V LCSS-7 STP
11000 Volt Ground Time-Current Characteristic Curves8 - PATH:GRID-RMP1000kVA TRAFO
12-27-201422:33:07
newjanki_06122014
.01
.11
1010
010
0010
000
Tim
e in
Sec
onds
.5 1 10 100 1000 10000Current in Amperes
415 V LCSS-7 STP
GCB
RMP3
TR_CB
11000 Volt Phase Time-Current Characteristic Curves11 - Path:2600 kW MOTOR
12-27-201422:27:46
newjanki_06122014
.01
.11
1010
010
0010
000
Tim
e in
Sec
onds
.5 1 10 100 1000 10000Current in Amperes X 10
6.6kV_LBSS1_IC1
1F1:HT MOTOR2600kW
S
Hot Stall TimeCold Stall Time
11000 Volt Phase Time-Current Characteristic Curves12 - Path:315kW MOTORFEEDER
12-27-201422:25:49
newjanki_06122014
.01
.11
1010
010
0010
000
Tim
e in
Sec
onds
.5 1 10 100 1000 10000Current in Amperes X 10
AH03
AH21
AH FAN1_315kW
S
Hot Stall TimeCold Stall Time
11000 Volt Phase Time-Current Characteristic Curves12 - Path:1000kW MOTORFEEDER
12-27-201422:23:40
newjanki_06122014
.01
.11
1010
010
0010
000
Tim
e in
Sec
onds
.5 1 10 100 1000 10000Current in Amperes X 10
AH03
AH19
IDFAN_1000kW
S
Hot Stall TimeCold Stall Time
4641
SC
A @
110
00V
(IDFA
N_1
000k
W)
Observations and Comments:
1) The Single line diagram furnished by the customer has got many discrepencies with actuals at
site,especially the CT details furnished in the drawing are not matching.The customer has to prepare as fitted
drawing for their future reference.2) The Second Turbo Generator 3 MW set has got CT ratio of 300/1.However it is noticed that the incomer
in the 11 kV switch board from this Generator has got CT of 1250/1.We have given the settings assuming this
CT will be matched with Generator CTs3) There is one overall Differential Protection Relay, CTs from 15 MW Generator,HV side and LV side of
Generator Transformer connected.This relay operation will be in order when only one Generator 15 MW is in
operation.If the 3 MW set is in operation , this differential relay will pick up and trip the Breaker.Modification
of the circuitary is required.