ADMINISTRATION /MULTI-PURPOSE
BUILDING
SEARS LN
HIGHWAY 57
EXISTING PARKING AREA TO BE USED BY CONTRACTOR FOR PARKING, LAY-DOWN AREA, AND PLACEMENT OF PORTABLE BATHROOM.
SHEET NUMBER
01 OF 19 SHEETS
G-000
OWNER: STATE OF MISSOURI
MICHAEL L. PARSON,
GOVERNOR
PROJECT
MANAGEMENT:
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES MANAGEMENT,
DESIGN AND CONSTRUCTION
DESIGNER: IMEG Corporation
#15 Sunnen Drive, Suite 104
St. Louis, Missouri 63143
PROJECT NUMBER: H1901-01
SITE NUMBER: 7701FACILITY NUMBER: 8877701004
Upgrade HVAC & Controls - Administration & Multipurpose BuildingW.E. Sears Youth Center
Poplar Bluff, Missouri
DEPARTMENT OF SOCIAL SERVICES -
DIVISION OF YOUTH SERVICES. IMEG NUMBER: 19002696.00
BID DOCUMENTS SET
DRAWING INDEX:
CODE BLOCK:
APPLICABLE CODES:2012 INTERNATIONAL BUILDING CODE
2006 INTERNATIONAL MECHANICAL CODE
2017 NATIONAL ELECTRIC CODE
G-000 PROJECT COVERSHEET
M-000 MECHANICAL COVERSHEET
M-100 LOWER LEVEL ADMIN PLANS - MECHANICAL
M-101 FIRST FLOOR ADMIN PLANS - MECHANICAL
M-200 ENLARGED PLANS - MECHANICAL
M-201 ENLARGED PLANS - MECHANICAL
M-202 MECHANICAL SECTIONS
M-300 MECHANICAL DETAILS
M-400 MECHANICAL FLOW DIAGRAMS
M-401 MECHANICAL FLOW DIAGRAMS
M-402 MECHANICAL CONTROL DIAGRAMS
M-403 MECHANICAL CONTROL DIAGRAMS
M-404 MECHANICAL CONTROL DIAGRAMS
M-500 MECHANICAL SCHEDULES
M-501 MECHANICAL SCHEDULES
E-000 ELECTRICAL COVERSHEET
E-100 LOWER LEVEL ADMIN PLANS - ELECTRICAL
E-101 FIRST FLOOR ADMIN PLAN - ELECTRICAL
E-300 ELECTRICAL DETAILS AND ONE LINE DIAGRAM
JUNE 23, 2021
MTR
R
DSD
AI
AO
DI
DO
T
T
T
T
H
H
PRESSURE SWITCHPS
MECHANICAL ABBREVIATION KEY
ABBR: DESCRIPTION:
DIFFERENTIAL PRESSURE GAUGE (RANGE)DPG (0-2")
DIFFERENTIAL PRESSURE SWITCHDPS
ABOVE FINISHED FLOORAFF
NC NEW CONNECTION
NOT IN CONTRACTNIC
EA EXHAUST/RELIEF AIR
FD FIRE DAMPER
MA MIXED AIR
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
TRANSFER DUCTTD
TERMINAL AIR BOXTAB
TYPICALTYP
UNO UNLESS NOTED OTHERWISE
CEILING DIFFUSER - EXISTINGCD-E
NORMALLY CLOSEDN.C.
NORMALLY OPENN.O.
BFP BACKFLOW PREVENTER
VENT THROUGH ROOFVTR
EXISTINGE
AC AIR COMPRESSOR
RR-E RETURN REGISTER - EXISTING
CLOSEDC
NOT ALL SYMBOLS MAY APPLY
EG EXHAUST GRILLE
FTR FINNED TUBE REHEAT
RG RETURN GRILLE
SUPPLY DIFFUSERSD
FAN
MOTOR
CONTACTOR
PUMP
STATIC SWITCH
DUCT SMOKE DETECTOR
ACT
DS
DP
FM
ANALOG INPUT
ANALOG OUTPUT
DIGITAL INPUT
DIGITAL OUTPUT
HEATING/ COOLING COIL
FILTER
NORMALL CLOSED CONTACT
NORMALLY OPEN CONTACT
MECHANICAL SYMBOL LIST
SYMBOL: DESCRIPTION:
NOT ALL SYMBOLS MAY APPLY.
ACTUATOR
DOOR SWITCH
DIFFERENTIAL PRESSURE SWITCH
FLOW METER
SP
CD-16/115
AIR TERMINAL PROPERTIES SYMBOLNECK SIZE/CFM
TERMINAL AIR BOX###
### TERMINAL AIR BOX w/REHEAT COIL
HUMIDIFIERH
OPPOSED BLADE DAMPER (REFER TO SCHEDULE)
PARALLEL BLADE DAMPER (REFER TO SCHEDULE)
AIRFLOW MEASUREMENT SYMBOLXX - AHU SYMBOLY - SEQUENTIAL NUMBER
XX-Y
CONTROL VALVE (TWO-WAY)
MECHANICAL SYMBOL LIST
SYMBOL: DESCRIPTION:
PITCH PIPE IN DIRECTION
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
NEW CONNECTION
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
THROTTLING VALVE
AUTOMATIC BALANCING VALVE
CONTROL VALVE (THREE-WAY)
SOLENOID VALVE
CHECK VALVE
SAFETY/RELIEF VALVE
TRIPLE DUTY VALVE (ANGLE TYPE)
TRIPLE DUTY VALVE (IN-LINE TYPE)
VACUUM BREAKER
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE AND HOSE CONNECTION WITH CAP
FLEXIBLE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG
REDUCER - REFERENCE SPECIFICATIONFOR CONCENTRIC/ECCENTRIC AND FOT/FOB
DRAIN VALVE WITH HOSE CONNECTION AND CAP
ALIGNMENT GUIDE
PIPE ANCHOR
EXPANSION JOINT
BOILER BLOW DOWNBD
BOILER FEED WATERBF
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
NOT ALL SYMBOLS MAY APPLY.
PUMP
CHECK VALVE
SAFETY/RELIEF VALVE
T
THERMOSTAT
TEMPERATURE SENSOR (DUCT MOUNTED)
TEMPERATURE SENSOR WITH WELLT
THERMOMETER WITH WELL (DIAL TYPE)T
THERMOMETER WITH WELL (FILLED TYPE)
AVERAGING TEMPERATURE SENSOR
PROBE TEMPERATURE SENSOR
LOW LIMIT TEMPERATURE SWITCH
HUMIDITY SENSOR (DUCT MOUNTED)
H
HUMIDISTAT SENSOR
HUMIDISTAT / SENSOR
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P
P PRESSURE SENSOR (DUCT MOUNTED)
FLOW METERFM
FLOW SWITCHF
FS FLOW SENSOR
ANGLE VALVE
BUTTERFLY VALVE WITH MONITOR SWITCH
PRESSURE SWITCHP
INSPECTOR TEST AND DRAIN VALVE
MONITOR SWITCH
AUTOMATIC DRAIN VALVE
COLD WATER - POTABLECW
DRAIND
HOT WATER - POTABLEHW
HOT WATER CIRCULATING - POTABLEHWC
PIPE SERVING FIXTURE ON FLOOR ABOVE(EXAMPLE: FD = FLOOR DRAIN)FD
ROUTE TO DRAIN
DIRECTION OF AIR FLOW
FLEXIBLE DUCT
MANUAL VOLUME DAMPER
RISE IN DIRECTION OF AIR FLOWR
DUCT CAP
DROP IN DIRECTION OF AIR FLOWD
DUCT DOWN
DUCT UP
SUPPLY/OUTSIDE AIR DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST/RELIEF AIR DUCT SECTION
LIQUID PROPANELP
1. THE SIZE OF BRANCH PIPING TO TERMINAL HEATING DEVICES AND COILS SHALL BE 3/4"UNLESS NOTED OTHERWISE.
2. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST FLOOR DRAIN.
PIPING GENERAL NOTES:
1. NEW THERMOSTATS SHALL BE PLACED IN THE SAME LOCATION AS THE EXISTING REMOVEDTHERMOSTATS.
2. PROVIDE ACCESS DOORS AT ALL DUCT MOUNTED EQUIPMENT.3. CONTRACTOR MAY REUSE PORTIONS OF EXISTING DUCT PROVIDED SIZES AND PRESSURE
CLASSES ARE CORRECT, DUCT IS THOROUGHLY CLEANED AND FREE OF DEFECTS, AND ALLTRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS ARE SEALEDAS SPECIFIED FOR NEW DUCTWORK.
VENTILATION GENERAL NOTES:
1. REFER TO EQUIPMENT SCHEDULES TO CROSS REFERENCE WHICH CONTROL DIAGRAMSAPPLY TO WHICH ITEMS OF EQUIPMENT. REFER TO TERMINAL AIR BOX (TAB) SCHEDULESFOR TEMP SENSOR REQUIREMENTS FOR EACH TAB.
2. EACH D.I., D.O., A.I. AND A.O. POINT SHOWN FOR ALL CONTROL DIAGRAMS SHALL BEDISCRETE FROM ALL OTHER POINTS EXCEPT AS SPECIFICALLY NOTED.
3. ALL WIRING, CONTROL COMPONENTS, DEVICES AND PROGRAMMING SHOWN ON THESECONTROL DRAWINGS SHALL BE PROVIDED BY THE TCC UNLESS SPECIFICALLY NOTEDOTHERWISE.
4. TEMPERATURE CONTROL CABLING, CONDUIT, BOXES, IDENTIFICATION: REFER TO THESPECIFCATIONS FOR A COMPLETE LIST OF REQUIREMENTS. THE FOLLOWING SCHEDULE ISPROVIDED AS A CONVENIENCE. REFER TO SECTION 23 09 00 FOR ADDITIONAL DETAILEDREQUIREMENTS.
A. CABLE/WIRE JACKET COLOR: GREYB. CONDUIT AND BOX COLOR: FACTORY STANDARD FINISHC. CABLE/WIRE INSTALLATION: IN CONDUIT
5. ALL ACTUATORS SHALL BE OF THE ELECTRICAL TYPE FOR THIS PROJECT UNLESS ANACTUATOR IS SPECIFICALLY INDICATED ON THE DRAWINGS OR SPECIFICATIONS TO BEPNEUMATIC.
6. ALL MODULATING DAMPER AND VALVE ACTUATORS SHOWN WITH POSITION FEEDBACKSHALL HAVE THE VALVE POSITION DISPLAYED ON GRAPHICAL SCREEN ADJACENT TO THEDAMPER/VALVE COMMAND SIGNAL. DISPLAYED VALVE POSITION SHALL BE FROM THEFEEDBACK DEVICE/CIRCUIT (OUTPUT SIGNAL FROM THE FMCS TO THE ACTUATOR IS NOTACCEPTABLE)
7. MODULATING SIGNALS SHALL BE DISPLAYED AS % OPEN (SIGNALS DISPLAYED AS %CLOSED ARE NOT ACCEPTABLE).
8. PRESSURE TRANSMITTERS WHOSE SIGNAL IS UTILIZED FOR MAINTAINING DUCT STATICPRESSURE SHALL BE WIRED DIRECTLY TO THE CONTROLLER THAT MODULATES FANSPEED. SIGNAL SHALL BE COMPLETELY INDEPENDENT OF THE FMCS NETWORK.
9. PRESSURE TRANSMITTERS WHOSE SIGNAL IS UTILIZED FOR MAINTAINING DIFFERENTIALPRESSURE OF ANY PUMPED WATER SYSTEM (E.G. HEATING HOT WATER, CHILLED WATERAND THE LIKE) SHALL BE WIRED DIRECTLY TO THE CONTROLLER THAT MODULATES PUMPSPEED. SIGNAL SHALL BE COMPLETELY INDEPENDENT OF THE FMCS NETWORK.
10. ALL CONTROL COMPONENTS SUCH AS RELAYS, SWITCHES, DDC CONTROLLERS, ETC.SHALL BE MOUNTED IN STEEL ENCLOSURES WITH STEEL MOUNTING BACKPLATES PERSPECIFICATION 23 09 00.
11. EACH CONTROL PANEL SHALL HAVE A LAMINATED COPY OF THE APPLICABLE SEQUENCE OFOPERATION AND CONTROL DIAGRAM INDICATING THE POINTS, COMPONENTS ANDOPERATION OF EQUIPMENT ASSOCIATED WITH EACH PANEL. REFER TO SECTION 23 09 00FOR ADDITIONAL REQUIREMENTS.
12. TCC SHALL EXTEND CONTROL SIGNAL FROM ADDRESSABLE RELAY DEVICE SERVING EACHAIR HANDLING UNIT. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS. TCC SHALLEXTEND AND TERMINATE WIRING AS REQUIRED FOR EQUIPMENT SHUTDOWN.
13. TCC SHALL EXTEND 24 VOLT POWER FROM CONTROL POWER JUNCTION BOX SHOWN ONFLOOR PLANS TO ALL TERMINAL AIR BOX CONTROLLER JUNCTION BOXES. TCC SHALLPROVIDE ALL WIRING, SUPPORTS, FUSING SPACE, TOGGLE SWITCHES, AND ALL OTHERELECTRICAL COMPONENTS REQUIRED FOR COMPLETE INSTALLATION.
14. TCC SHALL EXTEND 120 VOLT POWER FROM CONTROL POWER JUNCTION BOX TO ALLTERMINAL AIR BOX CONTROLLERS SHOWN ON MECHANICAL PLANS. TCC SHALL PROVIDEALL TRANSFORMERS WIRING, SUPPORTS, FUSING,TOGGLE SWITCHES, AND ALL OTHERELECTRICAL COMPONENTS REQUIRED FOR COMPLETE INSTALLATION.
15. ELEMENT LENGTHS FOR BOTH MIXED AIR TEMP SENSORS AND LOW LIMIT TEMP SWITCHESSHALL BE MINIMUM 1 LINEAR FOOT PER SQUARE FOOT OF COIL SURFACE AREA. PROVIDEMULTIPLE SENSORS AND SWITCHES AS NEEDED TO ACHIEVE REQUIRED ELEMENTLENGTHS. LOCATE RESET SWITCHES MAX. 6'-6" ABOVE ADJACENT STANDING SURFACE (E.G.ROOF, PLATFORM OR FLOOR) SO THE RESET SWITCH CAN BE CYCLED WITHOUT THE NEEDFOR A LADDER.
16. TO PREVENT GENERATOR OVERLOADING, TCC SHALL PROGRAM A STAGGERED START TIMEFOR ALL MECHANICAL EQUIPMENT THAT IS CONTROLLED BY FMCS TO INCLUDE, BUT NOTLIMITED TO, AIR HANDLERS, PUMPS, EXHAUST FANS, AND CHILLERS. THE FIRST EQUIPMENTSHALL START 2 MINUTES (ADJ.) FROM THE TIME THE FMCS RECEIVES THE SIGNAL THAT THETRANSFER SWITCH CHANGED TO EMERGENCY POWER SOURCE WITH ALL EQUIPMENTBEING ENERGIZED WITHIN A 20 MINUTE (ADJ.) TIME SPAN. COORDINATE ORDER OFEQUIPMENT STAGING WITH OWNER'S REPRESENTATIVE.
17. CONTROL DIAGRAMS ARE SCHEMATIC IN NATURE AND DO NOT SHOW ALL REQUIREDCONTROL DEVICES AND COMPONENTS. REFER TO FLOOR PLANS, FLOW DIAGRAMS ANDDETAILS FOR ADDITIONAL CONTROL DEVICES, COMPONENTS AND REQUIREMENTS NOTSHOWN ON THESE CONTROL DRAWINGS.
18. TCC SHALL PROVIDE ALL CONTROL COMPONENTS AND ACCESSORIES AS REQUIRED FOREQUIPMENT TO BE CONTROLLED AS DESCRIBED IN THE SEQUENCE OF OPERATIONREGARDLESS OF WHETHER ALL CONTROL COMPONENTS OR POINTS ARE SHOWN IN THEASSOCIATED CONTROL DIAGRAM.
TEMPERATURE CONTROL GENERAL NOTES:
MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. AREDIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETEINSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDINGCONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROMARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS ORPHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDECLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TOVERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TOVERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCESOR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDINGWITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKEREASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPERACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TOCOORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OREXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICALCHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OFDESIGN.
7. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE ISRESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, ANDFINISH.
8. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THEGC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATEPANEL TYPE AND COLOR WITH OWNER. NOTIFY THE GC OF THE REQUIRED ACCESS PANELSPRIOR TO BIDDING.
9. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING,AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BESEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURERFOR OUTDOOR USE.
10. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL,PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISETRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELSWITHIN ROOMS.
11. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVEDOPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALLRELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
12. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENTMANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES ANDREQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,PIPING, DUCTWORK, ETC.
13. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.14. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR
STARTERS, SWITCHES, AND DISCONNECTS.15. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.16. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BECRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELDSURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS ANDREPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONSBEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFOREFABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELDCONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORKAND SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHER UTILITIES AREREQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OFWORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATEDWITH HIS WORK.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OFCEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALLCONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TOBIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITHNEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALLEITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT ITDOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICALSYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURINGCONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THATREMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER AT LEAST 48 HOURS BEFORE SHUTTING DOWN ANYSYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAINUNTIL NEW SYSTEMS ARE INSTALLED. MINIMIZE OUTAGE DURATION.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FORTIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS ANDCONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELYDRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENTTHAT HAS BEEN REMOVED.
1. BEFORE ANY DEMOLITION WORK BEGINS A PRE-BALANCE TEST SHALL BE PERFORMED OFEXISTING SYSTEMS BY THE TESTING, ADJUSTING AND BALANCING (TAB) CONTRACTOR PERSPECIFICATION 23 05 93.
2. TAB CONTRACTOR SHALL COMPILE AND SUBMIT THE FINAL PRE-DEMOLITION REPORTWITHIN 10 WORKING DAYS AFTER THE FIELD MEASUREMENTS ARE COMPLETED. FINAL TABREPORT SHALL BE SUBMITTED FOR REVIEW TO THE ARCHITECT/ENGINEER. TESTING SHALLINCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.
3. PRIOR TO DEMOLITION, CONTRACTOR SHALL SURVEY ALL EXISTING VAV BOXES FORPROPER OPERATION. CONTRACTOR SHALL INFORM OWNER OF ANY EXISTING BOXES THATARE DAMAGED OR NOT WORKING PROPERLY. CONTRACTOR SHALL BE RESPONSIBLE FORREPAIR OR REPLACEMENT OF ANY VAV BOXES THAT WERE NOT REPORTED PRIOR TODEMOLITION. REFER TO SPECIFICATION SECTION 23 05 93 FOR PRE-TESTING ANDBALANCING REQUIREMENTS.
TAB PRE-DEMOLITION NOTES:
1. AFTER CONSTRUCTION ACTIVITIES ARE COMPLETE, TESTING, ADJUSTING (TAB) ANDBALANCING CONTRACTOR SHALL BALANCE ALL EQUIPMENT LISTED IN SPECIFICATION 23 0593 INCLUDING EXISTING AIR INLETS AND OUTLETS.
2. EXISTING AIR INLET AND OUTLET CFM SHOWN ON DRAWINGS ARE FROM EXISTINGDRAWINGS, AND ARE FOR REFERENCE ONLY. CONTRACTOR SHALL USE PRE-BALANCEVALUES, AND NOT EXISTING CFM SHOWN ON DRAWINGS, UNLESS DIRECTED BY ENGINEERBASED ON PRE-DEMOLITION BALANCE REPORT.
3. TAB CONTRACTOR SHALL COMPILE AND SUBMIT COPIES OF THE FINAL POST-CONSTRUCTION TAB REPORT AS REQUIRED BY SECTION 23 05 93.
4. THE FINAL POST CONSTRUCTION REPORT SHALL INCLUDE ALL ITEMS REQUIRED IN THESPECIFICATIONS.
TAB POST-CONSTRUCTION NOTES:
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
1VIEW NAME1/8" = 1'-0"
1
M101
14
32
T101
SIMDETAIL REFERRED TO BY ELEVATION
SHEET DETAIL IS LOCATED ON
INDICATES SIMILAR DETAIL REFERENCED IN MULTIPLE LOCATIONS
SIM
INDICATES SIMILAR DETAIL REFERENCED IN MULTIPLE LOCATIONS
LEVEL NAME
10' - 0" HEIGHT ABOVE PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL
NO R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
NEW WORK UNDERFLOOR OR UNDERGROUND BY THIS CONTRACTOR (DARK LONG DASHED LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
LINE TYPE KEY:
TEMPERATURE CONTROLS CONTRACTORT.C.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
1. BID ALTERNATE #1: DEMOLISH EXISTING VARIABLE AIR VOLUME BOXES AND PROVIDE NEW.2. BID ALTERNATE #2: PROVIDE USAGE METERING BY THE BUILDING AUTOMATION SYSTEM
FOR ELECTRICAL, WATER, AND LIQUID PROPANE UTILITIES SERVING BUILDING.
