Date post: | 25-Oct-2015 |
Category: |
Documents |
Upload: | vo-thach-bao |
View: | 72 times |
Download: | 3 times |
24519/2 Te
TeSys motor starters - open version
Levels of service
The standard defines tests at different levels of current; the purpose of these tests is to place the equipmentin extreme conditions.The standard defines 2 types of coordination, according to the condition of the components after testing:iiiii type 1iiiii type 2
Type 1 coordination
Damage to the contactor and to the overload relay is permissible, provided that:- there is no risk for the operator,- components other than the contactor and the overload relay are not damaged.
Type 2 coordination
Slight welding of the contactor or starter contacts is permissible, provided that they can be easily separated.
After type 2 coordination tests, the control and protection equipment must be able to operate.
To ensure proper type 2 coordination, the standard requires 3 fault currenttests to be performed to check that the equipment is operating correctly underoverload and short-circuit conditions.
Current “Ic” (overload I < 10 In)The thermal overload relay provides protection against this type of fault, up toa value Ic (depending on Im) defined by the manufacturer.
Standard IEC 947-4-1 specifies the 2 tests to be performed to guaranteecoordination between the thermal overload relay and the short-circuit protec-tion device:- at 0.75 Ic only the thermal overload relay must trip,- at 1.25 Ic the short-circuit protection device must operate.
After the tests at 0.75 and 1.25 Ic, the tripping characteristics of the thermaloverload relays must remain unchanged.Type 2 coordination therefore increases reliability of operation.The contactor can close automatically after the fault has been eliminated.
Current “r” (low level short-circuit 10 < I < 50 In)The main cause of this type of fault is the deterioration of insinuating materials
Standard IEC 947-4-1 defines an intermediate short-circuit current “r”. Thistest current makes it possible to check whether the protection device isproviding protection against low-level short-circuits.
After the test, the contactor and the thermal overload relay must retain theiroriginal characteristics.The circuit-breaker must trip within a time ≤ 10 ms for a fault current ≥ 15 In.
Operational current Ie Current “r”(AC-3) (A) (kA)Ie ≤ 16 116 < Ie ≤ 63 363 < Ie ≤ 125 5125 < Ie ≤ 315 10315 < Ie ≤ 630 18
Current “Iq” (short-circuit > 50 In)This type of fault is relatively rare; it can be caused by a connection error duringmaintenance work. Short-circuit protection is provided by fast operatingdevices.Standard IEC 947-4-1 defines a current “Iq” that is generally ≥ 50 kA.This current “Iq” makes it possible to check coordination performance of thevarious devices in a motor supply line.
After this test under extreme conditions, all the coordinated devices mustremain operational.
c k In1 10 50In
t
0,75 Ic 1,25 IcIc Ir Iq
1
3 6
7
4
5
2
1 Motor thermal overload relay curve2 Fuse3 Reliability of operation4 Thermal limit of the circuit-breaker (MA)5 Thermal overload relay limit6 Circuit breaker compulsory trip7 Magnetic trip (MA)
Overload zone Short-circuit zoneLow-level short-circuitzone
Type 1 and type 2coordination accordingto the standard
24519/3Te
No coordination
Considerable risks to the operator, and also of physical injury and damage to equipment.Not authorised by standards:- NF C 15-100 article 133-1,- EN 60-204-1 article 1.1/4.2,- IEC 947-4-1 article 7.2.5.
Type 1 coordination
The most frequently used solution.Equipment costs are lower.Before restarting, it may be necessary to repair the motor starter; reliability of operation is not a requirement.Consequences :i significant amount of machine downtime,i skilled maintenance personnel required to repair, check, obtain supplies.
Example: air conditioning in commercial premises,...
Type 2 coordination
This solution ensures reliability of operation
Consequencesi reduced machine downtime,i simple operation.
Example: escalators,...
Total coordination
With this solution, no damage or misadjustment is permissible
Consequencesi immediate return to service,i no special precautions required.
Example : smoke extraction, fire-fighting pumps,...
Selection
X0009_Ver2.10-EN.fm/2 Schneider Electric
a.c. supply
starting,breaking.
plugging, inching
‘
d.c. supply
inductive or slightlyinductive loads
starting,counter-currentbraking, inching
starting,counter-currentbraking, inching
a.c. supply
d.c. supply
(1) The value 6 P (in watts) is based on practical observations and is considered to represent the majority of magneticloads up to the maximum limit of P = 50 W i.e. 6 P = 300 ms = L/R.Above this, the loads are made up of smaller loads in parallel. The value 300 ms is therefore a maximum limit whateverthe value of current drawn.
Contactors
Making and breaking conditions Making and breaking conditions(normal operation) (occasional operation)
Typical Utilisation Making Breaking Making Breakingapplications category I U cos ϕ I U cos ϕ I U cos ϕ I U cos ϕ
Resistors, non AC-1 Ie 1.05 Ue 0.8 Ie 1.05 Ue 0.8 1.5 Ie 1.05 Ue 0.8 1.5 Ie 1.05 Ue 0.8inductive or slightlyinductive loads
Motors
Slip ring motors: AC-2 2 Ie 1.05 Ue 0.65 2 Ie 1.05 Ue 0.65 4 Ie 1.05 Ue 0.65 4 Ie 1.05 Ue 0.65
Squirrel cage motors: AC-3starting, breaking le ≤ 100 A 2 Ie 1.05 Ue 0.45 2 Ie 1.05 Ue 0.45 10 Ie 1.05 Ue 0.45 8 Ie 1.05 Ue 0.45whilst motor running.
Ie > 100 A 2 Ie 1.05 Ue 0.35 2 Ie 1.05 Ue 0.35 10 Ie 1.05 Ue 0.35 8 Ie 1.05 Ue 0.35
Squirrel cage or slip AC-4ring motors: starting, le ≤ 100 A 6 Ie 1.05 Ue 0.45 6 Ie 1.05Ue 0.45 12 Ie 1.05 Ue 0.35 10 Ie 1.05 Ue 0.35
Ie > 100 A 6 Ie 1.05 Ue 0.35 6 Ie 1.05 Ue 0.35 12 Ie 1.05 Ue 0.35 10 Ie 1.05 Ue 0.35
Typical Utilisation Making Breaking Making Breakingapplications category I U L/R (ms) I U L/R (ms) I U L/R (ms) I U L/R (ms)
Resistors, non DC-1 Ie Ue 1 Ie Ue 1 1.5 Ie 1.05 Ue 1 1.5 Ie 1.05 Ue 1
Shunt wound motors: DC-3 2.5 Ie 1.05 Ue 2 2.5 Ie 1.05 Ue 2 4 Ie 1.05 Ue 2.5 4 Ie 1.05 Ue 2.5
Series would motors: DC-5 2.5 Ie 1.05 Ue 7.5 2.5 Ie 1.05 Ue 7.5 4 Ie 1.05 Ue 15 4 Ie 1.05 Ue 15
Auxiliary contacts and control relays
Making and breaking conditions Making and breaking conditions(normal operation) (occasional operation)
Typical Utilisation Making Breaking Making Breakingapplications category I U cos ϕ I U cos ϕ I U cos ϕ I U cos ϕ
Electromagnets- < 72 VA AC-14 6 Ie Ue 0.3 Ie Ue 0.3 6 Ie 1.1 Ue 0.7 6 Ie 1.1 Ue 0.7 - > 72 VA AC-15 10 Ie Ue 0.3 Ie Ue 0.3 10 Ie 1.1 Ue 0.3 10 Ie 1.1 Ue 0.3
Typical Utilisation Making Breaking Making Breakingapplications category I U L/R (ms) I U L/R (ms) I U L/R (ms) I U L/R (ms)
Electromagnets DC-13 Ie Ue 6 P Ie Ue 6 P 1.1 Ie 1.1 Ue 6 P Ie 1.1 Ue 6 P(1) (1) (1) (1)
Technical informationTests according to standard utilisation categoriesconforming to IEC 947based on rated operational current Ieand rated operational voltage Ue
X0009_Ver2.10-EN.fm/3Schneider Electric
U V W
(1) Values conforming to the NEC (National Electrical Code).
These values are given as a guide. They may vary depending on the type of motor and manufacturer.
3-phase 4-pole motors, 50/60 Hz
Power 200/ 433/ 500/ in volts 208 220 230 380 400 415 440 460 525 575 660 690 750 1000
(1) (1) (1)
kW HP A A A A A A A A A A A A A A0.37 0.5 2 1.8 2 1.03 0.98 – 0.99 1 1 0.8 0.6 – – 0.4
0.55 0.75 3 2.75 2.8 1.6 1.5 – 1.36 1.4 1.21 1.1 0.9 – – 0.60.75 1 3.8 3.5 3.6 2 1.9 2 1.68 1.8 1.5 1.4 1.1 – – 0.75
1.1 1.5 5 4.4 5.2 2.6 2.5 2.5 2.37 2.6 2 2.1 1.5 – – 11.5 2 6.8 6.1 6.8 3.5 3.4 3.5 3.06 3.4 2.6 2.7 2 – – 1.3
2.2 3 9.6 8.7 9.6 5 4.8 5 4.42 4.8 3.8 3.9 2.8 – – 1.93 – 12.6 11.5 – 6.6 6.3 6.5 5.77 – 5 – 3.8 3.5 – 2.5
– 5 – – 15.2 – – – – 7.6 – 6.1 – – – 34 – 16.2 14.5 – 8.5 8.1 8.4 7.9 – 6.5 – 4.9 4.9 – 3.3
5.5 7.5 22 20 22 11.5 11 11 10.4 11 9 9 6.6 6.7 – 4.57.5 10 28.8 27 28 15.5 14.8 14 13.7 14 12 11 6.9 9 – 6
9 – 36 32 – 18.5 18.1 17 16.9 – 13.9 – 10.6 10.5 – 711 15 42 39 42 22 21 21 20.1 21 18.4 17 14 12.1 11 9
15 20 57 52 54 30 28.5 28 26.5 27 23 22 17.3 16.5 15 1218.5 25 70 64 68 37 35 35 32.8 34 28.5 27 21.9 20.2 18.5 14.5
22 30 84 75 80 44 42 40 39 40 33 32 25.4 24.2 22 1730 40 114 103 104 60 57 55 51.5 52 45 41 54.6 33 30 23
37 50 138 126 130 72 69 66 64 65 55 52 42 40 36 2845 60 162 150 154 85 81 80 76 77 65 62 49 46.8 42 33
55 75 200 182 192 105 100 100 90 96 80 77 61 58 52 4075 100 270 240 248 138 131 135 125 124 105 99 82 75.7 69 53
90 125 330 295 312 170 162 165 146 156 129 125 98 94 85 65110 150 400 356 360 205 195 200 178 180 156 144 118 113 103 78
132 – 480 425 – 245 233 240 215 – 187 – 140 135 123 90– 200 520 472 480 273 222 260 236 240 207 192 152 – 136 100
160 – 560 520 – 300 285 280 256 – 220 – 170 165 150 115– 250 – – 600 – – – – 300 – 240 200 – – 138
200 – 680 626 – 370 352 340 321 – 281 – 215 203 185 150220 300 770 700 720 408 388 385 353 360 310 288 235 224 204 160
250 350 850 800 840 460 437 425 401 420 360 336 274 253 230 200280 – – – – 528 – – – – – – – – – 220
315 – 1070 990 – 584 555 535 505 – 445 – 337 321 292 239– 450 – – 1080 – – – – 540 – 432 – – – 250
355 – – 1150 – 635 605 580 549 – 500 – 370 350 318 262– 500 – – 1200 – – – – 600 – 480 – – – 273
400 – – 1250 – 710 675 650 611 – 540 – 410 390 356 288450 600 – – 1440 – – – – 720 – 576 – – – 320
500 – – 1570 – 900 855 820 780 – 680 – 515 494 450 350560 – – 1760 – 1000 950 920 870 – 760 – 575 549 500 380
630 – – 1980 – 1100 1045 1020 965 – 850 – 645 605 550 425710 – – – – 1260 1200 1140 1075 – 960 – 725 694 630 480
800 1090 – – – 1450 – 1320 1250 – 1100 – 830 790 – 550900 1220 – – – 1610 – 1470 1390 – 1220 – 925 880 – 610
Technical informationAverage full-load currents of 3-phase squirrel cage motors
24539_Ver3.20-EN.fm/2 Schneider Electric
TeSys motor starters - open version 1
D.O.L. starters with circuit-breakerand overload protection built into the circuit-breaker
0.06 to 110 kW at 400/415 V: type 1 coordination
Standard power ratings of 3-phase Circuit-breaker Contactormotors 50/60 Hz in category AC-3 Reference Setting Reference400/415 V 440 V 500 V (2) range ofP Ie Iq (1) P Ie Iq (1) P Ie Iq (1) thermal tripskW A kA kW A kA kW A kA A
0.06 0.22 50 0.06 0.19 50 – – – GV2-ME02 0.16…0.25 LC1-K06 or LC1-D090.09 0.28 50
0.09 0.36 50 0.12 0.37 50 – – – GV2-ME03 0.25…0.40 LC1-K06 or LC1-D090.12 0.42 50 – – – – – –0.18 0.6 50 0.18 0.55 50 – – – GV2-ME04 0.40…0.63 LC1-K06 or LC1-D090.25 0.88 50 0.25 0.76 50 – – –0.37 0.98 50 0.37 0.99 50 – – – GV2-ME05 0.63…1 LC1-K06 or LC1-D09– – – – – – 0.37 1 500.55 1.5 50 0.55 1.36 50 0.55 1.21 50 GV2-ME06 1…1.6 LC1-K06 or LC1-D09
– – – – – – 0.75 1.5 50 GV2-ME06 1…1.6 LC1-K06 or LC1-D090.75 2 50 0.75 1.68 50 – – –– – – 1.1 2.37 50 1.1 2 50 GV2-ME07 1.6….2.5 LC1-K06 or LC1-D091.1 2.5 50 – – – 1.5 2.6 501.5 3.5 50 1.5 3.06 50 2.2 3.8 50 GV2-ME08 2.5…4 LC1-K06 or LC1-D092.2 5 50 2.2 4.42 50 – – –– – – 3 5.77 50 3 5 50 GV2-ME10 4…6.3 LC1-K06 or LC1-D093 6.5 50 – – – 4 6.5 104 8.4 50 4 7.9 15 5.5 9 10 GV2-ME14 6…10 LC1-K09 or LC1-D09
5.5 11 15 5.5 10.4 8 7.5 12 6 GV2-ME16 9…14 LC1-K12 or LC1-D127.5 14.8 15 7.5 13.7 8 9 13.9 6– – – 9 16.9 8 – – – GV2-ME20 13…18 LC1-D18
9 18.1 15 11 20.1 6 11 18.4 4 GV2-ME21 17…23 LC1-D25
11 21 15 – – – 15 23 4 GV2-ME22 20…25 LC1-D25
15 28.5 10 15 26.5 6 18.5 28.5 4 GV2-ME32 24…32 LC1-D32
18.5 35 35 18.5 32.8 25 18.5 28.5 8 GV3-ME40 25…40 LC1-D38
– – – 22 39 25 22 33 8 GV3-ME40 25…40 LC1-D40
22 42 35 – – – 30 45 8 GV3-ME63 40…63 LC1-D50
30 57 35 30 51.5 25 37 55 8 GV3-ME63 40…63 LC1-D65
– – – 37 64 10 45 65 4 GV3-ME80 56…80 LC1-D65
– – – 37 64 25 45 65 18 GV7-RE80 48…80 LC1-D65
37 69 15 45 76 10 55 80 4 GV3-ME80 56…80 LC1-D80
37 69 25 45 76 25 55 80 18 GV7-RE80 48…80 LC1-D80
45 81 25 – – – – – – GV7-RE100 60…100 LC1-D95
– – – 50 90 25 – – – GV7-RE100 60…100 LC1-D115
55 100 25 – – – 75 105 30 GV7-RE150 90…150 LC1-D115
75 135 35 75 125 35 90 129 30 GV7-RE150 90…150 LC1-D150
– – – 90 146 35 – – – GV7-RE150 90…150 LC1-F185
90 165 35 – – – 110 156 30 GV7-RE220 132…220 LC1-F185– – – – – – 132 187 30– – – 110 178 35 160 220 30 GV7-RE220 132…220 LC1-F265
110 200 35 132 215 35 – – – GV7-RE220 132…220 LC1-F225(1) The breaking performance of circuit-breakers GV2-ME can be increased by adding a current limiter GV1-L3, see page 24509/5.(2) For reversing operation, replace the reference prefix LC1 by LC2.
Combinations for assembly by the customer
24539_Ver3.20-EN.fm/3Schneider Electric
TeSys motor starters - open version 1
D.O.L. starters with circuit-breakerand overload protection built into the circuit-breaker
0.06 to 110 kW at 400/415 V: type 2 coordination
Standard power ratings of 3-phase Circuit-breaker Contactormotors 50/60 Hz in category AC-3 Reference Setting Reference400/415 V 440 V 500 V (2) range of (3)P Ie Iq (1) P Ie Iq (1) P Ie Iq (1) thermal tripskW A kA kW A kA kW A kA A
0.06 0.22 130 0.06 0.19 130 – – – GV2-P02 or GV2-ME02 0.16…0.25 LC1-D09– – – 0.09 0.28 130 – – –0.09 0.36 130 0.12 0.37 130 – – – GV2-P03 or GV2-ME03 0.25…0.4 LC1-D090.12 0.42 130 – – – – – –0.18 0.6 130 0.18 0.55 130 – – – GV2-P04 or GV2-ME04 0.4…0.63 LC1-D090.25 0.88 130 0.25 0.76 130 – – –0.37 0.98 130 0.37 0.99 130 – – – GV2-P05 or GV2-ME05 0.63…1 LC1-D09– – – – – – 0.37 1 1300.55 1.5 130 0.55 1.36 130 0.55 1.21 130 GV2-P06 or GV2-ME06 1…1.6 LC1-D09
– – – – – – 0.75 1.5 130 GV2-P06 or GV2-ME06 1…1.6 LC1-D090.75 2 130 0.75 1.68 130 – – –– – – 1.1 2.37 130 1.1 2 130 GV2-P07 or GV2-ME07 1.6…2.5 LC1-D091.1 2.5 130 – – – 1.5 2.6 1301.5 3.5 130 1.5 3.06 130 2.2 3.8 130 GV2-P08 or GV2-ME08 2.5…4 LC1-D09– – – – – – – – –2.2 5 130 – – – – – – GV2-P10 or GV2-ME10 4…6.3 LC1-D09– – – 2.2 4.42 50 – – –– – – 3 5.77 50 3 5 50 GV2-ME10 4…6.3 LC1-D09– – – 2.2 4.42 130 – – –– – – 3 5.77 130 3 5 130 GV2-P10 4…6.3 LC1-D093 6.5 130 – – – – – –4 8.4 130 – – – – – – GV2-P14 or GV2-ME14 6…10 LC1-D09– – – 4 7.9 15 4 6.5 10– – – – – – 5.5 9 10 GV2-ME14 6…10 LC1-D09– – – – – – 4 6.5 50– – – 4 7.9 130 5.5 9 50 GV2-P14 6…10 LC1-D125.5 11 130 5.5 10.4 50 7.5 12 42– – – 7.5 13.7 50 9 13.9 42 GV2-P16 or GV2-ME16 9…14 LC1-D25
7.5 14.8 50 9 16.9 20 – – – GV2-P20 or GV2-ME20 13…18 LC1-D259 18.1 50 11 20.1 20 11 18.4 10 GV2-P21 or GV2-ME21 17…23 LC1-D25
11 21 50 – – – – – – GV2-P22 or GV2-ME22 20…25 LC1-D25– – – – – – 15 23 10 GV2-P22 20…25 LC1-D32
15 28.5 35 15 26.5 25 18.5 28.5 10 GV2-P32 or GV2-ME32 25…40 LC1-D3215 28.5 70 15 26.5 65 18.5 28.5 50 GV7-RS40 25…40 LC1-D4018.5 35 70 18.5 32.8 65 22 33 50 GV7-RS40 25…40 LC1-D40– – – 22 39 65 – – – GV7-RS40 25…40 LC1-D80
– – – – – – 30 45 50 GV7-RS50 30…50 LC1-D80– – – – – – 37 55 50 GV7-RS80 48…80 LC1-D80
22 42 70 – – – – – – GV7-RS50 30…50 LC1-D8030 57 70 30 51.5 65 – – – GV7-RS80 48…80 LC1-D80
37 69 70 37 64 65 – – – GV7-RS80 48…80 LC1-D80
– – – 45 76 65 – – – GV7-RS80 48…80 LC1-D80
– – – – – – 45 65 50 GV7-RS80 48…80 LC1-D115
– – – – – – 55 80 50 GV7-RS80 48…80 LC1-D11545 81 70 – – – – – –– – – 55 90 65 – – – GV7-RS100 60…100 LC1-D11555 100 70 75 125 65 – – –75 135 70 90 146 65 90 129 50 GV7-RS150 90…150 LC1-D150
90 165 70 110 178 65 110 156 50 GV7-RS220 132…220 LC1-F185
110 200 70 132 215 65 – – – GV7-RS220 132…220 LC1-F225– – – – – – 132 187 50– – – – – – 160 220 50 GV7-RS220 132…220 LC1-F265(1) The breaking performance of circuit-breakers GV2-P can be increased by adding a current limiter GV1-L3, see page 24509/5.(2) Combinations with circuit-breaker GV2-ME are type 2 coordinated only at 400/415 V and 440 V.(3) For reversing operation, replace the reference prefix LC1 by LC2.
Combinations for assembly by the customer
24540_Ver2.10-EN.fm/2 Schneider Electric
TeSys motor starters - open version 1
D.O.L. starters with circuit-breakerand overload protection by separate thermal overload relay
(1) Irm: magnetic trip setting current.(2) For reversing operation, replace the reference prefix LC1 by LC2.(3) Products marketed under the Merlin Gerin brand. Reference to be completed by replacing the () with the breaking performance code
0.06 to 250 kW at 400/415 V: type 1 coordination
Standard power ratings of 3-phase Circuit-breaker Contactor Thermal overload relaymotors 50/60 Hz in category AC-3 Reference Rat- Irm Reference Reference Setting400/415 V 440 V 500 V ing (1) (2) rangeP Ie Iq P Ie Iq P Ie IqkW A kA kW A kA kW A kA A A A0.06 0.22 50 0.06 0.19 50 – – – GV2-LE03 0.4 5 LC1-K06 LR2-K0302 0.16…0.23– – – 0.09 0.28 50 – – – GV2-LE03 0.4 5 LC1-K06 LR2-K0303 0.23…0.360.09 0.36 50 0.12 0.37 50 – – – GV2-LE03 0.4 5 LC1-K06 LR2-K0304 0.36…0.540.12 0.42 50 – – – GV2-LE04 0.63 8 LC1-K06 LR2-K0304 0.36…0.540.18 0.6 50 0.18 0.55 50 – – – GV2-LE04 0.63 8 LC1-K06 LR2-K0305 0.54…0.8– – – 0.25 0.76 50 – – – GV2-LE05 1 13 LC1-K06 LR2-K0305 0.54…0.80.25 0.88 50 – – – – – –0.37 1 50 0.37 1 50 0.37 1 50 GV2-LE05 1 13 LC1-K06 LR2-K0306 0.8…1.20.55 1.5 50 0.55 1.36 50 0.55 1.21 50– – – – – – 0.75 1.5 50 GV2-LE06 1.6 22.5 LC1-K06 LR2-K0307 1.2…1.8– – – 0.75 1.68 50 – – – GV2-LE07 2.5 33.5 LC1-K06 LR2-K0307 1.2…1.80.75 2 50 – – – – – –1.1 2.5 50 1.1 2.37 50 1.1 2 50 GV2-LE07 2.5 33.5 LC1-K06 LR2-K0308 1.8…2.61.5 3.5 50 1.5 3.06 50 1.5 2.6 50 GV2-LE08 4 51 LC1-K06 LR2-K0310 2.6…3.7– – – – – – 2.2 3.8 50 GV2-LE08 4 51 LC1-K06 LR2-K0312 3.7…5.52.2 5 50 2.2 4.4 50 3 5 50 GV2-LE10 6.3 78 LC1-K06 LR2-K0312 3.7…5.5– – – 3 5.77 50 – – – GV2-LE10 6.3 78 LC1-K06 LR2-K0314 5.5…8– – – 4 7.9 15 – – – GV2-LE14 10 138 LC1-K09 LR2-K0314 5.5…83 6.5 50 – – – 4 6.5 10 GV2-LE14 10 138 LC1-K09 LR2-K0314 5.5…84 8.4 50 – – – – – – GV2-LE14 10 138 LC1-K09 LR2-K0316 8…11.55.5 11 15 5.5 10.4 8 7.5 12 6 GV2-LE16 14 170 LC1-K12 LR2-K0321 10…14
7.5 13.7 8 9 13.9 6 GV2-LE16 14 170 LC1-D18 LRD-21 12…187.5 14.8 15 9 16.9 8 – – – GV2-LE20 18 223 LC1-D18 LRD-21 12…189 18.1 15 – – – 11 18.4 4 GV2-LE22 25 327 LC1-D25 LRD-22 16…2411 21 15 11 20.1 6 15 23 4 GV2-LE22 25 327 LC1-D25 LRD-22 16…2415 28.5 10 15 26.5 6 18.5 26.5 4 GV2-LE32 32 416 LC1-D32 LRD-32 23…3218.5 35 70 18.5 32.5 65 – – – NS80HMA 50 500 LC1-D38 LRD-35 30…38– – – – – – 22 33 25 NS80HMA 50 450 LC1-D40 LRD-3355 30…40– – – 22 39 65 – – – NS80HMA 50 650 LC1-D40 LRD-3357 37…5022 42 70 – – – 30 40 25 NS80HMA 50 650 LC1-D50 LRD-3357 37…5030 57 70 30 51.5 65 – – – NS80HMA 50 880 LC1-D65 LRD-3359 48…65– – – 37 64 65 37 55 25 NS80HMA 80 960 LC1-D65 LRD-3359 48…65– – – – – – 45 65 25 NS80HMA 80 960 LC1-D80 LRD-3361 55…7037 69 70 45 76 65 55 80 25 NS80HMA 80 1040 LC1-D80 LRD-3363 63…8045 81 (3) – – – – – – NS100MA (3) 100 1300 LC1-D95 LRD-3365 80…104– – – – – – 50 90 (3) NS100MA (3) 100 1200 LC1-D115 LRD-4365 80…104– – – – – – 75 105 (3) NS160MA (3) 150 1500 LC1-D115 LRD-4367 95…12055 100 (3) – – – – – – NS160MA (3) 150 1350 LC1-D115 LRD-4367 95…12075 135 (3) 75 125 (3) 90 129 (3) NS160MA (3) 150 1800 LC1-D150 LRD-4369 110…140– – – 90 146 (3) – – – NS160MA (3) 150 1950 LC1-F185 LR9-F5371 132…22090 165 (3) – – – 110 156 (3) NS250MA (3) 220 2200 LC1-F185 LR9-F5371 132…220110 200 (3) – – – – – – NS250MA (3) 220 2640 LC1-F225 LR9-F5371 132…220– – – 110 178 (3) – – – NS250MA (3) 220 2420 LC1-F225 LR9-F5371 132…220– – – – – – 132 187 (3) NS250MA (3) 220 2640 LC1-F265 LR9-F5371 132…220– – – 132 215 (3) – – – NS250MA (3) 220 2860 LC1-F265 LR9-F5371 132…220132 240 (3) – – – – – – NS400MA (3) 320 3200 LC1-F265 LR9-F7375 200…330– – – – – – 160 220 (3) NS400MA (3) 320 2860 LC1-F265 LR9-F7375 200…330– – – 160 256 (3) – – – NS400MA (3) 320 3520 LC1-F330 LR9-F7375 200…330160 285 (3) 200 321 (3) – – – NS400MA (3) 320 4160 LC1-F330 LR9-F7375 200…330– – – – – – 200 281 (3) NS400MA (3) 320 3840 LC1-F330 LR9-F7375 200…330– – – – – – 220 310 (3) NS400MA (3) 320 4160 LC1-F400 LR9-F7379 300…500200 352 (3) 220 353 (3) – – – NS630MA (3) 500 5000 LC1-F400 LR9-F7379 300…500– – – 250 401 (3) – – – NS630MA (3) 500 5550 LC1-F400 LR9-F7379 300…500– – – – – – 250 360 (3) NS630MA (3) 500 5000 LC1-F400 LR9-F7379 300…500220 388 (3) – – – – – – NS630MA (3) 500 5500 LC1-F400 LR9-F7379 300…500250 437 (3) 280 470 (3) 315 445 (3) NS630MA (3) 500 6000 LC1-F500 LR9-F7379 300…500– – – – – – 355 500 (3) NS630MA (3) 500 6500 LC1-F500 LR9-F7381 380…630
Breaking performance Iq (kA) NS100MA NS160MA and NS250MA NS400MA and NS630MA400/415 V 25 70 36 70 70 130440 V 25 65 35 65 65 130500 V 18 50 30 50 50 70660/690 V 8 10 8 10 20 35Code N H N H H L
Combinations for assembly by the customer
24540_Ver2.10-EN.fm/3Schneider Electric
TeSys motor starters - open version 1
D.O.L. starters with circuit-breakerand overload protection by separate thermal overload relay
(1) Irm: magnetic trip setting current.(2) For reversing operation, replace the reference prefix LC1 by LC2.(3) Products marketed under the Merlin Gerin brand. Reference to be completed by replacing the () with the breaking performance code: see page opposite.
0.06 to 250 kW at 400/415 V: type 2 coordination
Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 Circuit-breaker Contactor Thermal overload relay400/415 V 440 V 500 V Reference Rating Irm Reference Reference SettingP Ie Iq P Ie Iq P Ie Iq (1) (2) rangekW A kA kW A kA kW A kA A A A0.06 0.22 130 0.06 0.19 130 – – – GV2-L03 or LE03 0.4 5 LC1-D09 LRD-02 0.16…0.250.09 0.36 130 0.09 0.28 130 – – –– – – 0.12 0.37 130 – – – GV2-L03 or LE03 0.4 5 LC1-D09 LRD-03 0.25…0.400.12 0.42 130 0.12 0.37 130 – – –0.18 0.6 130 0.18 0.55 130 – – – GV2-L04 or LE04 0.63 8 LC1-D09 LRD-04 0.4…0.630.25 0.88 130 0.25 0.76 130 – – –0.37 0.98 130 0.37 0.99 130 – – – GV2-L05 or LE05 1 13 LC1-D09 LRD-05 0.63…1– – – 0.37 0.99 130 0.37 1 130 GV2-L05 or LE05 1 13 LC1-D09 LRD-06 1…1.70.55 1.6 130 – – – 0.55 1.21 130– – – 0.55 1.36 130 0.75 1.5 130 GV2-L06 or LE06 1.6 22.5 LC1-D09 LRD-06 1…1.70.75 2 130 0.75 1.68 130 1.1 2 130 GV2-L07 or LE07 2.5 33.5 LC1-D09 LRD-07 1.6…2.51.1 2.5 130 1.1 2.37 130 1.5 2.6 1301.5 3.5 130 – – – 2.2 3.8 130 GV2-L08 or LE08 4 51 LC1-D09 LRD-08 2.5…4– – – 1.5 3.06 130 – – – GV2-L08 or LE08 4 51 LC1-D09 LRD-10 4…62.2 5 130 – – – – – –– – – – – – 3 5 13 GV2-L10 or LE10 6.3 78 LC1-D09 LRD-10 4…6– – – 2.2 4.42 50 – – –– – – 3 5.77 50 3 5 50 GV2-LE10 6.3 78 LC1-D09 LRD-10 4…6– – – 2.2 4.42 130 – – –– – – 3 5.77 130 3 5 130 GV2-L10 6.3 78 LC1-D09 LRD-10 4…63 6.5 130 – – – – – – GV2-L14 or LE14 10 138 LC1-D09 LRD-12 5.5…8– – – – – – 4 6.5 10 GV2-LE14 10 138 LC1-D12 LRD-12 5.5…8– – – – – – 4 6.5 50 GV2-L14 10 138 LC1-D12 LRD-12 5.5…84 8.4 130 – – – – – – GV2-L14 or LE14 10 138 LC1-D09 LRD-14 7…10– – – 4 7.9 15 – – – GV2-LE14 10 138 LC1-D09 LRD-14 7…10– – – 4 7.9 130 – – – GV2-L14 10 138 LC1-D09 LRD-14 7…10– – – – – – 5.5 9 10 GV2-LE14 10 138 LC1-D09 LRD-14 7…10– – – – – – 5.5 9 50 GV2-L14 10 138 LC1-D09 LRD-14 7…105.5 11 130 5.5 10.4 50 7.5 12 42 GV2-L16 14 170 LC1-D25 LRD-16 9…13– – – 7.5 13.7 50 – – – GV2-L16 14 170 LC1-D25 LRD-21 12…187.5 14.8 50 9 16.9 20 9 13.9 42 GV2-L20 18 223 LC1-D25 LRD-21 12…189 18.1 50 – – – – – –11 21 50 11 20.1 20 – – – GV2-L22 25 327 LC1-D25 LRD-22 16…24– – – – – – 11 18.4 10– – – – – – 15 23 10 GV2-L22 25 327 LC1-D32 LRD-22 16…2415 28.5 50 15 26.5 20 18.5 28.5 10 GV2-L32 32 416 LC1-D40 LRD-3353 23…32– – – – – – 22 33 25 NS80HMA 50 450 LC1-D40 LRD-3353 23…3218.5 35 70 18.5 32.5 65 – – – NS80HMA 50 550 LC1-D40 LRD-3355 30…4022 42 70 22 39 65 30 45 25 NS80HMA 50 650 LC1-D50 LRD-3357 37…50– – – 30 51.5 65 – – –30 57 70 37 64 65 37 55 25 NS80HMA 80 880 LC1-D65 LRD-3359 48…65– – – – – – 37 55 (3) NS100MA (3) 100 880 LC1-D80 LRD-3359 48…65– – – – – – 45 65 (3) NS100MA (3) 100 960 LC1-D80 LRD-3361 55…7037 69 70 45 76 65 – – – NS80HMA 80 1000 LC1-D80 LRD-3363 63…80– – – – – – 55 80 (3) NS100MA (3) 100 1040 LC1-D80 LRD-3363 63…8045 81 (3) 55 90 (3) – – – NS100MA (3) 100 1300 LC1-D115 LR9-D5367 60…10055 100 (3) – – – – – – NS160MA (3) 150 1500 LC1-D115 LR9-D5369 90…150– – – – – – 75 105 (3) NS160MA (3) 150 1050 LC1-D115 LR9-D5369 90…15075 135 (3) 75 125 (3) – – – NS160MA (3) 150 1950 LC1-D150 LR9-D5369 90…150– – – 90 146 (3) – – – NS160MA (3) 150 1950 LC1-D150 LR9-D5369 90…150– – – – – – 90 129 (3) NS160MA (3) 150 1200 LC1-D150 LR9-D5369 90…15090 165 (3) 110 178 (3) – – – NS250MA (3) 220 2420 LC1-F185 LR9-F5371 132…220– – – – – – 110 156 (3) NS250MA (3) 220 1540 LC1-F185 LR9-F5371 132…220110 200 (3) – – – – – – NS250MA (3) 220 2860 LC1-F225 LR9-F5371 132…220– – – 132 215 (3) 132 187 (3) NS250MA (3) 220 2200 LC1-F265 LR9-F5371 132…220132 240 (3) 160 256 (3) – – – NS400MA (3) 320 3520 LC1-F265 LR9-F7375 200…330– – – – – – 160 220 (3) NS400MA (3) 320 2200 LC1-F265 LR9-F7375 200…330160 285 (3) – – – – – – NS400MA (3) 320 4000 LC1-F330 LR9-F7375 200…330– – – 200 321 (3) – – – NS400MA (3) 320 4000 LC1-F330 LR9-F7379 300…500– – – – – – 200 281 (3) NS400MA (3) 320 3500 LC1-F400 LR9-F7375 200…330– – – – – – 220 310 (3) NS400MA (3) 320 3500 LC1-F400 LR9-F7379 300…500– – – 220 353 (3) – – –200 352 (3) 250 401 (3) – – – NS630MA (3) 500 5500 LC1-F400 LR9-F7379 300…500– – – – – – 250 360 (3)– – – – – – 315 445 (3) NS630MA (3) 500 4500 LC1-F500 LR9-F7379 300…500220 388 (3) – – – – – –250 437 (3) – – – – – – NS630MA (3) 500 6250 LC1-F500 LR9-F7379 300…500– – – – – – 355 500 (3) NS630MA (3) 500 5000 LC1-F630 LR9-F7381 380…630
Combinations for assembly by the customer
24541_Ver3.11-EN.fm/2 Schneider Electric
TeSys motor starters - open version 1
D.O.L. starters with fuse protection (NF C or DIN fuses)
(1) For breaking under load, add a rotary switch disconnector.(2) For reversing operation, replace the reference prefix LC1 by LC2.(3) 400 V maximum.
0.06 to 55 kW at 400/415 V: type 1 coordination
Standard power ratings of 3-phase Fuse carrier (1) aM fuses Contactor Thermal overload relaymotors 50/60 Hz in category AC-3 (basic block) Size Rating Reference400/415 V 440 V 500 V Reference (2) Reference SettingP Ie P Ie P Ie rangekW A kW A kW A A A
0.06 0.22 0.06 0.19 – – LS1-D32 10 x 38 2 LC1-K06 LR2-K0302 0.16…0.23
– – 0.09 0.28 – – LS1-D32 10 x 38 2 LC1-K06 LR2-K0303 0.23…0.360.09 0.36 – – – –0.12 0.42 0.12 0.37 – – LS1-D32 10 x 38 2 LC1-K06 LR2-K0304 0.36…0.540.18 0.6 0.18 0.55 – –– – 0.25 0.76 – – LS1-D32 10 x 38 2 LC1-K06 LR2-K0305 0.54…0.80.25 0.88 – – – –0.37 1 0.37 1 0.37 1 LS1-D32 10 x 38 2 LC1-K06 LR2-K0306 0.8…1.20.55 1.5 0.55 1.36 0.55 1.21– – 0.75 1.68 0.75 1.5 LS1-D32 10 x 38 2 LC1-K06 LR2-K0307 1.2…1.80.75 2 – – 1.1 21.1 2.5 1.1 2.37 1.5 2.6 LS1-D32 10 x 38 4 LC1-K06 LR2-K0308 1.8…2.6
1.5 3.5 1.5 3.06 – – LS1-D32 10 x 38 4 LC1-K06 LR2-K0310 2.6…3.72.2 5 – – 2.2 3.8– – – – 3 5 LS1-D32 10 x 38 6 LC1-K06 LR2-K0312 3.7…5.5
– – 2.2 4.42 – – LS1-D32 10 x 38 8 LC1-K06 LR2-K0312 3.7…5.5
3 6.5 3 5.77 4 6.5 LS1-D32 10 x 38 8 LC1-K09 LR2-K0314 5.5…8
4 8.4 4 7.9 5.5 9 LS1-D32 10 x 38 12 LC1-K09 LR2-K0316 8…11.5
5.5 11 5.5 10.4 7.5 12 LS1-D32 10 x 38 16 LC1-K12 LR2-K0321 10…14
7.5 14.8 7.5 13.7 9 13.9 LS1-D32 10 x 38 16 LC1-D18 LRD-21 12…18
– – 9 16.9 – – LS1-D32 10 x 38 20 LC1-D25 LRD-21 12…189 18.1 – – 11 18.411 21 11 20.1 15 23 GK1-EK 14 x 51 25 LC1-D25 LRD-22 16…24
15 28.5 15 26.5 18.5 28.5 GK1-EK 14 x 51 32 LC1-D32 LRD-32 23…32
18.5 35 18.5 32.8 22 33 GK1-EK 14 x 51 40 LC1-D40 LRD-3355 30…40
22 42 22 39 30 45 GK1-FK 22 x 58 50 LC1-D50 LRD-3357 37…50
– – 30 51.5 – – GK1-FK 22 x 58 80 LC1-D50 LRD-3359 48…65
– – – – 37 55 GK1-FK 22 x 58 80 LC1-D65 LRD-3359 48…65
30 57 37 64 – – GK1-FK 22 x 58 80 LC1-D65 LRD-3361 55…70
– – – – 45 65 GK1-FK 22 x 58 80 LC1-D80 LRD-3361 55…70
37 (3) 69 45 76 – – GK1-FK 22 x 58 100 LC1-D80 LRD-3363 63…80
45 81 – – 55 80 GK1-FK 22 x 58 100 LC1-D95 LRD-3365 80…93
– – 55 90 – – GK1-FK 22 x 58 125 LC1-D115 LRD-4365 80…104
55 100 – – 75 105 GK1-FK 22 x 58 125 LC1-D115 LRD-4367 95…120
Combinations for assembly by the customer
24541_Ver3.11-EN.fm/3Schneider Electric
TeSys motor starters - open version 1
D.O.L. starters with fuse protection (NF C or DIN fuses)
(1) For reversing operation, replace the reference prefix LC1 by LC2.
0.06 to 315 kW at 400/415 V: type 2 coordination
Standard power ratings of 3-phase Switch-disconnector- aM fuses Contactor Thermal overload relaymotors 50/60 Hz in category AC-3 fuse Size Rating Reference400/415 V 440 V 500 V (1) Reference SettingP Ie P Ie P Ie Reference rangekW A kW A kW A A A
0.06 0.22 0.06 0.19 – – GS1-DD 10 x 38 2 LC1-D09 LRD-02 0.16…0.25– – 0.09 0.28 – – GS1-DD 10 x 38 2 LC1-D09 LRD-03 0.25…0.40.09 0.36 – – – –0.12 0.42 0.12 0.37 – – GS1-DD 10 x 38 2 LC1-D09 LRD-04 0.4…0.630.18 0.6 0.18 0.55 – –– – 0.25 0.76 – – GS1-DD 10 x 38 2 LC1-D09 LRD-05 0.63…10.25 0.88 – – 0.37 10.37 1 0.37 1 0.55 1.210.55 1.5 0.55 1.36 0.75 1.5 GS1-DD 10 x 38 2 LC1-D09 LRD-06 1…1.70.75 2 0.75 1.68 – –– – 1.1 2.37 1.1 2 GS1-DD 10 x 38 4 LC1-D09 LRD-07 1.6…2.51.1 2.5 – – 1.5 2.61.5 3.5 1.5 3.06 2.2 3.8 GS1-DD 10 x 38 4 LC1-D09 LRD-08 2.5…42.2 5 2.2 4.42 3 5 GS1-DD 10 x 38 6 LC1-D09 LRD-10 4…63 6.5 3 5.77 4 6.5 GS1-DD 10 x 38 8 LC1-D09 LRD-12 5.5…84 8.4 4 7.9 5.5 9 GS1-DD 10 x 38 10 LC1-D09 LRD-14 7…105.5 11 5.5 10.4 7.5 12 GS1-DD 10 x 38 16 LC1-D12 LRD-16 9…137.5 14.8 7.5 13.7 9 13.9 GS1-DD 10 x 38 16 LC1-D18 LRD-21 12…18– – 9 16.9 – – GS1-F 14 x 51 20 LC1-D25 LRD-21 12…189 18.1 11 20.1 11 18.411 21 – – 15 23 GS1-F 14 x 51 25 LC1-D25 LRD-22 16…2415 28.5 15 26.5 18.5 28.5 GS1-F 14 x 51 32 LC1-D32 LRD-32 23…3218.5 35 18.5 32.8 22 33 GS1-F 14 x 51 40 LC1-D40 LRD-3355 30…40
22 42 22 39 30 45 GS1-J 22 x 58 50 LC1-D50 LRD-3357 37…50– – 30 51.5 – – GS1-J 22 x 58 80 LC1-D50 LRD-3359 48…65– – – – 37 55 GS1-J 22 x 58 80 LC1-D65 LRD-3359 48…6530 57 37 64 – – GS1-J 22 x 58 80 LC1-D65 LRD-3361 55…70– – – – 45 65 GS1-J 22 x 58 80 LC1-D95 LRD-3361 55…7037 69 45 76 – – GS1-J 22 x 58 100 LC1-D80 LRD-3363 63…80– – – – 55 80 GS1-J 22 x 58 100 LC1-D115 LR9-D5367 60…10045 81 – – – – GS1-J 22 x 58 100 LC1-D95 LRD-3365 80…93
55 100 55 90 75 105 GS1-L 22 x 58 125 LC1-D150 LR9-D5369 90…150
75 135 75 125 90 129 GS1-L T0 160 LC1-D150 LR9-D5369 90…150
90 165 90 146 110 156 GS1-N T0 200 LC1-F185 LR9-F5371 132…220110 200 110 178 132 187 GS1-N T1 250 LC1-F225 LR9-F5371 132…220
132 240 132 215 160 220 GS1-QQ T2 315 LC1-F265 LR9-F7375 200…330– – 160 256 – – GS1-QQ T2 315 LC1-F330 LR9-F7375 200…330160 285 200 321 200 281 GS1-QQ T2 400 LC1-F330 LR9-F7375 200…330– – – – 220 310 GS1-QQ T2 400 LC1-F400 LR9-F7375 200…330200 352 – – – –220 388 220 353 250 360 GS1-S T3 500 LC1-F400 LR9-F7379 300…500
250 437 250 401 – – GS1-S T3 500 LC1-F500 LR9-F7379 300…500– – – – 315 445– – – – 355 500 GS1-S T3 630 LC1-F500 LR9-F7381 380…630315 555 315 505 – – GS1-S T3 630 LC1-F630 LR9-F7381 380…630
– – 355 549 – –– – 400 611 400 540 GS1-V T4 800 LC1-F630 LR9-F7381 380…630
Combinations for assembly by the customer
24542_Ver2.10-EN.fm/2 Schneider Electric
TeSys motor starters - open version 1
Star-delta starters with circuit-breakerand overload protection built into the circuit-breaker
Maximum operating rate: LC3-K: 12 starts/hour; LC3-D: 30 starts/hour.Maximum starting time: 30 seconds.
(1) IrD: current in the motor windings in delta connection.(2) The breaking performance of motor circuit breakers GV2-ME can be increased by adding a current limiter, GV1-L3, see page 24509/5.
1.5 to 110 kW at 400/415 V: type 1 coordination
Standard power ratings of 3-phase Circuit-breaker Star-deltamotors 50/60 Hz in category AC-3 Reference Setting range contactors400/415 V 440 V of ReferenceP Ie IrD (1) Iq (2) P Ie IrD (1) Iq (2) thermal tripskW A A kA kW A A kA A
1.5 3.5 2 50 1.5 3.06 1.8 50 GV2-ME08 2.5…4 LC3-K062.2 5 2.9 50 2.2 4.42 2.6 50– – – – 3 5.77 3.3 50 GV2-ME10 4…6.3 LC3-K063 6.5 3.8 50 – – – –4 8.4 4.9 50 4 7.9 4.6 15 GV2-ME14 6…10 LC3-K06
5.5 11 6.4 15 5.5 10.4 6 8 GV2-ME16 9…14 LC3-K06
7.5 14.8 8.6 15 7.5 13.7 7.9 8 GV2-ME20 13…18 LC3-K09
– – – – 9 16.9 9.8 8 GV2-ME20 13…18 LC3-D12A
9 18.1 10 15 11 20.1 12 6 GV2-ME21 17…23 LC3-D12A
11 21 12 15 – – – – GV2-ME22 20…25 LC3-D12A
15 28.5 17 10 15 26.5 15 6 GV2-ME32 24…32 LC3-D18A
18.5 35 20 35 18.5 32.8 19 25 GV3-ME40 25…40 LC3-D18A
– – – – 22 39 23 25 GV3-ME40 25…40 LC3-D18A
22 42 24 35 30 51.5 30 10 GV3-ME63 40…63 LC3-D32A
– – – – 30 51.5 30 25 GV7-RE80 48…80 LC3-D32A
30 57 33 35 – – – – GV3-ME63 40…63 LC3-D32A
30 57 33 25 – – – – GV7-RE80 48…80 LC3-D32A
37 69 40 15 37 64 37 10 GV3-ME80 56…80 LC3-D40
37 69 40 25 37 64 37 25 GV7-RE80 48…80 LC3-D40
– – – – 45 76 44 10 GV3-ME80 56…80 LC3-D50
– – – – 45 76 44 25 GV7-RE80 48…80 LC3-D5045 81 47 25 – – – –55 100 58 25 55 90 52 25 GV7-RE100 60…100 LC3-D50
75 135 78 35 75 125 72 35 GV7-RE150 90…150 LC3-D80
– – – – 90 146 84 35 GV7-RE150 90…150 LC3-D11590 165 95 35110 200 115 35 110 178 103 35 GV7-RE220 132…220 LC3-D115
– – – – 132 215 124 35 GV7-RE220 132…220 LC3-D150
Combinations for assembly by the customer
24542_Ver2.10-EN.fm/3Schneider Electric
TeSys motor starters - open version 1
Star-delta starters with circuit-breakerand overload protection built into the circuit-breaker
Maximum operating rate: LC1-D: 30 starts/hour; LC1-F: 12 starts/hour.Maximum starting time: LC1-D: 30 seconds; LC1-F: 20 seconds.
(1) The breaking performance of motor circuit breakers GV2-P can be increased by adding a current limiter GV1-L3, see page 24509/5.
1.5 to 110 kW at 400/415 V: type 2 coordination
Standard power ratings of 3-phase Circuit-breaker Star-deltamotors 50/60 Hz in category AC-3 Reference Setting range contactors400/415 V 440 V of ReferenceP Ie Iq P Ie Iq (1) thermal tripskW A kA kW A kA A
1.5 3.5 130 1.5 3.06 130 GV2-P08 2.5…4 3 x LC1-D09
2.2 5 130 2.2 4.42 130 GV2-P10 4…6.3 3 x LC1-D18
– – – 3 5.77 130 GV2-P10 4...6.3 3 x LC1-D18
3 6.5 130 – – – GV2-P14 6…10 3 x LC1-D18
4 8.4 130 4 7.9 130 GV2-P14 6…10 3 x LC1-D18
5.5 11 130 5.5 10.4 50 GV2-P16 9…14 3 x LC1-D25
– – – 7.5 13.7 50 GV2-P16 9…14 3 x LC1-D25
7.5 14.8 50 9 16.9 20 GV2-P20 13…18 3 x LC1-D25
9 18.1 50 11 20.1 20 GV2-P21 17…23 3 x LC1-D25
11 21 50 – – – GV2-P22 20…25 3 x LC1-D25
15 28.5 70 15 26.5 65 GV7-RS40 25…40 3 x LC1-D80
18.5 35 70 18.5 32.8 65 GV7-RS40 25…40 3 x LC1-D80
– – – 22 39 65 GV7-RS40 25…40 3 x LC1-D80
22 42 70 – – – GV7-RS50 30…50 3 x LC1-D80
30 57 70 30 51.5 65 GV7-RS80 48…80 3 x LC1-D80
37 69 70 37 64 65 GV7-RS80 48…80 3 x LC1-D80
– – – 45 76 65 GV7-RS80 48…80 3 x LC1-D80
45 81 70 – – – GV7-RS100 60…100 3 x LC1-D115
55 100 70 55 90 65 GV7-RS100 60…100 3 x LC1-D115
75 135 70 75 125 65 GV7-RS150 90…150 3 x LC1-D150
– – – 90 146 65 GV7-RS150 90…150 3 x LC1-D150
90 165 70 110 178 65 GV7-RS220 132…220 3 x LC1-F185
110 200 70 132 215 65 GV7-RS220 132…220 3 x LC1-F225
Combinations for assembly by the customer
24543_Ver2.11-EN.fm/2 Schneider Electric
TeSys motor starters - open version 1
Star-delta starters with circuit-breakerand overload protection by separate thermal overload relay
Maximum operating rate: LC3-K and LC3-F: 12 starts/hour; LC3-D: 30 starts/hour.Maximum starting time: LC3-K and LC3-D: 30 seconds; LC3-F: 20 seconds.
