METRIC
142[5.6]
OPTIONALISOLATORSPRINGS
65025.6
2850112.2
92536.4
186373.3
MLCBHEIGHT
(NOTE 2)
61624.2
HIGH VOLTAGESTUB-UP
602.4
A
ALT AIROUT
ALT AIROUT
RADIATOR DRAIN(NOTE 3)
FUEL FILTER
PRIMARYCIRCUITBREAKER
OIL DRAIN(NOTE 3)
204280.4
EXHAUST OUTLET(NOTE 3)
1415.5
RADIATORCAP
36914.5
RADIATORCAP
39615.6
RADIATORCAP
105041.3
EXHAUST OUTLET(NOTE 3)
OPTIONALSECONDARYCIRCUITBREAKER
BATTERYLOCATION(NOTE 1)
PRIMARY CIRCUITBREAKER
OPTIONAL BATTERYLOCATION (NOTE 1)
PRIMARY BLOCKHEATER LOCATION
SECONDARYBLOCKHEATER
LOCATION
209882.6
BASE WIDTH
1049[41.3]
1706.7
176869.6RAD.
OPEN AREA(NOTE 4)
181071.3
RAD. OPEN AREA(NOTE 4)
RADIATORDRAIN
(NOTE 3)
90035.4
C/C MTG.HOLES
200679.0
C/C MTG. HOLES
208882.2FLEX
CONN. 186573.4EXH.
OUTLET
238994.0
4565179.7
4X 127[5.0]
LIFTING EYE
AIRDISCHARGE
SEENOTE 9
DETAIL ASCALE 1 : 12
FUELOUT
FUELIN
15.00°
53321.0
47618.8B.C.
12X 1.12[28.6]THRU
2228.8
SCALE 1:24
32012.6
28011.0B.C.
8X 23[0.9]THRU
ENGINECONNECTION(JIS 200MM)
NOTES:1. BATTERY (24 VOLT GROUND SYSTEM)2. MAIN LINE CIRCUIT BREAKER (MLCB), AC LOAD LEADS. (DIMENSIONS MAY VARY DUE TO UNIT CONFIGURATION)3. ENGINE SERVICE CONNECTIONS: INLET DIESEL = 3/4" NPT RETURN DIESEL = 3/4" NPT OIL DRAIN = 3/4" NPT COUPLING RADIATOR DRAIN = 3/4" NPT FLEX PIPE OUTLET - 21" O.D. (14" ASA) EXHAUST OUTLET = 200MM (8IN) JIS FLANGE4. GENERATOR SET MUST BE INSTALLED SUCH THAT FRESH COOLING AIR IS AVAILABLE AND DISCHARGE AIR FROM THE RADIATOR IS NOT RECIRCULATED.5. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND RECIRCULATION.6. EXHAUST SYSTEM MAXIMUM BACK PRESSURE = 23"7. OPTIONAL ISOLATOR SPRINGS INCREASES UNIT HEIGHT BY APPROXIMATELY 5.6"8. CONNECT THE OPEN SET EXHAUST PER NFPA 37.9. OPTIONAL ALTERNATORS: (480 V. 125 C TEMP. RISE ALTERNATOR SHOWN.)10. ALL DIMENSIONS ARE IN MM [INCHES]
INSTALLATION DRAWING
EXHAUSTCONNECTION
(14 IN ASA)
D
C
B
AA
B
C
D
12345678
8 7 6 5 4 3 2 1
SLS-SD
-750-800-OP
D
C
B
AA
B
C
D
12345678
8 7 6 5 4 3 2 1
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT THE EXPRESS
WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
GENERAC POWER SYSTEMS 2013
000000858864
SD/MD/750/800 KWINSTALLATION DRAWING OPEN SET D33.9
SLS-SD-750-800-OP
-- -
-1:48 SHEETWT-KGSCALE:B
REV/VERDWG NO.CAGE NO.SIZEDRAWN BY:
DATEAPPROVALPAINT SURFACE
FINISHGENERAC MATL SPECIFICATION
MATERIALc
INTERPRET DIM AND TOLPER ASME Y14.5M-1994
TITLE