BID ALTERNATES:
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-000
MECHANICALCOVERSHEET
KATDENSCORPZKATDEN
06/23/2021
2
M-000
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
CLASSROOM130
CLASSROOM 129
CLASSROOM133
CLASSROOM134
TOILET136
CLASSROOM123
LABORATORY128
OFFICE 126
OFFICE127
LIBRARY121
FOYER102
CUST.105
WORK ROOM108
CONFERENCE RM.109
INFIRMARY 107
EXAM. RM.106
WOMEN217
OFFICE112
OFFICE111
OFFICE110
STO.118
WOMEN117
MEN116
TEST CENTER113
CLASSROOM122
TOILET104
STO.115
CUSTODIAN135
TT
TT
T
T
T
T
T
T
T T
T
CLASSROOM130
CLASSROOM 129
CLASSROOM133
CLASSROOM134
TOILET136
CLASSROOM123
LABORATORY128
OFFICE 126
OFFICE127
LIBRARY121
FOYER102
CUST.105
WORK ROOM108
CONFERENCE RM.109
INFIRMARY 107
EXAM. RM.106
WOMEN217
OFFICE112
OFFICE111
OFFICE110
STO.118
WOMEN117
MEN116
TEST CENTER113
CLASSROOM122
TOILET104
STO.115
CUSTODIAN135
T
TT
TT
T
T
T
T
T
T
T T
T
SG-E
24x8/300
RR-E SG-E
24x8/300
SG-E
24x8/300
VAV 1-4
VAV 1-5
SG-E
24x8/300
RR-E SG-E
24x8/300
SG-E
24x8/300
RR-E SG-E
24x8/300
VAV 1-2
VAV 1-3
SG-E
24x8/300
RR-E
SD-E
6/150
RG-E SD-E
6/150RG-E
SD-E
8/175SD-E
8/175
26x14 36x14
24x10
EG-E
12/400EG-E
12/400
26x8
SD-E
6/135
RG-E
RG-E
SD-E
8/200
SD-E
10/300
RG-E
VAV 1-10
SD-E
10/300
VAV 1-11
VAV 1-12
SD-E
10/250
SD-E
10/250
RG-E
SD-E
8/200RG-E
SD-E
8/200
RG-E RG-E
SD-E
8/200
VAV 1-14
VAV 1-13
EG-E
12/300
SD-E
10/300
RG-E
EG-E
12/300
SD-E
6/135
SD-E
6/135
VAV 1-9
SD-E
6/135
RG-E
RG-E
SD-E
10/300
VAV 1-8
SD-E
8/190
SD-E
8/190
SD-E
8/190SD-E
8/190
VAV 1-7
RR-E
VAV 1-6
SG-E
22x8/400
VAV 1-1
RG-E
30x1
426x1
420x1
4
22x8
22x8
30x1
2
10x8
10x8
16x8
16x8
16x14
10x8
10x8 16x8
16x8
3/4"HWS
3/4"HWR
14x103/4"HWS3/4"HWR
46x183/4"HWR
3/4"HWS
2"HWR2"HWS
42x20
3/4"HWS3/4"HWR
12x8
1 1/4"HWR
1 1/4"HWS
1 1/2"HWS1 1/2"HWR1 1/4"HWS
1 1/4"HWR
1"HWR1"HWS
3/4"HWS
3/4"HWR
3/4"HWR
3/4"HWS
3/4"HWS3/4"HWR
3/4"HWR3/4"HWS
3/4"HWR3/4"HWS
3/4"HWR3/4"HWS
8x12
14x4
8x4
8x4
RR-E
RR-E
12x12
3/4"HWS3/4"HWR
3/4"HWS
3/4"HWR
3/4"HWR3/4"HWS
3/4"HWR3/4"HWS12x10
6x12
3/4"HWR3/4"HWS
1"HWR1"HWS
3/4"HWR3/4"HWS
6x10
1 1/4"HWR1 1/4"HWS
14x10
10x12
1"HWR
1"HWS
3/4"HWR3/4"HWS
46x18 SA UP
42x20 RA UP
46x18 EA UP
22
2
2
2
2
2
2
2
2
2
2
2
UH-E
AC-E
8
1
1
1
1
FTR-E FTR-E FTR-E FTR-E
FTR-E
FTR-E
FTR-E FTR-E FTR-E FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E FTR-E
1
1
1
1
3/4" HWR DN
3/4" HWS DN
3/4" HWS DN3/4" HWR DN
UH-E
UH-E
3/4" HWR DN
3/4" HWS DN
3/4" HWS UP & DN3/4" HWR UP & DN
6
3" CWS & CWR TO
CHILLERS
3" CWS & CWR UP
3" LP UP
3" CW UP
REMOVE EXISTING STATIC PRESSURE SENSOR AND ASSOCIATED SUPPORTS AND PNEUMATIC TUBING.
SP
3/4" HWS UP
3/4" HWR UP
3/4" HWS UP
3/4" HWR UP
3/4" HWR UP
3/4" HWS UP
3/4" HWR UP
3/4" HWS UP
3/4" HWR UP
3/4" HWS UP
2" HWS UP
2" HWR UP
8
8
8
8
8
8
8
8
CV 1-5 1
CV 1-6 1
1 CV 1-4
CV 1-1
CV 1-2
1
CV 1-3
3/4" HWS UP
3/4" HWR UP
1
20x1
426x1
430x1
4
36x1426x1416x14
16x8
16x8
10x8
10x8 46x18
16x8
16x8
10x8
10x83/4"HWR
3/4"HWS
1 1/4"HWR1 1/4"HWS
3/4"HWS3/4"HWR
1 1/4"HWR
1 1/4"HWS
3/4"HWS3/4"HWR
3/4"HWR3/4"HWS
3/4"HWR
3/4"HWS
3/4"HWR3/4"HWS
3/4"HWR3/4"HWS
1"HWR
1"HWS
1 1/4"HWR1 1/4"HWS
1 1/2"HWR1 1/2"HWS
3/4"HWS
3/4"HWR
1"HWR1"HWS
3/4"HWS3/4"HWR
3/4"HWS
3/4"HWR
3/4"HWR3/4"HWS
3/4"HWS3/4"HWR
12x8
14x10
SG-E
24x8/300
14x4
12x12
6x12
12x10 6x1010x12
22x826x8
24x10
30x12
14x10
3/4"HWS
3/4"HWR
42x20
8x4
8x4
8x12
3/4"HWR3/4"HWS
SG-E
24x8/300
RR-E SG-E
24x8/300
RR-E SG-E
24x8/300
SG-E
24x8/300RR-E
SG-E
24x8/300
RR-E SG-E
24x8/300
SG-E
24x8/300
VAV 1-4
VAV 1-5
VAV 1-3
VAV 1-2
VAV 1-7
SD-E
8/175
SD-E
8/175
SD-E
6/150SD-E
6/150
RR-E
SD-E
8/190
SD-E
8/190
SD-E
8/190
SD-E
8/190
RG-E
RG-E
SD-E
6/135
SD-E
6/135
VAV 1-9
SD-E
6/135
EG-E
12/300
SD-E
6/135
RG-E
RG-E
SD-E
8/200
RR-E RR-E
VAV 1-10
SD-E
10/300
SD-E
10/300
VAV 1-11
RG-E
SD-E
10/250
SD-E
10/250
VAV 1-12
RG-E RG-E
SD-E
8/200
RG-E
SD-E
8/200RG-E
SD-E
8/200
VAV 1-14
VAV 1-13
SD-E
10/300
RG-E
EG-E
12/300
SD-E
10/300
EG-E
12/400EG-E
12/400
RR-E
3/4"HWS
3/4"HWR
3/4"HWR3/4"HWS
2"HWR2"HWS
SG-E
22x8/400
RG-E
RG-E
RG-E
VAV 1-1
VAV 1-6
VAV 1-8
12x8
46x18 SA UP
42x20 RA UP
46x18 EA
UP
UH-E
4
4
4
4
4
5
4
4
4
4
4
7
5
4
5
5
7
7
FTR-E FTR-E FTR-E FTR-E
FTR-E
FTR-E
FTR-E FTR-E FTR-E FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E FTR-E
3/4" HWR DN
3/4" HWS DN
3/4" HWS DN3/4" HWR DN
3/4" HWR DN
3/4" HWS DN
3/4" HWS UP & DN3/4" HWR UP & DN
3
3
3
CONDUIT SHALL PENETRATE FLOOR OF EXISTING MECHANICAL ROOM 220. CONDUIT SHALL BE ROUTED APPROXIMATELY AS SHOWN TO NEW BAS CONTROL PANEL IN CUSTODIAN 135.UH-E
UH-E
7
7
7
7
7
7
7
APPROXIMATE LOCATION OF NEW BAS CONTROL PANEL IN CUSTODIAN 135. MOUNT PANEL ON CMU WALL. COORDINATE EXACT LOCATION WITH OWNER. COORDINATE POWER, DATA CONNECTION, AND INSTALLATION WITH ELECTRICAL.
3" CWS & CWR TO
CHILLERS
3" CWS & CWR UP
3" LP UP
6" CW UP
PROVIDE NEW STATIC PRESSURE SENSOR AND CONNECT TO NEW BAS. REFER TO AIR HANDLING UNIT CONTROL DIAGRAM ON M-403.
SP
4
4
4
3/4" HWS UP
3/4" HWR UP
3/4" HWS UP
3/4" HWR UP
3/4" HWR UP
3/4" HWS UP
3/4" HWR UP
3/4" HWS UP
3/4" HWR UP
3/4" HWS UP
2" HWS UP
2" HWR UP
CV 1-6 9
9CV 1-5
CV 1-49
9 CV 1-1
9 CV 1-2
3/4" HWR UP3/4" HWS UP
CV 1-3 9
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-100
LOWER LEVEL ADMINPLANS - MECHANICAL
KATDENSCOPRZKATDEN
06/23/2021
3
M-100NO R HT
1/8" = 1'-0"1 LOWER LEVEL ADMIN PLAN - MECHANICAL DEMOLITION
GENERAL SHEET NOTES:
1. EXISTING CONDITIONS SHOWN ARE BASED ON INFORMATION AVAILABLE FROM EXISTING DRAWINGS AND LIMITED FIELD VERIFICATION. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK.
2. REMOVE CEILING TILES AS NEEDED TO ACCESS VAV BOXES DURING CONSTRUCTION. DOCUMENT AND NOTIFY OWNER OF ALL CEILING TILES DAMAGED PRIOR TO REMOVAL. CEILING TILES SHALL BE CAREFULLY REMOVED AND STORED FOR REINSTALLATION. TILES SHALL BE REPLACED BY CONTRACTOR AT NO COST TO OWNER IF DAMAGE IS OBSERVED DURING CONSTRUCTION OR AFTER AND NOT PREVIOUSLY DOCUMENTED.
3. BID ALTERNATE #1: DEMOLISH ALL EXISTINGVAVS SHOWN ON FLOOR PLANS AND REPLACE WITH ALL NEW VAVS WITH DDC CONTROLS IN LIEU OF RETROFITTING EXISTING VAVS WITH DDC CONTROLS. REMOVE ALL EXISTING HANGERS, BRACKETS, SUPPORTS, PNEUMATIC TUBING, ACCESSORIES, ETC. REMOVE PORTION OF DUCTWORK AND INSULATION UPSTREAM OF DOWNSTREAM OF EXISTING VAV AS REQUIRED TO CONNECT EXISTING DUCTWORK TO NEW VAV. VAVS THAT HAVE HYDRONIC REHEAT COILS SHALL BE PROVIDED WITH DDC CONTROL VALVES.
#
NO R HT
1/8" = 1'-0"2 LOWER LEVEL ADMIN PLAN - MECHANICAL NEW WORK
KEYNOTES:
1. REMOVE EXISTING PNEUMATIC HEATING WATER CONTROL VALVE AND ASSOCIATED PNEUMATIC TUBING. PREPARE FOR NEW CONNECTIONS FOR DDC SENSORS AND CONTROLS.
2. REMOVE EXISTING PNEUMATIC THERMOSTAT AND ASSOCIATED WIRING, HANGERS, ACCESSORIES, ETC. REMOVE ASSOCIATED PNEUMATIC TUBING.
3. PROVIDE NEW TWO-WAY DDC CONTROL VALVE ON UNIT HEATING WATER OUTLET. CONNECT CONTROL VALVE TO NEW BAS.
4. PROVIDE NEW DDC THERMOSTAT AND ALL ASSOCIATED WIRING, HANGERS, ACCESSORIES, ETC. CONTRACTOR SHALL PATCH AND PAINT WALL TO MATCH EXISTING AS REQUIRED. CONTRACTOR SHALL USE WIRE MOLD MATCHING EXISTING WALL COLOR FOR NEW THERMOSTAT WIRING ON CMU WALLS.
5. PROVIDE NEW TWO-WAY DDC CONTROL VALVE ON UNIT HEATING WATER OUTLET, DISCHARGE AIR TEMPERATURE SENSOR, SUPPLY AIRFLOW SENSOR, AND DAMPER ACTUATOR TO BE CONNECTED TO NEW BAS.
6. REMOVE EXISTING AIR COMPRESSOR, AIR DRYER, AND ASSOCIATED HANGERS, SUPPORTS, ACCESSORIES, ETC. REMOVE ASSOCIATED PNEUMATIC TUBING. ALL EXISTING EQUIPMENT SHALL BE RETURNED TO THE OWNER.
7. PROVIDE NEW DDC DISCHARGE AIR TEMPERATURE SENSOR, SUPPLY AIRFLOW SENSOR, AND DAMPER ACTUATOR TO BE CONNECTED TO NEW BAS.
8. REMOVE EXISTING PNEUMATIC CONTROLS AND ASSOCIATED PNEUMATIC TUBING. PREPARE FOR NEW CONNECTIONS FOR DDC SENSORS AND CONTROLS.
9. PROVIDE NEW DDC THREE-WAY CONTROL VALVE ON HWR SERVING EXISTING FTR UNITS. CONNECT CONTROL VALVE TO NEW BAS.
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
WOMEN217
MEN218
RECEPTION 226
OFFICE 222
SECRETARIAL AREA213
OFFICE214
OFFICE 215
OFFICE 212
SECRETARY 210
OFFICE 208
FILE RM.209
CONFERENCE RM.207
OFFICE 206
OFFICE 205
WAITING 202
RECEPT ST.231
OFFICE 227
FILE229
FILE228
OFFICE 223
OFFICE 224
BUSINESS OFFICE230
T
T
T
T
T
T
TT
T
TT
T
T
WOMEN217
MEN218
RECEPTION 226
OFFICE 222
SECRETARIAL AREA213
OFFICE214
OFFICE 215
OFFICE 212
SECRETARY 210
OFFICE 208
FILE RM.209
CONFERENCE RM.207
OFFICE 206
OFFICE 205
WAITING 202
RECEPT ST.231
OFFICE 227
FILE229
FILE228
OFFICE 223
OFFICE 224
BUSINESS OFFICE230
T
T
T
T
T
T
TT
T
TT
T
T
16x12
20x20
12x8
SD-E
10/350
SD-E
10/350
SD-E
8/200
SD-E
8/200
SD-E
8/200
SD-E
8/200
SD-E
8/200
RG-E
RG-E
RG-E
VAV 2-1
RG-E
SG-E
30x8/700
RG-ESD-E
8/350
SD-E
8/400
SD-E
8/200
RG-E
VAV 2-5
VAV 2-4
VAV 2-8
SD-E
12/400
RG-E
VAV 2-9
VAV 2-13
VAV 2-6
SD-E
6/150
RG-E
SD-E
10/300
SD-E
10/300
RG-E
VAV 2-11
VAV 2-12VAV 2-10
SD-E
10/350
SD-E
10/350
RG-E
SD-E
8/200
RG-E RG-E
SD-E
8/200
SG-E
24x8/300
SG-E
24x4/200
SG-E
26x8/600
RG-E
VAV 2-2
VAV 2-3
SG-E
24x8/300
RR-E
42x2
0
14ø
10x10
14x10
14x10
14x10
36x18
42x18
16ø
20x12
26ø
3/4"HWR
3/4"HWS
10x8
3/4"HWR3/4"HWS
3/4"HWR3/4"HWS
3/4"HWR3/4"HWS
12x8
1"HWS
1"HWR
8x8
28ø
EG-E
12/450
EG-E
12/450
10x10
20x10
EXISTING
EXHAUST FAN
30x12
M-2002
4
4
4
44
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E FTR-E
FTR-E
3
6
7
7
M-2012
7
7
7
PROVIDE NEW STATIC PRESSURE SENSOR AND CONNECT TO NEW BAS. REFER TO AIR HANDLING UNIT CONTROL DIAGRAM ON M-403.
SP
CV 2-1
9
9
CV 2-2
CV 2-3
CV 2-4CV 2-5
9
99
9
CV 2-6
9CV 2-7
EXISTING EXHAUST LOUVER
EXISTING DAMPER
SD-E
8/200
SD-E
8/200
SD-E
10/350
SD-E
10/350
RG-E
RG-E
RG-ESD-E
8/350
RG-E
SD-E
8/200
SD-E
8/400
VAV 2-5
VAV 2-4
SD-E
12/400
VAV 2-8
RG-E
SD-E
10/350
RG-ESD-E
10/350
RG-E
SD-E
8/200 RG-E
SD-E
8/200
VAV 2-12
VAV 2-10
VAV 2-11
SD-E
10/300
SD-E
10/300
RG-E
SD-E
6/150
VAV 2-13
VAV 2-6
RG-E
RR-ESG-E
24x8/300
SG-E
24x8/300
SG-E
24x4/200
SG-E
26x8/600
SD-E
8/200
RG-ESD-E
8/200
RG-E
SD-E
8/200
VAV 2-3
RG-E
VAV 2-1
SG-E
30x8/700
16x12
20x20
42x2
0
12x8
14ø
10x10
14x10
14x10 14x10
42x18
28ø
20x1216ø
8x8
12x8
3/4"HWR3/4"HWS26ø
1"HWR1"HWS
3/4"HWS3/4"HWR
3/4"HWR3/4"HWS
VAV 2-2
VAV 2-9
EG-E
12/450
EG-E
12/450
10x10
20x10
30x12
M-2001
2
2
2
22
2
2
2
2
2
2
2
2
1
8
1
1
1
1
1
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
FTR-E
1
EXISTING
EXHAUST FAN
M-2011
REMOVE EXISTING STATIC PRESSURE SENSOR AND ASSOCIATED SUPPORTS AND PNEUMATIC TUBING.
SP
8
8
8
88
1
CV 2-1
1
CV 2-2
1 CV 2-3
CV 2-41 CV 2-5
1
CV 2-6
1
1CV 2-7
EXISTING EXHAUST LOUVER
EXISTING DAMPER
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-101
FIRST FLOOR ADMINPLANS - MECHANICAL
KATDENSCOPRZKATDEN
06/23/2021
4
M-101NO R HT
1/8" = 1'-0"2 FIRST FLOOR ADMIN PLAN - MECHANICAL NEW WORK
GENERAL SHEET NOTES:
1. EXISTING CONDITIONS SHOWN ARE BASED ON INFORMATION AVAILABLE FROM EXISTING DRAWINGS AND LIMITED FIELD VERIFICATION. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK.
2. REMOVE CEILING TILES AS NEEDED TO ACCESS VAV BOXES DURING CONSTRUCTION. CEILING TILES SHALL BE CAREFULLY REMOVED AND STORED FOR REINSTALLATION. TILES SHALL BE REPLACED BY CONTRACTOR IF DAMAGED DURING CONSTRUCTION. DOCUMENT AND NOTIFY OWNER OF ALL CEILING TILES DAMAGED PRIOR TO REINSTALLATION.
3. BID ALTERNATE #1: DEMOLISH ALL EXISTINGVAVS SHOWN ON FLOOR PLANS AND REPLACE WITH ALL NEW VAVS WITH DDC CONTROLS IN LIEU OF RETROFITTING EXISTING VAVS WITH DDC CONTROLS. REMOVE ALL EXISTING HANGERS, BRACKETS, SUPPORTS, PNEUMATIC TUBING, ACCESSORIES, ETC. REMOVE PORTION OF DUCTWORK AND INSULATION UPSTREAM OF DOWNSTREAM OF EXISTING VAV AS REQUIRED TO CONNECT EXISTING DUCTWORK TO NEW VAV. VAVS THAT HAVE HYDRONIC REHEAT COILS SHALL BE PROVIDED WITH DDC CONTROL VALVES.
KEYNOTES:
1. REMOVE EXISTING PNEUMATIC HEATING WATER CONTROL VALVE AND ASSOCIATED PNEUMATIC TUBING. PREPARE FOR NEW CONNECTIONS FOR DDC SENSORS AND CONTROLS.
2. REMOVE EXISTING PNEUMATIC THERMOSTAT AND ASSOCIATED WIRING, HANGERS, ACCESSORIES, ETC. REMOVE ASSOCIATED PNEUMATIC TUBING BACK.
3. PROVIDE NEW TWO-WAY DDC CONTROL VALVE ON UNIT HEATING WATER OUTLET. CONNECT CONTROL VALVE TO NEW BAS.
4. PROVIDE NEW DDC THERMOSTAT AND ALL ASSOCIATED WIRING, HANGERS, ACCESSORIES, ETC. CONTRACTOR SHALL PATCH AND PAINT WALL TO MATCH EXISTING AS REQUIRED. CONTRACTOR SHALL USE WIRE MOLD MATCHING EXISTING WALL COLOR FOR NEW THERMOSTAT WIRING ON CMU WALLS.
5. PROVIDE NEW TWO-WAY DDC CONTROL VALVE ON UNIT HEATING WATER OUTLET, DISCHARGE AIR TEMPERATURE SENSOR, SUPPLY AIRFLOW SENSOR, AND DAMPER ACTUATOR TO BE CONNECTED TO NEW BAS.
6. PROVIDE NEW RELAY AND CURRENT TRANSFORMER TO CONNECT EXISTING EXHAUST FAN TO NEW BAS.
7. PROVIDE NEW DDC DISCHARGE AIR TEMPERATURE SENSOR, SUPPLY AIRFLOW SENSOR, AND DAMPER ACTUATOR TO BE CONNECTED TO NEW BAS.
8. REMOVE EXISTING PNEUMATIC CONTROLS AND ASSOCIATED PNEUMATIC TUBING. PREPARE FOR NEW CONNECTIONS FOR DDC SENSORS AND CONTROLS.
