SECTION 28 35 00 FIRE ALARM AND DETECTION SYSTEMS Copyright 2009 - 2009 ARCAT, Inc. - All rights reserved ** NOTE TO SPECIFIER ** Bosch Security Systems; security and life safety systems. . This section is based on the products of Bosch Security Systems, which is located at: 130 Perinton Pkwy. Fairport, NY 14450 Toll Free Tel: 800-289-0096 Tel: 585-223-4060 Fax: 585-223-9180 Email:request info ([email protected]) Web:www.boschsecurity.us [Click Here ] for additional information. Bosch Security Systems, Inc. works closely with an extensive network of certified dealers and integrators to design dependable security and life safety solutions for the market. Our broad portfolio of products and systems for video surveillance, access control, and intrusion and fire detection are used by major schools and universities, government agencies, correctional facilities, retail stores, casinos and in many other commercial environments throughout North America. Our significant investment in research and development is unsurpassed in the security industry and enables us to regularly update our existing products and introduce new technologies. These advancements are continually recognized by the market. For example, the products we manufacture for networked video systems have won 11 awards in the last three years. Our solution for integrating building security and management systems across an enterprise has been implemented by various Fortune 500 companies and can facilitate centralized management of an organization's assets. Testing by independent certified regulatory compliance organizations verifies updates to our intrusion and fire systems extend beyond minimum compliance requirements. And, while technological innovation is important, we ensure that new product development addresses all the concerns paramount in the world of security and life safety today, including performance, quality, and ease of installation, maintenance and use. 28 30 00-1
Transcript

SECTION 28 35 00FIRE ALARM AND DETECTION SYSTEMS

Copyright 2009 - 2009 ARCAT, Inc. - All rights reserved

** NOTE TO SPECIFIER ** Bosch Security Systems; security and life safety systems..This section is based on the products of Bosch Security Systems, which is located at:130 Perinton Pkwy.Fairport, NY 14450Toll Free Tel: 800-289-0096Tel: 585-223-4060Fax: 585-223-9180Email:request info ([email protected])Web:www.boschsecurity.us[Click Here] for additional information.

Bosch Security Systems, Inc. works closely with an extensive network of certified dealers and integrators to design dependable security and life safety solutions for the market. Our broad portfolio of products and systems for video surveillance, access control, and intrusion and fire detection are used by major schools and universities, government agencies, correctional facilities, retail stores, casinos and in many other commercial environments throughout North America.

Our significant investment in research and development is unsurpassed in the security industry and enables us to regularly update our existing products and introduce new technologies. These advancements are continually recognized by the market. For example, the products we manufacture for networked video systems have won 11 awards in the last three years. Our solution for integrating building security and management systems across an enterprise has been implemented by various Fortune 500 companies and can facilitate centralized management of an organization's assets. Testing by independent certified regulatory compliance organizations verifies updates to our intrusion and fire systems extend beyond minimum compliance requirements. And, while technological innovation is important, we ensure that new product development addresses all the concerns paramount in the world of security and life safety today, including performance, quality, and ease of installation, maintenance and use.

For more than 100 years, the Bosch name has stood for quality and reliability. We are there for our customers during all crucial phases of a project: before, during and after the sale..

PART 1 GENERAL

1.1 SECTION INCLUDES** NOTE TO SPECIFIER ** FPA 1000 Product. Delete items below not required for project.

A. The contractor shall furnish and install a complete 24 VDC, electrically supervised, analog addressable fire alarm system as specified herein and indicated on the drawings. The system shall include but not be limited to all control panels, power supplies, initiating devices, audible and visual notification appliances, alarm devices, and all accessories required to provide a complete operating fire alarm system.

28 30 00-1

1. System cabinet.2. Power supply.3. One SLC loop, plus one optional SLC loop.4. 4 x 20 character LCD annunciator.5. Dedicated LEDs Display's for Fire alarm, Gas alarm, trouble.6. Programming keypad.7. Up to 254 detectors/pull stations/modules plus 254 analog sounder bases ending up

to a total of 508 addressable points.8. Built in dual line Digital Communicator.9. Built in web server for IP communication for alarm transmitting with full single, double,

and backup reporting and programming.10. Associated peripheral devices.11. Batteries.12. Wiring.13. Conduit.

** NOTE TO SPECIFIER ** FPD 7024 Product. Delete items below not required for project.

B. The contractor shall furnish and install a complete 24 VDC, electrically supervised, conventional / addressable fire alarm system as specified herein and indicated on the drawings. The system shall include but not be limited to all control panels, power supplies, initiating devices, audible and visual notification appliances, alarm devices, and all accessories required to provide a complete operating fire alarm system.1. System cabinet.2. Power supply.3. Two optional multiplex buss.4. 32 character LCD annunciator.5. Programming keypad.6. Four to eight programmable conventional zones.7. Up to 247 addressable points in addition to 8 conventional zones.8. Built in dual line Digital Communicator.9. IP communications with a DX4020 Network Interface.10. Module installed) with full single, double, and backup reporting.11. Associated peripheral devices.12. Batteries.13. Wiring.14. Conduit.

1.2 RELATED SECTIONS** NOTE TO SPECIFIER ** Delete any sections below not relevant to this project; add others as required.

A. Section 05 50 00 - Metal Fabrications.

B. Division 16 - Electrical: Wiring, conduit, disconnects and connection to power supply and control devices.

1.3 REFERENCES** NOTE TO SPECIFIER ** Delete references from the list below that are not actually required by the text of the edited section.

A. National Electric Code, Article 760.

B. National Fire Protection Association Standards:1. NFPA 70 - National Electrical Code.2. NFPA 72 - National Fire Alarm Code.3. NFPA 101 - Life Safety Code.

28 30 00-2

C. Local and State Building Codes:1. BOCA, National Building Code, Mechanical Code, Fire Prevention Code.

D. Local Authorities Having Jurisdiction (AHJ).

E. Underwriters Laboratories 1nc.:1. Equipment shall be approved by Underwriters Laboratories, Inc. for its intended

purpose, listed as power limited by Underwriters Laboratories, Inc., for the following standards as applicable.

2. UL 864 9th Editions UOJZ - Control units for Fire Protective Signaling Systems:Local Signaling Unit..Central Station Signaling Protected Premises Unit.Remote Signaling Protected Premises Unit.Auxiliary System Control Unit.

3. UL 268 - Smoke Detectors for Fire Protective Signaling systems.4. UL 268A - Smoke Detectors for duct applications.5. UL 217 - Smoke Detectors for Single Stations.6. UL 521 - Heat Detectors for Fire Protective Signaling systems.7. UL 228 - Door Holders for Fire Protective Signaling systems.8. UL 464 - Audible Signaling appliances.9. UL 1638 - Visual Signaling appliances.10. UL 38 - Manually Activated Signaling Boxes.11. UL 346 - Water flow indicators for Fire Protective Signaling systems.12. UL 1481 - Power Supplies for Fire Protective Signaling systems.

F. Americans with Disabilities Act (ADA):1. All visual notification appliances and manual pull stations shall comply with the

requirements of the Americans with Disabilities Act.

G. California State Fire Marshal (CSFM)1. 71650801:177.

H. New York City's Materials and Equipment Acceptance system (NYC-MEA):1. MEA 12-92-E Vol. VII (Conventional version only, addressable pending).

1.4 REGULATORY REQUIREMENTS

A. Listings:1. All fire alarm system equipment shall be listed for it's intended purpose and be

compatibility listed to assure the integrity of the complete system.

1.5 SUBMITTALS

A. Submit under provisions of Section 01 30 00.

B. Product Data: Manufacturer's data sheets on each product to be used, including:1. Submit required documentation within thirty calendar days after award of the purchase

order. Indicated in the document will be the type, size, rating, style, catalog number, manufacturers' names, photos, and /or catalog data sheets for all items proposed to meet these specifications. The proposed equipment shall be subject to the approval of the Architect/Engineer and no equipment shall be ordered or installed on the premises without that approval.

C. Shop Drawings: Indicate dimensions and required tolerances, connection details, anchorage spacing, installation details, and special conditions.1. Submittal of shop drawings shall contain at least three copies of original manufacturer

specification and installation instruction sheets. Subsequent information may be copies. All equipment and devices on the shop drawings to be furnished under this contract shall be clearly marked in the specification sheets.

28 30 00-3

D. Qualification Submittals:1. Supplier's qualifications shall be submitted indicating years in business, service

policies, warranty definitions, NICET certification, and completion of factory training program and a list of similar installations.

2. Contractor qualifications shall be supplied indicating years in business and prior experience with installations that include the type of equipment that is to be supplied.

3. The contractor shall provide hourly Service Rates, performed by a technician for this installed Life Safety System with the submittal. These hourly service rates shall be guaranteed for a 1-year period.

