Top SecretSecret
Internal use onlyPublic
Water FancoilsWater Fancoils –– service presentationservice presentation
FWT-FWF-FWC FWT-FWF-FWC
2Apr 21, 2023
Internal Use Only Content
Fancoil Product List FWT,FWC,FWF – slide 3
Product PCB Features W2 pcb types – slide 11
PCB Features detail – slide 18
General operation – slide 33
Handsets and controllers – slide 84
PCB connections – slide 108
Water valves – slide 121
Diagnostics – slide 134
Content
3Apr 21, 2023
Internal Use Only
Model OYL Daikin
Wall Mounted
WM07GW-AXAC-R56
FWT02
WM10GW-AXAC-R56
FWT03
WM15GW-AXAC-R56
FWT04
WM20GW-AXAC-R56
FWT05
WM25GW-AXAC-R56
FWT06
Indoor Wall Mounted
FCU Product List
4Apr 21, 2023
Internal Use Only
Model Cooling Capacity
(kW)
Heating Capacity (kW)
FWT02 2.3 3.0
FWT03 2.8 3.75
FWT04 3.2 4.1
FWT05 4.8 6.01
FWT06 5.3 6.74
2 Pipes Application
FCU Product List
Indoor Wall Mounted FWT
5Apr 21, 2023
Internal Use Only
Model OYL Daikin
2 P
ipes
3 x 3 Ceiling Cassette
CK20AW-AXBE-R56 FWC07
CK25AW-AXBE-R56 FWC08
CK30AW-AXBE-R56 FWC10
CK40AW-AXBE-R56 FWC11
CK50AW-AXBE-R56 FWC12
Panel PLCKAW-G8 HEAT-R56
DCP900 TA/TB
4 P
ipes
3 x 3 Ceiling Cassette
CK20AWH-AXAA-R56 FWC02
CK25AWH-AXAA-R56 FWC03
CK30AWH-AXAA-R56 FWC04
CK40AWH-AXAA-R56 FWC05
CK50AWH-AXAA-R56 FWC06
Panel PLCKAWH-G8 AP-R56 DCP900 FA/FB
Indoor Ceiling Cassette
FCU Product List
6Apr 21, 2023
Internal Use Only
Model Cooling Capacity
(kW)
Heating Capacity (kW)
FWC07 6.63 8.4
FWC08 7.5 9.5
FWC10 8.8 11.0
FWC11 9.95 12.0
FWC12 10.8 12.9
2 Pipes Application
FCU Product List
Indoor Ceiling Cassette FWC
7Apr 21, 2023
Internal Use Only
Model Cooling Capacity
(kW)
Heating Capacity (kW)
FWC02 3.8 10.5
FWC03 4.0 11.0
FWC04 4.6 12.5
FWC05 5.0 13.5
FWC06 5.2 13.8
4 Pipes Application
FCU Product List
8Apr 21, 2023
Internal Use Only
Flexibility in selecting and installation.
Built-in high drain pump.
FCU Product List
9Apr 21, 2023
Internal Use Only
Model OYL Daikin
2 P
ipes
2 x 2 Ceiling Cassette
CK10CW-AXBE-R56 FWF02
CK15CW-AXBE-R56 FWF03
CK20CW-AXBE-R56 FWF04
Panel PLCKCW-G8 HEAT-R56
DCP600 TA/TB
Indoor Ceiling Cassette FWF
FCU Product List
10Apr 21, 2023
Internal Use Only
Model Cooling Capacity
(kW)
Heating Capacity (kW)
FWF02 2.34 3.22
FWF03 4.1 5.12
FWC04 4.25 5.42
2 Pipes Application
FCU Product List
Indoor Ceiling Cassette FWF
Top SecretSecret
Internal use onlyPublic
ProductProduct FeaturesFeatures
12Apr 21, 2023
Internal Use Only
All chilled water FCUs are using W2 control algorithm (W2 PCB). Hardware wise there are three types of pcb’s:
FWT 2 pipe - version
FWF 2 pipe, FWC 2pipe – version (are identical)
FWC 4 pipe - version
Despite the software used is the same on all fancoil types, the hardware of the pcb’s is unique for the three types of fancoils ,according the model some functions of the “W2” algorithm will be available or not .
FCU Features
13Apr 21, 2023
Internal Use Only W2 PCB types
FWT pcb location (only two pipe) (mentioned pic is valid for FWT02-03-04, for FWT05/06 pcb layout is slightly different but all connections and connector names are the same)
14Apr 21, 2023
Internal Use Only W2 PCB types
FWF pcb location (exist only in two pipe version)
15Apr 21, 2023
Internal Use Only W2 PCB types
FWC pcb location
16Apr 21, 2023
Internal Use Only W2 PCB types
FWC-T (two pipe version)
17Apr 21, 2023
Internal Use Only W2 PCB types
FWC-F (four pipe version)
18Apr 21, 2023
Internal Use Only FCU Features
(*) = possible (-) = not present
(a) Auto mode i.e. automatic selection of cool or heating mode based on the difference of the T setpoint and T room, is only possible with 4-pipe system and pcb configured as model 3, this means one coil is connected to a cold water system and the second coil to a hot water system.
(b) On the pcb’s of the 4-pipe fancoil cassettes the model “selection” of the pcb can be choosen between model 3 and 4 by means of a jumper. On the two pipe versions the pcb comes standard as a model 1 and no selection is to be made.
(c) The delay timer up to 15 hrs is only in combination with the wired controller SRC. On units with WRC or MERCA the internal
clock of the controller is used for timer functionality
W2 pcb features
19Apr 21, 2023
Internal Use Only Features detail
PCB Model selection On the pcb’s of the four pipe versions (FWC 02~06) some model selection is possible in order to
activate some features of the pcb. All two pipe versions pcb’s come standard as model 1, and should not be changed! Model 2 is not valid for water fancoils.
Model selection is done via jumpers on the pcb, for fwt no selection jumpers are present. The fwf and fwc two pipe versions are factory wise configures as model 1, don’t change!Model 1 makes heating and cooling possible, no auto mode. Model 2 is not used for Daikin units
20Apr 21, 2023
Internal Use Only
PCB Model selection - differences
– Model 3, with auto mode, this 4 pipe application requires one coil connected to cold water second coil should be connected to warm water. System will automatically activate the coils in order to achieve correct room temperature independant from selected working mode.
– Model 3 without auto mode, this is in fact standard 4 pipe functioning of the fcu, meaning one coil used for cooling and one coil for heating. Coil is selected depending on selection of heating or cooling by the user.
– Model 4, in this mode one coil is considered cool/heat (thus must me connected to heatpump system. Second coil is a booster coil which is activated when water from first coil is not hot enough. This is a not so common application
21Apr 21, 2023
Internal Use Only Features detail
PCB Model selection 4 pipesdifferences between model 3 and model 4
For model 4 it’s important that primary coil Tc is connected to “heatpump” system in other words a system that can supply hot or cold water depending season. Second coil is booster coil and only used under certain conditions. Model 3 has always one cool coil and one heating coil.
Coil 1 (Tc)
Coil 2 (Tb)
Coil 2 (Tb)
Coil 1 (Tc)
booster
22Apr 21, 2023
Internal Use Only Features detail
PCB Model selection
FWC – 4 pipe selection between model 3 and 4
Jumper open = activate model !
Exampl.= model 3 , put jumper on M4!
From factory fwc 4 pipes are standard configured as model 4!
The model 3 selection on FWC 4 pipes basically activates the socalled Auto mode,This needs the pressence of hot and cold water at the same time in the coils of the fcu .If wired controller is used, also jumper configuration in the wired controller needed.
23Apr 21, 2023
Internal Use Only Features detail
Auto Mode – model 3 only (FWC – 4 pipe) one coil is connected to cold water one coil to hot water connected. Note: in case the wired controller Merca is used, it needs to be configured for “Auto mode”
During Auto heat mode, when room temperature rises and equals to the cool switch point, system will automatically switch to Auto cool mode. If room temperature falls down and reaches heat switch pointsystem will again change to Auto heat mode.
