LASERSPEED 8000/9000
I/O MODULE
INSTRUCTION HANDBOOK
- installation, setup, technical reference -
Manual Part Number: 93342 • Manual Drawing Number: 0921-01516 • English • Revision E • © Copyright Dec 2013
www.betalasermike.com
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Part No. 93342 / Drawing No. 0921-01516 Page 2 of 84 Revision E (Dec 2013)
Contents
Proprietary Statement .............................................................................. 3
European Commission Requirements .................................................... 4
Declaration of Conformity ....................................................................... 5
Safety Information .................................................................................... 6 General Safety Information .....................................................................6 Intended Use ..........................................................................................6
Introduction .............................................................................................. 7 I/O Module Front Panel ...........................................................................7
Installation ................................................................................................ 8 Rear Panel Pin-outs ................................................................................8 Parallel Outputs .................................................................................... 16 Parallel Outputs .................................................................................... 20 Elongation/Synchronization .................................................................. 24 Master/Slave I/O Modules..................................................................... 24 Synchronization .................................................................................... 26 Elongation/Differential Speed Calculation ............................................. 27
Setup ........................................................................................................28 Data Format.......................................................................................... 28 Serial Communications ......................................................................... 31 I/O Module Configuration Commands ................................................... 34 I/O Module-to-LaserSpeed Communication .......................................... 60
Operation .................................................................................................61 Understanding the Front Panel ............................................................. 61 Profibus Operation ................................................................................ 62 Ethernet Network Operation ................................................................. 75
Servicing Your Equipment ......................................................................79 Returning Equipment for Service .......................................................... 79
Specifications ..........................................................................................80 Stand-alone Dimensions ....................................................................... 80 Rack Mounting Dimensions .................................................................. 80 Bottom Mounting Dimensions ............................................................... 81 General Specifications .......................................................................... 82
Index .........................................................................................................84
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Proprietary Statement
Part No. 93342 / Drawing No. 0921-01516 Page 3 of 84 Revision E (Dec 2013)
Proprietary Statement Manufacturer/Distributor Beta LaserMike, 8001 Technology Blvd., Dayton, OH 45424, USA
About This Manual This manual contains descriptions, drawings, and specifications for a Beta LaserMike product. Equipment or
products made prior to or subsequent to the publication date of this manual may have parts, features, options,
or configurations that are not covered by this manual. Specifications contained herein are subject to change
by Beta LaserMike without prior notice. Beta LaserMike is not responsible for errors or omissions that may be
contained herein or for incidental or consequential damages in connection with the furnishing or use of this
information.
The information contained in this manual is the property of Beta LaserMike. The information disclosed in this
document is furnished in confidence and upon the condition that individual and corporate intellectual rights,
whether patented or not, will be respected. If this document is supplied on removable media (e.g. CD), an
electronic copy (stored on-site) and one printout is permitted. If this document is supplied in printed form, no
part of this document may be reproduced or scanned without the prior written consent of Beta LaserMike.
This document may not be distributed or circulated to third parties.
Limited Warranty Beta LaserMike will correct by repair, or at Beta LaserMike‘s option, by replacement, F.O.B Beta LaserMike’s
plant, any defect in workmanship or material in any equipment manufactured by Beta LaserMike which
appears under normal and proper use within twelve months from the date of shipment (eighteen months for
OEM’s), provided Beta LaserMike is given reasonable opportunity to inspect the alleged defective equipment
at the place of its use and under conditions of its use.
EXCLUSIONS: This warranty does not cover products which have been modified, altered, or repaired by any
other party than Beta LaserMike or its authorized agents. Furthermore, any product which has been, or is
suspected of being damaged as a result of negligence, misuse, incorrect handling, servicing, or maintenance;
or has been damaged as a result of excessive current/voltage or temperature; or has had its serial number(s),
any other markings, or parts thereof altered, defaced, or removed will also be excluded from this warranty.
WARRANTY SERVICE AT CUSTOMER SITE: Warranty service performed at the customer’s facility will be
free of charge for parts and labor; however, the customer will be liable for transportation and living expenses
of personnel dispatched to effect such repair. A purchase order or other written confirmation of the
acceptance of these charges, signed by an authorized individual, will be required prior to commencement of
repairs. Additional charges may be assessed the customer if: 1) The equipment is not made available on a
timely basis, 2) The equipment is found to be without fault, and/or 3) It is determined the equipment is not
under warranty, whether by expiration of the warranty or any act which voids the warranty.
OTHER THAN AS SET FORTH HEREIN, BETA LASERMIKE MAKES NO WARRANTIES, EXPRESSED OR
IMPLIED, OF MERCHANTABILITY AS TO THE EQUIPMENT MANUFACTURED BY IT, AND THERE ARE
NO EXPRESSED OR IMPLIED WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE
FACE THEREOF. Beta LaserMike’s obligation to correct defects in such equipment by repair or replacement
in accordance with the foregoing provisions is in lieu of any other warranties, expressed or implied, and in no
event shall Beta LaserMike be liable for incidental or consequential damages. No service of Beta LaserMike’s
equipment is permitted during the warranty period without the specific written consent of Beta LaserMike.
Note:
For information
about servicing
and returning
your equipment,
see the section
at the end of this
manual.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
European Commission Requirements
Part No. 93342 / Drawing No. 0921-01516 Page 4 of 84 Revision E (Dec 2013)
European Commission Requirements
This equipment is intended for use in a heavy industrial environment. The equipment generates, uses and
can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may
cause harmful interference to other equipment. There is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to other equipment the user is
encouraged to try to correct the interference by one or more of the following measures:
- Re-orientate or relocate the equipment.
- Increase the separation between the pieces of equipment.
- Connect the pieces of equipment on separate mains circuits.
- Ensure that the relevant items of equipment are properly and securely earthed to a common earth point
using adequately sized cable or other means of connection.
Where supplied or specified, shielded interconnection cables must be employed with this equipment to ensure
compliance with the pertinent RF limits. Changes or modifications not expressly approved by the company
could void the user’s authority to operate the equipment.
This product has been rigorously tested to comply with the European EMC (Electromagnetic Compatibility)
Directive. With regard to this, Beta LaserMike recommends that any non-Beta LaserMike peripheral
equipment is CE marked for the Heavy Industrial environment (EN50082-2). Beta LaserMike also
recommends that any cables not supplied by Beta LaserMike, but used for powering Beta LaserMike
equipment, be built using good EMC practices (i.e. cables with braided shield, and connectors with 360
termination of the braid to a metal/metalised shell connector at both ends). If you have any questions
regarding this, contact the Beta LaserMike Service Department.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Declaration of Conformity
Part No. 93342 / Drawing No. 0921-01516 Page 5 of 84 Revision E (Dec 2013)
Declaration of Conformity
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Safety Information
Part No. 93342 / Drawing No. 0921-01516 Page 6 of 84 Revision E (Dec 2013)
Safety Information
General Safety Information
Under NO circumstances should the earth/ground safety connections be broken – internal damage to sensitive electronic components may occur and at worst electrocution to personnel may result.
The protective conductor terminal symbol is shown to the right.
This equipment must be earthed/grounded.
Relays and associated wiring are rated for SELV levels i.e. 60 Vdc & 30 vac rms. These levels must not be exceeded.
Maintenance, repairs and electrical connections should be performed by a suitably qualified person for the country of installation.
Do not position the equipment so that it is difficult to operate the disconnecting device.
Intended Use
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
Note: If the
equipment is not
used in the
manner specified
by Beta
LaserMike, the
protection
provided by the
equipment may
be impaired.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Introduction
Part No. 93342 / Drawing No. 0921-01516 Page 7 of 84 Revision E (Dec 2013)
Introduction
The LaserSpeed I/O Module is used to translate the serial output data, Speed,
Length and Gauge Status, from a LaserSpeed 8000 or 9000 Series Gauge to a
parallel output. Optional Profibus and Ethernet field bus are also available in the
I/O Module. The I/O Module connects to the LS9000/LS8000 gauge through a
gauge cable via an RS422 connection, and provides a pass-through connector
for direct access to all the Inputs and Outputs of the LS9000/LS8000 Series
Gauge. A Light Stack connector provides signals to drive a visual indicator (a
light stack) to display the status of the gauge. The I/O Module can also be used
calculate the Elongation Ratio/Differential Speed between two LS8000/LS9000
Series gauges. In addition, the I/O Module can be used to synchronize the
outputs of multiple gauges to output their data at the same time.
I/O Module Front Panel
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 8 of 84 Revision E (Dec 2013)
Installation
Rear Panel Pin-outs
The following sections describe the various connections to the I/O Module’s rear
panel. Refer to the LS9000/LS8000 Instruction Handbook for further information
about connections to the Gauge.
Power
Accepts IEC 320 power cords. AC power requirements are 90-260VAC,
50/60Hz, 1.5Amps.
I/O Setup
A computer can be connected to this port using a straight-through 9-pin serial
cable for diagnostics and configuration. LaserTrak 4.0 can be used to configure
the LaserSpeed gauge through this port. A NULL modem is not required.
Display
Connects directly to the LaserSpeed I/O Module Display, part number 85871.
This is an LCD indicator that shows the current Length, Velocity, Quality Factor,
and Status.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 9 of 84 Revision E (Dec 2013)
Light Stack
Output to drive a light stack. Outputs pull up to +24 volts.
Color Meaning Laser Emission?
Green Laser OFF No
Yellow Laser ON, Shutter is CLOSED No
Red Laser ON, Shutter is OPEN Yes
LaserSpeed Gauge
TO GAUGE 37 pin D connector for connection to the LaserSpeed gauge
cable. This connector is compatible with all cables that have
part number 85277.
PASS-THROUGH Passes signals from the DB25 connector on a
LS9000/LS8000. The pinout of this connector is compatible
with 25-pin LaserSpeed breakout boxes. Signal descriptions
are listed in a table below.
ETHERNET Pass-through connector for the LS9000/LS8000 gauge’s
optional Ethernet connection that provides a direct
connection to the gauge over Ethernet. If the attached
gauge does not have the Ethernet option installed, then this
connector is not used.
RS-232 Pass-through connector for the LS9000/LS8000 gauge’s RS-
232 serial port. This connector can be connected to a PC
using a straight-through DB9 serial cable. LaserTrak or a
terminal program can be used to communicate directly with
the gauge via this serial port.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 10 of 84 Revision E (Dec 2013)
SYNC IN and OUT connector
Used to connect multiple I/O modules together for gauge-gauge synchronization,
and Elongation/Differential Speed calculation. The Sync Out connector of one
I/O module connects to the Sync In connector of the next I/O Module with a
straight-through RJ-45 cable.
IN Connects to the Master I/O module.
OUT Connects to SYNC IN of the next I/O Module in the Daisy Chain.
Parallel Outputs
STATUS Parallel Output for Status / Interlock Control / Shutter Control
VELOCITY Parallel output for Velocity
LENGTH/ELONGATION Parallel output for Length or Elongation Ratio
The LENGTH/ELONGATION port can output either Length or the Elongation
Ratio between two gauges, depending on the I/O Module’s position in the
system. All I/O Modules except for the last I/O module in the Daisy Chain
calculate the Elongation Ratio or Differential Speed. The last I/O module in the
Daisy Chain always outputs Length on the Length/Elongation port. All other I/O
Modules output Elongation Ratio if the port is configured for Auto-Elongation
Mode. The ~I:Elongation command is used to configure this mode. By default,
the ~I:Elongation setting should be set to 1 on all I/O Modules. This will cause
the I/O Module to automatically output Elongation if it is being calculated. See
the Elongation/Synchronization section for more information about Elongation.
Note: Elongation Ratio will only be calculated when two gauges are synchronized
together by connecting the Sync Out of one I/O Module to the Sync In of the
other I/O Modules.
unconnected
Middle
SlaveMiddle
Slave
Last
SlaveMaster
to sensor
I/O Module
to Master to Slave
unconnected
I/O Module
to Master to Slave
I/O Module
to Master to Slave
I/O Module
to Master to Slave
INOUT INOUT INOUT
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 11 of 84 Revision E (Dec 2013)
Connections
Connect the LaserSpeed 8000/9000 to the TO GAUGE input using the supplied
cable.
