Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 1 of 32
Basics of IDEAL Industries 800 Series Power Analyzer
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 2 of 32
Objective of Demo
• Gain a understanding of the Analyzer and Software.– Interactive or real time measurements– Setting up for Data logging – Download of data and Software
• This presentation was done using a hair dryer as a load, and a line splitter with a standard DMM test lead set for quick and easy set-up. This was done for demonstration purposes to get familiar with the analyzer before attaching analyzer to an unknown circuit. (Hair dryer is not in Demo Case)
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 3 of 32
Simple Set-up To For Learning the IDEAL
Analyzer. • Attach the Black lead to N
input and the Red lead to the VL1 input of the analyzer.
• Connect the leads to the 2 test point holes on the line splitter, and plug splitter in to a 120V receptacle.
• Attach one of the clamps to the IL1, then clamp around the x10 loop of the line splitter.
• Use a hair drier as a load.
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 4 of 32
Interactive Operation
• First, the analyzer may be used in an interactive or real time mode– The interactive functions do not
hinder the performance of the analyzer mode of operation
– To begin Lets make Sure that the Analyzers is not taking “storing” data.
– You should see STOP in the lower left corner of the display
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 5 of 32
Interactive Operation
• Table Display Mode– Turn on unit and observe
Display– After a few moments
you should see on the analyzer the Table Display
• Note Measurement– Vp-n– A– KW– etc
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 6 of 32
Interactive Operation
• Large Display Mode– Press ESC– Note the reading on
the display– This display can be
configured to read any three values that the analyzer can measure
– Press Enter
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 7 of 32
Interactive Operation
• To make changes to the display you must de-select the measurement you don’t desire – Use arrow keys to Identify
measurement and press SET to select (On) or de-select(Off)
• Remember only three can be selected, so to start, you must first de-select at least one
– Press Enter to return to Large display screen
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 8 of 32
Interactive Operation
• BAR Graph Mode– Press ESC
– Note the reading on the display
– This display can be configured to read any of the three phase measurements on the analyzer
– Press Enter
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 9 of 32
Interactive Operation
• Use the Up and Down Arrow key to select your desired function {Vp-p, Vp-n, A, KW etc.} – In this example
Select A for amperes
– Enter
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 10 of 32
Interactive Operation
• Set graph ZERO value to the desired value– For example set ZERO value to 0 – Use arrow keys and the SET key to select Value
on key pad in the bottom right of screen
• Set graph Full Scale value to the desired value– For example, set Full Scale value to 130– Use arrow keys and the SET key to select Value
on key pad in the bottom right of screen.
• Return to Bar Graph display and note changes
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 11 of 32
Interactive Operation
• Waveform Display– Note the display– Phase Values are to the
left of screen– Adq is hi-lited
• Press enter to acquire new waveform data
– Use the arrow keys to select a phase measurement
– Example: A L1– Press enter
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 12 of 32
Interactive Operation
• Waveform Zoom– Note display
– Use left & right arrow keys to move cursor across waveform
– Note cursor data reading
– Press Enter
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 13 of 32
Interactive Operation
• Harmonics Bar Graph display– Note Display
reading
– Use left and right arrow keys to move between harmonics
– Note changes in the reading
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 14 of 32
Power Analyzer setup
• This screen shows how the analyzer is set up– Right screen
defines setup perimeters
– Left screen is how this analyzer is set up Setup PerimetersAnalyzer Setup
Analyzer Setup screen
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 15 of 32
Before you Begin• Initial Considerations 61-805 Unit Set-up
– Set run/stop to STOP– Check Files– Clear ENERGY value– Clear Maximum & Minimum values– Check or Set Time and Date– Name of file with desired file type
• It is a good idea to delete all files to have maximum memory available.
• Check to make sure that any files in analyzers have been transferred or backup to the Power Provision software supplied with analyzer
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 16 of 32
Menus of the AnalyzerSETUP MAIN Menu
DISPLAY < OPTIONS / CONTRASTRUN < RUN / STOP
FILES < DIR / DELETE / FORMATCLEAR < ENERGY / MAX MIN
SETUP sub-SETUP MenusMEASURE MEASURE < MEASURE MenuRECORD CIRCUIT < Three Phase or AronCOMM TR.REL < C.T. and V.T ratiosCLOCK RECALL RECORD < RECORD Menu
PERIOD < hh:mm:ss (1s to 4hrs)TRIGGER < Level or Time
NAME < File Name (8 chars)TYPE < Standard or Special
PARAM < Special file parameters
COMM < Baud/Parity/Bits/sBits
CLOCK < dd/mm/yy hh:mm:ss
RECALL < RECALL STANDARDRecalls std Setup <yes> <no>
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 17 of 32
Unit Setup-Password
• Setup Menu– Press SET
– Enter Password
• [<] [SET] [^] [SET]
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 18 of 32
Unit Setup- Run/Stop & Clear
• From Main Menu select RUN- Press enter– Use arrow keys to select
Stop- press enter– Esc or arrow back to
Main Menu
• Select CLEAR-press enter– Select energy and clear– Select MAX MIN and
clear– Esc or arrow back to
Main Menu
SETUP MAIN MenuDISPLAY < OPTIONS / CONTRAST
RUN < RUN / STOPFILES < DIR / DELETE / FORMATCLEAR < ENERGY / MAX MIN
SETUP MAIN MenuDISPLAY < OPTIONS / CONTRAST
RUN < RUN / STOPFILES < DIR / DELETE / FORMATCLEAR < ENERGY / MAX MIN
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 19 of 32
Unit Setup-Period & Trigger
• ESC or Arrow key back to RECORD Menu
• Select PERIOD – Press enter – Set the period from 15
minutes {default is 00:15:00} to 1 minute [ 00:01:00 ]
– Record may also be triggered by level or time.
