STRUCTURAL CALCULATION
SUSPENDED BRIDGE
7/27/2019 Suspended Bridge
2/23
PEDESTRIAN SUSPENDED BRIDGE
7/27/2019 Suspended Bridge
3/23
TABLE OF CONTENTS
1.1 INTRODUCTION 2
1.2 ARCHITECTURAL INPUTS 2
1.3 LOAD ANALYSIS 4
1.3.1 CONSTANT LOAD 4
1.3.2 LIVE LOAD 4
1.3.3 ACCIDENTAL LOAD 4
1.3.4 WIND LOAD 4
1.3.5 LOAD COMBINATIONS 4
1.4 STRUCTURAL DESIGN 5
1.4.1 SUSPENDERS 5
1.4.2 HANDRAIL 6
1.4.3 MAIN CABLES 7
1.4.4 DECKING 11
1.4.5 CROSS BEAMS 13
2. CONNECTIONS 14
2.1 TOP SUSPENSION ROPE CONCRETE COLUMN 14
2.2 HANDRAIL CONCRETE COLUMN 15
2 3 BOTTOM SUSPENSION ROPE CONCRETE COLUMN 16
7/27/2019 Suspended Bridge
4/23
Pedestrian Suspension Bridge1.1 INTRODUCTIONThe span for pedestrian suspended cable bridge is 20,7m divided in 10 parts. Bridge walkable width is80 cm. Referenced floor level is 140.70 but in middle of span level of horizontal suspension cable is
0.5m lower. Top suspension cables are attached to concrete columns 900x20cm on elevation 143.30mnm.
1.2 ARCHITECTURAL INPUTS
7/27/2019 Suspended Bridge
5/23
Pedestrian Suspension Bridge
7/27/2019 Suspended Bridge
6/23
Pedestrian Suspension Bridge1.3 LOAD ANALYSIS1.3.1 CONSTANT LOAD
Assumptions/Conversions Loading
SuspendersGERRO16-B (or equivalent)
SL1 2,5m 4 pcs
SL2 1,8m 4 pcs
SL3 1,5m 4 pcs
SL4 1,2m 4 pcs
SL5 1,1m 2 pcs
Weight: insignificant
Cross beams PFCH 100x50x10mm, L= 1000mm
(11 pcs)
Weight: 0,102 KN/m
Weight: 1.122 kN
Decking
4 cm x 75 cm x 210 cm,
V1 = 0.063 m (10pcs), V10=0,63m3
Decking area: 15,52 m2
Timber, assume 9,5 KN/ m
15.52m2
0,38 5,89KN
Total: 5,89KN
Cables12 mm 7x19 Stainless Steel Wire,
W i ht i i ifi t
7/27/2019 Suspended Bridge
7/23
Pedestrian Suspension Bridge
1.4 STRUCTURAL DESIGN
1.4.1 SUSPENDERSSuspenders transfer the loads from the deck to main cables, and are attached to crossbeamsat 2 meter intervals. Thus, with a 0,80 meter deck width, each suspender has a tributary area of2x0,4=0.8 m, Comb 1 =5,49 KN/m
2and thus must be able to carry 4.39 KN.
According manufacturer specifications for above analyzed loads and conditions,
GC16-B, GC16-BK and rope GC16-R (or equivalent) is recommended for suspenders and fittings.
GERRO COMBI Combination Rope consists of a combination of steel and fibre rope.
Steel wire strands covered with Polypropylene (PP) multifilament. Minimum tensile strength of wire: Galvanized 160 kp/mm=1570 N/mm. Different colours are available; red, blue, green, yellow, black and also
as a mix of these.
7/27/2019 Suspended Bridge
8/23
Pedestrian Suspension Bridge1.4.2 HANDRAIL
7/27/2019 Suspended Bridge
9/23
Pedestrian Suspension Bridge1.4.3 MAIN CABLESFor calculation of internal cable forces it was made realistic model of bridge.Bridge span is 20,7m separated into 10 parts, each part lenght is 2,07m.
