Date post: | 20-Feb-2015 |
Category: |
Documents |
Upload: | mspiso2000 |
View: | 153 times |
Download: | 5 times |
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
1 Energy Conservation & Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
2 Energy Conservation & Management
ENERGY CONSERVATION & MANAGEMENT
TECHNICAL SESSION – VII
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
3 Energy Conservation & Management
Detailed Energy Audit Report on
11/0.4 kV Distribution Transformer and
33/11kV Power Transformer
of Pushkar, Ajmer
Er. R.N.Vaishnawa & Er. P.C. Tiwari
Definition & Description of terms
Primary winding: The winding where incoming power supply is connected. Usually this refers to High
Voltage side in distribution transformers
Secondary winding: the winding where the principal load is connected. Usually this refers to Low Voltage
side in Distribution transformers.
No load loss: The losses taking place in a transformer when only primary winding is energized and all
secondary windings are open. They represent constant losses in a transformer.
Dielectric loss: The losses taking place in a stressed dielectric medium (insulation) subjected to stress
reversals.
Iron losses: The losses taking place in the magnetic core. There are two types; hysterisis losses and eddy
current losses.
Hysteresis losses: This loss depends upon the area of the hysteresis loop, which is depending upon the
maximum flux density, the type of material and frequency. It is independent of the waveform
Eddy current losses in core: This is loss due to circulating currents induced by voltage in the thickness of
core laminations. It depends upon thickness of lamination, path resistance which is depended upon the type of
material, R.M.S. flux density i.e. waveform and square of frequency
Eddy losses in a conductor: For a thick conductor, the induced voltage within the conductor cross section
due to self linkage and due to current in other conductor varies. The difference in induced voltage in the local
path in the thickness of the conductor causes extra eddy current loss : This loss varies with square of current and
square of frequency.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
4 Energy Conservation & Management
Stray losses: All current dependant losses in a winding other than the basic I2R losses. Stray losses include
eddy loss in the conductor, eddy losses in structural paths in close proximity to outgoing conductor and the eddy
loss in general in the structural parts. In dry type transformers, the last two mentioned types of stray losses are
absent.
Form factor: It is the ratio of the r.m.s. value of a waveform to the average value over one half cycle. For a
sine wave the value of form factor is 1.11. For distorted waves with higher peak values, the form factor is
higher.
Harmonics: Frequencies other than the main fundamental frequency of current or voltage which are present in
a distorted wave as multiples of base fundamental frequency.
Ajmer Discom Profile
Ajmer Vidyut Vitran nigam Limited (ERSTWHILE RSEB) has been established under the Companies Act,
1956 by Govt. of Rajasthan. AVVNL has been created with the principal object of engaging in the business of
distribution and supply of electricity in 11 districts of Rajasthan viz., Ajmer, Bhilwara, Nagaur, Sikar,
Jhunjhunu, Udaipur, Banswara, Chittorgarh, Rajsamand, Dungarpur and Pratapgarh. The area of operation of
AVVNL is 87,256 sq km. The population in this area is 19.8 million as per 2001 census with population density
of 227 persons/sq km. The power supply in the AVVNL is managed by 9 distribution circles i.e. Ajmer,
Bhilwara, Nagaur, Udaipur, Chittorgarh, Banswara, Sikar, Rajsamand & Jhunjhunu. AVVNL has 3 Zones, 9
O&M Circles, 34 Divisions, 153 Sub-Divisions and 375 Sub Offices. The total consumers of various tariff
categories are around 2.95 million.
Inception Report
Distribution transformers are very efficient, with losses of less than 0.5% in large units. Smaller units have
efficiencies of 97% or above. It is estimated that transformer losses in power distribution networks are 15 billion
kWh i.e. 3% of the total electrical power generated in India. Reducing losses can increase transformer
efficiency. There are two components that make up transformer losses. The first is "core" loss (also called no-
load loss), which is the result of the magnetizing and de-magnetizing of the core during normal operation. Core
loss occurs whenever the transformer is energized; core loss does not vary with load. The second component of
loss is called coil or load loss, because the efficiency losses occur in the primary and secondary coils of the
transformer. Coil loss is a function of the resistance of the winding materials and varies withthe load on the
transformer.
In selecting equipments, one often conveniently avoids the concept of life cycle costing. But the truth is that
even the most efficient energy transfer equipment like a transformer, concept of life cycle cost is very much
relevant. The total cost of owning and operating a transformer must be evaluated, since the unit will be in
service for decades.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
5 Energy Conservation & Management
Estimation of transformer efficiency The total losses in a transformer at base kVA as well as at the actual
load are estimated. The losses in a transformer are as under.
1. Dielectric Loss
2. Hysteresis Losses in the Core
3. Eddy current losses in the Core
4. Resistive Losses in the winding conductors
5. Increased resistive losses due to Eddy Current Losses in conductors.
6. For oil immersed transformers, extra eddy current losses in the tank structure.
From the rated output and measured output, transformer efficiency is calculated as follows.
Reduction of losses due to improvement of power factor-
Transformer load losses vary as square of current. Industrial power factor vary from 0.6 to 0.8. Thus the loads
tend to draw 60% to 25% excess current due to poor power factor. For the same kW load, current drawn is
proportional to KW/pf. If p.f. is improved to unity at load end or transformer secondary, the saving in load
losses is as under.
Saving in load losses = (Per unit loading as per kW)2 X Load losses at full load X {(1/pf)2-1)} Thus, if p.f is 0.8
and it is improved to unity, the saving will be 56.25% over existing level of load losses. This is a relatively
simple opportunity to make the most of the existing transformer and it should not be missed. It should also be
kept in mind that correction of p.f downstream saves on cable losses, which may be almost twice in value
compared to transformer losses.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
6 Energy Conservation & Management
Core Material- Losses in Core:-
There are two important core materials used in transformer manufacturing. Amorphous metal and CRGO. It can
be seen that losses in amorphous metal core is less than 25% of that in CRGO.
The objective of this study is to find out how the technical losses varies with the % loading as well as
unbalancing and power factor in the 11/0.4kV Distribution Transformers and 33/11kV Power Transformers. The
area for case study has been choosen is the Pushkar Sub-station. The 33/11kV Substation at Pushkar (Ganaheda)
is having 4 nos. of 33/11kV Power Transformers of 3X3.15MVA + 1X1.5MVA Capacity. Total 9 nos. 11kV
feeders are emanating from these power transformers feeding the area.
• _ Transformer No.1 of 3.15MVA
o 11 kV Banseli feeder
o 11 kV Budha Pushkar
• _ Transformer No.2 of 3.15MVA
o 11 kV Mela Ground Feeder
o 11 kV Pushkar city Pushkar
• _ Transformer No.3 of 3.15MVA
o 11 kV Dev Nagar Feeder
o 11 kV Ganahera (Rural)
o 11 kV Kishanpura
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
7 Energy Conservation & Management
• _ Transformer No.4 of 1.5MVA
o 11 kV Leela Sevadi Feeder (24 Hrs.)
o 11 kV Ganahera (24 Hrs.)
The 33/11kV Sub-station is fed from 132/33kV MDSU Grid Sub-station, Ajmer.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
8 Energy Conservation & Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
9 Energy Conservation & Management
Case Study #1
For the 56 nos. DT’s studied, the total loss due to over/ under sizing and improper loading/ unbalancing as well
as poor power factor is 1.47LU per year. The Power saving is around 34kW. The CO2 emission saving shall be
around 300 tons per year. The national saving against power plant cost shall be Rs.27 Lacs.
If these transformers are replaced by appropriate size amorphous core distribution transformers, then 1.83 LU of
electrical energy can be saved. The CO2 emission saving shall be around 382 tons per year. The national saving
against power plant cost shall be Rs.35 Lacs.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
10 Energy Conservation & Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
11 Energy Conservation & Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
12 Energy Conservation & Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
13 Energy Conservation & Management
Case Study#2
A sample of 56 Transformers are studied for their phasewise % loading and neutral current due to unbalance
loading is measured. Neutral current flows in the neutral conductor having some resistance depending on the
size of the conductor. This current cause losses in the conductor in the form of heat and proportional to the
square of the neutral current.
The average value of neutral current in all 56 Transformers is found to be 15.4Amps. Assuming 500m length of
neutral conductor per transformer, the calculation for losses occurring is as follows:
15.4AX15.4AX0.9116 ohm/kmX56 Nos. of DT X 0.5 km/TransformerX50%(Distribution factor)=3.026kW
=3.026X8760 = 26514 kWh/annum
This can save 53 tons of CO2/annum.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
14 Energy Conservation & Management
As the Discom as a whole, if this figure is calculated, it can be million of tons of CO2/ nnum that can be saved
by proper balancing of transformers to some extent.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
15 Energy Conservation & Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
16 Energy Conservation & Management
Case Study #3
Power Transformer #1 for 11kV Banseli & Budha Pushkar Feeder of 3.15MVA The no-load loss is 3kW and
Copper loss is 16kW at unity power factor. The maximum efficiency of the transformer is achieved at the load
where no load loss and copper loss are equal i.e.
Loading for maximum efficiency of the transformer = (No load loss/Copper loss)1/2
For this transformer, the maximum efficiency is achieved at (3/16)1/2= 43.3% loading i.e.
1364kVA.
The loading pattern of this power transformer for 26-7-10 to 22-09-10 (1503 Hrs) is as follows-
It is found that the loading average loading on the transformer is 722kVA and the transformer is loaded for only
20-30% of its rate capacity. The technical loss of the transformer at 23% loading and 0.9 PF is 0.59%. If the
load of transformer #4 is connected with this transformer (225kVA) then the loading on this transformer shall be
950kVA, then loss of 1.5MVA Transformer will be saved which is equal to 1.9kWx8760 = 16644kWh per
annum. This can save 33 tons of CO2 per annum. Also this will improve efficiency of the existing 3.15MVA
Power Transformer.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
17 Energy Conservation & Management
Case Study #4
Power Transformer # 2 for 11kV Mela Feeder and Pushkar City Feeder of 3.15MVA
Capacity of Power Transformer # 2 is 3.15MVA. Two nos. 11kv Urban feeders emanates from this transformer
namely 11kV Mela Ground Feeder and 11kV Pushkar City Feeder. The no-load loss is 3kW and Copper loss is
16kW at unity power factor. The maximum efficiency of the transformer is achieved at the load where no load
loss and copper loss are equal i.e. Loading for maximum efficiency of the transformer = (No load loss/Copper
loss)1/2 For this transformer, the maximum efficiency is achieved at (3/16)1/2= 43.3% loading i.e. 1364kVA.
The loading pattern of this power transformer for 26-7-10 to 22-09-10 (1392 Hours) is as follows-
From the loading pattern, it is clear that the transformer is mainly have 70-80% loading for more than 45%
period and average loading on the transformer is 2125kVA and maximum load is 3600kVA.
The Technical losses at 0.9PF for 3.15MVA Power Transformer at 2125kVA (75%) loading is 0.56% while the
loss for 5MVA Transformer for 2125kVA(42.5%) loading is 0.42% i.e. an improvement of 0.14% improvement
in efficiency.
It is therefore proposed to augment the 3.15MVA Power transformer by 5MVA Power Transformer.
The total saving of Energy shall be ~34000kWh per year. It will save 68 ton of CO2 per annum.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
18 Energy Conservation & Management
Case Study # 5
Power Transformer #3 is 3.15MVA for 11kV Devnagar, Ganaheda and kishanpura feeder
Capacity of Power Transformer #3 is 3.15MVA. Three nos. 11kv Rural area feeders emanates from this
transformer. The no-load loss is 3kW and Copper loss is 16kW at unity power factor. The maximum efficiency
of the transformer is achieved at the load where no load loss and copper loss are equal i.e.
Loading for maximum efficiency of the transformer = (No load loss/Copper loss)1/2
For this transformer, the maximum efficiency is achieved at (3/16)1/2= 43.3% loading i.e.
1364kVA.
The loading pattern of this power transformer for 28-3-10 to 23-09-10 (4320 Hours) is as follows-
From the loading pattern, it is clear than for more than 11% of period, the Power Transformer is idle and around
3000kWh/annum are lost due to no load losses. This can be saved if GO switch is made OFF during idle period.
Operating the ransformer beyond 1364kVA is due to mismanagement of Block Supply given to rural areas for
3-phase pump sets. It is proposed that whenever 3-phase supply is given to 11kV kishanpura feeder than other
two feeders should not be operated in three phase block. For 31% time, the loadings are beyond the ideal
loading condition resulting into excess copper losses of 30,000 kWh/ annum. The total saving possible is
33,000kWh/ annum which can result into 66 tons of CO2 per annum.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
19 Energy Conservation & Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
20 Energy Conservation & Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
21 Energy Conservation & Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
22 Energy Conservation & Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
23 Energy Conservation & Management
Case Study # 6
Power Transformer #4 is 1.5MVA for 11kV Leela Sevadi & Ganaheda (24 Hrs. supply) feeder
Capacity of Power Transformer #4 is 1.5MVA. Two nos. 11kV 24 hours supply feeders namely Leela Sevadi
and Ganahera (U) feeders emanates from this transformer. The no-load loss is 1.9kW and Copper loss is 10kW
at unity power factor. The maximum efficiency of the transformer is achieved at the load where no load loss and
copper loss are equal i.e. Loading for maximum efficiency of the transformer = (No load loss/Copper loss)1/2
For this transformer, the maximum efficiency is achieved at (1.9/10)1/2= 43.59% loading i.e. 654kVA. The
loading pattern of this power transformer for Study period 25-July-10 to 23-09-10 (1490 hours) is as follows
It is evident from the loading pattern of the transformer that all the time, the transformer is underloaded and the
maximum loading on the transformer is 20% and mainly the % loading is 10 to 15%. This load can be shifted to
transformer # 1 of 3.15MVA which is also under loaded. The possible saving is due to saving of no-load losses
of this transformer and improving of efficiency of Transformer # 1. The total saving expected is
6650kWh/annum which can result into 33 tons of CO2 per annum.. This will also save the capital amount of
1.5MVA
Transformer.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
24 Energy Conservation & Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
25 Energy Conservation & Management
Energy Savings Opportunities on Transformers in Thermal Power Plant-
Case Study
Devendra Shringi [email protected]
Abstract
A Study on Transformers to find out the losses due to loading on transformers.
Out of 69 L.T. transformers based on loading record of few Months, 30 nos. heavily loaded transformers were
selected for study .And calculation has been done for Transformers Losses and the results are as follows:-
Total Losses in Transformers of one unit of 210 MW are = 687KW or 0.33% of 210MW
Contribution of Power Transformers in Losses per unit 210 MW = 659 KW
Contribution of Service (L.T.) Transformers in Losses per 210 Mw = 29 KW
Total Transformer Losses in Plant of 1240 MW = 4040 KW
Annual Amount Loss due to Transformer Losses which could have been sent out = Rs.6.7 crores /year
Overall Auxiliary Consumption of 1240 MW is 9.72 % and Excluding Power Transformer losses it is 9.39 %.