(1) IrD: current in the motor windings in delta connection.(2) Irm: magnetic trip setting current.(3) Products marketed under the Merlin Gerin brand. Reference to be completed by replacing the () with the breaking performance code
1.5 to 315 kW at 400/415 V: type 1 coordination
Standard power ratings of 3-phase Circuit-breaker Star-delta Thermal overload relaymotors 50/60 Hz in category AC-3 Reference Rating Irm contactors Reference Setting400/415 V 440 V (2) Reference rangeP Ie IrD(1) Iq P Ie IrD(1) IqkW A A kA kW A A kA A A A– – – – 1.5 3.06 1.8 501.5 3.5 2 50 2.2 4.42 3 50 GV2-LE08 4 51 LC3-K06 LR2-K0308 1.8…2.62.2 5 3 50 3 5.77 3 50 GV2-LE10 6.3 78 LC3-K06 LR2-K0310 2.6…3.73 6.5 4 50 – – – – GV2-LE14 10 138 LC3-K06 LR2-K0312 3.7…5.5– – – – 4 7.9 5 50 GV2-LE10 6.3 78 LC3-K06 LR2-K0312 3.7…5.54 8.4 5 50 – – – – GV2-LE14 10 138 LC3-K06 LR2-K0312 3.7…5.5– – – – 5.5 10.4 6 15 GV2-LE14 10 138 LC3-K06 LR2-K0314 5.5…85.5 11 6 15 – – – – GV2-LE16 14 170 LC3-K06 LR2-K0314 5.5…8– – – – 7.5 13.7 8 8 GV2-LE16 14 170 LC3-K09 LR2-K0316 8…11.57.5 14.8 9 15 – – – – GV2-LE20 18 223 LC3-K09 LR2-K0316 8…11.5– – – – 9 16.9 10 8 GV2-LE16 14 170 LC3-D12A LRD-16 8…11.59 18.1 10 15 – – – – GV2-LE22 25 327 LC3-K12 LR2-K0316 8…11.5– – – – 11 20.1 12 8 GV2-LE20 18 223 LC3-K12 LR2-K0321 10…1411 21 12 15 – – – – GV2-LE22 25 327 LC3-K12 LR2-K0321 10…14– – – – 15 26.5 15 6 GV2-LE22 25 327 LC3-D18A LRD-21 12…1815 28.5 16 10 – – – – GV2-LE32 32 384 LC3-D18A LRD-21 12…18
18.5 35 20 70 18.5 32.8 19 65 NS80HMA 50 350 LC3-D18A LRD-22 16…24– – – – 22 39 23 65 NS80HMA 50 400 LC3-D18A LRD-22 16…2422 42 24 70 – – – – NS80HMA 50 400 LC3-D32A LRD-32 23…32– – – – 30 51.5 30 65 NS80HMA 80 560 LC3-D32A LRD-32 23…3230 57 33 70 – – – – NS80HMA 80 560 LC3-D32A LRD-35 30…38– – – – 37 64 37 65 NS80HMA 80 560 LC3-D40 LRD-3355 30…40– – – – 45 76 44 65 NS80HMA 80 640 LC3-D40 LRD-3357 37…50– – – – 55 90 52 65 NS80HMA 80 800 LC3-D50 LRD-3359 48…6537 69 40 70 – – – – NS80HMA 80 640 LC3-D40 LRD-3359 48…65
– – – – 75 125 72 (3) NS160MA (3) 150 1200 LC3-D80 LRD-3363 63…8045 81 47 (3) – – – – NS100MA (3) 100 800 LC3-D50 LRD-3357 37…5055 100 58 (3) – – – – NS100MA (3) 100 1200 LC3-D50 LRD-3361 55…7075 135 78 (3) – – – – NS160MA (3) 150 1200 LC3-D80 LRD-3363 63…80– – – – 90 146 85 (3) NS160MA (3) 150 1200 LC3-D115 LRD-4365 80…10490 165 96 (3) 110 178 103 (3) NS250MA (3) 220 1760 LC3-D115 LRD-4365 80…104– – – – 132 215 125 (3) NS250MA (3) 220 1760 LC3-D150 LRD-4369 110…140110 200 116 (3) – – – – NS250MA (3) 220 1760 LC3-D115 LRD-4369 110…140– – – – 160 256 148 (3) NS400MA (3) 320 2240 LC3-D150 LR9-D5369 90…150– – – – 200 321 186 (3) NS630MA (3) 500 3150 LC3-F225 LR9-F5371 132…220132 240 139 (3) – – – – NS400MA (3) 320 2240 LC3-D150 LRD-4369 110…140160 285 165 (3) – – – – NS400MA (3) 320 2560 LC3-F185 LR9-F5371 132…220200 352 204 (3) 220 353 204 (3) NS630MA (3) 500 3150 LC3-F225 LR9-F5371 132…220220 388 225 (3) 250 401 233 (3) NS630MA (3) 500 3500 LC3-F265 LR9-F7375 200…330280 480 278 (3) – – – – NS630MA (3) 500 4000 LC3-F330 LR9-F7375 200…330
– – – 315 505 295 (3) C801+STR35ME 800 4000 LC3-F330 LR9-F7375 200…330315 555 322 (3) 355 518 300 (3) C801+STR35ME 800 4500 LC3-F330 LR9-F7375 200…330– – – 375 575 334 (3) C801+STR35ME 800 5000 LC3-F400 LR9-F7379 300…500
Breaking NS100MA NS160MA NS400MA C801performance Iq (kA) NS250MA NS630MA +STR35ME400/415 V 25 70 36 70 70 130 70 150440 V 25 65 35 65 65 130 65 100Code E S E S H L H L
Combinations for assembly by the customer
24543_Ver2.11-EN.fm/3Schneider Electric
TeSys motor starters - open version 1
Star-delta starters with circuit-breakerand overload protection by separate thermal overload relay
Maximum operating rate: LC3-D: 30 starts/hour; LC3-F: 12 starts/hour.Maximum starting time: LC3-D: 30 seconds; LC3-F: 20 seconds.
(1) Irm: magnetic trip setting current.(2) Products marketed under the Merlin Gerin brand. Reference to be completed by replacing the () with the breaking performance code
1.5 to 250 kW at 400/415 V: type 2 coordination
Standard power ratings of 3-phase Circuit-breaker Star-delta Thermal overload relaysmotors 50/60 Hz in category AC-3 Reference Rating Irm contactors Reference Setting400/415 V 440 V (1) Reference rangeP Ie Iq P Ie IqkW A kA kW A kA A A A
1.5 3.5 130 1.5 3.06 130 GV2-L08 4 51 3 x LC1-D18 LRD-08 2.5…42.2 5 130 2.2 4.42 1303 6.5 130 3 5.77 130 GV2-L10 6.3 78 3 x LC1-D18 LRD-10 4…6– – – 4 7.9 20 GV2-L14 10 138 3 x LC1-D18 LRD-14 7…104 8.4 130 – – – GV2-L14 10 138 3 x LC1-D18 LRD-16 9…135.5 11 50 5.5 10.4 20 GV2-L16 14 170 3 x LC1-D25 LRD-16 9…137.5 14.8 50 7.5 13.7 20 GV2-L20 18 223 3 x LC1-D25 LRD-21 12…18– – – 9 16.9 20 GV2-L22 25 327 3 x LC1-D25 LRD-21 12…189 18.1 50 – – –11 21 50 11 20.1 20 GV2-L22 25 327 3 x LC1-D25 LRD-22 16…24
15 28.5 70 15 26.5 65 NS80HMA 50 300 3 x LC1-D40 LRD-3353 23…3218.5 35 70 18.5 32.8 65 NS80HMA 50 350 3 x LC1-D50 LRD-3355 30…4022 42 70 22 39 65 NS80HMA 50 400 3 x LC1-D50 LRD-3357 37…5030 57 70 30 51.5 65– – – 37 64 65 NS80HMA 80 560 3 x LC1-D65 LRD-3359 48…6537 69 70 45 76 65 NS80HMA 80 640 3 x LC1-D80 LRD-3363 63…80
45 81 (2) 55 90 (2) NS100MA (2) 100 800 3 x LC1-D115 LR9-D5367 60…100
55 100 (2) – – – NS160MA (2) 150 1200 3 x LC1-D115 LR9-D5369 90…150– – – 75 125 (2) NS160MA (2) 150 1200 3 x LC1-D150 LR9-D5369 90…15075 135 (2) 90 146 (2) NS160MA (2) 150 1200 3 x LC1-D150 LR9-D5369 90…150
90 165 (2) 110 178 (2) NS250MA (2) 220 1760 3 x LC1-F185 LR9-F5371 132…220110 200 (2) – – – NS250MA (2) 220 1760 3 x LC1-F225 LR9-F5371 132…220– – – 132 215 (2) NS250MA (2) 220 1760 3 x LC1-F225 LR9-F7375 200…330
132 240 (2) 160 256 (2) NS400MA (2) 320 2240 3 x LC1-F265 LR9-F7375 200…330160 285 (2) – – – NS400MA (2) 320 2560 3 x LC1-F330 LR9-F7375 200…330– – – 200 321 (2) NS400MA (2) 320 2880 3 x LC1-F330 LR9-F7379 300…500
200 352 (2) 220 353 (2) NS630MA (2) 500 3150 3 x LC1-F400 LR9-F7379 300…500220 388 (2) 250 401 (2) NS630MA (2) 500 3500 3 x LC1-F400 LR9-F7379 300…500250 437 (2) – – – NS630MA (2) 500 4000 3 x LC1-F500 LR9-F7379 300…500
Breaking NS100MA NS160MA NS400MAperformance Iq (kA) NS250MA NS630MA400/415 V 25 70 36 70 70 130440 V 25 65 35 65 65 130Code E S E S H L
Combinations for assembly by the customer
24544_Ver3.11-EN.fm/2 Schneider Electric
TeSys motor starters - open version 1
Star-delta starters with fuse protection (NF C or DIN fuses)
Maximum operating rate: LC3-K and LC3-F: 12 starts/hour; LC3-D: 30 starts/hour.Maximum starting time: LC3-K and LC3-D: 30 seconds; LC3-F: 20 seconds.
(1) IrD: current in the motor windings in delta connection.
1.5 to 315 kW at 400/415 V: type 1 coordination
Standard power ratings of 3-phase Fuse carrier aM fuses Star-delta Thermal overload relaymotors 50/60 Hz in category AC-3 (basic block) Size Rat- contactors Reference Setting 400/415 V 440 V Reference ing Reference rangeP Ie IrD Iq P Ie IrD Iq
(1) (1)kW A A kA kW A A kA A A
1.5 3.5 2 50 1.5 3.06 2 50 LS1-D32 10 x 38 4 LC3-K06 LR2-K0308 1.8…2.62.2 5 3 50 – – – – LS1-D32 10 x 38 6 LC3-K06 LR2-K0310 2.6…3.7– – – – 2.2 4.42 3 50– – – – 3 5.77 3 50 LS1-D32 10 x 38 8 LC3-K06 LR2-K0310 2.6…3.73 6.5 4 50 – – – – LS1-D32 10 x 38 8 LC3-K06 LR2-K0312 3.7…5.54 8.4 5 50 4 7.9 5 50 LS1-D32 10 x 38 12 LC3-K06 LR2-K0312 3.7…5.55.5 11 6 50 5.5 10.4 6 50 LS1-D32 10 x 38 16 LC3-K06 LR2-K0314 5.5…87.5 14.8 9 50 7.5 13.7 8 50 LS1-D32 10 x 38 16 LC3-K09 LR2-K0316 8…11.59 18.1 10 100 9 16.9 10 50 LS1-D32 10 x 38 20 LC3-D12A LRD-16 9…13
11 21 12 100 11 20.1 12 100 GK1-EK 14 x 51 25 LC3-D12A LRD-16 9…1315 28.5 16 100 15 26.5 15 100 GK1-EK 14 x 51 32 LC3-D18A LRD-21 12…1818.5 35 20 100 18.5 32.8 19 100 GK1-EK 14 x 51 40 LC3-D18A LRD-22 16…24
– – – – 22 39 23 100 GK1-FK 22 x 58 50 LC3-D18A LRD-22 16…2422 42 24 100 – – – – GK1-FK 22 x 58 50 LC3-D32A LRD-32 23…32– – – – 30 51.5 30 100 GK1-FK 22 x 58 63 LC3-D32A LRD-32 23…3230 57 33 100 37 64 37 100 GK1-FK 22 x 58 80 LC3-D40 LRD-3355 30…4037 69 40 100 – – – – GK1-FK 22 x 58 80 LC3-D40 LRD-3357 37…50– – – – 45 76 44 100 GK1-FK 22 x 58 80 LC3-D50 LRD-3357 37…5045 81 47 100 – – – – GK1-FK 22 x 58 100 LC3-D50 LRD-3357 37…50
– – – – 55 90 52 100 GS1-K 22 x 58 100 LC3-D50 LRD-3359 48…6555 100 58 100 – – – – GS1-K 22 x 58 125 LC3-D50 LRD-3361 55…70
75 135 78 100 75 125 72 100 GS1-L T0 160 LC3-D80 LRD-3363 63…80– – – – 90 146 84 100 GS1-L T0 160 LC3-D115 LRD-4365 80…104
90 165 95 100 – – – – GS1-N T1 200 LC3-D115 LRD-4367 95…120110 200 115 100 110 178 103 100 GS1-N T1 200 LC3-D115 LRD-4367 95…120
132 240 139 100 132 215 124 100 GS1-QQ T2 250 LC3-D150 LRD-4369 110…140160 285 165 100 160 256 148 100 GS1-QQ T2 315 LC3-F185 LR9-F5371 132…220– – – – 200 321 185 100 GS1-QQ T2 400 LC3-F225 LR9-F5369 132…220220 388 225 100 – – – – GS1-QQ T2 400 LC3-F265 LR9-F7375 200…330
– – – – 250 401 233 100 GS1-S T3 500 LC3-F265 LR9-F7375 200…330280 480 278 100 – – – – GS1-S T3 500 LC3-F330 LR9-F7375 200…330– – – – 315 505 293 100315 555 322 100 355 518 300 100 GS1-S T3 630 LC3-F330 LR9-F7375 200…330– – – – 375 575 334 100 GS1-S T3 630 LC3-F400 LR9-F7379 300…500
Combinations for assembly by the customer
24544_Ver3.11-EN.fm/3Schneider Electric
TeSys motor starters - open version 1
Star-delta starters with fuse protection (NF C or DIN fuses)
Maximum operating rate: LC1-D: 30 starts/hour; LC1-F: 12 starts/hour.Maximum starting time: LC1-D: 30 seconds; LC1-F: 20 seconds.
1.5 to 355 kW at 400/415 V: type 2 coordination
Standard power ratings of 3-phase Switch- aM fuses Star-delta Thermal overload relaymotors 50/60 Hz in category AC-3 disconnector- Size Rating contactors Reference Setting400/415 V 440 V fuse Reference rangeP Ie Iq P Ie Iq ReferencekW A kA kW A kA A A A
1.5 3.5 50 1.5 3.06 50 GS1-DD 10 x 38 4 3 x LC1-D09 LRD-08 2.5…42.2 5 50 2.2 4.42 50 GS1-DD 10 x 38 6 3 x LC1-D09 LRD-10 4…63 6.5 50 3 5.77 50 GS1-DD 10 x 38 8 3 x LC1-D09 LRD-12 5.5…84 8.4 50 4 7.9 50 GS1-DD 10 x 38 10 3 x LC1-D09 LRD-14 7…105.5 11 50 5.5 10.4 50 GS1-DD 10 x 38 16 3 x LC1-D12 LRD-16 9…137.5 14.8 50 7.5 13.7 50 GS1-DD 10 x 38 16 3 x LC1-D18 LRD-21 12…189 18.1 100 9 16.9 10011 21 100 11 20.1 100 GS1-F 14 x 51 25 3 x LC1-D25 LRD-22 16…2415 28.5 100 15 26.5 100 GS1-F 14 x 51 32 3 x LC1-D32 LRD-32 23…3218.5 35 100 18.5 32.8 100 GS1-F 14 x 51 40 3 x LC1-D40 LRD-3355 30…4022 42 100 22 39 100 GS1-F 22 x 58 50 3 x LC1-D50 LRD-3357 37…50
30 57 100 30 51.5 100 GS1-J 22 x 58 80 3 x LC1-D65 LRD-3361 55…7037 69 100 37 64 100 GS1-J 22 x 58 80 3 x LC1-D80 LRD-3363 63…80– – – 45 76 100 GS1-J 22 x 58 80 3 x LC1-D80 LRD-3365 80…9345 81 100 – – – GS1-J 22 x 58 100 3 x LC1-D115 LR9-D5367 60…100
– – – 55 90 100 GS1-L T0 125 3 x LC1-D115 LR9-D5369 90…15055 100 100 – – – GS1-L T0 125 3 x LC1-D150 LR9-D5369 90…150– – – 75 125 100 GS1-L T0 160 3 x LC1-D150 LR9-D5369 90…15075 135 100 – – – GS1-L T0 160 3 x LC1-F185 LR9-D5369 90…150
90 165 100 90 146 100 GS1-N T1 200 3 x LC1-F185 LR9-F5371 132…220110 200 100 110 178 100 GS1-N T1 250 3 x LC1-F225 LR9-F5371 132…220
132 240 100 132 215 100 GS1-QQ T2 315 3 x LC1-F265 LR9-F7375 200…330160 285 100 160 256 100 GS1-QQ T2 315 3 x LC1-F330 LR9-F7375 200…330– – – 200 321 100 GS1-QQ T2 400 3 x LC1-F330 LR9-F7379 300…500200 352 100 220 353 100220 388 100 250 401 100 GS1-S T3 500 3 x LC1-F400 LR9-F7379 300…500250 437 100 – – – GS1-S T3 500 3 x LC1-F500 LR9-F7379 300…500315 555 100 315 505 100 GS1-S T3 630 3 x LC1-F630 LR9-F7381 380…630
– – – 355 549 100– – – 400 611 100 GS1-V T4 800 3 x LC1-F630 LR9-F7381 380…630355 605 100 – – – GS1-V T4 800 3 x LC1-F780 LR9-F7381 380…630
Combinations for assembly by the customer
24545-EN_Ver2.11.fm/2 Schneider Electric
TeSys motor starters - open version 1
D.O.L. starters with fuse protection (BS fuses)
(1) For reversing operation, replace the reference prefix LC1 by LC2.
0.06 to 375 kW at 415 V: type 2 coordination
Standard power ratings of 3-phase Switch- BS fuses Contactor Thermal overload relaymotors 50/60 Hz in category AC-3 disconnector- Size Rating Reference Reference Setting415 V 440 V 500 V fuse (1) rangeP Ie P Ie P Ie ReferencekW A kW A kW A A A
0.06 0.22 0.06 0.19 – – GS1-DDB A1 NIT 2 LC1-D09 LRD-02 0.16…0.25– – 0.09 0.28 – – GS1-DDB A1 NIT 2 LC1-D09 LRD-03 0.25…0.40.09 0.36 – – – –0.12 0.42 0.12 0.37 – – GS1-DDB A1 NIT 2 LC1-D09 LRD-04 0.4…0.630.18 0.6 0.18 0.55 – – GS1-DDB A1 NIT 2 LC1-D09 LRD-05 0.63…1– – 0.25 0.76 – – GS1-DDB A1 NIT 4 LC1-D09 LRD-05 0.63…10.25 0.88 0.37 1 0.37 10.37 1 0.55 1.36 0.55 1.20.55 1.5 0.75 1.68 0.75 1.5 GS1-DDB A1 NIT 6 LC1-D09 LRD-06 1…1.70.75 2 – – – – GS1-DDB A1 NIT 10 LC1-D09 LRD-07 1.6…2.5– – – – 1.5 2.6 GS1-DDB A1 NIT 10 LC1-D09 LRD-08 2.5…41.5 3.5 1.5 3.06 2.2 3.8 GS1-DDB A1 NIT 16 LC1-D09 LRD-08 2.5…42.2 5 2.2 4.42 3 5 GS1-DDB A1 NIT 16 LC1-D09 LRD-10 4…63 6.5 3 5.77 4 6.5 GS1-DDB A1 NIT 20 LC1-D09 LRD-12 5.5…84 8.4 4 7.9 5.5 9 GS1-DDB A1 NIT 20 LC1-D09 LRD-14 7…105.5 11 5.5 10.4 7.5 12 GS1-DDB A1 NIT 20M25 LC1-D12 LRD-16 9…137.5 14 7.5 13.7 9 13.9 GS1-DDB A1 NIT 20M32 LC1-D18 LRD-21 12…18
9 18.1 9 16.9 – – GS1-GB A2 TIA 32M35 LC1-D18 LRD-21 12…1811 21 11 20 11 18.4– – – – 15 23 GS1-GB A2 TIA 32M50 LC1-D25 LRD-22 16…2415 28.5 15 26.5 – – GS1-GB A2 TIA 32M63 LC1-D32 LRD-32 23…32– – – – 22 33 GS1-GB A3 TIS 63M80 LC1-D40 LRD-3355 30…4022 42 22 39 30 45 GS1-GB A3 TIS 63M100 LC1-D50 LRD-3357 37…50– – 30 51.5 – – GS1-GB A3 TIS 63M100 LC1-D50 LRD-3359 48…6530 57 – – – – GS1-GB A3 TIS 63M100 LC1-D65 LRD-3359 48…65
– – 45 76 45 65 GS1-LLB A4 TCP 100M125 LC1-D80 LRD-3363 63…8045 81 – – 55 80 GS1-LLB A4 TCP 100M125 LC1-D95 LRD-3365 80…9355 100 – – – – GS1-LLB A4 TCP 100M160 LC1-D115 LR9-D5369 90…150– – 55 90 – – GS1-LLB A4 TCP 100M160 LC1-D115 LR9-D5367 60…100
– – – – 80 116 GS1-LB B2 TF 200 LC1-D150 LR9-D5369 90…15080 138 80 132 – – GS1-LB B2 TF 200M250 LC1-D150 LR9-D5369 90…150– – – – 100 143– – – – 110 156 GS1-LB B2 TF 200M250 LC1-F185 LR9-F5371 132…220
100 182 100 162 – – GS1-MMB B2 TF 200M250 LC1-F185 LR9-F5371 132…220110 196 110 178 – – GS1-MMB B2 TF 200M315 LC1-F225 LR9-F5371 132…220
– – – – 140 200 GS1-NB B3 TKF 315M355 LC1-F265 LR9-F5371 132…220140 250 140 226 160 220 GS1-NB B3 TKF 315M355 LC1-F265 LR9-F7375 200…330
160 285 160 256 – – GS1-QQB B4 TKF 315M355 LC1-F330 LR9-F7375 200…330– – – – 220 310 GS1-QQB B4 TMF 400 LC1-F400 LR9-F7379 300…500220 388 220 353 257 362 GS1-QQB B4 TMF 400M450 LC1-F400 LR9-F7379 300…500
– – – – 270 380 GS1-SB C2 TTM 500 LC1-F500 LR9-F7379 300…500257 450 257 412 – –270 460 270 433 – – GS1-SB C2 TTM 500 LC1-F500 LR9-F7381 380…630375 610 375 577 375 508– – – – 425 556 GS1-SB C2 TTM 630 LC1-F630 LR9-F7381 380…630
Combinations for assembly by the customer
24545-EN_Ver2.11.fm/3Schneider Electric
TeSys motor starters - open version 1
Star-delta starters with fuse protection (BS fuses)
Maximum operating rate: LC1-D: 30 starts/hour; LC1-F: 12 starts/hour.Maximum starting time: LC1-D: 30 seconds; LC1-F: 20 seconds.
1.5 to 375 kW at 415 V: type 2 coordination
Standard power ratings of 3-phase Switch- BS fuses Contactor Thermal overload relaymotors 50/60 Hz in category AC-3 disconnector- Size Rating Reference Reference Setting415 V 440 V fuses rangeP Ie Iq P Ie Iq ReferencekW A kA kW A kA A A
1.5 3.5 50 1.5 3.06 50 GS1-DDB A1 NIT 16 3 x LC1-D09 LRD-08 2.5…4
2.2 5 50 2.2 4.42 50 GS1-DDB A1 NIT 16 3 x LC1-D09 LRD-10 4…6
3 6.5 50 3 5.77 50 GS1-DDB A1 NIT 20 3 x LC1-D09 LRD-12 5.5…8
4 8.4 50 4 7.9 50 GS1-DDB A1 NIT 20 3 x LC1-D09 LRD-14 7…10
5.5 11 50 5.5 10.4 50 GS1-DDB A1 NIT 20M25 3 x LC1-D12 LRD-16 9…13
7.5 14.8 50 7.5 13.7 50 GS1-DDB A1 NIT 20M32 3 x LC1-D18 LRD-21 12…18
9 18.1 50 9 16.9 50 GS1-GB A2 TIA 32M35 3 x LC1-D18 LRD-21 12…18
11 21 50 11 20.1 50 GS1-GB A2 TIA 32M50 3 x LC1-D25 LRD-22 16…24
15 28.5 50 15 26.5 50 GS1-GB A2 TIA 32M63 3 x LC1-D32 LRD-32 23…32
22 42 50 22 39 50 GS1-GB A3 TIS 63M80 3 x LC1-D40 LRD-3355 30…40
– – – 30 51.5 50 GS1-GB A3 TIS 63M100 3 x LC1-D50 LRD-3359 48…65
30 57 50 – – – GS1-GB A3 TIS 63M100 3 x LC1-D65 LRD-3359 48…65
45 81 50 45 76 50 GS1-LLB A4 TCP 100M125 3 x LC1-D80 LRD-3363 63…80
55 100 80 55 90 80 GS1-LLB A4 TCP 100M160 3 x LC1-D115 LR9-D5369 90…150
80 138 80 80 132 80 GS1-LB B2 TF 200M250 3 x LC1-D150 LR9-D5369 90…150
100 182 80 100 162 80 GS1-MMB B2 TF 200M250 3 x LC1-F185 LR9-F5371 132…220
110 196 80 110 178 80 GS1-MMB B2 TF 200M315 3 x LC1-F225 LR9-F5371 132…220
140 250 80 140 226 80 GS1-NB B3 TFK 315M355 3 x LC1-F265 LR9-F7375 200…330
160 285 80 160 256 80 GS1-QQB B3 TFK 315M355 3 x LC1-F330 LR9-F7375 200…330
220 388 80 220 353 80 GS1-QQB B4 TMF 400M450 3 x LC1-F400 LR9-F7379 300…500257 450 80 257 412 80270 460 80 270 433 80 GS1-SB C2 TTM 500 3 x LC1-F500 LR9-F7379 300…500
375 610 80 375 577 80 GS1-SB C2 TTM 630 3 x LC1-F630 LR9-F7381 380…630
Combinations for assembly by the customer
24570_Ver2.10-EN.fm/2 Schneider Electric
TeSys motor starters - open version 1
D.O.L. starters with integral 18, 32 and 63 contactor breakers with overload protection by separate module
(1) Iq = 40 kA for LD1-LB; Iq = 70 kA for LD-LC.(2) Irth min to Irth max.(3) For LB1-LB, the magnetic protection is fixed, set at 15 Irth max. For LB1-LC, the magnetic protection is adjustable from 6 to 12 Irth max.
0.06 to 4 kW at 400/415 V (total coordination)
Standard power ratings of 3-phase Contactor breaker Protection modulemotors 50/60 Hz in category AC-3 Without control With control Reference Setting range400/415 V 440 V 500 V test function test function Thermal MagneticP Ie Iq P Ie Iq P Ie Iq Reference Reference (2) (3)kW A kA kW A kA kW A kA A A
0.06 0.22 70 0.06 0.19 70 – – – LD1-LB030 – LB1-LB03P02 0.16…0.25 3.8
0.09 0.36 70 0.09 0.28 70 – – – LD1-LB030 LB1-LB03P03 0.25…0.4 6or LD1-LC030 LD4-LC130 LB1-LC03M03 0.25…0.4 2.4…4.8
– – – 0.12 0.37 70 – – – LD1-LB030 LB1-LB03P03 0.25…0.4 6or LD1-LC030 LD4-LC130 LB1-LC03M03 0.25…0.4 2.4…4.8
0.12 0.42 70 0.18 0.55 70 – – – LD1-LB030 LB1-LB03P04 0.4…0.63 9.5or LD1-LC030 LD4-LC130 LB1-LC03M04 0.4…0.63 3.8…7.6
0.18 0.6 70 – – – – – – LD1-LB030 LB1-LB03P04 0.4…0.63 9.5or LD1-LC030 LD4-LC130 LB1-LC03M04 0.4…0.63 3.8…7.6
0.25 0.88 70 0.25 0.76 70 0.37 1 70 LD1-LB030 LB1-LB03P05 0.63…1 15or LD1-LC030 LD4-LC130 LB1-LC03M05 0.63…1 6…12
0.37 1 70 0.37 1 70 0.55 1.21 70 LD1-LB030 LB1-LB03P06 1…1.6 24or LD1-LC030 LD4-LC130 LB1-LC03M06 1…1.6 9.5…19
0.55 1.5 70 0.55 1.36 70 0.75 1.5 70 LD1-LB030 LB1-LB03P06 1…1.6 24or LD1-LC030 LD4-LC130 LB1-LC03M06 1…1.6 9.5…19
0.75 2 70 0.75 1.68 70 1.1 2 70 LD1-LB030 LB1-LB03P07 1.6…2.5 37.5or LD1-LC030 LD4-LC130 LB1-LC03M07 1.6…2.5 15…30
– – – 1.1 2.37 70 – – – LD1-LB030 LB1-LB03P07 1.6…2.5 37.5or LD1-LC030 LD4-LC130 LB1-LC03M07 1.6…2.5 15…30
1.1 2.5 70 – – – 1.5 2.6 70 LD1-LB030 LB1-LB03P08 2.5…4 60or LD1-LC030 LD4-LC130 LB1-LC03M08 2.5…4 24…48
1.5 3.5 70 1.5 3.06 70 2.2 3.8 70 LD1-LB030 LB1-LB03P08 2.5…4 60or LD1-LC030 LD4-LC130 LB1-LC03M08 2.5…4 24…48
2.2 5 70 2.2 4.42 (1) 3 5 15 LD1-LB030 LB1-LB03P10 4…6 90or LD1-LC030 LD4-LC130 LB1-LC03M10 4…6.3 38…76
– – – 3 5.77 (1) – – – LD1-LB030 LB1-LB03P10 4…6 90or LD1-LC030 LD4-LC130 LB1-LC03M10 4…6.3 38…76
3 6.5 70 4 7.9 (1) 4 6.5 15 LD1-LB030 LB1-LB03P13 6…10 150or LD1-LC030 LD4-LC130 LB1-LC03M13 6.3…10 60…120
4 8.4 70 – – – 5.5 9 15 LD1-LB030 LB1-LB03P13 6…10 150or LD1-LC030 LD4-LC130 LB1-LC03M13 6.3…10 60…120
Combinations for assembly by the customer
24570_Ver2.10-EN.fm/3Schneider Electric
TeSys motor starters - open version 1
D.O.L. starters with integral 18, 32 and 63 contactor breakers with overload protection by separate module
(1) Iq = 40 kA for LD1-LB ; Iq = 70 kA for LD-LC.(2) Iq = 10 kA for LD1-LB ; Iq = 25 kA for LD-LC.(3) Irth min to Irth max.(4) For LB1-LB, the magnetic protection is fixed, set at 15 Irth max. For LB1-LC and LB1-LD, the magnetic protection is adjustable from 6 to 12 Irth max.
5.5 to 30 kW at 400/415 V (total coordination)
Standard power ratings of 3-phase Contactor breaker Protection modulemotors 50/60 Hz in category AC-3 Without control With control Reference Setting range400/415 V 440 V 500 V test function test function Thermal MagneticP Ie Iq P Ie Iq P Ie Iq Reference Reference (3) (4)kW A kA kW A kA kW A kA A A
5.5 11 70 5.5 10.4 (1) 7.5 12 (2) LD1-LB030 LB1-LB03P17 10…16 240or LD1-LC030 LD4-LC130 LB1-LC03M17 10…16 95…190
7.5 14.8 70 7.5 13.7 (1) – – – LD1-LB030 LB1-LB03P17 10…16 240or LD1-LC030 LD4-LC130 LB1-LC03M17 10…16 95…190
– – – – – – 9 13.9 (2) LD1-LB030 LB1-LB03P21 12…18 270or LD1-LC030 LD4-LC130 LB1-LC03M17 10…16 95…190
9 18.1 70 9 16.9 (1) – – – LD1-LB030 LB1-LB03P21 12…18 270or LD1-LC030 LD4-LC130 LB1-LC03M22 16…25 150…300
11 21 70 11 20.1 70 11 18.4 20 LD1-LC030 LD4-LC130 LB1-LC03M22 16…25 150…300
– – – – – – 15 23 20 LD1-LC030 LD4-LC130 LB1-LC03M22 16…25 150…300
15 28.5 70 15 26.5 30 18.5 28.5 15 LD1-LC030 LD4-LC130 LB1-LC03M53 23…32 190…380
18.5 35 70 18.5 32.8 70 22 33 35 LD1-LD030 LD4-LD130 LB1-LD03M55 28…40 240…480
– – – 22 39 70 – – – LD1-LD030 LD4-LD130 LB1-LD03M55 28…40 240…480
22 42 70 – – – 30 45 35 LD1-LD030 LD4-LD130 LB1-LD03M57 35…50 300…600
30 57 70 30 51.5 40 37 55 35 LD1-LD030 LD4-LD130 LB1-LD03M61 45…63 380…760
– – – 33 58.5 40 – – – LD1-LD030 LD4-LD130 LB1-LD03M61 45…63 380…760
Combinations for assembly by the customer
4573 Ver2.00-EN.fm/2 Schneider Electric
TeSys motor starters - open versionD.O.L. starters with circuit-breakerand overload protection built into the circuit-breaker
(1) The breaking capacity of circuit-breakers GV2-ME can be increased to 15 kA by adding a current limiter LA9-LB920, see page 24512/3.(2) NS400H, NS630H and STR43ME: products marketed under the Merlin Gerin brand, please consult your Regional Sales Office.(3) For reversing operation, replace LC1 by LC2.
0.37 to 475 kW at 690 V: type 1 coordination
Standard power ratings of 3-phase motors Circuit-breaker Contactor50/60 Hz in category AC-3 Reference Setting range of Reference690 V (2) thermal trips (3)P Ie Iq (1)kW A kA A
0.37 0.6 3 GV2-ME05 0.63…1 LC1-D090.55 0.9 3 GV2-ME05 0.63…1 LC1-D090.75 1.1 3 GV2-ME06 1…1.6 LC1-D091.1 1.6 3 GV2-ME07 1.6…2.5 LC1-D091.5 2 3 GV2-ME07 1.6…2.5 LC1-D092.2 2.9 3 GV2-ME08 2.5…4 LC1-D093 3.8 3 GV2-ME08 2.5…4 LC1-D094 5 3 GV2-ME10 4…6.3 LC1-D095.5 6.7 3 GV2-ME14 6…10 LC1-D097.5 8.8 3 GV2-ME14 6…10 LC1-D1210 12 3 GV2-ME16 9…14 LC1-D1811 13 3 GV2-ME16 9…14 LC1-D2515 16.5 3 GV2-ME20 13…18 LC1-D2518.5 21 3 GV2-ME21 17…23 LC1-D32
22 25 8 GV7-RE40 25…40 LC1-D4030 33 8 GV7-RE40 25…40 LC1-D4033 35 8 GV7-RE50 30…50 LC1-D5037 41 8 GV7-RE50 30…50 LC1-D6545 49 8 GV7-RE50 30…50 LC1-D8055 60 8 GV7-RE80 48…80 LC1-D11580 86 8 GV7-RE100 60…100 LC1-D11590 95 8 GV7-RE100 60…100 LC1-D150100 105 8 GV7-RE150 90…150 LC1-D150110 115 8 GV7-RE150 90…150 LC1-F185129 132 8 GV7-RE150 90…150 LC1-F225132 139 8 GV7-RE150 90…150 LC1-F265160 167 8 GV7-RE220 132…220 LC1-F265200 202 8 GV7-RE220 132…220 LC1-F330
220 224 20 NS400H+STR43ME 190…320 LC1-F330250 253 20 NS400H+STR43ME 190…320 LC1-F400280 284 20 NS400H+STR43ME 190…320 LC1-F400315 321 20 NS630H+STR43ME 300…500 LC1-F500335 335 20 NS630H+STR43ME 300…500 LC1-F500400 400 20 NS630H+STR43ME 300…500 LC1-F630450 450 20 NS630H+STR43ME 300…500 LC1-F630475 470 20 NS630H+STR43ME 300…500 LC1-F780
Combinations for assembly by the customer
24573 Ver2.00-EN.fm/Schneider Electric
TeSys motor starters - open versionD.O.L. starters with circuit-breakerand overload protection built into the circuit-breaker
(1) The breaking capacity of circuit-breakers GV2-P can be increased to 50 kA by adding a current limiter LA9-LB920, see page 24512/3.(2) NS400L, NS630L and STR43ME: products marketed under the Merlin Gerin brand, please consult your Regional Sales Office.(3) For reversing operation, replace LC1 by LC2.
0.37 to 475 kW at 690 V: type 2 coordination
Standard power ratings of 3-phase motors Circuit-breaker Contactor50/60 Hz in category AC-3 Reference Setting range of Reference690 V (2) thermal trips (3)P Ie Iq (1)kW A kA A
0.37 0.6 8 GV2-P05 0.63…1 LC1-D250.55 0.9 8 GV2-P05 0.63…1 LC1-D250.75 1.1 8 GV2-P06 1…1.6 LC1-D251.1 1.6 8 GV2-P07 1.6…2.5 LC1-D251.5 2 8 GV2-P07 1.6…2.5 LC1-D252.2 2.9 8 GV2-P08 2.5…4 LC1-D253 3.8 8 GV2-P08 2.5…4 LC1-D254 5 6 GV2-P10 4…6.3 LC1-D255.5 6.7 6 GV2-P14 6…10 LC1-D257.5 8.8 6 GV2-P14 6…10 LC1-D2510 12 6 GV2-P16 9…14 LC1-D2511 13 6 GV2-P16 9…14 LC1-D2515 16.5 4 GV2-P20 13…18 LC1-D2518.5 21 4 GV2-P21 17…23 LC1-D32
22 25 10 GV7-RS40 25…40 LC1-D8030 33 10 GV7-RS40 25…40 LC1-D8033 35 10 GV7-RS50 30…50 LC1-D8037 41 10 GV7-RS50 30…50 LC1-D8045 49 10 GV7-RS50 30…50 LC1-D8055 60 10 GV7-RS80 48…80 LC1-D11580 86 10 GV7-RS100 60…100 LC1-D11590 95 10 GV7-RS100 60…100 LC1-D150100 105 10 GV7-RS150 90…150 LC1-F185110 115 10 GV7-RS150 90…150 LC1-F185129 132 10 GV7-RS150 90…150 LC1-F265132 139 10 GV7-RS150 90…150 LC1-F265160 167 10 GV7-RS220 132…220 LC1-F265200 202 10 GV7-RS220 132…220 LC1-F330
220 224 35 NS400L+STR43ME 190…320 LC1-F330250 253 35 NS400L+STR43ME 190…320 LC1-F400280 284 35 NS400L+STR43ME 190…320 LC1-F500315 321 35 NS630L+STR43ME 300…500 LC1-F500335 335 35 NS630L+STR43ME 300…500 LC1-F630400 400 35 NS630L+STR43ME 300…500 LC1-F630450 450 35 NS630L+STR43ME 300…500 LC1-F630475 470 35 NS630L+STR43ME 300…500 LC1-F780
Combinations for assembly by the customer
4574 Ver2.00-EN.fm/2 Schneider Electric
TeSys motor starters - open versionD.O.L. starters with circuit-breakerand overload protection by separate thermal overload relay
(1) The breaking capacity of circuit-breakers GV2-LE can be increased to 15 kA by adding a current limiter LA9-LB920, see page 24512/3.(2) NSpppHMA: products marketed under the Merlin Gerin brand, please consult your Regional Sales Office.(3) For reversing operation, replace LC1 by LC2.
0.37 to 475 kW at 690 V: type 1 coordination
Standard power ratings of 3-phase motors Circuit-breaker Contactor Thermal overload relay50/60 Hz in category AC-3 Reference Rating Reference Reference Setting690 V (2) (3) rangeP Ie Iq (1)kW A kA A A
0.37 0.6 3 GV2-LE05 1 LC1-D09 LRD-05 0.63…10.55 0.9 3 GV2-LE05 1 LC1-D09 LRD-05 0.63…10.75 1.1 3 GV2-LE06 1.6 LC1-D09 LRD-06 1…1.71.1 1.6 3 GV2-LE07 2.5 LC1-D09 LRD-07 1.6…2.51.5 2 3 GV2-LE07 2.5 LC1-D09 LRD-07 1.6…2.52.2 2.9 3 GV2-LE08 4 LC1-D09 LRD-08 2.5…43 3.8 3 GV2-LE08 4 LC1-D09 LRD-08 2.5…44 5 3 GV2-LE10 6.3 LC1-D09 LRD-10 4…65.5 6.7 3 GV2-LE14 10 LC1-D09 LRD-12 5.5…87.5 8.8 3 GV2-LE14 10 LC1-D12 LRD-14 7…1010 12 3 GV2-LE16 14 LC1-D18 LRD-16 9…1311 13 3 GV2-LE16 14 LC1-D25 LRD-16 9…1315 16.5 3 GV2-LE20 18 LC1-D25 LRD-21 12…1818.5 21 3 GV2-LE22 25 LC1-D32 LRD-22 16…24
22 25 8 NS100NMA 25 LC1-D40 LRD-3353 23…3230 33 8 NS100NMA 50 LC1-D40 LRD-3355 30…4033 35 8 NS100NMA 50 LC1-D50 LRD-3355 30…4037 41 8 NS100NMA 50 LC1-D65 LRD-3357 37…5045 49 8 NS100NMA 50 LC1-D80 LRD-3357 37…5055 60 8 NS100NMA 100 LC1-D115 LRD-3359 48…6580 86 8 NS100NMA 100 LC1-D115 LR9-D5367 60…10090 95 8 NS100NMA 100 LC1-D150 LR9-D5367 60…100
100 105 10 NS160HMA 150 LC1-D150 LR9-D5369 90…150110 115 10 NS160HMA 150 LC1-F185 LR9-F5369 90…150129 132 10 NS160HMA 150 LC1-F225 LR9-F5369 90…150132 139 10 NS160HMA 150 LC1-F265 LR9-F5371 132…220
160 167 10 NS250HMA 220 LC1-F265 LR9-F5371 132…220200 202 10 NS250HMA 220 LC1-F330 LR9-F5371 132…220
220 224 20 NS400HMA 320 LC1-F330 LR9-F7375 200…300250 253 20 NS400HMA 320 LC1-F400 LR9-F7375 200…300280 284 20 NS400HMA 320 LC1-F400 LR9-F7375 200…300
315 321 20 NS630HMA 500 LC1-F500 LR9-F7379 300…500335 335 20 NS630HMA 500 LC1-F500 LR9-F7379 300…500400 400 20 NS630HMA 500 LC1-F630 LR9-F7381 380…630450 450 20 NS630HMA 500 LC1-F630 LR9-F7381 380…630475 470 20 NS630HMA 500 LC1-F800 LR9-F7381 380…630
Combinations for assembly by the customer
24574 Ver2.00-EN.fm/Schneider Electric
TeSys motor starters - open versionD.O.L. starters with circuit-breakerand overload protection by separate thermal overload relay
(1) The breaking capacity of circuit-breakers GV2-L can be increased to 50 kA by adding a current limiter LA9-LB920, see page 24512/3.(2) NSpppLMA: products marketed under the Merlin Gerin brand, please consult your Regional Sales Office.(3) For reversing operation, replace LC1 by LC2.
0.37 to 475 kW at 690 V: type 2 coordination
Standard power ratings of 3-phase motors Circuit-breaker Contactor Thermal overload relay50/60 Hz in category AC-3 Reference Rating Reference Reference Setting690 V (2) (3) rangeP Ie Iq (1)kW A kA A A
0.37 0.6 8 GV2-L05 1 LC1-D25 LRD-05 0.63…10.55 0.9 8 GV2-L05 1 LC1-D25 LRD-05 0.63…10.75 1.1 8 GV2-L06 1.6 LC1-D25 LRD-06 1…1.71.1 1.6 8 GV2-L07 2.5 LC1-D25 LRD-07 1.6…2.51.5 2 8 GV2-L07 2.5 LC1-D25 LRD-07 1.6…2.52.2 2.9 8 GV2-L08 4 LC1-D25 LRD-08 2.5…43 3.8 8 GV2-L08 4 LC1-D25 LRD-08 2.5…44 5 6 GV2-L10 6.3 LC1-D25 LRD-10 4…65.5 6.7 6 GV2-L14 10 LC1-D25 LRD-12 5.5…87.5 8.8 6 GV2-L14 10 LC1-D25 LRD-14 7…1010 12 6 GV2-L16 14 LC1-D25 LRD-16 9…1311 13 6 GV2-L16 14 LC1-D25 LRD-16 9…1315 16.5 4 GV2-L20 18 LC1-D25 LRD-21 12…1818.5 21 4 GV2-L22 25 LC1-D32 LRD-22 16…24
22 25 35 NS100LMA 100 LC1-D80 LRD-3353 23…3230 33 35 NS100LMA 100 LC1-D80 LRD-3355 30…4033 35 35 NS100LMA 100 LC1-D80 LRD-3355 30…4037 41 35 NS100LMA 100 LC1-D80 LRD-3357 37…5045 49 35 NS100LMA 100 LC1-D80 LRD-3357 37…5055 60 35 NS100LMA 100 LC1-D115 LRD-3359 48…6580 86 35 NS100LMA 100 LC1-D115 LR9-D5367 60…10090 95 35 NS100LMA 100 LC1-D150 LR9-D5367 60…100
100 105 35 NS160LMA 150 LC1-F185 LR9-F5369 90…150110 115 35 NS160LMA 150 LC1-F185 LR9-F5369 90…150129 132 35 NS160LMA 150 LC1-F265 LR9-F5369 90…150132 139 35 NS160LMA 150 LC1-F265 LR9-F5371 132…220
160 167 35 NS250LMA 220 LC1-F265 LR9-F5371 132…220200 202 35 NS250LMA 220 LC1-F330 LR9-F5371 132…220
220 224 35 NS400LMA 320 LC1-F330 LR9-F7375 200…300250 253 35 NS400LMA 320 LC1-F400 LR9-F7375 200…300280 284 35 NS400LMA 320 LC1-F500 LR9-F7375 200…300
315 321 35 NS630LMA 500 LC1-F500 LR9-F7379 300…500335 335 35 NS630LMA 500 LC1-F630 LR9-F7379 300…500400 400 35 NS630LMA 500 LC1-F630 LR9-F7381 380…630450 450 35 NS630LMA 500 LC1-F630 LR9-F7381 380…630475 470 35 NS630LMA 500 LC1-F780 LR9-F7381 380…630
Combinations for assembly by the customer
4575 Ver2.00-EN.fm/2 Schneider Electric
TeSys motor starters - open versionD.O.L. starters with protection by NF C or DIN fuses
0.37 to 475 kW at 690 V: type 1 coordination
Standard power ratings of 3-phase motors Rating (1) Contactor Thermal50/60 Hz in category AC-3 gG aM Reference overload relay690 V (2) Reference SettingP Ie rangekW A A A
0.37 0.6 2 1 LC1-D09 LRD-05 0.63…10.55 0.9 4 2 LC1-D09 LRD-05 0.63…10.75 1.1 4 2 LC1-D09 LRD-06 1…1.71.1 1.6 4 2 LC1-D09 LRD-07 1.6…2.51.5 2 6 4 LC1-D09 LRD-07 1.6…2.52.2 2.9 8 4 LC1-D09 LRD-08 2.5…43 3.8 10 4 LC1-D09 LRD-08 2.5…44 5 12 6 LC1-D09 LRD-10 4…65.5 6.7 16 8 LC1-D09 LRD-12 5.5…8
7.5 8.8 20 10 LC1-D12 LRD-14 7…10
10 12 32 16 LC1-D25 LRD-16 9…1311 13 32 16 LC1-D25 LRD-16 9…13
15 16.5 40 20 LC1-D32 LRD-21 12…1818.5 21 50 25 LC1-D32 LRD-22 16…24
22 25 50 32 LC1-D40 LRD-3353 23…32
30 33 63 40 LC1-D50 LRD-3355 30…40
33 35 63 40 LC1-D65 LRD-3355 30…4037 41 80 50 LC1-D65 LRD-3357 37…50
45 49 100 63 LC1-D80 LRD-3357 37…50
55 60 125 80 LC1-D115 LRD-3359 48…6580 86 160 100 LC1-D115 LR9-D5367 60…100
90 95 200 125 LC1-D150 LR9-D5367 60…100
100 105 200 125 LC1-F185 LR9-F5369 90…150110 115 250 160 LC1-F185 LR9-F5369 90…150
129 132 250 160 LC1-F225 LR9-F5369 90…150
132 139 250 160 LC1-F265 LR9-F5371 132…220160 167 315 200 LC1-F265 LR9-F5371 132…220
200 202 400 250 LC1-F330 LR9-F5371 132…220220 224 500 315 LC1-F330 LR9-F7375 200…300
250 253 500 315 LC1-F400 LR9-F7375 200…300280 284 630 400 LC1-F400 LR9-F7375 200…300
315 321 630 400 LC1-F500 LR9-F7379 300…500335 335 800 500 LC1-F500 LR9-F7379 300…500
400 400 800 500 LC1-F630 LR9-F7381 380…630450 450 800 500 LC1-F630 LR9-F7381 380…630
475 470 800 500 LC1-F800 LR9-F7381 380…630(1) For on-load breaking, add a switch-disconnector.(2) For reversing operation, replace LC1 by LC2.
Combinations for assembly by the customer
24575 Ver2.00-EN.fm/Schneider Electric
TeSys motor starters - open versionD.O.L. starters with protection by NF C or DIN fuses
0.37 to 475 kW at 690 V : coordination type 2
Standard power ratings of 3-phase motors Rating (1) Contactor Thermal50/60 Hz in category AC-3 gG aM Reference overload relay690 V (2) Reference SettingP Ie rangekW A A A
0.37 0.6 2 1 LC1-D09 LRD-05 0.63…10.55 0.9 4 2 LC1-D09 LRD-05 0.63…10.75 1.1 4 2 LC1-D09 LRD-06 1…1.71.1 1.6 4 2 LC1-D09 LRD-07 1.6…2.51.5 2 6 4 LC1-D09 LRD-07 1.6…2.52.2 2.9 8 4 LC1-D09 LRD-08 2.5…43 3.8 10 4 LC1-D09 LRD-08 2.5…44 5 12 6 LC1-D09 LRD-10 4…65.5 6.7 16 8 LC1-D09 LRD-12 5.5…8
7.5 8.8 20 10 LC1-D12 LRD-14 7…10
10 12 32 16 LC1-D25 LRD-16 9…1311 13 32 16 LC1-D25 LRD-16 9…13
15 16.5 40 20 LC1-D32 LRD-21 12…1818.5 21 50 25 LC1-D32 LRD-22 16…24
22 25 50 32 LC1-D40 LRD-3353 23…32
30 33 63 40 LC1-D50 LRD-3355 30…40
33 35 63 40 LC1-D65 LRD-3355 30…4037 41 80 50 LC1-D65 LRD-3357 37…50
45 49 100 63 LC1-D80 LRD-3357 37…50
55 60 125 80 LC1-D115 LRD-3359 48…6580 86 160 100 LC1-D115 LR9-D5367 60…100
90 95 200 125 LC1-D150 LR9-D5367 60…100
100 105 200 125 LC1-F185 LR9-F5369 90…150110 115 250 160 LC1-F185 LR9-F5369 90…150
129 132 250 160 LC1-F225 LR9-F5369 90…150
132 139 250 160 LC1-F265 LR9-F5371 132…220160 167 315 200 LC1-F265 LR9-F5371 132…220
200 202 400 250 LC1-F330 LR9-F5371 132…220220 224 500 315 LC1-F330 LR9-F7375 200…300
250 253 500 315 LC1-F400 LR9-F7375 200…300280 284 630 400 LC1-F400 LR9-F7375 200…300
315 321 630 400 LC1-F500 LR9-F7379 300…500335 335 800 500 LC1-F500 LR9-F7379 300…500
400 400 800 500 LC1-F630 LR9-F7381 380…630450 450 800 500 LC1-F630 LR9-F7381 380…630
475 470 800 500 LC1-F780 LR9-F7381 380…630(1) For on-load breaking, add a switch-disconnector.(2) For reversing operation, replace LC1 by LC2.