E. Contract Close-out Submittals:1. Deliver two copies of the following to the owner's representative within Thirty days of

system acceptance. The closeout submittals shall include:a. Installation and Programming manuals for the installed Life Safety System.b. Point to point diagrams of the entire Life Safety System as installed. This shall

include all connected smoke detectors and addressable field modules.2. All drawings shall reflect device address as verified in the presence of the engineer

and/or end user.

1.6 QUALITY ASSURANCE

A. Manufacturers/Distributors Services:1. The following supervision shall be provided by an authorized factory trained service

technician from the dealer of the fire alarm equipment. The technician shall have a minimum of two years of service experience in the fire alarm industry. The technician shall have the appropriate state licenses where applicable. The technician's name shall appear on equipment submittals. The technician shall be responsible for the following items:a. A pre installation visit to the job site to review equipment submittals and to

verify the method by which the system is to be wired.b. During the installation the technician shall be on site or make periodic visits to

verify installation and wiring of the system. He shall also supervise the completion of conduit rough, wires pulled into conduit and wiring rough, and ready for trim.

c. Upon completion of wiring, final checkout and certification of the system shall be made under the supervision of this technician.

d. At the time of the formal checkout, technician shall give operational instructions to the owner and/or his representative on the system.

B. Installer Qualifications: Company experienced in manufacturer's products and certified by the manufacturer.

1.7 DELIVERY, STORAGE, AND HANDLING

A. Store products in manufacturer's unopened packaging until ready for installation.

B. Store and dispose of solvent-based materials, and materials used with solvent-based materials, in accordance with requirements of local authorities having jurisdiction.

1.8 PROJECT CONDITIONS

A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits.

1.9 WARRANTY

28 30 00-4

A. Warrant all materials, installation and workmanship for a three year period, unless otherwise specified. A copy of the manufacturer's warranty shall be provided with the close out documentation.

PART 2 PRODUCTS

2.1 MANUFACTURERS

A. Acceptable Manufacturer: Bosch Security Systems, which is located at: 130 Perinton Pkwy. ; Fairport, NY 14450; Toll Free Tel: 800-289-0096; Tel: 585-223-4060; Fax: 585-223-9180; Email:request info ([email protected]); Web:www.boschsecurity.us

** NOTE TO SPECIFIER ** Delete one of the following two paragraphs; coordinate with requirements of Division 1 section on product options and substitutions.

B. Substitutions: Not permitted.

C. Requests for substitutions will be considered in accordance with provisions of Section 01 60 00.

D. Products:1. The Life Safety System requirements shall be conformed to in their entirety to ensure

that the installed and programmed Life Safety System will accommodate all of the requirements and operations required by the building owner. Any specified item or operational feature not specifically addressed prior to the bid date will be required to be met without exception.

2. Submission of product purported to be equal to those specified herein will be considered as possible substitutes only when all of the following requirements have been met:a. Any deviation from the equipment, operations, methods, design or other criteria

specified herein shall be submitted in detail to the specifying Architect or Engineer a minimum of ten working days prior to the scheduled submission of bids. Each deviation from the operation detailed in these specifications shall be documented in detail, including page number and section number, which lists the system function for which the substitution is being proposed.

b. A complete list of such substituted products with three copies of working drawings thereof shall be submitted to the approved Architect and/or Consulting Engineer not less than ten working days prior to the scheduled submission of bids.

c. The contractor or substitute bidder shall functionally demonstrate that the proposed substitute products are in fact equal in quality and performance to those specified herein.

E. General Equipment and Materials Requirements:1. All equipment furnished for this project shall be new and unused. All components

shall be designed for uninterrupted duty. All equipment, materials, accessories, devices and other facilities required or as noted on the contract drawings shall be best suited for the intended use and shall be provided by a single manufacturer. If any of the equipment provided is by different manufacturers, then that equipment shall be "Listed" as to its compatibility by Underwriters Laboratories (UL), if such compatibility is required by UL standards.

F. Design Intent:1. It is the contractor's responsibility to meet the entire intent of these specifications.2. Deviations from the specified items shall be at the risk of the contractor until the date

of final acceptance by the architect, engineer, and owner's representative.3. All costs for removal, relocation, or replacement of a substituted item shall be at the

risk of the contractor.

28 30 00-5

** NOTE TO SPECIFIER ** FPA-1000 Product. Delete if not required.

2.2 GENERAL DESCRIPTION

A. Control Panel:1. The Fire Alarm Control Panel (FACP) shall be the Bosch FPA-1000-UL analog

addressable control panel. The FACP shall have a 5.5 amp power supply be capable to support a maximum battery capacity of 40 Ah.

2. The FACP shall be capable of supporting two (2) Signaling Line Circuits (SLC) configurable as two Class B Style 4 or one Class A Style 6 or 7

3. Each SLC shall be capable of supporting up to 127 sensors/pull stations / modules, plus 127 analog sounder bases, for a total of 254 addressable points per SLC. Systems that are not capable of this SLC capacity shall not be acceptable.

4. The panel shall have a built in 4 x 20 character LCD annunciator/keypad with the capability of having an additional eight supervised remote annunciators/keypads connected in the field. The LCD annunciator/keypads shall have additional dedicated LEDs for fire alarm, gas alarm and trouble.

5. The FACP shall have a built in UL approved digital communicator. The communicator shall transmit in Modem IIIa2, SIA, CID.

6. The FACP shall have a built in IP communication and interface for alarm signaling transmitting. The Web Server shall transmit in Modem IIIa2, SIA, CID. The server shall allow local and remote up/downloading of system operating options, event history, and detector sensitivity data for addressable detectors. System requiring proprietary software to access system operating system and perform these functions shall not be permitted.

7. The FACP shall have three onboard programmable Form C relay with default operation for common Fire alarm, common trouble and common supervisory.

8. The FACP shall have two onboard Class A (Style Z) or Class B (Style Y) programmable Notification Appliance Circuits rated at 2.5 amps / 24V.

9. Class A or B configuration on both IDC and NAC devices shall not require adaptors.10. The main communication bus (options bus) shall be capable of Class A or Class B

configuration with a total bus length of 5,900 feet (1,798 m).

B. System Wiring:1. The SLC Bus and the Data Communication Bus (options bus) shall be wired with

standard NEC 760 compliant wiring, no twisted, shielded or mid capacitance wiring is required for standard installations. All FACP screw terminals shall be capable of accepting 14 AWG (1.8 mm) to 18 AWG (1.2 mm) wire. All system wiring shall be in accordance with the requirements of NFPA 70, the National Electrical Code (NEC) and also comply with article 760 of the NEC.

2. Power Limited Wiring: For Power Limited wiring, use FPL, FPLR or FPLP approved wiring.

C. SLC Bus:1. The SLC Bus shall be capable of a wiring distance of 10.000 feet from the signaling

line circuit module (FPE-1000-SLC). Every signaling line circuit module shall be capable to support 127 detectors and/or pull-stations and/or modules plus 127 analog sounder bases, for a total of 254 addressable points. The communication protocol shall be digital transmitting analog. The SLC bus shall be capable of functioning as two Class B Style 4 or one Class A Style 6 or 7 configuration.

D. SLC Bus Loop Devices:1. Devices supported shall include addressable photoelectric smoke detectors,

addressable heat detector, addressable input modules, input/relay output modules, dual input modules, and addressable eight input modules. There shall be no device type limit.

28 30 00-6

E. Detector Functions:1. FACP shall receive analog information from all analog addressable sensors/detectors

to be processed to determine whether normal, alarm, pre-alarm, or trouble conditions exist for each sensor/detector. The software shall automatically maintain the sensor/detector's desired sensitivity level by adjusting for the effects of environmental factors, including the accumulation of dust in each sensor/detector. The panel will assess the sensor/detector analog data to determine when the fire condition is reached and the alarm must be generated. The analog information shall also be used for automatic detector testing/calibration and for the automatic determination of detector maintenance requirements. See Drift Compensation and Calibration portions of this document for additional details

F. Annunciators:1. The main control must have a built in annunciator with a 4x20 character LCD display

and feature LED's for Fire Alarm, Gas Alarm, System Trouble, System Silence, Supervisory, and Power. The LEDs for Fire Alarm and Gas Alarm must have different colours in order to be distinguishable. Systems that do not include these indications shall not be acceptable. All controls and programming keys are membrane style buttons. The annunciator must be able to silence and reset alarms by pushing the desired function key, the access to the function keys shall either be granted by a key switch or by user code, depending on how the system is configured. The annunciators must have four levels of user codes that will allow the limitation of operating system programming to authorized individuals.

G. Remote Annunciators:1. The fire system shall be capable of supporting up to eight remote annunciators.The

LCD Remote annunciator Model FMR-1000-RCMD shall have the same control and display layout so that they match identically the built in annunciator. Remote annunciators shall have the same functionality and operation as the built in annunciator. All annunciators shall have 4x20 character LCD display and shall feature LED's for Fire Alarm, Gas Alarm, System Trouble, System Silence, Supervisory, and Power. The LEDs for Fire Alarm and Gas Alarm must have different colors in order to be distinguishable. Systems that do not include these indications shall not be acceptable.