Status pins 17, 18, and 26 and 19, 27, and 30 must be connected as shown for
the gauge to operate. An interlock shunt connector is supplied with the interlock
connections pre-wired. Beta LaserMike recommends that you use the supplied
key switch to operate the Laser Interlock. This will provide you with a laser
shutoff for maintenance or material changes.
Pin 18 = Laser Interlock (+)
Pin 19 = Laser Interlock (-)
Pin 26 = Shutter Interlock (+)
Pin 27 = Shutter Interlock (-)
+5-24VDC
Ground
+5-24VDC
Ground
1819
2627
17
30
Pin 17=+5V 18=Laser+19=Laser-26=Shutter+27=Shutter-30=Ground
Pin Pin Pin Pin Pin
Note: The Setup
section of this
manual will help
you configure the
I/O Module with
the LaserSpeed
Gauge. Use the
LaserTrak
software to setup
the LaserSpeed
Gauge itself.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 12 of 84 Revision E (Dec 2013)
Pass-through Connector Pinout
Male 25-Pin D-Subminiature
Pin Pin Description
1 RS232 Transmit (From Gauge to User)
2 RS232 Receive (From User to Gauge)
3 Phase A True – Fixed Output
4 Phase A False – User Selectable
5 Phase A False – Fixed Output
6 Phase B True – User Selectable
7 Phase B True – Fixed Output
8 Phase B False – User Selectable
9 Phase B False – Fixed Output
10 Material Present Input
11 Signal Ground for Inputs/Outputs/Serial
12 No Connection
13 No Connection
14 Measurement Direction Input
15 Phase A True – User Selectable
16 No Connection
17 No Connection
18 Length Reset 1
19 Signal Ground for Inputs/Outputs/Serial
20 User Vin: Voltage Input for Isolated Pulse Outputs (5 to 28 V DC). The
voltage supplied will be the voltage level of the pulse outputs supplied by
the LS4000-1. If a Voltage is not supplied, the pulse outputs will be TTL
level, or 3.7 volts minimum. Because this voltage input is isolated from
the power input, it must be references to one of the Signal Ground pins.
For example, if you want the pulse outputs to be 12 V outputs, use a 12
V power supply by connecting the positive terminal to pin 20 and the
ground terminal pin to pin 11, 19, or 21.
21 Signal Ground for Inputs/Outputs/Serial
22 Index (Printer) Pulse True
23 Index (Printer) Pulse False
24 +24V Power Input (Fused)
25 +24V Power Input (Fused)
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 13 of 84 Revision E (Dec 2013)
Gauge Connector Pinout
Female 37-Pin D-Subminiature
The Gauge connector is connected to the LS9000/LS8000.
Pin Pin Description
1 RS232 Transmit (From Gauge to User)
2 RS232 Receive (From User to gauge)
3 Phase A True – High Speed output
4 Phase A False – User Selectable
5 Phase A False – High Speed Output
6 Phase B True – User Selectable
7 Phase B True – Highs Speed Output
8 Phase B False – User Selectable
9 Phase B False High Speed Output
10 Measurement Hold Input, can be activated by I/O Module
11 Signal Ground for Inputs/Outputs/Serial
12 Power Ground for 24V
13 Power Ground for 24V
14 Measurement Direction Input 1
15 Phase A True – User Selectable
16 Laser Interlock
17 Shutter control
18 Length Reset 1, can be activated by I/O Module
19 Signal Ground for Inputs/Outputs/Serial
20 User Vin: Voltage Input for Isolated Pulse Outputs (5 to 28 V DC). The
voltage supplied will be the voltage level of the pulse outputs supplied by
the LS4000-1. If a Voltage is not supplied, the pulse outputs will be TTL
level, or 3.7 volts minimum. Because this voltage input is isolated from the
power input, it must be references to one of the Signal Ground pins. For
example, if you want the pulse outputs to be 12 V outputs, use a 12 V
power supply by connecting the positive terminal to pin 20 and the ground
terminal pin to pin 11, 19, or 21.
21 Signal Ground for Inputs/Outputs/Serial
22 Index (Printer) Pulse True
23 Index (Printer) Pulse False
24 +24V Power Output (Fused)
25 +24V Power Output (Fused)
26 RS422 Transmit +
27 RS422 Transmit -
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 14 of 84 Revision E (Dec 2013)
28 RS422 Receive +
29 RS422 Receive -
30 Ana log Output voltage
31 Signal ground
32 Core sync input+
33 Core sync input-
34 Ethernet tx+
35 Ethernet rx-
36 Ethernet tx-
27 Ethernet rx-
Note 1: User Input requiring 5 to 28 V to activate.
General Note: The Laser Interlock is in series with the front panel switch.
Gauge RS-232 Connector
Female 9-Pin D-Subminiature
1 NC
2 RS232 Xmit from gauge
3 RS232 Rec to gauge
4 NC
5 Signal ground
I/O Setup Connector
Female 9-Pin D-Subminiature
1 NC
2 RS232 Xmit from I/O module
3 RS232 Rec to I/O module
4 NC
5 Signal ground
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 15 of 84 Revision E (Dec 2013)
Light Stack Connector Pinout
Female 9-Pin D-Subminiature
1 Pulled up to 24 volts for red light stack
2 Pulled up to 24 volts for yellow light stack
3 Pulled up to 24 volts for green light stack
4 +24 volts
5 24 volts ground
6 +24 volts
7 Reserved – Do Not Connect
8 Reserved – Do Not Connect
9 NC
Notes:
Pin 1 (or Red on the Light Stack) is active when the Status Input from the
LS9000/LS8000 shows power is being sent to the laser and that the
Shutter is open.
Pin 2 (or Yellow on the Light Stack) is active when the Status Input from
the LS9000/LS8000 shows power is being sent to the laser and the
shutter is closed.
Pin 3 (or Green on the Light Stack) is active when there is no power
being sent to the laser.
Pin 4 and 6 are 24 volts at 1 amp for the Light Stack.
Pin 5 is signal ground.
When the red and yellow lamps flash alternately, this indicates that there are no
communications from the LaserSpeed gauge.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 16 of 84 Revision E (Dec 2013)
Parallel Outputs
There are three, 37-pin D-Subminiature, Parallel output ports:
Parallel Port Description
Status Outputs the system status and accepts control inputs
Length/Elongation Outputs either Length from the gauge or Elongation
Ratio that is Calculated in the I/O Module.
Speed Outputs the Velocity measurement from the gauge
Status Signals
Status Signals (pins numbered 1–16) are generated as solid state closures. The
contacts close when the condition is true. The contact maximum voltage and
current ratings are: 200mA at 30 VAC/VDC for resistive loads.
System input signals (pins numbered 20–31) are optically-isolated input signals
between 5VDC and 30VDC. The input should be applied to the INPUT+ pin, and
ground should be applied to the INPUT– pin for each signal used. Refer to the
following table pin-out information.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 17 of 84 Revision E (Dec 2013)
Pin Assignment for System Status
Pin Signal Name I/O Description
1 Material Present+ Output+ Contact Closure Output indicating the Material Present
state.
Closed = Material is Present
Open = Material is Not Present
2 Material Present- Output-
3 Valid Measurement+ Output+ Contact Closure Output indicating when the LaserSpeed
gauge is making valid measurements
Closed = LaserSpeed gauge is Measuring
Open = LaserSpeed gauge is Not Measuring
4 Valid Measurement – Output-
5 System Ready + Output+ Contact Closure Output indicating if the system is ready
to measure. This output is closed when the Laser is ON,
the Shutter is Open, and the Laser is at the correct
temperature.
Closed = System is Ready to Measure
Open = System is Not Ready to Measure
6 System Ready – Output-
7 Laser Power + Output+ Contact Closure Output indicating if the Laser Power is
on.
Closed = Laser is ON
Open = Laser is OFF
8 Laser Power – Output-
9 Reserved Output+ Reserved Contact Closure Output
Do Not Connect 10 Reserved Output-
11 Laser Temperature+ Output+ Contact Closure Output indicating if the Laser is at the
correct temperature.
Closed = Laser Temperature is Ok
Open = Laser Temperature is not within tolerance
12 Laser Temperature – Output-
13 Laser Operational+ Output+ Laser is Operational: Shutter Open + Laser Power
Closed = Laser is Operational (Laser emission)
Open = Laser is not Operational (no Laser emission)
14 Laser Operational – Output-
15 Comm Error + Output+ Contact Closure Output indicating if the I/O Module is
communicating with the LaserSpeed gauge.
Closed = Communication Ok
Open = Not Communicating
16 Comm Error – Output-
17 +5 volts (fused, 1A) Output +5VDC Output for connection to interlock signals when
wiring as contact closure Inputs.
18 Laser Interlock+ Input+ Laser Interlock input to LS9000/LS8000. See
connection diagram for wiring instructions. See also note
at end of table. 19 Laser Interlock- Input-
20 Reserved Input+ Do not use
21 Reserved Input-
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 18 of 84 Revision E (Dec 2013)
22 External Material
Present +
Input+ The External Material Present input is used to control
when the gauge will measure. The gauge will measure
when External Material Present is active and will not
measure when External Material Present is not active.
External Material Present is enabled and disabled via
serial commands for the gauge. See Serial Commands
listing in the gauge manual.
23 External Material
Present –
Input-
24 Reserved Input+ Do not use
25 Reserved Input-
26 Shutter + Input+ Shutter Control Input to LS9000/LS8000. See
connection diagram for wiring instructions 27 Shutter - Input-
28 Reserved N/C Do not use
29 Reserved NC
30 GND Ground Ground for connection of I/O Signals
31 Reserved Do not use
32 Elongation Analog Output Elongation Ratio Analog Output. Minimum and
Maximum are configurable. An output of 0V
corresponds to the Minimum Elongation, and an output
of 2.048V corresponds to the Maximum Elongation.
33 GND Elongation Analog Output ground
34 Velocity Analog Output Velocity Analog Output. Minimum and Maximum are
configurable. An output of 0V corresponds to the
Minimum Velocity, and an output of 2.048V corresponds
to the Maximum Velocity.
35 GND Velocity analog Output ground
36 Quality Factor
Analog
Output Quality Factor Analog Output – voltage output changes
linearly from Quality Factor 0 to Quality Factor 15.
0 = 0 Quality Factor
2.048V = 15 Quality Factor
37 GND Quality Factor Analog Output ground
Note: The Laser interlock (Pins 18, 19) on the Status Port is in series with the
front panel Key Switch. The Key Switch and Pins 18 and 19 must be activated to
turn on the Laser.
External Material Present (MP)
This is an input to the bi-directional System Status port. This input is functional
only when the gauge is configured for External Material Present. When this
mode is at a Logic Low (or No Input), measurements are enabled. When this
input is at a Logic High (5 –30 volts), measurements are disabled.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 19 of 84 Revision E (Dec 2013)
Analog Outputs
Pins 32-37 of the SYSTEM STATUS port are used for various analog outputs.
Every I/O Module contains three analog outputs.
Elongation Analog Output – only used when using multiple I/O modules
are configured for Synchronization.
Velocity Analog Output
Quality Factor Analog Output
All analog outputs are non-isolated. You may set the scaling of the elongation
and speed outputs to fit your application. See the Serial Commands section.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 20 of 84 Revision E (Dec 2013)
Parallel Outputs
Data is updated to the bus in one of two modes. The first is called "Data Ready"
mode and the other is called "Data Request" mode. In "Data Ready" mode, the
system will automatically update the data on the Parallel Output Bus each User
Update Period. In "Data Request" mode, the system will update the data on the
Parallel Output Bus only when a Data Requested Signal is received on the Data
Request Input Pin. There are Data Request Input Pins on the Parallel Length/
Elongation port and the Parallel Velocity port. The data output mode is
configured by ~I:AckMode serial command:
Command Parallel Port Mode
~I:AckMode=0 Data Ready Mode
~I:AckMode=1 Data Request Mode
Data Ready Mode
In Data Ready mode, the I/O module outputs data each time a new measurement
is received from the LaserSpeed gauge. An optically isolated signal called "Data
Ready," located on the Length/Elongation and the Velocity Output connectors,
are provided to indicate when data has been upated and is valid. The Data
Ready pulse indicates that the data bus has been updated with new data and that
the signals on the bus are completely settled. Both Data Ready True (Rising
Edge Trigger, signal driven from ground to Voltage high) and Data Ready False
(Falling Edge Trigger, signal driven from Voltage high to ground) are provided.
