Publication SBP200AF-60 Rev. C
(DRAWINGS INCLUDED IN THIS PACKAGE ARE FOR STANDARDCONTROLLERS. ACTUAL “AS BUILT” DRAWINGS MAY DIFFER
FROM THOSE SEEN HERE).
Submittal Package
Remote Alarm Panels For Use With 1-Electric and 1-Diesel Engine Fire Pump Controller
FTA200-AF
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.
3412 Apex PeakwayApex, North Carolina 27502P 919 460 5200F 919 460 5250www.firetrol.com
Project Information
Firetrol Remote Alarm Panelsfor Use With Diesel Engine and Electric Fire Pump ControllersFTA200-A, 200-AA, 200-F, 200-FF & 200-AFSpecifications
1.0 Alarm PanelThe main fire pump controller shall be a factory assembled, wired and tested unit.
1.1 Standards, Listings & ApprovalsThe controller shall conform to all the requirements of the latest editions of:NFPA 20, Standard for the Installation of Stationary Pumps for Fire ProtectionNFPA 70, National Electrical Code.Factory Mutual (FM)
The controller shall be listed by:Underwriters Laboratories, Inc., in accordance with UL508, Standard for Industrial ControlsCanadian Standards Association CSA-C22.2, Standard for Industrial Control Equip-ment (cUL)
1.2 EnclosureThe controller components shall be housed in a NEMA Type 1 (IEC IP20) drip-proof, wall mounted enclosure with bottom entry gland plate.
1.3 OperationThe alarm panel shall have individual LED lights to indicate its alarm condition which shall remain lighted until the alarm condition has been corrected. The alarm panel shall also have an audible alarm which will sound when the alarm conditions occur and may be silenced by pressing a SILENCE ALARM push-button.Each alarm initiation shall be subsequent to any and all previous alarm conditions so that the silence push-button acknowledgment of any one alarm will not prevent the audible alarm from sounding on successive alarm conditions.The alarm panel shall have a PUSH-TO-TEST push-button for manually testing all LED lights, audible alarms and output circuits. All alarm LED’s and push-buttons shall be plainly marked for identification.
1.4 ManufacturerThe alarm panel shall be a Firetrol model FTA200-A for use with electric fire pump controllers, FTA200-AA for use with 2 electric fire pump controllers or model FTA200-F for use with diesel engine fire pump controllers, FTA200-FF for use with 2 diesel en-gine fire pump controllers or a FTA200-AF for use with 1 electric fire pump controller and 1 diesel engine fire pump controller.
Publication SP200-60
3412 Apex PeakwayApex, North Carolina 27502P +1 919 460 5200F +1 919 460 5250www.firetrol.comWhile every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.
Description—Firetrol® FTA200 alarm panels are designed to meet the NPFA 20 speci-fications requiring a remote alarm panel when the pump house or pump room is not constantly attended. The alarm panel must be installed in a location that is un-der supervision at all times.
Approvals—These alarm panels are listed by Underwriter’s Laboratories, Inc., in ac-cordance with UL508, Standard for Indus-trial Controls, certified by CSA, Standard for Industrial Control Equipment (cUL) and approved by Factory Mutual. They are designed to meet or exceed the require-ments of the approving authorities listed above as well as NFPA 20, Installation of Centrifugal Fire Pumps.
Standard Features—The following are in-cluded as standard with each controller:Type A Section - Provides audible and visible alarm indication for the following conditions:• Supervisory Power On (Visible Only)• Power / Phase Failure (Audible and Visible)• Phase Reversal (Audible and Visible)• Motor Trouble (Audible and Visible)• Pump Room Alarm (Audible and Visible)• Pump Running (Audible and Visible)
Type F Section - Provides alarm indication for the following conditions:• Main Switch In Hand or Off (Audible and
Visible)• Controller Trouble (Audible and Visible)• Pump Room Alarm (Audible and Visible)• Engine Trouble (Audible and Visible)• Engine Running (Audible and Visible)
Construction - FTA200 alarm panels make use of printed circuit boards which pro-vide reliable and trouble free service. The enclosures are NEMA Type 1 (IEC IP20) for indoor wall mounting. A bottom entry gland plate is provided in the enclosure. The standard enclosure color is red. Mounted on the enclosure door are the LED lights for visible alarm indication, the SILENCE ALARM push-button and the LAMP TEST push-button. An alarm bell for audible indication is mounted on the side of the enclosure. Each LED will illuminate to indicate its alarm condition and will remain lighted until the abnormal condition has been corrected. The audible alarm will sound when the alarm conditions occur and will continue to sound until the abnormal con-dition has been corrected or the SILENCE ALARM push-button has been pressed. Pressing the SILENCE ALARM push-button will silence the audible alarm but will not extinguish the LED. If another alarm condi-tion occurs the audible alarm will again sound until silenced by the SILENCE ALARM push-button or until the abnormal condi-tion has been corrected. The LAMP TEST push-button is supplied for manually testing the LED’s.
