+ All Categories
Home > Documents > 00897129

00897129

Date post: 01-Jun-2018
Category:
Upload: christos-apostolopoulos
View: 216 times
Download: 0 times
Share this document with a friend

of 6

Transcript
  • 8/9/2019 00897129

    1/6

    Zero-sequence components in unit-connected generator

    with ungrounded neutral during ground-faults

    M.Fulczyk

    ABB Corporate

    Research

    Krakbw.

    Poland

    Abstract: An analysis of voltage zero-sequence components in

    generator during normal operation (pre-fault conditions) and during

    ground-faults in stator winding of generato r with ungrounded

    neutral is presented. The changes in voltage zero-sequence

    components of fundamental frequency and

    3d

    harmonic during

    generator pre-fault conditions, ground-faults in generator stator

    winding and ground-faults in power system are shown. The analysis

    was done for generator with ungrounded neutral for different values

    of the generator and main transformer parameters and additional

    capacitance to ground

    of

    the generator breakers. Different

    resistances of a breakdown channel and different locations

    of

    the

    ground-faults in the generator stator winding were considered in

    analysis. It has

    been

    found that

    in

    the generator with ungrounded

    neutral, the parameters of generator and transformer, additional

    capacitance to ground of the generator breakers, phase

    of

    interrupted

    arcing ground-fault (level of the fault resistance) and the ground-

    fault location have a substantial influence on the zero-sequence

    voltages feeding different generator protection systems. The voltage

    zero-sequence components

    in

    generator neutral and the distribution

    of 3d harmonic voltages in generator stator winding are determined

    mainly by a l l these parameters.

    Keywords: generators, grounding, protection, windings.

    I. INTRODUCTION

    The ground-faults in the g enerator stator windings a re very

    dangerous for the unit-connected generator. These faults are

    the most frequent causes of dam age

    to

    the stator winding of

    the unit-connected generator and also the direct cause of

    phase-to-phase faults. Faults that are not d etected can cause,

    that fault transforms into phase-to-phase fault what may

    immediately damage generator. The additional capacitance to

    ground of the generator breakers connected into the zero-

    sequence circuit of the unit-connected generator increases the

    value of ground-fault current.

    So

    high current values can

    cause very extensive damage to the generator magnetic

    circuit. Therefore it is necessary to reduce or even totally

    eliminate such dangers. To ensure maximum safety for the

    generator stator magnetic circuit, a system grounding the

    generator neutral should operate with a ground-fault

    protection covering 100 of the ge nera tor stator windings.

    Considering the results of investigations of the ground-

    fault processes and the results of analysis of failures of

    currently used unit-connected gen erators it is thought that the

    ground-fault protections of the stator windings should detect

    ground-faults at any point of the winding, including the

    generator neutral [1,2,3]. Moreover, in order to m inimise the

    possibility of improper operation

    of

    the generator ground-

    fault protection system, the particular types of protections

    forming this system should use different excitation

    parameters [4,5,6]. Additionally it would ensure maximum

    redundancy in protection for th e generator stator.

    By influencing the parameters of the sy stem grounding the

    generator neutral it is possible to create conditions under

    which erosion of the magnetic circuit caused by a ground-

    fault arc is insignificant or is even totally eliminated and

    ground-fault overvoltages are not dangerous to the stator

    main insulation. Then the occurrence of phase-to-phase faults

    in the generator circuits, if the ground-fault protection

    operates property, is practically impossible.

    The grounding methods of the generator neutral and the

    capacitance to grou nd of the generator breakers can imp rove

    the operating conditions of the particular ground-fault

    protection schemes. Howev er these parameters influence the

    level of voltages and currents in generato r neutral and in the

    breakdown channel at ground-fault location. To ensure the

    proper operation of ground-fault protection schemes it is

    necessary to know the levels of these voltages and currents

    and to determine the relation between elements grounding

    neutral and voltages and c urrents feeding these systems.

    In this paper, the influen ce parameters of the generator and

    transformer, the additional capacitance to ground of the

    generator breakers on voltage and currents zero-sequence

    components in generator with ungrounded neutral was

    determined. The analysis of zero-sequence components was

    carried out for unit-connected gene rators of power up to 1110

    MVA.

    The voltage zero-sequence components feeding the

    measuring element of the protections were determined at

    ground faults along the whole length of the generator stator

    winding.

    Results of experimental studies of ground-fault

    phenomena, carried out in real conditions on the unit-

    connected generators, were taken into accou nt in the analysis.