(A) Savings for 1240 MW due to reduced Station Transformer Losses by P.F. Improvement = RS. 4.20 Lac/year
(B) Savings for 1240 MW due to reduced Distribution Losses by P.F. Improvement = Rs.5.9 crores /year
By Station Transformers Loading Adjustment one no. of Station Transformer can be put-off that will reduce the
Total Losses of 44.50KW plus Service Transformers of EPT, WT, and DMT can also be put-off which will also
reduce 16KW Losses. And by selecting G.T. of 350 MVA its Loading will reduce to 60% .Thus Total Losses
reduction will be up to 136 KW.
(C) Overall by Optimization strategy Annual saving @Rs.2.13/-will is (2.13*325*24*136) Rs.23 lacs.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
26 Energy Conservation & Management
Expected Total yearly saving on Improving Power Factor and Transformer optimisation for 1240 Mw Power
Plant (A+B+C) = Rs.6.17 crore
Expected Total Saving by improving power factor for 1240 mw Power Plant = RS. 5.95 crores
Expected Total Investment including the installation = Rs. 1.19 crores
Simple Pay back Period = 65 days
Expected Total saving by improving power factor from .83 to .99 and loading optimization on transformers by
distribution companies on 1240 Mw = Rs. 13 crores/year
Key Words: Overall Transformer Losses, Reduction in Transformer Losses by Optimisation, Savings by
improving power factor
1.0 Introduction
1.1 General Plant details
Kota Thermal Power Station is first major coal power station of Rajasthan. Its present installed capacity is 1240
MW. It is located on the left bank of Chambal River at Kota. KTPS has established a record of excellence and
has earned meritorious productivity awards from the Ministry of Power, Govt. of India during
1984,1987,1989,1991 and every year since 1992-93 onwards. In 2008-09 its Gross Generation was 8874 MU at
94.76% PLF with Auxiliary Power consumption 9.37% and Sp. Oil consumption 0.43 ml/kWh.
1.2 Transformers
Types of Transformers:-
Transformers are classified as two categories: power transformers and distribution transformers.
Power transformers are used for transmission of power at high voltage i.e. 400 kV, 200 kV, 110 kV, 66 kV, 33
kV deployed for step-up and step down the power as per requirement.
Distribution transformers are used for distribution of power at low voltage as a means of end user connectivity
i.e. 11 kV, 6.6 kV, 3.3 kV, 440 V, 230 V.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
27 Energy Conservation & Management
2.0 Methods and Materials
2.1 Transformer losses and Efficiency
The efficiency varies anywhere between 96 to 99 percent. The efficiency of the transformers not only depends
on the design, but also, on the effective operating load.
Transformer losses consist of two parts: No-load loss and On-Load loss
1. No-load loss (also called core loss) is the power consumed to sustain the magnetic field in the transformer’s
steel core. Core loss occurs whenever the transformer is energized; core loss does not vary with load. Core
losses are caused by two factors: hysteresis and eddy current losses. Hysteresis losses occur due to the energy
loss by reversing the magnetic field in the core as the magnetizing AC rises and falls and reverses directions.
2. On-Load loss (also called copper loss) is associated with full-load current flow in the transformer windings.
Cooper loss is power loss in the primary and secondary windings of a transformer due to the resistance of the
windings. Cooper loss varies with the square of the load current. (P = I2R)
For a given transformer, the manufacturer, supply values for no-load loss, PNO-LOAD, and On-load loss, PLOAD.
The total transformer loss, PTOTAL, at any load level can then be calculated from:
PTOTAL = PNO-LOAD + (% Load/100)2 x PLOAD , Where transformer loading is known, the actual transformers loss
at given load can be computed as: No load loss + kVA Load 2 X (full load loss)
Rated kVA
Transformer Efficiency at Unity Power factor = {1-(Total Losses/%Loading*Rated KVA)*100
3.0 Observations and Measurements
3.1 Transformer Losses Calculation
A Study was done on transformers to find out the losses due to loading on transformers. Out of 69 transformers
based on loading record of few Months, 30 heavily loaded transformers were selected for study.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
28 Energy Conservation & Management
UNTI 7 LOAD CALCULATIONS AT 7.15PM
S.No SERVICES Load
KVA
RATED
KVA
%age
Loading
NO-LOAD
LOSS KW
LOAD
LOSS
TOTAL
LOSS* KW
Transform
er Eff.
1 AHT7A 296 1600 18.50 1.60 13.50 2.06 99.30
2 CTT7A 547 2000 27.35 1.90 15.00 3.02 99.45
3 CTT7B 649 2000 32.45 1.90 15.00 3.48 99.46
4 EPT7A 65 2500 2.60 2.20 20.00 2.21 96.59
5 EPT7B 160 2500 6.40 2.20 20.00 2.28 98.57
6 UST7B 333 2000 16.65 1.90 15.00 2.32 99.30
7 UST7A 353 2000 17.65 1.90 15.00 2.37 99.33
8 SSIVA/IVB 11564 50000 23.13 34.60 185.00 44.50 99.62
9 SST 5A 490 2500 19.60 2.20 20.00 2.97 99.39
10 SST 5B 319 2500 12.76 2.20 20.00 2.53 99.21
11 UAT7A 3904 15000 26.03 8.17 50.34 11.58 99.70
12 UAT7B 8228 15000 54.85 8.17 50.34 23.32 99.72
13 G.T.7 219640 250000 87.86 119.34 599.10 581.77 99.74
SUB-TOTAL 246548 684.39
CHP 338 2.42
TOTAL LOSSES 686.81
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
29 Energy Conservation & Management
UNIT 7 LOAD CALCULATIONS
S.
No
1
SERVICES
2
Load
KVA AT
2.30PM
3
Load
KVA AT
7.15PM
4
Load KW
AT
7.15PM
5
RATED
KVA
6
%
Loadi
ng
7=3/6
No-Load
LOSS
KW
8
LOAD
LOSS
9
TOTAL
LOSSES
KW
10
1 SSIVA/IVB 9136.00 11564.00 9621.25 50000.00 18.27 34.60 185.00 40.78
2 UAT7A 7884.00 3904.00 3162.24 15000.00 52.56 8.17 50.34 22.08
3 UAT7B 6630.00 8228.00 6664.68 15000.00 44.20 8.17 50.34 18.00
4 GEN.TRANS. 218000.0 219640.00 210000.00 250000.00 87.20 119.34 599.10 574.89
SUB-TOTAL 23650.0 23696.00 19448.17 TOTAL
LOSS
655.74
CHP 338.00 338.00 287.30
TOTAL 23988.0 24034.00 19735.47
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
30 Energy Conservation & Management
STATION TRANSFORMERS
S. No. Unit No. Unit Cap. Unit Transf. Cap. Input/Output Volt. Make
1 Unit #1 110 MW 50 MVA 220/7/7 KV Crompton Bombay
2 Unit #2 110 MW 50 MVA 220/7/7 KV Crompton Bombay
3 Unit #3 210 MW 50 MVA 220/7/7 KV BHEL Bhopal
4 Unit #4 210 MW 50 MVA 220/7/7 KV TELK Kerala
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
31 Energy Conservation & Management
UNIT AUXILIARY TRANSFORMERS
S. No. Unit No. Unit Cap. Unit Transform Cap. Input/Output Voltage Make
1 Unit #1 110 MW 15 MVA 11/7 KV BHEL Jhansi
2 Unit #2 110 MW 15 MVA 15.75/7 KV BHEL Jhansi
3 Unit #3 210 MW 2*15 MVA 15.75/7 KV BHEL Jhansi
4 Unit #4 210 MW 2*15 MVA 15.75/7 KV BHEL Jhansi
5 Unit #5 210 MW 2*15 MVA 15.75/7 KV Bharat Bijlee Mumbai
6 Unit #6 195 MW 2*15 MVA 15.75/7 KV BHEL Jhansi
7 Unit #7 195 MW 2*15 MVA 15.75/7 KV BHEL Jhansi
GENERATOR TRANSFORMERS
S. No. Unit No. Unit Cap. Unit Transform Cap. Input/Output Voltage Make
1 Unit #1 110 MW 125 MVA 11KV/240 KV BHEL Jhansi
2 Unit #2 110 MW 125 MVA 15.75KV/240 KV BHEL Jhansi
3 Unit #3 210 MW 230 MVA 15.75KV/240 KV BHEL Jhansi
4 Unit #4 210 MW 250 MVA 15.75KV/240 KV BHEL Jhansi
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
32 Energy Conservation & Management
5 Unit #5 210 MW 250 MVA 15.75KV/240 KV Bharat Bijlee Mumbai
6 Unit #6 195 MW 250 MVA 15.75KV/240 KV BHEL Jhansi
7 Unit #7 195 MW 250 MVA 15.75KV/240 KV BHEL Jhansi
TABLE OF SELECTED TRANSFORMERS FOR ANALYSIS
S.
No
SERVICES AV.
LOAD
AMP.
Load
KVA
RATED
KVA
%age
Loading
NO-LOAD
LOSS KW
LOAD
LOSS
TOTAL
LOSS*
KW
Transfo
rmer
Eff.
1 SST- 1A 60.00 686.00 1600.00 42.88 1.60 13.50 4.08 99.41
2 SST- 1B 65.00 743.00 1600.00 46.44 1.60 13.50 4.51 99.39
3 BCW-1 45.00 514.00 1600.00 32.13 1.60 13.50 2.99 99.42
4 SST II A 55.00 629.00 2000.00 31.45 1.90 15.00 3.38 99.46
5 Compressor IIA 35.00 400.00 1600.00 25.00 1.60 13.50 2.44 99.39
6 EPT3C 50.00 572.00 1600.00 35.75 1.60 13.50 3.33 99.42
7 EPT3A 25.00 286.00 1600.00 17.88 1.60 13.50 2.03 99.29
8 EPT4C 25.00 286.00 1600.00 17.88 1.60 13.50 2.03 99.29
9 Compressor IIA 20.00 229.00 1600.00 14.31 1.60 13.50 1.88 99.18
10 SST II B 55.00 629.00 2000.00 31.45 1.90 15.00 3.38 99.46
11 AHT II B 40.00 457.00 1600.00 28.56 1.60 13.50 2.70 99.41
12 UST5A 25.00 286.00 1600.00 17.88 1.60 13.50 2.03 99.29
13 SSTIIIB 25.00 286.00 2000.00 14.30 1.90 15.00 2.21 99.23
14 Const. Supply 20.00 229.00 1600.00 14.31 1.60 13.50 1.88 99.18
15 SST4A 25.00 286.00 2000.00 14.30 1.90 15.00 2.21 99.23
16 SST4B 30.00 343.00 2000.00 17.15 1.90 15.00 2.34 99.32
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
33 Energy Conservation & Management
17 EPT 6B 45.00 514.00 1600.00 32.13 1.60 13.50 2.99 99.42
18 CT-6A 40.00 457.00 1600.00 28.56 1.60 13.50 2.70 99.41
19 CHP-IIA 20.00 229.00 2000.00 11.45 1.90 15.00 2.10 99.08
20 CHP-IIIA 40.00 457.00 2000.00 22.85 1.90 15.00 2.68 99.41
21 WT-IIA 40.00 457.00 2000.00 22.85 1.90 15.00 2.68 99.41
22 AHT7A 21.00 247.00 1600.00 15.44 1.60 13.50 1.92 99.22
23 CTT7A 47.00 547.00 2000.00 27.35 1.90 15.00 3.02 99.45
24 CTT7B 56.00 649.00 2000.00 32.45 1.90 15.00 3.48 99.46
25 EPT7A 6.00 73.00 2500.00 2.92 2.20 20.00 2.22 96.96
26 EPT7B 9.00 108.00 2500.00 4.32 2.20 20.00 2.24 97.93
27 UST7B 56.00 650.00 2000.00 32.50 1.90 15.00 3.48 99.46
28 UST7A 53.00 602.00 2000.00 30.10 1.90 15.00 3.26 99.46
29 SST 5A 39.00 455.00 2500.00 18.20 2.20 20.00 2.86 99.37
30 SST 5B 38.00 427.00 2500.00 17.08 2.20 20.00 2.78 99.35
TOTAL
LOSSES
81.85
4.0 Results and Discussions
4.1 Power Factor Calculations
KVAr required = P(Kw)(tan 01 – tan 02)
COS o1 = 0.83 COS o2 = 0.99 KVAr rating = 10462 kvar
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
34 Energy Conservation & Management
BEFORE CAPACITOR BANK
Auxiliary Load = 19740 KW; Power Factor = 0.83; KVA LOAD = 24034
KVAr = SQRT(240342 – 197402) = 13710 KVAr
AFTER INSTALLING CAPACITOR BANK
Auxiliary Load = 19740 KW; Power Factor = 0.99;
KVAr = 13710 KVAr – 10462 KVAr (Proposed Bank) = 3248 KVAr
KVA Load = SQRT (197402 + 32482 ) = 20005
Reduction in KVA Load = 24034 – 20005 = 4029 KVA
Loading on STATION TANSFORMER after proposed reduction = 9136 -4029 = 5107 KVA
% Loading of STATION TRANSFORMER = (5107/50000)*100 = 10.21%
Losses of STATION TRANFORMER after Power Factor correction = 34.6 + (5107/50000)2 * 185 = 36.52 KW
Reduction in STATION TRANSFORMER Losses after Power factor correction = 40.78 – 36.52 = 4.26 KW
Saving Potential = 4.26 * 24 * 325 * 2.13 = Rs. 71000.00 /year/210MW
(A)Saving Potential for 1240 MW = RS. 4.20 Lacs/year
Reduced current = 4029/6.6*1.732 = 352 Amp.
Reduction in Distribution losses = 352*352*R WATTS
Distribution Losses before Power Factor correction= (24034/1.732*6.6)2*R
% Reduction in Distribution Losses = (352*352*R / (24034/1.732*6.6)2*R)*100 = 2.8%
Saving Potential = .028 * 19740 * 24*325 *2.13 = Rs. 1 crore/year/210MW
(B)Saving Potential for 1240 MW = (1/210)*1240=Rs.5.9 crores /year
Total Annual Savings for 1240 MW Generation (A+B) = Rs 5.942 crores
Expected Annual Saving by Distribution Company @Rs.4.5/unit will be Rs. 1.94 crores/210mw
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
35 Energy Conservation & Management
Expected Annual Saving by Distribution Company for 1240 Mw power plant is Rs. 11.46 crores.
Expected Total year saving by Improving the Power Factor for 1240 Mw Power Plant (A+B) = Rs.5.94 crore
Expected Total Investment including the Capacitor Bank installation = Rs. 1.19 crores
Simple Pay back Period = 70 days
4.2 Transformers Losses Calculations and the results are as follows:-
Total Losses in Transformers of one unit of 210 MW are = 687KW or 0.33% of 210MW
Contribution of Power Transformers in Losses per unit 210 MW = 659 KW
Contribution of Service (L.T.) Transformers in Losses per 210 Mw = 29 KW
Total Transformer Losses in Plant of 1240 MW = 4040 KW
Annual Amount Loss due to Transformer Losses which could have been sent out = Rs.6.7 crores /year
Transformer Losses contributes to share in Auxiliary power Consumption = 3.5 %
Overall Availability of Plant has been considered 325 days in a year
Overall Auxiliary Consumption of 1240 MW is 9.72 % and Excluding Power Transformer losses it is 9.39 %.
By Station Transformers Loading Adjustment one no. of Station Transformer can be put-off that will reduce the
Total Losses of 44.50KW plus Service Transformers of EPT, WT, and DMT can also be put-off which will also
reduce 16KW Losses. Thus Total Losses reduction will be up to 60 KW.
