Date post: | 02-Apr-2015 |
Category: |
Documents |
Upload: | aaliyah-hawthorne |
View: | 214 times |
Download: | 1 times |
© ABB Group April 11, 2023 | Slide 1
SWEDE 2009 Conference2010 National Efficiency Standards
Wes Patterson, ABB Transformers North America, May 8, 2009
Over $4.5 billion orders
15,000 employees
Global manufacturing capability: 57 plants
Global presence: revenues in more than 100 countries
Complete range of power and distribution transformers, associated products and services
Voltage range up to 800 kV (1000 kV)
Homepage: www.abb.com/transformers
ABB Transformers (2007 data)
© ABB Group April 11, 2023 | Slide 3
One Global Factory serving customers everywhere with a full range of products
Wherever located, you have one transformer specialist close to you, for you
Wherever your project is, we will produce your transformers in the factory most suitable to you
57 Transformer Factories in 30 countries
© ABB Group April 11, 2023 | Slide 4
World Map ABB Transformer Factories 2007World Map ABB Transformer Factories 2007
South Korea – Chonan-si
USA – South Boston
USA - Jefferson City
USA – Bland
Peru – Lima
Columbia – Pereira
South Africa – Cape Town
South Africa – Booysens
South Africa – Pretoria
Tanzania – Arusha
Egypt – 10th of Ramadan
Saudi Arabia – Riyadh
Ireland – Waterford
Spain – Zaragosa
Finland – Vaasa
Poland – Lodz
Sweden – LudvikaNorway – Steinkjer
Germany – Brilon
Italy– Monselice
Turkey– Istanbu
China– Hefei
China– Shanghai
Vietnam – Hanoi
Singapore – Singapore
New Zealand – New Plymouth
Sweden – PiteaNorway – Drammen
Russia – Khotkovo
Sweden – Mjolby
Sweden – FigeholmGermany – Bad Honnef
Germany – Roigheim
Italy– LegnanoGermany – Halle
Switzerland – Geneve
Spain – Bilbao
Spain – Cordoba
China– Chongquing
China– Zhongshan
Thailand – Bangkok
USA – Alamo
USA – St Louis
Canada – Varennes
India – Baroda
Brazil – Guarulhos
Brazil – Blumenau
Canada – Quebec City
Australia – Darra
Australia – Perth
Australia – Moorebank
Switzerland – Zurich
© ABB Group April 11, 2023 | Slide 5
Jefferson CitySt. Louis
Alamo
PPI-Athens
Bland
Varennes
Quebec
South Boston
Transformer Factories in North America
© ABB Group April 11, 2023 | Slide 6
The largest Transformer manufacturer worldwide
ABB delivers :
2.000 Power Transformers / y
500.000 Distribution Transformers / y
2,5%
2,8%
4,0%
5,0%
9,0%
21,0%
2,0%CGL-PAUWELS
WAUKESHA
HOWARD
SCHNEIDER
AREVA
SIEMENS-VATECH
ABB
Leader in Transformers Business
© ABB Group April 11, 2023 | Slide 7
What ever you need from our broad portfolio -> ABB is your “one-stop” supplier
Complete Transformer Portfolio
IEC & ANSI standards
© ABB Group April 11, 2023 | Slide 8
IEC & ANSI Standards
Distribution Transformers
© ABB Group April 11, 2023 | Slide 9
System System transformerstransformers
Generator Step-Generator Step-Up transformersUp transformers
Power Transformers
© ABB Group April 11, 2023 | Slide 10
Agenda
Describe the new efficiency standards for distribution transformers for use in or shipped into the United States and its territories that will be effective January 1, 2010
Review the standard’s development process as well as the scope of transformers that are effected
Discuss design strategies and associated cost impact of those strategies
Address the methodologies for insuring conformance with the standards by the manufacturers
© ABB Group April 11, 2023 | Slide 11
Agenda
Describe the new efficiency standards for distribution transformers for use in or shipped into the United States and its territories that will be effective January 1, 2010
Review the standard’s development process as well as the scope of transformers that are effected
Discuss design strategies and associated cost impact of those strategies
Address the methodologies for insuring conformance with the standards by the manufacturers
© ABB Group April 11, 2023 | Slide 12
National Efficiency Standard – Where did it come from
Energy Policy Act of 1975
Empowers the Secretary of Energy to determine the need for energy efficiency standards
Establishes definition of “States” that includes US Territories and Possessions
Energy Policy and Conservation Act (EPACT) of 1992
Empowers the DOE to determine the need for energy efficiency standards for Appliances and Commercial
Technologically feasible
Economically justifiable
Produces significant energy savings
Puts the spot light on all distribution transformers
Oak Ridge National Laboratory (ORNL) study initiated
© ABB Group April 11, 2023 | Slide 13
National Efficiency Standard – Where did it come from
1997 DOE publishes Notice of Determination
Technologically feasible
Economically justifiable
Significant energy saving
2000 DOE publishes it’s Framework for establishing a standard
2004 DOE publishes it’s Advance Notice of Proposed Rulemaking (ANOPR)