    This refers mainly to the fault resistance of the breakdown

    channel in the main insulation of the generator stator

    windings during interrupted arcing ground-faults. The

    breakdown channel resistances in range from

    1052

    (the

    resistance in the quasi-galvanic phase of the ground-fault

    after carbonisation of the organic parts in the main insulation

    of the stator winding) to

    2k 2

    (the resistance of the ground-

    fault during first

    arc

    ignitions) were assumed in analysis

    W I

    II.

    GENERATOR-TRANSFORMER

    UNIT

    SCHEME

    The analysis of the zero-sequence voltages feeding the

    generator protection system s were carried out fo r a generator-

    transformer unit equipped with the additional capacitance to

    ground of ge nerator breakers and without this capacitance.

    0-7803-6338-8/00/$10.00(~)2000EEE

    83

  • 8/9/2019 00897129

    2/6

    The voltage zero-sequence compon ent feedin g the m easuring

    element of the generator protection system at a ground fault

    in the generato r stator and in power system were determined

    on the base of the system equivalent scheme shown in F ig.1.

    In

    this scheme the generator neutral is not connected with

    ground. The simplifications introduced into

    t h i s

    scheme do

    not have any significant effect on the voltages feeding the

    measuring element of the prote ction system.

    CT1-2

    Rg

    .

    Sche me of u nitconn ected generatorwth ungrounded neutral;

    G-equivalent phase capacitance of statorwndi ngto grou nd , C g c - p h a s e

    capacitanceto ground seen

    h m

    enerator erminal, C@-phase apacitance

    to

    groundof generator breaker,N-neutral, Rrfault resistan ce,

    CT,.Z-capacitance

    between

    low and high Windings

    of transformer,

    III.

    ZERO-SEQUENCE VOLTAGES

    IN

    GENERATOR

    A.

    Voltage zero-sequence com pone nt in generator neutral

    during faults in gen erator stator winding

    The voltage zero-sequence in generator neutral in

    primary

    winding of voltage transformer can be determined using the

    simplified equivalent scheme of the unit-connected gen erator

    shown in

    figure

    2.

    Fig.2 . Equivalent scheme of generator during ground-fault;; ,-generator

    phase voltage, x-lw ation of ground-faultin generator stator winding (01).

    U~ zemsequenceoltage in generator neutral,

    Zero-sequence component IJ ) in secondary winding of

    grounding transformer con nected in generator neutral (Fig.3)

    can

    be

    recalculated using formula (1).

    where:

    Un

    .B -

    ratio of grounding transformer

    (

    -

    .

    100

    &-

    Fig.3. Scheme of generator wth grounded neutral

    The effective value of the voltage zero-sequence component

    in generator neutral, when there is no element connected

    between generator neutral and groun d, during steady state of

    the ground-fault in stator winding after carbonisation of

    insulation organic parts is determined by follo wing relation:

    1

    R f +

    where:

    w

    -

    pulsation for fundamental frequency.

    It is seen from

    (2)

    that the voltage zero-sequence

    component in generator neutral depends only on the

    parametas of generator and parameter of elements seen from

    generator terminal (transformer, generator breaker and

    elements connected directly to the buses con necting generator

    and transformer). But it also significantly depends on the

    resistanc e of breakdown c hann el and ground-fault location in

    the stator winding. These zero-sequence components in

    secondary winding of grounding transformer are shown in

    Fig.4. For low fault resistance this voltage depends linearly

    on number of shorted coils during fault (fault location). In

    case of fault w ith h igher fault resistance

    this

    is also linear

    relation but maximum voltage reach only part of total zero-

    sequence component in generator.

    gmundfautt location [XI

    gmun&fault

    resistance

    [Ohm]

    832

  • 8/9/2019 00897129

    3/6

    ground-fault ocation [ I

    ooo-0

    ground-fault esistance [Ohm]

    c)

    generator capacitance

    IF]

    gmund-fault resistance [ Ohm]

    Hg.4. Voltage zero-sequence component n generator neutral during ground-

    fault in generator statorwinding; a) C .2

    p

    C e O

    @;

    b)C 8 . 6

    @,

    C .4 @; c) cgt=o.2 F,x= l

    During faults at particular locations in the stator winding the

    voltages take higher values in the systems with lower total

    capacitance to ground (Fig.4a,4b). For lower capacitance to

    ground the voltages in generator neutral de crease linearly as

    fault resistance increases, whereas for higher cap acitance this

    decreasing is not linear (Fi g.4 ~).

    B. Voltage zero-sequence component in generator neutral

    during faults in power system

    During faults in power system zero-sequence component

    may transform

    from

    power system to unit-connected

    generator through capac itance between winding of main

    transformer. The level of transformed voltage is determined

    by parameters of particular component forming this system.

