Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 1 of 40
Understanding Power Quality Monitoring
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 2 of 40
Objectives
• What is Power Quality and how do we determine Methods of test. – Describe the nature of several different types of
power-related problems.– Describe the methods for testing for the
different types of problems.
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 3 of 40
What is Power Quality
Except for complete failure, most really don’t pay close attention to the power we are supplied.
With the emergence of the “Electronics Age” there has be a change in the requirement of our electrical distribution systems.
Unlike traditional load, like lighting or motors, Sensitive loads are more susceptible to power disturbances.
Electronic equipment requires a much more stable power source.
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 4 of 40
Importance of Power Quality
• Consequences of poor Power Quality can result in:– Lost productivity
– Lost/corrupt data
– Damaged equipment
– Poor power efficiency
• U.S. companies waste an estimated $26 billion on electrical power-related issues each year*
*Electrical Contractor Magazine, “Surveying Power Quality Options”
March 2000
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 5 of 40
Power Quality
• There is no absolute definition of power quality, but many define it as the degree to which both the utilization and the performance of electric power affects the performance of an electrical distribution system.
• Organizations such as the IEEE -Institute of Electrical and Electronics Engineer and ANSI -American National Standards Institute are setting Stringent requirements for power Quality.– IEEE 519-81 Recommended limits on Harmonics
– ANSI C84.1 Specification on normal voltage ratings and tolerances
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 6 of 40
Power Quality
• Power and Power Factor– Measure of how efficiently Power is used
• Disturbances– Momentary disruptions to the Electrical system
• Harmonics– Integers of the Fundamental Frequency which have an
effect on the electrical systems and loads
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 7 of 40
Power Quality
• Power is measured in KW or Kilowatts• Kilowatt is defined as Volts x Amps x Cos Φ
– Φ is the phase angle difference between the Voltage and current.
Power And Power Factor
Most utilities have an additional charge
if PF is less than .95 to .90
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 8 of 40
Power Quality
• The NIST -National Institute of Standards and Technology shows that disturbances can be defined in two categories,
• Steady State or Intermittent. – Steady state disturbances are Noise, Harmonics, long
term Over-voltage or Under-voltage conditions.
– Intermittent disturbances are Sages, Swells, Impulse, Transients, and interruption,
Disturbances
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 9 of 40
Power Quality
– Voltage Sags and Swells– Under-voltage or Over-voltage– Transients spikes, impulses and surges– Outages– Harmonics– Noise
Power disturbances
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 10 of 40
• Voltage Sag– Momentary decrease in line Voltage
– Caused by the start of heavy loads or fault occurrence on source.
• Voltage Swells–Momentary increase in line Voltage
–Occurs due to sudden load decrease or de-energizing of heavy equipment.
Power Quality
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 11 of 40
Power Quality
• Over-Voltage– Abnormally high voltage
– Power voltage regulation
• Under-Voltage– Abnormally low Voltage
– Result for clearing of a fault or intentional utility regulation.
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 12 of 40
Power Quality
• Impulse (Transients): – Short duration high
amplitude pulses are surges that are superimposed on a normal voltage waveform.
– Vary widely from twice the normal voltage to several thousand volts in time from < microsecond to a few hundreds of a second.
– Result for loads cycling on and off in a building, utility, or lighting
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 13 of 40
Power Quality
• Outages– Outage is a complete loss
of power lasting from a few milliseconds to several hours.
– Caused by power system failure due to damage to supply lines or equipment failure
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 14 of 40
• NOISE: is an unwanted signal or distortion that is superimposed on a normal voltage waveform– Normal Mode noise
– Common Mode noise
– RFI: Radio Frequency interference
– EMI: Electromagnetic interference
Power Quality
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 15 of 40
Power Quality
• Harmonics are multiple of the fundamental frequency
• For us in the USA this is 60 Hz– Harmonics in our electrical
systems are normally caused by distortion of either our Voltage or Current waveform
– Major cause of harmonics is electronic loads that draw there currents in short pulses.
Harmonics
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 16 of 40
Power Quality
• Non-Linear loads
– Computers, printer, copiers, electronics lighting
– Adjustable speed drives and other microprocessor controlled equipment
– Effects on electrical systems or odd harmonics 3rd, 5th, 7th etc.
Harmonics
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 17 of 40
Harmonics
• Total Harmonic Distortion – Expressed as %THD
– Percentage of distortion to the sine wave
– Should not exceed 5% of line voltage or 20% of current
• Harmonic FFT’s– Breakdown of the THD to the individual harmonics
– Show the amount of harmonic as a percentage of the fundamental.
Knowing each harmonic and its effect can help in determines
the impact on the system
Harmonics
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 18 of 40
Power Quality- Standards
• ITIC, Information Technology Industry Council is just one of may professional or governing agency that have adopted acceptable tolerance for power delivered to our sensitive electronic equipment.
ITIC (CBEMA) Curve
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 19 of 40
Plan, Investigate & Test
• Where to start – Plan your site survey
– Investigate suspected areas
– Test or monitor
– Analyze results or date
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 20 of 40
Plan
Make a block diagram of you facility.