THIRD ANGLE PROJECTIONGENERAL TOLERANCES UNLESS NOTED
TDR:REF:MODEL NO:REV. DESC:
00-
98.M2800-G1
12:42:56 12/02/2014
-
PGMICG0-
2OF1
-
METRIC
59723.5
1359
53.5
212183.5
2883113.5
3645143.5
209982.7
200679.0
MTG.HOLE
CENTERS
4565179.7
97438.4
90035.4
MTG.HOLE
CENTERS
100339.5
105041.3
45017.7
48719.2
522.0
152
6.0
71128.0
38115.0
25410.0
1526.0
199678.6
1526.0
903.5
29511.6
125749.5
143056.3
ELECTRICALSTUB-UP
AREA
OPTIONALSECONDARYSTUB-UPAREA
FUELSTUB-UP
AREA
10X 22[0.87] MTG HOLES
BATTERY RACKLOCATION
D
C
B
AA
B
C
D
12345678
8 7 6 5 4 3 2 1
SLS-SD
-750-800-OP
D
C
B
AA
B
C
D
12345678
8 7 6 5 4 3 2 1
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT THE EXPRESS
WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
GENERAC POWER SYSTEMS 2013
000000858864
SD/MD/750/800 KWSTUB-UP INSTALLATION DRAWING OP D33.9
SLS-SD-750-800-OP
-- -
-1:16 SHEETWT-KGSCALE:B
REV/VERDWG NO.CAGE NO.SIZEDRAWN BY:
DATEAPPROVALPAINT SURFACE
FINISHGENERAC MATL SPECIFICATION
MATERIALc
INTERPRET DIM AND TOLPER ASME Y14.5M-1994
TITLE
THIRD ANGLE PROJECTIONGENERAL TOLERANCES UNLESS NOTED
TDR:REF:MODEL NO:REV. DESC:
1-
98.M2800-G1
12:42:56 12/02/2014
A
PGMICG0-
2OF2
-
METRIC
ZY
X
CGREFERENCE POINT(0,0,0)(NO TANK OPTION)
STANDARDENCLOSUREOUTLINE
CGREFERENCE POINT(0,0,0)(TANK OPTION)
PRIMARYCIRCUITBREAKER
INSTALLATION DRAWING
LO ENCLOSURE, STEEL
OPEN UNIT
LO ENCLOSURE, ALUMINUM
L2 ENCLOSURE, ALUMINUML2 ENCLOSURE, STEEL
L1 ENCLOSURE, STEEL L1 ENCLOSURE, ALUMINUM
UNIT VOLTAGE WEIGHT (KG) WEIGHT (LBS) CofG DIM X CofG DIM Y CofG DIM Z TANK OPTION
SD800 208/480/600V 10204 22496 2316 [91.2"] 1102 [43.4"] 835 [32.9"] NO TANK11996 26446 2391 [94.1"] 1189 [46.9"] 1110 [43.7"] 12 HR TANK12620 27822 2399 [94.4"] 1190 [46.9"] 1365 [53.7"] 24 HR TANK
UNIT VOLTAGE WEIGHT (KG) WEIGHT (LBS) CofG DIM X CofG DIM Y CofG DIM Z TANK OPTION
SD800 208/480/600V 12723 28049 2347 [92.4"] 1191 [46.9"] 1221 [48.1"] NO TANK13644 30078 2361 [93.0"] 1193 [47.0"] 1267 [49.9"] 12 HR TANK14268 31454 2370 [93.3"] 1194 [47.0"] 1524 [60.0"] 24 HR TANK
UNIT VOLTAGE WEIGHT (KG) WEIGHT (LBS) CofG DIM X CofG DIM Y CofG DIM Z TANK OPTION
SD800 208/480/600V 12198 26890 2339 [92.1"] 1189 [46.8"] 1201 [47.3"] NO TANK13118 28919 2354 [92.7"] 1192 [46.9"] 1246 [49.1"] 12 HR TANK13742 30295 2363 [93.0"] 1193 [47.0"] 1500 [59.1"] 24 HR TANK
UNIT VOLTAGE WEIGHT (KG) WEIGHT (LBS) CofG DIM X CofG DIM Y CofG DIM Z TANK OPTION
