WeLightS+

Post on 23-Mar-2016

212 views 0 download

Tags:

description

WeLightS+ datasheet english

transcript

Period of return on investment (ROI) Power ROI 15KVA 1,091 year 20KVA 0,97 year 25KVA 0,83 year 30KVA 0,65 year 45KVA 0,5 year 60KVA 0,47 year

INPUT Voltage: 3x380V-400V-415V Tolerance: +15, -6% Operating frequency: 48÷63 Hz Protection: breaker phase unipolar

OUTPUT Voltage: 3x380V-400V Starting voltage lamps: programmable (205V/210V) Reduced voltage switch selectable:185V-190V-195V-200V Reduced voltage selectable through remote management:180÷215V Accuracy of output voltage: <±2% Regulation: phase-independent Harmonic distortion: none

ENVIRONMENTAL Enviromental temperatureMaximum altitude: Reduce each 500m 2.5% excess power useTemperature Range: -40o÷60oC; Ambient humidity: 0 to 97% noncondensing Cooling: natural or forced air

REGULATIONS Standards applied:• Electromagnetic compatibility: UNE EN-61000 • Manufacturing ISO 9001; Marked: CE • Certificate: TÜV • Designed in accordance with the regulations: EA0032, EA0033

ENCLOSURES Degree of Protection: • IP-44 outdoor usage• IP-20 in panel (installation instructions)

BY- PASS Solid-state phase-independentTransient over-current: 200% 240 “ Imbalance between phases: : up to 100%

VOLTMETER Between phases and neutral switch selectable

POWERS Three phase to 120kVASingle phase up to 40kVA