. , , I . JUl 31imlO July 27, 2000 Ms. Sue Thayer Vermont Department of Environmental Conservation Waste Management Division 103 South Main St. / West Bldg. Waterbury, VT 05671-0404 RE: After-the-Fact UST Closure Assessment, Former Desautels Trucking, Enosburg Falls, Vermont. Facility ID# 2497 Dear Ms. Thayer: This letter contains a summary of the after-the-fact underground storage tank (UST) closure assessment conducted at the above referenced site. This investigation was conducted to assess soil quality in the vicinity of a former 10,000-gallon diesel UST which did not have a site assessment conducted at the time of its removal. This work was completed by Griffin International, for Luc Desautels. The UST was estimated to be at least 17 years old. The UST had a capacity of 10,000 gallons, and was used to store diesel fuel for use in the company's vehicles. The UST was of single-wall steel construction and was not replaced. The UST was reportedly removed.from the subsurface during the summer of 1992, .A site--assessment was not conducted at the time of the UST removal. The after-the-fact UST closure inspection was conducted on July 24, 2000. Excavation was performed by Mr. Desautels. Excavation was performed in the vicinity of the former UST. Mr. Desautels identified the area as being the location of the former UST. Excavation was extended to a depth of approximately 12 feet below grade. Soil samples were collected from the excavation for field screening. Soil samples were screened for volatile organic compounds (VOCs) using a properly calibrated Hnu Model HW-101 photoionization device (PID) equipped with a minimum 10.2 eV bulb. Soils from grade to an approximate depth of 12 feet were comprised of coarse gravel. Soils in this area were observed to be stained gray and contained an odor resembling P.O. Box 943. Williston, VT 05495. Phone 802-865-4288 • Fax 802-657-4129 59 Clinton Street. Plattsburgh, NY 12901 • Phone 518-562-4666 • Fax 518-561-6832
Transcript
Page 1: , I JUl 31imlO · 2014. 4. 18. · , I . JUl . 31imlO . July 27, 2000 . Ms. Sue Thayer Vermont Department of Environmental Conservation Waste Management Division . 103 South Main

. , , I

. JUl 31imlO

July 27, 2000

Ms. Sue Thayer Vermont Department of Environmental Conservation Waste Management Division 103 South Main St. / West Bldg. Waterbury, VT 05671-0404

RE: After-the-Fact UST Closure Assessment, Former Desautels Trucking, Enosburg Falls, Vermont. Facility ID# 2497

Dear Ms. Thayer:

This letter contains a summary of the after-the-fact underground storage tank (UST) closure assessment conducted at the above referenced site. This investigation was conducted to assess soil quality in the vicinity of a former 10,000-gallon diesel UST which did not have a site assessment conducted at the time of its removal. This work was completed by Griffin International, Inc:~(Griffin) for Luc Desautels.

The UST was estimated to be at least 17 years old. The UST had a capacity of 10,000 gallons, and was used to store diesel fuel for use in the company's vehicles. The UST was of single-wall steel construction and was not replaced. The UST was reportedly removed.from the subsurface during the summer of 1992, .A site--assessment was not conducted at the time of the UST removal.

The after-the-fact UST closure inspection was conducted on July 24, 2000. Excavation was performed by Mr. Desautels.

Excavation was performed in the vicinity of the former UST. Mr. Desautels identified the area as being the location of the former UST. Excavation was extended to a depth of approximately 12 feet below grade. Soil samples were collected from the excavation for field screening. Soil samples were screened for volatile organic compounds (VOCs) using a properly calibrated Hnu Model HW-101 photoionization device (PID) equipped with a minimum 10.2 eV bulb.

Soils from grade to an approximate depth of 12 feet were comprised of coarse gravel. Soils in this area were observed to be stained gray and contained an odor resembling

P.O. Box 943. Williston, VT 05495. Phone 802-865-4288 • Fax 802-657-4129 59 Clinton Street. Plattsburgh, NY 12901 • Phone 518-562-4666 • Fax 518-561-6832

Page 2: , I JUl 31imlO · 2014. 4. 18. · , I . JUl . 31imlO . July 27, 2000 . Ms. Sue Thayer Vermont Department of Environmental Conservation Waste Management Division . 103 South Main

Ms, Sue Thayer 07/27/00 Page 2

diesel fuel; a PID response ranging from 50 to 120 parts per million (ppm) was observed in these soils. Groundwater was observed to enter the excavation from the north side at an approximate depth of 5 feet below grade. Field screening results are presented in Table 1.