SD800 208/480/600V 14268 31454 2604 [102.5"] 1193 [47.0"] 1243 [48.9"] NO TANK14999 33067 2677 [105.4"] 1195 [47.0"] 1164 [45.8"] 12 HR TANK15521 34217 2709 [106.6"] 1196 [47.1"] 1339 [52.7"] 24 HR TANK
UNIT VOLTAGE WEIGHT (KG) WEIGHT (LBS) CofG DIM X CofG DIM Y CofG DIM Z TANK OPTION
SD800 208/480/600V 13742 30295 2521 [99.3"] 1191 [46.9"] 1208 [47.6] NO TANK13955 30764 2607 [102.6"] 1193 [47.0"] 1126 [44.3"] 12 HR TANK14476 31914 2643 [104.1"] 1194 [47.0"] 1299 [51.1"] 24 HR TANK
UNIT VOLTAGE WEIGHT (KG) WEIGHT (LBS) CofG DIM X CofG DIM Y CofG DIM Z TANK OPTION
SD800 208/480/600V 14803 32633 2665 [104.9"] 1195 [47.0"] 1339 [50.0"] NO TANK16052 35388 2739 [107.8"] 1197 [47.1"] 1198 [47.2"] 12 HR TANK16574 36538 2767 [108.9"] 1197 [47.1"] 1375 [54.1"] 24 HR TANK
UNIT VOLTAGE WEIGHT (KG) WEIGHT (LBS) CofG DIM X CofG DIM Y CofG DIM Z TANK OPTION
SD800 208/480/600V 13313 29349 2558 [100.7"] 1192 [46.9"] 1299 [48.2"] NO TANK14481 31924 2643 [104.1"] 1194 [47.0"] 1146 [45.1"] 12 HR TANK15003 33074 2677 [105.4"] 1195 [47.0"] 1320 [52.0"] 24 HR TANK
D
C
B
AA
B
C
D
12345678
8 7 6 5 4 3 2 1
SLS-SD
-800-CG
D
C
B
AA
B
C
D
12345678
8 7 6 5 4 3 2 1
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT THE EXPRESS
WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
GENERAC POWER SYSTEMS 2013
--
SD/MD/750/800KWINSTALLATION DRAWING CG D33.9
SLS-SD-800-CG
-- -
-1:75 SHEETWT-KGSCALE:B
REV/VERDWG NO.CAGE NO.SIZEDRAWN BY:
DATEAPPROVALPAINT SURFACE
FINISHGENERAC MATL SPECIFICATION
MATERIALc
INTERPRET DIM AND TOLPER ASME Y14.5M-1994
TITLE
THIRD ANGLE PROJECTIONGENERAL TOLERANCES UNLESS NOTED
ECO:REF:MODEL NO:REV. DESC:
1-
98.M2800-G1
4/17/2015
A
MRADEMACINITIAL RELEASE
1OF1
-
R
MH18481 MH46743 MH25279File Numbers:
LUR
Underwriters
LISTED
Laboratories, Inc.
R
MH18481 MH46743 MH25279File Numbers:
LUR
Underwriters
LISTED
Laboratories, Inc.
ULR
UnderwritersLaboratories, Inc. Listed
R
MH18481FILE NO. MH46743
MH25279
6682 W. GREENFIELD AVEWEST ALLIS, WI 53214
PH (414)475-3000 FAX (414) 475-3441
www.globalpowercomponents.com
GLOBAL POWER COMPONENTS
68
3FLANGE
14 14 25.5
65 1.5
END
L
9
21.5
32 0
33
23
58
53
48
43
38
28
16
6
0 5
12
18
26
34
53 58 9
S
YUV T
X
TOP
A
Z
H
B RAD
IATO
R EN
D
F
G
K
J
H
2X 1/2" X 1.125"WELD STUD
42
5TYP
9
68 17.5
28.5
5612
2
C
SIDE
4X 1516" HOLEBOTTOM
REVISIONSREV. DESCRIPTION DATE BY
BILL OF MATERIALS
ITEM PART NUMBER DESCRIPTION QTY.