By selecting G.T. of 350 MVA its Loading will reduce to 60% and 76KW Transformer Losses will also reduce.
(C)Overall by Optimization strategy Annual saving @Rs.2.13/-will be (2.13*325*24*136)Rs.23 lacs.
Expected Total yearly Saving on Improving Power Factor and Transformer optimisation for 1240 Mw Power
Plant(A+B+C) = Rs.6.17 crore
Expected Annual Saving by Distribution Company on Improving Power Factor and Transformer optimisation
for 1240 Mw power plant is Rs. 13 crores
5.0 Conclusion
5.1 Recommendations
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
36 Energy Conservation & Management
1) Equal loading shall be done on Service Transformers shall be done to avoid under loading and overloading
2) The transformers at minimum loading shall be replaced from high rated capacity to low required capacity or
shall be switched off by transferring that load on other transformer to avoid losses and maintenance cost.
3) Routine and Preventive maintenance of transformers shall be carried out to avoid tripping.
4) By load analysis - Total losses can be reduced which will reduce the Overall Auxiliary Consumption of
KTPS, and more power will be available to fulfil the gap between demand and supply.
5) Two transformers operating in parallel, should be technically identical in all aspects and more important both
should have the same impedance level .This will minimize the circulating current between transformers.
6)Where the load is fluctuating in nature, it is preferable to have more than one transformer running in parallel,
so that the load can be operated close to the maximum efficiency range by this operation.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
37 Energy Conservation & Management
6.0 References
• The following books, Literature and websites were referred in preparing this report:-
• Technical Specification Sheets of Transformers
• Tests Reports of Transformers
• Website of RRVUNL
• Guide Books for National Certification Examination on Energy Audit and Energy Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
38 Energy Conservation & Management
Experimental Investigation & Analysis to Reduce Boiler Tube Failure in
Thermal Power Plant.
Amol M. Andhare
Assistant Professor in Industrial Engg.,SRKNEC, Nagpur
Bhushan V. Lande,
Lecturer in Mechanical Engg. , PCE, Nagpur
Abstract
Boiler tube failures continue to be the leading cause of forced outages in fossil-fired boilers. To get boiler back
on line and reduce or eliminate future forced outages due to tube failure, it is extremely important to determine
and correct the root cause. Experience shows that a comprehensive assessment is the most effective method of
determining the root cause of a failure. In the modern World, requirement of power has become necessity for
day to day activity. Today’s power generation in the Country is dominated by thermal power plants to the extent
of 65%. Boiler tube failures are conditions that utilities have been battling since the day boilers were invented.
They amount to millions of dollars of lost generation and anything done in this field to aid root cause and
solution determination would be of great benefit to the utility industry. Hence availability of boiler is very much
essential for thermal power generating stations. One of the main reasons for boiler forced outages is boiler tube
leakage. The plan was to carry out the experimental investigation and analysis of the boiler tube failure, and
then run experiments with different power plants and failure techniques until it was considered “effective”.
Improvements between the tubes failure could be measured and recommendations made to the management.
This paper covers the major reason of tube Leakages and recommended remedies to avoid the same.
Index term: leak detection; boiler tube failure root cause analysis system; solution determination; failure
mechanism; physical failure appearance; Knowledge-based cause and effect diagrams; Koradi Thermal Power
Station, Nagpur, Maharashtra, India.
Keywords: Boiler failures; Economizer tube; Corrosion; Failure analysis; Metallurgical examination, Boiler
tube leakage, experimental investigation & analysis, power generation unit.
Problem Identification
In Present Work, data of boiler tube Failure at Koradi thermal power station Collected for last ten years which is
given below. From above data of boiler tube failure shows that maximum tube failure occurs in economizer and
reheater, in reheater section most of the boiler tube failure occurs due to short term overheating and long term
overheating. An accurate analysis of the deposits indicates the source of the problem and the steps needed for
correction. Metallographic analyses are useful, at times, in confirming whether a short- or long-term exposure to
overheating conditions existed prior to failure. Such analyses are helpful also when metal quality or
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
39 Energy Conservation & Management
manufacturing defects are suspected, although these factors are significant only in isolated instances. If the
problem is remains as it is then boiler performance will affect and result in following factors.
Improper availability
Increased forced outage costs.
More cost to repair
Minimum component life
Repeated root cause analysis
In determinant commonalities across the boiler fleet
Repeated Plan for future outages
Please refer table below for the data collection of boiler tube failure. Tube Failure instances from 1994-1995 to
2008-2009
UNIT
NO. ECO
WATER
WALL CAGE PRISH/H
PLATEN
S/H
SEC
S/H R/H TOTAL
1 31 3 6 9 NIL 7 20 76
2 22 2 6 16 NIL 7 21 74
3 14 10 7 7 1 13 10 62
4 16 8 2 3 9 12 12 62
5 16 15 3 5 NIL 4 9 52
6 4 22 4 1 NIL 3 17 51
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
40 Energy Conservation & Management
7 18 16 3 4 NIL 0 12 53
Table 1 Tube Failure instances from 1994-1995 to 2008-2009.
Introduction
The failure of industrial boilers has been a prominent feature in fossil fuel fired power plants. The contribution
of one or several factors appears to be responsible for failures, culminating in the partial or complete shutdown
of the plant. The use of high sulfur or/and vanadium-containing fuel, exceeding the design limit of temperature
and pressure during operation, and poor maintenance are some of the factors which have a detrimental effect on
the performance of materials of construction. A survey of the literature pertaining to the performance of steam
boilers during the last 30 years shows that abundant cases have been referred to concerned with the failure of
boilers due to fuel ash corrosion, overheating, hydrogen attack, carburization and decarburization, corrosion
fatigue cracking, stress corrosion cracking, caustic embrittlement, erosion, etc. Corrosion problems in boiler
tubes arisen due to overheating are quite common. This mode of failure is predominantly found in superheaters,
reheaters and water wall tubes, and in the result of operating conditions in which tube metal temperature
exceeds the design limits for periods ranging from days to years. The phenomenon of overheating is manifested
by the presence of significant deposits, which impart a reduction in water flow and excessive fire-side heat
input. Due to this rise in temperature, steel loses its strength, causing rupture or bulging of the tube due to
internal pressure. In a recent investigation. The failures have been attributed to accelerated corrosion, hydrogen
attack and overheating. In another study, corrosion of stainless superheater tubes occurred due to carburization
resulting in intergranular wastage of steel near the exposed surface. The causes of the majority of failures are
attributed to the upset in water quality and/or steam purity. The mechanisms of failures due to short term
overheating & long term overheating. This paper presents the results of two separate investigations carried out
to determine the causes of failure of boiler tubes of Koradi thermal Power station and Desalination Plants. The
main aim of this paper to investigation and acquaint the operation and maintenance personnel with the different
corrosion modes involved in failures of boiler tubes due to short term overheating & long term overheating, and
to suggest some measures for preventing the recurrence of such failures.
The objectives of today for any power plants are to increase the availability, efficiency and reliability of power
generating systems. Boilers are considered heart of steam and power generation systems. Unpredictable failures
in boilers can bring down operation of power and steam generation to a halt for many days based on the severity
of failure / damage.
Proper operation and maintenance of boilers can ensure prolonged and safe operations of the power / steam
generation systems. However, during downtime of these equipment, inspection and repair at the fastest possible
time play a major role in bringing back the power and generation systems. Inspection and repair time are very
crucial as the failure down time of boilers directly affect other dependent plants in terms of supply of electric
power and utility steam.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
41 Energy Conservation & Management
Koradi Thermal Power Station is the plant operated by Maharashtra State Power Generation Co. Ltd. Koradi
Thermal Power Plant is 8 Km away from Nagpur. Total capacity of plant is 1110 MW. Plants consist of 7 units,
4 units of 120 MW & 3 units of 210 MW. The Boilers are used in power plant supplied by ABL & BHEL. The
boiler used as front fired & corner fired. The material used for boiler tube is SA 210 T1 & SA213 C22 as per the
unit capacity. In Koradi Thermal Power Plant boiler tube failure is the main reason for boiler forced outages. In
this paper an attempt is being made to present failure analysis of boiler, corrective methods followed and
inspection and repair execution to bring the boilers back to operation at the shortest possible time.
Brief Description of Failure
The boiler had tripped on high furnace pressure caused due to water leak from the riser furnace water wall tube.
On opening the boiler furnace chamber, the chamber was found filled with water. Furnace water wall tube
facing the fire side of the chamber was found leaking. Two of the tubes were found ruptured opened up and two
tubes were found with pinhole leak. The location of the rupture / pin holes is as shown in the layout of the
furnace chamber.
Graph 1 Tube Failures (Causewise)
Graph 2 Tube Failures (Areawise)
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
42 Energy Conservation & Management
Types Of Boiler Tubes Failure
State of the art materials evaluation techniques support reliability engineering efforts to maintain and improve
overall plant performance. Materials failure analysis is a specialized, but important, part of the systems
approach to plant reliability. Frequently, materials failure types is the first step on the path of determining the
root cause failure mechanisms.
1 Stress Rupture
The term “overheating” failure often misused but generally means the failure resulting from operation of a tube
higher than expected in design selection of the tube steel for a period of time sufficient to cause a stress rupture
failure. Time and temperature is an important factor and these types of failure are often called “short term and
long term overheating” failures.
1.1 Short Term Overheating
A short term overheating is one in which a signal indicates exposes the tube steel to an extensively high
temperature (hundred of degree above) to the point where the deformation of the yielding occurs.
Figure 1 Failure due to Short term overheating.
1.2 Long Term Overheating
Long term overheating Failures results from a relatively continuous extended period of slight overheating, a
slowly increasing level of temp or stress. Accumulation from several periods of excessive overheating. Metal
degradation and permanent deformation will occur with time depending on the actual temperature & stress
levels. Figure 2 shows the pin holes on failure boiler tube, this feature just similar to failure occur in long term
overheating.
Figure 2 Failure due to long term overheating
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
43 Energy Conservation & Management
2 Dissimilar metal Weld
Dissimilar metal weld (DMW) failures between carbon steels and stainless steels occur in many industrial
applications. These failures are generally attributed to the very sharp changes in composition and corresponding
properties which occur along the fusion line of the weld and the formation of locally high stresses associated
with a thermal expansion mismatch between the carbon steel and stainless steel.
Similarly the other types of boiler tube failure are
3 Water side corrosion:-
Caustic gouging
Hydrogen damage
Acid Phosphate Corrosion
Pitting Corrosion
Graphitization
Stress Corrosion Cracking
4 Fire side corrosion
Coal Ash
Oil Ash
Furnace wall Corrosion
Exfoliation
5 Erostion
Fly Ash erosion
Soot blower erosion
Coal particle erosion
Falling slag damage
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
44 Energy Conservation & Management
6 Fatigue
Thermal Fatigue
Corrosion Fatigue
Rubbing of tubes
7 Lack of quantity control
Chemical cleaning damage Maintenance damage Material Flaes & Welding Flaws
Selection Of Factor And Observation
The below mention table is the total no of observation of boiler tube failure. Tube Failure instances from 1994-
1995 to 2008-2009. Refer table 1 for detail observations.
Eco
Water
Wall Cage Prish/H
Platen
S/H
Sec
S/H R/H
121 76 31 45 10 46 101
Table 2 Total no of boiler tube failure.
Graph 3 Total no of boiler tube failure (1994-95 to 2008-09)
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
45 Energy Conservation & Management
Methodology
Boiler tube failures continue to be the number one cause of forced outages at power generating stations. Great
strides are taken to identify where tubes are wearing so that preventative actions can be taken to avoid failures
during peak operation, but failures still continue to occur. To operate at peak capacity, a plant needs to find
ways to avoid tube failures, as well as to recover from them quickly when they caused forced outages. Fossil
fired boilers of all sizes continue to experience boiler tube failures and if the boiler tube root cause and scope of
damage is not identified repairs will be incomplete and worse a dangerous condition may exist. AIS
Metallurgical Testing has a decade of experience with boiler tube failures including steam drums and water
drums (mud drums) as well as boiler headers and economizer tubes. After identifying failure on tube sample,
testing of failure tube sample was carried out in Metallurgy department of VNIT NAGPUR.
Experimental investigation & analysis were carried out as per Indian Boiler Regulation act 1950.
Testing Of Boiler Tubes
A tube testing system consists of two subassemblies, the probe and the applicator. The probe uses a stack of
Belleville style washers that when compressed allow the locking fingers to relax and the probe to be inserted
into the tube. Once the probe is placed in the correct location using the applicator, the Belleville style washers
are allowed to expand, locking in the fingers and engaging the urethane seals. As the water fills the tube, the air
is pushed through a bleed hole in the mandrel of the probe. The bleed hole leads to a chamber in the top of the
probe that contains a plastic ball. The ball floats on water and as the chamber fills, the ball seals off the leak path
and the tube can then be pressurized and the test performed. Once the test is complete, the water is drained and
using the applicator, the probe is removed from the tube.
Types Of Boiler Tube Testing
1Metallographic Test: - One of the failed tube ends supplied to CTL was sectioned longitudinally through the
groove and crack for metallographic examination. The presence of thick black oxide on the groove and parts of
the crack surface, as well as lack of deformation in the microstructure, confirmed that corrosion was the cause of
the grooving. Deformation of the microstructure at the crack surfaces indicated that the final failure was by
ductile tearing. The microstructure itself consisted of pearlite in an equiaxed ferrite matrix, typical of low carbon
steel, refer fig 3 & 4 below.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
46 Energy Conservation & Management
Figure 3 Polished metallographic longitudinal cross-section showing oxide-filled groove and crack. Light-
colored material indicated by white arrows is oxide. Yellow arrow indicates crevice attack on part of tube rolled
into tube sheet. (18X Original Magnification)
Figure 4 Microstructure of failed tube showing pearlite in equiaxed ferrite matrix. (2% nital etch) (125X
Original Magnification)
2 Flattening test: - This is usually applied to the boiler tube and involves flattening a sample of tube between
two parallel faces without the tube showing flaws or cracks. The length of the test piece and degree to which it
is to be flattened (i.e. the distance between the parallel faces) are specified. A section of the tube not less than 40
mm length shall be flattened cold between parallel plates. No cracks or breaks in the metal shall occur until the
distance between the plates is less than the given by the following formula. Evidence of lamination or burnt
material or incomplete penetration of the weld shall not develop during the testing.
(1 + e) t
H = ----------------
e + (t /D)
Where t = Specified thickness of tube (in mm)
D = Specified outside diameter of tube (in mm)
e = Flattening test constant as given below:
0.10 for tube grade WC 1
0.07 for tube grades WC2 & WC3.
(ii) The weld shall be placed 90 degree from the line of direction of the applied force.
(iii) Superficial rupture as a result of minor surface imperfections shall not be cause for rejection.
adopted shall be specified.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
47 Energy Conservation & Management
3 Corrosion test: Various corrosion mechanisms contribute to boiler tube failure. Stress corrosion may result in
either intercrystalline or transgranular cracking of carbon steel. It is caused by a combination of metal stress and
the presence of a corrosive. A metallurgical examination of the failed area is required to confirm the specific
type of cracking. Once this is determined, proper corrective action can be taken.