Table 1 Soil Screening Results Former Desaultels Trucking Enosburg Falls, VT July 24, 2000

Sample Number

PID Reading (ppm) Location

1 70 2 feet below grade 2 120 4 feet below grade 3 50 8 feet below grade 4 92 10 feet below grade 5 102 12 feet below grade 6 50 12 feet below grade 7 50 12 feet below grade 8 100 12 feet below grade Note: Soils screened with HNu Model HW-I0l PID

All of the soils excavated from the UST area were returned to the excavation.

A visual survey of the area surrounding the site was conducted at the time of the assessment. The site is located in an area that is mixed commercial and residential properties. The area is served by a private supply well; according to Mr. Desautels, the well is completed in bedrock to a depth of 465 feet below grade. The supply well is located approximately 300 feet to the northeast of the UST area. A shallow dug spring is located approximately 75 feet to the southwest of the source area; the spring is constructed of clay tile. On July 24, 2000, the water in the spring was observed to be approximately 20 feet below grade. The spring is used to supply water to the site garage; this water is reportedly not used for drinking. There were no surface water bodies observed in the direct vicinity of the site.

The adjacent garage building is constructed on a slab foundation; therefore, there is likely little risk of petroleum vapor migration impact to the garage building. The nearby residence is constructed on a basement foundation; the residence is located in what is perceived to be an upgradient location and is therefore likely at little risk of petroleum vapor migration impact. No complaints of petroleum odors are known to have been reported in the immediate vicinity of the site.

Page 3: , I JUl 31imlO · 2014. 4. 18. · , I . JUl . 31imlO . July 27, 2000 . Ms. Sue Thayer Vermont Department of Environmental Conservation Waste Management Division . 103 South Main

Ms, Sue Thayer 07/27/00 Page 3

Other than soil and groundwater, there are no known receptors currently impacted by the residual petroleum contamination at this site. Please call with any questions regarding this site.

Robert Higgins Engineer

Cc: Mr. Luc Desautels, Desautels Trucking Mr. David Stowe GI#70041720

Page 4: , I JUl 31imlO · 2014. 4. 18. · , I . JUl . 31imlO . July 27, 2000 . Ms. Sue Thayer Vermont Department of Environmental Conservation Waste Management Division . 103 South Main

, ..

State of Vermont

. AGENCY OF NATURAL RESOURCES Department or Environmental Conservation

Department of Fish and Wildlife Waste Management Division

Department of Forests. ParXll and Recreation 103 South Main StreetlWest Office

Department of Environmental Conservation Waterbury. Vermont 05671-0404 Stale Geologist (802) ~41-3888, FAX (802) 241-3296 RELAY SERVICE FOR THE HEARING IMPAIRED 1·800·253'()191 TDD>Voice 1·800·253'() 195 Voice>TOO SITE INVESTIGATION EXPRESSWAY NOTIFICATION FORM

Lee: TIe c:;G2 u±e1Site Owner;_--==-=::...--'-=---.;lI....5......l.o'--l..~~ _

Site Name, Town: LIJe...- ]ASa u te t\s TtyC 1..(,'\(11'\ ,\/ -~.

~ Yes, this site will participate in the Site Investigation Expressway Process.

No, this site will not participate in the Site Investigation Expressway Process..

If yes, please complete the checklist below:

,/ Contamination present in soils above action levels

If yes, summarize levels:

No

,/

,/

,/

Free product observed _ Yes v;;;: Groundwater contamination observed _ Yes ~ Surface water contamination obse~ed _ Yes ~ Suspected release of hazardous su~s~nces ~ _ No

If yes, please explain:

,/ Affected receptors Z"'_NO If yes, please identify receptors including names and addresses of third party receptors;

Sol l '

'0 / Please provide an ''t;::1J;n;;:r you expect In submit SIte Investigation Repn~; '. 2i/,' if:J ,f ( Owner's SignaturelD:te~ try Ls: ~kJ,> Consultant's Signature/Date: k'.:- .:e:fj ttL)) [,)..:1,;;:.-.-'"

The SMS has reviewed this expressway notification form and approves / disapproves of this action.

SMS Signature/Date: _

-/ Chlorine Free 100% Recycled Paper

Regional Offices .. Barre/Essex JctJPittsford/Rudan&N. Springfield/51. Johnsbury

Page 5: , I JUl 31imlO · 2014. 4. 18. · , I . JUl . 31imlO . July 27, 2000 . Ms. Sue Thayer Vermont Department of Environmental Conservation Waste Management Division . 103 South Main

.. ) ",- ~i

, " I ....1

.' , I I", ,1

N ' " \, " I

0 , "I '

'....~) I . '.R .---<\ ~ J.;. ..- - "T

_ , ..~.i _ '" ;--:f-­ .- ­i:

"

rH

/,1 .~I ....

