+ All Categories
Home > Documents > 07 TT 02 Using-The-protection

07 TT 02 Using-The-protection

Date post: 14-Apr-2018
Category:
Upload: long-leo
View: 217 times
Download: 0 times
Share this document with a friend

of 6

Transcript
  • 7/29/2019 07 TT 02 Using-The-protection

    1/6

    energize - July 2013 - Page 38

    TRANSMISSION AND DISTRIBUTION

    However, if non-standard connections are

    used, e.g. transformer windings connected

    in wye and CTs in wye, the current inputs

    to the differential calculations in the relay

    must be modified to compensate for a

    30 shift in the transformer and to subtract

    zero-sequence current as necessary.

    To accomplish this, the relay applies aconnection compensation factor for each

    winding.

    The unit includes five three-phase current

    inputs and three single-phase current inputs

    for restricted earth fault (REF) protection. It

    also includes six voltage inputs. Several

    examples for delta-connected high-side

    windings and wye connected low-s ide

    windings are shown here. These examples

    provide correct settings for two-winding

    transformer examples, but can also be

    applied to transformers with additional

    windings.

    The device contains settings for transformer

    phase rotation (PHROT), CT connections

    (CTCONn), internal/external CT connection

    compensation (ICOM), and connection

    compensation (TnCTC).

    Phase rotation setting (PHROT)

    It is recommended that the CT secondary

    circuits are wired to the relays terminal

    block such that the system phase is

    connected to the same relay phase

    (i.e. connect system A-phase to the

    relay A-phase). This product uses the

    phase rotat ion set t ing to determine

    negative-sequence current (3I2). The

    phase differential element calculations do

    not use the phase rotation setting, but the

    setting must be correct for one to use the

    negative-sequence differential element

    in the relay, i.e. the system phase rotation

    must be known to select the connection

    compensation settings properly.

    Current transformer connections (CTCONn)

    The current transformer connection may

    be set for either wye (Y) or delta (D). Innew installations, it is recommended

    to use wye-connected CTs whenever

    possible to maximise available protection,

    simplify overcurrent relay settings, CT

    wi ri ng and troubleshoot ing. If CTs are

    Using the protection relay in delta-wyepower transformer applications

    by George Alexander, Schweitzer Engineering Laboratories

    Application of traditional connections such as transformer windings connected in wye and CTs in delta, or transformer windings connected

    in delta and CTs in wye, involves no modification of current inputs to differential calculations in the relay.

    Fig. 1: ANSI standard delta-wye transformer, ABC system rotation, A-B-C connected to H1-H2-H3.

    Fig. 2: System phase angles for DABY connection, ABC system rotation.

    Fig. 3: Winding compensation with delta winding as reference.

    Fig. 4: Winding compensation with wye winding as reference.

  • 7/29/2019 07 TT 02 Using-The-protection

    2/6

    energize - July 2013 - Page 40

    TRANSMISSION AND DISTRIBUTION

    that use wye-connected CTs. In general,

    wye-connected CTs are easier to draw,

    wire, and t roubleshoot. Us ing the CTCONn

    setting in the relay will automatically

    calculate the TAPn setting if MVA is set to

    a value other than OFF. If MVA = OFF, the

    CTCONn setting can be used for metering

    and overcurrent elements.

    Internal/external CT connection

    compensation (ICOM)

    If ICOM = N, the traditional CT connections

    external to the relay must be used (e.g.,

    transformer windings connected in wye

    and CTs in delta, or transformer windings

    connected in delta and CTs in wye) to

    accomplish the CT and transformer phase-

    shift compensation. The CTs must be

    connected such that the current entering

    the polarity marks of the relay windings

    are 180 out of phase for load andexternal faults. If ICOM = Y, the relay will

    compensate internally for the transformer

    and CT phase shifts.