3.1 Caustic Embrittlement: - Caustic embrittlement, a specific form of stress corrosion, results in the
intercrystalline cracking of steel. Intercrystalline cracking results only when all of the following are present:
specific conditions of stress, a mechanism for concentration such as leakage, and free NaOH in the boiler water.
Therefore, boiler tubes usually fail from caustic embrittlement at points where tubes are rolled into sheets,
drums, or headers.
The possibility of embrittlement may not be ignored even when the boiler is of an all-welded design. Cracked
welds or tube-end leakage can provide the mechanism by which drum metal may be adversely affected. When
free caustic is present, embrittlement is possible.
The device, illustrated in Figure 5, was developed by the United States Bureau of Mines. If boiler water
possesses embrittling characteristics, steps must be taken to protect the boiler from embrittlement-related failure.
Figure 5 Embrittlement related failure protecting device
Sodium nitrate is the standard treatment for inhibiting embrittlement in boilers operating at low pressures. The
ratios of sodium nitrate to sodium hydroxide in the boiler water recommended by the Bureau of Mines depend
on the boiler operating pressure. These ratios are as follows:
Pressure,psi NaNO3 /NaOH Ratio
Up to 250 0.20
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
48 Energy Conservation & Management
Up to 400 0.25
Up to 1000 0.40-0.50
The formula for calculating the sodium nitrate/sodium hydroxide ratio in the boiler water is:
NaNO3 ppm nitrate (as NO3 -)
=
NaOH ppm M alkalinity - ppm phosphate
(As CaCO3) (As PO4 3- )
At pressures above 900 psig, coordinated phosphate/pH control is the usual internal treatment. When properly
administered, this treatment method precludes the development of high concentrations of caustic, eliminating
the potential for caustic embrittlement.
3.2 Fatigue & Corrosion Fatigue: - Transgranular cracking primarily due to cyclic stress is the most common
form of cracking encountered in industrial boilers. In order to determine the cause of a transgranular failure, it is
necessary to study both the design and the operating conditions of the boiler. Straight tube, shell-and-tube waste
heat boilers frequently develop tube and tube sheet failures due to the imposition of unequal stresses.
3.3 Stress-Induced Corrosion: - Certain portions of the boiler can be very susceptible to corrosion as a result
of stress from mechanical forces applied during the manufacturing and fabrication processes. Damage is
commonly visible in stressed components, such as rolled tube ends, threaded bolts, and cyclone separators.
However, corrosion can also occur at weld attachments throughout the boiler (see Figure 6) and can remain
undetected until failure occurs. Regular inspection for evidence of corrosion, particularly in the windbox area of
Kraft recovery boilers, is recommended because of the potential for an explosion caused by a tube leak.
Figure 6 Stress induced corrosion at weld attachment
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
49 Energy Conservation & Management
3.4 Caustic Attack:- Caustic attack (or caustic corrosion), as differentiated from caustic embrittlement, is
encountered in boilers with dematerialized water and most often occurs in phosphate-treated boilers where tube
deposits form, particularly at high heat input or poor circulation areas. Deposits of a porous nature allow boiler
water to permeate the deposits, causing a continuous buildup of boiler water solids between the metal and the
deposits.
Because caustic soda does not crystallize under such circumstances, caustic concentration in the trapped liquid
can reach 10,000 ppm or more. Complex caustic-ferritic compounds are formed when the caustic dissolves the
protective film of magnetic oxide. Water in contact with iron attempts to restore the protective film of magnetite
(Fe3O4). As long as the high caustic concentrations remain, this destructive process causes a continuous loss of
metal. The thinning caused by caustic attack assumes irregular patterns and is often referred to as caustic
gouging (see Figure 7). When deposits are removed from the tube surface during examination, the characteristic
gouges are very evident, along with the white salts deposit which usually outlines the edges of the original
deposition area.
Figure 7 Caustic Attack Causing the failure of caustic gouging
The whitish deposit is sodium carbonate, the residue of caustic soda reacting with carbon dioxide in the air.
3.5 Acidic Attack: - This results in a visually irregular surface appearance, as shown in Figure 8. Smooth
surfaces appear at areas of flow where the attack has been intensified. In severe occurrences, other components,
such as baffling, nuts and bolts, and other stressed areas, may be badly damaged or destroyed, leaving no doubt
as to the source of the problem.
Figure 8 Acidic Attack Causing the failure
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
50 Energy Conservation & Management
3.6 Corrosion Due to Copper: - Pitting of boiler drums and tube banks has been encountered due to metallic
copper deposits, formed during acid cleaning procedures which do not completely compensate for the amount of
copper oxides in the original deposits. Dissolved copper may be plated out on freshly cleaned steel surfaces,
eventually establishing anodic corrosion areas and forming pits very similar in form and appearance to those
caused by oxygen. Copper deposits and temperatures over 1600°F can cause liquid metal embrittlement. Weld
repair of a tube containing copper deposits leads to the failure shown in Figure 9.
Figure 9 Failure due to metallic copper deposits
3.7 Hydrogen Attack: - Since around 1960, hydrogen attack, or embrittlement, has been encountered with
increasing frequency in high-pressure, high-purity systems. It is not encountered in the average industrial plant
because the problem usually occurs only in units operating at pressures of 1500 psig or higher. When
contaminants lower the boiler water pH sufficiently, the acid attack of the steel generates hydrogen. If this
occurs under hard, adherent, nonporous tube deposits, the hydrogen pressure within the deposit can build up to
the point at which the hydrogen penetrates the steel tubing. Ruptures are violent and sudden, and can be
disastrous (see Figure 10)
Figure 10 Hydrogen Attack Causing the Ruptures
4 Tensile Testing. Two 12-inch sections were processed through a typical infiltration brazing furnace cycle
without the application of cladding material. One sample was subsequently normalized at 1,675º F and rapidly
cooled (specific rates are proprietary). A third 12-inch control sample was cut and left in its original state. All
three 12-inch tube sections were then sent to an independent laboratory for ASTM E8 tensile testing. Three
samples from each of the three 12-inch sections, for a total of nine samples, were tensile tested.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
51 Energy Conservation & Management
5 Proximate Analysis Test: - Proximate Analysis test is carried out to determine the percentage of fixed
carbon, moisture, ash, and volatile matter is coal
Result & Discussion
1 Metallographic Test Result - Microstructure of failure tube sample shown that alternate regions of pearlier
(dark) & ferrite (bright), it is a rolled structure.
Discussion - After carried out careful observation of microstructure as shown in figure 12, there is no
transformation of ferrite to Austenite. In above test the microstructure shows that there is alternate region
pearlite & ferrite shows given structure is rolled structure and there is no effect on increasing temperature of
steam in reheater on tube.
Lab Test Report –
The Metallurgical tests were conducted in the laboratory of metallurgy in VNIT, Nagpur and the following test
reports were taken accordingly as per experiment conducted. See figure 13 for the test report of microstructure
at away from the fracture when Normal ferrite & pearlite and figure 14 for the test report of microstructure at
fracture for Martensite / bainite & no free ferrite.
Fig.ure No 11 Microstructure at 100X
(The above Microstructure shows Alternate Region of Normal ferrite & pearlite.)
Figure. No 12 Microstructure at away from fracture (Normal ferrite & pearlite)
Figure. No 13 Microstructure at fracture (Martensite / bainite & no free ferrite)
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
52 Energy Conservation & Management
2 Flattening Test Result:
A section of tube of length equal to 1.5 times the outside diameter, but not less than 50 mm, shall stand being
flared with a tool having 60 or 45 degree included angle until the tube at the mouth of the flare has expanded to
the percentage given below without cracking.
Tube
Grade
% expansion in outside diameter D for
a d/D
0.6 and
under
Over 0.6 to 0.8
including
Over
0.8
WC1 12 15 19
WC1 12 15 19
WC3 10 12 17
d = inside diameter of tube.
Table 3 flattering test results.
Discussion:-The flatting test is performed as IBR act 1950. In this test calculate distance H = 32.84 mm
indicates no cracks present on given tube. This indicates the given material of tube is ductile material and failure
of the tube is not occur do to short term overheating.
3 Corrosion Test Result:
Corrosion product is to found loose, brown in color.
Pitting is not found on both the surfaces.
Oxide film is not found on both the surfaces
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
53 Energy Conservation & Management
Discussion
The third result of corrosion test is directly related failure of tube is due to hydrogen damage in hydrogen
damage failure damages occur due to heavy scales deposit on water/ steam side of boiler tube concentrate
sodium hydroxide will remove the protective magnetic film. In hydrogen damage when the protective oxide
layer destroyed from inner side and outer side of tube the reaction of iron with concentrate sodium hydroxide
form sodium ferrite and atomic hydrogen.
Fe + 2 NaoH - Na2Feo2 + 2 H
When hydrogen trapped between steel a scale, hydrogen react with iron carbide formed methane. Methane
Formation weakens the steel. It is necessary to avoid excessive water deposition & control Ph value the feed
water. The given tube fail is due to hydrogen damage because of protective oxide layer from inner side and
outer side is reduces.
4 Tensile Test Results: - Tensile test results of Tensile Testing and calculated Yield Strength are tabulated
below. Results shown in the center section of the table indicate that subjecting the tubes to a typical brazing
cycle reduced the tensile strength of the material to its minimum allowable level of 60 ksi, and reduced the
material yield strength to below its minimum allowable level of 37 ksi.
Tensile Test Result
Tensile Yield Elongation
Strength
(ksi)
Strength
(ksi) (%)
Control sample
1 68 46.7 34.6
Control sample
2 69 46.5 35.2
Control sample 67 46.2 35
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
54 Energy Conservation & Management
3
Average 68 46.5 34.9
Braze Cycle
Sample 1 59.5 33.4 33.5
Braze Cycle
Sample 2 60.5 33.1 32.9
Braze Cycle
Sample 3 60 32.8 31.6
Average 60 33.1 34.9
Brazed and
Normalized
Sample 1
59.5 36.1 36.3
Brazed and
Normalized
Sample 2
60.5 37.7 38
Brazed and
Normalized
Sample 3
60 37.1 37.8
Average 60 37 34.9
Table 4 Tensile test result.
The normalization heat treatment process, as shown in the bottom section of the table, increased the material
yield strength to the minimum allowable level of 37 ksi
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
55 Energy Conservation & Management
Graph 4 Tensile test result
5 Proximate Analysis Test Result:-
Proximate Analysis Test Result
Moisture content in coal 5.82%
Ash content in coal 40.25%
Fixed carbon in coal 30.44%
Volatile matter in coal 23.49%
C.V. of Coal 3840Kcal
Chemical Composition (W / T %)
% C % SI % MN % S % P
0.19 0.26 0.48 0.014 0.016
Discussion:-The above value of moisture Ash, fixed carbon, and volatile matter in coal indicate the quality of
coal is used in power plant is not inferior and there is no effect of coal quality on tube failure.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
56 Energy Conservation & Management
Conclusions
After carrying out failure analysis of boiler tube, it is found that major failure occurred in reheater, super heater
and economiser tube. In reheater due to high temperature of steam, tube failure occurred. The reason for such
failure is short term overheating and long term overheating. To avoid the failure of boiler tube due to short term
overheating, the flow starvation due to low drum level is suggested. Also it is necessary to flush the boiler 2-3
times before hydraulic test. Another reason for tube failure is corrosion. To avoid the failure of boiler tube due
to corrosion, it is suggested to maintain water chemistry, not to run the boiler in condenser leakage condition
and also maintain PH value is 9.3.
Presence of sulfur in the oil ash deposited on the fireside surfaces of the tube appears to be the main cause of the
failure of the boiler tubes at Al-Khobar Power Plant.
References:
• Reid, W. T. External Corrosion and Deposits - Boilers and Gas Turbines. New York :Elsvier 1971.
• Stringer, J. “High Temperature Problems in the Electric Power Industry and their Solutions”, in High
Temperature Corrosion. Ed., R. A. Rapp. Houston : National Association of Corrosion Engineers,
1983, p. 389.
• French, D. N. “Liquid Ash Corrosion Problems in Fossil Fuel Boilers”, Porc, Electrochem Soc.,
(1983), 83-85, p. 68.
• “Corrosion in Fossil Fuel Power Plants”, in Metal Handbook, Vol. 13 ed. B. C. Syratt, Metals, Park,
Ohio : American Society for Metals, 1987, p. 985.
• Porta R. D. and H. M. Herro, “The Nalco Guide to Boiler Failure Analysis. New York : McGrawll Hill,
1991.
• Dooley, R B. “Boiler Tube Failures - A Perspective and Vision”, Proceedings International Conference
on Boiler Tube Failures in Fossil Plants, Palo Alto, California : EPRI, 1992.
• Calannino J., “Prevent Boiler Tube
• Calannino, J. “Prevent Boiler Tube Failures Part II : Waterside Mechanisms”, Chemical Engg.
Progress, November 1993, p. 73.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
57 Energy Conservation & Management
• Hendrix, D. E., “Hydrogen Attack on waterwall Tubes in High Pressure Boilers”, Materials
performance, (1995), 32(8), p. 46.
• Public Works Technical Bulletin 420-49-21, “Boiler Water Treatment – Lessons Learned”, Nov. 1999.
• 11. R. K. Dayal and N. Parvathavarthini, “Hydrogen embrittlement in power plant steels”, pp 431-451,
Sadhana, Vol. 28, Aug. 2003.
• 12. Glenn N. Showers, PE, “ The importance of Burner Management Control”, pp 39-41, HPAC, Dec.
1997.
• 13. S. Tuurna, O. Cronwall, L. Heikinheimo, M. Hanninen, H. Talja, O. Tiihonen, "State of Art Report
Lifetime Analyis of Boiler Tubes”, VTT Technical Research, Oct. 2003.
• M. N. Hovinga, G. J. Nakoneczny, “Standard Recommendations for Pressure Part Inspection during a
Boiler Life Extension Programme”, International Conference on Life Management and Life Extension
of Power Plant, May 2000.
• Darryl Rosario, Peter Riccardella and Thomas Sherlock, “A Risk Management Approach for Boiler
Waterwall Tube Failure”, EPRI Maintenance Conference, June 1999.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
58 Energy Conservation & Management
Designing 5 MW Grid connected solar power plant with software
simulation
DR.R.N. Singh and Kumar Pawar
[email protected], [email protected]
Abstract
The present report is based on the designing of 5 MW Grid Connected Solar PV Power Plant to be
installed in Rajgarh District of Madhya Pradesh. The report covers the various aspect of designing of grid
connected solar PV Power Plant including collection of meteorological data, selection of module and inverter,
designing of mounting structures, shadow analysis, and The PV designing software PVSYST is also used for the
designing and simulation of this Power Plant.
Keywords:
Handbook of solar radiation by Anna Mani.
Solar energy and surface metrology (NASA).
1. Introduction
Tata International Limited was established in 1962 as Commercial and Industrial Exports Ltd (CIEL) to promote
exports of Tata Group products and services as well as those of other reputed Indian manufacturers. The
company was renamed as Tata Exports in 1968 and has evolved to become an International Business Company.
