SUbMittaL Data: pLa-a30ba & pUZ-Ha30nHa 30,000 btU/H ...€¦ · generaL FeatUreS • Innovative...

Post on 23-Apr-2018

215 views 1 download

transcript

Job Name: Location: Date:

Purchaser: Engineer:

Submitted to: For Reference Approval Construction

Unit Designation: Schedule No.:

Cooling*Rated Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30,000 Btu/hMinimum Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . .18,000 Btu/hSEER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15.6 Btu/h/WTotal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..2,450 WHeating*Rated Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32,000 Btu/hMinimum Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . .18,000 Btu/hHSPF (IV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8.8 Btu/h/WTotal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..3,440 WHeating at 17°F*Rated Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32,000 Btu/hTotal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..5,720 W* Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB / 67ºF (19ºC) WB.Outdoor: 95ºF (35ºC) DB / 75ºF (24ºC) WB.(Heating) - Indoor: 70ºF (21ºC) DB / 60ºF (16ºC) WB. Outdoor: 47ºF (8ºC) DB /43ºF (6ºC) WB. (Heating) - Indoor: 70ºF (21ºC) DB / 60ºF (16ºC) WB. Outdoor: 17ºF (-8ºC) DB /15ºF (-9ºC) WB.

Power Supply . . . . . . . . . . . . . . . . . . . . 208 / 230V, 1-Phase, 60 HzBreaker Size. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 AVoltageIndoor - Outdoor S1-S2 . . . . . . . . . . . . . . . . . . . . . . AC 208 / 230VIndoor - Outdoor S2-S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . .DC 24VIndoor - Wired Remote Controller. . . . . . . . . . . . . . . . . . . . .DC 12V

Operating rangeIndoor Intake Air Temp. Outdoor Intake Air Temp.

Cooling Maximum 90ºF (32ºC) DB, 73ºF (23ºC) WB 115ºF (46ºC) DB

Minimum 66ºF (19ºC) DB, 59ºF (15ºC) WB 0ºF** (-18ºC) DB

Heating Maximum 83ºF (28ºC) DB 70ºF (21ºC) DB, 59ºF (15ºC) WB

Minimum 63ºF (17ºC) DB -13ºF (-25ºC) DB, -13ºF (-25ºC) WB

** With optional wind baffle accessory installed. If not installed, the minimum temperature will be 23ºF (-5ºC) DB.

Indoor Unit: PLA-A30BA

Outdoor Unit: PUZ-HA30NHAindoor UnitMCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 A Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.51 F.L.A.Fan Motor Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 WAirflow (Lo - M1 - M2 - Hi) . . . . . . . 490 - 570 - 640 - 740 Dry CFM 460 - 530 - 600 - 710 Wet CFMSound Pressure Level (Lo - M1 - M2 - Hi) . . 28 - 30 - 32 - 34 dB(A)

DiMenSiOnS Unit inCHeS / MM paneL inCHeS / MMW 33-1/16 / 840 37-3/8 / 950D 33-1/16 / 840 37-3/8 / 950H 10-3/16 / 258 1-3/8 / 35

Weight (Unit/Grille)lbs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 / 13kg . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 / 6Field Drainpipe Size O.D. . . . . . . . . . . . . . . . . . . . . . 1-1/4" / 32 mmWall-mounted Remote Controller . . . . . . . . . . . . . . . . . PAR-21MAA

(See Data Submittal Sheet)

Outdoor UnitCompressor . . . . . . . . . . . . . . . . . . . . . . . DC Inverter-driven ScrollMCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.4 + 0.4 F.L.A.Sound Pressure LevelCooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 dB(A)Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 dB(A) DiMenSiOnS inCHeS / MMW 37-3/8 / 950D 13 + 1-3/16 / 330 + 30H 53-1/8 / 1,350

Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .267 lbs. / 121 kgRefrigerant Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R410ARefrigerant Pipe Size O.D. Gas Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5/8" / 15.88 mm Liquid Side. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3/8" / 9.52 mmMax. Refrigerant Pipe Length. . . . . . . . . . . . . . . . . . . . . 245' / 75 mMax. Refrigerant Pipe Height Difference . . . . . . . . . . . . 100' / 30 mConnection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Flared

SUbMittaL Data: pLa-a30ba & pUZ-Ha30nHa 30,000 btU/H CeiLing CaSSette Hyper Heat-pUMp SySteM

Remote Controller: PAR-21MAA

OptiOnaL aCCeSSOrieS indoor Unit• Multi-function Casement (PAC-SH53TM-E)• Air Outlet Shutter Plates (PAC-SH51SP-E) • Wireless Signal Receiver (PAR-SA9FA-E)• i-see Sensor Corner Panel (PAC-SA1ME-E)• High-efficiency (MERV 10) Filter (PAC-SH59KF-E)Outdoor Unit• M-NET Adapter (PAC-SF80MA-E)• Air Outlet Guide (PAC-SG59SG-E; two pieces are required)• Wind Baffle (WB-PA2; two pieces are required)

generaL FeatUreS• Innovative flash technology enables high heating capacity at lower outside temperatures• Exhibits 100% of rated heating capacity at 5ºF; 90% of rated heating capacity at -4ºF• Built-in drain lift mechanism for condensate removal; lifts up to 33-7/16 in.• Wide air flow pattern for better air distribution; independently adjustable vanes• Auto wave airflow in heating mode—unit independently cycles through horizontal and vertical positions for a more even heat distribution• Self-check function—integrated diagnostics• Hard-wired, wall-mounted, remote controller (PAR-21MAA)• Limited warranty: five years on parts and defects and seven years on

compressors

Dimensions: PLA-A30BA

14-27/3211-3/162-3/8

+5 0

(7.5

)

