Steam boilers
Heat pumps
Technical manual
Technical manualHeat pumps
The Viessmann GroupD-35107 Allendorf (Eder)Telephone +49 (0)6452 70-0Fax +49 (0)6452 70-2780www.viessmann.com
9440 134 GB 03/2012Subject to technical modifications
Technical manualHeat pumps
Table of contents
6/7
11 Foreword
12 Introduction
12 How to use this manual
14 A Principles of heat pump technology
16 A.1 History of heat pump development
18 A.2 Physical principles
19 A.2.1 Condensing and evaporating19 A.2.2 Refrigerant circuit21 A.2.3 Coefficient of performance (COP)22 A.2.4 Seasonal performance factor (SPF)
24 A.3 Main components
25 A.3.1 Compressor28 A.3.2 Expansion valve29 A.3.3 Heat exchanger31 A.3.4 Refrigerant
32 A.4 Primary source potentials
33 A.4.1 Ground as heat source37 A.4.2 Water as heat source37 A.4.3 Outdoor air as heat source38 A.4.4 Availability and efficiency – assessment of the primary sources38 A.4.5 Waste heat as heat source39 A.4.6 Absorber with solar backup40 A.4.7 Phase change as "storage" on the primary side
42 A.5 Alternative types of heat pump
43 A.5.1 Compression heat pumps with internal combustion engine43 A.5.2 Absorption heat pumps45 A.5.3 Adsorption heat pumps
Table of contents
46 B General conditions
48 B.1 "Electrical power" as the driving energy
49 B.1.1 Power mix in Germany51 B.1.2 Security of supply53 B.1.3 Smart metering54 B.1.4 Heat pumps and photovoltaics55 B.1.5 Competition for electric power
56 B.2 Statutory framework conditions
57 B.2.1 Heat pumps in the EnEV59 B.2.2 Heat pumps in the Renewable Energies Heat Act [EEWärmeG]59 B.2.3 European framework directives
60 B.3 Economic considerations
62 C Engineering and sizing the primary source
64 C.1 Brine/water heat pumps
65 C.1.1 Sizing the heat source69 C.1.2 Heat transfer medium70 C.1.3 Flow rate and pressure drop in the brine circuit
72 C.2 Water/water heat pumps
73 C.2.1 Groundwater75 C.2.2 Coolant
76 C.3 Air/water heat pumps
77 C.3.1 Air/water heat pumps with unregulated compressor77 C.3.2 Sizing/engineering79 C.3.3 Acoustic engineering82 C.3.4 Air routing for internally sited air/water heat pumps
84 D System engineering
86 D.1 Operating modes
87 D.1.1 Mono mode operation87 D.1.2 Dual mode operation89 D.1.3 Cascade systems90 D.1.4 Combination with renewables
92 D.2 Secondary circuit
93 D.2.1 DHW heating106 D.2.2 Heating operation111 D.2.3 Cooling
116 D.3 Output calculation and engineering aids
117 D.3.1 Determining the heat pump output118 D.3.2 Sizing aids for heat pump systems
Table of contents
8/9
122 Appendix
124 The path to an efficient heat pump system
130 Information on inspection and optimisation
132 Keyword index
136 The company
136 Individual solutions with efficient systems
138 Futureproof heating technology for all requirements
140 Viessmann – climate of innovation
142 Production
10/11
Foreword
Climate protection and the provision of futureproof affordable energy are two of the most serious challenges of our time. In order to prevent the atmosphere from heating up further, emissions of greenhouse gases, among them particularly CO2, must be minimised. This can only be achieved through a significant reduction in the consumption of fossil fuels. This reduction is unavoidable – quite apart from efforts to reduce the effects of climate change – because these resources are finite. Although supplies will still be available for the foreseeable future, prices will continue to rise. Consequently, improving energy efficiency and extending the scope of renewables are key areas of interest.
Politicians have determined ambitious goals for both climate protection and saving energy. The heating sector, as the largest consumer, can make a substantial contribution to these aims. It is, therefore, essential that existing outdated and inefficient heating equipment is replaced as soon as possible. The technology required for this is available right now.
The comprehensive range from Viessmann not only offers highly efficient condensing technology for oil and gas, but also biomass boilers, solar thermal systems and heat pumps for any application area.
Over the past few years, heat pumps have established their place in the heating technology sector. Their share of the new build market is now equal to that of gas condensing systems. However, in modernisation projects, too, heat pumps are gaining in importance. Correctly sized and installed, they can provide heat economically in almost any building and for almost any requirement, whilst treating resources as carefully as possible.
Viessmann expects that in the years to come, heat pumps will play an even greater role in our industry. Firstly, product development continues apace. Large heat pumps can cover additional types of buildings and commercial applications. In the lower output ranges, there is a clear trend towards more compact solutions that make engineering and implementation significantly easier. Our trade partners can be sure that everything fits together as it should. Secondly, an increasing number of heating contractors feel more confident with this technology that is still rather unfamiliar to many. I'm glad that, with this technical manual, we can support our trade partners to propel them to even greater success.
Dr Martin Viessmann
Introduction
12/13
How to use this manual
Compared with conventional heat generators, heat pumps are complex machines that require detailed explanation in order to be properly understood, not only by end users, but also by heating contractors and design engineers alike. The basic functions of a boiler operating with oil, gas or biomass, are fairly comprehensible. With heat pumps, however, many fail to overcome the paradox that a "cold" primary source – such as the ground, groundwater or ambient air – can provide heat that is useful for heating the interior of a building. This manual, therefore, dedicates much of its attention to the explanation of the working principles of this fascinating technology.
The following illustrations and descriptions aim to raise the level of understanding of the workings of the most important heat pump system components. Consequently, the diagrams illustrate working principles,
and should not be seen as complete installation instructions. These are found in the product documentation, the appliance-specific technical guides and the Viessmann scheme browser.Information on practical implementation is only represented in this manual if there are specific considerations that must be taken into account when installing heat pump systems.
All other electronic engineering aids mentioned in the following chapters, such as the engineering programs, for example, are available to Viessmann trade partners from their sales engineer contacts; alternatively, they can be downloaded from the internet.
Introduction
This manual provides important information concerning the engineering, layout and operation of heat pump systems. It is intended to be a work of reference as much as a training manual and consultation guide.
14/15
Heat pumps are able to raise this energy to a useful temperature level.
This chapter explains the principles behind this technology and also describes the essential components of a heat pump.
Generally, we perceive warmth as a feeling rather than something quantifiable. We sense that a sunny summer's day, or a cosily heated house in winter is warm and a winter's day or an unheated house is cold.
Scientifically speaking, however, down to absolute zero (0 K = -273.15 °C) matter still contains heating energy.
16 A.1 History of heat pump development
18 A.2 Physical principles
19 A.2.1 Condensing and evaporating19 A.2.2 Refrigerant circuit21 A.2.3 Coefficient of performance (COP)22 A.2.4 Seasonal performance factor (SPF)
24 A.3 Main components
25 A.3.1 Compressor28 A.3.2 Expansion valve29 A.3.3 Heat exchanger31 A.3.4 Refrigerant
32 A.4 Primary source potentials
33 A.4.1 Ground as heat source37 A.4.2 Water as heat source37 A.4.3 Outdoor air as heat source38 A.4.4 Availability and efficiency – assessment of the primary sources38 A.4.5 Waste heat as heat source39 A.4.6 Absorber with solar backup40 A.4.7 Phase change as "storage" on the primary side
42 A.5 Alternative types of heat pump
43 A.5.1 Compression heat pumps with internal combustion engine43 A.5.2 Absorption heat pumps45 A.5.3 Adsorption heat pumps
A Principles of heat pump technology
Heat pumps can exploit the latent heat in the environment, bringing it up to useful temperatures. Their potential is almost limitless.
For thousands of years, heat was used mainly to heat interiors, to prepare food and to smelt metals.
The invention of the steam engine in the early 18th century brought a further use that revolutionised the world – it converted heat into a mechanical force. To this day, our productivity, mobility and comfort rely on the exploitation of this principle.
History of heat pump development
The history of the heat pump goes back much further than is commonly thought. The advanced equipment we use today has its origins in the first refrigeration machines developed almost two centuries ago.
A.1 History of heat pump development
Fig. A.1–1 Newcomen steam engine
Steam engines were known for decades, however, before a proper scientific understanding of the correlation between heat and power was attained.
Viessmann heat pump L-08
from 1981
16/17
The findings of Nicolas Léonard Sadi Carnot, generally acknowledged as the "Father of thermodynamics", were of fundamental importance. He investigated cause and effect in steam engines and discovered that all processes involved the conversion from heat into power were generally reversible.