S 3165 FLANGE, 5", EMERGENCY VENT 2T 3650R FLANGE, 2", FUEL RETURN W/ 1/2" DIP TUBE 1U 3650S FLANGE, 2", FUEL SUPPLY W/ 1/2" DIP TUBE 1V 1000 FLANGE, 2", LOW LEVEL ALARM (SET AT 21") 1X 1001 FLANGE, 2", KRUEGER FUEL GAUGE (SET AT 39") 1Y 3152 FLANGE, 2", STANDARD VENT CAP 1Z 3005 FLANGE, 2", LOCKING FILL PORT 1A 4300 FLANGE, 2", FUEL IN BASIN ALARM (TOP MOUNT) 1B 3502 FLANGE, 1/2", BASIN DRAIN 1C 8410 1/4" FLUSH MOUNT LIFTING PLATE 4
F1010 FLANGE, 2", HIGH LEVEL ALARM (SET AT 4-3/4") 11020 CRITICAL HIGH LEVEL ALARM (SET AT 2-3/4") 1
G 3600 FLANGE, 2", 1/2" DIP TUBE 1H 3195 FLANGE, 2", EXTRA FITTING W/ PLUG 4J 3191 FLANGE, 1/2", EXTRA FITTING W/ PLUG 1K 4306 FUEL IN BASIN ALARM 1L 3185 FULL COUPLING, 2", EXTRA FITTING (PUMP CONTAINMENT) 2
1380 SERIES 400 CONTROLLER SINGLE W/ REVERSE 12025 SINGLE PUMP SYSTEM 1
6040
1/3 HP CARBONATE MOTOR, SINGLE PHASE1
115/208-230V, 50/60Hz, 48YZ FRAMEBRONZE CLOSE COUPLED 4 GPM
1ROTARY GEAR PUMP, 3/8" PORTS
SPECIAL PUMP CONTAINMENT BOX W/ PUMP BASE 1700-1025 1/2" FUEL STRAINER, Y-STYLE (SHIP LOOSE) 1700-1096 1/2" SOLENOID VALVE (120VAC, NC) (SHIP LOOSE) 1700-1065 1/2" SPRING CHECK VALVE (SHIP LOOSE) 1
1055-AFP4STEEL REMOTE ALARM FILL STATION (FLUSH MOUNT) 1
REMOTE FOUR ALARM FILL PANEL W/ RELAYS 1SPECIAL MORRISON DRY DISCONNECT ADAPTOR (927-0200A, 2") 1SPECIAL MORRISON DUST CAP (735DC-2500ACEVR) 1700-1055 2" BALL VALVE 1700-1080 2" SPRING CHECK VALVE 1700-1118 2" SOLENOID VALVE (120VDC, NO) 1
DW-101 DOUBLE WALL SECONDARY CONTAINMENTPAINT COLOR GLOSS BLACK (9638)
JOB # TANK CAPACITY ACTUAL GENSET MODELTANK WEIGHTAPPROVED BY: DATE:26510 518 GAL X 1800 LBS
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OFGLOBAL POWER COMPONENTS. ANY REPRODUCTION IN PART OR WHOLE WITHOUT
THE WRITTEN PERMISSION OF GLOBAL POWER COMPONENTS IS PROHIBITED.
TANK CAPACITY USEABLE
500 GALGENSET FOOTPRINT
X
15-26510B
DESCRIPTION
SHEET 2 OF 6
DWG. NO.SIZE
SCALE: 1:24
FREESTANDING TANK WITH RUPTURE BASIN
DRAWING REFERENCE:
JOB REFERENCE:
CUSTOMER NAME:
X
LE MERIDEN AC HOTEL MARRIOTT
GEN TECH 8/18/2016
RCK
DATE
DRAWN BY
THIRD ANGLE PROJECTION
REV. ± .1± .06± 2°± .005
.X.XX
THE TOLERANCES ARE:
ONE PLACETWO PLACEANGLEHOLE DIA.