Combinations for assembly by the customer
0248Q-EN_Ver2.11.fm/2 Schneider Electric
TeSys motor starters - open version 1
Applications Pre-assembled starters
Small machines starting under full load: D.O.L. starters Machines requiringsmooth starting orslowing down
Type of starter D.O.L. starters with circuit-breakers D.O.L. starters with Soft start units orfuse protection in association with
Level of service Type 1 co-ordination Type 2 co-ordination
Power at 400 V Up to 5.5 kW Up to 15 kW Up to 37 kW Up to 45 kW
Type of components Combination automatic motor starter with overload Fuse carrier Soft start unitprotection built into the circuit-breaker + plate mounted
contactor
Pages 24520/2 and 24520/3 24520/4 and 24520/5 24520/6 and 24520/7 24546/2 24075/2 and 24075/3
Selection guide
0248Q-EN_Ver2.11.fm/3Schneider Electric
1
Starters for customer assembly
Machines starting under Small machines starting under full load: D.O.L. starters no-load: star-delta starters Machines starting under no-load: star-delta starters
star-delta starters to be used D.O.L. or star-delta starters with circuit-breakers D.O.L. or star-delta starters with fusesa circuit-breaker or fuses
Total co-ordination Type 1 and type 2 co-ordination
Up to 132 kW Up to 30 kW Up to 110 kW Up to 315 kW Up to 315 kW Up to 355 kW
3 contactors (line, star and delta, mounted on plate or rail)
Contactor- Thermal magnetic Thermal-magnetic Fuse carrier Switch-disconnector-fusebreaker circuit-breaker circuit-breaker + contactor(s) + contactor(s)
+ contactor(s) + contactor(s) + thermal overload + thermal overload relay + thermal overload relay relay
24547/3 24570/2 and 24570/3 24539/2 and 24539/3 24540/2 and 24540/3 24541/2 and 24544/2 24541/3 and 24544/3 to 24545/324542/2 and 24542/3 24543/2 and 24543/3
24520-EN_Ver5.2.fm/2 Schneider Electric
TeSys motor starters - open version 1
Combination automatic motor starterswith overload protection built into the circuit-breaker
This pre-assembled combination comprises:- 1 motor circuit-breaker type GV2-ME,- 1 3-pole contactor,- 1 combination block GV2-AF01.
D.O.L. starters, non-reversing
(1) The breaking performance of circuit-breakers GV2-ME can be increased by adding a current limiter GV1-L3, seepage 24509/5.(2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office).
(3) Please consult your Regional Sales Office.(4) Coil: low consumption (1.5 W), wide range (0.7…1.3 Uc) with integral suppression device as standard.
D.O.L. starters, non-reversing, from 0.37 to 5.5 kW at 400/415 V, type 1 coordination
Characteristics
Starter type GV2- ME06K1 ME07K1 ME08K1 ME10K1 ME14K1 ME16K1
Breaking capacity (Iq) (1) To IEC-947-4-1 400/415 V kA 50 50 50 50 50 15440 V kA 50 50 50 50 15 8500 V kA 50 50 50 50 10 (4 kW) 6
6 (5.5 kW)
References
Standard Setting Fixed For customer assembly Pre-assembled Weightpower ratings range of magnetic Motor Contactor Basic reference.of 3-phase thermal tripping circuit- Reference Complete with codemotors trips current breaker to be indicating control50/60 Hz 13 Irth Reference completed (3) circuit voltage (2)in AC-3400/415V 440V 500VkW kW kW A A kg
0.37 0.37 0.37 1…1.6 22.5 GV2-ME06 LC1-K06 GV2-ME06K1pp 0.4600.55 0.55 0.55– – 0.75
0.75 0.75 – 1.6…2.5 33.5 GV2-ME07 LC1-K06 GV2-ME07K1pp 0.460– 1.1 1.1
1.1 – 1.5 2.5…4 51 GV2-ME08 LC1-K06 GV2-ME08K1pp 0.4601.5 1.5 2.2
2.2 2.2 – 4…6.3 78 GV2-ME10 LC1-K06 GV2-ME10K1pp 0.460– 3 3
3 – 4 6…10 138 GV2-ME14 LC1-K09 GV2-ME14K1pp 0.4604 4 5.5
5.5 5.5 7.5 9…14 170 GV2-ME16 LC1-K12 GV2-ME16K1pp 0.460
Add-on blocksDescription Sold Unit Weight
in referencelots of kg
Combination block between circuit-breaker and contactor 10 GV2-AF01 0.020
Volts 24 110 220/230 230 230/240 380/400a 50/60 Hz B7 F7 M7 P7 U7 Q7c (4) BW3 – – – – –
GV2-ME06K1pp
8104
84References
Dimensions:page 24536/2
Schemes:page 24536/3
24520-EN_Ver5.2.fm/3Schneider Electric
TeSys motor starters - open version 1
Combination automatic motor starterswith overload protection built into the circuit-breaker
This pre-assembled combination comprises:- 1 motor circuit-breaker type GV2-ME,- 1 3-pole reversing contactor,- 1 combination block GV2-AF01.
D.O.L. starters, reversing
400/
(1) The breaking performance of circuit-breakers GV2-ME can be increased by adding a current limiter GV1-L3, seepage 24509/5.(2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office).
(3) Please consult your Regional Sales Office.(4) Coil: low consumption (1.5 W), wide range (0.7…1.3 Uc) with integral suppression device as standard.
D.O.L. starters, reversing, from 0.37 to 5.5 kW at 400/415 V, type 1 coordination
Characteristics
Starter type GV2- ME06K2 ME07K2 ME08K2 ME10K2 ME14K2 ME16K2
Breaking capacity (Iq) (1) To IEC-947-4-1 400/415 V kA 50 50 50 50 50 15440 V kA 50 50 50 50 15 8500 V kA 50 50 50 50 10 (4 kW) 6
6 (5.5 kW)
References
Standard Setting Fixed For customer assembly Pre-assembled Weightpower ratings range of magnetic Motor Reversing Basic reference.of 3-phase thermal tripping circuit- contactor Complete with codemotors trips current breaker Reference indicating control50/60 Hz 13 Irth Reference to be circuit voltage (2)in AC-3 completed (3)
415V 440V 500VkW kW kW A A kg
0.37 0.37 0.37 1…1.6 22.5 GV2-ME06 LC2-K06 GV2-ME06K2pp 0.4600.55 0.55 0.55– – 0.75
0.75 0.75 – 1.6…2.5 33.5 GV2-ME07 LC2-K06 GV2-ME07K2pp 0.460– 1.1 1.1
1.1 – 1.5 2.5…4 51 GV2-ME08 LC2-K06 GV2-ME08K2pp 0.4601.5 1.5 2.2
2.2 2.2 – 4…6.3 78 GV2-ME10 LC2-K06 GV2-ME10K2pp 0.460– 3 3
3 – 4 6…10 138 GV2-ME14 LC2-K09 GV2-ME14K2pp 0.4604 4 5.5
5.5 5.5 7.5 9…14 170 GV2-ME16 LC2-K12 GV2-ME16K2pp 0.460
Add-on blocksDescription Sold Unit Weight
in referencelots of kg
Combination block between circuit-breaker and contactor 10 GV2-AF01 0.020
Volts 24 110 220/230 230 230/240 380/400a 50/60 Hz B7 F7 M7 P7 U7 Q7c (4) BW3 – – – – –
GV2-ME06K2pp
8104
85
References
Dimensions:page 24536/2
Schemes:page 24536/3
24520-EN_Ver5.2.fm/4 Schneider Electric
TeSys motor starters - open version 1
Combination automatic motor starterswith overload protection built into the circuit-breaker
This pre-assembled combination comprises:- 1 motor circuit-breaker type GV2-ME,- 1 3-pole contactor,- 1 combination block GV2-AF3.
D.O.L. starters, non-reversing (3)
400/
(1) The breaking performance of circuit-breakers GV2-ME can be increased by adding a current limiter GV1-L3, seepage 24509/5.(2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office).
(3) Can be combined with type 2, see page 24539/3.(4) See page 24501/2.(5) Coil with integral suppression device as standard.
D.O.L. starters, non-reversing, from 0.06 to 15 kW at 400/415 V, type 1 coordination
Characteristics
Starter type GV2- DM102 DM114 DM116 DM120 DM121 DM122 DM132to DM110
Breaking capacity (Iq) (1) To IEC-947-4-1 400/415 V kA 50 50 15 15 15 15 10440 V kA 50 15 8 8 6 6 6500 V kA 50 10 6 6 4 4 4
References
Standard Setting Fixed For customer assembly Pre-assembled Weightpower ratings range of magnetic Motor Contactor Basic reference.of 3-phase thermal tripping circuit- Reference Complete with codemotors trips current breaker to be indicating control50/60 Hz 13 Irth Reference completed (4) circuit voltage (2)in AC-3
415V 440V 500VkW kW kW A A kg
0.06 0.06 – 0.16…0.25 2.4 GV2-ME02 LC1-D09pp GV2-DM102pp 0.5960.09 0.09 –– 0.12 – 0.25…0.40 5 GV2-ME03 LC1-D09pp GV2-DM103pp 0.5960.12 –0.18 0.18 – 0.40…0.63 8 GV2-ME04 LC1-D09pp GV2-DM104pp 0.5960.25 0.25 –0.37 0.37 – 0.63…1 13 GV2-ME05 LC1-D09pp GV2-DM105pp 0.596– – 0.370.55 0.55 0.55 1…1.6 22.5 GV2-ME06 LC1-D09pp GV2-DM106pp 0.596– – 0.750.75 0.75 –– 1.1 1.1 1.6…2.5 33.5 GV2-ME07 LC1-D09pp GV2-DM107pp 0.5961.1 – 1.51.5 1.5 2.2 2.5…4 51 GV2-ME08 LC1-D09pp GV2-DM108pp 0.5962.2 2.2 –– 3 3 4…6.3 78 GV2-ME10 LC1-D09pp GV2-DM110pp 0.5963 – 44 4 5.5 6…10 138 GV2-ME14 LC1-D09pp GV2-DM114pp 0.596
5.5 5.5 7.5 9…14 170 GV2-ME16 LC1-D12pp GV2-DM116pp 0.6017.5 7.5 –– 9 9 13…18 223 GV2-ME20 LC1-D18pp GV2-DM120pp 0.606
9 11 11 17…23 327 GV2-ME21 LC1-D25pp GV2-DM121pp 0.646
11 – 15 20…25 327 GV2-ME22 LC1-D25pp GV2-DM122pp 0.646
15 15 18.5 24…32 416 GV2-ME32 LC1-D32pp GV2-DM132pp 0.651
Add-on blocksDescription Mounting of Sold in Unit Weight
GV2 lots of reference kg
Combination block between circuit-breaker 5 rail 10 GV2-AF3 0.016and contactor
Mtg. plate 10 GV2-AF4 0.016LAD-311
Volts 24 220 23050/60 Hz B7 M7 P7c (5) BD – –
810
486
GV2-DM102pp
References
Dimensions:page 24536/2
Schemes:page 24536/3
24520-EN_Ver5.2.fm/5Schneider Electric
TeSys motor starters - open version 1
Combination automatic motor starterswith overload protection built into the circuit-breaker
This pre-assembled combination comprises:- 1 motor circuit-breaker type GV2-ME,- 1 3-pole reversing contactor,- 1 combination block GV2-AF3.
D.O.L. starters, reversing (3)
(1) The breaking performance of circuit-breakers GV2-ME can be increased by adding a current limiter GV1-L3, seepage 24509/5.(2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office).
(3) Can be combined with type 2, see page 24540/3.(4) See page 24501/2.(5) Coil with integral suppression device as standard.
D.O.L. starters, reversing, from 0.06 to 15 kW at 400/415 V, type 1 coordination
Characteristics
Starter type GV2- DM202 DM214 DM216 DM220 DM221 DM222 DM232to DM210
Breaking capacity (Iq) (1) To IEC-947-4-1 400/415 V kA 50 50 15 15 15 15 10440 V kA 50 15 8 8 6 6 6500 V kA 50 10 6 6 4 4 4
References
Standard Setting Fixed For customer assembly Pre-assembled Weightpower ratings range of magnetic Motor Reversing Basic reference.of 3-phase thermal tripping circuit- contactor Complete with codemotors trips current breaker Reference indicating control50/60 Hz 13 Irth Reference to be circuit voltage (2)in AC-3 completed (4)400/ 415V 440V 500VkW kW kW A A kg
0.06 0.06 – 0.16…0.25 2.4 GV2-ME02 LC2-D09pp GV2-DM202pp 0.9630.09 0.09 –– 0.12 – 0.25…0.40 5 GV2-ME03 LC2-D09pp GV2-DM203pp 0.9630.12 – –0.18 0.18 – 0.40…0.63 8 GV2-ME04 LC2-D09pp GV2-DM204pp 0.9630.25 0.25 –0.37 0.37 – 0.63…1 13 GV2-ME05 LC2-D09pp GV2-DM205pp 0.963– – 0.370.55 0.55 0.55 1…1.6 22.5 GV2-ME06 LC2-D09pp GV2-DM206pp 0.963– – 0.750.75 0.75 –– 1.1 1.1 1.6…2.5 33.5 GV2-ME07 LC2-D09pp GV2-DM207pp 0.9631.1 – 1.51.5 1.5 2.2 2.5…4 51 GV2-ME08 LC2-D09pp GV2-DM208pp 0.9632.2 2.2 –– 3 3 4…6.3 78 GV2-ME10 LC2-D09pp GV2-DM210pp 0.9633 – 44 4 5.5 6…10 138 GV2-ME14 LC2-D09pp GV2-DM214pp 0.963
5.5 5.5 7.5 9…14 170 GV2-ME16 LC2-D12pp GV2-DM216pp 0.9737.5 7.5 –– 9 9 13…18 223 GV2-ME20 LC2-D18pp GV2-DM220pp 0.983
9 11 11 17…23 327 GV2-ME21 LC2-D25pp GV2-DM221pp 1.063
11 – 15 20…25 327 GV2-ME22 LC2-D25pp GV2-DM222pp 1.063
15 15 18.5 24…32 416 GV2-ME32 LC2-D32pp GV2-DM232pp 1.073
Add-on blocksDescription Mounting Sold in Unit Weight
of GV2 lots of reference kg
Combination block between circuit-breaker 5 rail 10 GV2-AF3 0.016and contactor
Mtg. plate 10 GV2-AF4 0.016LAD-311
Volts 24 220 23050/60 Hz B7 M7 P7c (5) BD – –
8104
87
GV2-DM202pp
References
Dimensions:page 24536/2
Schemes:page 24536/3
24520-EN_Ver5.2.fm/6 Schneider Electric
TeSys motor starters - open version 1
Combination automatic motor starterswith overload protection built into the circuit-breaker
This pre-assembled combination comprises:- 1 motor circuit-breaker type GV2-P,- 1 3-pole contactor,- 1 combination block GV2-AF3
D.O.L. starters, non-reversing
400/
(1) The breaking performance of circuit-breakers GV2-P can be increased by adding a current limiter GV1-L3, seepage 24509/5.(2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office).
(3) See page 24501/2.(4) Coil with integral suppression device as standard.
D.O.L. starters, non-reversing, from 0.06 to 15 kW at 400/415 V, type 2 coordination
Characteristics
Starter type GV2- DP102 DP114 DP116 DP120 DP121 DP122 DP132to DP110
Breaking capacity (Iq) (1) To IEC-947-4-1 400/415 V kA 130 130 130 50 50 50 50440 V kA 130 130 50 20 20 20 20500 V kA 130 50 42 10 10 10 10
References
Standard Setting Fixed For customer assembly Pre-assembled Weightpower ratings range of magnetic Motor Contactor Basic reference.of 3-phase thermal tripping circuit Reference Complete with codemotors trips current breaker to be indicating control50/60 Hz 13 Irth Reference completed (3) circuit voltage (2)in AC-3
415V 440V 500VkW kW kW A A kg
0.06 0.06 – 0.16…0.25 2.4 GV2-P02 LC1-D09pp GV2-DP102pp 0.686– 0.090.09 0.12 – 0.25…0.40 5 GV2-P03 LC1-D09pp GV2-DP103pp 0.6860.12 – –0.18 0.18 – 0.40…0.63 8 GV2-P04 LC1-D09pp GV2-DP104pp 0.6860.25 0.25 –0.37 0.37 – 0.63…1 13 GV2-P05 LC1-D09pp GV2-DP105pp 0.686– – 0.370.55 0.55 0.55 1…1.6 22.5 GV2-P06 LC1-D09pp GV2-DP106pp 0.686– – 0.750.75 0.75 –– 1.1 1.1 1.6…2.5 33.5 GV2-P07 LC1-D09pp GV2-DP107pp 0.6861.1 – 1.51.5 1.5 2.2 2.5…4 51 GV2-P08 LC1-D09pp GV2-DP108pp 0.6962.2 2.2 –– 3 3 4…6.3 78 GV2-P10 LC1-D09pp GV2-DP110pp 0.7363 – 44 4 5.5 6…10 138 GV2-P14 LC1-D09pp GV2-DP114pp 0.7365.5 5.5 7.5– 7.5 9 9…14 170 GV2-P16 LC1-D25pp GV2-DP116pp 0.741
7.5 9 – 13…18 223 GV2-P20 LC1-D25pp GV2-DP120pp 0.736
9 11 11 17…23 327 GV2-P21 LC1-D25pp GV2-DP121pp 0.741
11 – 15 20…25 327 GV2-P22 LC1-D25pp GV2-DP122pp 0.741
15 15 18.5 24…32 416 GV2-P32 LC1-D32pp GV2-DP132pp 0.741
Add-on blocksDescription Mounting of Sold in Unit Weight
GV2 lots of reference kg
Combination block between circuit-breaker 5 rail 10 GV2-AF3 0.016and contactor
Mtg. plate 10 GV2-AF4 0.016LAD-311
Volts 24 220 23050/60 Hz B7 M7 P7c (4) BD – –
GV2-DP102pp
810
488
References
Dimensions:page 24536/2
Schemes:page 24536/3
24520-EN_Ver5.2.fm/7Schneider Electric
TeSys motor starters - open version 1
Combination automatic motor starterswith overload protection built into the circuit-breaker
This pre-assembled combination comprises:- 1 motor circuit-breaker type GV2-P,- 1 3-pole reversing contactor,- 1 combination block GV2-AF3.
D.O.L. starters, non-reversing
400/
(1) The breaking performance of circuit-breakers GV2-P can be increased by adding a current limiter GV1-L3, seepage 24509/5.(2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office).
(3) See page 24501/2.(4) Coil with integral suppression device as standard.
D.O.L. starters, reversing, from 0.06 to 15 kW at 400/415, type 2 coordination
Characteristics
Starter type GV2- DP202 DP214 DP216 DP220 DP221 DP222 DP232to DP210
Breaking capacity (Iq) (1) To IEC-947-4-1 400/415 V kA 130 130 130 50 50 50 50440 V kA 130 130 50 20 20 20 20500 V kA 130 50 42 10 10 10 10
References
Standard Setting Fixed For customer assembly Pre-assembled Weightpower ratings range of magnetic Motor Reversing Basic reference.of 3-phase thermal tripping circuit- contactor Complete with codemotors trips current breaker Reference indicating control50/60 Hz 13 Irth Reference to be circuit voltage (2)in AC-3 completed (3)
415V 440V 500VkW kW kW A A kg
0.06 0.06 – 0.16…0.25 2.4 GV2-P02 LC2-D09pp GV2-DP202pp 1.053– 0.090.09 0.12 – 0.25…0.40 5 GV2-P03 LC2-D09pp GV2-DP203pp 1.0530.12 – –0.18 0.18 – 0.40…0.63 8 GV2-P04 LC2-D09pp GV2-DP204pp 1.0530.25 0.25 –0.37 0.37 – 0.63…1 13 GV2-P05 LC2-D09pp GV2-DP205pp 1.053– – 0.370.55 0.55 0.55 1…1.6 22.5 GV2-P06 LC2-D09pp GV2-DP206pp 1.053– – 0.750.75 0.75 –– 1.1 1.1 1.6…2.5 33.5 GV2-P07 LC2-D09pp GV2-DP207pp 1.0531.1 – 1.51.5 1.5 2.2 2.5…4 51 GV2-P08 LC2-D09pp GV2-DP208pp 1.0732.2 2.2 –– 3 3 4…6.3 78 GV2-P10 LC2-D09pp GV2-DP210pp 1.1533 – 44 4 5.5 6…10 138 GV2-P14 LC2-D09pp GV2-DP214pp 1.1535.5 5.5 7.5– 7.5 9 9…14 170 GV2-P16 LC2-D25pp GV2-DP216pp 1.163
7.5 9 – 13…18 223 GV2-P20 LC2-D25pp GV2-DP220pp 1.153
9 11 11 17…23 327 GV2-P21 LC2-D25pp GV2-DP221pp 1.163
11 – 15 20…25 327 GV2-P22 LC2-D25pp GV2-DP222pp 1.163
15 15 18.5 24…32 416 GV2-P32 LC2-D32pp GV2-DP232pp 1.163
Add-on blocksDescription Mounting Sold Unit Weight
of in referenceGV2 lots of kg
Combination block between circuit-breaker 5 rail 10 GV2-AF3 0.016and contactor
Mtg. plate 10 GV2-AF4 0.016LAD-311
Volts 24 220 23050/60 Hz B7 M7 P7c (4) BD – –
810
489
GV2-DP202pp
References
Dimensions:page 24536/2
Schemes:page 24536/3
24536-EN_Ver2.11.fm/2 Schneider Electric
90
152
66
87
11
c1
c45
b
45
152
90
b
1
c1c
d1
125
± 3
1
c1
c
125
± 3
c1
c
d1
d
45
b
90
b
GV2-MEppKppp
GV2-DMppppp
GV2-DPppppp
On mounting rail AM1-DE200 GV2-MEppK1pp GV2-MEppK2pp
On mounting rail AM1-DE200 With adapter plate LAD-311 GV2-DM1pppp GV2-DM2pppp
GV2- DMp02pp to DMp21pp to GV2- DMp02pp to DMp21pp toDMp20pp DMp32pp DMp20pp DMp32pp
b 176.4 186.8 b 234 234c 99.6 105.9 c 135.6 141.9c1 94.1 100.4 c1 130.1 136.4
d 112.5 112.5d1 107 107
On mounting rail AM1-DE200 With adapter plate LAD-311 GV2-DP1pppp GV2-DP2pppp
GV2- DPp02pp to DPp10pp to GV2- DPp02pp to DPp10pp toDPp08pp DPp32pp DPp08pp DPp32pp
b 176.4 186.8 b 234 234c 105.6 111.9 c 141.6 147.9c1 100.1 106.4 c1 136.5 142.4d 100.5 100.5d1 95 95
TeSys motor starters - open version 1
Combination automatic motor starters
Dimensions, mounting
References :pages 24520/2 to 24520/7
24536-EN_Ver2.11.fm/3Schneider Electric
– KM1
A2
A2
0102 02
– KM2
01
A1
A1
– KM1
A1
A2
A1
A2
0101
0202
– KM2
– KM1 – KM2
A1
A2
A2
A1
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
T1/
2
T2/
4
T3/
6
13/N
O14
A1
A2
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
14
A1
A2
12
34
56
L1 L2 L3
12
34
56
U V W
13/N
O
1413
/NO
A1
A2
2221
/NC
2221
/NC
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
14
A1
A2
12
34
56
L1 L2 L3
12
34
56
U V W
13/N
O
1413
/NO
A1
A2
2221
/NC
2221
/NC
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
T1/
2
T2/
4
T3/
6
13/N
O
T1/
2
T2/
4
T3/
614
13/N
O14
A1
A2
1/L1
3/L2
5/L3
A1
A2
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
T1/
2
T2/
4
T3/
6
A1
A2
1413
/NO
2221
/NC
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
T1/
2
T2/
4
T3/
6
A1
A2
1413
/NO
2221
/NC
Mechanical interlockwith integral electrical contacts
GV2-MEppK1pp GV2-DM1pppp GV2-DP1pppp
GV2-MEppK2pp GV2-DM2pppp GV2-DP2pppp
Control circuit a Control circuit c
TeSys motor starters - open version 1
Combination automatic motor starters
Schemes
References :pages 24520/2 to 24520/7
24546-EN_Ver2.11.fm/2 Schneider Electric
(1) Thermal overload relay to be ordered separately (see pages 24514/3 and 24515/2).(2) Standard control circuit voltages.
For other voltages, please consult your Regional Sales Office.(3) Up until this date, the products will continue to be available with LS1-D2531A65 fuse carriers.
r Available 1st quarter 2002 (3)
Utilisation category AC-3 Fuses to Basic reference. WeightStandard power ratings Opera- be fitted by Complete with codeof 3-phase motors tional the customer indicating control50/60 Hz current circuit voltage (2)220 V 380 V 660 V 440 V Size Type230 V 400 V 415 V 440 V 500 V 690 V up to aMkW kW kW kW kW kW A A kg
2.2 4 4 4 5.5 – 9 10 x 38 12 LC4-D09App rr 0.870
3 5.5 5.5 5.5 7.5 – 12 10 x 38 16 LC4-D12App rr 0.870
4 7.5 9 9 10 – 18 10 x 38 20 LC4-D18App rr 1.150
5.5 11 11 11 15 – 25 10 x 38 25 LC4-D25App rr 1.580
7.5 15 15 15 18.5 18.5 32 14 x 51 32 LC4-D32App 2.630
11 18.5 22 22 22 30 40 14 x 51 40 LC4-D40pp 2.930
15 22 25 30 30 33 50 22 x 58 63 LC4-D50pp 3.200
18.5 30 37 37 37 37 65 22 x 58 80 LC4-D65pp 3.340
22 37 45 45 55 45 80 22 x 58 80 LC4-D80pp 3.650
Specifications
Pre-wired power and control circuit connections.
3-pole isolating device
LC4-D09App
106
558_
1
Volts 24 42 48 110 220 230 240 380 400 415 44050/60 Hz B7 D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7
aTeSys motor starters - open version 1
D.O.L. starters, plate mounted, for motor control 4 to 37 kW, (1), with isolating device, pre-assembled
References
Dimensions :page 24546/3
Schemes :page 24546/3
24546-EN_Ver2.11.fm/3Schneider Electric
c1
3612
4
110
88
90
165
==
173
b
c1
79
98
55
71
86
==
==
5063
3311
0
c
c1
c2
bb1
G
a
= =
==
60
100/
110
==
2 4 6
– Q1
2 4
1 3
– KM1
1/L1
3/L2
5/L3
65
LC4-D40…D80
D.O.L. starters
D.O.L. startersPlate mounted, pre-assembledLC4-D09A…D25A LC4-D32A
LC4- D09A…D18A D25A LC4- D32Ab 218 221 c1 without cover or add-on blocks 100c1 without cover or add-on blocks 94 100 with cover, without add-on block 102
with cover, without add-on block 96 102 with LAD-N or C (2 or 4 contacts) 133with LAD-N or C (2 or 4 contacts) 127 133 with LA6-DK10 145with LA6-DK10 139 145 with LAD-T, R, S 153with LAD-T, R, S 147 153 with LAD-T, R, S and sealing cover 157with LAD-T, R, S and sealing cover 151 157
LC4- D40…D65 D80a 281 311b 143 143c 130 140c1 without cover or add-on blocks 124 135
with cover, without add-on block 129 140with LA1-DN (1 contact) 149 160with LAD-N or C (2 or 4 contacts) 157 168with LA6-DK 169 180with LAD-T, R, S 177 188with LAD-T, R, S and sealing cover 181 192
c2 100 178
LC4-D09A to D80
TeSys motor starters - open version 1
D.O.L. starters, plate mounted, for motor control 4 to 37 kW, (1), with isolating device, pre-assembled
Dimensions, schemes
References :page 24546/2
24547-EN_Ver3.11.fm/2 Schneider Electric
0
1
2
3
4
5
6
7
0 0,25 0,50 0,75 1
1
2
0
0,5
0 0,25 0,50 0,75 1
1
2
3
(1)1
1,5
2
2,5
TeSys motor starters - open version 1
Star-delta starters for motor control
This method of starting is applicable to motors on which all6 stator terminals are accessible and whose delta connectionvoltage corresponds to the mains voltage and
Star-delta starting should be used for motors starting onno-load or having a low load torque and gradual build-up: - the starting torque in star connection is reduced to onethird of the direct starting torque, i.e. about 50% of therated torque;- the starting current in star connection is about 1.8 to 2.6times the rated current.
The transition from star to delta connection must occur whenthe machine has run up to speed. A too rapid build-up in loadtorque would cause the stabilised run-up speed to be too lowand would therefore eliminate any advantage in this methodof starting: this is the case with certain machines whose loadtorque depends on the machine speed (a characteristic ofcentrifugal machines, for example).
All star-delta starters are supplied with a special LA2-DS2or LA2-KT2 time delay relay which imposes a delay on thedelta contactor during the transition period in order to allowthe star contactor sufficient breaking time.
For ratings D115 and D150, this function is performed bya time delay auxiliary contact block LA2-DT2 and a controlrelay.
1 Starting in direct delta connection2 Starting in star connection3 Machine resistive torque
(1) Motor manufacturers generally specify machine load torques. Example: maximum resistive torque on completion of star-delta start (expressed as a proportion of the rated torque).
Star-delta starting
Presentation
Current
Speed
Speed
Torque
1 Starting in direct delta connection2 Starting in star connection
24547-EN_Ver3.11.fm/3Schneider Electric
TeSys motor starters - open version 1
Star-delta starters for motor control5.5 to 132 kW, (1), without isolating device,pre-assembled
delta connection
Maximum operating rate: 30 starts/hour. Maximum starting time: 30 seconds.
Maximum operating rate: 12 starts/hour. Maximum starting time: 30 seconds.
(1) Protection must be provided by the addition of an overload relay, to be ordered separately. Select appropriate overloadrelay for setting at 0.58 of the full load rated motor current (see pages 24514/2 and 24514/3).(2) Standard control circuit voltages
Star-delta starters LC3-K06 and K09
Star-delta starters LC3-D09A...D150, LC3-D090A…D320A
For other voltages, please consult your Regional Sales Office.(2) One auxiliary contact block type LAD-N can also be fitted, see page 24511/3.(3) These starters consist of contactors LC1-D115 or D150 without connectors.
Standard power ratings Auxiliary contacts available Star Basic reference. Weightof squirrel cage motors on each contactor delta Complete with
line delta star mechanical code indicatingKM2 KM3 KM1 interlock control circuit voltage (2)
Mains voltage -
220/ 380/230 V 400 V 415 V 440 VkW kW kW kW kg
Plate mounted
4 7.5 7.5 7.5 – – – – (3) – 1 With LC3-D09A 1.530
5.5 11 11 11 – – – – (3) – 1 With LC3-D12A 1.530
11 18.5 22 22 – – – – (3) – 1 With LC3-D18A 1.730
15 25 30 30 – – – – (3) – 1 With LC3-D32A 2.030
18.5 37 37 37 – 1 1 – (3) – 1 Without LC3-D40 4.360With LC3-D40A64 4.500
30 55 59 59 – 1 1 – (3) – – (3) Without LC3-D50 4.360With LC3-D50A64 4.500
37 75 75 75 – 1 1 – (3) – – (3) Without LC3-D80 5.200With LC3-D80A64 5.400
63 110 110 110 – 1 1 – (3) – – (3) Without LC3-D115 (4) 11.800With LC3-D115A64 (4) 12.100
75 132 132 147 – 1 1 – (3) – 1 (3) Without LC3-D150 (4) 12.100With LC3-D150A64 (4) 12.100
Rail mounted (35 mm rail)
3 5.5 5.5 5.5 – – – – – 1 With LC3-K06 0.740
4 7.5 7.5 7.5 – – – – – 1 With LC3-K09 0.740
Maximum operating rate: 30 starts/hour. Maximum starting time: 30 seconds.
4 7.5 7.5 7.5 – – – – (3) – 1 With LC3-D090A 1.530
5.5 11 11 11 – – – – (3) – 1 With LC3-D120A 1.530
11 18.5 22 22 – – – – (3) – 1 With LC3-D180A 1.730
15 25 30 30 – – – – (3) – 1 With LC3-D320A 2.030
Volts 50/60 Hz 24 36 42 48 110 220 230 240 380 400 415 440
Code B7 C7 D7 E7 F7 M7 P7 U7 – – – –
Code B7 – D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7
References
LC3-D32A
Dimensions : pages 24549/2 and 24549/3
Schemes :page 24549/3
24548-EN_Ver4.0.fm/2 Schneider Electric
KM2
KM2
KM2
KM1
KM3
1c
1c2 1a
1b
a
a
a
a
a
1b
1
24548-EN_Ver4.0.fm/3Schneider Electric
TeSys motor starters - open version 1
Star-delta starters, for motor control,7.5 to 132 kW (1), without mechanical interlock,for customer assembly (on plate or on mounting rail) (2)
Maximum operating rate: 30 starts/hour. Maximum starting time : 30 seconds
Separate parts
Maximum operating rate : 30 starts/hour. Maximum starting time : 30 seconds
(1) Protection must be provided by the addition of a thermal overload relay, to be ordered separately. Select appropriateoverload relay for setting at 0.58 of the rated motor current, see pages 24514/2 and 24514/3.(2) For mounting, assembly and cabling: refer to installation instructions supplied with the equipment.(3) See comments on page 24547/2.(4) See page 24501/2.(5) For D115 and D150 components, see illustration and separate parts on pages 24548/4 and 24548/5.(6) A D12 component is adequate for the application, but use of a D18 is recommended.(connection capacity, correct use of power connection kit and connections).(7) A D18 component is adequate for the application, but use of a D25 is recommended. (connection capacity, correct use of power connection kit and connections).
Starters for direct combination with circuit-breaker
Standard power ratings Motor Contactors (basic references to be completedof squirrel cage motors (3) thermal- with code indicating the voltage) (4)Mains voltage-delta magnetic400/ MCB415 V 440 V line delta starkW kW KM2 KM3 KM1
7.5 7.5 GV2-ME20 LC1-D09pp LC1-D09pp LC1-D09pp– 9 GV2-ME20 LC1-D12pp LC1-D12pp LC1-D09pp9 11 GV2-ME21 LC1-D12pp LC1-D12pp LC1-D09pp11 – GV2-ME22 LC1-D12pp LC1-D12pp LC1-D09pp15 15 GV2-ME32 LC1-D18pp LC1-D18pp LC1-D09pp
Description Illustration Reference Weightitem no. kg
Mounting kit comprising: power circuit connections a LAD-912GV 0.130and 1 time delay contact block LAD-S2
Starters for mounting separately from upstream protection
Standard power ratings Contactors (basic references to be completed Separate partsof squirrel cage motors (3) with code indicating the voltage) (4) (see below)Mains voltage-delta220/ 380/230 V 400 V 415 V 440 V line delta starkW kW kW kW KM2 KM3 KM1 Component types
4 7.5 7.5 7.5 LC1-D09pp LC1-D09pp LC1-D09pp D095.5 11 11 11 LC1-D18pp (6) LC1-D12pp LC1-D09pp D1211 18.5 22 22 LC1-D25pp (7) LC1-D25pp (7) LC1-D09pp D1815 25 30 30 LC1-D32pp LC1-D32pp LC1-D18pp D3218.5 37 37 37 LC1-D40pp LC1-D40pp LC1-D40pp D4030 55 59 59 LC1-D50pp LC1-D50pp LC1-D40pp D5037 75 75 75 LC1-D80pp LC1-D80pp LC1-D50pp D8063 110 110 110 LC1-D115pp LC1-D115pp LC1-D80pp D115 (5)75 132 132 147 LC1-D150pp LC1-D150pp LC1-D115pp D150 (5)
Separate partsDescription Illustration For Reference Weight
item no. componentstype (5)
kg
Mounting kit comprising: D09 and D18 LAD-91217 0.180- 1 time delay contact block LAD-S2 1 a(D09…D80) (3) D18 and D32 LAD-93217 0.310- power circuit connections 1 b(D09…D80) D40 and D50 LA9-D5017 0.380- screws and clamps for fixing 1 ccontactors to the plate (D40…D80). D80 LA9-D8017 0.680
Equipment mounting plate 2 D09, D12, D18 LA9-D12974 0.150
D32 LA9-D32974 0.180
D40 and D50 LA9-D40973 0.300
D80 LA9-D80973 0.300
References
a
Illustrations :page 24548/2
Dimensions : pages 24549/2 and 24549/3
Schemes :page 24549/3
24548-EN_Ver4.0.fm/4 Schneider Electric
13 7 129 11 10 3
854
6
14
8
8
24548-EN_Ver4.0.fm/5Schneider Electric
TeSys motor starters - open version 1
Star-delta starters, for motor control,7.5 to 132 kW (1), without mechanical interlock,for customer assembly (on plate or on mounting rail) (2)
(1) Protection must be provided by the addition of a thermal overload relay, to be ordered separately. Select appropriateoverload relay for setting at 0.58 of the rated motor current, see pages 24514/2 and 24514/3.(2) For mounting, assembly and cabling: refer to installation instructions supplied with the equipment.(3) See page 24525/3.(4) Pour vente par lot sous emballage collectif, voir page A0005/3
Separate parts (continued)
Description Illustration For No. Sold in Unit Weightitem no. use on lots of reference kg
Instantaneous auxiliary 1 D115 1 1 LAD-N10 0.020contact block (star)1N/O
Auxiliary contactor 3 D115, D150 1 1 CAD-32pp (3) 0.320
Time delay auxiliary 4 D115, D150 1 1 LAD-T2 0.060contact blocks
Lead sealing kit for 5 D115, D150 1 1 LA9-D901 0.005time delay auxiliarycontact blocks
Thermal magnetic 6 D115, D150 2 6 GB2-CB05 0.060circuit-breaker forcontrol circuit (200…415 V)
Set of 3 connectors for 7 D115, D150 1 1 LA9-FG980 0.200wider terminations (optional)
Set of power connections 8 D115 1 1 LA9-D11517 0.800with fixing accessories
D150 1 1 LA9-D15017 1.050
Spare volt free terminals 9 D115, D150 1 10 DZ3-HA3 0.007
2 10 DZ3-GA3 0.006
Lug-connector 10 D115, D150 1 10 AB1-BC9535 0.236terminal block
Terminal end stop 11 D115, D150 3 100 AB1-AB8M35 0.005
Mounting rail 5 35 mm 12 D115, D150 1 10 AM1-ED021 0.210
Pre-slotted plate 13 D115, D150 1 1 AM3-PA65 1.950
Screw with captive washer 14 D115, D150 12 100 AF1-VA618 0.006
2 100 AF1-VA410 0.002
References (continued)
a
Illustrations :page 124548/4
Dimensions : pages 24549/2 and 24549/3
Schemes :page 24549/3
24549-EN_Ver3.22.fm/2 Schneider Electric
94
110
175
150
175 (1)
4514
3
263
281
==
60
=10
0/11
0
==
=
a
G
H
c
b
c 4
124
b
90= =
a
110KM2
KM3 KM1
110
183 (1)
4714
3
293
311
==
60
=10
0/11
0
==
=
Dimensions TeSys motor starters - open version 1
Star-delta starters for motor control
References : pages 24547/2 to 24548/5
Schemes : page 24549/3
Star-delta starters
Pre-assembled: LC3-D115, D150For customer assembly: 3 x LC1-D with components D115 or D150
Plate mounted, pre-assemled Pre-assembled: LC3-K LC3-D09A…D32A
For customer assembly: 3 x LC1-D with components D09 to D32
LC3- D09A D12A D18A D32Aa 143 143 144 165b 26.5 26.5 26.5 32.5c with LAD-S 139 139 139 145
with LAD-S and sealing cover 143 143 143 149Pre-assembled: LC3-D40, D50 Pre-assembled: LC3-D80For customer assembly: 3 x LC1-D with components D40 or D50 For customer assembly: 3 x LC1-D with components D80
(1) + 4 mm with sealing cover (1) + 4 mm with sealing cover
a b c G HLC3-D115 or 3 x LC1-D with components D115 450 555 205 425 526LC3-D150 or 3 x LC1-D with components D150 450 555 205 425 526
On starters LC3-D09A to D18A, a connection block is mounted on the upper part of contactor KM2, increasing the overall height of the product by 6.5 mm.
24549-EN_Ver3.22.fm/3Schneider Electric
c
b
2xØ7
160
175
KM2KM3 KM1
U1
V1
W1
U2
V2
W2
2 4 6
– KM2
12
34
56
– KM3
12
34
56
– KM1
12
34
56
U1
V1
W1
U2
V2
W2
1 3 5
2 4 6
L1 L2 L3
(1)
KM2 : 1 (N)
O
T
T
I
Y
L
KM3 : 5
– KM3 – KM2– KM1
– KM154 53
A1
A2
A1
A2
A1
A2
A1
A2
– KM1– KM3
2122
2221
1516
9596
– KM2
1413
A1
A2
– KM1
1314
2122
2221
– KM355
56
– KM2
1314
– KM1
9596
KM3/5
O
l
6867
– KM2
A1
A2
– KM3
2221
– KM1
A1
A2
– KM2
1314
– KM2
KM3/1
N
Remotecontrol
– KM2
12
34
56
– KM3
12
34
56
– KM1
12
34
56
U1
V1
W1
U2
V2
W2
1 3 5
2 4 6
L1 L2 L3
U1
V1
W1
U2
V2
W2
2 4 6
(1)
Recommended cabling for reversal of motor rotation (standard motor, viewed from shaft end).
A1
A2
– KM1
1314
2122
162
161
– KM3
5556
– KM2
184
183
– KM1
9596
– F1
– F1
O
l
153
154
– KM2
A1
A2
– KA1
A1
A2
– KM2
153
154
– KM1
– F2
171
6768
– KM2
172
– KM1
1314
A1
A2
– KM3
– KA1
Y L
Remotecontrol
Dimensions, schemes
TeSys motor starters - open version 1
Star-delta starters for motor control
References : pages 24547/2 to 24548/5
Star-delta startersOn mounting rail AM1-DP, pre-assembledLC3-D090A to D320A
Schemes
LC3-D090A to D320A
LC3-D115 and D150
LC3- D090A to D180A D320b 153 137c with LAD-S 139 145
with LAD-S and sealing cover 143 149
LC3-K, LC3-D09A to D80 LC3-K LC3-D
LC3-D09A to D18Amechanical interlockbetween KM3 and KM1(1) Recommended cabling forreversal of motor rotation(standard motor, viewed from shaft end)
25015_Ver4.10-EN.fm/2 Schneider Electric
0 0,25 0,50 0,75 1
1
2
0
,5
0 0,25 0,50 0,75 1
1
2
3
(1)1
,5
2
,5
Presentation Motor starters - open version 1
Star-delta starters for motor control
This method of starting is only applicable to 3-phasemotors whose delta connection corresponds to the mainsvoltage and on which all 6 stator terminals are accessible.
Star-delta starting should be used for motors starting onno-load or having a low load torque and gradual build-up:- the starting torque in star connection is reduced to onethird of the direct starting torque, i.e. about 50% of therated torque;- the starting current in star connection is about 1.8 to 2.6times the rated current.
The transition from star to delta connection must occurwhen the machine has run up to speed. A too rapid build-up in load torque would cause the stabilised run-up speedto be too low and would therefore eliminate any advantagein this method of starting: this is the case with certainmachines whose load torque depends on its speed (acharacteristic of centrifugal machines, for example).
Switching from star to delta connection must be completedwithin a minimum time.This function is performed by a control relay and a timedelay auxiliary contact block.
1 Starting in delta connection2 Starting in star connection
1 Starting in delta connection2 Starting in star connection3 Machine resistive torque
(1) Motor manufacturers generally specify the machine load torques.Example: maximum resistive torque on completion of star-delta start (expressed as a proportion of the rated torque).
Star-delta starting
Current
Speed
Speed
Torque
25015_Ver4.10-EN.fm/3Schneider Electric
Motor starters - open version 1
Star-delta starters for motor control,90 to 375 kW, (1) without isolating device, pre-assembled
Star-delta starters, pre-assembled
Maximum operating rate : 12 starts/hour.Maximum starting time :- LC3-F: 20 seconds.- LC3-FA64: 30 seconds (3 identical contactors).Composition of starters without mechanical interlock, see pages 25018/3 and 25018/5.
Standard power ratings Auxiliary contacts Star-delta Basic reference. Weightof squirrel cage motors available on mechanical Complete with code
each contactor interlock indicating controlline delta star circuit voltage (2)KM2 KM3 KM1
Mains voltage -delta connection220/ 380/ 415 V 440 V230 V 400 V (3)kW kW kW kW kg
90 160 160 185 1 2 2 1 1 1 Without LC3-F185 16.500
With LC3-F185A64 16.625
100 200 200 220 1 2 2 1 1 1 Without LC3-F225 16.500
With LC3-F225A64 16.625
110 220 220 250 1 2 2 1 1 1 Without LC3-F265 27.300
With LC3-F265A64 27.425
160 280 280 315 1 2 2 1 1 1 Without LC3-F330 37.000
With LC3-F330A64 37.125
185 315 355 375 1 2 2 1 1 1 Without LC3-F400 37.000
With LC3-F400A64 37.125
(1) Protection must be provided by the addition of an overload relay, to be ordered separately. Select appropriate relayfor setting at 0.58 of the full load rated motor current, see pages 27074/2 and 27074/3.(2) Standard control circuit voltages.
Volts 50/60 Hz 48 110 115 220/230 230 240 380/400 400 415Code E7 F7 FE7 M7 P7 U7 Q7 V7 N7For other voltages, please consult your Regional Sales Office.(3) One auxiliary contact block type LAD-N can be fitted.
References
LC3-FA64
Illustrations :page 25015/2
Dimensions :page 25019/2
Schemes :page 25019/3
25018_Ver2.10-EN.fm/2 Schneider Electric
See page 25018/4*
1
25018_Ver2.10-EN.fm/3Schneider Electric
Motor starters - open version 1
Star-delta starters for motor control, 90 to 375 kW, (1), for customer assembly (on chassis)
(1) Protection must be provided by the addition of an overload relay, to be ordered separately. Select appropriate relayfor setting at 0.58 the full load rated motor current, see pages 27074/2 and 27074/3.(2) Contactors supplied with coil. Complete the reference by adding the control circuit voltage code.Standard control circuit voltages (variable delivery times, please consult your Regional Sales Office).
LC1-D150
(3) For longer starting times, please consult your Regional Sales Office.(4) For other accessories, see page 25018/5.(5) Coil LX1: LC1-F265, F330 and F400; coil LX9: LC1F185 and F225.(6) Except for LC1-F400.
Contactors
Standard power ratings Contactors (2) Accessoriesof squirrel cage motors line delta star (see below)220/230 V 380/400 V 415 V 440 VkW kW kW kW KM2 KM3 KM1 Component type
Maximum operating rate: 12 starts/hour. Maximum starting time: 20 seconds (3)
90 160 160 185 LC1-F185 LC1-F185 LC1-D150 F185
100 200 200 220 LC1-F225 LC1-F225 LC1-F185 F225
110 220 220 250 LC1-F265 LC1-F265 LC1-F185 F265
160 280 280 315 LC1-F330 LC1-F330 LC1-F265 F330
185 315 355 375 LC1-F400 LC1-F400 LC1-F265 F400
Accessories (4)
Description Illustration For No. Sold in Unit Weightitem no. use with lots of reference kg
Instantaneous auxiliary 1 F185 to F400 3 1 LAD-N22 0.050contact blocks2 N/O + 2 N/C
Control relay 2 F185 to F400 1 1 CAD-N32 0.580
Time delay auxiliary 3 F185 to F400 1 1 LAD-T2 0.060contact blocks
Lead sealing kit 4 F185 to F400 1 1 LA9-D901 0.005
Thermal magnetic 5 F185 to F400 2 6 GB2-CB10 0.050circuit breaker for5 A control circuit
Set of 3 connectors for 6 F185 1 1 LA9-FG980 0.200wider terminals (option)
F225 to F400 1 1 LA9-FJ980 0.490
Sets of 7 F185 1 1 LA9-F18517 0.800power connections
F225 1 1 LA9-F22510 1.400
F265 1 1 LA9-FH610 1.400
F330 and F400 1 1 LA9-FJ610 1.500
Set of 3 busbars for 8 F185 to F400 1 1 LA7-F (Selected according to sizethermal overload of thermal overload relay) see pagesconnections 27074/2 and 27074/3.
Volts 48 110 115 120 220 230 240 380 400 41550/60 Hz E7 F7 FE7 G7 M7 P7 U7 Q7 V7 N7
LC1-F185 and F225Volts 48 110 115 120 220 230 240 380 400 41550 Hz (coil LX1) E5 F5 FE5 – M5 P5 U5 Q5 V5 N560 Hz (coil LX1) E6 F6 – G6 M6 – U6 Q6 – –
LC1-F185 to F400Volts 48 110 115 120 220 230 240 380 400 41540… 400 Hz (5) E7 (6) F7 FE7 G7 M7 P7 U7 Q7 V7 N7Standard voltages, see page 25008/2.For other voltages between 24 and 660 V, see pages 25014/2 to 25014/9.
References
Illustrations :page 25018/2
Dimensions :page 25019/2
Schemes :page 25019/3
25018_Ver2.10-EN.fm/4 Schneider Electric
See page 25018/2*
1
25018_Ver2.10-EN.fm/5Schneider Electric
Motor starters - open version 1
Star-delta starters for motor control, 90 to 375 kW, (1), for customer assembly (on chassis)
(1) Protection must be provided by the addition of an overload relay, to be ordered separately.Select appropriate relayfor setting at 0.58 the full load rated motor current, see pages 27074/2 and 27074/3.(2) Supplied in 2 m lengths. See page 25019/2 for cutting to length.
