1 www.cableco.com.jo National Cable and Wire Manufacturing Company CABLECO Overhead Transmission Lines & ABC Twisted Cables
Transcript
Page 1: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

1www.cableco.com.jo

National Cable and Wire Manufacturing Company

CABLECO

Overhead Transmission Lines&

ABC Twisted Cables

Page 2: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...
Page 3: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

3www.cableco.com.jo

INDEX

Contents Page

Introduction--------------------------------------------------------------------------------------------------------------- 5

1-Hard Drawn Copper Stranded Conductor Overhead Lines----------------------------------------------------- 6

2-PVC Insulated Hard Drawn Copper Stranded Conductor------------------------------------------------------- 8

3-All Aluminum Conductor--------------------------------------------------------------------------------------------- 9

4-All Aluminum Alloy Conductor------------------------------------------------------------------------------------ 11

5-Aluminum Conductor Steel Reinforced-------------------------------------------------------------------------- 13

6-Aerial Bundled (ABC) Twisted Cable------------------------------------------------------------------------------ 18

7-Technical Information----------------------------------------------------------------------------------------------- 19

8-Ordering Guide------------------------------------------------------------------------------------------------------- 23

Page 4: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...
Page 5: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

5www.cableco.com.jo

National Cable and Wire Manufacturing Company (CABLECO) was established in 1983 in Jordan, for production of electrical wires and cables (Armoured and Non Armoured).

The factory is located at Zarqa city, and equipped with series 0f production lines designed to produce wires and cables of copper or Aluminum conductors insulated /sheathed by (ordinary PVC or special types of PVC) or (XLPE) or (P.E) or (synthetic rubber EPR) or (XLLSHF, LSHF HALOGEN FREE) according to the International, British or German standards (IEC, BS, VDE) to comply with Jordanian and international markets.

The factory is also equipped with series of (Testing and Measuring) equipments calibrated according to international standards/Traceability to monitor and to control the quality of our production, starting from raw material, going through various productions /manufacturing stages and up to delivery stages/finished products.

In 2011, the company has produced cables with special international standards like (LAN Data cables & Fire Resistant Cables), to be compatible with modern technologies and international safety standards in public and private buildings.

Our objective is to produce high quality cables to satisfy the customer requirements therefore, we have achieved registration to ISO 9002/1994 in year 1996 and ISO 9001/2000 in year 2003,and in year 2009 we have achieved registration to ISO 9001/2008.

óbh á«FÉHô¡µdG πHGƒµdGh ∑Ó°SC’G êÉàfE’ 1983 ΩÉY ¿OQC’G ‘(ƒµ∏Ñ«c) á«FÉHô¡µdG ∑Ó°SC’Gh πHGƒµdG áYÉæ°üd á«æWƒdG ácô°ûdG â°ù°SCÉJ ( áë∏°ùŸG h ájOÉ©dG) πHGƒµdGh ∑Ó°SC’G ™«æ°üàd á«LÉàfE’G •ƒ£ÿG øe á∏°ù∏°ùH õ¡› ƒgh,AÉbQõdG áæjóe ‘ ácô°ûdG ™æ°üe º«bCG •É£ŸG hCG (P.E) hCG (XLPE) hCG Ö∏£dG Ö°ùM ™æ°üJ »àdGh á°UÉÿG hCG ájOÉ©dG ( PVC ) ∫G IOÉà ádhõ©ŸG Ωƒ«æŸC’G hCG »°SÉëædG π°UƒŸG äGP ≥aGƒà∏d (IEC,BS,VDE) á«fÉŸC’G hCG á«fÉ£jÈdG hCG á«dhódG äÉØ°UGƒŸG Ö°ùM ≈∏Y (XLLSHF,LSHF HALOGEN FREE) hCG ( EPR) »YÉæ°üdG International) á«dhódG äÉÑ∏£àŸG Ö°ùM IôjÉ©ŸGh ¢SÉ«≤∏d á°UÉÿG Iõ¡LC’G øe á∏°ù∏°ùH ™æ°üŸG OhR óbh , »ŸÉ©dGh ÊOQC’G ¥ƒ°ùdG ™e πµ°ûdÉH èàæŸG º«∏°ùJ ≈àMh áØ∏àîŸG ™«æ°üàdG πMGôà GQhôeh á«dhC’G OGƒŸG øe ájGóH ÉæJÉéàæŸ IOƒ÷G §Ñ°Vh áÑbGôe ºà«d (Traceability

.¿ƒHõ∏d »FÉ¡ædG

ÖcGƒàd (LAN Data Cables & Fire Resistant Cables) :πãe á«ŸÉY á°UÉN äÉØ°UGƒe äGP πHGƒc êÉàfEG ≈∏Y πª©dG ” 2011 ΩÉY ‘h.á°UÉÿGh á«eƒµ◊G ÊÉÑŸGh äÉ°ù°SDƒŸG ‘ áeÉ©dG áeÓ°ùdG ÒjÉ©eh áãjó◊G É«LƒdƒæµàdG ᪶fCG ≈∏Y π°UÉ◊G Qƒ£àdG

(ISO 9000) hõjB’G äÉØ°UGƒe Ö°ùM π«gCÉàdG äÉÑ∏£àe ‘ƒà°ùJ ¿CG ΩGôµdG É¡æFÉHõd IOƒ÷ÉH Égõ«“h É¡JQó≤d ÉJÉÑKEG ácô°ûdG äCÉJQG óbh. 2003 ΩÉY ‘ ISO 9001/2000 hõjB’G IOÉ¡°T ∂dòch 1996 ΩÉY ‘ ISO 9002/1994 hõjC’G IOÉ¡°T ≈∏Y ∫ƒ°ü◊G ” ób å«M

.∫ÉéŸG Gòg ‘ Ióªà©ŸG äÉ¡÷G øe ISO 9001/2008 hõjB’G IOÉ¡°T ≈∏Y ∫ƒ°ü◊G ” 2009 ΩÉY ‘h

Introduction

Page 6: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

6 www.cableco.com.jo

1- Hard Drawn Copper Stranded Conductor Overhead Lines

Application: Hard drawn copper conductors are used in overhead distribution network