The company assumed the name Tata International Limited (TIL) in March 1998 to reinforce its evolution from
an exporter to an internation0al business company. TIL is one of largest export houses in India with the status of
Five Star Export House. The company has five Global Business Units namely Leather & Leather Products
(L&LP), Steel, Minerals, Engineering and Bulk Commodities & Chemicals.
The L&LP business started in 1975 with the establishment of integrated Leather Complex at Dewas;
manufacturing Finished Leather, Leather Garments and Footwear. The business has since consistently grown
and has taken a global shape with a subsidiary in Hongkong; front offices in Shanghai, Dong Guan, London;
supply chain bases in Bangladesh, China and across India (primarily Chennai); and global sourcing of raw
materials & other inputs. L&LP Dewas & Chennai operations are ISO-9001 certified and the own
manufacturing set-up at Dewas ISO 14001 certified tannery, largest in India.
L&LP operates its business through three business lines – Finished Leather, Leather Garments & Articles and
Footwear. The three businesses are lead by respective Global Business Heads. L&LP is largest exporter of
leather & leather products from India since 1982, with 3.8% share. L&LP has consolidated its leadership in the
industry as world’s largest producer of Goat & Sheep leathers, being among top 10 producers.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
59 Energy Conservation & Management
Of Finished Leather worldwide and has already strategic plans in place for an exponential growth of
around 20% per annum in next 3 years.
The Leather Garment and Footwear Business exports products to the leading brands of the world. The Articles
business is integrated with the Leather Garments Business and includes wide range of products from Luggage &
Portfolios to Wallets & Purses. Our association with best international designers and design studio in Italy and
Spain enable us to produce value added and customized products in vogue with the latest International trends.
The Company is committed to good corporate citizenship by being proactive, integral and responsible member
of communities and environment in which it operates. The company’s Environmental Policy demonstrates its
commitment to the environment.
The principal potential impact of the L&LP operations on society is from its Dewas manufacturing facility.
L&LP has been certified with ISO 14001 at Dewas which ensures that systems and processes are implemented
for improved environment management. It won the Rajiv Gandhi National award for environment protection in
the year 2002 and MP State Award for Environment Conservation In 2004.
2. Methods and Materials
2.1 Data collection methods and using material:
As Handbook of solar radiation was not available so Data has been taken from NASA (Surface meteorology and
solar energy). Following data has been collected from NASA for the assessment of solar energy potential in
Rajgarh.
Average solar radiation on horizontal surface in Rajgarh.
Average solar radiation on tilted surfaces in Rajgarh.
Average maximum and minimum solar radiation in Rajgarh.
Average ambient air temperature in Rajgarh.
Average sunshine hours in Rajgarh.
Average wind speed.
All the analysis has been done with the help of this data.
2.2 Selection of PV Modules
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
60 Energy Conservation & Management
After the collection of Meteorological data different PV modules were compared according to their efficiencies
and types. PV modules based on thin film technology are not considered as their efficiency is less and there is
probability of breakage. Around 5 % of breakage has been reported as per different case studies. Only Mono
crystalline and polycrystalline PV modules have been considered for the project. Both monocrystalline and
polycrystalline modules were compared on the basis of their efficiencies and cost. A Chinese company has been
considered to supply the modules. Only modules with rated power greater than 200W have been considered for
the project.
2.3 Selection of inverters
Different inverters of rating 500 kW are compared from different companies as per the information given by the
vendors. As inverter is to be connected to grid, only grid connected inverters are considered for the project.
Inverters are compared on the basis of following parameters.
Efficiency
Total harmonic distortion.
IP protection rating.
MPPT voltage rating.
Software for control and monitoring.
Technology used in the inverter.
Isolation protection.
Standby losses.
Maximum DC input current and DC voltage.
2.4 PVSYST software simulation
The calculations done in the software are based on following inputs.
Planned capacity.
Location.
Type of system.
Type of module and type of mechanism required for mounting of PV array.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
61 Energy Conservation & Management
Inverter capacity.
For shadow analysis we have to give the distance between the rows. Although this distance can also be
optimized.
After giving these inputs all the necessary calculations regarding number of modules to be connected in series
and number of strings to be paralleled are done by software and based on these necessary calculations for the
energy output of the system are done by software.
3. Observations and Measurements
Table 3.1 Monthly Average Maximum Global solar Radiation on tilted surfaces:
S.No Month
Solar Radiation (kWh/m2/day)
Tilt angle =250 Tilt angle =400
1 Jan 6.44 6.97
2 Feb 6.74 7.02
3 Mar 7.32 7.23
4 Apr 7.27 6.24
5 May 6.71 5.89
6 Jun 6.27 5.86
7 Jul 5 4.44
8 Aug 5.3 4.91
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
62 Energy Conservation & Management
9 Sep 5.6 5.38
10 Oct 6.66 6.81
11 Nov 6.42 6.91
12 Dec 6.25 6.85
13 Avg 5.85 6.32
Table – 3.2 Specification of PV array for 5 MW
S.No Parameter Specification Unit
1 Module’s rated power 260 W
2 Modules in a string 18 Nos
3 String power rating 4.691 kW
4 Strings in an array 108 Nos
5 Total arrays 10 Nos
6 Array power rating 507 kW
7 Total number of modules
required 19440 Nos
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
63 Energy Conservation & Management
Table – 3.3 Area requirements with the help of shadow analysis for PV arrays corresponding to tilt angle 250
and 400
Tilt angle 25 o 40 o
Area required for one string (Sq m) 54.04 73.86
Area required for 216 strings (1.008 MW) (Sq m) 11673 15953
Area required for 1080 strings (5.04 MW) (Sq m) 58363 79768
Area required for 5 MW (Acre) 14 19
4. Result and Discussion
Fig 4.1 Block diagram for 5 MW solar PV power plant PVSYST software simulations
Table-4.1Calculations of power decrement with rise in temperature
Onth Wp (Tavg)amb (NOCT)rated
(°C)
solar
insolation
(kWh/m2
Monthly
Avg Day
light
(Gavg)
(W/m2) (Tcell)avg
η
Power at
cell temp
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
64 Energy Conservation & Management
day) hours W/0C (W)
Jan 260 21.6 45 5.56 10.9 510 34.35 -0.5% 247.842
Feb 260 23.65 45 6.24 11.4 547 37.33 -0.5% 243.965
Mar 260 28.4 45 6.59 12 549 42.12 -0.5% 237.732
Apr 260 31.5 45 6.49 12.6 545 44.37 -0.5% 234.804
May 260 31.95 45 6.18 13.2 468 43.65 -0.5% 235.749
Jun 260 29.10 45 5.52 13.5 408 39.32 -0.5% 241.381
Jul 260 26.55 45 4.03 13.3 303 34.12 -0.5% 248.137
Aug 260 26.10 45 3.12 12.9 288 33.30 -0.5% 249.197
Sep 260 27.15 45 4.83 12.3 392 36.96 -0.5% 244.442
Oct 260 27.45 45 5.83 11.6 502 40.01 -0.5% 240.480
Nov 260 25.35 45 5.82 11 529 38.57 -0.5% 242.344
Dec 260 22.40 45 5.36 10.8 496 34.80 -0.5% 247.250
Avg 280 26.31 45 5.51 12.13 459 38.24 -0.5% 242.788
Table 4.2 PVSYST software simulation
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
65 Energy Conservation & Management
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
66 Energy Conservation & Management
5. Conclusions
After theoretical calculations the simulation of Grid connected 5 MW solar PV Power Plant was done with the
help of PVSYST software. The module, inverter and all the meteorological data is taken from the software
database and also the weather data files are imported from NASA database. The different tables and reports
generated according to the inputs given in the software are given on the upcoming pages.
System can be sized as per the requirement.
Orientation and tilt angle can be optimized for maximum power production.
Shadow analysis can be done in the software.
Different losses can be calculated with the help of software.
Calculations for normalized performance coefficients Calculations for inverter losses.
Solar pumping systems and stand alone systems can also be designed and simulated with this software
Cost analysis can also be done with the help of software.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
67 Energy Conservation & Management
References
• Solar Energy- Principle of thermal collection and storage by S P Sukhatme and J K Nayak, Thired
Edition, Tata-McGraw-Hill Publication company ltd, Delhi.
• Planning and Installing Photovoltaic System by- A guide for installers, Architect’s and Engineer’s
• www.susdesign.com
• www.solarphotovoltaic.net
• www.wikipedia.org
• www.indiasolar.com/
• www.pvresources.com/en/inverter.php
• www.solardirect.com/pv/inverters/inverters.htm
• www.automation.siemens.com/mcms/solar-inverter.aspx
• PVSYST Software- Simulation and Shading analysis.
Adaptation of New Technology on “Carbon Capture, Sequestration and conversion of fly ash into artificial
zeolites
SP Singh
Ex. Member (UPSEB)
Council Member, Institution of Engineers (I)
Reference:
• International Conference on Green Power Generation–Vision 2020 organized by The Institutions of
Engineers (India), Anpara Local Centre at HINDALCO (Renusagar Power Division) Renusagar, Distt.
Sonbhadra (UP) on 10th to 12th December 2010.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
68 Energy Conservation & Management
Carbon Capture & Sequestration
Government of India has declared its policy on CO2 abatement by the announcement and adoption of the
‘National Action Plan on Climate Change’. It has also made voluntary commitment at the Copenhagen Summit
that the Country shall decrease its Carbon Intensity by 20% by 2020 and 50% by 2050. The path chosen makes
it imperative that the CO2 which forms 95% of the GHG emissions be reduced. The bulk of CO2 is emitted by
the Thermal Plants in the Power Sector. For EPA regulations to be implemented there have to be a road map as
to how this can be done without major impact on the cost or efficiency. RGTU Bhopal has taken lead in
establishing India’s first CO2 Capture & Sequestration Plant.
The thermal plants in India have a thermal efficiency of 35% and an emission ratio of 0.90Kg/kWh of CO2
emissions as published by CEA. The reduction of 20% intensity would translate to a decrease of 0.20Kg/kWh of
CO2 emissions to 0.70Kg/kWh CO2 emissions by 2020. This decrease is possible by a combination of
abatement and recycling measures. However, the CO2 reduction by an Amine system of 30% CO2 capture
would mean a decrease of Thermal Efficiency by 2%. This, can be demonstrated only after establishment of full
scale CO2 Capture and Sequestration plant on an actual coal fired Unit and carrying out System Optimization
studies.
It is the need for the future looking to environment & climate change issues, and decided to have round table on
the above said issues to discuss in detail.
The round table was held and following issues were discussed:
Adaptation Technology on Existing Plant / Green Field Units
Technology Transfer v/s Departments within the country
Funding aspect from GOI.
The round table unanimously concluded that “Carbon Capture & Sequestration” should be installed in one of
the plant in the existing power belt of Singrauli region. Following Plants were suggested-
Anpara Thermal Power Station 3 X 210 MW & 2 X 500 MW
Renusagar Power 60 MW unit-1.
STPS NTPC Shaktinagar
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
69 Energy Conservation & Management
RGTU will be Principal consultant to this project and Institution of Engineers (I) will coordinate the entire
activity.
Another new technology discussed by the I E (I) forum is the “Conversion of Fly Ash into Artificial Zeolites”
had to be installed in one of the above plants in the existing power belt of Singrauli region.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
70 Energy Conservation & Management
An Electronic Sensor Based Photo Voltaic Tracking System
Mr. Priyadarshi
Abstract
This paper presents a cost effective way of tracking of Solar PhotoVoltaic panel using electronic sensors.
Solar PhotoVoltaic Panels are used to harness Solar Energy. The main objective of this work is to utilize the
maximum of solar radiation by minimizing the angle between solar incident ray and the normal to the tilted
surface i.e. to minimize angle of Incidence.
Introduction
Electricity generation is the process of creating electricity from other forms of energy. Solar power is the
conversion of sunlight into electricity, directly using photovoltaics (PV). The photoelectric effect refers to the
emission, or ejection, of electrons from the surface of, generally, a metal in response to incident light.
A photo voltaic panel is a series combination of PN junction. When sun radiation full of photons falls on PN
Junction, results in diffusion which starts power generation. PV converts light into electric current using the
photoelectric effect.
Photovoltaic power generation employs solar panels comprising a number of cells containing a photovoltaic
material. Materials presently used for photovoltaics include monocrystalline silicon, polycrystalline silicon,
amorphous silicon, cadmium telluride, and copper indium selenide/sulfide.
Sun path refers to the apparent significant seasonal-and-hourly positional changes of the sun (and length of
daylight) as the Earth rotates, and orbits around the sun.
With respect to earth sun moves in two paths –
East To West
North To South and vice versa
Due to the rotation of earth on its own axis east to west movement of sun is possible. At every place on earth
sun rises in east and sets to west. Due to this action the solar azimuth angle and air mass ratio continuously
changes. As a result the resultant radiation continuously changes.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
71 Energy Conservation & Management
As we know the earth is tilted at 23.5° on its pole-to-pole axis. Due to this there is seasonal variation found
where sun travels back and forth from north to south. The sun comes overhead at the places which are in
between Tropic of cancer and Tropic of Capricorn. Due to this variation there is a slight change in radiation
coming on earth.
Solar PV Tracking
There are various tracking systems as- Concentrated Photovoltaic (CPV) Module Trackers, Single Axis
Trackers, Horizontal Single Axis Tracker (HSAT), Vertical Single Axis Tracker (VSAT), Tilted Single Axis
Tracker (TSAT), Polar Aligned Single Axis Trackers (PASAT), Dual Axis Trackers , Tip – Tilt Dual Axis
Tracker (TTDAT), Azimuth-Altitude Dual Axis Tracker (AADAT), Active tracker, Passive tracker,
Chronological tracker.
Suggested Single Axis Tracking
The major sections of this tracking are listed below and will be explained in detail.
Sensor
Ball Bearing
PV panel
Electronic Ckt.
DC Motor
LDR SENSORS
Panel
Ball Bearing
E- Ckt
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
72 Energy Conservation & Management
Observations and Measurements
By Implementing The methodology I found drastic change in efficiency of PV module. The measurements are
listed below-
S.No.
Without
tracking(KWh/m2/Day)
(From Nasa)
With Tracking(KWh/m2/Day)
1. 6.18 7.4
2. 6.68 7.8
3. 6.72 7.9
4. 5.62 6.6
Results and Discussion
We can see after tracking the panel we are collecting more and more solar radiation. The efficiency increase
varies from 18 -20 %.
If we increase the resolution and go for dual axis tracking the efficiency can be increased up to 30-35%.
The same concept of tracking can be easily extended for dual axis tracking.
Conclusions
The system developed is found to be very easy to implement. The maintenance is very less. System complexity
is very less.
The concept can be extended to Concentrator tracking with further R& D.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
73 Energy Conservation & Management
Technical paper on Energy Saving Aspect in Boiler Feed Pump in Thermal
power plant
Santosh M. Mestry and Paresh Kumar Parhi
[email protected], [email protected]
Profile
Power Plant Name Dahanu thermal Power Station
Location Dahanu, Distt- Thane, Maharashtra
Power Plant Capacity 2*250 Mw
Introduction
In a thermal power plant, steam is produced and used to spin a turbine that operates a generator. Shown here is
a diagram of a conventional thermal power plant, which uses coal, oil, or natural gas as fuel to boil water to
produce the steam. The electricity generated at the plant is sent to consumers through high-voltage power lines.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
74 Energy Conservation & Management
Introduction on BFP of Thermal Power Plant
There are two 100% capacity Boiler Feed Pumps per unit. Boiler feed pump set consists of a booster stage
pump, directly driven from one end of the shaft of an electric motor, a pressure stage pump driven from the
opposite end of the motor shaft through a variable speed drive ( Hydraulic Coupling ) unit.