Switchpoints :
Cool switch point = T setpoint + 1°C
Heat switch point = T setpoint – 1°C
Auto HeatAuto Heat Auto CoolAuto Cool Auto HeatAuto Heat
TsTs
Ts + 1°CTs + 1°C
Ts - 1°CTs - 1°C
24Apr 21, 2023
Internal Use Only Features detail
Auto Mode config – Merca pcb (wired controller) jumper selection , configuration of jumpers needed on pcb of wired controller Merca, For the wireless WRC controller no configuration needed!
25Apr 21, 2023
Internal Use Only Features detail
Bar Heat mode setting – valid for all types of pcb.
On every pcb it’s possible to disable the heating function.This can be interessting for creating a cooling only system, and to avoid heating selection from the remote or wired control to avoid wrong temperature control.
FWF - FWC
FWT
Jumper HEAT:
Open : No heating selectable on control (remote or wired)
Short : Heating mode enabled
26Apr 21, 2023
Internal Use Only Features detail
FAN PRIO setting - not possible on FWT pcbThis feature configures the behaviour of the fan during thermostat off cycle in other words when the watervalve is closed because setpoint has been reached (valid for auto fan or manual selection of fanspeed). Note that for valveless application this function is invalid and cannot be used, jumper must be shorted! . In FAN mode, this function will NOT influence the behaviour of the fan.
FWF
FWC
FWT, Fan prio feature not possible, fan will always run on low or in super low speed even in thermostat off cycle. Note super low speed stands for interval on/off of the fan during 5 minutes
Jumper Fan_P:
Open : Fan stops when thermostat off (valve off)
Short : Fan keeps running according manual selected or in low speed if auto fan was selected
27Apr 21, 2023
Internal Use Only Features detail
Valve – Valveless selection - all pcb’sAll pcb’s can be configured by means of a jumper on the pcb for operating with or without watervalve. Actual temperature control of fancoil will differ between valve or valveless operation.
FWF - FWC
FWT
Jumper VALVE:
Open : without watervalve
Short : with watervalve
28Apr 21, 2023
Internal Use Only Features detail
Load shedding – only FWC 4 pipe pcb not for FWF/FWT – FWC 2 pipe
This feature, when active will close the valve and stop the fan. The function is activated by closing a dry contact connected to the SHED terminal on the pcb. Actually the unit goes into stanby mode, control of the drainpump remains active. Note that the antrifreeze feature can override an active load shed function. This function allows “hardwired” enabling standby mode from remote eg by BMS system.
Dry contact SHED:
Open for 5 sec : deactivate load shedding
Close for 5 sec: activate load shedding
FWC
Note: on socalled dry contacts no exterrnal voltage should be apllied. The voltage (5V dc) is supplied by the pcb. Dry inputs are activated by simply closing a hardwired contact, eg from external relais controlled by an centralized control system.
29Apr 21, 2023
Internal Use Only Features detail
Window open – only for FWC 4 pipe pcb not for FWF/FWT/FWC-2pipe
This feature when active will only close the water valve, the fan of the unit will run according FAN_prio setting which means if unit is thermostat on cycle mode the fan will keep runing
Dry contactW-open
Jumper FAN_P Thermostat off cycle Thermostat on cycle
Closed for 30 seconds
open Water valve closedfan off
Water valve closedFan on according temp difference (T room – Tset)
Closed for 30 seconds
shorted Water valve closedFan according user set speed OR low speed when unit was in auto fan mode
Water valve closedFan according user set speed OR
Fan on according temp difference (T room – Tset) in auto fan mode.
FWC 4 – pipe
30Apr 21, 2023
Internal Use Only Features detail
Preprogrammed Unoccupied Setpoints - only for FWC 4 pipe not for FWF/FWT/FWC-2pipe
The fancoil can be forced to run at fixed setpoints under COOL or HEAT mode in order to save energy when for eg the room is not occupied. This function is activated by means of a dry contact.
Dry contactUNOCP
COOL mode HEAT mode
Closed for 5 seconds
Setpoint will be fixed at 30°C Setpoint will be fixed at 14°C
Open for 5 seconds
Go back to normal mode Go back to normal mode
FWC 4 – pipe
Override function: the user can override the unoccupied mode by changing the setpoints by means of the wireless controller or wired controller, override function will be valid for two hours.
31Apr 21, 2023
Internal Use Only Features detail
Preprogrammed anti freeze setpoints – only for FWC 4 pipe not for FWF/FWT/FWC-2pipe
In order to protect the room from freezing, the unit will forced to achieve a room temperature of 10°C when function is activated by means of a dry contact. This function is only availabele when unit is working in HEAT mode.
Control algoritm:
Tr < 7.25°C?No
Yes
OFF mode or Thermostat off
cycle
Force ON 2 minutes
Indoor fan > force to Low fan
Tc > 25°C? Tr > 10°C?Stop 9
minutesOn valve, Low fan
No Yes
Yes
No
Tr = temp room
Tc = coil temp
32Apr 21, 2023
Internal Use Only Features detail
Preprogrammed anti freeze setpoints
W2 (1)A_FRZ
W2 (2)A_FRZ
W2 (n)A_FRZ
SWGlobal
A_FRZ
Switch
Dry contact A_FRZ:
Open for 5 sec : deactivate anti freeze mode
Close for 5 sec: activate anti freeze mode
FWC 4 – pipe
Top SecretSecret
Internal use onlyPublic
General operationGeneral operation
34Apr 21, 2023
Internal Use Only
Unit ON/OFF
Power up settings / Auto random restart
Sleep function
Fan Speeds Auto/ High/ Medium/ Low indoor fan speed control
Room Temperature sensing
Water Pipe water sensing (2 & 4 pipe systems)
Cool/ Heat/ Dry*/ Auto*/FAN - Modes
Real time clock, ON/OFF timer
Valve and valve less control options
Water pump and water overflow protection control
Built in Self Diagnostic
General Operation
35Apr 21, 2023
Internal Use Only
Unit On/OFF– Via On/Off triggering
– Via delay timer
– Via real time On/Off timer
1. Via ON/OFF Triggering
Pressing the remote controller ON/OFF button will toggle either the system
status from ON to OFF or from OFF to ON.
2. Via delay timer (only for SRC simple wired controller)This delay timer (1 to 15 hrs) will simulate the ON/OFF pressing, after a setting of hours and minutes into the delay function. After delay time has been elapsed it will be set back to 0 hours. Delay timer is reset by pressing ON/OFF button.
3. Via real time ON/OFF timer (only in combination with Merca and WRC)Unit can be switched ON/OFF by programming real time ON and OFF switch points into the rtc timer. Timer settings are retained so that switching can occur each 24 hrs.
General operation
36Apr 21, 2023
Internal Use Only
Power Up Settings / Auto Random restart
During power up, system is setup to memorize the settings prior to shutdown (= standard factory setting)
The memorized settings are:
* Mode & On/Off status* Setpoints* Fan speeds* Swing flap function
To disable Auto Memorized function remove shorted jumper J_LST at the main board
General Operation
37Apr 21, 2023
Internal Use Only
J_LST
Auto Random Restart (memorization) for all pcb’s
Jumper J_LST:
Open : No memorization
Short : memorization active (standard factory setting)
General Operation
38Apr 21, 2023
Internal Use Only
Power UpPower Up
J_LST <SHORT>J_LST <SHORT>
User Set ModeUser Set Mode
User Set TemperatureUser Set Temperature
User Set Fan SpeedUser Set Fan Speed
Mode = COOLMode = COOL
Set Temperature = 24˚CSet Temperature = 24˚C
ID Fan Speed = HIGHID Fan Speed = HIGH
Swing Mode = OFFSwing Mode = OFF
ON/OFF statusON/OFF status
J_LST <OPEN>J_LST <OPEN>
Auto Random Restart, valid for all pcb’s
General Operation
39Apr 21, 2023
Internal Use Only
Sleep Function Only available in COOL and HEAT modes. This function will increase temperature
setpoint (COOL mode) or decrease temperature setpoint (HEAT mode) according certain fixed time shedule.
General Operation
SLEEP set onSLEEP set on SLEEP set offSLEEP set off
TsTsTs + 1/2Ts + 1/2
Ts + 1Ts + 1
Ts + 2Ts + 2
00 1/21/2 11 22HoursHours
COOL mode
40Apr 21, 2023
Internal Use Only
HEAT mode
SLEEP set onSLEEP set on SLEEP set offSLEEP set off
TsTs
Ts - 3Ts - 3
Ts - 2Ts - 2
Ts - 1Ts - 1
00 1/21/2 11 22 HoursHours
Sleep function
General Operation
41Apr 21, 2023
Internal Use Only
FAN Speed Control:
– 3 indoor fan speeds are available, manually selectable :-
- High
- Medium
- Low
– In Auto fan mode, the fan speed will run depending on the difference between room/ return air temp and the set point temp.
