08.00-00ADWG.
SECTION 8 - SWITCHES AND PROTECTIVE DEVICES
TABLE OF CONTENTS
CUTOUTS AND ARRESTERS GENERAL 08.00-03
08.01-01ARRESTERS, 10KV
CUTOUTS AND BRACKETS 08.01-1008.01-11CUTOUTS AND ARRESTERS 2 OR 3 EACH ON TRIPLE MOUNTING BRACKET
"L" BRACKET
08.01-13
08.01-12CUTOUTS AND ARRESTERS SINGLE-PHASE TERMINATION ON POLE MOUNTED
BRACKET
HORIZONTAL CONSTRUCTION TO BRANCH LINE 08.01-3608.01-37HORIZONTAL CONSTRUCTION WITH LIGHTNING ARRESTER
HORIZONTAL CONSTRUCTION TO HORIZONTAL DEADEND 08.01-3208.01-33HORIZONTAL CONSTRUCTION TO HORIZONTAL WITH CUTOUT (FLYING TAP)
DOUBLE CIRCUIT CONSTRUCTION WITH LIGHTNING ARRESTER 08.01-2908.01-28VERTICAL CONSTRUCTION WITH LIGHTNING ARRESTER
ELECTRONIC RESETTABLE SECTIONALIZERS 08.04-02
08.05-00RECLOSERS, SECTIONALIZERS, TRANSFERS AND THREE-PHASE RECLOSER
RECLOSER IDENTIFICATION 08.05-01
08.05-17B
08.05-15A
RECLOSER ON VERTICAL DOUBLE CIRCUIT WITH VERTICAL BYPASS SWITCH 08.06-1008.06-08BRECLOSER ASSEMBLY, THREE-PHASE, WITH VERTICAL BYPASS SWITCH
RECLOSER AND FRAME, THREE-PHASE, WITH VERTICAL BYPASS SWITCH 08.06-08A
RECLOSER ASSEMBLY, THREE-PHASE, VERTICAL, 600 AMP SWITCH 08.06-22A08.06-22BRECLOSER ASSEMBLY, THREE-PHASE, VERTICAL, 600 AMP SWITCH
CUTOUT AND ARRESTER, (2) OR (3)-PHASE TERMINATION ON TRIPLE MOUNTING
RECLOSER ASSEMBLY, VERTICAL CONSTRUCTION
08.00-01DISTRIBUTION SURGE ARRESTERS
0
3
2
1
APPR.REVISED BY CK'D
08.05-02TYPICAL SINGLE-PHASE RECLOSER DIMENSIONS, WEIGHTS AND OIL CAPACITIES
08.01-04APPLICATION OF DIRECT CONNECTED ARRESTERS ON DISTRIBUTION TRANSFORMERS
ELKINSGUINNCECCONI11/30/10
08.05-15BOIL CIRCUIT RECLOSER - SINGLE-PHASE INSTALLATION BYPASS CUTOUT BRACKET
RECLOSER ASSEMBLY, HORIZONTAL CONSTRUCTION08.05-17ARECLOSER ASSEMBLY, HORIZONTAL CONSTRUCTION
LIGHTNING ARRESTER MOUNTING DETAIL
08.05-16ARECLOSER ASSEMBLY, VERTICAL CONSTRUCTION, FEEDER
08.06 RECLOSERS - THREE-PHASE CONFIGURATIONS
08.05 RECLOSERS - SINGLE-PHASE CONFIGURATIONS
08.04 SECTIONALIZERS
08.01 CUTOUTS AND ARRESTERS
08.00 GENERAL
ELKINSBURLISONCECCONI9/28/11
08.01-32DWG.
NOTES:
1. CUTOUTS WILL NORMALLY BE INSTALLED ON THE TAP POLE.
HORIZONTAL CONSTRUCTION TO
HORIZONTAL DEADENDELKINSGUINNROBESON8/11/10
FRONT VIEW FRONT VIEW
PLAN VIEW
PLAN VIEW
NEUTRAL
72"
36"
4"
6"72"
4"
6"
8"18"16"34"8"
6"
6"
18"
16"
34"
8"
0
3
2
1
APPR.REVISED BY CK'D
8"
6"
4"
2. SEE SECTION 01 FOR ADDITIONAL GROUNDING DETAILS.
#6 SD BC
#6 SD BC
ELKINSBURLISONBURLISON8/31/11
KHLC40N6F
KHLC7933FOR
08.01-33DWG.
HORIZONTAL CONSTRUCTION TOHORIZONTAL WITH CUTOUT
(FLYING TAP)ELKINSGUINNROBESON8/11/10
NEUTRAL
FRONT VIEW
PLAN VIEW
6"
16"
16"
42"
0
3
2
1
APPR.REVISED BY CK'D
36"
62"
4"
6"
6"
6"
NEUTRAL
NEUTRAL
#6 SD BC
1. SEE SECTION 01 FOR ADDITIONAL GROUNDING DETAILS.
NOTES:
KHLC40N6F
KHLC7933FOR
ELKINSBURLISONBURLISON8/31/11
08.01-36DWG.
