W. Mark McGinley, Ph. D., PEFASTM MASONRYSEMINAR …... · Vertical Expansion Joints in ClayMasonry...

Post on 17-Aug-2020

1 views 0 download

transcript

J.B

.SPE

EDSC

HO

OL

OF

ENG

INEE

RIN

G

1

High Performance Exterior Masonry Wall Design and

Detailing for Water Resistance, Thermal Control

and Crack Control

MASONRY SEMINARMasonry Institute of Iowa

Thursday, March 2, 2017

W. Mark McGinley, Ph. D., PE FASTM

IntroductionThe presentation will address the following learning objectives:• Describe the functions of exterior wall

systems and discuss their behavior as it relates to their function as a building envelope. Address moisture, air, vapor and vapor and thermal barriers.

• Present fault tolerant masonry detailing for moisture penetration, vapor transmission, etc

2

Introduction• Present an overview of masonry crack

control and detailing for differential movements.

• Discuss thermal resistance, U and R values and thermal mass effects on energy use in walls systems.

• Present a number of “high” performanceexterior masonry wall configurations andcosts.

3

Exterior Wall SystemsFunctions

• Resist loads• Control movement of air• Control movement of

moisture (and vapor)• Control thermal movements• Control sound• Control fire – Masonry does

so inherently• Others

Must do so in a aesthetically pleasing, durable,cost effective manner 4

Drainage Walls – Moisture Resistance

5

Single wythes ofmasonry can leak

Drainage Walls

OTHER TYPE BARRIER WALLAll Single wythe

To be effective moisture barrier must detail forFault Tolerance at Critical Locations

Extend flashing on sill up behind window

Make Cavity at least 2 in – Free to allow for tolerance and mortar fins-code – 1” Consider Extending flashing to shelf angle instead under sill brick –short heights –BIA.org -

Positively Anchor Sill

6

7

Show and detail end dams where needed

Step flashing down

7

Design for Fault Tolerance

at Critical Locations

Design for Fault Tolerance atCritical Locations

Stainless steel edge 8

Detail and show how to attached flashing to backing system

Extend flashing or you likely have brick staining

If you don’t like drip edge look Alternative way to provide this

PermaBarrier

more later

Be Careful Using Standard Details

PoorWet Bat. insulation

9

This is what can be built if you are not careful with details

1010

Back to Envelope Function: Thermal/Air MovementsThree major mechanisms of thermal energy loss/gain through exterior wall systems:

- Conduction– Radiation- Convection

Lump these into an overall heat transfer coefficient U - See earlier talk - more later

Note R= 1/U11

Thermal Resistance

For conductive Thermal movements -Do one of:

a) Meet prescriptive R , U values in Energy code

b) Do a detailed energy analysis (LEED)

c) Comply with ASHREA 90.1 – Prescriptive& Detailed analysis

See my earlier Talk

12

Thermal/Air MovementsAlso a significant amount of heat energy can move through wall systems via air movement in the wall systems. –up to 30%?

So ASHREA 90.1- IBC –Bldgs. must have an air barrier and it must be continuous – JOINTS & PENETRATIONS ARE VERYIMPORTANT – Must be flexible &strong enough to resist pressures.

13

ASHREA 90.1 Walls – (Not windows or doors)can be air barriers if they:

(a)Have materials that have an air permeance not exceeding 0.004 cfm/ft2 under a pressure differential of 0.3” w.g. (1.57psf) OR

(b) Assemblies that have average air leakage not toexceed 0.04 cfm/ft2 under a pressure differential of 0.3”w.g. (1.57psf). OR

(c) Building demonstrates air leakage rates of ≤ 0.40cfm/ft2 at a pressure differential of 0.3” w.g. (1.57 psf)(2.0 L/s.m2 @ 75 Pa)

Exception: Buildings in Zones 1, 2, and 3 constructed with mass walls are exempt.

14

Vapor ControlWater vapor moves from high to lowvapor pressure: Temp and RH relateda) Put vapor barrier on warm side of

insulation when cooling degree days are greater than heating degree days andhave a vapor permeable Air/moisture barrier.

b) In mixed climates and some wall systems its hard to find warm side- Do not have two vapor retarders!

c) Some times better to have no vapor barrier. Know condensation point!

