• User interface is present on the top of the SG-BWS-T4 for signalling and configuration.
• Two units made of 8 dip-switches are present on the top of the SG-BWS-T4-MT model. These switches activate/deactivate and configure additional functions integrated in the device.
• Signalling interface and dip-switches are protected from non-authorized access by transparent lids that can be opened using a specific tool.
The EDM and MAN/AUTO Restart functions integrated in SG-BWS-T4 model can be selected through specific control unit lines (refer “CONNECTION” section of the present document).
www.automation.datalogic.com
SETTINGS
DIP PURPOSE OFF (Default) ON
1 ENABLE EDM ENABLED DISABLED
2 RESET MODE AUTOMATIC MANUAL
3 MUTING TIME-OUT 10 MINUTES INFINITY
4 MUTING DIRECTION T L
2 OVERRIDE EDGED TRIGGERED
6 MUTING SELECTIONSee specific table
7 MUTING SELECTION
8 MUTING SELECTION
INDICATORS
An user interface is present for viewing warnings and setup is present on the top of both SG-BWS-T4 and SG-BWS-T4-MT control unitsBesides the 7-segment display (for diagnostics purposes), the warning components include 3 LEDs:
LED INDICATION
POWER Device is powered correctly
NORMAL No danger: safety outputs closed
SAFE Danger or fault: safety outputs open
The 7-segment display shows detailed information on control unit current status
DOUBLE MUTING FUNCTION SETTING
DIP-SWITCH SETUP PHOTOCELLS LIGHT CURTAIN 1 LIGHT CURTAIN 2
000 A A A
001 A A B
010 A B B
011 - A B
100 A B -
101 - A A
110 A - -
111 - - -
0=OFF, 1=0N, A(B)=Device associated to channel A(B) Default setting: 000
MUTING WARNING DEVICES
To use the Muting function it is also required to connect the external Muting warning (lamp) since control unit would lock out if it is missing. One lamp shall be used per channel. If device is preset for use of just one channel, both warning devices are associated to it: in this way, failure of one of the lamps would not lock out system operation.SG-BWS-T4-MT allows installation of both incandescent lamps and LEDs. For the latter case, polarity shall be carefully complied with, as indicated aside.
Note: the Muting lamp is not supplied with the device. Please refer to “Accessory selection and order information table.”
Thanks to its two separate muting channels, SG-BWS-T4-MT can accept the muting request output by sensors without interrupting the safety function on light curtain or safety sensors of both channels.
DIMENSIONS
SG-BWS-T4
mm
SG-BWS-T4-MT
www.automation.datalogic.com
SIGNAL CONTACT CONNECTION
VCC 1 External 24Vdc
START/TEST/RESET 2 - Contact NC towards 24Vdc
EDM ENABLE 3- 24Vdc > EDM DEACTIVATED
- Not connected > EDM activated
EDM 4- NC contact of external relays towards 24Vdc (with EDM activated)
- Not connected > with EDM deactivated
0V 5 External 0Vdc
MAN/AUTO 6- OSSD1 (7) > AUTOMATIC RESTART
- OSSD2 (8) > MANUAL RESTART
OSSD1 7 Reel of external relay 1 (positive)
OSSD2 8 Reel of external relay 2 (positive)
RX1 9 PNP output of receiver photocell 1 (black)
RX2 10 PNP output of receiver photocell 2 (black)
RX3 11 PNP output of receiver photocell 3 (black)
RX4 12 PNP output of receiver photocell 4 (black)
TX1 13 TEST of emitter photocell 1 (black)
TX2 14 TEST of emitter photocell 2 (black)
TX3 15 TEST of emitter photocell 3 (black)
TX4 16 TEST of emitter photocell 4 (black)
SG-BWS-T4 CONNECTIONS
NOTE : As SG-BWS-T4 has OSSD Safety outputs in order to have relay outputs, the device must have EDM function connected to the CS-ME EDM relay box as represented below:
SG-BWS-T4-MT CONNECTIONS
www.automation.datalogic.com
SIGNAL CLAMP CONNECTION FUNCTION
VDC 1 External 24Vdc Power supply
START 2 NO contact towards 24Vdc Reset function
TEST/RESET 3 NC contact towards 24Vdc Test/Reset function
EDM 4- NC contact of external relays towards 24Vdc
(with EDM activated)- NOT CONNECTED (with EDM deactivated)
Input EDM
0V 5 0Vdc external Power supply
MUTEN A 6 NO contact towards 24Vdc Muting activation
MUTEN B 7 NO contact towards 24Vdc Muting activation
DEFLAMP 8 Positive terminal signaling device Lamp fault signaling
MUTA1 9 PNP output of the A1 Muting sensor Muting input
OVRA1 10 Contact of Override A1 NO towards 24Vdc Override input
MUTB1 11 PNP output of the B1 Muting sensor Muting input
OVRB1 12 Contact of Override B1 NO towards 24Vdc Override input
MUTA2 13 PNP output of A2 Muting sensor Muting input
OVRA2 14 Contact of Override A2 NO towards 24Vdc Override input
MUTB2 15 PNP output of B2 Muting sensor Muting input
OVRB2 16 Contact of Override B2 NO towards 24Vdc Override input
LAMPA- 17 Negative terminal of the A Muting lamp Muting lamp output
LAMPA+ 18 Positive terminal of the A Muting lamp Muting lamp output