2006 DOE publishes Notice of Proposed Rulemaking (NOPR)
Technical Support Documents (TSD’s)
Analytical Spreadsheets
2007 Final Rule issued on October 12th (72 FR 58190)
© ABB Group April 11, 2023 | Slide 14
DOE Web Site
http://www1.eere.energy.gov/buildings/appliance_standards/
© ABB Group April 11, 2023 | Slide 15
The National Efficiency Standard
Liquid & Dry Distribution Transformers
Domestic and Imported production
Manufactured in or imported into the United States and its territories* on or after Jan 1, 2010
Product – ABB Operational Impact: Overhead – Athens Pads, Secondary Unit Subs & Networks
– Jefferson City & South Boston Dry Type - Bland
Industry Impact: Utility Industrial Construction
* Note: Applies to Puerto Rico, Guam, and all other territories and possessions
10 CFR Part 431 Subpart K October 12, 2007
72 FR 58190
CFR = Code of Federal Regulation
© ABB Group April 11, 2023 | Slide 16
The National Efficiency Standard
Liquid & Dry Transformers
60 Hz, < 34.5 kV Input & < 600 V Output
Oil-filled Capacity 1Φ 10 to 833 kVA 3Φ 15 to 2500 kVA
Dry-type Capacity
20-45 kV BIL : 15 to 833 (1Φ) & 2500 (3Φ) kVA
46-95 kV BIL : 15 to 833 (1Φ) & 2500 (3Φ) kVA
> 95kV BIL : 75 to 833 (1Φ) & 225 to 2500 (3Φ) kVA
© ABB Group April 11, 2023 | Slide 17
National Standard - Transformer Exclusions
Autotransformer
Drive (isolation)
Grounding
Machine-tool (control)
Non-ventilated
Rectifier
Regulating
Sealed
Special Impedance*
Step-up Transformers
Testing
Tap range > 20%
Uninterruptible power supply
Welding
* Note: Standard Impedances
© ABB Group April 11, 2023 | Slide 18
The National Efficiency Standard
Re-builders exempt unless found to be circumventing the “spirit” of the standard
Inventories manufactured before start date can be sold after the start date however…
Inventory build up in advance of the start date also seen as circumventing the “spirit” of the standard
DOE forewarning manufacturers not to take steps to side-step the National Efficiency Standard
© ABB Group April 11, 2023 | Slide 19
Benefits – 95 BIL Ventilated Dry Type Example
kVA Typical TSL1 DOE % Watts Annual Savings Add Price Pay Back Yrs15 94.50% 96.80% 97.19% 48.91% 219 192$ 36$ 0.230 95.40% 97.30% 97.63% 48.48% 363 318$ 71$ 0.245 96.00% 97.60% 97.86% 46.50% 454 398$ 107$ 0.375 97.00% 97.90% 98.20% 40.00% 488 428$ 179$ 0.4
112.5 97.20% 98.10% 98.30% 39.29% 671 588$ 268$ 0.5150 97.50% 98.20% 98.42% 36.80% 749 656$ 357$ 0.5225 97.80% 98.40% 98.57% 35.00% 940 823$ 536$ 0.7300 98.10% 98.50% 98.67% 30.00% 928 813$ 715$ 0.9500 98.50% 98.80% 98.83% 22.00% 895 784$ 829$ 1.1750 98.80% 98.90% 98.95% 12.50% 610 535$ 1,138$ 2.1
1000 98.82% 99.00% 99.03% 17.80% 1139 998$ 2,382$ 2.41500 98.95% 99.00% 99.12% 16.19% 1383 1,212$ 2,988$ 2.52000 98.97% 99.20% 99.13% 15.53% 1736 1,521$ 3,147$ 2.12500 99.10% 99.20% 99.23% 14.44% 1763 1,544$ 3,934$ 2.5
Efficiency (%)
Dry-Type Medium Voltage Three Phase (46-95 kV BIL)Loss Reduction DOE to Typical $$$$
Notes: 1. Efficiency and Losses at 50% Load and PF=1.02. Savings assumes 8760 h/yr and $0.10/watt
© ABB Group April 11, 2023 | Slide 20
National Benefits of The National Energy Standard
Saves 2.74 quads (1015 BTU’s) of energy over 29 years 1 Quad = 1 Quadrillion (1015) Btu (1,000,000,000,000,000)
Energy of 27 million US households in a single year
Eliminating need for 6 new 400 MW power plants
Reduce greenhouse gas emission of ~238 million tons of CO2
Equivalent to removing 80% of all light vehicles for one year
Others emission reductions not included in final justification
Greater than 46 thousand tons (kt) of nitrous oxide (NO2)
Greater than 4 tons of mercury (Hg)
Payback ranges from 1 to 15 years based on design line Net present value of $1.39 billion using a 7% discount rate
Net present value of $7.8 billion using a 3% discount rate
Cumulative from 2010 to 2073 in 2006$
© ABB Group April 11, 2023 | Slide 21
Consumer Benefits
Increased system capacity due to lower loads
Lower input load requirements leads to less heat generated Lower A/C & ventilation costs/requirements if located indoors
Lower temperature rise
Longer transformer life expectancy
May not need use of forced air (FA) to fulfill capacity requirements
Better efficiency means less input energy required to produce equal output energy
Decreased operating costs = increased profits
Decreased environmental impact from input energy generation emissions
Shorter payback period due to increased profits Lower total ownership costs over the life of the transformer
© ABB Group April 11, 2023 | Slide 24
Electronic Code of Federal Regulations
http://ecfr.gpoaccess.gov/cgi/t/text/text-idx?c=ecfr&tpl=/ecfrbrowse/Title10/10cfr431_main_02.tpl
© ABB Group April 11, 2023 | Slide 25
Agenda