15

Movements in Clay MasonryMovements are produced by:• Thermal differences• Shrinkage• Moisture Expansion• Elastic- deformation both of the masonry

and any supporting structural systems• Creep• Foundation Settlements

See BIA Tech Notes 18 and 18A and NCMATEK Notes 10-1A , 10-2A, 10-3

Movements of Clay Masonry Assemblies Irreversible Moisture

Expansion

Brick are the smallest when cooled from the kiln. Expansion ranges from 0.0002 to 0.0009 in/in Codes gives ke= 0.0003 in/in.

17

18

Control of Movements of Clay Masonry Assemblies (WALLS)

Clay masonry wall panels generally expand if unrestrained.

There is usually no problem in these wallsif they are allowed to move freely.

However, rarely are these wallsunrestrained unless properly detailed.

Control of Movements of ClayMasonry Assemblies (WALLS)

Clay masonry can expand significantlyBenson Conv.Sealant

forced out

19

20

Control of Movements of Clay Masonry Walls

There is two ways in which the designer can deal with this expansion:1. Design the masonry and surroundingelements to resist the stress induced

by the restrained masonry. TECHNote 182. Design the systems so that masonrycan move freely. See TECH Note 18A

21

Expansion Joints in Clay MasonryThe primary function of this joint is allow free expansion of the masonry but must also resists water penetration and air movement

Note that expansion joints and control joints not the same

BIA Tech note 18A Vertical Expansion Joints

Note that most sealants require a backer rod and the sealant depth should be about ½ the width of the joint (min ¼”) – Types include urethanes, silicones, polysulfides.

22

Expansion Joints Clay Masonry

23

Vertical Expansion Joints in Clay Masonry

A conservative estimate of verticalexpansion joint spacing, Se, can be madeusing wej

e (ke k f kt t)100S

w = is the width of the joint (in)

ej = the extensibility of the sealant (%)

Tech note 18 and 18 A suggest equation above can be reduced to

0.09j

e

weS

Vertical Expansion Joints inClay Masonry

For Example: for a 50% sealant, 3/8” joint, and 3/8” joint with the simplified equation:

Se = 17’-4”

½” joint would have a spacing of 23’- 2”

25

Placement - Vertical Expansion Joints- Clay Masonry

Consideration should be given for vertical expansion joints at:Corners Offsets OpeningsWall intersections Changes in wall heights Parapets

26

Placement of Vertical Expansion Jointsin Clay Masonry

Corners Place jointsnear corner or cracks will developBIATechNote 18A

27

Placement of Vertical ExpansionJoints in Clay Masonry

Walls do moveFoundation was bonded to wall and went with movementFlashing canstop this

Corner opening cracks

Placement of Vertical Expansion Joints in Clay Masonry

29

You even get this with opening near the corner

Shalimar

Not an expansion joint just caulk

Placement of Vertical ExpansionJoints in Clay Masonry

30

Be careful with support at corners

Backing wall

Must have at least two ties on each Leg of column cover

Placement of Vertical ExpansionJoints in Clay Masonry

31

OffsetsThis is sort of acorner and an offset movementBenton Cov.

Placement of Vertical Expansion Joints in Clay Masonry

32

Placement of Vertical ExpansionJoints in Clay Masonry

Openings

No expansion joint creates crack as shown (TMS)These arenot due tosettlement(up) Sections with openings

move less and providerestraint to upper portions

33

Placement of Vertical Expansion Joints in Clay Masonry

Placement of Vertical Expansion Joints in Clay Masonry

Openings

There are openings above and below and a solid section between the edge column section is connected to both and creates distress due to differential movement

34

Placement of Vertical Expansion Joints in Clay Masonry

Openings

You should place a vertical expansion joint atopening edges - note if a loose angle is used it must be allowed to expand independent of brick - note min 4”bearing length of angleNeed to put on both sides if large opening or lintel supported on backing

35

36

Placement of Vertical Expansion Joints in Clay Masonry

Intersections and junctions

You should place a vertical expansion joint at changes in heights, thickness an types of walls and on walls that undergo differential warming

3

Placement of Vertical Expansion Joints in Clay Masonry

The parapet wall is exposed on three sidesand usually moves more than other walls. Also a parapet has much less dead load restraint.The usual rule of thumb is reduce thespacing of vertical expansion joints inparapet to ½ elsewhere.