Accessories (continued from page 25018/3)
Description Illustration For No. Sold in Unit Weightitem no. use with lots of reference
Spare volt free terminal 9 F185 3 10 DZ3-GA3 0.006
F225…F400 3 10 DZ3-HA3 0.007
Neutral terminals with 10 F185 1 10 AB1-BC9535 0.236stop and sparevolt free terminal 2 100 AB1-AB8P35 0.006(for control circuit)
1 10 DZ3-HA3 0.007
F225 & F265 1 10 AB1-BC15035 0.277
2 100 AB1-AB8M35 0.007
1 10 DZ3-JA3 0.010
F330 & F400 1 10 AB1-BC24035 0.287
2 100 AB1-AB8M35 0.007
1 10 DZ3-JA3 0.010
Reducer bracket 11 F400 2 1 LA9-F100 0.100
Mounting rails (2) 12 F185…F400 1 10 AM1-DE200 0.900
13 F185…F400 1 4 AM1-EC200 2.980
Uprights (2) 14 F115…F400 2 4 AM1-EC200 2.980
1/4 turn sliding 15 F185…F400 2 10 AF1-CD061 0.020nuts and boltsfor mounting rail AM1-DE
100 AF1-VA618 0.006
1/4 turn sliding 16 F185…F400 8 10 AF1-CD081 0.020nuts and boltsfor mounting rail AM1-EC
10 AF1-VC820 0.024
1/4 turn sliding 17 F185…F330 15 10 AF1-CD061 0.020nuts and boltsfor mounting equipment 100 AF1-VA618 0.006
F400 8 10 AF1-CD061 0.020
10 AF1-CD081 0.020
100 AF1-VA618 0.006
10 AF1-VC820 0.024
4 – 25 x H6 screws with washers
Enclosures: metal, – F185…F225 1 1 ACM-GV763 19.090grey RAL 7032
F265 1 1 ACM-GV973 33.310
F330 & F400 1 1 ACM-GV1084 54.000
Fixing lugs – – 4 4 AE3-FX122 0.080adjustable forenclosure ACM
References (continued)
Illustrations :page 25018/4
Dimensions :page 25019/2
Schemes :page 25019/3
Motor starters - open versionintegral 18, 32 and 63 contactor breakers and reversing contactor breakers
Applications 3-phase automatic motor starter ensuring operating reliability. Overall concept allowing protection, power switching, fully
Standard 220/240 0.06 0.09 0.12 0.25 0.55 0.75 1.5 2.2 4power 0.18 0.37 1.1 3ratings 400/415 0.06 0.09 0.12 0.18 0.37 0.55 1.1 1.5 3 4 9of motors 0.25 0.75 2.2 5.5(50/60 Hz), 440 V 0.37 0.55 1.1 1.5 2.2 4 5.5 9in kW 480/525 V 0.37 0.75 1.1 2.2 3.7 5.5 7.5 11
600/690 V 0.37 0.55 1.1 1.5 3 4 7.5 10 15
Adjustable thermal protection Min 0.10 0.16 0.25 0.40 0.63 1.00 1.6 2.5 4 6 10 12(Irth) (A) Max 0.16 0.25 0.40 0.63 1.00 1.60 2.5 4 6 10 16 18
Magnetic protection (A)Fixed at 15 x Irth max 2.4 3.75 6 9.45 15 24 37.5 60 90 150 195 270
Adjustable: 6 Min – – – – – – – – – – – –to 12 Irth max Max – – – – – – – – – – – –
Breaking 220/240 V ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 50 (65) 50 (65) 50 (65)capacity 400/415 V ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 50 (65) 50 (65) 50 (65)in kA w/o 440 V ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 50 (65) 50 (65) 25 (65) 25 (65)(or with) 480/525 V ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 50 (65) 10 (65) 7.5 (65) 7.5 (65)limiter (1) 600/690 V ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 50 (50) 50 (50) 5 (42) 5 (42) 2 (42) 2 (42)
Rated operational 18 Acurrent in AC-43
Number of poles and 3-pole, non reversingoperating directions 2 x 3-pole, reversing
LockingWithout control test functioon YesWith control test function No
Type references of LD1-LB (2) + LB1-LB03P.contactor-breakers + LD5-LB (2) + LB1-LB03Pprotection modulesor complete unit (2) or LD3-LB (3)
Pages 21154/2 to 21154/11 There are no standard power ratings for these motors.(1) The breaking capacity with current limiter is shown in brackets.(2) Without control test function, with padlocking facility.
Selection guide
visible isolation and padlocking. For control and protection of resistive circuits in AC-1, see references pages 4/116 and 4/117
0.06 0.09 0.18 0.37 0.55 1.1 1.5 3 5.5 7.5 3 4 5.5 7.5 9 11 150.12 0.25 0.75 2.2 2.2
1.1 1.5 2.2 4 7.5 11 15 5.5 9 11 15 22 25 33
0.37 0.55 1.1 1.5 2.2 4 7.5 11 15 5.5 9 11 15 22 25 33 0.37 0.75 1.1 2.2 3.7 5.5 10 15 18.5 7.5 11 15 18.5 25 33 40 0.55 1.1 1.5 3 4 7.5 11 18.5 25 10 15 18.5 22 33 45 55
0.25 0.40 0.63 1.00 1.6 2.5 4 6.3 10 16 23 10 13 18 23 28 35 450.40 0.63 1.00 1.60 2.5 4.0 6.3 10 16 25 32 13 18 25 32 40 50 63
– – – – – – – – – – – 195 270 375 480 600 750 945
2.4 3.78 6 9.6 15 24 37.8 60 96 150 192 78 108 150 192 240 300 3784.8 7.56 12 19.2 30 48 75.6 120 192 300 384 156 216 300 384 480 600 756
≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 50 (65) 50 (65) ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 50 (65) 50 (65) ≥130 ≥130 ≥130 50 50 50 50≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 50 (65) 50 (65) 50 (65) ≥130 ≥130 50 50 50 50 50≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 ≥130 15 (65) 15 (65) 15 (65) ≥130 ≥130 35 35 30 30 30≥130 ≥130 ≥130 ≥130 ≥130 ≥130 15 (42) 10 (42) 4 (42) 4 (42/20) 4 (42/20) 10 10 10 10 10 10 10
32 A 63 A
3-pole, non reversing2 x 3-pole, reversing
3-pole, non reversing2 x 3-pole, reversing
Yes YesYes Yes
LD1-LC (2) + LB1-LC03P (5). LD1-LD (2) + LB1-LD03 (6).LD4-LC (4) + LB1-LC03P (5). LD4-LD (4) + LB1-LD03 (6),LD5-LC (4) + LB1-LC03P (5) LD5-LD (4) + LB1-LD03 (6)
21157/2 to 21157/13 21160/2 to 21160/13(3) Complete unit consisting of a contractor-breaker with protection module, supplied assembled.(4) With control test function and padlocking facility. Black or red knob on yellow background.(5) Fixed magnetic protection. (6) LB1-LD03M for adjustable magnetic protection or LB1-LD03P for fixed magnetic protection.
21151_Ver2.10-EN.fm/2 Schneider Electric
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
General
Integral : a high performance concept for reliability of operation
Functions performedby integral units
Power switching
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Dimensions, schemes :pages 21009/2 to 21011/5
Integral 18, 32 and 63 contactor breakers combine all the functions of a powerswitching assembly up to 63 A in a single compact device.
They conform to the main standards currently in force, in particular IEC 947-1,IEC 947-2, IEC 947-3, IEC 947-4-1 and IEC 947-6-2 (welding of power polesimpossible), as well as to international approvals UL, CSA…, and the Europe-an directives.
The integral range ensures reliability of operation up to 63 A. In addition tosafety of operation, integral has numerous other functions: increased protection,communication, remote control, fault identification, isolation, padlocking.
The equipment in a power switching circuit must perform 4 main functions: power switching, isolation, overload protection, short-circuit protection.These functions are traditionally performed by separate devices which must be combined to form a motor starterassembly, the most common being:- fuses + contactor + thermal overload relay,- circuit breaker + contactor + thermal overload relay.
Contactor (for automatic and remote control)
Operational power for use in cate-gory AC-43 : - up to 30 kW at 400/415 V 50 Hz.- up to 33 kW at 440 V 50 Hz.
Electrical life in number of operat-ing cycles, in category AC-43, at415 V and at rated power:- 2 million for integral 18, - 1.5 million for integral 32, - 1.2 million for integral 63.
Mechanical life in number of oper-ating cycles:- 20 million operating cycles for inte-gral 18, - 10 million for integral 32, - 5 million for integral 63.
Reversing pairs
Two 3-pole contactors, horizontallymounted:- mechanically and electrically inter-locked for integral 18.- mechanically interlocked for inte-gral 32 and 63.
Can be fitted with the same protec-tion modules as integral contactorbreakers.
21151_Ver2.10-EN.fm/3Schneider Electric
Isolation conforming to IEC 947
Integral 18, 32 and 63 contactor breakers provide isolation and padlockingfunctions conforming to standards IEC 947. In addition, integral 32 and 63 “LD4” contactor breakers and “LD5” reversingcontactor breakers incorporate specific poles for control testing and padlock-ing.
Thermal-magnetic protection module (for protection against overload andovercurrent)
A range of interchangeable modulesallows the equipment to be adaptedto suit: the rated operational current (rat-
ing and settings), the application:- motors,- frequent starting motors,- distribution circuits.
High breaking capacity current limiting circuit breaker
For short-circuit protection.
High breaking capacity with short-circuit limited by ultra-fast tripping.
Possibility of increasing the breakingcapacity of the integral unit by addinga current limiter (LA9-LB920).
The current limiter is fitted upstreamof the integral unit.Several integral units may be fitteddownstream of the current limiter
These devices provide comprehensive local signalling:- pole position indicator,- different signalling for “overload” and “short-circuit”.
They also allow dialogue with the automated control system by means of numer-ous add-on blocks:- auxiliary contact and signalling blocks,- remote electrical reset device for integral 32 and 63,- undervoltage and shunt trips for integral 32 and 63,- control circuit switching,- etc.
Integral 18 and 32 contactor breakers and reversing contactor breakers clip directly onto 35 mm rails.Integral 63 contractor breakers and reversing contactor breakers fit onto 75 mm rails using a separatemounting plate.Integral units can also be mounted on:- panels,- pre-slotted mounting plates type AM1-P,- 2 x 35 mm rails using sliding clip nuts,- CMD prefabricated plug-in busbar trunking (providing an economical assembly, combining safety andsimplicity of use),- AK5 panel busbar systems.
(Ith = 63 A, Ie = 32 A).
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
General
Signalling and attachments
Simple fixing andcabling methods
Functions performed by integral units (continued)
Isolation
Overloadprotection
Short-circuitprotection
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Dimensions, schemes :pages 21009/2 to 21011/5
21151_Ver2.10-EN.fm/4 Schneider Electric
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Note: these definitions are based on extracts from standard IEC 947.
(1) Conventional free air thermal current, conforming to IEC standards.
Altitude The rarefied atmosphere at high altitude reduces the dielectric strength of theair and hence the rated operational voltage of the contactor breaker. It alsoreduces the cooling effect of the air and hence the rated operational currentof the contactor breaker (unless the temperature drops at the same time).
No derating is necessary up to 3000 m.
Derating factors to be applied above this altitude for main pole operationalvoltage and current (a.c. supply) are as follows:
Altitude 3500 m 4000m 4500m 5000m
Rated operational voltage 0.90 0.80 0.70 0.60Rated operational current 0.92 0.90 0.88 0.86
Ambient air temperature The temperature of the air surrounding the device, measured near to thedevice. The operating characteristics are given:- with no restriction for temperatures between - 5 and + 55 °C.- with no restrictions, if necessary, for temperatures between - 50 and + 70 °C.
Rated operational current (le) This is defined taking into account the rated operational voltage, operatingrate and duty, utilisation category and air temperature around the device.
Rated conventional thermal current(Ith) (1)
The current which a closed contactor breaker can sustain for a minimum of 8hours without its temperature rise exceeding the limits given in the standards.
Short time rating The current which a closed contactor breaker can sustain for a short time,after a period of no load, without dangerous overheating.
Rated operational voltage (Ue) This is the voltage value which, in conjunction with the rated operational cur-rent, determines the use of the contactor breaker or starter, and on which thecorresponding tests and the utilisation category are based. For 3-phase cir-cuits, it is expressed as the voltage between phases.Apart from exceptional cases such as rotor short-circuiting, the rated opera-tional voltage Ue is less than or equal to the rated insulation voltage Ui.
Rated control circuit voltage (Uc)
The rated value of the control circuit voltage, on which the operating charac-teristics are based. For a.c. applications, the values are given for a near sinu-soidal wave form (less than 5% total harmonic distortion).
Rated insulation voltage (Ui) This is the voltage value used to define the insulation characteristics of adevice and referred to in dielectric tests determining leakage paths andcreepage distances. As the specifications are not identical for all standards,the rated values given for each of them are not necessarily the same.
Rated impulse withstand voltage (Uimp)
This is the highest peak value of an impulse voltage, of prescribed form andpolarity, which the device is able to withstand without failure under specifiedtest conditions, and to which isolation clearance values are referred.The ratedimpulse withstand voltage of a device must be equal to or higher than the val-ues stated for the transient overvoltages appearing in the circuit in which thedevice is fitted
Rated operational power(expressed in kW)
The rated power of the standard motor which can be switched by the contac-tor breaker, at the stated operational voltage.
Terminology
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Dimensions, schemes :pages 21009/2 to 21011/5
21151_Ver2.10-EN.fm/5Schneider Electric
t
T
Note: these definitions are based on extracts from standard IEC 947.
(1) For a.c. applications, the breaking and making capacities are expressed by the rms value of the symmetricalcomponent of the short-circuit current. Taking into account the maximum asymmetry which may exist in the circuit, thecontacts therefore have to withstand a peak asymmetrical current which may be twice the rms symmetrical component.
Rated breaking capacity(lq) (1)
This is the current value which the contactor breaker can break in accordancewith the breaking conditions specified in the IEC standard
Rated making capacity (1) This is the current value which the contactor breaker can make in accordancewith the making conditions specified in the IEC standard.
On-load factor (m) This is the ratio between the time the current flows (t) and the duration of thecycle (T):
m =
Cycle duration: duration of current flow + time at zero current.
Pole impedance The impedance of one pole is the sum of the impedance of all the circuitcomponents between the input terminal and the output terminal.
The impedance comprises a resistive component (R) and an inductivecomponent (X = Lω). The total impedance therefore depends on thefrequency and is normally given for 50 Hz. The average value is given for thepole at its rated operational current.
Electrical durability This is the average number of on-load operating cycles which the main polecontacts can perform without maintenance. The electrical durability dependson the utilisation category, the rated operational current and the ratedoperational voltage.
Mechanical durability This is the average number of no-load operating cycles (i.e. with zero current flow through the main poles) which the contactor breaker can perform without mechanical failure.
Coordination The coordination of protection devices involves combining, in a selective way,a short-circuit protection device (fuses or magnetic circuit breakers) with acontactor and an overload protection device. Its objective is to break anyabnormal current, in plenty of time, without any danger to personnel whilstproviding adequate protection of the equipment against an overload or ashort-circuit current.
Type 1 - IEC 947-4-1In a short-circuit condition, the contactor or starter must not present any dangerto personnel or installations and may not be able to resume operation withoutrepair or the replacement of parts.
Type 2 - IEC 947-4-1In a short-circuit condition, the contactor or starter must not present any dangerto personnel or installations and must be able to resume operation. The risk ofcontact welding is permissible if they can be easily separated.
Total, ensuring reliability of operation - IEC 947-6-2In the event of a short-circuit, no damage or risk of welding is permissible onthe equipment constituting the motor starter. Operation can be resumedwithout any maintenance.
Terminology (continued) Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
tT
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Dimensions, schemes :pages 21009/2 to 21011/5
21151_Ver2.10-EN.fm/6 Schneider Electric
The standard utilisation categories define the current values which the contactor breaker must be able to make or break.These values depend on:- the type of load being switched: squirrel cage or slip ring motor, resistors,- the conditions under which making or breaking takes place: motor stalled, starting or running, reversing, plugging.
IEC 947-6-2: control and protection devices
IEC 947-4-1Standard IEC 947-4-1: covering contactors and electromechanical motor starters.It concerns:- types of equipment with main contacts designed for connection to circuits whose rated operational voltage does notexceed 1000 V for a.c. applications or 1500 V for d.c. applications,- contactors used in conjunction with overload and/or short-circuit protection devices,- motor starters used in conjunction with separate short-circuit protection devices and/or with separate short-circuitprotection devices and built-in overload protection devices,- contactors and combination motor starters which incorporate their own short-circuit protection device.
Utilisation categories for a.c. applications
Category AC-1This category applies to all types of a.c. load with a power factor equal to or greater than 0.95 (cos ϕ ≥ 0.95). Noninductive or slightly inductive loads.Application examples: heating, distribution.
Category AC-2This category applies to starting, plugging and inching of slip ring motors. On closing, the contactor breaker makes the starting current, which is about 2.5 times the rated current of the motor. On opening, it must break the starting current, at a voltage less than or equal to the mains supply voltage.
Category AC-3This category applies to squirrel cage motors with breaking during normal running of the motor. On closing the contactor breaker makes the starting current, which is about 5 to 7 times the rated current of the motor. On opening, it breaks the rated current drawn by the motor; at this point, the voltage at the contactor breaker
terminals is about 20% of the mains supply voltage. Breaking is light.Application examples: all standard squirrel cage motors (lifts, escalators, conveyor belts, bucket elevators,compressors, pumps, mixers, air conditioning units, etc.)
Category AC-4This category covers applications with plug braking and inching of squirrel cage motors.On closing, the contactor breaker makes a current peak which may be as high as 5 or 7 times the rated motor
current.On opening, it breaks this same current at a voltage which is higher, the lower the motor speed. This voltage can
be the same as the mains voltage. Breaking is severe.Application examples: printing machines, wire drawing machines, hoisting equipment, metallurgy industry.
IEC 947-5Standard IEC 947-5-1: covers switching devices and components for control circuits.It concerns electromechanical devices for control circuits.
Utilisation categories for a.c. applications
Category AC-14 (2)This category applies to the switching of electromagnetic loads whose power drawn with the electromagnet closed isless than 72 VA.Application example: switching the operating coil of contactors and relays.
Category AC-15 (2)This category applies to the switching of electromagnetic loads whose power drawn with the electromagnet closed isgreater than 72 VA.Application example: switching the operating coil of contactors.
(1) Ir = protection module setting current(2) Replaces category AC-11.(3) Replaces category DC-11.
IEC 947-1: general rules IEC 947-2: circuit breakers IEC 947-3: isolating devices
Tripping classes The creation of thermal tripping classes allows better adaptation of the thermalof protection modules Class 10 A
Tripping time at 7.2 Ir (1) 2…10 seconds
Terminology (continued) Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Definition
Reminder of standardsIEC 947
Standards for contactor breakers
Standards forauxiliary contacts
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Dimensions, schemes :pages 21009/2 to 21011/5
21151_Ver2.10-EN.fm/7Schneider Electric
1
IEC 947-6-2Standard IEC 947-6: covers multi-function equipment.It concerns connection, switching and protection devices (or equipment) with main contacts designed for connection to circuits whose rated operational voltageis less than or equal to 1000 V for a.c. applications, or 1500 V for d.c. applications. Such devices are designed to perform both the power switching function and the protection of remotely controlled circuits function; they can also perform otherfunctions, such as isolation.
After short-circuit (Isc) tests, the products must be able to make and break the currents corresponding to the specified utilisation categories, and to thenumber of operating cycles specified in the standard, without failing. This series of tests is completed by temperature rise tests. Standard IEC 947-6-2specifies that, in the event of a short-circuit, no damage or risk of contact welding is permissible on the devices constituting the motor starter.The integral contactor breaker, through its design, ensures reliability of operation. After eliminating the fault, operation can be resumed instantlywithout any maintenance work on the product, other than resetting.
Utilisation categories for a.c. applications
Category AC-41This category applies to all types of a.c. device (load) with a power factor equal to or greater than 0.95 (cos ϕ ≥ 0.95). Non inductive or slightly inductive loads.Application examples: heating, distribution
Category AC-42This category applies to starting, plugging and inching of slip ring motors. On closing, the contactor breaker makes the starting current, which is about 2.5 times the rated current of the motor. On opening, it must break the starting current, at a voltage less than or equal to the mains supply voltage.
Category AC-43This category applies to squirrel cage motors with breaking while motor running; inching or occasional reversing of limited duration are permissible if the numberof operating cycles does not exceed 5 per minute, or 10 within a 10 minute period. On closing the contactor breaker makes the starting current, which is about 5 to 7 times the rated motor current. On opening, it breaks the rated current drawn by the motor; at this point, the voltage at the contactor breaker terminals is about 20% of the mains supplyvoltage. Breaking is light.Application examples: all standard squirrel cage motors (lifts, escalators, conveyor belts, bucket elevators, compressors, pumps, mixers, air conditioning units,etc...).
Category AC-44This category covers applications with plug braking and inching of squirrel cage or slip ring motors. On closing, the contactor breaker makes a current peak which may be as high as 5 or 7 times the rated motor current. On opening, it breaks this same current at a voltage which is higher, the lower the motor speed. This voltage can be the same as the mains voltage. Breakingis severe.Application examples: printing machines, wire drawing machines, hoisting equipment, metallurgy industry.
protection to suit different motor and application technologies (short or long starting times). Conforming to IEC 947-4-1 and IEC 947-6-2.
Utilisation category for d.c. applications
Category DC-13 (3)This category applies to the switching of electromagnetic loads for which the time taken to reach 95 % of the steady state current (T = 0.95) is equal to 6times the power P drawn by the load (with P ≤ 50 W).Application example: switching the operating coil of contactor breakers.
IEC 947-4-1: contactors and motor starters IEC 947-5-1: control and signalling units
10 20 304...10 seconds 6…20 seconds 9…30 seconds
21152_Ver2.11-EN.fm/2 Schneider Electric
PEN B B'
C C'
When designing an installation, it is essential to take into account precise criteria for determining the conductor c.s.a.and selecting equipment.
In particular:- permissible currents for the conductors,- maximum voltage drops,- short-circuit protection,- protection against indirect contact.
The latter three criteria must be taken into account when selecting the integral unit.
The principle behind the rules described below is, on the whole, common to all European publications. However, thecalculations and values concerning protection against indirect contact are based on French standard NF C 15-100, andit is up to the user to check the regulations in force in the country concerned.
To achieve this, the thermal setting value Irth selected must be greater than the current drawn IB and less than or equalto the permissible current Iz in the cable to be protected.IB < Irth ≤ Iz
Breaking capacity rule: check that the breaking capacity (BC) of the integral unit is equal to or greater than theprospective short-circuit current (Isc max) at the point where it is to be installed.BC ≥ Isc max
Breaking time rule: 2 conditions must be fulfilled:
- The short-circuit current at the end of the circuit, Isc min, must be greater than or equal to the minimum currentrequired for magnetic tripping of the device,
- The short-circuit current at the start of the circuit, Isc max, must be such that:
These 2 checks need only be made when modules with a low rating are used.
Example: for a 6.3/10 A module, a cable c.s.a. ≥ than 2.5 mm2 is required to withstand Isc max = 50 kA.
Multiple earthed neutral scheme
Neutral is connected to earth.
The earths are connected to neutral.
Any phase/earth insulation fault causes a short-circuit.
As contact voltage is dangerous, breaking must occur at the first fault.
The PE conductor and the neutral conductor may be:- combined (TNC scheme),- separate (TNS scheme).
Cable protection against short-circuit
Short-circuit protection
I2sc max tm ≤ I2oto I2oto = permissible thermal stress limit for the circuit,tm = operating time of the integral unit or of the short-circuit protection device.
Protection against indirect contact in TN schemes
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Equipment selection for starters
General :pages 21151/2 to 21151/7
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Dimensions and schemes :pages 21009/2 to 21011/5
A
TNC scheme
21152_Ver2.11-EN.fm/3Schneider Electric
c.q.Uo.Sph2ρ.1.µ Irth
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Protection against indirect contact (TN schemes), for dead shorts only, requires that the following 2 conditions befulfilled simultaneously:
- The fault current Id must be greater than or equal to the minimum current required for magnetic tripping of the integralunit, i.e. 1.12 µ Irth max.
c = coefficient taking into account the upstream part of the fault loop impedanceassumed to be equal to 0.8, unless otherwise indicated.q = coefficient dependent on the earth connection scheme and equal to 1 in the TNscheme.Uo = phase-neutral voltage in volts.Zb = fault loop impedance in mΩ/m such that: Zb ≠ R (fault loop resistance).
L = length of the fault loop equal to twice the length Lc of the circuit.S = Sph, c.s.a of the phase conductors = SPE = c.s.a. of the protective conductorsρ = resistivity of the copper = 0.0225.
µ = ratio between the magnetic tripping current and the maximum setting current ofthe instantaneous thermal tripping device.
- The contact voltage (UL) for a dead short is at most equal to the value determined by the safety curve for the operatingtime tm of the integral unit in its magnetic tripping zone.This condition is generally fulfilled for power supplies of 230/415 V. (In fact, for UL = 50 V, a tm ≤ 500 ms would berequired and for UL = 25 V, a tm ≤ 110 ms would be required).
The first condition allows us to calculate the maximum length of the circuit to provide protection against indirect contactin the TN scheme.
For the TN scheme:
i.e. L max =
Protection against indirect contact in TN schemes (continued)
L ≤
Maximum length of 230/415 V circuits with TN scheme
Irth max µ = 3 µ = 6 µ = 12 µ = 15mm2 A m m m m
1.5 10 180 90 45 3616 112 56 28 22
2.5 10 298 149 75 6016 186 93 47 3725 118 59 32 –32 92 46 23 –
4 16 296 148 74 6025 190 95 48 –32 148 74 37 –40 118 59 30 –
6 25 284 142 71 –3240 178 89 45 –50 142 71 36 –
10 32 370 185 93 –40 296 148 74 –50 236 118 59 –63 188 94 47 –
16 32 590 295 148 –40 472 236 118 –50 378 189 95 –63 300 150 75 –
25 32 922 461 281 –40 738 369 185 –50 590 295 148 –63 468 234 117 –
Equipment selection for starters
R = ρ = 2 ρLS
LcS
0.8 x Uo x Sph2 x 0.0225 x 1.2 µ Irth max
Id = c.q.Uo Zb
General :pages 21151/2 to 21151/7
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Dimensions and schemes :pages 21009/2 to 21011/5
21152_Ver2.11-EN.fm/4 Schneider Electric
1 1,5 2 3 4 5 67
8
9
10
20 40 60
80
1001502003000,01
0,02
0,04
0,060,08
0,1
0,2
0,4
0,60,8
1
1,52
4568
10
20
18 45
12
1 1,5 2 3 4 5 67
8
9
10
20 40 60 80
100
150200300
32 63 160
0,01
0,02
0,04
0,060,08
0,1
0,2
0,4
0,60,8
1
1,52
4568
10
20
(63 A)
(32 A)
112
AC-3AC-42AC-43AC-2
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Rated operational currents (according to the rated operational voltage)
Rated operational powers (for standard motors)
Electrical durability
Control and protection of motors at Ue ≤ 415 V :- in utilisation categories AC2, AC3 conforming to IEC 947-4-1,- in utilisation categories AC42, AC43 conforming to IEC 947-6-2.
1 Not having previously broken a short-circuit current2 Having broken a short-circuit current 10 times at 30 Ie (most common values of short-circuit current during operation)
Selection for a temperature θ ≤ 40 °C
Rated operational voltage V 220/240 400/415 440 480/525 600/690
integral 18 A 18 18 18 18 18
integral 32 A 32 32 32 32 32
integral 63 A 63 63 63 63 63
integral 18 kW 4 9 9 11 15
integral 32 kW 7.5 15 15 18.5 25
integral 63 kW 15 33 33 37 55
integral 18 integral 32 and 63
Selection according to utilisation category and required electrical durability
Currentbreakinglimits
In categories
Millions of operating cycles Millions of operating cycles
Current broken in A Current broken in A
General :pages 21151/2 to 21151/7
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Dimensions and schemes :pages 21009/2 to 21011/5
21152_Ver2.11-EN.fm/5Schneider Electric
0,01
0,02
0,04
0,060,08
0,1
0,2
0,4
0,60,8
1
1,52
4568
10
20
3 4 5 6 7 8 9 10 18 32 6320 40 60 80 100
(18 A) (32 A)
(63 A)
Rated operational currents (according to ambient temperature)
Maximum operating rates in operating cycles/hour
Electrical durability Ue ≤ 415 V
Note: for use in category AC-44, please consult your Regional Sales Office.
a.c. supply, utilisation categories AC-1, AC-3, AC-41, AC-43
With cable c.s.a. θ ≤ 40 °C θ ≤ 55 °C θ ≤ 70 °C
integral 18 4 mm2 A 18 16 14
integral 32 6 mm2 A 32 28 25
integral 63 16 mm2 A 63 55 50
a.c. supply, utilisation categories AC-1, AC-41
On-load factor 85 % On-load factor 25 % Operation Operation Operation
at Ie max at 0.5 Ie at Ie max
integral 18 Operating cycles/h 600 1200 900
integral 32 Operating cycles/h 1200 2400 1800
integral 63 Operating cycles/h 1200 2400 1800
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Selection according to utilisation category and required electrical durability
Current broken in A
Millions of operating cycles
General :pages 21151/2 to 21151/7
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Dimensions and schemes :pages 21009/2 to 21011/5
21153_Ver3.10-EN.fm/2 Schneider Electric
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakers
(1) With converter.(2) The closing time “C” is measured from the moment the coil supply is switched on to initial contact of the main poles.The opening time “O” is measured from the moment the coil supply is switched off to the moment the main poles separate.
Type integral 18Number of poles 3
Rated operational current (Ie) In AC-43 A 18Rated operational voltage (Ue) V 690
Electrical durability in AC-43 at 415 V 2 million operating cycles
Mechanical durability at Uc 10 million operating cycles
Maximum operating rate 1200 operating cycles/hourat ambient temperature ≤ 55 °C with converter 600 operating cycles/hour
Environment
Conforming to standards IEC: 947-1, 947-2, 947-3, 947-4-1, 947-6-2VDE: 0100, 0110, 0113, 0170, 0171, 471, 0660EN 60 947-1, 60 947-2, 60 947-3, 60 947-4-1, 60 947-6-2NEN, NBN
Product certifications ASE, ASEFA, ASTA, CSA DEMKO, DNV NEMKO, RINA, SEMKO, SETI, UL
Protective treatment “TH”
Ambient air temperature Operation °C - 20…+ 60around the device Storage °C - 40…+ 80
Operation °C - 25…+ 50(1) Storage °C - 25…+ 70
Vibration resistance 5…100 Hz Energised state: 3 gn Permissible acceleration De-energised state: 3 gn
Shock resistance Impulse duration: 11 ms Energised state: 8 gn Permissible acceleration De-energised state: 8 gn
Degree of protection To IEC 144 and 529 IP 20BTo VDE 0106 Protection against direct finger contact
Flame resistance Conforming to IEC 295-2-1, NF C 20-455, and decree of 22-12-81 (JO 27 NC of 1st and 2/2/1982)Conforming to UL 94 - V0 and NF T 51-072
Maximum operating altitude Without derating m 3000
Operating positions In relation to From fixing From main(without derating) normal vertical plane axis
mounting plane (fore-aft (left-righttilt) tilt)
Control circuit characteristics
Rated control 50 Hz V 21…660 circuit voltage (Uc) 60 Hz V 21…600
with converter V 24
Voltage limits Operating 0.85…1.1 Ucat θ ≤ 55 °C Drop out 0.25…0.7 Uc
Average consumption Inrush VA 75 (50 Hz), 90 (60 Hz)at 20 °C and at Uc Sealed VA 8 (50 Hz), 9 (60 Hz)
(1) Inrush W 100Sealed W 1.5
Heat dissipation W 2.5 (50 Hz), 2.8 (60 Hz)
Operating time (2) 50/60 Hz “C” ms 9…25at 20 °C and at Uc “O” ms 7…25
with “C” ms 15…20converter “O” ms 20…25
Characteristics
General:pages 21151/2 to 21151/7
Selection:pages 21152/2 to 21152/5
References:pages 21162/2 to 21164/3
Dimensions, schemes:pages 21009/2 to 21011/5
21153_Ver3.10-EN.fm/3Schneider Electric
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakers
Type integral 18
Pole characteristics
Conventional thermal current (Ith) θ ≤ 40 °C A 18Frequency limits of operational current Hz 40…60Rated impulsewithstand voltage (Uimp) Conforming to IEC 947-4 kV 6 in enclosure
Rated insulation voltage (Ui) Conforming to IEC 947-1 V 690
Heat dissipation in the power Operational current A 0.16 0.25 0.4 0.6 1 1.6 2.5 4 6 10 16 18circuits of the contactor breakerand its protection module Power per pole, hot state W 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.4 2.9 3.2 3.8 3.8
Rated making I rms Conforming to IEC 947-4 A 15 x Ith (above this value, the breaker trips)capacity I peak Conforming to IEC 947-2 kA 105
Rated breaking capacity Operating voltage V 220/240 380/415 440 480/525 600/690to IEC 947-2 Value of cos ϕ 0.25 0.25 0.25 0.3 0.5
Icu (O-t-CO) kA rms 50 50 40 10 4Ics (O-t CO-t-CO) kA rms 50 50 50 10 5
to IEC 947-6-2 Icu = Ics kA rms 50 50 25 7.5 2ensuring reliability of operation O-t-CO-t-rCO
O: breaking short-circuit current (open); t: timeCO: closing on short-circuit, breaking short-circuit current (closed-open - manual)rCO: closing on short-circuit, breaking short-circuit current (closed-open - remote control)
Total breaking time ms 2.5
Thermal limit With Isc max at 415 V, 50 Hz A2s 100 x 103
American Wire GaugeCabling Maximum c.s.a. Minimum c.s.a. AWG
Flexible cable without cable end mm2 2 x 6 2 x 1.5 2 x AWG 16 toFlexible cable with cable end mm2 2 x 4 or 1 x 6 2 x 1 2 x AWG 10Solid cable mm2 2 x 6 2 x 1.5
Tightening torque N.m 1.7
Characteristics of thermal-magnetic or magnetic only protection modules
Type LB1-LB03P
Protection Standard motorsConforming to standards IEC 947-6-1, IEC 947-6-2Number of poles 3Number of protected poles 3Rated operational voltage V 690Maximum continuous current A 0.16…18
Thermal protection Setting range (Irth min/Irth max) A 0.1/0.16…12/18
Temperature compensation °C - 20…+ 60
Protection against Withphase imbalance
Tripping class 10
Magnetic protection Instantaneous trip current Fixed at 15 Irth maxconforming to IEC 947-1/2/4/6-2 setting range
Tripping tolerance ± 20 %
Characteristics of versions without control test function, with padlocking facility
Conforming to standards IEC 947
Rated operational voltage V 690
Electrical durability Operating cycles 10 000
Padlocking facility 1 padlock, Ø 5 shank
Characteristics
General:pages 21151/2 to 21151/7
Selection:pages 21152/2 to 21152/5
References:pages 21162/2 to 21164/3
Dimensions, schemes:pages 21009/2 to 21011/5
21153_Ver3.10-EN.fm/4 Schneider Electric
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakersAdd-on current limiter and auxiliary contacts
(1) Electrical durability on an inductive load such as the coil of an electromagnet:making current (cos ϕ 0.7) = 10 times the breaking current (cos ϕ 0.4).(2) Electrical durability on an inductive load such as the coil of an electromagnet, the time constant increasing with theload.(3) Lamp load: peak current = 10 times the rated current.(4) Inductive load: cos ϕ 0.4 for a.c. operation; time constant 7 ms for d.c. operation.(5) Motor: peak current = 6 times the rated current.
Add-on current limiter LA9 LB920
Rated insulation voltage (Ui) Conforming to IEC 947-1 V 690 (50/60 Hz)
Rated operational voltage (Uc) V 690 (50/60 Hz)
Conventional thermal current (Ith) Conforming to IEC 947-6-2 A 63
Operational thermal current (Ie) A 32
Operating threshold rms current A 1000 (non adjustable threshold)
Cabling Solid cable mm2 1 x 1.5 to 25 conductor, or 2 x 1.5 to 10 identical conductorsFlexible cable without cable end mm2 1 x 1.5 to 25 conductor , or 2 x 1.5 to 10 conductorsFlexible cable with cable end mm2 1 x 1.5 to 16 conductor , or 2 x 1.5 to 4 conductors
Tightening torque N.m 2.2
Instantaneous auxiliary contacts
Conventional thermal current (Ith) A 10
Rated insulation voltage (Ui) Conforming to IEC 947-5-1 V 690
Switching capacity With U ≥ 17 V and I ≥ 10 mA mVA 600
Rated category AC-15 (1) Voltage V 48 110/127 220/240 380/415 440operational 1 million operating cycles VA 300 500 600 520 500power 1.5 million operating cycles VA 160 300 330 300 280
Making capacity category AC-15 VA 1500 3500 6000 7500 7000
Rated category DC-13 (2) Voltage V 24 48 110 220 440operational 1 million operating cycles W 120 90 75 68 61power 1.5 million operating cycles W 70 50 38 33 28
Making capacity category DC-13 W 800 700 400 260 220
Cabling mm2 Maximum c.s.a.: 2 x 2.5. Minimum c.s.a.: 2 x 1
Signalling contacts
Conventional thermal current (Ith) A 6
Rated insulation voltage (Ui) Conforming to IEC 947-5-1 V 690
Operational power Voltage V – – 110/127 220for 200 000 operating cycles Resistive load VA – – 600 750
Lamp load (3) VA – – 90 125
Inductive load (4) VA – – 875 500
Motor (5) VA – – 160 200
Voltage V 24 48 110/125 200
Resistive load W 100 100 50 50
Lamp load (3) W 50 50 6 7.5
Inductive load (4) W 75 75 50 50
Motor (5) W 75 75 6 7.5
Cabling mm2 Maximum c.s.a.: 2 x 2.5 - Minimum c.s.a.: 2 x 1
Characteristics (continued)
General:pages 21151/2 to 21151/7
Selection:pages 21152/2 to 21152/5
References:pages 21162/2 to 21164/3
Dimensions, schemes:pages 21009/2 to 21011/5
21153_Ver3.10-EN.fm/5Schneider Electric
01
01
t01
01
t
01
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakersElectronic serial timer modules
Type LA4-DT (On-delay) LA4-DR (Off-delay)
Environment
Conforming to standards IEC 255-5 IEC 255-5Product certifications Pending UL, CSA UL, CSA
Protective treatment “TH” “TH”Degree of protection Conforming to VDE 0106 Against direct finger contact Against direct finger contact
Ambient air temperature Storage °C - 40…+ 80 - 40…+ 80around the device Operation °C - 25…+ 55 - 25…+ 55
Operation at Uc °C - 25…+ 70 - 25…+ 70
Rated insulation voltage (Ui) Conforming to IEC 947-1 and V 250 250VDE 0110 (group C)
Control circuit characteristics
Built-in protection On input By varistor By varistorContact breaker By varistor By peakcoil suppression limiting diode
Rated control circuit voltage (Uc) V or 24…250 24…250 Voltage limits 0.8…1.1 Uc 0.8…1.1 Uc
Control type By mechanical contact only By mechanical contact only(connecting cable < 10 m)
Cabling Flexible or solid cable, mm2 Minimum c.s.a.: 1 x 1 Minimum c.s.a.: 1 x 1with or without cable end Maximum c.s.a.: 2 x 2.5 Maximum c.s.a.: 2 x 2.5
Time delay characteristics
Timing ranges s 0.1…2 - 1.5…30 - 25…500 0.1…2 - 1.5…30 - 25…500
Repeat accuracy 0…40 °C ± 3 % (10 ms minimum) ± 3 % (10 ms minimum)
Reset time During the time delay ms 100 225After the time delay ms 50 –
Immunity to micro-breaks During the time delay ms 10 20After the time delay ms 2 –
Minimum control pulse duration ms – 40
Time delay signalling By LED Illuminates during time delay Illuminates during time delay
Switching characteristics (solid state type)
Maximum power dissipated W 2 3.5
Leakage current mA < 5 < 5
Residual voltage V 3.3 3.3Overvoltage protection 3 kV; 0.5 joule 3 kV; 0.5 joule
Electrical durability Millions of operating cycles 30 30
Operating diagrams
Electronic on-delay timer LA4-DT Electronic off-delay timer LA4-DR
Uc supply(A1 - A2)
Uc supply Control(A1 - A2) (A2 - B2)
Time delay output Time delay outputContactor breaker coil Contactor breaker coil
Red LED Red LED
Characteristics
General:pages 21151/2 to 21151/7
Selection:pages 21152/2 to 21152/5
References:pages 21162/2 to 21164/3
Dimensions, schemes:pages 21009/2 to 21011/5
21153_Ver3.10-EN.fm/6 Schneider Electric
KA1
A2
E1
+
E2
–
KA1
A2
E1
+
E2
–
KA1
A2
E1
+
E2
–
+
– (0V)
E1
E3E2
A1
A2
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakersInterface modules and converters
(1) The operating times depend on the type of electromagnet driving the contactor breaker and its control method. The closing time “C” is measured from the momentthe integral coil supply is switched on to initial contact of the main poles. The opening time “O” is measured from the moment the coil supply is switched off to themoment the main poles separate.
Type Interface modules Converters
Used for direct control of By a programmable controller, with a.c. control of the electromagnet By a programmable controller, with the integral 18 d.c. control of the electromagnet.
Control on d.c. supply
Protective treatment “TH” “TH”
Ambient air temperature °C Storage: - 40…+ 80 Storage: - 40…+ 80 around the device
Operation: - 25…+ 55 Operation: - 25…+ 50
Rated insulation V 250 conforming to IEC 158-1 and 947-1 and VDE 0110 (group C) –voltage (Ui)
Protection against direct finger contact Conforming to VDE 0106 Conforming to VDE 0106
Cabling mm2 Min: 1 x 1 - Max: 2 x 2.5 Min: 1 x 1 - Max: 2 x 2.5
Operating limits – 0.8...1.1 Uc (2)
Protection Of the input and against reverse polarity: by diode. Against reverse polarity (by diode)and against overvoltage
Control circuit characteristics
Module or converter type LA4-DFB LA4-DFE LA4-DLB LA4-DLE LA4-DWB LA1-LB080BD
Technology Relay Relay + override Solid state Solid state
Schemes
Indication of input state By built-in LED –
Input signals Voltage V 24 48 24 48 5…24 24 (logic side) (E1-E2) (E1-E2) (E1-E2) (E1-E2) (E1-E2) (E2-E3)
Current mA 25 15 25 15 8.5 for 5 V 1015 for 24 V
State “0” guaranteed for U V < 2.4 < 4.8 < 2.4 < 4.8 < 2.4 < 7 or
I mA < 2 < 1.3 < 2 < 1.3 < 2 < 5
State “1” guaranteed for U V 17 < U < 30 33 < U < 60 17 < U < 30 33 < U < 60 5 < U < 30 U > 14
Supply voltage V 24…250 24(A1-A2) (E1-E2) (2)
Operating characteristics
Electrical durability 10 10 3 3 20 2in millions of operating cycles
Immunity to ms 4 4 4 4 1 –micro-breaks
Average consumption W 0.6 0.6 0.6 0.6 0.4 Inrush: 100at 20 °C Sealed: 1.5
Operating Pull-in ms 15…30 15…30 15…30 15…30 – 30time (1)at 20 °C and at Uc Drop-out ms 20…35 20…35 20…35 20…35 – 15
(2) Warning: for supply from rectified a.c., the power supply must exceed 150 VA and the maximum ripple must be ≤ 14 %.
Characteristics (continued)
General:pages 21151/2 to 21151/7
Selection:pages 21152/2 to 21152/5
References:pages 21162/2 to 21164/3
Dimensions, schemes:pages 21009/2 to 21011/5
21153_Ver3.10-EN.fm/7Schneider Electric
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakers
Breaking capacity of integral 18 contactor breakers, ensuring reliability of operation, according to the operational voltageand protection module fitted.
Breaking capacity without current limiter
Protection module Operational voltageReference Irth 220/240 V 400/415 V 440 V 480/525 V 600/690 V
min maxA A kA kA kA kA kA
LB1-LB03P01 0.1 0.16 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB1-LB03P02 0.16 0.25 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB1-LB03P03 0.25 0.4 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB1-LB03P04 0.4 0.63 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB1-LB03P05 0.63 1 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB1-LB03P06 1 1.6 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB1-LB03P07 1.6 2.5 ≥ 130 ≥ 130 ≥ 130 ≥ 130 50
LB1-LB03P08 2.5 4 ≥ 130 ≥ 130 ≥ 130 ≥ 130 50
LB1-LB03P10 4 6 ≥ 130 ≥ 130 50 50 5
LB1-LB03P13 6 10 50 50 50 10 5
LB1-LB03P17 10 16 50 50 25 7.5 2
LB1-LB03P21 12 18 50 50 25 7.5 2
Breaking capacity with current limiter LA9-LB920
LB1-LB03P01 0.1 0.16 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB1-LB03P02 0.16 0.25 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB1-LB03P03 0.25 0.4 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB1-LB03P04 0.4 0.63 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB1-LB03P05 0.63 1 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB1-LB03P06 1 1.6 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB1-LB03P07 1.6 2.5 ≥ 130 ≥ 130 ≥ 130 ≥ 130 50
LB1-LB03P08 2.5 4 ≥ 130 ≥ 130 ≥ 130 ≥ 130 50
LB1-LB03P10 4 6 ≥ 130 ≥ 130 65 65 50
LB1-LB03P13 6 10 65 65 65 65 42
LB1-LB03P17 10 16 65 65 65 65 42
LB1-LB03P21 12 18 65 65 65 65 42
Characteristics
General:pages 21151/2 to 21151/7
Selection:pages 21152/2 to 21152/5
References:pages 21162/2 to 21164/3
Dimensions, schemes:pages 21009/2 to 21011/5
21153_Ver3.10-EN.fm/8 Schneider Electric
0,1
0,2
0,4
0,60,8
1
2
4
68
10
20
40
6080
100
0,1 0,2 0,4 0,6 1 2 4 6 8 10 20 50 100130
200
65
4
7
2
1
3
cos
=0,5
=0,3
=0,2
5
ϕ =0,7
8
100
60
80
40
20
108
6
4
2
11 2 4 6 8 10 20 50 100 200
2
3
4
5
678
130
300min
100min
10min
1 min
10 s
0,1 s
0,01 s
0,1 0,2 0,4 0,6 1 2 4 6 10 20 40 60 100 200 400 600 1000
0,160,25
0,40,63 1,6
2,54
1 610
1216
180,1
P01
P03P02P04
P05P06
P07P08
P10P13
P17P21
0,15
2,4 6
3,75 9,45
15
24
37,5
60
90 180
150
270
240
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakers
By thermal-magnetic modules (1) LB1-LB03P
(1) Thermal protection: the average operating times shown in thesecurves are for an ambient air temperature of 20 °C, without prior currentflow (cold state). The average operating time after prolonged currentflow (hot state) can be calculated by applying the coefficient 0.5.
3-phase 400/415 V, 50 Hz
Motor protection
Current limitation and thermal limit on short-circuit
Current limitation on short-circuit Maximum thermal limit on short-circuit
1 0.63…1 A 5 4…6 A2 1…1.6 A 6 6…10 A3 1.6…2.5 A 7 10…16 A4 2.5…4 A 8 12…18 A
Selection of protection module according to the tripping characteristics
Time
Maximum peak current in kA Thermal limit in kA2sin the magnetic operating zone
Prospective rms short-circuit current in kA Prospective rms short-circuit current in kA
Current in A
General:pages 21151/2 to 21151/7
Selection:pages 21152/2 to 21152/5
References:pages 21162/2 to 21164/3
Dimensions, schemes:pages 21009/2 to 21011/5
21153_Ver3.10-EN.fm/9Schneider Electric
0,1
0,2
0,4
0,60,8
1
2
4
68
10
20
40
6080
100
0,1 0,2 0,4 0,6 1 2 4 6 8 10 20 50 100
130
200
6 5
4
7
21
3
cos
=0,5
=0,3
=0,2
5
ϕ =0,7
8
100
60
80
40
20
108
6
4
2
11 2 4 6 8 10 20 50 100 200
2
3
4
56
78
130
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakers
3-phase 480/525 V, 50 Hz
Current limitation and thermal limit on short-circuit (continued)
Current limitation on short-circuit Maximum thermal limit on short-circuit
1 0.63…1 A 5 4…6 A2 1…1.6 A 6 6…10 A3 1.6…2.5 A 7 10…16 A4 2.5…4 A 8 12…18 A
Selection of protection module according to the tripping characteristics
Maximum peak current in kA Thermal limit in kA2sin the magnetic operating zone
Prospective rms short-circuit current in kA Prospective rms short-circuit current in kA
General:pages 21151/2 to 21151/7
Selection:pages 21152/2 to 21152/5
References:pages 21162/2 to 21164/3
Dimensions, schemes:pages 21009/2 to 21011/5
21162_Ver2.10-EN.fm/2 Schneider Electric
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakers (for customer assembly)
Without control test function, with padlocking facility
Black knob (VDE 0113)
(1) For the unit to function, it must be fitted with a protection module, to be ordered separately, see above.(2) Standard control circuit voltages (variable delivery times, please consult your Regional Sales Office).
(3) UL 508 “type E” approved version (SPCD) at 347/600 V, as standard.(4) For use on , the unit is supplied with 1 or 2 converters, including coil suppression device (2 converters forreversing contactor breakers). (5) Protection modules UL and CSA approved.
3-pole contactor breakers without protection module (1)
Standard power ratings Operational Breaking Basic reference (3) Weightof 3-phase motors in category AC-43 current capacity Complete with
(Iq) code indicating220 V 400 V 480 V 600 V for control circuit240 V 415 V 440 V 525 V 690 V Ue ≤ 415 V voltage (2) Usual voltageskW kW kW kW kW A kA kg
Without control test function, with padlocking facility
Black knob
4 9 9 9 15 18 50 LD1-LB030 B E F M Q 0.650
3-pole reversing contactor breakers without protection module (1)
4 9 9 9 15 18 50 LD5-LB130 B E F M Q 1.600
Thermal-magnetic protection modules (compensated and differential for normal starting motors) (5)
Standard power ratings Thermal Reference Weightof 3-phase motors setting50/60 Hz in category AC-43 range220 V 400 V 480 V 600 V (Irth min240 V 415 V 440 V 525 V 690 V to Irth max)kW kW kW kW kW A kg
Fixed magnetic protection, set at 15 Irth max
0.1…0.16 LB1-LB03P01 0.250
0.06 0.16…0.25 LB1-LB03P02 0.250
0.06 0.09 0.25…0.4 LB1-LB03P03 0.250
0.12 0.37 0.4…0.63 LB1-LB03P04 0.2500.18
0.09 0.25 0.37 0.37 0.55 0.63…1 LB1-LB03P05 0.2500.12
0.18 0.37 0.55 0.75 1.1 1…1.6 LB1-LB03P06 0.2500.25 0.55
0.37 0.75 1.1 1.1 1.5 1.6…2.5 LB1-LB03P07 0.250
0.55 1.1 1.5 2.2 3 2.5…4 LB1-LB03P08 0.2500.75 1.5
1.1 2.2 2.2 3.7 4 4…6 LB1-LB03P10 0.250
1.5 3 4 5.5 7.5 6…10 LB1-LB03P13 0.2502.2 4
3 5.5 7.5 10 11 10…16 LB1-LB03P17 0.2507.5
4 9 9 11 15 12…18 LB1-LB03P21 0.250 There are no standard power ratings for these motors.