HORIZONTAL CONSTRUCTION TO
BRANCH LINEELKINSGUINNROBESON8/11/10
TANGENT CONSTRUCTION
PLAN VIEW
FRONT VIEW
GUY ATTACHMENTAND 78" GUY STICK
FRONT VIEW
NEUTRAL
SOURCE
LOAD
DEADEND TO DEADEND
PLAN VIEW
36"
72"
4"
4"
2"
TOP BOLT OF'L' BKT
72"
6"
0
3
2
1
APPR.REVISED BY CK'D
ELKINSBURLISONBURLISON8/31/11
KHLC40N6F
KHLC7933FOR
08.05-16ADWG.
RECLOSER ASSEMBLY,
VERTICAL CONSTRUCTION, FEEDER0APPR.REVISED BY CK'D
1
2
9/28/11 BURLISON ELKINSBURLISON
3
60"
60"
72"
16"
5"
4"
11"
08.06-08ADWG.
NOTES:
1. SWITCHES TO BE ON ROAD SIDE.
4. A 45' CLASS 4 POLE IS THE MINIMUM TO BE USED FOR THIS INSTALLATION.5. TOTAL WEIGHT OF THE RECLOSER AND FRAME IS 850 LBS.6. ISSUE TAPS TO SWITCHES SEPARATELY (WIRE, CONNECTORS, AND LUGS). BOLTS WILL BE ON SWITCH.
8. NEUTRAL MAY BE DOUBLE DEADENDED OR STRAIGHT THROUGH ON SPOOL AS NEEDED.
RECLOSER AND FRAME, THREE-PHASE,
WITH VERTICAL BYPASS SWITCHELKINSGUINNHOFFMAN10/12/10
9. SEE DWG. 08.06-08B FOR BILL OF MATERIALS.
FRONT VIEW
#2 SD BC
6
12
1
11
8
54
37"
35"
48" MIN.
#6 SD BC
72"
48"
48"
5"
6"
38"
24"
24"
6"
PT
#6 SD BC
BOLT ON TAMPERGUARD FORCONTROL CABLEPLUG
L1
L2
BLACK
GREEN - GROUND
SECONDARYARRESTER
TERMINAL L1
BLACK
SECONDARY ARRESTER CONNECTION
3
0
2
1
APPR.REVISED BY CK'D
2. PT TO BE LOCATED ON SOURCE SIDE. RELOCATE ON RECLOSER FRAME IF NECESSARY.3. SIX ARRESTERS REQUIRED: 3 ON EACH SIDE. CONNECT TO TERMINALS OF RECLOSER WITH CONNECTOR UNDER WILDLIFE PROTECTORS.
SIDE VIEW
7. ALL BOLTS ON PRIMARY CONNECTIONS ARE TO BE TORQUED TO 40 FT-LBS. DO NOT EXCEED!
10. SEE SECTION 01 FOR ADDITIONAL GROUNDING DETAILS.3
2
7
1/2" SS
ROUNDWASHER
DETAIL "B"
BOLT
4 HOLESPADE ONRECLOSER
#6 BC
ROUNDBOLT
#6 BC
NUT
LOCKWASHER
9
10
ELKINSBURLISONSIMMONS1/27/12
DWG.
08.06-08B
RECLOSER ASSEMBLY, THREE-PHASE
WITH VERTICAL BYPASS SWITCHELKINSGUINNHOFFMAN11/9/10
NOTES:
5. ALL BOLTS ON PRIMARY CONNECTIONS ARE TO BE TORQUED TO 40 FT-LBS:
1. GROUND RESISTANCE TO BE 15 OHMS OR LESS.2. A 45' CLASS 4 POLE IS THE MINIMUM TO BE USED FOR THIS INSTALLATION.
4. ISSUE TAPS TO SWITCHES SEPARATELY (WIRE, CONNECTORS, AND LUGS). BOLTS WILL BE ON SWITCH.3. TOTAL WEIGHT OF RECLOSER ASSEMBLY IS 850 LBS.
