Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved. Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved. 02_VRF Network Design 1
Transcript

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved. Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

02_VRF Network Design

1

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

2

Transmission line

2. Connectable to the Module Link network

(“Module link”)

・Outdoor Unit

1. Connectable to the LonWorks® - Network

(“transmission line”)

・Indoor Unit

・Outdoor Unit (Master)

・System Controller

・Touch Panel Controller

・Central Remote Controller

・Network Converter

-(for single split system)

-(for Group Remote Controller)

・Network Converter for LonWorks®

・Service Tool

・Web Monitoring Tool

・Signal Amplifier (*) * Design the signal amplifier after bring out

the transmission line

■ WIRING SYSTEM of VRF V-II

3. Connect for Remote control network

(“Remote controller line”)

・Wired Remote Controller

・Simple Remote Controller

・External Switch Controller

・Wireless Remote Controller

Module link

Remote controller link

VRF Network

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

3

Transmission Wiring Flow

Module link Network

Remote control Network

-Wired Remote controller connection-

-Simple Remote Controller connection-

-External Switch Controller connection-

LonWorks® Network - Connected product restrictions -

- Transmission line design -

- Signal amplifier connection -

- Terminal resistor connection -

- Network converter connection -

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

4

LonWorks® Network

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

5

Restriction to design of LonWorks® Network

■ MAXIMUM CABLE LENGTH

Maximum cable length (m)

VII V

Total (each VRF network system)

3,600 2,000

Total (each VRF network segment)

500 500

Between units 400 400

LonWorks® Network

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

6

Restriction to design of LonWorks® Network

Maximum connectable units (each VRF network system)

VII V

Outdoor unit 100 unit 100 count

Indoor unit 400 unit 400 unit

■ MAXIMUM CONNECTABLE UNITS

LonWorks® Network

Outdoor Units Units / Counts - explanation

VII V

only Master 1 unit 1 count

Master & Slave 1 2 units 4 counts

Master & Slave 1 & Slave 2

3 units 5 counts

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

7

Restriction to design of LonWorks® Network

■ two different limitations :

1. traffic limitation

-> max. 100 Outdoor Units (V-II-Series)

-> max. 100 Counts (V-Series)

2. network segment limitation

-> max. 64 units (nodes)

-> LonWorks® network regulation

LonWorks® Network

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

8

CENTRAL CONTROL

Product System

Controller

Touch Panel

Controller

Central Remote

Controller

Group Remote

Controller

Design

Product

Name

UTY-APGX UTY-DTGY

UTY-DTGG

UTY-DCGY

UTY-DCGG

UTY-CGGY

UTY-CGGG

Feature Indoor unit

1,600units

Outdoor unit :

400units

Indoor unit

400units

Outdoor unit

100units

Indoor unit

100 units

Indoor unit

96units

Controller Line up

LonWorks® Network

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

9

ADAPTOR CONVERTOR SERVICE &

MONITORING

Product Signal

Amplifier

Network

Convertor

Network

Convertor

for

LonWorks®

BACnet

Gateway

Service

Tool

WEB

Monitoring

Tool

Design

Product

Name

UTY-VSGX UTY-VGGX UTY-VLGX UTY-ABGX UTY-ASGX UTY-AMGX

Feature

Adaptor / Convertor / Service and Monitoring Line up

1.Convertor for

Split system

2.Convertor for

group remote controller

It uses when

system expand

more than 500m or

64 units

Connection to

LonWorks® BMS.

Diagnose for

service and

commissioning on

site

Monitoring the

operation status via

internet

Connection to

BACnet BMS.

LonWorks® Network

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

10

■ THE MAXIMUM CONNECTABLE UNITS

*1: Maximum 100 Refrigerant system.

*2: Maximum connectable indoor unit number per one Network Convertor. (Please check the System Diagram (Item:5-3-2) for proper configuration)

*3: A maximum of 4 Network Convertors for LONWORKS® can be connected to 1 BMS.

*4 For “16 / system”, the number of Network Convertor for LonWorks® and BACnet® Gateway is also included.