When using Data Ready True, data should be read from the bus on the rising
edge of the signal, and when using Data Ready False, data should be read on
the falling edge. Either the leading edge or the active level of the signal can be
used to trigger a read by your interface.
Ringing on the line can occur if the cable is not properly terminated. This can
cause the data to be unstable during the time of the active edge of the data ready
signal. Allow for extra settling time if ringing occurs.
Signal Activity Data Valid On:
Data Ready (True) Active High Rising Edge
Data Ready (False) Active Low Falling Edge
Data is valid from the time that the Data Ready signal is asserted until the time
that the next data point is received from the gauge. This time varies depending
on the gauge’s Update Rate configuration setting. See the timing specifications
below for detailed timing information.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 21 of 84 Revision E (Dec 2013)
Data Ready (True) Timing
Data Ready (False) Timing
Parameter Symbol Value
Data Setup Time T1 300 µs (min.)
Data Ready Pulse Width T2 ReadyLn x 500µs
Data Valid Time T3 Update Rate - 500µs (min.)
Update Rate T4 1-2000 ms
The Data Ready Pulse Width and the Update Rate parameters can be configured
with a serial command. See the RS-232 Configuration Commands section for
details.
Choosing the correct polarity of "Data Ready" is important. Improper polarity
choice can lead to data that appears to be noisy or has spikes or is completely
invalid since the data may not be stable when it is read. In most cases, choosing
the correct "Data Ready" polarity for the interface is made before consideration of
the "Data Bit" polarity. The polarity of the Data Bits may or may not have to be
inverted by ~I:AckMode before the input module reads the data correctly.
DATA_READY
(True)
DATA
T1
T2
T3
T4
DATA_READY
(False)
DATA
T1
T2
T3
T4
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 22 of 84 Revision E (Dec 2013)
Data Request Mode
When the system is configured for Data Request mode, a "Data Request" signal
issued by the PLC/Control System is used to notify the I/O Module that new data
is requested by your interface. The following figure shows Data Request Mode,
indicating typical waveforms and listing the timing information necessary to use
this mode. "Data Request" is an optically isolated input and requires a pulse
supplied by your interface (5 to 24 volts DC).
Data Request Parallel Port Timing
*Data Ready False has the opposite polarity
Parameter Symbol Value
Data Request Period T1 1 ms (min.)
Data Request Pulse Width T2 20µs (min.)
Data Ready Response Time T3 570 µs (nominal)
Data Hold Time T4 120 µs (min.)
Data Setup Time T5 300 µs (min.)
Data Ready Pulse Width T6 ReadyLn x 500µs
Note: T6 is set using the serial command “~I:ReadyLn=X”, where X is an integer.
Divide the desired pulse width by 500µs, and use this value for X. When
configured in the "Data Request" mode, any Data Request from either Length or
Velocity will cause all "Data Request" type system outputs to be updated. Data
will remain on the output until a new "Data Request" is received. Only a single
Data Request Line from either the Length/Elongation Connector or the Velocity
connector should be utilized.
Note: If the Data Ready pulse length is configured to be longer than the Data
Request Period (T6>T1), the Data Ready output will always be high, and erratic
data may be read from the interface. Make sure that you configure the Data
Ready Pulse Width to be half the Data Request Period or less.
DATA_READY*
DATA
T5
T6
DATA_REQUEST
T4
T3
T1
T2
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 23 of 84 Revision E (Dec 2013)
Example: If data is required every 2 ms, the PLC should pulse the Data Request
signal every 2ms. The Data Ready Pulse Width should be configured to be less
than half the Data Request Period. Use the command ~I:ReadyLn=2 to configure
the Data Ready Pulse Width for approx 1ms.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 24 of 84 Revision E (Dec 2013)
Elongation/Synchronization
Multiple I/O Modules can be connected together for applications that require
measurement synchronization and calculation of length elongation/differential
speed. This is accomplished by interconnecting the I/O Modules’ SYNC ports,
which are located on the rear panel. The shortest user update rate is 2 ms when
calculating the elongation ratio. If 1 ms user update rate is selected in the gauge
the I/O Module will only update its outputs every 2 ms.
Master/Slave I/O Modules
I/O Modules can either be masters or slaves, depending on where they are
located in the system. The way that the I/O Modules’ SYNC ports are
interconnected determines their relationship. When measuring elongation
ratio/differential speed, the Master gauge is located before the first roller stand.
This gauge measures the lowest speed of all the gauges in the system. All the
other gauges in the system are Slaves. The Slaves’ measurements are
synchronized to the Master, and make all their measurements at the same time
as the Master.
See the drawing on the following page.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 25 of 84 Revision E (Dec 2013)
In the figure above, the I/O Modules are configured as follows:
Gauge Type
Calculates
Elongation?
Length/Elongation Port
Output
1 Master Yes Elongation
2 Middle Slave Yes Elongation
3 Middle Slave Yes Elongation
4 Last Slave No Length
This configuration assumes that the Auto-Elongation feature is enabled for the
Parallel Data Output. This feature automatically switches the Length/Elongation
port to output Elongation Ratio/Differential Speed when available. The last gauge
in the system (#4 in this example) outputs its measured length, which is the final
product length.
SYNC PORTSYNC PORTSYNC PORTSYNC PORT
Velocity
IN OUT IN OUT IN OUT IN OUT
Sync Signal
Velocity
Sync Signal
Velocity
Sync Signal
Velocity
Master Middle Slave Middle Slave Last Slave
Me
asu
rem
en
ts
Sync S
igna
l
S
ync S
ignal
S
ync S
ignal
S
ync S
ignal
Me
asu
rem
en
ts
Me
asu
rem
en
ts
Me
asu
rem
en
ts
1 2 3 4
Elongation Measurement System
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 26 of 84 Revision E (Dec 2013)
Synchronization
The High Speed Pulse Output can be used to generate the Synchronization
signal needed to synchronize all gauges in the system. This is accomplished by
configuring the High Speed Pulse output in LaserTrak Software to output the
Synchronization signal. In this configuration the gauge will output the
Synchronization pulse in place of Phase B of the High Speed Pulse output. The
Synchronization signal will automatically be routed to the gauge connected to the
I/O module and it will also be routed to the Synchronization Out connector that
goes to the first slave in the system. Each Slave in the system will replicate the
Synchronization signal, sending the Synchronization signal to its gauge and
outputting it on its Synchronization out connector. All Slaves can be Daisy
chained in this fashion. To enable Synchronization in the LaserSpeed gauges, all
the High Speed Pulse Outputs should be configured to output the synchronization
signal. This can be done using LaserTrak, or by setting the $H configuration
setting to 9. While only the Master gauge truly needs to output this signal,
configuring all the gauges and I/O Modules the same way will allow the gauges
and/or I/O Modules to be interchangeable with spares or moved around the
system without having to reconfigure any gauge settings.
The I/O Module does not require configuration to enable
Synchronization/Elongation Measurement. This functionality is automatically
enabled when the I/O Module detects that a Synchronization cable has been
attached.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Installation
Part No. 93342 / Drawing No. 0921-01516 Page 27 of 84 Revision E (Dec 2013)
Elongation/Differential Speed Calculation
Slave I/O Modules automatically transmit their gauge’s measured velocity out of
the SYNC port to the I/O Module connected to the SYNC IN connector. The
connected I/O Module receives this velocity and calculates elongation using the
following formula:
( )
where:
V1 is the velocity of the slave gauge
V0 is the velocity of the master gauge (connected to the I/O Module that
is calculating elongation.
The figure above shows a typical elongation measurement system. The I/O
Modules are numbered 1-4, with #1 as the Master and #4 as the Last Slave. I/O
Modules 1-3 calculate elongation by:
( )
( )
( )
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 28 of 84 Revision E (Dec 2013)
Setup
The Setup Port can be used to set up the I/O Module and/or to set up the
LaserSpeed Gauge. Commands sent to the gauge are described in the
LaserSpeed Gauge Instruction Handbook. The I/O Module commands are
preceded by a ‘~’ character. A command preceded by a “.” instead of a “~” will
return the values comma delimited without the identifiers. The sequence is the
same as the ~ command.
Note: The voltage output for MaxVel is 2.048 volts, and the output voltage for
the MinVel is 0.0 volts. First enter the velocity for an output of 0.0 volts (MinVel),
and then enter the velocity for an output of 2.048 volts (MaxVel).
Data Format
The table below illustrates the value represented by each output bit. The value is
dependent upon the units of measure chosen in the processor configuration.
Units Length/Bit Velocity/Bit
Units Length Resolution Velocity Resolution
Feet/Min 0.001 ft/bit 0.001 ft/min/bit
Inches/Min 0.001 inches/bit 0.001 inches/min/bit
Meters/Sec 0.001 meters/bit 0.00001 m (10 m/sec/bit)
Meters/Min 0.001 meters/bit 0.001 m (1 mm/sec/bit)
The largest length that can be measured is 999,999.999 (meters, mm, feet,
yards, or inches). To output the decimal number as an integer, it is multiplied by
1000 to yield 999999999. To convert it back to a decimal number divide by 1000.
In hexadecimal notation, this number is 3B9AC9FF, which takes 30 bits to
represent. If the measured length exceeds this value, the output will remain
999999999. The maximum velocity, that can be measured, is 50,000.000
(meters/minute, mm/min, feet/minute or inches/second). To output the decimal
number as an integer, it is multiplied by 1000 to yield 50,000,000. To convert the
number back to decimal, divide by 1000. In hexadecimal notation this number is
2FAF080, which takes 26 bits to represent.
The resolution of the measurement increases to 5 places to the right of the
decimal point when the units of measurement are meters/second. In this case the
maximum velocity is 254.00000 meters/second. To output this decimal as an
integer, it is multiplied by 100,000 to yield 25,400,000 (18392C0 in hexadecimal).
This takes 25 bits to represent. To convert this number back to decimal, divide
by 100,000. Thus a length measurement requires 30 bits maximum for output
and a velocity measurement requires a maximum of 25 bits of value and 1 bit for
sign.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 29 of 84 Revision E (Dec 2013)
Pinout Values
The following tables illustrate the pin-out assignments of the length/elongation
and velocity output connectors. Refer to the following table for the pin numbering
information of the 37pin "D-sub" connector.
Length/Elongation Connector Pinout
Pin # Description Bit Value Pin # Description Bit Value
1 Data bit 1 20 20 Data bit 20 219
2 Data bit 2 21 21 Data bit 21 220
3 Data bit 3 22 22 Data bit 22 221
4 Data bit 4 23 23 Data bit 23 222
5 Data bit 5 24 24 Data bit 24 223
6 Data bit 6 25 25 Data bit 25 224
7 Data bit 7 26 26 Data bit 26 225
8 Data bit 8 27 27 Data bit 27 226
9 Data bit 9 28 28 Data bit 28 227
10 Data bit 10 29 29 Data bit 29 228
11 Data bit 11 210 30 Sign Bit
12 Data bit 12 211 31 Data Ready
13 Data bit 13 212 32 Data Ready False
14 Data bit 14 213 33 Data Request
15 Data bit 15 214 34 User Supply
16 Data bit 16 215 35 User Supply
17 Data bit 17 216 36 User Ground
18 Data bit 18 217 37 User Ground
19 Data bit 19 218
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 30 of 84 Revision E (Dec 2013)
Velocity Connector Pinout
Pin # Description Bit Value Pin # Description Bit Value
1 Data bit 1 20 20 Data bit 20 219
2 Data bit 2 21 21 Data bit 21 220
3 Data bit 3 22 22 Data bit 22 221
4 Data bit 4 23 23 Data bit 23 222
5 Data bit 5 24 24 Data bit 24 223
6 Data bit 6 25 25 Data bit 25 224
7 Data bit 7 26 26 Sign
8 Data bit 8 27 27 Quality LSB 20
9 Data bit 9 28 28 Quality LSB 21
10 Data bit 10 29 29 Quality MSB 22
11 Data bit 11 210 30 Quality MSB 23
12 Data bit 12 211 31 Data Ready
13 Data bit 13 212 32 Data Ready False
14 Data bit 14 213 33 Data Request
15 Data bit 15 214 34 User Supply
16 Data bit 16 215 35 User Supply
17 Data bit 17 216 36 User Ground
18 Data bit 18 217 37 User Ground
19 Data bit 19 218
Note: The Data Ready and Data Request are connected in parallel for both
Velocity and Length. Only one DataRead and DataRequest should be used.