– For valve less configuration, additional ‘super’ low fan speed is created. This is a interval mode of the fan, 5min On – 5min OFF
General Operation
43Apr 21, 2023
Internal Use Only
Pipe Temperature Sensing:
General Operation
NTC
NTCT° coilMounted on coil
NTC
NTC
NTC
T° roomMounted in airintake section of fcu
2 -pipe
4 -pipe
Tc° cool coilMounted on coil
Tb° Heat coilMounted on coil
T° roomMounted in airintake section of fcu
• For model 3 fcu, second coil is considered as primary heating coil.
•For model 4, second coil is considered as a booster, first coil is considered as primary cool + heat coil.
44Apr 21, 2023
Internal Use Only
Pipe Water Temp. Sensing
At startup of the fcu unit, water temperature in the coil(s) will be checked before going into so called thermostat control. The coil sensor Tc is used for this purpose .Tb refers to second coil which is considered as booster coil (model 4) or heating coil for (model 3) fcu.
Temperature test is performed during:
a) Power ON reset and unit is turned ON
or
b) Mode change
or
c) Unit recover from faults
The applied test procedure depends on presence of a valve and on the selected mode (COOL or HEAT)
General Operation
45Apr 21, 2023
Internal Use Only
9 mins elapsed?
9 mins elapsed?
2 mins confirm?
2 mins confirm?
Check TrCheck Tc Check Tc
Enter into cooling thermostat cycle
14°C < Tr < 47°C
Tc < Tr + 2°C
(Force valve to ON)
Force On (Valve) 2 mins User set speed indoor fan.
If Auto fan -> low fan
Others
(Force valve to ON)
No No
Yes Yes
NoNo
(Force valve OFF 9 mins)Yes Yes
(Force valve OFF 9 mins)
Tc > Tr + 3°C(Water not suitable)
Tc > 30°C(Water not suitable)
With Water Valve – Cooling – 2 pipe
Tc < 29°C
General Operation
Only when room temp is very high > 47°
46Apr 21, 2023
Internal Use Only
With Water Valve – Cooling – 2 pipe
After starting/power-up the unit, the water alve will be opened and fan will be forced to low speed during 2 minutes (allow coil to cool down, after opening of the valve) . After these 2 minutes, unit goes into a 2 minutes temperature check procedure, in case AUTO FAN was selected fan will now run with speed depending on the difference between T room and T setpoint.
If after these 2 minutes (sensing coil temperature) temperature is not suitable (Tc>Troom+3°) valve will be closed and fan will be run on low speed for 9 minutes.If fan prio jumper is open fan will stop completely.
When these 9 minutes are elapsed, unit will again perform first the two min force valve open / low fan mode and then the two minute sensing test unitil the coil temperature is cold enough. Note that no errors will be displayed in valve mode if temperature is not ok! As long the temp is not ok unit will stay in the 2+2 min On / 9 min OFF loop.
Remark: during first start-up depending of the mode (cool or heat) a cold or hot start will be considered by the pcb’s software. This means actual setpoint will be offset internally with +2°for heat mode and -2°for cooling. After 20 minutes these offsets are reset and set point becomes again equal to selected value on the controller
General Operation
47Apr 21, 2023
Internal Use Only
9 mins elapsed?
9 mins elapsed?
2 mins confirm?
2 mins confirm?
Check TrCheck Tc Check Tc
Enter into heating thermostat cycle
14°C < Tr < 47°C
(Force valve to ON)
Force On (Valve) 2 mins User set speed indoor fan.
If Auto fan -> low fan
Others
(Force valve to ON)
No No
Yes Yes
NoNo
(Force valve OFF 9 mins)Yes Yes
(Force valve OFF 9 mins)
Tc < Tr - 3°C(Water not suitable)
Tc < 25°C(Water not suitable)
With Water Valve – Heating 2 pipe
Tc > Tr + 3°C Tc > 30°C
General Operation
Only when room te^p is very low < 14°
48Apr 21, 2023
Internal Use Only
With Water Valve – Heating – 2 pipe
After starting/power-up the unit the water valve will be opened and fan will be forced to low speed during 2 minutes (allow the coil to heat up). After these 2 minutes, unit goes into 2 minutes temperature check procedure, in case AUTO FAN was selected fan will now run with speed depending on the difference between T room and T setpoint.
If after 2 minutes (sensing coil temperature) temperature is not suitable (Tc < Troom-3°) valve will be closed and fan will run on low speed for 9 minutes. In case fan prio jumper is open fan will stop completely.
When these 9 minutes are elapsed, unit will again perform first the two min force valve open / low fan mode and then the two minute sensing test unitil the coil temperature is warm enough. Note that no errors will be displayed in valve mode if temperature is not ok! As long the temp is not ok unit will stay in the 2+2 min On / 9 min OFF loop.
Remark: during first start-up depending of the mode (cool or heat) a cold or hot start will be considered by the pcb’s software. This means actual setpoint will be offset internally with +2°for heat mode and -2°for cooling. After 20 minutes these offsets are reseted and setpoint becomes again equal to selected value on the controller.
General Operation
49Apr 21, 2023
Internal Use Only
9 mins elapsed?
9 mins elapsed?
2 mins confirm?
2 mins confirm?
Check TrCheck Tc Check Tc
Enter into cooling thermostat cycle
14°C < Tr < 47°C
Tc < Tr + 2°C
(Force valve to ON)
Force On (Valve) 2 mins User set speed indoor fan.
If Auto fan -> low fan
Others
(Force valve to ON)
No No
Yes Yes
NoNo
(Force valve OFF 9 mins)Yes Yes
(Force valve OFF 9 mins)
Tc > Tr + 3°C(Water not suitable)
Tc > 30°C(Water not suitable)
With Water Valve – Cooling – 4 pipe (model 4)
Tc < 29°C
General Operation
Only when room temp is very high > 47°
50Apr 21, 2023
Internal Use Only
With Water Valve – Cooling – 4 pipe (model4)
After starting/power-up the unit, the water valve C_VLV will be opened and fan will be forced to low speed during 2 minutes (allow coil Tc to cool down, after opening of the valve) . After these 2 minutes, unit goes into a 2 minutes temperature check procedure, in case AUTO FAN was selected fan will now run with speed depending on the difference between T room and T setpoint.
If after these 2 minutes (sensing coil temperature) temperature is not suitable (Tc>Troom+3°) valve will be closed and fan will run on low speed for 9 minutes. In case fan prio jumper is open fan will stop completely.
When these 9 minutes are elapsed, unit will again perform first the two min force valve open / low fan mode and then the two minute sensing test unitil the coil temperature is cold enough. Note that no errors will be displayed in valve mode if temperature is not ok! As long the temp is not ok unit will stay in the 2+2 min On / 9 min OFF loop.
Remark: during first start-up depending of the mode (cool or heat) a cold or hot start will be considered by the pcb’s software. This means actual setpoint will be offset internally with +2°for heat mode and -2°for cooling. After 20 minutes these offsets are reset and set point becomes again equal to selected value on the controller
General Operation
51Apr 21, 2023
Internal Use Only
9 mins elapsed?
9 mins elapsed?
2 mins confirm?
2 mins confirm?
Check TrCheck Tc Check Tc
Enter into heating thermostat cycle
14°C < Tr < 47°C
(Force valve to ON)
Force On C_VLV, Valve, 2 mins User set speed indoor
fan. If Auto fan -> low fan
Others
(Force valve to ON)
No No
Yes Yes
NoNo
(Force valve OFF 9 mins)Yes Yes
(Force valve OFF 9 mins)
Tc < Tr - 3°C(Water not suitable)
Tc < 25°C(Water not suitable)
With Water Valve – Heating 4 pipe (model 4)
Tc > Tr + 3°C Tc > 30°C, no booster
Tr-2°C < Tc < Tr + 2°C
Use booster (2nd coil)
26°C < Tc < 29°C
Use booster (2nd coil)
General Operation
Only when room temp is very low < 14°
52Apr 21, 2023
Internal Use Only
With Water Valve – Heating – 4 pipe (model 4)
If after 2 min. force low fan, valve C_VLV will open, pcb will go into 2 minutes water temp. mode (sensing coil temperature Tc of first coil) if temperature is not suitable (Tc <Troom - 3) C_VLV valve will be closed and fan will run on low speed for 9 minutes. In case fan prio jumper is open fan will stop completely.
