TOP, The Output Processor TOP, The Output Processor Training Presentation Electrotek Concepts.

Post on 19-Dec-2015

238 views 1 download

Tags:

transcript

TOP, The Output ProcessorTOP, The Output Processor

Training Presentation

Electrotek Concepts

What is TOP?What is TOP?

TOP is an acronym for “The Output Processor”, a software tool which reads data from a variety of measurement instruments and transforms it into simplified power system analyses for inclusion in reports and documents.

System RequirementsSystem Requirements

386/486 IBM Compatible PC 4 MB RAM or more 80387 Math Co-processor Windows 3.1 or greater Windows Compatible Video Card Windows Compatible Printer Windows Compatible DOS

Data SharingData Sharing

The data being visualized in a window can be exported to a variety of other file formats including: IEEE Comtrade (.CFG) Windows Metafile (.WMF) Tagged Image Format (.TIF) Windows Bitmap (.BMP) Comma Separated Variable (.CSV)

Data Management CapabilityData Management Capability

TOP uses a system called the stack to simplify handling data from various sources.

Data DisplayData Display

TOP provides a variety of ways to visualize the data of interest. Waveform and spectrum plots Frequency response plots Summary tables Summary bar/volume charts Cumulative probability charts Probability density charts

Output ExamplesOutput Examples

Exporting Data: PASS to TOPExporting Data: PASS to TOP

Method 1: Using the TOP icon in PASS.

Select TOP Icon in PASSto automatically load andplot graph in TOP.

Exporting Data: PASS to TOPExporting Data: PASS to TOP

Method 2: Using the Copy Special feature.

Exporting Data: PASS to TOPExporting Data: PASS to TOP

Method 2

Getting Started - Saving FilesGetting Started - Saving Files

Saving files in PASSSave as .CSV file.

Getting Started - Opening Getting Started - Opening FilesFiles

Opening files in TOP.CSV files are automaticallyloaded on to the stack.

Getting Started - Using Quick Getting Started - Using Quick GraphGraph

Getting Started - Loading Getting Started - Loading DataData

Opening IEEE Comtrade files (.CFG)

Dialog Box for loading data on the stack.

Graphical ManipulationsGraphical Manipulations

Working with multiple graphs. Using the zoom feature. Formatting graphs

Multiple GraphsMultiple Graphs

Plotting multiple graphs in a single frame.

PASS>SAMPLE-VA_WF(02/16/92)(02:26:18)

0 20 40 60-150

-100

-50

0

50

100

150

Time (mS)

Volta

ge (V

)

Max:Min:Avg:Abs:

RMS:CF :FF :

112.886 -138.884 63.0064 138.884 71.6969 1.9371 1.13793

PASS Disturbance

PASS>SAMPLE-VA_WF(02/16/92)(02:26:18)PASS>SAMPLE-VB_WF(02/16/92)(02:26:18)PASS>SAMPLE-VC_WF(02/16/92)(02:26:18)

Multiple Graphs, cont.Multiple Graphs, cont.

Plotting multiple graphs in a single window.

PASS>SAMPLE-VC_WF(02/16/92)(02:26:18)

0 20 40 60-100

-50

0

50

100

150

Time (mS)

Volt

age

(V)

Max:Min:Avg:Abs:RMS:CF :FF :

106.74 -97.5211 32.0213 106.74 46.5987 2.29062 1.45524

PASS Disturbance

PASS>SAMPLE-VB_WF(02/16/92)(02:26:18)

0 20 40 60-100

-50

0

50

100

150

Time (mS)

Volt

age

(V) Max:

Min:Avg:Abs:RMS:CF :FF :

103.235 -97.2967 33.5975 103.235 45.2992 2.27897 1.34829

PASS Disturbance

PASS>SAMPLE-VA_WF(02/16/92)(02:26:18)

0 20 40 60-150

-100

-50

0

50

100

150

Time (mS)

Volt

age

(V)

Max:Min:Avg:Abs:RMS:CF :FF :

112.886 -138.884 63.0064 138.884 71.6969 1.9371 1.13793

PASS Disturbance

CAPMAG> 480A(Type 1)

0 20 40 60 80 100-1000

-800

-600

-400

-200

0

200

400

600

800

1000

Time (mS)

Voltage (V)

CAPMAG> 480A(Type 1)

10.0 20.0 30.0 40.0 50.0-600

-400

-200

0

200

400

600

800

Time (mS)

Voltage (V)

Zooming with the MouseZooming with the Mouse

To zoom in on a portion of the graph, click and drag the right mouse button to create a rectangular box around the area of interest and then release the button.

Formatting graphs in TOPFormatting graphs in TOP

Data labels Axis scaling Creating legends and more!

TOPCalc FunctionsTOPCalc Functions

Add, Subtract Multiply, Divide FFT, DFT, IDFT Power, energy and I2t Integration, square

square root X-Y combine Filter, time shift V, I, & power dB ratio Cumulative probability

TOPCalc ExampleTOPCalc Example

Calculation of line-line voltage, Calculation of line-line voltage, VAl-l, from , from phase Aphase Al-g voltage and phase B voltage and phase Bl-g voltage voltage waveforms.waveforms. WAVE2>1591-VA_WV(10/01/93)(04:01:44)

0 5 10 15-150

-100

-50

0

50

100

150

Time (mS)

Volt

age (

V)

Max:Min:Avg:Abs:

RMS:CF :FF :

100.445 -100.621 63.9686 100.621 70.9931 1.41733 1.10981

PASS Disturbance

WAVE2>1591-VA_WV(10/01/93)(04:01:44)WAVE2>1591-VB_WV(10/01/93)(04:01:44)WAVE2>1591-VC_WV(10/01/93)(04:01:44)

VAl-g = 100VVBl-g = 100VVCl-g = 100V

TOPCalc Example, cont.TOPCalc Example, cont.

VAl-l = VAl-g - VBl-g

TOPCalc Example, cont.TOPCalc Example, cont.

Line - to - Line Voltage

0 5 10 15-200

-150

-100

-50

0

50

100

150

200

Time (mS)

Volt

age (

V)

Max:Min:Avg:Abs:

RMS:CF :FF :

173.516 -173.269 110.543 173.516 122.867 1.41223 1.11149

VAl-l = 173VVBl-l = 173VVCl-l = 173V

TOPCalc creates result of operation as another quantity specified with a DERIVED tag name.

Data FormattingData Formatting

Preferences can be changed to customize your output:

Base quantities (per unitizing)Units (axis labels and multipliers)Data, comment, and annotation blocksDisplay colorsCumulative probability chartsAxis scaling, grid lines, labels

Changing PreferencesChanging Preferences

Creating TablesCreating Tables

TOP can simply provide a table for the following parameters.

Creating Tables, cont.Creating Tables, cont.

Table can be utilized with any spreadsheet for further analysis.

AvailabilityAvailability

TOP, The Output Processor is available for download from Electrotek Concepts’ Web site at www.electrotek.com/top

Support is available from the TOP Forum, a threaded Internet discussion group, also accessible from the TOP download site