Volts 24 36 42 48 110 120 220 230 240 380 415 440 480 500 600 660400
50 Hz LD-LB B – D E F – M P/PU7 U Q N R – S – Y60 Hz LD-LB BC CC – D K FC LC MC MC/PU7 – – Q N – S – (4) LD-LB BD – – – – – – – – – – – – – – –
References
LD1-LB030
LD5-LB130
Dimensions and schemes :pages 21009/2 to 21011/5
LB1-LB03P06
21162_Ver2.10-EN.fm/3Schneider Electric
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakers (pre-assembled)
Control circuit voltage: 220 V, 50 Hz
3-pole contactor breakers with thermal-magnetic protection module
Standard power ratings Thermal Breaking Reference Weightof 3-phase motors setting capacity50/60 Hz in category AC-43 range (Iq)220 V 400 V 480 V 600 V (Irth min for240 V 415 V 440 V 525 V 690 V to Irth max) Ue ≤ 415 VkW kW kW kW kW A kA kg
0.09 0.25 0.37 0.37 0.55 0.63…1 ≥ 130 LD3-LB130M05 0.9000.12
0.18 0.37 0.55 0.75 1.1 1…1.6 ≥ 130 LD3-LB130M06 0.9000.25 0.55
0.37 0.75 1.1 1.1 1.5 1.6…2.5 ≥ 130 LD3-LB130M07 0.900
0.55 1.1 1.5 2.2 3 2.5…4 ≥ 130 LD3-LB130M08 0.9000.75 1.5
1.1 2.2 2.2 3.7 4 4…6 ≥ 130 LD3-LB130M10 0.900
1.5 3 4 5.5 7.5 6…10 50 LD3-LB130M13 0.9002.2 4
3 5.5 7.5 10 11 10…16 50 LD3-LB130M17 0.9007.5
References
LD3-LB130M
Dimensions and schemes :pages 21009/2 to 21011/5
21163_Ver2.10-EN.fm/2 Schneider Electric
1
LD5-LB + LB1-LB
AUTO
O
TRIP. +
LA1-LB021
LA1-LB0211
AUTO
O
TRIP. +
LA1-LB001
LA1-LB0311
LA1-LB034
LA1-LB031
LA1-LB0341
LD1-LB + LB1-LBLD3-LB
AUTO
O
TRIP. +
LA1-LB015
LA1-LB001
21163_Ver2.10-EN.fm/3Schneider Electric
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakersAdd-on blocks
Current limiter (IP 20)
For Function Reference Weightuse on kg
LD1 or LD5 Increases the breaking capacity of the integral unit LA9-LB920 0.320
Instantaneous auxiliary contact blocks (IP 20)
For Type and number Composition Reference Weightuse on of blocks per unit
N/O N/C kg
LD1 or LD5 1 block of 5 contacts comprising: LA1-LB015 0.100Mounted on - 3 signalling contacts “contactor state” 2 1RH side - 2 signalling contacts “tripped” 1 1
LD1 1 block of 2 signalling contacts 2 – LA1-LB031 0.100Mounted on “control knob in any positionLH side other than «Auto»”
1 block of 2 signalling contacts 1 1 LA1-LB0311 0.100“control knob in any positionother than «Auto»”
1 block of 4 contacts comprising: LA1-LB034 0.100- 2 signalling contacts “control knob 2 –in any position other than «Auto»” - 2 signalling contacts 1 1“tripped on short-circuit”
1 block of 4 contacts comprising: LA1-LB0341 0.100- 2 signalling contacts “control knob 1 1in any position other than «Auto»” - 2 signalling contacts 1 1“tripped on short-circuit”
LD5 1 block of 5 contacts comprising: LA1-LB021 0.100Mounted on - 3 signalling contacts “contactor state” 2 1LH side - 2 signalling contacts “control knob 2 –
in any position other than «Auto»”
1 block of 5 contacts comprising: LA1-LB0211 0.100- 3 signalling contacts “contactor state” 2 1- 2 signalling contacts “control knob 1 1other than «Auto»”
Complementary block with one instantaneous auxiliary contact (IP 10)
LD1 or LD5 1 block comprising – 1 LA1-LB001 0.035Mounted on 1 signalling contact “contactor state”RH side orLH side
Test device
Application Reference Weightkg
For control circuits LA9-LB398 0.010
References
Dimensions and schemes:pages 21009/2 to 21011/5
LA9-LB398
LA9-LB920
21163_Ver2.10-EN.fm/4 Schneider Electric
1
AUTO
O
TRIP. +
AUTO
O
TRIP. +
AUTO
O
TRIP. +
LA9-D09982
LA1-LB080BD
LD1-LB + LB1-LBLD3-LB
LD5-LB + LB1-LB
21163_Ver2.10-EN.fm/5Schneider Electric
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakersAccessories and spare parts
(1) For reversing contactor breakers, order 2 interface modules or 2 voltage converters.(2) For use on 24 V, the integral unit must be fitted with a 21 V coil (see page 21164/3).(3) An RC circuit provides effective protection for circuits highly sensitive to high frequency interference. Voltage limitedto 3 Uc max and oscillating frequency limited to 400 Hz max.Slight increase in drop-out time (1.2 to 2 times the usual time).(4) When used on rectified single-phase or 3-phase supply, the ripple must be equal to or less than 0.14 of the averagevoltage.Operating limits 0.8 to 1.1 Uc for an ambient temperature ≤ 40 °C.(5) It is essential that the voltage converter be associated with the specific coil indicated.(6) The 24 V converter can be operated by “low level input”. In this case, the control circuit voltage must be the sameas the supply voltage (24 V).
Interface modules (1)
Mounting Type Control Supply voltage Reference Weightvoltage 50/60 HzV V kg
On top Solid state 5…24 24…250 LA4-DWB 0.045of theintegral Relay output 24 24…250 LA4-DFB 0.050unit 48 24…250 LA4-DFE 0.050
Relay output 24 24…250 LA4-DLB 0.045(with override) 48 24…250 LA4-DLE 0.045
Electronic serial timer modules
Mounting Type Time delay Operational voltage Reference Weight50/60 Hz (2)
s V kg
On top On-delay 0.1…2 24…250 LA4-DT0U 0.040of the 1.5…30 24…250 LA4-DT2U 0.040integral 25…500 24…250 LA4-DT4U 0.040unit
Off-delay 0.1…2 24…250 LA4-DR0U 0.0401.5…30 24…250 LA4-DR2U 0.05025…500 24…250 LA4-DR4U 0.050
Suppressor modules
Mounting Type Operational voltage Reference Weight50/60 HzV kg
On top RC circuit (resistor-capacitor) (3) 24…48 LA4-DA2E 0.018of the Screw connections to 50…127 LA4-DA2G 0.018integral coil of integral unit 110…250 LA4-DA2U 0.018unit
Varistor (peak limiting) 24…48 LA4-DE2E 0.018Screw connections to 50…127 LA4-DE2G 0.018coil of integral unit 110…250 LA4-DE2U 0.018
Clip-on RC circuit ≤ 250 LA9-D09982 0.010(resistor-capacitor) (3)
Automatic-Manual-Stop control modules
On top Automatic- 24…100 LA4-DMK 0.040of the Manual-integral unit Stop 100…250 LA4-DMU 0.040
Replacement voltage converters (1) for control circuit operation
Mounting For use Operational Consumption Description Reference (5) Weighton integral voltage Inrush Sealed
(4)V W W kg
On top LD-LBBD 24 (6) 100 1.5 Coil LX1-LB024 0.065of theintegral unit Converter LA1-LB080BD 0.045
References
Dimensions and schemes: pages 21009/2 to 21011/5
21164_Ver2.10-EN.fm/2 Schneider Electric
Protection accessories
Description For use Sold in Unit Weighton lots of reference kg
Sealing cover Protection module 1 LA1-LB090 0.010
Protective Protection of 5 GV1-G10 0.005end cover unused busbars
Mounting accessories
Description For use Mounting Reference Weighton on kg
Mounting plate LD1, LD3, LD5 2 x 32 mm LA9-LC010 0.150 rails
Cabling accessories
Description For Pitch Reference Weightmm kg
Terminal blocks, Cable entry – GV1-G09 0.04063 A, 3-pole from abovefor incoming supplyto one or morebusbar sets Cable entry – LA9-LB960 0.110
from below
Busbar set, Supply to 57 LA9-LB930 0.03763 A, 3-pole 2 or more
integral units72 GV2-G272 0.050
Supply to 72 GV2-G472 0.0854 or moreintegral units
Supply to 72 LA9-LB940 0.0501 current limiter on LH side1 integral unit on RH side
Flush mounting accessories
Description For Sold in Unit Weightlots of reference kg
Recessed terminals Auxiliary contact 2 LA9-LB910 0.001associated with flushmounted integral 18
Blanking plate integral 18 10 GA1-C6 0.001
Locking accessory
Control knob Fixing on front face 1 LA9-LB390 0.160locking kit 3 padlocks, Ø 6 mm
shank max.(padlocks not supplied)
Door interlock mechanism (IP 54)
Type For use Colour Reference Weighton of knob kg
Adjustable LD1, LD3, LD5 Red LA9-LB330 0.400from 0 to 185 mmwith extension(control knob mounted Black LA9-LB331 0.400on plate or door)
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakersAccessories
References
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
Characteristics :pages 21153/2 to 21153/9
Dimensions and schemes :pages 21009/2 to 21011/5
GV1-G09
LA1-LB090
LA9-LB960
LA9-LB930
LA9-LB390
21164_Ver2.10-EN.fm/3Schneider Electric
Motor starters - open version 1
integral 18 contactor breakers and reversing contactor breakersCoils (replacement parts)
The integral 18 can operate on a d.c. supply when fitted with a standard coil and a corresponding voltage converter :see page 21163/5.(1) Coil voltage reference code, used to complete the basic reference when ordering an integral unit.
a.c. operation
Rated control circuit Average Inductance Voltage Reference Weightvoltages resistance of closed referenceUc Uc at 20 °C ± 10 % circuit code50 Hz 60 Hz (1)V V Ω H kg
– 21 3.27 0.14 JV LX1-LB019 0.065
21 24 4.07 0.18 BC LX1-LB021 0.065
24 – 5.17 0.23 B LX1-LB024 0.065
– 36 8.96 0.40 CC LX1-LB032 0.065
42 48 16.41 0.72 D LX1-LB042 0.065
48 – 21.13 0.95 E LX1-LB048 0.065
– 110 87.04 4 K LX1-LB100 0.065
– 115/120 102.22 4.4 FC LX1-LB105 0.065
110 – 109 5 F LX1-LB110 0.065
127 – 137 6.6 G LX1-LB127 0.065
– 220 353 16 LC LX1-LB200 0.065
– 230/240 379 17.5 MC LX1-LB210 0.065
220 – 448 20 M LX1-LB220 0.065
230 – 463 22 P LX1-LB230 0.065
230 240 463 22 PU7 LX1-LB234 0.065
240 – 493 24 U LX1-LB240 0.065
380/400 440 1389 60 Q LX1-LB380 0.065
415 460/480 1491 70 N LX1-LB415 0.065
440 – 1779 80 R LX1-LB440 0.065
500 575/600 3312 102 S LX1-LB500 0.065
660 – 3554 180 Y LX1-LB660 0.065
Consumption at 50 Hz : inrush (cos ϕ : 0.55) 75 VA ; sealed (cos ϕ : 0.28) 8 VA.
Consumption at 60 Hz : inrush (cos ϕ : 0.55) 90 VA ; sealed (cos ϕ : 0.30) 9 VA.
d.c. operation
References
LX1-LB
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
Characteristics :pages 21153/2 to 21153/9
Dimension and schemes :pages 21009/2 to 21011/5
21155_Ver2.10-EN.fm/2 Schneider Electric
LD1
LA1-LB015 LA1-LB001 LA1-LB031 LA1-LB034LA1-LB0311 LA1-LB0341
AUTO
AUTO
TRIP. +
TRIP. +
TRIP. +
RESET
TRIP. +
1/L1
3/L2
5/L3
2/T
1
4/T
2
6/T
3
A2A1
0Auto + 0Auto + 0Auto + 0Auto +
16 18
15 17
16 18
15 17
16 18
15 17
16 18
15 17
1516
1718
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
1314 32
312324
16 18
15 17
16 18
15 17
16 18
15 17
16 18
15 17
1516
1718
41
42
41
42
41
42
41
42
4241
0705
06 08
0705
06 08
0705
06 08
0605 07
08
96 98
95 97
96 98
95 97
96 98
95 97
96 98
95 97
96 98
95 97
9695 97
98 1615 17
18
1715
16 18
15 17
16 18
15 17
16 18
1715
16 18
1817 15
16
1517
18 16
17 15
18 16
17 15
18 16
1517
18 16
16 18
15 1713 23 31
14 24 32 16 18
15 1741
42
1715
16 18
1517
18 16
16 18
15 1713 23 31
14 24 32 16 18
15 1741
42
1715
16 18
1517
18 16
96 98
95 97
16 18
15 1713 23 31
14 24 32 16 18
15 1741
42
1715
16 18
1517
18 16
0605 07
08
0705
06 08
0705
06 08
0705
06 08
0705
06 08
0705
06 08
0705
06 08
0705
06 08
0705
06 08
0705
06 08
0705
06 08
96 98
95 97
0705
06 08
Auxiliary contact actuators
Auxiliary contacts
Operation Motor starters - open version 1
integral 18 contactor breakersAuxiliary contact states according to the positions of the control knob
Off after short-circuit
Manual reset
Off
On, contactor open
On, contactor closed
Tripped on overload
Tripped on short-circuit
contact opencontact closed
General : pages 21151/2 to 21151/7
Characteristics : pages 21153/2 to 21153/9
References : pages 21162/2 to 21164/3
Dimensions : pages 21009/2 and 21009/3
21155_Ver2.10-EN.fm/3Schneider Electric
LD5
LA1-LB015 LA1-LB001 LA1-LB021 LA1-LB001LA1-LB0211
RESET
TRIP. +
TRIP. +D clench
D clench
R arm.
TRIP. +D clench
AUTO
AUTO
TRIP. +
AUTO
1/L1
3/L2
5/L3
A2A1
A2A1
6/T
3
2/T
1
4/T
2
0Auto +
II I
0Auto +
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
1314 32
312324
96 98
95 97
96 98
95 97
96 98
95 97
96 98
95 97
96 98
95 97
96 98
95 97
9695 97
98
41
42
41
42
41
42
41
42
41
42
4241
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
1314 32
312324
16 18
15 17
16 18
15 17
16 18
15 17
16 18
15 17
16 18
15 17
1516
1718
41
42
41
42
41
42
41
42
41
42
4241
0705
06 08
0705
06 08
0705
06 08
0705
06 08
0705
06 08
0705
06 08
0705
06 08
0605 07
08
1314 32
312324
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
1517
18 16
1517
18 16
13 23 31
14 24 32 96 98
95 97
96 98
95 97
41
42
13 23 31
14 24 32 16 18
15 17 41
42
0705
06 08
13 23 31
14 24 32
1517
18 16
13 23 31
14 24 32
41
42
13 23 31
14 24 32 16 18
15 17 41
42
13 23 31
14 24 32
1517
18 16
13 23 31
14 24 32
41
42
13 23 31
14 24 32 16 18
15 17 41
42
13 23 31
14 24 32
1517
18 16
17 15
18 16
17 15
18 16
17 15
18 16
1817 15
16
Auxiliary contact actuators
Auxiliary contacts
Off after short-circuit
Tripped on overload
Tripped on short-circuit
Manual reset
Motor starters - open version 1
integral 18 reversing contactor breakersAuxiliary contact states according to the positions of the control knob
Operation
contact opencontact closed
Off
On, contactors open
On, closed
On, closed
On theintegral
General : pages 21151/2 to 21151/7
Characteristics : pages 21153/2 to 21153/9
References : pages 21162/2 to 21164/3
Dimensions : pages 21009/2 and 21009/3
21156_Ver3.11-EN.fm/2 Schneider Electric
(1) With converter.(2) The closing time “C” is measured from the moment the coil supply is switched on to initial contact of the main poles.The opening time “O” is measured from the moment the coil supply is switched off to the moment the the main polesseparate.
Type integral 32Number of poles 3
Rated operational current (Ie) In AC-43 A 32Rated operational voltage (Ue) V 690
Electrical durability in AC-43 at415 V 1.5 million operating cycles
Mechanical durability at Uc 10 million operating cycles
Maximum operating rate 3600 operating cycles/hourat ambient temperature ≤ 55 °C with converter 600 operating cycles/hour
Environment
Conforming to standards IEC: 947-1, 947-2, 947-3, 947-4-1, 947-6-2VDE: 0100, 0110, 0113, 0170, 0171, 471, 0660BS: 5424, 4752, 4941NEN, NBN
Product certifications ASE, ASEFA, ASTA, BV, CSA DEMKO, DNV, GL NEMKO, NKK, ÖVE, PTB, RINA, SCC, SEMKO, SETI, UL, USSR, LROS
Protective treatment “TH”
Ambient air temperature Operation °C - 25…+ 60around the device Storage °C - 40…+ 80
Operation °C - 25…+ 50(1) Storage °C - 25…+ 70
Vibration resistance 5…100 Hz Energised state: 3 gn Permissible acceleration De-energised state: 3 gn
Shock resistance Impulse duration : 11 ms Energised state 8 gn Permissible acceleration De-energised state: 8 gn
Degree of protection To IEC 144 and 529 IP 20BTo VDE 0106 Protection against direct finger contact
Flame resistance Conforming to IEC 295-2-1, NF C 20-455, and to decree of 22-12-81 (JO 27 NC of 1st and 2/2/1982)Conforming to UL 94 - V0 and NF T 51-072
Maximum operating altitude Without derating m 3000
Operating positions In relation to From fixing From main(without derating) normal vertical plane axis
mounting plane (fore-aft (left-righttilt) tilt)
Control circuit characteristics
Rated control 50 Hz V 21…660circuit voltage (Uc) 60 Hz V 21…600
with converter V 24, 48, 110
Voltage limits Operating 0.85…1.1 Ucat θ ≤ 55 °C Drop-out 0.25…0.7 Uc
Average consumption Inrush VA 160 (50 Hz), 185 (60 Hz)at 20 °C and at Uc Sealed VA 12 (50 or 60 Hz)
(1) Inrush W 250 for 50 msSealed W 4
Heat dissipation W 4 (50 Hz), 5 (60 Hz)
Operating time (2) 50/60 Hz “C” ms 9…25at 20 °C and at Uc “O” ms 7…20
with “C” ms 25…35converter “O” ms 10…20
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakers
Characteristics
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21165/2 to 21168/3
Dimensions and schemes :pages 21009/2 to 21011/5
21156_Ver3.11-EN.fm/3Schneider Electric
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakers
(1) Conforming to BS 4752 36 kA cycle P2, 50 kA cycle P1.
Type integral 32
Pole characteristics
Convential thermal current (Ith) θ ≤40 °C A 32Frequency limits ofoperational current Hz 40…60Rated impulsewithstand voltage (Uimp) Conforming to IEC 947-4 kV 8Rated insulation voltage (Ui) Conforming to IEC 947-1 V 690
Heat dissipation in the power Operational current A 1.6 2.5 4 6.3 10 16 25 32circuits of the contactor breakerand its protection module Power per pole, hot state W 1.6 1.8 1.8 2 2 3.4 4.8 6
Rated making I rms Conforming to IEC 947-4 A 12 x Ith (above this value, the breaker trips)capacity I peak Conforming to IEC 947-2 kA 105
Rated breaking capacity Operational voltage V 220/240 380/415 440 480/525 600/690to IEC 947-2 Value of cos ϕ 0.25 0.25 0.25 0.3 0.8
Icu (O-t-CO) kA rms 50 50 50 (1) 20 5 (cos ϕ 0.7)Ics (O-t CO-t-CO) kA rms 50 50 35 (1) 20 5
to IEC 947-6-2ensuring reliability of operation Icu = Ics (O-t-CO-t-rCO) kA rms 50 50 50 15 4
O: breaking short-circuit current (open); t: timeCO: closing on short-circuit, breaking short-circuit current (closed-open - manual)rCO: closing on short-circuit, breaking short-circuit current (closed-open - remote control)
Total breaking time ms 4
Thermal limit With Isc max at 415 V, 50 Hz A2s 100 x 103
Cabling Maximum c.s.a. Minimum c.s.a.Flexible cable without cable end mm2 1 x 10 or 2 x 6 1 x 1Flexible cable with cable end mm2 1 x 6 or 2 x 4 1 x 1Solid cable mm2 1 x 10 or 2 x 6 1 x 1
Tightening torque N.m 2
Characteristics of thermal-magnetic or magnetic only protection modules
Type LB1-LC03M LB6-LC03M LB1-LCLFrequent
Protection Standard motors starting motors Distribution circuitsIEC 947-4 type 2 (Iq = 50 kA)
Conforming to standards NF C 63-650 NF C 63-650 NF C 63-120Number of poles 3 3 3 4 4Number of protected poles 3 3 3 3 4Rated operational voltage V 690 690 690Maximum continuous current A 0.4…32 0.4…32 10…32
Thermal protection Setting range (Irth min/Irth max) A 0.25/0.40…23/32 – 6.3/10…23/32Temperature compensation °C - 20…+ 60 - 20…+ 60 - 20…+ 60Protection againstphase imbalance With Without WithoutTripping class 10 – –
Magnetic protection Instantaneous trip current 6…12 Irth max (usual 6…12 Irth max 3…6 Irth maxconforming to IEC 947-1/2/4/6-2 setting range setting 9…10 Irth max)
Tripping tolerance ± 20 % ± 20 % ± 20 %
Characteristics of versions without control test function, with padlocking facility
Conforming to standards IEC 947Rated operational voltage V 690Mechanical durability Operating cycles 10 000Padlocking facility 1, 2 or 3 padlocks, shank Ø 8 mm max and Ø 5 mm min
Characteristics of versions with control test function and padlocking facility
Conforming to standards IEC 947, NF C 63-130, VDE 0660, VDE 0113Rated operational voltage 690Mechanical durability Operating cycles 10 000
1, 2 or 3 padlocks, shank Ø 8 mm max and Ø 5 mm min. When flush Padlocking facility mounting, interlocking of the enclosure or cabinet door is possible.
Characteristics
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21165/2 to 21168/3
Dimensions and schemes :pages 21009/2 to 21011/5
21156_Ver3.11-EN.fm/4 Schneider Electric
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakersAdd-on current limiter and auxiliary contacts
1) Electrical durability on an inductive load such as the coil of an electromagnet:making current (cos ϕ 0.7) = 10 times the breaking current (cos ϕ 0.4).(2) Electrical durability on an inductive load such as the coil of an electromagnet, the time constant increasing with theload.(3) Lamp load: peak current = 10 times the rated current.(4) Inductive load: cos ϕ 0.4 for a.c. operation; time constant 7 ms for d.c. operation.(5) Motor: peak current = 6 times the rated current.
Add-on current limiter LA9-LB920
Rated insulation voltage (Ui) Conforming to IEC 947-1 V 690 (50/60 Hz)
Rated operational voltage (Uc) V 690 (50/60 Hz)
Conventional thermal current (Ith) Conforming to IEC 947-1 A 63
Operational thermal current (Ie) A 32
Operating threshold rms current A 1000 (non adjustable threshold)
Cabling Solid cable mm2 1 x 1.5 to 25 conductor or 2 x 1.5 to 10 identical conductorsFlexible cable without cable end mm2 1 x 1.5 to 25 conductor or 2 x 1.5 to 10 conductorsFlexible cable with cable end mm2 1 x 1.5 to 16 conductor or 2 x 1.5 to 4 conductors
Tightening torque N.m 2.2
Instantaneous auxiliary contacts
Conventional thermal current (Ith) A 6
Rated insulation voltage (Ui) Conforming to IEC 947-5-1 V 690
Switching capacity With U ≥ 17 V and I ≥ 10 mA mVA 600
Rated category AC-15 (1) Voltage V 48 110/127 220/240 380/415 440operational 1 million operating cycles VA 300 500 600 520 500power 1.5 million operating cycles VA 160 300 330 300 280
Making capacity category AC-15 VA 1500 3500 6000 7500 7000
Rated category DC-13 (2) Voltage V 24 48 110 220 440operational 1 million operating cycles W 120 90 75 68 61power 1.5 million operating cycles W 70 50 38 33 28
Making capacity category DC-13 W 800 700 400 260 220
Cabling mm2 Maximum c.s.a.: 2 x 2.5. Minimum c.s.a.: 2 x 1
Signalling contacts
Conventional thermal current (Ith) A 3
Rated insulation voltage (Ui) Conforming to IEC 947-5-1 V 250
Operational power Voltage V – – 110/127 220for 200 000 Resistive load VA – – 600 750operating cycles Lamp load (3) VA – – 90 125
Inductive load (4) VA – – 875 500Motor (5) VA – – 160 200
Voltage V 24 48 110/125 200Resistive load W 100 100 50 50Lamp load (3) W 50 50 6 7.5Inductive load (4) W 75 75 50 50Motor (5) W 75 75 6 7.5
Cabling mm2 Maximum c.s.a.: 2 x 2.5 - Minimum c.s.a.: 2 x 1
Isolating auxiliary contacts
Conventional thermal current (Ith) A 6
Rated insulation voltage (Ui) a.c. supply V 690conforming to IEC 947 and NF C 63-130 d.c. supply V 125
Cabling mm2 Maximum c.s.a.: 2 x 1.5 or 1 x 2.5
Characteristics
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21165/2 to 21168/3
Dimensions and schemes :pages 21009/2 to 21011/5
21156_Ver3.11-EN.fm/5Schneider Electric
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakersInterface modules and converters
(1) For direct control by external contact: connect E1-E3.(2) Warning: for supply from rectified a.c., the power supply must exceed 250 VA and and the maximum ripple mustbe ≤ 14 %.
Type Interface modules Converters
Used for direct control of By a programmable controller, with a.c. control of - By a programmable controller, with d.c. control of the the integral 32 the electromagnet electromagnet
- Control on d.c. supply
Ambient air temperature °C Storage : - 25…+ 70 Storage : - 25…+ 70 around the device
Operation : - 25…+ 50 Operation : - 25…+ 50
Insulation rms voltage between inputs and outputs: 2.5 kV Common negative terminal
Cabling mm2 Minimum c.s.a.: 1 x 1 - Maximum c.s.a.: 2 x 2.5 Minimum c.s.a.: 1 x 1 - Maximum c.s.a.: 2 x 2.5
Operating limits 0.85... 1.1 Uc 0.8…1.1 Uc (2)
Protection Against reverse polarity (by diode) Against reverse polarity (by diode)and against overvoltage and against overvoltage
Indication of input state By LED –
Converter module type LA1-LC LA1-LC580BD 580ED 180BD 080BD 080ED 080FD
Schemes LA1-LC580D LA1-LC180BD LA1-LC080BD LA1-LC080FDLA1-LC080ED
Input signals(logic side)
Voltage V 24 48 5…24 24 (1) 48 (1) () (E1-E2) (E1-E2) (E1- E2) (E3-E2) (E3-E2) –
Current mA 30 20 15…24 V 20 10 –8.5…5 V
State “0” guaranteed for U V < 2.4 < 4.8 < 2.5 < 7 < 14 – or
I mA < 2 < 2 < 2 < 5 < 2.5 –
State “1” guaranteed for U V > 20.4 > 40.8 > 4 > 14 > 28 –
Supply voltage V (2) (2) (2)24…240 24…240 24…240 24 48 110(A1-A2) (A1-A2) (A1-A2) (E1-E2) (E1-E2) (E1-E2)
Electrical durabilityin millions of operating cycles
5 1
Average Inrush 50 Hz VA 160 160 160 – – –con-sumption 60 Hz VA 185 185 185 – – –
W – – – 250 250 250
Sealed 50/60 Hz VA 12 12 12 – – –
W – – – 4 4 4
Operating Pull-in ms 15…30 15…30 10…35 30 30 30timeat 20 °Cand at Uc Drop-out ms 22…35 22…35 8…30 15 15 15
Characteristics
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21165/2 to 21168/3
Dimensions and schemes :pages 21009/2 to 21011/5
+
– (0V)
E1
E3
E2
A1
A2
+ E1
– E2
A1
A2
+ E1
– E2
A1
A2
+
– (0V)
E1
E2
A1
A2
21156_Ver3.11-EN.fm/6 Schneider Electric
Environment
Conforming to standards IEC 337-1
Protective treatment “TH”
Ambient air temperature Storage °C - 40…+ 80 around the device
Operation °C - 25…+ 55
Permissible for operation at Uc °C - 25…+ 70
Protection against Conforming to VDE 0106direct finger contact
Tripping devices
Type LA1-LC070, LC072 LA1-LC071
Pull-in voltage 0.8…1.1 Uc 0.7…1.1 Uc
Drop-out voltage 0.35…0.7 Uc –
Average consumption Inrush VA 8 8
Sealed VA 4 4
Minimum impulse duration ms – 10
Reset devices
Type LA1-LC052
Consumption VA 9
Duration of a reset cycle s 9
Minimum impulse duration s 0,5
Mechanical durability Operating cycles ≥ 10 000
Suppressor module LA9-D09982
Type RC (resistor-capacitor)
Scheme
Operational voltage V ≤ 250
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakersTripping and reset devices, coil suppressor module
Characteristics
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21165/2 to 21168/3
Dimensions and schemes :pages 21009/2 to 21011/5
21156_Ver3.11-EN.fm/7Schneider Electric
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakers
Breaking capacity of integral 32 contactor breakers, ensuring reliability of operation, according to the operational voltageand protection module fitted.
(1) 42 kA for 600 V - 20 kA for 690 V.
Breaking capacity without current limiter
Protection module Operational voltageReference Irth 220/240 V 400/415 V 440 V 500 V 600/690 V
min maxA A kA kA kA kA kA
LB-LC03M03 0.25 0.4 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB-LC03M04 0.4 0.63 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB-LC03M05 0.63 1 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB-LC03M06 1 1.6 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB-LC03M07 1.6 2.5 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB-LC03M08 2.5 4 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB-LC03M10 4 6.3 ≥ 130 ≥ 130 ≥ 130 ≥ 130 15
LB-LC03M13 6.3 10 ≥ 130 ≥ 130 ≥ 130 ≥ 130 10
LB-LC03M17 10 16 ≥ 130 ≥ 130 50 15 4
LB-LC03M22 16 25 50 50 50 15 4
LB-LC03M53 23 32 50 50 50 15 4
Breaking capacity with current limiter LA9-LB920
LB-LC03M03 0.25 0.4 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB-LC03M04 0.4 0.63 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB-LC03M05 0.63 1 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB-LC03M06 1 1.6 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB-LC03M07 1.6 2.5 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB-LC03M08 2.5 4 ≥ 130 ≥ 130 ≥ 130 ≥ 130 ≥ 130
LB-LC03M10 4 6.3 ≥ 130 ≥ 130 ≥ 130 ≥ 130 42
LB-LC03M13 6.3 10 ≥ 130 ≥ 130 ≥ 130 ≥ 130 42
LB-LC03M17 10 16 ≥ 130 ≥ 130 65 65 42
LB-LC03M22 16 25 65 65 65 65 42/20 (1)
LB-LC03M53 23 32 65 65 65 65 42/20 (1)
Characteristics
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21165/2 to 21168/3
Dimensions and schemes :pages 21009/2 to 21011/5
21156_Ver3.11-EN.fm/8 Schneider Electric
300min
100min
10min
1 min
10 s
1 s
0,1 s
0,01 s
0,1 0,2 0,4 0,6 1 2 4 6 10 20 40 60 100 200 400 600
M03M04M05M06
M07M08M10M13
M17M22M53
0,25 0,40 0,63 1 1,6 2,5 4 6,3 10 16 23 25 32 irth
2,4 4,8 7,6 12 19 30 48 76 120 190 380
3,8 6 9,5 15 24 38 60 95 150 300
M06 M08 M13 M22
0,8 1 2 4 6 10 20 40 60 100 200 400 600 1000
0,01 s
0,1 s
1 s
10 s
1 min
100min
300min
10min
9,5 15 24 38 60 95 150190
19 30 48 76 190 300380
M07 M10 M17 M53
120
0,8 1 2 4 6 10 20 40 60 100 200 400 600 1000
0,01 s
0,1 s
1s
10 s
1 min
100min
300min
10min L13
L17L22L53
60 95 150190
9530 48 75
6,3 10 16 32 irth2325
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakers
Motor protection
Standard motors Frequent starting motorsBy thermal-magnetic modules (1) LB1-LC03M By magnetic modules LB6-LC03M
Distribution circuit protection
By thermal-magnetic modules (1) LB1-LCL
(1) Thermal protection: the average operating times shown in these curves are for an ambient air temperature of 20° C, without prior currentlow (cold state). The average operating time after prolonged current flow(hot state) can be calculated by applying the coefficient 0.5.
Selection of protection module according to tripping characteristics
Time Time
Current in A
Current in A
Current in A
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21165/2 to 21168/3
Dimensions and schemes :pages 21009/2 to 21011/5
Time
21156_Ver3.11-EN.fm/9Schneider Electric
0,1
0,2
0,4
0,60,8
1
2
4
68
10
20
40
6080
100
0,1 0,2 0,4 0,6 1 2 4 6 8 10 20 50 100 200
1
2
3
4
56
8 (1)
ϕco
s=0
,7
=0,5
=0,3
=0,2
5
7
10080
60
40
20
10
8
6
4
2
11 2 4 6 8 10 15 20 50 100 200
2
3
4
5678(1)
0,1
0,2
0,4
0,60,8
1
2
4
68
10
20
40
608000
0,1 0,2 0,4 0,6 1 2 4 6 8 10 50 100 20015
3
20
ϕco
s=0
,7
=0,5
=0,3
1
2
3
45
76
8 (1)
100
60
80
40
20
108
6
4
2
11 2 4 6 8 10 20 50 100 200
2
3
4
678
5
(1)
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakers
3-phase 400/415 V, 50 Hz
- up to a rating of 6.3…10 A at 440-500 V.
3-phase 480/525 V, 50 Hz
- up to a rating of 6.3…10 A at 440-500 V.
Current limitation and thermal limit on short-circuit
Current limitation on short circuit Maximum thermal limit on short-circuit
1 1…1.6 A 4 4…6.3 A 7 16…25 A For 1 to 1.6 A ratings, the thermal limit is less than 1x103 A2s.2 1.6…2.5 A 5 6.3…10 A 8 23…32 A 3 2.5…4 A 6 10…16 A
(1) Associated thermal protection rating. The breaking capacity is unlimited on contactor breakers fitted with modules:- up to a rating of 10…16 A at 220-380-415V.
Current limitation on short circuit Maximum thermal limit on short-circuit
1 1…1.6 A 4 4…6.3 A 7 16…25 A For 1 to 1.6 A ratings, the thermal limit is less than 1x103 A2s.2 1.6…2.5 A 5 6.3…10 A 8 23…32 A 3 2.5…4 A 6 10…16 A
(1) Associated thermal protection rating. The breaking capacity is unlimited on contactor breakers fitted with modules:- up to a rating of 10…16 A at 220-380-415V.
Selection of protection module according to tripping characteristics
Maximum peak current in kA Thermal limit I2t in kA2s in the short-circuit protection zone
Prospective rms short-circuit current in kA
Thermal limit I2t in kA2s in the short-circuit protection zoneMaximum peak current inkA
Prospective rms short-circuit current in kA Prospective rms short-circuit current in kA
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21165/2 to 21168/3
Dimensions and schemes :pages 21009/2 to 21011/5
Prospective rms short-circuit current in kA
21165_Ver3.30-EN.fm/2 Schneider Electric
With control test function and padlocking facility
Black knob (CNOMO, VDE 0113)
(1) For the unit to function, it must be fitted with a protection module, to be ordered separately, see page opposite.(2) Standard control circuit voltages (variable delivery times, please consult your Regional Sales Office).
(3) Variant: UL 508 approved version (starter) at 600 V, to order, add suffix H51 to the reference.Example: LD1-LC030MH51.(4) For use on , the unit is supplied with 1 or 2 voltage converters, including coil suppression device(s) (2 convertersfor reversing contactor breakers). (5) It is essential to provide electrical locking for reversing contactor breakers integral 32.
3-pole contactor breakers without protection module (1)
Standard power ratings Operational Breaking Basic reference (3) Weightof 3-phase motors current capacity Complete with code50/60 Hz in category AC-43 (Iq) indicating control220 V 400 V for circuit voltages240 V 415 V 440 V 500 V 660 V Ue ≤ 415 V (2) Usual voltageskW kW kW kW kW A kA kg
Without control test function, with padlocking facility
Black knob (CNOMO, VDE 0113)
7.5 15 15 18.5 25 32 50 LD1-LC030 B E F M Q 1.430
With control test function and padlocking facility
Black knob (CNOMO, VDE 0113)
7.5 15 15 18.5 25 32 50 LD4-LC130(5) B E F M Q 1.450
Red knob on yellow background (CNOMO) Emergency Stop
7.5 15 15 18.5 25 32 50 LD4-LC030(5) B E F M Q 1.450
3-pole reversing contactor breakers without protection module (1)
7.5 15 15 18.5 25 32 50 LD5-LC130 B E F M Q 2.800
Red knob on yellow background (CNOMO) Emergency Stop
7.5 15 15 18.5 25 32 50 LD5-LC030 B E F M Q 2.800
Volts 24 36 42 48 110 120 220 230 240 380 415 440 480 500 600 660400
50 Hz B – D E F – M M U Q N N – S – Y60 Hz BC CC – D FC FC MC MC/PU7 MC – – Q Q – S – (4) BD – – ED FD – – – – – – – – – – –
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakers for the control and protection of motors (for customer assembly)
References
LD1-LC030
LD4-LC130
LD4-LC030
LD5-LC030
Dimensions, schemes : pages 21009/2 to 21011/
5
21165_Ver3.30-EN.fm/3Schneider Electric
(1) Protection modules UL and CSA approved.
(2) To order PTB approved versions, add suffix H8 to the reference. Example: LB1-LC03M03H8.
Thermal-magnetic protection modules (compensated and differential for normal starting motors) (1)
Standard power ratings Thermal Magnetic Reference Weightof 3-phase motors setting protection50/60 Hz in category AC-43 range220 V 400 V 480 V 600 V (Irth min 240 V 415 V 440 V 525 V 690 V to Irth max)kW kW kW kW kW A A kg
Adjustable magnetic protection, from 6 to 12 Irth max (2)
0.06 0.25…0.4 2.4…4.8 LB1-LC03M03 0.400
0.4…0.63 3.8…7.6 LB1-LC03M04 0.400
0.09 0.37 0.37 0.55 0.63…1 6…12 LB1-LC03M05 0.4000.12
0.18 0.55 0.75 1.1 1…1.6 9.5…19 LB1-LC03M06 0.4000.25
0.37 1.1 1.1 1.1 1.5 1.6…2.5 15…30 LB1-LC03M07 0.400
0.55 1.5 1.5 2.2 3 2.5…4 24…48 LB1-LC03M08 0.4000.75
1.1 2.2 2.2 3.7 4 4…6.3 38…76 LB1-LC03M10 0.400
1.5 4 4 5.5 7.5 6.3…10 60…120 LB1-LC03M13 0.4002.2
3 7.5 7.5 10 11 10…16 95…190 LB1-LC03M17 0.4004
5.5 11 11 15 18.5 16…25 150…300 LB1-LC03M22 0.400
7.5 15 15 18.5 25 23…32 190…380 LB1-LC03M53 0.400
Magnetic only protection modules (for frequent starting motors)
Standard power ratings Magnetic Reference Weightof 3-phase motors protection50/60 Hz in category AC-43220 V 400 V 480 V 600 V240 V 415 V 440 V 525 V 690 VkW kW kW kW kW A kg
0.18 0.55 0.75 1.1 9.5…19 LB6-LC03M06 0.4000.25
0.37 1.1 1.1 1.1 1.5 15…30 LB6-LC03M07 0.400
0.55 1.5 1.5 2.2 3 24…48 LB6-LC03M08 0.4000.75
1.1 2.2 2.2 3.7 4 38…76 LB6-LC03M10 0.400
1.5 4 4 5.5 7.5 60…120 LB6-LC03M13 0.4002.2
3 7.5 7.5 10 11 95…190 LB6-LC03M17 0.4004
5.5 11 11 15 18.5 150…300 LB6-LC03M22 0.400
7.5 15 15 18.5 25 190…380 LB6-LC03M53 0.400
There are no standard power ratings for these motors.
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakersfor the control and protection of motors (for customer assembly)
References
LB1-LC03M
Dimensions, schemes : pages 21009/2 to 21011/
5
LB6-LC03M
21166_Ver3.10-EN.fm/2 Schneider Electric
PEN
N
- the PEN conductor must not be isolated.- all live conductors must be isolated. Neutral protection optional.
Selecting the type of contactor breaker and protection module
Neutral point Type Equipment Combinationconnection of scheme contactor breaker + protection module
circuit
Neutral TNC 3-pole LD1-LC030 + LB1-LC03Lconnect- (neutral + PENion and PE
combined) LD4-LC130 + LB1-LC03L
LD4-LC030 + LB1-LC03L
TNS 3-pole LD1-LC030 + LB1-LC03L(neutraland PEseparated) LD4-LC130 + LB1-LC03L
LD4-LC030 + LB1-LC03L
3-pole + N LD1-LC040 + LB1-LC04L
LD4-LC140 + LB1-LC04L
LD4-LC040 + LB1-LC04L
LD1-LC040 + LB1-LC05L
LD4-LC140 + LB1-LC05L
LD4-LC040 + LB1-LC05L
Note :
Selection Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakersfor control and protection of resistive circuits in category AC-1
Dimensions, schemes : pages 21009/2 to 21011/
5
21166_Ver3.10-EN.fm/3Schneider Electric
Thermal-magnetic (compensated)
(1) For the unit to function, it must be fitted with a protection module, to be ordered separately.(2) Standard control circuit voltages (variable delivery times, please consult your Regional Sales Office).
(3) For use on d.c., the unit is supplied with a converter, including coil suppression device.
3 and 4-pole contactor breakers without protection module (1)
Rated Maximum Maximum Breaking Number Basic reference. Weightthermal operational operational capacity of Complete with current current voltage (Iq) poles code indicatingI th AC-1 for control circuitθ ≤ 40 °C θ ≤ 40 °C Ue ≤ 415 V voltage (2) Usual voltagesA A V kA kg
Without control test function, with padlocking facility
32 32 690 50 3 LD1-LC030 B E F M Q 1.430
4 LD1-LC040 B E F M Q 1.750
With control test function and padlocking facilityBlack knob on blue background (CNOMO, VDE 0113)
32 32 690 50 3 LD4-LC130 B E F M Q 1.450
4 LD4-LC140 B E F M Q 1.780
Red knob on yellow background (CNOMO) Emergency stop
32 32 690 50 3 LD4-LC030 B E F M Q 1.450
4 LD4-LC040 B E F M Q 1.780
Protection modules (for customer assembly)
Thermal Magnetic Number Number Reference Weightsetting setting of ofrange range poles protected(Irth min (3…6 Irth max) polesto Irth max)A A kg
6.3…10 30…60 3 3 LB1-LC03L13 0.400
4 4 LB1-LC04L13 0.500
3 LB1-LC05L13 0.500
10…16 48…95 3 3 LB1-LC03L17 0.400
4 4 LB1-LC04L17 0.500
3 LB1-LC05L17 0.500
16…25 75…150 3 3 LB1-LC03L22 0.400
4 4 LB1-LC04L22 0.500
3 LB1-LC05L22 0.500
23…32 95…190 3 3 LB1-LC03L53 0.400
4 4 LB1-LC04L53 0.500
3 LB1-LC05L53 0.500
Volts 24 36 42 48 110 120 220 230 240 380 415 440 480 500 600 660400
50 Hz B – D E F – M M U Q N N – S – Y60 Hz BC CC – D FC FC MC MC MC – – Q Q – S – (3) BD – – ED FD – – – – – – – – – – –
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakersfor control and protection of resistive circuits in category AC-1
References
LB1-LC03L
LD1-LC030
LD4-LC030
Dimensions, schemes : pages 21009/2 to 21011/
5
21167_Ver2.00-EN.fm/2 Schneider Electric
1
21167_Ver2.00-EN.fm/3Schneider Electric
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakersAdd-on blocks
(1) UL and CSA approved.
Current limiter (IP 20)
For Function Reference Weightuse on kg
LD1 or LD5 Increases the breaking capacity of the integral unit LA9-LB920 0.320Mounted on LH side, on RH side or above
Instantaneous auxiliary contact blocks (IP 20) (1)
For Type and number Composition Reference Weightuse on of blocks per unit
N/O N/C C/O kg
LD1, LD4 1 block of 6 contacts comprising: LA1-LC010 0.280or LD5 - 3 signalling contacts 2 1 –Mounted on “contactor state” – – 1RH side - 1 signalling contact “control knob
in any position other than «Auto»” – – 1- 1 signalling contact “tripped on short-circuit” – – 1- 1 signalling contact “tripped”
1 block of 5 contacts comprising: LA1-LC012 0.220- 3 signalling contacts 2 1 –“contactor state” 1 – –- 1 signalling contact “tripped on short-circuit” 1 – –- 1 signalling contact “tripped”
1 block of 4 contacts comprising: LA1-LC025 0.170- 3 signalling contacts 2 1 –“contactor state” 1 1 –- 1 signalling contact “tripped”selectable by the user
1 block of 3 signalling contacts 2 1 – LA1-LC020 0.100“contactor state”
LD4 1 control circuit isolating block 1 – – LA1-LC030 0.035Mounted on (1 or 2 blocks per integral unit)LH side
LD5 1 block of 3 signalling contacts 2 1 – LA1-LC021 0.100Mounted on “contactor state”LH side
1 control circuit isolating block 2 – – LA1-LC031 0.100comprising 2 contacts
Complementary block with one instantaneous auxiliary contact (IP 10) (1)
LD1, LD4 or 1 block comprising – 1 – LA1-LC001 0.035LD5 1 signalling contact “contactor state”
Mounted on LH side or RH side
References
Dimensions, schemes : pages 21009/2 to 21011/
5
LA9-LB920
21167_Ver2.00-EN.fm/4 Schneider Electric
1
21167_Ver2.00-EN.fm/5Schneider Electric
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakersAccessories
(1) Standard control circuit voltages (variable delivery times, please consult your Regional Sales Office).
Electrical tripping and remote reset devices
For Type of block and Basic reference. Weightuse on number per unit Complete with kg
code indicatingcontrol circuitvoltage (1) Usual voltages
LD1, LD4 1 tripping block for operation Time delay 0.2 s LA1-LC070 B E F M Q 0.150or LD5 on de-energisationfitted with an (undervoltage trip)LA1-LC010orLA1-LC012add-on block
Instantaneous LA1-LC072 B E F M Q 0.150
or 1 tripping block for operation Instantaneous LA1-LC071 B E F M Q 0.150on energisation(shunt trip)
LD1, LD4 1 remote electrical 24 V 50/60 Hz LA1-LC052B – 0.320or LD5 reset blockfitted with anLA1-LC010orLA1-LC012add-on block
42 V 50 Hz LA1-LC052E – 0.32048 V 50/60 Hz
100/127 V 50/60 Hz LA1-LC052F – 0.320
200/240 V 50/60 Hz LA1-LC052M – 0.320
Volts 24 48 110 120 220/230 240 380/400 415 44050 Hz B E F – M U Q N N60 Hz B E F F M M Q – N
References
Dimensions, schemes : pages 21009/2 to 21011/
5
21167_Ver2.00-EN.fm/6 Schneider Electric
OOff
AUTO
TRIP. +
RESET
OOff
AUTO
TRIP. +
RESET
LA9-D09982
OOff
AUTO
TRIP. +
RESET
1
21167_Ver2.00-EN.fm/7Schneider Electric
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakersAccessories and spare parts
For control circuit operation
(1) (1) For reversing contactor breakers, order 2 interface modules or 2 voltage converters.(2) When used on rectified single-phase or 3-phase supply, the ripple must be equal to or less than 0.14 of the averagevoltage.Operating limits 0.8 to 1.1 Uc for an ambient temperature ≤ 40 °C.(3) It is essential that the voltage converter be associated with the specific coil indicated.(4) 24 V and 48 V converters can be operated by “low level input”. In this case, the control circuit voltage must be the sameas the supply voltage (24 or 48 V).(5) An RC circuit provides effective protection for circuits highly sensitive to high frequency interference. Voltage limitedto 3 Uc max. and oscillating frequency limited to 400 Hz max.Slight increase in drop-out time (1.2 to 2 times the normal time).
Interface modules (1)
Mounting Type Control Operational Reference Weightvoltage voltage 50/60 HzV V kg
On top Solid state 5…24 24…240 LA1-LC180BD 0.110of theintegralunit
Relay output 24 24…240 LA1-LC580BD 0.110
48 24…240 LA1-LC580ED 0.110
Replacement coils and voltage converters (1)
Mounting For Operational Consumption Description Reference (3) Weightintegral voltage Inrush Sealed
(2)V W W kg
On top LD-LCBD 24 (4) 250 4 Coil LX1-LC0249 0.120of theintegralunit
Converter LA1-LC080BD 0.150
LD-LCED 48 (4) 250 4 Coil LX1-LC0489 0.120
Converter LA1-LC080ED 0.150
LD-LCFD 110 250 4 Coil LX1-LC1109 0.120
Converter LA1-LC080FD 0.150
Suppressor module
Mounting Type Operational Reference Weightvoltage 50/60 HzV kg
Clip-on RC circuit (resistor-capacitor) (5) ≤ 250 LA9-D09982 0.010
References
Dimensions, schemes : pages 21009/2 to 21011/
5
21168_Ver2.10-EN.fm/2 Schneider Electric
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakersAccessories
Protection accessories
Description For Sold Unit Weightuse on in reference
lots of kg
Power terminal Upstream power 5 LA9-LC701 0.050protection shrouds terminals (L1, L2, L3)
Sealing covers Protection module 1 LA1-LC090 0.010
Mounting accessories
Description For Mounting Reference Weightuse on on kg
Mounting plates LD1, LD4, LD5 2 x 32 mm LA9-LC010 0.150 rails
1 x 75 mm LA9-LC012 0.450 railor 2 x 32 mm rails
Height Integral 32 (raises Panel or LA9-LC011 0.200compensation its front face to mounting plateplate the same height as LA9-LD010
the integral 63)
Adaptation
Description Application Reference Weightkg
Kit for lockable For converting a black, non-lockable LA9-LC393 0.100knob (LD1) control knob to a locking knob
Door interlock mechanisms (IP54)
Type For Colour Reference Weightuse on of knob kg
Adjustable LD1 Red LA9-LC330 0.400from 0 to 185 mm(control knob mountedon plate or door)
Black LA9-LC331 0.400
LD4, LD5 Red LA9-LC530 0.400
Black LA9-LC531 0.400
References
LA9-LC701
LA1-LC090
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
Characteristics :pages 21156/2 to 21156/9
Dimensions, schemes :pages 21009/2 to 21011/5
21168_Ver2.10-EN.fm/3Schneider Electric
Motor starters - open version 1
integral 32 contactor breakers and reversing contactor breakersCoils (replacement parts)
Integral 32 can operate on a d.c. supply when fitted with a special coil and corresponding voltage converter: see page21167/7.
(1) Coil voltage reference code letter(s), used to complete the basic reference when ordering an integral unit.
a.c. operation
Rated Average Inductance Voltage Reference Weightcontrol circuit voltages resistance of referenceUc Uc at 20 °C ± 10 % closed code50 Hz 60 Hz circuit (1)V V Ω H kg
– 24 1.225 0.107 BC LX1-LC020 0.120
24 – 1.78 0.142 B LX1-LC024 0.120
– 36 2.92 0.24 CC LX1-LC030 0.120
42 48 5.56 0.45 D LX1-LC042 0.120
48 – 7.10 0.59 E LX1-LC048 0.120
– 110/120 29.51 2.43 FC LX1-LC100 0.120
110 – 37.15 3.12 F LX1-LC110 0.120
127 – 54.28 4.19 G LX1-LC127 0.120
– 220/240 117.4 9.7 MC LX1-LC190 0.120
220/230 – 168.2 13 M LX1-LC220 0.120
230 240 168.72 13 PU7 LX1-LC234 0.120
240 – 203 15.4 U LX1-LC240 0.120
380/400 440/480 515.1 39 Q LX1-LC380 0.120
415/440 – 581.8 46 N LX1-LC415 0.120
500 550/600 741.2 59 S LX1-LC500 0.120
660 – 1603 117 Y LX1-LC660 0.120
Consumption at 50 Hz: inrush (cos ϕ: 0.55) 150 to 200 VA; sealed (cos ϕ: 0.28) 10 to 16 VA.