When these 9 minutes are elapsed, unit will again perform the two + two minute temp sensing test until the coil temperature is hot enough.
Note that after the Hot start time has been elapsed (20 min) the unit will (can) start to check second coil Tb (booster) in case water on first coil is still to cold. First a simular 2+2 min temp check will be performed on the booster coil.If booster temp is not ok, it will be forced off for 5 minutes.
If Tb > 28°C and Tb > Tr +5° boiler will be used. Booster will run only for 9 minutes, after this, system will again perform 2+2 min tempt test on coil one (Tc)!
This sequence will be repeated until water temp on coil Tc is hot enough, as this is the primary heating coil!
From moment the water in first coil (Tc) is hot enough thus Tc > Tr + 3,the booster coil will again be closed by the H_VLV valve.
Only circomstance where both coils could be active is when Tc is close to room temperature in this case both coils will be used for heating until temperature on Tc > Tr + 3C . In This case unit works in thermostat control mode and will follow temp control algorithm valid for thermostat control.
General Operation
53Apr 21, 2023
Internal Use Only
With Water Valve – Heating – 4 pipe (model 4) booster function.
General Operation
20 min hot start elapsed
2 mins confirm?
Check TrCheck Tc
Enter into heating thermostat cycle
14°C < Tr < 47°C
(Force valve to ON)
Force On C_VLV, Valve, 2 mins User
set speed indoor fan. If Auto fan -> low fan
No
Yes
Yes
Tc < Tr - 3°C
(Water not suitable)
Tc > Tr + 3°C
Tr-2°C < Tc < Tr + 2°C
9 min force off C_VLV elpased
Yes
Check booster T
Tb >28° + Tb > Ts+5
Force On H_VLV, Valve, 2 mins User
set speed indoor fan. If Auto fan -> low fan
Temp ok, H_VLV open for 9 min. User set speed indoor fan. If Auto fan -> low fan
9 mins elapsed?
Yes
Yes
H_VLV close for 5 min. Fan speed follows Fan_prio
setting
NoNo
Room temp control
Tr > Ts-1 close H_vlv
Tr < Ts-2 H_vlv close
No
Booster 9 min
been in use ?
Yes
No
H_VLV close
No
Use Tc + Tb ( booster) !
Use onlyTb ( booster) !
Use only Tc !
54Apr 21, 2023
Internal Use Only
Booster operation - Remarks
– Booster coil Tb only for 9 min contineous in operation, when water temperature on Tc (primary coil for heat/cool is to low.
– Booster coil Tb can operate together with Tc only if water temperature on primary coil Tc is according following equations: in other words close to the room temperature.
Tr-2°C < Tc < Tr + 2°C
Tb > 28°and Tb > Ts +5°
– As soon water temperature on primary coil Tc rises above Tr+3°the booster will be shut off!
General Operation
55Apr 21, 2023
Internal Use Only General Operation
With water valve , 4 pipe (model 3) - Heating
9 mins elapsed?
9 mins elapsed?
2 mins confirm?
2 mins confirm?
Check TrCheck Tb Check Tb
Enter into heating thermostat cycle
14°C < Tr < 47°C
(Force valve to ON)
Force On H_VLV, Valve, 2 mins User set speed indoor
fan. If Auto fan -> low fan
Others
(Force valve to ON)
No No
Yes Yes
(Force valve OFF 9 mins)Yes Yes
(Force valve OFF 9 mins)
Tb < Tr - 3°C(Water not suitable)
Tb < 25°C(Water not suitable)
Tb > Tr + 3°C Tb > 30°C
Tr-2°C < Tb < Tr + 2°C
Only when room te^p is very low < 14°
56Apr 21, 2023
Internal Use Only
With Water Valve – Heating – 4 pipe (model 3)
If after 2 min. force low fan, valve H-VLV open, pcb will go into 2 minutes water temp. mode (sensing coil temperature Tb of heaing coil) if temperature is not suitable (Tb < Troom -3) C_VLV valve will be closed and fan will be run on low speed for 9 minutes. In case fan prio jumper is open fan will stop completely.
When these 9 minutes are elapsed, unit will again perform the two + two minute temp sensing test until the coil Tb temperature is hot enough. No errors are displayed in case water is not suitable. In case Tb is close to room tempTr-2<Tb<Tr+2 unit will also go into thermostat control, this can create some uncomfortable situation!.
Remark: during first start-up depending of the mode (cool or heat) a cold or hot start will be considered by the pcb’s software. This means actual setpoint will be offset internally with +2°for heat mode and -2°for cooling. After 20 minutes these offsets are reseted and setpoint becomes again equal to selected value on the controller
General Operation
57Apr 21, 2023
Internal Use Only
9 mins elapsed?
9 mins elapsed?
2 mins confirm?
2 mins confirm?
Check TrCheck Tc Check Tc
Enter into cooling thermostat cycle
14°C < Tr < 47°C
Tc < Tr + 2°C
(Force valve to ON)
Force On (Valve) 2 mins User set speed indoor fan.
If Auto fan -> low fan
Others
(Force valve to ON)
No No
Yes Yes
NoNo
(Force valve OFF 9 mins)Yes Yes
(Force valve OFF 9 mins)
Tc > Tr + 3°C(Water not suitable)
Tc > 30°C(Water not suitable)
With Water Valve – Cooling – 4 pipe (model 3)
Tc < 29°C
General Operation
Only when room temp is very high > 47°
58Apr 21, 2023
Internal Use Only
With Water Valve – Cooling – 4 pipe (model3)
After starting/power-up the unit, the water valve C_VLV will be opened and fan will be forced to low speed during 2 minutes (allow coil Tc to cool down, after opening of the valve) . After these 2 minutes, unit goes into a 2 minutes temperature check procedure, in case AUTO FAN was selected fan will now run with speed depending on the difference between T room and T setpoint.
If after these 2 minutes (sensing coil temperature) temperature is not suitable (Tc>Troom+3°) valve will be closed and fan will be stopped for 9 minutes in case fan prio jumper is open. Otherwise fan will run on low speed.
When these 9 minutes are elapsed, unit will again perform first the two min force valve open / low fan mode and then the two minute sensing test unitil the coil temperature is cold enough. Note that no errors will be displayed in valve mode if temperature is not ok! As long the temp is not ok unit will stay in the 2+2 min On / 9 min OFF loop.
Remark: during first start-up depending of the mode (cool or heat) a cold or hot start will be considered by the pcb’s software. This means actual setpoint will be offset internally with +2°for heat mode and -2°for cooling. After 20 minutes these offsets are reset and set point becomes again equal to selected value on the controller
General Operation
59Apr 21, 2023
Internal Use Only
2 mins confirm?
2 mins confirm?
Check TrCheck Tc Check Tc
Enter into cooling thermostat cycle
14°C < Tr < 47°C
Tc < Tr - 3°C Tc < 25°C
Tr – 2°C < Tc < Tr + 2°C
Force On 2 mins Indoor fan -> force low fan
Others
26°C < Tc < 29°C
No No
(Fault declared, LED blinking)
Yes Yes
(Fault declared, LED blinking)
Tc > Tr + 3°C
(Water not suitable)
Tc > 30°C
(Water not suitable)
Without Water Valve – Cooling – 2 pipe
(Indoor fan -> force SLo fan) (Indoor fan -> force SLo fan)
(Indoor fan -> force Lo fan) (Indoor fan -> force Lo fan)
(Fault terminated, LED stop blinking)
(Fault terminated, LED stop blinking)
General Operation
Only when room temp is very high > 47°
60Apr 21, 2023
Internal Use Only
Without Water Valve – Cooling – 2 pipe
After starting the unit’s fan will be forced to low speed during 2 minutes. After these 2 minutes, unit goes into another 2 minutes temperature check procedure, in case AUTO FAN was selected fan will now run with speed depending on the difference between T room and T setpoint.