-, : ,.I

..' .:

. ..1 ..•• .•• • , ... ... l .. c­. , I -"

i 1.1 ... i :

I,j

· ·- ·" I~·~ I

I '" .'

~.... . ( 1

Q ~ " "'L--/- ~" " ! , ' : .-: ; ­ /....' f "

. ' .J ,',

" ....r :-...,;;­

I " ,? '

, "

(-" " ;'

,, -

....

-"

. ....'.

.'

;'­.

I __ " -, 1

.' / '

.-::

I ." .. .-" ,-.. -­ _. ­

...1 '

I'

,1 ··•.

r l ' I

.- -, '-.:,.~-" )

( . . -~

,..

Griffin Job Number: 70041 720

Source: USGS Mapping Enosbu rg Falls Quadrangle 1986

Luc Desautels Trucking, Enosburg Falls, Vermont

Site Location Map USGS Mapping~RIFFIN

MERNATIONAL Date: 07/27/00 Drawing No. 0 Scale: 1:24,000 By: RH

Page 6: , I JUl 31imlO · 2014. 4. 18. · , I . JUl . 31imlO . July 27, 2000 . Ms. Sue Thayer Vermont Department of Environmental Conservation Waste Management Division . 103 South Main

. '

Luc Desautel's Trucking Facility ID 2497 UST Closure Inspection 07/27/00

General view of site

UST Excavation

Griffin International, Inc.

Page 7: , I JUl 31imlO · 2014. 4. 18. · , I . JUl . 31imlO . July 27, 2000 . Ms. Sue Thayer Vermont Department of Environmental Conservation Waste Management Division . 103 South Main

UNDERGROUND STORAGE TANK PERMANENT CLOSURE FORM Vermont Agency of Natural Resources, Department of Environmental Conservation, Waste Management Division

103 South Main Street, West Building, Waterbury, Vermont 05671-0404, Telephone: (802) 241-3888

Agency Use Only " ..." Date of scheduled Activlry 1:-1?:!1ltiWacili DEC initials: ~j/ - S S

Section A. Facility Information: Name of facility: ,--LIe{)E:4vn-z 5 'TYlQ~jJlr-" '. N~ber of employees: (}Y7kmwl1 Street address: 1'17-5 ~"'22~n~dk.. ~-.L lk!c.JIe- 10 s= Town/city cnt7'S/;vg.. rallS Owner of UST(s) to be closed:-.tpc.. 7>esav+.eJs Contact(if differe~ than owner): Mailing address of owner: 130x 35/ ~nne7C/e 7?t::t;HI. . 3cl. :/l:J;-cl, VI- -~~'9-I=----=~'---L--P---Telephone number of owner: 2'02- Z~T- 7-/c:;O Contact telephone #: _

Section B. UST Closure Information: (please check one& t> Reason for initiating UST closure: _Suspected Leak ~Liability _Replacement~Abandoned

liSTs (nininl! is considered a part of UST system) underzoina oermanent closure. Include condition of USTs

UST # Product Size (gallons) Tank age Tank Condition Piping age Piping condition , n,pc;~( 10000 11"7­ I '~1 kilt I'kfV'­ 11­ , .m, tUldW Y\

Which tanks, if any, will be closed in-place: USTs# 1'10i't~ Authorized by: k/A....: Date: / / Disposal/destruction of removed UST(s): Location k'vt kVl~ Method--1h1 kl1Ok11A.. Date: -// ­Amount (gal.) and type of waste generated from USTs: I J It1 l( Ir1 4'kM-­(tank contents are hazardous wastes unless recovered as usable prod:-T:":"uc::':t~)~-lQ"..LIo-I"""""= _

Tank cleaning company (must be trained in confined space entry) V~ k 11{!16.tV\.. ­Certified hazardous waste hauler :12vt 1A V] lY1A.oo... --G=-en-e--.:rlo£.a....:.to.1..r~I.;!!D:u-'-nu""m"-;--b-"=er"---:-----,---------Uti knc~

Section C. Initial site characterization: Work in this section must he completed by a professional environmental consultant or hydrogeologist with experience in environmental sampling fllr the presence of hazardous materials. A full report from the consultant must accompany this form. Ij;.xcavation information: (some tank pulls reauire more than one excavation)

Tankts) II Depth Groundwater and Peak of Avg Bedrock encountered?