2. The annunciator must be able to silence and reset alarms by pushing the desired function key, the access to the function keys shall either be granted by a key switch or by user code, depending on how the system is configured. The annunciators must have four levels of user codes that will allow the limitation of operating system programming to authorized individuals.

3. The control panel shall allow all annunciators to accommodate multiple users input simultaneously. Remote annunciators shall be capable of operating at a distance of 4000 feet (1219 m) from the main control panel on unshielded non-twisted cable.

4. An annunciator with 4x20 character LCD display, acknowledge and scroll buttons shall be available.

H. Annunciator Modules:1. The fire system shall be able to support up to eight LED annunciator modules

(D7030X) that shall be used to drive eight LED's for zone annunciation. The D7030X shall reside on the option bus, and can be up to 3300 feet (1010 m) from the control.

I. Distributed Power Panel:1. The contractor shall supply a FPP-RNAC-8A-4C power module compatible with the

FPA-1000-UL fire alarm control panel. The power module shall have 8 Amps of output power, four NAC circuits rated at 2.5 Amps each, and one Form C trouble relay. The four NAC circuits shall have similar functionality as the NAC circuits on the main panel. The fire system shall be capable of supporting up to four (4) power modules.

28 30 00-7

The 4 NAC circuits of each of the 4 FPP-RNAC-8A-4C power modules shall be synchronized and individually controlled for a total of 16 NAC circuits. The distributed Power module shall be capable of being connected via an option system bus at a maximum distance of 4000 ft. (1,219 m) from the main control panel.

2. Each NAC circuit shall be able to produce the output patterns Steady, Temporal Code Pulsed, California March, Wheelock Synch, System Sensor Synch.

3. The FPP-RNAC-8A-4C power module shall provide 8 LEDs which indicate AC ok, Trouble NAC circuit 1, Trouble NAC circuit 2, Trouble NAC circuit 3, Trouble NAC circuit 4, Input active, Ground fault. The power module shall be able to monitor ground fault and indicate if necessary.

J. seq subsub Digital Communicator:1. The digital communicator shall be an integral part of the control panel and be capable

of reporting all points and all zones of alarm, supervisory, and trouble as well as all system status information such as loss of AC, low battery, ground fault, loss of supervision to any remote devices with individual and distinct messages to a central station or remote station. The communicator shall also be capable of up/downloading of all system programming options, Event history and Sensitivity compliance information to a PC on site or at a remote location.

2. The communicator shall have an answering machine bypass feature that will allow the panel to respond to communication even on phone lines that have other communication equipment present. The communicator shall be capable of reporting via SIA, Contact ID, 3/1 formats and Modem IIIa2. The communicator shall have a delayed AC loss report function which will provide a programmable report delay to help ease traffic to the central station during a power outage.

K. Web Server1. The Web Server shall be an integral part of the control panel and be capable of

reporting all points and all zones of alarm, supervisory, and trouble as well as all system status information such as loss of AC, low battery, ground fault, loss of supervision to any remote devices with individual and distinct messages to a central station or remote station. The communicator shall also be capable of up/downloading of all system programming options, Event history and Sensitivity compliance information to a PC on site or at a remote location.

2. The software to connect to the integrated Web server shall be Microsoft Internet Explorer or Mozilla Firefox. There shall be no proprietary software needed to assess the panel. Systems that do not include these indications shall not be acceptable.

L. Dry Contacts:1. The FACP shall have three onboard programmable Form C relays with default

operation for common Fire alarm, common trouble and common supervisory which shall programmable to other conditions, if necessary.

M. Ground Fault Detection:1. A ground fault detection circuit shall be provided to detect positive and negative

grounds on all field wiring. The ground fault detector shall operate the general trouble devices as specified but shall not cause an alarm to be sounded. A single ground fault will not interfere with the normal operation, such as alarm, or other trouble conditions.

N. seq subsub Test Functions:1. A "Walk Test" mode shall be a standard feature of the fire alarm control panel. The

walk test feature shall function silently or audible. In the audible mode that each alarm input tested will operate the associated notification appliance for 5 seconds or 10 seconds. The FACP will then automatically perform a reset and confirm normal device operation.

2. A "Fire Drill" mode shall allow the manual testing of the fire alarm system notification circuits. The "Fire Drill" shall be capable of being controlled at the main annunciator,

28 30 00-8

and remote annunciators FMR-1000-RCMD.3. A "disable Mode" shall allow for any point or NAC circuit to be disabled without

affecting the operation of the total fire system.

O. Remote Input Capabilities:1. The control panel shall have provisions for supervised switch inputs for the purpose of

Alarm reset and silence operations.

P. seq subsub Notification Appliance Mapping Structure:1. All notification circuits and modules shall be programmable via a mapping structure

that allows output activation to be flexibly associated with input activation or system conditions. Each of these outputs shall have the ability to be triggered by any of the panel's 128 software zones or 6 global zones. Any number of inputs shall be mapped to a software zone. Any software zone may trigger outputs individually. Global zones may be triggered by global conditions such as global alarms, global trouble global gas Additionally each output can be individually configured to control the cadence pattern of the output so that sounders can indicate a variety of conditions.

Q. seq subsub On board programmer:1. The FACP shall have an on board programmer which will allow for all system

functions and options to be programmed via the on board annunciator keypad. Any panel that does not have this capability will not be accepted.

R. seq subsub Language descriptions:1. The FACP shall provide the ability to have a text description of up to 20 characters for

each input point, on the system. The use of individual lights to provide descriptions will not be acceptable.

2. The FACP shall be able to switch its operating and programming language between English, Spanish and Portuguese. The display of the main board annunciator and the remote annunciator should be adaptable to English, Spanish, and Portuguese.

** NOTE TO SPECIFIER ** FPD-7024 Product. Delete if not required.

2.3 GENERAL DESCRIPTION

A. Control Panel:1. The Fire Alarm Control Panel (FACP) shall be the Bosch FPD-7024 conventional

/addressable control panel. The FACP shall have a 4 amp power supply and be capable of expansion to a maximum of 32 total amps via bus connected expander modules that supervise low battery, loss of AC and loss of communication.

2. The panel shall be NetCom compatible.3. The FACP shall be capable of supporting up to eight (8) conventional fire zones and

247 addressable points combined in one system.4. The panel shall have a built in 32 character LCD annunciator/keypad with the

capability of having an additional four supervised remote annunciators/keypads connected in the field.

5. The FACP shall have a built in UL approved digital communicator. The communicator shall transmit in Modem IIIa2, SIA, CID, BFSK and 4/2, 3/1 Tone Burst. The communicator shall allow local and remote up/downloading of system operating options, event history, and detector sensitivity data for addressable detectors.

6. Class A or B configuration on both IDC and NAC devices shall not require adaptors.7. The main communication bus (options bus) shall be capable of Class A or Class B

configuration with a total bus length of 5,900 feet (1,798 m).

B. System Wiring:1. The multiplex buss and Data Communication Bus (options bus) shall be wired with

standard NEC 760 compliant wiring, no twisted, shielded or mid capacitance wiring is required for standard installations. All FACP screw terminals shall be capable of

28 30 00-9

accepting 14 AWG (1.8 mm) to 18 AWG (1.2 mm) wire. All system wiring shall be in accordance with the requirements of NFPA 70, the National Electrical Code (NEC) and also comply with article 760 of the NEC.

2. Power Limited Wiring: For Power Limited wiring, use FPL, FPLR or FPLP approved wiring.

C. Multiplex Bus:1. Each multiplex bus shall be capable of a wiring distance of 5,900 feet from the

multiplex bus driver module (D7039) and be capable of supporting 128 devices. The communication protocol to multiplex bus devices shall be digital. Any multiplex bus loop device, which goes into alarm, shall interrupt the polling cycle for priority response from the FACP. The FACP shall respond consistently to a device that goes into alarm on a multiplex buss in less than 3 seconds. The multiplex buss shall be capable of functioning in a Class A or Class B configuration.

D. Multiplex Bus Loop Devices:1. Devices supported shall include addressable photoelectric smoke detectors,

addressable input modules, input/relay output modules, dual input modules, and addressable eight input modules. There shall be no device type limit.

E. Detector Functions:1. The products of photoelectric detectors shall communicate values using a digital

protocol to the FACP using the following values:a. Automatic compliance with NFPA 72 standards for detector sensitivity.b. Trouble alert when a detector is out of tolerancec. Alert control panel of values that indicate fire.

F. Maintenance Function:1. The FACP shall have the ability to poll its multiplex smoke detectors for detectors that

are getting close to their compliance limits. When a detector has reached near these limits it will send maintenance or "Chamber Check" alert to the control. The FACP will indicate the condition via the LCD display and record it to the buffer. The end user shall have the ability to access this information from the Annunciator and from the remote software.