92200852319220087168
EXTERNAL PT FOR ABB OVR RECL, 13.8V, 110BIL, VOG-11, 60:1COASTAL EXT. PT- ABB OVR RECL, 13.8 KV, 125 KV BIL, W/60:1 RATIO
9220102215 CABLE LOCKING SLEEVE - ABB RECL. CTRL CABLE CONNECTOR9220087542 BATTERY, RECLOSER, PCD CNTRL, 48VDC (SET OF 4-12VDC)9220100256 CABLE-PT, ABB RECLOSER, 8 FOOT, W/2-5-PRONG CONNECTORS9220085226 ABB PCD SINGLE-PHASE TRIP CARD9220102547 COM5 MODULE/CARD FOR ABB PCD CONTROL (SLOT-E)9220127574 ABB PCD UPS CARD TYPE 3, 48VDC (SLOT-A)9220127570 ABB PCD UPS CARD TYPE 2, 48VDC (SLOT-A)9220127579 ABB PCD DIO-2B I/O CARD (SLOT-B)9220127587 ABB PCD DIO-1 I/O CARD (SLOT-C)9220127588 ABB PCE CPU-2 CARD (SLOT-D)9220127589 ABB PCD COM-2A CARD (SLOT-E)9220127564 ABB PCD PT/CT 600:1 CARD (SLOT-F)
6. SEE DWG. 08.06-08A DESIGN SPECIFICATIONS.
0
3
2
1
APPR.REVISED BY CK'D
3
8765
4
2
1
BILL OF MATERIALS
CATALOGDESCRIPTION
1
6444
3
1
1
QTY
1
PERCU
NUMBERMACRO UNIT
-
CUITEMNO.
COMPATIBLE UNIT
QTYREQ'D
RECLOSER TYPE OVR 630 AMP ELEC. 15KV VRT MNTG W/1PTBOLT, MACHINE, SQ, NUT, 5/8" X 12"WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLTWASHER, ROUND, FLAT, STAINLESS STEEL, 304 ALLOYBOLT, MACHINE, STAINLESS STEEL, HEX HEAD, 1/2" X 2"NUT, STAINLESS STEEL, HEX, 304 ALLOY, COARSE THREADWIRE, TIE, #4 SD BC, SLDRECLOSER CONTROL PCD 2000 FOR ABB RECLRECLOSER CONTROL CABLE FOR ABB VR3 AND OVR, 40FTWASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.BOLT, MACHINE, SQ, NUT, 5/8" X 12"SWITCH, BYPASS, 3-SLD BLADE DISCONNECT, 15KV, LBKBRACKET, FIBERGLASS STAND-OFF, 1-3/8" THREADINSULATOR, 25 KV POLYMER, 1-3/8" THREADPLASTIC TIE WRAP FOR 2-7/8" F-NECK INSULATORARRESTER, LIGHTNING, 10KV HD MOV W/SILICONE RUBBER POLYBOLT, MACHINE, STAINLESS STEEL, HEX HEAD, 1/2" X 2"NUT, STAINLESS STEEL, HEX, 304 ALLOY, COARSE THREADWASHER, FLAT, ROUND, SILICON, BRONZE, FOR 1/2" BOLTLUG, COMP 2H 500 ALWASHER, ROUND, RD, 1/2, SS, 1.375" ODLUG, 2-HOLE, TIN-PLATED, NEMA, 90 DEGREECABLE, XLP UG AL 500GUARD, PVC, CABLE, 2-1/4" X 10'BANDING, STAINLESS STEEL, 316, 3/4" WIDE, .030 THBANDING, BUCKLE, SS, 3/4", FOR BANDINGARRESTER, LIGHTNING, SEC 120-240 3 WIRE
9
13
12
1110
6
1
2
66
9220090147152107013308013264013128013407010928012277
922006924492200875509220100429
013264013308152107260123
922008786892200910189220068094
220202010928012277013163155326
105425049220068102
202112323422434122434142220139
RCOVR630E15V1F
RCCNTLPCDABBFRCOVRCAB40F
SW156BYPF
BKTFBGPIN15138FIPIN25PF
TTIEF500COVALPFAREQOH10F
KLC2H50ALF
KLC2H50AL90DFRCRISER500ALF
CRIS1UGPVC225CF
AREQSC120F
ADDITIONAL PARTS FOR REPLACEMENT
24
333231302928272625
23222120191817
CATALOGDESCRIPTION
--------------
-
---------
-
--
-
11
1111
1
111111111
QTY
1
11
1
11
1111
PERCU
NUMBERMACRO UNIT
-
CUITEMNO.
COMPATIBLE UNIT
QTYREQ'D
RECLOSER, ABB OVR-630 AMP, 12KA, 27KV-HV EDGEMOUNT COASTALRECLOSER, PCD,CONTROL,LV,MODULE,WITHOUT,SINGLE-PHASE,TRIRECLOSER, CONTROL, PCD 2000 COOPER RETROFITTRANSFORMER, POTENTIAL, 15KV,7200VTRANSFORMER, POTENTIAL, 25KV,14400V OUTDOOR TRANSFORMERMODULE, LOOP CONTROL, RECLOSER, ABB, FOR PCD CONTROL.
9220087177922008521992200876332080094220800983
9220087552
RCOVR630E27V1FR