+35

-5

(160)(5

00)

(950

)

Floor

Min.94-1/2(2400)from floor

Entireperiphery

(36)(83)

(83)

(36) (500)

(950)

(597

)

(597)

( 1

58)

(ø175)(350)

(ø150)

(14-ø2.8)

(167

)(1

55)

(130

)(1

00)(90) (90)

(100) (100)

(35)

(17

)

+3/1

60

(190

)

(156

)(1

05)

(50~

70)

(140

)

(170

)

(377)(284)(60)

(24)

(187.5)(840)

(160)(1

60)

(20~

45)

to 1

-25/

32(8

60~

910)

(620

)

(605

)-3

/16

+1-

3/8

(90)

(150

)(1

60)

(7.5

)

(20 ~

45)

1-25

/32

Corner pocket

In case of wireless remote controllerIn case of standard grilleDrain lift mechanism cleanhole and Drain emergency drainage hole

For MA-Remote controllerterminal block

Emergency operation switch<Cooling>

Emergency operation switch<Heating>

Indoor unit

Ceiling

Cut out hole

Burring hole pitch3-ø1/8(3-ø2.8)Burring hole

Detail drawing of ventilation air intake connection

Burring hole14-ø1/8

Cut out hole

Burring hole pitch

Cut out hole

Detail connecting of branch duct (nominal 6"round or nominal 4 x 14" rectangular)

(77)3-1/32

(85)3-11/32

(298)11-3/411-1/16

(281)

(74)(80)(258)(241)2-29/323-5/3210-3/16

PLA-A36BAPLA-A42BA

PLA-A24BAPLA-A30BA

9-1/2

DCBA2

Refrigerant pipe ····ø15.88mmFlared connection····5/8

Refrigerant pipe ····ø12.7mmFlared connection····1/2

1

Refrigerant pipe ····ø6.35mmFlared connection····1/4

Refrigerant pipe ····ø9.52mmFlared connection····3/8

ModelsPLA-A12BAPLA-A18BA

Min.19-11/16(500)

Grille

Ceiling

Suspension bolt lower edge

Vane motor

Air intake grille

Air outlet hole

Air

outle

t hol

e

Auto vane(Air outlet)

Air

inta

ke h

ole

Air intake hole

GrilleCeiling

Keep 25/64(10)to 19/32(15)between unit ceiling and ceiling slab.

)(Connected the attachedflexible pipe or socket.

Drainpipe connected to1-1/4 in. O.D. PVC tube

Suspension bolt M10 or 3/8

Branch duct hole

Ventilation air intake hole

Branch ducthole

Cei

ling

hole

Sus

pens

ion

bolt

pitc

h

Suspension bolt pitch

Ceiling hole

(5/1

6)(5

/16)

23-1

3/16

24-1

3/32

DEFROST/STAND BY lampReceiverOperation lamp

For wiring replacement kit terminal block

6-5/16

6-5/16

1

2

3-15

/16

5-1/

8

13-25/32

3-17/32

3-15/16 3-15/16

3-17/32

* 6-9

/16

* 6-3

/32

ø5-29/32

ø6-7/8

19-11/16

19-1

1/16

23-1/2

M

M

M

M

3-17/641-27/64

37-3/8

3-17

/64

1-27

/64

37-3

/8

23-1

/2

1-15

/16~

2-3/

4

* 5-

1/2

* 6-

11/16

1-3/

8

11/1

6

* 4-

1/8

* 6-

9/64

* 7-

15/3

2 A

* B

6-5/

16

33-1

/16(

840)

5-29

/32

3-17

/32

C D

33-1/16

7-3/8

25/32 to 1-25/32(20~45)25/32 to 1-25/32(20~45) 33-27/32 to 35-13/16(860~910)

31-7/8(810)

25/3

2 to

33-2

7/32

to 3

5-13

/16

25/3

2

15/1

66-

5/16

Indoor unit/Outdoor unit connecting terminal block

ø4-29/32(ø125)

ø3-15/16(ø100)

6-7/

32 120˚

120˚

**

Note1. Use 1-1/4 in. O.D. (32) PVC TUBE.Drain lift mechanism is included.

2. Suspension bolt, use M10 or W3/8. (Field supplied)

3. Electrical box may be removed for service purposes.Make sure to include a little slack in the electrical wire for control/power wires connections.

4. The clearance between the grille and the unit is adjustable to compensatefor ceiling height.

5. For the installation of the optional high efficiency filter,the optional multi-functional casement is required.1) Add 5-5/16 (135mm) to the dimensions marked with an * in the figures 2) The high ef ficiency filter requires the multi-functional casement.

6. When installing the branch ducts, be sure to insulate adequately.Otherwise condensation may occur.

7. As for necessary installation/service space, please refer to the bottom left figure.

3400 Lawrenceville Suwanee RdSuwanee, GA 30024Tele: 678-376-2900 • Fax: 800-889-9904Toll Free: 800-433-4822 (#3)www.mehvac.comSpecifications are subject to change without notice.C SD - PLA-A30BA / PUZ-HA30NHA - 200810 © MITSUBISHI ELECTRIC / HVAC 2008

Dimensions: PUZ-HA30nHA