Model Necessary

Equipment

The number

that can be

connected

The number of

management

[Indoor units]

Connectable

outdoor unit

Controller Central

Controller

System Controller UTY-APGX USB Adaptor 1 / system 1600 (×4 VRF Network)

400 (×4 VRF Network)

Group Remote Controller UTY-CGG* UTY-VGGX 4 / UTY-VGGX 96 (2 refrigerants system)

6

16 / system

*4 Touch Panel Controller UTY-DTG* - 400

100 Central Remote Controller UTY-DCG* - 100

Adaptor Signal Amplifier UTY-VSGX - 8 / system - -

Convertor Network Convertor UTY-VGGX - 100 / system *1 - -

Network Convertor for

LonWorks® *3 UTY-VLGX - 1 / system 128 *2 100

BACnet® Gateway UTY-ABGX USB Adaptor 1 / system 1600 (×4 VRF Network)

400 (×4 VRF Network)

Service and

Maintenance

Service Tool UTY-ASGX USB Adaptor 1 / system

400 100

Web Monitoring Tool UTY-AMGX USB Adaptor 1600 (×4 VRF Network)

400 (×4 VRF Network)

LonWorks® Network

Using communication PCB Including product PCB Including USB Adaptor

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

11

Transmission line

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

12

Please refer to Design and Technical

Manual (6-4-3).

��■ TRANSMISSION CABLE SPECIFICATIONS

Use the shielded wire specified and always ground it both end. 22AWG (0.65mm) Level 4 cable with shielded

(National Electrical Manufacturers Association (NEMA) Differs from the Category 4 specification proposed by

the Electronic Industries Association / Telecommunication Industry Association (EIA/TIA)

● Reference specifications for transmission cable

LonWorks® Network Specifications

Transmission line

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

Transmission line

Case 2

Case 1

Do you use

Indoor Unit Automatic Address Setting?

Case 1 or Case2 Only Case 2

No Yes

Decide to use feature of Automatic Address

Setting depending on system design

Design this to make

the transmission line

short.

Design this to make each

refrigerant system

independent.

13

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

14

What’s Indoor Unit Automatic Address setting ?

Network between outdoor units (route between Z1 and Z2) is disconnected.

1. The outdoor unit seeks a response from all indoor units via the connected network.

2. The indoor units responds to the outdoor unit via the connected network.

3. Addresses are assigned to the indoor units recognized by the outdoor unit.

4. The outdoor unit network recovers after the Refrigerant System 1 addressing is finished.

Transmission line

Terminal

Register

• INDOOR UNIT AUTOMATIC ADDRESS SETTING (F3-11)

Case 1 Case 2

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

Case 2 : Enable Automatic Address setting

Case 1 : Disable Automatic Address setting

1

1

2

3

2

3

Caution

The address is not assigned properly. (Because all indoor units have been recognized as

Refrigerant System 1.)

*An error will occur if there are more than 48 indoor units.

*An error will not occur if there are 48 or fewer indoor units,

but the address will not be assigned correctly.

Note : Precautions during automatic Address

setting

The controller unit will not run. (Because all the refrigerant systems cannot be connected.)

When Automatic Address Setting of indoor unit is performed for

refrigerant system 2, controller unit connected to refrigerant

system 1 (system controller, touch panel, etc.) cannot control

refrigerant system 3 unit.

Transmission line

The address can be assigned.

(It will take about 10 to 30 min.)

15

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

16

Transmission wiring method Case 1

Transmission line

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

17

Transmission wiring method Case 2

Transmission line

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

18

■ Separation of Transmission line

Separate on the terminal for

transmission line.

Branch the transmission line as required by the

indoor unit side.

Transmission line

1 2 3

Connection of three or more lines may

cause poor communication for one

terminal. In this case, please use a

terminal box.

Bad Example

Do not use loop wiring.

This may lead to parts

damage

and erroneous

operation.

(Because the signal

will conflict and cause

the power to increase.)

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

19

Signal Amplifier

(UTY-VSGX)

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

20

LSI Micro-

computer LSI

Signal Amplifier (UTY-VSGX)

Regenerate signal output

■ Role of the Signal Amplifier (UTY-VSGX)

Communication reliability improvement

① Regenerate signal output

② Divide LonWorks® Network (Segment)

Remove noise

Regenerate

Signal Amplifier

Reception

Discards

defective data Transmission

Regenerate signal

No

Amp

Attenuation

Signal attenuation continues without a signal amplifier.

If the signal output entering the signal amplifier is

low, the microcomputer removes the noise

component from the signal. Therefore, the signal is

not output from the signal amplifier.

BAD Example

Remove

noise

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

21

Signal Amplifier (UTY-VSGX)

Divide into segments

VRF Network

VRF Network

■ Role of the Signal Amplifier (UTY-VSGX)

Communication reliability improvement

① Regenerate the signal output

② Divide LonWorks® Network (Segment)

・Insufficient Neuron chip drive

capacity

・Signal quantity increases

(signal opportunity) and possibility

of collision increases.