    Internal connection compensation settings

    (TnCTC)

    With internal CT connect ion compensation

    enabled (ICOM = Y), the relay can correct

    for phase shifts in a transformer or CTs. It

    is best to wire all CTs in wye configuration

    to maximise available protection, simplify

    overcurrent protection, and CT wiring. The

    relay setting, CT connection (CTCONn,

    where n is the winding input), defines theCT connection as delta or wye. Where CTs

    are connected in wye as recommended,

    the relay setting for internal winding/CT

    connection compensation (ICOM) will

    need to be set to Y to accommodate for

    30 phase shifts in the transformer. Setting

    ICOM equal to Y turns on the settings for

    connection compensation (TnCTC, where

    n is the winding input) to properly account

    for phase shifts in transformer winding

    connections and CT connections.

    The re lay can compensate in 30

    increments wi th a set t ing range of

    0 12. A setting of zero applies no phase

    shift compensation. A setting of twelve

    applies 360 of phase shift compensation,

    which results in 0 of compensation but

    the removal of zero-sequence currents.

    A sett ing of one appl ie s a 30 phase

    shift in the counterclockwise direction

    for ABC system rotation, and a setting of

    eleven applies a 330 phase shift in the

    counterclockwise direction for ABC system

    rotation.

    In all of the application examples, the

    following assumptions apply:

    CTs are connected in wye on bothsides of the transformer (CTCONS =

    CTCONT = Y).

    The sys tem phases connect to

    complementary labeled bushings on

    both the high side and low side of the

    Fig. 5: ANSI standard delta-wye transformer, ACB system rotation,

    A-B-C connected to H1-H2-H3.

    Fig. 6: System phase angles for DABY connection, ACB system rotation.

    Fig. 7: Winding compensation with delta winding as reference.

    Fig. 8: Winding compensation with wye winding as reference.

    wye-connected, the relay can provide

    phase, negative-sequence, and residual

    overcurrent elements for that winding. The

    residual elements respond to 3 I0, where

    3 I0 = Ia + Ib + Ic. However, the relaydisables residual overcurrent elements

    automatically if the CTs are connected

    for the associated winding in delta. Delta-

    connected CTs cannot deliver any residual

    operating current to the relay.

    If CTs are wye-connected, the relay

    calculates secondary amps it receives

    by dividing the primary amps by the CT

    ratio. If the CTs are delta-connected,

    the secondary amps that the relayreceives are larger by3, the overcurrent

    pick up settings must be adjusted by

    3. This can introduce confusion when

    coordinating the relay with downstream

    relays (e.g., distribution feeder relays)

  • 7/29/2019 07 TT 02 Using-The-protection

    3/6

    energize - July 2013 - Page 41

    TRANSMISSION AND DISTRIBUTION

    transformer (i.e., high-voltage A-phase

    connects to the H1 bushing and low-

    voltage A-phase connects to the X1

    bushing).

    Application examples

    Example 1

    For the transformer nameplate drawing

    in Fig. 1, ABC phase rotation is assumed,

    and the high-side currents will lead the

    associated low-side currents by 30. This is

    a DABY connection because the polarity

    of A-phase connects to the nonpolarity of

    B-phase. Because the CTs are connected

    in a wye configuration, the relay mustcompensate for the 30 phase shift.

    The phasor diagram in Fig. 2 shows the

    A-phase load current flow through the

    transformer and the 180 shift of the

    A-phase current on the CT secondar y

    as a result of the opposite CT polarity on

    the secondary of the transformer. The CT

    secondary current angles in the figure are

    the correct angles for a DABY transformer

    with ABC phase rotation.

    For this example, there are mult iple

    choices for winding compensation that

    wi ll produce the correc t 30 sh if t. The

    recommended method is to select

    the high-side winding as the reference

    windi ng and shif t the low-s ide currents

    by the appropriate amount. In Fig. 3, the

    delta winding from neutral to A-phase is

    chosen as the reference. The wye current

    is adjusted by 30 in the counterclockwise

    direction (because of ABC rotation) to

    align with the reference. Therefore, setting

    TSCTC = 0 and TTCTC = 1 achieves the

    proper selection of winding compensation.