Cables are wire rope
1
12mm 7x19 timber cross-beams are 100x100mm and decking plates height is 40 mm.GEOMETRY
7/27/2019 Suspended Bridge
10/23
Pedestrian Suspension Bridge
LOADS
Dead Load
7/27/2019 Suspended Bridge
11/23
Pedestrian Suspension Bridge
Wind load
7/27/2019 Suspended Bridge
12/23
Pedestrian Suspension Bridge
RESULTS
Comb 1: Axial force in cable
7/27/2019 Suspended Bridge
13/23
Pedestrian Suspension Bridge
Top suspension rope:
Max Fx1=70.83KN
7x19 steel rope
MBL - Minimum Break Load= The stress which, when steadily applied to a structural member, is just sufficientto break or rupture it. Also known as ultimate load.
SWL - Safe Working Load= Briefly defined, the 'safe working load' of a line is the load that can be applied withoutcausing any kind of damage to the wire rope. In manufacturer table above safety factor is 6.
According manufacturer specifications2
and for above analyzed loads and conditions,12mm 7x19 Stainless Steel Wire Rope (or equivivalent) is recommended for top suspension cable.
7/27/2019 Suspended Bridge
14/23
Pedestrian Suspension Bridge
TIMBER STRUCTURE CALCULATIONS-------------------------------------------------------------------------------------------------------------------CODE: EN 1995-1:2004/A1:2008
ANALYSIS TYPE: Member Verification-------------------------------------------------------------------------------------------------------------------CODE GROUP:MEMBER: Timber Plank-------------------------------------------------------------------------------------------------------------------LOADS:Governing Load Case: 5 COMB 1 1*1.40+2*1.60-------------------------------------------------------------------------------------------------------------------
7/27/2019 Suspended Bridge
15/23
Pedestrian Suspension Bridge1.4.5 CROSS BEAMSFloor load: 5,49KN/m
2, Tributary area length = 2,07m
Cross beam load: 11,36 KN/m
Moments: Mmax=(q*L2)/8=11,36*1
2/8=1,42 KNm
STEEL DESIGN-------------------------------------------------------------------------------------------------------------------CODE: British Standard BS 5950:2000ANALYSIS TYPE: Member Verification-------------------------------------------------------------------------------------------------------------------CODE GROUP:MEMBER: Pedestrian bridge cross beam PFCH 100x50x10
S
7/27/2019 Suspended Bridge
16/23
Pedestrian Suspension Bridge
2. CONNECTIONS
2.1 TOP SUSPENSION ROPE CONCRETE COLUMN
The tensile cable force is 70,83 KN.
Anchors are compound by U shaped steel bar S235; Tensile load is dissipated to 4 bars. As-
sumption is that load dissipation is asymmetrical (ratio 2:3).
The largest computational load per pair of bars is L=70.83 x(2/3) = 47,22 KN
Steel properties: S=235 MPa=0,235 KN/mm2
Bar section area: 47,22/0,235=200,9 mm2
For anchors is recommended to install
4 steel bars (S235), diameter 14mm. Bars are prepared and fixed in right position before con-
creting of column.
P d t i S i B id
7/27/2019 Suspended Bridge
17/23
Pedestrian Suspension Bridge
2.2 HANDRAIL CONCRETE COLUMN
Pedestrian Suspension Bridge
7/27/2019 Suspended Bridge
18/23
Pedestrian Suspension Bridge2.3 BOTTOM SUSPENSION ROPE CONCRETE COLUMN
Pedestrian Suspension Bridge
7/27/2019 Suspended Bridge
19/23
Pedestrian Suspension Bridge
2.5 SUSPENDERS HANDRAIL ROPE
GERRO GC16-C
2.6 SUSPENDERS - CROSS BEAMS
Pedestrian Suspension Bridge
7/27/2019 Suspended Bridge
20/23
Pedestrian Suspension Bridge
3. QUANTITIES OF MATERIALS
POS DESCRIPTION UNITS TOTAL
1 Supports in concrete wall
Fittings anchored into columns
Fork tensioner wire rope assembly
pcs 6
2 Suspenders, GERRO GC16-R (or equivalent)
SL1 2,02m
SL2 1,61m
SL3 1,31m
SL4 1,15m
SL5 1,10m
pcs4 pcs
4 pcs
4 pcs
4 pcs
2 pcs
3Main Cables: 12 mm 7x19 Stainles Steel
CL1 21,08 m
CL2 20,58 m
pcs
2pcs
2pcs
4Handrails: GERRO GC16-R (or equivalent)
HL1 20,68 mpcs 2pcs