If after the 2 + 2 minutes (sensing coil temperature) temperature is not suitable (Tc >Troom+3°) fan will be forced into SLO mode (5min interval On/OFF). Error E5 will be displayed (on wired controllers) or fault code with blinking leds on front panel of the unit. As soon Tc is < Tr-3°unit will go in thermostat control. Note that only for FWT extra E04 error exists for “poor” water temp wich actually correspond to equation Tr-2<Tc<Tr+2
Remark: during first start-up depending of the mode (cool or heat) a cold or hot start will be considered by the pcb’s software. This means actual setpoint will be offset internally with +2°for heat mode and -2°for cooling. After 20 minutes these offsets are reseted and setpoint becomes again equal to selected value on the controller
General Operation
61Apr 21, 2023
Internal Use Only
2 mins confirm?
2 mins confirm?
Check TrCheck Tc Check Tc
Enter into heating thermostat cycle
14°C < Tr < 47°C
Force On 2 mins Indoor fan -> force low fan
Others
No No
YesYes
Tc < Tr - 3°C Tc < 25°C
Without Water Valve - Heating
Tc > Tr + 3°C Tc > 30°C(Fault terminated, LED
stop blinking)(Fault terminated, LED
stop blinking)
(Fault declared, LED blinking) (Fault declared, LED blinking)
(Indoor fan -> force SLo fan) (Indoor fan -> force SLo fan)
Tr-2° < Tc < Tr + 2° 26°C < Tc < 29°C
General Operation
Only when room te^p is very low < 14°
(Indoor fan -> force SLo fan) (Indoor fan -> force SLo fan)
62Apr 21, 2023
Internal Use Only
Without Water Valve – Heating – 2 pipe
After starting the unit’s fan will be forced to low speed during 2 minutes. After these 2 minutes, unit goes into another 2 minutes temperature check procedure, in case AUTO FAN was selected fan will now run with speed depending on the difference between T room and T setpoint.
If after 4 minutes (sensing coil temperature) temperature is not suitable (Tc < Troom-3°) fan will be forced into SLO mode (5min interval On/OFF). Error E5 will be displayed (on wired controllers) or fault code with blinking leds on front panel of the unit. As soon Tc is > Tr+3°unit will go in thermostat control.
Remark: during first start-up depending of the mode (cool or heat) a cold or hot start will be considered by the pcb’s software. This means actual setpoint will be offset internally with +2°for heat mode and -2°for cooling. After 20 minutes these offsets are reseted and setpoint becomes again equal to selected value on the controller
General Operation
63Apr 21, 2023
Internal Use Only
Thermostat Control – COOL with water valve, for all models: Thermostat control becomes active after startup pipe sensing procedure
(checking of water temperatures)
- If water becomes to hot during cooling operation, pcb will go again into temp check mode (see flowcharts on pipe water sensing).
- Water Valve ON, if Tr => Ts + 1°C
- Water Valve OFF, if Tr <= Ts
- During cold start, Ts will offset by -2°C until water valve cut OFF or unit has run for at least 20 minutes
- Minimum thermostat cut in or out time is 30s
- 9 Minutes Water Valve force OnIf water valve is idle for more than 9 minutes in cool/dry mode and Tr=Ts or warmer the water valve will be forced to be ON for 2 min
- Fan Speed control:
* Indoor fan speed follow jumper FAN_PRIO setting
* For manual speed, indoor fan run as per user set speed
* For AUTO fan speed, the indoor fan speed will run depending of how far room temperature is from the setpoint
General Operation
64Apr 21, 2023
Internal Use Only
With Water Valve - AUTO fan speed selected, COOLING :
Fan&valve reaction
Ts + 1Ts + 1
TsTs
°C°C
HH LLMM MM LLHHWater Valve Water Valve
ONONWater Valve Water Valve
ONONWater Valve Water Valve
OFFOFFWater Valve Water Valve
OFFOFF
Note: - When FAN_P jumper is open, fan will stop when water valve OFF - For FWT no FAN_P is available, only SLO mode (interval 5min
ON/OFF)
General Operation
65Apr 21, 2023
Internal Use Only
With Water Valve - AUTO fan speed selected, COOLING :
Fan&valve reaction -example
Ts + 1Ts + 1
TsTs
°C°C
HH L/offL/offMM MM L/offL/offHHWater Valve Water Valve
ONONWater Valve Water Valve
ONONWater Valve Water Valve
OFFOFFWater Valve Water Valve
OFFOFF
General Operation
example Ts=22 (set on remote or wired control)
2323
2222
Remark: in cooling mode setpoint Ts, is only offset by +2° during start ,Cold start, cold start takes 20 min after startup .
If Fan_Prio open, during valve OFF, fan will be OFF
66Apr 21, 2023
Internal Use Only
Without Water Valve – Manual Fan speed selected, COOL
TsTs
-1.0°C-1.0°C
-0.5°C-0.5°C
SLoSLo
SLoSLo
User set User set speed speed (H/M/L)(H/M/L)
User set User set speed speed (H/M/L)(H/M/L)
SLo region = indoor low fan ON 5 minute, OFF 5 minute
General Operation
67Apr 21, 2023
Internal Use Only
Without Water Valve – Manual Fan speed selected, COOLexample
General Operation
Remark: in cooling mode setpoint Ts, is only offset by +2° during start ,Cold start, cold start takes 20 min after startup .
TsTs
-1.0°C-1.0°C
-0.5°C-0.5°C
SLoSLo
SLoSLo
User set User set speed speed (H/M/L)(H/M/L)
User set User set speed speed (H/M/L)(H/M/L)
example Ts=22 (set on remote or wired control)
2222
2121
21.521.5
68Apr 21, 2023
Internal Use Only
Without Water Valve – with Auto Fan speed selected, COOL:
SLo region = indoor low fan ON 5 minute, OFF 5 minute
TsTs
-1.0°C-1.0°C
-0.5°C-0.5°C
SLoSLo
SLoSLo
+1.0°C+1.0°C
TsTs
-0.5°C-0.5°C
+0.5°C+0.5°C
LL
LL
MM
MM
HH
HH
General Operation
Minimum fan speed change time is 30s
69Apr 21, 2023
Internal Use Only
Without Water Valve – with Auto Fan speed selected, COOL:
General Operation
Minimum fan speed change time is 30s - example
Remark: in cooling mode setpoint Ts, is only offset by +2° during start ,Cold start, cold start takes 20 min after startup .
TsTs
-1.0°C-1.0°C
-0.5°C-0.5°C
SLoSLo
SLoSLo
+1.0°C+1.0°C
TsTs
-0.5°C-0.5°C
+0.5°C+0.5°C
LL
LL
MM
MM
HH
HH
example Ts=22 (set on remote or wired control)
2222
21.521.5
2323
2222
21.521.5
22.522.5
2121
70Apr 21, 2023
Internal Use Only
Dry mode runs under COOL mode with AUTO fan mode for 12 minutes or Until Tr=< Ts
After 12 minutes, the DRY mode operates like COOL cycle, however only low fan is allowed to cut in.
Dry mode can only work if water is suitable (Tc <Tr-3°)
General Operation
71Apr 21, 2023
Internal Use Only
Thermostat Control – HEAT with water valve, for all models: Thermostat control becomes active after startup pipe sensing procedure
(checking of water temperatures)
- Water Valve ON, if Tr <= Ts - 1°C
- Water Valve OFF, if Tr >= Ts
- During cold start, Ts will offset by +2°C until water valve cut OFF or unit has run for at least 20 minutes
- Minimum thermostat cut in or out time is 30s
- Fan Speed control:
* Indoor fan speed follow jumper FAN_PRIO setting
* For manual speed, indoor fan run as per user set speed
* For AUTO fan speed, the indoor fan speed will run as follows:-
General Operation
Remark: in heating setpoint is always offset by +2° even after the hot start of 20 min, this is to compensate room temperature stratifcation effect
72Apr 21, 2023
Internal Use Only
With Water Valve – AUTO fan speed selected, HEAT :fan&valve reaction
Note: - When FAN_P jumper is open, fan will stop when water valve OFF - For FWT no FAN_P is available.