Describe the new efficiency standards for distribution transformers for use in or shipped into the United States and its territories that will be effective January 1, 2010
Review the standard’s development process as well as the scope of transformers that are effected
Discuss design strategies and associated cost impact of those strategies
Address the methodologies for insuring conformance with the standards by the manufacturers
© ABB Group April 11, 2023 | Slide 26
The Oak Ridge Study
Design LinesCombination Lines
44,000+ Designs evaluated
© ABB Group April 11, 2023 | Slide 31
National Efficency Standard impact on Total Owning Cost (TOC) relative to TSL0
0
1
2
3
4
5
6
7
8
9
0 1 2 3 4 5 6 7 8 9 10
"A" values (core loss evaluation) $/watt
"B"
va
lue
s (
co
il l
os
s e
va
lua
tio
n)
$/w
att
> 1.25
≤ 1.25
≤ 1.15
≤ 1.05
≤ 1
TOC Variation relative to TSL0
Liquid-Filled 1ph 10-167 kVA Pad
RectTank
RoundTank
101525
37.55075100167250333500667833
kVA
Liq-1phPC1
DL
1
DL
2D
L 3
RU
RU
RU
RU
Max: 1.33
© ABB Group April 11, 2023 | Slide 33
Evolution of a National Standard
DOE publishes Notice of Proposed Rulemaking (NOPR)
Defined 6 levels of efficiency – August 4, 2006
TSL1 = NEMA TP1
TSL2 = 1/3 difference between TSL1 and TSL4
TSL3 = 2/3 difference between TSL1 and TSL4
TSL4 = minimum LCC (Life Cycle Cost)
TSL5 = maximum efficiency with no change in the LCC
TSL6 = theoretical maximum possible efficiency
Recommended that TSL2 become the National Standard
Set Sep 2007 target for establishing the Final Rule
Solicited comments from concerned parties
TSL = Trial Standard Level
© ABB Group April 11, 2023 | Slide 34
Transition between NOPR to Final Rule
DOE received numerous comments to liquid-filled
Technical discrepancy in liquid 3Φ curves
3-1Φ would be less efficient than one equivalent 3Φ liquid
DOE resolution creates 4 new efficiency levels for liquid called Design Lines (DL) combining TSL levels:
TSLA: DL1-TSL5 & DL3-TSL4
TSLB: DL4-TSL2 & DL5-TSL4
TSLC: DL4-TSL2 & DL5-TSL3
TSLD: DL1-TSL4, DL3-TSL2, DL4-TSL2 & DL5-TSL3
© ABB Group April 11, 2023 | Slide 35
NOPR Liquid-Filled 3Φ Discontinuity
NOPR Liquid-Filled Three Phase
96.5%
97.0%
97.5%
98.0%
98.5%
99.0%
99.5%
100.0%
15 30 45 75 112.5 150 225 300 500 750 1000 1500 2000 2500
kVA
Eff
icie
ncy
0-Min
0-Avg
TSL1
TSL2
TSL3
TSL4
TSL5
TSL6
The efficiency of the 300/500 kVA being more than the 750/1000/1500 kVA’s would artificially disrupt the markets of the 300/500 kVA units
© ABB Group April 11, 2023 | Slide 40
Final Rule – The National Standard
Final Rule Published Oct 12, 2007
Federal Register - 72 FR 58190
DOE Final Selection
TSLC for 1Φ and 3Φ Liquid-filled
TSL2 for Dry-types
Liquid and dry-type distribution transformers manufactured in or imported into the United States and its territories on or after Jan 1, 2010
© ABB Group April 11, 2023 | Slide 41
National Standard - Liquid-filledDesignLine KVA
AveBaseCaseEff
MinBaseCaseEff TP1
1/3 DiffbetweenTP1 andMin LCC
2/3 DiffbetweenTP1 andMin LCC Min LCC
Max EnergySavings withNo Changein LCC
MaxEnergySavings C
ombi
natio
n of
DL1
-TS
L5 a
ndD
L3-T
SL4
Com
bina
tion
ofD
L4-T
SL2
and
DL5
-TS
L4
Com
bina
tion
ofD
L4-T
SL2
and
DL5
-TS
L3
Com
bina
tion
ofD
L1-T
SL4
, D
L4-
TS
L2D
L3-T
SL2
, D
L5-
KVA 0-Avg 0-Min 1 2 3 4 5 6 Standard A B C D5
10 98.42% 97.77% 98.40% 98.40% 98.44% 98.48% 98.69% 99.32% 98.62% 98.79% 98.62% 98.62% 98.48%15 98.57% 97.99% 98.60% 98.56% 98.59% 98.63% 98.82% 99.39% 98.76% 98.91% 98.76% 98.76% 98.63%
DL2 25 98.74% 98.23% 98.70% 98.73% 98.76% 98.79% 98.96% 99.46% 98.91% 99.04% 98.91% 98.91% 98.79%37.5 98.86% 98.40% 98.80% 98.85% 98.88% 98.91% 99.06% 99.51% 99.01% 99.13% 99.01% 99.01% 98.91%
DL1 50 98.97% 98.56% 98.90% 98.90% 98.90% 99.04% 99.19% 99.59% 99.08% 99.19% 99.08% 99.08% 99.04%75 99.04% 98.66% 99.00% 99.04% 99.06% 99.08% 99.21% 99.59% 99.17% 99.27% 99.17% 99.17% 99.08%
100 99.11% 98.75% 99.00% 99.10% 99.12% 99.14% 99.26% 99.62% 99.23% 99.32% 99.23% 99.23% 99.14%167 99.22% 98.90% 99.10% 99.21% 99.23% 99.25% 99.35% 99.66% 99.25% 99.40% 99.32% 99.32% 99.25%250 99.24% 98.89% 99.20% 99.26% 99.36% 99.45% 99.69% 99.70% 99.32% 99.45% 99.37% 99.31% 99.26%333 99.29% 98.97% 99.20% 99.31% 99.40% 99.49% 99.71% 99.72% 99.36% 99.49% 99.41% 99.36% 99.31%
DL3 500 99.36% 99.07% 99.30% 99.38% 99.46% 99.54% 99.74% 99.75% 99.42% 99.54% 99.47% 99.42% 99.38%667 99.40% 99.13% 99.40% 99.42% 99.50% 99.57% 99.76% 99.77% 99.46% 99.57% 99.51% 99.46% 99.42%833 99.44% 99.18% 99.40% 99.45% 99.52% 99.60% 99.77% 99.78% 99.49% 99.60% 99.53% 99.49% 99.45%
KVA 0-Avg 0-Min 1 2 3 4 5 6 Standard A B C D15 98.06% 97.19% 98.10% 98.36% 98.68% 98.68% 99.25% 99.31% 98.36% 98.56% 98.36% 98.36% 98.36%30 98.37% 97.64% 98.40% 98.62% 98.89% 98.89% 99.37% 99.42% 98.62% 98.79% 98.62% 98.62% 98.62%45 98.53% 97.87% 98.60% 98.76% 99.00% 99.00% 99.43% 99.47% 98.76% 98.91% 98.76% 98.76% 98.76%75 98.70% 98.12% 98.70% 98.91% 99.12% 99.12% 99.50% 99.54% 98.91% 99.04% 98.91% 98.91% 98.91%