    The voltage zero-sequence component in generator neutral

    during ground-fault in power system can be determined using

    the simplified equivalent scheme of the unit-connected

    generator shown in figu re 5

    Rg.5.

    Equivalent scheme of generator during ground-fault

    in

    power system;

    Uos-zero-sequencevoltage

    in

    power system recalculated

    to

    gener tor

    voltage, Uw-z ereseque nce voltagein generator neutral

    The value of the voltage zero-sequence component in

    generator neutral during faults in power system through low

    resistance can be determined using following relation:

    After some sim plification can be transformed to following

    form:

    Then the zero-sequence component in generator neutral

    transformed from power system is given per units in relation

    to the zero-sequence voltage at fault location in power system

    recalculated to generator level.

    It is clearly seen from (4) that in the generator with

    ungrounded neutral the voltage zero-sequence component in

    generator neutral durin g faults in power system depends only

    on the capacitance to ground of generator, transformer,

    generator breaker and elements connected directly to the

    buses connecting generator and transformer.

    These zero-sequence com ponen ts in generator neutral

    are

    show n in Fig.6. For lower capacitance to ground of generator

    the zero-sequence voltages take higher values. Influence

    of

    capacita nce between windings of main transformer is more

    visible in genera tors with low er capacitanc e to ground

    equipped with generator breaker without additional

    cap acit anc e to groun d Oi;ig.6a, 6b). In gene rato rs with hi ghe r

    capacitance to ground

    of

    stator winding the additional

    capacita nce to ground of generator breakers do not influence

    analysed phenomena (Fig.6b). Zero-sequence component in

    generator with ungrounded neutral transformed from power

    system during faults in this system assumes the lowest values

    in generators with high ca pacitanc e to ground of stator

    winding and additional capac itance to ground of generator

    break ers (Fig.6b).

    833

  • 8/9/2019 00897129

    4/6

    I

    breaker capacitance

    F1

    transformator capacitance [F]

    4 0.5

    Y 1u

    transformator capacdance [F]

    Hg.6. Voltage mo-sequence

    in

    generator neutral during ground-fault n

    power

    system;

    a)

    C d . 2

    pF,

    b) w . 6 F

    x 10.

    breaker capscdance

    [F]

    C .

    Third harm onic voltage in generator neutral

    In the unit-connected generator the total 3rd harmonic

    phase voltage between the generator neutral and generator

    terminals is a vector s u m of the voltages induced in the

    particular bars of a one pha se of the g enerator stator winding.

    Because the g enerator current influences the resolution of the

    curve of the magnetic induction in the generator air-gap, the

    3rd harmonic voltages also change in adequate proportions

    with changes in generator load [6,7,8]. The third harmonic

    voltages in gener ator neutral and a t generator terminals were^

    determined on the base of detailed analysis of the 3rd

    harmonic voltag e distribution in the generator stator windings

    [3,4]. The analysis was made using an equivalent scheme of

    the unit-connected generator for third harmonic component

    during pre-fault conditions and during ground-faults in the

    stator winding (fig.7). The voltages in generator neutral and

    at its terminal during generator normal operation (pre-fault

    conditions) and during gro und -faults in stator winding were

    analysed considering all param eters of the unitconnected

    generator having a significant effect on the value of the

    voltage 3rd harmonics. Figure 7 shows the simplified real

    distribution of 3rd harmonic voltage vectors in the generator

    stator winding during pre-fault conditions and during ground

    fault in stator winding at point x through fault admittance

    L

    Hg.7 Equivalent scheme of un itcamaected generator for

    3rd

    harmonic and

    distributionof voltage 3rd harmonic vectors in generator stator; a ) during

    normal

    operation

    b) during ground -fault at point x; Emi-total3rd

    harmonic

    voltage betw een neutral and termnals E3n-voltages 3rd harmonic

    between neutral and fault locatio n and between fault location and terminals,

    Ym, Yn-admittauce

    in

    neutral and at

    terminals

    Yrfault adm ittance at

    ground-fault ocation, N,T-generator neutral and

    terminal.

    The equivalent admittance Y N 3 and

    Y n

    of fault admittance

    connected in generator neutral and at generator terminals can

    be evaluated using the fo llowing relations:

    1

    3

    xT3y G f

    +j(2w3c,

    - 3 c z

    6)

    where:

    G -ph ase conductance of g enerator stator winding,

    - pulsation for 3Tdarmonic.