    T h e a p p r o p r i a t e s e t t i n g s a r e :

    PHROT = ABC, CTCONS = Y, CTCONT = Y,

    ICOM = Y, TSCTC = 0, TTCTC = 1

    A second choice for winding compensation

    would be to se lect the wye winding as the

    reference and rotate the delta A-phase by

    the appropriate number of degrees to be

    in phase with the wye winding A-phase. As

    Fig. 4 shows, the A-phase-to-neutral on the

    delta winding must be rotated by 330 in

    the counterclockwise direction to align with

    A-phase-to-neutral on the wye winding.

    One might think that the compensation

    settings would, therefore, be TSCTC = 11

    and TTCTC = 0. However, winding two is

    a wye winding with wye-connected CTs;

    the proper selection would therefore beTTCTC = 12 to remove zero-sequence

    currents. Setting the winding compensation

    to twelve introduces a 360 phase shift and

    removes zero-sequence currents. Removal

    of the zero-sequence currents is important

    because phase-to-ground faults external

    to the differential zone of protection could

    cause a false assertion of the differential

    element. The false assertion results from

    the zero-sequence current source of

    the directly grounded or impedance-

    grounded wye transformer neutral creating

    an apparent, but incorrect, increase in the

    secondary phase currents to the relay.

    In this case, the appropriate settings would

    be: PHROT = ABC, CTCONS = Y, CTCONT = Y,

    ICOM = Y, TSCTC = 11, TTCTC = 12

    Example 2

    For the transformer nameplate drawing

    in Fig. 5, ACB phase rotation is assumed

    and the highside currents will lag the

    associated low-side currents by 30. This is

    a DABY connection because the polarity

    of A-phase connects to the nonpolarity of

    B-phase. Because the CTs are connected

    in a wye configuration, the relay must

    compensate for the 30 phase shift.

    The phasor diagram in Fig. 6 shows the

    A-phase load current flow through the

    transformer and the 180 shift of the

    A-phase current on the CT secondar y

    as a result of the opposite CT polarity on

    the secondary of the transformer. The CT

    Fig. 9: ANSI standard delta-wye transformer, ABC system rotation, C-B-A connected to H1-H2-H3.

    Fig. 11: Winding compensation with delta winding as reference.

    Fig. 12: Winding compensation with wye winding as reference.

    Fig. 10: System phase angles for DACY connection, ABC system rotation.

  • 7/29/2019 07 TT 02 Using-The-protection

    4/6

    energize - July 2013 - Page 42

    TRANSMISSION AND DISTRIBUTION

    secondary current angles in the figure are

    the correct angles for a DABY transformer

    with ACB phase rotation.

    For this example, there are also multiple

    choices for winding compensat ion.

    The recommended method is to select

    the high-side winding as the referencewinding, and to shif t the low-side currents

    by the appropriate amount. In Fig. 7, the

    delta winding from neutral to A-phase was

    chosen as the reference. The wye current

    must be adjusted by 30 in the clockwise

    direction (because of ACB rotation) to

    align with the reference. Therefore, setting

    TSCTC = 0 and TTCTC = 1 achieves the

    proper selection of winding compensation.

    The winding compensation setting does

    not change, although the phase rotation

    changed. This is because, for ACB rotation,

    the phase-angle rotation was adjusted

    in the clockwise direction by the TnCTC

    setting.

    T h e a p p r o p r i a t e s e t t i n g s a r e :

    PHROT = ACB, CTCONS = Y, CTCONT = Y,

    ICOM = Y, TSCTC = 0, TTCTC = 1

    A second choice for winding compensation

    would be to select the wye winding as the

    reference and rotate the delta A-phase

    by the appropriate number of degrees to

    be in phase with the wye winding A-phase.

    As Fig. 8 shows, A-phase-to-neutral on the

    delta winding would need to be rotated by

    330 in a clockwise direction to align with

    A-phase-to-neutra l on the wye winding.

    Again, as in example 1, the compensation

    set t ings could be TSCTC = 11 and

    TTCTC = 12.