112.5 98.83% 98.30% 98.80% 99.01% 99.20% 99.20% 99.55% 99.58% 99.01% 99.13% 99.01% 99.01% 99.01%DL4 150 98.91% 98.42% 98.90% 99.08% 99.26% 99.26% 99.58% 99.61% 99.08% 99.19% 99.08% 99.08% 99.08%
225 99.02% 98.57% 99.00% 99.17% 99.33% 99.33% 99.62% 99.65% 99.17% 99.27% 99.17% 99.17% 99.17%300 99.08% 98.67% 99.00% 99.23% 99.38% 99.38% 99.65% 99.67% 99.23% 99.32% 99.23% 99.23% 99.23%500 99.19% 98.83% 99.10% 99.32% 99.45% 99.45% 99.69% 99.71% 99.25% 99.40% 99.32% 99.27% 99.32%750 99.24% 98.97% 99.20% 99.24% 99.31% 99.37% 99.66% 99.66% 99.32% 99.45% 99.37% 99.31% 99.31%
1000 99.29% 99.04% 99.20% 99.29% 99.36% 99.41% 99.68% 99.68% 99.36% 99.49% 99.41% 99.36% 99.36%DL5 1500 99.36% 99.13% 99.30% 99.36% 99.42% 99.47% 99.71% 99.71% 99.42% 99.54% 99.47% 99.42% 99.42%
2000 99.40% 99.19% 99.40% 99.40% 99.46% 99.51% 99.73% 99.73% 99.46% 99.57% 99.51% 99.46% 99.46%2500 99.44% 99.23% 99.40% 99.44% 99.49% 99.53% 99.74% 99.74% 99.49% 99.60% 99.53% 99.49% 99.49%
TSL
TSLProduct Class 2
Table EA.4
Product Class 1Table EA.3
Liquid-Immersed Medium Voltage Three Phase TransformerTSL
TSLLiquid-Immersed Medium Voltage Single Phase Transformer
Note: National Standard Efficiency calculated using load at 50% & PF (COS θ) = 1.0
© ABB Group April 11, 2023 | Slide 42
National Standard - Liquid-filled
Loss Loss
DOE TLS1 Reduction DOE TLS1 Reduction
10 98.62% 98.40% 13.7% 15 98.36% 98.10% 13.7%15 98.76% 98.60% 11.4% 30 98.62% 98.40% 13.7%25 98.91% 98.70% 16.2% 45 98.76% 98.60% 11.4%
37.5 99.01% 98.80% 17.5% 75 98.91% 98.70% 16.2%50 99.08% 98.90% 16.4% 112.5 99.01% 98.80% 17.5%75 99.17% 99.00% 17.0% 150 99.08% 98.90% 16.4%
100 99.23% 99.00% 23.0% 225 99.17% 99.00% 17.0%167 99.25% 99.10% 16.7% 300 99.23% 99.00% 23.0%250 99.32% 99.20% 15.0% 500 99.25% 99.10% 16.7%333 99.36% 99.20% 20.0% 750 99.32% 99.20% 15.0%500 99.42% 99.30% 17.1% 1000 99.36% 99.20% 20.0%667 99.46% 99.40% 10.0% 150 99.42% 99.30% 17.1%833 99.49% 99.40% 15.0% 2000 99.46% 99.40% 10.0%
2500 99.49% 99.40% 15.0%
Efficiency (%) Efficiency (%)
Single-Phase Three-Phase
kVA kVA
Loss Reduction @ 50% Load compared to TLS1 (NEMA TP-1) as the base case
© ABB Group April 11, 2023 | Slide 45
National Standard - Dry-type
KVA 0-Avg 0-Min 1 2 3 4 5 6 Standard
15 98.02% 97.45% 97.60% 98.10% 98.46% 98.81% 99.05% 99.05% 98.10%25 98.26% 97.75% 97.90% 98.33% 98.64% 98.95% 99.17% 99.17% 98.33%
37.5 98.43% 97.97% 98.10% 98.49% 98.77% 99.05% 99.25% 99.25% 98.49%50 98.54% 98.11% 98.20% 98.60% 98.86% 99.12% 99.30% 99.30% 98.60%75 98.68% 98.29% 98.40% 98.73% 98.97% 99.20% 99.37% 99.37% 98.73%
DL9 100 98.77% 98.41% 98.50% 98.82% 99.04% 99.26% 99.41% 99.41% 98.82%167 98.92% 98.60% 98.80% 98.96% 99.16% 99.35% 99.48% 99.48% 98.96%250 99.01% 98.56% 98.90% 99.05% 99.17% 99.27% 99.42% 99.42% 99.07%333 99.08% 98.66% 99.00% 99.11% 99.23% 99.32% 99.46% 99.46% 99.14%
DL10 500 99.17% 98.79% 99.10% 99.20% 99.30% 99.39% 99.51% 99.51% 99.22%667 99.23% 98.87% 99.20% 99.26% 99.35% 99.43% 99.54% 99.54% 99.27%833 99.27% 98.93% 99.20% 99.30% 99.38% 99.46% 99.57% 99.57% 99.31%
KVA 0-Avg 0-Min 1 2 3 4 5 6 Standard
15 97.40% 96.64% 96.80% 97.50% 97.97% 98.44% 98.75% 98.75% 97.50%30 97.81% 97.17% 97.30% 97.90% 98.29% 98.68% 98.95% 98.95% 97.90%45 98.02% 97.45% 97.60% 98.10% 98.46% 98.81% 99.05% 99.05% 98.10%75 98.26% 97.75% 97.90% 98.33% 98.64% 98.95% 99.17% 99.17% 98.33%
112.5 98.43% 97.97% 98.10% 98.49% 98.77% 99.05% 99.25% 99.25% 98.49%150 98.54% 98.11% 98.20% 98.60% 98.86% 99.12% 99.30% 99.30% 98.60%225 98.68% 98.29% 98.40% 98.73% 98.97% 99.20% 99.37% 99.37% 98.73%
DL9 300 98.77% 98.41% 98.60% 98.82% 99.04% 99.26% 99.41% 99.41% 98.82%500 98.92% 98.60% 98.80% 98.96% 99.16% 99.35% 99.48% 99.48% 98.96%750 99.01% 98.56% 98.90% 99.05% 99.17% 99.27% 99.42% 99.42% 99.07%
1000 99.08% 98.66% 99.00% 99.11% 99.23% 99.32% 99.46% 99.46% 99.14%DL10 1500 99.17% 98.79% 99.10% 99.20% 99.30% 99.39% 99.51% 99.51% 99.22%
2000 99.23% 98.87% 99.20% 99.26% 99.35% 99.43% 99.54% 99.54% 99.27%2500 99.27% 98.94% 99.20% 99.30% 99.38% 99.46% 99.57% 99.57% 99.31%
KVA 0-Avg 0-Min 1 2 3 4 5 6 Standard
15 97.46% 96.87% 97.60% 97.86% 98.14% 98.41% 98.54% 98.54% 97.86%25 97.77% 97.24% 97.90% 98.12% 98.36% 98.60% 98.71% 98.71% 98.12%
37.5 97.98% 97.51% 98.10% 98.30% 98.52% 98.73% 98.84% 98.84% 98.30%50 98.12% 97.68% 98.20% 98.42% 98.62% 98.82% 98.92% 98.92% 98.42%75 98.30% 97.90% 98.40% 98.57% 98.75% 98.94% 99.02% 99.02% 98.57%
DL11 100 98.42% 98.05% 98.50% 98.67% 98.84% 99.01% 99.09% 99.09% 98.67%167 98.61% 98.28% 98.80% 98.83% 98.98% 99.13% 99.20% 99.20% 98.83%250 99.02% 98.58% 98.90% 98.95% 99.08% 99.23% 99.42% 99.42% 98.95%333 99.09% 98.68% 99.00% 99.03% 99.15% 99.28% 99.46% 99.46% 99.03%