Given the right heat transfer medium, and by applying energy, not only can heat be added to a medium, it can also be extracted from the same – independent of the ambient temperature.
The American, Jacob Perkins, was the first to succeed in implementing this principle. He applied for a patent for one of the earliest compression refrigeration machines in 1835. Until that time, technical temperature reductions were only possible through negative pressure – a discovery that went back to the middle of the 18th century.
All principle components used in modern refrigeration machines and heat pumps can be found in the machine designed by Perkins: a compressor, heat-absorbing and heat-transferring components and a pressure reducing facility. It used ether as its heat transfer medium, which enabled it to achieve temperatures below freezing point. John Gorrie, who received the patent for his ice machine 1851, and James Harrison, who developed the first commercially viable applications (for cooling foodstuffs) brought the idea along further still. The discovery of ammonia as a heat transfer medium by Ferdinand Carre enabled highly explosive ether to be replaced in refrigeration machines in 1859, making their operation far more safe. During the final decades of the 19th century, refrigeration technology established itself in industry, whilst the first decades of the 20th century saw the first refrigerators designed for use in the home.
William Thomson Kelvin provided proof in 1852 that you can also heat with a refrigeration machine and that, by utilising heating energy from the ambience, overall less energy needs to be employed than systems combusting wood or coal. However, it took around 100 more years before the heat pump was first used in building technology.
Fig. A.1–2 Nicolas Léonard Sadi Carnot
Fig. A.1–3 Linde refrigeration machine from 1877
Following the oil crisis of the 1970s, heat pumps had their first boom in Germany. When oil prices fell again during the 1980s, demand for heat pumps also fell rapidly. Advanced heat pumps, as we know them today, have only been established in the domestic technology sector for about ten years.
Until now, electricity has remained the main driving force for the compressor; in the higher output ranges combustion engines have also been used for the past 30 years, the heat of the exhaust gases also being brought into the heating supply system.
A.2 Physical principles
Physical principles
Heating technology in applied situations does not generally have to concern itself with the physical principles of heat generators.
A vessel filled with boiling water, for example, will cool down under normal ambient temperatures until it has reached the same temperature as the ambient air. Heat pumps cannot change this law of physics. Instead, they use a different effect, i.e. energy that is brought into a substance does not only lead to an increase in temperature, but also to a change in its aggregated state.
For example, if additional energy is supplied to the vessel containing boiling water, then it will evaporate without increasing its temperature. The amount of energy involved in this change of state is the "secret" with which the heat pump yields energy at a useful temperature level from a "cold" heat source.
In most cases it is sufficient to observe the technical rules in order to ensure reliable engineering, installation and commissioning. However, it is useful to take a look at the physical correlations, in order to better understand the conditions under which a heat generator, particularly a heat pump, can be best used.
Heat is one form of the inner energy of matter, or in thermodynamic terms, of a system. A heat flux is created where there is the possibility of this energy transferring to another substance (a different system). This always flows towards the lower temperature and never the other way round, i.e. this flow is non-reversible.
18/19
A.2.1 Condensing and evaporating
Condensing and evaporating are two central processes that take place inside a heat pump. "Condensing" describes the phase change of a gas or gas mixture into its liquid aggregation state. "Evaporation" describes the phase change of a liquid or liquid mixture into its gaseous aggregation state.
The amount of energy required for evaporating a liquid differs depending on the substance involved – known as evaporation enthalpy. The evaporation enthalpy is transferred back to the ambience as condensation heat, when the condensing temperature is undershot. Under static pressure conditions, the phase changes are isothermal, i.e. the liquid temperature – irrespective of whether liquid or gaseous – remains unchanged.
Fig. A.2.1–1 shows that 116 Wh of energy is required to raise one litre of water from 0 °C to 100 °C. So it can be deduced that increasing the water temperature by 1 °C requires 1.16 Wh. If the water temperature exceeds 100 °C under normal atmospheric conditions, the water will have to be evaporated completely. In order to achieve that, 627 Wh is required, in other words, more than 500-times the amount of energy will be needed. The same amount of energy will be released, when water vapour condenses again.
A.2.2 Refrigerant circuit
Heat pumps work according to this basic principle: The absorption of heat through evaporation at a relatively low temperature is transferred again at a higher temperature level through condensation. These phase changes take place under constant pressure, but without changes in temperature (isothermal). Consequently, the pressure must be increased through the application of mechanical energy in order to reach a higher temperature level.
Fig. A.2.2–1 shows the four stages of a typical circular process in a compression heat pump.
Heating 1 litre (kilogram) of water to boiling point
requires 116 Wh. A further 627 Wh are required to
fully evaporate the water (saturated steam point).
Tem
per
atu
re (
°C)
116Wh/kg
627Wh/kg
93Wh/kg
0
1003
EDCB
2
1
1 Freezing point
Boiling point
Saturated steam point
2
3
A Ice
Water + ice
Water
B
C
D Water + steam
Steam/vapourE
A
Fig. A.2.1–1 Energy content of steam
Technical literature frequently refers to energy in thermodynamic systems in units of kilojoules (kJ). However, in this manual, watt-hours (Wh) are used.
1 J = 1 Ws3.6 kJ = 1 Wh3600 kJ = 1 kWh
Note
2
1
1 3
Evaporator
Scroll compressor
Condenser
Expansion valve4
3
Liquid
Gaseous
4
Heating energyEnvironmental heat
2
Fig. A.2.2–1 Heat pump function
The refrigerant evaporates at low temperatures and in the process absorbs heat. Compression increases the
vapour temperature and the heat is then transferred again through condensation.
To aid understanding, this circular process can be illustrated in a pressure/enthalpy diagram (Fig. A.2.2–2). This marks off the pressure (p) logarithmically on the Y axis.
Appliances that employ this process are differentiated according to their use. If the use of the appliance lies on the evaporation side, in other words, involving the extraction of
A.2 Physical principles
40
50
30
20
10
5
4
3
2
1
Energy content h (Wh/kg)
Pre
ssu
re p
ab
solu
te (
bar
)
100 110 120 130 140 15080 907050 604030
0°C
10°C
-10°C
20°C
-20°C
30°C
-30°C
-40°C
70°C
60°C
80°C
60°C
40°C
100
°C
120
°C
140
°C
Evaporation
Condenser
Exp
ansi
on
Com
pres
sion
Superheated steam
Steam/vapour
Liquid
1 2
34
Fig. A.2.2–2 The log p,h diagramThe log p,h diagram applied in
this example shows the physical
properties of the R 407C refrigerant
used in Viessmann air/water
heat pumps.
As part of the heat pump operation, the refrigerant undergoes the following changes in state:
Evaporation
The refrigerant evaporates. The energy required for this (evaporation enthalpy) is extracted from the
environment, e.g. from the outdoor air.
Compression
With the aid of its drive energy, the compressor raises the pressure and thereby the temperature of the
refrigerant vapour. The enthalpy (the energy content) increases.
Condensing
The refrigerant vapour condenses. During this change, the environmental energy that has been absorbed,
plus the drive energy drawn by the compressor, is transferred again.
Expansion
The refrigerant is expanded, in other words the temperature and pressure of the refrigerant are returned into
their original state by means of an expansion valve. The medium can again be evaporated and the process
starts again.
The technical term for the energy content in a thermodynamic system is enthalpy [h] (Greek: en = in and thalpein = to heat).
Note heat, then we are talking about a refrigeration machine. Where the utilisation lies on the condensing side, i.e. the transfer of heat, then we are looking at a heat pump. In general, every refrigeration machine can provide heating and every heat pump can provide cooling.
A.2.3 Coefficient of performance (COP)
The coefficient of performance is a measure of efficiency and is defined as the ratio between cost and benefit. In relation to a heat pump, this is defined as follows: The benefit is the amount of heat transferred at a high temperature level (condensation), the cost is the drive energy (compression) required to achieve this. For heat pumps, the level of efficiency is expressed as a coefficient of performance – the English abbreviation, COP, is commonly used).
Applying the log p,h diagram, the coefficient of performance of a heat pump is defined as follows:
COP = h3 - h4
h3 - h2
COP coefficient of performanceh2 enthalpy at the start of compressionh3 enthalpy at the end of compression /
start of heat transferh4 enthalpy at the end of condensation /
end of heat transfer
The coefficient of performance of modern heat pumps lies between 3.5 and 5.5. A coefficient of performance of 4 means, for example, that four times as much energy is transferred as useful heating energy than was expended in the form of electrical energy.
20/21
Heating output
Heat from the environment
Power consumption
4 kW3 kW
1 kW
?