SAFNC11 19NO relay 230V 1 output
Safety contact
SAFNC21 20 Safety contact
LAMPB- 21 Negative terminal of the B Muting lamp Muting lamp output
LAMPB+ 22 Positive terminal of the B Muting lamp Muting lamp output
SAFNC12 23NO relay 230V 2 output
Safety contact
SAFNC22 24 Safety contact
RX1 25 PNP output of the photocell receiver 1 (black) Photocell input
RX2 26 PNP output of the photocell receiver 2 (black) Photocell input
RX3 27 PNP output of the photocell receiver 3 (black) Photocell input
RX4 28 PNP output of the photocell receiver 4 (black) Photocell input
TX1 29 TEST of the photocell emitter 1 (black) Photocell output
TX2 30 TEST of the photocell emitter 2 (black) Photocell output
TX3 31 TEST of the photocell emitter l 3 (black) Photocell output
TX4 32 TEST of the emitter photocell 4 (black) Photocell output
24VRX12 33 24Vdc photocell receivers 1 and 2 (brown) Power supply output
0VRX12 34 0 Vdc photocell receivers 1 and 2 (blue) Power supply output
24VRX34 35 24 Vdc photocell receivers 3 and 4 (brown) Power supply output
0VRX34 36 0Vdc photocell receivers 3 and 4 (blue) Power supply output
24VTX12 37 24Vdc photocell emitters 1 and 2 (brown) Power supply output
0VTX12 38 0Vdc photocell emitters 1 and 2 (blue) Power supply output
24VTX34 39 24Vdc photocell emitters 3 and 4 (brown) Power supply output
0VTX34 40 0Vdc photocell emitters 3 and 4 (blue) Power supply output
OSSD11 41 OSSD 1 output of the light curtain 1 (grey) Light curtain input
OSSD21 42 OSSD 1 output of the light curtain 2 (grey) Light curtain input
24LRX12 43 24Vdc receivers of light curtain 1 and 2 (brown) Power supply output
0LRX12 44 0Vdc receivers of light curtain 1 and 2 (brown) Power supply output
OSSD12 45 OSSD 2 output of light curtain 1 (pink) Light curtain input
OSSD22 46 OSSD 2 output of light curtain 2 (pink) Light curtain input
24LTX12 47 24Vdc light curtain emitters 1 and 2 (brown) Power supply output
0LTX12 48 0Vdc light curtain emitters 1 and 2 (brown) Power supply output
NO: Normally open – NC: Normally closed
NOTE : Both SG-BWS-T4 and SG-BWS-T4-MT models are equipped with extractable screw clamps. It’s possible to replace them with corresponding spring clamps provided as accessories, if necessary.
(*) Spring clamps are available as accessories
ELECTRICAL DATA
SG-BWS-T4 SG-BWS-T4-MT
Power supply: 24 Vdc ± 15% 24 Vdc ± 15%
Consumption: 2.1 W max 3.8 W max
Output contacts: 2 PNP 2 normally open relays, 250 Vac 5A - 24 Vdc 5A
Response time: Short circuit protection: 1.4 A max 39ms (includes response time of photocells)
Safety category: Type 4 (ref. EN 61496-1) Type 4 (ref. EN 61496-1)
SIL: SIL 3 (ref. IEC 61508 and IEC 62061) SIL 3 (ref. IEC 61508 and IEC 62061)
PL: PL e (ref. EN ISO 13849-1) PL e (ref. EN ISO 13849-1)
PFHd min (1/h): 1,60E-09 1,74E-09
MTTFd (years): 545 428
Accessory functions: Reset / EDM selection / auto-man selectionReset / EDM selection / auto-man selection
Single/Double Muting selectionEdged/Triggered Override Selection
Overload protection:Cat. II (250 Vac) – Cat. III (24Vdc)
(ref. EN 50178)
Connections: Clamps (*) Clamps (*)
Cable lengths (power supply): 50 m. max 50 m. max
Pollution degree: 2 2
MECHANICAL AND ENVIRONMENTAL DATA
Operating temperature: 0…55°C 0…55°C
Storage temperature: -25…+ 70 °C -25…+ 70 °C
Temperature class: T6 T6
Humidity: 15…95 % (no condensation) 15…95 % (no condensation)
Mechanical protection: IP 20 (EN 60529) IP 20 (EN 60529)
Vibrations:0.35 mm amplitude, 10 … 55Hz frequency 20 sweeps for
axis, 1octave/min (EN 60068-2-6)0.35 mm amplitude, 10 … 55Hz frequency 20 sweeps per
axis, 1octave/min (EN 60068-2-6)
Shock resistance: 16 ms (10 G) 1.000 shocks for axis (EN 60068-2-29) 16 ms (10 G) 1.000 shocks for axis (EN 60068-2-29)
Housing material: Nylon PA66 Nylon PA66
Weight:
TECHNICAL DATA
MODEL SELECTION TABLE
ACCESSORY SELECTION AND ORDER INFORMATION
MODEL DESCRIPTION ORDER N°
SG-DM 150 deviating mirror h=150mm 95ASE1670
LMS muting lamp 95ASE1830
LMS-1 modular muting lamp 95ACC1990
LMS-2 muting lamp – horizontal mounting 95ACC2000
LMS-3 muting lamp - vertical mounting 95ACC2010
SU-LMS-1A base module for lms-1 95ACC2020
SU-LMS-1B tower module for lms-1 95ACC2030
MODEL DESCRIPTION ORDER N°
SG-BWS-T4 cat. 4 safety control unit with edm and man/auto restart 957051000
SG-BWS-T4-MT cat. 4 safety control unit with double muting 957051010
The company endeavours to continuously improve and renew its products; for this reason the technical data and contents of this catalogue may undergo variations without prior notice. For correct installation and use, the company can guarantee only the data indicated in the instruction manual supplied with the products.