DL12 500 99.18% 98.81% 99.10% 99.12% 99.23% 99.35% 99.51% 99.51% 99.12%667 99.24% 98.89% 99.20% 99.18% 99.28% 99.40% 99.54% 99.54% 99.18%833 99.28% 98.95% 99.20% 99.23% 99.32% 99.43% 99.57% 99.57% 99.23%
Product Class 5Table EA.5
Product Class 6Table EA.6
Dry-Type Medium Voltage Three Phase Transformer (20-45 kV BIL)
Product Class 7Table EA.7
Dry-Type Medium Voltage Single Phase Transformer (46-96 kV BIL)TSL
TSL
Dry-Type Medium Voltage Single Phase Transformer (20-45 kV BIL)TSL
KVA 0-Avg 0-Min 1 2 3 4 5 6 Standard
15 96.66% 95.88% 96.80% 97.19% 97.55% 97.91% 98.08% 98.08% 97.18%30 97.19% 96.53% 97.30% 97.63% 97.94% 98.24% 98.38% 98.38% 97.63%45 97.46% 96.87% 97.60% 97.86% 98.14% 98.41% 98.54% 98.54% 97.86%75 97.77% 97.24% 97.90% 98.12% 98.36% 98.60% 98.71% 98.71% 98.12%
112.5 97.98% 97.51% 98.10% 98.30% 98.52% 98.73% 98.84% 98.84% 98.30%150 98.12% 97.68% 98.20% 98.42% 98.62% 98.82% 98.92% 98.92% 98.42%225 98.30% 97.90% 98.40% 98.57% 98.75% 98.94% 99.02% 99.02% 98.57%
DL11 300 98.42% 98.05% 98.50% 98.67% 98.84% 99.01% 99.09% 99.09% 98.67%500 98.61% 98.28% 98.80% 98.83% 98.98% 99.13% 99.20% 99.20% 98.83%750 99.02% 98.58% 98.90% 98.95% 99.08% 99.23% 99.42% 99.42% 98.95%
1000 99.09% 98.68% 99.00% 99.03% 99.15% 99.28% 99.46% 99.46% 99.03%DL12 1500 99.18% 98.81% 99.00% 99.12% 99.23% 99.35% 99.51% 99.51% 99.12%
2000 99.24% 98.89% 99.20% 99.18% 99.28% 99.40% 99.54% 99.54% 99.18%2500 99.28% 98.95% 99.20% 99.23% 99.32% 99.43% 99.57% 99.57% 99.23%
KVA 0-Avg 0-Min 1 2 3 4 5 6 Standard
75 98.72% 98.22% 98.40% 98.53% 98.79% 99.05% 99.22% 99.22% 98.53%100 98.81% 98.34% 98.50% 98.63% 98.88% 99.12% 99.28% 99.28% 98.63%167 98.95% 98.54% 98.70% 98.80% 99.01% 99.22% 99.36% 99.36% 98.80%250 99.05% 98.68% 98.80% 98.91% 99.11% 99.30% 99.42% 99.42% 98.91%333 99.12% 98.77% 98.90% 98.99% 99.17% 99.35% 99.46% 99.46% 98.99%500 99.20% 98.89% 99.00% 99.09% 99.25% 99.41% 99.52% 99.52% 99.09%
DL13 667 99.26% 98.97% 99.00% 99.15% 99.30% 99.45% 99.55% 99.55% 99.15%833 99.30% 99.03% 99.10% 99.20% 99.34% 99.48% 99.57% 99.57% 99.20%
KVA 0-Avg 0-Min 1 2 3 4 5 6 Standard
225 98.72% 98.22% 98.40% 98.53% 98.79% 99.05% 99.22% 99.22% 98.53%300 98.81% 98.34% 98.50% 98.63% 98.88% 99.12% 99.28% 99.28% 98.63%500 98.95% 98.54% 98.70% 98.80% 99.01% 99.22% 99.36% 99.36% 98.80%750 99.05% 98.68% 98.80% 98.91% 99.11% 99.30% 99.42% 99.42% 98.91%
1000 99.12% 98.78% 98.90% 98.99% 99.17% 99.35% 99.46% 99.46% 98.99%1500 99.20% 98.89% 99.00% 99.09% 99.25% 99.41% 99.52% 99.52% 99.09%
DL13 2000 99.26% 98.97% 99.00% 99.15% 99.30% 99.45% 99.55% 99.55% 99.15%2500 99.30% 99.03% 99.10% 99.20% 99.34% 99.48% 99.57% 99.57% 99.20%
Product Class 9Table EA.9
Product Class 10Table EA.10
Dry-Type Medium Voltage Three Phase Transformer (>96 kV BIL)TSL
TSLDry-Type Medium Voltage Single Phase Transformer (>96 kV BIL)
TSLProduct Class 8
Table EA.8Dry-Type Medium Voltage Three Phase Transformer (46-96 kV BIL)
Note: National Standard Efficiency calculated using load at 50% & PF (COS θ) = 1
© ABB Group April 11, 2023 | Slide 46
National Standard - Dry Type
Loss Reduction @ 50% Load compared to TLS1 (NEMA TP-1) as the base case
DOE TLS1 DOE TLS115 97.86% 97.60% 10.8% 15 97.18% 96.80% 11.9%25 98.12% 97.90% 10.5% 30 97.63% 97.30% 12.2%
37.5 98.30% 98.10% 10.5% 45 97.86% 97.60% 10.8%50 98.42% 98.20% 12.2% 75 98.12% 97.90% 10.5%75 98.57% 98.40% 10.6% 112.5 98.30% 98.10% 10.5%
100 98.67% 98.50% 11.3% 150 98.42% 98.20% 12.2%167 98.83% 98.80% 2.5% 225 98.57% 98.40% 10.6%250 98.95% 98.90% 4.5% 300 98.67% 98.50% 11.3%333 99.03% 99.00% 3.0% 500 98.83% 98.80% 2.5%500 99.12% 99.10% 2.2% 750 98.95% 98.90% 4.5%667 99.18% 99.20% -2.5% 1000 99.03% 99.00% 3.0%833 99.23% 99.20% 3.8% 1500 99.12% 99.00% 12.0%
2000 99.18% 99.20% -2.5%2500 99.23% 99.20% 3.8%
Single-Phase Dry-type
kVAEfficiency (%) Loss
Reduction
Three-Phase Dry-type
kVAEfficiency (%) Loss
Reduction
© ABB Group April 11, 2023 | Slide 49
Final Rule: Liquid and Dry Comparison
© ABB Group April 11, 2023 | Slide 50
Agenda
Describe the new efficiency standards for distribution transformers for use in or shipped into the United States and its territories that will be effective January 1, 2010
Review the standard’s development process as well as the scope of transformers that are effected
Discuss design strategies and associated cost impact of those strategies
Address the methodologies for insuring conformance with the standards by the manufacturers
© ABB Group April 11, 2023 | Slide 51
What is transformer efficiency?
%Efficiency = 100 x Output Watts / Input Watts
Output being less than input due to losses in form of heat
% Efficiency =L . kVA . COS . 105
L . kVA . COS . 103 + Fe + L2 . (LL)
L (pu) = Load V
r
No-Load Losses (A)
Load Losses (B)