Velocity and Length are updated simultaneously.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 31 of 84 Revision E (Dec 2013)
Serial Communications
The Setup port can be used to configure the I/O module and the LaserSpeed
gauge. Commands intended for the I/O module are preceded by a “~” and
commands intended for the LaserSpeed gauge are not preceded by the “~”.
When communicating to the LaserSpeed gauge via the Setup Port, the
commands are intercepted by the I/O module’s processor. The I/O module’s
processor checks for a “~” to determine if the command is intended for the I/O
module or the LaserSpeed gauge. If the command is preceded with a “~” the I/O
module will process the command. If the command is not preceded by a “~” the
command will be resent to the LaserSpeed gauge via a RS-422 Serial connection
between the I/O Module’s processor and the LaserSpeed gauge.
It is important to note that there are two communication links in the chain. The
first link is a RS-232 serial connection between the PLC or PC control computer
and the I/O module. The second link is a RS-422 serial connection between the
I/O Module and the LaserSpeed gauge. Each link has its own Baud Rate and
Framing Parameters. Both the RS-232 connection between the PLC or PC
control computer and the RS-422 connection between the I/O module and the
LaserSpeed gauge’s parameters have to be set correctly before the system will
function properly.
The most common mistake made is to set the RS-232 communication
parameters between the PLC or PC and the I/O module and not set the RS-422
communication parameters between the I/O module and the LaserSpeed gauge.
Set the RS-232 Baud Rate, number of data bits, parity, and number of stop bits
the same in the PC/PLC and the I/O Module.
Set the RS-422 Baud Rate, number of data bits, parity, and number of stop bits
the same in the I/O Module and the LaserSpeed gauge.
Note: When sending commands to the LaserSpeed gauge, the status, velocity,
and length output data will be temporarily stop while the gauge is operating on
the command. Data will be interrupted on the Ethernet, Profibus, Parallel I/O,
and Serial connections. Data transmission will automatically resume once the
gauge has acted on the command.
RS-422 RS-232 PC/
PLC
I/O
Module
Laserspeed
Gauge
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 32 of 84 Revision E (Dec 2013)
Default Communication Settings
The default communication Baud Rate and framing for the RS232 Setup Port is
115200 Baud Rate, 7 data bits, 2 stop bits, No Parity. Set the PC or PLC to this
Baud Rate and framing to begin communicating with the I/O module. Once you
have established communication with the I/O module you may change the Baud
Rate and framing to any Baud Rate and framing supported by the ~J command.
See section I/O Module Configuration Commands for details.
If you have trouble establishing communication with the I/O module at the default
setting, the Baud Rate and framing settings may have been changed. To
establish communications, Set the PC/PLC Baud Rate and framing to 115200, 8
data bits, 1 stop bit, No Parity and power the I/O module off, wait 60 seconds,
then power back on. On power up, the I/O module will output the following
message at 115200 Baud Rate, 8 data bits, 1 stop bit, No Parity:
Waiting 2sec to start 'A' to abort
Configured IP = 192.168.10.249
Configured Mask = 255.255.255.0
MAC Address= 00:03:f4:06:09:17
I/O Module Software P/N 93064 Rev E, Fri Nov 15 15:07:17
2013
Waiting 20 seconds for Gauge to power up
Waiting 1 sec.
Type 'R' to set Setup port to 115200 8-N-1.
Continue at current baud.
I/O Module ready.
The I/O module will remain at 115200 Baud Rate, 8 data bits, 1 stop bit, no parity
if you send an R<CR> in the first 15 seconds after power up, If you do not send a
‘R’<CR> within 15 seconds after power up, the I/O module will switch the Baud
Rate and framing to what is was last time it was configured.
Once communication has been established between the PC/PLC and the I/O, all
the configuration parameters can be extracted from the I/O using the ~H
command. See section I/O Module Configuration Commands. Any or all
configuration parameters may be changed to suit the application requirements.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 33 of 84 Revision E (Dec 2013)
Setting Validation
Introduced in revision E software, all input settings are validated by the I/O
Module. If a setting value does not meet the validation criteria defined by the I/O
Module, the I/O Module will respond with a validation error and the entire
command will be ignored.
~B
Gauge_Serial
BaudRate 115200
StopBits 2
DataBits 7
Parity NONE
SyncMode 0
ElongAvg 10
~B99999,2,7,NONE,0,10
BaudRate: validation error
Also introduced in Revision E software, the I/O Module now supports the
backspace key on the IO Setup port. The user can now use the backspace key
to correct typing mistakes when entering I/O Module setups using HyperTerminal
or similar terminal program.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 34 of 84 Revision E (Dec 2013)
I/O Module Configuration Commands
Command
Group
Description
~A Analog Output Configuration
~B I/O Module ↔ Gauge RS-422 Communication Settings
~D Test Mode
~F Ethernet Configuration Settings
~H Dump All Parameter Settings
~I Parallel Port Configuration Settings
~J I/O Module Setup Port ↔ Computer RS-232
Communication Settings
~O Profibus/Ethernet Byte Order (Endianness)
~T Gauge Type
~Y Master/Slave Connection Status
~Z I/O Module Software Revision
~A:MaxVel Analog Output Maximum Velocity
~A:MaxVel<CR> Read Setting
Response Format:
Analog MaxVel <N><CR>
~A:MaxVel=<N><CR> Set Value
Factory Default: 200000 Minimum: -999999999 Maximum: 999999999
Where <N> is the velocity at which the Velocity Analog Output reaches its
maximum value of 2.048V. This value is normally positive, but can also be
negative. This value is scaled by 1000.
Example: Assuming Measurement Units are m/min, sending the command
~A:MaxVel=300000<CR> sets the full scale analog output of 2.048 volts to 300
m/min. When the measured velocity is > 300 m/min, the analog output will be
limited to the maximum output voltage of 2.048V.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 35 of 84 Revision E (Dec 2013)
~A:MinVel Analog Output Minimum Velocity
~A:MinVel<CR> Read Setting
Response Format:
Analog MinVel <N><CR>
~A:MinVel=<N><CR> Set Value
Factory Default: 0 Minimum: -999999999 Maximum: 999999999
Where <N> is the velocity at which the Velocity Analog Output reaches its
minimum value of 0V. This value can be a positive or negative value, or can be
zero. This value is scaled by 1000.
Example: Assuming Measurement Units are m/min, sending the command
~A:MinVel=100000<CR> sets the minimum scale analog output of 0.0 Volts to
100 m/min. When the measured velocity is < 100 m/min, the analog output will
be limited to the minimum output voltage of 0V.
~A:MaxElg Analog Output Maximum Elongation
~A:MaxElg<CR> Read Setting
Response Format:
Analog MaxElg <N><CR>
~A:MaxElg=<N><CR> Set Value
Factory Default: 10000 Minimum: -999999999 Maximum: 999999999
Where <N> is the elongation ratio at which the Elongation Analog Output reaches
its maximum value of 2.048V. This value can be a positive or negative value, or
can be zero. This value is a percentage value that is scaled by 100.
Example: Sending the command ~A:MaxElg=500<CR> will set the elongation
full scale analog output to 2.048V for an elongation ratio of 5%. When the
elongation measurement is > 5%, the analog output will be limited to the
maximum output voltage of 2.048V.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 36 of 84 Revision E (Dec 2013)
~A:MinElg Analog Output Minimum Elongation
~A:MinElg<CR> Read Setting
Response Format:
Analog MinElg <N><CR>
~A:MinElg=<N><CR> Set Value
Factory Default: 0 Minimum: -999999999 Maximum: 999999999
Where <N> is the elongation ratio at which the Velocity Analog Output reaches its
minimum value of 0V. This value can be a positive or negative value, or can be
zero.
Example: Sending the command ~A:MinElg=0<CR> will set the minimum
elongation ratio analog output to 0.0V when the elongation ratio is 0%. When the
elongation ratio is < 0%, the analog output will be limited to the minimum output
voltage of 0V.
~A / .A Analog Output Configuration
~A<CR> Read All Settings (with labels)
Example Response Format:
Analog
MaxVel 400000
MinVel 300000
MaxElg 1000
MinElg -500
Write Settings
~A<MaxVel>,<MinVel>,<MaxElg>,<MinElg><CR>
.A<CR> Read All Settings (without labels)
Example Response Format:
400000,300000,1000,-500<CR>
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 37 of 84 Revision E (Dec 2013)
Example: Write All Analog Settings
~A300000,100000,500,0
Sets the following:
Max velocity = 300
Min Velocity = 100
Max elongation ratio = 5%
Min elongation ratio = 0%
To calculate the velocity from the analog voltage, use the following formula.
Velocity:
( )
To calculate the elongation ratio from the analog voltage, use the following
formula.
~B / .B IO Module Gauge RS-422 Communication Settings
~B<CR> Read Settings
Response Format:
Gauge_Serial
BaudRate <B>
StopBits <S>
DataBits <D>
Parity <P>
SyncMode <M>
ElongAvg <E>
Elongation:
( )
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 38 of 84 Revision E (Dec 2013)
Set Value
~B<B>,<S>,<D>,<P>,<M>,<E><CR>
.B<CR> Read Settings (without labels)
Example Response Format:
230400,1,8,NONE,0,10<CR>
Where <B>, <S>, <D>, <P>, <M> and <E> are as follows:
Parameter Description Valid Values
<B> Baud Rate 230400, 115200, 57600,
38400, 19200, 4800
<S> Stop Bits 1, 2
<D> Data Bits 7, 8
<P> Parity Should always be set to
NONE
<M> Sync Mode 0 or 1
<E> Elongation Averaging Number of elongation
readings to average
from 1 to 1000
Default 10
This command configures the baud rate and framing for the RS-422
communication link between the I/O Module and the LaserSpeed gauge. These
settings must be set to match the gauge’s communication settings for
communication between the two devices to function. The valid baud rates are
listed in the table above.
Recommended settings:
Setting Value
Baud Rate 230400
Stop Bits 1
Data Bits 8
Parity None
SyncMode 0
ElongAvg 10
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 39 of 84 Revision E (Dec 2013)
The recommended settings will enable binary communication mode between the
gauge and the I/O module and allow for the fastest possible data throughput. If
you are using a different baud rate/framing configuration, you can change the
LaserSpeed gauge’s baud rate/framing to the recommended settings by sending
the command @11<CR> to the gauge. To set the I/O module to the same baud
rate/framing, sending the following command to the I/O Module:
~B230400,1,8,None<CR>.
Note: When synchronizing multiple gauges, the SyncMode setting should be set
to 1, and all gauges’ $H settings set to 9. This will allow the I/O Module to rely on
the gauge’s synchronization output timing for increased performance. This is
required when operating synchronized gauges with fast update rates.
Note: The gauge’s RS422 baud rate should be changed before changing this
setting (using the @ command), as changing the I/O Module’s baud rate will make
the I/O Module unable to communicate with the gauge if the two devices’ baud
rates no longer match.
Note: Communication between the I/O Module and the gauge can be check by
viewing the lights on the I/O Module’s front panel. If the lights are functioning
properly the gauge and the I/O module are communicating properly.
Note: The order for the baud rate/framing for the I/O module is:
Baud Rate, Stop Bits, Data Bits, Parity, not
Baud Rate, Data Bits, Stop Bits, Parity.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 40 of 84 Revision E (Dec 2013)
The following table lists the various RS-422 communication settings supported by
LaserSpeed gauges, and the command that should be used to set the I/O Module
and gauge to use these settings.