Conductor: Hard Drawn Copper

Standard: DIN 48201

Cable Code

Cond.Area

ConductorConstruction

ConductorDiameter

ConductorWeight

Breaking Load Conductor Resistance

Stranded Conductor Minimum

Wire before stranding

Wire afterstranding

Nominal at 20ºC

Maximum at 20ºC

mm² No. x mm mm Kg/Km N N N Ohm/Km Ohm/Km

08250DN10SRC 10 7X1.35 4.05 90 4020 651 583 1.788 1.805

08250DN16SRC 16 7X1.7 5.1 143 6374 1010 923 1.128 1.138

08250DN25SRC 25 7X2.1 6.3 219 9708 1540 1409 0.7391 0.746

08250DN35SRC 35 7X2.5 7.5 310 13777 2185 1997 0.5215 0.5265

08250DN50SRC 50 7X3.0 9.0 447 19808 3146 2875 0.3622 0.3656

08250DN50(19)SRC 50 19X1.8 9.0 438 19416 1130 1035 0.3727 0.376

08250DN70SRC 70 19X2.1 10.5 597 26378 1540 1409 0.2738 0.2762

08250DN95SRC 95 19X2.5 12.5 846 37361 2185 1997 0.1932 0.1949

08250DN120SRC 120 19X2.8 14.0 1061 46873 2741 2505 0.154 0.1554

08250DN150SRC 150 37X2.25 15.7 1337 58934 1771 1618 0.1233 0.1238

08250DN185SRC 185 37X2.5 17.5 1651 72760 2185 1997 0.09981 0.1003

08250DN240SRC 240 61X2.25 20.2 2208 97178 1771 1618 0.0748 0.0753

08250DN300SRC 300 61X2.5 22.5 2726 119976 2185 1997 0.0606 0.0610

08250DN400SRC 400 61X2.89 26 3643 160279 2918 2684 0.0453 0.0456

08250DN500SRC 500 61X3.23 29.1 2551 200239 3604 3315 0.0363 0.0365

Page 7: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

7www.cableco.com.jo

1- Hard Drawn Copper Stranded Conductor Overhead Lines

Conductor: Hard Drawn Copper

Standard: BS 7884

Cable Code

Cond.Area

ConductorConstruction

ConductorDiameter

ConductorWeight

Breaking Load Conductor Resistance

Stranded Conductor Minimum

Wire before stranding

Wire afterstranding

Nominal at 20ºC

Maximum at 20ºC

mm² No. x mm mm Kg/Km N N N Ohm/Km Ohm/Km

08250BS10SRC 10 7X1.35 4.05 89.82 3752 651 583 1.788 1.829

08250BS14SRC 14 7X1.6 4.8 126.2 5267 915 818 1.273 1.303

08250BS16(3)SRC 16 3X2.65 5.7 148.3 6194 2452 2244 1.082 1.106

08250BS16SRC 16 7X1.7 5.1 142.4 5946 1010 923 1.128 1.154

08250BS25SRC 25 7X2.1 6.3 217.3 9073 1540 1409 0.7391 0.7563

08250BS32SRC 32 3X3.75 8.06 296.9 12400 4802 4494 0.5405 0.5520

08250BS32(7)SRC 32 7X2.46 7.38 298.2 12442 2114 1932 0.5386 0.5497

08250BS35SRC 35 7X2.5 7.5 308 12860 2185 1997 0.5215 0.5337

08250BS50SRC 50 7X3.0 9.0 443.5 18520 3146 2875 0.3622 0.3706

08250BS50(19)SRC 50 19X1.8 9.0 435.8 17700 1130 1035 0.3727 0.3819

08250BS70SRC 70 7X3.55 10.65 621.1 25930 4307 4027 0.2586 0.2646

08250BS70(19)SRC 70 19X2.1 10.5 593.2 24090 1540 1409 0.2738 0.2806

08250BS95SRC 95 19X2.5 12.5 840.7 34140 2185 1997 0.1932 0.1980

08250BS100SRC 100 7X4.3 12.9 911.2 36540 6244 5675 0.1763 0.1810

08250BS120SRC 120 19X2.8 14.0 1055 42830 2741 2505 0.1540 0.1578

08250BS125SRC 125 19X2.9 14.5 1131 45940 2942 2687 0.1436 0.1471

08250BS150SRC 150 19X3.2 16.0 1377 55940 3538 3271 0.1180 0.1208

08250BS150(37)SRC 150 37X2.25 15.75 1334 53880 1771 1618 0.1233 0.1264

08250BS185SRC 185 19X3.55 17.75 1695 68860 4307 4027 0.09582 0.09815

08250BS185(37)SRC 185 37X2.5 17.5 1647 66490 2185 1997 0.09981 0.1024

Page 8: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

8 www.cableco.com.jo

2- PVC Insulated Hard Drawn Copper Stranded Conductor

Application: used for protection to the public from low voltage lines in case of accidental contact, also to give protection to telecommunication lines where crossed by power lines distribution network.

Conductor: Hard Drawn Copper Conductor

Insulation: Black or Green extruded PVC

Note: Materials Conductors (AAC, AAAC, and ACSR) can be insulated for the same purpose.

Standard: BS 6485 for 650 V and 11000 V

Cable Code Cond

ucto

r Are

a

Cond

ucto

rCo

nstr

uctio

n

Cond

ucto

rD

iam

eter

Cond

ucto

rW

eigh

t

Breaking Load Conductor Resistance

Insulated Conductor 650V

Insulated Conductor 11000V

Stra

nded

Co

nduc

tor

Wire

bef

ore

stra

ndin

g

Wire

aft

erst

rand

ing

Nom

inal

at 2

0ºC

Max

imum

at

20ºC

Aver

age

Thic

knes

s

Ove

rall

Dia

met

er

Wei

ght

Aver

age

Thic

knes

s

Ove

rall

Dia

met

er

Wei

ght

mm² No. x mm mm Kg/Km N N N Ohm/Km Ohm/Km mm mm Kg/Km mm mm Kg/Km

08251BS10SRC 10 7X1.35 4.05 89.82 4129 651 583 1.788 1.829 1.0 6.1 118 1.8 7.75 144

08251BS14SRC 14 7X1.6 4.8 126.2 5744 915 818 1.273 1.303 1.0 6.85 160 1.8 8.5 188

08251BS16(3)SRC 16 3X2.65 5.7 148.3 6590 2452 2244 1.082 1.106 1.0 7.75 193 1.8 9.4 225

08251BS16SRC 16 7X1.7 5.1 142.4 6590 1010 923 1.128 1.154 1.0 7.15 178 1.8 8.8 208

08251BS25SRC 25 7X2.1 6.3 217.3 10170 1540 1409 0.7391 0.7563 1.2 8.8 270 2.0 10.4 306

08251BS32SRC 32 3X3.75 8.06 296.9 12710 4802 4494 0.5405 0.5520 1.2 10.5 376 2.0 12.15 418

08251BS32(7)SRC 32 7X2.46 7.38 298.2 12710 2114 1932 0.5386 0.5497 1.2 9.85 360 2.0 11.5 400

08251BS35SRC 35 7X2.5 7.5 308 14097 2185 1997 0.5215 0.5337 1.2 10.0 371 2.0 11.6 412

08251BS50SRC 50 7X3.0 9.0 443.5 19497 3146 2875 0.3622 0.3706 1.4 11.9 530 2.0 13.1 567

08251BS50(19)SRC 50 19X1.8 9.0 435.8 19497 1130 1035 0.3727 0.3819 1.4 11.9 524 2.0 13.1 552

08251BS70SRC 70 7X3.55 10.65 621.1 26880 4307 4027 0.2586 0.2646 1.4 13.55 728 2.0 14.75 767

08251BS70(19)SRC 70 19X2.1 10.5 593.2 26880 1540 1409 0.2738 0.2806 1.4 13.4 690 2.0 14.6 728

08251BS95SRC 95 19X2.5 12.5 840.7 37361 2185 1997 0.1932 0.1980 1.6 15.8 972 2.0 16.6 1000

08251BS100SRC 100 7X4.3 12.9 911.2 37640 6244 5675 0.1763 0.1810 1.6 16.2 1060 2.0 17.0 1090

3- All-Aluminum Conductor (AAC)

Page 9: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

9www.cableco.com.jo

Application: All-Aluminum Conductors are the most favored type for use on relatively short spans, particularly low and medium voltage distribution lines. their popularity is principally due to their ability to carry a given current of lowest capital cost .this cost does not however, take the total line into account, including poles and lower heights,spans,wind and ice loads, etc. when these factors are considered the low strength to weight ratio of all-aluminum conductor becomes limiting factor.

Conductor: Hard Drawn Aluminum Conductor

Standard: DIN 48201-5:1981

Cable Code

Cond.Area

ConductorConstruction

Actual Area

ConductorDiameter

ConductorWeight

Calculated Breaking Load

Calculated Resistance

at 20ºC

BreakingLength

mm² No. x mm mm² mm Kg/Km Kgf KN Ohm/Km Km

08001DN16SRC 16 7X1.7 15.89 5.1 43 290 2.84 1.8017 6.74

08001DN25SRC 25 7X2.1 24.25 6.3 66 425 4.17 1.1806 6.44

08001DN35SRC 35 7X2.5 34.36 7.5 94 589 5.78 0.8332 6.27

08001DN50SRC 50 7X3.0 49.48 9.0 135 810 7.94 0.5786 6.00

08001DN50(19)SRC 50 19X1.8 48.35 9.0 133 862 8.45 0.5950 6.48

08001DN70SRC 70 19X2.1 65.81 10.5 181 1154 11.32 0.4371 6.38

08001DN95SRC 95 19X2.5 93.27 12.5 256 1599 15.68 0.3084 6.25

08001DN120SRC 120 19X2.8 117.0 14.0 322 1915 18.78 0.2459 5.95

08001DN150SRC 150 37X2.25 147.1 15.75 405 2580 25.30 0.1960 6.37

08001DN185SRC 185 37X2.5 181.6 17.5 500 3114 30.54 0.1588 6.23

08001DN240SRC 240 61X2.25 242.5 20.25 669 4029 39.51 0.1192 6.03

08001DN300SRC 300 61X2.5 299.4 22.5 826 4864 47.70 0.09651 5.90

08001DN400SRC 400 61X2.89 400.1 26.01 1104 6206 60.86 0.07222 5.63

08001DN500SRC 500 61X3.23 499.8 29.07 1379 7614 74.67 0.05782 5.53

08001DN625SRC 625 91X2.96 626.2 32.56 1733 9713 95.25 0.04625 5.60

08001DN800SRC 800 91X3.35 802.1 36.85 2219 12072 118.39 0.03610 5.44

08001DN1000SRC 1000 91X3.74 999.7 41.14 2766 14863 145.76 0.02897 5.37

3- All-Aluminum Conductor (AAC)