Note: National Standard Efficiency calculated using load at 50% & PF (COS θ) = 1
© ABB Group April 11, 2023 | Slide 52
Transformer Losses
Total Loss = No-Load Loss + Load Loss
No Load Losses - Core Loss
Hysteresis Loss - steel chemistry, coating, processing
Eddy Loss - steel thickness
Load Losses - Conductor loss
I2R Loss - material (CU vs. AL), size and length
Eddy Loss - geometry, proximity to steel parts
© ABB Group April 11, 2023 | Slide 53
Load Losses – Conductor I2R
I = Rated Current
R = Resistance of the conductor
AreaConductor
Length Conductor y Resistivit R
Resistivity - property of the material
Copper = 0.017
Aluminium = 0.028
© ABB Group April 11, 2023 | Slide 54
Load Losses - Conductor Eddy Loss
Less of an impact than I2R
Eddy loss in the conductor
Thin conductors have less eddy loss
Eddy loss in adjacent ferrous metal
LV Lead close to tank wall sets up eddy currents in the tank
© ABB Group April 11, 2023 | Slide 55
No Load Losses – Core Eddy Loss
0.20.40.60.8
11.21.41.61.8
22.22.4
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8Induction (Tesla)
ARMCO .17mmARMCO .23mmARMCO .36mm
0.014 inch = M6
0.009 inch = M3
0.006 inch = M2
© ABB Group April 11, 2023 | Slide 56
AreaCore Turns
voltage Rated Constant
f
Induction
Where
Rated voltage and number of turns refer to either the high voltage or low voltage coil
Induction is a function of the electrical steel limited by its saturation value
f is the frequency
No Load Losses – Core Eddy Loss
© ABB Group April 11, 2023 | Slide 57
Ways to Reduce No-Load Loss Ways to Reduce Load Loss
Use better grade of core steel Use copper rather than aluminum
Use thinner core steel laminations Use a conductor with a larger area
Use more turns in the coil Use fewer turns in the coil
Use a core with larger leg area
How to Reduce Losses?
© ABB Group April 11, 2023 | Slide 58
Amorphous Cores
ABB performed considerable research on amorphous core steel in the early 1990’s
Numerous patents granted
Prototypes built – all type test performed (passed)
Production units produced thru 2002
However, during this time, the cost of the material was prohibitive to maintain a commercial line
With the recent upswing in the cost of CGO (conventional grain oriented) steel and the reduction in the cost of Amorphous material the economic equation has changed
With loss evaluations in the range of $5/w NL the Amorphous material approaches economic viability
Further potential improvements in the cost model may produce an economic option to meet the DOE standard
Note: TSL6 was computed with Amorphous Cores
© ABB Group April 11, 2023 | Slide 60
Impact to the Customer
Increased price of transformer
Increased size & weight
Financial valuation & justification
A/B factors related to National Standard
Transition strategy
Wait to last minute or move now
Potential pre-buy decision based on applicable date
Risk of delayed projects that cross the applicable date
© ABB Group April 11, 2023 | Slide 61
% Shipments Meeting Final Ruling
Overheads 20%
Padmount* 1Φ - 47% S3Φ < 750 kVA - 53% L3Φ > 750 kVA – 59%
Cast Coil 20-45 kV BIL 6% 46-95 KV BIL 20% > 95 KV BIL 3%
Open Wound 20-45 kV BIL 1% 46-95 KV BIL 10% > 95 KV BIL 0%
*Note: All customer segments for shipments from 10/06 to 08/07
© ABB Group April 11, 2023 | Slide 62
Price Impact – Overhead
Estimated based on high volume styles
1Φ (kVA)ABB Base
CostTP1 DOE
10 - 25 1.00 1.07 1.20
37.5 - 50 1.00 1.07 1.20
75 - 100 1.00 1.06 1.18
© ABB Group April 11, 2023 | Slide 63
Price Impact - Padmount
Note 1: Analysis of all active designs
Note 2: Using current manufacturing limitations
Note 3: Average estimations across kVA range
Note 4: 7200 HV + Taps; 240/120 LV 1 Φ; 480Y/277 LV 3 Φ
1Φ (kVA)ABB Base
CostTP1 DOE
25-50 1.00 1.04 1.18
75-100 1.00 1.02 1.18
250 1.00 1.00 1.12
3Φ (kVA) ABB Base Cost TP1 DOE
75-150 1.00 1.01 1.10
225-500 1.00 1.01 1.18
750-1000 1.00 1.01 1.08
1500-2000 1.00 1.01 1.04
2000-3000 1.00 1.01 1.12
© ABB Group April 11, 2023 | Slide 64
20-45 KV BIL 1.00 1.10 1.10-1.15
46-95 KV BIL 1.00 1.10 1.05-1.10
> 95 KV BIL 1.00 1.20 1.05-1.15
20-45 KV BIL 1.00 1.10 1.10-1.20
46-95 KV BIL 1.00 1.10 1.10-1.15
> 95 KV BIL 1.00 1.20 1.10-1.20
Open Wound ABB Base
Cost TP1
ABB Base
Cost TP1Cast Coil
DOE
DOE
Note: Actual Price impact is dependent on:• KVA• Temperature Rise• Conductor• BIL• Impedance
Price Impact – Dry Type
© ABB Group April 11, 2023 | Slide 65
National Efficency Standard impact on Unit Footprint relative to TSL0
0
1
2
3
4
5
6
7
8
9
0 1 2 3 4 5 6 7 8 9 10
"A" values (core loss evaluation) $/watt
"B"
va
lue
s (
co
il l
os
s e
va
lua
tio
n)
$/w
att
> 1.09
≤ 1.09
≤ 1.06
≤ 1.03
≤ 1
Footprint Variation relative to TSL0
RectTank
RoundTank
101525
37.55075100167250333500667833
kVA
Liq-1phPC1
DL
1
DL
2D
L 3
RU
RU
RU
RU
Liquid-Filled 1ph 10-167 kVA Pad