Each pump set is supplied with suction strainer, NRV on the pressure stage pump discharge and modulating
minimum flow re-circulation system. Recirculation line is provided before discharge valve with a pneumatic
control valve, which maintains a minimum flow of 240 T/hr. Each pump is of three stage horizontal cartridge
type.
Boiler feed pump is the major power consumer among all power consuming equipment in the power plant. HT
motor consumes almost 95% power in thermal power plant. Out of which BFP is a major contributor of
auxiliary power consumption. It is illustrated in following chart.
There are 3-case study explained on Energy Saving Aspect in Boiler Feed Pump
Replacement of pump cartridge
Drum Level Controlled by BFP SCOOP operation in 3-Element mode instead of DP mode
Replacement Of Recirculation Valve Of Boiler Feed Pump
Case Study-1: Replacement of pump cartridge
Background
One of the major auxiliaries of DTPS is Boiler Feed Pump (9000 KW). The purpose of Boiler Feed Pump is to
pump feed water to boiler drum, provide spray water to HPBP, APRDS, De-super heater station. One BFP
caters to entire requirement of the process. The second pump remains as an auto stand by equipment.
AUX. POWER CONSUMPTION PATTERN
HT MOTOR LOAD 94%
LT MOTOR LOAD
5%
MISC.1%
2.78
0.22
1.381.41
0.26
0.74
0.35
0.29
0.26
2.37
BFPsFD FANSIDFANSPAFANSCEPMILLSCHPAHPComp.airOthers
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
75 Energy Conservation & Management
Observation
The Boiler Feed Pump at DTPS is of multistage (three stage) type. It was observed that the BFP-2B is taking
much higher current than other BFPs. From performance curve of the pump also it was clear that it is consuming
much higher power corresponding to the flow.
Technical & Financial analysis
Three root causes shortlisted from technical analysis.
Wear & tear of pump internals due to ageing
Possible damage to internal gasket
Short-circuiting of suction and discharge chambers
It was concluded that loss is taking place due to interstage leakage or recirculation.
Hence decision was taken to replace the cartridge of pump.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
76 Energy Conservation & Management
Impact of Implementation
After replacing the cartridge the current drawn reduced by 70 Amp.
Power saved per day = √3*V*I*PF* 24
= 1.73*6.6Kv*70amps*0.85 * 24=16304 KWH
Power saved per year=5950960 KWH
Saving of cost= 5950960*3.5= Rs2,08,28,360
Simple Pay Back Period: 70 days with 40 Lakh Rs. Investment
Case Study -2 :
Drum Level Controlled by BFP SCOOP operation in 3-Element mode instead of DP mode.
Background
Boiler drum level control is done by BFP scoop & feed water regulating station (FRS) control valve in two
ways,
DP mode
Three element mode
In DP mode BFP scoop maintain the DP across the FRS as per set point & control valve regulate feed water
flow as per three element errors to maintain drum level as per set point. Whereas in three element mode, scoop
maintain the drum level as per three element error keeping FRS control valve wide open.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
77 Energy Conservation & Management
Observation:
In most of units having MD BFP only, drum level control is accomplished through DP mode because it believed
that is robust control. But it results in appreciable energy loss due to throttling of FRS valve. DP set point for
scoop is observed between the range of 7-10 kg/cm2;
hence same is the pressure drop across FRS valve. Reason of high DP set point to increase differential pressure
to improves the control. Disadvantage of DP mode is increased pressure loss & Energy loss.
Technical & Financial Analysis:
Energy Saving potential in throttled FRS valve is given below which clearly indicates pump power loss can be
optimized by minimizing pressure drop across the valve.
DP optimization in “DP” mode gives no substantial energy saving due to action of FRS valve. Further pressure
drop reduction is only possible in three element mode scoop operation where FRS valve is kept fully open
Pump power (100- efficiency) Pump losses % = ------------------------------------
Generated Load
In 250 MW capacity unit having overall efficiency of 38 %
and for pump power = 7 MW, DP =7.5 kg/cm2,
Total pr. Developed by pump = 180 kg/cm2,
Pressure drop across the valve x Pump Power
Energy Saving Potential = -------------------------------------------------------------
Total Pressure rise across the Pump
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
78 Energy Conservation & Management
Energy saving potential & Calculated pump loss is given below which are unusually high figure.
Energy saving potential =29 %
Calculated pump loss = 1.736 % of Boiler Heat I/P
As flow control by throttling in case of high power pump like BFP is inefficient, flow control by speed
regulation by means of BFP scoop is adopted.
Effect on System Curve with Throttling HEAD
Pump
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
79 Energy Conservation & Management
FLOW
In the above system, pump system curve get shifted to lower efficiency region as throttling increases. Point A is
the best efficiency point (BEP) where valve is full open at the pump’s best efficiency point (BEP). But, in actual
operation, amount of flow in valve full open condition is not necessary hence we throttle the valve. To point B
to get desired flow.
The reduction in flow rate has to be effected by a throttle valve. In other words, we are introducing an artificial
resistance in the system. Due to this additional resistance, the frictional part of the system curve increases and
thus the new system curve will shift to the left -this is shown as the red curve. So the pump has to overcome
additional pressure in order to deliver the reduced flow. Now, the new system curve will intersect the pump
curve at point B. At point B, pump head is increased the red double arrow line shows the additional pressure
drop due to throttling. You may note that the best efficiency point has shifted from 82% to 77% efficiency. So
what we want is to actually operate at point C which is on the original system curve for the same required flow.
The head required at this point is reduced. What we now need is a new pump which will operate with its best
efficiency point at C. But there are other simpler options rather than replacing the pump.
The speed of the pump can be reduced or the existing impeller can be trimmed (or new lower size impeller). The
blue pump curve represents either of these options. It is not feasible to replace pump or trimming of impeller,
best solution is to reduce the speed. Hence flow control by speed control method is more efficient.
DP control mode & three element mode schematic is given below.
Scoop operation in DP mode
Scoop operation in three element mode
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
80 Energy Conservation & Management
Changeover philosophy from DP mode to three element mode. (SCOOP Operation- DP mode & Auto. FRS
valve- Auto)
Take SCOOP and FRS control Valve in MAN.
Select three element mode of scoop operation.
Put scoop in AUTO. Observe scoop operation.
Gradually open the FRS valve fully.
Changeover philosophy from Three element mode to DP mode. (SCOOP Operation- Three element mode &
Auto. FRS valve- Manual)
Set the required DP set point
Gradually close the FRS valve so that DP across valve matches the DP set point
Take SCOOP in MAN. Select DP mode from three element mode.
Put SCOOP & FRS valve in AUTO. Observe the response.
DP mode is suitable in case of emergency & fluctuating load condition whereas three element mode is suitable
in steady load condition.
Impact of Implementation:
AMP. Gain/Hr KW saving/Hr GHG reduction KG/Hr
1 BFP-1A 10 97 83
2 BFP-1B 2.6 25 21
3 BFP-2A 4.2 40 35
4 BFP-2B 14.2 137 118
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
81 Energy Conservation & Management
In DTPS, BFP scoop operation successfully tested in three element mode for each BFP.
Pressure drop across FRS valve is observed to be @ 3.5 kg/cm2 in valve full open condition.
Ampere saving achieve is given above Table.
Difference in energy saving may be due to change in vacuum, operating drum pressure & metering error.
BFP hydraulic coupling’s response time and subsequent change in drum level shows that drum level control
directly through BFP scoop operation in three element mode variation is quite feasible especially under steady
operating condition.
Simple Pay Back Period: Immediate with Nil investment
Case Study - 3 :
Replacement Of Recirculation Valve Of Boiler Feed Pump
Background
Boiler Feed pump is supplied with suction strainer, NRV on the pump discharge and modulating minimum flow
re-circulation system. Recirculation line is provided before discharge valve with a pneumatic control valve,
which maintains a minimum flow of 240 T/hr. This valve avoids dry run and overheating of pump.
Observation
It was observed that after certain running hours the suction flow of a loaded pump was much higher than the
discharge feed water flow.
Technical & Financial analysis
When recirculation valve of the BFP was further closed, the difference got reduced. Hence the manual isolating
valve was closed and it resulted in drastic reduction of suction flow .
Now the suction flow was matching with the discharge feed water flow. Hence it was suspected that some flow
is passing through valve seat.
After due maintenance of the existing valve not much improvement was observed. Hence it was decided to
replace the existing valve with an advanced class of drag technology valve.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
82 Energy Conservation & Management
Impact of Implementation:
After replacement of valve the current drawn by the motor of pump reduced by 60 amp.
Power saved due to the reduction current drawn by motor = 6.6*60*1.73*0.85
Power saved= 582 KWH/HR
Saving in cost/hr = 582*3.5= Rs 2037
Saving/year =2037*24*365=1,78,44,120
Investment = Rs 2500000
Simple Payback period = 2500000 / 2037 = 51days
Same valve replaced in all the 4 BFP with an investment of 1 crore which resulted in saving of Rs 7,13,76,480.
Conclusion
Thermal power plants contribute 70% of India’s power generation installed capacity. It is not possible to meet
the growing demand due to long gestation period of power plant. Only solution is to reduce auxiliary power
consumption by energy conservation & energy efficiency practices.
There is tremendous scope in power sector for reducing auxiliary power consumption (APC). In India, It is
estimated that; reduction in APC by 1%, equvivalant of generation of 5000 Mu of energy per annum. Saved
energy can be sold out. to minimize the gap between supply & demand.
This changed scenario impacted the bottom line of power generation utilities.
Hence the ways to retains one’s competitive edge in the fiercely competitive industry.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
83 Energy Conservation & Management
Heat Recovery Hot Water Heater Desuperheater in Refrigeration System
Vrajalal Kanetkar
[email protected] • www.refreconmagic.com
Process Industries / hospitality Industries requiring hot water
Hospitality Industry
Hospitals
Chemical and Pharmaceutical Industries
Economiser for Boiler water Pre-heater
Dairies and milk processing plants
Engineering Industries
Compressor Heat Recovery for Air Compressor
Waste heat recovery to make hot water from air conditioning compressor (use of our Desuperheater ) is one the
major tools available for Hospitality industry in general. Hospitality, Pharmaceutical, Dairies, and Process
Industries have also adopt this in recent past. Techno-commercial advantages of this heat recovery are incredible
and this is why international institutes like ASHRAE, CADDET, AEE, DOE in USA and now number of Indian
users are strongly supporting this concept.
Dairies and Hotels are bulk consumers of hot water at 500 to 700C. Invariably this hot water is generated using
prime energy either fuels or using electricity. In recent past good number of users meet their requirement
through solar hot water heaters. .
Using high-grade waste heat to generate hot water for boiler was a common practice adopted by users as well as
manufacturers for decades. There are number of good manufacturers to supply this system for industrial
application.
We are discussing here commercial success of low-grade heat in reciprocating or screw compressors to generate
hot water. At REFRECON we have now more than 100 successful installations saving crores of rupees for our
customers (Aggregate savings withal installations put together.)
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
84 Energy Conservation & Management
Users or refrigeration systems and air compressors are at great advantage to offset their hot water heating cost
by implementing heat recovery. Users of REFRECON system have reduced 50 to 70% of hot water heating cost
along with number of other benefits. Successful heat recovery normally has several cascaded hidden benefits.
Refrecon has several success stories of recovery of this low-grade heat.
Adiabatic compression process generates high temperatures depending upon type of compressors used.
Reciprocating compressors have higher temperature after compression where as screws normally have lower
delivery gas temperature. But both have potential to deliver usable hot water for process need.
Dairies and Star Hotels are potentially large consumers of refrigeration and hot water. Cascading heat recovery
with cooling effect has great advantage for the system efficiency improvement along with reduction of energy
cost by adopting this heat recovery. Retrofitting old systems or installing new systems with hot water
desuperheater gives great advantage of operating cost reduction as well as stable and efficient operation of
refrigeration system.
Superheat in refrigeration is necessity for stable and safe process operation. Same superheat is also cause to
reduce operation efficiency of compression. Heat Recovery Hot Water Heater - Desuperheater installation with
refrigeration is boost to dairy and hotel industry in general saving operating energy cost and avoiding pollution
due to fuel use. This also has added advantage of eco-friendly image building when globally every one talks of
green gas emission reduction.
All compressors deliver hot gas/air at outlet and this gas is either condensed or cooled after compression
rejecting heat to atmosphere. Converting this hot gas into hot water substantially reduces heating cost to
generate hot water.
Enclosed schematic technically explains mode of connecting this heat recovery system. Material of Construction
(MOC) will depend upon the type of gas/air handled by compressor. While SS is most safe for water some times
comer also can be deployed to optimise cost of manufacturing. Some built in safeties are essential to ensure
We will discuss two specific applications in this paper.
Dairy and milk Processing
Hotels, hospitals or hospitality industry
1. Dairy and milk Processing
Refrigeration and boiler constitute more than 75 % of operating energy cost of dairy. As much as dependability
of these systems is important, operating plant efficiency and consistency in performance is also required to limit
processing cost of milk. Built-in improvement in operating efficiency constitutes major saving opportunities in
dairy utility system. Installation of desuperheater for recovery of waste heat is major step in this direction.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
85 Energy Conservation & Management
REFRECON has several successful desuperheater installations in operation since past eight years. The
technology is successfully implemented for various systems using ammonia and R 22 refrigerants.
Dairy cooling requirement
1. Pasteurisation 2. Cold storage 3. Milk chilling
Hot water requirement
a. Boiler feed water b. Crate / Can washing
c. Tanker washing d. CIP
Conventional mode of hot water generation
a. Use of direct fuel fired hot water heaters
b. Direct steam injection
c. Condensate recovery after steam use in plant
Desuperheater mode of “ FREE “ hot water generation in Dairy
With cold storage and IBT in operation in dairy, chilling plants and refrigeration compressors operate almost 24
hours per day. IBT takes care for fluctuating cooling demand by generating appropriate ice thickness on
ammonia coils to chill the milk protecting product quality.
Adiabatic compression in ammonia compressor results in high discharge gas temperatures at compressor outlet.
(1200 C and above) This gas is cooled and condensed in condenser and stored in receiver at 12 to 16 - kg/cm2
pressure and atmospheric temperature. Condensing temperature (varying between 300to450 C) vary depending
upon type of condenser cooling and atmospheric conditions.
Desuperheater installed in ammonia circuit between compressor discharge and condenser, removes high
temperature gas heat and passes entire gas to condenser to condense similar to normal refrigeration cycle. Gas
heat removed in desuperheater heats circulating water up to 550 – 700 C. This recovered heat in the form of hot
water is available free of cost for various requirement in dairy. Refrigeration plant operates almost 24 hours per
day generating hot water at specific rate. This hot water is stored in adequately sized hot water tank to meet
demand of hot water in plant as and when required.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
86 Energy Conservation & Management
ADS series of REFRECON desuperheater is specifically designed for ammonia compressors. MOC and process
parameters are appropriately matched for life long consistency in performance. The fully welded construction of
desuperheater has complete safeties required for installation and infinite life of operation. The desuperheater is
capable to withstand 40 bar pressure and is tested for bubble-tight leak-proof performance at 25 bar pressure in
the manufacturing process. The perfected design results in flaw less commissioning during field installation.
