Bedrock Automation SPS.500 Quick Start BRDOC110_003
SPS.500Quick Start
Guide
12 - Specifications
SPS.500 LED Status Codes System State Color Blink Rate
Normal operation Green Steady
Input under voltage Red 1 per second
Internal fault Red 2 per second
Output over current Orange 1 per second
Input frequency out of range Red 3 per second
Over power Orange 2 per second
Image updating Green 2 per second
Image update validation failed Blue 4 per second for 10 seconds
Power Out
“OR”ing Out
Relay
PIN 1PIN 2PIN 3PIN 4PIN 5PIN 6
DRAIN WIRE
PIN 1PIN 2PIN 3PIN 4PIN 5PIN 6
DRAIN WIRE
RELAY A (NC)
RELAY A (COM)
RELAY A (NO)
RELAY B (NC)
RELAY B (COM)
RELAY B (NO)
PIN 1
PIN 2
PIN 3
PIN 4
PIN 5
PIN 6
DRAIN WIRE
RELAY
CAUTION: See panel 12 for relay contact rating specification.
9 – SPS Cables
Note: See panel 10 for pin out tables. Connect drain wire to panel ground.
AC Power In
PIN 1
PIN 2
PIN 3
11 – Cable Alignment
Step 1: Align open arrow with arrow on mating connector and then press together.
Step 2: Rotate ¼ turn clockwise to the locked position.
8 – Clamp SPS
3
3
4
DRAIN WIRE
1
2
10 – Cable Pin Outs
Power Out
“OR”ing Out
Relay
Pin/Wire Function Color DRAIN WIRE GROUND N/A
PIN 1 24 V DC RED
PIN 2 24 V DC RED
PIN 3 24 V DC RED
PIN 4 24 V RET BLACK
PIN 5 24 V RET BLACK
PIN 6 24 V RET BLACK
CAUTION: Each contact is rated for 10 amps at
25°C. In order to support full capacity, all wires must be connected to their respective contacts.
CAUTION: Each contact is rated for 10 amps at 25°C. In order to support full capacity, all wires must be connected to their respective contacts.
AC Power In
Pin/Wire Function Color PIN 1 LINE BLACK
PIN 2 NEUTRAL WHITE
PIN 3 GROUND GREEN
PIN PE DRAIN WIRE N/A
Pin/Wire Function Color PIN 1 RELAY A (NC) BLACK
PIN 2 RELAY A (COM) RED
PIN 3 RELAY A (NO) WHITE
PIN 4 RELAY B (NC) GREEN
PIN 5 RELAY B (COM) ORANGE
PIN 6 RELAY B (NO) BLUE
PIN 7 DRAIN WIRE N/A
Pin/Wire Function Color DRAIN WIRE GROUND N/A
PIN 1 24 V DC RED
PIN 2 24 V DC RED
PIN 3 24 V DC RED
PIN 4 24 V RET BLACK
PIN 5 24 V RET BLACK
PIN 6 24 V RET BLACK
Note: Figures show the connector end of each cable.
NOTE: Cable length should not exceed 9 meters (29.5 ft.).