Max: 1.10
© ABB Group April 11, 2023 | Slide 66
National Efficency Standard impact on Unit Weight relative to TSL0
0
1
2
3
4
5
6
7
8
9
0 1 2 3 4 5 6 7 8 9 10
"A" values (core loss evaluation) $/watt
"B"
va
lue
s (
co
il l
os
s e
va
lua
tio
n)
$/w
att
> 1.25
≤ 1.25
≤ 1.15
≤ 1.05
≤ 1
Weight Variation relative to TSL0
Liquid-Filled 1ph 10-167 kVA Pad
RectTank
RoundTank
101525
37.55075100167250333500667833
kVA
Liq-1phPC1
DL
1
DL
2D
L 3
RU
RU
RU
RU
Max: 1.29
© ABB Group April 11, 2023 | Slide 67
Impact of A/B factors
Loss Evaluation
Cost Of Losses (COL) =
(A x No Load Loss) + (B x Load Loss)
($/watt x watts) + ($/watt x watts)
Total Owning Cost (TOC) =
Transformer Price + COL
A & B factors result in most cost-effective design over product life cycle based on customers’ cost of energy
ABB & PPI recommend customers’ re-evaluate and/or establish factors at or above the national efficiency standards
Loss
Cos
t
Cost ofLosses
TransformerCost
Note: A = PW Inflation x Annual $/kW x n yrs; B = A x (load p.u.)2 x Conductor Temp Correction
© ABB Group April 11, 2023 | Slide 70
Where: EL = Purchaser’s cost of electricity ($/kWH) N = Number of years P = Per unit Load = 50% for Medium Voltage> 600 volt class transformers D = Duty Cycle = % of daily usage NL = No load (core) loss at 20C in watts LL = Load loss at its full load reference temperature consistent with C57.12.00 (liquid)
and C57.12.01(dry) in watts. T = Load loss temperature correction factor to correct specified temperature, i.e., 75C for
dry- and 85C for liquid-transformers.
Standard A/B Calculation
TOC = A (NL) + B (LL) + Sell price
A = $EL x 8760 hr/yr x N (Core Contribution NL)
B = $EL x (P)2 x T x D x 8760 hr/yr x N (Load Loss Contribution LL)
© ABB Group April 11, 2023 | Slide 74
National Efficency Standard impact on Total Owning Cost (TOC) relative to TSL0
0
1
2
3
4
5
6
7
8
9
0 1 2 3 4 5 6 7 8 9 10
"A" values (core loss evaluation) $/watt
"B"
va
lue
s (
co
il l
os
s e
va
lua
tio
n)
$/w
att
> 1.25
≤ 1.25
≤ 1.15
≤ 1.05
≤ 1
TOC Variation relative to TSL0
Liquid-Filled 1ph 10-167 kVA Pad
RectTank
RoundTank
101525
37.55075100167250333500667833
kVA
Liq-1phPC1
DL
1
DL
2D
L 3
RU
RU
RU
RU
Max: 1.33
© ABB Group April 11, 2023 | Slide 77
Impact to the Customer
Increased price of transformer
Increased size & weight
Financial valuation & justification
A/B factors related to National Standard
Transition strategy
Wait to last minute or move now
Potential pre-buy decision based on applicable date
Risk of delayed projects that cross the applicable date
© ABB Group April 11, 2023 | Slide 78
Impact to Customer
Transition Strategy – now or later
Generally there is an economic benefit for any unit where to A/B are A <= $3.00, B<= $1.00
NEMA Premium Transformer initiative
Potential pre-buy decision based on ‘applicable’ date
DOE cautions against ‘building stock’ prior to circumvent to standard
Risk of delayed projects that the ‘applicable’ date
Standard applies to ALL units shipped after January 1, 2010
© ABB Group April 11, 2023 | Slide 79
Impact to Manufacturer
Redesign and re-optimize
Impact of unit weight and size
Material selection and availability
Compliance & Enforcement
© ABB Group April 11, 2023 | Slide 80
Design Impact
Increase in conductor cross section
Copper consumption for overheads
Copper and aluminum for pads
Weights and dimensions increase in most cases
Transportation cost increase as less units per truck load
Average oil volume per unit increases due to wider & deeper tanks not being offset by reduction in tank height
Some cases higher efficiency leads to lower losses, less heating and a reduction in tank size and/or elimination of radiators
© ABB Group April 11, 2023 | Slide 81
% Shipments Meeting Final Ruling
Overheads 20%
Padmount* 1Φ - 47% S3Φ < 750 kVA - 53% L3Φ > 750 kVA – 59%
Cast Coil 20-45 kV BIL 6% 46-95 KV BIL 20% > 95 KV BIL 3%
Open Wound 20-45 kV BIL 1% 46-95 KV BIL 10% > 95 KV BIL 0%
*Note: All customer segments for shipments from 10/06 to 08/07
© ABB Group April 11, 2023 | Slide 82
Impact to Manufacturer
Redesign and re-optimize
Impact of unit weight and size
Material selection and availability
Compliance & Enforcement
© ABB Group April 11, 2023 | Slide 83
Impact on E-Steel Grade Distribution
© ABB Group April 11, 2023 | Slide 84
Greatest impact of all commodities
Limited worldwide production
Limited capacity of higher grades
Expanding global demand
US Producers raising prices to match world levels
Materials – E-Steel MOST Critical
© ABB Group April 11, 2023 | Slide 85
E-Steel – Demand & Supply Sensitivity
From 2007 thru 2010 … E-steel req. 09.2/2.7 = China CAGR = 9.2%, all others 2.7% E-steel req. 15.0/2.7 = China CAGR = 15%, all others 2.7% E-steel req. 20.0/3.0 = China CAGR = 20%, all others 3.0% E-steel req. 25.0/3.0 = China CAGR = 25%, all others 3.0%