Consumption at 60 Hz: inrush (cos ϕ: 0.55) 170 to 230 VA; sealed (cos ϕ: 0.30) 12 to 18 VA.
d.c. operation
References
LX1-LC
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
Characteristics :pages 21156/2 to 21156/9
Dimensions, schemes :pages 21009/2 to 21011/5
21158_Ver2.10-EN.fm/2 Schneider Electric
53
54
53
54
53
54
53
54
53
54
53
54
53
54
53
54
16 18
15
16 18
15
41
42
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
16 18
15
16 18
15
06 08
05
96 98
95
13 23 31
14 24 32
08
05 95
98 13 23 31
14 24 32 95
96
95
98 13 23 31
14 24 32
53
54
41
42
06 08
05
96 98
95
13 23 31
14 24 32
08
05 95
98 13 23 31
14 24 32 95
96
95
98 13 23 31
14 24 32
41
42
06 08
05
06 08
05
06 08
05
06 08
05
96 98
95
96 98
95
13 23 31
14 24 32
08
05
08
05
08
05
08
05
95
98
95
98
13 23 31
14 24 32 95
96
95
98
95
96
95
98
13 23 31
14 24 32
41
42
96 98
95
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
16 18
15
16 18
15
16 18
15
16 18
15
16 18
15
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
95
98
95
96
95
98 41
42
41
42
41
42
41
42
41
42
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
96 98
95 95
98
95
96
95
98
06 08
05
06 08
05
96 98
95
08
05
08
05
95
98
95
96
95
98
96 98
95
96 98
95
95
98
95
98
95
96
95
98
95
96
95
98
LA1-LC010 LA1-LC012 LA1-LC025 LA1-LC001
LA1-LC030
LA1-LC020
LD1 LD4
LD1 LD4
06 08
05
08
05
TRIP. +
RESET
TRIP. +
RESET
TRIP. + TRIP. +
TRIP. + TRIP. +
TRIP. + TRIP. +
AUTO AUTO
AUTO AUTO
TRIP. + TRIP. +
2/T
1
4/T
2
6/T
35/
L3
3/L2
1/L1
A2A1
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
A2A1
U
1314 32
31232415
16 18
0506 08
9596 98 08
05
9895 95
96 9895
ou
4241 (5
3)(5
4)63
64
0Auto +
U U
1314 32
312324
1314 32
312324
1314 32
312324
13 23 31
14 24 32
13 23 31
14 24 32
Motor starters - open version 1
integral 32 contactor breakersAuxiliary contact states according to the positions of the control knob
Auxiliary contact actuators
Auxiliary contacts
Operation
Off after short-circuit
General : pages 21151/2 to 21151/7
Characteristics : pages 21156/2 to 21156/9
References : pages 21165/2 to 21168/3
Dimensions : pages 21009/2 and 21009/3
Off + control test function
Off
Off after overload
Tripped on overload
Tripped on short-circuit
Manual reset
contact open
On, contactor open
On, contactor closed
contact closed
21158_Ver2.10-EN.fm/3Schneider Electric
LD5
LA1-LC021
LA1-LC010 LA1-LC012 LA1-LC025 LA1-LC020
LA1-LC001
LA1-LC031
95
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
15
16 18
15
16 18
0608
05
0608
05
0608
05
0608
05
95
96 98
95
96 98
95
96 98
95
96 98
13 23 31
14 24 32
08
05 95
98 13 23 31
14 24 32 95
96
95
98 13 23 31
14 24 32
13 23 31
14 24 32
08
05 95
98 13 23 31
14 24 32 95
96
95
98 13 23 31
14 24 32
13 23 31
14 24 32
08
05 95
98 13 23 31
14 24 32 95
96
95
98 13 23 31
14 24 32
13 23 31
14 24 32
08
05 95
98 13 23 31
14 24 32 95
96
95
98 13 23 31
14 24 32
42
41 13 23 31
14 24 32
53
54
63
64
16 18
15
16 18
15
53
54
63
6442
41 13 23 31
14 24 32
53
54
63
6442
41 13 23 31
14 24 32
53
54
63
64
0608
05 95
96 98 08
05 95
98
95
96
95
9816 18
15
53
54
63
64
13 23 31
14 24 32
06 08
05
08
05
060805
96 98
95
08
05 95
98
95
96
95
98
96 98
95 95
98
95
96
95
98060805
08
05
96 98
95 95
98
95
96
95
98
96 98
95 95
98
95
96
95
98
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
41
42
13 23 31
14 24 32
0608
05
08
05
53
54
63
64
13 23 31
14 24 32
41
42
41
42
13 23 31
14 24 3295
96
95
9813 23 31
14 24 32
9813 23 31
14 24 32
96 98
95
16 18
15
13 23 31
14 24 32
0608
05
08
05
53
54
63
64
13 23 31
14 24 32
41
42
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
16 18
15
13 23 31
14 24 32
53
54
63
64
13 23 31
14 24 32
41
42
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
16 18
15
13 23 31
14 24 32
53
54
63
64
13 23 31
14 24 32
41
42
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
16 18
15
13 23 31
14 24 32
53
54
63
64
13 23 31
14 24 32
41
42
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
16 18
15
13 23 31
14 24 32
TRIP. +
TRIP. +
TRIP. +
TRIP. +
TRIP. +
RESET
AUTO
AUTO
AUTO
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
A2 A1
A2 A1
U
1314 32
312324 15
16 18
0506 08
9596 98 08
05
9895 95
96 9895
ou
4241 53
54
6364
ou0Auto +
U U
1314 32
312324
1314 32
312324
1314 32
312324
1314 32
312324
Motor starters - open version 1
integral 32 reversing contactor breakersAuxiliary contact states according to the positions of the control knob
Auxiliary contact actuators
Auxiliary contacts
Operation
Manual reset
Off after short-circuit
Tripped on short-circuit
Off after overload
Tripped on overload
On, closed
On, closed
On, reversing contactor open
Off
Off + control test function
contact opencontact closed
General : pages 21151/2 to 21151/7
Characteristics : pages 21156/2 to 21156/9
References : pages 21165/2 to 21168/3
Dimensions : pages 21009/2 and 21009/3
21159_Ver3.10-EN.fm/2 Schneider Electric
(1) With converter.(2) The closing time “C” is measured from the moment the coil supply is switched on to initial contact of the main poles. The opening time “O” is measured from the moment the coil supply is switched off to the moment the main poles separate.
Type integral 63Number of poles 3
Rated operational current (Ie) In AC-3 A 63Rated operational voltage (Ue) V 690
Electrical durability in AC-3 at 400 V 1.2 million operating cycles
Mechanical durability at Uc 5 million operating cycles
Maximum operating rate 3600 operating cycles/hourat ambient temperature ≤ 55 °C with converter 600 operating cycles/hour
Environment
Conforming to standards IEC : 158-1, 204-1, 204-2, 364, 947-1/2 and 4UTE : NF C 63-110, C 63-120, C 63-130, C 63-650, C 79-100, C 20-040VDE : 0100, 0110, 0113, 0170, 0171, 471, 0660BS : 5424, 4752, 4941NEN, NBN
Product certifications ASE, ASEFA, ASTA, BV, CSA, DEMKO, DNV, GL NEMKO, NKK, ÖVE, RINA, SCC, SETI, UL, USSR, LROS pending
Protective treatment “TH”
Ambient air temperature Operation °C - 20…+ 60around the device Storage °C - 40…+ 80
Operation °C - 25…+ 50(1) Storage °C - 25…+ 70
Vibration resistance 5…100 Hz Energised state: 3 gn Permissible acceleration De-energised state: 3 gn
Shock resistance Impulse duration: 11 ms Energised state: 8 gn Permissible acceleration De-energised state: 8 gn
Degree of protection To IEC 144 and 529 IP 20BTo VDE 0106 Protection against direct finger contact
Flame resistance Conforming to to IEC 295-2-1, NF C 20-455, and to decree of 2-12-81 (JO 27 NC of 1st and 2/2/1982)Conforming to UL 94 - V0 and NF T 51-072
Maximum operating altitude Without derating m 3000
Operating positions In relation to From (without derating) normal vertical main axis
mounting plane (left-righttilt)
Control circuit characteristics
Rated control 50 Hz V 24…660 circuit voltage (Uc) 60 Hz V 24…600
with converter V 24, 48, 110
Voltage limits Operating 0.85…1.1 Ucat θ ≤ 55 °C Drop-out 0.25…0.7 Uc
Average consumption Inrush VA 375 (50 Hz), 450 (60 Hz)at 20 °C and at Uc Sealed VA 25 (50 Hz or 60 Hz)
(1) Inrush W 300 duration 50 msSealed W 8
Heat dissipation W 8 (50 Hz), 11 (60 Hz)
Operating time (2) 50/60 Hz “C” ms 12…35at 20 °C and at Uc “O” ms 7…20
with “F” ms 25…40converter “C” ms 15…25
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakers
Characteristics
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21169/2 to 21172/3
Dimensions :pages 21009/2 and 21009/3
21159_Ver3.10-EN.fm/3Schneider Electric
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakers
Type integral 63
Pole characteristics
Conventional thermal current (Ith) θ ≤ 40 °C A 63Frequency limits ofoperational current Hz 40…60Rated impulsewithstand voltage (Uimp) Conforming to IEC 947-4 kV 8Rated insulation voltage (Ui) Conforming to IEC 947-1 V 690
Heat dissipation in the power Operational current A 25 32 40 50 63circuits of the contactor breakerand its protection module Power per pole, hot state W 4.4 5 5.8 7 9
Rated making I rms Conforming to IEC 947-4 A 12 or 15 x Ith (above this value, the breaker trips)capacity I peak Conforming to IEC 947-2 kA 105
Rated breaking capacity Operational voltage V 220/240 380/415 440 480/525 600/690conforming to IEC 947-2 Value of cos ϕ 0.25 0.25 0.25 0.25 0.5
Cycle P1 (O-t-CO) Icu kA rms 50 50 50 35 10Cycle P2 (O-t-CO-t-CO) Ics kA rms 50 50 50 35 10O: breaking short-circuit current (open); t: timeCO: closing on short-circuit, breaking short-circuit current (closed-open)
conforming to IEC 947-6-2ensuring reliability of operation Icu = Ics kA rms 50 50 50 30 10
Total breaking time ms 4
Electrical durability in AC-3 Prospective rms short-circuit kA 3 10 25 35 50at Ie max at 415 V current at terminals ofafter 1 cycle O-CO-r-CO at Ics a new device
Millions of operating cycles 1 0.9 0.6 0.5 0.2Thermal limit With Isc max at 415 V, 50 Hz A2s 300 x 103
Cabling Maximum c.s.a. Minimum c.s.a.Flexible cable without cable end mm2 1 x 50 or 2 x 35 1 x 6Flexible cable with cable end mm2 2 x 25 1 x 6Solid cable mm2 1 x 50 1 x 6
Tightening torque N.m 6
Characteristics of thermal-magnetic or magnetic only protection modules
Type LB1-LD03P LB1-LD03M LB6-LD03P LB1-LD03LStandard Standard Frequent Distribution
Protection motors motors starting motors circuitsConforming to standards NF C 63-650 NF C 63-650 NF C 63-650 NF C 63-120Number of poles 3 3 3 3Number of protected poles 3 3 3 3Rated operational voltage V 690 690 690 690Maximum continuous current A 13…63 13…63 13…63 13…63
Thermal protection Setting range (Irth min/Irth max) A 10/13…45/63 10/13…45/63 – 10/13…45/63Temperature compensation °C - 20…+ 60 - 20…+ 60 - 20…+ 60 - 20…+ 60Protection againstphase imbalance With With Without WithoutTripping class 20 20 – –
Magnetic protection Instantaneous trip Fixed at 15 Irth 6…12 Irth max 6…12 Irth max 3…6 Irth maxconforming to IEC 947-1/2/4/6-2 current setting range max (usual setting
9…10 Irth max)Tripping tolerance ± 20 % ± 20 % ± 20 % ± 20 %
Characteristics of versions without control test function, with padlocking facility
Conforming to standards IEC 947Rated operational voltage V 690Mechanical durability Operating cycles 10 000Padlocking facility 1, 2 or 3 padlocks, Ø 8 mm shank
Characteristics of versions with control test function and padlocking facility
Conforming to standards IEC 947, NF C 63-130, VDE 0660, VDE 0113Rated operational voltage V 690Mechanical durability Operating cycles 10 000Padlocking facility By 1, 2 or 3 padlocks (shank Ø 8 mm max and Ø 5 mm min). When flush
mounting, interlocking of the enclosure or cabinet door is possible.
Characteristics
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21169/2 to 21172/3
Dimensions :pages 21009/2 and 21009/3
21159_Ver3.10-EN.fm/4 Schneider Electric
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakersAuxiliary contacts
1) Electrical durability on an inductive load such as the coil of an electromagnet:making current (cos ϕ 0.7) = 10 times the breaking current (cos ϕ 0.4).(2) Electrical durability on an inductive load such as the coil of an electromagnet, the time constant increasing with theload.(3) Lamp load: peak current = 10 times the rated current.(4) Inductive load: cos ϕ 0.4 for a.c. operation; time constant 7 ms for d.c. operation.(5) Motor: peak current = 6 times the rated current.
Instantaneous auxiliary contacts
Conventional thermal current (Ith) A 6
Rated insulation voltage (Ui) Conforming to IEC 947-5-1 V 690
Switching capacity With U ≥ 17 V and I ≥ 10 mA mVA 600
Rated category AC-15 (1) Voltage V 48 110/127 220/240 380/415 440operationalvoltage 1 million operating cycles VA 300 500 600 520 500
1.5 million operating cycles VA 160 300 330 300 280
Making capacity category AC-15 VA 1500 3500 6000 7500 7000
Rated category DC-13 (2) Voltage V 24 48 110 220 440operationalpower 1 million operating cycles W 120 90 75 68 61
1.5 million operating cycles W 70 50 38 33 28
Making capacity category DC-13 W 800 700 400 260 220
Cabling mm2 Maximum c.s.a.: 2 x 2.5. Minimum c.s.a.: 2 x 1
Signalling contacts
Rated thermal current (Ith) A 3
Rated insulation voltage (Ui) Conforming to IEC 947-5-1 V 250
Operational power Voltage V – – 110/127 220for 200 000 operating cycles Resistive load VA – – 600 750
Lamp load (3) VA – – 90 125
Inductive load (4) VA – – 875 500
Motor (5) VA – – 160 200
Voltage V 24 48 110/125 200
Resistive load W 100 100 50 50
Lamp load (3) W 50 50 6 7.5
Inductive load (4) W 75 75 50 50
Motor (5) W 75 75 6 7.5
Cabling mm2 Maximum c.s.a.: 2 x 2.5 - Minimum c.s.a.: 2 x 1
Isolating auxiliary contacts
Rated thermal current (Ith) A 6
Rated insulation voltage (Ui) a.c. supply V 690To IEC 947 and NF C 63-130
d.c. supply V 125
Cabling mm2 Maximum c.s.a.: 2 x 1.5 or 1 x 2.5
Characteristics
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21169/2 to 21172/3
Dimensions :pages 21009/2 and 21009/3
21159_Ver3.10-EN.fm/5Schneider Electric
+
– (0V)
E1
E2
A1
A2
+
– (0V)
E1
E3
E2
A1
A2
+ E1
– E2
A1
A2
+ E1
– E2
A1
A2
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakersInterface modules and converters
(1) For direct control by external contact: connect E1-E3.(2) Warning: for supply from rectified a.c., the power supply must exceed 300 VA and the maximum ripple must be≤ 14 %.
Type Interface modules Converters
Used for direct control of By a programmable controller, with a.c. control of the - By a programmable controller, with d.c. control of the the integral 63 electromagnet electromagnet.
- Control on d.c. supply
Ambient air temperature °C Storage : - 25…+ 70 Storage : - 25…+ 70 around the device
Operation : - 25…+ 50 Operation : - 25…+ 50
Insulation rms voltage between the inputs and outputs: 2.5 kV Common negative terminal
Cabling mm2 Minimum c.s.a.: 1 x 1 - Maximum c.s.a.: 2 x 2.5 Minimum c.s.a.: 1 x 1 - Maximum c.s.a.: 2 x 2.5
Operating limits 0.85... 1.1 Uc 0.8…1.1 Uc (2)
Protection Against reverse polarity (by diode) and Against reverse polarity (by diode) andagainst overvoltage against overvoltage
Indication of input state By LED –
Converter module type LA1-LD LA1-LD580BD 580ED 180BD 080BD 080ED 080FD
Schemes LA1-L580D LA1-L180BD LA1-L080BD LA1-L080FDLA1-L080ED
Input signals Voltage V 24 48 5…24 24 48 5…24 24 (1) 48 (1) 24 (1) 48 (1) –(logic side) () (E1-E2) (E1-E2) (E1- E2) (E1-E2) (E1-E2) (E1-E2) (E3-E2) (E3-E2) – (E3-E2) (E3-E2) –
Current mA 30 20 15…24 V 50 25 15…24 V 20 10 – 20 10 –8.5…5 V 8.5…5 V
State “0” guaranteed for U V < 2.4 < 4.8 < 2.5 < 2.4 < 4.8 < 2.5 < 7 < 14 – < 7 < 14 –or
I mA < 2 < 2 < 2 < 2 < 2 < 2 < 5 < 2.5 – < 5 < 2.5 –
State“1” guaranteed for U V > 20.4 > 40.8 > 4 > 20.4 > 40.8 > 4 > 14 > 28 – > 14 > 28 –
Supply voltage V (2) (2) (2) (2) (2) (2)24…240 24…240 24…240 24…240 24…240 24…240 24 48 110 24 48 110(A1-A2) (A1-A2) (A1-A2) (A1-A2) (A1-A2) (A1-A2) (E1-E2) (E1-E2) (E1-E2) (E1-E2) (E1-E2) (E1-E2)
Electrical durability 5 1in millions of operating cycles
Average Inrush 50 Hz VA 160 160 160 375 375 375 – – – – – –con-sumption 60 Hz VA 185 185 185 450 450 450 – – – – – –
W – – – – – – 250 250 250 300 300 300
Sealed 50/60 Hz VA 12 12 12 25 25 25 – – – – – –
W – – – – – – 4 4 4 8 8 8
Operating Pull-in ms 15…30 15…30 10…35 20…40 20…40 10…45 30 30 30 35 35 35timeat 20 °Cand at Uc Drop-out ms 22…35 22…35 8…30 25…45 25…45 8…30 15 15 15 20 20 20
Characteristics
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21169/2 to 21172/3
Dimensions :pages 21009/2 and 21009/3
21159_Ver3.10-EN.fm/6 Schneider Electric
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakersTripping and reset devices, coil suppressor module
Environment
Conforming to standards IEC 337-1
Protective treatment “TH”
Ambient air temperature Storage °C - 40…+ 80 around the device
Operation °C - 25…+ 55
Permissible for operation at Uc °C - 25…+ 70
Protection against Conforming to VDE 0106direct finger contact
Tripping devices
Type LA1-LC070, LC072 LA1-LC071
Pull-in voltage 0.8…1.1 Uc 0.7…1.1 Uc
Drop-out voltage 0.35…0.7 Uc –
Average consumption Inrush VA 8 8
Sealed VA 4 4
Minimum impulse duration ms – 10
Reset devices
Type LA1-LC052
Consumption VA 9
Duration of a reset cycle s 9
Minimum impulse duration s 0.5
Coil suppressor module LA9-D09982
Type of protection RC (Resistor-Capacitor)
Scheme
Operational voltage V ≤ 250
Characteristics
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21169/2 to 21172/3
Dimensions :pages 21009/2 and 21009/3
21159_Ver3.10-EN.fm/7Schneider Electric
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakers
Breaking capacity of integral 63 contactor breakers according to the rated voltage and protection module fitted.
Breaking capacity
Protection module Operational voltageReference Irth 220/240 V 400/415 V 440 V 500 V 660/690 V
min maxA A kA kA kA kA kA
LB-LD0316 10 13 ≥ 130 ≥ 130 ≥ 130 ≥ 130 10
LB-LD0321 13 18 ≥ 130 ≥ 130 ≥ 130 ≥ 130 10
LB-LD0322 18 25 ≥ 130 ≥ 130 50 35 10
LB-LD0353 23 32 ≥ 130 50 50 35 10
LB-LD0355 28 40 ≥ 130 50 50 30 10
LB-LD0357 35 50 ≥ 130 50 50 30 10
LB-LD0361 45 63 ≥ 130 50 50 30 10
Characteristics
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21169/2 to 21172/3
Dimensions :pages 21009/2 and 21009/3
21159_Ver3.10-EN.fm/8 Schneider Electric
6 10 20 40 60 100 200 400 600 1000 20000,01 s
0,1 s
1 s
10 s
1 min
10min
100min
300min
15 30 54
40 s
P16P21P22P53P55
P61P57
irth35 45
10 13 18 2523
3228
40 5063
195
270
375
480
600
750
945
6 10 20 40 60 100 200 400 600 1000 20000,01 s
0,1 s
1 s
10 s
1 min
10min
100min
300min
irth10 18 2523
3228 35
4045 63
50
M16M21 M22M53M55M57M61
1313
190
380
600
78
108
240
216150
156
300
480
760
1313
By thermal-magnetic modules LB1-LD03P (1)
By thermal-magnetic modules LB1-LD03M (1)
(1) Thermal protection: the average operating times shown in these curves are for an ambient air temperature of 20° C,without prior current flow (cold state). The average operating time after prolonged current flow (hot state) can be calculatedby applying the coefficient 0.5.
Motor protection (normal starting)
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakers
Selection of protection module according to tripping characteristics
Current in A
Time
Time
Current in A
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21169/2 to 21172/3
Dimensions :pages 21009/2 and 21009/3
The
rmal
zon
eM
agne
tic z
one
21159_Ver3.10-EN.fm/9Schneider Electric
6 10 20 40 60 100 200 400 600 1000 20000,01 s
0,1 s
1 s
10 s
1 min
10min
100min
300min
80 110
190
380
600
78
108
240
216150
156
300
480
760
6 10 20 40 60 100 200 400 600 1000 20000,01 s
0,1 s
1 s
10 s
1 min
10min
100min
300min
18 23 63 irth25
2832
3540
4550
L22L53L55L57
L61
150
150
190120 240
300380190
7595
By magnetic modules LB6-LD03M
Motor protection (frequent starting)
Distribution circuit protection
By thermal-magnetic modules LB1-LD03L
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakers
Selection of protection module according to tripping characteristics
Time
Current in A
The
rmal
zon
e
Time
Current in A
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21169/2 to 21172/3
Dimensions :pages 21009/2 and 21009/3
Mag
netic
zon
e
21159_Ver3.10-EN.fm/10 Schneider Electric
1008060
40
10
20
86
43
2
10,80,6
0,4
0,2
0,10,20,1 0,4 0,3 1 2 4 6 8 10 15 50 100 20020
cos ϕ =
0,7
= 0,
5
= 0,
3
= 0,
25
1 (1)
1000800
600
400
200
100
80
60
40
20
101 2 4 6 8 10 15 20 50 100 200
(1)1
3-phase 400/415 V, 50 Hz
1 18 to 25 A up to 45 to 63 A
Maximum thermal limit on short-circuit
1 18 to 25 A up to 45 to 63 A
(1) LB1-LD0322 to LD0361: rating of associated thermal overload module.
Current limitation and thermal limit on short-circuit
Current limitation on short-circuit
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakers
Selection of protection module according to tripping characteristics
Thermal limit I2t in kA2 sin the short-circuit protection zone
Prospective rms short-circuit current in kA
Prospective rms short-circuit current in kA
Maximum peak current in kA
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21169/2 to 21172/3
Dimensions :pages 21009/2 and 21009/3
21159_Ver3.10-EN.fm/11Schneider Electric
1008060
40
10
20
86
43
2
10,80,6
0,4
0,2
0,10,20,1 0,4 0,3 1 2 4 6 8 10 15 50 100 20020 35
ϕco
s =
0,7
= 0,
5
= 0,
3
= 0,
25
(1)1
1000800
600
400
200
100
80
60
40
20
101 2 4 6 8 10 15 20 50 100 20035
(1)1
3-phase 480/500 V, 50 Hz
Current limitation on short-circuit
1 18 to 25 A up to 63 A
Maximum thermal limit on short-circuit
1 18 to 25 A up to 63 A
(1) LB1-LD0322 to LD0361: rating of associated thermal overload module.
Current limitation and thermal limit on short-circuit (continued)
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakers
Selection of protection module according to tripping characteristics
Prospective rms short-circuit current in kA
Prospective rms short-circuit current in kA
Thermal limit I2t in kA2sin the short-circuit protection zone
Maximum peak current in KA
General :pages 21151/2 to 21151/7
Selection :pages 21152/2 to 21152/5
References :pages 21169/2 to 21172/3
Dimensions :pages 21009/2 and 21009/3
21169_Ver2.10-EN.fm/2 Schneider Electric
With control test function, with padlocking facility
Black knob (CNOMO, VDE 0113)
(1) For the unit to function, it must be fitted with a protection module, to be ordered separately, see page opposite.(2) Standard control circuit voltages (variable delivery times, please consult your Regional Sales Office).
(3) Variant: UL 508 “type E” approved version (SPCD) at 347/600 V; to order, add suffix H5 to the reference. Ex : LD1-LD030MH5.(4) For use on d.c., the unit is supplied with 1 or 2 voltage converters, including coil suppression device(s) (2 convertersfor reversing contactor breakers).
3-pole contactor breakers without protection module (1)
Standard power ratings Operational Breaking Basic reference (3) Weightof 3-phase motors current capacity Complete with 50/60 Hz in category AC-43 (Iq) code indicating
for control circuit220 V 400 V Ue ≤ 415 V voltage240 V 415 V 440 V 500 V 660 V (2) Usual voltageskW kW kW kW kW A kA kg
Without control test function and padlocking facility
Black knob
15 30 33 37 55 63 50 LD1-LD030 B E F M Q 3.70033
With control test function and padlocking facility
Black knob (CNOMO, VDE 0113)
15 30 33 37 55 63 50 LD4-LD130 B E F M Q 3.80033
Red knob on yellow background (CNOMO) Emergency Stop
15 30 33 37 55 63 50 LD4-LD030 B E F M Q 3.80033
3-pole reversing contactor breakers without protection module (1)
15 30 33 37 55 63 50 LD5-LD130 B E F M Q 7.60033
Red knob on yellow background (CNOMO) Emergency Stop
15 30 33 37 55 63 50 LD5-LD030 B E F M Q 7.60033
Volts 24 36 42 48 110 120 220 230 240 380 415 440 480 500 600 660400
50 Hz B – D E F – M M U Q N N – S – Y60 Hz BC CC – CE K FC LC MC MC – – UX Q – S – (4) BD – – ED FD – – – – – – – – – – –
References Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakersfor the control and protection of motors (for customer assembly)
LD1-LD030
LD5-LD030
Dimensions, schemes :pages 21009/2 to 21011/
5
21169_Ver2.10-EN.fm/3Schneider Electric
(1) Protection modules UL and CSA approved.
Thermal-magnetic protection modules (compensated and differential for normal starting motors) (1)
Standard power ratings Thermal Magnetic Reference Weightof 3-phase motors setting protection50/60 Hz in category AC-43 range220 V 400 V 480 V 600 V (Irth min240 V 415 V 440 V 525 V 690 V to Irth max)kW kW kW kW kW A A kg
Fixed magnetic protection, set at 15 Irth max, for mounting on integral 63
3 5.5 5.5 7.5 10 10…13 – LB1-LD03P16 0.780
4 9 9 11 15 13…18 – LB1-LD03P21 0.780
5.5 11 11 15 18.5 18…25 – LB1-LD03P22 0.780
7.5 15 15 18.5 22 23…32 – LB1-LD03P53 0.780
9 22 22 25 33 28…40 – LB1-LD03P55 0.780
11 25 25 33 45 35…50 – LB1-LD03P57 0.780
15 33 33 40 55 45…63 – LB1-LD03P61 0.780
Adjustable magnetic protection, from 6 to 12 Irth max, for mounting on integral 63
3 5.5 5.5 7.5 10 10…13 78…156 LB1-LD03M16 0.780
4 9 9 11 15 13…18 108…216 LB1-LD03M21 0.780
5.5 11 11 15 18.5 18…25 150…300 LB1-LD03M22 0.780
7.5 15 15 18.5 22 23…32 190…380 LB1-LD03M53 0.780
9 22 22 25 33 28…40 240…480 LB1-LD03M55 0.780
11 25 25 33 45 35…50 300…600 LB1-LD03M57 0.780
15 33 33 40 55 45…63 380…760 LB1-LD03M61 0.780
Magnetic protection modules for frequent starting motors
Standard power ratings Magnetic Reference Weightof 3-phase motors protection50/60 Hz in category AC-43220 V 400 V 480 V 600 V240 V 415 V 440 V 525 V 690 VkW kW kW kW kW A kg
3 5.5 5.5 7.5 10 78…156 LB6-LD03M16 0.780
4 9 9 11 15 108…216 LB6-LD03M21 0.780
5.5 11 11 15 18.5 150…300 LB6-LD03M22 0.780
7.5 15 15 18.5 22 190…380 LB6-LD03M53 0.780
9 22 22 25 33 240…480 LB6-LD03M55 0.780
11 25 25 33 45 300…600 LB6-LD03M57 0.780
15 33 33 40 55 380…760 LB6-LD03M61 0.780
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakersfor the control and protection of motors (for customer assembly)
References
LB1-LD03M
Dimensions, schemes :pages 21009/2 to 21011/
5
LB6-LD03M
21170_Ver3.10-EN.fm/2 Schneider Electric
PEN
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakersfor control and protection of resistive circuits in category AC-1
Note : The PEN conductor must not be isolated
Note : All live conductors must be isolated. Neutral protection optional.
Selecting the type of contactor breaker and protection module
Neutral point Type Equipment Combinationconnection of scheme contactor breaker + protection module
circuit
Neutral TNC 3-pole LD1-LD030 + LB1-LD03Lconnect- (neutral + PENion and PE
combined)LD4-LD130 + LB1-LD03L
LD4-LD030 + LB1-LD03L
TNS 3-pole LD1-LD030 + LB1-LD03L(neutraland PEseparated)
LB4-LD130 + LB1-LD03L
LD4-LD030 + LB1-LD03L
Selection
Dimensions, schemes :pages 21009/2 to 21011/
5
21170_Ver3.10-EN.fm/3Schneider Electric
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakersfor control and protection of resistive circuits in category AC-1
Thermal-magnetic (compensated)
(1) For the unit to function, it must be fitted with a protection module, to be ordered separately.(2) Standard control circuit voltages (variable delivery times, please consult your Regional Sales Office).
(3) For use on d.c., the unit is supplied with a voltage converter, including coil suppression device.
3-pole contactor breakers without protection module (1)
Rated Maximum Maximum Breaking Number Basic reference. Weightthermal operational operational capacity of Complete withcurrent current voltage (Iq) poles code indicatingI th AC-1 for control circuitθ ≤ 40 °C θ ≤ 40 °C Ue ≤ 415 V voltage (2) Usual voltagesA A V kA kg
Without control test function, with padlocking facilityBlack knob
63 63 690 50 3 LD1-LD030 B E F M Q 3.700
With control test function and padlocking facilityBlack knob (CNOMO, VDE 0113)
63 63 690 50 3 LD4-LD130 B E F M Q 3.800
Red knob on yellow background (CNOMO) Emergency Stop
63 63 690 50 3 LD4-LD030 B E F M Q 3.800
Protection modules (for customer assembly)
Thermal Magnetic Number Number Reference Weightsetting setting of ofrange range poles protected(Irth min (3…6 Irth max) polesto Irth max)A A kg
10…13 39…78 3 3 LB1-LD03L16 0.780
13…18 54…108 3 3 LB1-LD03L21 0.780
18…25 75…150 3 3 LB1-LD03L22 0.780
23…32 95…190 3 3 LB1-LD03L53 0.780
28…40 120…240 3 3 LB1-LD03L55 0.780
35…50 150…300 3 3 LB1-LD03L57 0.780
45…63 190…380 3 3 LB1-LD03L61 0.780
Volts 24 36 42 48 110 120 220 230 240 380 415 440 480 500 600 660400
50 Hz B – D E F – M M U Q N N – S – Y60 Hz BC CC – CE K FC LC MC MC – – UX Q – S – (3) BD – – ED FD – – – – – – – – – – –
References
LD1-LD030
LB1-LD03L
Dimensions, schemes :pages 21009/2 to 21011/
5
21171_Ver2.10-EN.fm/2 Schneider Electric
1
21171_Ver2.10-EN.fm/3Schneider Electric
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakersAdd-on blocks
(1) UL and CSA approved.
Instantaneous auxiliary contact blocks (IP 20) (1)
For Type and number Composition Reference Weightuse on of blocks per unit
N/O N/C C/O kg
LD1. LD4 1 block of 6 contacts comprising: LA1-LC010 0.280or LD5 - 3 signalling contacts “contactor state” 2 1 –Mounted on - 1 signalling contact “control knob – – 1RH side in any position other than «Auto»”
- 1 signalling contact – – 1“tripped on short-circuit”- 1 signalling contact “tripped” – – 1
1 block of 5 contacts comprising: LA1-LC012 0.220- 3 signalling contacts “contactor state” 2 1 –- 1 signalling contact 1 – –“tripped on short-circuit”- 1 signalling contact “tripped” 1 – –
1 block of 4 contacts comprising: LA1-LC025 0.170- 3 signalling contacts “contactor state” 2 1 –- 1 signalling contact “tripped”, 1 1 –selectable by the user
1 block of 3 signalling contacts 2 1 – LA1-LC020 0.100“contactor state”
LD4 1 control circuit isolating block 1 – – LA1-LC030 0.035Mounted on (1 or 2 blocks per unit)LH side
LD5 1 block of 3 signalling contacts 2 1 – LA1-LC021 0.100Mounted on “contactor state”LH side
1 control circuit isolating block 2 – – LA1-LC031 0.100comprising 2 contacts
Complementary block with one instantaneous auxiliary contact (IP 10) (1)
LD1. LD4 or 1 block comprising – 1 – LA1-LC001 0.035LD5 1 signalling contact “contactor state”
Mounted on LH side or RH side
References
Dimensions, schemes :pages 21009/2 to 21011/
5
21171_Ver2.10-EN.fm/4 Schneider Electric
1
21171_Ver2.10-EN.fm/5Schneider Electric
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakersAccessories
(1) Standard control circuit voltages (variable delivery times, please consult your Regional Sales Office).
Electrical tripping and reset devices
For Type and number Basic reference. Weightuse on per unit Complete with code kg
indicating controlcirc. voltage (1) Usual voltage
LD1, LD4 1 tripping block for operation Time delay 0.2 s LA1-LC070p B E F M Q 0.150or LD5 on de-energisationfitted with an (undervoltage trip)LA1-LC010orLA1-LC012add-on block
Instantaneous LA1-LC072p B E F M Q 0.150
or 1 tripping block for Instantaneous LA1-LC071p B E F M Q 0.150operation on energisation(shunt trip)
LD1, LD4 1 remote electrical 24 V 50/60 Hz LA1-LC052B – 0.320or LD5 reset blockfitted with anLA1-LC010orLA1-LC012add-on block
42 V 50 Hz LA1-LC052E – 0.32048 V 50/60 Hz
100/127 V 50/60 Hz LA1-LC052F – 0.320
200/240 V 50/60 Hz LA1-LC052M – 0.320
Volts 24 48 110 120 220/230 240 380/400 415 44050 Hz B E F – M U Q N N60 Hz B E F F M M Q – N
References
Dimensions, schemes :pages 21009/2 to 21011/
5
21171_Ver2.10-EN.fm/6 Schneider Electric
1
21171_Ver2.10-EN.fm/7Schneider Electric
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakersAccessories and spare parts
For c control circuit operation
(1) For reversing contactor breakers, order 2 interface modules or 2 voltage converters.(2) When used on rectified single-phase or 3-phase supply, the ripple must be equal to or less than 0.14 of the averagevoltage.Operating limits 0.8 to 1.1 Uc for an ambient temperature ≤ 40 °C.(3) It is essential that the voltage converter be associated with the specific coil indicated.(4) 24 V and 48 V converters can be operated by “low level input”. In this case, the control circuit voltage must be thesame as the supply voltage (24 or 48 V).(5) An RC circuit provides effective protection for circuits highly sensitive to high frequency interference. Voltage limitedto 3 Uc max. and oscillating frequency limited to 400 Hz max.Slight increase in drop-out time (1.2 to 2 times the normal time).
Interface modules (1)
Mounting Type Control Operational Reference Weightvoltage c voltage 50/60 HzV V kg
On top Sold state 5…24 24…240 LA1-LD180BD 0.110of theintegralunit
Relay output 24 24…240 LA1-LD580BD 0.110
48 24…240 LA1-LD580ED 0.110
Replacement coils and voltage converters (1)
Mounting For Operational Consumption Description Reference (3) Weightintegral voltage Inrush Sealed
c (2)V W W kg
On top LDp-LDpppBD 24 (4) 300 8 Coil LX1-LD0249 0.300of theintegralunit
Converter LA1-LD080BD 0.150
LDp-LDpppED 48 (4) 300 8 Coil LX1-LD0489 0300
Converter LA1-LD080ED 0.150
LDp-LDpppFD 110 300 8 Coil LX1-LD1109 0.300
Converter LA1-LD080FD 0.150
Coil suppressor module
Mounting Type Operational Reference Weightvoltage 50/60 HzV kg
Clip-on RC circuit (resistor-capacitor) (5) ≤ 250 LA9-D09982 0.010
References
Dimensions, schemes :pages 21009/2 to 21011/
5
21172_Ver2.10-EN.fm/2 Schneider Electric
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakersAccessories (to be ordered separately)
Protection accessories
Description For Sold Unit Weightuse on in reference
lots of kg
Power terminal Upstream power 5 LA9-LD701 0.050protection shrouds terminals (L1, L2, L3)
Sealing covers Protection 1 LA1-LC090 0.010module
Mounting accessories
Description For Mounting Reference Weightuse on on kg
Mounting plates LD1, LD4, LD5 1 x 75 mm LA9-LD010 0.450 railor 2 x 32, rails
Door interlock mechanisms (IP54)
Type For Colour Reference Weightuse on of knob kg
Adjustable LD1 Red LA9-LC330 0.400from 0 to 185 mmwith extension(control knob mountedon plate or door)
Black LA9-LC331 0.400
LD4, LD5 Red LA9-LC530 0.400
Black LA9-LC531 0.400
References
LA9-LD010
LA1-LC090
General : pages 21151/2 to 21151/7
Selection : pages 21152/2 to 21152/5
Characteristics : pages 21159/2 to 21159/11
Dimensions, schemes : pages 21009/2 to 21011/5
21172_Ver2.10-EN.fm/3Schneider Electric
Motor starters - open version 1
integral 63 contactor breakers and reversing contactor breakersCoils (Replacement parts)
Consumption at 50 Hz: inrush (cos ϕ: 0.55) 350 to 400 VA; sealed (cos ϕ: 0.28) 20 to 30 VA.
Consumption at 60 Hz: inrush (cos ϕ: 0.55) 420 to 500 VA; sealed (cos ϕ: 0.30) 24 to 36 VA.
Integral 63 can operate on a d.c. supply when fitted with a special coil and a corresponding voltage converter:see page 21171/7.
(1) Coil voltage reference code letter(s), used to complete the basic reference when ordering an integral unit.
a.c. operation
Rated Average Inductance Voltage reference Weightcontrol circuit voltages resistance of referenceUc Uc at 20 °C ± 10 % closed code50 Hz 60 Hz circuit (1)V V Ω H kg
– 24 0.213 0.045 BC LX1-LD020 0.300
24 – 0.323 0.071 B LX1-LD024 0.300
– 36 0.503 0.106 CC LX1-LD030 0.300
– 48 0.845 0.19 CE LX1-LD040 0.300
42 – 0.987 0.22 D LX1-LD042 0.300
48 – 1.26 0.29 E LX1-LD048 0.300
– 110 4.88 1 K LX1-LD090 0.300
– 115/120 5.89 1.18 FC LX1-LD100 0.300
110 – 6.48 1.48 F LX1-LD110 0.300
127 – 9.80 2.13 G LX1-LD127 0.300
– 220 19.82 4.2 LC LX1-LD180 0.300
– 230/240 23.24 4.5 MC LX1-LD190 0.300
220/230 – 30.51 6.7 M LX1-LD220 0.300
240 – 37.66 7.9 U LX1-LD240 0.300
– 440 80.46 16.7 UX LX1-LD360 0.300
380/400 460/480 93.63 20 Q LX1-LD380 0.300
415/440 – 116.46 23.7 N LX1-LD415 0.300
500 575/600 152.18 31 S LX1-LD500 0.300
660 – 290.80 60 Y LX1-LD660 0.300
d.c. operation
References
LX1-LD
General : pages 21151/2 to 21151/7
Selection : pages 21152/2 to 21152/5
Characteristics : pages 21159/2 to 21159/11
Dimensions, schemes : pages 21009/2 to 21011/5
21161_Ver2.10-EN.fm/2 Schneider Electric
53
54
53
54
53
54
53
54
53
54
53
54
53
54
53
54
16 18
15
16 18
15
41
42
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
16 18
15
16 18
15
06 08
05
96 98
95
13 23 31
14 24 32
08
05 95
98 13 23 31
14 24 32 95
96
95
98 13 23 31
14 24 32
53
54
41
42
06 08
05
96 98
95
13 23 31
14 24 32
08
05 95
98 13 23 31
14 24 32 95
96
95
98 13 23 31
14 24 32
41
42
06 08
05
06 08
05
06 08
05
06 08
05
96 98
95
96 98
95
13 23 31
14 24 32
08
05
08
05
08
05
08
05
95
98
95
98
13 23 31
14 24 32 95
96
95
98
95
96
95
98
13 23 31
14 24 32
41
42
96 98
95
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
16 18
15
16 18
15
16 18
15
16 18
15
16 18
15
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
95
98
95
96
95
98 41
42
41
42
41
42
41
42
41
42
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
96 98
95 95
98
95
96
95
98
06 08
05
06 08
05
96 98
95
08
05
08
05
95
98
95
96
95
98
96 98
95
96 98
95
95
98
95
98
95
96
95
98
95
96
95
98
LA1-LC010 LA1-LC012 LA1-LC025 LA1-LC001
LA1-LC030
LA1-LC020
LD1 LD4
LD1 LD4
06 08
05
08
05
TRIP. +
RESET
TRIP. +
RESET
TRIP. + TRIP. +
TRIP. + TRIP. +
TRIP. + TRIP. +
AUTO AUTO
AUTO AUTO
TRIP. + TRIP. +
2/T
1
4/T
2
6/T
35/
L3
3/L2
1/L1
A2A1
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
A2A1
U
1314 32
31232415
16 18
0506 08
9596 98 08
05
9895 95
96 9895
ou
4241 (5
3)(5
4)63
64
0Auto +
U U
1314 32
312324
1314 32
312324
1314 32
312324
13 23 31
14 24 32
13 23 31
14 24 32
Motor starters - open version 1
integral 63 contactor breakersAuxiliary contact states according to the positions of the control knob
Auxiliary contact actuators
Auxiliary contacts
Operation
Off after short-circuit
General : pages 21151/2 to 21151/7
Characteristics : pages 21152/2 to 21159/
11References :
pages 21169/2 to 21172/3Dimensions :
pages 21009/2 and 21009/3
Off + isolation
Off
Off after overload
Tripped on overload
Tripped on short-circuit
Manual reset
contact open
On, contactor open
On, contactor closed
contact closed
21161_Ver2.10-EN.fm/3Schneider Electric
LD5
LA1-LC021
LA1-LC010 LA1-LC012 LA1-LC025 LA1-LC020
LA1-LC001
LA1-LC031
95
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
15
16 18
15
16 18
0608
05
0608
05
0608
05
0608
05
95
96 98
95
96 98
95
96 98
95
96 98
13 23 31
14 24 32
08
05 95
98 13 23 31
14 24 32 95
96
95
98 13 23 31
14 24 32
13 23 31
14 24 32
08
05 95
98 13 23 31
14 24 32 95
96
95
98 13 23 31
14 24 32
13 23 31
14 24 32
08
05 95
98 13 23 31
14 24 32 95
96
95
98 13 23 31
14 24 32
13 23 31
14 24 32
08
05 95
98 13 23 31
14 24 32 95
96
95
98 13 23 31
14 24 32
42
41 13 23 31
14 24 32
53
54
63
64
16 18
15
16 18
15
53
54
63
6442
41 13 23 31
14 24 32
53
54
63
6442
41 13 23 31
14 24 32
53
54
63
64
0608
05 95
96 98 08
05 95
98
95
96
95
9816 18
15
53
54
63
64
13 23 31
14 24 32
06 08
05
08
05
060805
96 98
95
08
05 95
98
95
96
95
98
96 98
95 95
98
95
96
95
98060805
08
05
96 98
95 95
98
95
96
95
98
96 98
95 95
98
95
96
95
98
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
41
42
13 23 31
14 24 32
0608
05
08
05
53
54
63
64
13 23 31
14 24 32
41
42
41
42
13 23 31
14 24 3295
96
95
9813 23 31
14 24 32
9813 23 31
14 24 32
96 98
95
16 18
15
13 23 31
14 24 32
0608
05
08
05
53
54
63
64
13 23 31
14 24 32
41
42
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
16 18
15
13 23 31
14 24 32
53
54
63
64
13 23 31
14 24 32
41
42
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
16 18
15
13 23 31
14 24 32
53
54
63
64
13 23 31
14 24 32
41
42
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
16 18
15
13 23 31
14 24 32
53
54
63
64
13 23 31
14 24 32
41
42
13 23 31
14 24 32
13 23 31
14 24 32
13 23 31
14 24 32
16 18
15
13 23 31
14 24 32
TRIP. +
TRIP. +
TRIP. +
TRIP. +
TRIP. +
RESET
AUTO
AUTO
AUTO
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
A2 A1
A2 A1
U
1314 32
312324 15
16 18
0506 08
9596 98 08
05
9895 95
96 9895
ou
4241 53
54
6364
ou0Auto +
U U
1314 32
312324
1314 32
312324
1314 32
312324
1314 32
312324
Motor starters - open version 1
integral 63 reversing contactor breakersAuxiliary contact states according to the positions of the control knob
Auxiliary contact actuators
Auxiliary contacts
Operation
Manual reset
Off after short-circuit
Tripped on short-circuit
Off after overload
Tripped on overload
On, closed
On, closed
On, reversing contactor open
Off
Off + isolation
contact opencontact closed
General : pages 21151/2 to 21151/7
Characteristics : pages 21159/2 to 21159/
11References :
pages 21169/2 to 21172/3Dimensions :
pages 21009/2 and 21009/3
21009_Ver6.11-EN.fm/2 Schneider Electric
128,
512
1,5
146
158,5
192
250
LA1-LD080
28
=90
104,
545
100,
5
210
16,5
=
= =
135
==
4,5 90
45
45
99
135
==364,5
45
45123
7078
,5
148,
5
109,5
139123
7097
,5
167,
5
109,5
139
LA1-LB080
135
364,5
45
45
100
88
109
123
9989
188
LA1-LC080
155= =
66
74,5
68,5
19= = 816
0
45
85
52 33
38= =
100
88
109
123
9989
188
LA1-LC080
155= =
66
74,5
68,5
19= = 816
0
45
85
52 33
38= =
94
88
109
123
155
9389
182
45
132
33= 85 8
160
68,5
68,5
=
121,
515
3,5
275
148
160,5
194 181
45
100,
545
129,
5
59 63 59
210
16,5
121,
512
1,5
146
158,5
192
243
= =28
= =90
97,5
4510
0,5
210
16,5
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Contactor breakers and reversing contactor breakers integral 18Control circuit : a.c. Control circuit : d.c.
LD1-LB030 LD5-LB130 LD-LB30 + LB-LB03P + LA1-LB080 + LB-LB03P + LB-LB03PLD3-LB
Contactor breakers integral 32Control circuit : a.c. Control circuit : d.c.