Baud Rate Framing1
Gauge
Command I/O Module Command
230400 8n1 @11<CR> ~B230400,1,8,None<CR>
7n2 @1<CR> ~B230400,2,7,None<CR>
115200 8n1 @12<CR> ~B115200,1,8,None<CR>
7n2 @2<CR> ~B115200,2,7,None<CR>
57600 8n1 @13<CR> ~B57600,1,8,None<CR>
7n2 @3<CR> ~B57600,2,7,None<CR>
38400 8n1 @14<CR> ~B38400,1,8,None<CR>
7n2 @4<CR> ~B38400,2,7,None<CR>
19200 8n1 @15<CR> ~B19200,1,8,None<CR>
7n2 @5<CR> ~B19200,2,7,None<CR>
9600 8n1 @16<CR> ~B9600,1,8,None<CR>
7n2 @6<CR> ~B9600,2,7,None<CR>
4800 8n1 @17<CR> ~B4800,1,8,None<CR>
7n2 @7<CR> ~B4800,2,7,None<CR>
1 In this table, 7n2 denotes “7 data bits, 2 stop bits, no parity”, and 8n1 denotes “8 data bits, 1 stop bit,
no parity”
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 41 of 84 Revision E (Dec 2013)
~D Test Mode
~D<CR> Read Settings
Response Format:
Test
TestMode <A>
TestNumber <B>
Testonoff <C>
~D<A><CR> Set Value
Factory Default: 0 Minimum: 0 Maximum: 2
Where <A> is the current test mode, and <B> and <C> are not used (should be
set to 0). <A> should be set to 0 for normal operation.
Mode <A> Description
0 Normal Operation
1 Cycle Front Panel Lights
2 Simulate Normal Operation
~F:IP Ethernet IP Address
~F:IP<CR> Read Setting
Response Format:
ABEtherNet IP <IP><CR>
~F:IP=<IP><CR> Set Value
Factory Default: 192.168.1.111
Where <IP> is the IP address that the I/O Module will use for Ethernet
Communication.
This setting is only used when the I/O Module is equipped with an Ethernet
fieldbus card.
Example: To set the IP address to 192.10.1.100, send the command:
~F:IP=192.168.1.100<CR>
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 42 of 84 Revision E (Dec 2013)
~F:Netmask Ethernet Netmask
~F:Netmask<CR> Read Setting
Response Format:
ABEtherNet Netmask <IP><CR>
~F:Netmask=<IP><CR> Set Value
Factory Default: 255.255.255.0
Where <IP> is the Ethernet NetMask. Contact your network administrator for the
correct value for this setting.
This setting is only used when the I/O Module is equipped with an Ethernet
fieldbus card.
Example: To set the NetMask to 255.255.255.0, send the command:
~F:Netmask=255.255.255.0<CR>
~F:Gateway Ethernet Gateway Address
~F:Gateway<CR> Read Setting
Response Format:
ABEtherNet Gateway <IP><CR>
~F:Gateway=<IP><CR> Set Value
Factory Default: 0.0.0.0
Where <IP> is the address of the Gateway Server. Contact your network
administrator for the correct value for this setting.
This setting is only used when the I/O Module is equipped with an Ethernet
fieldbus card.
Example: To set the Gateway Address to 192.168.10.2, send the command:
~F:Gateway=192.168.10.2<CR>
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 43 of 84 Revision E (Dec 2013)
~F:UdpPort Ethernet UDP Port
~F:UdpPort<CR> Read Setting
Response Format:
ABEtherNet UdpPort <N><CR>
~F:UdpPort=<N><CR> Set Value
Factory Default: 4750 Minimum: 0 Maximum: 65535
Where <N> is the port on the host to which UDP messages will be sent. The
UDP message receiver should listen on this port for UDP messages.
This setting is only used when the I/O Module is equipped with an Ethernet
fieldbus card.
Example: To set the UDP Port 4750, send the command:
~F:UdpPort=4750<CR>
~F:TcpPort Ethernet TCP Port
~F:TcpPort<N> Read Setting
Response Format:
ABEtherNet TcpPort <N><CR>
~F:TcpPort=<N><CR> Set Value
Factory Default: 4751 Minimum: 0 Maximum: 65535
Where <N> is the local port for TCP configuration messages. The host computer
should open a TCP connection to this port in order to send configuration
messages.
This setting is only used when the I/O Module is equipped with an Ethernet
fieldbus card.
Example: To set the TCP Port 4751, send the command:
~F:TcpPort=4751<CR>
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 44 of 84 Revision E (Dec 2013)
~F:UdpIP Ethernet UDP Destination Address
~F:UdpIP<CR> Read Setting
Response Format:
ABEtherNet UdpIP <IP><CR>
~F:UdpIP=<IP><CR> Set Value
Factory Default: 192.168.1.100
Where <IP> is the remote IP address to which UDP data messages will be sent.
This setting is only used when the I/O Module is equipped with an Ethernet
fieldbus card.
Example: To set the UDP Destionation Address to 192.168.10.111, send the
command:
~F:UdpIP=192.168.1.111<CR>
~F: .F Ethernet Configuration Settings
~F<CR> Read All Settings (with labels)
Example Response Format:
ABEtherNet
IP 192.168.1.111
Netmask 255.255.255.0
Gateway 0.0.0.0
UdpPort 4750
TcpPort 4751
UdpIP 192.168.1.100
Set All Values
~F<IP>,<NM>,<GW>,<UP>,<TP>,<UI><CR>
.F<CR> Read All Settings (without labels)
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 45 of 84 Revision E (Dec 2013)
Example Response Format:
192.168.1.111,255.255.255.0,0.0.0.0,4750,4751,192.168.1.100
Where <IP>, <NM>, <GW>, <UP>, <TP>, and <UI> are as follows:
Parameter Description
<IP> Ethernet IP Address
<NM> Ethernet Netmask
<GW> Ethernet Gateway Address
<UP> Ethernet UDP Port
<TP> Ethernet TCP Port
<UI> Ethernet UDP Destination Address
This setting is only used when the I/O Module is equipped with an Ethernet
fieldbus card.
Example: To set the UDP Destination Address to 192.168.10.111, send the
command:
~F:UdpIP=192.168.1.111<CR>
~I:ReadyFlag Parallel Port Data Ready Output Polarity
~I:ReadyFlag<CR> Read Setting
Response Format:
ParallelPort ReadyFlag <N><CR>
~I:ReadyFlag=<N><CR> Set Value
Factory Default: 1 Minimum: 0 Maximum: 1
Where <N> indicates the polarity of the Data Ready output signal. This output
indicates when new data is available on the parallel output port.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 46 of 84 Revision E (Dec 2013)
Value Polarity New Data Available On:
0 Active Low Falling Edge (High→Low Transition)
1 Active High Rising Edge (Low→High Transition)
Example: To set the Data Ready Output Polarity to Active High, send the
command ~I:ReadyFlag=1<CR>. To set the Data Ready Output Polarity to
Active Low, send the command ~I:ReadyFlag=0<CR>.
~I:StrobeFlag Parallel Port Data Request Input Polarity
~I:StrobeFlag<CR> Read Setting
Response Format:
ParallelPort StrobeFlag <N><CR>
~I:StrobeFlag=<N><CR> Set Value
Factory Default: 1 Minimum: 0 Maximum: 1
Where <N> indicates the polarity of the Data Request input signal.. When the I/O
Module’s parallel port is in Data Request Mode, this output controls when the
parallel port updates with new data.
Value Polarity Parallel Port Updated On:
0 Active Low Falling Edge (High→Low Transition)
1 Active High Rising Edge (Low→High Transition)
This setting is only used when the I/O Module is configured for Data Request
Mode. The I/O Module can be placed in this mode using the ~I:AckMode
command.
Example: To set the Data Request Input Polarity to Active High, send the
command ~I:StrobeFlag=1<CR>. To set the Data Request Input Polarity to
Active Low, send the command ~I:StrobeFlag=0<CR>.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 47 of 84 Revision E (Dec 2013)
~I:DataFlag Parallel Port Data Output Polarity
~I:DataFlag<CR> Read Setting
Response Format:
ParallelPort DataFlag <N><CR>
~I:DataFlag=<N><CR> Set Value
Factory Default: 1 Minimum: 0 Maximum: 1
Where <N> indicates the polarity of the output Data. Data true high or Data true
low
Value Logic ‘0’ Logic ‘1’
0 High Voltage Low Voltage
1 Low Voltage High Voltage
When operating the parallel output as an open collector output bus:
Value Logic ‘0’ Logic ‘1’
0 Open 0V
1 0V Open
Example: To set the Data Output Polarity to Active High, send the command
~I:DataFlag=1<CR>. To set the Data Output Polarity to Active Low, send
the command ~I:DataFlag=0<CR>.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 48 of 84 Revision E (Dec 2013)
~I:AckMode Parallel Port Update Mode
~I:AckMode<CR> Read Setting
Response Format:
ParallelPort AckMode <N><CR>
~I:AckMode=<N><CR> Set Value
Factory Default: 0 Minimum: 0 Maximum: 1
Where <N> indicates the Parallel Port Update Mode.
Value Update Mode
0 Data Ready Mode
1 Data Request Mode
When in Data Ready Mode, the I/O Module automatically updates the parallel
port when new data is received from the gauge. The update rate is determined
by the gauge’s update rate. When in Data Request Mode, the I/O Module
updates the parallel port when the Data Request Input is asserted. In this mode,
the update is rate is determined by the device controlling the Data Request
signal.
Example: To set the Parallel Port Update Mode to Data Ready Mode, send the
command ~I:AckMode=0<CR>. To set mode to Data Request Mode, send the
command ~I:AckMode=0<CR>.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 49 of 84 Revision E (Dec 2013)
~I:ReadyLn Parallel Port Data Ready Pulse Length
~I:ReadyLn<CR> Read Setting
Response Format:
ParallelPort ReadyLn <N><CR>
~I:ReadyLn=<N><CR> Set Value
Factory Default: 8 Minimum: 1 Maximum: 255
Where <N> indicates the length of the Data Ready Output Pulse. This is an
integer value from 1 to 255. This allows a pulse length from 500µs to
approximately 125ms in 500µs increments. The value for this setting can be
calculated with the following formula:
Example: To set the Data Ready strobe width to 10ms:
To configure the value, send the command ~I:ReadyLn=20<CR>
~I:Elongation Parallel Port Elongation Mode
~I:Elongation<CR> Read Setting
Response Format:
ParallelPort Elongation <N><CR>
~I:Elongation=<N><CR> Set Value
Factory Default: 1 Minimum: 0 Maximum: 1
Where <N> indicates the on/off status of Auto-Elongation Mode.
Value Auto-Elongation Mode
0 Disabled
1 Enabled
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 50 of 84 Revision E (Dec 2013)
When Auto-Elongation Mode is enabled, and the I/O Module is measuring
elongation, the Length parallel output is replaced with Elongation. Since the last
slave in a chain of I/O Modules does not measure elongation, it always outputs
length. See the Elongation/Synchronization section for more information. When
the Auto-Elongation Mode is disabled, the Length/Elongation port will always
output length.
Example: To enable Auto-Elongation Mode, send the command
~I:Elongation=1<CR>. To disable Auto-Elongation Mode, send the command
~I:Elongation=0<CR>.
~I:ElongRes Parallel Port Elongation Resolution
~I:ElongRes<CR> Read Setting
Response Format:
ParallelPort ElongRes <N><CR>
~I:ElongRes=<N><CR> Set Value
Factory Default: 1 Minimum: 0.001 Maximum: 1
Where <N> indicates the Elongation resolution multiplier.
Value Elongation Multiplier
1 Elongation x 1
0.1 Elongation x 0.1
0.01 Elongation x 0.01
0.001 Elongation x 0.001
This command allows to user to reduce the output resolution of the elongation
measurement by scaling the measurement result.
