WWW.DOVETAILDECK.COM2.0D BEKAERT | APRIL 2019

Normal Weight Concrete (145 pcf)

Total Slab

Depth(in.)

Theoretical Concrete Volume

(yd3/100 ft2)

Min. As for T&S(in.2)

Recommended Reinforcing for Temperature and Shrinkage

Bekaert Dramix® Steel Fibers Alternate to WWR (pcy)

WWR (OR) 3D 65/60BG 3D 80/60BG 4D 65/60BG4D 80/60BG or

5D 65/60BG

4 1.12 0.028 6x6-W1.4xW1.4 27 22 33 34

4½ 1.28 0.028 6x6-W1.4xW1.4 22 14 33 34

4¾ 1.35 0.028 6x6-W1.4xW1.4 20 14 33 34

5 1.43 0.028 6x6-W1.4xW1.4 19 14 33 34

5¼ 1.51 0.029 6x6-W2.1xW2.1 18 14 33 34

5½ 1.58 0.032 6x6-W2.1xW2.1 18 14 33 34

6 1.74 0.036 6x6-W2.1xW2.1 18 14 33 34

6¾ 1.97 0.043 6x6-W2.9xW2.9 18 14 33 34

Notes: 1. Recommended WWR reinforcing is for minimum temperature and shrinkage per SDI‐C. Larger WWR may be required to comply with UL Fire Resistant Designs.2. FRC reinforcement is based on IAPMO UES ER-497 and ISO 17025 facility test data.3. Dramix® 4D 65/60BG, 4D 80/60BG and 5D 65/60BG should only be used when both required for diaphragm reinforcement and with minimum f’c= 4 ksi.4. Dramix® fibers may be used in UL or ULC fire rated assemblies in lieu of WWR. See UL file R13907 for additional information.5. For information on Bekaert Dramix® fibers contact 770-514-2295 or infobuilding@bekaert.com.

2.0D FORMLOK DECK-SLAB• 2” Deep Composite Deck• f’c = 3000 psi (min.)• UL Fire Rated

Light Weight Concrete (110 pcf)

Total Slab

Depth(in.)

Theoretical Concrete Volume

(yd3/100 ft2)

Min. As for T&S(in.2)

Recommended Reinforcing for Temperature and Shrinkage

Bekaert Dramix® Steel Fibers Alternate to WWR (pcy)

WWR (OR) 3D 65/60BG 3D 80/60BG 4D 65/60BG4D 80/60BG or

5D 65/60BG

4 1.12 0.028 6X6-W1.4xW1.4 N/A 33 33 34

4½ 1.28 0.028 6x6-W1.4xW1.4 30 27 33 34

5 1.43 0.028 6x6-W1.4xW1.4 23 24 33 34

5¼ 1.51 0.029 6x6-W2.1xW2.1 22 23 33 34

5½ 1.58 0.032 6x6-W2.1xW2.1 22 23 33 34

6 1.74 0.036 6x6-W2.1xW2.1 22 23 33 34

The information in this product data sheet is presented for general information only and is not to be used or relied upon for any application without independent verification by a professional engineer or other qualified professional. Nucor Corporation and its affiliates (collectively, “Nucor”) expressly disclaim (i) any and all representations, warranties and conditions, express or implied, related to the information in this product data sheet, including but not limited to warranties of merchantability, fitness for a particular purpose, and non-infringement; and (ii) any and all liability whatsoever arising out of or related to this product data sheet or its use, including but not limited to liability by reason of death, personal injury or damage to property.

NUCOR, VULCRAFT, VERCO, and FORMLOK are registered trademarks of Nucor. DRAMIX is a registered trademark of Bekaert.

VULCRAFT® 2.0D FORMLOK® COMPOSITE DECK-SLABWITH BEKAERT DRAMIX® STEEL FIBERS

WWW.DOVETAILDECK.COM3.5D BEKAERT | APRIL 2019

VULCRAFT® 3.5D FORMLOK® COMPOSITE DECK-SLAB

Normal Weight Concrete (145 pcf)

Total Slab

Depth(in.)