    When determining the 3rd harmonic voltages between

    generator neutral and ground-fault locationx (or ground

    z

    it

    is necessary to take into co nsideration the real resolution of

    t h i s

    voltage along the stator winding and non-linear

    dependence on the number of shorted coils [3,4,7]. Therefo re

    admittances of breakdown channel which are splinted into

    two separated equivalent admittances

    (YN3f

    and

    Ymf)

    can be

    calculatedfrom he follow ing equations:

    Y N 3 f =[1-k(x)I.Y,

    9

    x3Tf = d X ) - x f 9 7)

    where:

    k-coefficient reflecting non-linear distribution of 3d harmonic

    in generator stator winding:

    834

  • 8/9/2019 00897129

    5/6

    0 x 5

    0.5

    0.5

    .

    8)

    - x) =

    p 2 5 (1

    -

    ix'2n)

    0.25. (3 eJ'Xzn)

    1) generator normal operation (p re-fau lt conditions)

    The relative value of the third harmonic voltages during

    generator normal operation were determined in relation

    to

    the

    total third harmonic voltage induced in generator stator

    winding which is represented by

    U

    voltage between

    generator neutral and terminals. The relative value of the

    voltages U,, in generator neutral dur ing pre-fault conditions

    can be determined using formula:

    In Fig.8 the voltage

    3d

    harmonic in generator neutral during

    normal operation (pre-fault conditions) for different

    capacitance to ground of generator stator winding insulation

    and capacitance to ground of generator breaker is shown. It is

    clearly seen that in generator without fault the

    3d

    harmonic

    voltage in generator neutral is higher then 50% of total

    3d harmonic voltage induced in generator stator windings.

    Additionally it can be noticed that capacitance to ground of

    the generator breakers increases this voltage for any

    generator, but this influence is m ore visible for the generators

    with lower capacitan ce to ground of the stator winding

    insulation (Fig.8).

    1

    7 0 8

    -

    .-

    f O

    g 0.4

    m

    0.2

    0

    breaker

    capacltance [Fl

    10

    generator capacltance

    [FI

    Fig.8. Voltage

    3d

    harmonicin

    generator neutral during normal operation

    2) ground-fault in stator winding (fault conditions)

    During faults in th e generator stator the distribution of 3d

    harmonic voltages is mainly influenced by th e fault resistance

    (admittance) at fault location. Then the 3d harmonic in stator

    winding between the generator neutral and fault location

    x

    (or

    ground Z was determined applying relation:

    In F ig 9 the voltage 3d harmon ic in the neutral of generator

    during ground faults along the whole length of the stator

    winding for different capacitance to ground of generator

    stator winding insulation and capacitance to ground of

    generator breaker is show n. For low fault resistan ce this

    voltage varies from minimum at faults close to the generator

    neutra l to maximum du ring ground faults at the terminals. At

    these faults 3d harmonic voltages in the generator neutral

    reach values of total 3d harmonic voltage induced in the

    generator stator winding. Th e fault resistan ce influences more

    significantly

    3d

    harmonic voltages in generators with lower

    capacitance to ground of stator winding insulation and

    without additional capacitan ce to ground of th e generator

    break ers (Fig.9).

    1

    -

    2 0 8

    -

    .-

    E 06

    0 4

    B

    0 2

    0

    2m

    m

    m

    m

    >

    '0 -

    fault location I

    ault

    resistance

    [Ohm]

    b)

    1

    3

    0.8

    a

    y

    f

    0.6

    E 0.4

    -

    L

    m

    m

    g 0.2

    0

    p m

    im

    0 -0 -

    fault

    location I

    ault resistance Ohm]

    Fig.9. Voltage

    3d

    harmonic

    in

    generatorneutral during faults;

    a) CF0.2P C g 4

    PEb) W 6PE d . 4 PF

    The 3d harmonic in generator neutral changes significantly

    during fault in stator winding. Fig.10 shows the absolute

    differe nce in voltages 3rd harmonic in generator neutral

    during normal operation and during fault in stator winding for

    differe nt capac itance to ground of generator stator and

    capac itance to ground of g enera tor breaker at different fault

    locatio ns and fault resistances. The maximum d ifferen ces in

    these voltages occur for low fault resistance in neutral of

    835

  • 8/9/2019 00897129

    6/6

    generator with higher stator capac itance to ground and

    equipped with the generator breakers with capacitance to

    ground. In such systems during faults till 20 of generator

    stator length these differences reach

    50

    of total

    3d harmonic voltage induced in ge nerato r stator (Fig.lOb).

    a)

    1

    -

    2o.e

    -

    0.6

    0 4

    c

    m

    -o

    2

    0

    0

    0

    fault location [ ]

    fault resistance [Ohm]

    b)

    1

    -

    2 0 8

    50 2

    -

    6 6

    0.4

    m

    0

    0

    0

    w

    faun location

    I

    fault resistance [Ohm]

    Rg.10. Absolute difference in voltages 3 harmonic in generator neutral

    during

    norm l

    operation and during ground-fault in generator;

    a) C ~ 0 . 2

    p

    &

    I@

    b) C .6

    p

    6 . 4

    V.

    CONCLUSIONS

    The zero-sequence voltage transformed from power

    system

    to

    generator during faults in power system takes

    higher values for generators with lower capacitance to

    ground. The minimum values are reached in the

    genera tors with high capa citance to ground of stator

    winding and additional capacitance to ground of the

    genera tor breakers.

    The

    3d

    harmonic voltag e in generator neutral depends on

    the capacitan ce to gro und of th e generator breakers and

    capacita nce to ground of the stator w inding insulation.

    The fault resistance in fluenc es more significantly neutral

    3d

    harmonic voltages in gene rators with lower stator

    capacita nce o ground and without additional capacitance

    to ground of the generator breakers. The change in the

    neutral 3d harmonic caused by fault takes maximum for

    low resistance fault in the neutral of generator with

    higher stator capa citance to ground and equipped with

    the generato r breakers with capacitance o ground.

    VI. REFERENCES

    J.W.Pope, A comparison

    of

    100% stator ground fault protection

    schemes for generator stator

    windings ZEEE Trmuction on Power

    Apparafus andSystems, vol. PAS-103, no.4. April 1984. pp.832-840.

    X.G.Ym, O.Malik, G.Hope., D.Chen, Adaptive ground fault

    protection schemes for turbogenerators based

    on third

    harmonic

    voltages,

    ZEEE Tr-ctzons on Power Del ive ry,

    ~01.5,

    no.2,

    1990,

    SShiwen, S.Binhua, Analysis of ground protection

    of

    unit connected

    generator using third harmonic,

    Fourth Znternational Conference on

    Developments

    UI

    ower Protection,

    Edinburgh, UK 1989, pp.254-258.

    W.W.Xie Xiaoping, Zxiling, New developments of third harmonic

    ground fault protection schemes

    for

    turbine-generator stator

    windings,

    Fourth Znternational Conference

    on

    Developments in

    Powe r System Protection,

    Edinburgh, UK 1989, pp. 250-253.

    MZelichowski., M.Fulczyk, Influence

    of

    voltage transformers on

    operating conditions of ground-fault protection system for unit-

    connected generator,

    Inremational

    ournal of

    Electric Power &

    Energy Systems, ~01.20, o .5,1998, pp.313-319.

    J. Basilesco, J. Taylor.

    Report

    on methods for earthing of generator

    step-up mansformer and generator winding neutrals as practised

    throughout the word. CIGRE. N0.121,pp.86-101,1988.

    M. Zelichowski. Erosion du circuit magnetique des stators de

    turbogeneratem pendant les courts-circuits a l terre. Revue

    Electricite.vol. IX o.12

    pp.

    226-234 980.

    G.W.Buckley, R.L.Schalke. Performance of

    third

    harmonic ground

    fault protection schemes for generator stator windings.

    IEEE

    saction on Power Apparatus and Systems, vol. PAS-100, No.7,

    pp. 595-603.

    pp. 3195-3202,1981.

    W IOGRAPHY

    In genera tor with ungrounded neutra l, the parameters of

    Marek Fulczyk (1968) received the M.Sc. and

    generator and transformer,

    additional capacitance

    to,

    Ph.D. degree in Elect~icalEngineering from the

    ground of th e generator breakers, fault resistance and the

    Wroclaw University of Technology, Poland in

    1993 and 1997, respectively.

    In

    1997 he joined

    groun d-fault location have a su bstantia l influence on the

    ABB Group

    as

    a research scientist. Now he is a

    zero-sequence componen ts in generator during pre-fault

    leader of Engineering Systems

    &

    Automation

    cond itions and during ground-faults.

    Group at ABB Corporate Research in Krak6w,

    The voltage zero-sequence component in generator

    Poland. His fields of interests include power

    system protection, voltage stability,

    neutral during faults in stator sig nificantly depe nds on

    collaborative technology, 3D mcdelling and

    the fault resistance and g round-fault location in the stator

    simulations

    of phenomena in power system.

    winding. For low fault resistance this voltage depends

    (ABB Corporate Research, Starowisha 13A,

    mainly linearly on fault locatio n, whereas for higher fault

    31-038 Krakow, Poland,

    resistance it depends

    also

    on the total capac itance to

    Phone 4 8 2 14295027,

    ground of th e system.

    Fax.

    8- 12 I4224906, E-mail:[email protected])

    .

    836