Example: To reduce the elongation resolution by a factor of 10x
~I:ElongRes=0.1<CR>.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 51 of 84 Revision E (Dec 2013)
~I:LenRes Parallel Port Length Resolution
~I:LenRes<CR> Read Setting
Response Format:
ParallelPort ElongRes <N><CR>
~I:LenRes=<N><CR> Set Value
Factory Default: 1 Minimum: 0.001 Maximum: 1
Where <N> indicates the Length resolution multiplier.
Value Length Multiplier
1 Length x 1
0.1 Length x 0.1
0.01 Length x 0.01
0.001 Length x 0.001
This command allows to user to reduce the output resolution of the length
measurement by scaling the measurement result.
Example: To reduce the length resolution by a factor of 10x
~I:LenRes=0.1<CR>.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 52 of 84 Revision E (Dec 2013)
~I:VelRes Parallel Port Velocity Resolution
~I:VelRes<CR> Read Setting
Response Format:
ParallelPort VelRes <N><CR>
~I:VelRes=<N><CR> Set Value
Factory Default: 1 Minimum: 0.001 Maximum: 1
Where <N> indicates the Velocity resolution multiplier.
Value Velocity Multiplier
1 Velocity x 1
0.1 Velocity x 0.1
0.01 Velocity x 0.01
0.001 Velocity x 0.001
This command allows to user to reduce the output resolution of the velocity
measurement by scaling the measurement result.
Example: To reduce the velocity resolution by a factor of 10x
~I:VelRes=0.1<CR>.
~I:DisplayType Parallel Port Display Type
~I: DisplayType<CR> Read Setting
Response Format:
ParallelPort DisplayType <N><CR>
~I:DisplayType =<N><CR> Set Value
Factory Default: 0 Minimum: 0 Maximum: 1
Where <N> indicates the display output type.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 53 of 84 Revision E (Dec 2013)
Value Type
0 AM7704 Displays:
Velocity, Length, Quality Factor, Status
1 AM8096 Displays:
Length, Elongation %, Velocity, Quality Factor,
Status
This setting must match the display type (defined by AM####) used with the
system.
~I / .I Parallel Port Configuration Settings
~I<CR> Read All Settings (with labels)
Example Response Format:
ParallelPort
ReadyFlag 1
StrobeFlag 1
DataFlag 1
AckMode 0
ReadyLn 1
Elongation 1
ElongRes 1
LenRes 1
VelRes 1
DisplayType 0
Set All Values
~I<R>,<S>,<D>,<A>,<L>,<E>,<ER>,<LR>,<VR>,<DT><CR>
.I<CR> Read All Settings (without labels)
Example Response Format:
1,1,1,0,1,1,1,1,1,0<CR>
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 54 of 84 Revision E (Dec 2013)
Where <R>, <S>, <D>, <A>, <L>, <E>, <ER>, <LR>, <VR>, and <DT> are as
follows:
Value Description Values
<R> Parallel Port Data Ready
Output Polarity
0 – Active Low
1 – Active High (default)
<S> Parallel Port Data Request
Input Polarity
0 – Active Low
1 – Active High (default)
<D> Parallel Port Data Output
Polarity
0 – Active Low
1 – Active High (default)
<A> Parallel Port Update Mode 0 – Data Ready Mode (default)
1 – Data Request Mode
<L> Parallel Port Data Ready
Strobe Length
0-255
<E> Parallel Port Elongation
Mode
0 – Disabled
1 – Enabled (default)
<ER> Elongation Resolution
Multiplier values:
1 = Elongation x 1 (default),
0.1 = Elongation x 0.1
0.01 = Elongation x 0.01
0.001 = Elongation x 0.001
<LR> Length Resolution
Multiplier values:
1 = Length x 1 (default),
0.1 = Length x 0.1
0.01 = Length x 0.01
0.001 = Length x 0.001
<VR> Velocity Resolution
Multiplier values:
1 = Velocity x 1 (default),
0.1 = Velocity x 0.1
0.01 = Velocity x 0.01
0.001 = Velocity x 0.001
<DT> Display Type 0 = AM7704
1 = AM8096
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 55 of 84 Revision E (Dec 2013)
~J / .J IO Module Setup Port Computer RS232 Communication Settings
~J<CR> Read Settings
Example Response Format:
IO_Serial
BaudRate 115200
StopBits 1
DataBits 8
Parity None
Set Value
~J<B>,<S>,<D>,<P><CR>
.J<CR> Read Settings (without labels)
Example Response Format:
115200,1,8,None<CR>
Where <B>, <S>, <D>, and <P> are as follows:
Parameter Description Valid Values
<B> Baud Rate 230400, 115200, 57600, 38400, 19200, 4800
<S> Stop Bits 1, 2
<D> Data Bits 7, 8
<P> Parity
Odd – Odd Parity
Even – Even Parity
None – No Parity
This command configures the baud rate and framing for the RS-232
communication link between the I/O Module’s setup port and a computer or PLC.
These settings must be set to match the computer/PLC’s serial communication
settings. The valid baud rates are listed in the table above with the factory
default settings highlighted.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 56 of 84 Revision E (Dec 2013)
Note: The communication settings for the RS-422 communication link
between the I/O Module and the LaserSpeed gauge are independent from these
settings, and are configured with the ~B command.
Example: To configure the I/O Module’s setup port for 115.2kBaud, 2 stop bits, 7
data bits, and no parity, send the command ~J115200,2,7,None<CR>.
~O / .O Profibus/Ethernet Byte Order (Endianness)
~O<CR> Read Setting (with labels)
Example Response Format:
BigLittleEndian
Order 1
~O<N><CR> Set Value
Factory Default: 1 Minimum: 0 Maximum: 1
.O<CR> Read Setting (without labels)
This setting configures which byte is transmitted first over the Profibus and
Ethernet connections.
Value Endianness Description
0 Little Endian LSB transmitted first, MSB transmitted last
1 Big Endian MSB transmitted first, LSB transmitted last
See http://en.wikipedia.org/wiki/Endianness for more information about
Endianness.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 57 of 84 Revision E (Dec 2013)
~T Gauge Type
~T<CR> Read Value
Response Format:
GaugeType
Type ls9k
~T<X><CR> Set Value
Factory Default: ls9k
Where <X> is the type of gauge connected to the I/O Module. This setting should
be set to “ls9k”.
Example: To configure the I/O Module to communicate with LS8000/LS9000
gauges, send the command ~Tls9k<CR>.
~Y Master/Slave Connection Status
~Y<CR> Read Value
Response Format:
Master:<X1> Slave:<X2>
Where <M> indicates if a Master is connected, and <S> indicates if a Slave is
connected.
This command returns the connection state of the rear panel Sync In and Sync
Out connectors. The I/O Module detects whether or not a Master and/or Slave is
connected. This information is used to calculate Elongation, and to control the
function of the Length/Elongation parallel port if Auto-Elongation Mode
(~I:Elongation setting).
<X1> and <X2> are each either Connected or None.
<X1> <X2> I/O Module Behavior
None None Stand Alone
None Connected Master
Connected None End Slave
Connected Connected Middle Slave
See the Elongation/Synchronization section for details about Elongation.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 58 of 84 Revision E (Dec 2013)
~Z IO Module Software Revision
~Y<CR> Read Value
This command returns the software revision and build date of the software that
the I/O Module is running.
~H Dump All Parameter Settings
~H<CR> Read Value
This command returns all the Parameters settings of the I/O Module.
Example: The I/O Module will return a response similar to the following listing in
response to the ~H<CR> command:
~B Gauge_Serial
BaudRate 115200
StopBits 2
DataBits 7
Parity NONE
SyncMode 0
ElongAvg 10
Status: Port 2, BaudRate 115200, StopBits 2, DataBits 7,
Parity N
Normal Ascii Mode
~J IO_Serial
BaudRate 115200
StopBits 1
DataBits 8
Parity N
Status: Port 0, BaudRate 115200, StopBits 1, DataBits 8,
Parity N
~F ABEtherNet
IP 192.168.5.100
Netmask 255.255.255.0
Gateway 192.168.5.5
UdpPort 4751
TcpPort 4751
UdpIP 192.168.5.100
Status: IP 192.168.005.100, NetMask 255.255.255.000
Gateway 192.168.005.005, UDPIP 192.168.005.100
UDPport 4751, TCPPort 4751
~O BigLittleEndian
Order 0
Status: Anybus output is LittleEndian
~T GaugeType
Type ls9k
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 59 of 84 Revision E (Dec 2013)
Status: Gauge selected LS9000-3
~I ParallelPort
ReadyFlag 0
StrobeFlag 0
DataFlag 0
AckMode 0
ReadyLn 28
Elongation 0
ElongRes 1
LenRes 1
VelRes 1
DisplayType 0
Status: ReadyOut: INVERT, DataReqIn: INVERT, DataOut: INVERT,
AckMode: DATA RDY MODE, ReadyLength: 14.0ms,
Len/ElongOutput: LENGTH, ElongRes: 1.000
VelRes: 1.000, LenRes: 1.000
DisplayType: Len/Vel
~A Analog
MaxVel 2000000
MinVel 0
MaxElg 200
MinElg 0
Status: MaxVel 2000000, MinVel 0, MaxElg 200, MinElg 0
~D Test
TestMode 0
TestNumber 0
Testonoff 0
Status: TestMode 0, TestNumber 0 onoff 0
I/O Module Software P/N 93064 Rev E, Fri Nov 15 15:07:17 2013
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Setup
Part No. 93342 / Drawing No. 0921-01516 Page 60 of 84 Revision E (Dec 2013)
I/O Module-to-LaserSpeed Communication
If the LaserSpeed baud rate/framing is different from the I/O Modules baud
rate/framing, the communication link between them will not work. Check the
lights on the front panel of the I/O Module to see it they are functioning properly.
The I/O Module-to-Gauge communication link is not working when the front panel
lights are not functioning properly. If the I/O Module is not communicating with
the gauge, check the flashing COMM lamp on the gauge during power up to
determine the baud rate. See the gauge handbook to determine the baud rate
from the flashing COMM Light. Set the I/O Module to match the gauge’s baud
rate.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 61 of 84 Revision E (Dec 2013)
Operation
Understanding the Front Panel
Front Panel Item Description
Key Switch The key switch is used to turn the LaserSpeed
Gauge’s laser on and off. The switch is connected in
series with the laser power jumper on the rear panel
on the connector labeled STATUS. The Key Switch
must be on, and the Interlock must be active to turn
on the Laser.
Interlock Indicator This indicator is lit when power is supplied to the
laser, indicating that the interlock is on.
Quality Indicator This indicator shows the signal quality to the
LaserSpeed Gauge. Green indicates “Ok”, yellow in
the middle region indicates “good”, and red in the
lower region indicates a bad signal.
Valid Measurement Light When lit, indicates that good measurements are
being received from the LaserSpeed.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 62 of 84 Revision E (Dec 2013)
Material Present Light When lit, indicates that material is present in front of
the LaserSpeed. ONLY USED WITH
LS9000/LS8000-2 GAUGES.
Laser at Temperature Light When lit, indicates that laser is at operational
temperature.
Laser Power Light When lit, indicates that power is applied to the laser
diode.
Shutter Open Light When lit, indicates that the laser gauge’s shutter is
open.
Note that all indicators are blank when there is no communication from the
LaserSpeed gauge.
Profibus Operation
The Profibus module is automatically detected.
Status indications are described in the LaserSpeed I/O Module Operator Guide.
Profibus Command Structure
Values are updated every time the LS9000/LS8000 is updated.
The Status/Command, Velocity, Length, Quality Factor, and Status information is
updated at the User update
Use 93434 I/O Module hms1003.gds file for setting up the profibus. This is
supplied on a CD with the I/O Module.
Rate specified by the LS9000/LS8000.
Note: When sending configuration parameters to the LS9000/LS8000, the
status, velocity and length transmission from the gauge is temporarily halted
while the LS9000/LS8000 is updating its configuration parameters. This will
interrupt data being output via the Ethernet, Profibus, Serial and Parallel I/O
ports.
PUV – Status Command Word
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit2 Bit 1 Bit 0
0 0 0 0 0 0 Retrieves data
from
LaserSpeed
Send Data to
LaserSpeed
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 63 of 84 Revision E (Dec 2013)
To send configuration parameters to the LS9000/LS8000:
1) The Profibus Master sets all the configuration parameters in the DP
Slave
2) The Master sets Bit 0 of the Status & Command byte to a “1”. PUV = 1
3) The I/O Module sends all the configuration parameters to the
LaserSpeed gauge.