Page 10: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

10 www.cableco.com.jo

Conductor: Hard Drawn Aluminum Conductor

Standard: BS 215-2:1970

Cable Code Code Name Cond.Area

ConductorConstruction

Actual Area

ConductorDiameter

Cond.Weight

Calculated Breaking Load

Calculated Resistance

at 20ºC

BreakingLength

mm² No. x mm mm² mm Kg/Km Kgf KN Ohm/Km Km

08024BS22SRC Midge 22 7x2.06 23.33 6.18 64 407 3.99 1.227 6.36

08003BS25SRC Aphis 25 3x3.35 26.44 7.22 73 420 4.12 1.083 5.68

08018BS25SRC Gnat 25 7x2.21 26.85 6.63 74 468 4.59 1.066 6.32

08031BS30SRC Weevil 30 3x3.66 31.56 7.89 87 495 4.86 0.9070 5.63

08025BS35SRC Mosquito 35 7x2.59 36.88 7.77 101 614 6.03 0.7763 6.08

08022BS40SRC Ladybird 40 7x2.79 42.80 8.37 117 701 6.87 0.6689 5.99

08002BS50SRC Ant 50 7x3.1 52.83 9.30 145 844 8.28 0.5419 5.82

08017BS60SRC Fly 60 7x3.4 63.55 10.20 174 1010 9.9 0.4505 5.80

08006BS70SRC Bluebottle 70 7x3.66 73.65 10.98 202 1156 11.33 0.3887 5.72

08016BS75SRC Earwig 75 7x3.78 78.55 11.34 215 1217 11.94 0.3645 5.66

08019BS80SRC Grasshopper 80 7x3.91 84.05 11.73 230 1303 12.78 0.3406 5.67

08012BS90SRC Clegg 90 7x4.17 95.60 12.51 262 1482 14.53 0.2995 5.66

08030BS100SRC Wasp 100 7x4.39 106.0 13.17 290 1633 16.01 0.2702 5.63

08005BS100SRC Beetle 100 19x2.67 106.4 13.35 293 1773 17.39 0.2704 6.05

08004BS125SRC Bee 125 7x4.9 132.0 14.70 361 2033 19.94 0.2169 5.63

08014BS150SRC Cricket 150 7x.5.36 157.9 16.08 432 2432 23.85 0.1813 5.63

08020BS150SRC Homet 150 19x3.25 157.16 16.25 434 2519 24.7 0.1825 5.80

08008BS175SRC Caterpillar 175 19x3.53 185.9 17.65 511 2917 28.61 0.1547 5.71

08010BS200SRC Chafer 200 19x3.78 213.2 18.90 587 3305 32.41 0.1349 5.63

08028BS225SRC Spider 225 19x3.99 237.6 19.95 654 3683 36.12 0.1211 5.63

08013BS250SRC Cockroach 250 19x4.22 265.7 21.10 731 4118 40.39 0.1083 5.63

08007BS300SRC Butterfly 300 19x4.65 322.7 23.25 888 4970 48.74 0.08916 5.60

08026BS350SRC Moth 350 19x5.0 373.1 25.00 1027 5746 56.36 0.07711 5.59

08015BS350SRC Drone 350 37x3.58 372.4 25.06 1027 5844 57.31 0.07742 5.69

08021BS400SRC Locust 400 19x5.36 428.7 26.80 1180 6603 64.76 0.06711 5.60

08009BS400SRC Centipede 400 37x3.78 415.2 26.46 1145 6435 63.11 0.06944 5.62

08023BS450SRC Maybug 450 37x4.09 486.1 28.63 1340 7535 73.89 0.05931 5.62

08027BS500SRC Scorpion 500 37x4.27 529.8 29.89 1461 8160 80.03 0.05442 5.59

08011BS600SRC Cicada 600 37x4.65 628.3 32.55 1732 9678 94.9 0.04589 5.59

08029BS750SRC Tarantula 750 37x5.23 794.9 36.61 2192 12244 120.07 0.03627 5.59

3- All-Aluminum Conductor (AAC)

Page 11: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

11www.cableco.com.jo

4- All-Aluminum Alloy Conductor (AAAC)

Application: All-Aluminum Alloy Conductor when compared with AAC conductors they have a far superior tensile strength and surface hardness. These prosperities provide potential for reducing sags or increasing spacing between towers, and make the conductor less prone to surface damage during installation. Other advantages are no galvanic corrosion, the ability to use less complex installation fittings, and reduced vulnerability to surface damage which can be an important consideration on high voltage lines from corona point of view.