Theoretical Concrete Volume

(yd3/100 ft2)

Min. As for T&S(in.2)

Recommended Reinforcing for Temperature and Shrinkage

Bekaert Dramix® Steel Fibers Alternate to WWR (pcy)

WWR (OR) 3D 65/60BG 3D 80/60BG 4D 65/60BG4D 80/60BG or

5D 65/60BG

5½ 1.44 0.028 6x6-W1.4xW1.4 27 22 33 34

5¾ 1.52 0.028 6x6-W1.4xW1.4 25 16 33 34

6 1.60 0.028 6x6-W1.4xW1.4 22 14 33 34

6½ 1.75 0.028 6x6-W1.4xW1.4 19 14 33 34

7 1.91 0.032 6x6-W2.1xW2.1 18 14 33 34

7¼ 1.98 0.034 6x6-W2.1xW2.1 18 14 33 34

7½ 2.06 0.036 6x6-W2.1xW2.1 18 14 33 34

8 2.22 0.041 6x6-W2.1xW2.1 18 14 33 34

3.5D FORMLOK DECK-SLAB• 3½” Deep Composite Deck• f’c = 3000 psi (min.)• UL Fire Rated

WITH BEKAERT DRAMIX® STEEL FIBERS

Light Weight Concrete (110 pcf)

Total Slab

Depth(in.)

Theoretical Concrete Volume

(yd3/100 ft2)

Min. As for T&S(in.2)

Recommended Reinforcing for Temperature and Shrinkage

Bekaert Dramix® Steel Fibers Alternate to WWR (pcy)

WWR (OR) 3D 65/60BG 3D 80/60BG 4D 65/60BG4D 80/60BG or

5D 65/60BG

5½ 1.44 0.028 6x6-W1.4xW1.4 N/A 33 33 34

5¾ 1.52 0.028 6x6-W1.4xW1.4 34 30 33 34

6 1.60 0.028 6x6-W1.4xW1.4 30 27 33 34

6½ 1.75 0.028 6x6-W1.4xW1.4 23 24 33 34

7 1.91 0.032 6x6-W2.1xW2.1 22 23 33 34

7½ 2.06 0.036 6x6-W2.1xW2.1 22 23 33 34

8 2.22 0.041 6x6-W2.1xW2.1 22 23 33 34Notes: 1. Recommended WWR reinforcing is for minimum temperature and shrinkage per SDI‐C. Larger WWR may be required to comply with UL Fire Resistant Designs.2. FRC reinforcement is based on IAPMO UES ER-497 and ISO 17025 facility test data.3. Dramix® 4D 65/60BG, 4D 80/60BG and 5D 65/60BG should only be used when both required for diaphragm reinforcement and with minimum f’c= 4 ksi.4. Dramix® fibers may be used in UL or ULC fire rated assemblies in lieu of WWR. See UL file R13907 for additional information.5. For information on Bekaert Dramix® fibers contact 770-514-2295 or infobuilding@bekaert.com.

The information in this product data sheet is presented for general information only and is not to be used or relied upon for any application without independent verification by a professional engineer or other qualified professional. Nucor Corporation and its affiliates (collectively, “Nucor”) expressly disclaim (i) any and all representations, warranties and conditions, express or implied, related to the information in this product data sheet, including but not limited to warranties of merchantability, fitness for a particular purpose, and non-infringement; and (ii) any and all liability whatsoever arising out of or related to this product data sheet or its use, including but not limited to liability by reason of death, personal injury or damage to property.

NUCOR, VULCRAFT, VERCO, and FORMLOK are registered trademarks of Nucor. DRAMIX is a registered trademark of Bekaert.

WWW.VULCRAFT.COM1.5VL BEKAERT | APRIL 2019

VULCRAFT® 1.5VL / 1.5VLI / 1.5PVLI COMPOSITE DECK-SLAB

Normal Weight Concrete (145 pcf)

Total Slab

Depth(in.)

Theoretical Concrete Volume

(yd3/100 ft2)

Min. As for T&S(in.2)

Recommended Reinforcing for Temperature and Shrinkage

Bekaert Dramix® Steel Fibers Alternate to WWR (pcy)

WWR (OR) 3D 65/60BG 3D 80/60BG 4D 65/60BG4D 80/60BG or

5D 65/60BG

3½ 0.78 0.028 6x6-W1.4xW1.4 27 22 33 34

4 0.94 0.028 6x6-W1.4xW1.4 22 14 33 34

4½ 1.09 0.028 6x6-W1.4xW1.4 19 14 33 34

5 1.24 0.032 6x6-W2.1xW2.1 18 14 33 34

5½ 1.40 0.036 6x6-W2.1xW2.1 18 14 33 34

6 1.55 0.041 6x6-W2.1xW2.1 18 14 33 34

1.5VL / 1.5VLI / 1.5PLVI DECK-SLAB• 1½” Deep Composite Deck• f’c = 3000 psi (min.)• UL Fire Rated

WITH BEKAERT DRAMIX® STEEL FIBERS

Light Weight Concrete (110 pcf)

Total Slab

Depth(in.)