9. PROVIDE NEW DDC THREE-WAY CONTROL VALVE ON HWR SERVING EXISTING FTR UNITS. CONNECT CONTROL VALVE TO NEW BAS.
#
NO R HT
1/8" = 1'-0"1 FIRST FLOOR ADMIN PLAN - MECHANICAL DEMOLITION
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
26x30
32x2
6
30x2644x20
30x2632x26
AHU-1E
AHU-2E
42x2
0
20x1
2
12x8
26x26
BLR-1E
BLR-2E
EXPANSION TANK
EXISTING WATER
HEATER
EXISTING RETURN FAN R-1
EXISTING RETURN FAN R-2
8'x4' OA LOUVER
EXISTING BOILER FLUE THROUGH ROOF. REMOVE ALL FLUE DUCTWORK AND ASSOCIATED HANGERS, BRACKETS, SUPPORTS, ETC.
EXISTING MOTOR
OPERATED DAMPERS
FD-E AT FLOOR
PENETRATION
FD-E
FD-E
FD-E FD-E FD-E
CH-2E CH-1E
EMERGENCY GENERATOR
AND DAY TANK
1
1
3
EXISTING PLUMBING
CIRCULATION PUMP
VAV 2-7 5
P-5EP-4E
P-3E
P-1EP-2E
EXISTING CHILLER EXISTING CHILLER
FD-E AT FLOOR PENETRATION
REMOVE EXISTING 10x10 COMBUSTION AIR INTAKE DUCT THAT EXTENDS TO FLOOR BACK TO OA PLENUM AND SEAL AIRTIGHT.
6
6
REMOVE EXISTING DUCTWORK BACK TO MAIN AND SEAL AIRTIGHT.
EXISTING MOTOR OPERATED
DAMPERS
3
REMOVE EXISTING MA DUCTWORK IN THE VERTICAL AND PREPARE FOR NEW CONNECTIONS. REFER TO 2/M-202 FOR NEW DUCTWORK CONNECTIONS.
1
M-202VAV 2-7
44x20
26x30
26x26
EXPANSION TANK
NEW RETURN FAN R-2.
42x2
0
20x1
2
8'x4' OA LOUVER
12x8
EXISTING MOTOR OPERATED DAMPERS
BLR-1 BLR-2
CH-2E CH-1E
EMERGENCY GENERATOR
AND DAY TANK
22x19
22x19
FD-E FD-E FD-E
2
M-202
PROVIDE PENETRATION IN FLOOR AT APPROXIMATELY THIS LOCATION TO ROUTE CONTROLS CONDUIT FROM MECHANICAL ROOM EQUIPMENT TO NEW BAS CONTROL PANEL ON LOWER LEVEL. CONDUIT SHALL BE USED TO ROUTE ANY CONTROL WIRING REQUIRED TO RUN FROM THE FIRST FLOOR TO THE NEW BAS CONTROL PANEL. COORDINATE PENETRATION LOCATION WITH MECHANICAL ROOM EQUIPMENT AND LOWER LEVEL STRUCTURE AND EXISTING CONDITIONS. REFER TO 2/M-100 LOWER LEVEL ADMIN PLAN - MECHANICAL FOR APPROXIMATE CONDUIT ROUTING.
AHU-2
AHU-1
NEW RETURN FAN R-1
2
P-1
P-2
P-3
P-4P-5
4
EXISTING WATER HEATER
EXISTING PLUMBING
CIRCULATION PUMP
EXISTING CHILLER EXISTING CHILLER
FD-E AT FLOOR PENETRATION
30x2
6
26x3
0
PROVIDE DUCT TRANSITIONS AS REQUIRED TO CONNECT DUCTWORK TO AHU SA CONNECTION.
PROVIDE DUCT TRANSITIONS AS REQUIRED TO CONNECT DUCTWORK TO AHU SA CONNECTION.
6
6
PROVIDE NEW 22x20 DUCT TAP OFF OF THE BOTTOM OF EXISTING 30x26 DUCT. PROVIDE DUCT TRANSITIONS AS REQUIRED TO CONNECT DUCTWORK TO AHU RA CONNECTION.
PROVIDE NEW 22x20 DUCT CONNECTION IN THE VERTICAL. PROVIDE DUCT TRANSITIONS AS REQUIRED TO CONNECT DUCTWORK TO AHU RA CONNECTION.
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-200
ENLARGED PLANS -MECHANICAL
KATDENSCOPRZKATDEN
06/23/2021
5
M-200
NO R HT
1/2" = 1'-0"1 ENLARGED ADMIN MECHANICAL ROOM PLAN - VENTILATION DEMOLITION
NO R HT
1/2" = 1'-0"2 ENLARGED ADMIN MECHANICAL ROOM PLAN - VENTILATION NEW WORK
GENERAL SHEET NOTES:
1. EXISTING CONDITIONS SHOWN ARE BASED ON INFORMATION AVAILABLE FROM EXISTING DRAWINGS AND LIMITED FIELD VERIFICATION. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK.
KEYNOTES:
1. REMOVE EXISTING AHU AND ALL ASSOCIATED SUPPORTS, HANGERS, BRACKETS, ACCESSORIES, CONTROLS, ETC. REMOVE ASSOCIATED DUCTWORK AS INDICATED AND PREPARE DUCTWORK FOR NEW CONNECTIONS. REMOVE ALL ASSOCIATED PNEUMATIC TUBING AND CONTROLS.
2. PROVIDE NEW DDC DISCHARGE AIR TEMPERATURE SENSOR, SUPPLY AIRFLOW SENSOR, AND DAMPER ACTUATOR TO BE CONNECTED TO NEW BAS.
3. REMOVE EXISTING PNEUMATIC ACTUATORS FOR RELIEF AIR DAMPERS, RETURN AIR DAMPERS, AND OUTSIDE AIR DAMPERS. REMOVE ALL ASSOCIATED PNEUMATIC TUBING. PREPARE DAMPERS FOR NEW ACTUATOR.
4. PROVIDE NEW DDC ACTUATORS FOR EXISTING PNEUMATICALLY CONTROLLED RELIEF AIR DAMPERS, RETURN AIR DAMPERS, AND OUTSIDE AIR DAMPERS. FIELD VERIFY EXISTING DAMPER SIZES AND QUANTITIES PRIOR TO ORDERING ACTUATOR.
5. REMOVE EXISTING PNEUMATIC CONTROLS AND ASSOCIATED PNEUMATIC TUBING. PREPARE FOR NEW CONNECTIONS FOR DDC SENSORS AND CONTROLS.
6. REMOVE EXISTING SUSPENDED RETURN FANS R-1 & R-2 AND ALL ASSOCIATED SUPPORTS,HANGERS, BRACKETS, CONTROLS, PNEUMATIC TUBING, ACCESSORIES, ETC. REMOVE EXISTING RETURN DUCTWORK TO ALLOW FOR NEW DUCTWORK CONNECTIONS TO NEW FANS. PROVIDE NEW RETURN FANS AND ASSOCIATED CONTROLS TO CONNECT TO NEW BAS. PROVIDE SUPPORTS TO SUSPEND FANS FROM STRUCTURE. REFER TO 4/M400 FOR SUSPENDED UTILITY FAN MOUNTING DETAIL. BALANCE FANS TO SCHEDULED CFMS.
#
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
MECH. RM.220
MECH. RM.220
1
M-202
AHU-1EAHU-2E
BLR-1E
BLR-2E
REMOVE EXISTING HEATING WATER EXPANSION TANK LOCATED APPROXIMATELY 94" AFF AND ALL ASSOCIATED SUPPORTS, BRACKETS, HANGERS, ACCESSORIES, ETC.
EXISTING WATER HEATER
RETURN FAN R-1E
RETURN FAN R-2E
CH-2E CH-1E
EMERGENCY GENERATOR
AND DAY TANK
3" CW DN
1
3" LP DN BELOW GRADE TO
ROUTE TO EXISTING LP TANKS
SOUTHWEST OF BUILDING
2
M-202
3"LP
CW
R
HW
R HW
S
CWR
CW
R
CWR
HW
S
HW
R
CWR
HWS
HWR
HWR
CWR
HWR
HWR
HWS
EXISTING CHILLER EXISTING CHILLER
44
5
5
6
6
6
P-5E
P-3EP-1E
P-2E
P-4E REMOVE EXISTING 3" CWS & CWR PIPING IN THE VERTICAL TO APPROXIMATELY 24" AFF AND PREPARE PIPING FOR NEW CONNECTIONS.
EXISTING PLUMBING
CIRCULATION PUMP
6
1
M-202
PROVIDE NEW EXPANSION TANK SUSPENDED FROM STRUCTURE. REFER TO DETAIL 4/M-300 FOR EXPANSION TANK SUPPORT DETAIL.
EXISTING WATER HEATER
RETURN FAN R-1
BLR-1BLR-2
CH-2E CH-1E
EMERGENCY GENERATOR
AND DAY TANK
3" CW DN
2 2
4" FLUE VENT THROUGH ROOF3
2
M-202
PROVIDE NEW CONNECTIONS TO EXISTING 3" CWS & CWR PIPING IN THE VERTICAL.
3"LP
3" LP DN BELOW GRADE TO
ROUTE TO EXISTING LP TANKS
SOUTHWEST OF BUILDING
HWRHWS
HWR
AHU-1
1 1
/2"H
WR
1 1
/2"H
WS
CWS
1 1/2"HWS1 1/2"HWR
RETURN FAN R-2
AHU-2
EXISTING CHILLER EXISTING CHILLER
P-1
P-2
P-3
P-4
P-5
LP CONNECTION TO BOTTOM OF BOILER
4" BOILER AIR INTAKE THROUGH WALL. PROVIDE INSECT SCREEN ON OPENING.
PROVIDE SOLENOID VALVE FOR EMERGENCY LP SHUTOFF. COORDINATE WITH ELECTRICAL FOR CONNECTION TO EMERGENCY SHUTOFF SWITCHES.
LOCATE NEW AHU HEATING COIL PUMP ASSEMBLIES HERE.
EXISTING PLUMBING
CIRCULATION PUMP
6
6
6
6
7
7
1" LP
3" LP
CWR
CWS
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-201
ENLARGED PLANS -MECHANICAL
KATDENSCOPRZKATDEN
06/23/2021
6
M-201
NO R HT
1/2" = 1'-0"1 ENLARGED ADMIN MECHANICAL ROOM PLAN - MECHANICAL PIPING DEMOLITION
NO R HT
1/2" = 1'-0"2 ENLARGED ADMIN MECHANICAL ROOM PLAN - MECHANICAL PIPING NEW WORK
GENERAL SHEET NOTES:
1. EXISTING CONDITIONS SHOWN ARE BASED ON INFORMATION AVAILABLE FROM EXISTING DRAWINGS AND LIMITED FIELD VERIFICATION. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK.
2. REFER TO SHEETS M400 AND M401 FOR HEATING AND CHILLED WATER FLOW DIAGRAMS.
3. PROVIDE FLEXIBLE PIPE CONNECTIONS ON ALL PIPING CONNECTIONS TO EQUIPMENT.
KEYNOTES:
1. REMOVE EXISTING PIPING BACK AS INDICATED ALONG WITH ALL HANGERS, BRACKETS, SUPPORTS, ACCESSORIES, ETC. PREPARE PIPING FOR NEW CONNECTION.
2. CONNECT EXISTING CHILLERS TO NEW BAS FOR MONITORING OF EXISTING PACKAGED CONTROLS. REFER TO 1/M-401 AIR COOLED CHILLER FLOW DIAGRAM.
3. PROVIDE NEW PENETRATION IN EXISTING ROOF FOR NEW BOILER FLUE ROUTE AIR INTAKE AND FLUE VENT PER BOILER MANUFACTURER'S RECOMMENDATIONS FOR INSTALLATION AND SIZING. PROVIDE GOOSENECK ELBOW ON ROOF WITH BIRD SCREEN. FLASH PER EXISTING ROOF MANUFACTURER'S INSTRUCTIONS TO MAINTAIN WARRANTY.
4. REMOVE EXISTING PUMP AND ALL ASSOCIATED BRACKETS, SUPPORTS, ACCESSORIES, ETC. REMOVE ALL ASSOCIATED PNEUMATIC TUBING AND CONTROLS.
5. REMOVE EXISTING BOILER AND ALL ASSOCIATED BRACKETS, SUPPORTS, ACCESSORIES, ETC. REMOVE ALL ASSOCIATED PNEUMATIC TUBING AND CONTROLS.
6. REMOVE EXISTING CHILLED WATER PIPING AND ASSOCIATED SUPPORTS, ACCESSORIES, ETC. AS REQUIRED TO PROVIDE NEW CHILLED WATER CONNECTIONS TO NEW AHUS AND ALL NEW COMPONENTS AS SHOWN ON FLOW DIAGRAM ON SHEET M-401. REMOVE EXISTING CHILLED WATER PUMPS P-1, P-2, AND P-3, AND ALL ASSOCIATED BRACKETS, SUPPORTS, ACCESSORIES, PIPING, INSULATION, ETC. REMOVE ALL ASSOCIATED PNEUMATIC TUBING AND CONTROLS. PROVIDE NEW CHILLED WATER PUMPS, ASSOCIATED PIPING, INSULATION, SUPPORTS, ETC. PROVIDE NEW DDC CONTROLS TO CONNECT NEW PUMPS TO BAS. BALANCE PUMPS TO SCHEDULED GPMS.
7. BID ALTERNATE #2: PROVIDE USAGEMETERING BY THE BUILDING AUTOMATION SYSTEM FOR WATER AND LIQUID PROPANE UTILITIES SERVING BUILDING. PROVIDE METERS AT UTILITY ENTRANCE TO MECHANICAL ROOM. REFER TO 7/M-402 FOR UTILITY METERING CONTROL. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL METERING INFORMATION.
#
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
BLR-2 BLR-1
P-1 P-2 P-3 P-4 P-51 1 1
3"CWS
3"CWS3"CWS
3"CWS
2"HWS
2 1/2"HWS
3"CWS
3"CWS
2"HWS
2"HWR
2"HWS
2"HWR
2 1/2"HWS
LP CONNECTION TO UNDERSIDE OF BOILER
2"HWR
4" BOILER FLUE (BEHIND)
4" BOILER AIR INTAKE4" BOILER AIR
INTAKE
4" BOILER FLUE (BEHIND)
4" BOILER AIR INTAKE
2 1/2"HWR
2"HWS
2"HWS
2"HWS
2"HWS
2"HWS
2 1/2"HWS
3"CWR
3"CWR
20x44 MA
19x22 SA
AHU-1
96x48 MA OA PLENUM
26x30 MA
22x19 SA
MOTOR OPERATED
DAMPERS
EXPANSION TANK
MOTOR OPERATED
DAMPER
26x30 OA
VFD
NEW SA DUCTWORK CONNECTION TO EXISTING SA MAIN. REFER TO 2/M-200 FOR DUCT CONNECTION.
FAN SECTION
ACCESS DOOR
HEATING COIL SECTION
COOLING COIL SECTION
ACCESS DOOR
FILTER SECTION
ACCESS DOOR
FILTER SECTION
AHU-2
COOLING COIL SECTION
HEATING COIL SECTION
ACCESS DOOR
FAN SECTION
VFD
22x20 MA
22x20 MA
N.C.
N.C.
1 1/2"HWS
1 1/2"HWR
30x26 MA
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-202
MECHANICALSECTIONS
KATDENSCOPRZKATDEN
06/23/2021
7
M-202
1" = 1'-0"1 SECTION IN MECHANICAL ROOM FACING NORTH
1" = 1'-0"2 SECTION IN MECHANICAL ROOM FACING SOUTH
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
GENERAL SHEET NOTES:
1. REFER TO SHEETS M400 AND M401 FOR HEATING AND CHILLED WATER FLOW DIAGRAMS.
2. REFER TO SHEET M-403 FOR AIR HANDLING UNIT CONTROL DIAGRAM.
3. PROVIDE FLEXIBLE PIPE CONNECTIONS ON ALL PIPING CONNECTIONS TO EQUIPMENT.
KEYNOTES:
1. REMOVE EXISTING CHILLED WATER PUMPS P-1, P-2, AND P-3, AND ALL ASSOCIATEDBRACKETS, SUPPORTS, ACCESSORIES, PIPING, INSULATION, ETC. REMOVE ALL ASSOCIATED PNEUMATIC TUBING AND CONTROLS. PROVIDE NEW CHILLED WATER PUMPS, ASSOCIATED PIPING, INSULATION, SUPPORTS, ETC. PROVIDE NEW DDC CONTROLS TO CONNECT NEW PUMPS TO BAS. BALANCE PUMPS TO SCHEDULED GPMS.
D1>D2
45 DEGREE
BUTT FLANGESTRAIGHT TAP
ENTRY Θ 45°45 DEGREE CONICAL
CLINCH LOCK
CORNER FILLERPIECE OR USEGASKET (TYP.)
45 DEGREE LEAD IN
DOVETAIL JOINT
FLANGED
NOTE:STRAIGHT TAP WITH BUTTFLANGE FOR BRANCH AND TEECONNECTION IN RECTANGULAR DUCTSUNDER 1" PRESSURE CLASS ONLY.
ENTRY Θ 45°
D1
W
L
Θ
D2
(L = 4" OR W/4; WHICHEVER IS LARGER)
NOTES:
1. DO NOT USE CONNECTIONS WITH SCOOPS.2. FIT ALL CONNECTIONS TO AVOID VISIBLE OPENINGS AND
SECURE THEM SUITABLY FOR THE PRESSURE CLASS.3. ADDITIONAL MECHANICAL FASTENERS ARE REQUIRED FOR
4"W.G. AND OVER.4. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION.
RECTANGULAR
MITERED ELBOW
WITH VANESTYPE RE2
RECTANGULAR
MITERED ELBOWTYPE RE6
USE ONLY AS PART OF OFFSETS AND TRANSITIONS PER FIGURE 4-7 TYPE 2 OR AS SHOWN ON DRAWINGS. OFFSETS ABOVE 30° SHALL BE TYPE RE1.
RECTANGULAR
RADIUS ELBOWTYPE RE1
R/W = 1.0 (MINIMUM)R/W < 1.0 SHALL BE TYPE RE3
RECTANGULAR
RADIUS ELBOW WITH VANESTYPE RE3
REFER TO SMACNA HVAC SYSTEMS DUCT DESIGN MANUAL, FOURTH EDITION, SECTION 5.14 "SPLITTER VANES" AND SMACNA HVAC DUCT CONSTRUCTION STANDARDS, THIRD EDITION, FIGURES 4-2 AND 4-9 AND CHARTS 4-1 AND 4-1M. ELBOW SHALL HAVE THREE SPLITTER VANES AND r/W = 0.10 (R/W = 0.60) UNLESS NOTED OTHERWISE.
RECTANGULAR
RADIUS ELBOW WITH
SQUARE THROAT
NOT ALLOWED
RECTANGULAR / OVAL / ROUND
MITERED ELBOW
WITHOUT VANES
TYPE RE4
NOT ALLOWED
OVAL / ROUND
RADIUS ELBOWSMOOTH OR 5 GORE (MINIMUM)
R/W = 1.5 (MINIMUM)
W W
R
R
W
r R1 R
2
R R3
W
W
30°
EX
CE
ED
NO
T T
O
W
W
90°
90°
W
W
NOTES:
1. BEAD, CROSSBREAK, AND REINFORCE FLAT SURFACES AS INSTRAIGHT DUCT.
2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.3. DEFAULT ELBOW SHALL BE TYPE "RE1".4. ELBOW TYPES SHALL BE INSTALLED AS SHOWN AND NOT BE
SUBSTITUTED WITHOUT PERMISSION. EXCEPTION: RE1 OR RE3MAY BE SUBSTITUTED FOR RE2.
MINIMUM 2 DUCT DIAMETERS
PLAN VIEW SIDE VIEW
(4) 1/2"Ø A36THREADEDROD SUPPORTS
4x4x1/4 STEELANGLE PLATFORM
TYPE H2 VIBRATIONISOLATORS, 1 1/2 MAX.DEFLECTION (TYPICAL)
SECURE TO STRUCTUREABOVE FAN - VERIFYEXACT CONFIGURATION.
SECURE FANTO PLATFORM
FULL RADIUS ELBOW OR SHORT ELBOW WITH TURNING VANES AS SHOWN
INLET DUCT WITHCURVED END: SEEPLANS FOR ROUTING
ROUND FAN INLET CONNECTION
FLEXIBLE CONNECTION (TYP.)
RECTANGULAR OUTLETDUCT: SEE PLANS FORROUTING AND DISCHARGE
FIRE SEALANT
FIRE SEALANT
NOTE 2
NOTE 3
PENETRATING ITEM
NOTE 4
NOTE 3
NOTE 4
PENETRATING ITEM
NOTE 2
NOTE 3
RATED WALL(CONSTRUCTION VARIES)
RATED FLOOR(CONSTRUCTION VARIES)
NOTES:
1. THIS GENERAL DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL MOVEMENT. REFER TO SPECIFICATION SECTION 23 05 03 FOR SELECTION OF THROUGH PENETRATION FIRE STOPPING.
2. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL. EACH CONTRACTOR FURNISHES SLEEVE TO G.C., COORDINATES SLEEVE LOCATIONS AND DEBURS SLEEVE. G.C. BUILDS SLEEVE INTO WALL OR FLOOR ALLOWING NO GAP AROUND SLEEVE. IF SLEEVE IS NOT PROVIDED WHEN WALL OR FLOOR IS BUILT, CONTRACTOR SHALL INSTALL SLEEVE. SLEEVE SIZE SHALL ALLOW ANNULAR SPACE REQUIRED BY THE SELECTED FIRE STOP SYSTEM.
3. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION LISTING. SECURE TO WALL OR FLOOR TO ALLOW LONGITUDINAL MOVEMENT OF PENETRATING ITEM WITHOUT MOVEMENT OF FIRE BARRIER.
4. WATERTIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET METAL ANGLE FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF WATERPROOF SEALANT BETWEEN FLOOR AND BOTTOM OF ANGLE FRAME. SECURE TO FLOOR WITH MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS. MULTIPLE PENETRATING ITEMS MAY BE ENCLOSED IN ONE FRAME.
THREADED ROD.(TYP.)
OVERSIZE HANGER TO ALLOW LONGITUDINAL PIPE EXPANSION AND PIPE INSULATION TO PASS THROUGH UNBROKEN. (TYP.)
UNI-STRUT OR EQUIVALENT
HIGH DENSITY INSULATION INSERT AS REQUIRED IN SPECIFICATIONS.
THREADED ROD.(TYP.)
PIPE INSULATION(TYP.)
INSULATION SHIELD (TYP.)
INSULATION SHIELD
INSTALL CLAMP ON ALL PIPES LESS THAN 4"Ø
THREADED ROD
INSULATION
CLEVIS HANGER
HIGH DENSITY INSULATION INSERT AS REQUIRED IN SPECIFICATIONS.
NOTES:
1. REFER TO SPECIFICATION SECTIONS 23 05 29 & 23 07 19
INSULATION SHIELD (TYP.)
EXPANSION TANK
COUPLING NUT.
ALL THREADED ROD. (TYP.)
TUBE STEEL VERIFY LENGTH
DOUBLE NUTS
EXISTING BAR JOISTS
6"x6" STEEL PLATE DRILLED FOR ROD.PROVIDE DOUBLE NUT CONNECTION ONTOP. (TYP.)
SUPPORT BRACKET CUT TO MATCH SHAPE OF TANK. WELD TO ANGLE.
NOTE 1
NOTES:
1. FIELD VERIFY ALL DIMENSIONS.
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-300
MECHANICALDETAILS
KATDENSCOPRZKATDEN
06/23/2021
8
M-300
NO SCALE1 BRANCH CONNECTIONS
NO SCALE2 ELBOW CONSTRUCTION
NO SCALE4 SUSPENDED UTILITY FAN MOUNTING DETAIL
NO SCALE3 RATED FIRE BARRIER PENETRATION
NO SCALE5 PIPE SUPPORT DETAIL
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
NO SCALE6 EXPANSION TANK SUPPORT DETAIL (SUSPENDED)
ROUTE TO DRAIN (TYP.) PROVIDE IN-LINE DRAIN NEUTRALIZATION.
BLR-1 BLR-2
MANUAL AIR VENT INSTALL AT ALL HIGH POINTS OF SYSTEM. PIPE TO AN ACCESSIBLE AREA SEE 23 21 00.
2" HWS
2" HWS
BYPASS (POT) FEEDERDRAIN VALVE
RADIATION PIPING
AIR SEPARATOR. SAME SIZE AS PIPING. SEE SPECIFICATION SECTION 23 21 00.
2"H
WS
2"H
WS
2-1/2"HWS
2-1/2"HWS
2-1/2"HWR
2-1
/2"H
WS
2-1
/2"H
WS
3/4
"HW
S
2-1/2"HWR
2"H
WR
2"H
WR
2-1/2"HWR
2-1/2"HWS
3/4
"HW
R
PUMP P-525 GPM
PUMP P-425 GPM
VFD
VFD
2"HWS
2"HWS
HOUSEKEEPING PAD (TYP.)
ROUTE TO DRAIN (TYP.) PROVIDE IN-LINE DRAIN NEUTRALIZATION.
HOUSEKEEPING PAD (TYP.)
MANUAL AIR VENT
HEATING WATER FLOW DIAGRAM SYMBOL LIST
SYMBOL: DESCRIPTION:
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
COLD WATER - POTABLECW
PITCH PIPE IN DIRECTION
DIRECTION OF FLOW IN PIPE
FLEXIBLE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG
REDUCER - REFERENCE SPECIFICATIONFOR CONCENTRIC/ECCENTRIC AND FOT/FOB
METERM
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
SUCTION DIFFUSER WITH SUPPORT FOOT
AUTOMATIC AIR VENT
MANUAL AIR VENT W/ BALL VALVE
DRAIN WITH HOSE CONNECTION, CAP & BALL VALVE
TEMPERATURE SENSOR WITH WELLT
THERMOMETER WITH WELL (FILLED TYPE)
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
THROTTLING VALVE
BALANCING VALVE
CONTROL VALVE (TWO-WAY)
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE AND HOSE CONNECTION WITH CAP
CHECK VALVE
SAFETY/RELIEF VALVE
PRESSURE REDUCING VALVE (LIQUID/GAS)
UNION/FLANGE
CONTROL VALVE (THREE-WAY)
FLOW SWITCH
FLOW METER
BOILER PROOF OF FLOW (TYP)
TWO-WAY CONTROL VALVE TIED INTO BOILER CONTROL PANEL.
TWO-WAY CONTROL VALVE TIED INTO BOILER CONTROL PANEL.
AIR HANDLING UNIT HEATING
COIL(TYP. AHU-1 &
AHU-2)
PUMP P-6/P-7
(15 GPM)
VAV REHEAT COIL,
UNIT HEATER
3/4
"HW
R
3/4
"HW
S
SHUTOFF VALVE
MANUAL AIR VENT AT HIGH
POINT OF PIPING NEXT TO
COIL (TYP.)
REFER TO FLOOR PLANS FOR EXISTING HEATING WATER ROUTE THROUGH BUILDING.
#KEYNOTES:
1. TEMPERATURE SENSOR PROVIDED BY BOILER MANUFACTURER AS A PART OF PACKED CONTROLS.
1 1 1 1
NOT ALL SYMBOLS MAY APPLY
BALANCE TO GPM SCHEDULED IN EXISTING VARIABLE AIR VOLUME UNIT SCHEDULE ON SHEET M-501.
BALANCE TO GPM SCHEDULED IN FINNED TUBE REHEAT CONTROL VALVE SCHEDULE ON SHEET M-501.
PROVIDE NEW COMPONENTS AND DEVICES AS INDICATED. COORDINATE INSTALLATION WITH CONTROLS CONTRACTOR. (TYP.)
NC
1-1/2" HWR1-1/2" HWS
SAME SIZE AS AIR SEPARATOR OUTLET
1" COLD WATER MAKEUP
HIGH CAPACITY AIR VENT. PIPE DISCHARGE TO DRAIN.
MANUAL AIR VENT.
EXPANSION TANK. SPECIFICATION SECTION 23 21 00. 20 PSIG INITIAL CHARGE 10 MINIMUM ACCEPTANCE GALLONS 20 TOTAL VOLUME GALLONS
SYSTEM CONNECTION BELOW CENTERLINE OF TANK.
ANTI-THERMOSYPHON LOOP TO PREVENT GRAVITY HEATING OF TANKS THAT ARE ABOVE THE CONNECTION TO THE MAX.
LOCKED OPEN SHUTOFF VALVE
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-400
MECHANICAL FLOWDIAGRAMS
KATDENSCOPRZKATDEN
06/23/2021
9
M-400
NO SCALE1 HEATING WATER FLOW DIAGRAM - CONDENSING BOILER VARIABLE/PRIMARY
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
3"
CW
R
3" CWR
3"
CW
R 3"C
WS
3"C
WS
3"C
WS
3"CWS
AHU-1 COOLING COIL
PIPE DRAIN PAN TO FLOOR DRAIN.
EXTEND PIPING ASREQUIRED FORACCESS TO VALVES. (TYP.)
VFD
VFD
COLD WATER - POTABLECW
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
DRAIN LINED
NON-POTABLE COLD WATERNCW
PITCH PIPE IN DIRECTION
DIRECTION OF FLOW IN PIPE
UNION/FLANGE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
THROTTLING VALVE
BALANCING VALVE (NO. INDICATES GPM)0.5
AUTOMATIC DRAIN VALVE
CONTROL VALVE (THREE-WAY)
CONTROL VALVE (TWO-WAY)
CHECK VALVE
SAFETY/RELIEF VALVE
PRESSURE REDUCING VALVE (LIQUID/GAS)
"WYE" - STRAINER
"WYE" - STRAINER W/SHUTOFF VALVE AND HOSE CONNECTION WITH CAP
FLEXIBLE CONNECTION
PRESSURE/TEMPERATURE TEST PLUG
REDUCER - REFERENCE SPECIFICATIONFOR CONCENTRIC/ECCENTRIC AND FOT/FOB
METERM
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)
P
SUCTION DIFFUSER WITH SUPPORT FOOT
AUTOMATIC AIR VENT
MANUAL AIR VENT W/ BALL VALVE
DRAIN WITH HOSE CONNECTION, CAP & BALL VALVE
TEMPERATURE SENSOR WITH WELLT
THERMOMETER WITH WELL (FILLED TYPE)
FLOW METER
FM
FLOW DIAGRAM SYMBOLS LIST
SYMBOL: DESCRIPTION:
SOLENOID/TWO POSITION VALVE
VENTURI VALVE
EVAPORATOR
EVAPORATOR
FC-1 (TYP)
3"CWR
3"CWS
EXISTING CHILLER #1
EXISTING CHILLER #2
VFD
PUMP P-1
PUMP P-2
PUMP P-3
D
D
3"CWS
2-1/2" DECOUPLE LINEWITH MINIMUM LENGTHOF 8 PIPE DIAMETERS
2-1/2" CWR & 2-1/2" CWS
AHU-2 COOLING COIL
PIPE DRAIN PAN TO FLOOR DRAIN.
EXTEND PIPING ASREQUIRED FORACCESS TO VALVES. (TYP.)
2-1/2" CWR & 2-1/2" CWS
NOT ALL SYMBOLS MAY APPLY
EXISTING AIR SEPARATOR.
EXISTING EXPANSION TANK
1" COLD WATER
MAKEUP
PROVIDE NEW DDC CONTROL VALVES TO CONNECT TO NEW BAS.
1
1
PROVIDE NEW CONNECTIONS TO EXISTING CWS PIPES PRIOR TO EXISTING PENETRATION IN THE FLOOR OF MECHANICAL ROOM 220. REFER TO M-201 FOR MORE INFORMATION.
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-401
MECHANICAL FLOWDIAGRAMS
KATDENSCOPRZKATDEN
06/23/2021
10
M-401
NO SCALE1 AIR COOLED CHILLER FLOW DIAGRAM - PRIMARY/SECONDARY
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
KEYNOTES:
1. REMOVE EXISTING CHILLED WATER PIPING AND ASSOCIATED SUPPORTS, ACCESSORIES, ETC. AS REQUIRED TO PROVIDE NEW CHILLED WATER CONNECTIONS TO NEW AHUS AND ALL NEW COMPONENTS AS SHOWN ON FLOW DIAGRAM ON SHEET M-401. PROVIDE NEW DDC CONTROL VALVES ON CHILLED WATER SUPPLY CONNECTIONS TO EXISTING CHILLERS. CONNECT EXISTING CHILLERS TO NEW BAS FOR MONITORING. REMOVE EXISTING CHILLED WATER PUMPS P-1, P-2, AND P-3, AND ALL ASSOCIATED BRACKETS, SUPPORTS, ACCESSORIES, PIPING, INSULATION, ETC. REMOVE ALL ASSOCIATED PNEUMATIC TUBING AND CONTROLS. PROVIDE NEW CHILLED WATER PUMPS, ASSOCIATED PIPING, INSULATION, SUPPORTS, ETC. PROVIDE NEW DDC CONTROLS TO CONNECT NEW PUMPS TO BAS. BALANCE PUMPS TO SCHEDULED GPMS.
#
1
1
1
AI
AO AI
DO
T
AOAI
AI
AO
AI
T
MTR
R2
FS
DSDFM
HH
T T
H
T
C2
C
O
P
S
T
AI
AO
DI
DO
AI
AIAO
AI
AO
AI
T
T
AI
AI
DO
DI DI
DI
DI
WALL MTDTEMP SENSOR
SUPPLY
AIRRETURN
AIR
START / STOP
SUPPLY
FAN
HEATING
COIL
N.O.HWR
HWS
VALVE MOD
VLVFDBK
SEQUENCE OF OPERATION:
THE CABINET HEATER SHALL BE FURNISHED WITH A UNIT MOUNTED FAN SPEED SELECTOR SWITCH (OFF-HIGH-MED-LOW). THE UNIT SHALL MAINTAIN A SPACE TEMPERATURE OF NO MORE THAN 60°F.
WHEN THE SPACE TEMPERATURE IS ABOVE 60°F, THE CONTROL VALVE SHALL BE CLOSED AND THE FAN SHALL STOP.
WHEN THE SPACE TEMPERATURE IS BELOW 55°F, THE FMCS SHALL MODULATE THE CONTROL VALVE TO MAINTAIN SETPOINT AND THE FAN SHALL RUN CONTINUOUSLY.
ALARMS, INTERLOCKS & SAFETIES:
• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF SPACE TEMPERATURE FALLS 10°F (ADJ.) BELOWSETPOINT.
SEQUENCE OF OPERATION:
• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER AND PERIMETER RADIATION CONTROL VALVE TOMAINTAIN SPACE TEMPERATURE OF 72°F (ADJ.) WITH 5°F (ADJ.) DEAD BAND BASED ON A SIGNAL FROM A WALLMOUNTED TEMPERATURE SENSOR. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS. WALLMOUNTED TEMPERATURE SENSORS IN THE SPACE SHALL NOT BE ADJUSTABLE.
• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION. PERIMETER RADIATION CONTROL VALVESHALL BE CLOSED.
• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL MODULATE CLOSED UNTIL SPACE SETPOINT ISMAINTAINED, OR UNTIL IT REACHES ITS MINIMUM SCHEDULED CFM POSITION PER THE TAB SCHEDULE. THEPERIMETER RADIATION CONTROL VALVE SHALL BE CLOSED.
• THE TAB CONTROLLER SHALL ENABLE PERIMETER RADIATION CONTROLS WHEN THE O.A. TEMP DROPS BELOW 55°F (ADJ.). WHEN THE O.A. TEMP RISES ABOVE 55°F (ADJ.) PERIMETER RADIATION CONTROLS SHALL BE DISABLED.
• AS SPACE TEMP DROPS BELOW SETPOINT AND TAB DAMPER IS AT MINIMUM SCHEDULED CFM, TAB CONTROLLERSHALL MODULATE THE PERIMETER RADIATION CONTROL VALVE OPEN AS REQUIRED TO MAINTAIN SPACE TEMP.
• UPON A FURTHER FALL IN SPACE TEMPERATURE, TAB SHALL OPEN TO MAINTAIN SETPOINT UNTIL TAB AIRFLOWREACHES ITS MAXIMUM HEATING SETTING.
• THE FMCS SHALL UTILIZE OUTPUT FROM ALL TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLY DUCTDIFFERENTIAL STATIC PRESSURE.
ALARMS, INTERLOCKS & SAFETIES:
SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE SPACE TEMPERATURE IS MORE THAN 10°F (ADJ.) ABOVE OR BELOW SETPOINT.
HWR
HWS
FAIL IN PLACE
PERIMETER
RADIATION
VLVFDBK
MOD
WALL MTDTEMP SENSOR
PRIMARY AIR FROM ZONE
CONDITIONING AHU
SUPPLY
AIR
ACTVELOCITY AND STATIC SENSOR
EXISTING PRESSURE
INDEPENDENT TERMINAL
AIR BOX (TAB)
DAMPER ACTUATORDAMPER MOD.
TABAIRFLOW
GENERAL CONTROL NOTES:1. REFER TO EQUIPMENT SCHEDULES TO CROSS REFERENCE WHICH CONTROL
DIAGRAMS APPLY TO WHICH ITEMS OF EQUIPMENT. REFER TO TERMINAL AIR BOX (TAB) SCHEDULES FOR TEMP SENSOR REQUIREMENTS FOR EACH TAB.
2. EACH D.I., D.O., A.I. AND A.O. POINT SHOWN FOR ALL CONTROL DIAGRAMS SHALL BE DISCRETE FROM ALL OTHER POINTS EXCEPT AS SPECIFICALLY NOTED.
3. ALL WIRING, CONTROL COMPONENTS, DEVICES AND PROGRAMMING SHOWN ON THESE CONTROL DRAWINGS SHALL BE PROVIDED BY THE TCC UNLESS SPECIFICALLY NOTED OTHERWISE.
4. ALL ACTUATORS SHALL BE OF THE ELECTRICAL TYPE FOR THIS PROJECT UNLESS AN ACTUATOR IS SPECIFICALLY INDICATED ON THE DRAWINGS OR SPECIFICATIONS TO BE PNEUMATIC..
5. ALL MODULATING DAMPER AND VALVE ACTUATORS SHOWN WITH POSITION FEEDBACK SHALL HAVE THE VALVE POSITION DISPLAYED ON GRAPHICAL SCREEN ADJACENT TO THE DAMPER/VALVE COMMAND SIGNAL. DISPLAYED VALVE POSITION SHALL BE FROM THE FEEDBACK DEVICE/CIRCUIT (OUTPUT SIGNAL FROM THE FMCS TO THE ACTUATOR IS NOT ACCEPTABLE)
6. MODULATING SIGNALS SHALL BE DISPAYED AS % OPEN (SIGNALS DISPLAYED AS % CLOSED ARE NOT ACCEPTABLE).
7. PRESSURE TRANSMITTERS WHOSE SIGNAL IS UTILIZED FOR MAINTAINING DUCT STATIC PRESSURE SHALL BE WIRED DIRECTLY TO THE CONTROLLER WHICH MODULATES FAN SPEED. SIGNAL SHALL BE COMPLETELY INDEPENDENT OF THE FMCS NETWORK.
8. PRESSURE TRANSMITTERS WHOSE SIGNAL IS UTILIZED FOR MAINTAINING DIFFERENTIAL PRESSURE OF ANY PUMPED WATER SYSTEM (E.G. HEATING HOT WATER, CHILLED WATER AND THE LIKE) SHALL BE WIRED DIRECTLY TO THE CONTROLLER WHICH MODULATES PUMP SPEED. SIGNAL SHALL BE COMPLETELY INDEPENDENT OF THE FMCS NETWORK.
9. ALL CONTROL COMPONENTS SUCH AS RELAYS, SWITCHES, DDC CONTROLLERS, ETC. SHALL BE MOUNTED IN STEEL ENCLOSURES WITH STEEL MOUNTING BACKPLATES PER SPECIFICATION 23 09 00.
10. EACH CONTROL PANEL SHALL HAVE A LAMINATED COPY OF THE APPLICABLE SEQUENCE OF OPERATION AND CONTROL DIAGRAM INDICATING THE POINTS, COMPONENTS AND OPERATION OF EQUIPMENT ASSOCIATED WITH EACH PANEL. REFER TO SECTION 23 09 00 FOR ADDITIONAL REQUIREMENTS.
11. TCC SHALL WIRE THE CONTROL SIGNAL FROM THE ASSOCIATED AIR HANDLING UNIT CONTROL PANEL TO CONTROL THE OPERATION OF DAMPERS IN ACCORDANCE WITH SEQUENCE OF OPERATION. TCC SHALL PROVIDE ALL WIRING, CONDUIT, TRANSFORMERS, FUSING AND ALL OTHER ELECTRICAL COMPONENTS REQUIRED FOR COMPLETE INSTALLATION.
12. TCC SHALL EXTEND CONTROL SIGNAL FROM ADDRESSABLE RELAY DEVICE SERVING EACH AIR HANDLING UNIT. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS. TCC SHALL EXTEND AND TERMINATE WIRING AS REQUIRED FOR EQUIPMENT SHUTDOWN.
13. TCC SHALL EXTEND 120 VOLT POWER FROM CONTROL POWER JUNCTION BOX TO ALL TERMINAL AIR BOX CONTROLLERS SHOWN ON MECHANICAL PLANS. TCC SHALL PROVIDE ALL TRANSFORMERS WIRING, SUPPORTS, FUSING,TOGGLE SWITCHES, AND ALL OTHER ELECTRICAL COMPONENTS REQUIRED FOR COMPLETE INSTALLATION.
14. TCC SHALL PROVIDE CONDUIT RUNS AS REQUIRED FOR OUTDOOR EQUIPMENT AND FOR EQUIPMENT INSTALLED REMOTELY FROM THE MAIN BUILDING THAT IS BEING MONITORED OR CONTROLLED BY THE FMCS.
15. TCC SHALL PROVIDE THERMOSTATS FOR AUTOMATIC CONTROL OF EQUIPMENT AS REQUIRED BY THESE CONTROL DRAWINGS. THERMOSTAT CONTACT AMP RATING SHALL BE MINIMUM 125% OF THE MAX. CURRENT DRAW FOR THE EQUIPMENT BEING SERVED. WHERE THERMOSTATS CONTROL THE STARTING OF MOTORS (I.E. FANS), THERMOSTATS SHALL BE RATED FOR MOTOR STARTING APPLICATIONS.
16. ELEMENT LENGTHS FOR BOTH MIXED AIR TEMP SENSORS AND LOW LIMIT TEMP SWITCHES SHALL BE MINIMUM 1 LINEAR FOOT PER SQUARE FOOT OF COIL SURFACE AREA. PROVIDE MULTIPLE SENSORS AND SWITCHES AS NEEDED TO ACHIEVE REQUIRED ELEMENT LENGTHS. LOCATE RESET SWITCHES MAX. 6'-6" ABOVE ADJACENT STANDING SURFACE (I.E. ROOF, PLATFORM OR FLOOR) SO THE RESET SWITCH CAN BE CYCLED WITHOUT THE NEED FOR A LADDER.