Conductor: Hard Drawn Aluminum Alloy Conductor

Standard: DIN 48201-6:1981

Cable Code Cond.Area

ConductorConstruction

Actual Area

ConductorDiameter

ConductorWeight

Calculated Breaking Load

Calculated Resistance at

20ºC

BreakingLength

mm² No. x mm mm² mm Kg/Km Kgf KN Ohm/Km Km

08043DN16SRC 16 7X1.7 15.89 5.10 43 453 4.44 2.0908 10.53

08043DN25SRC 25 7X2.1 24.25 6.30 66 690 6.77 1.3700 10.45

08043DN35SRC 35 7X2.5 34.36 7.50 94 979 9.60 0.9669 10.41

08043DN50SRC 50 7X3.0 49.48 9.00 135 1409 13.82 0.6713 10.44

08043DN50(19)SRC 50 19X1.8 48.35 9.00 133 1377 13.50 0.6903 10.35

08043DN70SRC 70 19X2.1 65.81 10.50 181 1874 18.38 0.5072 10.35

08043DN95SRC 95 19X2.5 93.27 12.50 256 2656 26.05 0.3579 10.38

08043DN120SRC 120 19X2.8 117.0 14.00 322 3332 32.68 0.2853 10.35

08043DN120SRC 150 37X2.25 147.1 15.75 405 4190 41.09 0.2275 10.35

08043DN185SRC 185 37X2.5 181.6 17.50 500 5172 50.73 0.1842 10.34

08043DN240SRC 240 61X2.25 242.5 20.25 669 6906 67.74 0.1383 10.34

08043DN300SRC 300 61X2.5 299.4 22.50 826 8527 83.63 0.1120 10.34

08043DN400SRC 400 61X2.89 400.1 26.01 1104 11390 111.70 0.08381 10.33

08043DN500SRC 500 61X3.23 499.8 29.07 1379 14235 139.60 0.06709 10.34

08043DN625SRC 625 91X2.96 626.2 32.56 1733 17835 174.90 0.05367 10.29

08043DN800SRC 800 91X3.35 802.1 36.85 2219 22852 224.00 0.04190 10.30

08043DN1000SRC 1000 91X3.74 999.7 41.14 2766 28470 279.20 0.03362 10.29

Page 12: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

12 www.cableco.com.jo

Conductor: Hard Drawn Aluminum Alloy Conductor

Standards: BS 3242:1970

Cable Code Code Name Cond.Area

ConductorConstruction

Actual Area

ConductorDiameter

Cond.Weight

Calculated Breaking Load

Calculated Resistance

at 20ºC

BreakingLength

mm² No. x mm mm² mm Kg/Km Kgf KN Ohm/Km Km

08043BS10SRC ---- 10 7x1.47 11.88 4.41 32 340 3.33 2.771 10.63

08048BS15SRC Box 15 7x1.85 18.82 5.55 51 537 5.27 1.749 10.53

08044BS20SRC Acacia 20 7x2.08 23.79 6.24 65 680 6.67 1.384 10.46

08045BS25SRC Almond 25 7x2.34 30.10 7.02 82 861 8.44 1.093 10.50

08049BS30SRC Cedar 30 7x2.54 35.47 7.62 97 1014 9.94 0.9281 10.45

08043BS35SRC ---- 35 7x2.77 42.18 8.31 115 1205 11.82 0.7804 10.48

08051BS40SRC Fir 40 7x2.95 47.84 8.85 131 1367 13.41 0.6881 10.44

08052BS50SRC Hazel 50 7x3.30 59.87 9.90 164 1711 16.78 0.5498 10.43

08055BS60SRC Pine 60 7x3.61 71.65 10.83 196 2048 20.08 0.4594 10.45

08043BS70SRC ---- 70 7x3.91 84.05 11.73 230 2402 23.56 0.3917 10.44

08062BS75SRC Willow 75 7x4.04 89.73 12.12 245 2565 25.15 0.3669 10.47

08043BS80SRC ---- 80 7x4.19 96.52 12.57 264 2758 27.05 0.3411 10.45

08043BS90SRC ---- 90 7x4.45 108.9 13.35 298 3112 30.52 0.3023 10.44

08054BS100SRC Oak 100 7x4.65 118.9 13.95 325 3398 33.32 0.2769 10.46

08043BS100SRC ---- 100 19x2.82 118.7 14.1 326 3393 33.27 0.2787 10.41

08053BS125SRC Mulberry 125 19x3.18 150.9 15.9 415 4312 42.29 0.2192 10.39

08047BS150SRC Ash 150 19x3.48 180.7 17.4 497 5164 50.64 0.1831 10.39

08050BS175SRC Elm 175 19x3.76 211.0 18.8 580 6030 59.13 0.1568 10.40

08056BS200SRC Poplar 200 37x2.87 239.4 20.09 659 6841 67.09 0.1385 10.38

08043BS225SRC ---- 225 37x3.05 270.3 21.35 744 7724 75.75 0.1227 10.38

08058BS250SRC Sycamore 250 37x3.23 303.2 22.61 835 8664 84.97 0.1093 10.38

08060BS300SRC Upas 300 37x3.53 362.1 24.71 997 10350 101.5 0.09156 10.38

08061BS350SRC Walnut 350 37x3.81 421.8 26.67 1162 12053 118.2 0.07860 10.37

08063BS400SRC Yew 400 37x4.06 479.0 28.42 1319 13685 134.2 0.06921 10.38

08059BS425SRC Totara 425 37x4.14 498.1 28.98 1372 14233 139.6 0.06656 10.37

08057BS500SRC Rubus 500 61x3.50 586.9 31.50 1620 16771 164.5 0.05662 10.35

08046BS700SRC Araucaria 700 61x4.14 821.1 37.26 2266 23450 230.0 0.04047 10.35

4- All-Aluminum Alloy Conductor (AAAC)

Page 13: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

13www.cableco.com.jo

5- Aluminum Conductor Steel Reinforced (ACSR)

Application: This type of conductor possesses a higher strength to weight ratio than AAC and because of this it can be used on longer spans and in more severe weather conditions. It also possesses a higher modulus of elasticity and a lower coefficient of thermal expansion, both of which enhance its mechanical characteristics. These prosperities can be varied by altering the aluminum to steel ratio in the stranding geometry. Higher strength steel can also be used which gives an improved strength to weight ratio without affecting any other property.

For given current rating the cost of ACSR will be greater than AAC but the mechanical advantages it possesses mean it is superior economically when the total line is considered. It is this fact which makes it currently the most commonly used type of conductor

Page 14: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

14 www.cableco.com.jo

Conductor: Hard Drawn Aluminum Conductor Steel Reinforced

Standard: DIN 48204:1984

Cable Code

Cond

ucto

rAr

ea

ConductorConstruction Actual Area

Cond

ucto

r D

iam

eter

Conductor Weight

Calculated Breaking Load

Calc

ulat

ed R

esis

tanc

e at

20

ºC

Ungreased Grease

Alum

inum

Stee

l

Alum

inum

Stee

l

Tota

l

Alum

inum

Stee

l

Tota

l

Stee

l Onl

y

All i

nner

la

yers

mm

²

No.

x m

m

No.

x m

m

mm

²

mm

²

mm

²

mm

Kg/K

m

Kg/K

m

Kg/K

m

Kg/K

m

Kg/K

m

Kgf KN

Ohm

/Km

08064DN16/2.5SRC 16/2.5 6x1.8 1x1.8 15.27 2.54 17.81 5.40 42 20 62 0.5 - 592 5.81 1.879

08064DN25/4SRC 25/4 6x2.25 1x2.25 23.86 3.98 27.84 6.75 65 31 96 0.8 - 920 9.02 1.203

08064DN35/6SRC 35/6 6x2.7 1x2.7 34.35 5.73 40.08 8.10 94 45 139 1.1 - 1295 12.70 0.8353

08064DN44/32SRC 44/32 14x2.0 7x2.4 43.98 31.67 75.65 11.20 122 248 370 5.8 - 4636 45.46 0.6573

08064DN50/8SRC 50/8 6x3.2 1x3.2 48.25 8.04 56.29 9.60 132 63 195 1.6 - 1752 17.18 0.5946

08064DN50/30SRC 50/30 12x2.33 7x2.33 51.17 29.85 81.02 11.65 141 234 375 5.5 - 4515 44.28 0.5644

08064DN70/12SRC 70/12 26x1.85 7x1.44 69.89 11.40 81.29 11.72 193 89 282 2.1 7.8 2683 26.31 0.4130

08064DN95/15SRC 95/15 26x2.15 7x1.67 94.39 15.33 109.72 13.61 260 120 380 2.8 11 3586 35.17 0.3058

08064DN95/55SRC 95/55 12x3.2 7x3.2 96.51 56.30 152.81 16.00 266 441 707 10.0 - 8178 80.20 0.2992

08064DN105/75SRC 105/75 14x3.1 19x2.25 105.67 75.55 181.22 17.45 292 594 886 15.0 - 10879 106.69 0.2736

08064DN120/20SRC 120/20 26x2.44 7x1.9 121.57 19.85 141.42 15.46 335 156 491 3.6 14 8583 44.94 0.2374

08064DN120/70SRC 120/70 12x3.6 7x3.6 122.15 71.25 193.40 18.00 337 558 895 13.0 - 10009 98.16 0.2364

08064DN125/30SRC 125/30 30x2.33 7x2.33 127.92 29.85 157.77 16.31 353 234 587 5.5 16 5900 57.86 0.2259

08064DN150/25SRC 150/25 26x2.7 7x2.1 148.86 24.25 173.11 17.10 411 190 601 4.5 17 5544 54.37 0.1939

08064DN170/40SRC 170/40 30x2.7 7x2.7 171.77 40.08 211.85 18.90 474 314 788 7.4 22 7853 77.01 0.1682

08064DN185/30SRC 185/30 26x3.0 7x2.33 183.78 29.85 213.63 18.99 507 234 741 5.5 21 6759 66.28 0.1571

08064DN210/35SRC 210/35 26x3.2 7x2.49 209.10 34.09 243.19 20.27 577 267 844 6.3 24 7642 74.94 0.1380

08064DN210/50SRC 210/50 30x3.0 7x3.0 212.06 49.48 261.54 21.00 585 388 973 9.1 27 9407 92.25 0.1363

08064DN230/30SRC 230/30 24x3.5 7x2.33 230.91 29.85 260.75 20.99 636 234 870 5.5 24 7453 73.09 0.1249

08064DN240/40SRC 240/40 26x3.45 7x2.68 243.05 39.49 282.54 21.84 670 309 979 7.2 27 8816 86.46 0.1188

08064DN265/35SRC 265/35 24x3.74 7x2.49 263.66 34.09 297.75 22.43 727 267 994 6.3 27 8457 82.94 0.1094

08064DN300/50SRC 300/50 26x3.86 7x3.0 304.26 49.48 353.74 24.44 839 388 1227 9.1 34 10716 105.09 0.09487

08064DN305/40SRC 305/40 54x2.68 7x2.68 304.62 39.49 344.11 24.12 841 309 1150 7.2 43 10126 99.30 0.09490

08064DN340/30SRC 340/30 48x3.0 7x2.33 339.29 29.85 369.14 24.99 936 234 1170 5.5 45 9438 92.56 0.08513

08064DN380/50SRC 380/50 54x3.0 7x3.0 381.70 49.48 431.18 27.00 1054 388 1442 9.1 55 12329 120.91 0.07573

08064DN385/35SRC 385/35 48x3.2 7x2.49 386.04 34.09 420.13 26.67 1065 267 1332 6.3 51 10637 104.31 0.07482

08064DN435/55SRC 435/55 54x3.2 7x3.2 434.29 56.30 490.59 28.80 1199 441 1640 10.0 62 13896 136.27 0.06656

08064DN450/40SRC 450/40 48x3.45 7x2.68 448.71 39.49 488.20 28.74 1238 309 1547 7.2 59 12256 120.19 0.06437