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 21 of 40
Investigate
• Investigate suspected areas
• Try to establish time of occurrence and duration history
• Equipment usage cycles or new equipment instillation
• Personnel
• Interview others- Find out what they have observed
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 22 of 40
Test
• Power and Power Factor, Inductive or Capacitive reactance, or how efficient we use the power that is delivered. – A Power Analyzer is the tool of choose when the measurement
of Power usage are efficiency is desired.• Disturbances, like Sage Swell and Impulse are
normally generated within a facility and affecting our sensitive electronics equipment – In the pass Power analyzers my have been used at a main or sub-
panel, but were not cost effective for branch circuit monitoring.– Today, however we have a small inexpensive tools that can be
plug at the device or equipment that is being effected.
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 23 of 40
• Most power quality failures may be tracked down to one of three areas. – Supply- Utilities and its distribution. – Internal Distribution- Feeders and Branches,
Grounding, wiring and termination– Internal Loads- load disturbances and
Harmonics
Testing
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 24 of 40
Testing
• Supply Disturbances and service area – Utility faults,
• switching transients, regulation
– Lighting, • Transients, outages
– Accidents to Transmission lines
• outages
– Failure of backup sources• Outage, under of over
voltages
Supply – Utilities Disturbance
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 25 of 40
Testing
• Many studies have been conducted and found that 80% of power Quality problems are generated within a facility
• Of this, 80% of those are related to inadequate wiring or poor grounding.
• Power and Power reactance.• Line to Neutral Voltage
– Sags& Swells, under-voltage & over-voltage, Impulse, Distortion.
• Neutral to Ground Voltage– High resistance grounds, Load imbalance, Harmonics
Internal Disturbances
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 26 of 40
Testing
• A Hospital is wanting to add new diagnostic equipment.
• Before the equipment is added to the service they need to determine if the present system can handle the additional load.
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 27 of 40
Testing
• This is an example of data taking at a hospital in North Carolina. Two observation can be made from this data.
– First, is a drop in Voltage during Wednesday, not seen in any other days data. Why?
– Second, is a load imbalance, where phase 2 and 3 are drawing around 40 amps more that phase 1
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 28 of 40
Testing
• When we look at the Power of each phase we can also see that Phase 1 average is 4000 Watts less that phase 2 and 3. Both phase 2 and 3 average in the range of 7000 Watts.
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 29 of 40
Testing
• Line to Neutral Voltage– Transients, Sags& Swells,
Voltage drops, Flat toping
• Neutral to Ground Voltage– Tripling harmonics, High
ground impedance.
–
Branch Circuits
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 30 of 40
Testing
• Voltage Distortion can be caused by large harmonic currents from Nonlinear loads or Power sources with no sinusoidal Voltage Characteristic
• Linear loads have small effects on voltage distortion.
• Non-Linear loads have a larger effect on voltage distortion Excessive Current drawn as the Voltage waveform
reaches Peak can cause Voltage distortion. Referred
to as Flat Topping or Clipping.
Branch Circuits
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 31 of 40
• Major loads affected– Computers– Copiers, Laser printers, and
other Large office loads– HVAC Equipment– Industrial equipment, Like
ASD’s (Adjustable Speed Drives)
– Lighting– UPS systems
Branch Circuits
Testing
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 32 of 40
Testing
Key Points for comparison
• Only important evens are logged
• Events are sorted by Time (log)
• Events are sorted by Type (event)
• Waveform shape is measured for THD
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 33 of 40
Testing
Events Log?• Sag – low voltage for
brief periods (dips)
• Swell- high voltage for brief periods (surges)
• Voltage Transient- impulses (spikes)
• THD for Total Harmonic Distortion (noise)
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 34 of 40
Testing
What cause the event and When ?• Amplitude of the event
• Number of Cycles (duration)
• Time of event
• Date of event
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 35 of 40
Test Equipment
• Test or Monitor , Basic measurement tools– Circuit Analyzer
– Multimeter or ClampMeters
• (True RMS responded)
– Receptacle Event Recorder
– Power Quality Monitor.
– Infrared temperature device
Always follow proper Safety precautionsLock-out Tag-out, safety gear like glasses and gloves
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 36 of 40
Test Equipment
• Most equipment, like circuit Analyzers, meters and clamps are slow responding.– They sample at speeds around 2 or 3 times a
second. – OK for steady state problems– To slow for intermittent disturbances.– Intermittent disturbances require equipment
which samples at a number of samples per cycle.
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 37 of 40
Test Equipment
• 160 Series SureTest Circuit Analyzers
• 830 Voltage Performance Monitor
• 800 Series Power Analyzer
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 38 of 40
SureTest Circuit Analyzers
• Circuit Analysis– Measures voltage drop
under full 15 Amp load,
– Neutral to Ground Voltage
– Ground Impedance
– Hot and Neutral Conductor Impedance.
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 39 of 40
830 Voltage Performance Monitor
• 830 Voltage Performance Monitor is great for evaluation clean Power on a branch circuits.– Sag– Swells– Impulses– %THD
• Depth and duration of each event is log with time and date stamp
• The powerful box with the Power Quality Engineer inside
Basics of Power Quality Monitoring© 2007 Ideal Industries www.idealindustries.com 40 of 40
800 Series Power Analyzer
• Power measurements– kW, Power Factor, kVA,
kVAR
• Harmonic measurements– %THD, harmonic
factorization to 51st harmonic
• Disturbances– Capture level 2 transients
(0.5µs)