Fig. A.2.3–1 The efficiency level as coefficient of performance
Fig. A.2.3–2 Temperature differential and coefficient of performance
12
10
8
6
4
2
0
Temperature differential ΔT (K)
Co
effi
cien
t o
f p
erfo
rman
ce
50 40 30 20 10 0
A B
B
A At ΔT = 25 K the COP
is almost 6
At ΔT = 50 K the COP
is only 3.3
Example
For the example (red line) in Fig. A.2.2–2 the
coefficient of performance is calculated as follows:
COP = coefficient of performance
h2 = 114 Wh/kg
h3 = 126 Wh/kg
h4 = 69 Wh/kg
COP = 126 Wh/kg – 69 Wh/kg
126 Wh/kg – 114 Wh/kg
In this example the heat pump, therefore, has a
calculated refrigerant circuit COP of 4.75.
The heating output transferred in this example is four times
higher than the expended electrical energy.
The COP is 4.
The lower the temperature differential between the heating circuit flow temperature and the heat source inlet temperature, the higher the coefficient of performance.
The following rule of thumb applies: Flow temperature 1 K lower
COP 2.5 % higher Source temperature 1 K higher
COP 2.7 % higher
A.2 Physical principles
In order to provide comparable coefficient of performances for heat pumps, calculations are made in accordance with DIN EN 14511 and measurements taken at fixed operating points. The operating point is the product of the inlet temperature of the heat source medium (air A, brine B, water W) in the heat pump and the heating water outlet temperature (secondary circuit flow temperature).
For the following heat pump types, the operating points below apply:
Type Inlet
temperature,
heat source
Secondary
circuit flow
temperature
Air/water A 2 °C W 35 °C
Brine/water B 0 °C W 35 °C
Water/water W 10 °C W 35 °C
A stands for airB stands for brineW stands for water
The standard takes the drive output of the heat pump, plus the power consumption of the heat pump control unit, as well as a proportion of auxiliary energy into account, that is required in order to overcome the internal pressure drop of both heat exchangers.
This includes the amount of power used by pumps, control units, etc. The result is given as the seasonal performance factor :
= QWPWEL
seasonal performance factorQWP amount of heat in kWh delivered by the
heat pump over the course of a yearWEL electrical power in kWh supplied to the
heat pump over the course of a year
For forecasting purposes, the simplified calculation process according to VDI guideline 4650 has become the established norm. The so-called BIN process to DIN 18599 is significantly more accurate, but also more complicated.
At www.viessmann.com the seasonal performance factor calculator is available to use with heat pumps.
Note
A.2.4 Seasonal performance factor (SPF)
The coefficient of performance (COP) is the ratio between the heating output and the power consumption at a single operating point. The seasonal performance factor is this ratio over a period of 12 months.
The coefficient of performance is used to compare heat pumps with regard to efficiency, yet it is derived from a particular operating point under defined temperature conditions.
For engineering purposes (for example, to be able to specify the consumption costs arising from using a heat pump), it is necessary to consider the system's operation over the whole year. For this, the heat volume transferred over the year is given in relation to the overall electrical power drawn by the heat pump system over the same period.
22/23
A.3 Main components
The primary circuit of a heat pump includes all of the components that are required for the absorption of environmental energy – e.g. the heat exchangers, brine pumps or fan motors; in the case of water/water heat pumps also the intermediate heat exchangers.
The secondary circuit includes all components required to transfer the energy gain to the consumer.
Main components
Excellent heat pump systems are characterised by their efficiency and operational reliability. This requires the choice of tried and tested components that interact perfectly – from heat source to heat transfer.
24/25
Static spiral block
Moving spiral block
A.3.1 Compressor
The compressor is the part of the heat pump that acts as the "pump" – it sucks in and compresses the gaseous refrigerant. All compressors are designed to compress gases and would be damaged if liquid droplets in the vapour were to be drawn in. The vapour must therefore be slightly superheated prior to entering the compressor. This superheating is regulated by the expansion valve, the accurate control of this component being vital to overall heat pump efficiency.
A.3.1.1 Compressor types
The effectiveness of the compression process is crucial to the efficiency of a heat pump. Scroll compressors really come into their own when used in heat pumps. This type of compressor is comprised of two interlocking spirals which compress the refrigerant. Scroll compressors operate quietly and with low vibrations; they are maintenance free and extremely durable.
Rotating piston compressors, reciprocating piston and screw compressors are also used. Rotating piston compressors tend to cover the lower output ranges, scroll compressors the low to medium and screw compressors the higher output range.
Fig. A.3.1–1 The scroll compressor
The scroll compressor features two interlocking spiral blocks – one static and one moving.
The moving spiral block makes an eccentric rotation, during which three processes take place simultaneously:
intake (blue segments), compression (violet segments), expulsion (red segments).
A.3.1.2 Output control
The importance of output control in compressors is gaining in significance. For heat pumps operating with outdoor air as a primary source, output control is particularly suitable, as with this type of heat source major fluctuations in the seasonal performance factor can occur.
Design output
Design temperature
Heating limit temperature
Outside temperature (°C)
Ou
tpu
t (k
W)
3
3
2
2
1
1
Unregulated air/water heat pump Heat demand
Regulated air/water heat pump
10 20 30 40 50 60 70 80 90 100
0
2
3
4
1
5
0
8
4
12
16
20
Coefficient of performance Heating output (kW)
Co
effi
cien
t o
f p
erfo
rman
ce
Rotating field frequency (Hz)
Hea
tin
g o
utp
ut
(kW
)
3.13
1.27
4.055.15
6.69 7.218.56
9.66
6.42
2.61
3.70 3.673.76
3.59 3.463.14
3.603.77
In addition, there is a counter-acting trend between output demand and output provision – the colder the outdoor air heat source, the higher the demand for heating energy, and the greater the temperature differential between source and available temperature with corresponding implications for the COP. If the outside temperature increases, the heat demand falls whilst the appliance output rises. In order to prevent frequent cycling of the heat pump, its output is matched to these framework conditions. The compressor output – and consequently also the refrigerant pressure and temperature – are regulated accordingly.
Output control can be achieved by several means. The most frequently applied method for regulating the compressor output involves the deployment of inverter technology – this generates a DC current from the supply voltage (e.g. 230 V ~). Subject to the frequency of the rotating field, the compressor will operate at different speeds and consequently deliver different output ratings. Particularly in partial load operation, inverter compressors operate with a high degree of efficiency.
Fig. A.3.1–2 Output control
Fig. A.3.1–3 Inverter compressor for controlled output
The output control principle
becomes apparent upon inspection
of these actual values: the heating
output is raised as the speed
increases.
The heat pump output is matched
to the prevailing demand to prevent
frequent cycling.
A.3 Main components
Example
Compressor with output control through
pressure reduction valve
Seconds
Seconds
50 10 15 20
50 10 15 20
Pre
ssu
reP
ress
ure
Compression process Pressure reduction phase
30% output
70% output
Output control via a pressure reducing valve in the compressor is another option.
If the solenoid valve opens, the compressor runs without pressure, consequently there is no heating output. Subject to the duration of runtimes, with and without pressure, the output can be regulated between 30 % and 100 %.
2
1
1
6
3
Evaporator
Scroll compressor
Condenser
5
6
45
Heat exchanger
Expansion valve
Expansion valve
4
3
Liquid
Gaseous
Heating energyEnvironmental heat
Enhanced VapourInjection (EVI)
2
Fig. A.3.1–4 Enhanced Vapour Injection (EVI)
26/27
A.3.1.3 Enhanced Vapour Injection – EVI
In buildings, the target temperatures in the secondary circuit are determined by the required heating surface and DHW temperatures. Enhanced Vapour Injection (EVI) into the compressor may be used in order to enable operation, even when there are significant temperature differentials between the source and useful temperature.
The maximum temperature that commercially available refrigerants may reach in the compression process is currently 135 °C; temperatures that are any higher would damage the compressor. With Enhanced Vapour Injection (EVI), the compressed refrigerant vapour is cooled. This happens at a point where compression has been approximately two thirds completed (see Fig. A.3.1–4 and Fig. A.3.1–5).
Standard solutions without EVI achieve a temperature rise of 60 K, however with EVI a rise of 80 K can be achieved. Vapour injection enables a flow temperature of 65 °C to be reached, even with low heat source temperatures. This makes EVI particularly appropriate for use with air/water heat
Some of the refrigerant is used downstream of the condenser (3) in order to generate vapour with the aid of
an additional heat exchanger (4) and an additional expansion valve (5). This vapour is then injected directly
into the compressor (2). This happens at a point where compression has been approximately two thirds
completed. EVI cools the refrigerant vapour that has been compressed up to this point.
A heat pump without EVI (red line)
can achieve a flow temperature of
only 55 °C at a source temperature
of –10 °C, since the compression
process must stop at 135 °C.