G. On board programmable conventional inputs:1. The FACP shall support four (4) on board conventional input circuits that are each

capable of supporting up to 20 two wire conventional smoke detectors. A four- (4) conventional input module (FPC-7034) expander can be added to give the FACP the ability to provide eight (8) conventional zones and a total of 160 conventional smoke detectors.

H. Annunciators:1. The main control must have a built in annunciator with a 32-character LCD display

and feature LED's for General Alarm, System Trouble, System Silence, Supervisory, Ground Fault and Power. All controls and programming keys are membrane style buttons. The annunciator must be able to silence and reset alarms through the use of a keypad-entered code, or by just pushing the desired function key, depending on how the system is configured. The annunciators must have four levels of user codes that will allow the limitation of operating system programming to authorized individuals.

I. Remote Annunciators:1. The fire system shall be capable of supporting up to four remote annunciators. LCD

Remote annunciator Model FPC-7033 shall have the same control and display layout so that they match identically the built in annunciator. Remote annunciators shall have the same functionality and operation as the built in annunciator. All annunciators shall

28 30 00-10

have 32-character LCD displays and shall feature four LED's for general alarm, system trouble, system silence, and system power. All controls and programming keys are silicone mechanical type with tactical and audible feedback. Keys shall have a travel of .040 inches (.01 cm). No membrane style buttons will be permitted.

2. The annunciator shall be able to silence and reset alarms through the use of a code entered on the annunciator keypad. The annunciator shall have three levels of user codes that will limit the operating system programming to authorized individuals. The control panel shall allow all annunciators to accommodate multiple users input simultaneously. Remote annunciators shall be capable of operating at a distance of 2,000 feet (610 m) from the main control panel on unshielded non-twisted cable.

3. An annunciator with 2 line LCD display, silence and reset buttons protected by key switch shall be available.

J. Annunciator Modules:1. The fire system shall be able to support up to eight LED annunciator modules

(D7030X) that shall be used to drive eight LED's for zone annunciation. These annunciators will only follow the fifty programmable zones on the control. The D7030X shall reside on the option buss, and can be up to 1,000 feet (305 m) from the control.

K. Distributed Power Panel:1. The contractor shall supply a D7038 compatible with the FPD-7024 fire alarm control

panel. The power module shall have 6 Amps of output power, four NAC circuits rated at 2.5 Amps each, and one trouble relay circuits. The fire system shall be capable of supporting up to two (2) D7038 modules. The four NAC circuits shall have similar functionality as the NAC circuits on the main panel. The Distributed Power Supply shall be capable of being connected via an option system buss at a maximum distance of 4000 ft. (1,219 m) from the main control panel.

L. seq subsub Digital Communicator:1. The digital communicator shall be an integral part of the control panel and be capable

of reporting all points and all zones of alarm, supervisory, and trouble as well as all system status information such as loss of AC, low battery, ground fault, loss of supervision to any remote devices with individual and distinct messages to a central station or remote station. The communicator shall also be capable of up/downloading of all system programming options, Event history and Sensitivity compliance information to a PC on site or at a remote location.

2. The communicator shall have an answering machine bypass feature that will allow the panel to respond to communication even on phone lines that have other communication equipment present. The communicator shall be capable of reporting via 4/2, BFSK, SIA, Contact ID, 3/1 formats and Modem IIIa2. The communicator shall have a delayed AC loss report function which will provide a programmable report delay to help ease traffic to the central station during a power outage. No controls that use External modems for diagnostics control shall be accepted.

M. Dry Contacts:1. The FACP will have 3 form "C" dry contacts that can be programmed for alarm,

trouble notification, water flow, and supervisory.

N. Ground Fault Detection:1. A ground fault detection circuit shall be provided to detect positive and negative

grounds on all field wiring. The ground fault detector shall operate the general trouble devices as specified but shall not cause an alarm to be sounded. A single ground fault will not interfere with the normal operation, such as alarm, or other trouble conditions.

O. Over current Detection:1. All low voltage circuits will be protected by microprocessor controlled circuit breakers

or has a self restoring circuit breaker for the following: smoke detector power, main

28 30 00-11

power supply, indicating appliance circuits, battery standby power and auxiliary output.

P. seq subsub Test Functions:1. A "Walk Test" mode shall be a standard feature of the fire alarm control panel. The

walk test feature shall function so that each alarm input tested will operate the associated notification appliance for two seconds. The FACP will then automatically perform a reset and confirm normal device operation.

2. A "Fire Drill" mode shall allow the manual testing of the fire alarm system notification circuits. The "Fire Drill" shall be capable of being controlled at the main annunciator, and remote annunciators.

3. A "disable Mode" shall allow for any point or NAC circuit to be disabled without affecting the operation of the total fire system.

Q. Remote Input Capabilities:1. The control panel shall have provisions for supervised switch inputs for the purpose of

Alarm reset and silence operations.

R. seq subsub Notification Appliance Mapping Structure:1. All notification circuits and modules shall be programmable via a mapping structure

that allows output activation to be flexibly associated with input activation or system conditions. Each of these shall have the ability to be triggered by any of the panel's 50 input Zones or 10 system zones. An input zone may trigger outputs individually, or zones may be triggered by global conditions such as fire alarms, water flow alarms, system trouble or other system zones. Additionally each output can be individually configured to control the cadence pattern of the output so that sounders can indicate a variety of conditions.

S. seq subsub On board programmer:1. The FACP shall have an on board programmer which will allow for all system

functions and options to be programmed via the on board annunciator keypad. Any panel that does not have this capability will not be accepted.

T. seq subsub Downloading Software:1. The fire alarm control panel must support up/downloading of system programming

from a PC with Remote Programming software using DX4010I, D4010V2 or DX4020 Network interface modules.

2. The FACP shall also be able to download the detector "Chamber Check" state of the addressable detectors, and 500-event system buffer to the PC. Communication shall take place via the same telephone lines as the built in digital communicator and shall not require an external modem to be connected to the panel. The downloading software shall contain a code that will block unauthorized persons from accessing the panel via direct connection or over the phone lines.

U. seq subsub English language descriptions:1. The FACP shall provide the ability to have a text description of up to 16 characters for

each input point, on the system. The use of individual lights to provide descriptions will not be acceptable.

2.4 SYSTEM OPERATION

A. Alarm:1. When a device indicates any alarm condition the control panel shall respond within

three seconds. The General Alarm LED on the annunciator(s) should light and the LCD should prompt the user as to the current events. The alarm information shall be stored in event memory for later review. When the alarmed device is restored to normal, the control panel shall be required to be manually reset to clear the alarm

28 30 00-12

condition, except that the alarms may be silenced as programmed.2. An alarm shall be silenced by the silenced button at the main or on the remote

annunciators. When silenced, this shall not prevent the resounding of subsequent events if another event should occur (subsequent alarm feature). When alarms are silenced the silenced LED on the control panel, and on any remote annunciators shall remain lit, until the alarmed device is returned to normal.

B. Troubles:1. When a device indicates a trouble condition, the control panel System Trouble LED

should light and the LCD should prompt the user as to the current events. The trouble information shall be stored in event memory for later review.

2. When the device in trouble is restored to normal, the control panel shall be automatically reset. The trouble restore information shall be stored in event memory for later review. Pushing the silence button at the main control or entering a code and pushing the silence button on the remote annunciators shall silence a trouble. When silenced, this shall not prevent the resounding of subsequent events if another event should occur.

C. Supervision Methods:1. Each loop shall be electrically supervised for opens and ground faults in the circuit

wiring, and shall be so arranged that a fault condition on any loop will not cause an alarm to sound. Additionally, every addressable device connected to the multiplex buss will be supervised and individually identified if in a fault condition. The occurrence of any fault will light a Supervisory LED and sound the system trouble sounder, but will not interfere with the proper operation of any circuit which does not have a fault condition.

2. Each indicating appliance circuit shall be electrically supervised for opens, grounds and short circuit faults, on the circuit wiring, and shall be so arranged that a fault condition on any indicating appliance circuit or group of circuits will not cause an alarm to sound. The occurrence of any fault will light the trouble LED and sound the system trouble sounder, but will not interfere with the proper operation of any circuit which does not have a fault condition.

* NOTE TO SPECIFIER ** FPD-7024 Product only. Delete if not required.

D. Ground Faults:1. A Yellow GND Fault LED - lights whenever the system detects a ground fault

condition. A single ground fault will not interfere with the normal operation, such as alarm, or other trouble conditions.

2.5 CONTROL UNIT

A. System Cabinet:1. Mounting: The system cabinet shall be red and can be surface or semi-flush mounted.

The cabinet door shall be easily removable to facilitate installation and service.2. Key lock to prevent tampering: The cabinet shall have a physical key and lock system

to prevent unauthorized tampering to the control panel, power supply and any wiring within the cabinet.