Theoretical Concrete Volume

(yd3/100 ft2)

Min. As for T&S(in.2)

Recommended Reinforcing for Temperature and Shrinkage

Bekaert Dramix® Steel Fibers Alternate to WWR (pcy)

WWR (OR) 3D 65/60BG 3D 80/60BG 4D 65/60BG4D 80/60BG or

5D 65/60BG

3½ 0.78 0.028 6x6-W1.4xW1.4 N/A 33 33 34

4 0.94 0.028 6x6-W1.4xW1.4 30 27 33 34

4½ 1.09 0.028 6x6-W1.4xW1.4 23 24 33 34

4¾ 1.17 0.029 6x6-W2.1xW2.1 22 23 33 34

5 1.24 0.032 6x6-W2.1xW2.1 22 23 33 34

5¾ 1.48 0.038 6x6-W2.1xW2.1 22 23 33 34Notes: 1. Recommended WWR reinforcing is for minimum temperature and shrinkage per SDI‐C. Larger WWR may be required to comply with UL Fire Resistant Designs.2. FRC reinforcement is based on IAPMO UES ER-497 and ISO 17025 facility test data.3. Dramix® 4D 65/60BG, 4D 80/60BG and 5D 65/60BG should only be used when both required for diaphragm reinforcement and with minimum f’c= 4 ksi.4. Dramix® fibers may be used in UL or ULC fire rated assemblies in lieu of WWR. See UL file R13907 for additional information.5. For information on Bekaert Dramix® fibers contact 770-514-2295 or infobuilding@bekaert.com.

The information in this product data sheet is presented for general information only and is not to be used or relied upon for any application without independent verification by a professional engineer or other qualified professional. Nucor Corporation and its affiliates (collectively, “Nucor”) expressly disclaim (i) any and all representations, warranties and conditions, express or implied, related to the information in this product data sheet, including but not limited to warranties of merchantability, fitness for a particular purpose, and non-infringement; and (ii) any and all liability whatsoever arising out of or related to this product data sheet or its use, including but not limited to liability by reason of death, personal injury or damage to property.

NUCOR, VULCRAFT, VERCO, and FORMLOK are registered trademarks of Nucor. DRAMIX is a registered trademark of Bekaert.

WWW.VULCRAFT.COM1.5VLR BEKAERT | APRIL 2019

VULCRAFT® 1.5VLR COMPOSITE DECK-SLAB

Normal Weight Concrete (145 pcf)

Total Slab

Depth(in.)

Theoretical Concrete Volume

(yd3/100 ft2)

Min. As for T&S(in.2)

Recommended Reinforcing for Temperature and Shrinkage

Bekaert Dramix® Steel Fibers Alternate to WWR (pcy)

WWR (OR) 3D 65/60BG 3D 80/60BG 4D 65/60BG4D 80/60BG or

5D 65/60BG

3½ 0.92 0.028 6x6-W1.4xW1.4 27 22 33 34

4 1.07 0.028 6x6-W1.4xW1.4 22 14 33 34

4½ 1.22 0.028 6x6-W1.4xW1.4 19 14 33 34

5 1.38 0.032 6x6-W2.1xW2.1 18 14 33 34

5½ 1.53 0.036 6x6-W2.1xW2.1 18 14 33 34

6 1.69 0.041 6x6-W2.1xW2.1 18 14 33 34

1.5VLR DECK-SLAB• 1½” Deep Composite Deck• f’c = 3000 psi (min.)• UL Fire Rated

WITH BEKAERT DRAMIX® STEEL FIBERS

Light Weight Concrete (110 pcf)

Total Slab

Depth(in.)