EVI (3 to 4, blue line) cools the
refrigerant. The pressure can
continue to be increased without
exceeding the permissible
maximum temperature. A flow
temperature of 65 °C can be
achieved.
40
50
30
20
10
5
4
3
2
1
Pre
ssu
re p
ab
solu
te (
bar
)
Energy content h (Wh/kg)
100 110 120 130 140 15080 907050 604030
0°C
10°C
-10°C
20°C
-20°C
30°C
-30°C
-40°C
70°C
60°C
80°C
60°C
40°C
100
°C
120
°C
140
°C
Superheated steam
Steam/vapour
Liquid 1 2
34
3
56
4
Heat pump without EVI Heat pump with EVI Heat pump without EVI
Evaporation
Condenser
Exp
ansi
on
Com
pres
sion
Fig. A.3.1–5 EVI effect
pumps, as lower source temperatures can be expected than with geothermal heat or groundwater, for example.
A.3.2 Expansion valve
In the heat pump circuit, the expansion valve has the job of expanding, i.e. reducing the pressure of the liquid refrigerant post heat transfer to the heating system, when the refrigerant is still under high pressure. Consequently, the refrigerant is used in a state that enables the renewed absorption of environmental heat. In order to prevent liquid from entering the compressor, the expansion valve regulates the amount of refrigerant (refrigerant mass flow rate) so that only as much refrigerant enters the evaporator as can be fully evaporated there. The valve ensures that only superheated vapour enters the compressor.
Fluctuations in the source temperature and output necessitate the use of a regulated expansion valve, since the pressure within the refrigerant circuit and consequently also the required temperature changes upstream of the compressor.
2
2
1 Thermostat Expansion valve
1
4
4
3
2
2
1 Temperature sensor Controller
Pressure sensor Expansion valve
1
3
Fig. A.3.2–1 Thermostatic expansion valve Fig. A.3.2–2 Electronic expansion valve
Fig. A.3.2–3 Superheating
A.3.2.1 Thermostatic expansion valve
The thermostatic expansion valve is a temperature-controlled valve. It captures the temperature of the suction line to the compressor and regulates the refrigerant metering into the evaporator accordingly.
A.3.2.2 Electronic expansion valve
The electronic expansion valve captures the temperature, as well as the pressure, upstream of the compressor. An electric servomotor inside the expansion valve enables fast and precise control of the refrigerant mass flow rate, resulting in the superheating (in Kelvin) being able to be held constant across the entire range of the compressor output.
Thermostatic expansion valves, on the other hand, only achieve the minimum required superheating at their design point; superheating in all other operating points will be higher.
However, the higher the temperature of the superheated refrigerant, the lower the maximum possible temperature at the condenser (see Fig. A.3.1–5). In addition, the compressor needs to work harder and the heat pump efficiency drops.
A.3 Main components
-20 -10 0
Source temperature (°C)
Su
per
hea
tin
g (
K)
+10
10
12
8
6
4
2
0
A
A
Electronic expansion valve
Thermostatic expansion valve
Design point
The electronic expansion valve quickly and accurately
controls the refrigerant mass flow rate, keeping superheating
constant across the entire output range.
The thermostatic expansion valve only achieves optimum
superheating at the design point – at all other operating
points superheating will be too high.
The thermostatic expansion
valve is hydraulically regulated
via a capillary tube.
Fig. A.3.3–1 Evaporator with and without distributor
Without refrigerant distributor With refrigerant distributor
2
1
°C
0
-1
-2
-3
-4
-5
-6
28/29
A.3.3 Heat exchanger
This chapter describes the fundamental properties of the heat exchangers in a heat pump. Different heat pump types, some already mentioned above, are described in chapter A.4.
A.3.3.1 Evaporator
Generally speaking, plate heat exchangers are used as evaporators in brine/water and water/water heat pumps, as these enable high heat transfer rates to be achieved within a comparatively compact design. Under exceptional conditions, coaxial heat exchangers are also used in water/water applications. These safeguard high operational reliability in the case of contaminated water. Special designs are available for the utilisation of waste heat, for example from waste water.
A refrigerant distributor can be employed to increase the output of plate heat exchangers. These distribute the refrigerant evenly across the entire evaporator area, thereby effectively preventing it from simply "shooting through" the heat exchanger. This ensures optimum utilisation of the available area.
Finned heat exchangers are used in air/water heat pumps. On their primary side, these feature an exceedingly large surface area, because the thermal capacity of air is much lower than that of water or glycol:water mixtures.
At temperatures near freezing point and below, the water vapour contained in the air freezes onto the heat exchanger fins. Wide fin spacing slows down the icing of the evaporator, but cannot prevent it all together. Iced-up heat exchangers run more noisily and the fans draw more power. In other words, they need periodic defrosting. With advanced air source heat pumps, this takes place automatically and according to need. The less defrost energy is expended, the more efficient the heat pump operation. Finned heat exchangers from Viessmann feature a special coating that ensures that the evaporator is protected from corrosion and that the water runs off quickly during the defrost cycle.
The thermographies illustrate the effect of the refrigerant distributor. Without it (left), refrigerant could "shoot through", resulting in an uneven flow through the heat exchanger.
An even flow pattern is achieved with the refrigerant distributor (right).
A.3.3.2 Condenser
In the condenser area, too, plate heat exchangers with a remarkably high heat transfer capacity have been selected. Different designs are only deployed in the output range above 100 kW.
A.3.3.3 Suction gas heat exchanger
The expansion valve control ensures that the refrigerant at the compressor entry point is superheated, in other words completely evaporated. A suction gas heat exchanger improves the operational reliability, particularly with refrigerant mixtures, the constituents of which may have different boiling points. This ensures that no liquid constituents remain in the refrigerant vapour.
A.3.3.4 Hot gas separation
Prior to the refrigerant vapour reaching the condenser, part of the hot gas energy can be "siphoned off" and used for raising consumers to a higher temperature level – generally DHW heating. The amount of energy utilised in separation is generally approximately 10 percent of the total amount of heat. The main amount of heat is then transferred, via the condenser, at a slightly lower temperature level to the heating circuit.
Viessmann heat pumps do not employ hot gas separation, as, particularly with fluctuating DHW consumption, there is a risk of the hot gas energy not being required. In this case, the higher pressure drop in the refrigerant circuit on account of the additional heat exchanger would then reduce heat pump efficiency unnecessarily.
2
1
1
4
3
Evaporator
Scroll compressor
Condenser
5
5
Suction gas heat exchanger
Expansion valve
4
3
Liquid
Gaseous
Heating energyEnvironmental heat
2
2
1
1 4
3
Evaporator
Scroll compressor
Hot gas separation
5
5
Condenser
Expansion valve
4
3
Liquid
Gaseous
Heating energyEnvironmental heat
2
Fig. A.3.3–3 Suction gas heat exchanger
Fig. A.3.3–4 Hot gas separation
A.3 Main components
Fig. A.3.3–2 Air/water heat pump
Air/water heat pump
Vitocal 350-A
30/31
A.3.4 Refrigerant
The refrigerant draws heating energy from the heat source (air, ground or water) during evaporation and transports it to the consumer, where it condenses again. Energy is always available in these phase changes. Purely theoretically, though, any substance can be thought of as a refrigerant.
However, a refrigerant suitable for heat pumps must possess some special properties, i.e. it should have as low a boiling point as possible, a low evaporation volume and a high cooling capacity, relative to its volume. In addition, it must not be corrosive to the components and lubricants employed, if possible it should be non-poisonous, non-explosive and non-flammable. Effects on the ozone layer (ODP = Ozone Depletion Potential) and its greenhouse effect (GWP = Global Warming Potential) should be as low as possible.
Partially halogenated chlorofluorocarbons (H-CFC) best meet these requirements, and so are generally used in heat pumps. Apart from synthesised refrigerants, natural refrigerants, such as CO2, propane or butane are also used in some applications. Since the latter two substances are explosive, their use would place high demands on the safety equipment.
DIN 8960 defines the designation of refrigerants. They start with letter "R" (for refrigerant), the following figures then permit conclusions as to their chemical composition (see Fig. A.3.4–1).
All refrigerants that have a numbered sequence following the letter "R" starting with a "4" are mixtures of different refrigerants that are not designated in accordance with the system described above. Mixtures are characterised by particularly good physical properties and very favourable environmental characteristics. Selection of the optimum refrigerant depends on the operating conditions of the heat pump, in other words, on the source and target temperature.
To be "halogenated"
means that a molecule
contains not only carbon,
but halogens, too, in other
words fluorine, chlorine,
bromine or iodine. This
may be as complete (fully
halogenated) or as partial
(partially halogenated)
compounds.
Partially halogenated
hydrocarbons also include
hydrogen. The risk they
pose to the environment
(GWP) is substantially
lower than that of
fully halogenated, or
saturated, hydrocarbons.
