Extended Protection Features
On the ADVC Controller
With the flexVUE Operator Interface
7/28/2019 05 ADVC_206K_FV Extended Protection Features
2/19
Schneider Electric 2 < AUTHOR >
Extended Protection Features
There are two Extended
Protection features that can be
enabled on an ADVC controller.
1. Protection control settings per
protection group.
2. Individual Maximum Time setting for
each protection trip that uses an
inverse curve.
7/28/2019 05 ADVC_206K_FV Extended Protection Features
3/19
Schneider Electric 3 < AUTHOR >
Enabling the Extended Protection Features - OCP
Extended Protection features are
disabled by default and can be
enabled individually.
Extended Protection features can be
enabled via the ADVCs Operator
Interface in the Engineering Menu:
Configuration Menu
Feature Selection
Protection
Extended Standard Protection
Maximum Time setting per protection
curve
PROTECTION
Extnd Std Prot OFF
PROTECTION
Max Time/Curve OFF
7/28/2019 05 ADVC_206K_FV Extended Protection Features
4/19
Schneider Electric 4 < AUTHOR >
Enabling the Extended Protection Features - WSOS
Extended Protection features are
disabled by default and can be
enabled individually.
Extended Protection features can also
be enabled via WSOS in Feature
Selection.
7/28/2019 05 ADVC_206K_FV Extended Protection Features
5/19
Schneider Electric 5 < AUTHOR >
Protection Control Settings ON/OFF
The existing ON/OFF controls for the
Protection Control Settings are global.
-Protection
-Auto Reclose
-Negative Phase Sequence Protection
-Earth Fault Protection
-Sensitive Earth Fault Protection
i.e. Once configured they will apply
regardless of which protection group
is active.
Extended Protection functionality
will allow the ON/OFF status for these
settings to be determined by the
active protection group.
OPERATOR CONTROLS
Auto Reclose OFF
OPERATOR CONTROLS
E/F OFF, SEF OFF
OPERATOR CONTROLS
NPS OFF
7/28/2019 05 ADVC_206K_FV Extended Protection Features
6/19
Schneider Electric 6 < AUTHOR >
Changing Protection Groups
Group A Group B
When the Protection Group is changed, e.g. A to B,
the protection control settings may also change if the
DEFAULT settings for the selected group are different
to the previously active settings.
7/28/2019 05 ADVC_206K_FV Extended Protection Features
7/19Schneider Electric 7 < AUTHOR >
Default Protection Control Settings
When Extended Protection isenabled, each protection group
has its own DEFAULT ProtectionControl settings.
These settings are referred to asnon-volatile as they will be retained
in the protection group settingsdespite changes to the operationalsettings when their group is active.
These settings can be viewed on theoperator interface in the Engineering
MenuProtection Menu
Protection Global
Global Control
The same options are available as for
the Operator Settings.
N.B. Protection OFF is included in theAuto Reclose ON/OFF field.
GLOBAL CONTROL A
Auto Reclose OFF
GLOBAL CONTROL A
NPS OFF
GLOBAL CONTROL A
E/F OFF, SEF OFF
Auto Reclose ONProtection OFF
NPS Trip Mode ON
NPS Alarm Mode ON
E/F ON, SEF OFF
E/F ON, SEF ON
7/28/2019 05 ADVC_206K_FV Extended Protection Features
8/19Schneider Electric 8 < AUTHOR >
Extended Protection on the Operator Interface
PROTECTION GLOBAL
Global control
(Display, Copy, Trips to
lockout, Seq reset time,
Max time, Auto restore,Auto reclose, Protection
OFF, NPS, E/F_ SEF)
Global pickup
(Current & mult for Phase,
Earth, SEF, NPS)
Fault reset
(FR time, Reset Threshold
Mult for Phase, Earth andNPS, Start at Rst
Thresh/Pickup)
PROT TRIP SETTINGS
Trip 1, 2, 3, 4
(Reclose time, Protection &
reset curve for P, E, SEF,
NPS)Single Shot
(SS reset time, Protection
& reset curve for P, E, SEF,
NPS)
Work Tag
(Protection & reset curve
for P, E, SEF, NPS)
Under Over Frequency
(Under, Over, Normal
Close, Low V inhibit,
Bushing)
Under Over Voltage
(Under, Over, Config)
Loss of Phase
(On/Off/Alarm, Voltage,
Timeout)
PROTECTION CONTROL
Cold Load Pickup
(On/Off, Time, Multiplier)
Inrush Restraint
(On/Off, Time, Multiplier)
High Current Lockout
(On/Off, Current, Trip)
Dead Lockout On/Off
Live Load Blocking On/Off
Sequence Control On/Off
DIRECTIONAL ELEMENT
Directional Blocking
(Phase, Earth, SEF, NPS,
System Voltage, High Vzps
Alarm, balance)Directional Protection
(Phase, Earth, SEF, NPS,
System Voltage, High Vzps
Alarm, balance)
PROTECTION MENU
ENGINEER MENU
PROTECTION MENU
7/28/2019 05 ADVC_206K_FV Extended Protection Features
9/19Schneider Electric 9 < AUTHOR >
Default Settings in WSOS
Settings
applied here
become the
default
settings forthat group
7/28/2019 05 ADVC_206K_FV Extended Protection Features
10/19Schneider Electric 10 < AUTHOR >
Active Protection Control Settings
Changing the active protection
group causes the default
protection control settings for
that group to become active
and appear on the Control page.