1,450,000
1,650,000
1,850,000
2,050,000
2,250,000
2,450,000
2,650,000
2005 2006 2007 2008 2009 2010
Me
tric
To
ns
E-steel Capacity E-steel req. 9.2/2.7 E-steel req. 15.0/2.7 E-steel 20.0/3.0 E-steel 25.0/3.0
© ABB Group April 11, 2023 | Slide 86
Impact to Manufacturer
Redesign and re-optimize
Impact of unit weight and size
Material selection and availability
Compliance & Enforcement
© ABB Group April 11, 2023 | Slide 87
Agenda
Describe the new efficiency standards for distribution transformers for use in or shipped into the United States and its territories that will be effective January 1, 2010
Review the standard’s development process as well as the scope of transformers that are effected
Discuss design strategies and associated cost impact of those strategies
Address the methodologies for insuring conformance with the standards by the manufacturers
© ABB Group April 11, 2023 | Slide 88
National Standard Enforcement
Standard requires the manufacturer to comply no matter country of origin
Enforcement - assumes and Honor System- depends on third party or other source reporting suspected ‘violators’ to the DOE
DOE meets with suspect manufacturer reviewing its underlying test data as to the models in question
DOE commences enforcement testing procedures if previous step does not resolve compliance issues
Non-compliance results in manufacturer “ceasing distribution of the basic model” until dispute resolution
DOE might seek civil penalties
© ABB Group April 11, 2023 | Slide 89
National Standard Compliance
Manufacturer determines efficiency of a basic model either by testing or by an Alternative Efficiency Determination Method (AEDM).
Basic model being same energy consumption along with electrical features being kVA, BIL, voltage and taps
Calculated load at 50% & PF=1.0; NL 20°C & LL 55°C
Auxiliary devices – circuit breakers, fuses and switches – excluded from calculation of efficiency
AEDM approach is offered in 10 CFR 431 “to ease the burden on manufacturers”
ABB & Power Partners have elected to use the AEDM approach for asserting compliance
© ABB Group April 11, 2023 | Slide 90
Distribution of efficiencies forall units of abasic model
Standard Level for Efficiency perTable I.1. of 10 CFR 431; example,99.08% for 50 kVA Single Phase
Higher
Efficiency
Similar to quoting average losses today
The mean efficiency of a basic model will be at or above the standard
DOE Compliant
© ABB Group April 11, 2023 | Slide 91
Compliance by Test
If 5 or fewer units of a Basic Model are produced over 180 days then the manufacturer must test each unit
If more than 5 units of a Basic Model are produced over 180 days then the manufacturer may select and test a random sample of at least 5 units
Determine the average efficiency of the sample
where…
Xi is the measured efficiency of unit (i)
n is the number of units in the sample
Criteria: where…
RE is the required efficiency
n is the number of units tested
n
iiXn
X1
1
1
10008.011
100
REn
X
© ABB Group April 11, 2023 | Slide 92
Compliance by AEDM
Randomly select 5+ Basic Models Two must be the highest volume unit in the prior year No two shall have the same power / voltage rating At least one shall be 1-ph and at least one 3-ph
Calculate the Power Loss ( ) for each Basic Model (i, ) Determine the Power Loss by Test ( ) for at least 5 units (j, ) of
each Basic Model (i, ) Determine the mean tested power loss ( ) for each Basic Model
mean tested power loss of Basic Model (i)
Criteria #1: for each Basic Model (i) Criteria #2: for all Basic Models
for Basic Model (i), the calculated power loss as a percentage
of the mean tested power loss
the average of all Basic Model percentages of calculated as
percentage of mean tested power loss
iOSCP
ijOSTP 5j
5i
n
jOSTOST ijiP
nP
1
1
iii OSTOSCOST PPP 05.195.0
%103%%97 OSCP
100% i
i
i
OST
OSCOSC P
PP
m
iOSCOSC iP
mP
1
1%
iOSTP
5i
© ABB Group April 11, 2023 | Slide 93
Distribution of efficiencies forall units of abasic model
Standard Level for Efficiency perTable I.1. of 10 CFR 431; example,99.08% for 50 kVA Single Phase
Higher
Efficiency
The mean efficiencyof a basic model willbe above the standard
mean
Specified Minimum Efficiency >> DOE
ABBPreferred
Specification
© ABB Group April 11, 2023 | Slide 94
Specified Minimum Efficiency >> DOE
100% of the units to meet or exceed efficiency standard
Customer should clearly state in its specification
Suggested wording could be, “The tested efficiency of all units shipped by serial number and/or stock code must meet or exceed the values in 10 CFR 431, Table I.1. for liquid-immersed distribution transformers. Certified test data by serial number must be provided to confirm compliance with this requirement.”