13 – Specifications and Certifications
IEC Environmental Testing
IEC 60068-2-27 Shock
IEC 60068-2-6 Vibration
FCC Testing
CFR FCC Part 15 Subpart B, Class A (2016) Radiated Emissions
CE Testing - European EMC Directive 2014/30/EU including: EN 61326-1 EMC Requirements
CISPR 11: 2010 Radiated Emissions
IEC 61000-4-2 ESD Immunity
IEC 61000-4-3 Radiated RF Immunity
IEC 61000-4-4 Electrical Fast Transient/Burst Immunity
IEC 61000-4-5 Surge Immunity
IEC 61000-4-6 Conducted RF Immunity
IEC 61000-4-11 Voltage Dips
IEC 61000-4-14 Voltage Fluctuation
IEC 61000-4-28 Variation of Power Frequency
SPS.500 General Specifications Communication/output ports:
Two Type C relay contacts rated
Max switching voltage 125 V DC, 150 V AC
Max switching current 1 amp
One 10/100 Ethernet port with IEEE-1588 timestamp
Status indicators:
Tri-color status LED See SPS.500 LED Status Codes Table
Yellow Ethernet link LED On indicates Ethernet link
Yellow Ethernet activity LED On indicates Ethernet activity
Dimensions
Height 232 mm (9.13 inches)
Depth 152 mm (5.98 inches)
Width 139 mm (5.47 inches )
Weight 4.76 kg (10.5 pounds)
Enclosure IP66/IP67 Metal: Aluminum Coating: Electroless nickel plated
Safety Certifications
UL 508 Industrial Control Equipment
IEC/UL 60950-1 Information Technology Equipment - Safety
CE mark
SPS.500 Environmental Specifications Operating temperature -25°C to 80°C with derating curve above 50°C
Storage temperature -40°C to 85°C
Operating humidity 5% to 100% relative humidity
SPS.500 Electrical Specifications Input voltage range 95-264 V AC @ 50/60 Hz
Input frequency 47-400 Hz
Inrush current (typ) (cold start) 20 amps
Line regulation 100 mV
Load regulation 100 mV
Ripple and noise 50 mV
Power factor > 0.95
Main supply output holdup time > 20 ms
Microcontroller holdup time 1.0 seconds
Standby power draw 1.2 watts
Maximum load current 20 amps
Short circuit current 22 amps
Output voltage range 22-28 V DC
Peak efficiency 94%
Redundant operation “OR”ed Output
Series operation Possible
Cooling Convection
6 – Parts List (Pipe Mount)
2
3
1
45
7 – Mount SPS
2
1 - Status LEDs
Tri-color SPS Status
Ethernet Link
Ethernet Activity
2 - Ports
Note: TE Connectivity part no. 2120864-1 must be used for the Ethernet connector in order to maintain the IP66/67 rating.
5 – Parts List (Panel Mount)
2
3
1
Note: A shielded Ethernet cable is required.
3 – SPS.500 Block DiagramImportant User Information
Never attempt to open the SPS.500
enclosure. The enclosure is securely
sealed. Opening the enclosure will void
the warranty and cause the SPS.500 to
be inoperable.
Always use an appropriate fuse on the
power in and power out connections.
Dangerous voltages are present within
the power supply. Do not attempt to
open the SPS.500 enclosure. Do not
come in contact with the incoming line
voltage.
High Voltage Warning
Workstation Running OPC UA
SIO4.E
PowerSupply
Recommended Fusing / Circuit
Breaker
PowerIn
PowerOut
Recommended Fusing / Circuit
Breaker
Relay Output
E the rne t
Optional Bedrock UPS.500 Power
Supply
Load
AC Mains
Load
Ethernet
Relay
PowerIn
PowerOut
“OR”ingOutput
1
ITEM
NO. DESCRIPTION QTY.
1 SPS.500 ASSEMBLY 1
2 #14 x 1” SELF TAPPING
SCREW 4
3 SPS MOUNTING BRACKET
ASSEMBLY 1
ITEM
NO. DESCRIPTION QTY.
1 SPS.500 ASSEMBLY 1
2 3/8”-16 x 3/4 HEX BOLT 4
3 SPS MOUNTING BRACKET
ASSEMBLY 1
4 2” SCHEDULE 40 PIPE
MOUNTING BRACKET 1
5 3/8”-16 HEX NUT 4
4 – Redundancy Block Diagram
Workstation Running OPC UA
Recommended Fusing / Circuit
Breaker
PowerIn
“OR”ed Power Out
Recommended Fusing / Circuit
Breaker
Relay Output
E the rne t
AC Mains A
Load
SIO4.EEthernetSwitch
PowerIn
“OR”ed Power Out
Recommended Fusing / Circuit
Breaker
Recommended Fusing / Circuit
Breaker
AC Mains B
10/100E the rne t
10/100E the rne t
Relay Output
E the rne t