7/28/2019 05 ADVC_206K_FV Extended Protection Features
11/19
Schneider Electric 11 < AUTHOR >
Changing Active Protection Control Settings
The active settings can be
changed for operational
purposes but this does not
affect the default settings.
7/28/2019 05 ADVC_206K_FV Extended Protection Features
12/19
Schneider Electric 12 < AUTHOR >
Reinstating the Default Settings
The next time Group A is
made active, its default
settings will become active
again.
7/28/2019 05 ADVC_206K_FV Extended Protection Features
13/19
Schneider Electric 13 < AUTHOR >
Volatile and Non Volatile Settings
Volatile
Non Volatile
7/28/2019 05 ADVC_206K_FV Extended Protection Features
14/19
Schneider Electric 14 < AUTHOR >
Quick Keys
Any changes made to the active
settings using the Quick Keys will stay
in force until:
The Protection Group is changed.
or
The operator makes another
change
7/28/2019 05 ADVC_206K_FV Extended Protection Features
15/19
Schneider Electric 15 < AUTHOR >
Maximum Time
The second of the Extended
Protection features changes the
way the Maximum Time settingcan be used.
Normally there is only one Maximum
Time setting for each protection
Group.
Maximum Time is a Global setting
which means that it applies to all trip
settings in that group which use an
inverse curve for timing.
Extended Protection provides a
separate Maximum Time setting for
each inverse curve that has been
applied. (Max 18)
Extended Protection reduces the
minimum value for Maximum Time
settings from 2.0s to 0.2s.
7/28/2019 05 ADVC_206K_FV Extended Protection Features
16/19
Schneider Electric 16 < AUTHOR >
Extended Max Time per Curve OFF
7/28/2019 05 ADVC_206K_FV Extended Protection Features
17/19
Schneider Electric 17 < AUTHOR >
Extended Max Time per Curve ON
7/28/2019 05 ADVC_206K_FV Extended Protection Features
18/19
Schneider Electric 18 < AUTHOR >
Maximum Time Settings on the Operator Interface
PROTECTION GLOBAL
Global control
(Display, Copy, Trips to
lockout, Seq reset time,
Max time, Auto restore,Auto reclose, NPS, E/F_
SEF)
Global pickup
(Current & mult for Phase,
Earth, SEF, NPS)
Fault reset
(FR time, Reset Threshold
Mult for Phase, Earth andNPS, Start at Rst
Thresh/Pickup)
PROT TRIP SETTINGS
Trip 1, 2, 3, 4
(Reclose time, Protection &
reset curve for P, E, SEF,
NPS) P, E, NPS Max TimeSingle Shot
(SS reset time, Protection,
reset curve, SEF & Max
Time for P, E, NPS)
Work Tag
(Protection, reset curve,
SEF & Max time for P, E,
NPS)Under Over Frequency
(Under, Over, Normal
Close, Low V inhibit,
Bushing)
Under Over Voltage
(Under, Over, Config)
Loss of Phase
(On/Off/Alarm, Voltage,Timeout)
PROTECTION CONTROL
Cold Load Pickup
(On/Off, Time, Multiplier)
Inrush Restraint
(On/Off, Time, Multiplier)
High Current Lockout
(On/Off, Current, Trip)
Dead Lockout On/Off
Live Load Blocking On/Off
Sequence Control On/Off
DIRECTIONAL ELEMENT
Directional Blocking
(Phase, Earth, SEF, NPS,
System Voltage, High Vzps
Alarm, balance)Directional Protection
(Phase, Earth, SEF, NPS,
System Voltage, High Vzps
Alarm, balance)
PROTECTION MENU
ENGINEER MENU
PROTECTION MENU
7/28/2019 05 ADVC_206K_FV Extended Protection Features
19/19
Schneider Electric 19 < AUTHOR >
Extended Protection Features - Summary
Each Protection Group has its own
default Protection Control settings
which become active when thatProtection Group becomes active.
An operator can change the active
protection control settings but if the
changed settings are different to the
default setting for the active Protection
Group they will only survive until:
-The active Protection Group is changed.
-Another setting change is made to the
active settings.
A separate Maximum Time setting can
be configured for each trip curve. The minimum Maximum Time setting is
0.2s.
Extended Protection features are
disabled by default.