The performance consistency has been proven with number of installations. Though available heat potential for
reciprocating compressors is large REFRECON has successfully installed desuperheaters on ammonia screw
compressors (180 TR and 250 TR) and proved its commercial viability.
2. Hotels and Hospitality Industry
Air conditioning has been primary need of hospitality industry. At the same time fuel fired (Diesel or Furnace
oil) boilers are used to generate hot water for domestic use, cleaning, or kitchen. Air conditioning rejects heat to
atmosphere through air-cooled or water-cooled condensers. Heat rejection and fresh hot water generation is
done across the wall at facility basement and seldom noticed for complimenting each other. While this energy is
of low-grade, it still represents waste energy. Combining these two, (waste heat and fresh heat generation) make
cleaver sense of energy conservation and saves substantial money.
In the tropical country like India, cooling is a non-compromising need. Interruptions in air conditioning or loss
of efficiency of cooling are normally not acceptable, as it directly reflects quality and cost of facility service.
Under this circumstance facility owners need comfort from O & M staff as well as consultants to implement the
change in the system.
Heat recovery is a secondary activity. Generally it has standby operating system to provide required hot water.
Any change made in the total comfort system must ensure no alteration in the performance of refrigeration
cycle. In fact present experience is that cooling capacity of existing system has improved to a small extent.
Economics of Heat Recovery Desuperheater
The economics of this heat recovery is attractive. It is important to ensure recovered hot water displaces prime
energy used by facility. The economics can be adversely affected due to poor operating hours of compressor.
The system evaluation and total integration with facility hot water system is essential step to ensure favorable
economics of project. Though there are other advantages of heat recovery system, over empathising of these
benefits can create serious situation. While system is conceptualised use of hot water should be properly
estimated so that recovered heat is not wasted. Providing metering of hot water flow and recording the operating
temperature will help to monitor and compare post implementation performance of system.
Following general norms may be useful for estimating hot water need by process
1 liter of fuel oil delivers 270 liters of hot water at 550C
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
87 Energy Conservation & Management
1 kWh of electricity delivers 28 liters of hot water at 550C
Hotel uses 200 to 300 liters hot water per occupied room
Dairy needs 0.5 to 0.75 liter hot water at 600C for general sanitation per liter of milk processed.
There are hundreds of success stories of heat recovery desuperheater. Every year Beuro of Energy Efficiency
(BEE) under Ministry of Power gives energy conservation awards for outstanding efficiency improvement
performance in India. Since 2006 award winners in dairy sector successively have been honored who have been
users of REFRECON desuperheater and it is proud moment for us to say that each of these award winners have
praised for REFRECON desuperheaters in their presentation to BEE as well as expressed same opinion on their
website. Needles to say we are proud of our customers for this action.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
88 Energy Conservation & Management
Cold storage design and operational parameters influencing energy
consumption in composite climate of Indore
R.K. Singh, S.P. Singh, R.L. Sawhney
Abstract
With high economic growth rates India is a significant consumer of energy resources. Like the other sectors,
cold storages are also the significant consumers of electrical energy. In this paper, few energy influencing
parameters of cold storages were discussed. The study is based on the survey results of the actual potato cold
storages and it is able to explain the energy consumption patterns and energy consumption levels of cold
storages. The trend analysis and regression methods were used in the study to explain the influence of the
parameters on specific energy consumption. The results show that the capacity utilization factor, aspect ratio and
overall heat transfer coefficients of cold storages significantly affect the energy consumption of the cold
storages.
Key words: Cold storage, Energy consumption, Energy efficient building
Introduction
With high economic growth rates and over 15 percent of the world’s population, India is a significant consumer
of energy resources. In 2009, India was the fourth largest oil consumer in the world, after the United States,
China, and Japan. Despite the global financial crisis, India’s energy consumption has risen remarkably in the
past few decades. As the energy demand increases, energy conservation has been included on the agenda of the
developing countries like India [1]. Like the other sectors, cold storages are also the significant consumers of
electrical energy and will increase in future. Potato is a most eatable vegetable and used throughout the year in
human diet. The perishable nature of potato forces to keep it in a controlled environment. India is one of the
countries where potato is grown in large quantities. Being a second largest producer of potato, India produces
about 30 million tons of potato every year. The huge quantity of potato has gone wastage every year due to lack
of sufficient storage facility in the country [2]. Therefore, it is urgent need to develop the sufficient storage
facility for reducing wastage and emergences the opportunity to the producers for selling out their potato
commodity at good value.
Energy saving potential in Indian potato cold storages was reported earlier [3]; however, there is no clear cut
indication of energy consumption pattern of cold storage. In this situation, it becomes very significant to identify
and figure out the parameters those influence energy consumption of potato cold storages to further
development of new energy efficient cold storages, so as to put forward the corresponding energy saving
measures.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
89 Energy Conservation & Management
In this study, the impact of aspect ratio and effective overall heat transfer coefficient on the energy consumption
of potato cold storages were discussed using the trend analysis. Also, the variation in energy consumption with
capacity utilization factor was analyzed. Results arising from this study provide important reference materials
for the cold storage designers, architects, consultants, owners and operators in assessing electricity energy
consumption patterns and selecting a more accurate approach to estimate future energy demand. However, study
is limited for a small cluster of the composite climate in the country and results may influence in other part of
the same climate or in other climatic conditions. Therefore, similar study for other parts of the country would be
more significant for better results.
Study region
The surveyed cold storages are located in Indore region, which is a big chunk of cold storages. Indore is located
in the mid western part of India South of the Tropic of Cancer (latitude 22.71N, longitude of 75.91E). About 52
cold storages are functioning for preserving perishable items like potato and help greatly to regulate the demand
and consumption of these items throughout the year. The climate of Indore is composite having three distinct
seasons summer, monsoon and winter.
Data collection and analysis
This study intends to determine the energy consumption pattern of potato cold storages through field survey and
experimental procedures. A survey of 10 potato cold storages out of 52 in Indore and nearby area was
conducted. The survey was targeted to obtain data about construction pattern of buildings; design features of
building i.e. aspect ratio and orientation; types of refrigeration are being used and the intensities of their uses;
electrical energy consumption and storage pattern of cold storages.
The questionnaire was prepared and issued to the responsible person of the respective cold storages. Besides, the
questionnaire; also interviewed the owners, managers and operators during the data collection. Each interview
was performed for group of people. The obtained data was consisted the monthly electricity bills, building
construction pattern, storage pattern, refrigeration units and indoor environmental conditions. Out of the 10
surveyed cold storages in the sample, 7 were in private sector and 3 in Co-operative sector. The questionnaire
survey was used for surveying the cold storages situated in Indore and nearer area. This was considered a
reliable and efficient method because the author should had sufficient easy to justify the given information and
could visit frequently the considered cold storages and enable them to respond correctly to the questions in the
questionnaire. To improve the accuracy and completeness of the energy consumption information, the monthly
electricity bills were collected directly from the Madhya Pradesh State Electricity Board (MPSEB), Indore
region. MPSEB is responsible for supplying electricity to the cold storages in the region. Site visits had also
been made to all cold storages to justify the information provided in the questionnaire and measurements of
indoor environmental parameters like storage temperature.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
90 Energy Conservation & Management
Data of energy consumption and storage pattern for 10 cold storages were collected for four consecutive years
(2001-2004). The Specific energy consumptions (SEC) for four consecutive years (2001-2004) are given in
Table 1. The respective storage patterns of cold storages are shown in Figure 1.
Table 1. Annual Specific Energy Consumption (SEC) of Potato cold storages
Cold
Storage
Annual Specific Energy consumption(kWh/ton)
Y-2004 Y-2003 Y-2002 Y-2001
A 10.07 10.86 10.77 10.49
B 10.01 9.92 12.33 13.69
C 9.00 9.90 12.79 13.00
D 14.63 14.96 13.67 21.47
E 12.79 13.38 11.30 12.58
F 9.47 9.92 10.17 9.66
G 9.70 10.84 10.38 10.61
H 15.56 16.82 9.64 10.80
I 11.35 12.05 26.08 13.81
J 12.15 8.90 11.93 12.38
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
91 Energy Conservation & Management
Figure 1. Annual potato storage patterns for years 2001-2004
Buildings of cold storages still remain the second largest consumer of energy and will be singled out for the
present study as a target for energy conservation. In general, the factors that affect cooling energy consumption
in a cold storages building include thermal conduction gains through building envelop and infiltration. The
amount of thermal conduction gain mainly depends on aspect ratio; envelop orientation, exterior colour,
construction materials as well as shape of buildings [4-7]. The survey was done for all described parameters of
building envelop of cold storages. The buildings were insulated and rectangular in size with sloping roofs. A
false flat ceiling were constructed and sloping roof works as shading device, which restricts the direct solar
radiation from the roof. Building envelope for all cold storages were constructed in similar manner and bricks,
and RCC used as construction materials. The walls and roof consists of a number of layers with different
thicknesses and construction materials. The arrangement patterns of layers used in construction of buildings of
surveyed cold storages are given in Table 2.
Table 2. Construction pattern of false ceiling and walls
Construction layers
False
ceiling Wood Tarcol Sheet Thermocole Plaster Wood
Walls Plaster Brick Plaster Thermocole Iron net Plaster
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
92 Energy Conservation & Management
Refrigeration units require to controls the indoor storage environment at required temperature level and maintain
the quality and flavour of stored produce. Surveyed storages were maintaining at 20C and 80-95% humidity
using the conventional vapour compressor refrigeration systems. The major components of a vapor-compression
refrigeration system include a reciprocating compressor, a condenser, receiver, expansion valve and an
evaporator. The compressors room of a cold storage’s refrigeration unit is shown in Figure 3.
Figure 3. Compressor’s room of a refrigeration unit in a cold storage
Two types, i) bunker type and ii) fan coil units (FCUs), of air-handling units (AHUs) were used in the cold
storage for inside air circulation (Figure 4). About 80 percent cold storages were using bunker type air handling
units and other 20% fan coil unit type. The air handling units were kept in the top of the cold storages chambers
and cool the inside air by re-circulating the indoor air continuously. The indoor air removes completely in the
morning hours every day and fills fresh air into the chambers accordingly.
Figure 4. Air handling unit a) Banker type b) Fan coil unit
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
93 Energy Conservation & Management
Results and discussions
We know that factors affecting energy consumption are interactive. Trend analysis can be used for data analysis
to investigate the relationships between variables and ascertain the causal effect of others factors on energy
consumption of cold storage.
The parameters, which may influence the energy consumption, were capacity utilization factor (CUF), overall
heat transfer coefficient (Ueff), aspect ratios of buildings, capacities of refrigeration units and air handling units.
The trend analysis is particularly helpful for identifying the general behavior of the interpreter and also
examines changes in its behavior across the whole spectrum of its numerical values. The capacity utilization
factor is determined by dividing the used capacity by total capacity of the cold storage. The capacity utilization
factor can be expressed as follows:
ns)storage(to cold ofcapacity Fullns)storage(to cold ofcapacity Usedfactorn utilizatioCapacity =
The specific energy consumption is the only suitable and sufficient parameter to explain the energy consumption
pattern of cold storages. It can be seen from Table 1, the specific energy consumption is varying between 9-25
kWh/ton/year that clearly indicates the sufficient potential for reducing it. The variation in specific energy
consumption defiantly influenced by various buildings as well as refrigeration parameters. The trend analysis
focuses on the impact of individual predictors on SEC acting alone.
Effect of capacity utilization
From the surveyed data, it was observed that the capacities of the cold storages were not utilized at its full
capacity at all time. The capacity utilization mainly depends on the crop yield in that respective year and market
demand. The capacity utilization influences the specific energy consumption significantly. Fig. 5 shows the
relationship between the average specific energy consumption as a function of capacity utilization factors of the
cold storages with corresponding regression line.
y = -14.163x + 17.907R2 = 0.6267
5
7
9
11
13
15
17
0.2 0.3 0.4 0.5 0.6 0.7
Capacity utilization factor(ton/ton)
Spe
cific
ene
rgy
cons
umpt
ion(
kWh/
ton)
Figure 5. SEC vs. capacity utilization
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
94 Energy Conservation & Management
The average negative slope of the SEC with changes in CUF was 14.163 kWh/ton that mean the increase in
CUF by 0.1 decreases the energy consumption by 1.46 kWh/ton. Beyond a CUF of 0.35, the change in SEC is
marginal and before 0.35 value of CUF, the SEC increases significantly. This indicates that the specific energy
consumption is affected a little for capacity utilization factor above 0.35; however, lower value of capacity
utilization factor is one of the significant causes for higher energy consumption. It is recommended to the
owners and operators, to operate the cold storages for higher value of CUF or they should use the partial volume
of the cold storages for efficient operation.
Effect of aspect ratio of building
The shape of the building envelope plays a significant role since it determines the surface of the external
envelope [6]. Compactness is expressed by the aspect ratios of building envelope for a specified volume. As
the losses are proportional to the surface of the envelope, the more it is compact, the more the losses of heat will
be less. The aspect ratios of the surveyed cold storages were not found same, however, the shape of the
buildings were similar. The buildings were made rectangular in shape with trusted roof. Figure 6 shows the
effect of aspect ratios of building envelope on specific energy consumption
10
11
12
13
14
15
16
17
0.20 0.21 0.33 0.43 0.59 0.64
W/L
Ave
rage
spe
cific
ene
rgy
cons
umpt
ion(
kWh/
ton/
year
)
0.4 0.37 0.8 0.63 0.91 1
H/L
Figure 6. SEC vs. aspect ratios
The minimization of the external surface area for a specified volume will reduce the heat gain through the
building envelope and ultimately energy consumption. As clear from the Figure 6, the specific energy
consumption of cold storages vary with aspect ratio and found the building having W/L=0.64, H/L=1 values of
aspect ratio is better from the energy efficiency point of view. However, the values of aspect ratios for lower
energy consumption may change with location and climatic conditions. Therefore, further studies for other
climates and locations would strengthen the concept and helpful to setup the guidelines for designing energy
efficient cold storage in future.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
95 Energy Conservation & Management
Effect of U value
Overall heat transfer coefficient of building envelope is one of the most important thermophysical properties
affect the thermal performance of the building envelope and it is easy to control by minor modification or
adopting energy efficient designs. The values of overall effective heat transfer coefficients were calculated for
each cold storage from the collected data and correlated with respective specific energy consumption as shown
in Figure 7. The expected pattern of energy consumption can be observed from the Fig. 7. Higher the effective
heat transfer coefficients, higher the energy consumption. The optimization of effective overall heat transfer
coefficient values are recommended for composite as well as other climatic conditions for minimizing the
energy consumption of the cold storages.
y = 29.501x + 2.879R2 = 0.252
5
7
9
11
13
15
17
0.2 0.25 0.3 0.35 0.4
Ueff(W/m2-K)
Aver
age
spec
ific e
nerg
y co
nsum
ptio
n(kW
h/to
n)
Figure 7. SEC vs Ueff
Effect of sizes of refrigeration and air handling units
In this section the effect of refrigeration and air handling units on the energy consumption of cold storages were
discussed. The Figures 8 & 9 shows the variation in specific energy consumption with specific refrigeration
capacity and specific capacity of AHUs.
y = 142.85x + 7.6389R2 = 0.0094
02468
1012141618
0.03 0.031 0.032 0.033 0.034 0.035
Specif ic refrigeration capacity(kW/ton)
Aver
age
spec
ific e
nerg
y co
nsum
ptio
n(kW
h/to
n)
Figure 8. SEC vs. Specific refrigeration capacity
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
96 Energy Conservation & Management
y = -0.5681x + 13.662R2 = 0.0007
02468
1012141618
2.35 2.4 2.45 2.5 2.55 2.6 2.65
AHU specif ic capacity(W/ton)
Aver
age
spec
ific e
nerg
y co
nsum
ptio
n(kW
h/to
n)
Figure 9. SEC vs. Specific AHU capacity
The trend indicates the minor increment in the specific energy consumption with increase in specific
refrigeration capacity, on the other hand negative slope in the trend line indicates the specific energy
consumption decreases with increase in specific capacity of AHU. However, the correlation coefficients are not
so strong and needs further study of greater number of samples.