UNLESS OTHERWISE SPECIFIEDDIMENSIONS ARE IN INCHES
ULR
UnderwritersLaboratories, Inc. Listed
R
MH18481FILE NO. MH46743
MH25279
6682 W. GREENFIELD AVEWEST ALLIS, WI 53214
PH (414)475-3000 FAX (414) 475-3441
www.globalpowercomponents.com
GLOBAL POWER COMPONENTS
ISO VIEW
15-26510B
DESCRIPTION
SHEET 3 OF 6
DWG. NO.SIZE
SCALE: 1:10
JOB # APPROVED BY: DATE:26510
FREESTANDING TANK WITH RUPTURE BASINISO VIEW
DRAWING REFERENCE:
JOB REFERENCE:
CUSTOMER NAME:
X
LE MERIDEN AC HOTEL MARRIOTT
GEN TECH 8/18/2016
RCK
DATE
DRAWN BY
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OFGLOBAL POWER COMPONENTS. ANY REPRODUCTION IN PART OR WHOLE WITHOUT
THE WRITTEN PERMISSION OF GLOBAL POWER COMPONENTS IS PROHIBITED.
REV.
THIRD ANGLE PROJECTION
± .1± .06± 2°± .005
.X.XX
THE TOLERANCES ARE:
ONE PLACETWO PLACEANGLEHOLE DIA.
UNLESS OTHERWISE SPECIFIEDDIMENSIONS ARE IN INCHES
ULR
UnderwritersLaboratories, Inc. Listed
R
MH18481FILE NO. MH46743
MH25279
6682 W. GREENFIELD AVEWEST ALLIS, WI 53214
PH (414)475-3000 FAX (414) 475-3441
www.globalpowercomponents.com
GLOBAL POWER COMPONENTS
12
2
30
24
8 1TYP
A
5
4TYP
4TYP
2X 2" FULL COUPLING
1.38TYP
4.25TYP
2.13TYP
2.75TYP
DETAIL ASCALE 1 : 4
4X 1/4" X 1-1/4" SLOTS
NOTE:WELD 2" FULL COUPLINGS HALF WAY THROUGH
15-26510BSHEET 6 OF 6
DWG. NO.SIZE
SCALE: 1:8
JOB # APPROVED BY: DATE:26510
PUMP BOX
DRAWING REFERENCE:
JOB REFERENCE:
CUSTOMER NAME:
X
LE MERIDEN AC HOTEL MARRIOTT
GEN TECH 8/18/2016
RCK
DATE
DRAWN BY
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OFGLOBAL POWER COMPONENTS. ANY REPRODUCTION IN PART OR WHOLE WITHOUT
THE WRITTEN PERMISSION OF GLOBAL POWER COMPONENTS IS PROHIBITED.
REV.
THIRD ANGLE PROJECTION
± .1± .06± 2°± .005
.X.XX
THE TOLERANCES ARE:
ONE PLACETWO PLACEANGLEHOLE DIA.
UNLESS OTHERWISE SPECIFIEDDIMENSIONS ARE IN INCHES
DESCRIPTION
Low Voltage Customer Connections Panel
AU
X C
ontacts
N.C.
N.O.
COM
178 (0)
183
Automatic Transfer Switch
Utility P
ow
er S
upply
240 V
AC
, 30 A
mp
TB1
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
RS485+
RS485-
SHLD
178 (0)
183
Common
D 14 (N.O.)
D 13 (N.C.)
B+
B-
TB2
TB4
1
2
3
4
5
6
7
8
9
10
11
12
13
14
L1
Neutral
L2
GN
D
Located in High Voltage Customer Connection Module
BLK
WHT
BLK
GRN
Provides AC power for AC powered Accessories
21 Light Remote
Annunciator Panel
Ext Alarm Com
Ext. Alarm N/O
Screen
SHLD
Battery -
Battery + (12V/24V)
RS485 -
RS485 +
TB1-9
TB1-11
TB1-8
E-STOP
TB1 - E-STOP
TB1 - E-STOP
REMOTE EMERGENCY STOP
1
2
E-STOP
E-STOP
#14 Ga. Stranded Wire
#14 Ga. Stranded Wire
#14 Ga. Stranded Wire
Single twisted pair, 16 ga., shielded (RS485)
#14 Ga. Stranded Wire
GENERAC CONTROL WIRING DIAGRAM
N.O.