08064DN490/65SRC 490/65 54x3.4 7x3.4 490.28 63.55 553.83 30.60 1354 498 1852 12.0 70 15586 152.85 0.05896

08064DN495/35SRC 495/35 45x3.74 7x2.49 494.36 34.09 528.48 29.91 1364 267 1631 6.3 63 12268 120.31 0.05843

08064DN510/45SRC 510/45 48x3.68 7x2.87 510.54 45.28 555.82 30.69 1409 355 1764 8.3 68 13698 134.33 0.05657

08064DN550/70SRC 550/70 54x3.6 7x3.6 549.65 71.25 620.90 32.40 1518 558 2076 13.0 78 17072 167.42 0.05259

08064DN560/50SRC 560/50 48x3.86 7x3.0 561.70 49.48 611.18 32.16 1550 388 1938 9.1 74 14916 146.28 0.05142

08064DN570/40SRC 570/40 45x4.02 7x2.68 571.16 39.49 610.65 32.16 1576 309 1885 7.2 72 14070 137.98 0.05057

08064DN650/45SRC 650/45 45x4.3 7x2.87 653.49 45.28 698.77 34.41 1803 355 2155 8.3 83 15859 155.52 0.04420

08064DN680/85SRC 680/85 54x4.0 19x2.4 678.58 85.95 764.53 36.00 1874 676 2550 17.0 98 21413 209.99 0.04260

08064DN1045/45SRC 1045/45 72x4.3 7x2.87 1045.58 45.28 1090.86 43.01 2889 355 3244 8.3 149 22216 217.87 0.02766

5- Aluminum Conductor Steel Reinforced (ACSR)

Page 15: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

15www.cableco.com.jo

5- Aluminum Conductor Steel Reinforced (ACSR)

Conductor: Hard Drawn Aluminum Conductor Steel Reinforced

Standard: BS 215-2:1970

Cable CodeCode Name

Cond

ucto

rAr

eaConductor

Construction Actual Area

Cond

ucto

r Dia

met

er

Conductor Weight

Calculated Breaking

Load

Calc

ulat

ed R

esis

tanc

e at

20

ºC

Ungreased Grease

Alum

inum

Stee

l

Alum

inum

Stee

l

Tota

l

Alum

inum

Stee

l

Tota

l

Stee

l Onl

y

All i

nner

laye

rs

mm

²

No.

x m

m

No.

x m

m

mm

²

mm

²

mm

²

mm

Kg/K

m

Kg/K

m

Kg/K

m

Kg/K

m

Kg/K

m

Kgf KN

Ohm

/Km

08089BS10SRC Mole 10 6X1.5 1X1.5 10.6 1.77 12.37 4.50 29 14 43 0.4 0.4 421 4.13 2.70708097BS20SRC Squirrel 20 6X2.11 1X2.11 20.98 3.50 24.48 6.33 58 27 85 0.7 0.7 807 7.91 1.36808080BS25SRC Gopher 25 6X2.36 1X2.36 26.25 4.37 30.62 7.08 72 34 106 0.9 0.9 979 9.6 1.09308099BS30SRC Weasel 30 6X2.59 1X2.59 31.61 5.27 36.88 7.77 87 41 128 1.0 1.0 1167 11.44 0.907708078BS35SRC Fox 35 6X2.79 1X2.79 36.68 6.11 42.79 8.37 101 48 149 1.2 1.2 1342 13.16 0.782308077BS40SRC Ferret 40 6X3.0 1X3.0 42.41 7.07 49.48 9.0 116 55 171 1.4 1.4 1553 15.23 0.676608093BS50SRC Rabbit 50 6X3.35 1X3.35 52.88 8.81 61.69 10.05 145 69 214 1.7 1.7 1872 18.36 0.542608088BS60SRC Mink 60 6X3.66 1X3.66 63.13 10.52 73.65 10.98 173 82 255 2.1 2.1 2223 21.8 0.454508096BS60SRC Skunk 60 12X2.59 7X2.59 63.22 36.88 100.1 12.95 175 289 464 6.7 6.7 5396 52.92 0.456808067BS70SRC Beaver 70 6X3.99 1X3.99 75.02 12.50 87.52 11.97 205 98 303 2.5 2.5 2626 25.75 0.382508082BS70SRC Horse 70 12X2.79 7X2.79 73.36 42.80 116.2 13.95 203 335 538 7.8 7.8 6240 61.19 0.393608094BS75SRC Raccoon 75 6X4.10 1X4.10 79.22 13.20 92.42 12.30 217 103 320 2.6 2.6 2774 27.2 0.362208091BS80SRC Otter 80 6X4.22 1X4.22 83.92 13.99 97.91 12.66 230 109 339 2.8 2.8 2939 28.82 0.341908071BS90SRC Cat 90 6X4.50 1X4.50 95.43 15.90 111.3 13.50 262 124 386 3.2 3.2 3330 32.66 0.300708081BS100SRC Hare 100 6X4.72 1X4.72 105.0 17.50 122.5 14.16 288 137 425 3.5 3.5 3666 35.95 0.273308075BS100SRC Dog 100 6X4.72 7X1.57 105.0 13.55 118.6 14.15 288 106 394 2.5 2.5 3332 32.68 0.273308083BS100SRC Hyena 100 7X4.39 7X1.93 106.0 20.48 126.5 14.57 293 160 453 3.7 3.7 4183 41.02 0.272808072BS125SRC Cougar 125 18X3.05 1X3.05 131.5 7.31 138.8 15.25 362 57 419 1.4 9.3 3062 30.03 0.219008085BS125SRC Leopard 125 6X5.28 7X1.75 131.4 16.84 148.2 15.81 361 132 493 3.1 3.1 4156 40.76 0.218408098BS125SRC Tiger 125 30X2.36 7X2.36 131.2 30.62 161.8 16.52 363 240 603 5.6 17 5914 58.0 0.220308074BS150SRC Dingo 150 18X3.35 1X3.35 158.7 8.81 167.5 16.75 437 69 506 1.7 11 3642 35.72 0.181408100BS150SRC Wolf 150 30X2.59 7X2.59 158.1 36.88 195.0 18.13 437 289 726 6.7 20 7061 69.24 0.182808070BS175SRC Caracal 175 18X3.61 1X3.61 184.2 10.24 194.4 18.05 507 80 587 2.0 13 4191 41.1 0.156308087BS175SRC Lynx 175 30X2.79 7X2.79 183.4 42.80 226.2 19.53 507 335 842 7.8 23 8136 79.79 0.157608084BS200SRC Jaguar 200 18X3.86 1X3.86 210.6 11.70 222.3 19.30 580 91 671 2.3 15 4749 46.57 0.136708092BS200SRC Panther 200 30X3.0 7X3.0 212.1 49.48 261.6 21.0 586 388 974 9.0 27 9407 92.25 0.136208086BS225SRC Lion 225 30X3.18 7X3.18 238.3 55.60 293.9 22.26 659 436 1095 10 30 10248 100.5 0.121308066BS250SRC Bear 250 30X3.35 7X3.35 264.4 61.70 326.1 23.45 731 483 1214 11 34 11339 111.2 0.109308079BS300SRC Goat 300 30X3.71 7X3.71 324.3 75.67 400.0 25.97 896 593 1489 14 41 13848 135.8 0.0891108095BS350SRC Sheep 350 30X3.99 7X3.99 375.1 87.53 426.6 27.93 1037 686 1723 16 48 15938 156.3 0.0770408065BS350SRC Antelope 350 54X2.97 7X2.97 374.1 48.50 422.6 26.73 1034 380 1414 8.8 53 12084 118.5 0.0772708068BS350SRC Bison 350 54X3.0 7X3.0 381.7 49.48 431.2 27.0 1055 388 1443 9.0 54 12328 120.9 0.0757308073BS400SRC Deer 400 30X4.27 7X4.27 429.6 100.2 529.8 29.89 1187 785 1972 18 55 18202 178.5 0.0672708101BS400SRC Zebra 400 54X3.18 7X3.18 428.9 55.60 484.5 28.62 1186 436 1622 10 61 13450 131.9 0.0674008076BS450SRC Elk 450 30X4.50 7X4.5 477.1 111.3 588.4 31.50 1318 872 2190 20 61 20221 198.3 0.0605708069BS450SRC Camel 450 54X3.35 7X3.35 476.0 61.70 537.7 30.15 1316 483 1799 11 67 14878 145.9 0.0607308090BS500SRC Moose 500 54X3.53 7X3.53 528.5 68.51 597.0 31.77 1461 537 1998 12 75 16417 161.0 0.05470