7

38

Placement of Vertical ExpansionJoints in Clay Masonry

Hidden jointscan

improve Aesthetics

Horizontal Expansion Joints inClay Masonry

Brick moves up

Frame shortens

Horizontal expansion joints typically placed below shelf angles

They should be sized for the masonry and frame movements

Ensures Masonry Non loadbearing39

Note that the total joint size must include the angle thickness and it will be very difficult to get a 3/8” thickness

40

The space below the shelf angle must be free to move and is the critical dimension for the joint size

Horizontal Expansion Joints in Clay Masonry

41

Can hide the joint with lipped brick – BUT THESE CAN CHIP BADLY

What’s wrong withthis detail?

Placement of HorizontalExpansion Joints in Clay Masonry

42

Problems – Closed mortar joints - Harbor

Placement of Horizontal Expansion Joints in Clay Masonry

Popped out –no ties

Crackedaway

43

Problems – Closed mortar joints – BentonConv

Placement of Horizontal Expansion Joints in Clay Masonry

Spalled Faces

44

Shrinkage (contraction)Control in Concrete MasonryUsually shrinkage in concrete masonry only a problem if restrained - NCMA Tek 10-1A, 10-2C, 10-3.

45

Control joints - creates a weakness in the masonry wall and allows thecracks to form in the joint NCMA Tek Note 10-2A

46

Control joints - BOND BEAMS – need specialdetailing

47

Control Joints in ConcreteMasonry

Use control joints with a minimum amount of reinforcing shown in Table 1 of NCMA Tek 10-2 C - based on experience may be adjusted

48

Control Joints in Concrete Masonry Placement NCMA Tek Note 10-2A

49

Some Other ConsiderationsDifferential Movements of Masonry andthe structure can be an issue:•Don’t rigidly connect masonry that is supported on the structure to masonry that is supported on the ground.•Allow the exterior wythe of masonry tomove independently.•Use adjustable ties with enough travel

50

Ties

51

Some Other Considerations

Differential Movements of different masonry elements is an issue:

Be careful of movement of different color, and or types of masonry, they move differently

Also separate load bearing andnon load bearing walls

52

Some Other ConsiderationsConcrete block and brick - different color

53

Some Other Considerations

Had controljoints but too farapart.

No cracking in dark CMU but cracking in lighter CMU

54

Some Other Considerations

Separate dissimilar materials

55

Some Other ConsiderationsCoping is very important ( joints need sealing)

Movement of outer wythe will add up and be the worst at copingMay pop the coping and or roll over the parapet Recommend a flexible coping or expansion joint & TWF

56

Some Other ConsiderationsDETAILS – DETAILS – DETAILSVery important that joints go through all systems

High Performance Masonry Walls?

57

58

NCMA- TEK 6-1B

ICF From WebMasonry Cavity Wall

I was asked a while back whether you can design a high performance masonry wall – Like ICF

The answer is yes !!!!!

. Data from Sherman Carter Barnhart –Architects

Typical ICF system – R 23 –has an integral Air/moisture and vapor barrier – also structural

~ $31.4/SF (KY-values)

Note - This is 16”+ thick wall

If this ICF Wall defines high performance Can a masonry wall be designed to perform similarly?

YES 59

.Try rigid insulation board in the cavity – Initially assume polyisocyanurate 3”Note the R value ranges from 24.3 to about 25.8 depending on the density of the materials and the temperature in the air spaceThe air/vapor barrier on the masonry wall can be achieved by a spray-on mastic or trowel-on material behind the insulationOr – use foil faced insulation and taped seams – note that R value goes up to 25.8 to 28.3 with the foil facing in cavity.

R-Value =24.3

Spray or trowel-on air barrier or seal insulation seams

60

8-in. concrete masonry backup wythe, grouted48 in. o.c. vertically and 12 ft o.c. horizontally

3 in. polyisocyanuraterigid board insulation1 in. airspace4-in. clay brick veneer

Point- the insulation, air barrier, vapor barrier and moisture barrier protectedin cavity

. Try more conventional rigid insulation board in the cavity –Say assume 3.5”polyurethane, R~22

Note if 3” of insulation is used R value ranges from 18.7 to about19.8 depending on the density ofthe materials and the

The air barrier on the masonry wall can be achieved by a spray on mastic behind the insulation or tape/seal seams.

Spray on mastic will also formwater/vapor barrier.