4) The I/O Module sets Masters PUV to 1.
5) Master detects PUV set to 1 and sets the I/O Module PUV to 0.
6) The PUV status Bit 1 is cleared in the PUV byte when the configuration
parameters have been updated in the gauge. Wait until Master PUV =
0.
The least significant 2 bits (LS-nibble) of the PUV Command Status Byte
determine the mode of operation of the I/O Module. The Fieldbus Master may
change any of the user bytes. A bit in the PUV signals when the data has
changed. A simple handshake scheme between the Fieldbus Master and the I/O
Module accomplish the configuration.
The Master writes appropriate data into the Output Data Block and then sets the
LS-nibble of its PUV Command Status to 0x01 (hexadecimal value) to begin the
initialization process. The I/O Module reads the PUV value every 100
milliseconds and begins a configuration sequence when the PUV = 0x01. The
I/O Module uses the data then writes 0x01 back to the Master’s PUV to signal the
transfer. The Master sets the PUV to 0x00. The configuration sequence ends with
the I/O Module setting its corresponding PUV Command Status byte to 0x00. The
Master reads this value as acknowledgment of the configuration. No other
configuration should ever be required until a setup change is desired.
To get existing setups:
1) The Master Sets 2nd
bit in the Status & Command to 1. PUV = 2
2) The I/O Module reads the PUV= 2, the I/O Module will get the
configuration parameters from the gauge and update the Master’s
Profibus memory.
3) The I/O Module sets Master PUV = 2
4) When the Master sees PUV=2, the Master can read the configuration
parameters.
5) Master sets PUV to 0.
When retrieving data from the LS9000/LS8000 gauge, data is first downloaded
from the gauge and then sent to the Profibus connection. This can take several
seconds.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 64 of 84 Revision E (Dec 2013)
To retrieve data, the least significant 2 bits (LS-nibble) of the PUV Command
Status Byte determine the mode of operation of the I/O Module. The data
corresponds to Output Data block. A simple handshake scheme between the
Fieldbus Master and the I/O Module accomplish configuration. The Master sets
the LS-nibble of its PUV Command Status to 0x02 (hexadecimal value) to begin
the initialization process. The I/O Module reads the PUV value at every 100
milliseconds and begins a configuration sequence when the PUV = 0x02. The
I/O Module gets the configuration parameters from the gauge and updates
Master’s Output Data block, then writes 0x02 back to the Master’s PUV to signal
start of transfer. The Master sets the PUV to 0x00. The configuration sequence
ends with the LaserSpeed setting its corresponding PUV byte to 0x00. The
Master then reads data.
PUV, Velocity, Length, Status, Quality Factor
These locations are updated on each user update period.
Status Bits
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit2 Bit 1 Bit 0
Toggle 0 0 Valid
measurement
Material
present
Shutter
Open
Laser
On
At
Temperature
Quality Factor Bits
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 – Bit 0
0 0 0 0 0- 15
Velocity Sign Bits
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 0 0 Sign
Sign 1 = minus, 0 = +.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 65 of 84 Revision E (Dec 2013)
Profibus Memory Structure
The I/O Module GSD File organizes the Profibus data into 6 blocks, as shown in
the table below. There are a total of 96 Profibus data bytes.
Block Type Organization Size Description
0 Input/Output bytes 1 byte PUV value
1 Input bytes 14 bytes Measurement Data
2 Input/Output words 16 words Configuration Settings
3 Input/Output words 12 words Configuration Settings
4 Input/Output byte 9 bytes Configuration Settings
5 Input/Output byte 16 bytes Gauge Version
Byte2
Block
Byte/Word Description Format
0 0.0 PUV Register 8-bit byte (See below for PUV Register Format)
1
2
3
4
1.0
1.1
1.2
1.3
Velocity 32-bit 2's complement signed integer representing
the current velocity x 1000.
5 (msb)
6
7
8 (lsb)
1.4
1.5
1.6
1.7
Length 32-bit 2's complement signed integer representing
the current length x 1000.
9 1.8 Quality Factor 8-bit unsigned integer. Value can be 0-15.
10 1.9 Status 8-bit bitfield - see below for format
11 (msb)
12
13
14 (lsb)
1.10
1.11
1.12
1.13
Elongation
32-bit 2's complement signed integer representing
the current Elongation x 100%
(a value of +1000 indicates an elongation of +10%
15 (msb)
16
17
18 (lsb)
2.0
2.1
Hold Velocity
32-bit unsigned integer
Hold Velocity if Above Setting
Serial Command: "B"
2 Table shows configuration for Big Endianness (~O=1)
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 66 of 84 Revision E (Dec 2013)
19 (msb)
20
21
22 (lsb)
2.2
2.3
Calibration Trim
32-bit unsigned integer
Calbiration Trim Factor Setting
Serial Command: "C"
23 (msb)
24
25
26 (lsb)
2.4
2.5
Analog Full Scale
32-bit unsigned integer
Analog Full Scale Setting
Serial Command: "D"
27 (msb)
28
29
30 (lsb)
2.6
2.7
Material Present
Dropout Time
32-bit unsigned integer
Material Present Dropout Time Setting
Serial Command: "F"
31 (msb)
32
33
34 (lsb)
2.8
2.9
Material Present
Validation Time
32-bit unsigned integer
Material Present Validation Time Setting
Serial Command: "G"
35 (msb)
36
37
38 (lsb)
2.10
2.11
Hour Meter
32-bit unsigned integer (Read Only)
Hour Meter - Indicates Hours of Operation
Serial Command: "H"
39 (msb)
40
41
42 (lsb)
2.12
2.13
High Speed Pulse
Resolution
32-bit unsigned integer
Pulses/Unit Length for High Speed Pulses
Serial Command: "L"
43 (msb)
44
45
46 (lsb)
2.14
2.15
Analog Zero Scale
32-bit unsigned integer
Analog Output Zero Scale (LS8000 Only)
Serial Command: "N"
47 (msb)
48
49
50 (lsb)
3.0
3.1
Low Speed Pulse
Resolution
32-bit unsigned integer
Pulses/Unit Length for Low Speed Pulses
Serial Command: "P"
51 (msb)
52
53
54 (lsb)
3.2
3.3
Calibration Number
32-bit unsigned integer (Read Only)
Calibration Number - Set at Factory
Serial Command: "TC"
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 67 of 84 Revision E (Dec 2013)
55 (msb)
56
57
58 (lsb)
3.4
3.5
Walking Threshold
32-bit unsigned integer
Walking Threshold Setting
Serial Command: "W"
59 (msb)
60
61
62 (lsb)
3.6
3.7
Minimum Final
Length
32-bit unsigned integer
Minimum Final Length Setting
Serial Command: "X"
63 (msb)
64
65
66 (lsb)
3.8
3.9
Gauge Temperature
32-bit unsigned integer
Current Gauge Temperature
Serial Command: "I"
67 (msb)
68
69
70 (lsb)
3.10
3.11
Material Present
Threshold
32-bit unsigned integer
Material Present Threshold Setting
Serial Command: "M"
71 4.0 Reserved 8-bit byte - Don't use (set to 0)
72 4.1 Baud Rate
8-bit byte
Baud Rate Setting
Serial Command: "J"
73 4.2 Filter Lockouts
8-bit byte
Filter Enable Settings (leave set to 31)
Serial Command: "E"
74 4.3 Averaging Time
8-bit byte
Averaging Time (aka DIP Average)
Serial Command: "K"
75 4.4 Measurement Units
8-bit byte
Measurement Units
Serial Command: "U"
76 4.5 Reset Length
8-bit byte (Write Only)
Length Reset - set to 1 to reset the length
Serial Command: "R"
77 4.6 Material Present
Mode
8-bit byte
Material Present Input Mode Setting
Serial Command: "S"
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 68 of 84 Revision E (Dec 2013)
78 4.7 Reserved 8-bit byte - Don't use (set to 0)
79 4.8 User Update Rate
8-bit byte
User Update Rate Setting
Serial Command: "O"
80 (start)
↓
95 (end)
5.0 (start)
↓
5.15 (end)
Gauge Version
String (8 bit, NULL terminated char array)
Gauge Firmware String (similar to "LS9KVC"
Serial Command: "Z"
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 69 of 84 Revision E (Dec 2013)
PUV Register Format
MSB LSB
bit 7:2 1 0
Input (Write to I/O Module) - READ_SETUP WRITE_SETUP
Output (Read from I/O Module) Reserved (0) READ_STATUS WRITE_STATUS
READ_SETUP The Profibus Master sets this bit to a 1 to instruct the I/O
Module to read the current configuration settings from the
attached LaserSpeed gauge.
WRITE_SETUP The Profibus Master sets this bit to 1 to instruct the I/O
Module to transmit the configuration settings transmitted in
the Profibus Data Exchange message to the attached
LaserSpeed gauge.
READ_STATUS The I/O Module sets this bit in its output Profibus message
in response to the Profibus master setting the
READ_SETUP bit. When this bit is set to 1, the I/O Module
has completed reading the configuration settings from the
LaserSpeed gauge, and has copied them into the Data
Exchange message. When this bit is 1, the settings in the
Data Exchange message contain valid data.
WRITE_STATUS The I/O Module sets this bit to 1 in its output Profibus
message to acknowledge that is has received the
WRITE_SETUP command. The I/O module clears this bit to
0 after the configuration settings have been transmitted to
the LaserSpeed gauge and verified.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 70 of 84 Revision E (Dec 2013)
Read Setup Cycle
READ_SETUP – PUV Bit 1
(Sent from Master)
READ_STATUS – PUV Bit 1
(Sent from I/O Module)
Event
Note: MEASUREMENT DATA IS NOT VALID BETWEEN EVENTS A AND C
Event A Profibus Master Sets READ_SETUP bit (PUV bit 1) to 1.
I/O Module reads this bit, and begins reading setup from
the LaserSpeed gauge.
Event B I/O Module sets READ_STATUS bit to 1, indicating that
settings in the current Data Exchange message are valid.
Event C Profibus Master sets READ_SETUP bit back to 0
Event D I/O Module sets READ_STATUS bit back to 0
A B C D
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 71 of 84 Revision E (Dec 2013)
Write Setup Cycle
WRITE_SETUP – PUV Bit 0
(Sent from Master)
WRITE_STATUS – PUV Bit 0
(Sent from I/O Module)
Event
Note: MEASUREMENT DATA IS NOT VALID BETWEEN EVENTS A AND C
Event A Profibus Master Sets WRITE_SETUP bit (PUV bit 0) to 1
I/O Module reads this bit, and begins writing setup to the
LaserSpeed gauge. It then verifies the settings.
Event B I/O Module sets WRITE_STATUS bit to 1, indicating that the
settings have been stored and verified in the LaserSpeed
gauge.
Event C Profibus Master sets WRITE_SETUP bit back to 0
Event D I/O Module sets WRITE_STATUS bit back to 0
A B C D
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 72 of 84 Revision E (Dec 2013)
Status Register Format
MSB LSB
bit 7 6:5 4 3 2 1 0
Status Bit TOG 00 VALID MP SHUTTER LASER TEMP
TOG Toggles after each update from the gauge. Each time this bit
changes value, the I/O Module has new data.
MP Material Present Status Bit 0 - Material is Not Present
1 - Material is Present
VALID Valid Measurement Status
Bit
0 - LaserSpeed gauge is not making
measurements
1 - LaserSpeed gauge is making
valid measurements
SHUTTER Beam Shutter Status Bit 0 - Beam Shutter is Closed (no laser
emission)
1 - Beam Shutter is Open (laser
emission)
LASER Laser Interlock Status Bit 0 - Laser is Off (no laser emission)
1 - Laser is ON (laser emission)
TEMP Laser at Temperature
Status Bit
0 - Laser is not at the correct
temperature
1 - Laser is at the correct
temperature
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 73 of 84 Revision E (Dec 2013)
Profibus Status indicator
LED Meaning
1 Not Used
2 (Green) Indicates that the module is On-Line on the
fieldbus.