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.3. Dead front door to protect circuit's board and wiring. The cabinet shall have an extra

dead front door to prevent touching the circuit boards, power supply and wirings. The dead front door shall be easily removable to facilitate installation and service.

* NOTE TO SPECIFIER ** FPD-7024 Product only. Delete if not required.4. Audible System Trouble Sounder: An audible system trouble sounder shall be an

integral part of the control unit. Provisions shall also be provided for an optional supervised remote trouble signal.

28 30 00-13

B. Power Supply and Charger:1. The entire system shall operate on 24 VDC power supply with the rated current

available of 4 Amps. The FACP shall have a battery charging circuit capable of complying with the following requirements:a. Sixty (60) hours of battery standby with five (5) minutes of alarm signaling at

the end of this sixty (60) hour period (as required per NFPA 72 remote station signaling requirements) using rechargeable batteries with automatic charger to maintain standby sealed lead-acid batteries in a fully charged condition.

* NOTE TO SPECIFIER ** Delete above or below option for battery standby power duration.b. Twenty-four (24) hours of battery standby with five (5) minutes of alarm

signaling at the end of this twenty-four (24) hour period (as required per NFPA 72 central station signaling requirements) using rechargeable batteries with automatic charger to maintain sealed lead-acid batteries in a fully charged condition.

2. The power supply shall comply with UL Standard 864 9th Edition for power limiting.3. The FACP will indicate a trouble condition if there is a loss of AC power or if the

batteries are missing or of insufficient capacity to support proper system operation in the event of AC failure. A "Battery Test" will be performed automatically every three minutes to check the integrity of the batteries. The test shall disconnect the batteries from the charging circuit and place a load on the battery to verify the battery condition.

* NOTE TO SPECIFIER ** FPD-7024 Product only. Delete if not required.4. In the event that it is necessary to provide additional power one or more of the model

D7038 Distributed Modules shall be used to accomplish this purpose.

C. Connections and Circuits:1. Connections to the light and power service shall be on a dedicated branch circuit in

accordance with the National Fire Alarm Code NFPA 72, National Electrical Code (NEC) NFPA 70, and the local authority having jurisdiction (AHJ).

2. The circuit and connections shall be mechanically protected.3. A circuit disconnecting means shall be accessible only to authorized personnel and

shall be clearly marked "FIRE ALARM CIRCUIT CONTROL".

2.6 ACCESSORY COMPONENTS

A. Control & Option Data Bus Device Support:1. The FACP shall support the following devices on the control and option data buss:

a. D7030X: Eight-point LED Annunciator (eight red).b. D7030X-S2: Eight-point LED Annunciator (two yellow, six red).c. D7030X-S8: Eight-point LED Annunciator (eight yellow).d. D7032: Eight-point LED Annunciator expander (eight red).

* NOTE TO SPECIFIER ** FPD-7024 Product only. Delete 70 series components if not required.e. -7033: LCD fire system keypad.f. -7036: LCD Annunciator.g. D7030: LED remote Annunciator.h. D7035: Octal relay module.i. D7039: Multiplex bus processor board.j. D7042/B: 8 Input Module.

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.k. FMR-1000-RCMD: Remote Command Center.l. FMR-1000-RA: Remote Annunciator.m. D7035/B: Octal relay module.n. D7048/B: Octal driver module.o. FPP-RNCA-8A-4C: Remote NAC Booster.

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

28 30 00-14

B. SLC Loop Device Support:1. The FACP shall support the operation of 127 total devices per SLC loop without

regard to device type. The following devices shall be supported:a. FAP-325: Addressable Photoelectric Smoke Detector Head.b. FAH-325: Addressable Photoelectric Heat Detector Head.c. FAI-325: Analog Ionization Smoke Detector Head.d. FAA-325-B4: Analog Detector Base (4 inches (102 mm)).e. FAA-325-B6: Analog Detector Base (6 inches (152 mm)).f. FAD-325-DH: Analog DUCT Detector.g. FMM-325A: Analog Single Action Manual Station.h. FMM-325A-D: Analog Double Action Manual Station.i. FLM-325-CZM4: Conventional Zone Module.j. FLM-325-2I4 : Dual Input Monitor.k. FLM-325-2R4: Dual Relay Module.l. FLM-325-ISO: Short Circuit Isolator.m. FLM-325-N4: Supervised Output Module.n. FLM-325-I: Contact Monitor.

2. On top of these 127 devices the FCAP shall support the operation of up to 127 base sounders per SLC loop of the following type:a. FAA-325-B6S: Analog base sounder.

3. Addressable devices shall be simple to install and not require mechanical DIP or rotary address switches. Devices shall be digital and able to be addressed electronically via a hand held programmer.

4. Addressable devices, which use a mechanical address setting method, such as a DIP-switch, or decade dial (rotary) switches shall not be acceptable.

5. Addressable detectors/sensors shall be intelligent, analog, addressable, and shall connect with two wires to the fire alarm control panel signaling Line Circuits.

6. Addressable detectors/sensors shall provide dual alarm and polling LED indicators. The indicators shall flash red under normal conditions, indicating that the detector/sensor is operational and in regular communication with the control panel. The indicators shall be placed into steady red illumination by the control panel, indicating that an alarm condition has been detected. An output connection shall also be provided in the base to connect an external remote alarm LED indicator.

7. The fire alarm control panel shall permit addressable detector/sensor sensitivity adjustment through keypad programming of the system or by assessing the build in web browser. The panel on a time-of-day basis shall automatically adjust and alternate sensitivity between Day and Night modes.

8. The addressable detectors/sensors shall automatically compensate for dust accumulation and other slow environmental changes that may affect their performance via intelligence and control from the panel per calibration and drift compensation functions. The detectors/sensors and control panel shall meet the calibrated sensitivity test requirements of NFPA Standard 72-2002, Chapter 10, section 10.4.3.2.4.

9. Addressable detectors/sensors shall include a separate twist-lock base. The bases shall permit direct interchange with the Bosch Security System FAI-325 ionization type smoke sensor, FAP-325 photoelectric smoke sensor, and the FAH-325 heat sensor. The vandal-resistant, security locking feature shall be used in those areas required by the application and implemented per the manufacturer's instructions. The locking feature shall be optional and can be implemented when required. Both 4-inches (102 mm) and 6-inches (152 mm) model electronics free bases shall be supported and shall be Bosch Security System FAA-325-B4 and FAA-325-B6 respectively.

10. Addressable detectors/sensors shall provide an integral test means whereby an internal fire test of the chamber or sensor shall be performed by the control panel automatically during each 24 hour calibration cycle. This operation shall guarantee every detector/sensor in the system is operational with each calibration cycle and any detectors/sensors that do not pass this test method shall indicate a trouble and

28 30 00-15

maintenance alert on the control panel.11. Addressable devices shall also store an internal identifying type code that the control

panel shall use to identify the type of device specifically. The panel shall identify the exact type of detector/sensor, module, etc. Addressable devices of different types or variant models shall not use the same type code.

12. Addressable detectors/sensors shall operate in an analog fashion, where the detector measures its environment variable and transmits an analog value to the control panel based on real-time measured values of the ambient conditions. The control panel, not the detector/sensor, shall make the alarm/normal decision, thereby allowing the sensitivity of each detector/sensor to be set and monitored by the control panel. The system operator shall have the ability to view the current analog value of each detector/sensor.

13. Addressable modules shall mount in a standard 4-inches (102 mm) square electrical construction box. Mini-Modules shall fit inside a standard 4-inch square or single-gang box.

14. Addressable devices shall be capable of accepting up to 14-gauge wire sizes.15. Addressable devices shall be UL listed and compatible with the Bosch Security

Systems America analog/addressable control panel employing DCP Protocol, such as the FPA-1000-UL series.

16. Addressable device addresses shall be electrically programmable and stored in EEPROM.

17. Addressable device shall use Digital Communication Protocol (DCP), which is noise immune and utilizes alarm interrupts for fast response to fires.

18. Addressable devices shall be programmed / addressed by using the TCH-B100 Hand-held device programmer.

19. Addressable detectors, sensors, and modules shall operate on SLC addresses 1 - 127. Addressable sounder bases shall operate on SLC addresses 128-254. The SLC shall support 254 addresses total.

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

C. Analog Photoelectric Smoke Detector - (FAP-325):1. Analog photo smoke sensors shall have a UL listed operating range from .88%/ft. to

3.57%/ft. obscuration graduated across an air velocity range up to 4000 fpm. Analog photo smoke sensors that do not support this operating range or velocity capability shall not be acceptable.

2. Analog photo smoke sensors shall have a low profile design, only 1.97 inches (50.04 mm) high, including base.

3. Optical fire test feature shall be built-in.4. The plastics shall be a PC/ABS blend and shall be resistant to yellowing from

prolonged UV exposure. The color shall be bone.5. The smoke chamber shall be removable to allow ease of maintenance and cleaning.