Hydrocarbons that are
free of chlorine pose no
risk to the ozone layer, in
other words their ODP
is zero.
Note
Refrigerant Heat pump type
Type
Composition
Brine/water
Water/water
Air/ water
R-410A50 % R-32 (CH2F2, difluoromethane)
50 % R-125 (C2HF5, pentafluoroethane)x x x
R-407C
25 % R-125
23 % R-32
52 % R-134a (CF3CH2F, tetrafluoroethane)
x x x
R-134a 100 % CF3CH2F, tetrafluoroethane x x
Fig. A.3.4–2 Viessmann refrigerant table
Fig. A.3.4–1 Extract from DIN 8960
Not every refrigerant or refrigerant mixture is
suitable for every heat pump type.
Example
The organic refrigerant pentafluoroethane:
This molecule consists of two carbon atoms (C), one
hydrogen atom (H) and five fluorine atoms (F).
The sum formula for this compound
is therefore C2HF5 (R-125).
A.4 Primary source potentials
Primary source potentials
Heat pumps predominantly use heat from the ground, outdoor air or water as a primary energy source. However, heat pumps can also convert waste heat that would otherwise be left unused, into useful energy.
The following chapters describe the different primary sources and the different types of heat pump that can be used to exploit them.
Heat from the sun is stored in the air, water and the ground. This environmental heat is therefore a renewable form of energy that can be utilised by heat pumps.
32/33
A.4.1 Ground as heat source
"Ground" here, refers to the top layer of the ground, which represents a stable heat source. For example, the temperatures at two metres below ground are relatively constant throughout the year, i.e. between 7 °C and 13 °C.
Energy is recovered with the help of a heat exchanger that is laid in an area near the building to be heated. A heat transfer medium (brine) – a mixture of water and antifreeze – courses through a geothermal collector that spreads out over a large horizontal area or through vertically sunk geothermal probes, and absorbs the heat stored in the ground and transports it to the evaporator of the so-called "brine/water" heat pump. The term "brine/water" heat pump, therefore, means brine in the primary circuit and water in the secondary circuit. Geothermal collectors utilise that amount of heat that penetrates the ground through insolation, rain or melt water.
Fig. A.4.1–1 Annual temperature curve under ground
A.4.1.1 Geothermal collector
With a geothermal collector, plastic pipes are buried under ground at a depth of between 1.2 and 1.5 m. At this depth, the temperature over the whole year is sufficiently stable – the slightly higher amount of heat at lower levels could not justify the additional construction effort (nor the resulting financial outlay).
Wherever possible, the individual lines should be of equal length in order to create identical pressure drop values and consequently identical flow conditions. Where possible they should not exceed 100 m in length, otherwise the resulting pressure drop would demand excessively high pump ratings. The pipe ends come together in return manifolds that are arranged at a slightly higher level (venting), and each line can be shut off separately. Brine is pumped through the plastic pipes using a circulation pump, and in the process it absorbs the heat stored under ground.
A temporary minor frost under ground around the pipelines caused by the heat pump operation has no negative impact, either on the system operation, or on the vegetation above. However, to protect the system, plants
Fig. A.4.1–2 Heat source – geothermal collector
0
5
10
15
18
Temperature (°C)
Dep
th (
m)
15 201050
1 February 1 August
1 November1 May
with deep roots should be not be grown near geothermal collectors.
The geothermal collector is comprised of plastic pipes laid horizontally into the ground at a depth of 1.2 to 1.5 m.
The area above the geothermal collectors must not be built on or sealed, in order to permit the cooled-down ground to be replenished during spring and summer. Insolation and precipitation ensure that the ground as heat store is available again for heating purposes during the following heating season.
The earthworks required for laying the collector can be accommodated during new build projects without excessive cost implications. For cost reasons, "retrofitting" an existing building with a brine/water heat pump and geothermal collectors is usually not viable.
The available amount of heat, and therefore the size of the required collector area, is largely dependent on the thermophysical properties of the ground and on the insolation energy, i.e. it is subject to the prevailing climatic conditions. For this, ground variables such as the proportion of water, the proportion of mineral constituents, such as quartz or feldspar, as well as the proportion and size of the air-filled pores are important. Storage properties and thermal conductivity are better the more water and mineral constituents are in the ground and the fewer pores are prevalent.
The heat extraction rating for underground areas lies between approx. 10 and 35 W/m2.
Fig. A.4.1–3 Heat source – geothermal collector
A.4 Primary source potentials
3
2
1 Geothermal collector
Brine circuit pump
Brine/water heat pump3
2
1
Fig. A.4.1–4 Heat extraction rate – ground
Possible specific extraction rates for
geothermal collectors.
Subsoil Specific
extraction rate
Dry sandy soil 10 – 15 W/m2
Damp sandy soil 15 – 20 W/m2
Dry loamy soil 20 – 25 W/m2
Damp loamy soil 25 – 30 W/m2
Ground with groundwater 30 – 35 W/m2
34/35
Fig. A.4.1–6 Geothermal probe borehole
Fig. A.4.1–7 Drill types
A.4.1.2 Geothermal probe
Major earthworks are required for installing geothermal collectors at a depth greater than 1 m. Installing geothermal probes, on the other hand, can be accomplished in only a few hours using modern drilling equipment. Arrangement and drilling depth are vital factors when installing systems with geothermal probes. Consequently, geologists, or specialist drilling contractors with the corresponding level of expertise, undertake the installation of geothermal probes. Furthermore, an extraction capacity can be contractually agreed with these specialist contractors. Packs that offer heat pump and drilling from a single source promise a high degree of engineering security with guaranteed extraction rate.
In Germany, geothermal probe systems require a permit from a local water board. In most regions, drilling up to a depth of 100 m falls within the responsibility of the local water board. Boreholes that are any deeper need approval from the relevant mining authorities as well.
A pre-fabricated probe is inserted into the borehole, the hollow space between the probe pipe and the borehole is then compacted with a filler material.
Costs for such boreholes including probe, connection line and filling matter are, subject to ground properties, €60 to €80 per meter. A typical detached house, built as a low energy house, requires approximately 6 kW to provide comfortable heating with a heat pump. This requires a borehole depth of approximately 100 metres, which would entail costs of approx. €6000 to €8000.
Design and installation require sound knowledge of ground conditions, the order of ground strata, the ground resistance and the presence, or otherwise, of ground or stratum water, including the determination of water levels and flow direction. Under standard hydrogeology conditions, an average heat extraction of 50 watt per metre probe length can be assumed for geothermal probe systems (according to VDI 4640). Higher extraction rates can be achieved if the probe is installed in a rich seam of groundwater.
Fig. A.4.1–5 Heat source – geothermal probe
4
3
1 Geothermal probes
Brine distributor
Brine circuit pump
Brine/water heat pump
2
2
3
4
1
Setting a geothermal probe in
three stages: drilling the hole;
inserting the probe; compacting the
filling material.
Different types of drills are used, subject to the subsoil and probe dimensions.
Experienced drilling contractors know "their" substrates and can also draw conclusions about the likely extraction rate from drilling samples. In larger probe arrays, test drilling for a Thermal Response Test may also be advisable in order to obtain more accurate bases for engineering.
Brine is used in geothermal probes, as in geothermal collectors, as a heat transfer medium. Brine flows in two pipes from the distributor downwards into the probe and is returned by two further pipes upwards to the header.
Fig. A.4.1–9 Extraction rate – geothermal probes
Fig. A.4.1–8 Brine distributor for geothermal probes
Possible specific extraction rates
for geothermal probes (double
U-shaped tubular probes) to
VDI 4640 Sheet 2.Subsoil
Specific
extraction rate
Standard values
Poor ground (dry sediment) 20 W/m
Normal solid rock subsoil and water-saturated sediment 50 W/m
Solid rock with high thermal conductivity 70 W/m
Individual rocks
Gravel, sand, dry < 20 W/m
Gravel, sand, aquiferous 55 – 65 W/m
Clay, loam, damp 30 – 40 W/m
Limestone (solid) 45 – 60 W/m
Sandstone 55 – 65 W/m
Acidic magmatite (e.g. granite) 55 – 70 W/m
Basic magmatite (e.g. basalt) 35 – 55 W/m
Gneiss 60 – 70 W/m
A.4 Primary source potentials
Thermal Response Test (TRT):A defined amount of heat is channelled to the geothermal probe, and the outlet temperature of the water from the probe is captured over several days. The TRT enables the calculation of the effective thermal conductivity of the subsoil around the probe.