LD-LC30 LD-LC40 LD-LC0 + LB-LC0 + LA1-LC080+ LB-LC03 + LB1-LC0 LD-LC30 LD-LC40
Contactor breakers integral 63Control circuit : a.c. Control circuit : d.c.LD-LD30 + LB-LD03 LD-LD30 + LBLD03 + LA1-LD080
Contactor breakers and reversing contactor breakers integral 32 Contactor breakers and reversing contactor breakers integral 63LD5-LC30 + LB-LC03M LD5-LC30 + LB-LC03M
Dimensions
General :pages 21151/2 to 21151/7
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Schemes :pages 21011/2 to 21011/5
21009_Ver6.11-EN.fm/3Schneider Electric
6
53,5
146
2ØM4
103
115
51 12 12
b
13
LA1-LC001
11
LA1-LC012
26
LA1-LC010
LA1-LC070LA1-LC071LA1-LC072
51 12 9 9
LA1-LC001
1112
LA1-LC025
b
1311
LA1-LC025
LA1-LC021
LA1-LC001
12 26
LA1-LC031
LA1-LC021
13 11
LA1-LC012
LA1-LC001
26
LA1-LC010
LA1-LC070LA1-LC071LA1-LC072
51 12
11 12 12 11
LA1-LB021, LB0211
LA1-LB001
LA1-LB001
LA1-LB015
1112
LA1-LB001
LA1-LB015
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
For mounting on contactor breakers integral 32 and 63
Add-on blocksFor mounting on contactor breakers and reversing contactor breakers integral 18
Add-on blocksFor mounting on contactor breakers and reversing contactor breakers integral 32 and 63
Current limiter Add-on blocksLA9-LB920 For mounting on contactor breakers integral 18
LA1-LB015 LA1-LB031 LA1-LB034 LA1-LB080BDLA1-LB001 LA1-LB0311 LA1-LB0341 LA4-D
LA1-LB080BD b = 19LA4-DA, DE, DF, DT b = 12LA4-DL, DM, DR, DW b = 19
Add-on blocks
LA1-LC012 LA1-LC010 LA1-LC052 LA1-LC020 LA1-LC030 LA1-LC025LA1-LC001 LA1-LC07 (1 or 2) LA1-LC001
LA1-LB015 LA1-LB080BDLA1-LB021, LB0211, LA1-LB001 LA4-D
LA1-LB080BD b = 19LA4-DA, DE, DF, DT b = 12LA4-DL, DM, DR, DW b = 19
LA1-LC021, LC025 LA1-LC031 LA1-LC012 LA1-LC010 LA1-LC052 LA1-LC020LA1-LC001 LA1-LC001 LA1-LC07
Dimensions, mounting
General :pages 21151/2 to 21151/7
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Schemes :pages 21011/2 to 21011/5
21009_Ver6.11-EN.fm/4 Schneider Electric
c 15 c
210
G 4xØM5
75G
220
210
DZ5-ME9
GAF1-EA5
210
c 33
137,
512
8,5
266
LA9-LD010
155 (AM1-DE200)
182
10
8993
15155 155 G
160
AF1-EA4a
170
G
160
DZ5-ME8
(AM1-DE200)
148,
5
10139
7078
,5
15139139
45AF1-EA4 36
135
145
36
DZ5-ME8
135
100
min
i10
0 m
ini LA9-LB930
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
integral 18
integral 32
integral 32 with current limiter LA9-LB920
integral 63
On 35 mm rail On 32 mm rails, at 145 mm centres On pre-slotted mounting plate AM1-P
integral 18 with current limiter LA9-LB920 Several integral 18 units with current limiter LA9-LB920LH side Upstream
On 35 mm rail On 32 mm rails, at 170 mm centres On pre-slotted mounting plate AM1-P
a G GLD1-LC30 66 LD1-LC30 19 LD1-LC30 19LD1-LC40 85 LD1-LC40 38 LD1-LC40 38LD4-LC30 66 LD4-LC30 19 LD4-LC30 19LD4-LC40 85 LD4-LC40 38 LD4-LC40 38LD5-LC30 132 LD5-LC30 85 LD5-LC30 85
LH side Upstream
On 75 mm rail, with mounting plate LA9-LD010 On 32 mm rails, at 220 mm centres On pre-slotted mounting plate AM1-P
a b c G c G c GLD1 266 137.5 192 28 LD1 192 28 LD1 192 28LD4 266 137.5 192 28 LD4 192 28 LD4 192 28LD5 282 153.5 194 63 LD5 194 63 LD5 194 63
Mounting
General :pages 21151/2 to 21151/7
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Schemes :pages 21011/2 to 21011/5
21009_Ver6.11-EN.fm/5Schneider Electric
110
120
36139
110
96
155 33
206
LA9-LC012
160
19
75
120
110
40
DZ5-ME5
155
LA9-LC012
31
3650
110
120
155 36
28
208
4xM5,5
75
28
210
155 37
LA9-LC011
33
LA9-LD010
160
155 37
LA9-LC011
160
c 31
G
LA9-LD010
68
120
110
40
DZ5-ME5
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
integral 18 With mounting plate LA9-LC010On 32 mm rails, at 120 mm centres
integral 32
With height compensation plate LA9-LC011 (1)
On 75 mm rail
integral 63 With mounting plate LA9-LD010On 32 mm rails, at 120 mm centres
With mounting plate LA9-LC010 With mounting plate LA9-LC012 With mounting plate LA9-LC012On 32 mm rails, at 120 mm centres On 75 mm rail On 32 mm rails, at 120 mm centres
With mounting plate LA9-LD010 On pre-slotted mounting plate AM1-P
(1) For raising the front face of the integral 32 to the same height as that of the integral 63.
c GLD1 192 78LD4 192 78LD5 194 94
Mounting
General :pages 21151/2 to 21151/7
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
Schemes :pages 21011/2 to 21011/5
21173_Ver2.10-EN.fm/2 Schneider Electric
2
446 =
=
1
a
a1
a2
(1)
(2)
4 (1)
46 ==
1
a
a1
a2
(2)
(3)
2020
4 (1)
46 ==
1
a
a1
a2
(2)
(3)
2020
3030
integral 18 contactor breakers and reversing contactor breakers
(2) Fixing centreintegral 32 contactor breakers and reversing contactor breakers
(3) Fixing centreintegral 63 contactor breakers and reversing contactor breakers
(1) Maximum door thickness for interlocking by
Flush mounting Safety clearance
a a1 a2LD1-LB030 46 – –LD5-LB130 100 – –LA1-LB0 – 13.5 –2 x LA1-LB0 – – 27(1) Centre of operating knob
Flush mounting Safety clearance
a a1 a2LD1-LC030 66 – –LD4-LC30 66 – –LD1-LC040 85 – –LD4-LC40 85 – –LD5-LC30 122 – –LA1-LC010 – 13 –LA1-LC012 – 13 –LA1-LC010 + LA1-LC052 – – 51LA1-LC012 + LA1-LC052 – – 51(1) Maximum door thickness for interlocking byLD4 and LD5(2) Centre of operating knob
Flush mounting Safety clearance
a a1 a2LD1-LD030 90 – –LD4-LD30 90 – –LD5-LD30 181 – –LA1-LC010 – 13 –LA1-LC012 – 13 –LA1-LC010 + LA1-LC052 – – 51LA1-LC012 + LA1-LC052 – – 51
LD4 and LD5(2) Centre of operating knob(3) Fixing centre
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Mounting
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
21173_Ver2.10-EN.fm/3Schneider Electric
19= =
80
66
==
38= =
80
85
52 33
85= =
80
132
99 33
8080
54 170…320
65 182
= =28
105
90
==
243
6359 59
105
105
181
45
27510
510
5
207…357 (LD4)209…359 (LD5)
54
65
148,
5
180…34054
65
=
36
63,2
5
45
=
135
=
63,2
5
90
99
=
135
= =
==
54
54
= =
==
54
54
= =
==
54
54
integral 18Adjustable door interlock mechanism LA9-LB33
integral 32Adjustable door interlock mechanism LA9-LC33 and LA9-LC53For mounting on LD4-LC30 and LC40, LD5-LC30
integral 63Adjustable door interlock mechanism LA9-LC33 and LA9-LC53For mounting on LD4-LD30 and LD5-LD30
Door drillings
For mounting on LD1-LB030 + LB-LB03PLD5-LB130 + LB-LB03P
LD1-LB030 LD5-LB130+ LB-LB03P + LB-LB03P
Door drillings
LD4-LC30 LD4-LC40 LD5-LC30
Door drillings
LD4-LD30 LD5-LD30
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Mounting of accessories
References Integral 18 :pages 21162/2 to 21164/3
References Integral 32 :pages 21165/2 to 21168/3
References Integral 63 : pages 21169/2 to 21172/3
21011_Ver7.11-EN.fm/2 Schneider Electric
13 23 31
14 24 32
9695
9897
4142
LA1-LB015 LA1-LB001
1/L1
3/L2
5/L3
A2A1
A2A1
6/T
3
2/T
1
4/T
2
II I
1817
LA1-LB0341
0506
0708
1615
LA1-LB0311
1615
1817 Auto 0
13 23 31
14 24 3218
17
LA1-LB0211
1615
4142
LA1-LB001
080705
06
Auto 0
1/L1
3/L2
5/L3
/T1
/T2
/T3
A2A1
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
2/T
1
4/T
2
6/T
3
A2A1
1817
A1-LB034
0506
0708
1615
LA1-LB031
1615
1817 Auto 0
13 23 31
14 24 3218
17
LA1-LB021
1615
4142
LA1-LB001
080705
06
Auto 0
Add-on blocks
Contactor breakers integral 18 Reversing contactor breakers integral 18 Current limiter LA9-LB920 +with protection module LB with protection module LB contactor breakers integral 18LD1-LB030 + LB1-LB03P LD5-LB130 + LB1-LB03P with protection module LBLD3-LB130M LD1-LB030 + LB1-LB03P
For contactor breakers LD1 and LD3 For contactor breakers LD1, LD3 and reversing contactor breakers LD5Mounted on LH side Mounted on RH side
For reversing contactor breakers LD5Mounted on LH side
Schemes Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Breaker
Contacts incor-porated in unit
Control knob position
Signalling
Breaker
Control knob position
Signalling
Short-circuitsignalling
Short-circuitsignalling
Short-circuitsignalling
Signalling
Control knob position
Breaker
Trip signalling
Short-circuitsignalling
Signalling
Control knob position
General :pages 21151/2 to 21151/7
References :pages 21162/2 to 21164/3
Dimensions:pages 21009/2 to 21173/3
Contacts incor-porated in unit
21011_Ver7.11-EN.fm/3Schneider Electric
2/T
1
4/T
2
6/T
3
N2
1/L1
3/L2
5/L3
N1
A2A1
2/T
1
4/T
2
6/T
3
N2
1/L1
3/L2
5/L3
N1
2/T
1
4/T
2
6/T
3
N2
A2A1
2/T
1
4/T
2
6/T
3
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
A2 A1
A2 A1
5453
5453(6
3)(6
4)
LA1-LC030
13 23 31
14 24 32
1314
3132
9598
1314
3132
4142
LA1-LC010 LA1-LC012 LA1-LC020 LA1-LC001
9895
96
0805
0618
15
160Auto +
2324
0508
2324
1314
3132
LA1-LC025
2324
9895
9695
ou
ou
1314
3132
4142
LA1-LC021LA1-LC001
2324
5453
6463
LA1-LC031
/T1
/T2
/T3
2/T
1
4/T
2
6/T
3
A2A1
1/L1
3/L2
5/L3
1/L1
3/L2
5/L3
Current limiter LA9-LB920 + Contactor breakers integral 32 with protection module LBLD-LC30 + LB1-LC03M
Add-on blocksFor reversing contactor breakers LD5Mounted on LH side
Contactor breakers integral 32 Reversing contactor breakers integral 32with protection module LB with protection module LBLD1-LC00 + LB1-LC0 LD4-LC0 + LB1-LC0 LD5-LC30 + LB1-LC03M
LB1-LC05L
LB6-LC03M
LB6-LC03M
Add-on blocks Add-on blocksFor contactor breakers LD4 For contactor breakers LD1 or LD4 and reversing contactor breakers LD5Mounted on LH side Mounted on RH side
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Schemes
Isolator
Isolator
1 or 2 LA1-LC030
Short-circuitsignalling
Control knob positionsignalling
Breaker
Trip signalling
General :pages 21151/2 to 21151/7
References :pages 21165/2 to 21168/3
Dimensions :pages 21009/2 to 21173/3
21011_Ver7.11-EN.fm/4 Schneider Electric
2/T
1
4/T
2
6/T
3
A2A1
–Q1
1/L1
3/L2
5/L3
2/T
1
4/T
2
6/T
35/
L3
3/L2
1/L1
A2A1
Q1
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
A2 A1
A2 A1
2/T
1
4/T
2
6/T
3
5453
5453(6
3)(6
4)
LA1-LC030
13 23 31
14 24 32
1314
3132
9598
1314
3132
4142
LA1-LC010 LA1-LC012 LA1-LC020 LA1-LC001
9895
96
0805
0618
15
160Auto +
2324
0508
2324
1314
3132
LA1-LC025
2324
9895
9695
ou
ou
1314
3132
4142
LA1-LC021LA1-LC001
2324
5453
6463
LA1-LC031
2/T
1
4/T
2
6/T
3
Add-on blocks
Contactor breakers integral 63 Reversing contactor breakers integral 63 with protection module LB with protection module LBLD1-LD030 + LB1-LD03 LD4-LD30 + LB1-LD03 LD5-LD30 + LB1-LD03M or LD03P
LB6-LD03M LB6-LD03M
For contactor breakers LD4 For contactor breakers LD1 or LD4 and reversing contactor breakers LD5Mounted on LH side Mounted on RH side
For reversing contactor breakers LD5 Mounted on LH side
Schemes Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Isolator
1 or 2 LA1-LC030
Control knob positionsignalling
Short-circuitsignalling
Tripsignalling
Breaker
Isolator
General :pages 21151/2 to 21151/7
References :pages 21169/2 to 21172/3
Dimensions :pages 21009/2 to 21173/3
21011_Ver7.11-EN.fm/5Schneider Electric
+
– (0V)
E1
E3
E2
A1
A2
+
– (0V)
E1
E2
A1
A2
+
–(0V)
E1
E3
E2
A1
A2
+–
KA1
A2
E1
+
E2
–
+ E1
– E2
A1
A2
+ E1
– E2
A1
A2
KA1
A2
A1
A2
t0
D1
D2
U<
KA1
A2
E1
+
E2
–
KA1
A2
A1 A
2
t0
B2
C1
C2
MB4
B2
B3
B1
KA1
A2
E1
+
E2
–
KA1
A2
A2
B1
A1
(1)
I/O
AUTO/MAN
The use of instantaneous auxil-iary contact block LA1-LC020prevents the use of tripping de-vices or electrical reset devices
(1) For contactor breakers and reversing contactor breakers already fitted with an LA1-LC010 or LA1-LC012 instantaneous auxiliary contact block.Interface modules
Interface modules
Voltage convertersLA1-LB080, LC080, LD080(supplied with contactor breakers for control circuit operation)
(1) PLC.
Tripping devices (1) for LD1, LD4, LD5 Remote electrical reset devices (1) for LD1, LD4, LD5LA1-LC071 LA1-LC070, LC072 LA1-LC052
LA4-DW solid state LA4-DF relay output LA4-DL relay output(with manual override)
LA1-LC180, LD180 LA1-LC580, LD580
Switching by control contact Switching by “Low level” input24 or 48 V 24 or 48 V
Electronic serial timer modules Control modules Automatic-Manual-StopLA4-DT On-delay LA4-DR Off-delay LA4-DM
Motor starters - open version 1
integral 18, 32 and 63 contactor breakers and reversing contactor breakers
Schemes
Auto
0
Lowlevelinput
Sup
ply
TRIP +RESET
General :pages 21151/2 to 21151/7
References :pages 21162/2 to 21164/3,
21165/2 to 21168/3,21169/2 to 21172/3
Dimensions:pages 21009/2 to 21173/3
24581_Ver2.10-EN.fm/2 Schneider Electric
TeSys motor starters - open versionAdaptors for use with busbar systems
Presentation
Reducing the installation time of components is an important factor that also increases productivity.The comprehensive range of adaptors and mounting accessories allows this objective to be achieved.There are numerous advantages:- saving of space in enclosures,- reduced size of enclosures,- reduced wiring time,- increased protection of personnel against accidental direct contact (IP 20) through the use of insulated mounting rails,- flexibility and modularity of equipment- reliable operation of the equipment with easier maintenance.
DescriptionPower distribution is achieved by a 3-pole or 5-pole busbar system.The adaptors clip directly onto the busbar system, providing instantaneous electrical connection.Busbar system pitch: 40 or 60 mm.These adaptors allow mounting of motor starter components such as:- GV2-ME, GV2-P or GV3-ME motor circuit-breakers,- K and D range contactors up to 38 A,- integral 18, 32 and 63 contactor breakers,- LH4-N1 and LH4-N2 soft starters.They are available in different sizes to allow easy installation of varying component combinations.These adaptors can be used in conjunction with interface modules communicating with an AS-i bus, see pages 21087/2 to 21087/7. This enables motor starters to be set up on an AS-i bus, bringing all the advantages of the 2 technologies.
General characteristics
Conforming to standards IEC 60439Degree of protection IP 20 with insulated mounting rail LA9-Z098
Temperature resistance °C 120
Rated frequency of current Hz 50/60Rated operational current
Depending on type of busbar mm 12 x 5 12 x 10 15 x 5 20 x 5 20 x 10 25 x 5 30 x 5 30 x 10and at 35 °C A 200 360 250 320 520 400 450 630
Coefficient K to be applied °C 35 40 45 50 55 60according to ambient temperature K 1 0.9 0.75 0.65 0.55 0.35
Rated insulation voltage V 690 conforming to IEC 60947-1 and NF C 20-040Rated operational voltage V 690Rated permissible peak current
With busbar support LA9-Z11098 and Z11099 LA9-Z11100 and Z11101Busbar size mm 12 x 5 12 x 10 12 x 5 12 x 10 20 x 10 30 x 5 30 x 10Rated current kA 35 35 30 35 35 45 55
Maximum let-through energy A2s 1 x 108 4 x 108 1 x 108 11 x 108 11 x 108 6.2 x 108 24.8 x 108
Support fixing, by screws mm 4 x 6 4 x 5
Cabling, by connectors LA9-Z11103 LA9-Z11104 LA9-Z11105Min Max Min Max Min Max
Flexible cable with cable end mm2 4 35 16 70 120 120Multi-strand cable mm2 4 35 16 70 35 120Solid cable mm2 4 35 – – – –Tightening torque mm2 1 x 6 1 x 10 3 x 12
Characteristics of adaptors for use with busbar systems (3-phase)
LA9- LA9- LA9- LA9- LA9- LA9-Types Z32196, Z32199, Z32200, Z32343, Z32344, Z32345 Z32253 Z32248
Z32228, Z32229. Z32208 to Z32210. Z40132, Z60132, Z32249Z32238, Z32239 Z32232 Z40232, Z60232
Degree of protection to IEC 60529 IP 20
Conductor c.s.a. mm2 4 6 6 10 16 2.5(colour: black) AWG 12 AWG 10 AWG 10 AWG 8 – AWG 22/14
Type of conductor insulation PVC 105 °C –
Permissible current A 25 32 32 63 80 15
Rated insulation voltage V 690 conforming to NF C 20-040 and IEC 60947-1 250
Rated peak current kA 6 6 6 10 10 –Maximum let-through energy A2s 2 x 105 2 x 105 2 x 105 3 x 105 3 x 105 –
Presentation, characteristics
LA9-Z32199
References :pages 24582/2 to 24582/9
Dimensions :pages 24583/2 and 24583/3
24581_Ver2.10-EN.fm/3Schneider Electric
50
40
30
20
10
0200 300 400 500 600
12 x 5 et 12 x 10
70
60
50
40
30
20200 300 400 500 600
12 x 5
12 x 10et 20 x 10
30 x 5
30 x 10
,2
,1
,0
,9
,8
,7
,6
,5
,4
,3
,2
,1
,0
,9
,8
,7
,6
,5
,4
,350 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125
0°C
51015
2025
3035404550
5560
65
TeSys motor starters - open versionAdaptors for use with busbar systemsShort-circuit resistance
Determining the spacing between busbar supports (1)
Busbar system with 40 mm pitch Busbar system with 60 mm pitch
(1) Depending on the prospective short-circuit current.
Current capacity of busbars
For an ambient temperature of 35°C and a busbar temperature of 65°CC.s.a. mm2 12 x 5 15 x 5 20 x 5 25 x 5 30 x 5 12 x 10 20 x 10 30 x 10Permissible current A 200 250 320 400 450 360 520 630
If the above climatic conditions are modified, consult the chart below to find the correction factor K2 to be applied.
Example: in normal operating conditions, a set of 30 x 10 tinned busbars can withstand a continuous load of 630 A. For a load of 800 A, the correction coefficient K2 to be applied will be 1.3 ( 800 A ). It follows that the temperature riseof the busbars will be 82.5 °C. 630 A
Characteristics
References :pages 24582/2 to 24582/9
Dimensions :pages 24583/2 and 24583/3
Factor k2
Am
bie
nt t
emp
era
ture
Busbar tempterature (°C)
Pe
ak c
urr
ent I
pk
(kA
)
Busbar support fixing centres (mm) Busbar support fixing centres (mm)
Pe
ak c
urr
ent I
pk
(kA
)
24582-EN_Ver2.10.fm/2 Schneider Electric
5003
34
5003
36
5003
37
500
335
40 mm : LA9-Z32196
40 mm : LA9-Z3222860 mm : LA9-Z32229
40 mm : LA9-Z4013260 mm : LA9-Z60132
40 mm : LA9-Z3219960 mm : LA9-Z32200
GV2-ME, GV2-P
GV2-ME, GV2-P
GV2-ME, GV2-P
GV2-ME, GV2-P
LC1, LP1, LP4-K06...K12
LC1, LP1, LP4-K06...K12
LC1-D09...D38
LC1-D09...D38
24582-EN_Ver2.10.fm/3Schneider Electric
TeSys motor starters - open versionAdaptors for use with busbar systems
Adaptors for busbar systems with 40 mm pitch - non-reversing
Motor starter type Operational Width Sold Unit Weightcurrent x height in referenceAC-3 of lots of440 V adaptorA mm kg
GV2-ME + LC1, LP1, LP4-K06…K12 12 45 x 139 4 LA9-Z32196 0.788orGV2-P
45 x 182 4 LA9-Z32228 0.984
GV2-ME + LC1-D09…D38 32 45 x 182 4 LA9-Z40132 0.984orGV2-P
54 x 182 4 LA9-Z32199 1.144
Adaptors for busbar systems with 60 mm pitch - non-reversing
Motor starter type Operational Width Sold Unit Weightcurrent x height in referenceAC-3 of lots of440 V adaptorA m km
GV2-ME + LC1, LP1, LP4-K06…K12 12 45 x 182 4 LA9-Z32229 0.984orGV2-P
GV2-ME + LC1-D09…D38 32 45 x 182 4 LA9-Z60132 0.984orGV2-P
54 x 182 4 LA9-Z32200 1.220
References
Characteristics : pages 24581/2 and 24581/3
Dimensions : pages 24583/2 and 24583/3
24582-EN_Ver2.10.fm/4 Schneider Electric
5003
39
500
340
5003
41
500
342
40 mm : LA9-Z32232
60 mm : LA9-Z32210
40 mm : LA9-Z4023260 mm : LA9-Z60232
40 mm : LA9-Z3220860 mm : LA9-Z32209
GV2-ME, GV2-P
GV2-ME, GV2-P
GV2-ME, GV2-P
GV2-ME, GV2-P
LC2, LP2, LP5-K06...K12
LC2, LP2, LP5-K06...K12
LC2-D09...D38
LC2-D09...D38
24582-EN_Ver2.10.fm/5Schneider Electric
TeSys motor starters - open versionAdaptors for use with busbar systems
Adaptors for busbar systems with 40 mm pitch - reversing
Motor starter type Operational Width Sold Unit Weightcurrent x height in referenceAC-3 of lots of440 V adaptorA mm kg
GV2-ME + LC2, LP2, LP5-K06…K12 12 90 x 139 2 LA9-Z32232 0.788orGV2-P
GV2-ME + LC2-D09…D38 32 90 x 182 4 LA9-Z40232 1.884or GV2-P
135 x 182 1 LA9-Z32208 0.638
Adaptors for busbar systems with 60 mm pitch - reversing
Motor starter type Operational Width Sold Unit Weightcurrent x height in referenceAC-3 of lots of440 V adaptorA mm kg
GV2-ME + LC2, LP2, LP5-K06…K12 12 90 x 182 4 LA9-Z32210 1.868orGV2-P
GV2-ME + LC2-D09…D38 32 90 x 182 4 LA9-Z60232 1.948orGV2-P
135 x 182 1 LA9-Z32209 0.651
References
Characteristics : pages 24581/2 and 24581/3
Dimensions : pages 24583/2 and 24583/3
24582-EN_Ver2.10.fm/6 Schneider Electric
GV2-ME, GV2-P
5003
49
500
350
GV3-ME
GV2-ME, GV2-P
LH4-N2
5003
51
500
352
LD5-LB, LC
500
354
5003
53
60 mm : LA9-Z32238 60 mm : LA9-Z32239
60 mm : LA9-Z32343
60 mm : LA9-Z32345
60 mm : LA9-Z32344
LH4-N1
LD1-LDLD4-LD
LD1-LB, LCLD4-LC
60 mm : LA9-Z32253
24582-EN_Ver2.10.fm/7Schneider Electric
TeSys motor starters - open versionAdaptors for use with busbar systems
Adaptors for busbar systems with 60 mm pitch - non-reversing
Motor starter type Operational Width Sold Unit Weightcurrent x height in referenceAC-3 of lots of440 V adaptorA mm kg
Integral LD1-LB 18 67.5 x 182 1 LA9-Z32343 0.590
Integral LD1, LD4-LC 32 67.5 x 182 1 LA9-Z32343 0.590
Integral LD1, LD4-LD 63 108 x 244 1 LA9-Z32345 0.887
GV2-ME + LH4-N1 25 45 x 242 4 LA9-Z32238 1.476orGV2-P
LH4-N2 25 90 x 242 2 LA9-Z32239 1.476
GV3-ME 80 72 x 182 1 LA9-Z32253 0.347
Adaptors for busbar systems with 60 mm pitch - reversing
Motor starter type Operational Width Reference Weightcurrent x height AC-3 of440 V adaptorA mm kg
Integral LD5-LB 18 135 x 182 LA9-Z32344 1.001
Integral LD5-LC 32 135 x 182 LA9-Z32344 1.001
References
or
Characteristics : pages 24581/2 and 24581/3
Dimensions : pages 24583/2 and 24583/3
24582-EN_Ver2.10.fm/8 Schneider Electric
LA9-Z11099 LA9-Z11098 LA9-Z11103
LA9-Z32936 LA9-Z098pp
LA9-Z32ppp
40
mm
60 m
m
LA9-Z11099LA9-Z11098
LA9-Z32248LA9-Z32249
LA9-Z11101LA9-Z11100
LA9-Z098ppLA9-Z32ppp
LA9-Z11105LA9-Z91413
LA9-Z11102
LA9-Z11100
LA9-Z11104LA9-Z11101
LA9-Z11118 LA9-Z11105
LA9-Z32248LA9-Z32249
24582-EN_Ver2.10.fm/9Schneider Electric
TeSys motor starters - open versionAdaptors for use with busbar systems
(1) For dimensions and rated operational current, see pages 24581/2 and 24581/3.(2) Supplied complete with protective cover.
Accessories for busbar sets with 40 mm pitch
Description Sold Unit Weightin referencelots of kg
Busbar system supports (1) 3-pole 10 LA9-Z11098 1.040
3-pole + N + T 10 LA9-Z11099 1.400
Insulated rails (length 1 m) For busbars, 10 LA9-Z09818 0.420 thickness 5 mm
For busbars, 10 LA9-Z09820 0.940thickness 10 mm
Connector Capacity 35 mm2 50 LA9-Z11103 2.300
Protective cover For connector 1 LA9-Z91413 0.160LA9-Z11103
Side module, 13.5 x 182 mm For increasing the 4 LA9-Z32936 0.472width of the adaptor
Plug-in terminal blocks Width 54 mm 1 LA9-Z32248 0.066for use with LA9-Z32ppp (7-pole)
Width 45 mm 1 LA9-Z32249 0.055
Accessories for busbar sets with 60 mm pitch
Description Sold Unit Weightin referencelots of kg
Busbar system supports (1) 3-pole 10 LA9-Z11100 2.100
3-pole + N 10 LA9-Z11101 2.660
Insulated terminal shroud 3-pole 10 LA9-Z11102 0.310
4-pole 10 LA9-Z11118 0.380
Insulated rails (length 1 m) For busbars, 10 LA9-Z09819 0.800thickness 5 mm
For busbars, 10 LA9-Z09820 0.940thickness 10 mm
Connectors Capacity 70 mm2 25 LA9-Z11104 1.875
3-pole 1 LA9-Z11105 (2) 0.719capacity 120 mm2
Protective cover For connector 1 LA9-Z91413 0.160LA9-Z11104
Plug-in terminal blocks Width 54 mm 1 LA9-Z32248 0.066for use with LA9-Z32ppp (7-pole)
Width 45 mm 1 LA9-Z32249 0.055
References of mounting and cabling accessories
Characteristics : pages 24581/2 and 24581/3
Dimensions : pages 24583/2 and 24583/3
4583 Ver2.00-EN.fm/2 Schneider Electric
(1) LC = Low Consumption
GV2-ME or P + LCp, LPp-K GV2-ME or P + LCp-D
Motor starter combinations, non-reversing
Motor starter type a b 40 mm system 60 mm system e1c Adaptor c Adaptora c or LC(1) reference a c or LC(1) Other reference
GV2-ME + LC1, LP1 or LP4-K06 to K12 45 152 125 125 LA9-Z32196 – – – – 40
GV2-P + LC1, LP1 or LP4-K06 to K12 45 152 145 145 LA9-Z32196 – – – – 40
GV2-ME + LC1, LP1 or LP4-K06 to K12 45 184 125 125 LA9-Z32228 135 135 – LA9-Z32229 40
GV2-P + LC1, LP1 or LP4-K06 to K12 45 184 145 145 LA9-Z32228 155 155 – LA9-Z32229 40
GV2-ME + LC1-D09 to D18 45 200 139 139 LA9-Z40132 149 149 – LA9-Z60132 40
GV2-P + LC1-D09 to D18 45 200 142 142 LA9-Z40132 152 152 – LA9-Z60132 40
GV2-ME + LC1-D25 to D38 45 200 146 146 LA9-Z40132 156 156 – LA9-Z60132 40
GV2-P + LC1-D25 to D38 45 200 146 146 LA9-Z40132 156 156 – LA9-Z60132 40
GV2-ME + LC1-D09 to D18 54 200 131 137 LA9-Z32199 141 147 – LA9-Z32200 33
GV2-P + LC1-D09 to D18 54 200 142 142 LA9-Z32199 152 152 – LA9-Z32200 33
GV2-ME + LC1-D25 to D38 54 200 140 146 LA9-Z32199 150 156 – LA9-Z32200 33
GV2-P + LC1-D25 to D38 54 200 142 146 LA9-Z32199 152 156 – LA9-Z32200 33
Integral 18 LD1 68 184 – – – – – 195 LA9-Z32343 33
Integral 32 LD1, LD4 68 184 – – – – – 225 LA9-Z32343 33
Integral 63 LD1, LD4 108 244 – – – – – 250 LA9-Z32345 50
GV2-ME + LH4-N1 45 242 – – – – – 163 LA9-Z32238 33
GV2-P + LH4-N1 45 242 – – – – – 163 LA9-Z32238 33
GV2-ME + LH4-N2 90 242 – – – – – 163 LA9-Z32239 33
GV2-P + LH4-N2 90 242 – – – – – 163 LA9-Z32239 33
GV3-ME 72 182 – – – – – 180 LA9-Z32253 50
X electrical clearance Ue ≤ 415 V Ue = 440 V Ue = 500 and 600 VGV2-ME 40 40 40GV2-P 40 80 120Integral 18 or 32 30 20 30Integral 63 20 20 20GV3-ME 40 40 50
Dimensions Motor starters - open versionAdaptors for use with busbar systemsMotor starter combinations for customer assembly
Characteristics : pages 24581/2 and 24581/3
References :pages 24582/2 to 24582/9
24583 Ver2.00-EN.fm/Schneider Electric
Motor starters - open versionAdaptors for use with busbar systemsMotor starter combinations for customer assembly
(1) LC = Low Consumption
GV2-ME or P + LC2, LP2-K Integral GV2-ME or P + LH4-Npp
Motor starter combinations, reversing
Motor starter type a b 40 mm system 60 mm system e1c Adaptor c Adaptora c or LC(1) reference a c or LC(1) LD5 reference
GV2-ME + LC2, LP2-K06 to K12 90 150 125 125 LA9-Z32232 – – – – 40
GV2-P + LC2, LP2-K06 to K12 90 150 145 145 LA9-Z32232 – – – – 40
GV2-ME + LC2, LP2-K06 to K12 90 184 – – – 135 135 – LA9-Z32210 40
GV2-P + LC2, LP2-K06 to K12 90 184 – – – 155 155 – LA9-Z32210 40
GV2-ME + LC2-D09 to D18 90 200 139 139 LA9-Z40232 149 149 – LA9-Z60232 40
GV2-P + LC2-D09 to D18 90 200 142 142 LA9-Z40232 152 152 – LA9-Z60232 40
GV2-ME +LC2-D25 to D38 90 200 146 146 LA9-Z40232 156 156 – LA9-Z60232 40
GV2-P + LC2-D25 to D38 90 200 146 146 LA9-Z40232 156 156 – LA9-Z60232 40
GV2-ME + LC2-D09 to D18 135 203 131 137 LA9-Z32208 141 147 – LA9-Z32209 33
GV2-P + LC2-D09 to D18 135 203 142 142 LA9-Z32208 152 152 – LA9-Z32209 33
GV2-ME + LC2-D25 to D38 135 201 140 146 LA9-Z32208 150 156 – LA9-Z32209 33
GV2-P + LC2-D25 to D38 135 201 142 146 LA9-Z32208 152 156 – LA9-Z32209 33
GV2-ME + LP5-K06 to K12 90 150 – 125 LA9-Z32232 – – – – 40
GV2-P + LP5-K06 to K12 90 150 – 145 LA9-Z32232 – – – – 40
GV2-ME + LP5, K06 to K12 90 184 – – – – 135 – LA9-Z32210 40
GV2-P + LP5, K06 and K12 90 184 – – – – 155 – LA9-Z32210 40
Integral 18 LD5 135 184 – – – – – 195 LA9-Z32344 33
Integral 32 LD5 135 184 – – – – – 195 LA9-Z32344 33
Dimensions
Characteristics : pages 24581/2 and 24581/3
References : pages 24582/2 to 24582/9
0243Q-EN_Ver2.22.fm/2 Schneider Electric
General selection guide TeSys enclosed starters 2
Applications D.O.L. starters
Type Standard starters Starters for safetyapplications
Standard power ratings 4…37 kW 0.06…45 kW 0.55…30 kW 0.37…5.5 kW 0.25…45 kW 2.2…45 kW 0.06…11 kWof 3-phase motors in AC-3 400/415 V
Starters
Manual p p p – – – p
Auto – – – p p p –
Isolation
Switch p – – – – – –
Circuit-breaker – p p p – – p
Disconnector – – – – – p –
Protection
Short-circuit – p p p – p p
Overload – p p p p p p
Communication – – – – – – –
References VpF GV2-ME GV2-LC LE1-GVME LE1-M LE4-K GV2-ME
Non reversing VCFN GV3-CE GV-NGC LE1-D LE4-D
VpFX
Reversing– – – – LE2-K LE8-K
LE8-D
LE2-D
–
LE2-D
Pages 23008/2 and 23008/3
80263/2 and 80263/3
24110/2 24111/2 24101/2, 24101/3 and 24105/2
24103/2 and 24103/3
21058/2 and 21058/3
(1) Please consult your Regional Sales Office.
0243Q-EN_Ver2.22.fm/3Schneider Electric
2
Soft start units Variable speed controllers
AS-i bus Standard Electronicstarters star-delta soft start -
starters soft stop units
0.06…9 kW 0.06…9 kW 0.06…5.5 kW 5.5… 7.5… 0.37…11 kW 0.37…4 kW 0.75…75 kW132 kW 75 kW
– – – – – p (LH7-0M) p p
p p p p p p (LH7-KP) p p
p – – – – – p p (from 7.5 kW)
p p p – – p – p (up to 5.5 kW)
– – – – p – – –
p p p – p p p p
p p p p p p p p
– – p – – – – p
LG1-K LG7-K LF1-M LE3-K LE6-D LH7-0 ATV-28E ATV-58E
LG1-D LG7-D LF1-P LE3-D LE3-D LH7-K
LJ7-K LF7-P LE3-F(1)
– LG8-K LF2-M – – – ATV-28E ATV-58E
LJ8-K LF2-P
LF8-P
24026/3 24026/2 and 24026/4,26044/2 and 26044/3
24084/2 to 24088/3
24106/2 and 24106/3
24108/2 and24108/3
24073/2 and 24073/3
(1)
23008_Ver3.10-EN.fm/2 Schneider Electric
Enclosed starters 2
VARIO enclosed switch disconnectors, pre-assembled
- 3-pole switch disconnectors, 10 to 140 A, rotary operator, conforming to IEC 947-4-1 and IEC 204.- Padlockable handle (padlocks not included).- IP 65 degree of protection enclosure, lead sealable and lockable.- Lockable cover in position “I” (ON) up to 63 A rating.- Marking on front plate
3-pole main and emergency stop switch disconnectors (1)
- 3-pole switch disconnectors, 10 to 32 A, rotary operator, conforming to IEC 947-4-1.- Degree of protection IP 55.
3-pole main and emergency stop switch disconnectors (1)
(1) For characteristics of switch disconnectors, please consult your Regional Sales Office.(2) For VCF and VBF enclosures, see page 23009/2. For VCFN enclosures, see page 23009/3.
Enclosed switch disconnectors for high performance applications
Operator Ithe Power Incorp- Possible Reference WeightHandle Front plate AC-23 orated attach-
Dimensions at 400 V switch ments body (2)
mm A kW kg
Red Yellow 10 4 V02 2 VCF-02GE 0.500Padlockable, 60 x 60up to 3 locks 16 5.5 V01 2 VCF-01GE 0.500(Ø 4 to 8 shank)
20 7.5 V0 2 VCF-0GE 0.500
25 11 V1 2 VCF-1GE 0.500
32 15 V2 2 VCF-2GE 0.500
50 22 V3 3 VCF-3GE 0.930
63 30 V4 3 VCF-4GE 0.930
Red cross Yellow 100 37 V5 1 VCF-5GE 2.190type 90 x 90Padlockable,up to 3 locks 140 45 V6 1 VCF-6GE 2.190(Ø 4 to 8 shank)
3-pole main stop switch disconnectors (1)
Black Black 10 4 V02 2 VBF-02GE 0.500Padlockable, 60 x 60up to 3 locks 16 5.5 V01 2 VBF-01GE 0.500(Ø 4 to 8 shank)
20 7.5 V0 2 VBF-0GE 0.500
25 11 V1 2 VBF-1GE 0.500
32 15 V2 2 VBF-2GE 0.500
50 22 V3 3 VBF-3GE 0.930
63 30 V4 3 VBF-4GE 0.930
Black cross Black 100 37 V5 4 VBF-5GE 2.190type 90 x 90Padlockable,up to 3 locks 140 45 V6 4 VBF-6GE 2.190(Ø 4 to 8 shank)
Enclosed switch disconnectors for standard applications
Red Yellow 10 4 VN-12 2 VCFN-12GE (2) 0.422Padlockable, 60 x 60either by 1 lock 16 5.5 VN-20 2 VCFN-20GE (2) 0.422(Ø 8 shank)or by 3 locks 20 7.5 V0 0 VCFN-25GE 0.512(Ø 6 shank)
25 11 V1 0 VCFN-32GE 0.512
32 15 V2 0 VCFN-40GE 0.512
References
VCF-0GE
VCF-3GE
VBF-0GE
VCFN-12GE
Dimensions :page 23010/2
Schemes :page 23010/3
23008_Ver3.10-EN.fm/3Schneider Electric
Enclosed starters 2
VARIO enclosed switch disconnectors, assembled by user
IP 65 enclosure with red padlockable handle operator and yellow front plate (for mounting a main or emergency stop switch disconnector)
(1) See pages 23009/2 and 23009/3.(2) For characteristics of switch disconnectors, please consult your Regional Sales Office.
Empty enclosures
For switch Ithe Possible Reference Weightbody attachments (1)
A kg
VN-12, VN-20 10…32 2 VCFX-GE1 0.340V02…V2
V02…V2 10…32 4 VCFX-GE4 0.660
V3 and V4 50…63 3 VCFX-GE2 0.660
4 VCFX-GDXE 0.660
IP 65 enclosure with black padlockable handle and black front plate (for mounting main stop switch disconnector) For switch Ithe Possible Reference Weightbody attachments (1)
A kg
VN-12, VN-20 10…32 2 VBFX-GE1 0.340V02…V2
V02…V2 10…32 4 VBFX-GE4 0.660
V3 and V4 50…63 3 VBFX-GE2 0.660
4 VBFX-GDXE 0.660
Switch bodies for standard applications (2)
Description Rating Reference WeightA kg
3-pole switch disconnectors 10 VN-12 0.110
16 VN-20 0.110
Switch bodies for high performance applications (2)
Description Rating Reference WeightA kg
3-pole switch disconnectors 10 V02 0.200
16 V01 0.200
20 V0 0.200
25 V1 0.200
32 V2 0.200
50 V3 0.200
63 V4 0.200
References
VBFX-GE2
V0
Dimensions :pages 23010/2 and 23010/3
Schemes :page 23010/3
23009_Ver2.10-EN.fm/2 Schneider Electric
1 add-on module on each side of the switch body.
2 add-on modules on each side of the switch body.
Note: The add-on modules mounted next to the switch body are main poles. Maximum of 3 main poles per switch body.(1) Late make N/O contact, early break N/C contact
Add-on modules for enclosures VCF and VBF
Description Rating Reference WeightA kg
Main pole module 10 VZ-02 0.050(mounted in enclosure)
16 VZ-01 0.050
20 VZ-0 0.050
25 VZ-1 0.050
32 VZ-2 0.050
50 VZ-3 0.100
63 VZ-4 0.100
Neutral pole modules 10 to 32 VZ-11 0.050with early make andlate break contacts 50 and 63 VZ-12 0.100
100 and 140 VZ-13 0.250
Earthing modules 10 to 32 VZ-14 0.050
50 and 63 VZ-15 0.100
100 and 140 VZ-16 0.250
Auxiliary contact block modules N/O + N/C (1) VZ-7 0.050with 2 auxiliary contacts
N/O + N/O VZ-20 0.050
Maximum number of add-on modules which can be fitted on a switch body
VZ-7 or VZ-20 + V0 + VZ-7 or VZ-20
or or
VZ-11 or VZ-12 +V0
+ VZ-11 or VZ-12
or or
VZ-14 or VZ-15 + to + VZ-14 or VZ-15
orV4
or
VZ-0/VZ-0 to VZ-4 + + VZ-0/VZ-0 to VZ-4
VZ-0 + VZ-0 + V0 + VZ-0 + VZ-7 or VZ-20 or VZ-11 or VZ-14
VZ-0 + VZ-0 + V0 + VZ-0 + VZ-7 or VZ-20 or VZ-11 or VZ-14
VZ-1 + VZ-1 + V1 + VZ-1 + VZ-7 or VZ-20 or VZ-11 or VZ-14
VZ-2 + VZ-2 + V2 + VZ-2 + VZ-7 or VZ-20 or VZ-11 or VZ-14
VZ-3 + VZ-3 + V3 + VZ-3 + VZ-7 or VZ-20 or VZ-12 or VZ-15
VZ-4 + VZ-4 + V4 + VZ-4 + VZ-7 or VZ-20 or VZ-12 or VZ-15
Enclosed starters 2
VARIO enclosed switch disconnectorsAdd-on modules
References
VZ-11VZ-0
VZ-20VZ-15
Schemes :page 23010/3
23009_Ver2.10-EN.fm/3Schneider Electric
Enclosed starters 2
VARIO enclosed switch disconnectorsAdd-on modules
Add-on modules for enclosures VCFN-12GE and 20GE
Description Rating Reference WeightA kg
Main pole module 10 VZN-12 0.020
16 VZN-20 0.020
Neutral pole module with early 10 and 16 VZN-11 0.020make and late break contacts
Earthing module 10 and 16 VZN-14 0.016
Auxiliary contact block module 1 late make N/O contact VZN-05 0.020
1 early break N/C contact VZN-06 0.020
Maximum number of add-on modules which can be fitted on switch body
VZN-12 or VZN-20 + + VZN-12 or VZN-20
VN-12 or
or VZN-11
or VN-20 or
VZN-05 or VZN-06
or
VZN-05 or VZN-06 VZN-14
References
VZN-11
VZN-14
VZN-05
Schemes :page 23010/3
23010_Ver2.10-EN.fm/2 Schneider Electric
82,5106
131
90
==
c
c1
b
a
= =
H
126
191
190
220
201
=
=
280
Enclosed starters 2
VARIO enclosed switch disconnectors
VCFN-12GE to VCFN-40GE
VCF or VBF-5GE and 6GE
Cable glands: 2 x 16 P top and bottom
VCF or VBF-02GE to 4GEVCFX or VBFX-GE1 to GE4
a b c c1 HVF-02GE to VF-2GE, VFX-GE1 (1) 90 146 85 131 130VF-3GE and VF-4GE (2) 150 170 106 152 164VFX-GE2 and VFX-GE4 (2) 150 170 106 152 164
(1) Cable glands 2 x 16 P top and bottom(2) Cable glands 2 x 16/21/29 P top and bottom
Dimensions
References :page 23008/2
Schemes :page 23010/3
23010_Ver2.10-EN.fm/3Schneider Electric
1/
L12/
T1
3/L2
4/T
2
5/L3
6/T
3
222113
14
1314 24
23
1314 22
21
86
162
130
168
180
=
=
220
Enclosed starters 2
VARIO enclosed switch disconnectors, for customer assembly
Empty enclosuresVCFX or VBFX-GDXE
Schemes
Auxiliary contact blocks
Switch disconnectors Main pole Neutral poleenclosed module moduleor switch bodies
VZ-7 VZ-20 VZN-05 VZN-06
Dimensions
References :page 23008/3
21020-EN_Ver6.1.fm/2 Schneider Electric
GV2-MC
GV2-SN
GV2-E01
GV2-K011
GV2-V01
GV2-MP
GV2-CP
GV2-K04
4
21020-EN_Ver6.1.fm/3Schneider Electric
Safety solutions using Preventa 4
Enclosed thermal-magnetic motor circuit breakers model GV2-MEand accessories, assembled by customer
Motor-circuit breakers and accessories: see pages 4/28 and 4/29.The starter consisting of an enclosed motor circuit-breaker GV2-ME conforms to IEC 947-4-1.
Ithe en-
(1) The GV2-MCK04 enclosure has a GV2-K04 mushroom head Stop pushbutton fitted as standard.(2) Supplied with IP 55 sealing kit. For use with GV2-M01.(3) Padlockable in “Off” position using Ø 4 to 8 mm shank padlocks.
Thermal-magnetic motor circuit breakers GV2-ME
GV2- ME01 ME02 ME03 ME04 ME05 ME06 ME07 ME08 ME10 ME14 ME16 ME20 ME21 ME22
closed (A)0.16 0.25 0.4 0.63 1 1.6 2.5 4 6.3 9 13 17 21 23
Enclosures for thermal-magnetic motor circuit breakers GV2-ME
Type Degree of protection Possible attachments Reference Weighton side of GV2-MELeft Right kg
Surface IP 41 1 1 GV2-MC01 0.290mountingDouble,insulated with IP 55 1 1 GV2-MC02 0.300protective or GV2-MCK04 (1) 0.420conductor.Sealable IP 55 for 1 1 GV2-MC03 0.300cover temperature < + 5 °C
Flush IP 41 (front face) 1 1 GV2-MP01 0.115mounting IP 41 (reduced flush mounting) – 1 GV2-MP03 0.115with protective IP 55 (front face) 1 1 GV2-MP02 0.130conductor IP 55 (reduced flush mounting) – 1 GV2-MP04 0.130
Front plate
Description Sold in Unit Weightlots of reference kg
For direct control, through a panel IP 55 1 GV2-CP21 0.800of a chassis-mounted GV2-ME
Accessories common to all enclosures (to be ordered separately)
Padlocking device (2) 1 to 3 padlocks 1 GV2-V01 0.075for GV2-ME operator (padlocking is only Ø 4 to 8 mmpossible in “O” position)
Mushroom Spring return (2) 1 GV2-K011 0.052head“Stop” Latching (2) Key release 1 GV2-K021 0.160pushbutton IP 55 key n° 455Ø 40 mm,red Turn to 1 GV2-K031 0.115
release 1 GV2-K04 (3) 0.120
Sealing kit For enclosures IP 55 10 GV2-E01 0.012and front plate IP 55
for θ < + 5 °C 10 GV2-E02 0.012
Neutral terminal 100 AB1-VV635UBL 0.015
Partition 50 AB1-AC6BL 0.003Description Voltage Colour Sold in Unit Weight
V lots of reference kg
Neon 110 Green 10 GV2-SN13 0.019indicator Red 10 GV2-SN14 0.019light Orange 10 GV2-SN15 0.019
Clear 10 GV2-SN17 0.019220/240 Green 10 GV2-SN23 0.019
Red 10 GV2-SN24 0.019Orange 10 GV2-SN25 0.019Clear 10 GV2-SN27 0.019
380/440 Green 10 GV2-SN33 0.019Red 10 GV2-SN34 0.019Orange 10 GV2-SN35 0.019Clear 10 GV2-SN37 0.019
References
Dimensions :page 21026/2
Schemes :page 21026/3
21026-EN_Ver4.1.fm/2 Schneider Electric
147
84
145,5
(1) 2xØ5,3x6,3
=
130
==
=93
147
84
(1)
93 =
130
==
=
1...4
12
76
93
7,5
118
21
133
= =62
11,5
1...6
a12
140
=12
7=
= 93,5 =
106,5
71
936,5
117
133
71
= =
9,5
Safety solutions using Preventa 4
Enclosed thermal-magnetic motor circuit breakers model GV2-ME
Surface mounting enclosure GV2-MCK04
Flush mounting enclosures GV2-MP0 (panel cut-out)
Surface mounting enclosures GV2-MC0
(1) 4 knock-outs for 16 mm plastic cable gland or 16 mm conduit.
(1) 4 knock-outs for 16 mm plastic cable gland or 16 mm conduit.
GV2-MP0 GV2-MP01, MP02 GV2-MP03, MP04 Front plate GV2-CP21
GV2- aMP01, MP02 –MP03, MP04 86
Dimensions,mounting
21026-EN_Ver4.1.fm/3Schneider Electric
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
1314 12
11 1314 22
21 1314
2324
9798
535452
51
969553
549695
9798
5152
(62) 32
(61) 31 43 (73)
44 (74)
(64) 34
(63) 33 43 (73)
44 (74)
050608
D1
D2
C1
C2
D1
D2
E1
E2
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
D1
D2
E2
E1
GV2-ME
Instantaneous auxiliary contacts
Side mounting add-on blocksFault signalling + instantaneous auxiliary contacts
Undervoltage and shunt trips
Wiring diagram for undervoltage trip used on potentially dangerous machines, conforming to INRS
Front mounting add-on blocks
GV-AE1 GV-AE11 GV-AE20
GV-AD0110 GV-AD0101 GV-AD1010 GV-AD1001
Instantaneous auxiliary contacts Short-circuit signalling contactsGV-AN11 GV-AN20 GV-AM11
GV-AU GV-AS GV-AX
Schemes
or
10 AgG max.
Safety solutions using Preventa 4
Enclosed thermal-magnetic motor circuit breakers model GV2-ME
1036 Ver2.00-EN.fm/2 Schneider Electric
(1) Spare part.(2) Characteristics: please consult your Regional Sales Office.(3) Use in association with a contactor is recommended. Warning: operating current in enclosure limited to 30 A.
Metal enclosure
Application Type Degree of protection Reference Weightof enclosure kg
For MCB Surface mounting IP 55 GV3-CE01 2.000up to 30 A with or without accessories
Enclosure accessories (to be ordered separately)
Description Sold in Unit Weightlots of reference kg
Sealing For θ ≥ 5 °C 10 GV1-EA01 0.012membrane (1)
For θ < 5 °C (silicone) 10 GV1-EA02 0.012
IP 55 padlocking device for operators (when padlocked, the 1 GV1-V01 0.044motor circuit breaker is automatically in the “Open” (OFF) position)
Stop pushbutton Spring return 1 GV1-K01 0.052Ø 40 mm, red,mushroom head(supplied with Latching Key release 1 GV1-K02 0.095IP 55 sealing kit) (key n° 45)
Turn 1 GV1-K03 0.052to release
Thermal-magnetic motor circuit breakers
Standard power ratings of 3-phase Rating Asso- Reference Weightmotors 50/60 Hz in category AC-3 ciated230 V 400 V 440 V 500 V 660 V fuses240 V 415 V 690 VkW kW kW kW kW A kg
0.18 0.37 0.37 0.37 0.75 1…1.6 (2) GV3-M06 0.6000.25 0.55 0.55 0.55 1.1
0.75
0.37 0.75 0.75 1.1 1.5 1.6…2.5 (2) GV3-M07 0.6001.1
0.55 1.1 1.5 1.5 2.2 2.5…4 (2) GV3-M08 0.6000.75 1.5 2.2 3
1.1 2.2 2.2 3 4 4…6 (2) GV3-M10 0.6003
1.5 3 4 4 5.5 6…10 (2) GV3-M14 0.6002.2 4 5.5 7.5
4 7.5 7.5 9 9 10…16 (2) GV3-M20 0.60011
5.5 9 9 11 15 16…25 (2) GV3-M25 0.60011 11 15 18.5
7.5 15 15 18.5 22 25…40 (2) GV3-M40 (3) 0.7009 18.5 18.5 22 30
22
Enclosed starters and equipmentEnclosed thermal-magnetic motor circuit breakers type GV3-M
References
GV3-CE01
Dimensions :page 21038/2
Schemes :page 21038/3
GV1-V01
GV1-K01
GV3-M20
21036 Ver2.00-EN.fm/Schneider Electric
Enclosed starters and equipmentEnclosed thermal-magnetic motor circuit breakers type GV3-M
(1) 1 voltage trip OR 1 fault signalling contact to be fitted inside the motor circuit breaker.