17. TO PREVENT GENERATOR OVERLOADING, TCC SHALL PROGRAM A STAGGERED START TIME FOR ALL MECHANICAL EQUIPMENT THAT IS CONTROLLED BY FMCS TO INCLUDE, BUT NOT LIMITED TO, AIR HANDLERS, PUMPS, EXHAUST FANS, AND CHILLERS. THE FIRST EQUIPMENT SHALL START 2 MINUTES (ADJ.) FROM THE TIME THE FMCS RECEIVES THE SIGNAL THAT THE TRANSFER SWITCH CHANGED TO EMERGENCY POWER SOURCE WITH ALL EQUIPMENT BEING ENERGIZED WITHIN A 20 MINUTE (ADJ.) TIME SPAN. COORDINATE ORDER OF EQUIPMENT STAGING WITH OWNER'S REPRESENTATIVE.
18. CONTROL DIAGRAMS ARE SCHEMATIC IN NATURE AND DO NOT SHOW ALL REQUIRED CONTROL DEVICES AND COMPONENTS. REFER TO FLOOR PLANS, FLOW DIAGRAMS AND DETAILS FOR ADDITIONAL CONTROL DEVICES, COMPONENTS AND REQUIREMENTS NOT SHOWN ON THESE CONTROL DRAWINGS.
19. TCC SHALL PROVIDE ALL CONTROL COMPONENTS AND ACCESSORIES AS REQUIRED FOR EQUIPMENT TO BE CONTROLLED AS DESCRIBED IN THE SEQUENCE OF OPERATION REGARDLESS OF WHETHER ALL CONTROL COMPONENTS OR POINTS ARE SHOWN IN THE ASSOCIATED CONTROL DIAGRAM.
CONTROL SYMBOLS LIST
SYMBOL: DESCRIPTION:
FAN
MOTOR
CONTACTOR
PUMP
STATIC SWITCH
SP
AVERAGING TEMPERATURE SENSOR
PROBE TEMPERATURE SENSOR
HUMIDITY SENSOR
HUMIDIFIER
DUCT FLOW METER
DUCT SMOKE DETECTOR
LOW LIMIT TEMPERATURE SWITCH
AIR FLOW SWITCH
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT SENSOR
OCCUPANCY SENSOR
PRESSURE SENSOR / MONITOR
SENSOR
THERMOSTAT
H HUMIDISTAT/SENSOR (DUCT MOUNTED)
P PRESSURE SENSOR (DUCT MOUNTED)
T TEMPERATURE SENSOR (DUCT MOUNTED)
ACT ACTUATOR
DS DOOR SWITCH
DP DIFFERENTIAL PRESSURE SWITCH
CS CURRENT SWITCH
VS VIBRATION SWITCH
FM FLOW METER
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
HEATING WATER RETURNHWR
HEATING WATER SUPPLYHWS
CONTROL VALVE (THREE-WAY)
CONTROL VALVE (TWO-WAY)
CHECK VALVE
TEMPERATURE SENSOR WITH WELLT
FLOW SWITCH
EA EXHAUST/RELIEF AIR
MA MIXED AIR
N.C. NORMALLY CLOSED
NORMALLY OPENN.O.
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
F
ANALOG INPUT
ANALOG OUTPUT
DIGITAL INPUT
DIGITAL OUTPUT
HEATING/ COOLING COIL
FILTER
AIR BLENDER
OPPOSED BLADE DAMPER
PARALLEL BLADE DAMPER
TERMINAL AIR BOX
TERMINAL AIR BOX W/REHEAT
NORMALL CLOSED CONTACT
NORMALLY OPEN CONTACT
MANUAL MOTOR STARTER W/THERMAL OVERLOAD
NOT ALL SYMBOLS MAY APPLY
WALL MTDTEMP SENSOR
HWS
HWR
PRIMARY AIR FROM ZONE
CONDITIONING AHU
SUPPLY
AIR
ACTVELOCITY AND STATIC SENSOR
EXISTING PRESSURE
INDEPENDENT TERMINAL
AIR BOX (TAB)
FAIL IN PLACE
DAMPER ACTUATORDAMPER MOD.
TABAIRFLOW
2-WAY CONTROL VALVE(REFER TO FLOORPLANS FOR WHERE 3-WAY VALVES ARE REQ'D)
SEQUENCE OF OPERATION:
• FMCS TAB CONTROLLER SHALL MODULATE THE TAB DAMPER AND TAB HWREHEAT COIL CONTROL VALVE TO MAINTAIN SPACE TEMPERATURE OF 72°F(ADJ.) WITH 5°F (ADJ.) DEAD BAND BASED ON A SIGNAL FROM A WALL MOUNTEDTEMPERATURE SENSOR. SEE DRAWINGS FOR TEMPERATURE SENSORREQUIREMENTS. WALL MOUNTED TEMPERATURE SENSORS IN THE SPACE SHALLNOT BE ADJUSTABLE.
• AT FULL COOLING, THE TAB SHALL BE OPEN TO MAXIMUM CFM POSITION. THEREHEAT COIL CONTROL VALVE SHALL BE CLOSED.
• UPON A FALL IN SPACE TEMPERATURE, THE TAB SHALL MODULATE CLOSEDUNTIL SPACE SETPOINT IS MAINTAINED, OR UNTIL IT REACHES ITS MINIMUMSCHEDULED CFM POSITION PER THE TAB SCHEDULE. THE REHEAT COILCONTROL VALVE SHALL BE CLOSED.
• UPON A FURTHER FALL IN SPACE TEMPERATURE, THE REHEAT COIL CONTROLVALVE SHALL MODULATE OPEN TO MAINTAIN SPACE SETPOINT UNTIL THESUPPLY AIR TEMPERATURE IS 20°F ABOVE ROOM TEMPERATURE SETPOINT.
• UPON A FURTHER FALL IN SPACE TEMPERATURE, TAB SHALL OPEN TO MAINTAINSETPOINT UNTIL TAB AIRFLOW REACHES ITS MAXIMUM HEATING SETTING. THEREHEAT CONTROL VALVE SHALL CONTINUE TO MODULATE OPEN TO MAINTAINMAXIMUM DELTA T LISTED ABOVE.
• THE FMCS SHALL UTILIZE OUTPUT FROM ALL TERMINAL AIR BOX POSITIONS TORESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.
• WHEN FLOATING CV'S ARE USED, FMCS SHALL PERFORM AN AUTO-ZEROFUNCTION EVERY NIGHT DURING UNOCCUPIED TIMES. THE FMCS SHALLSTAGGER AUTO-ZERO SEQUENCES SO THAT ALL VALVES DO NOTSIMULTANEOUSLY CLOSE.
ALARMS, INTERLOCKS & SAFETIES:
THE FOLLOWING CONDITIONS SHALL INDICATED AN ALARM AT THE FMCS OPERATOR INTERFACE:• THE SPACE TEMPERATURE IS MORE THAN 10°F (ADJ.) ABOVE OR BELOW
SETPOINT.• THE HYDRONIC CONTROL VALVE FAILS.
SUPPLY AIR TEMPLOCATE TEMPERATURE SENSOR 4'-0" DOWNSTREAM OF COIL IN THE CENTER OF DUCT
MOD
VLVFDBK
SEQUENCE OF OPERATION:PROVIDE GLOBAL O.A. DRY-BULB TEMPERATURE AND RELATIVE HUMIDITY TRANSMITTERS.
GLOBAL SENSORS SHALL CONTINUOUSLY UPDATE FMCS FOR USE IN CONTROLLING MECHANICAL EQUIPMENT AS REQUIRED IN SEQUENCES OF OPERATION.
MOUNT ON NORTH FACE OF BUILDING. VERIFY FINAL INSTALLATION LOCATION WITH OWNER/ENGINEER UNLESS SHOWN ON DRAWINGS FOR EXACT LOCATION.
GLOBAL O.A. TEMP SENSOR W/ SUNSHIELD
GLOBAL O.A. RELATIVE HUMIDITY SENSOR
H
T
FAN STATUS
CS
START/ STOP
EXHAUST AIR
SEQUENCE OF OPERATION:EXHAUST FAN SHALL RUN CONTINUOUSLY.
ALARMS, INTERLOCKS AND SAFETIES:AN ALARM SHALL BE GENERATED AT THE FMCS OPERATOR WORKSTATION IN THE EVENT THE FMCS COMMANDS THE EXHAUST FAN TO OPERATE AND THE CURRENT SENSING RELAY DETECTS INSUFFICIENT CURRENT DRAW.
EXISTING BATHROOM EXHAUST FAN
EXISTING GRAVITY DAMPER
PROVIDE ACCESS POINT FOR LAPTOP CONNECTION TO NEW BAS. PROVIDE COMPONENTS PER SPECIFICATION SECTION 23 09 00 REQUIREMENTS. CONTROL SYSTEM SHALL BE CAPABLE OF BEING REMOTELY ACCESSED VIE INTERNET CONNECTION AND STANDARD INTERNET BROWSERS. COORDINATE SECURITY LOGIN AND PASSWORD WITH OWNER.
NCU
NCU
PROVIDE QUANTITY OF NCUs NECESSARY TO ALLOW FOR MINIMUM 25% SPARE CAPACITY ON EACH NCU. PROVIDE NCUS AND OTHER COMPONENTS PER SPECIFICATION SECTION 23 09 00 REQUIREMENTS.
EXTEND TO EQUIPMENT CONTROLLERS PER REQUIREMENTS OF CONTROL DIAGRAMS AND SECTION 23 09 00.
MASTER CONTROL
PANEL
LOWER LEVEL CUSTODIAN 135
CONTROLS
CONTROLS
CONTROLS
GAS USAGE
WATER USAGE
ELEC USAGE
FROM EXISTING LIQUID PROPANE TANKS
TO BUILDING
FROM UTILITY COMPANY TO BUILDING
FROM UTILITY COMPANY TO BUILDING
GAS METER
WATER METER
ELECTRICAL METER
SEQUENCE OF OPERATION:
GENERAL:THE UTILITIES ARE METERED THROUGH THE DDC VIA THE FMCS.
UTILITY METERING CONTROL:
• GAS METERING:THE TCC SHALL CONNECT THE FMCS TO THE GAS METER TO PROVIDE GAS CONSUMPTION INFORMATION.
• WATER METERING:THE TCC SHALL CONNECT THE FMCS TO THE WATER METER TO PROVIDE WATER USAGE INFORMATION.
• ELECTRIC METERING:
THE TCC SHALL CONNECT THE FMCS TO THE ELECTRICAL METER FOR ELECTRICAL USAGE INFORMATION.
UTILITY METERING REPORT GENERATION:
• FMCS SHALL MONITOR THE FOLLOWING POINTS ON 5 MINUTE (ADJ.) INTERVALS WITHIN ASINGLE TREND. THE TREND SHALL RUN FOR A 14-DAY (ADJ.) DURATION AT WHICH POINT THENEWEST VALUES SHALL OVERWRITE THE OLDEST VALUES:
·· DATE·· TIME·· GLOBAL OUTSIDE AIR TEMP. (°F)·· GLOBAL OUTSIDE AIR DEWPOINT TEMP. (°F)·· GAS USE (THERMS)·· WATER USE (GALLONS)·· ELECTRICAL USE (KW)
• THIS INFORMATION SHALL BE ACCESSIBLE TO VIEW IN EITHER TABULAR OR GRAPHICAL FORMON THE FMCS OPERATOR INTERFACE.
• ONCE PER MONTH, THE FMCS SHALL RECORD THE LARGEST GAS USE (IN KW), WATER USE (INLITERS), AND ELECTRICAL USE (IN KW) WHICH OCCURRED DURING THAT MONTH. THE DATE AND TIME THAT COINCIDED WITH THAT EVENT SHALL ALSO BE RECORDED. THIS INFORMATION SHALL BE STORED TO A MEMORY LOCATION ON THE FMCS OPERATOR INTERFACE THAT IS MAINTAINED (NOT AUTOMATICALLY OVERWRITTEN).
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-402
MECHANICALCONTROL DIAGRAMS
KATDENSCOPRZKATDEN
06/23/2021
11
M-402
NO SCALE1 UNIT HEATER CONTROL - HYDRONIC
NO SCALE2 TAB CONTROL W/ COOLING ONLY AND PERIMETER RADIATION - TAB-A
NO SCALE3 TAB CONTROL W/ HOT WATER REHEAT - TAB-B
NO SCALE4 GLOBAL REFERENCE POINTS
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
NO SCALE5
EXHAUST FAN CONTROL -CONTINUOUS OPERATION -EXISTING BATHROOM EXHAUSTFAN
NO SCALE6FMCS NETWORK REQUIREMENTS
NO SCALE7UTILITY METERING CONTROL
NOTES:
1. FOR USE WITH BID ALTERNATE #2. REFER TO DRAWINGS M-201 AND E-300 FOR MORE INFORMATION.
AIAI
AI
AODI
DO
DI
AOAI
AOAI
AO AI
AI
AI
DI
AOAIDO
DI
AI
AODI
DO
DI
AI AI
AI
AI
AI
AI
AI
AI
DI
DI
DI
AO AI
AITH
FM
VFD
FM
T T T
FM
VFD
H T
T
LL TEMPSWITCH#1
SP
RETURNAIR
DUCT MOUNTED TEMPERATURE & HUMIDITY SENSORS
RETURN DUCT MOUNTED LOW STATIC SWITCH
RETURNAIRFLOW
COMMUNICATION LINK BETWEEN VFD GATEWAY & FMCS (TYPICAL EACH VFD)
MODALRM
START/STOP
CS
FAN STATUS
ACT
N.C.
DMPRMOD.
DMPRFDBK
RELIEF AIR
EXISTING
RELIEF
AIR
DAMPER
ACT
ACT
OUTSIDEAIRFLOW
N.C.
O.A.
DMPRMOD.
DMPRFDBK
SP
MIXED AIR LOW STATIC
SWITCH
DMPRFDBK
DMPRMOD.
DP DP
FILTER STATUS
FILTER STATUS
PRE HEAT COIL
VALVFDBK
VALVMOD.
HWRN.O.
LL TEMPSWITCH#2
CS
HWS
PUMP STATUS
SP
EXISTING
RETURN
AIR
DAMPERN.O.
EXISTING
OUTSIDE
AIR
DAMPER
M.A.TEMP
PRE-FILTER (30%)
PRE-FILTER (60%)
START/STOP
CWR
CWS
DIFF. PRESS. SWITCH (0-1" W.G. SCALE) (TYP.2)
COOLING COIL
MOUNT FLOWMETER DISPLAY WITHIN SERVICE VESTIBULE OF EACH RTU OR ON EXTERIOR OF AHU FOR INDOOR UNITS. (TYP.)
MODALRM
CS
FAN STATUS
HIGH STATIC SWITCH
DUCT MOUNTED TEMPERATURE & HUMIDITY SENSORS
MOUNT IN DISCHARGE PLENUM OF AHU.
SP
SUPPLYAIR
STATIC PRESS. TRANS.
LOCATE DUCT DIFFERENTIAL STATIC PRESSURE SENSOR NEAR MOST REMOTE TERMINAL AIR BOX.
AHU REPORT GENERATION:DDC FMCS SHALL MONITOR THE FOLLOWING POINTS ON 10 MINUTE (ADJ.) INTERVALS WITHIN A SINGLE TREND. THE TREND SHALL RUN FOR A 100-DAY (ADJ.) DURATION AT WHICH POINT THE NEWEST VALUES SHALL AUTOMATICALLY OVERWRITE THE OLDEST VALUES:
• DATE• TIME• GLOBAL OUTSIDE AIR TEMP [°F]• GLOBAL OUTSIDE AIR HUMIDITY [%RH]• SUPPLY AIRFLOW [CFM]• SUPPLY AIR TEMP (SAT) [°F]• SUPPLY AIR TEMP SETPOINT [°F]• SUPPLY AIR RELATIVE HUMIDITY [%]• RETURN AIRFLOW [CFM]• RETURN AIR TEMP (RAT) [°F]• RETURN AIR RELATIVE HUMIDITY [%]• OUTSIDE AIRFLOW [CFM]• MIXED AIR TEMP [°F]• PREHEAT COIL DISCHARGE AIR TEMP [°F]• PRE-FILTER LOADING (30% FILTER) [INCHES W.G.]• PRE-FILTER LOADING (60% FILTER) [INCHES W.G.]• HEATING WATER VALVE POSITION [% OPEN]• HEATING PUMP [ON/OFF]• CHILLED WATER VALVE POSITION [% OPEN]• SUPPLY DUCT STATIC PRESSURE SETPOINT [INCHES W.G.]• SUPPLY DUCT STATIC PRESSURE [INCHES W.G.]• SUPPLY FAN VFD OUTPUT [% FULL SPEED]• RETURN FAN VFD OUTPUT [% FULL SPEED]• OUTSIDE AIR DAMPER POSITION [% OPEN]• RETURN AIR DAMPER POSITION [% OPEN]
THIS INFORMATION SHALL BE ACCESSIBLE TO VIEW IN GRAPHICAL FORM ON THE FMCS OPERATOR WORKSTATION.
ONCE PER MONTH, THE DDC FMCS SHALL RECORD THE LARGEST AHU AIRFLOW WHICH OCCURED DURING THAT MONTH. THE DATE, TIME, OUTSIDE AIR TEMP (AND ALL OTHER VALUES LISTED ABOVE) THAT COINCIDED WITH THAT EVENT SHALL ALSO BE RECORDED. THIS INFORMATION SHALL BE STORED TO A MEMORY LOCATION ON THE FMCS OPERATOR WORKSTATION THAT IS MAINTAINED (NOT AUTOMATICALLY OVERWRITTEN).
AIR HANDLER REPORT GENERATIONTYPICAL FOR AHU-1 & AHU-2
SEQUENCE OF OPERATION:
WHEN AHU/RTU IS INDEXED TO RUN, THE FOLLOWING SHALL OCCUR:• AFTER A 30 SECOND DELAY (ADJ.). SUPPLY FAN SHALL BE ENABLED TO RUN.• WHEN THE SUPPLY FAN HAS STARTED THE RETURN SHALL START.
SUPPLY FAN OPERATION:FMCS SHALL MODULATE SIGNAL TO SUPPLY FAN VFD TO MAINTAIN DUCT STATIC PRESSURE AS MEASURED BY STATIC PRESSURE TRANSMITTER NEAR THE MOST REMOTE TERMINAL AIR BOX.
RETURN FAN OPERATION:RETURN FAN SHALL BE INDEXED TO RUN WHENEVER THE SUPPLY FAN IS INDEXED TO RUN. FMCS SHALL MODULATE SIGNAL TO RETURN FAN VFD AS REQUIRED TO MAINTAIN THE AIRFLOW OFFSET AS INDICATED IN THE RETURN FAN AIRFLOW SCHEDULE.
STATIC PRESSURE RESET:FMCS SHALL RESET SUPPLY DUCT STATIC PRESSURE SETPOINT BELOW THE MAXIMUM SETPOINT AS REQUIRED TO MAINTAIN AT LEAST ONE SUPPLY TAB DAMPER 90% (ADJ.) OPEN. FMCS SHALL MONITOR ALL SUPPLY TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.
DISCHARGE AIR TEMPERATURE SET POINT:DISCHARGE AIR SET POINT SHALL BE 72ºF (ADJ.).
DISCHARGE AIR TEMPERATURE RESET:RESET DISCHARGE AIR TEMPERATURE BASED ON THE ZONE WITH THE GREATEST CALL FOR COOLING. RESET THE TEMPERATURE AS FOLLOWS: • WHEN WORST CASE TAB IS LESS THAN 90% (ADJ.) OPEN FOR TEN MINUTES (ADJ.) THEN THE DISCHARGE AIR TEMPERATURE SHALL INCREASE BY 1ºF (ADJ.). THIS SHALL CONTINUE UNTIL
AHU MAXIMUM DISCHARGE AIR TEMPERATURE OF 60ºF (ADJ.) IS ACHIEVED.• WHEN WORST CASE TAB IS MORE THAN 90% OPEN FOR TEN MINUTES (ADJ.) THEN THE DISCHARGE AIR TEMPERATURE SHALL DROP BY 1ºF (ADJ.). THIS SHALL CONTINUE UNTIL AHU
MINIMUM DISCHARGE AIR TEMPERATURE OF 55ºF (ADJ.) IS ACHIEVED.• THE MAXIMUM ALLOWABLE RETURN AIR HUMIDITY SETPOINT SHALL BE 60% (ADJ.). IF RETURN AIR HUMIDITY IS GREATER THAN SETPOINT, RESET DISCHARGE AIR TEMPERATURE TO 55°F
UNTIL RETURN AIR HUMIDITY IS 5% LESS THAN MAXIMUM SETPOINT FOR 10 MINUTES (ADJ.).
STATIC PRESSURE AND DISCHARGE AIR TEMPERATURE RESET PRIORITY: RESET THE DISCHARGE AIR TEMPERATURE PRIOR TO RESETTING THE DUCTWORK STATIC PRESSURE SETPOINT. ONCE THE MAXIMUM SUPPLY TEMPERATURE IS REACHED THEN THE SYSTEM SHALL ENABLE THE STATIC PRESSURE RESET.
VENTILATION AIR CONTROL:WHENEVER THE AIR HANDLING UNIT IS IN OCCUPIED MODE, THE OUTSIDE AIR DAMPER SHALL BE FULLY OPEN. THE RETURN AIR AND RELIEF AIR DAMPER SHALL MODULATE IN OPPOSITION TO MAINTAIN THE MINIMUM OUTSIDE AIR FLOW RATE, OR TO SATISFY THE ECONOMIZER DISCHARGE AIR SEQUENCE.