General Operation
Remark: in heating setpoint Ts, is always offset by +2° even after the hot start of 20 min, this is to compensate room temperature stratifcation effect
Ts - 1Ts - 1
TsTs
°C°C
HHLL MM MMLL HHWater Valve Water Valve
ONONWater Valve Water Valve
ONONWater Valve Water Valve OFFOFF
Water Valve Water Valve OFFOFF
Ts - 2Ts - 2
73Apr 21, 2023
Internal Use Only
With Water Valve – AUTO fan speed selected, HEAT :fan&valve reaction - example
General Operation
Remark: in heating setpoint Ts, is always offset by +2° even after the hot start of 20 min, this is to compensate room temperature stratifcation effect
Ts - 1Ts - 1
TsTs
°C°C
HHLL MM MMLL HH
Water Valve Water Valve ONON Water Valve Water Valve
ONON
Water Valve Water Valve OFFOFF
Water Valve Water Valve OFFOFF
Ts - 2Ts - 2
example Ts=22 (set on remote or wired control)
2424
2323
2222
Ts+2
74Apr 21, 2023
Internal Use Only
AUTO (cool/heat) MODE – switching between modes- Only applicable for Model 3 (four pipe + selection on pcb).
- Fan operates as normal Cool mode or Heat mode.
TrTr
Auto HeatAuto Heat Auto CoolAuto Cool Auto HeatAuto Heat
TsTs
Ts + 1°CTs + 1°C
Ts - 1°CTs - 1°C
During Auto heat mode, when room temperature rises and equals to the cool switch point, systeem will automatically switch to Auto cool mode. If room temperature falls down and reaches heat switchsetpoint system will again change to Auto heat mode.
General Operation
Remark: in AUTO cool/heat mode for determing switchpoint the heat setpoint offset by - 1° , for cooling switchpoint no offset is applied
75Apr 21, 2023
Internal Use Only
AUTO (cool/heat) MODE – switching between modes- Only applicable for Model 3 (four pipe + selection on pcb).
- Fan operates as normal Cool mode or Heat mode.
General Operation
Remark: in AUTO cool/heat mode setpoint is offset by - 1°, for determining heat switch poinr, no offset is applied for cool switchpoint
TrTr
Auto HeatAuto Heat Auto CoolAuto Cool Auto HeatAuto Heat
TsTs
Ts + 1°CTs + 1°C
Ts - 1°CTs - 1°C
example Ts=22 (set on remote or wired control)Ts-1 Ts
2323
2222
2020
2323
2121
2020
76Apr 21, 2023
Internal Use Only
AUTO (cool/heat) MODE – temp control&fan control- Only applicable for Model 3 (four pipe + selection on pcb).
- Fan operates as normal Cool mode or Heat mode.
General Operation
example Ts=22 (set on remote or wired control)Ts-1
Ts +1HH
2121
2222
2020
MM L/offL/off
2323
2424
L/offL/off HH
HH MM
MM L/offL/off
COOL VALVECOOL VALVE ONON
HEAT VALVEHEAT VALVE ONON
During L/OFF cycle valves are closed
HH MM
2323
Switchpoint to cool >23°
Switchpoint to heat < 20°
L/offL/off HH MM L/offL/off
Tr
Remark: in AUTO cool/heat mode, for the fan & temp control, cool and heat setpoint are both offset by 1°.
77Apr 21, 2023
Internal Use Only
Without Water Valve – Manual fan speed selected, HEAT:
Minimum fan speed change time is 30s
TsTs
+1.5°C+1.5°C
+1.0°C+1.0°C
SLoSLo
SLoSLo
User set User set speed speed (H/M/L)(H/M/L)
User set User set speed speed (H/M/L)(H/M/L)
SLo region = indoor low fan ON 5 minute, OFF 5 minute
General Operation
Remark: in heating setpoint Ts, is always offset by +2° even after the hot start of 20 min, this is to compensate room temperature stratifcation effect
78Apr 21, 2023
Internal Use Only
Without Water Valve – Manual fan speed selected, HEAT:
Minimum fan speed change time is 30s – example
General Operation
Remark: in heating setpoint Ts, is always offset by +2° even after the hot start of 20 min, this is to compensate room temperature stratifcation effect
TsTs
+1.5°C+1.5°C
+1.0°C+1.0°C
SLoSLo
SLoSLo
User set User set speed speed (H/M/L)(H/M/L)
User set User set speed speed (H/M/L)(H/M/L)
example Ts=22 (set on remote or wired control)Ts+2
2424
2525
25.525.5
79Apr 21, 2023
Internal Use Only
Without Water Valve – AUTO fan speed selected, HEAT :
SLo region = indoor low fan ON 5 minute, OFF 5 minute
TsTs
-1.0°C-1.0°C
-2.0°C-2.0°C
SLoSLoSLoSLo
+1.5°C+1.5°C
TsTs
+1.0°C+1.0°C
+2.0°C+2.0°CLL
LL
MM
MM
HH
HH
General Operation
Remark: in heating setpoint Ts, is always offset by +2° even after the hot start of 20 min, this is to compensate room temperature stratifcation effect
80Apr 21, 2023
Internal Use Only
Without Water Valve – AUTO fan speed selected, HEAT :example
General Operation
Remark: in heating setpoint Ts, is always offset by +2° even after the hot start of 20 min, this is to compensate room temperature stratifcation effect
TsTs
-1.0°C-1.0°C
-2.0°C-2.0°C
SLoSLoSLoSLo +1.5°C+1.5°C
TsTs
+1.0°C+1.0°C
+2.0°C+2.0°CLL
LL
MM
MM
HH
HH
example Ts=22 (set on remote or wired control)Ts+2
2424
2222
25.525.52626
2525
2323
2424
Ts+2
81Apr 21, 2023
Internal Use Only
FAN MODE:
- Valves stays closed (no water flow !)Fan Mode is not available for valve less control systems
- 3 fan speed are available in Fan mode:
* High
* Medium
* Low
- Irrespective of jumper FAN_Prio setting
General Operation
82Apr 21, 2023
Internal Use Only
• 70
0 m
m h
ea
d
pre
ss
ure
Condensate drainage- FWC/FWF Cassette units are equipped with drainpump & level detection
witch(normal closed)
- Pressure head 700 mm
- FWT needs field installed drainpump for cooling operation
Level switch
General Operation
83Apr 21, 2023
Internal Use Only
Condensate drainage
Water Level Switch (Float Switch):
- Normally closed switch.
- If switch is close (>60s), water valve is allowed to cut in.
- If switch is open (>30s), it will force the water valve to cut off, water pump always on and show error E6 or blinking LED.
Water Pump:
- Water pump will on if the water valve is on or float switch contact is opened.
- Water Pump remain on for at least 5mins after the water valve is off or COOL mode switch to HEAT.
General Operation
Top SecretSecret
Internal use onlyPublic
Types of HandsetsTypes of Handsets
85Apr 21, 2023
Internal Use Only Handsets - controllers
Wireless remote controllers:
WRC-COB for cooling only applicationWRC-HPB for heat pump application
Note: WRC-COA / WRC-HPA was the previous version of handset
Wired remote controllers:
Standard: MERCA for both applicationsSimplified: SRC-COA for cooling only application SRC-HPA for heat pump application
Handsets & controllers
86Apr 21, 2023
Internal Use Only Handsets- controllers
Handsets & controllers
All handsets and controllers can be combined for whole fcu range
WRC
MERCA
SRC
87Apr 21, 2023
Internal Use Only Handsets - controllers
xx type of FCU;CO for cooling only FCUor HP for Heat pump FCU controller
Handsets & controllers
Wireless controller:– WRC-xxB Wireless
– supplied with decoration panel kit
Wired controller:– MERCA Standard
– SRC-xxA Simplified
General features:
3 selectable fan speed
Automatic swing (optional)
Dehumidification function
Sleep mode: energy saving option allowing prevention of excessive cooling during summer and excessive heating during night for a comfortable rest.