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

D. Analog Ionization Smoke Detector - (FAI-325):1. Analog ion smoke sensors shall have a UL listed operating range from .55%/ft. to

1.15%/ft. obscuration.2. Analog ion smoke sensors shall have a low profile design, only 2.22 inches (56.34

mm) high, including base.3. Fire test feature shall be built-in.4. The plastics shall be a PC/ABS blend and shall be resistant to yellowing from

prolonged UV exposure. The color shall be bone.* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

E. Analog Thermal/Heat Detector - (FAH-325):

28 30 00-16

1. Analog heat sensors shall have a UL listed operating range from 135 to 150 degree Fahrenheit when used as a fire detection device. The analog heat sensor shall support an increased operating range from 32 to 158 degree Fahrenheit when used as a supervisory device.

2. Analog heat sensors shall have a low profile design, only 2.0 inches (51 mm) high, including base.

3. Fire test feature shall be built-in.4. The plastics shall be a PC/ABS blend and shall be resistant to yellowing from

prolonged UV exposure. The color shall be bone.* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

F. Analog Photoelectric Duct Smoke Detector - (FAD-325):1. Analog photo duct smoke sensors shall have a UL listed operating range from .88%/ft.

to 2.75%/ft. obscuration across an air velocity range from 300 to 4000 fpm. Analog photo duct smoke sensors that do not support this operating range or velocity capability shall not be acceptable.

2. Optical Fire test feature shall be built-in.3. The plastics shall be a PC/ABS blend and shall be resistant to yellowing from

prolonged UV exposure. The color shall be bone.4. Analog photo duct smoke sensors shall include two built-in programmable Form C

relays, rated at 10 Amps @ 250VAC. An alternate non-relay two-wire model shall also be available that does not require 24VDC input power. The relay model operates on four-wires and requires 24VDC input power.

5. The duct detector housings shall be of metal construction and complete mechanical installation may be performed without removal of detector cover. The duct detector shall not require additional filters or screens which must be maintained. The housing shall contain a base which will accept an analog photoelectric duct sensor head. The housing cover shall be clear for easy inspection. Terminal connections shall be of the screw type and be a minimum of a #6 size screw. For installations requiring relay function (FAD-325-R), terminals shall be provided for remote pilot, remote alarm indication, strobe/ horn and remote key switch. A manual reset switch shall be located on front of the device. For installations not requiring relay function (FAD-325), visual indication of alarm and power must be provided.

6. The smoke chamber and head shall be removable to allow ease of maintenance and cleaning.

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

G. Addressable Sounder Base - (FAA-325-B6S):1. The addressable sounder base shall be fully programmable and operate on an

independent SLC address. The addressable sounder base shall not require extra control wiring, DIP switches, decade dial (rotary) switches, etc. to link multiple, independent sounder bases, or groups of sounder bases together. The addressable sounder base shall accommodate all analog sensors, such as photo, ion, or heat.

2. The addressable sounder base shall be UL listed as an indication device that provides 85 decibels of sound level output at 10 feet (3 m) and shall have programmable audible patterns for temporal, continuous, or march time.

3. The addressable sounder base shall be programmable to operate from any global event category, zone, point, or Cause & Effect logic. The flexible programming and operation shall allow multiple trigger sources for fire alarm, supervisory, and other logic to support hotel and high-rise apartment style applications, all from intelligent addressable output control from the panel.

4. The sounder base shall include support for a remote alarm LED indicator as an option.

5. The addressable sounder base shall be self addressing based on the host sensor address it is attached to, not requiring any special device address programming. The addressable sounder base shall automatically add 127 plus the detector address to

28 30 00-17

obtain its independent address. The addressable sounder base shall operate in the higher SLC address range from 128 to 254. Systems which cannot automatically address the sounder base, sounder bases that are not fully programmable, or SLC that do not support 254 addresses shall not be accepted.

6. The plastics shall be a PC/ABS blend and shall be resistant to yellowing from prolonged UV exposure. The color shall be bone.

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

H. Addressable Manual Pull-Station - (FMM-325A):1. Manual pull stations shall be Hochiki addressable AMS-series single or dual action

models, FMM-325A or FMM-325A-D. Models shall be made of 14 AWG CRS and painted with Red enamel. The words Fire Alarm shall be in a contrasting color and be embossed text 1/2" tall. The electronics shall be fully integrated into the manual pull station requiring only connection to the SLC loop of the control panel. Programming of the manual pull station address must be possible with the manual pull station fully installed.

2. Manual pull stations shall be Underwriters Laboratories Inc. Listed, CSFM Approved, and be installed within the limits defined in the American Disabilities Act.

3. The Addressable Manual Pull-Station shall have the following features and options:a. Addressable integrated designb. All metal constructionc. Single and dual action models availabled. Extremely easy to operatee. Bi-colored status LED indicates Standby and Alarm conditionsf. Address is programmable in EEPROMg. Address can be programmed when installedh. Key lock or hex key lock models availablei. Terminals accept up to 14AWG wirej. Surface mount back box availablek. ADA compliant

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

I. Addressable Conventional Zone Module - (FLM-325-CZM4):1. Addressable Conventional Zone Module shall provide one supervised IDC initiating

zone for conventional alarm initiating devices and will connect to the SLC.2. The Conventional Zone Module shall be suitable for Style D (Class A) or Style B

(Class B) operation.3. The Conventional Zone Module shall provide an address point for a conventional

initiating zone (IDC) of up to 25 conventional smoke detectors depending on the model and brand. Conventional devices with a N.O. dry contact output may also be used and do not have a restriction of 25 devices. UL 2-wire compatibility is required on all conventional zone powered devices used on the IDC of the CZM module. Devices with N.O. dry contact output shall not require UL 2-wire compatibility.

4. The Conventional Zone Module shall have a bi-colored LED indicator that flashes green when polled and latches on red (controlled by panel) when activated for alarms.

5. The Conventional Zone Module shall require a 24VDC auxiliary power source to provide IDC power for the conventional zone of detectors.

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

J. Addressable Dual Input Monitor Module - (FLM-325-2I4):1. The Dual Input Monitor Module shall provide two independently monitored inputs to

connect N.O. dry contact type initiating devices to the SLC. Each input shall be capable of independent operation, such as one input for water-flow (Fire), and the other for valve tamper (Supervisory). The two inputs shall not interfere with each other or require common function and shall be capable of programmable operation, such as

28 30 00-18

water-flow (Fire), valve tamper (Supervisory), manual pull-station (Fire), and other general event categories.

2. The Dual Input Monitor Module shall only occupy one SLC address. The two inputs shall be sub-addresses that operate under the single SLC address of the module. An SLC using FLM-325-2I4 shall be capable of (254) inputs when all (127) SLC addresses are used.

3. The DIMM shall operate on Style 4, 6, or 7 SLC. The inputs shall be capable of being programmed for N.O. or N.C contacts, with an option for non-supervised N.C. (no EOL) operation.

4. The Dual Input Monitor Module shall have a bi-colored LED indicator for displaying device polling and alarm status.

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

K. Addressable Contact Monitor Module - (FLM-325-I):1. Addressable Contact Monitor Module shall provide a monitored input to connect N.O.

dry contact type initiating devices to the SLC. The input shall be capable of programmable operation, such as water-flow (Fire), valve tamper (Supervisory), manual pull-station (Fire), and other general event categories.

2. The Addressable Contact Monitor Module shall operate on Style 4, 6, or 7 SLC. The input shall be capable of being programmed for a N.O. or N.C contact, with an option for non-supervised N.C. (no EOL) operation.

3. The Addressable Contact Monitor Module shall have a bi-colored LED indicator for displaying device polling and alarm status.

4. The Addressable Contact Monitor Module should be either come in a 4 inches (102 mm) back box (FLM-325-I4), or as mini module with terminal screws (FLM-325-IS) or as mini module with pigtail (FLM-325-IW).

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

L. Addressable Supervised Output Module - (FLM-325-N4):1. The Supervised Output Module shall provide supervision and controlled activation of

polarized 24VDC audio/visual notification appliances and other 24VDC powered devices.

2. The Supervised Output Module shall provide a voltage output rated at 24VDC @ 2.0 Amps. The output shall be wired for Style Y (Class B) operation. The output shall provide reverse polarity operation for supervision of the device circuit. Outputs patterns shall be Temporal, Continuous, and March. There shall be a silence-able option.

3. The Supervised Output Module shall have capability of up to 16 different control states and modulation patterns for multi-state programming. The operating parameters for the FLM-325-N4 shall be maintained in the module after device initialization and will not require individual control commands from the control panel during fire conditions to operate. The control panel shall instead broadcast system-wide commands on the SLC and the FLM-325-N4 or group of FLM-325-N4 will respond based on individual programming allowing simultaneous group device activations from a single control panel command. Systems that do not meet this requirement shall not be acceptable.