Page 16: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

16 www.cableco.com.jo

Conductor: Hard Drawn Aluminum Conductor Steel Reinforced

Standard: ASTM B 232:1986

Cable Code Code Name

Cond

ucto

rAr

ea

ConductorConstruction Actual Area

Cond

ucto

r Dia

met

er Conductor Weight

Calculated Breaking

Load

Calc

ulat

ed

Resi

stan

ce a

t 20º

C

Ungreased Grease

Alum

inum

Stee

l

Alum

inum

Stee

l

Tota

l

Alum

inum

Stee

l

Tota

l

Stee

l Onl

y

All i

nner

la

yers

MCM

No.

x m

m

No.

x m

m

mm

²

mm

²

mm

²

mm

Kg/K

m

Kg/K

m

Kg/K

m

Kg/K

m

Kg/K

m

Kgf KN

Ohm

/Km

08---AB26.24SRC Turkey 26.24 6x1.68 1x1.68 13.30 2.22 15.52 5.04 37 17 54 0.4 0.4 540 5.29 2.150

08—AB33.22SRC Thrush 33.22 6x1.89 1x1.89 16.83 2.81 19.64 5.67 46 22 68 0.6 0.6 678 6.65 1.699

08---AB41.74SRC Swan 41.74 6x2.12 1x2.12 21.18 3.53 24.71 6.36 58 27 85 0.7 0.7 846 8.3 1.350

08---AB41.74SRC Swanate 41.74 7x1.96 1x2.61 21.12 5.35 26.47 6.53 58 42 100 1.1 1.1 1067 10.46 1.354

08---AB52.68SRC Swallow 52.68 6x2.38 1x2.38 26.69 4.45 31.14 7.14 73 35 108 0.9 0.9 1042 10.22 1.071

08---AB66.36SRC Sparrow 66.36 6x2.67 1x2.67 33.59 5.6 39.19 8.01 92 44 136 1.1 1.1 1289 12.64 0.8513

08---AB66.36SRC Sparate 66.36 7x2.47 1x3.30 33.54 8.55 42.09 8.24 92 67 159 1.7 1.7 1650 16.18 0.8526

08—AB80SRC Grouse 80.0 8x2.54 1x4.24 40.54 14.12 54.66 9.32 111 110 221 2.8 2.8 2359 23.13 0.7053

08---AB83.69SRC Robin 83.69 6x3.0 1x3.0 42.41 7.07 49.48 9.0 116 55 171 1.4 1.4 1612 15.81 0.6742

08---AB101.8SRC Petrel 101.8 12x2.34 7x2.34 51.61 30.10 81.71 11.7 143 235 378 5.5 5.5 4699 46.08 0.5595

08---AB105.6SRC Raven 105.6 6x3.37 1x3.37 53.52 8.92 62.44 10.11 147 69 216 1.8 1.8 1987 19.49 0.5343

08---AB110.8SRC Minorca 110.8 12x2.44 7x2.44 56.11 32.73 88.84 12.2 155 256 411 6.0 6.0 5110 50.11 0.5146

08---AB133.1SRC Quail 133.1 6x3.78 1x3.78 67.33 11.22 78.55 11.34 185 87 272 2.2 2.2 2401 23.55 0.4247

08—AB134.6SRC Leghorn 134.6 12x2.69 7x2.69 68.2 39.78 108 13.45 189 311 500 7.3 7.3 6164 60.44 0.4234

08---AB159SRC Guinea 159.0 12x2.92 7x2.92 80.36 46.88 127.2 14.6 223 367 590 8.6 8.6 7236 70.96 0.3595

08---AB167.8SRC Pigeon 167.8 6x4.25 1x4.25 85.12 14.19 99.31 12.75 234 110 344 2.8 2.8 3006 29.48 0.3359

08---AB176.9SRC Dotterel 176.9 12x3.08 7x3.08 89.41 52.15 141.6 15.40 248 408 656 9.6 9.6 7844 76.92 0.3230

08---AB190.8SRC Dorking 190.8 12x3.2 7x3.2 96.51 56.30 152.8 16.0 267 440 707 10.0 10.0 8468 83.04 0.2992

08—AB203.2SRC Brahma 203.2 16x2.86 19x2.48 102.8 91.78 194.6 18.12 285 721 1006 19.0 19.0 12871 126.2 0.2809

08---AB211.3SRC Cochin 211.3 12x3.37 7x3.37 107 62.44 169.4 16.85 296 488 784 12.0 12.0 9391 92.09 0.2699

08---AB211.6SRC Penguin 211.6 6x4.77 1x4.77 107.2 17.87 125.1 14.31 294 139 433 3.5 3.5 3787 37.14 0.2667

08---AB266.8SRC Waxwing 266.8 18x3.09 1x3.09 135 7.5 142.5 15.45 372 58 430 1.5 10 3118 30.58 0.2129

08---AB266.8SRC Owl 266.8 6x5.36 7x1.79 135.4 17.62 153 16.09 371 138 509 3.2 3.2 4406 43.21 0.2112

08---AB266.8SRC Partridge 266.8 26x2.57 7x2.0 134.9 21.99 156.9 16.28 374 172 546 4.0 15 5113 50.14 0.2141

08—AB300SRC Ostrich 300 26x2.73 7x2.12 152.2 24.71 176.9 17.28 422 193 615 4.5 17 5756 56.45 0.1897

08---AB336.4SRC Merlin 336.4 18x3.47 1x3.47 170.2 9.46 179.7 17.35 469 74 543 1.9 12 3931 38.55 0.1688

08---AB336.4SRC Linnet 336.4 26x2.89 7x2.25 170.6 27.83 198.4 18.31 473 217 690 5.1 19 6413 62.89 0.1693

08---AB336.4SRC Oriole 336.4 30x2.69 7x2.69 170.5 39.78 210.3 18.83 474 311 785 7.3 22 7866 77.14 0.1698

08---AB397.5SRC Chickadee 397.5 18x3.77 1x3.77 200.9 11.16 212.1 18.85 554 87 641 2.2 14 4500 44.13 0.1430

08---AB397.5SRC Brant 397.5 24x3.27 7x2.18 201.6 26.13 227.7 19.62 559 204 763 4.8 21 6645 65.16 0.1432

08—AB397.5SRC Ibis 397.5 26x3.14 7x2.44 201.3 32.73 234 19.88 558 256 814 6.0 23 7378 72.35 0.1434

08---AB397.5SRC Lark 397.5 30x2.92 7x2.92 200.9 46.88 247.8 20.44 558 367 925 8.6 26 9203 90.25 0.1441

08---AB477SRC Pelican 477 18x4.14 1x4.14 242.3 13.46 255.8 20.7 668 105 773 2.7 17 5347 52.43 0.1186

08---AB477SRC Flicker 477 24x3.58 7x2.39 241.6 31.4 273 21.49 669 245 914 5.8 25 7791 76.4 0.1195

08---AB477SRC Hawk 477 26x3.44 7x2.67 241.6 39.19 280.8 21.77 669 306 975 7.2 29 8844 86.73 0.1195

08---AB477SRC Hen 477 30x3.2 7x3.2 241.3 56.3 297.6 22.4 670 440 1110 10 31 10784 105.75 0.1200

08—AB556.5SRC Osprey 556.5 18x4.47 1x4.47 282.5 15.69 298.2 22.35 779 122 901 3.1 20 6233 61.12 0.1017

08—AB556.5SRC Parakeet 556.5 24x3.87 7x2.58 282.3 36.6 318.9 23.22 782 286 1068 6.7 29 9000 88.26 0.1023

08—AB556.5SRC Dove 556.5 26x3.72 7x2.89 282.6 45.92 328.5 23.55 783 359 1142 8.4 32 10260 100.62 0.1022

08—AB556.5SRC Eagle 556.5 30x3.46 7x3.46 282.1 65.82 347.9 24.22 783 515 1298 12 36 12607 123.63 0.1026

5- Aluminum Conductor Steel Reinforced (ACSR)

Page 17: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

17www.cableco.com.jo

5- Aluminum Conductor Steel Reinforced (ACSR)