WRC
MERCA
SRC
88Apr 21, 2023
Internal Use Only
Wireless controller
Handsets - controllers
Real Time Clock
LCD Display
Operating Mode
Fan Speed
ON/OFF Switch
Transmission
“Sleep” Function
Timer Switch Setting
Swing
TemperatureSetting
WRC-xxA (previous version)
89Apr 21, 2023
Internal Use Only
WRC-xxB (latest version 09/2009)
Handsets - controllers
1. IR transmission source
2. Signal transmission indication
3. ON/OFF button
4. Fan speed selection
5. Mode selection
6. Swing activation
7. -
8. Timer OFF setting
9. RTC setting
10.Timer ON setting
11.Sleep function
12.Personalize button
13.Temperature setting
90Apr 21, 2023
Internal Use Only
Operation mode– Cooling only:
• Cool, Dry and Fan
– Heating mode:• Auto, Cool, Dry, Fan and Heat
– Automode only available for 4-pipe system (mode 3)
Timer setting: to turn ON/OFF the air conditioner at the desired time
– ON Timer setting:• Activation by pressing on SET
• Time setting by pressing continuously on SETuntil desired time is selected
• Cancel to cancel the ON Timer setting
– OFF Timer setting• Activation by pressing on SET
• Time setting by pressing continuously on SETuntil desired time is selected
• Cancel to cancel the ON Timer setting
Wireless controller – Main functions
ON Timer OFF Timer
WRC-xxB
Handsets - controllers
91Apr 21, 2023
Internal Use Only
Sleep Mode: energy saving option while optimising
comfort conditions by temperature adjustment
In cooling mode, this function will prevent
excessive cooling during summer season– After the first 1/2h, T0°→ T0° + 0,5°C
– After 1h, T0°→ T0° + 1°C
– After 2h, T0°→ T0° + 2°C
In heating mode, this function will prevent
night sweat– After the first 1/2h, T0°→ T0°-1°C
– After 1h, T0°→ T0°-2°C
– After 2h, T0°→ T0°-3°C
Wireless controller – Main functions
Energy Saving Comfort
Sleep Mode activated
Sleep Mode activated
WRC-xxB
Handsets - controllers
92Apr 21, 2023
Internal Use Only
Wireless controller – Optional functions
Automatic air swing
Activation of automatic air swing
Air distribution according to a specific direction is possible: 1. press on SWING until the louver moves to the desired direction 2. press on SWING once again
WRC-xxB
Handsets - controllers
93Apr 21, 2023
Internal Use Only
Personalize Setting (memory)– Possibility to save two settings:
• Press personalize button for 3 sec
• P1 will start to blink In display
• Toggle on to switch between P1 & P2
• Make preference settings, after 4 sec without pressing any button settings will be save under selected memory
• To activate saved setting toggle shortlyon the button.
• To deactivate any selected memorizedsetting, press any key
Wireless controller – Main functions WRC-xxB
Handsets - controllers
94Apr 21, 2023
Internal Use Only
Wireless controller – Main functions
Operation mode– Cooling only:
• Cool, Dry and Fan
– Heating mode:• Auto, Cool, Dry, Fan and Heat
– Automode only available for 4-pipe system
Timer setting: to turn ON/OFF the air conditioner at the desired time
– ON Timer setting:• Activation by pressing on SET
• Time setting by pressing continuously on SETuntil desired time is selected
• CLR to cancel the ON Timer setting
– OFF Timer setting• Activation by pressing on SET
• Time setting by pressing continuously on SETuntil desired time is selected
• CLR to cancel the ON Timer settingON Timer OFF Timer
WRC-xxA
Handsets - controllers
95Apr 21, 2023
Internal Use Only
Sleep Mode: energy saving option while optimising
comfort conditions by temperature adjustment
In cooling mode, this function will prevent
excessive cooling during summer season– After the first 1/2h, T0°→ T0° + 0,5°C
– After 1h, T0°→ T0° + 1°C
– After 2h, T0°→ T0° + 2°C
In heating mode, this function will prevent
night sweat– After the first 1/2h, T0°→ T0°-1°C
– After 1h, T0°→ T0°-2°C
– After 2h, T0°→ T0°-3°C
Wireless controller – Main functions
Energy Saving Comfort
Sleep Mode activated
Sleep Mode activated
WRC-xxA
Handsets - controllers Handsets - controllers
96Apr 21, 2023
Internal Use Only
Wireless controller – Optional functions
Automatic air swing
Activation of automatic air swing
Air distribution according to a specific direction is possible: 1. press on SWING until the louver moves to the desired direction 2. press on SWING once again
WRC-xxA
Handsets - controllers
97Apr 21, 2023
Internal Use Only
Fan
Temperature Setting
Operating Mode
ON/OFF Switch
LCD Display
Real Time Clock
Swing
ON/OFF Timer
Sleep
Timer Active
Standard wired controller
Handsets - controllers
MERCA wired controller for FWT-FWF-FWC
98Apr 21, 2023
Internal Use Only
Standard wired – Main functions
Operation mode– Cool, Heat, Auto, Dry, Fan
– Automode only available for 4-pipe system
Time setting:– CLOCK: activates or disable the Real Time Clock setting mode (RTC)
• Under RTC setting mode: setting thanks to keys DAY, HOUR and MINUTE
– 3 events programmable and 7-days programmable timers
• Each timer has ON TIMER and OFF TIMER
• Timer setting mode of event i is enabled by pressing on ON TIMER (or OFF TIMER) i times
Handsets - controllers
99Apr 21, 2023
Internal Use Only
Mode config – Merca pcb (wired controller),configuration of jumpers needed on
pcb of the wired controller Merca. Note:Auto mode only valid for 4 pipe systems.
Auto mode system (auto switching between cool/heat)
Cool/ Heat system (heat pump)
Jd short, Jh short
Jd open, Jh short
Handsets - controllers
100Apr 21, 2023
Internal Use Only
Mode config – Merca pcb (wired controller),configuration of jumpers needed on
pcb of the wired controller Merca,
Cooling only system Jd short, Jh open
Jumper J4 determines user setting range for room setpoint
J4 open : 16-30° - J4 short: 20-30°C
Handsets - controllers
101Apr 21, 2023
Internal Use Only
Standard wired – Main functions
Operation mode– Cool, Heat, Auto, Dry, Fan
– Auto-mode only available for 4-pipe system
Time setting:– CLOCK: activates or disable the Real Time Clock setting mode (RTC)
• Under RTC setting mode: setting thanks to keys DAY, HOUR and MINUTE
– 3 events programmable and 7-days programmable timers
• Each timer has ON TIMER and OFF TIMER
• Timer setting mode of event i is enabled by pressing on ON TIMER (or OFF TIMER) i times
Handsets - controllers
102Apr 21, 2023
Internal Use Only
Standard wired – Main functions
Timer Active: activates or de-activates all set timers
– Override function: when activated, all the timers will bypassed and turn ON the unit for a fix periodof 1, 2 or 4 hours (depending on the selection) and then turn off
• Activation by pressing HOUR (one time for 1 hour, 2 times for 2 hours and 3 for 4 hours)
• Deactivation by pressing HOUR
Automatic Air Swing:– Activation of automatic air swing
Handsets - controllers
103Apr 21, 2023
Internal Use Only
Standard wired – Main functions
Sleep Mode:: energy saving option while optimising
comfort conditions by temperature adjustment
In cooling mode, this function will prevent
excessive cooling during summer season
– After the first 1/2h, T0°→ T0° + 0,5°C
– After 1h, T0°→ T0° + 1°C
– After 2h, T0°→ T0° + 2°C
In heating mode, this function will prevent
night sweat
– After the first 1/2h, T0°→ T0°-1°C
– After 1h, T0°→ T0°-2°C
– After 2h, T0°→ T0°-3°C
Sleep Mode activated
Sleep Mode activated
Energy Saving Comfort
Handsets - controllers
104Apr 21, 2023