COOLING COIL OPERATION:WHEN IN MINIMUM OUTSIDE AIR MODE, FMCS SHALL MODULATE CHILLED WATER CONTROL VALVE AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SET POINT.
WHEN IN ECONOMIZER MODE, FMCS SHALL NOT MODULATE COOLING CONTROL VALVE UNLESS RETURN AIR DAMPER IS 5% (ADJ.) OPEN AND RELIEF AIR DAMPER IS 95% (ADJ.) OPEN.
PREHEAT COIL OPERATION:PREHEAT COIL CONTROLS SHALL BE ENABLED WHEN OUTSIDE AIR TEMP DROPS BELOW 70°F (ADJ.). PREHEAT COIL CONTROLS SHALL BE DISABLED WHEN OUTSIDE AIR TEMP RISES ABOVE 54°F (ADJ.).
WHEN OUTSIDE AIR TEMPERATURE RISES ABOVE 50°F (ADJ.) FOR 10 MINUTES (ADJ.) HEATING WATER COIL CIRCULATION PUMP SHALL OPERATE ONLY WHEN HEATING IS CALLED FOR (HEATING WATER VALVE IS COMMANDED TO OPEN). WHEN OUTSIDE AIR TEMP DROPS BELOW 50°F (ADJ.) HEATING WATER COIL CIRCULATION PUMP SHALL OPERATE CONTINUOUSLY. ONCE ENERGIZED, HEATING WATER COIL CIRCULATION PUMP SHALL REMAIN IN OPERATION FOR MINIMUM 5 MINUTES (ADJ.) TO PREVENT SHORT CYCLING.
FMCS SHALL MODULATE HEATING WATER CONTROL VALVE AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SET POINT.
ECONOMIZER OPERATION:WHEN THE OUTSIDE AIR DRY BULB TEMPERATURE IS LESS THAN THE RETURN AIR DRY BULB TEMPERATURE THE FMCS SHALL ENABLE ECONOMIZER CONTROLS. WHEN OUTSIDE AIR DRY BULB TEMPERATURE IS GREATER THAN THE RETURN AIR DRY BULB TEMPERATURE FOR 10 MINUTES THE FMCS SHALL DISABLE ECONOMIZER CONTROLS AND SHALL RETURN THE UNIT TO MINIMUM OUTSIDE AIR MODE. ONCE ECONOMIZER CONTROLS HAVE BEEN ENABLED OR DISABLED, THE UNIT SHALL CONTINUE TO OPERATE IN THAT MODE FOR A MINIMUM OF 10 MINUTES (ADJ.) BEFORE BEING ALLOWED TO SWITCH BACK (TO PREVENT SHORT CYCLING). ECONOMIZER CONTROLS SHALL BE DISABLED WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 62°F (ADJ.).
IN ECONOMIZER MODE THE FMCS SHALL MODULATE THE RETURN AND RELIEF DAMPERS AS REQUIRED TO MAINTAIN DISCHARGE AIR TEMPERATURE SETPOINT.
ALARMS, INTERLOCKS, AND SAFETIES:WHEN FIRE ALARM CONTROL PANEL INDICATES AN ALARM CONDITION, AHU SHALL BE SHUTDOWN.
THE FOLLOWING CONDITIONS SHALL SHUTDOWN THE AHU AND SHALL INDICATE AN ALARM CONDITION AT THE FMCS WORKSTATION:• LOW STATIC PRESSURE SWITCH INDICATES RETURN DUCT PRESSURE LESS THAN THE SPECIFIED DUCT PRESSURE CLASS.• LOW STATIC PRESSURE SWITCH INDICATES MIXED AIR PRESSURE LESS THAN THE SPECIFIED DUCT PRESSURE CLASS OF THE OUTSIDE AIR DUCTWORK.• HIGH STATIC PRESSURE SWITCH INDICATES SUPPLY DUCT STATIC PRESSURE GREATER THAN THE SPECIFIED DUCT PRESSURE CLASS.• SHOULD ANY ONE FOOT SECTION OF THE MANUAL RESET LOW LIMIT TEMPERATURE SWITCH #1 SENSE AIR TEMP <34°F (ADJ.). IF MULTIPLE FREEZE STATS ARE REQUIRED, WIRE ALL TO A
COMMON RESET SWITCH.
THE FOLLOWING CONDITIONS SHALL INDICATE AN ALARM AT THE FMCS, HOWEVER AHU SHALL CONTINUE TO OPERATE:• HEATING COIL CIRCULATION PUMP IS COMMANDED TO RUN AND CURRENT RELAY INDICATES INSUFFICIENT CURRENT FLOW.• AN ALARM IS INDICATED AT ANY SUPPLY FAN VFD OR RETURN FAN VFD.• DIFFERENTIAL PRESSURE SWITCH ACROSS PRE-FILTER (30%) BANK EXCEEDS 0.6 INCHES W.G. (ADJ.)• DIFFERENTIAL PRESSURE SWITCH ACROSS PRE-FILTER (60%) BANK EXCEEDS 0.8 INCHES W.G. (ADJ.)• THE TOTAL DIFFERENTIAL PRESSURE ACROSS ALL FILTER BANKS EXCEEDS 1.6 INCHES W.G. (ADJ.)• SHOULD ANY ONE FOOT SECTION OF THE AUTO RESET LOW LIMIT TEMPERATURE SWITCH #2 SENSE AIR TEMPERATURE <38°F (ADJ.) THE FOLLOWING SHALL OCCUR:
• THE RETURN AIR DAMPER SHALL FULLY OPEN.• THE OUTSIDE AIR AND RELIEF DAMPERS SHALL FULLY CLOSE.• THIS ACTION SHALL OCCUR INDEPENDENT OF THE FMCS AHU CONTROLLER. ONCE THE LOW LIMIT TEMPERATURE SWITCH #2 AIR TEMPERATURE RISES ABOVE SET POINT,
OPERATION OF THE OUTSIDE AIR, RELIEF AIR, AND RETURN AIR DAMPERS SHALL BE RESTORED. HOWEVER, THE ALARM SHALL CONTINUE UNTIL ACKNOWLEDGED AND MANUALLYRESET BY THE FMCS OPERATOR.
• SEND AN ALARM TO THE FMCS OPERATOR INTERFACE IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 5°F (ADJ.) ABOVE OR BELOW SETPOINT.
IN THE EVENT SUPPLY FAN IS NOT RUNNING (AS INDICATED BY THE CURRENT SENSING RELAYS) RETURN AIR FAN SHALL BE DE-ENERGIZED.
WHENEVER AHU/RTU IS SHUTDOWN THE FOLLOWING SHALL OCCUR:• THE OUTSIDE AIR DAMPER AND RELIEF AIR DAMPER SHALL FULLY CLOSE.• RETURN AIR DAMPER SHALL FULLY OPEN.• PREHEAT COIL HEATING WATER CIRCULATION PUMP AND HEATING WATER CONTROL VALVE SHALL REMAIN UNDER CONTROL OF ITS INPUT SENSOR.• CHILLED WATER CONTROL VALVE SHALL FULLY CLOSE.• SUPPLY FAN AND RETURN FAN VFDS SHALL BE DE-ENERGIZED.
UNOCCUPIED MODE:PROVIDE TIME OF DAY SCHEDULE TO ALLOW AHU TO ENTER UNOCCUPIED MODE PER SCHEDULE. COORDINATE SCHEDULE WITH OWNER.
• THE SUPPLY AND RETURN FANS SHALL CONTINUE RUNNING.• THE OUTSIDE AIR AND RELIEF AIR DAMPERS SHALL CLOSE AND THE RETURN AIR DAMPER SHALL OPEN. ECONOMIZER CYCLE SHALL TAKE PRECEDENCE OVER DAMPER POSITION.• ALL SPACE TEMPERATURES SHALL BE ALLOWED TO VARY +/- 10°F (ADJ.) FROM OCCUPIED SETPOINT.
HEATING OPTIMUM START-UP:• THIS CYCLE SHALL OVERRIDE THE UNOCCUPIED CYCLE. IF THE SYSTEM WAS OPERATING AS A RESULT OF THE UNOCCUPIED CYCLE, THE SYSTEM SHALL CONTINUE TO OPERATE. THE DDC
SYSTEM SHALL DETERMINE THE MINIMUM RUNTIME TO WARM THE SPACES TO THEIR SETPOINT WHEN THE COMPUTED START TIME IS REACHED. THE AIR HANDLING UNIT DISCHARGE AIRTEMPERATURE SHALL BE MAINTAINED AT A SETPOINT OF 85ºF (ADJ.). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL TEMPERATURES EXCEED A SETPOINT OF 68ºF(ADJ.). AT THAT TIME, THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL.
COOLING OPTIMUM START-UP:• THIS CYCLE SHALL OVERRIDE THE UNOCCUPIED CYCLE. IF THE SYSTEM WAS OPERATING AS A RESULT OF THE UNOCCUPIED CYCLE, THE SYSTEM SHALL CONTINUE TO OPERATE. THE DDC
SYSTEM SHALL DETERMINE THE MINIMUM RUNTIME TO COOL THE SPACES TO THEIR SETPOINT WHEN THE COMPUTED START TIME IS REACHED. THE AIR HANDLING UNIT DISCHARGE AIRTEMPERATURE SHALL BE MAINTAINED AT A SETPOINT OF 55ºF (ADJ.). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL TEMPERATURES ARE LESS THAN A SETPOINT OF72ºF (ADJ.). AT THAT TIME, THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL.
GRAPHICAL DISPLAY:DISPLAY THE GLOBAL OUTSIDE AIR TEMPERATURE AND HUMIDITY ON AHU GRAPHIC PAGE.
A
B
C
D
E
F
R
A
B
C
D
E
F
AUX CONTACT TO FMCS TO INITIATE CONTROL
TERMINAL STRIP SPEED
CONTROL SIGNALRETURN FAN
VFD SECTION
SPEED CONTROL SIGNALSUPPLY FAN
VFD SECTION
TERMINAL STRIP
AUX CONTACT TO FMCS TO INITIATE CONTROL
SAFETY CIRCUITS
NH
FIR
E A
LA
RM
SY
ST
EM
DU
CT
HIG
H S
TA
TIC
DU
CT
LO
W S
TA
TIC
LO
W L
IMIT
TE
MP
SW
ITC
H
SUPPLY & RETURN FAN VFD CONTROL
HWR TEMP
HWS TEMP
CWR TEMP
CWS TEMP
P.H.TEMP
SUPPLY FAN. REFER TO UNIT SCHEDULE FOR QUANTITY AND CONFIGURATION OF FANS.
RELIEF AIR, RETURN AIR, AND OUTSIDE AIR DAMPERS ARE EXISTING DAMPERS IN EXISTING DUCTWORK AND ARE TO REMAIN. PROVIDE NEW DDC ACTUATORS TO BE INSTALLED IN EXISTING DAMPERS. REFER TO SHEET M-200 FOR MORE INFORMATION.
NEW DUCTWORK CONNECTION TO EXISTING DUCTWORK
NEW DUCTWORK CONNECTION TO EXISTING DUCTWORK
VALVMOD
VALVFDBK
N.C.
RETURN FAN AIRFLOW
SYSTEM SUPPLY CFM RETURN FANS PRESSURIZATION CFM
REMARKS
AHU-1
AHU-2
7,600
7,300
R-1
R-2
2,300
1,000
NOTE 1
NOTE 1
NOTES:
1. RETURN FAN AIRFLOW SETPOINT SHALL BE THE SUPPLY FAN AIRFLOW (AS MEASURED BY THE AFMS) MINUS THE PRESSURIZATION CFM.
IONIZATION STATUS
BI-POLAR IONIZATION BAR
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-403
MECHANICALCONTROL DIAGRAMS
KATDENSCOPRZKATDEN
06/23/2021
12
M-403
NO SCALE1 AIR HANDLING UNIT CONTROL - AHU-1 & AHU-2
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
DODI
DODI
VFD
DI AO
DIDO
VFD
DI AO
DI
DO
DO
AI
AI
AI
AI AI
AI
FLOW PROOF. INTERLOCK WITH BOILER OPERATION PER MANUFACTURER'S INSTRUCTIONS (TYPICAL EACH BOILER).
CONTROLS
BLR-2N.O.
ON/OFF
VLVFDBK
CONTROLS
BLR-1N.O.
ON/OFF
VLVFDBK
HW
R
HW
S
HWS
HWR NON-POTABLE WATER SUPPLY TO HYDRONIC SYSTEM
LOOPFLOW
HWR
CS
PUMP STATUS
ALARM MOD
START/STOP
MODALARM
CS
PUMP STATUS
HWP-1
HWP-2
START/STOP
MOD
VALVEFDBK
LOOPFLOW
HWS
HWR
DIFF. PRESS.
N.O.
REFER TO FLOOR PLANS FOR LOCATION OF DP SENSOR
BYPASS VALVE TO MAINTAIN MINIMUM FLOW THROUGH BOILERS. SIZE VALVE TO FLOW MINIMUM GPM AS REQUIRED BY BOILER MANUFACTURER FOR A SINGLE BOILER AT MAXIMUM 10 PSI DIFFERENTIAL PRESSURE ACROSS VALVE. PROVIDE ACTUATOR CAPABLE OF FULL CLOSE TO FULL OPEN POSITION WITHIN 30 SECONDS.
COMMUNICATION LINK BETWEEN VFD GATEWAY & FMCS (TYPICAL EACH VFD)
0 10 20 30 40 50 60 70 80 90 100
110
120
130
140
150
160
170
180
190
HW
S T
EM
P °
F
OUTSIDE AIR TEMP °F
HEATING WATER SUPPLY TEMPERATURE RESET SCHEDULE
SEQUENCE OF OPERATION:HEATING WATER BOILERS SHALL HAVE UNIT MOUNTED CONTROLS AND A BOILER MANAGEMENT CONTROL PANEL PROVIDED BY THE BOILER MANUFACTURER. TCC SHALL INTERFACE WITH BOILER MANUFACTURER CONTROLS AS DESCRIBED IN THIS SEQUENCE OF OPERATION. BOILER MANUFACTURER SHALL PROVIDE A GATEWAY INTERFACE CARD THAT IS COMPATIBLE WITH THE COMMUNICATION PROTOCOL OF THE FMCS NETWORK. SEQUENCES OF OPERATION FOR BOTH BOILER CONTROL SYSTEM AND FMCS SHALL BE AS FOLLOWS:
BOILER CONTROL PANEL SEQUENCE OF OPERATION:WHEN THE FMCS ENABLES THE BOILER MASTER CONTROLLER TO RUN, THE BOILER MASTER CONTROLLER SHALL ENABLE THE LEAD BOILER, OPEN THE ASSOCIATED TWO-POSITION ISOLATION VALVE, AND ENERGIZE THE LEAD PUMP.
THE ON BOARD BOILER SEQUENCING CONTROLLER SHALL STAGE AND MODULATE THE BOILER PLANT TO MAINTAIN THE HIGHEST PLANT EFFICIENCY THAT WILL PROVIDE THE REQUIRED SUPPLY WATER TEMPERATURE. THE ON BOARD BOILER SEQUENCING CONTROLLER SHALL OPEN AND CLOSE BOILER ISOLATION VALVES IN SUCH A WAY AS TO PROVIDE PRE AND POST FLOW. THE ON BOARD BOILER SEQUENCING CONTROLLER SHALL VERIFY PROOF OF WATER FLOW BEFORE FIRING BOILERS. THE BOILER SEQUENCING CONTROLLER CAN STAGE ON MULTIPLE BOILERS AT PART LOAD TO INCREASE THE EFFICIENCY OF THE PLANT. BOILER SEQUENCING CONTROLLER PANEL SHALL START/STOP BOILERS ON A FIRST ON/FIRST OFF BASIS TO EQUALIZE RUN TIME BETWEEN BOILERS. TWO-POSITION ISOLATION VALVE OPERATION SHALL BE CONTROLLED BY THE BOILER CONTROL PANEL OF THE RESPECTIVE BOILER THEY SERVE.
THE FOLLOWING BOILER SEQUENCING CONTROLLER POINTS (TO INCLUDE BUT NOT LIMITED TO) SHALL BE CONTROLLED BY THE FMCS AND DISPLAYED ON THE OPERATOR WORKSTATION GRAPHICAL SCREEN:• BOILER SYSTEM STATUS: ENABLE/DISABLE• BOILER OUTLET WATER TEMPERATURE SETPOINT: [°F]
THE FOLLOWING BOILER SEQUENCING CONTROLLER POINTS (TO INCLUDE BUT NOT LIMITED TO) SHALL BE MONITORED BY THE FMCS AND DISPLAYED ON THE OPERATOR WORKSTATION GRAPHICAL SCREEN:• BOILER STATUS: DISABLED/STANDBY/MANUAL OPERATION/REMOTE OPERATION/AUTO/FAULT• FIRING RATE INPUT: [0 - 100%]• FIRING RATE OUTPUT: [0 - 100%]• ACTIVE SETPOINT: [°F]• SYSTEM HWR TEMP: [°F]• SYSTEM HWS TEMP: [°F]• FAULT MESSAGE DISPLAY CODE: [NUMERICAL]• RUN CYCLES: [NUMERICAL]• RUN HOURS: [NUMERICAL]
ALARMS, INTERLOCKS & SAFETIES:BOILER CONTROLS SHALL BE PROGRAMMED TO MAINTAIN CONSTANT SETPOINT (LAST KNOWN VALUE) IN THE EVENT THE FMCS NETWORK COMMUNICATION SIGNAL IS LOST.
FMCS SEQUENCE OF OPERATION:FMCS SHALL OPERATE HEATING WATER SYSTEM 24 HOURS/DAY, 365 DAYS/YEAR.
ONLY ONE HEATING WATER PUMP SHALL RUN AT TIME. THE SECOND HEATING WATER PUMP IS FULLY REDUNDANT. FMCS SHALL AUTOMATICALLY ROTATE THE LEAD HEATING WATER PUMP ONCE/WEEK (10:00 AM EACH TUESDAY, ADJ.) TO EQUALIZE RUN TIME BETWEEN PUMPS. PROVIDE GRAPHICAL BUTTON ON OPERATOR WORKSTATION GRAPHICAL SCREEN TO ALLOW FMCS OPERATOR TO SWITCH LEAD PUMP TO NEXT ROTATION IN THE EVENT THE CURRENT LEAD PUMP REQUIRES MAINTENANCE.
FMCS SHALL MODULATE SIGNAL TO LEAD PUMP VFD AS REQUIRED TO MAINTAIN HEATING WATER DIFFERENTIAL PRESSURE (DP) SETPOINT. FMCS SHALL RESET HEATING WATER DIFFERENTIAL PRESSURE (DP) SETPOINT AS REQUIRED TO MAINTAIN AT LEAST ONE HEATING WATER VALVE 95% (ADJ.) OPEN. FMCS SHALL UTILIZE COMMAND TO ALL HEATING WATER VALVE POSITIONS TO RESET THE HEATING WATER DIFFERENTIAL PRESSURE. IN NO EVENT SHALL THE FMCS DECREASE THE HEATING WATER (DP) SETPOINT BELOW 4 PSI (ADJ.) OR ABOVE 10 PSI (ADJ.).
ALL CONTROLLED AND MONITORED POINTS LISTED IN THE BOILER CONTROL PANEL SEQUENCE ABOVE SHALL BE DISPLAYED ON THE OPERATOR WORKSTATION GRAPHICAL SCREEN.
MINIMUM HEATING WATER FLOW CONTROL:FMCS SHALL MODULATE THE HEATING WATER BYPASS CONTROL VALVE AS REQUIRED TO MAINTAIN MINIMUM FLOW THROUGH EACH OPERATIONAL BOILER. TCC SHALL VERIFY THE MINIMUM FLOW LIMIT OF EACH BOILER WITH EQUIPMENT MANUFACTURER. ADEQUATE FLOW THROUGH EACH BOILER SHALL BE DETERMINED BY THE FLOW METER IN THE HEATING WATER RETURN PIPING.
ALARMS, INTERLOCKS & SAFETIES:TCC SHALL COORDINATE ALL SAFETY AND INTERLOCK REQUIREMENTS WITH BOILER MANUFACTURER. TCC SHALL COORDINATE AND PROVIDE THE INSTALLATION AND WIRING OF BOILER WATER DIFFERENTIAL PRESSURE/FLOW SWITCHES AND OTHER COMPONENTS PROVIDED WITH THE BOILER AS REQUIRED FOR PROPER OPERATION. TCC SHALL PROVIDE AND TERMINATE ALL SAFETY AND INTERLOCK WIRING WITH BOILER CONTROL PANELS AS REQUIRED.
FMCS SHALL AUTOMATICALLY ENABLE THE LAG HEATING WATER PUMP TO RUN IN THE EVENT THE LEAD HEATING WATER PUMP FAILS TO OPERATE.
TCC SHALL VERIFY THE ACCEPTABLE TEMPERATURE RANGES THE BOILERS ARE APPROVED TO OPERATE AT AS PUBLISHED IN THE BOILER MANUFACTURER'S LITERATURE. IF THE TEMPERATURE RANGES LISTED IN THE MANUFACTURER'S LITERATURE DIFFER FROM THOSE IN THIS SEQUENCE OF OPERATION, CONTACT PROJECT ARCHITECT/ENGINEER FOR DIRECTION.