Theoretical Concrete Volume

(yd3/100 ft2)

Min. As for T&S(in.2)

Recommended Reinforcing for Temperature and Shrinkage

Bekaert Dramix® Steel Fibers Alternate to WWR (pcy)

WWR (OR) 3D 65/60BG 3D 80/60BG 4D 65/60BG4D 80/60BG or

5D 65/60BG

3½ 0.92 0.028 6x6-W1.4xW1.4 N/A 33 33 34

4 1.07 0.028 6x6-W1.4xW1.4 30 27 33 34

4½ 1.22 0.028 6x6-W1.4xW1.4 23 24 33 34

4¾ 1.30 0.029 6x6-W2.1xW2.1 22 23 33 34

5 1.38 0.032 6x6-W2.1xW2.1 22 23 33 34

5¾ 1.61 0.038 6x6-W2.1xW2.1 22 23 33 34Notes: 1. Recommended WWR reinforcing is for minimum temperature and shrinkage per SDI‐C. Larger WWR may be required to comply with UL Fire Resistant Designs.2. FRC reinforcement is based on IAPMO UES ER-497 and ISO 17025 facility test data.3. Dramix® 4D 65/60BG, 4D 80/60BG and 5D 65/60BG should only be used when both required for diaphragm reinforcement and with minimum f’c= 4 ksi.4. Dramix® fibers may be used in UL or ULC fire rated assemblies in lieu of WWR. See UL file R13907 for additional information.5. For information on Bekaert Dramix® fibers contact 770-514-2295 or infobuilding@bekaert.com.

The information in this product data sheet is presented for general information only and is not to be used or relied upon for any application without independent verification by a professional engineer or other qualified professional. Nucor Corporation and its affiliates (collectively, “Nucor”) expressly disclaim (i) any and all representations, warranties and conditions, express or implied, related to the information in this product data sheet, including but not limited to warranties of merchantability, fitness for a particular purpose, and non-infringement; and (ii) any and all liability whatsoever arising out of or related to this product data sheet or its use, including but not limited to liability by reason of death, personal injury or damage to property.

NUCOR, VULCRAFT, VERCO, and FORMLOK are registered trademarks of Nucor. DRAMIX is a registered trademark of Bekaert.

WWW.VULCRAFT.COM2VLI BEKAERT | APRIL 2019

VULCRAFT® 2VLI / 2PLVLI COMPOSITE DECK-SLAB

Normal Weight Concrete (145 pcf)

Total Slab

Depth(in.)

Theoretical Concrete Volume

(yd3/100 ft2)

Min. As for T&S(in.2)

Recommended Reinforcing for Temperature and Shrinkage

Bekaert Dramix® Steel Fibers Alternate to WWR (pcy)

WWR (OR) 3D 65/60BG 3D 80/60BG 4D 65/60BG4D 80/60BG or

5D 65/60BG

4 0.93 0.028 6x6-W1.4xW1.4 27 22 33 34

4½ 1.08 0.028 6x6-W1.4xW1.4 22 14 33 34

5 1.23 0.028 6x6-W1.4xW1.4 19 14 33 34

5½ 1.39 0.032 6x6-W2.1xW2.1 18 14 33 34

6 1.54 0.036 6x6-W2.1xW2.1 18 14 33 34

6½ 1.70 0.041 6x6-W2.1xW2.1 18 14 33 34

2VLI / 2PLVLI DECK-SLAB• 2” Deep Composite Deck• f’c = 3000 psi (min.)• UL Fire Rated

WITH BEKAERT DRAMIX® STEEL FIBERS

Light Weight Concrete (110 pcf)

Total Slab

Depth(in.)

Theoretical Concrete Volume

(yd3/100 ft2)

Min. As for T&S(in.2)

Recommended Reinforcing for Temperature and Shrinkage

Bekaert Dramix® Steel Fibers Alternate to WWR (pcy)

WWR (OR) 3D 65/60BG 3D 80/60BG 4D 65/60BG4D 80/60BG or

5D 65/60BG

4 0.93 0.028 6x6-W1.4xW1.4 N/A 33 33 34

4½ 1.08 0.028 6x6-W1.4xW1.4 30 27 33 34

5 1.23 0.028 6x6-W1.4xW1.4 23 24 33 34

5¼ 1.31 0.029 6x6-W2.1xW2.1 22 23 33 34

5½ 1.39 0.032 6x6-W2.1xW2.1 22 23 33 34

6¼ 1.62 0.038 6x6-W2.1xW2.1 22 23 33 34Notes: 1. Recommended WWR reinforcing is for minimum temperature and shrinkage per SDI‐C. Larger WWR may be required to comply with UL Fire Resistant Designs.2. FRC reinforcement is based on IAPMO UES ER-497 and ISO 17025 facility test data.3. Dramix® 4D 65/60BG, 4D 80/60BG and 5D 65/60BG should only be used when both required for diaphragm reinforcement and with minimum f’c= 4 ksi.4. Dramix® fibers may be used in UL or ULC fire rated assemblies in lieu of WWR. See UL file R13907 for additional information.5. For information on Bekaert Dramix® fibers contact 770-514-2295 or infobuilding@bekaert.com.