    T h e a p p r o p r i a t e s e t t i n g s a r e :

    P H R O T = A C B , C T C O N S = Y ,

    CTCONT = Y, ICOM = Y, TSCTC = 11,

    TTCTC = 12

    Example 3

    The transformer nameplate in example 3

    is exactly like the nameplate in examples

    1 and 2, but now the system phase

    connections to the H1, H2, and H3 terminals

    have changed. A-phase now connects to

    H3, and C-phase now connects to H1,

    and the system A-phase connects to the

    relay IAS input. This is a DACY connection

    because the polarity of A-phase connects

    to the nonpolarity of C-phase. For the

    nameplate diagram in the example and

    ABC system phase rotat ion, the high-side

    currents will lag the associated low-side

    currents by 30, and the relay must

    account for this phase angle shift.

    The phasor diagram in Fig. 10 shows

    the A-phase load current flow through

    the transformer and the 180 shift of the

    A-phase curr ent on the CT secondar y

    because of the opposite CT polarity on

    the secondary of the transformer. The CT

    secondary current angles in the figure are

    the correct angles for a DACY transformer

    with ABC phase rotation.

    For this example, there are also multiple

    choices for winding compensat ion.

    The method recommended is to select

    the high-side winding as the reference

    winding and shif t the low-side currents by

    the appropriate amount. In Fig. 11, the

    delta winding from neutral to C-phase was

    chosen as the reference simply because

    it is at the 12 oclock position, althoughthe A-phase could have been chosen

    as the reference again and the same

    results would have been obtained. The

    wye current must adjusted by 330 in the

    counterclockwise direction (because of

    Fig. 13: Non-standard delta-wye transformer, ABC system rotation, A-B-C connected

    to H1-H2-H3.

    Fig. 15: Winding compensation with delta winding as reference.

    Fig. 16: Winding compensation with wye winding as reference.

    Fig. 14: System phase angles for DACY connection, ABC system rotation.

  • 7/29/2019 07 TT 02 Using-The-protection

    5/6

    energize - July 2013 - Page 44

    TRANSMISSION AND DISTRIBUTION

    ABC rotation) to align with the reference chosen. Therefore, the proper

    selection of winding compensation is TSCTC = 0 and TTCTC = 11.

    The appropriate sett ings are: PHROT = ABC, CTCONS = Y,

    CTCONT = Y, ICOM = Y, TSCTC = 0, TTCTC = 11

    A second choice for winding compensat ion would be to select the

    wye winding as the reference, and rotate the delta C-phase by the

    appropriate number of degrees to be in phase with the wye winding

    C-phase.

    As Fig. 12 shows, the C-phase to neutral on the delta winding would

    need to be rotated by 30 in the counterclockwise direction to align

    with C-phase-to-neutral on the wye winding and the compensation

    settings could be TSCTC = 1 and TTCTC = 12.

    The appropriate sett ings are: PHROT = ABC, CTCONS = Y,

    CTCONT = Y, ICOM = Y, TSCTC = 1, TTCTC = 12

    Example 4

    This transformer nameplate differs from the first three examples in

    that the polarity of the H1 winding now connects to the nonpolarity

    of the H3 winding. The system A-phase connects to the H1 winding,and the system C-phase connects to the H3 winding. This is a

    DACY connection because the polarity of A-phase connects to the

    nonpolarity of C-phase. For the nameplate diagram in the example

    and the ABC system phase rotation, the high-side currents will lag

    the associated low-side currents by 30, and the relay must account

    for this phase angle shift. The phasor diagram in Fig. 14 shows the

    A-phase load current flow through the transformer and the 180

    shift in the A-phase current on the CT secondary because of the

    opposite CT polarity on the secondary of the transformer. The CT

    secondary current angles in the figure are the correct angles for a

    DACY transformer with ABC phase rotation.