COM
Ele
va
to
r
Co
nta
cts
Pre
-S
ig
na
l
Co
nta
cts
#14 Ga. Stranded Wire
#14 Ga. Stranded Wire
ELEVATOR CONTROLLER
Ele
va
to
r
Co
nta
cts
Pre
-S
ig
na
l
Co
nta
cts
REMOTE GENERATOR START SWITCH
RSC-178 (0)
RSC-183
#14 Ga. Stranded Wire
SPARE OUTPUT RELAY
1
2
3
4
5
6
7
8
9
10
11
12
AU
X 1
Customer Connection Cabinet
Programable output relays
NO
NC
COM
AU
X 2
NO
NC
COM
AU
X 3
NO
NC
COM
AU
X 4
NO
NC
COM
Rem
ote S
tart
Rem
ote S
tart
#14 Ga. Stranded Wire
#14 Ga. Stranded Wire
#14 Ga. Stranded Wire
Single twisted pair, 16 ga., shielded (RS485)
AU
X C
ontacts
N.C.
N.O.
COM
178 (0)
183
Automatic Transfer Switch
#14 Ga. Stranded Wire
N.O.
COM
Ele
va
to
r
Co
nta
cts
Pre
-S
ig
na
l
Co
nta
cts
Rem
ote S
tart
RS485+
RS485-
SHLD
Single twisted pair, 16 ga., shielded (RS485)
RS485+
RS485-
SHLD
Single twisted pair, 16 ga., shielded (RS485)
Transfer Switch
Annunciator Panel
Screen
SHLD
Battery -
Battery + (12V/24V)
RS485 -
RS485 +
Single twisted pair, 16 ga., shielded (RS485)
#14 Ga. Stranded Wire
AU
X C
ontacts
N.C.
N.O.
COM
178 (0)
183
Automatic Transfer Switch
N.O.
COM
Ele
va
to
r
Co
nta
cts
Pre
-S
ig
na
l
Co
nta
cts
Rem
ote S
tart
RS485+
RS485-
SHLD
Single twisted pair, 16 ga., shielded (RS485)
AU
X C
ontacts
N.C.
N.O.
COM
178 (0)
183
Automatic Transfer Switch
N.O.
COM
Ele
va
to
r
Co
nta
cts
Pre
-S
ig
na
l
Co
nta
cts
Rem
ote S
tart
RS485+
RS485-
SHLD
Single twisted pair, 16 ga., shielded (RS485)
S2653
Le Meridien
AC Hotel Marriott
Generac SD 750 Generator Set
Wiring
2.01/10/2016
NTS
Wiring
Arizona Generator Technology
7901 North 70th Avenue
Glendale, Arizona 85303
-
GEN-TECH POWER GENERATION SPECIALISTS
Remote Start Circuit
ATS#4
Generator Controller Remote Start Circuit
Transfer Switch Control Conduit (Auto Start - ATS Control ) - #14ga Wire
Remote Annunciator Panel Remote Start Circuit
ATS#3
ATS#FP
For Reference Only, refer to Submittal Drawing for Additional Information
ATS#2ATS#1
2.29/25/2015
NTS
Pad Layout
Arizona Generator Technology
7901 North 70th Avenue
Glendale, Arizona 85303
-
GEN-TECH POWER GENERATION SPECIALISTS
S2653
La Meridien
AC Hotel Marriott
Generator Set
Wiring and Conduit Layout
Transfer Switch Switch Position
ATS-#2 (Critical)
Elevator Controller
Controller
Transfer Switch Control Conduit(Position and Pre Transfer Signal - Elevator Control ) - Qty 4 - #14ga
ATS-#2 (Critical)
Controller
Transfer Switch Elevator Pre-Signal Switch Elevator Controller
For Reference Only, refer to Submittal Drawing for Additional Information
2.39/25/2015
NTS
Pad Layout
Arizona Generator Technology
7901 North 70th Avenue
Glendale, Arizona 85303
-
GEN-TECH POWER GENERATION SPECIALISTS
S2653
Le Meridien
AC Hotel Marriott
Generator Set
Wiring and Conduit Layout
Master Remote Annunciator
RS-485 Communication (Mater Controller)
Annunciator
24 VDC Power (Mater Controller)
Generator Controller
Remote Annunicator Panel Control Conduit (Communication and Power )Qty 2 - #14ga DC Power,Qty 1 - RS-485 Communication
For Reference Only, refer to Submittal Drawing for Additional Information
Master Remote Annunciator
Annunciator
Generator Remote Annunciator Panel
Engineer's OfficeFire Command
Generator Remote Annunciator Panel
2.49/25/2015
NTS
Pad Layout
Arizona Generator Technology
7901 North 70th Avenue
Glendale, Arizona 85303
-
GEN-TECH POWER GENERATION SPECIALISTS
S2653
Le Meridien
AC Hotel Marriott
Generator Set
Wiring and Conduit Layout
Remote Stop Panel
Remote Emergency Stop Station
Remote Stop
Generator Controller
Generator Remote Stop StationQty 2 - #14ga control wire
For Reference Only, refer to Submittal Drawing for Additional Information
2.59/25/2015
NTS
Pad Layout
Arizona Generator Technology
7901 North 70th Avenue
Glendale, Arizona 85303
-
GEN-TECH POWER GENERATION SPECIALISTS
S2653
Le Meridien
AC Hotel Marriott
Generator Set
Wiring and Conduit Layout
Transfer Switch
Transfer Switch Control Conduit (Transfer Switch Indication - ATS Control ) - Qty 4 - #14ga for each ats
For Reference Only, refer to Submittal Drawing for Additional Information
ATS #1 - 4 Display Panel
ATS Remote Annunciator Panel
Transfer Switch Control Conduit (Transfer Switch Communication - ATS Control ) - Qty 1 - #RS-485, Qty 1 - 18ga Shielded Twisted Pair
ATS #1 - 4 Display Panel
ATS Remote Annunciator Panel
Engineer's OfficeFire Command
ATS # 4 ATS # 3 ATS # 2 ATS # 1
2.69/25/2015
NTS
Pad Layout
Arizona Generator Technology
7901 North 70th Avenue
Glendale, Arizona 85303
-
GEN-TECH POWER GENERATION SPECIALISTS
S2653
Le Meridien
AC Hotel Marriott
Generator Set
Wiring and Conduit Layout
Level Indication Sender
Remote Fill Station Panel Generator Fuel Tank - Fuel Tank Sender ( Communication)
Generator Set Remote Fill Station Control ConduitQty 1- Wire Control wires fuel Level Sender (RS-485)Qty 8 - #14ga Wire Control wires Fuel Level Full, High, and Critical High)Qty 2 - 120/208vac Power (control power (emergency))
120/208vac Power
Emergency Power 120/208 vac Panel
For Reference Only, refer to Submittal Drawing for Additional Information
Level Indication Sender
Full Indication Sender
Critical High Indication Sender
High Indication Sender
Full Indication Sender
Critical High Indication Sender
High Indication Sender
2.79/25/2015
NTS
Pad Layout
Arizona Generator Technology
7901 North 70th Avenue
Glendale, Arizona 85303
-
GEN-TECH POWER GENERATION SPECIALISTS
S2653
Le Meridien
AC Hotel Marriott
Generator Set
Wiring and Conduit Layout
Fire Alarm Control Panel
Generator Set and ATS Status
Fire Alarm Control PanelQty 2 - Control wire for Generator StatusQty 2 - Control wire for ATS Status
Generator Status - Run
Generator Set Status - Run Relay
ATS Status - Emergency
Automatic Transfer Switch ATS Status
For Reference Only, refer to Submittal Drawing for Additional Information
2.89/25/2015
NTS
Pad Layout
Arizona Generator Technology
7901 North 70th Avenue
Glendale, Arizona 85303
-
GEN-TECH POWER GENERATION SPECIALISTS
S2653
Le Meridien
AC Hotel Marriott
Generator Set
Wiring and Conduit Layout
Controller
Louver Control / Generator Air Supply
Run Relay
Generator Controller
Generator Louver ControlQty 2 - Control Wiring for Lovuver operation
For Reference Only, refer to Submittal Drawing for Additional Information
2.99/25/2015
NTS
Pad Layout
Arizona Generator Technology
7901 North 70th Avenue
Glendale, Arizona 85303
-
GEN-TECH POWER GENERATION SPECIALISTS
S2653
Le Meridien
AC Hotel Marriott
Generator Set
Wiring and Conduit Layout