ON = Module is On-Line and data exchange is
possible.
OFF = Module is not On-Line
3 (Red) Indicates that the module is Off-Line on the
fieldbus.
ON = Module is Off-Line and no data exchange is
possible.
OFF = Module is not Off-Line
4 (Red) Fieldbus Diagnostics. Indicates certain faults on
the Fieldbus side.
Flashing Red 1 Hz - Error in configuration: IN
and/or OUT length set during initialisation of the
module is not equal to the length set during
configuration of the network.
Flashing Red 2 Hz - Error in User Parameter data:
The length/contents of the User Parameter data
set during initialisation of the module is not equal
to the length/contents set during configuration of
the network.
Flashing Red 4 Hz - Error in initialisation of the
Profibus communication ASIC.
Turned Off - No diagnostics present
There is also one additional Bicolour Watchdog LED on the AnyBus-S module.
The functionality of this LED is the same for all AnyBus-S modules, and is
specified in the AnyBus-S Design Guide.
1 2
3 4
Profibus Status Indicator
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 74 of 84 Revision E (Dec 2013)
Profibus DB9 Connector Pinout
Pin Pin Name Description
1 Not Connected -
2 Not Connected -
3 B-Line Positive RxD/TxD according to RS-485 specification
4 RTS Request to Send
5 GND BUS Isolated GND from RS-485 side
6 +5V BUS Isolated +5V from RS-485 side
7 Not connected -
8 A-Line Negative RxD/TxD according to RS-485 specification
9 Not Connected
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 75 of 84 Revision E (Dec 2013)
Ethernet Network Operation
The Ethernet interface is automatically detected. The I/O Module’s interface
supports either T10 or T100. IP address and ports must be set up before use. A
dedicated peer-to-peer network is recommended due the high traffic rate of the
UDP broadcast when using a fast update rate.
Status indications are described in the LaserSpeed I/O Module Operator Guide.
IP Sets the Ethernet IP address of the I/O Module Default is
192.168.001.111
UdpIp Set the address the UDP will broadcast to. Should be the
IP of the Master.
UDP Port Port number for UDP broadcast. This is the port the
Master should use to receive data. Default = 4750
TCP port TCP port for sending and receiving setup data. Default =
4751
Gateway = 0.0.0.0
Mask = 255.255.255.000
UDP Data Broadcast
These values are updated every update period of the gauge and sent out by a
UDP broadcast to the IP at a port specified during setup.
Bytes Name Equivalent LS9000/LS8000 Command
4 Velocity Updated each User Update
4 Length Updated each User Update
1 Quality factor 0-15, 0 bad, 15 great
1 Status 1st bit gauge at temperature, 2nd bit laser on,
3rd bit shutter open, 4th bit valid measurement,
5th bit
Note: When sending configuration parameters to the LS9000/LS8000, the
velocity and length update from the gauge is temporarily halted while the
LS9000/LS8000 is updated to the new setup. This will interrupt data being sent
via the Ethernet connection.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 76 of 84 Revision E (Dec 2013)
TCP Setup
These values are sent and received by a TCP connection. The Status &
Command commands initiate the action.
1) To send new configuration parameters to the LS9000/LS8000
2) Change any setups in the Ethernet setting.
3) Send data to I/O Module using TCP.
4) Set 1st bit in Status & command to signal change.
5) The I/O Module checks for any differences in the Ethernet to what’s in
the LS9000/LS8000.
6) Any changed values are updated to the LS9000/LS8000.
7) Bit 1 is cleared in the Status & Command byte when the
LS9000/LS8000 is updated.
8) Status is sent back.
To get existing setups:
1) Set 2nd
bit in the Status & Command.
2) Send data to I/O Module using TCP.
3) The I/O Module will update the Ethernet memory and send it back to IP
in TCP.
4) 2nd
bit is cleared on the data sent back.
When retrieving data from the LS9000/LS8000 gauge, data is first downloaded
from the gauge and then sent to the Profibus connection. This can take several
seconds.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 77 of 84 Revision E (Dec 2013)
Ethernet Memory Structure
Bytes Name Equivalent LS9000/LS8000 command
1 Status/command 1st bit set LS setup, 2nd bit read LS put
in Fb
4 HoldVel; B hold velocity
4 CalTrim; C calibration trim
4 AnalogFull; D analog full scale
4 MatPresDrop; F Material present drop out time
4 MatPresValid; G Material present Valid time
4 Hour; H Hours since start r/o
4 PulseUnitHigh; L pulse per unit length
4 AnaZero; N analog zero value
4 PulsePerUnitLow; P Pulse per unit length, low speed
4 Calibration; TC reads calibration number
4 WalkThresh; W walking threshold
4 MinFinalLength; X minimum final length
2 Temperature; I internal temperature r/o
1 FinalLengthMode; TF Sets gauge to final length mode
1 Baud J baud rate select
1 FilterLock; E filter lock out
1 DipAvg K Dip averaging
1 Unit U units of measurement
1 ResetLength R Reset length R/O
1 MatPresent S Material present
1 ContTrans TE sets gauge to continuous transmit
1 MatPresThres M material present threshold
1 UserUpdate; O User Update rate
16 GaugeType[16]; Z gauge type
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Operation
Part No. 93342 / Drawing No. 0921-01516 Page 78 of 84 Revision E (Dec 2013)
Ethernet Status LEDS
Status LED Condition
1 – Link LED Green Steady on
Indicates that the module is connected
to an Ethernet network
2 - Status LED
Green 1 Hz
Indicates that the used IP address not is
set by the values on the dipswitches.
Red 1 Hz
The Ethernet MAC address is not
correct. The module will not be able to
initialize. Please contact your supplier.
Red 2 Hz
The module failed to load Ethernet
configuration from the FLASH.
Red 4 Hz
Internal error. Please contact your
supplier.
3 - Modbus/TCP
connection
Green
Indicates the number of Modbus/TCP
connections that is established to the
module. The LED flashes to indicate the
number of connections.
Example: If three connections is
established then this LED flashes three
times, the led is off for a short period
and then the led flashes three times
again, and so on.
4 - Activity LED
Green - Flashes from green to off when
a packet is received or transmitted.
1 2
3 4
Ethernet Status Indicator
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Servicing Your Equipment
Part No. 93342 / Drawing No. 0921-01516 Page 79 of 84 Revision E (Dec 2013)
Servicing Your Equipment
Your instrument was carefully inspected electrically and mechanically prior to
shipment. It should be free of surface mars and scratches, and it should be in
perfect working order upon receipt. If any indication of damage is found, file a
claim with the carrier immediately, prior to using the instrument. If no damage is
apparent, proceed by using this manual to install and setup this instrument.
Save the shipping carton and packing material for future storing or shipment of
the instrument. If, at some future time, the instrument must be returned to the
factory for service, include a full description of the instrument failure and the
mode of operation the instrument was in at the time of failure. Also include a
contact person to discuss the instrument failure.
Returning Equipment for Service
When returning equipment for service, it is important to first obtain a Return
Material Authorization (RMA) number. The RMA number is needed for proper
handling of returned equipment.
1) To obtain an RMA, go to www.betalasermike.com
2) Select Service
3) Select Equipment Return / RMA from the drop-down menu. Follow the
instructions to obtain an RMA.
Ship the instrument in the original carton, or, if the original carton is unavailable,
ship in a carton providing sufficient protection. Send the instrument to the Asia,
Europe, or USA office (addresses listed in the supplied Contacts/CE Compliance
Manual), whichever is closest to you or to the office indicated by your sales
engineer. Place the RMA number on the outside of the carton, and include a
purchase order number and any other information specific to your instrument.
Field warranty service is available, if the customer pays travel expenses by
advance purchase order. All service operations should be performed by skilled
electronics technicians, who have been trained by Beta LaserMike.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Specifications
Part No. 93342 / Drawing No. 0921-01516 Page 80 of 84 Revision E (Dec 2013)
Specifications
Stand-alone Dimensions
Rack Mounting Dimensions
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Specifications
Part No. 93342 / Drawing No. 0921-01516 Page 81 of 84 Revision E (Dec 2013)
Bottom Mounting Dimensions
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Specifications
Part No. 93342 / Drawing No. 0921-01516 Page 82 of 84 Revision E (Dec 2013)
General Specifications
Weight
6 lbs.; 13.2 kg
Input Voltage
100-240V, 50/60 Hz, 100VA.
Fuse
1.5A T 250V
Setup Connector
RS-232 not to exceed 10 meters in length.
DB-9 and DB-25 LaserSpeed Connectors
Cable length not to exceed 100 meters.
24Volts at 2 Amp fused supplied to gauge connector.
DB-9 Light Stack Connector
Cable length not to exceed 10 meters.
24volts at 0.2 Amp.
Analog Outputs
Voltage output range 0 to 2.048 V, RL = 10 k
Output load regulation accuracy VO = 2.048 V, RL= 2 k0.25 voltage % of FS
Ethernet Connection
RJ45, not to exceed 30 meters.
Profibus Connection
Transmission media: Profibus bus line, type A or B specified in EN50170
Topology: Master-Slave communication
Fieldbus connectors: 9 pin female DSUB, as standard.
Cable: Shielded copper cable, Twisted pair
Isolation: The bus is galvanically separated from the other electronics
with an on board DC/DC converter. Bus signals (A-line and B-line) are
isolated via opto-couplers.
Profibus-DP communication ASIC: SPC3 chip from Siemens.
Fieldbus type: PROFIBUS-DP EN 50 170 (DIN 19245)
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Specifications
Part No. 93342 / Drawing No. 0921-01516 Page 83 of 84 Revision E (Dec 2013)
Protocol version: ver. 1.10
Protocol stack supplier: SIEMENS
Extended functions supported: Diagnostics & User Parameter data,
accessed via mailbox telegram.
Auto baud rate detection supported. Baud rate range: 9.6 kbit-12Mbit
Hardware prepared for DP-V1 extensions.
Save/Load configuration in Flash supported.
Enclosure
IP50
Environmental Conditions
Indoor use
Altitude up to 2000m
Temperature 5C to 40C
Maximum relative humidity 80% for temperatures up to 31C decreasing
linearly to 50% relative humidity at 40C
MAINS supply voltage fluctuations up to 10% of nominal voltage
Transient over-voltage typically present on MAINS supply. NOTE: The
normal level of transient over-voltages is impulse withstand (over-
voltage) CATEGORY II of IED 60364-4-443.
Applicable rated pollution degree 2.
LaserSpeed 8000/9000 I/O Module Instruction Handbook
Index
Part No. 93342 / Drawing No. 0921-01516 Page 84 of 84 Revision E (Dec 2013)
Index Analog Outputs ......................................... 19
Configuration Commands ......................... 34
Data Ready Mode ..................................... 20
Data Request Mode .................................. 22
Default Communication Settings .............. 32
Dimensions ............................................... 80
Elongation/Differential Speed Calculation 27
Elongation/Synchronization ...................... 24
EMC Directive ............................................. 4
Ethernet Network Operation ..................... 75
External Material Present ......................... 18
Female 37-Pin D-Subminiature ................ 13
Front Panel ................................................. 7
Gauge RS-232 Connector ........................ 14
I/O Setup Connector ................................. 14
Industrial Environment ................................ 4
Intended Use .............................................. 6
Introduction ................................................. 7
LaserSpeed Communication .................... 60
LaserSpeed Gauge .................................... 9
Light Stack .................................................. 9
Light Stack Connector Pinout ................... 15
Male 25-Pin D-Subminiature .................... 12
Master/Slave I/O Modules ........................ 24
Operation .................................................. 61
Parallel Outputs ........................... 10, 16, 20
Profibus Operation .................................... 62
Rear Panel Pin-outs ................................... 8
Safety Information ...................................... 6
SELV levels ................................................ 6
Serial Communications ............................. 31
Servicing Your Equipment ........................ 79
Setting Validation ...................................... 33
Setup ........................................................ 28
Specifications............................................ 80
Status Signals ........................................... 16
SYNC IN and OUT ................................... 10
Synchronization ........................................ 26