Conductor: Hard Drawn Aluminum Conductor Steel Reinforced

Standard: ASTM B 232:1986

Cable Code

Code

Nam

e

Cond

ucto

rAr

ea

ConductorConstruction Actual Area

Cond

ucto

r Dia

met

er Conductor Weight

Calculated Breaking Load

Calc

ulat

ed

Resi

stan

ce a

t 20º

C

Ungreased Grease

Alum

inum

Stee

l

Alum

inum

Stee

l

Tota

l

Alum

inum

Stee

l

Tota

l

Stee

l Onl

y

All i

nner

la

yers

MCM

No.

x m

m

No.

x m

m

mm

²

mm

²

mm

²

mm

Kg/K

m

Kg/K

m

Kg/K

m

Kg/K

m

Kg/K

m

Kgf KN

Ohm

/Km

08---AB605SRC Peacock 605 24x4.03 7x2.69 306.1 39.78 345.9 24.19 848 311 1159 7.3 32 9771 95.82 0.09434

08—AB605SRC Squab 605 26x3.87 7x3.01 305.8 49.81 355.6 24.51 847 389 1236 9.1 34 11019 108.06 0.09443

08---AB605SRC Wood Duck 605 30x3.61 7x3.61 307.1 71.65 378.8 25.27 853 560 1413 13.0 39 13140 128.86 0.09426

08---AB605SRC Teal 605 30x3.61 19x2.16 307.1 69.62 376.7 25.24 853 545 1398 14.0 40 13568 133.06 0.09426

08---AB636SRC Kingbird 636 18x4.78 1x4.78 323.0 17.95 341 23.9 891 140 1031 3.6 23 7128 69.9 0.08896

08---AB636SRC Rook 636 24x4.14 7x2.76 323.1 41.88 365 24.84 891 327 1218 7.7 34 10299 101.0 0.08937

08---AB636SRC Grosbeak 636 26x3.97 7x3.09 321.8 52.49 374.3 25.15 892 410 1302 9.6 36 11428 112.07 0.08973

08—AB636SRC Scoter 636 30x3.7 7x3.7 322.6 75.26 397.9 25.9 896 588 1484 14.0 41 13803 135.36 0.08973

08---AB636SRC Egret 636 30x3.7 19x2.22 322.6 73.54 396.1 25.9 896 576 1472 22.0 69 14304 140.27 0.08973

08---AB636SRC Swift 636 36x3.38 1x3.38 323 8.97 382 23.66 891 70 961 1.8 35 6253 61.32 0.08896

08---AB666.6SRC Flamingo 666.6 24x4.23 7x2.82 337.3 43.72 381 25.38 935 342 1277 8.0 35 10752 105.44 0.08561

08---AB666.6SRC Gannet 666.6 26x4.07 7x3.16 338.3 54.9 393.2 25.76 937 429 1366 10.1 38.0 11978 117.46 0.08536

08---AB715.5SRC Stilt 715.5 24x4.39 7x2.92 363.3 46.88 410.2 26.32 1007 366 1373 8.6 38 11554 113.31 0.07948

08—AB715.5SRC Starling 715.5 24x4.21 7x3.28 361.9 59.15 421.1 26.68 1003 462 1932 11.0 41 12865 126.16 0.07979

08---AB715.5SRC Redwing 715.5 30x3.92 19x2.35 362.1 82.41 444.5 27.43 1006 645 1651 17.0 48 15650 153.47 0.07994

08---AB795SRC Tern 795 45x3.38 7x2.25 403.8 27.83 431.6 27.03 1119 217 1336 5.1 51 10027 98.33 0.07151

08---AB795SRC Condor 795 54x3.08 7x3.08 402.3 52.15 454.5 27.72 1115 407 1522 9.6 57 12771 125.24 007178

08---AB795SRC Cuckoo 795 24x4.62 7x3.08 402.3 52.15 454.5 27.72 1115 407 1522 9.6 42 12650 124.05 0.07178

08—AB795SRC Drake 795 26x4.44 7x3.45 402.6 65.44 468 28.11 1115 511 1626 12.0 45 14267 139.91 0.07172

08---AB795SRC Coot 795 36x3.77 1x3.77 401.9 11.16 413.1 26.39 1108 87 1195 2.2 43 7580 74.33 0.07150

08---AB795SRC Mallard 795 30x4.14 19x2.48 403.8 91.78 495.6 28.96 1121 718 1839 19.0 53 17439 171.02 0.07169

08---AB900SRC Ruddy 900 45x3.59 7x2.4 455.5 31.67 487.2 28.74 1262 247 1509 5.8 58 11094 108.79 0.06339

08---AB900SRC Canary 900 54x3.28 7x3.28 456.3 59.15 515.5 29.52 1264 462 1726 11.0 65 14484 142.04 0.06328

08---AB954SRC Rail 954 45x3.7 7x2.47 483.8 33.54 517.3 29.61 1340 262 1602 6.2 62 11772 115.44 0.05969

08—AB954SRC Catbird 954 36x4.14 1x4.14 484.6 13.46 498.1 28.98 1336 105 1441 2.7 52 8986 88.12 0.05930

08---AB954SRC Cardinal 954 54x3.38 7x3.38 484.5 62.81 547.3 30.42 1342 490 1832 12.0 69 15381 150.84 0.05960

08--AB1033.5SRC Ortlan 1033.5 45.x3.85 7x2.57 523.9 36.31 560.2 30.81 1452 284 1736 6.7 67 12578 123.35 0.05512

08---A1033.5SRC Tanager 1033.5 36x4.3 1x4.3 522.8 14.52 537.3 30.10 1441 113 1554 2.9 56 9694 95.06 0.05496

08--AB1033.5SRC Curlew 1033.5 54x3.51 7x3.51 522.5 67.73 590.2 31.59 1448 529 1977 12.0 75 16586 162.65 0.05527

08---AB1133SRC Bluejay 1133 45x4.0 7x2.66 565.5 38.90 604.4 31.98 1567 304 1871 7.1 71 13540 132.78 0.05106

08—AB1133SRC Finch 1133 54x3.65 19x2.19 565 71.57 636.6 32.85 1573 560 2133 15.0 82 17748 174.05 0.05136

08--AB1192.5SRC Bunting 1192.5 45x4.14 7x2.76 605.8 41.88 647.7 33.12 1678 327 2005 7.7 77 14531 142.5 0.04767

08--AB1192.5SRC Grackle 1192.5 54x3.77 19x2.27 602.8 76.89 679.7 33.97 1678 602 2280 16.0 88 19001 186.34 0.04814

08---AB1272SRC Bittern 1272 45x4.27 7x2.85 644.4 44.66 689.1 34.17 1785 349 2134 8.2 82 15471 151.72 0.04481

08---AB1272SRC Pheasant 1272 54x3.9 19x2.34 645.1 81.71 726.8 35.10 1796 640 2436 17.0 93 19789 194.06 0.04498

08---AB1272SRC Skylark 1272 36x4.78 1x4.78 646 17.95 664 33.46 1781 140 1921 3.6 69 11978 117.46 0.04448

08--AB1351.5SRC Dipper 1351.5 45x4.4 7x2.93 684.2 47.2 731.4 35.19 1896 369 2265 8.7 87 16380 160.63 0.04220

08--AB1351.5SRC Martin 1351.5 54x4.02 19x2.41 685.4 86.67 772.1 36.17 1908 678 2586 18.0 99 21008 206.02 0.04234

08—AB1431SRC Bobolink 1431 45x4.53 7x302 752.3 50.14 802.4 36.24 2084 392 2476 9.2 92 17398 170.62 0.03838

08—AB1431SRC Plover 1431 54x4.14 19x2.48 726.9 91.78 818.7 37.24 2024 718 2742 19.0 105 22264 218.33 0.03992

08--AB1510.5SRC Nuthatch 1510.5 45x4.65 7x3.10 764.2 52.83 817 37.20 2117 413 2530 9.7 97 18153 178.02 0.03779

08--AB1510.5SRC Parrot 1510.5 54x4.25 19x2.55 766.1 97.03 863.1 38.25 2133 759 2892 20.0 111 23500 230.46 0.03788

08---AB1590SRC Lapwing 1590 45x4.78 7x3.18 807.5 55.60 863.1 38.22 2237 434 2671 10.0 102 19154 187.84 0.03576

08---AB1590SRC Falcon 1590 54x4.36 19x2.62 806.2 102.4 908.6 39.26 2245 801 3046 21.0 117 24770 242.91 0.03599

Page 18: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

18 www.cableco.com.jo

6- Aerial Bundled Cable (ABC) or Twisted Cable

Description: This type of cable consists of two to four insulated cores of Aluminum conductors twisted around bare or insulated Aluminum Alloy Conductor (Messenger) and consist of following construction.