312 in. extruded polystyrene temperature in the air space

rigid board insulation

8-in. concrete masonrybackup wythe, grouted48 in. o.c. vertically and12 ft o.c. horizontally

1 in. airspace4-in. clay brick veneer

R-Value =21.7PossibleSpray or trowel-on barrier

61

Point- the insulation, air barrier, vapor barrier and moisture barrier protectedin cavity

. OR - Try spray on closed cell Polyurethane foam Insulation

62

Spray foam forms Moisture/Air/Vapor Barriers- Joints critical – Inspection by AABA certified individuals- (BASF-walltite)

63

.Try 3” of spray foam insulation in the cavity – R-6.8/inch

Note if 3” of insulation is used R value ranges from 23.4 to about25.7 depending on the density of the materials and the temperature in the air space

The air/moisture/vapor barrier on the masonry wall is integrally contained in the insulation system

8-in. concrete masonry backup wythe, grouted 48 in. o.c. vertically and 12 ft o.c. horizontally

3 in. spray polyurethane foaminsulation1 in. airspace

4-in. clay brickveneer

R-Value = 23.4

64

SUS.TAINABLE DESIGN “DOING MORE WITH LESS”– OR AT LEAST DOING THE SAME WITH LESS Perhaps most effective walls have R 14 to 15 – (colder climates R)

R-Value =14.2

8-in. concrete masonry backup wythe, grouted 48 in. o.c. vertically and 12 ft o.c. horizontally

2 in. extruded polystyrene rigid board insulation1 in. airspace4-in. clay brick veneer

R-Value = 15.1

8-in. concrete masonry backup wythe, grouted 48 in. o.c. vertically and 12 ft o.c. horizontally

1.5 in. polyisocyanurate rigid board insulation1 in. airspace

4-in. clay brick veneer65

R-Value = 14.2

48 in. o.c. vertically and 12 ft o.c. horizontally

2 in. extruded polystyrene rigid board insulation1 in. airspace4-in. clay brick veneer

Thermal massStudies at ORNL and elsewhere have shown the best performance in mass walls is obtained by putting the mass on the interior of the insulation

The mass on theinterior of insulation and exposed to regulated temp helps mitigate interior temp variations and shifts peak loading – saves energy and peak

8-in. concrete masonry shaves –possiblebackup wythe, grouted thermal storage use

Insulating mass from interior allows internal loads to spike temps and reduces effect of mass –up to 5% 66

Cost of this wall isapproximately :

$28.50/ft2 to 30.6/ft2 (KY values) Based on prevailing wages with spray-on air barrier

8-in. concrete masonry backup wythe, grouted48 in. o.c. vertically and12 ft o.c. horizontally

3 in. polyisocyanurate rigid board insulation1 in. airspace

4-in. clay brick veneer

R-Value =24.3

.Wall Costs

67

312 in. extruded polystyrene

rigid board insulation 1 in. airspace

8-in. concrete masonry backup wythe, grouted 48 in. o.c. vertically and 12 ft o.c. horizontally

4-in. clay brick veneer

. R-Value =21.7 PossibleSpray ortroweledbarrier

Cost of this wall is approximately about the same

$28.50/ft2 to 30.0/ft2

(KY Values)Based on prevailing wages with spray-on air barrier

Remember ICF Cost~$31.4/ft2

68

.Try 3” of spray foam insulation in the cavity – R-6.8/inch

Cost of moisture/air barrier is about ~$1.10/ft2 and the cost of the 3” polyiso. insulation ~

2$2.50/ft so

Spray insulation this is aboutthe same cost as the polyiso.foil faced board.

8-in. concrete masonry backup wythe, grouted 48 in. o.c. vertically and 12 ft o.c. horizontally

3 in. spray polyurethane foaminsulation1 in. airspace

4-in. clay brickveneer

R-Value =23.4

Cost of Spay insulation – General valuesf 1.0 inches = R- 6.3 Budget $1.80/sq.ft.

1.5 inches = R- 9.45 Budget $2.20/sq.ft.2.0 inches = R-12.60 Budget $2.80/sq.ft.2.5 inches = R-15.75 Budget $3.40/sq.ft3.0 inches = R-18.90 Budget $4.00/sq.ft

With joint sealing and opening flashing– about $4- 6/ft2

69

R-Value = 14.2

8-in. concrete masonry backup wythe, grouted 48 in. o.c. vertically and 12 ft o.c. horizontally

2 in. extruded polystyrene rigid board insulation1 in. airspace4-in. clay brick veneer

.Wall CostsMore conventional configurationshould be closer to about$28.5/ft2 - $29 (KY Values)

70

J.B

.SPE

EDSC

HO

OL

OF

ENG

INEE

RIN

G

THANK YOU !

QUESTIONS?

71