The study is based on a small cluster of composite climate and results may vary for other climates and locations,
therefore, further study for other climatic zones of India would be helpful to set the guidelines for setting up new
energy efficient cold storages.
Conclusion
Based on survey of 10 cold storages in composite climate of Indore, the parametric study was performed for
analyzing the impact on energy consumption. The trend analysis method is used to identify the factors of cold
storages that affect the specific energy consumption of cold storages. The factors, namely capacity utilization
factor, aspect ratio and overall heat transfer coefficients of cold storages are found to be significant parameters.
The purpose of this study was to establish a help for architects, engineers, consultants, owners and operators to
take into account the impacts of design and operation choices on energy consumption while designing and
operating the potato cold storages. Also, some recommendations were made for energy efficient operation and
designs of cold storages.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
97 Energy Conservation & Management
References
• Bureau of Energy Efficiency, Ministry of Power, Government of India (www.bee-india.nic.in)
• www.indiastat.com
• Ramkishore Singh, Singh, S.P., Singh R.N.(2010). Energy saving potential in Indian cold storages.
2ndBharatiya Vigyan Sammelan held on 1-3 December, 2010, DAVV, Indore.
• Kaur, J., Singh, S.P., Sawhney, R.L. and Sodha, M.S. (1991) Optimum Layered Distribution of
masonry and insulation of building component. International Journal of Energy Research, 15, 11-18.
• Kumar, A. Ashutosh, S. and Sodha, M.S. (1989) Optimum distribution of insulation over various
components of air-conditioned building, Building & Environment, 24(2), 169-178.
• Bansal N.K., Shail and Garg S.N. (1997) Calculation of solar radiation intercepted by Nubian Vault
and Dome Shaped Building. International Journal of Energy Research, 21, 723-736.
• Sodha, M. S., Jagjit Kaur and Sawhney, R. L. (1992) Effect of orientation on thermal performance of a
building. International Journal of Energy Research, 16, 709-715
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
98 Energy Conservation & Management
A concept in Energy Efficient Lighting - Electromagnetic Induction Light
CIMS Power Technologies Pvt. Ltd.
Present Scenario:
Economic growth, industrialization and growing population in the developing countries of Asia especially India
demand a huge growth in energy supplies in the region while global environmental problems call for cuts on
fossil fuel use, which keeps Power sector in continuous focus. Today the sustainable world energy policy is
based on end-use-oriented energy strategy technically called Demand Side Management (DSM).
If fusion of proper DSM models and mechanisms with proper technology can be achieved then the shortfall in
the energy production can be compensated to a greater extent by efficient use of energy. This energy-use-
oriented approach leads to an energy efficient future that is much-less capital and resource intensive and more
environmentally benign which is the need of the hour for countries like India. As per an estimate about 17% of
total power generated in INDIA is consumed for lighting alone and use of energy efficient lighting itself can
make a big difference in the total energy scene of the Nation (estimated total generation of the country is
150000MW and if even 15% of lighting load can be saved means 3825MW). At present the scope for energy
saving in lighting sector, especially in community light is up to 50%.
Electromagnetic Induction Light is the most energy efficient light source so far known to mankind for highway
lighting, but we are unable to explore the benefits of this light source. This paper will discuss the barriers
(Technological, commercial and policy intervention) in promoting the Electromagnetic Induction Light in the
country and also attempt to address the likely policy intervention for up scaling the use of Electromagnetic
Induction Light including the need of institutional/research capacity enhancement and public awareness.
Need for adopting energy efficiency measures:
• To reduce the ever increasing energy demand supply gap.
• To follow the concept: “ENERGY SAVED IS ENERGY PRODUCED”
• To utilize the available energy capacity in a more efficient way so that it’s widespread use can be
envisaged catering to a larger section of the society.
• To spend minimum while obtaining the maximum value for compulsory obligations like street lighting
this is, in general, commercially unproductive activity for the Government utilities.
• To look forward to the trends which are environment friendly and in pace with the
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
99 Energy Conservation & Management
• emerging technologies at international level.
What to be expected from an Energy Efficient Lighting Solution?
• Should be substantially energy efficient as compared to the lighting products which are being currently
used.
• Should provide at least the present standard of light quality, if not more.
• Should be able to address the concerns of environmental pollution effectively.
• Should provide good energy saving potential so that it can be commercially viable in the longer run.
Merits and Demerits of conventional lighting solutions:
Merits:
• Initial low cost of procurement, hence less initial investment.
• Easily available in almost all types of fittings and fixtures.
Demerits:
• Very high recurring energy usage costs and low power factor maintenance despite the initial low
procurement cost.
• Very less life ( Only 10000 to 12000 Hours of useful life)
• Poor illumination at the ground level for HPSV, LPSV, Metal Halide and CFL lamps.
• Severe degradation in Lumen Output after first 4000 Hours of operation (Up to 40%).
• Poor Color Rendering Index (CRI) – Well below the national and international standards for HPSV,
LPSV and Metal Halide Lamps.
• Very long start and re strike time (8 to 10 minutes) for HPSV, LPSV and Metal Halide Lamps.
• Generate excess amount of heat.
• Presence of UV radiation and liquid mercury poses environmental threat.
So the demerits of these lamps outweigh their merits in a big way.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
100 Energy Conservation & Management
Merits and Demerits of LED Lamps:
Merits:
• Long life of LED Lamp (up to 100000 Hours)
• Very good power factor maintenance (> 0.9)
• A wide color range is available.
Demerits:
• Very high initial cost of procurement.
• Very low life of the ballast or driver of the lamp primarily due to excess heat generation and high
current dependence for more light.( Up to 12000 Hours only)
• LED lamps of higher capacity (>18W) are very bulky and in certain cases rendered unfit for pole
mounting.
• LED lamps of capacities higher than 100W are not available easily and are very costly and LED lamps
of lower capacities are not suitable for outdoor street lighting.
• LED Lamps produce enormous glare at the top but provide very low lumen output at the ground level.
So the LED Lamps also prove to be a gloomy replacement option for the conventional lighting products.
With the above mentioned scenario and the analysis of presently available lighting solutions, the stage is now
set to look for such an option that addresses the present concern for energy efficiency, while accommodating the
mentioned merits and at the same time negating the demerits of the available conventional lighting systems as
well as much hyped LED lighting systems.
The first question that arises now is that – “Does such a lighting solution like this exist?”
Our answer is- “YES”
The second question that arises is that – “What is that option?”
The obvious answer is- “ELECTROMAGNETIC INDUCTION LIGHTING”
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
101 Energy Conservation & Management
In the following sections, we would like to highlight the details, advantages and disadvantages of
Electromagnetic Induction Lighting, its applications and its future commercial viability in a power hungry
country /economy like India.
History of Electromagnetic Induction Light
Nikolas Tesla
The dream of lighting inventors has been to produce a lamp with no internal electrodes so as to eliminate these
common failure modes. In an electrodeless lamp the envelope [bulb] is completely sealed and thus there is no
chance of atmospheric contamination due to seal failure and no electrodes to wear out over time. In June of
1891, Nicholas Tesla was granted a US patent to cover a very early form of Induction lamp.
Nikol a s Tesla demonstrated wired and wireless transfer of power to electrodeless fluorescent and incandescent
lamps in his lectures and articles in the 1890s, and subsequently patented a system of light and power
distribution on those principles. Noting the diagrams in Tesla's lectures and patents, a striking similarity of
construction to electrodeless lamps that are available in the market currently is readily apparent. Further, a
statement in 1929 by Tesla, published in The World :
“Surely, my system is more important than the incandescent lamp, which is but one of the known electric
illuminating devices and admittedly not the best. Although greatly improved through chemical and metallurgical
advances and skill of artisans it is still inefficient, and the glaring filament emits hurtful rays responsible for
millions of bald heads and spoiled eyes. In my opinion, it will soon be superseded by the electrodeless vacuum
tube which I brought out thirty-eight years ago, a lamp much more economical and yielding a light of
indescribable beauty and softness.”
How Electromagnetic Induction Light works?
Electromagnetic induction lamps are basically fluorescent lamps with electromagnets wrapped around a part of
the tube, or inserted inside the lamp. In external inductor lamps, high frequency energy, from the electronic
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
102 Energy Conservation & Management
ballast, is sent through wires, which are wrapped in a coil around the ferrite inductor, creating a powerful
magnet.
The induction coil produces a very strong magnetic field which travels through the glass and excites the mercury
atoms in the interior which are provided by a pellet of amalgam (a solid form of mercury). The mercury atoms
emit UV light and, just as in a fluorescent tube, the UV light is up-converted to visible light by the phosphor
coating on the inside of the tube. The system can be considered as a type of transformer where the inductor is
the primary coil while the mercury atoms within the envelope/tube form a single-turn secondary coil.
Applications of Electromagnetic Induction Light
• In hard-to-reach locations that make maintenance costs high, such as street lighting and tunnels, or in
high ceilings where there is continuous operation.
• Cold environments, such as supermarkets, walk-in coolers and freezers.
• Where high-quality lighting is required or highly desirable.
• Where reliability is highly valued.
• Where high lumen output is required.
• In areas that require lamps to reach full illumination immediately.
• In industrial factories, workshops, mines, backyard, sport, high security areas, etc.
They are also ideally suited for such applications where the advantages of fluorescent lighting are sought but a
light source is needed that can start and operate efficiently in extremely cold temperatures.
As a result, induction lighting is a suitable for a wide range of applications, including not only warehouses,
industrial buildings, cafeterias, gymnasiums, etc., but also signage, tunnels, bridges, roadways, outdoor area and
security fixtures, parking garages, public spaces, and freezer and cold storage lighting.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
103 Energy Conservation & Management
Why Electromagnetic Induction Light?
• The induction lamps are capable of saving a generous 40% over their counterparts and boast a life
expectancy of up to 100,000 hours
• Other advantages of induction lighting are better color rendition, and better control of the bulbs color
range from daylight to soft white. The Kelvin values match the accepted standard.
• Induction Lamps have no stroboscopic effect, no dazzle and no ultraviolet radiation in the spectrum;
therefore it is definitely recognized as a Green illumination, which protects us from diseases such as
myopia, headache, insomnia, tiredness, skin cancer, etc.
Advantages of using Electromagnetic Induction Light
• Moderately high initial cost of procurement as compared to HPSV, LPSV and Metal Halide Lamps and
very less as compared to LED Lamps.
• More lumen output while consuming almost half the wattage rating.
• Excellent power factor (> 0.9)
• Excellent Color Rendering Index (CRI) of 80.
• Very high S/P Factor ( 1.7 to 2.0)
• Instant start and no flicker.
• Very low lumen de rating (10% after 2000 Hours and then stable through out its life)
• Long life (80000 to 100000 Hours)
• No UV radiation, hence environment and health friendly.
• No liquid mercury thus ensuring safe disposal.
• Less heat generation.
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
104 Energy Conservation & Management
A tabular summary of advantages of using Electromagnetic Induction Lamps:
Comparison of Electromagnetic Induction Light with its conventional counterparts:
A new trend in light measurement – “Pupil Lumens” or “Visual Acuity Lumens”
Current codes and standards are based on measurements that do not address the impact of pupil lumens, and
pupil lumens are quite different from traditionally measured lumen output of lamps. Studies on the relevance of
light spectrum and the mechanics of vision are ongoing, and codes and standards will reflect that in the near
future.
Researchers have developed a conversion factor that applies the P/S ratio to lumen output of various light
sources, and then expresses the effective lumens the eye will perceive for vision based on the size of the pupil. It
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
105 Energy Conservation & Management
is called Pupil Lumens or Visual Acuity Lumens and is now being considered as the most important factor in
deciding the energy efficiency and quality of the light in addition to CRI and CCT.
Electromagnetic Induction Lamps score significantly here as they achieve very high P/S ratio of 2.0, whereas
low pressure sodium vapor and high pressure sodium vapor lamps achieve a low P/S ratio of 0.38 and 0.76 only
respectively eventually degrading their effective lumen output resulting in poor visibility. The economics of
using Induction lamps is favorable over life cycle.
Conclusion:
Electromagnetic Induction Light sources pose technical challenges, most of which have been addressed by
vendors now that the technology is nearly a decade old. Early systems faced concerns about electromagnetic
interference from the field generators, but today's products meet FCC 47CFR Part 18 Non-Consumer
certification, and complaints are just about nonexistent.
GOVERNMENTAL INTERVENTION REQUIRED FOR ACHIEVING ENERGY
CONSERVATION
• Unlike many other energy efficient gadgets, Electromagnetic Induction Light fails to attract the
attention of Government policy makers for a Electromagnetic Induction Light promotional scheme on
National level as in the case of Compact Fluorescent Lamp-CFL (National scheme of Bachat Lamp
Yojna is launched to promote use of CFL) In order to promote efficient use of available energy sources
specially in lighting sector followings are the suggestions for Energy efficiency measures under DSM:
• Government should make a Nation Wide Energy Efficiency-Demand Side Management (EE-DSM)
plan to promote use of Electromagnetic Induction Light where ever it is possible.
• Government should make stringent standards for quality Electromagnetic Induction Light gadgets, may
be Energy Star labeling be done on Electromagnetic Induction Light products to ensure the quality of
the gadget.
• For hoardings and signboards use of Electromagnetic Induction Light must be made mandatory.
• A National body that addresses the new research and carries quality testing for Electromagnetic
Induction Lighting gadget is also suggested.
From the details given above it becomes very clear that the option of Electromagnetic Induction lighting is one
of the most energy efficient way and will help in National Demand Side Management program. By keeping in
view the supply demand gap in the energy requirements of our country, Electromagnetic Induction lighting is
the need of the hour and it deserves due promotion and recognition from the government. Use of
Electromagnetic Induction lights is economical and environment friendly. With the help of Government
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011
106 Energy Conservation & Management
intervention use of Electromagnetic Induction lights can be made multifold and this will conserve energy which
can be used to bring the new era of lighting to those villages that are still away from even a light source.
Thanks & Regards
For further information and inquiry, please contact: