    Extended Protection Features

    On the ADVC Controller

    With the flexVUE Operator Interface

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    2/19

    Schneider Electric 2 < AUTHOR >

    Extended Protection Features

    There are two Extended

    Protection features that can be

    enabled on an ADVC controller.

    1. Protection control settings per

    protection group.

    2. Individual Maximum Time setting for

    each protection trip that uses an

    inverse curve.

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    3/19

    Schneider Electric 3 < AUTHOR >

    Enabling the Extended Protection Features - OCP

    Extended Protection features are

    disabled by default and can be

    enabled individually.

    Extended Protection features can be

    enabled via the ADVCs Operator

    Interface in the Engineering Menu:

    Configuration Menu

    Feature Selection

    Protection

    Extended Standard Protection

    Maximum Time setting per protection

    curve

    PROTECTION

    Extnd Std Prot OFF

    PROTECTION

    Max Time/Curve OFF

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    4/19

    Schneider Electric 4 < AUTHOR >

    Enabling the Extended Protection Features - WSOS

    Extended Protection features are

    disabled by default and can be

    enabled individually.

    Extended Protection features can also

    be enabled via WSOS in Feature

    Selection.

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    5/19

    Schneider Electric 5 < AUTHOR >

    Protection Control Settings ON/OFF

    The existing ON/OFF controls for the

    Protection Control Settings are global.

    -Protection

    -Auto Reclose

    -Negative Phase Sequence Protection

    -Earth Fault Protection

    -Sensitive Earth Fault Protection

    i.e. Once configured they will apply

    regardless of which protection group

    is active.

    Extended Protection functionality

    will allow the ON/OFF status for these

    settings to be determined by the

    active protection group.

    OPERATOR CONTROLS

    Auto Reclose OFF

    OPERATOR CONTROLS

    E/F OFF, SEF OFF

    OPERATOR CONTROLS

    NPS OFF

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    6/19

    Schneider Electric 6 < AUTHOR >

    Changing Protection Groups

    Group A Group B

    When the Protection Group is changed, e.g. A to B,

    the protection control settings may also change if the

    DEFAULT settings for the selected group are different

    to the previously active settings.

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    7/19Schneider Electric 7 < AUTHOR >

    Default Protection Control Settings

    When Extended Protection isenabled, each protection group

    has its own DEFAULT ProtectionControl settings.

    These settings are referred to asnon-volatile as they will be retained

    in the protection group settingsdespite changes to the operationalsettings when their group is active.

    These settings can be viewed on theoperator interface in the Engineering

    MenuProtection Menu

    Protection Global

    Global Control

    The same options are available as for

    the Operator Settings.

    N.B. Protection OFF is included in theAuto Reclose ON/OFF field.

    GLOBAL CONTROL A

    Auto Reclose OFF

    GLOBAL CONTROL A

    NPS OFF

    GLOBAL CONTROL A

    E/F OFF, SEF OFF

    Auto Reclose ONProtection OFF

    NPS Trip Mode ON

    NPS Alarm Mode ON

    E/F ON, SEF OFF

    E/F ON, SEF ON

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    8/19Schneider Electric 8 < AUTHOR >

    Extended Protection on the Operator Interface

    PROTECTION GLOBAL

    Global control

    (Display, Copy, Trips to

    lockout, Seq reset time,

    Max time, Auto restore,Auto reclose, Protection

    OFF, NPS, E/F_ SEF)

    Global pickup

    (Current & mult for Phase,

    Earth, SEF, NPS)

    Fault reset

    (FR time, Reset Threshold

    Mult for Phase, Earth andNPS, Start at Rst

    Thresh/Pickup)

    PROT TRIP SETTINGS

    Trip 1, 2, 3, 4

    (Reclose time, Protection &

    reset curve for P, E, SEF,

    NPS)Single Shot

    (SS reset time, Protection

    & reset curve for P, E, SEF,

    NPS)

    Work Tag

    (Protection & reset curve

    for P, E, SEF, NPS)

    Under Over Frequency

    (Under, Over, Normal

    Close, Low V inhibit,

    Bushing)

    Under Over Voltage

    (Under, Over, Config)

    Loss of Phase

    (On/Off/Alarm, Voltage,

    Timeout)

    PROTECTION CONTROL

    Cold Load Pickup

    (On/Off, Time, Multiplier)

    Inrush Restraint

    (On/Off, Time, Multiplier)

    High Current Lockout

    (On/Off, Current, Trip)

    Dead Lockout On/Off

    Live Load Blocking On/Off

    Sequence Control On/Off

    DIRECTIONAL ELEMENT

    Directional Blocking

    (Phase, Earth, SEF, NPS,

    System Voltage, High Vzps

    Alarm, balance)Directional Protection

    (Phase, Earth, SEF, NPS,

    System Voltage, High Vzps

    Alarm, balance)

    PROTECTION MENU

    ENGINEER MENU

    PROTECTION MENU

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    9/19Schneider Electric 9 < AUTHOR >

    Default Settings in WSOS

    Settings

    applied here

    become the

    default

    settings forthat group

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    10/19Schneider Electric 10 < AUTHOR >

    Active Protection Control Settings

    Changing the active protection

    group causes the default

    protection control settings for

    that group to become active

    and appear on the Control page.

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    11/19

    Schneider Electric 11 < AUTHOR >

    Changing Active Protection Control Settings

    The active settings can be

    changed for operational

    purposes but this does not

    affect the default settings.

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    12/19

    Schneider Electric 12 < AUTHOR >

    Reinstating the Default Settings

    The next time Group A is

    made active, its default

    settings will become active

    again.

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    13/19

    Schneider Electric 13 < AUTHOR >

    Volatile and Non Volatile Settings

    Volatile

    Non Volatile

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    14/19

    Schneider Electric 14 < AUTHOR >

    Quick Keys

    Any changes made to the active

    settings using the Quick Keys will stay

    in force until:

    The Protection Group is changed.

    or

    The operator makes another

    change

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    15/19

    Schneider Electric 15 < AUTHOR >

    Maximum Time

    The second of the Extended

    Protection features changes the

    way the Maximum Time settingcan be used.

    Normally there is only one Maximum

    Time setting for each protection

    Group.

    Maximum Time is a Global setting

    which means that it applies to all trip

    settings in that group which use an

    inverse curve for timing.

    Extended Protection provides a

    separate Maximum Time setting for

    each inverse curve that has been

    applied. (Max 18)

    Extended Protection reduces the

    minimum value for Maximum Time

    settings from 2.0s to 0.2s.

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    16/19

    Schneider Electric 16 < AUTHOR >

    Extended Max Time per Curve OFF

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    17/19

    Schneider Electric 17 < AUTHOR >

    Extended Max Time per Curve ON

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    18/19

    Schneider Electric 18 < AUTHOR >

    Maximum Time Settings on the Operator Interface

    PROTECTION GLOBAL

    Global control

    (Display, Copy, Trips to

    lockout, Seq reset time,

    Max time, Auto restore,Auto reclose, NPS, E/F_

    SEF)

    Global pickup

    (Current & mult for Phase,

    Earth, SEF, NPS)

    Fault reset

    (FR time, Reset Threshold

    Mult for Phase, Earth andNPS, Start at Rst

    Thresh/Pickup)

    PROT TRIP SETTINGS

    Trip 1, 2, 3, 4

    (Reclose time, Protection &

    reset curve for P, E, SEF,

    NPS) P, E, NPS Max TimeSingle Shot

    (SS reset time, Protection,

    reset curve, SEF & Max

    Time for P, E, NPS)

    Work Tag

    (Protection, reset curve,

    SEF & Max time for P, E,

    NPS)Under Over Frequency

    (Under, Over, Normal

    Close, Low V inhibit,

    Bushing)

    Under Over Voltage

    (Under, Over, Config)

    Loss of Phase

    (On/Off/Alarm, Voltage,Timeout)

    PROTECTION CONTROL

    Cold Load Pickup

    (On/Off, Time, Multiplier)

    Inrush Restraint

    (On/Off, Time, Multiplier)

    High Current Lockout

    (On/Off, Current, Trip)

    Dead Lockout On/Off

    Live Load Blocking On/Off

    Sequence Control On/Off

    DIRECTIONAL ELEMENT

    Directional Blocking

    (Phase, Earth, SEF, NPS,

    System Voltage, High Vzps

    Alarm, balance)Directional Protection

    (Phase, Earth, SEF, NPS,

    System Voltage, High Vzps

    Alarm, balance)

    PROTECTION MENU

    ENGINEER MENU

    PROTECTION MENU

  • 7/28/2019 05 ADVC_206K_FV Extended Protection Features

    19/19

    Schneider Electric 19 < AUTHOR >

    Extended Protection Features - Summary

    Each Protection Group has its own

    default Protection Control settings

    which become active when thatProtection Group becomes active.

    An operator can change the active

    protection control settings but if the

    changed settings are different to the

    default setting for the active Protection

    Group they will only survive until:

    -The active Protection Group is changed.

    -Another setting change is made to the

    active settings.

    A separate Maximum Time setting can

    be configured for each trip curve. The minimum Maximum Time setting is

    0.2s.

    Extended Protection features are

    disabled by default.


Recommended