AN ALARM SHALL BE INDICATED TO THE FMCS OPERATOR WORKSTATION IN THE EVENT ANY OF THE FOLLOWING OCCUR:• HWR TEMPERATURE DROPS BELOW 50°F (ADJ.) FOR 5 MINUTES (ADJ.) (AUTO RESET).• HWS TEMPERATURE RISES MORE THAN 10°F (ADJ.) ABOVE SETPOINT (AUTO RESET).• HWS TEMPERATURE DROPS MORE THAN 10°F (ADJ.) BELOW SETPOINT (AUTO RESET).• AN ALARM IS INDICATED AT ANY BOILER ALARM PANEL.• AN ALARM IS INDICATED AT ANY PUMP VFD• SHOULD THE FMCS COMMAND THE LEAD HEATING WATER PUMP TO OPERATE AND THE PUMP FAILS TO DO SO AS DETERMINED BY THE VFD STATUS, AN ALARM SHALL BE INDICATED AT THE FMCS OPERATOR
WORKSTATION AND THE LAG HW PUMP SHALL AUTOMATICALLY START.
R1
R2
DEDICATED CONTACTOR. TYPICAL OF 2.
BLR-1 BURNER CONTROL POWER SUPPLY SHUTDOWN CONTACT. TYPICAL FOR EACH BOILER.
EMERGENCY BOILER
SHUTDOWN
PROVIDE COLOR ENGRAVED PHENOLIC LABELS WITH MIN. 1/2" HIGH WHITE LETTERS ON RED BACKGROUND FOR EACH EMERGENCY BOILER SHUTDOWN SWITCH. SECURELY MOUNT TO WALL ABOVE EACH SWITCH.
ALARMS, INTERLOCKS, AND SAFETIES:TCC SHALL PROVIDE EMERGENCY BOILER SHUTDOWN SWITCH AT EACH BOILER ROOM EXIT MEETING CSD-1 REQUIREMENTS. ACTIVATION OF ANY SWITCH SHALL INTERRUPT POWER TO ALL BOILER CONTROLS VIA BOILER SAFETY SHUTDOWN CONTACTS.
TYPICAL FOR BLR-1, BLR-2
EMERGENCY BOILER SHUTDOWN
TWO WALL MOUNTED EMERGENCY STOP SWITCHES, MUSHROOM HEAD, N.C. CONTACT, TURN TO RELEASE. REFER TO ELECTRICAL PLANS FOR LOCATIONS. ACCEPTABLE MANUFACTURERS: SQUARE D (XAL K174), EATON (C22-PVT45P K11), OR GENERAL ELECTRIC (CR104PTR20A092).
FMCS ENABLE/DISABLE
BLR1
FMCS ENABLE/DISABLE
BLR2
120 V
CO
NT
RO
L
PO
WE
R N
EU
TR
AL1
20 V
CO
NT
RO
L
PO
WE
R H
OT
HEATING SYSTEM REPORT GENERATION
FMCS SHALL MONITOR THE FOLLOWING POINTS ON 5 MINUTE (ADJ.) INTERVALS WITHIN A SINGLE TREND. THE TREND SHALL RUN FOR A 14-DAY (ADJ.) DURATION AT WHICH POINT THE NEWEST VALUES SHALL OVERWRITE THE OLDEST VALUES:
• DATE• TIME• GLOBAL OUTSIDE AIR TEMP. (°F)• HEATING WATER SUPPLY TEMP. (°F)• HEATING WATER RETURN TEMP. (°F)• HEATING WATER FLOWRATE (GPM)• HEATING SYSTEM LOAD (BTU/HR.)• OPERATIONAL STATUS OF EACH HEAT EXCHANGER AND PUMP
THIS INFORMATION SHALL BE ACCESSIBLE TO VIEW IN EITHER TABULAR OR GRAPHICAL FORM ON THE FMCS OPERATOR INTERFACE.
ONCE PER MONTH, THE FMCS SHALL RECORD THE LARGEST HEATING SYSTEM LOAD (IN BTU/HR.) WHICH BOILER THAT MONTH. THE DATE, TIME, OUTSIDE AIR TEMPERATURE, SECONDARY HEATING WATER SUPPLY AND RETURN TEMPERATURES AND FLOW RATE THAT COINCIDED WITH THAT EVENT SHALL ALSO BE RECORDED. THIS INFORMATION SHALL BE STORED TO A MEMORY LOCATION ON THE FMCS OPERATOR INTERFACE THAT IS MAINTAINED (NOT AUTOMATICALLY OVERWRITTEN).
HEATING WATER SYSTEM REPORT GENERATION
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-404
MECHANICALCONTROL DIAGRAMS
KATDENSCOPRZKATDEN
06/23/2021
13
M-404
12" = 1'-0"1 HEATING CONTROL - CONDENSING BOILER VARIABLE/PRIMARY
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
NO SCALE2 HEATING WATER SYSTEM REPORT GENERATION
SCHEDULE GENERAL NOTES:A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND
INSTALLED BY:
MFR = MANUFACTURER
EC = ELECTRICAL CONTRACTOR.
MC = FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED
BY ELECTRICAL CONTRACTOR
MFR/EC = FURNISHED LOOSE BY MANUFACTURER
INSTALLED BY ELECTRICAL CONTRACTOR
ATC = AUTOMATIC TEMPERATURE CONTROL CONTRACTOR
B. DISCONNECT TYPE:
F = FUSED
NF = NON-FUSED
C. CONTROLLER STARTER TYPE:
FV = FULL VOLTAGE
WYE = WYE-DELTA
SS = SOLID STATE (SOFT START)MS = MANUAL STARTER
VFD = VARIABLE FREQUENCY DRIVE
VFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS
D. FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED VALUE,WITH THE SCHEDULED WHEEL TYPE. SUBSTITUTION OF BI OR BIA FANS
FANS FOR FC IS ACCEPTABLE IF EFFICIENCY IS NOT LOWER.
E. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR
NAME PLATE RATING.
F. MUST BE WITHIN +/- 10% OF SCHEDULED RPM.
FAN SCHEDULE
SYMBOL SERVICE CFMS.P.IN.
W.C.
FANCLASS
WHEELDIA.
INCHES
FANRPM
(NOTE F)
DRIVEMAX.AMCASONES
BACKDRAFTDAMPER
ELECTRICAL
MANUFACTURER(NOTE 1)
MODEL(NOTE 1)
REMARKSBHP
(NOTE E)MHP
(NOTE E)
VOLT-PHASE
CONTROLLER/STARTER
BY (NOTE A) TYPE (NOTE C) SCCR
R-1 AHU-1 5,300 1 1 22.0 1,010 DIRECT 25 MOTORIZED 1.6 2.0 230/3 EC VFD 5000 GREENHECK USF
R-2 AHU-2 6,300 1 1 22.0 1,135 DIRECT 28 MOTORIZED 2.3 3.0 230/3 EC VFD 5000 GREENHECK USF
NOTES:
1. SCHEDULED MANUFACTURER AND MODEL ARE BASIS OF DESIGN. REFER TO SPECIFICATIONS FOR APPROVED ALTERNATIVES.
PUMP SCHEDULE
SYMBOL SERVICE GPMPUMP FT.HEAD ATDESIGN
MIMIMUMPUMP
EFFICIENCY
INLET/IMPEL.SIZE IN.
VIBRATIONISOLATION
ELECTRICAL
MANUFACTURER(NOTE 2)
MODEL(NOTE 2)
REMARKSHP
(NOTE E)RPM
VOLT-PHASE
DISCONNECT CONTROLLER/STARTER
TYPE BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)
P-1 CHILLER #1 66.0 30 63.5 6.25 M1 1.0 1,566 230/3 - - EC VFD BELL & GOSSETT e-1531
P-2 CHILLER #2 66.0 30 63.5 6.25 M1 1.0 1,566 230/3 - - EC VFD BELL & GOSSETT e-1531
P-3BUILDING CHILLED
WATER106.0 40 72.0 6.75 M1 2.0 1,685 230/3 - - EC VFD BELL & GOSSETT e-1510
P-4BUILDING HEATING
WATER60.0 45 66.0 6.5 M1 2.0 1,760 230/3 - - EC VFD TACO 1207D
P-5BUILDING HEATING
WATER60.0 45 66.0 6.5 M1 2.0 1,760 230/3 - - EC VFD TACO 1207D
P-6AHU-1 HEATING
COIL15.0 20 50.0 1.25 M3 0.5 1,725 230/3 MFR F EC ECM BELL & GOSSETT e-90
P-7AHU-2 HEATING
COIL15.0 20 50.0 1.25 M3 0.5 1,725 230/3 MFR F EC ECM BELL & GOSSETT e-90
NOTES:
1. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.
2. SCHEDULED MANUFACTURER AND MODEL ARE BASIS OF DESIGN. REFER TO SPECIFICATIONS FOR APPROVED ALTERNATIVES.
HOT WATER BOILER SCHEDULE
SYMBOL FUELINLET FUELPRESSURE
(IN W.C.)
TURNDOWNRATIO
MINIMUMFLOW (GPM)
INPUTMBH
OUTPUTMBH
EWT °F LWT °FOPERATINGPRESSURE
(PSI)
ELECTRICAL
MANUFACTURER(NOTE 1)
MODEL(NOTE 1)
REMARKSHP
VOLT-PHASE
CONTROLLER/STARTER
BY (NOTE A)
BLR-1 LP 14 10:1 15 271 251 140 170 80 1/6 120/1 MFR LOCHINVAR KHB285L NOTE 2
BLR-2 LP 14 10:1 15 271 251 140 170 80 1/6 120/1 MFR LOCHINVAR KHB285L NOTE 2
NOTES:
1. SCHEDULED MANUFACTURER AND MODEL ARE BASIS OF DESIGN. REFER TO SPECIFICATIONS FOR APPROVED ALTERNATIVES.
2. PROVIDE IN-LINE NEUTRALIZATION FOR BOILER DRAIN.
AIR HANDLING UNITSCHEDULE - HOT/CHILLED WATER
SYMBOL AHU-1 AHU-2
SERVICE LOWER LEVEL FIRST FLOOR
SUPPLY FAN
CFM 7,600 7,300
MINIMUM CFM 3,000 2,800
EXTERNAL STATIC PRESSURE IN. W.C. 2.00 1.75
TYPE FORWARD CURVED FORWARD CURVED
FAN RPM (NOTE D) 1,251 1,800
BHP (NOTE E) 8.44 7.90
MHP (NOTE E) 10 10
MINIMUM OUTSIDE AIR CFM 3,000 2,800
VOLT- PHASE 230/3 230/3
HEATING COIL - HOT WATER
EAT °F 40 40
LAT °F 75 75
EWT °F 170 170
LWT °F 132 133
GPM 15.0 15.0
TOTAL MBH 288.0 277.0
MAX. A.P.D. IN. W.C. 0.15 0.13
W.P.D. FEET HEAD 1.61 1.60
COOLING COIL - CHILLED WATER
EAT °F DB 81 78
EAT °F WB 68 65
MAX. LAT °F DB 55 51
LAT °F WB 54.6 50
EWT °F 45 45
LWT °F 54 54
GPM 66.0 66.0
TOTAL MBH 318.0 313.0
MAX. A.P.D. IN. W.C. 0.87 1.12
W.P.D. FEET HEAD 11.60 14.30
FILTER
TYPE MERV 15 MERV 15
VELOCITY FT/MIN 565 543
VIBRATION ISOLATION
TYPE M4 M4
DEFLECTION (IN.) 0.75 0.75
ELECTRICAL
VOLT-PHASE 230/3 230/3
FLA/RLA 28.0 28.0
MCA 35.00 35.00
MOCP AMPS 60 60
DISCONNECT BY (NOTE A) MFR MFR
DISCONNECT TYPE (NOTE B) F F
CONTROLLER/STARTER BY (NOTE A) MFR MFR
CONTROLLER/STARTER TYPE (NOTE C) VFD VFD
SCCR 65000 65000
MANUFACTURER (NOTE 3) TRANE TRANE
MODEL NUMBER (NOTE 3) CSAA014 CSAA014
REMARKS NOTES 2 & 4 NOTES 2 & 4
NOTES:
1. LAT LISTED IS LEAVING SURFACE OF COIL.
2. PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.
3. SCHEDULED MANUFACTURER AND MODEL ARE BASIS OF DESIGN. REFER TO SPECIFICATIONS FOR APPROVED ALTERNATIVES.
4. PROVIDE IONIZATION BAR DIRECTLY UPSTREAM OF COOLING COIL. REFER TO AIR HANDLING UNIT SPECIFICATION 23 73 13 FOR MORE INFORMATION.
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-500
MECHANICALSCHEDULES
KATDENSCOPRZKATDEN
06/23/2021
14
M-500
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
SCHEDULE GENERAL NOTES:A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND
INSTALLED BY:
MFR = MANUFACTURER
EC = ELECTRICAL CONTRACTOR.
MC = FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED
BY ELECTRICAL CONTRACTOR
MFR/EC = FURNISHED LOOSE BY MANUFACTURER
INSTALLED BY ELECTRICAL CONTRACTOR
ATC = AUTOMATIC TEMPERATURE CONTROL CONTRACTOR
B. DISCONNECT TYPE:
F = FUSED
NF = NON-FUSED
C. CONTROLLER STARTER TYPE:
FV = FULL VOLTAGE
WYE = WYE-DELTA
SS = SOLID STATE (SOFT START)MS = MANUAL STARTER
VFD = VARIABLE FREQUENCY DRIVE
VFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS
D. FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED VALUE,WITH THE SCHEDULED WHEEL TYPE. SUBSTITUTION OF BI OR BIA FANS
FANS FOR FC IS ACCEPTABLE IF EFFICIENCY IS NOT LOWER.
E. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR
NAME PLATE RATING.
F. MUST BE WITHIN +/- 10% OF SCHEDULED RPM.
FINNED TUBE REHEAT (FTR) CONTROL VALVE SCHEDULE
SYMBOL ASSOCIATED VAV
HEATING WATER
REMARKSEWT (°F)
ASSOCIATED BALANCINGVALVE GPM
CV 1-1 1-10 170 1.2 NOTE 1
CV 1-2 1-12 170 0.9 NOTE 1
CV 1-3 1-14 170 1.2 NOTE 1
CV 1-4 1-2, 1-4 170 1.7 NOTE 1
CV 1-5 1-3, 1-5 170 1.8 NOTE 1
CV 1-6 1-6 170 0.9 NOTE 1
CV 2-1 2-5 170 1.1 NOTE 1
CV 2-2 2-8 170 1.4 NOTE 1
CV 2-3 2-9 170 1.4 NOTE 1
CV 2-4 2-10 170 0.5 NOTE 1
CV 2-5 2-12 170 0.5 NOTE 1
CV 2-6 2-7 170 1.3 NOTE 1
CV 2-7 2-7 170 0.5 NOTE 1
NOTES:
1. ASSOCIATED BALANCING VALVE SHALL BE SET TO SCHEDULED GPM.
EXISTING VARIABLE AIR VOLUME (VAV) UNIT SCHEDULE
SYMBOL AHU NUMBER
AIRFLOW HEATING WATERCONTROL
TYPE(NOTE 3)
REMARKSMAX.CFM
HEATINGCFM
MIN. CFM ROWS EAT (°F) LAT (°F) EWT (°F) GPM
1-1 1 650 325 325 1 75 95 170 0.5 B NOTES 1 & 2
1-2 1 600 - 150 - 75 75 - - A NOTES 1 & 2
1-3 1 600 - 150 - 75 75 - - A NOTES 1 & 2
1-4 1 600 - 150 - 75 75 - - A NOTES 1 & 2
1-5 1 600 - 150 - 75 75 - - A NOTES 1 & 2
1-6 1 400 - 100 - 75 75 - - A NOTES 1 & 2
1-7 1 750 375 375 1 75 95 170 0.5 B NOTES 1 & 2
1-8 1 300 - 75 - 75 75 - - A NOTES 1 & 2
1-9 1 400 200 200 1 75 95 170 0.3 B NOTES 1 & 2
1-10 1 650 - 175 - 75 75 - - A NOTES 1 & 2
1-11 1 300 - 75 - 75 75 - - A NOTES 1 & 2
1-12 1 500 - 125 - 75 75 - - A NOTES 1 & 2
1-13 1 300 150 150 1 75 95 170 0.2 B NOTES 1 & 2
1-14 1 600 - 150 - 75 75 - - A NOTES 1 & 2
2-1 2 400 200 200 1 75 95 170 0.3 B NOTES 1 & 2
2-2 2 350 175 175 1 75 95 170 0.3 B NOTES 1 & 2
2-3 2 400 200 200 1 75 95 170 0.3 B NOTES 1 & 2
2-4 2 400 200 200 1 75 95 170 0.3 B NOTES 1 & 2
2-5 2 1050 - 275 - 75 75 - - A NOTES 1 & 2
2-6 2 300 150 150 1 75 95 170 0.2 B NOTES 1 & 2
2-7 2 1300 - 325 - 75 75 - - A NOTES 1 & 2
2-8 2 950 - 225 - 75 75 - - A NOTES 1 & 2
2-9 2 700 - 175 - 75 75 - - A NOTES 1 & 2
2-10 2 200 - 50 - 75 75 - - A NOTES 1 & 2
2-11 2 600 300 300 1 75 95 170 0.4 B NOTES 1 & 2
2-12 2 200 - 50 - 75 75 - - A NOTES 1 & 2
2-13 2 150 75 75 1 75 95 170 0.1 B NOTES 1 & 2
NOTES:
1. BALANCE EXISTING VAV CFM AND GPM AS INDICATED.
2. BID ALTERNATE #1 SHALL FULLY REPLACE VAVS AS SCHEDULED. REFER TO SPECIFICATION SECTION 23 36 00 - AIR TERMINAL UNITS FOR VAV INFORMATION.
3. REFER TO 2/M-402 AND 3/M-402 FOR DESCRIPTION OF CONTROL TYPE.
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC & CONTROLS ADMINISTRATION & MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
M-501
MECHANICALSCHEDULES
KATDENSCOPRZKATDEN
06/23/2021
15
M-501
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
ELECTRICAL ABBREVIATION KEY
AFF ABOVE FINISHED FLOOR
N.O. NORMALLY OPEN
ABBR: DESCRIPTION:
TYP TYPICAL
C CONDUIT
UNO UNLESS NOTED OTHERWISE
GFI GROUND FAULT INTERRUPTER
1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES ORSPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENTNAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICALEQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.
ELECTRICAL GENERAL NOTES:
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FORACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILSON THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREEWITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FORBRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEENEACH PHASE.
3. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALLBE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OFTHROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATIONAND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
4. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALLMOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENTSUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHERCONTRACTOR.
5. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALLOPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THEEXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED ORSEALED INTO OPENINGS.
6. ELECTRICAL INDENTIFICATION. REFER TO SPECIFICATION SECTION 26 05 53 FORCOLOR/LABEL REQUIREMENTS FOR CONDUIT, BOX, CABLE/WIRE, AND EQUIPMENT.
ELECTRICAL INSTALLATION NOTES:
ECONN 26 05 33 ELECTRICAL CONNECTIONE
E
MDP 26 24 16 PANELBOARD - SURFACE MOUNT
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:SPEC
SECTION:DESCRIPTION:
RI-TECH-W 26 05 33 TECHNOLOGY ROUGH-IN, MOUNTED +54" AFF
EPO EPO 26 09 16 BOILER EMERGENCY STOP BUTTON
AR FA-161 ADDRESSABLE FIRE ALARM RELAY
DS-# 26 28 16 DISCONNECT. REFER TO DISC/STA SCHEDULE
SDFA-122 28 31 00 FIRE ALARM IN DUCT SMOKE DETECTOR
DPM DPM 26 09 13 DIGTAL POWER METER
W/RI
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELDSURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS ANDREPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT AND CONDUIT ARE SHOWN. VERIFY EXISTING CONDITIONSAND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CONDUITS BEFORE FABRICATION. RISESAND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH SUB-CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HERWORK AND SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHERUTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HERAREA OF WORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATEDWITH HIS/HER WORK.
6. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEWEQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHERARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOESNOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TOALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO POWER, AND SYSTEMS.
ELECTRICAL PHASING NOTES:THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO POWER AND SYSTEMS.
1. REFER TO GENERAL CONTRACTOR'S INSTRUCTIONS FOR MORE DETAILS, PHASINGSCHEDULES AND FOR CONCURRENT WORK. MECHANICAL AND ELECTRICAL DRAWINGSDEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL AND ELECTRICAL DRAWINGSDO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASINGCRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY LIGHTING, POWER, SYSTEMS, ETC. AS NEEDED TO MAINTAINSERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY LIGHTING, CIRCUITS, ETC. AS NECESSARY TO KEEP ALL OCCUPIEDSPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
1VIEW NAME1/8" = 1'-0"
1
M101
14
32
T101
SIMDETAIL REFERRED TO BY ELEVATION
SHEET DETAIL IS LOCATED ON
INDICATES SIMILAR DETAIL REFERENCED IN MULTIPLE LOCATIONS
SIM
INDICATES SIMILAR DETAIL REFERENCED IN MULTIPLE LOCATIONS
LEVEL NAME
10' - 0" HEIGHT ABOVE PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL
NO R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
NEW WORK UNDERFLOOR OR UNDERGROUND BY THIS CONTRACTOR (DARK LONG DASHED LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
LINE TYPE KEY:
TEMPERATURE CONTROLS CONTRACTORT.C.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
26 29 23VFD-#
ELECTRICAL EQUIPMENT TAGS
TAG:SPEC SECTION:
VARIABLE FREQUENCY DRIVE. REFER TO VFD SCHEDULE.
DESCRIPTION:
1. BID ALTERNATE #1: DEMOLISH EXISTING VARIABLE AIR VOLUME BOXES AND PROVIDE NEW.2. BID ALTERNATE #2: PROVIDE USAGE METERING BY THE BUILDING AUTOMATION SYSTEM
FOR ELECTRICAL, WATER, AND LIQUID PROPANE UTILITIES SERVING BUILDING.