Product Description FTA200-AF
Remote Alarm Panels for use with 1 Electric and 1 Diesel Engine Fire Pump Controller
Publication PD200-62 Rev. A
3412 Apex PeakwayApex, North Carolina 27502P +1 919 460 5200F +1 919 460 5250www.firetrol.comWhile every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.
For Model Number Information and Options & Modifications see Publication SD200-62
FTA NUMBER FTA200
Alarm Panel Type -AF Type AF Alarm Panel (For use with 1 Electric Controller and 1 Diesel Controller
FTA200-AF-__ (Example: FTA200-AF-Y)
Remote Alarm Panels For Use With Electric and Diesel Engine Fire Pump Controllers
Model Number Selection Guide
FTA200-AF
-Q Enclosure, NEMA Type 2 (IP22), Painted Steel
SPECIAL ENCLOSURES DescriptionOption
-EX Enclosure, NEMA Type 4 (IP66), Painted Steel
-FXP Enclosure, NEMA Type 4X (IP66), #304 Stainless Steel, Painted Finish
--- Enclosure, NEMA Type 1 (IP20), Painted Steel
Options & Modifications
-AM Alarm, Audible/Visible, Fail To Start
Optional Alarms - ELECTRIC DescriptionOption
-BY1 Alarm, Audible/Visible, Overcurrent -EJ1 Alarm, Audible/Visible, Flow Meter Open -Y Alarm, Specify Number Of Alarms, Function of Each & Nameplate Marking
-AV Alarm, Audible/Visible, Low Pump Room Temperature
Optional Alarms - DIESEL DescriptionOption
-AW Alarm, Audible/Visible, Reservoir Low -AY1 Configurable Low Suction Pressure Visible/Output Contacts with External Digital Input -AK Alarm, Audible/Visible, Low Oil Pressure -AL Alarm, Audible/Visible, High Water Temperature -AM Alarm, Audible/Visible, Fail To Start -AP1 Alarm, Audible/Visible, Main Switch In Manual -AR Alarm, Audible/Visible, Main Switch In Off -AS1 Alarm, Audible/Visible, Main Switch In Auto -BTC Alarm Output Contacts, Charger #1 & #2 Failure (Form-C, SPDT) -CFC Alarm Output Contacts, Battery #1 & #2 Failure (Form-C, SPDT) -LC Alarm, Audible/Visible, High Fuel Level -LE1 Alarm, Audible/Visible, Fuel Spill -Y Alarm, Specify Number Of Alarms, Function of Each & Nameplate Marking
-F Enclosure, NEMA Type 4X (IP66), #304 Stainless Steel, Brushed Finish
Publication SD200-62 Rev. B
3412 Apex PeakwayApex, North Carolina 27502P +1 919 460 5200F +1 919 460 5250www.firetrol.comWhile every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2019 Firetrol, Inc., All Rights Reserved.
INFORMATION REQUIRED WITH ORDER1) Catalog number of alarm panel.2) Catalog number of controller to be
used with alarm panel.3) Modifications if any.
-BS Fire Pump Start Push-button
Miscellaneous DescriptionOption
-BA AC Input, 220-240V
Dimensions andShipping Weight
Remote Alarm Panels For Use With 1 Electric & 1 Diesel Engine Fire Pump Controllers
FTA200AF
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.For drawing for approval or installation, please contact manufacturer.