Note
36/37
A.4.2 Water as heat source
Water is also a highly suitable heat source for heat pumps. Even on cold winter days, groundwater maintains a constant temperature of between 7 °C and 12 °C. In order to use groundwater for a heat pump, it must be extracted through a supply well and transported to the evaporator of a water/water heat pump. The cooled water is then routed through a return well.
Surface water, too, may be used as a heat source, although it should be noted that the temperatures will fluctuate quite dramatically depending on the season.
The water quality must meet the limits specified by the heat pump manufacturer – the highly efficient plate heat exchangers inside the heat pump are extremely sensitive to fluctuating water quality. In order to prevent any resulting damage, it is generally appropriate to utilise an intermediate circuit heat exchanger. Threaded stainless steel heat exchangers have proven to work well as intermediate circuit heat exchangers – these transfer the environmental heat to a brine circuit. This provides an appropriate level of protection for the heat pump.
A.4.3 Outdoor air as heat source
Using outdoor air as a heat source requires the least effort of all. Air is drawn in, cooled in the heat pump evaporator and finally discharged again to the ambience.
Advanced air/water heat pumps can generate heating energy from outdoor air temperatures as low as –20 °C. However, even with optimum sizing, at such low outside air temperatures, the heat pump can no longer meet the central heating demand completely. For this reason, an additional heat generator heats up the heating water pre-heated by the heat pump to the required flow temperature on very cold days.
Utilising an intermediate circuit requires additional pump power and alters the temperature spread – the heating output and the COP of the heat pump will, as a result, drop by a few percentage points.
The use of ground and surface water must also be approved by the relevant authority, generally the local water board.
Fig. A.4.2–1 Heat source water with intermediate circuit
Fig. A.4.3–1 Heat source – outdoor air (internal installation)
5
2
2
1
1
Return well
Supply well with suction pump
Intermediate circuit heat exchanger
Intermediate circuit circulation pump
Water/water heat pump
3
3
4
4
5
32
2
1
1
Supply air duct
Extract air duct
Air/water heat pump3
Air/water heat exchangers handle a relatively large volume of air (3000 to 4500 m3/h). Consequently the arrangement of the air intake and discharge apertures inside the building must take the noise development into account. The same applies for externally installed heat pumps.
5
2
2
1
1
Drain
Waste water
Waste water heat exchanger
Circulation pump
Water/water heat pump3
3
4
4
5
Fig. A.4.5–1 Heat source – waste water
Fig. A.4.5–2 Waste water heat exchanger
Fig. A.4.4–1 Availability and efficiency A.4.4 Availability and efficiency –
assessment of the primary sources
Fig. A.4.4–1 shows the relationship between different heat sources and heat pump efficiency. This makes it apparent that the heat pump is at its most efficient when coupled to groundwater as a heat source. However, groundwater that can be used for heat pumps is the least available heat source. This ratio is roughly in balance for ground as heat source. Outdoor air as a heat source is available almost without limit. However, heat pump efficiency suffers on account of fluctuating temperatures and the opposing cycle of "low outside temperature, high heat demand".
Water Ground Air
Efficiency
Availability
Waste water as a heat source
can provide a comparatively high
source temperature at a very
affordable rate.
A.4.5 Waste heat as heat source
Apart from air, water and the ground, waste heat, too, such as from extract air or waste water, can be used as a heat source. Developing waste heat as a heat source is frequently a very affordable measure for providing heat and cooling, as it can offer a comparatively high source temperature and may be available continuously. In industrial processes, the utilisation of waste heat can raise the heat pump COP or significantly optimise an entire process that requires both cooling and heating. Where food production requires cooling and heating, for example, "both sides" of the refrigeration machine can be usefully employed.
Extracting heat from extract air in a ventilation system and its use for heating domestic hot water or heating the supply air has a comparable positive effect. One highly appropriate form of heat recovery is the utilisation of waste water. Here residual energy is extracted from waste water from the living space or from industrial processes by special heat exchangers. This heat is then added to the upstream process.
A.4 Primary source potentials
38/39
Fig. A.4.6–1 Heat source – non-glazed absorberA.4.6 Absorber with solar backup
Solar collectors or non-glazed absorbers, too, can be used to improve the temperature level on the primary side of the heat pump. This way, the insolation is used directly for improving the efficiency level.
For example, non-glazed absorbers that utilise the ambient temperature as a heat source can be linked into the evaporator circuit. The absorber is regenerated by insolation in constant operation, in other words, the temperature is held at a high level. With this combination, the improvements of the COP depend on the weather, i.e. they are not constant, as particularly during the heating season insolation is not reliably available. In sizing the absorber, it must be taken into account that it might be covered by snow for certain periods, meaning that insolation can then not be used at all.
In the case of solar thermal systems for solar central heating backup, any energy in combi or buffer cylinders no longer useful to the heating circuit can be used, theoretically at least, for the heat pump by cooling down the cylinder by a few Kelvin. The efficiency of the heat pump (higher source temperature) and the collector system (lower return temperature) would be improved by such a combination.
However, in practical terms, the achievable utilisation would never justify the necessary technical effort. Utilising the phase change in heat stores [heat sources] offers a sensible combination of solar thermal system and heat pump.
Historic photographs of non-
glazed solar absorbers that
utilise insolation and ambient
temperature as heat source.
A.4.7 Phase change as "storage"
on the primary side
Where water, air and the ground are not available as immediate heat sources, cylinder methods can be deployed as a primary source to utilise the phase change.
Solidification enthalpy can be used as an energy source for heat pumps – the regeneration (melting) is caused by ambient heat and a solar thermal system. Apart from water (ice), paraffins, too, can be used, for
The phase change of one kilogram
of ice into water at the same
temperature requires 93 Wh.
Tem
per
atu
re (
°C)
116Wh/kg
627Wh/kg
93Wh/kg
0
1003
EDCB
2
1
1 Freezing point
Boiling point
Saturated steam point
2
3
A Ice
Water + ice
Water
B
C
D Water + steam
Steam/vapourE
A
Fig. A.4.7–1 Heat storage – phase change
A.4 Primary source potentials
example. The principle is always the same, i.e. the chain "gaseous to liquid" within the heat pump is extended by the link "liquid to solid" on the source side.
Practical experience has shown that a combined utilisation of a phase change storage and solar backup absorbers as "primary source" results in more efficient systems.
The phase change of water into
ice as heat storage is utilised in a
complex heat exchanger bank inside
an underground tank.
Fig. A.4.7–2 Heat storage – phase change
40/41
A.5 Alternative types of heat pump
Alternative types of heat pump
Heat pumps not only utilise energy contained in the change of an aggregated condition. Other types exist that work on different principles.
In previous chapters, types of heat pump were described that utilise the phase change from the liquid to the gaseous state. However, there are further state variables, the change of which is connected with deployment of energy, which make them available for heat pumps.
For example, if you add salt to a vessel containing water, the salt will dissolve and distribute evenly throughout the water. During this process, the water will cool down. If this process were to be reversed, energy would need to be added to the solution until the water has been evaporated and salt crystals remain.
This chapter describes heat pumps that drive liquids out of solutions or solid bodies utilising environmental energy.
42/43
A.5.1 Compression heat pumps with
internal combustion engine
Generally, compressor heat pumps can also operate with natural gas, diesel or biofuel (rapeseed oil). An internal combustion engine instead of an electric motor is used to drive the compressor. This requires additional effort/expenditure for sound insulation, exhaust gas routing and fuel supplies.
Compression heat pumps with internal combustion engine drive can also utilise the waste heat from the combustion process as heating energy.
A.5.2 Absorption heat pumps
Generally speaking, absorption heat pumps follow the same physical principles as compression heat pumps. Contrary to these, absorption heat pumps are generally operated with natural gas and are used with a thermal compressor in place of a mechanical one.
The solvent pump requires only little power input (electricity). Energy for the thermal compressor is supplied in the form of heat. Any number of heat generators can be utilised, and with certain combinations of materials, even solar thermal systems.
An absorption heat pump is highly efficient, it has no moving parts apart from the solvent pump and operates relatively quietly.
Absorption heat pumps with a high output range (in excess of 50 kW) are state of the art in the form of refrigeration machines. In the lower output range to approximately 2 kW, these appliances are used in propane-operated camping refrigerators, for example. Currently, there are no solutions suitable for standard production for deployment as heat generators in the medium output range.
Sorption describes all processes in which a material is enriched in a phase or on the periphery between two phases.
Absorption describes the enrichment within a phase. With this process, a substance enters the interior of a solid body or liquid.
Adsorption describes the enrichment on the periphery between two phases. Liquid or gaseous components are absorbed on a solid surface – e.g. of active charcoal or zeolites.
