Post on 27-Aug-2018
transcript
Page 1
Toshiba Air Conditioning—RAV SM / SP Data Sheet
RAV-###SDT-E RAV Slim Ducted Systems
All UK duties are based on Cooling Indoor air temperature 22oC DB/16oC WB Outdoor air temperature 28oC DB 50% RH, high fan speed, 5m pipe run. Heating Indoor air temperature 21oC DB Outdoor air temperature –4oC DB 100% RH, high fan speed, 5m pipe run. Values are based on the maximum compressor output.
Data obtained from Toshiba Air Conditioning Web Data July 2013.
www.cdlweb.info
The compact design of the slim duct provides an excellent solution
for applications where shallow ceiling voids are present and maximum control of airflow is required. The slim ducted system
offers improved airflow with ultra low noise levels and is ideal for areas with irregular shapes or large areas require maximum air
distribution.
Page 2
Toshiba Air Conditioning—RAV SM / SP Data Sheet
RAV-###SDT-E RAV Slim Ducted Systems
All UK duties are based on Cooling Indoor air temperature 22oC DB/16oC WB Outdoor air temperature 28oC DB 50% RH, high fan speed, 5m pipe run. Heating Indoor air temperature 21oC DB Outdoor air temperature –4oC DB 100% RH, high fan speed, 5m pipe run. Values are based on the maximum compressor output.
Data obtained from Toshiba Air Conditioning Web Data July 2013.
www.cdlweb.info
Model Reference RAV SM404SDT-E SM566SDT
Nominal Cooling (kW) 3.6 5.0
Nominal Heating (kW) 4.0 5.6
UK Cooling (SM / SP*) (kW) — / 3.4 4.7 / 4.7
UK Sensible Cooling (SM / SP*) (kW) — / 2.54 3.5 / 3.5
UK Heating (SM /SP*) (kW) — / 3.7 4.53 / 5.18
Annual Power Consumption (SM / SP*) (kWh) —- / 515 830 / 780
Sound Pressure (H / L) Rear (dB(A)) 39 / 33 45 / 36
Sound Pressure (H / L) Base (dB(A)) 30 / 26 33 / 28
Sound Power (H / L) Rear (dB(A)) 54 / 48 60 / 51
Sound Power (H / L) Base (dB(A)) 45 / 41 48 / 43
Air Flow (H—L) (m3/h) 690 / 522 780 / 582
Air Flow (H / L) (l/s) 192 / 145 217 / 162
External static pressure range (Pa) 10 - 50 ( 4 steps)
Default static pressure (Pa) 10
Total Dimension (HxWxD) (mm) 210 x 845 x 645
Weight (kg) 22
System Start Current (SM / SP*) (A) 1 / 1
Suggested Fuse Size (SM / SP*) (A) — / 16 16 / 16
Running Current (SM /SP*) (A) —- / 5.20 7.94 / 7.24
Power Supply—Outdoor (V-ph-Hz) 220/240-1-50/60#
Interconnecting Cable 3 Core & Earth
Pipe Sizes Liquid - Suction (inch) 1/4 - 1/2 1/4—1/2
EER / COP (SM / SP*) — / — 3.50 / 4.00 3.01 / 3.52 3.21/3.82
SEER / SCOP (SM / SP*) — / — 5.11 / 3.90 5.06 / 3.82 5.10 / 3.83
Energy Label Cool / Heat (SM / SP*) —/— A/A B/A A/A
Compatible Outdoor Units
Single (RAV-SM### / RAV-SP### AT-E) ——- /SP404 SM564/SP564
Twin (RAV-SM#### / RAV-SP#### AT-E) SM804/SP804 SM1104/SP1104
Triple (RAV-SM#### / RAV-SP#### AT(8)-E) SM1404/SP1404 SM1603/SP1604
Quad (RAV-SM#### / RAV-SP#### AT(8)-E) SM1603/SP1604 SM2244
* Refers to outdoor combination SM= Digital Inverter / SP= Super Digital Inverter # 4 series SM Only