BID ALTERNATES:
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC &
CONTROLS
ADMINISTRATION &
MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
E-000
ELECTRICAL
COVERSHEET
EVAMILZACCARMARHAR
06/23/2021
16
E-000
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
CLASSROOM130
CLASSROOM 129
CLASSROOM133
CLASSROOM134
TOILET136
CLASSROOM123
LABORATORY128
OFFICE 126
OFFICE127
LIBRARY121
FOYER102
CUST.105
WORK ROOM108
CONFERENCE RM.109
INFIRMARY 107
EXAM. RM.106
WOMEN217
OFFICE112
OFFICE111
OFFICE110
STO.118
WOMEN117
MEN116
TEST CENTER113
CLASSROOM122
TOILET104
STO.115
CUSTODIAN135
E
1
2AREA OF WORK
3
W/R
I
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC &
CONTROLS
ADMINISTRATION &
MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
E-100
LOWER LEVEL ADMIN
PLANS - ELECTRICAL
EVAMILZACCARMARHAR
06/23/2021
17
E-100N
O R HT
1/8" = 1'-0"1 LOWER LEVEL ADMIN PLAN - ELECTRICAL NEW WORK
KEYNOTES:
1. DATA DROP FOR BAS PANEL. PROVIDE (2) CAT 6 CABLES TERMINATED TO A RJ 45 JACK AT BAS. TERMINATE CABLES IN FIRST FLOOR TELECOMMUNICATIONS ROOM ON EXISTING MODULAR PATCH PANEL. COORDINATE EXACT LOCATION OF BAS PANEL WITH T.C.C. PRIOR TO ROUGH-IN.
2. BAS PANEL. PROVIDE DEDICATED 120V CIRCUIT FROM EXISTING PANEL 'EP' USING SPARE 20A/1P CIRCUIT WITH 2#12 & 1#12GND IN 3/4"C. COORDINATE EXACT LOCATION OF BAS PANEL WITH T.C.C. PRIOR TO PERFORMING ANY WORK.
3. PROPOSED CONDUIT RUN FROM FIRST FLOOR DISTRIBUTION PANEL TO BAS. EXACT ROUTE TO BE COORDINATED BY E.C. WITH EXISTING DISCIPLINES.
#
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
WOMEN217
MEN218
MECH. RM.220
RECEPTION 226
OFFICE 222
SECRETARIAL AREA213
OFFICE214
OFFICE 215
OFFICE 212
SECRETARY 210
OFFICE 208
FILE RM.209
CONFERENCE RM.207
OFFICE 206
OFFICE 205
WAITING 202
RECEPT ST.231
OFFICE 227
FILE229
FILE228
OFFICE 223
OFFICE 224
BUSINESS OFFICE230
EEEEE
EE
EE
E E
EP
O
EP
O
E
E
E E
WOMEN217
MEN218
MECH. RM.220
RECEPTION 226
OFFICE 222
SECRETARIAL AREA213
OFFICE214
OFFICE 215
OFFICE 212
SECRETARY 210
OFFICE 208
FILE RM.209
CONFERENCE RM.207
OFFICE 206
OFFICE 205
WAITING 202
RECEPT ST.231
OFFICE 227
FILE229
FILE228
OFFICE 223
OFFICE 224
BUSINESS OFFICE230
EEEEE
EE
E E
E
E
RETROFITTED 'MDP'
EXISTING TRANSFER
SWITCH
EXISTING PANEL 'EP'
AHU-1 AHU-2
P-5 P-4 P-3 P-2 P-1
1
SD SD
B-2B-1
AREA OF WORK
SD
SD
VFD-2VFD-2
VFD-2VFD-1VFD-1
P-6 P-7
2
2
DS-1
R-2
R-1
DS-1
4 4
VFD-2VFD-3
5
5
AR
AR
AR
AR
EXISTING GENERATOR
PLASMA BAR/AHU-2PLASMA BAR/AHU-177
EXISTING COMBO STARTERS AND BUSWAY
EXISTING AHU-1 MCCEXISTING AHU-2
EXISTING AHU-1
EXISTING TRANSFER
SWITCH
EXISTING PANEL 'EP'
AREA OF WORK
EXISTING BOILERS EXISTING GENERATOR
EXISTING R-1
EXISTING R-2
6
3 3
EXISTING P-2E
EXISTING P-1E
EXISTING P-1E
EXISTING P-4E
EXISTING P-5E
EXISTING AHU-2 MCC
EXISTING 'MDP'
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC &
CONTROLS
ADMINISTRATION &
MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
E-101
FIRST FLOOR ADMIN
PLAN - ELECTRICAL
EVAMILZACCARMARHAR
06/23/2021
18
E-101
NO R HT
3/16" = 1'-0"2 FIRST FLOOR ADMIN PLAN - ELECTRICAL NEW WORK
NO R HT
3/16" = 1'-0"1 FIRST FLOOR ADMIN PLAN - ELECTRICAL DEMOLITION
GENERAL SHEET NOTES:
1. REFER TO ONE-LINE DIAGRAM AND EQUIPMENT DATA SCHEDULE ON SHEET E-300 - ELECTRICAL DETAILS AND ONE-LINEDIAGRAM FOR CIRCUITING INFORMATION.
KEYNOTES:
1. PROVIDE STEEL-CHANNEL SUPPORT FOR MOUNTING OF VFD AND VERTICALLY STACK.
2. BOILER EMERGENCY STOP BUTTON. REFER TO EMERGENCY BOILER SHUTDOWN DIAGRAM ON SHEET M-404 - MECHANICAL CONTROL DIAGRAMS FOR MORE INFORMATION.
3. PROTECT EXISTING BOILER CONTROL CIRCUIT IN PLACE AND RECONNECT FOR NEW BOILER CONTROLS.
4. LOCATE DUCT DETECTORS AND ADDRESSABLE RELAY FOR AHU-1 AND AHU-2 IN ACCESSIBLE LOCATION WITHIN 5' OF STRAIGHT RUN OF DUCTS. PROVIDE REMOTE KEY INDICATE SWITCH ON WALL FOR TESTING AND RESET OF DETECTOR AT ACCESSIBLE LOCATION ON WALL. DEVICES SHALL MATCH THE TYPE AND MANUFACTURER OF THE EXISTING FIRE ALARM SYSTEM. SYSTEM OUTPUT SHALL BE AN ALARM SEQUENCE, ACTIVATION OF AUDIBLE AND VISUAL DEVICES AND AHU SHUTDOWN. REPROGRAM FIRE ALARM CONTROL PANEL AS REQUIRED.
5. LOCATE DUCT DETECTORS AND ADDRESSABLE RELAY FOR R-1 AND R-2 IN ACCESSIBLE LOCATION WITHIN 5' STRAIGHT RUN OF DUCTS. PROVIDE REMOTE KEY INDICATE SWITCH ON WALL FOR TESTING AND RESET OF DETECTOR IN ACCESSIBLE LOCATION ON WALL. DEVICES SHALL MATCH THE TYPE AND MANUFACTURER OF THE EXISTING FIRE ALARM SYSTEM. SYSTEM OUTPUT SHALL BE AN ALARM SEQUENCE, ACTIVATION OF AUDIBLE AND VISUAL DEVICES AND AHU SHUTDOWN. REPROGRAM FIRE ALARM CONTROL PANEL AS REQUIRED.
6. EXISTING INCOMING SWITCHBOARD TO BE REMOVED FOR MODIFICATION. REFER TO ONE-LINE DIAGRAMS ON E-300.
7. 120V, 15A, 1-PHASE ELECTRICAL CONNECTION FOR PLASMA BAR IONIZER LOCATED WITHIN NEW AHU. COORDINATE CONNECTION TO 120V:24V POWER SUPPLY WITH M.C.
#
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
EQUIPMENT DATA SCHEDULEDESCRIPTION LOAD DATA CONTROLS DISCONNECT AT EQUIP.
REMARKSMARK SERVES
FU
RN
ISH
ED
BY
INS
TA
LL
ED
BY
LOAD VOLTAGE
PH
AS
E
FU
RN
ISH
ED
BY
INS
TA
LL
ED
BY
CO
NT
RO
LW
IRIN
G
DIS
C. T
YP
E
DIS
C. S
IZE
FU
RN
ISH
ED
BY
INS
TA
LL
ED
BY
WIRE & CONDUIT
P-1 CHILLER 1MC MC
1 HP 240 3EC EC TC
- -- -
4#12 & 1#12 GND IN 3/4"CREFER TO ONE-LINE FOR VFDSIZE.
P-2 CHILLER 2MC MC
1 HP 240 3EC EC TC
- -- -
4#12 & 1#12 GND IN 3/4"CREFER TO ONE-LINE FOR VFDSIZE.
P-3BUILDING CHILLEDWATER MC MC
2 HP 240 3EC EC TC
- -- -
4#12 & 1#12 GND IN 3/4"CREFER TO ONE-LINE FOR VFDSIZE.
P-4BUILDING HEATINGWATER MC MC
2 HP 240 3EC EC TC
- -- -
4#12 & 1#12 GND IN 3/4"CREFER TO ONE-LINE FOR VFDSIZE.
P-5BUILDING HEATINGWATER MC MC
2 HP 240 3EC EC TC
- -- -
4#12 & 1#12 GND IN 3/4"CREFER TO ONE-LINE FOR VFDSIZE.
P-6 AHU-1 HEATING COIL MC MC 0.5 HP 240 3 MFR MFR MFR NF 30A EC EC 4#12 & 1#12 GND IN 3/4"C
P-7 AHU-2 HEATING COIL MC MC 0.5 HP 240 3 MFR MFR MFR NF 30A EC EC 4#12 & 1#12 GND IN 3/4"C
AHU-1 BLOWER COIL UNITMC MC
3 HP 240 3MFR MFR TC
- -- -
4#6 & 1#10 GND IN 1" C.REFER TO ONE-LINE FOR VFDSIZE.
AHU-2 BLOWER COIL UNITMC MC
3 HP 240 3MFR MFR TC
- -- -
4#6 & 1#10 GND IN 1" C.REFER TO ONE-LINE FOR VFDSIZE.
R-1 AHU-1 RETURN FANMC MC
2 HP 240 3EC EC TC
- -- -
4#12 & 1#12 GND IN 3/4"CREFER TO ONE-LINE FOR VFDSIZE.
R-2 AHU-2 RETURN FANMC MC
3 HP 240 3EC EC TC
- -- -
4#12 & 1#12 GND IN 3/4"CREFER TO ONE-LINE FOR VFDSIZE.
EQUIPMENT DATA NOTES:
HP / LOAD FURNISHED OR INSTALLED BY DISCONNECT TYPE SIZE
HORSEPOWER UNLESS EC ELECTRICAL CONTRACTOR NF NON-FUSED SWITCH FUSE/SWITCH SIZEKW, KVA, OR AMPSINDICATED
TCTEMPERATURE CONTROLSCONTRACTOR
TRIP SIZE
MFR MANUFACTURER
MC MECHANICAL CONTRACTOR
600A/3P
1
2
3
4
5
6
600 A
MP
BU
S
GROUND
120/240V, 3-PHASE, 4WHIGH-LEG DELTA
'EXISTING MDP'
200AS/3P
E
200AS/3P
E
200AS/3P
200AS/3P
E
200AS/3P
200A/3P
E
60AS/3P
60AS/3P
30AS/3P
30AS/3P
E
30AS/3P
E
30AS/3P
SPACE
SPACE
7
8
9
10
11
12
13
14
CHILLER #1
CHILLER #2
HOT WATER HEATER
UNKNOWN LOCATION
LP-1, LP-2
EXISTING AHU-1 MOTOR CONTROL CENTER
EXISTING AHU-2 MOTOR CONTROL CENTER
EXHAUST FAN
CHILLER PUMP #2
LP-3
CHILLER PUMP #1
ATS-1
E
E
AIC RATINGS LISTED FOR EQUIPMENT ARE MINIMUM REQUIREMENTS FOR BUS BRACING AND DEVICE RATING. ALL EQUIPMENT SHALL BE FULLY RATED UNLESS SPECIFICALLY NOTED AS SERIES RATED.
1.
2.
3.
4.
5.
6.
INDICATES DIRECT CONNECTION OF GROUND CONDUCTOR TO GROUND BUS. SUBSCRIPT "I" INDICATES DIRECT CONNECTION OF ISOLATED GROUND CONDUCTOR TO ISOLATED GROUND BUS.
INDICATES O.Z. GEDNEY OR EQUAL GROUND BUSHING BONDED TO GROUND BUS WITH CONDUCTOR SIZED TO MAXIMUM FEEDER GROUND CAPACITY.
CONDUCTOR AND CONDUIT SIZES ON THE LINE AND LOAD SIDES OF ALL NON-FUSIBLE DISCONNECT SWITCHES SHALL BE IDENTICAL UNLESS NOTED OTHERWISE.
ONE LINE DIAGRAM NOTES
FUSED LOW VOLTAGE SWITCH.
CIRCUIT BREAKER.
1 5/64"12"
WALL WITH INSULATION
FLANGES ON EACH SIDE OF WALL. CAULK AT WALL AND SLEEVE.
CONDUIT
SHEET METAL SLEEVE, 2" LARGER THAN CONDUIT OVERALL DIAMETER.
PACK AROUND CONDUIT WITH FIBERGLASS INSULATION
ESCUTCHEON PLATES ON BOTH SIDES
ANCHOR SUPPORTS TO PUMPCONCRETE BASE. INSTALLATIONSHALL NOT INTERFERE WITHPUMP OR MOTOR REPLACEMENT.PROVIDE ANGLE BRACE ANDFOOT ANCHORED TO FLOOR.
LIQUIDTIGHT FLEXIBLE CONDUIT,PROTECTED FROM PHYSICAL DAMAGE.
GALVANIZED STEEL SUPPORTCHANNELS. MOUNT VFD BETWEEN SUPPLY AND RETURN TO ALLOW INSTALLATION OF MOTOR AND PUMP.
600A/3P
1
2
3
4
5
6
600 A
MP
BU
S
GROUND
120/240V, 3-PHASE, 4W (HIGH-LEG DELTA)
'RETROFITTED MDP'65,000 SCCR
200AS/3P
200AS/3P
200AS/3P
200AS/3PLSI
200AS/3PLSI
200A/3P
60A/3P
60A/3P
E
30A/3P
15A/3P
15A/3P
15A/3P
7
8
9
10
11
12
13
14
TO AHU-1
TO AHU-2
P-1
P-2
P-3
E
E
E
E
15A/3P
P-4E
15A/3P
P-5E
E
E
EXISTING
CHILLER #2
EXISTING
HOT WATER HEATER
EXISTING UNKNOWN 200A
FEED, SHALL BE IDENFITIED
AND LABELED BY THE
CONTRACTOR
EXISTING
LP-1, LP-2
EXISTING
EXHAUST FAN
E
E EXISTING
CHILLER #1
EXISTING
ATS-1
[LSI]
15A/3P
P-6E
15A/3P
P-7E
15A/3P
R-1E
15A/3P
R-2E
(3)30A/3P
PREPARED SPACE
15
16
17
18
20
NE
UT
RA
L
VFD-1
VFD-1
VFD-2
VFD-2
VFD-2
VFD-2
VFD-3
DPMC.T.'S
(3)1
15A/1P
PLASMA BAR / AHU-1E19
E PLASMA BAR / AHU-2
2#12 AND 1#12 GND IN 3/4" C.
W. E. SEARS YOUTH
CENTER
POPLAR BLUFF, MO 639019400 SEARS LANE
UPGRADE HVAC &
CONTROLS
ADMINISTRATION &
MULTIPURPOSE BUILDING
POPLAR BLUFF, MISSOURI
H1901-01 7701 8877701004
06/23/2021
ISSUE DATE:
SHEET NUMBER:
SITE #
CHECKED BY:DRAWN BY:
DESIGNED BY:
DATE:REVISION:
FACILITY #
PROJECT #
SHEET TITLE:
REVISION:DATE:
REVISION:DATE:
CAD DWG FILE:
STATE OF MISSOURI
MICHAEL L PARSON,
GOVERNOR
OFFICE OF ADMINISTRATION
DIVISION OF FACILITIES
MANAGEMENT,
DESIGN AND CONSTRUCTION
OF 19 SHEETS
EN
GIN
EE
R
IME
G C
OR
P.
15 S
UN
NE
N, S
UIT
E 1
04, S
T. L
OU
IS, M
O 6
3143
E-300
ELECTRICAL DETAILS
AND ONE LINE
DIAGRAM
EVAMILZACCARMARHAR
06/23/2021
19
E-300
NO SCALE2 DISTRIBUTION PANEL MDP ONE-LINE DEMOLITION
NO SCALE3 CONDUIT WALL PENETRATION
NO SCALE4 PUMP CONNECTION DETAIL
NO SCALE1 DISTRIBUTION PANEL MDP ONE-LINE NEW WORK
420 - 4-20mA FOLLOWER
CONTROL:
DS - DISCONNECT SWITCH *ET - ELECTRONIC THERMAL OVERLOADS
LINE DISCONNECT: *MA - MANUAL SPEED ADJUSTMENT *SHZ - SKIP FREQUENCY CAPABILITY
(INCLUDES * ITEMS) *HA - HAND-OFF-AUTO DOOR SWITCH
PWM - PULSE WIDTH MODULATED SA - STANDARD ACCESSORIES *CT - CONTROL TRANSFORMER, FUSED, 120V
STARTER TYPE: REMARKS:
VARIABLE FREQUENCY DRIVE SCHEDULE
ITEM LINE DISC.DRIVE
BYPASS CONTROL
VOLTAGE DRIVE
NEMA ENCLOSURE REMARKS APPROVED MANUFACTURERSINPUT PH.H.P.
RATING TYPE
VFD-1 DS 3CONTACT
420 240 V 3 1 PWM 1 SA VARIABLETORQUE
TOSHIBA Q9 SERIESABB ACH 550 SERIESDANFOSS VLT6000 SERIESKOHLER KCS SERIES
VFD-2 DS 3CONTACT
420 240 V 3 2 PWM 1 SA VARIABLETORQUE
TOSHIBA Q9 SERIESABB ACH 550 SERIESDANFOSS VLT6000 SERIESKOHLER KCS SERIES
VFD-3 DS 3CONTACT
420 240 V 3 3 PWM 1 SA VARIABLETORQUE
TOSHIBA Q9 SERIESABB ACH 550 SERIESDANFOSS VLT6000 SERIESKOHLER KCS SERIES
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2021 IMEG CORP.
15 SUNNEN DR, SUITE 104SAINT LOUIS, MO 63143314.645.1132 FAX: 314.645.1173www.imegcorp.com
19002696.00
CB - CIRCUIT BREAKER *EO - ELECTRONIC OVERLOAD (3 PHASE MOTORS) *TA - TWO CONVERTIBLE AUXILIARY CONTACTS
NF - NON-FUSED *CT - CONTROL TRANSFORMER, FUSED 120V *RP - RED (RUN) PILOT LIGHT IN DOOR
FU - FUSED SA - STANDARD ACCESSORIES (INCLUDES * ITEMS) *HA - HAND-OFF-AUTO IN DOOR
DISCONNECT TYPE: REMARKS:
NOTE: ALL DISCONNECTS (EXCEPT MANUAL STARTERS) SHALL BE HEAVY DUTY TYPE.
E - DISCONNECT AND STARTER SCHEDULE
ITEM
DISCONNECT TYPE &RATING CIRCUIT
VOLTAGE POLESNEMA
ENCLOSURE REMARKS APPROVED MANUFACTURERSTYPE RATING
DS-1 NF 30 A 240 V 3 1 SA SQUARE D 3110 H361EATON TYPE DHGENERAL ELECTRIC TYPE THSIEMENS TYPE HF
EXISTING INCOMING SWITCHBOARD IS MANUFACTURED BY SQUARE D-MODEL QMB. DISCONNECT AND REMOVE ALL INTERIOR COMPONENTS OF PANEL. DISCONNECT AND PROTECT FEEDERS FOR EXISTING-TO-REMAIN LOADS. PROTECT EXISTING TUB IN PLACE FOR MODIFICATION AS INDICATED ON NEW WORK ONE-LINE DIAGRAM. BUILDING IS TO REMAIN OPERATIONAL DURING CONSTRUCTION. PROVIDE OVERTIME HOURS FOR RETROFITTING OF PANEL TO MINIMIZE DOWNTIME. PROVIDE OWNER WITH A MINIMUM 48HRS NOTICE OF ANY SCHEUDLED OUTAGES.
SQUARE D INTERIOR ONLY. PROVIDE NEW TRIM AND INTERIOR COMPONENTS TO EXISTING PANEL ENCLOSURE AS INDICATED. FIELD MEASURE EXISTING PANEL AS NECESSARY FOR ACCURATE MODIFICATION OF PANEL. RECONNECT EXISTING-TO-REMAIN LOADS.
2/E-300 GENERAL NOTE:
1. REFER TO EQUIPMENT DATA SCHEDULE FOR WIRE AND CONDUIT SIZING FORALL EQUIPMENT CIRCUITS.
ONE LINE DIAGRAM KEYED NOTES:
1. BASE BID: NO ELECTRICAL USAGE METERING TO BEMONITORED BY BUILDING AUTOMATION SYSTEM.BID ALTERNATE #2: PROVIDE ELECTRICAL USAGE METERING TOBE MONITORED BY BUILDING AUTOMATION CONTROLS SYSTEM.ELECTRICAL CONTRACTOR SHALL PROVIDE THE METER.COORDINATE WITH CONTROLS CONTRACTOR. REFER TO 7/M-402FOR UTILITY METERING CONTROL.
#