4. The Supervised Output Module shall be programmable to operate from any global event category, zone, point, or Cause & Effect logic. The flexible programming and operation shall allow multiple trigger source options for fire alarm, supervisory, and other logic to support hotel and high-rise apartment style applications, all from intelligent addressable output control from the panel.

5. The Supervised Output Module shall have a bi-colored LED indicator for displaying device polling and control status.

6. Systems that do not meet the FLM-325-N4 performance criteria shall not be acceptable.

28 30 00-19

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

M. Addressable Dual Relay Module - (FLM-325-2R4):1. The FLM-325-2R4 shall provide two independently controlled relay outputs to connect

devices requiring control from the fire system to the SLC. Each output shall be capable of independent operation. The two outputs shall not interfere with each other or require common function and shall be capable of programmable operation such as general event categories, zone control, point control, silence-able option.

2. The Dual Relay Module shall only occupy one SLC address. The two outputs shall be sub-addresses that operate under the single SLC address of the module. An SLC using FLM-325-2R4 shall be capable of 254 outputs when all 127 SLC addresses are used.

3. The Dual Relay Module shall operate on Style 4, 6, or 7 SLC. The outputs shall be two Form C relay contacts rated at .5 Amps @ 125VAC or 1 Amp 30VDC. The FLM-325-2R4 shall not require a 24VDC auxiliary power supply source.

4. The Dual Relay Module shall have 16 different control states for multi-state programming. The operating parameters for the FLM-325-2R4 shall be maintained in the module after device initialization and will not require individual control commands from the control panel during fire conditions to operate. The control panel shall instead broadcast system-wide commands on the SLC and the FLM-325-2R4 or group of FLM-325-2R4 will respond based on individual programming allowing simultaneous group device activations from a single control panel command. The FLM-325-2R4 shall also have the ability to receive individual commands (non-group commands) from the control panel along with the group command broadcasts. Systems that do not meet this requirement shall not be acceptable.

5. The Dual Relay Module shall be programmable to operate from any global event category, zone, point, or Cause & Effect logic. The flexible programming and operation shall allow multiple trigger source options for fire alarm, supervisory, and other logic to support elevator recall, fan/damper control, door holder/lock control, and other building control functions, all from intelligent addressable output control from the panel.

6. The Dual Relay Module shall have a bi-colored LED indicator for displaying device polling and control status.

7. Systems that do not meet the Dual Relay Module performance criteria shall not be acceptable.

* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

N. Short Circuit Isolator Module - (FLM-325-ISO):1. The Short Circuit Isolator Module shall be provide automatic isolation of wire-to-wire

short circuits on a Class A (Style 6 or 7) SLC or Class B (Style 4) SLC trunk and/or branch circuits. The isolator module shall prevent addressable devices from being rendered inoperative by a short circuit fault on the SLC when used in a NFPA 72-2002 Style 7 configuration. When used in Style 4 or 6 hybrid configurations (i.e. not fully Style 7 compliant), the isolator module shall limit the number of addressable devices from being rendered inoperative by a short circuit fault on the SLC.

2. If a wire-to-wire short occurs, the isolator module shall automatically open-circuit (disconnect) the segment of the SLC that is shorted. When the short circuit condition is corrected, the Short Circuit Isolator Module shall automatically reconnect the isolated segment.

3. The Short Circuit Isolator Module shall not require address-setting or an SLC address. The SCI operation shall be completely automatic. It shall not be necessary to replace or reset a Short Circuit Isolator Module after its normal operation. The Short Circuit Isolator Module shall have the ability to be placed anywhere on the SLC and shall not have a limit of how many can placed on a given SLC.

4. The Short Circuit Isolator Module shall provide a single yellow LED that shall illuminate steadily to indicate that a short circuit condition has been detected and

28 30 00-20

isolated.* NOTE TO SPECIFIER ** FPA-1000 Product only. Delete if not required.

O. The FACP shall provide sync signal for the following appliances:a. Wheelock.b. System Sensor.

* NOTE TO SPECIFIER ** FPD-7024 Product only. Delete if not required.

P. Multiplex Buss Loop Device Support:1. The FACP shall support the operation of 128 total devices per multiplex buss loop

without regard to device type. The following devices shall be supported:a. D7050: Addressable Photoelectric Smoke Detector Head.b. D7050TH: Addressable Photoelectric Smoke and Heat Detector Head.c. D7050 - B6: Detector Base.d. D7042: Multiplex eight - input remote module.e. D7042B: Multiplex eight - input remote module in box.f. D7044: Multiplex single - input module.g. D7044M: Mini multiplex single - input module.h. D7048: Multiplex octal driver.i. D7048B: Multiplex octal driver in box.j. D7052: Multiplex dual - input module.k. D7053: Multiplex input - output module.l. - 7045: Single - action manual station.m. - 7045 - D: Double - action manual station.

2. The FACP shall support these other devices via addressable input, conventional inputs, Notification circuits, or D7038 NAC expanders:a. Single Action Manual Pull Station - Key Reset.b. Dual action Manual Pull Station - Key Reset.c. Combination Horn Strobe or Strobe Only Devices.d. Up to 2 D7038 NAC supplies can be synced on the options bus.

** NOTE TO SPECIFIER ** Improvement to FPD-7024.e. NAC sync signal for Wheelock, Systems Sensor NAC appliance.

2.7 NOTIFICATION DEVICES

A. The visible and audible/visible signal shall be Bosch approved Multi-candela signal devices with field selectable settings of 15, 30, 75, 110cd and be listed by Underwriters Laboratories Inc.

B. The notification appliance (combination audible/visible units only) shall produce a peak sound output of 90dba or greater as measured in an anechoic chamber. The signaling appliance shall also have the capability to silence the audible signal while leaving the visible signal energized with the use of a single pair of wires. Additionally, the user shall be able to select either continuous or temporal tone output with the temporal signal having the ability to be synchronized.

C. The visible signaling appliance shall maintain a minimum flash rate of 1 Hz or greater regardless of power input voltage. The appliance shall also be capable of meeting the candela requirements of the blueprints presented by the Engineer and ADA.

D. The appliance shall be polarized to allow for electrical supervision of the system wiring. The unit shall be provided with terminals with barriers for input/output wiring and be able to mount to a single gang or double gang box or double workbox with the use of an adapter plate. The unit shall have an input voltage range of 16 - 33 Volts with either direct current or full wave rectified power.

28 30 00-21

2.8 SMOKE DETECTORS** NOTE TO SPECIFIER ** The FCP-500 Series smoke detectors have the lowest mounting profile in the industry so it nearly disappears when installed in the ceiling. In addition, the FCP-500 comes in standard white and a clear plastic model with 16 color-matching rings so it virtually disappears while it works. Where appearance and interior design are important considerations, this smoke detector - a Bosch exclusive - is the hands down favorite. Delete if not required.

A. Smoke detectors shall be Bosch model FCP 500 series ceiling mounted addressable photoelectric smoke detectors.1. Conventional Flush-mount Detectors shall be UL Listed, open area photoelectric

smoke detectors.* NOTE TO SPECIFIER ** Delete model not required.

2. Model FCP-500: Conventional 4-wire flush mount smoke detector; white.3. Model FCP-500-C: Conventional 4-wire flush mount smoke detector with CO element;

white.4. Model FCP-500-P: Conventional 4-wire flush mount smoke detector; transparent with

color ring kit.5. Model FCP-500-C-P: Conventional 4-wire flush mount smoke detector with CO

element; transparent with color ring kit.** NOTE TO SPECIFIER ** Intelligent automatic fire detector for smoke, optical component for flush fitting in steel-reinforced concrete ceilings or suspended ceilings with connection to a conventional line. Delete if not required.Planning:Monitoring range: max. 1290 sf (120 sq. m).Maximum installation height: 52.5 feet (16 m).Minimum installation height: 8 feet 10 inches (2.70 m).For flush fitting installation with ceiling mount back box:1) Thickness of false ceiling: up to 1-1/4 inches (32 mm).2) Required drill hole: 5 inches (130 mm) diameter.3) Installation Height: 4-3/8 inches (110 mm).Minimum distance from lights:1 feet 8 inches ( 0.5 m).

B. Smoke detectors shall be Bosch FCP-O 500 series ceiling mounted photoelectric smoke detectors. Complete with ceiling mount back box, base and panel.

* NOTE TO SPECIFIER ** Delete model not required.1. Model FCP-O 500:

a. Detector Housing Color: Signal white, RAL 9003.b. Detector Front Plate Color: Signal white.

2. Model FCP-O 500-P:a. Detector Housing Color: Signal white, RAL 9003.b. Detector Front Plate Color: Transparent/silver gray.

3. Detection Principle: Two independent scattering light sensors with sensing volumes directly beneath the detector. Contamination detection by means of a third optical system.