– Set Trigger to Auto
SETUP MAIN MenuDISPLAY < OPTIONS / CONTRAST
RUN < RUN / STOPFILES < DIR / DELETE / FORMATCLEAR < ENERGY / MAX MIN
SETUPMEASURERECORDCOMMCLOCKRECALL
RECORD < RECORD MenuPERIOD < hh:mm:ss (1s to 4hrs)
TRIGGER < Level or TimeNAME < File Name (8 chars)TYPE < Standard or Special
PARAM < Special file parameters
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 20 of 32
Unit Setup- File Name
• ESC or Arrow key back to RECORD Menu
• Select NAME – Press enter– Use the arrow keys to
move around the keyboard on screen
– Use set to enter each character (8 chars max)
– Press enter – Esc or arrow back to
SETUP Menu
SETUPMEASURERECORDCOMMCLOCKRECALL
RECORD < RECORD MenuPERIOD < hh:mm:ss (1s to 4hrs)
TRIGGER < Level or TimeNAME < File Name (8 chars)TYPE < Standard or Special
PARAM < Special file parameters
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 21 of 32
Unit Setup-Clock
• From the SETUP Menu select CLOCK – Press enter – Set Date as shown
• Date / Month/ Year
• dd/mm/yy
– Set Time as shown
• hours:minutes:seconds
• hh:mm:ss
SETUP MAIN MenuDISPLAY < OPTIONS / CONTRAST
RUN < RUN / STOPFILES < DIR / DELETE / FORMATCLEAR < ENERGY / MAX MIN
SETUPMEASURERECORDCOMMCLOCKRECALL
CLOCK < dd/mm/yy hh:mm:ss
Not necessary each time unit is set up
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 22 of 32
Unit Setup- Current Clamps• From Main Menu select
SETUP - Press enter• From Setup Menu select
MEASURE - Press Enter• In Measure Menu select
TR.REL - Press Enter – REL. A Primary CT value
{ CPR-1000 ratio is 1000A/2V, set to [ 1000 ]}
– REL.V Primary and Secondary voltage values should be set to 1
• “Do Not Change”
SETUP MAIN MenuDISPLAY < OPTIONS / CONTRAST
RUN < RUN / STOPFILES < DIR / DELETE / FORMATCLEAR < ENERGY / MAX MIN
SETUPMEASURERECORDCOMMCLOCKRECALL
sub-SETUP MenusMEASURE < MEASURE Menu
CIRCUIT < Three Phase or AronTR.REL < C.T. and V.T ratios
Not necessary each time unit is set up
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 23 of 32
Analyzer Setup screen
• Check the Analyzer setup for desired configuration– Check ratios:– Check Filename : – Check recording
parameters– Check Trigger: Setup PerimetersAnalyzer Setup
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 24 of 32
Before you Begin
• Make your phase to phase connections
• Confirm proper connection of analyzer to {L1,L2,L3}
• Check KW readings• Should not have
negative power
– Set run/stop to Run {When you are ready to start}
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 25 of 32
Software
• Insure the analyzer power communication cable is connected to the power interface adapter and the adapter is plugged in
• Insure serial cable is connected to the power interface adapter and your computer
• Connect analyzer power/interface adapter to the analyzer and adapter. – Use only the cables supplied with analyzer
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 26 of 32
Software
• Short Cut Icons– Energy
• Graphs energy data– Data Chart
• Graphs any stored data– Communication
• Sets device perimeters– Config Com
• Sets device port – Export Data
• Export read data file to be used by other applications
– Read Power Analyzer• Reads data file from
analyzer
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 27 of 32
Software
• Before you begin, make sure your software matches your Analyzers communication setting.
• To view analyzers setting, go to the SETUP screen last sections
• Example:Com: 9600 /no/8/1
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 28 of 32
Software
• Next is the proper setting of your COM port.
• If you aren’t sure check through Windows Control Panel which port is available.
• In this example:COM1– The modem was on
com2
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 29 of 32
Software
• Power Vision software was designed to make it easy to convert data taken by the analyzer and present it in easy to understand Table or graphical format.
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 30 of 32
Software
• Table Data
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 31 of 32
Software
• Graph Data
Intro To Ideal 800 Power Analyzer© 2007 Ideal Industries www.idealindustries.com 32 of 32
Software
• Harmonics