・The number of Neuron chip is kept

within capacity of drive.

・Possibility of collision is decreased.

This is because dividing into

segments decreases the number of

nodes within a segment.

Network

Segment 1

Network

Segment 1

Network

Segment 2

Network

Segment 3

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

22

Example 1

Confirm 1.

AB+BC+BD+DE+EF ≦ 500m

Confirm 2.

AC < 400m, AF < 400m

and CF < 400m.

①Signal Amplifier Installation Check Point

1. Make total transmission line length in each network segment 500 m or less.

2. Make the distance between units within 400 m.

Signal Amplifier (UTY-VSGX)

Example 2

Confirm 1.

AB+BC+BD ≦ 500m

DE+EF+EG ≦ 500m

Confirm 2.

AC < 400m, AD < 400m and CD<400m

DF < 400m, GF < 400m and DG<400m

GJ < 400m

JH < 400m

J

Example 2

Example 1

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

23

②Check Point for dividing the network into segments

The number of units included within each segment is 64 or less.

Note

Signal Amplifier (UTY-VSGX)

(1) Unit* means product connected for LonWorks® network directly.

(Group remote controller is not counted.)

(2) The signal amplifier is counted as 1 unit for each network segment.

Network segment 1

Number of unit *: 13

Network segment 2

Number of unit* : 64

Network segment 3

Number of unit* : 64

Network segment 4

Number of unit *: 64

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

24

Terminal Resistor

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

25

①The signal is reflected from the terminal device to become the noise component.

②If the reflected noise interferes with another signal, it disrupts the signal waveform.

③The disrupted waveform signal is not correctly recognized by the product.

In addition, since the output increases, there is a possibility the signal circuit board will be

damaged.

A terminal resistor to absorb the noise component is required to maintain overall network

signal reliability.

Be sure to set the terminal resistor according to specifications.

Set the terminal resistor for every network segment (NS).

● If terminal resistor is set in multiple devices, the overall communication system may be damaged.

● If terminal resistor is not set in a device, abnormal communication may occur.

Caution

Terminal Resistor

Terminal Resistor

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

26

5 cm 5 cm

Terminal resistor installation location

Terminal Resistor

SET 5 Terminal resistor Remarks

4

OFF Disable (Factory setting)

ON Enable -

1. Install in signal amplifier

2. Outdoor Dip Switch

Install 1 terminal resistor

for each segment.

Terminal resistor : ON

Terminal resistor : ON

Connect of Terminal resistor

Connect of Terminal resistor

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

27

Measure the resistance of the signal amplifier terminal

and the terminal of the indoor and outdoor units

connected farthest away from the device where

terminal resistor is measured.

A value from the table is displayed, depending on the

distance from the signal amplifier and the device where

the terminal resistor is set.

This value is an estimate.

Transmission cable connecting indoor units,

outdoor units, and signal amplifiers

Do not turn on the power if the resistance between the terminals of the transmission

cable is abnormal. Otherwise, the circuit board may be damaged.

Terminal Resistor

■ Confirmation

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

28

Network Convertor

(UTY-VGGX)

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

29

■ Network Convertor

① Group remote controller (UTY-CGGY) connection

② Single split, BIG MULTI connection

Max. connectable 4 Group Remote Controllers *)

Network Convertor (UTY-VGGX)

Up to a total of 16 Network Convertors (UTY-VGGX)

Central Remote Controller, Touch Panel Controllers,

Network Convertor for LonWorks® and BACnet ®

Gateway can be connected in a single VRF network

system.

*)2 refrigerant circuits can be covered by a single Network Convertor.

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

30

■ Network Convertor

① Group remote controller (UTY-CGGY) connection

② Single split, BIG MULTI connection

Max. connectable 16 single indoor units

Up to 100 network convertors can be

connected in one VRF network system.

* A single network convertor is considered as a single

refrigerant system, irrespective of the number of

connected single models.

Network Convertor (UTY-VGGX)

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

31

• Total remote controller cable length when connected to one converter 100m

Network Convertor (UTY-VGGX)

Maximum wiring length

Total length of group remote controller cable to convertor. 100m

Wiring Design

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

32

1. When Wired Remote Controller is supplied

Check the RC Number

*Connectable if RC number is the same as below

2. If it is not supplied or RC Number is different from

the above number Please purchase the following model Wired Remote

Controller

Network Convertor (UTY-VGGX)

Model name

UTB-*UB

Wiring Design

Caution Indoor units with G as the 4th digit of the model

name cannot be connected.