Note
A.5 Alternative types of heat pump
6
2
2
1
1
Evaporator
Expansion valve
Absorber 6
7
7
5
5
Expansion valve
Solvent pump
Generator
Condenser
4
4
3
3
Liquid
Gaseous
Heating energy
Environmental heat
Fig. A.5.2–1 Absorption heat pump function
Evaporation
The refrigerant (conventionally ammonia) is evaporated whilst environmental energy is absorbed (1).
Absorption
The refrigerant vapour flows into the absorber (3), where it is absorbed by a solvent (generally water). This condensation generates heat – it is transferred to the heating system by means of a heat exchanger.
Thermal compression
The combination of materials of refrigerant and solvent created in the absorber, is transported by the solvent pump (5) to the generator, also known as the "thermal compressor" (6). Both parts of the combination of materials have different boiling points – the dissolved refrigerant has the lower boiling point. The dissolved refrigerant is now driven out or evaporated with the aid of heat supplied or through a gas burner.
Condensing (I)
The liquid solvent separated in the generator and which is under high pressure, is returned to the absorber via an expansion valve (4). Here, solvent and refrigerant vapour meet and condense whilst transferring heat.
Condensing (II)
The refrigerant vapour, which also features high pressure and temperature levels, flows into the condenser (7) and transfers its condensation heat to the heating system.
Expansion
An expansion valve (2) expands (depressurises) the liquid refrigerant to its original pressure and temperature level in order to be able to be evaporated again whilst absorbing environmental heat.
44/45
A.5.3 Adsorption heat pumps
The adsorption heat pump operates with solid matter, such as active charcoal, silica gel (glass-like silicate) or zeolite, for example. The mineral, zeolite, has the property of attracting water vapour, to bind itself to same (to adsorb) and in the process to give off heat in the temperature range up to approx. 300 °C. This is described as exothermic reaction.
As for the heat pumps already described, the process of heat absorption and transfer is a circular process for adsorption heat pumps as well – however operation is periodical, i.e. in two distinct phases. Adsorption heat pumps of this type require a vacuum system.
Fig. A.5.3–1 Adsorption heat pump function
Just like the absorption heat pump described in Fig. A.5.2–1, this type, too, has been in use as a refrigeration machine in the higher output range for some time. The application for heating detached houses and two-family houses is currently under development. The technical effort is comparatively high due to the need for a vacuum.
2
2
1
1
2
1
Heat exchanger with zeolite
Heat exchanger
Heat supply (e.g. burner)
Heat transfer to the heating system
Heat supply (environment)
Heat transfer to the heating system
Steam/Vapour
Steam/Vapour
Desorption phase
Adsorption phase
Desorption
In the first phase, the heat exchanger coated with a solid material (silica gel or zeolite) (1) receives heat generated by a burner or a solar thermal system. The water bound in the solid material is driven out (desorbed) through this heat application and flows to the second heat exchanger (2) in the form of vapour.
Condensing
In this phase, that heat exchanger acts as a condenser. It transfers the heat that is released through condensing the water vapour to the heating system.Heat supply ends when the zeolite has reached the required level of dryness. The bound water is fully evaporated and condensed on the second heat exchanger.
Evaporation
In the second phase, the heat exchanger (2) takes on the function of evaporator. Environmental energy is supplied via this heat exchanger until the water has evaporated completely.
Adsorption
The water vapour flows back to the coated heat exchanger (1) and is adsorbed there as water by the silica gel or zeolite. The heat dissipated by the solid material during this stage reaches the heating system via the heat exchanger. A complete period of this heat pump process has been completed as soon as the water vapour has been adsorbed fully.
46/47
generators, questions about the availability and affordability of the electricity required to power the compressor remain deep areas of concern.
This chapter deals with the factors that are crucial for assessing the feasibility of using heat pumps.
Today, many factors influence the decision as to whether to invest in the potential this new type of heating system has to offer. How futureproof is the decision for a certain type of fuel? Does the system meet all statutory requirements? Is the investment worthwhile when it comes to the expected operating costs?
These questions must also be able to be answered in connection with the use of a heat pump. Contrary to conventional heat
48 B.1 "Electrical power" as the driving energy
49 B.1.1 Power mix in Germany51 B.1.2 Security of supply53 B.1.3 Smart metering54 B.1.4 Heat pumps and photovoltaics55 B.1.5 Competition for electric power
56 B.2 Statutory framework conditions
57 B.2.1 Heat pumps in the EnEV59 B.2.2 Heat pumps in the Renewable Energies Heat Act [EEWärmeG]59 B.2.3 European framework directives
60 B.3 Economic considerations
B General conditions
Before investing in a heat pump system, customers are sure to want to go through a proper consultation phase. To advise them successfully, a simple understanding of how the appliance works is no longer enough – greater expertise is required.
B.1 "Electrical power" as the driving energy
The utilisation of fossil fuels, which have provided us with heat over the past 100 years, is now in transition.
Effects on our climate, reducing availability and the rising costs of gas, oil and coal have contributed to the fact that solar energy and biomass, and now heat pumps, have become a permanent fixture in the portfolio and not only in the German heating technology sector. The number of heat pumps as a proportion of the heat generators installed each year in Germany has been on the rise since 1990.
"Electrical power" as the driving energy
For heat pumps with an electrical drive, power consumption is a key factor. The following chapter describes the way this subject should be correctly addressed.
48/49
Fig. B.1–1 The market trend for heat pumps
Fig. B1.11 Gross power generation 2009 in Germany
Sales figures indicate that the heat pump market is subject to fluctuations due to external influences that either encourage or retard its development (just as with solar thermal and biomass systems). Heat pumps are still not seen as an obvious choice, but rather as an exception to the rule. Many potential investors are put off by their lack of familiarity with the technology, as well as the general public perception of heat pumps as "electric heating systems". This uncertainty in coming to judgement is equally prevalent amongst public bodies and authorities. For example, it took seven years following the start of the market incentive scheme (MAP) initiated by the Federal government [of Germany], before heat pumps received subsidies, in other words before they were accepted as "renewables". For heat pump technology to succeed in the market it is necessary to address the subject of "heat pumps and electricity".
B.1.1 Power mix in Germany
In Germany, power is predominantly generated in condensing power stations – primarily coal fired or nuclear. Although the proportion of renewables, such as hydro-electric power, wind power and photovoltaics is on the increase, at only 18 percent, its contribution to the German power mix is still small.
This figure is at the root of one of the most important prejudices against the use of electricity in the heating market. It seems counter-intuitive to generate electricity by heat in a coal fired or nuclear power station with its associated low levels of efficiency, in order to reconvert this into heat in a building.
This objection is fully justified when it comes to electrical resistance heaters (e.g. night storage heaters), but not to heat pumps. Apart from the electrical auxiliary energy (e.g. circulation pumps), the heat pump only uses electrical power to drive the compressor. It is only the consumption of this amount of electricity that differentiates the heat pump
20102005200019951990198519800
20 000
40 000
60 000
Lignite
Nuclear energy
Renewables
Wind
Biomass
Water
PhotovoltaicHousehold waste
Anthracite
Natural gas
24 %
23 %
13 %41 %
27 %
20 %
7 %5 %
18 %
16 %
6 %
597 billionkWh
Fuel oil and misc.
Heat pumps experienced their first
successful phase around 1980 as a
result of the oil crisis. Stronger
market growth later on can be linked
to the rise in oil prices since 2000.
With the increasing proportion of
renewables in the power generation
mix in Germany, the ecological
quality of electricity improves – in
other words heat pump operation is
becoming ever "greener".
from conventional combustion technology and solar thermal systems.
The power consumption of heat pumps is, nevertheless, frequently used as a blanket argument against this technology; consequently a detailed consideration of this subject is appropriate.
Two factors are, therefore, highly relevant when assessing the energy facts concerning heat pumps and their comparability with alternative heat generators:
What is the ratio between expended power and the heating energy yielded from its deployment (seasonal performance factor)?
How is the electricity used to be assessed from an energy point of view?
To answer the second question, we need the primary energy factor determined by the legislature. This stipulates how electricity (as well as gas, oil and wood) should be assessed in primary energy terms (see Fig. B.1.1–2).
To calculate the primary energy factor of all electricity generated in Germany, a power station mix is applied, in other words an average for all types of generation.
The primary energy factor has been reduced twice since the introduction of the Energy Saving Ordinance (EnEV) in 2000, in other words, it has been adjusted to the average power generating structure in Germany. This reflects increasing efficiencies in generation, but it largely indicates the increasing proportion of power generated from renewables.
The constantly increasing proportion of power generated from renewable sources of primary energy in the power mix will continue to lower the primary energy factor, that is, it will make heat pump operation more "green".
B.1 "Electrical power" as the driving energy
Fig. B.1.1–2 Primary energy factor
Power generation in an average
condensing power station
Primary energy used 100 %
available electrical energy 38 % heat loss in coolant 54 % flue gas losses 8 %
Dividing the primary energy expended by the available electrical power results in the factor used to assess the primary energy of the generated electricity.
