 Powell Lightning DC Switchgear DC SWITCHGEAR INCORPORAT ING THE HAWKER SIDDELEY NDC HIGH SPEED CIRCUIT BREAKER Powered by Safety ® INTRODUCTION Powell Lightning DC Switchgear incorporating the Hawker Siddeley NDC High Speed DC circuit breaker provides a reliable product with proven technology for application in your transit project. Building on the 80 year track record of DC design this switchgear solution oers optimal safety and the high speed performance you require. KEY FEATURES  • Prov en technology and minimal maintenance  • A long service life designed t o exceed 30 y ears  • Superior c ompact design c oncept  • High speed op eration  • Direct ove rload and electrical trip ping  • Simple and r eliable mechanism - no mechanical latch  • Ergonomic , intuitive truck isolation and interlo cking  • Enhanced electrical and mechanical endur ance  • Patente d arc transf er coil  • Fully bi-directional curre nt interruption  • Silver tungste n carbide main contacts  • Hard-wearing and long-life main contacts RATINGS Rated Voltage (VDC) 800 1600 Rated Service Current (A) 4000/6000/8000 4000/6000 Nominal Voltage (VDC) 750 1500 Power- Frequency Withstand Level (kV) 9 9 Rated Short-Time Withstand Current (kAp/kA) 100/72 250ms 100/72 250ms Rated Track- Time-Constant (ms) 100 100 Rated Short-Circuit Current (kAp/kA) 200/120 100/60 Bi-directional Critical Current (A) 25 25 Mechanical Endurance 20,000 operations 20,000 operations Breaking Characteristic High Speed High Speed Rated Insulation Voltage (kV) 1.8 3 Auxiliary Operating Supply (VDC) 110 1 110 2 1 - Other options available.
Transcript
  • Powell Lightning DC SwitchgearDC SWITCHGEAR INCORPORATING THE HAWKER SIDDELEY NDC HIGH SPEED CIRCUIT BREAKER

    Powered by Safety

    INTRODUCTION

    Powell Lightning DC Switchgear incorporating the Hawker Siddeley NDC High Speed DC circuit breaker provides a reliable product with proven technology for application in your transit project. Building on the 80 year track record of DC design this switchgear solution offers optimal safety and the high speed performance you require.

    KEY FEATURES

    Proven technology and minimal maintenance A long service life designed to exceed 30 years Superior compact design concept High speed operation Direct overload and electrical tripping Simple and reliable mechanism - no mechanical latch Ergonomic, intuitive truck isolation and interlocking Enhanced electrical and mechanical endurance Patented arc transfer coil Fully bi-directional current interruption Silver tungsten carbide main contacts Hard-wearing and long-life main contacts

    RATINGSRated Voltage (VDC) 800 1600Rated Service Current (A) 4000/6000/8000 4000/6000Nominal Voltage (VDC) 750 1500Power-Frequency Withstand Level (kV) 9 9Rated Short-Time Withstand Current (kAp/kA) 100/72 250ms 100/72 250msRated Track- Time-Constant (ms) 100 100Rated Short-Circuit Current (kAp/kA) 200/120 100/60Bi-directional Critical Current (A) 25 25Mechanical Endurance 20,000 operations 20,000 operationsBreaking Characteristic High Speed High SpeedRated Insulation Voltage (kV) 1.8 3Auxiliary Operating Supply (VDC) 1101 1102

    1 - Other options available.

  • Powered by Safety 10/2014 v2Publication No. 03085Powell Electrical Systems, Inc.8550 Mosley RoadHouston, Texas 77075713.944.6900

    Powell Canada Inc.53032 Range Road 263AAcheson, Alberta T7X 5A5780.948.3300

    Powell (UK) Ltd.Ripley RoadBradford, West Yorkshire BD4 7EH+44.(0).1274.734221

    [email protected]

    2014 Powell Industries, Inc.. all rights reserved.

    STANDARDS

    Circuit breaker enclosure has been subjected to an internal arc withstand test in accordance with the requirements of IEC 60694:2002 and IEC 62271:2003. The equipment has been designed to ANSI C37.14:2002, ANSI C37.16:2000, and ANSI C37.20.1:2002.

    DIMENSIONS AND FEATURES

    TYPICAL WEIGHTS INCLUDING CIRCUIT BREAKER

    800VDC 1600VDC4000A 1276 lbs 1364 lbs6000A 1320 lbs 1408 lbs

    1 - The arc transfer system prevents internal contamination of the circuit breaker compartment and cubicle.

    2 - The Cold Cathode Arc Chute Assembly (1) dissipates all arcs while the transfer coil (2) provides additional magnetic flux across the contact gap, assisting with the interruption of low currents that would lead to long arcing times.

    3 - Fixed Contact

    4 - Moving Contact Assembly

    5 - Primary Disconnects

    6 - The patented Magnetic Latch mechanism provides the primary means of high speed tripping of the circuit breaker. Working in conjunction with the Magnetic Actuator, the latch directly holds the circuit breaker contacts closed.

    7 - The Magnetic Actuator is based on a solenoid plunger, and provides the motion required to close the main contacts and to reset the latch device on tripping.

    8 - The uni-directional Direct Acting Release trips the circuit breaker when the current in the main circuit exceeds the overload setting.