The information in this product data sheet is presented for general information only and is not to be used or relied upon for any application without independent verification by a professional engineer or other qualified professional. Nucor Corporation and its affiliates (collectively, “Nucor”) expressly disclaim (i) any and all representations, warranties and conditions, express or implied, related to the information in this product data sheet, including but not limited to warranties of merchantability, fitness for a particular purpose, and non-infringement; and (ii) any and all liability whatsoever arising out of or related to this product data sheet or its use, including but not limited to liability by reason of death, personal injury or damage to property.

NUCOR, VULCRAFT, VERCO, and FORMLOK are registered trademarks of Nucor. DRAMIX is a registered trademark of Bekaert.

WWW.VULCRAFT.COM3VLI BEKAERT | APRIL 2019

VULCRAFT® 3VLI / 3PLVLI COMPOSITE DECK-SLAB

Normal Weight Concrete (145 pcf)

Total Slab

Depth(in.)

Theoretical Concrete Volume

(yd3/100 ft2)

Min. As for T&S(in.2)

Recommended Reinforcing for Temperature and Shrinkage

Bekaert Dramix® Steel Fibers Alternate to WWR (pcy)

WWR (OR) 3D 65/60BG 3D 80/60BG 4D 65/60BG4D 80/60BG or

5D 65/60BG

5 1.08 0.028 6x6-W1.4xW1.4 27 22 33 34

5½ 1.23 0.028 6x6-W1.4xW1.4 22 14 33 34

6 1.39 0.028 6x6-W1.4xW1.4 19 14 33 34

6½ 1.54 0.032 6x6-W2.1xW2.1 18 14 33 34

7 1.70 0.036 6x6-W2.1xW2.1 18 14 33 34

7½ 1.85 0.041 6x6-W2.1xW2.1 18 14 33 34

3VLI / 3PLVLI DECK-SLAB• 3” Deep Composite Deck• f’c = 3000 psi (min.)• UL Fire Rated

WITH BEKAERT DRAMIX® STEEL FIBERS

Light Weight Concrete (110 pcf)

Total Slab

Depth(in.)

Theoretical Concrete Volume

(yd3/100 ft2)

Min. As for T&S(in.2)

Recommended Reinforcing for Temperature and Shrinkage

Bekaert Dramix® Steel Fibers Alternate to WWR (pcy)

WWR (OR) 3D 65/60BG 3D 80/60BG 4D 65/60BG4D 80/60BG or

5D 65/60BG

5 1.08 0.028 6x6-W1.4xW1.4 N/A 33 33 34

5½ 1.23 0.028 6x6-W1.4xW1.4 30 27 33 34

6 1.39 0.028 6x6-W1.4xW1.4 23 24 33 34

6¼ 1.47 0.029 6x6-W2.1xW2.1 22 23 33 34

6½ 1.54 0.032 6x6-W2.1xW2.1 22 23 33 34

7¼ 1.77 0.038 6x6-W2.1xW2.1 22 23 33 34Notes: 1. Recommended WWR reinforcing is for minimum temperature and shrinkage per SDI‐C. Larger WWR may be required to comply with UL Fire Resistant Designs.2. FRC reinforcement is based on IAPMO UES ER-497 and ISO 17025 facility test data.3. Dramix® 4D 65/60BG, 4D 80/60BG and 5D 65/60BG should only be used when both required for diaphragm reinforcement and with minimum f’c= 4 ksi.4. Dramix® fibers may be used in UL or ULC fire rated assemblies in lieu of WWR. See UL file R13907 for additional information.5. For information on Bekaert Dramix® fibers contact 770-514-2295 or infobuilding@bekaert.com.

The information in this product data sheet is presented for general information only and is not to be used or relied upon for any application without independent verification by a professional engineer or other qualified professional. Nucor Corporation and its affiliates (collectively, “Nucor”) expressly disclaim (i) any and all representations, warranties and conditions, express or implied, related to the information in this product data sheet, including but not limited to warranties of merchantability, fitness for a particular purpose, and non-infringement; and (ii) any and all liability whatsoever arising out of or related to this product data sheet or its use, including but not limited to liability by reason of death, personal injury or damage to property.

NUCOR, VULCRAFT, VERCO, and FORMLOK are registered trademarks of Nucor. DRAMIX is a registered trademark of Bekaert.