4. Detection Characteristics:a. Detection Principle: Scattered light measurement.b. Response Sensitivity: < 0.36 dB/m.c. Drift compensation.d. Protection against insects by means of a dual evaluation system.e. Protection against external light.f. Response sensitivity.g. Chamber integrity monitoring.h. Optical fault display.i. Fault relay for signalling faults.j. Can be removed from the base with an installation tool up to a ceiling height of

28 30 00-22

26 feet (8 m) without the need for access equipment.k. Activation of servicing mode on the detector itself by means of a reed switch.l. Windproof installation in suspended ceilings possible.m. Alarm indication identifiable from 360 degree.n. Connection for at least one external detector alarm display.o. Does not protrude more than 3/8 inch (10 mm) from the ceiling.p. Blends perfectly into white ceilings.

5. Electrical Data:a. Operating Voltage: 8.5 VDC to 33 VDC.b. Current Consumption: 3.5 mA.c. Alarm Output: Per relay, alarm resistance selectable: 680 O or 0 O.d. Indicator output relay switches 0 V via 1.5 kO, max. 20 mA.

6. Mechanical Data:a. Individual Display: Two-color LED red (alarm), green (test mode).b. Dimensions:

1) Detector: 4-7/16 inch diameter by 2-5/32 inch (113 mm diameter by 55 mm).

2) Detector with panel: 6 inches diameter by 2-3/8 inches (150 by 55 mm).3) Detector with panel and base: 6 inches diameter by 2-3/4 inches (150 by

70 mm).c. Housing Material: Polycarbonate.

7. Environmental Conditions:a. Protection Category per EN 60529: IP 53.b. Operating Temperature: -4 degree F to 149 degree F (-20 degree C to +65

degree C).c. Maximum Relative Humidity: 95% (without condensation)d. Maximum Air Speed: 4000 fpm (20 m/s).

** NOTE TO SPECIFIER ** Intelligent automatic fire detector for smoke and carbon monoxide, optical component for flush fitting in steel-reinforced concrete ceilings or suspended ceilings with connection to a conventional line. Delete if not required.Planning:Monitoring range: max. 1290 sf (120 sq. m).Maximum installation height: 52.5 feet (16 m).Minimum installation height: 8 feet 10 inches (2.70 m).For flush fitting installation with ceiling mount back box:1) Thickness of false ceiling: up to 1-1/4 inches (32 mm).2) Required drill hole: 5 inches (130 mm) diameter.3) Installation Height: 4-3/8 inches (110 mm).Minimum distance from lights:1 feet 8 inches ( 0.5 m).

C. Smoke detectors shall be Bosch FCP-OC 500 series ceiling mounted photoelectric smoke detector and chemical sensor system (CO). Complete with ceiling mount back box, base and panel.

* NOTE TO SPECIFIER ** Delete model not required.1. Model FCP-OC 500:

a. Detector Housing Color: Signal white, RAL 9003.b. Detector Front Plate Color: Signal white.

2. Model FCP-OC 500-P:a. Detector Housing Color: Signal white, RAL 9003.b. Detector Front Plate Color: Transparent/silver gray.

3. Detection Principle: Two independent scattering light sensors with sensing volumes directly beneath the detector in combination with independent chemical sensor system (CO) to detect combustion gases.

4. Detection Characteristics:a. Detection Principle: Combination of scattered light measurement and CO

28 30 00-23

measurement.b. Response Sensitivity: < 0.36 dB/m. Gas sensor in ppm rangec. Drift compensation.d. Protection against insects by means of a dual evaluation system.e. Protection against external light.f. Response sensitivity.g. Chamber integrity monitoring.h. Optical fault display.i. Fault relay for signalling faults.j. Can be removed from the base with an installation tool up to a ceiling height of

26 feet (8 m) without the need for access equipment.k. Activation of servicing mode on the detector itself by means of a reed switch.l. Windproof installation in suspended ceilings possible.m. Alarm indication identifiable from 360 degree.n. Connection for at least one external detector alarm display.o. Does not protrude more than 3/8 inch (10 mm) from the ceiling.p. Blends perfectly into white ceilings.

5. Electrical Data:a. Operating Voltage: 8.5 VDC to 33 VDC.b. Current Consumption: 3.5 mA.c. Alarm Output: Per relay, alarm resistance selectable: 680 O or 0 O.d. Indicator output relay switches 0 V via 1.5 kO, max. 20 mA.

6. Mechanical Data:a. Individual Display: Two-color LED red (alarm), green (test mode).b. Dimensions:

1) Detector: 4-7/16 inch diameter by 2-5/32 inch (113 mm diameter by 55 mm).

2) Detector with panel: 6 inches diameter by 2-3/8 inches (150 by 55 mm).3) Detector with panel and base: 6 inches diameter by 2-3/4 inches (150 by

70 mm).c. Housing Material: Polycarbonate.

7. Environmental Conditions:a. Protection Category per EN 60529: IP 33.b. Operating Temperature: 14 degree F to 122 degree F (-10 degree C to +50

degree C).c. Maximum Relative Humidity: 95% (without condensation)d. Maximum Air Speed: 4000 fpm (20 m/s).

* NOTE TO SPECIFIER ** Delete if not required.

D. Smoke detectors shall be Bosch model D7050 / D7050TH series ceiling mounted addressable photoelectric smoke detectors. The detector shall be UL listed compatible with the Bosch FPD-7024 fire alarm control panel.1. The smoke detector shall have a flashing status LED for visual supervision. When the

detector is actuated, the flashing LED will latch on solid. The LED shall flash at a 1/sec rate if the chamber is out of calibration range. The detector may be reset by actuating the control panel's reset switch.

2. The vandal security-locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable when required.

3. All detectors shall have the "Chamber Check" feature with the addressable detectors sending a contaminated chamber signal to the FACP.

* NOTE TO SPECIFIER ** Delete if not required.

E. Conventional smoke detectors shall be the Bosch D256A/D257A, D263/D263TH, D263S/D263THS, D285/D285TH or F220 two wire smoke detectors with appropriate bases.1. The smoke detector shall have a flashing status LED for visual supervision. When the

detector is actuated, the flashing LED will latch on solid. The LED shall flash at a

28 30 00-24

1/sec rate if the chamber is out of calibration range. The detector may be reset by actuating the control panel's reset switch.

2. The vandal security-locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be field selectable when required.

3. All detectors shall have the "Chamber Check" feature with the addressable detectors sending a contaminated chamber signal to the FACP.

PART 3 EXECUTION

3.1 WIRING

A. Installer's Responsibilities:1. The installer shall coordinate the installation of the fire alarm equipment.2. All conductors and wiring shall be installed according to the manufacturer's

recommendations.3. It shall be the installer's responsibility to coordinate with the supplier, regarding the

correct wiring procedures before installing any conduits or conductors.

B. Installation of System Components:1. System components shall be installed in accordance with the latest revisions of the

appropriate NFPA pamphlets, the requirements contained herein, National Electrical Code, local and state regulations, the requirements of the fire department and other applicable authorities having jurisdiction (AHJ).

2. All wire used on the fire alarm system shall be UL Listed as fire alarm protection signaling circuit cable per National Electrical Code, Article 760. The use of FPL, FPLR or FPLP wiring for power limited applications.

3.2 DEVICE INSTALLATION

A. Furnish and install, all devices where shown on the drawings, the following applicable codes, standards and manufacturer recommendation to ensure proper operations and functions as intended.

3.3 seq sub FINAL TEST

A. Before the installation shall be considered completed and acceptable by the awarding authority, a test of the system shall be performed as follows:1. The contractor's job foreman, a representative of the owner, and the fire department

shall operate every building fire alarm device to ensure proper operation and correct annunciation at the control panel.

2. At least one half of all tests shall be performed on battery standby power.3. Where application of heat would destroy any detector, it may be manually activated.

B. The communication loops and the indicating appliance circuits shall be opened in at least two locations per circuit to check for the presence of correct supervision circuitry.

C. When the testing has been completed to the satisfaction of both the contractor's job foreman and owner, a notarized letter cosigned by each attesting to the satisfactory completion of said testing shall be forwarded to the owner and the fire department.

D. The contractor shall leave the fire alarm system in proper working order, and, without additional expense to the owner, shall replace any defective materials or equipment provided by him under this contract within one year (365 days) from the date of final acceptance by the awarding authority.

E. Prior to final test the fire department shall be notified in accordance with local requirements.

3.4 AS BUILT DRAWINGS, TESTING, AND MAINTENANCE INSTRUCTIONS

28 30 00-25

A. As Built Drawings:1. A complete set of reproducible "as-built" drawings showing installed wiring, color

coding, and wire tag notations for exact locations of all installed equipment, specific interconnections between all equipment, and internal wiring of the equipment shall be delivered to the owner upon completion of system.

B. Operating and Instruction Manuals:1. Operating and instruction manuals shall be submitted prior to testing of the system.

Three complete sets of operating and instruction manuals shall be delivered to the owner upon completion. User operating instructions shall be provided prominently displayed on a separate sheet located next to the control unit in accordance with UL Standard 864.

END OF SECTION