Phase Conductors: Hard Drawn Aluminum Conductor insulated by black weather resistant polyethylene, XLPE or PVC

Lighting Conductor: Hard Drawn Aluminum Conductor insulated by black weather resistant polyethylene, XLPE or PVC

Messenger Conductor: Hard Drawn Aluminum Conductor Bare or insulated by black weather resistant polyethylene, XLPE or PVC and it is also Neutral Conductor

Standard: NFC 33-209

Cable Code

Cable Size Phase Conductor Messenger Conductor Lighting Conductor CompleteCable

No. x Size No. x Size InsulationThickness No. x Size Insulation

Thickness No. x Size InsulationThickness

Overall Diameter

No. x mm² No. x mm² mm No. x mm² mm No. x mm² mm mm

04035NF1X16+16SCC 1X16+16 1X16 1.2 16 1.2 - - 15.05

04037NF2X16+16SCC 2X16+16 2X16 1.2 16 - - - 19.6

04042NF3X16+16SCC 3X16+16 3X16 1.2 16 - - - 19.6

04041NF3X25+25SCC 3X25+25 3X25 1.4 25 1.4 - - 27.15

04041NF3X35+25SCC 3X35+25 3X35 1.6 25 1.4 - - 30.15

04038NF3X50+25+35SCC 3X50+25+35 3X50 1.6 35 1.4 25 1.4 33.65

04038NF3X70+35+70SCC 3X70+35+70 3X70 1.8 70 1.5 35 1.6 40.75

04039NF3X95+25+70SCC 3X95+25+70 3X95 1.8 70 1.6 25 1.4 43.9

04038NF3X120+50+70SCC 3X120+50+70 3X120 1.8 70 1.5 50 1.6 47.0

04040NF3X70+16+50SCC 3X70+16+50 3X70 1.4 50 1.2 16 1.4 37.1

04040NF3X95+16+70SCC 3X95+16+70 3X95 1.4 70 1.2 16 1.4 42.15

04040NF3X120+16+70SCC 3X120+16+70 3X120 1.6 70 1.2 16 1.4 45.85

Page 19: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

19www.cableco.com.jo

7- Technical Information

7.1-Characteristic of Conductor Metals

Units Aluminum AL AlloyGalvanized

SteelAluminumClad Steel

Hard Copper

AnnealedCopper

Conductivity %IACS 61 53 9 20 97.16 100

Volume Resistivity @ 20 ºC Ω/m x10 -6 0.028264 0.0325 0.192 0.0848 0.01774 0.01724

Resistance Ω/mm².Km 28.264 32.5 192 84.8 17.74 17.241

Temperature Coefficient of Resistance @ 20 Per ºC ---- 0.00403 0.0036 0.0054 0.0051 0.00382 0.00393

Coefficient of Linear Expansion Per ºC x10- 6 23 23 11.5 12.96 17.0 17.0

Density @ 20 ºC Kg/m³ 2703 2700 7800 6590 8900 8900

Weight Kg/mm².Km 2.703 2.7 7.8 6.59 8.9 8.9

Ultimate Tensile Strength N/ mm² 160-200 295 1330-1700 1100-1344 445-460 230-260

Modulus of Elasticity N/ mm² x10³ 70 70 200 162 100 ---

Page 20: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

20 www.cableco.com.jo

7.2- Practical Final Modulus of Elasticity and Coefficient of Linear Expansion for Conductors

- All Aluminum Conductors (AAC)

No. of Stranding Practical FinalModulus of Elasticity

Coefficient of Linear Expansion @ 20 ºC

N/ mm² Kg/ mm² X 10 - 6/ ºC

3 62000 6322 23

7 58850 6000 23

19 55900 5700 23

37 55900 5700 23

61 53950 5500 23

91 53950 5500 23

127 50500 5150 23

- All Aluminum Alloy Conductors (AAAC)

No. of Stranding Practical FinalModulus of Elasticity

Coefficient of Linear Expansion @ 20 ºC

N/ mm² Kg/ mm² X 10 - 6/ ºC

7 58850 6000 23

19 55900 5700 23

37 55900 5700 23

61 53950 5500 23

91 53950 5500 23

127 50500 5150 235150

Page 21: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

21www.cableco.com.jo

- Aluminum Conductor Steel Reinforced (ACSR)

No. of Stranding Practical FinalModulus of Elasticity

Coefficient of Linear Expansion @ 20 ºC

N/ mm² Kg/ mm² X 10 - 6/ ºC

6/1 79400 8096 19.1

7/1 82870 8450 17.7

8/1 98000 9993 16.9

18/1 66000 6730 21.2

36/1 59820 6100 22.0

9/3 88300 9004 17.0

6/7 75500 7699 19.8

7/7 78460 8000 18.4

12/7 104950 10702 15.3

14/7 107900 11003 15.0

24/7 72570 7400 19.6

26/7 75510 7700 18.9

30/7 80420 8200 17.8

45/7 61000 6220 20.9

48/7 62000 6322 20.5

54/7 68650 7000 19.3

72/7 60000 6118 21.7

14/19 109840 11200 15.0

16/19 117700 12002 14.2

30/19 78460 8001 18.0

32/19 80420 8200 17.5

36/19 79040 8060 16.9

54/19 66690 6800 19.4

66/19 66500 6781 18.3

76/19 60800 6200 21.25

84/19 63750 6500 20.6

20+42/19 76500 7800 18.4

54+66/19 78460 8000 18.0

Page 22: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

22 www.cableco.com.jo

7.3- Indicative Current Ratings of Overhead Conductors-(Approximate estimation)

Nominal Cross Section of Copper

or Aluminum Conductor

Nominal Cross Section of ACSR Conductor

AL/SteelCopper Conductor Aluminum Conductor ACSR Conductor

mm² mm²/ mm² Ampere Ampere Ampere

10 -- 90 --- ---

16 16/2.5 125 110 90

25 25/4.0 160 145 125

35 35/6.0 200 180 145

50 50/8.0 250 225 170

70 70/12 310 270 290

95 95/15 380 340 350

120 120/20 440 390 410

--- 125/30 --- --- 425

150 150/25 510 455 470

--- 170/40 --- --- 520

185 185/30 585 520 535

--- 210/35 --- --- 590

--- 210/50 --- --- 610

--- 230/30 --- --- 630

240 240/40 700 625 645

--- 265/35 --- --- 680

300 300/50 800 710 740

--- 305/40 --- --- 740

--- 340/30 --- --- 790

--- 380/50 --- --- 840

--- 385/35 --- --- 850

400 --- 960 855 ---

--- 435/55 --- --- 900

--- 450/40 --- --- 920

--- 490/65 --- --- 960

500 --- 1110 990 ---

--- 550/70 --- --- 1020

--- 560/50 --- --- 1040

625 --- --- 1140 ---

--- 680/85 --- --- 1150

800 --- --- 1340 ---

1000 --- --- 1540 ---

* Indicative Value for 50/60 HZ with wind-speed of 0.6 m/s and ambient temperature 20/35 ºC and when there is no air turbulence, the value should be reduced by 30%.

Page 23: CABLECO · ... AAAC, and ACSR) can be insulated for the same ... low strength to weight ratio of all-aluminum conductor ... Conductor Weight Calculated Breaking Load Calculated ...

23www.cableco.com.jo

Due to the wide range of cables in the catalogue, it is advisable, when ordering, to provide as much information as possible, please use the following information as a guide.

Ordering Guide

The following details will ensure that your enquiries and orders will be achieved quickly and efficiently:

1- Length of cables and individual drum lengths.

2- Voltage designation.

3- Relevant British or International Standard.

4- Number of Cores.

5- Conductor Size.

6- Type of Insulation.

7- Type of Bedding.

8- Type of Armouring.

9- Type of Outer Sheathing.

10- Any Other Special Requirements, e.g. Special Insulation or Sheath Material, etc.

Technical ServiceSpecialist advice and assistance on all matters, you can contact us on:

National Cable and Wire Manufacturing Company (CABLECO)

P.O.Box 927104, Amman-Jordan

Tel : 962-6-5511484 / 962-6-5511867 Fax: 962-6-5532081

E-mail: [email protected]

[email protected]

Website: www.cableco.com.jo