In this case, the primary energy factor is as follows: 100/38 = 2.6
Electrical energy
Energy in exhaust gas
8 %
54 %
38 %
Energy in coolant
100 %
50/51
B.1.2 Security of supply
The power supply system in Germany is one of the most reliable in the world. The high security of supply is, therefore, a relevant variable for the decision making process that speaks for or against the use of a heat pump – not least because the operation of most other heat generators in buildings also depends on electrical power (pumps, controllers, etc.).
In the endeavour to expand the application of heat pump technology it is important that a reliable, sustainable and affordable supply of electricity can be assured in the long term.
Fig. B.1.2–1 Monthly proportions of the annual consumption of power and heat (EFH sector)
Fig. B.1.2–2 Power from wind generation fed into the grid over the year
Pro
po
rtio
n o
f an
nu
al c
on
sum
pti
on
hea
t (%
)
Pro
po
rtio
n o
f an
nu
al c
on
sum
pti
on
pow
er (
%)
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec0
10
5
15
20
8
6
10
12
Heat Power
Pro
po
rtio
n o
f an
nu
al g
ener
atio
n (
%)
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec0
6
9
3
12
15
The growing proportion of wind
energy in power generation makes
the use of heat pumps for
generating heat ever more
appropriate, as generation and
consumption curves in the winter
months increasingly converge.
More and more heat pumps are
used as heat generators,
consequently increasing the power
demand in winter.
Heat pumps consume most power during the heating season. This makes for an excellent "fit" between the heat pump demand profile (relative to the required amount of electricity) and the generation profile of wind power systems, for example.
For heat pumps to find wider acceptance it is relevant whether their operation further increases load peaks in the grid or whether the system can be regulated so that it can be supplied with power at times of low demand.
When considering the typical power load curve for a single day (see Fig. B1.2–3) it is easy to recognise that the supply system experiences its peak (relative to the grid and power generation) during the middle of the day. During this time, power tariffs paid by the power supply utilities to the power exchange, are also at their peak.
This situation forms the background to the special heat pump power tariffs and the associated "power-OFF times" [in Germany]. Power supply utilities now sell electricity to their customers more cheaply during the low load times of the day. In return, they temporarily cut off the power supply to heat pumps during certain short periods.
This commercial approach also has technical consequences, for if, as a result of careful planning, the machines can operate outside the peak load times, then the daily load profile of the grid will be balanced.
Fig. B.1.2–3 Typical daily load profile in the power grid
0:00 2:00 4:00 6:00 8:00 10:00 12:00 14:00 16:00 18:00 20:00 22:00 24:00
75
50
25
0
100
Time of day
Load
pro
file
(%
)
To balance the daily load profile,
power supply utilities offer special
heat pump tariffs – with favourable
electricity tariffs at low load times
and short "power-OFF" times during
load peaks.
B.1 "Electrical power" as the driving energy
52/53
B.1.3 Smart metering
The rising proportion of power generated from renewables in the power mix requires ever more intelligent control of supply and demand. Smart metering aims to advance this control and to achieve the described "smoothing" of the load profile in power consumption. In addition, generation peaks from wind and solar power should be brought to suitable consumers in an appropriate way.
Now, smart metering ensures that the power supply increasingly determines power consumption and not – as happened until recently – that supply follows demand. The latter becomes increasingly difficult with increasing generation capacity, particularly from wind and solar power installations.
Heat pumps will play an ever more important role in this complex and fundamental restructuring of the power grid. There are many consumers that, with little technical effort, could be dovetailed into this system. For example, freezers can be switched off for several hours – insulation commonplace today prevents any critical temperature increase.
Without intelligent load management it would be pure coincidence whether an appliance switches its load to the power grid during peak times or not. However, if the appliance "knows" that there is a glut of energy right now, it could switch itself on. For freezers this means that it lowers the internal temperature a few degrees below the set value. This provides a buffer for a longer period when no power needs to be drawn.
Switching a heat pump follows a similar pattern. Possible overshoots or undershoots of the room temperature (during heating and cooling), appropriate sizing of buffer cylinders and a modulating operation, open up the possibility of linking heat pumps efficiently into an intelligent power grid.
B.1.4 Heat pumps and photovoltaics
It seems an obvious choice to install a photovoltaic system in conjunction with a heat pump. The PV system could then generate the amount of power consumed for heating the building during the year – in other words heating by heat pump without CO2 emissions.
In spite of the obvious imbalance between PV power generation (focus in the summer months) and heat consumption (focus in the winter months) shown in Fig. B.1.4–2, linking a heat pump and photovoltaic system is a sensible decision when considering the annual energy statement.
The more the power grid, advances, the better the it will be able to absorb seasonal fluctuations in power generation and distribution, and the less important will be the simultaneity of generation and consumption. The energetic assessment of a heat pump improves under this aspect, as it does when taking the changes in the power mix into account.
Fig. B.1.4–2 Monthly proportion of the annual heat consumption and PV power generation
Fig. B.1.4–1 Photovoltaic systems
Taking the annual energy statement into consideration, the linking of
a heat pump and PV system is a sensible decision.
Pro
po
rtio
n o
f an
nu
al c
on
sum
pti
on
hea
t (%
)
Pro
po
rtio
n o
f an
nu
al P
V p
ower
gen
erat
ion
(%
)
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec0
10
5
15
20
0
10
5
15
20
Heat (detached houses, existing) PV generation (Federal average)
B.1 "Electrical power" as the driving energy
54/55
Source: Bundesministerium für Wirtschaft und Technologie, 27/08/10 / "Energieszenarien für einEnergiekonzept der Bundesregierung - Szenario II A"
Nuclear energy
Anthracite
Lignite
Mineral oil
Natural gas
Miscellaneous Renewables
Source: AG Energiebilanzen, 23/02/11
22 %
33 % 11 %
12 %
11 %
10 %
2010
8 %
16 %
20 %
1 %
6 %
50 %2050
1 %
B.1.5 Competition for electric power
Within the context of the utilisation of electricity in heat pumps, the question frequently arises as to whether the use of power would not be more sensible in other energy sectors, in other words whether – ecologically speaking – better effects could not be achieved, for example in the use of electricity to provide mobility.
This discussion misses the point for the following reasons: All considerations on the future of energy provision take a very long view, some as far ahead as 2050 or the end of this century. Such considerations are necessary in order to be able to pave the way appropriately now for future developments. Most of these considerations result in our energy demand being covered either exclusively or at least predominantly by renewables at the end of the relevant period under consideration. In addition, rough estimates provide indicators as to the percental contribution likely to be made by the individual renewable primary energy sources. What these considerations cannot deliver is a detailed forecast as to the way in which the respective fuel types will make this contribution.
The question must therefore be asked in each case where energy is being consumed, where the potential for energy savings lie and which energy source is the most appropriate for covering the remaining demand. If we were to try and determine today the precise nature of consumption and generation mix and consequently also the technology mix 30 to 40 years ahead, technical progress would more likely be hindered rather than driven forward. For example, biomass can be combusted, liquefied or converted into power. Power generated from renewables can be consumed, stored centrally or in a consumer (vehicle battery or building heated by a heat
pump). Although storage and conversion will inevitably lead to lower efficiency, they are unavoidable for any realistic scenario.
We don't currently know where particular forms of energy will be available. In the building sector only time will be able to provide an answer to the following question: Which heat generator offers – relative to the actual project – the highest primary energetic efficiency? With this in mind, the heat pump will play a very important role.
Fig. B.1.5–1 Energy generation in the future
In Germany, the primary energy consumption in 2010 was 14,000 Petajoule (PJ) and is forecast for 2050 with
7000 PJ. The forecast for 2050 was produced on behalf of the Federal Ministry of Economics and Technology.
B.2 Statutory framework conditions
In Germany, the energy consumption of buildings accounts for approximately 40 % of total energy consumption. Consequently, this sector is highly important to the energy-political measures introduced by federal and regional governments. As a result, the German heating technology market is increasingly influenced by statutory framework conditions.
Statutory framework conditions
EnEV, Heating Act and Energy Label: The efficiency and linking of renewables in heat generation are also increasingly subject to statutory framework conditions. In this connection, heat pumps offer many benefits.
56/57
Fig. B.2.1–1 Heating energy demand in buildings (standard for the year of construction)
Fig. B.2.1–3 Primary energy factors
Hea
t d
eman
d (
kWh
/m²a
)
Year of build
1900
50
0
100
150
200
250
2000 20501950
B.2.1 Heat pumps in the EnEV
In 2002, [in Germany] previously appli