Internal Use Only
Temperature Display
Operating Mode
Fan Speed
ON/OFF Switch
IR Receiver
“Sleep” Function
Timer Switch Setting
Swing
TemperatureSetting
SRC-xxA FWT / FWF / FWC Two version available :
- SRC-HPA – heating/cooling- SRC-COA – cooling only
Handsets - controllers
105Apr 21, 2023
Internal Use Only
Simplified wired – Main functions Operation mode
– Cooling only:• Cool, Dry and Fan
– Heating mode:• Auto, Cool, Dry, Fan and Heat
– Automode: Not available
Fan Speed:: Low, medium, high or automatic
Timer switch setting: to turn ON/OFF the air conditioner
• By pressing on TIMER, the unit will turnON/OFF 1 up to 10 hours later
Handsets - controllers
106Apr 21, 2023
Internal Use Only
Sleep Mode:: energy saving option while optimising
comfort conditions by temperature adjustment
In cooling mode, this function will prevent
excessive cooling during summer season
– After the first 1/2h, T0°→ T0° + 0,5°C
– After 1h, T0°→ T0° + 1°C
– After 2h, T0°→ T0° + 2°C
In heating mode, this function will prevent
night sweat
– After the first 1/2h, T0°→ T0°-1°C
– After 1h, T0°→ T0°-2°C
– After 2h, T0°→ T0°-3°C
Simplified wired – Main functions
Energy Saving Comfort
Sleep Mode activated
Sleep Mode activated
Handsets - controllers
107Apr 21, 2023
Internal Use Only
Simplified wired – Optional function
Automatic air swing:
-- Activation of automatic air swing
- Air distribution according to a specific direction is possible: 1. press on SWING until the louver moves
to the desired direction 2. press on SWING once again
Handsets - controllers
Top SecretSecret
Internal use onlyPublic
PCB connectionsPCB connections
109Apr 21, 2023
Internal Use Only PCB connections
FWT (mentioned pic is valid for FWT02-03-04, for FWT05/06 pcb layout is slightly different but all connections and connector names are the same)
ASDC Swing motor
-Valve/Valveless Setting
- Bar Heat Setting
Room Sensor
Coil Sensor
IR ReceiverAssy. LED
110Apr 21, 2023
Internal Use Only
FWT
PCB connections
111Apr 21, 2023
Internal Use Only
FWT
PCB connections
112Apr 21, 2023
Internal Use Only
Low Fan
Medium FanHigh Fan
LIVE
NEUTRAL
Room Sensor
Coil Sensor
Water Valve
Water Pump
AC Swing
FWF
PCB connections
113Apr 21, 2023
Internal Use Only
Float Switch
- Fan Priority Setting
- Valve/Valveless Setting
- Bar Heat Setting
OR
MERCA SRCIR ReceiverAssy. LED
WRC
FWF
PCB connections
114Apr 21, 2023
Internal Use Only
FWF
PCB connections
115Apr 21, 2023
Internal Use Only
FWC - 2 pipe
OR
MERCA SRCIR ReceiverAssy. LED
WRC
PCB connections
116Apr 21, 2023
Internal Use Only
Low FanMedium Fan
High Fan
LIVE
NEUTRAL
Room Sensor
Coil Sensor
Water Valve
Water Pump
AC Swing
Float Switch
- Fan Priority Setting
- Valve/Valveless Setting
- Bar Heat Setting
FWC - 2 pipe
PCB connections
117Apr 21, 2023
Internal Use Only
FWC - 2 pipe (FWC-T)
PCB connections
118Apr 21, 2023
Internal Use Only
Unoccupied setting
Anti Freeze setting
Window Open setting
Float Switch
Load Shedding Setting
- Fan Priority Setting
- Valve/Valveless Setting
- Bar Heat Setting
OR
MERCA SRC IR ReceiverAssy. LED
WRC
Not used in water fcu !
PCB connections
FWC - 4 pipe (FWC-F)
119Apr 21, 2023
Internal Use Only
Low FanMedium Fan
High Fan
LIVE
NEUTRAL
Room Sensor
Coil Sensor cool coil
Water Valve - cool
Water Pump
AC Swing
Water Valve - heat
Coil Sensor heat coil
PCB connections
FWC - 4 pipe (FWC-F)
120Apr 21, 2023
Internal Use Only
FWC 4 pipe (FWC-F)
PCB connections
Top SecretSecret
Internal use onlyPublic
Water ValvesWater Valves
122Apr 21, 2023
Internal Use Only
VALVE KITS
– For FWF, MCKCW2T3VN kit is available.
– For FWC-T, MCKAW2T3VN kit is available.
– For FWC-F, MCKAWH4T3VN kit is availabele.
Kits consist of: valve, actuator, shut off valves and special designed piping for connection on fcu.
– For FWT no kit available, valve and pump are field supply.
Water valves
123Apr 21, 2023
Internal Use Only
4 port 3-way valve functioning (mixing) std config
Water valves
Close = de-energized NC actuator
Open = energized NC actuator
close open
Bypass direction
ININ
OUT
To IN FCU
OUT
From out FCU From out FCU
Watch symbol on
valve body
To IN FCU
124Apr 21, 2023
Internal Use Only
4 port 3-way valve functioning (diverting)
Water valves
Close = de-energized NC actuator
Open = energized NC actuator
close open
Bypass direction
ININ
OUT
To IN FCU
OUT
From out FCUFrom out FCU
Watch symbol on
valve body
To IN FCU
125Apr 21, 2023
Internal Use Only Water valves
FWF - MCKCW2T3VN – installation Kit includes:3 way/4 port on/off valve diametre ¾” thermo-electric NC actuator 230 vaccopper pipes diametre 18mm, welded connections ¾” gas niples
126Apr 21, 2023
Internal Use Only Water valves
FWF - MCKCW2T3VN – installation
Fan side
Ceiling sideWater drain
Drain tube
Diametre 20mm with collar of 20.5 mm
Water conn on unit. all ¾”
127Apr 21, 2023
Internal Use Only Water valves
FWC-T MCKAW2T3VN – installation Kit includes:3 way/4 port on/off valve diametre ¾” thermo-electric NC actuator 230 vaccopper pipes diametre 18mm, welded connections ¾” gas niples
128Apr 21, 2023
Internal Use Only Water valves
FWC - MCKAW2T3VN – installation
Fan sideFan side
Water drain
129Apr 21, 2023
Internal Use Only Water valves
FWC-F MCKAWH4T3VN – installation Kit includes:1 * 3 way/4 port on/off valve diametre ½ ”, secondary coil1* 3 way/4 port on/off valve diametre ¾” 2 * thermo-electric NC actuator 230 vaccopper pipes diametre 18mm, welded connections ¾” gas niples
130Apr 21, 2023
Internal Use Only Water valves
FWC – F MCKAWH4T3VN – installation
Fan sideFan side
Ceiling sideCeiling side
Primary coil Secondary coil
¾”
½ ”
Water conn on unit. all ¾”
131Apr 21, 2023
Internal Use Only Water valves
Hydraulic properties 3 way – 4 port valves ½” and ¾”
132Apr 21, 2023
Internal Use Only Water valves
Hydraulic properties 3 way valves ¾”
133Apr 21, 2023
Internal Use Only Water valves
Hydraulic properties 3 way valves ½”
Top SecretSecret
Internal use onlyPublic
Diagnostics
135Apr 21, 2023
Internal Use Only
Error messaging by means of COOL/HEAT led blinking on operation panel or by visualization of an error code on display wired controller.
FWT FWC-FWF
MercaSRC
Ionizer LED is not used with water fcu
Error Diagnosis
136Apr 21, 2023
Internal Use Only
COOL LED On Led panel unit
Error CodeOn display wired controller
MERCA or SRC
Descriptions
1 blink E1 Room Sensor short/open
2 blinks E2 Pipe Water Sensor short/open
6 blinks E6 Water Pump Error
5 blinks E5 Pipe Water Temperature Fault
3 blinks - Window Open Activated
7 blinks - Antifreeze Mode Activated
8 blinks - Load Shedding Activated
*Blinking (1s each) -> off 3s -> blinking (1s each)
Others LEDs OFF
Error table FWC-FWF
Error Diagnosis
137Apr 21, 2023
Internal Use Only
SLEEP LED
On panel unit
COOL/HEAT
LED
on panel unit
Timer LED
On Led panel unit
Error Code
On display wired controller
MERCA or SRC
Descriptions
On/off Green - - Unit in cool mode – sleep mode on or off
On/off Red - - Unit in heat mode – sleep mode on or off
1 blink - E1 Room Sensor short/open
Cont. blink 2 blink - E2 Pipe Water Sensor short/open
3 blink E4 Pipe Water Temperature poor (Tr-2<Tc<Tr+2)
1 blink E5 Pipe Water Temperature bad (Tc< Tr-3) for heating or Tc>Tr+3 for cooling
-
Error table FWT - only
Error Diagnosis
138Apr 21, 2023
Internal Use Only
Resistances NTC temp sensors
Error Diagnosis