Accessories (to be ordered separately)
Description Voltages Reference Weightkg
Voltage trips (1) 110, 120, 127 V 50 Hz GV3-B11 0.070Undervoltage 120, 127 V 60 Hztrips
220, 240 V 50 Hz GV3-B22 0.070240, 277 V 60 Hz
380, 415 V 50 Hz GV3-B38 0.070480 V 60 Hz
Voltage trips 110, 120, 127 V 50 Hz GV3-D11 0.070Shunt trips 120, 127 V 60 Hz
220, 240 V 50 Hz GV3-D22 0.070240, 277 V 60 Hz
380, 415 V 50 Hz GV3-D38 0.070480 V 60 Hz
Description Normal early break Sold in Unit Weighttype contacts lots of reference kg
Instantaneous N/C + N/O 1 GV1-A01 0.060auxiliarycontactblocks(1 per breaker) N/O + N/O 1 GV1-A02 0.060
N/C + N/O + N/O 1 GV1-A03 0.070
N/O + N/O + N/O 1 GV1-A05 0.070
N/O + N/O + 2 spare volt free terminals 1 GV1-A06 0.070
N/C + N/O + 2 spare volt free terminals 1 GV1-A07 0.070
Fault N/C 1 GV3-A08 0.030signallingcontacts (1)
N/O 1 GV3-A09 0.030
Padlocking – 5 GV1-V02 0.010devicefor Start button (on bare product)
Other versions Voltage trips from 24 to 690 V 50 or 60 Hz.Please consult your Regional Sales Office.
References
GV3-Bpp
GV1-A01
Schemes :page 21038/3
1038 Ver2.00-EN.fm/2 Schneider Electric
Surface mounting enclosure GV3-CE01
(1) 1 x 21 mm and 1 x 37.5 mm blanking plugs for cable entries(2) 1 x 21 mm and 2 x 37.5 mm blanking plugs for cable entries
Dimensions Enclosed starters and equipmentEnclosed thermal-magnetic motor circuit breakers type GV3-M
References :pages 21036/2 and 21036/3
21038 Ver2.00-EN.fm/Schneider Electric
GV3-M
Auxiliary contact blocks
Fault signalling contacts
Voltage trips
Motor circuit breakers
GV1-A01 GV1-A02 GV1-A03 GV1-A05 GV1-A06 GV1-A07
GV3-A08 GV3-A09
GV3-B GV3-D
Enclosed starters and equipmentEnclosed thermal-magnetic motor circuit breakers type GV3-M
Schemes
References :pages 21036/2 and 21036/3
24110_Ver2.10-EN.fm/2 Schneider Electric
TeSys enclosed starters 2
D.O.L. starters with manual control,with magnetic circuit breaker, 0.55 to 30 kW
Control by black rotary handle, padlockable in Off position (up to 3 padlocks with Ø 8 shank, to be ordered separately)
Starters with control by red rotary handle on yellow background
Add the letter R to the end of the references selected above. Example: GV2-LC0206 becomes GV2-LC0206R.
Enclosure without circuit-breaker, with rotary handle mounted on cover
(1) Circuit-breaker characteristics: - GV2-L see pages 24523/2 and 24523/3- NG 125L, product marketed under the Merlin Gerin, brand, please consult your Regional Sales Office.
(2) Avoid placing this material in contact with harsh substances (detergents, chlorinated solvents, ketones, alcohol,aromatic hydrocarbons).
Characteristics (1)
Conforming to standards IEC 947-4, IEC 439-1, VDE 0660-102 and EN 60947Degree of protection to IEC 529 IP 657Operational voltage Ue GV2-LC: 690 V, GV-NGC: 500 VMaterial Polycarbonate (2)
References
Rating Breaking capacity Icu Magnetic Reference WeightIn conforming to IEC 947-2 tripping
220 400 current230 V 415 V 440 V 500 V Id ± 20 %
A kA kA kA kA A kg
1.6 100 100 100 100 13 In GV2-LC0206 0.780
2.5 100 100 100 100 13 In GV2-LC0207 0.780
4 100 100 100 100 13 In GV2-LC0208 0.780
6.3 100 100 100 100 13 In GV2-LC0210 0.780
10 100 100 20 10 13 In GV2-LC0214 0.780
14 100 50 20 10 13 In GV2-LC0216 0.780
18 100 50 20 10 13 In GV2-LC0220 0.780
25 100 50 30 15 12 In GV-NGC0225 2.450
32 100 50 30 15 12 In GV-NGC0232 2.450
40 100 50 30 15 12 In GV-NGC0240 2.450
50 100 50 30 15 12 In GV-NGC0250 2.450
63 100 50 30 15 12 In GV-NGC0263 2.450
Variant
Description Rating Reference WeightA kg
Black rotary handle 1.6…18 GV2-LC02 0.300
25…63 GV-NGC02 0.550
Red rotary handle 1.6…18 GV2-LC02R 0.300on yellow background
25…63 GV-NGC02R 0.550
Characteristics, references
GV2-LC02
GV2-LC02
GV-NGC02
Dimensions :page 24110/3
Schemes :page 24110/3
24110_Ver2.10-EN.fm/3Schneider Electric
348
330
==
=167
237 186,3
=
2/T
1
4/T
2
6/T
3
1/L1
3/L2
5/L3
120
173
166
15065
==
=
88
=
TeSys enclosed starters 2
D.O.L. starters with manual control,with magnetic circuit-breaker. 0.55 to 30 kW
Dimensions
Knock-outs or blanking plugs for cable glands
Scheme
GV2-LC0206 to LC0220 GV-NGC0225 to NGC0263
Type of enclosure At top At bottomPG ISO PG ISO
GV2-LC 2 x 13 to 2 x 16 2 x 20 I 2 x 13 or 2 x 16 2 x 20 I
GV-NGC 2 x 13 or 2 x 16 or 2 x 20 I or 2 x 25 I or 2 x 13 or 2 x 16 or 2 x 20 I or 2 x 25 I or2 x 21 or 2 x 29 2 x 32 I or 2 x 40 I 2 x 21 or 2 x 29 2 x 32 I or 2 x 40 I
Dimensions, scheme
References :page 24110/2
24101_Ver3.01-EN.fm/2 Schneider Electric
TeSys enclosed starters 2
D.O.L. starters for motor control (1)
2.2 to 45 kW, without isolating device
Non-reversing starters
(1) Protection must be provided by addition of an overload relay, to be ordered separately, see pages 24514/2 and 24514/3.(2) Avoid placing this material in contact with harsh substances (detergents, chlorinated solvents, ketones, alcohol,aromatic hydrocarbons).(3) Standard control circuit voltages.
Other voltages: please consult your Regional Sales Office. (4) Selection according to the number of operating cycles, please consult your Regional Sales Office.
Characteristics
Conforming to standards IEC 947-4-1 and IEC 439-1, VDE 0660-102, EN 60947
Degree of protection to IEC 529 IP 659: LE2-K, IP 657: LE-D09 to D35 and IP 557: LE-D405 to D955
Ambient air temperature For operation: - 5 to + 40 °C
Operating positions Identical to positions for contactors
Material Polycarbonate (2): LE2-K and LE-D09 to D35. Sheet steel: LE-D405 to D955
References
Standard power ratings of 3-phase Maximum Basic reference. Weightmotors 50/60 Hz in category AC-3 current Complete with code220 V 380 V 660 V I the indicating control Standard230 V 400 V 415 V 440 V 500 V 690 V up to circuit voltage (3) voltageskW kW kW kW kW kW A kg
2.2 4 4 4 5.5 5.5 9 LE1-D09 F7 P7 V7 0.920
3 5.5 5.5 5.5 7.5 7.5 12 LE1-D12 F7 P7 V7 0.920
4 7.5 9 9 10 10 18 LE1-D18 F7 P7 V7 1.015
5.5 11 11 11 15 15 25 LE1-D25 F7 P7 V7 1.015
7.5 15 15 15 18.5 18.5 35 LE1-D35 F7 P7 V7 4.320
11 18.5 22 22 22 30 40 LE1-D405 F7 P7 V7 4.820
15 22 25 30 30 33 50 LE1-D505 F7 P7 V7 4.850
18.5 30 37 37 37 37 65 LE1-D655 F7 P7 V7 4.850
22 37 45 45 55 45 80 LE1-D805 F7 P7 V7 5.140
25 45 45 45 55 45 95 LE1-D955 F7 P7 V7 5.440
Reversing starters
1.5 2.2 2.2 3 – – 6 LE2-K065 F7 P7 V7 1.080
2.2 4 4 4 – – 9 LE2-K095 F7 P7 V7 1.080or LE2-D09 (4) F7 P7 V7 2.100
– – – – 5.5 5.5 9 LE2-D09 F7 P7 V7 2.100
3 5.5 5.5 5.5 7.5 7.5 12 LE2-D12 F7 P7 V7 2.100
4 7.5 9 9 10 10 18 LE2-D18 F7 P7 V7 2.410
5.5 11 11 11 15 15 25 LE2-D25 F7 P7 V7 2.570
7.5 15 15 15 18.5 18.5 35 LE2-D35 F7 P7 V7 4.100
11 18.5 22 22 22 30 40 LE2-D405 F7 P7 V7 5.270
15 22 25 30 30 33 50 LE2-D505 F7 P7 V7 5.470
18.5 30 37 37 37 37 65 LE2-D655 F7 P7 V7 5.470
22 37 45 45 55 45 80 LE2-D805 F7 P7 V7 6.700
25 45 45 45 55 45 95 LE2-D955 F7 P7 V7 7.000
LE1-D12
8101
7381
0174
LE2-D12
Volts 50/60 Hz 24 42 48 110 115 220 230 240 380 400 415 440LE2-K B7 D7 E7 F7 – M7 P7 U7 Q7 V7 N7 R7LE1, LE2-D B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7
Characteristics,references
Dimensions:page 24102/2
Schemes:page 24102/3
24101_Ver3.01-EN.fm/3Schneider Electric
TeSys enclosed starters 2
D.O.L. starters for motor control (1)
2.2 to 45 kW, without isolating device
Standard versions comprise:
1 red Stop/Reset button “O”
(1) See previous page.(2) Example: LE1-D09F7A04.
Description
For non-reversing starters: 1 green Start button “I”,1 red Stop/Reset button “O”.
For reversing starters:- LE2-K: 1 Start button ,
1 Start button ,1 red Stop/Reset button.
- LE2-D09 to D35: 1 2-position spring return selector switch “I”-“II”,1 red Stop/Reset button “O”.
- LE2-D405 to D955: 1 blue Reset button “R”.
Variants (pre-assembled)
Description Application Suffix to beadded to the starter reference (2)
No pushbuttons on cover LE1-D09…D955 A04LE2-D09…D955
1 green Start button “I” LE2-D405…D955 A111 green Start button “II”
1 blue Reset button “R” LE1-D09…D955 A05LE2-K06 and K09LE2-D09…D35
1 3-position stay put selector switch (“I”-“O”-“II”) LE1-D09…D35 A09(“I”: Automatic Start; “O”: Stop; “II”: Manual Start)1 blue Reset button “R”
1 2-position stay put selector switch “O”-“I” LE1-D09…D35 A13(“O”: Stop; “I”: Manual Start)1 blue Reset button “R”
1 3-position stay put selector switch “O”-“I” with LE1-D09…D35 A35spring return to centre position (“I”: Manual start; “O”: Stop, stay put)1 blue Reset button “R”
1 neutral terminal LE1-D09…D955 A59Fitted as standard on LE1 and LE2-D18 to D955 LE2-K06 and K09starters ordered with 220 V (M7), 230 V (P7) LE2-D09…D955or 240 V (U7) control supply
LE1-D12A04
8101
75
LE1-D12A05
8101
76
LE1-D12A09
8101
77
LE1-D12A13
8101
78
LE1-D12A35
8101
78
Accessory (for customer assembly)
Description Application Reference Weightkg
Start pushbutton latching device LE1-D405…D955 LA9-D09907 0.060for stay put operation(Start-Stop)
Other versions Possible combinations of 2 variants.Please consult your Regional Sales Office.
References
Schemes:page 24102/3
24102_Ver2.10-EN.fm/2 Schneider Electric
287
c1 =
367
= 22519
5=
=
146
120
84
175
150
165
19
c1
307
=
257
= 165
165
==
c1
166
150
==
=
88
=c1
183
= =
101
201
c1
312
=
181
= 105
195
==
LE2-D405 to D655
Knock-outs or blanking plugs for cable glands
LE1-D09 and D12 LE1-D18 to D35 LE1-D405 to D655LE2-D09 to D35
c1 c1 c1LE1-D LE2-D
Standard version 128.5 Standard version 153.5 160 Standard version 161Version A04 120 Version A04 145 145 Version A04 150Version A05 128.5 Version A05 153.5 153.5 Version A05 161Version A09 135 Version A09 160 –Version A13 135 Version A13 160 –Version A35 135 Version A35 160 –LE2-K06 and K09
LE1-D805 and D955 LE2-D805 and D955
c1 c1LE1-D LE2-D
Standard version 176 176 Standard version 194Version A04 165 165 Version A04 190Version A05 176 – Version A05 194Version A11 – 176
Type of enclosure At top At bottomPG ISO PG ISO
LE1-D09 and D12 2 x 13 or 2 x 16 2 x 20 I 2 x 13 or 2 x 16 2 x 20 I
LE1-D18 to D35 and LE2-D09 to D35 2 x 16 or 2 x 21 2 x 20 I or 2 x 25 I 2 x 16 or 2 x 21 2 x 20 I or 2 x 25 I
LE2-D405 1 x 13 and 1 x 21 1 x 20 I and 1 x 25 I 1 x 13 and 2 x 21 1 x 20 I and 2 x 25 I
LE1-D405 to D655 and LE2-D505 and D655 1 x 13 and 1 x 29 1 x 20 I and 1 x 32 I 1 x 13 and 2 x 29 1 x 20 I and 2 x 32 I
LE1 or LE2-D805 and D955 1 x 13 and 1 x 36 1 x 20 I and 1 x 40 I 1 x 13 and 2 x 36 1 x 20 I and 2 x 40 I
LE2-K 2 x 13 and 2 x 16 4 x 20 I 2 x 13 and 2 x 16 4 x 20 I
TeSys enclosed starters 2
D.O.L. starters for motor control2.2 to 45 kW, without isolating device
Dimensions
References : pages 24101/2 and
24101/3Schemes :
page 24101/3
24102_Ver2.10-EN.fm/3Schneider Electric
– KM1 – KM2
L1 L2 L3
U V W
– KM2
A
B
– KM1
– KM2– KM1
– KM2 – KM1
A1
A2
A1
A2
O
B
– KM2– KM1
– KM2 – KM1
A1
A2
A1
A2
A
R
– KM1 – KM2
L1 L2 L3
U V W
L1 L2
– KM1
U V WL3
B
A
A1
A2
– KM1
– KM1
O
I
1314
2122
A
O
l – KM1
B
A1
A2
– KM1
A1
A2
– KM1
– KM2
– KM2
A
A1
A2
– KM2
– KM1
B
– KM1
– S1III
– KM2
A1
A2
– KM1
2122
– KM2
A
O
A1
A2
– KM2
– KM1
B
R
l l l
– KM1
LE1-D09 to D955 LE1-D09 to D955 Variant A04 or A05
LE2-K06, K09 LE2-K06, K09 Variant A05
LE2-D09 to D955 LE2-D09 to D35 LE2-D405 to D955LE2-D09 to D955 with variants A04 or A05
Connections A B220 V, 230 V, 240 V LE2-K, LE1 and LE2-D09 and D12 L3 Neutral
LE1 and LE2-D18 to D955 L3 Neutral terminal380 V, 400 V, 415 V, 440 V All products L3 L1Other voltages LE1 and LE2-D09 to D35 Terminal 1 Terminal 2
LE2-K, LE1 and LE2-D405 and D955 Direct connection
TeSys enclosed starters 2
D.O.L. starters for motor control2.2 to 45 kW, without isolating device
Schemes
References : pages 24101/2 and
24101/3Dimensions :
page 24102/2
Remote control
Remote control
Remote control
24103_Ver4.10-EN.fm/2 Schneider Electric
TeSys enclosed starters 2
D.O.L. starters for motor control (1)2.2 to 45 kW, with isolating device
Non-reversing starters
Reversing starters
(1) Protection must be provided by addition of an overload relay, to be ordered separately, see pages 24514/2 and 24514/3.(2) Avoid placing this material in contact with harsh substances (detergents, chlorinated solvents, ketones, alcohol,aromatic hydrocarbons).(3) Standard control circuit voltages.
Other voltages : please consult your Regional Sales Office.(4) Selection according to dimensions and number of operating cycles, please consult your Regional Sales Office.(5) Supplied with 3 cable entries.
Characteristics
Conforming to standards IEC 947-4-1 and IEC 439-1, VDE 0660-102, EN 60947
Degree of protection to IEC 529 IP 659 : LE-K, IP 657 : LE-D09 to D35 and IP 55 : LE-D406 to D806
Ambient air temperature For operation : - 5 to + 40 °C
Operating positions Identical to positions for contactors
Material Polycarbonate (2) : LE-K and LE-D09 to D35. Sheet steel : LE-D406 to D806
References
Standard power ratings of 3-phase Current Fuses Basic reference. Weightmotors 50/60 Hz in category AC-3 I the to be fitted by Complete with code 220 V 380 V 660 V max. the customer indicating control Standard230 V 400 V 415 V 440 V 500 V 690 V up to Size Type aM circuit voltage (3) voltageskW kW kW kW kW kW A A kg
1.5 2.2 2.2 3 – – 6 10 x 38 10 LE4-K065 F7 P7 V7 1.4502.2 4 4 4 – – 9 10 x 38 12 LE4-K095 F7 P7 V7 1.450
or LE4-D09 (4) F7 P7 V7 1.960
2.2 4 4 4 5.5 – 9 10 x 38 12 LE4-D09 F7 P7 V7 1.960
3 5.5 5.5 5.5 7.5 – 12 10 x 38 16 LE4-D12 F7 P7 V7 1.960
4 7.5 9 9 10 – 18 10 x 38 20 LE4-D18 F7 P7 V7 2.200
5.5 11 11 11 15 – 25 10 x 38 25 LE4-D25 F7 P7 V7 2.200
7.5 15 15 15 18.5 18.5 35 14 x 51 32 LE4-D35 F7 P7 V7 5.190
11 18.5 22 22 22 30 40 14 x 51 40 LE4-D406 F7 P7 V7 5.770
15 22 25 30 30 33 50 22 x 58 63 LE4-D506 F7 P7 V7 6.440
18.5 30 37 37 37 37 65 22 x 58 80 LE4-D656 F7 P7 V7 6.670
22 37 45 45 55 45 80 22 x 58 80 LE4-D806 (5) F7 P7 V7 7.100
1.5 2.2 2.2 3 – – 6 10 x 38 10 LE8-K065 F7 P7 V7 1.6002.2 4 4 4 – – 9 10 x 38 12 LE8-K095 F7 P7 V7 1.600
or LE8-D09 (4) F7 P7 V7 3.550
– – – – 5.5 – 9 10 x 38 12 LE8-D09 F7 P7 V7 3.550
3 5.5 5.5 5.5 7.5 – 12 10 x 38 16 LE8-D12 F7 P7 V7 3.550
4 7.5 9 9 10 – 18 10 x 38 20 LE8-D18 F7 P7 V7 3.700
5.5 11 11 11 15 – 25 10 x 38 25 LE8-D25 F7 P7 V7 4.670
7.5 15 15 15 18.5 18.5 35 14 x 51 32 LE8-D35 F7 P7 V7 5.800
11 18.5 22 22 22 30 40 14 x 51 40 LE2-D406 F7 P7 V7 14.170
15 22 25 30 30 33 50 22 x 58 63 LE2-D506 F7 P7 V7 14.700
18.5 30 37 37 37 37 65 22 x 58 80 LE2-D656 F7 P7 V7 14.770
22 37 45 45 55 45 80 22 x 58 80 LE2-D806 F7 P7 V7 16.000
Volts 50/60 Hz 24 42 48 110 115 220 230 240 380 400 415 440LE-K B7 D7 E7 F7 – M7 P7 U7 Q7 V7 N7 R7LE-D B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7
Characteristics, references
LE4-D12
Dimensions :page 24104/2
Schemes :page 24104/3
LE8-D12
24103_Ver4.10-EN.fm/3Schneider Electric
TeSys enclosed starters 2
D.O.L. starters for motor control (1)2.2 to 45 kW, with isolating device
Standard versions comprise :
(1) See previous page(2) Example : LE4-D09F7A04.
Description
For non-reversing starters :- LE4-K and LE4-D09 to D656 : 1 green Start button “I”,
1 red Stop/Reset button “O”,
- LE4-D806 : no pushbuttons on cover.
For reversing starters :- LE8-K : 1 Start button ,
1 Start button ,1 red Stop/Reset button,
- LE8-D09 to D35 : 1 2-position spring return selector switch “I” “II”,1 red Stop/Reset button “O”,
- LE2-D406 to D806 : no pushbuttons on cover.
Protection Power circuit Control circuitLE4 and LE8-K 1 3-pole isolating device NoneLE4 and LE8-D09 to D35 1 3-pole isolating device + 1 additional pole LA8-D254LE4 and LE2-D406 to D806 1 3-pole isolating device + 1 circuit-breaker GB2-CB08
Variants (pre-assembled)
Description Application Suffix to beadded to thestarter reference (2)
No pushbuttons on cover LE4-D09…D656 A04LE8-D09…D35
1 green Start button “I” LE2-D406…D806 A111 green Start button “II”1 red Stop/Reset button “O”
1 blue Reset button “R” LE4-D09…D806 A05LE8-K06 and K09LE8-D09…D35LE2-D406…D806
1 neutral terminal LE4-K06 and K09 A59Fitted as standard on starters LE4-D18 to D806, LE4-D09…D806LE8-D18 to D35 and LE4-D406 to D806 LE8-K06 and K09ordered with 220 V (M7), 230 V (P7) and 240 V (U7) LE8-D09…D35control supply LE2-D406…D806
Accessories (for customer assembly)
Description Application Reference Weightkg
Start pushbutton latching device LE4-D406…D656 LA9-D09907 0.060for stay put operation(Start-Stop)
Other versions Possible combinations of 2 variants.Please consult your Regional Sales Office.
References
Schemes :page 24104/3
LE4-D12A04
LE4-D12A05
24104_Ver2.10-EN.fm/2 Schneider Electric
c1
20 84
17515
0
165
(1)
120
19
31
c1
348
330
==
=
186 31
=
287
c1 =
367
=
31
225
195
==
400
(1)
202
c1
== a-75
a-50
a
a+57,5
350
342,
5
325
==
4xM8x25
31
TeSys enclosed starters 2
D.O.L. starters for motor control2.2 to 45 kW, with isolating device
(1) For LE8 only.LE4-D406 to D656
LE2-D406 to D806LE4-D806
(1) + 14 mm with blanking plugs.
Knock-outs or blanking plugs for cable glands
LE4-K06 and K09 LE4-D09 to D35LE8-K06 and K09 LE8-D09 to D35
c1 c1LE4-K LE8-K LE4-D LE8-D
Standard version 146 146 Standard version 175.5 182Version A05 – 139 Version A04 167 167
Version A05 175.5 175.5
c1Standard version 201Version A04 190Version A05 201
LE2- aD406, D506, D656 300D806 400
LE4- aD806 400
c1LE2-D LE4-D
Standard version 218 218Version A05 218 218Version A11 – 218
Type of enclosure At top At bottomPG ISO PG ISO
LE4 and LE8-D09 to D35 2 x 13 or 2 x 16 or 2 x 20 I or 2 x 25 I or 2 x 13 or 2 x 16 or 2 x 20 I or 2 x 25 I or2 x 21 or 2 x 29 2 x 32 I or 2 x 40 I 2 x 21 or 2 x 29 2 x 32 I or 2 x 40 I
LE2-D09 to D35 1 x 16 or 2 x 21 2 x 20 I or 2 x 25 I 2 x 16 or 2 x 21 2 x 20 I or 2 x 25 I
LE2-D406 and LE4-D406 1 x 13 and 1 x 21 1 x 20 I and 1 x 25 I 1 x 13 and 2 x 21 1 x 20 I and 2 x 25 I
LE1-D506 to D656 and LE4-D506 and D6561 x 13 and 1 x 29 1 x 20 I and 1 x 32 I 1 x 13 and 2 x 29 1 x 20 I and 2 x 32 I
LE2-D806 and LE4-D806 1 x 13 and 1 x 36 1 x 20 I and 1 x 40 I 1 x 13 and 2 x 36 1 x 20 I and 2 x 40 I
LE4-K, LE8-K 2 x 13 and 2 x 16 4 x 20 I 2 x 13 and 2 x 16 4 x 20 I
Dimensions
References :pages 24103/2 and 24103/
3Schemes :
page 24104/3
24104_Ver2.10-EN.fm/3Schneider Electric
– Q1
– KM1 – KM2
L1 L2 L3
U V W
– KM1
O
I
– KM1
A1
A2
A
B
– KM2– KM1
– KM2
– KM2 – KM1
A1
A2
– Q1
– KM1
A1
A2
A
B
O
– KM2– KM1
– KM2 – KM1
A1
A2
A1
A2
R
A
B13
1421
22
O
l – KM1
A2
A1
– KM1
Q1– F1
B
A
Remote control
– Q1
– KM1 – KM2
L1 L2 L3
U V W
A1
A2
– KM1
– KM2
– KM2
A1
A2
– KM2
– KM1
– KM1
Q1Q1
A
B
– S1III
O
A
A1
A2
– KM1
– KM1
1817
Q1Q1
O
I
O
l
A1
A2
– KM1
– KM1
Q1– F1
B
A
– Q1
– KM1
L1 L2 L3
U WV
A1
A2
– KM1
2122
– KM2
– KM2
O
A1
A2
– KM2
– KM1
1314
l
– KM1
1314
l l
Q1– F1
A
B
TeSys enclosed starters 2
D.O.L. starters for motor control2.2 to 45 kW, with isolating device
LE4-K06, K09LE4-D09 to D806 LE4-K06, K09 LE4-D09 to D35 LE4-D406 to D656 LE4-D806
LE4-D09 to D656 with variant A04 or A05
LE8-K06, K09 LE8-K06, K09 Variante A05
LE8-D09 to LE2-D806 LE8-D09 to D35 LE2-D406 to D806
Connections A B220 V, 230 V, 240 V LE4 and LE8-K, LE4 and LE8-D09 and D12 L3 Neutral
LE4-D18 to D806, LE8-D18 to D35 and LE2-D406 to D806 L3 Neutral terminal
380 V, 400 V, 415 V, 440 V All products L3 L1Other voltages LE4 and LE8-D09 to D35 Terminal 1 Terminal 2
LE4 and LE2-D406 and D806 Direct connection
Schemes
Remote control
Remote control
References :pages 24103/2 and 24103/
3Dimensions :
page 24104/2
24105_Ver3.10-EN.fm/2 Schneider Electric
TeSys enclosed starters 2
D.O.L. starters for motor control0.25 to 7.5 kW with 3-phase thermal overload relay
Non-reversing starters
Starter LE1-M, combined with short-circuit protection components, provides type 1 or type 2 coordination, depending onthe type of devices used.
The standard version comprises:- 1 green Start button “I”,- 1 red Stop/Reset button “O/R”,- 1 yellow operating indicator.
Control may be pulsed or maintained. An earth terminal and a neutral terminal are provided on the bottom of the enclosure.
(1) Thermal overload relay fitted as standard.(2) The contactor coil is pre-wired between 2 phases of the power circuit
Characteristics
Conforming to standards IEC 947-4-1, IEC 439-1, VDE 0660-102 and EN 60947
Degree of protection to IEC 529 IP 65
Ambient air temperature For operation: - 5 to + 40 °C
Operating positions Identical to those for k contactors
Material Self-extinguishing ABS
References
Standard power ratings Setting range Basic reference. Weightof 3-phase motors 50/60 Hz in category AC-3 of thermal overload Complete with code 220 V 380 V relay LR2-K(1) indicating power230 V 240 V 400 V 415 V circuit voltage (2)kW kW kW kW A kg
0.12 0.12 0.25 0.25 0.54…0.8 LE1-M3505 0.600
0.18 0.18 0.37 0.37 0.8…1.2 LE1-M3506 0.600
0.25 0.25 0.55 0.55 1.2…1.8 LE1-M3507 0.600
0.37 0.37 1.1 0.75 1.8…2.6 LE1-M3508 0.600
0.55 0.55 1.5 1.5 2.6…3.7 LE1-M3510 0.600
1.1 0.75 2.2 2.2 3.7…5.5 LE1-M3512 0.600
1.5 1.1 3 3 5.5…8 LE1-M3514 0.600
2.2 2.2 4 4 8…11.5 LE1-M3516 0.600
3 3 5.5 5.5 10…14 LE1-M3521 0.600
3.7 4 7.5 7.5 12…16 LE1-M3522 0.600
Description
Variant
Starter without Delete the last 2 digits of the starter references selected above.thermal overload relay LR2-K Example: LE1-M35
Spare part
Description Basic reference. Complete Weightwith code indicatingpower circuit voltage (2) kg
Contactor LC1-KA80 0.180
The codes indicated below therefore correspond to the power circuit voltage.Volts 50/60 Hz 24 220 230 240 380 400 415 440Code B7 M7 P7 U7 Q7 V7 N7 R7Example: 380/400 V 3-phase supply, 4 kW motor: LE1-M35Q716
Characteristics, references
LE1-M35
Dimensions :page 24105/3
Schemes : page 24105/3
24105_Ver3.10-EN.fm/3Schneider Electric
78
160
130
(5"1
/8)
108
I
O/R
1
2
3
4
5
6
13
14
A1
A2
2 4 6
L1 L2 L3
Reset/OR
T1 T2 T3
U WV
2 4 6
1/L1
3/L2
5/L3
M
– KM1 I
A
B
1413
O/R
9596
– KM1 – H1
A2
A1
– KM1I
A
B
O
9596
– KM1 – H1
A2
A1
1413
KM1
DimensionsLE1-M35 (1)
Knock-outs or blanking plugs for cable glands
(1) Can be mounted on machine panel or frame. Knock-outs for 4 x 13 P cable glands.
Enclosure type At top At bottomPG ISO PG ISO
LE1-M 2 x 13 to 2 x 21 2 x 20 I or 2 x 25 I 2 x 13 to 2 x 21 2 x 20 I or 2 x 25 I
SchemesLE1-M35 Choice of type of control built into the product
Control by Control bylatching spring returnpushbuttons pushbuttons
Connections A B220 V, 230 V, 240 V L3 Neutral380 V, 400 V, 415 V, 440 V L3 L1Other voltages Terminal 1 Terminal 2
TeSys enclosed starters 2
D.O.L. starters for motor control0.25 to 7.5 kW with 3-phase thermal overload relay
Dimensions, schemes
References : page 24105/2
or
24111_Ver3.10-EN.fm/2 Schneider Electric
(1) Avoid placing this material in contact with harsh substances (detergents, chlorinated solvents, ketones, alcohol,aromatic hydrocarbons).(2) Standard control circuit voltages
Other voltages: please consult your Regional Sales Office.(3) Example: LE1-GVME06KF7A59(4) Supplied with IP 55 sealing kit.(5) Padlockable in position “O”, by padlock with Ø 4 to 8 mm shank.
Characteristics
Conforming to standards IEC 947-4-1, IEC 439-1, VDE 0660-102 and EN 60947Degree of protection to IEC 529 IP 55Ambient air temperature For operation: - 5 to + 40 °COperating positions Identical to those for K contactorsMaterial Polycarbonate (1)
References
Standard power ratings of 3-phasemotors 50/60 Hz in category AC-3
Settingrange of
Fixedmagnetic
Basic reference.Complete with code
Weight
400 thermal tripping indicating control230 V 415 V 440 V 500 V 690 V trips current 13 Irth circuit voltage (2)kW kW kW kW kW A A kg
0.18 0.37 0.37 0.37 0.75 1…1.6 22.5 LE1-GVME06K 1.2100.25 0.55 0.55 0.55 1.1
0.75
0.37 0.75 0.75 1.1 1.5 1.6…2.5 33.5 LE1-GVME07K 1.2101.1
0.55 1.1 1.5 1.5 2.2 2.5…4 51 LE1-GVME08K 1.2100.75 1.5 2.2 3
1.1 2.2 2.2 3 4 4…6.3 78 LE1-GVME10K 1.2103
1.5 3 4 4 5.5 6…10 138 LE1-GVME14K 1.2102.2 4 5.5 7.5
2.2 5.5 5.5 7.5 9 9…14 170 LE1-GVME16K 1.2103 7.5 11
Variant
Description Suffix to be added tothe starter reference (3)
Weightkg
Neutral terminal A59 –
Description Reference Weightkg
Enclosure without starter, LE1-GVMEK 0.740with sealing kit fitted(references of combination motor starters forcustomer assembly, see pages 24520/2 and 24520/3)
Accessories (to be ordered separately)
Description Sold inlots of
Unitreference
Weightkg
Padlocking device (4) 1 to 3 padlocks with 1 GV2-V01 0.075for padlocking the Ø 4 to 8 mm shankGV2-ME operator(Padlocking is only possiblein the “O” (Off) position)Mushroom Spring return (4) 1 GV2-K011 0.052head Stopbutton Latching Key release (key n° 455) 1 GV2-K021 0.160Ø 40 mm, (4) IP 55 Turn to release 1 GV2-K031 0.115red 1 GV2-K04 (5) 0.120Sealing IP 55 10 GV2-E01 0.012kit IP 55 for θ < + 5 °C 10 GV2-E02 0.012
Volts 50/60 Hz 24 42 48 110 115 220 230 240 380 400 415 440Code B7 D7 E7 F7 – M7 P7 U7 Q7 V7 N7 R7
TeSys enclosed starters 2
D.O.L. starters for motor control 0.37 to 5.5 kW with thermal magnetic circuit-breaker and contactor
Characteristics, references
LE1-GVMEK
LE1-GVMEK
Dimensions :page 24111/3
Schemes :page 24111/3
24111_Ver3.10-EN.fm/3Schneider Electric
A1
A2
O
I – KM1
– KM1
– Q1
A
B
Externalcontrol
86
94
183
201
= =
101
A1
A2
O
I – KM1
– KM1
– Q1
A
B
Externalcontrol
86
94
183
201
= =
101
DimensionsLE1-GVMEK
SchemesLE1-GVMEK
Connections A B220 V, 230 V, 240 V L3 Neutral380 V, 400 V, 415 V, 440 V L3 L1Other voltages Terminal 1 Terminal 2
TeSys enclosed starters 2
D.O.L. starters for motor control0.37 to 5.5 kW with thermal magnetic circuit-breaker and contactor
Dimensions, schemes
References :page 24111/2
L1 L2 L3
– KM1
– Q1
24106-EN_Ver2.12.fm/2 Schneider Electric
TeSys enclosed starters 2
Star-delta starters5.5 to 132 kW, without isolating device (1)
Maximum operating rate LE 3-K: 12 starts/hour and LE3-D: 30 starts/hour.Maximum starting time: 30 seconds.LE3-D: an LAD-S2 timer imposes a delay of 40 ms ± 15 ms on the delta contactor at the moment of changeover to ensurethat the star contactor has sufficient breaking time.
(1) Protection must be provided by the addition of an overload relay, to be ordered separately. Select appropriateoverload relay for setting at 0.58 of the full load rated motor current, see pages 24514/2 and 24514/3.(2) Avoid placing this material in contact with harsh substances (detergents, chlorinated solvents, ketones, alcohol,aromatic hydrocarbons).(3) Standard control circuit voltages.
Other voltages: please consult your Regional Sales Office. (4) Selection according to dimensions and the number of operating cycles, please consult your Regional Sales Office.
Characteristics
Conforming to standards IEC 947-4-1 and IEC 439-1, VDE 0660-102, EN 60947
Degree of protection to IEC 529 IP 659: LE3-K, IP 657: LE3-D09 to D35 and IP 557: LE3-D405 to D150
Ambient air temperature For operation: - 5 to + 40 °C
Operating positions Identical to positions for contactors
Material Polycarbonate (2): LE3-K and LE3-D09 to D35. Sheet steel: LE3-D405 to D150
References
Standard power ratings Basic reference. Weightof squirrel cage motors Complete with codeMains voltage - delta connection indicating control220 V 380 V 415 V 440 V circuit voltage
400 V (3)kW kW kW kW kg
3 5.5 5.5 5.5 LE3-K065 1.460
4 7.5 7.5 7.5 LE3-K095 1.460
or LE3-D09 (4) 3.650
5.5 11 11 11 LE3-D12 3.650
11 18.5 22 22 LE3-D18 3.750
15 30 30 30 LE3-D35 5.160
18.5 37 37 37 LE3-D405 8.160
30 55 59 59 LE3-D505 8.150
37 75 75 75 LE3-D805 14.000
63 110 110 110 LE3-D115 24.500
75 132 132 147 LE3-D150 24.500
Volts 50/60 Hz 24 42 48 110 115 220 230 240 380 400 415 440LE3-K B7 D7 E7 F7 – M7 P7 U7 – – – –LE3-D B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7
Characteristics, references
LE3-D12
Dimensions :page 24107/2
Schemes :page 24107/3
24106-EN_Ver2.12.fm/3Schneider Electric
TeSys enclosed starters 2
Star-delta starters5.5 to 132 kW, without isolating device
The standard version comprises:
(1) Example: LE3-D09F7A04
Description
- LE3-K and LE3-D09 to D35: 1 green Start button “I” 1 red Stop/Reset button “O”
- LE3-D405 to D150: no pushbuttons on cover.
Variants (pre-assembled)
Description Application Suffix to be addedto the starter reference (1)
No pushbuttons on cover LE3-D09…D35 A04
1 green Start button “I” LE3-D405…D150 A061 red Stop/Reset button “O”
1 blue Reset button “R” LE3-D09…D805 A05
1 neutral terminal LE3-K065 and K095 A59Fitted as standard on starters LE3-D09…D805LE3-D115 and D150
Mechanical interlock LE3-D405 to D150 A64Fitted as standard on starters LE3-K and LE3-D09 to D35
Other versions Possible combinations of 2 variants.Please consult your Regional Sales Office.
References
LE3-D12A04
LE3-D12A05
Schemes :page 24107/3
24107_Ver2.20-EN.fm/2 Schneider Electric
c1
348
330
==
=
186
=
84
175
150
146
120
165
19
287
c1 =
367
= 225
195
==
b (1
)
c1
c1 + 15,5
== a - 75
a - 50
a
a + 57,5
b -
50
b +
57,
5
b -
75=
=
TeSys enclosed starters 2
Star-delta starters5.5 to 132 kW, without isolating device
LE3-D805 to D150
Knock-outs or blanking plugs for cable glands
LE3-K065, K095 LE3-D09 to D35
c1Standard version 175.5Version A04 167Version A05 175.5
LE3-D405 and D505
c1Standard version 190Version A05 194Version A06 194
LE3- a bD805 400 400D1155 500 600D1505 500 600
c1LE3-D805 LE3-D115, D150
Standard version 202 252Version A05 218 –Version A06 218 268
(1) + 14 mm with blanking plugs.
Type of enclosure At top At bottomPG ISO PG ISO
LE3-D09 to D35 2 x 13 or 2 x 16 or 2 x 20 I or 2 x 25 I or 2 x 13 or 2 x 16 or 2 x 20 I or 2 x 25 I or2 x 21 or 2 x 29 2 x 32 I or 2 x 40 I 2 x 21 or 2 x 29 2 x 32 I or 2 x 40 I
LE3-D405 1 x 29 1 x 32 I 1 x 29, 2 x 13 and 2 x 21 1 x 32 I, 2 x 20 I and 2 x 25 I
LE3-D505 1 x 36 1 x 40 I 1 x 36, 2 x 13 and 2 x 29 1 x 40 I, 2 x 20 I and 2 x 32 I
LE3-D805 1 x 36 1 x 40 I 2 x 13 and 3 x 36 2 x 20 I and 3 x 40 I
LE3-K 2 x 13 and 2 x 16 4 x 20 I 2 x 13 and 2 x 16 4 x 20 I
Dimensions
References :pages 24106/2 and
24106/3
24107_Ver2.20-EN.fm/3Schneider Electric
A
O
– KM3 – KM2– KM1T
T
– KM1
I
Y
L
A1
A2
A1
A2
A1
A2
A1
A2
– KM1– KM3
– KM2
B
– KM2 – KM3 – KM1
L1 L2 L3
U1
V1
W1
U2
V2
W2
U1
V1
W1
U2
V2
W2
Recommended cabling for reversal of motor rotation (standard motor,viewed from shaftend).
U1
V1
W1
U2
V2
W2
Ð KM2 Ð KM3 Ð KM1
U1
V1
W1
U2
V2
W2
L1 L2 L3
Recommended cabling for reversal of motor rotation (standard motor, viewed from shaft end).
1718
l
A1
A2
– KM1
– KM3
– KM2
– KM1
– KM2
A1
A2
– KA1
A1
A2
– KM2
– KM1
– F2
– KM2
– KM1
A1
A2
– KM3
– KA1
YL
A
B
U1
V1
W1
U2
V2
W2
Ð KM2 Ð KM3 Ð KM1
U1
V1
W1
U2
V2
W2
L1 L2 L3
Recommended cabling for reversal of motor rotation (standard motor, viewed from shaftend).
A1
A2
– KM1
– KM3
– KM2
– KM1
– KM2
A1
A2
– KM3
– KM1
A1
A2
– KM2
– KM2
B
A
O
I
Y
L
A1
A2
– KM1
1718
– KM3
– KM2
– KM1
– KM2
A1
A2
– KM3
– KM1
A1
A2
– KM2
– KM2
B
A
I
Y
L
Note : in accordance with current installation regulations, short-circuit protection must be provided by fuses or a circuit-breaker.
LE3-K065 and K095 LE3-K065 and K095
LE3-D09 to D805 LE3-D09 to D35 LE3-D405 to D805
LE3-D115 and D150 LE3-D115 and D150
Connections A B220 V, 230 V, 240 V LD09 and D12 L3 Neutral
LE3-D18 to D150 L3 Neutral terminal380 V, 400 V, 415 V, 440 V All products L3 L1Other voltages LE3-D09 to D35 Terminal 1 Terminal 2
LE3-K and LE3-D405 to D150 Direct connection
TeSys enclosed starters 2
Start-delta starters5.5 to 132 kW, without isolating device
Schemes
Remotecontrol
Remotecontrol
References : pages 24106/2 and
24106/3Dimensions :
page 24107/2
24108_Ver2.10-EN.fm/2 Schneider Electric
TeSys enclosed starters 2
Star-delta starters (1)
7.5 to 75 kW with isolating device
Maximum operating rate: 30 starts/hour. Maximum starting time: 30 seconds.An LAD-S2 timer imposes a delay of 40 ms ± 15 ms on the delta contactor at the moment of changeover to ensure thatthe star contactor has sufficient breaking time.
(1) Protection must be provided by the addition of an overload relay, to be ordered separately. Select appropriate overloadrelay for setting at 0.58 of the full load rated motor current, see pages 24514/2 and 24514/3.(2) Avoid placing this material in contact with harsh substances (detergents, chlorinated solvents, ketones, alcohol,aromatic hydrocarbons).(3) Standard control circuit voltages.
Other voltages: please consult your Regional Sales Office.
Characteristics
Conforming to standards IEC 947-4-1 and IEC 439-1, VDE 0660-102, EN 60947
Degree of protection to IEC 529 IP 657: LE6-D09 to D18 and IP 557: LE3-D326 to D806
Ambient air temperature For operation: - 5 to + 40 °C
Operating positions Identical to positions for contactors
Material Polycarbonate (2): LE6-D. Sheet steel: LE3-D
References
Standard power ratings Fuses to be fitted Basic reference. Weightof squirrel cage motors by the customer Complete with codeMains voltage - Delta connection Size Type indicating control220 V 380 V 415 V 440 V aM circuit voltage Standard
400 V (3) voltageskW kW kW kW A kg
4 7.5 7.5 7.5 10 x 38 20 LE6-D09 F7 P7 V7 3.900
5.5 11 11 11 10 x 38 25 LE6-D12 F7 P7 V7 3.900
11 18.5 22 22 14 x 51 40 LE6-D18 F7 P7 V7 4.850
15 30 30 30 22 x 58 63 LE6-D326 F7 P7 V7 7.650
18.5 37 37 37 22 x 58 80 LE3-D406 F7 P7 V7 16.900
30 55 59 59 22 x 58 125 LE3-D506 F7 P7 V7 17.000
37 75 75 75 0 160 LE3-D806 F7 P7 V7 27.500
Volts 24 42 48 110 115 220 230 240 380 400 415 44050/60 Hz B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7
Characteristics, references
LE6-D12
Dimensions :page 24109/2
Schemes :page 24109/3
:
24108_Ver2.10-EN.fm/3Schneider Electric
TeSys enclosed starters 2
Star-delta starters7.5 to 75 kW with isolating device
The standard version comprises:
(1) Example: LE6-D09F7A04.
Description
- LE6-D09 to D18: 1 green Start button “I”1 red Stop/Reset button “O”
- LE3-D326 to D806 no pushbuttons on cover
Protection Power circuit Control circuitLE6-D09 and D12 1 3-pole isolating device + 1 additional pole LA8-D254LE6-D18 to LE3-D806 1 3-pole isolating device + 1 circuit breaker GB2-CB08
Variants (pre-assembled)
Description Application Suffix to be added tothe starter reference (1)
No pushbuttons on cover LE6-D09…D18 A04
1 green Start button “I” LE3-D326 to D806 A061 red Stop/Reset button “O”
1 blue Reset button “R” LE6-D09…LE3-D806 A05
1 neutral terminal LE6-D09…D806 A59
Mechanical interlock LE3-D326…D806 A64Fitted as standard on starters LE6-D09 to D18
References
LE6-D12A04
LE6-D12A05
Schemes :page 24109/3
24109_Ver2.10-EN.fm/2 Schneider Electric
190
367
225
==
=
287
=
31
195c1
348
330
==
=
186 31
=
b (1
)
c1
== a-75
a-50
a
a+57,5
b-50
b+57
,5
b-75
==
4xM8x25
31
TeSys enclosed starters 2
Star-delta starters7.5 to 75 kW, with isolating device
LE3-D406 to D806
Knock-outs or blanking plugs for cable glands
LE6-D09 to D18 LE3-D326
c1Standard version 175.5Version A04 167Version A05 175.5
LE3- a b c1D406, D506 400 500 218D806 500 700 269
(1) + 14 mm with blanking plugs.
Type of enclosure At top At bottomPG ISO PG ISO
LE6-D09 to D18 2 x 13 or 2 x 16 or 2 x 20 I or 2 x 25 I or 2 x 13 or 2 x 16 or 2 x 20 I or 2 x 25 I or2 x 21 or 2 x 29 2 x 32 I or 2 x 40 I 2 x 21 or 2 x 29 2 x 32 I or 2 x 40 I
LE3-D326 1 x 21 1 x 32 I 2 x 13, 2 x 16 & 1 x 21 2 x 20 I, 2 x 25 I &1 x 32 I
LE3-D406 1 x 29 1 x 32 I 2 x 13, 2 x 21 & 1 x 29 2 x 20 I, 2 x 25 I & 1 x 32 I
LE3-D506 1 x 36 1 x 40 I 2 x 13, 2 x 29 & 1 x 36 1 x 40 I, 2 x 20 I & 2 x 32 I
LE3-D806 1 x 36 1 x 40 I 2 x 13 & 3 x 36 2 x 20 I and 3 x 40 I
Dimensions
References :pages 24108/2 and 24108/3
Schemes :page 24109/3
24109_Ver2.10-EN.fm/3Schneider Electric
A1
A2
– KM1
– KM3
– KM2
– KM1
l
– KM2
A1
A2
– KM3
– KM1
A1
A2
– KM2
– KM2
B
O
A
Q1Q1
A1
A2
– KM1
1314
– KM3
– KM2
– KM1
l
– KM2
A1
A2
– KM3
– KM1
A1
A2
– KM2
– KM2
B
A
Q1– F1
2122
– S1
– KM2
12
34
56
– KM3
12
34
56
– KM1
12
34
56
U1
V1
W1
U2
V2
W2
1 3 5
2 4 6
– Q1
1/L1
2
3/L2
4
5/L3
6 U1
V1
W1
U2
V2
W2
2 4 6
U1
V1
W1
U2
V2
W2
2 4 6
– KM2
12
34
56
– KM3
12
34
56
– KM1
12
34
56
U1
V1
W1
U2
V2
W2
1 3 5
2 4 6
– Q1
1/L1
2
3/L2
4
5/L3
6
TeSys enclosed starters 2
Star-delta starters7.5 to 75 kW, with isolating device
Recommended cabling forreversal ofmotor rotation(standard motor,viewed from shaftend).
Recommended cabling forreversal ofmotor rotation(standard motor,viewed from shaftend).
LE6-D09 to D18 LE6-D09 to D18
LE3-D326 to D806 LE3-D326 to D806
Connections A B220 V, 230 V, 240 V LE6-D09 and D12 L3 Neutral
LE6-D18 to LE3-D806 L3 Neutral terminal380 V, 400 V, 415 V, 440 V All products L3 L1Other voltages LE6-D09 to D18 Terminal 1 Terminal 2
LE3-D326 to D806 Direct connection
Schemes
Remotecontrol
References :pages 24108/2 and 24108/3
Dimensions :page 24109/2
24120-EN_Ver1.2.fm/2 Schneider Electric
References TeSys enclosed starters 2
Replacement parts for starterswithout isolating device
(1) Do not forget to order adaptation kit LAD-9091 or LAD-91810, depending on size.(2) Do not forget to order adaptation kit LAD-9092.(3) Sold in lots of 10.(4) LE1, LE2, LE3, LE4, LE6 or LE8.
Heads for Start and Stop/Reset pushbuttonsDescription For use on Unit
referenceWeight
kg
Flush, green “I” (1) LE1-D09...D35 ZB5-AA331 0.018
Projecting, red “O” (1) LE1-D09...D35 ZB5-AL432 0.019
Adaptation kit for head ZB5-AL432
LE1-D09 and D12 LAD-9091 0.002
LE1-D18...D35 LAD-91810 0.003
Heads for Reset pushbuttons
Flush, blue “R” (2) LE1-D09...D35 ZB5-AA0 0.022
+ ZBA-639 (3) 0.001
Adaptation kit for head ZB5-AA0 + ZBA-639
LE1-D09 and D12 LAD-9092 0.002
LE1 or LE2-D18...D35 LAD-91810 0.003
LE3, LE6, LE4 or LE8-D09...D35
LAD-9T4 0.004
Heads for selector switches
3 position stay put LE1-D09...D35 ZB5-AD3 0.024
2 position stay put LE1-D09...D35 ZB5-AD2 0.024
3 position spring return to centre
LE1-D09...D35 ZB5-AD5 0.024
Contact blocks
1 N/O spring return
LE1-D09...D35 ZEN-L1111 0.010
1 N/C spring return
LE1-D09...D35 ZEN-L1121 0.010
Mounting for contact block LE1-D09 and D12 LAD-90909 0.008
LEp-D18...D35 (4) LAD-91809 0.014
ZB5-AA331
5001
18_
1
ZB5-AL432
500
120_
1
LAD-9091
500
117_
1
ZB5-ADp
5001
19_1
ZEN-L1111
500
121_
1
LAD-91809
5001
22_1
24120-EN_Ver1.2.fm/3Schneider Electric
References TeSys enclosed starters 2
Replacement parts for starterswithout isolating device
Empty enclosures for D.O.L. starters without isolating deviceIntended usage Head(s) mounted
on coverReference Weight
kg
LE1-D09, D12 Without DE1-DS1A04 0.300
1 flush blue head “R” DE1-DS1A05 0.300
1 flush green head “I” DE1-DS1 0.3001 projecting red head “O”
1 flush blue head “R”1 switch
DE1-DS1A13 0.300
LE1-D18...D35 Without DE1-DS2A04 0.500
1 flush blue head “R” DE1-DS2A05 0.500
1 flush green head “I” DE1-DS2 0.500
1 projecting red head “O”
1 flush blue head “R”1 switch
DE1-DS2A13 0.500
DE1-DS1A04
8101
75
DE1-DS1A05
810
176
DE1-DS1
810
173
DE1-DS1A13
8101
78