TB6-
NTB
6-C
TB5-
NTB
5-C
TB4-
NTB
4-C
TB3-
NTB
3-C
TB2-
NTB
2-C
TB1-
NTB
1-C
J5-2
J5-1
SW1-
5SW
1-4
SW1-
3SW
1-2
SW1-
1 J2-1J2-2
A
AR9-
NC
ON: Bell activated by input
Red
Black
OFF: Input does NOT activate bell
SW1 POSITIONS
MO
TOR
TR
OU
BLE
POW
ER/P
HAS
E FA
ILU
RE
PUM
P R
OO
M A
LAR
M
AR10
-NC
PHAS
E R
EVER
SAL
J5-G
AR11
-C
AR1-
CAR
1-N
CAR
1-N
O
AR12
-NO
TB12
-NTB
12-C
TB10
-CTB
9-N
TB9-
C
TB8-
CTB
7-N
AR2-
C
SW1-
11
SW1-
9
AR2-
NC
SW1-
8
POW
ER O
N
AR2-
NO
AR3-
CAR
3-N
CAR
3-N
OAR
4-C
AR4-
NC
AR4-
NO
AR5-
CAR
5-N
CAR
5-N
OAR
6-C
AR6-
NC
AR6-
NO
AR7-
CAR
7-N
CAR
7-N
OAR
8-C
AR8-
NC
AR8-
NO
AR9-
C
AR9-
NO
AR10
-C
11
AR10
-NO
14 12
AR11
-NO
AR11
-NC
AR12
-CAR
12-N
C
TB11
-N
MAI
N S
WIT
CH
IN
TB7
TB11
-CTB
10-N
TB8-
N
TB7-
C
SW1-
10
SUPE
RVI
SOR
Y
SW1-
7
4
Power Supply
ELECTRIC
ALARM PANEL ELECTRIC &
SUPERVISORY
DIESEL FIRE PUMPS
REVERSAL
POWER ON
LAMP TEST
PHASE
SILENCE
MOTOR
TROUBLE
TROUBLE
CONTROLLER
DIESEL PUMPRUNNING
MAIN SWITCH INHAND OR OFF
ENGINETROUBLE
DIESEL FIRE PUMP CONTROLLER
TB1
11
ENG
INE
TRO
UBL
E
TB6
ENG
INE
RU
N
1111
(Fai
l saf
e re
lay)
CO
NTR
OLL
ER T
RO
UBL
E
1414
11
14
CO
NTR
OLL
ER T
RO
UBL
E
RU
NN
ING
PUMP ROOMALARM
ENG
INE
TRO
UBL
E
ELECTRIC FIRE PUMP CONTROLLER
POW
ER A
VAIL
ABLE
(Fai
l saf
e re
lay)
TB2TB1
PHAS
E R
EVER
SAL
PUM
P R
OO
M A
LAR
M
MO
TOR
TR
OU
BLE
TB4
11 1111
TB3
14 14
11
12 14
MO
TOR
RU
N
11
14
TB2
PUM
P R
OO
M A
LAR
M
MAI
N S
WIT
CH
IN
HAN
D O
R O
FF
RU
NN
ING
PUM
P R
OO
M A
LAR
M
POWER / PHASEFAILURE
HAN
D O
R O
FF
ELECTRIC PUMP
PUMP ROOM
RUNNING
ALARM
MOTOR RUN
DIESEL
TB5
120Vac or220-240Vac
Dipswitch Selected(SW4)
SW4
SW4 POSITIONS120V: 120Vac240V: 220-240Vac
DIE
SEL
PUM
P
ELEC
TRIC
PU
MP
NOTES :: Internal Terminals
-Wire Size :-Torque :
-Type :-Wire Size :-Torque :
-Wire Size :-Torque :
- Power Supply :
- Alarm Contact :
- Field Connections :
12-24 AWG0.4Nm
SPDT14-24 AWG0.4Nm
12-22 AWG0.4Nm
: Related Controller Terminals-Wire Size :-Torque :
- Field Connections : 12-24 AWG0.5Nm
APPROVALFINAL
DRAWN BY
BY DATEECN NO
ECNNO
SIZE
DRAWING NUMBER
DWGREV
A REV
SHEET OF
BY APP DATEREVISION DESCRIPTION
PROJECTIONTHIRD ANGLE
© Firetrol, Inc. Not for construction.Subject to change without notice.
WS200AF-60- - 1 1
CIR 11-5-19
CIR 11-5-19
RELEASED - - CIR CIR 11-5-19
Wiring SchematicField Connections
Remote Alarm Panels For Use With 1 Electric & 1 Diesel Engine Fire Pump Controllers
FTA200AF