*Indoor units of 8 Room Multi cannot be connected.

Indoor units corresponding to Wired remote controller

(Indoor unit with supplied Wired remote controller

or with option setting for it)

・Connectable model

A U Y G 1 2 L V L A

・Connectable Wired Remote Controller

RC Number

AR-3TA**

Maximum wiring length

Remote controller to UTY – VGGX 100m

Indoor unit to UTY - VGGX 100m

Connect a single big multi system to a single

network convertor. Do not connect two big multi

systems, or a big multi system and a single model

system.

・Note

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

33

Module link Network

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

34

��■ TRANSMISSION WIRING SPECIFICATIONS

* Same as LonWorks® Network

Master Unit Slave Unit Slave Unit

A B C

Wiring rule :

AB ≦ 18 (m), BC ≦ 18 (m)

Module link Network

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

35

Module link Network

SET 3 Outdoor unit

Address Remarks

1 2

OFF OFF 0 Master unit only

OFF ON 1 Slave unit 1

ON OFF 2 Slave unit 2

ON ON - Forbidden

SET 3 Number of

connectable

outdoor units

Remarks 3 4

OFF OFF 0 Master unit only

OFF ON 1 1 Slave unit connected

ON OFF 2 2 Slave units connected

ON ON - Forbidden

Outdoor unit address setting

Number of slave units setting for outdoor unit*

* Master unit only

Dip switch settings

If the dip switches are not set correctly,

the initialization signal among the

outdoor units will not end, so the

outdoor units will not start operating.

Transmission cable connecting outdoor units in a refrigerant system

The resistance between the terminals of

the transmission cable is 45-60Ω.

This value is an estimate.

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

36

Remote control Network

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

37

INDIVIDUAL CONTROL

Product Wired Remote

Controller

Simple Remote

Controller

External Switch

Controller

Wireless Remote

Controller

Design

Product

Name

UTY-RNKY

UTY-RNKG

UTY-RNKYT

UTY-RSKY

UTY-RSKG

UTY-RHKY

UTY-RHKG

UTY-RSKYT

UTY-RHKYT

UTY-TEKX UTY-LNHY

UTY-LNHG

Feature Indoor unit

16 units

Indoor unit

16 units

Indoor unit

16 units

Air Conditioner

switching with

interlink to external

signal.

Controller Line up

Remote control Network

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

38

Remote control Network

MODEL TYPE CONNECT TO WIRE SIZE SPECIFICATIONS

Wired Remote

ControllerIndoor unit

Simple Remote

ControllerIndoor unit

Indoor unitRemote controller

cable0.33 mm

2 Shielded, Polar 3core

External input deviceExternal input

cable0.33 mm

2 Shielded, Polar 2core, Twisted pair

Sheathed vinyl cable, Polar 3core (Use shielded cable in accordance with local rules )

External Switch

Controller

Remote controller

cable *10.33 mm

2

■ Remote controller cable specification

Model The number that can be connected

Controller Individual

Controller

Wireless Remote Controller UTY - LNH* -

Wired Remote Controller UTY - RNK*

2 / Remote control group

Simple Remote Controller

(with operation mode)

UTY – RSK*

Simple Remote Controller

(without operation mode)

UTY – RHK*

External Switch Controller UTY – TEKX

■ THE MAXIMUM CONNECTABLE UNITS

*1) 10 m of Remote controller cable is included in product

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

39

WIRED REMOTE CONTROLLER (UTY-RNK*) (UTY-RNKYT)

SYSTEM DIAGRAM & WIRING DESIGN

Multiple Indoor Unit

Max. 16

A ≦500 m B+C ≦500 m

2 remote controller 1 remote controller

B C

A

D+E+F+G ≦500m

Y1 : 12V

Y2 : Signal

Y3 : COM

D E F G

SIMPLE REMOTE CONTROLLER (UTY-RSK*) / (UTY-RHK*) / (UTY-R*KYT)

Remote control Network

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

40

EXTERNAL SWITCH CONTROLLER (UTY - TEKX)

SYSTEM DIAGRAM & WIRING DESIGN

Less than 50 m Less than 50 m

Connection to external contacts

Wiring Design

System Diagram

Remote control Network

Copyrights 2010 Fujitsu General Limited, Sales Division, All rights reserved.

41

Thank you for listening