    For this example, there are also multiple choices for winding

    compensation. The recommended method is to select the high-sidewinding as the reference winding and shif t the low-side currents by

    the appropriate amount. In Fig. 15, the delta winding from neutral

    to A-phase was chosen as the reference. The wye current must be

    adjusted by 330 in the counterclockwise direction (because of ABC

    rotation) to align with the reference chosen. Therefore, the proper

    selection of winding compensation is TSCTC = 0 and TTCTC = 11.

    The appropr iate settings are: PHROT = ABC, CTCONS = Y, CTCONT = Y,

    ICOM = Y, TSCTC = 0, TTCTC = 11 A second choice for winding

    compensation would be to select the wye winding as the reference,

    and rotate the delta A-phase by the appropriate number of

    degrees to be in phase with the wye winding A-phase. As Fig. 16

    shows, A-phase-to-neutral on the delta winding would need to

    be rotated by 30 in the counterclockwise direction to align withA-phase-to-neut ral on the wye winding. Compensation sett ings are

    TSCTC = 1 and TTCTC = 12.

    The appropriate sett ings are: PHROT = ABC, CTCONS = Y,

    CTCONT = Y, ICOM = Y, TSCTC = 1, TTCTC = 12

    Example 5

    The transformer connections of Fig. 17 are the same as Fig. 2 for

    example 1. However, the CTs connect in the traditional manner

    (e.g., transformer windings connect in wye and CTs in delta, or

    transformer windings connect in delta and CTs in wye). Because of

    the CT connections, internal compensation is not necessary. For the

    transformer nameplate drawing in Fig. 17, if ABC phase rotation is

    assumed, then the high-side currents will lead the associated low-sidecurrents by 30. This is a DABY connection because the polarity of

    A-phase connects to the nonpolar ity of B-phase. The phasor d iagram

    in Fig. 2 shows the A-phase load current flow through the transformer.

    The high-side current, Ia, connects to the relays IAS terminal. The

    IAT terminal of the relay connects to Ia Ib, and the Ia Ib current

  • 7/29/2019 07 TT 02 Using-The-protection

    6/6

    energize - July 2013 - Page 45

    TRANSMISSION AND DISTRIBUTION

    shifts 180 on the CT secondary because of the opposite CT polarity on the

    secondary of the transformer. The CT secondary current angles in the figure

    are the correct angles for a DABY transformer with ABC phase rotation.

    The appropr ia te set t ings a re: PHROT = ABC, CTCONS = Y,

    CTCONT = D, ICOM = D

    Conclusions

    The relay winding compensation settings provide winding compensations in

    30 increments to allow for most transformer applications, including mobile

    transformer applications. Care must be taken to connect the CTs and

    system phases to the transformer to provide proper targeting and metering

    quantities. The following guidelines must be applied whenever possible:

    All CTs should be connected in wye.

    The system phase must be connected to the corresponding relayphase.

    The Global Phase Rotation Setting (PHROT) must be set to the phaserotation of the system.

    The system connection diagram, system phase rotat ion, andtransformer nameplate diagram must be used to determine proper

    winding compensation settings.

    The delta connection(s) must be identified as DAB or DAC by usingsystem phase connections and relay phase connections.

    TnCTC = 12 must be set for any winding that needs no phase angle

    correction but is a grounded wye winding with wye-connected CTs.

    Important points about delta connections:

    DABY transformers always result in the delta side leading the wye sidefor ABC system rotation.

    DABY transformers always result in the delta side lagging the wye sidefor ACB system rotation.

    DACY transformers always result in the delta side lagging the wye sidefor ABC system rotation.

    DACY transformers always result in the delta side leading the wye side

    for ACB system rotation.

    SEL commissioning assistant software is available at no charge to help verify

    CT connections and compensation settings for SEL-487E relays.

    Contact Rudolf van Heerden, SEL, Tel 012 664-5930,

    [email protected]

    Fig. 17: ANSI standard delta-wye transformer, ABC system rotation, A-B-C

    connected to H1-H2-H3, CTs connected wye-delta.

    Fig. 18: System phase angles for DABY connection, ABC system rotation.


Recommended