Excavation Depth Excavation PlD Peak PlD Depth (yIn) and at Soil type (A,B,C,rtf) (ft) size(ft%) reading (rt) reading (ft) depth (ft)

.i.__ 12­\00 rZO L./ ?-Cf Vu14l1U"­ lACS d

'5" a V71IJ'C:? J ()

Dig Safe Number:_----'~'-~!..I£.!lI~=- _ PID information: Makc:.l:i~_Model:--'--'-='----=-=---'--_Calibration information (date, time, gas): '7-9'1.60c::'ez, ~8'S-) 1'5C>

Locate all readings and samples on site diagram . Number of soil samples collected for laboratory analysis?~ results due date _/_/_ \, Have any soils been polyencapsulated on site? Yes_(#yd~__PID range above zero Inw __- __""ak) N04­Have any soils been transportedpff site? Yes_list amount (yds): NoX ~I Location transported £0: lLfp- DEC official who approved ~"",a-",=- _ Amount of soils backfilledtyds'): dS: PID range above zero I"w ~-lW peak

Have limits of contamination been defined? Yes No~. Is there any other known contamination on- site? Yes_N01\-Cominents: --- _

Free Phase product encountered? Yes :thickness sheen NoK . Groundwater encountered? Yes~ depth(ft) S-No_­& Are there existing monitoring wells on:sne? Yes how many:__(locate on site diagram)No . Have new monitoring wells been installed? Yes how many:__(locate on site diagram)No Samples obtained from monitoring wells.for lab analysis? Yes_ results due date _/_/_ NoJ(

Is there a water supply well on site? Yes \t (check type: shallow__rockLspring ) No_ Number of public water supply wells arel&ated within a 0.5 mile radius?_min. distance (ft.):_ tJ\,lklA~ Number of private water supply wells located within a 0.5 mile radius?JL.. min distance (ft.):,:-]b~eoQ.....t'!tJIi'I!!!~!.._=-~

Receptors impacted? ~Oil _indoor air _ambient air _groundwater _surface water _water sup~IY

Page 1 of2

Page 8: , I JUl 31imlO · 2014. 4. 18. · , I . JUl . 31imlO . July 27, 2000 . Ms. Sue Thayer Vermont Department of Environmental Conservation Waste Management Division . 103 South Main

Facility ID# ;;2tf9+­Section D: Tanks/Piping Remaining/installed ~egardless of size, includ~ USTs at site as to *status, e.g. "abandoned", "in use", or "to be installed". (Most Installations recurre nerrruts and advance notice to this office.)

usn Product Size(gallons) Tank age *Tank status Piping age ·Piping Status

2\-There are no other tanks at this site.

Section E. Statements of UST closure compliance: (must have both signatures or site assessment not complete)

As the party responsible for compliance with the Vermont UST Regulations and related statutes at this facility, I h by ce tify that r all of the, information provided on this form is true and correct to the best of my knowledge.

k '1J( k. ~kl) 1/~l/(ju Signature 0 ST owner or owner's authorized representative Date of signature

As the environmental consultant on site, I hereby certify that the site assessment requirements were performed in accordance with DEC policy and regulations, and that information which I have provided on this form is true and correct tlb the best )f my knowledge.

Sigt~nv' 1tfo1:~tureI t Company:_G . ~<' \At._ Telephone ;1f::KQ.Z:_~S- Date of Closure:1..)?1./{tmate of Assessmentt-/2<f! 00

Return form along with complete narrative report and photographs to the Department of Environmental Conservationt Dfit"), Underground Storage Tank Program within 72 hours of closure.

Site diagram

This Closure Form may only be issued for the facility and the date indicated at top of page 1. Changes in the scheduled closure date should be phoned in at least 48 hours in advance. Both the yellow and white copies of this form must be returned to the address on the top of paee 1 of this form: the pink copy should beretained by the UST owner. A written report from an environmental consultant covering all aspects of closure and site assessment, complete with photographs and any other relevant data, must accompany this form. All procedures must be conducted by qualified personnel, to include training required by 29 CFR 1910.120. Documentation of all methods and materials used must be adequate. All work must be performed in compliance with DEC policy "UST Closure and Site Assessment Requirements" as well as all applicable statues, regulations, and additional policies. The DEC may reject inadequate closure forms and reports.

Page 2 of2


Recommended